Installation Service Manual Gas-Fired Indirect Outdoor Make-Up Air Units – Models H-Series (5

Installation Service Manual Gas-Fired Indirect Outdoor Make-Up Air Units – Models H-Series (5

5-572.7

5H76233a1

July, 2010

installation and service manual gas-fired weatherproof duct furnaces/make-up air units gravity vented models HBG/HcG/HdG/HPG power vented models HBP/HcP/HdP/HPP

9900100

FOR YOUR SAFETY

The use and storage of gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous.

IMPORTANT

The use of this manual is specifically intended for a qualified installation and service agency.

A qualified installation and service agency must perform all installation and service of these appliances.

WARNING

Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death, and could cause exposure to substances which have been determined by various state agencies to cause cancer, birth defects or other reproductive harm.

Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.

inspection on arrival

1. Inspect unit upon arrival. In case of damage, report it immediately to transportation company and your local factory sales representative.

2. Check rating plate on unit to verify that power supply meets available electric power at the point of installation.

3. Inspect unit upon arrival for conformance with description of product ordered (including specifications where applicable).

FOR YOUR SAFETY

if you smell Gas:

1. don’t touch electrical switches.

2. extinguish any open flame.

3. immediately call your gas supplier.

THIS MANUAL IS THE PROPERTY OF THE OWNER.

PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.

sPecial Precautions / taBle of contents

sPecial Precautions

THE INSTALLATION AND MAINTENANCE INSTRUCTIONS

IN THIS MANUAL MUST BE FOLLOWED TO PROVIDE SAFE,

EFFICIENT AND TROUBLE-FREE OPERATION. IN ADDITION,

PARTICULAR CARE MUST BE EXERCISED REGARDING

THE SPECIAL PRECAUTIONS LISTED BELOW. FAILURE TO

PROPERLY ADDRESS THESE CRITICAL AREAS COULD

RESULT IN PROPERTY DAMAGE OR LOSS, PERSONAL

INJURY, OR DEATH. THESE INSTRUCTIONS ARE SUBJECT

TO ANY MORE RESTRICTIVE LOCAL OR NATIONAL CODES.

HaZard intensity levels

1.

danGer: Indicates an imminently hazardous situation which, if not avoided, WILL result in death or serious injury.

2. WarninG: Indicates a potentially hazardous situation which, if not avoided, COULD result in death or serious injury.

3. caution: Indicates a potentially hazardous situation which, if not avoided, MAY result in minor or moderate injury.

4.

imPortant: Indicates a situation which, if not avoided,

MAY result in a potential safety concern.

dANGER

Appliances must not be installed where they may be exposed to a potentially explosive or flammable atmosphere.

WARNING

1. All field gas piping must be pressure/leak tested prior to operation. Never use an open flame. Use a soap solution or equivalent for testing.

2. Gas pressure to appliance controls must never exceed 14"

W.C. (1/2 psi).

3. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.

4. All appliances must be wired strictly in accordance with wiring diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard to persons and property.

5. Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C.

6. To reduce the opportunity for condensation, the minimum sea level input to the appliance, as indicated on the serial plate, must not be less than 5% below the rated input, or

5% below the minimum rated input of dual rated units.

7. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% greater than the rated voltage.

8. When servicing or repairing this equipment, use only factory-approved service replacement parts. A complete replacement parts list may be obtained by contacting Modine

Manufacturing Company. Refer to the rating plate on the appliance for complete appliance model number, serial number, and company address. Any substitution of parts or controls not approved by the factory will be at the owners risk.

2 cAUTION

1. Appliances are designed for outdoor installation only.

DO NOT LOCATE APPLIANCES INDOORS.

2. Purging of air from gas lines should be performed as described in ANSI Z223.1 - latest edition “National Fuel

Gas Code”, or in Canada in CAN/CGA-B149 codes.

3. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% less than the rated voltage.

4. Do not reuse any mechanical or electrical component which has been wet. Such component must be replaced.

5-572.7

IMPORTANT

1. To prevent premature heat exchanger failure, do not locate

ANY gas-fired appliances in areas where corrosive vapors

(i.e. chlorinated, halogenated or acid) are present in the atmosphere.

2. To prevent premature heat exchanger failure, the input to the appliance, as indicated on the serial plate, must not exceed the rated input by more than 5%.

3. To prevent premature heat exchanger failure, observe heat exchanger tubes by looking at the heat exchanger through the field installed access openings in connecting ductwork in models HBG/HBP or the unit access doors in models

HDG/HDP, HCG/HCP, or HPG/HPP. If the bottom of the tubes become red while blower and duct furnace are in operation, check to be sure the blower has been set to the proper rpm for the application. Refer to page 15 for Blower

Adjustments.

