REYQ216TTJU

REYQ216TTJU
Submittal Data Sheet
18-Ton VRV-IV Heat Recovery Unit - 230V
REYQ216TTJU
FEATURES
Variable Refrigerant Temperature (VRT) control allows the VRV IV to
deliver up to 28% of improvement in seasonal cooling efficiency compared
to previous Daikin VRV heat recovery systems
Improved efficiency with IEER values now up to 29.3
Can provide heating down to -13°F WB as standard
Larger capacity single modules ranging up to 14 tons and systems up to 38
tons allow for a more flexible system design, when compared to VRV III
New configurator software designed to simplify the commissioning and
maintenance of the system
Standard Limited Warranty: 10-year warranty on compressor and all parts
Larger capacity single modules allow for opportunity to reduce electrical
connections, piping connections and outdoor unit mounting fixtures
All inverter compressors to increase the efficiency and avoid starting
current inrush
Assembled in the US to increase flexibility and reduce lead times
BENEFITS
Can operate up to 64 indoor units on a single piping network
Inverter control board cooled by refrigerant to avoid influence from ambient
temperatures
Integrated inverter technology deliver maximum efficiency during part load
conditions and provide precise individual zone control
Heat exchanger coil wraps around on all 4 sides of the unit to increase the
surface area/efficiency
Continuous heating during defrost and oil return allows constant comfort
control
Modular and lightweight - enables flexibility in system layout and installation
Ultra gold fin coating with a salt spray test rating of 1000 hours provides
superior corrosion resistance for applications near seacoasts and other
corrosive environments
Design flexibility with long piping lengths up to 3,280 ft. total and 100 ft.
vertical separation between indoor units
Designed with reduced MOP to optimize installation cost
Digital display on the unit for improved and faster configuration,
commissioning, and troubleshooting.
Daikin City Generated Submittal Data
Daikin North America LLC, 5151 San Felipe, Suite 500, Houston, TX, 77056
www.daikinac.com www.daikincomfort.com
(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without
incurring any obligations)
Page 1 of 3
Submittal Data Sheet
18-Ton VRV-IV Heat Recovery Unit - 230V
REYQ216TTJU
PERFORMANCE
Outdoor Unit Model No.
REYQ216TTJU
Outdoor Unit Name:
18-Ton VRV-IV Heat Recovery Unit 230V
Type:
Heat Recovery
Unit Combination:
REYQ120TTJU + REYQ96TTJU
Rated Cooling Conditions:
Indoor (°F DB/WB): 80 / 67
Ambient (°F DB/WB): 95 /
Rated Heating Conditions:
Indoor (°F DB/WB): 70 /
Ambient (°F DB/WB): 47 / 43
Rated Cooling Capacity (Btu/hr):
200,000
Rated Heating Capacity (Btu/hr):
226,000
Nom Cooling Capacity (Btu/hr):
216,000
Nom Heating Capacity (Btu/hr):
243,000
Cooling Input Power (kW):
16.10
Heating Input Power (kW):
22.20
EER (Non-Ducted/Ducted):
12.50 / 12.40
Heating COP (Non-Ducted/Ducted):
3.7 / 3.7
IEER (Non-Ducted/Ducted):
22.90 / 20.20
Heating COP 17F (Non-Ducted/Ducted):
2.5 / 2.3
SCHE (Non-Ducted/Ducted):
25.60 / 22.50
Rated Piping Length(ft):
Rated Height Difference (ft):
OUTDOOR UNIT DETAILS
Power Supply (V/Hz/Ph):
208-230 / 60 / 3
Compressor Type
Inverter
Power Supply Connections:
L1, L2, L3 Ground
Capacity Control Range (%):
5 - 100
Min. Circuit Amps MCA (A):
38+43
Capacity Index Limit:
-
Max Overcurrent Protection (MOP) (A):
45+50
Airflow Rate (H) (CFM):
5827+6286
Gas Pipe Connection (inch):
1-1/8
Max Starting Current MSC(A):
Rated Load Amps RLA(A):
(13.7+13.7)+(15.0+15.0)
Liquid Pipe Connection (inch):
5/8
Dimensions (Height) (in):
66-11/16
H/L Pressure Connection (inch)
1-1/8
Dimensions (Width) (in):
97-3/4
H/L Equalizing Connection (inch)
Dimensions (Depth) (in):
30-3/16
Sound Pressure () (dBA):
Net Weight (lb):
703+703
Sound Power Level (dBA):
Max. No. of Indoor Units:
Daikin City Generated Submittal Data
Daikin North America LLC, 5151 San Felipe, Suite 500, Houston, TX, 77056
37
www.daikinac.com www.daikincomfort.com
(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without
incurring any obligations)
Page 2 of 3
Submittal Data Sheet
18-Ton VRV-IV Heat Recovery Unit - 230V
REYQ216TTJU
SYSTEM DETAILS
Refrigerant Type:
R-410A
Cooling Operation Range (°F DB):
23 - 122
Holding Refrigerant Charge (lbs):
25.8+25.8
Heating Operation Range (°F WB):
-13 - 60
Additional Charge (lb/ft):
Max. Pipe Length (Vertical) (ft):
295
Pre-charge Piping (Length) (ft):
Cooling Range w/Baffle (°F DB):
-
Heating Range w/Baffle (°F WB):
-
Max. Pipe Length (Total) (ft):
540
Max Height Separation (Ind to Ind ft):
DIMENSIONAL DRAWING
Daikin City Generated Submittal Data
Daikin North America LLC, 5151 San Felipe, Suite 500, Houston, TX, 77056
www.daikinac.com www.daikincomfort.com
(Daikin's products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without
incurring any obligations)
Page 3 of 3