Liebert XD Horizontal Row Cooler (XDH )
™
GUIDE SPECIFICATIONS
1.0 GENERAL
1.1
SUMMARY
These specifications describe requirements for an air conditioning system designed for cooling of high
heat density equipment. The system shall be designed to maintain conditions within the space with heat
emitting equipment. The manufacturer shall design and furnish all equipment to be fully compatible with
heat dissipation requirements of the site.
1.2
DESIGN REQUIREMENTS
The air conditioning system shall be a Liebert XDH factory-assembled unit. The unit shall be designed
for draw-through air arrangement to ensure even air distribution to the entire face area of the coils.
1.3
SUBMITTALS
Submittals shall be provided with the proposal and shall include: Dimensional, Electrical and Capacity
data; typical Piping and Electrical Connection.
1.4
WARRANTY
The system shall be provided with a warranty against defects in material and workmanship.
1.5
QUALITY ASSURANCE
The specified system shall be factory-tested before shipment and designed to meet NRTL requirements.
The system shall be designed and manufactured according to world-class quality standards. The
manufacturer shall be ISO 9001 certified.
2.0 PRODUCT
2.1
STANDARD FEATURES XDH
2.1.1 XDH Module
XDH module shall include micro channel cooling coils and fans housed in a cabinet and be rated at 55°F
(12.8°C) entering fluid temperature, 98°F (37°C) entering air temperature, 50°F (10°C) or lower dew
point.
• XDH20 (60Hz) - Nominal cooling capacity of 22 kW (75,000 BTUH) at 2,500 CFM (4,200 m3/h)
• XDH32 (60Hz) - Nominal cooling capacity of 30 kW (102,000 BTUH) at 4,000 CFM (6,800 m3/h)
• XDH20 (50Hz) - Nominal cooling capacity of 22 kW (75,000 BTUH) at 2,428 CFM (4,125 m3/h)
• XDH32 (50Hz) - Nominal cooling capacity of 30 kW (102,000 BTUH) at 3,850 CFM (6,541 m3/h)
2.1.2 Cooling
Fluid shall be supplied to the XDH from a Liebert XD Pumping Unit (XDP) or a Liebert XD Chiller
(XDC) to prevent coil condensation and optimize the fluid temperature to the XDH module.
2.1.3 Fans
Each module shall consist of six (6) axial fans with finger guards.
2.1.4 Electrical
Each module shall be equipped with two (2) 10 ft. (3.0 m) power cords, primary and secondary, attached
with IEC connectors to the rear of the unit. Each cord shall have a NEMA 5-15P (IEC 320-C14) plug at
the end. CE listed version of the unit shall have permanently attached power cords.
SL-17205_REV03_06-09
1
Guide Specifications
Liebert XDH
2.1.5 Piping
Factory-installed piping shall be leak-tested and pressure-tested prior to shipment from the factory.
2.1.6 Dual Power Cords
Each module shall have dual power cords with automatic switching.
2.2
OPTIONAL FEATURES XDH
2.2.1 Smart Module
The XDH is available with optional factory-installed control boards and condensate detection for the drip
pan. The module shall have connection points (dry contacts) in the electrical box for connection of
outgoing alarm cables for condensate detection, fan failure and for remote shutdown.
2.2.2 Pipe Connection
The XDH is available with optional factory-installed “one-shot” type pipe connections (for field
connection of Flexible Piping).
2.2.3 Front Air Discharge Diffuser
The XDH is available with different front air discharge diffusers; for front air discharge to both sides or
for front air discharge to one side.
2.3
ELECTRICAL REQUIREMENTS
Each XDH32 module shall require 10 FLA at 120V-1ph-60Hz or 5 FLA at 230V-1ph-50Hz, respectively.
Each XDH20 module shall require 5 FLA at 120V-1ph-60Hz or 2.5 FLA at 230V-1ph-50Hz, respectively.
3.0 EXECUTION
3.1
INSTALLATION OF XDH
3.1.1 General
Install the unit in accordance with the manufacturer’s installation instructions. Maintain recommended
service clearances as outlined in the installation instructions.
3.1.2 Piping Connections
Install and connect devices furnished by the manufacturer but not specified to be factory-mounted.
Furnish a copy of the manufacturer’s piping connection diagram submittal to the piping contractor.
3.1.3 Supply and Return Piping
Connect supply and return connections to the XDH module.
3.2
FIELD QUALITY CONTROL
3.2.1 Startup
Start up the air conditioning unit in accordance with the manufacturer’s startup instructions. Test controls
and demonstrate compliance with requirements.
NOTE: These Guide Specifications comply with the outlines of the Construction Specifications Institute
per CSI MP-2-1 and MP-2-2. In correspondence, reference Liebert document SL-17205_REV03_06-09.
SL-17205_REV03_06-09
2
Guide Specifications