4. Start-up and adjustment procedures should be performed by a qualified service agency.

5. To check most of the Possible Remedies in the troubleshooting guide listed in Table 54.1, refer to the applicable sections of the manual.

table of contents

Inspection on Arrival ............................................................ 1

Special Precautions ............................................................. 2

SI (Metric) Conversion Factors ........................................... 3

Unit Location ....................................................................... 3

Combustible Material and Service Clearances ............ 3

Roof Curb/Slab Mounted Installation .................................. 4

Duct Installation ................................................................... 5

Rigging Instructions ............................................................. 6

Unit Installation .................................................................... 6

Venting .......................................................................... 6

Gas Connections .......................................................... 7

Electrical Connections .................................................. 8

Evaporative Cooler ....................................................... 8

Cooling Coil .................................................................. 9

Start-Up Procedure ........................................................... 11

Pilot and Main Burner Adjustment .............................. 12

Blower Adjustment ...................................................... 14

Lubrication Recommendations ................................... 14

Damper Linkage Adjustment ...................................... 14

Control Operating Sequence ...................................... 16

Options .............................................................................. 18

General Performance Data ............................................... 26

Unit Selection .................................................................... 28

Blower Performance Data ................................................. 30

Blower Sheave Assembly Data ......................................... 34

Electrical Data ................................................................... 38

Motor Data ......................................................................... 38

Dimensions ....................................................................... 43

Weights .............................................................................. 51

Maintenance ...................................................................... 52

Service & Troubleshooting ................................................ 54

Model Designations ........................................................... 56

Start-up Checklist .............................................................. 58

Model Nomenclature for System Units .............................. 59

Commercial Warranty .......................................... Back Page

si (metric) conversion factors / unit location

si (metric) conversion factors table 3.1

to convert multiply By to obtain

"W.C. 0.24 kPa psig

°F

6.893

(°F-32) x 0.555 kPa

°C

inches feet

CFM

25.4

0.305

0.028 m mm meters

3 /min

to convert multiply By to obtain

CFH

Btu/ft3

pound

Btu/hr

gallons psig

1.699

0.0374

0.453

0.000293

3.785

27.7 m 3 /min mJ/m kg kW/hr liters

"W.C.

3

For HBP/HCP/HDP/HPP units, be sure clearances are maintained to the combustion air inlet louvers and power exhauster discharge cover. Units are designed for installation on non-combustible surfaces or combustible surfaces with the minimum clearances shown in Figure 3.1,

Table 3.2, and Table 3.3

6. On units that have fresh air openings, a method should be provided to prevent water and debris from entering the unit such as a rainhood and bird screen, evaporative cooler, etc.

7. On HBG/HBP and HCG/HCP models, adequate space must be provided to install the discharge duct as shown in Figure

7.1. to insure even air flow across the heat exchanger.

unit location

dANGER

Appliances must not be installed where they may be exposed to potentially explosive or flammable atmosphere.

cAUTION

Appliances are designed for outdoor installation only.

DO NOT LOCATE APPLIANCES INDOORS.

IMPORTANT

To prevent premature heat exchanger failure, do not locate

ANY gas-fired appliances in areas where corrosive vapors (i.e. chlorinated, halogenated or acid) are present in the atmosphere.

table 3.2 - combustible material clearances

model size

75

100/125

150/175

200/225

250/300

350/400

500/600

700/800

840/960

access side

(a)

0”

0”

0”

0”

0”

0”

0”

0”

0”

G front & rear

(B)

0”

0”

3”

4”

5”

11”

5”

11”

11”

digit 3

P access side

(a)

3”

3”

3”

3”

3”

3”

3”

3”

3”

front & rear

(B)

3”

3”

3”

4”

5”

11”

5”

11”

11”

location recommendations

1. When locating the furnace, consider general space and heating requirements and availability of gas and electrical supply.

2. Unit must be installed on the positive pressure side of the circulating blower.

3. Be sure the structural support at the unit location site is adequate to support the weight of the unit and any other required support structure. For proper operation the unit must be installed in a level horizontal position.

4. Do not install units in locations where the flue products can be drawn into the adjacent building openings such as windows, fresh air intakes, etc.

5. Be sure that the minimum clearances to combustible materials and recommended service clearances are maintained. For HBG/HCG/HDG/HPG units, be sure clearances are maintained to the combustion air/vent cap.

table 3.3 - service clearances

model size

75

100/125

150/175

200/225

250/300

350/400

500/600

700/800

840/960

recommended service clearance access side

(a) nonaccess side (c)

18"

20"

6"

6"

25"

27”

30"

41"

6"

6”

6"

6"

30"

41"

41"

6"

6"

6"

figure 3.1 - combustible material & service clearances

G or P non-access side

( c )

0”

0”

0”

0”

0”

0”

0”

0”

0”

Combustion Air/Vent

Cap on Models with

Digit 3=G

B

27.00

36.00

B

C

Power Exhauster

Discharge Cover on Models with

Digit 3=P

ACCESS

SIDE

A

SIDE VIEW

Minimum clearance to combustible for

HBP/HCP/HDP/HPP is 1.0" from rooftop.

FRONT VIEW

5-572.7

3

unit location/roof curB installation

sound and vibration levels

All mechanical equipment generates some sound and vibration that may require attenuation. Libraries, private offices, and hospital patient rooms will require more attenuation and in such cases an acoustical consultant may be retained to assist in the application. Locating the equipment away from the critical area is desirable within ducting limitations. Frequently, units can be located above utility areas, corridors, restrooms, and other non-critical areas. Generally, a unit should be located within 15 feet of a primary support beam. Smaller defections mean lesser vibration and noise transmission.

Roof curb must be installed level. If roof is pitched it will be necessary to construct a sub-base on which to install the curb.

Install the unit over roof decking with 2" acoustic fiberglass lining within curb area for sound attenuation. The return air duct should be acoustically lined and should be installed with a flexible connection. If the ceiling space is used as a plenum, the acoustically lined return intake duct should form an inverted tee with five foot minimum legs in each direction.

The discharge duct should be acoustically insulated and should have a flexible connection as illustrated.

figure 4.1 - suggested sound attenuation

2" Acoustic Fiberglass, 3 Lb. Density

Within Curb On Top of Roof Deck

Structural

Truss

Roof

Curb

3. Outside dimensions must be held when installing curb.

Top surface must be level and straight to insure weathertightness. All corners must be square.

4. All dimensions are +1/8 inch.

5. Final electric and gas connections must be made after unit is installed to allow for tolerance in setting of unit on curb.

For electrical power supply allow approximately eight feet of wire, plus provisions for weathertight flexible conduit for connection to unit, as required by local codes.

6. Maintain an 12-inch minimum height from top of roof deck to top of curb.

7. Caulk butt joints after curb is assembled and installed on roof structural members and roof flashing is added.

figure 4.2 - typical curb details

Curb Gasketing*

2 x 4 Wooden

Nailing Strip*

Counterflashing

(By Others)

Roofing

Material

(By Others)

Insulation

(By Others)

Curb*

Cant Strip

(By Others)

2" Acoustic

Fiberglass

(By Others)

Balancing

Damper

Roof Insulation

(By Others)

Flexible

Connection

Acoustic Duct

Liner Inside

Suspended

Ceiling

Flexible

Connection

Acoustic Duct

Liner Inside

curb or sub-Base mounted sites

An optional 16-inch high roof curb is available to simplify site preparation and raise the unit above roof water and snow level for drainage. It can be installed with the roof, and in advance of the unit. The curb is shipped knocked down with separate instructions (Literature 5-590) for its assembly, flashing, and sealing with the roof. A sub-base must be furnished by the installer if no curb is supplied for the roof. The sub-base, either steel or concrete, must provide required support with the unit bolted to sub-base. The following are some general guidelines for roof curb installed units:

1. The roof structure must be adequately designed to support the live weight load of the unit and any other required support structure. For the bearing loads normally encountered, the roof curb should be supported at points no greater than five feet apart. Additional truss reinforcement should be provided, if necessary.

2. Roof curbs supplied by Modine are fabricated from 16 gauge galvanized steel and supplied knocked down for assembly on the job site. The curb consists of two side pieces, two end pieces, gasketing, four joiner angles, four 2x4 inch wood nailing strips, nuts, bolts, and washers. Roof curbs over 120 inches long include two additional side pieces and two splice plates.

4

5-572.7

Roof

Truss

6" Inverted

Channel

Both Sides

(By Others)

*Available as a factory supplied, field installed accessory.

Roof

Deck

slab mounted sites — models HBG/HBP &

HcG/HcP

For ground level installation of a front-discharge unit prepare a level concrete slab at least four inches thick on adequate footings and a generous bed of gravel for drainage. (See

Figure 5.1). The slab should include threaded 5/8-inch anchor bolts spaced according to Figure 5.2. Anchor bolts should extend at least 1-1/2" above the surface of the floor to allow clearance for mounting washers, nuts and bolts (mounting washers, nuts and bolts by others). The slab should extend out at least six inches around the perimeter of the unit.

slaB mount/duct installation

figure 5.1 - slab-mounted furnace figure 5.3 - duct connections

1/2"

DUCT FURNACE

GRAVEL

BED

90°

FLANGED

DUCTWORk

DUCTWOR k

ACCESS

PANEL

4"

6"

ANCHOR

BOLTS

CONCRETE

SLAB

figure 5.2 - slab anchor Bolt dimensions

A

B

model size

HBG/HBP 75

HBG/HBP 100/125

HBG/HBP 150/175

HBG/HBP 200/225

HBG/HBP 250/300

HBG/HBP 250/300

HBG/HBP 350/400

HBG/HBP 350/400

HBG/HBP 500/600

HBG/HBP 500/600

HBG/HBP 700/800

HBG/HBP 700/800

HBG/HBP 840/960

HcG/HcP 75

HcG/HcP 100/125

HcG/HcP 150/175

HcG/HcP 200/225

HcG/HcP 250/300

HcG/HcP 250/300

HcG/HcP 350/400

HcG/HcP 350/400

5/8 Dia. (4)

Blower type

(digit 16) a

All

All

All

All

82.91

82.91

82.91

82.91

E, F, G, or H 82.91

I, J, or k 118.50

E, F, G, or H 82.91

I, J, or k 118.50

G or H 116.03

I, J, k, or L 151.62

G or H 116.03

I, J, k, or L 151.62

All 185.02

All

All

All

All

106.89

106.89

106.89

106.89

E, F, G, or H 106.89

I, J, or k 142.48

E, F, G, or H 106.89

I, J, or k 142.48

B

33.85

36.36

40.61

42.71

45.75

45.75

57.27

57.27

45.75

45.75

57.27

57.27

57.27

33.85

36.36

40.61

42.71

45.75

45.75

57.27

57.27

duct installation for HBG/HBP and HcG/HcP (Horizontal discharge):

1. The blower section back and bottom and the furnace discharge are designed to accept 90° flanged ductwork. See

Figure 5.3. Provide an airtight seal between the ductwork and the unit. Seams with cracks in the ductwork should be caulked and/or taped and be of permanent type. All duct connections outside the building MUST be weathertight to prevent rain and snow from entering the ductwork.

2. Acoustic duct liners are recommended on all internal return air ducts.

5-572.7

3"

Min.

3"

Min.

3. When a roof curb is used in conjunction with a factory supplied return air connector, the ductwork can be fastened to the connectors prior to the unit installation.

The connectors will accept 90° flanged ductwork. See

Figure 6.1.

4. Provide uniform air distribution over the heat exchanger.

Use turning vanes where required to obtain uniform air distribution. See Figure 5.4.

5. On model HBG/HBP, provide removable access panels on the downstream side of the unit. See Figure 5.3.

These openings should be large enough to view smoke or reflect light inside the casing to indicate leaks in the heat exchanger and to check for hot spots on the heat exchanger due to a lack of sufficient air (CFM). Not required on model HCG/HCP because the cooling cabinet access door can be removed for this purpose.

figure 5.4 - recommended field installed discharge duct configurations for models HBG/HBP and HcG/HcP

3"

Min.

Dimension "B" should never be less than 1/2 of dimension "A"

Turning

Vanes

3" Max.

Provide leak tight access panels in discharge duct for heat exchanger inspection.

Air

Flow

B

Turning

Vanes

3" Max.

Air

Flow

B

A

A

Turning

Vanes

3" Max.

12"

Min.

12"

Min.

SIDE VIEW

Provide leak tight access panels in discharge duct for heat exchanger inspection.

TOP VIEW

Provide leak tight access panels in discharge duct for heat exchanger inspection and overheat control service.

5

Baffle

B

A

Air

Flow

Turning

Vanes

12"

Min.

SIDE VIEW

duct installation/riGGinG instructions/unit installation

for HdG/HdP and HPG/HPP (downturn discharge):

1. The blower section back and bottom and the downturn plenum bottom is designed to accept 90° flanged ductwork on both the supply and return air openings. Refer to the roof curb (Figure 48.1) or the unit base (Figure 47.1) dimensional drawings to determine the location of the openings.

2. Acoustic duct liners are recommended on all internal supply and return air ducts.

3. When ductwork is installed prior to unit arrival, flexible connections should be included to make connections easier and to simplify possible future service.

4. When a roof curb is used in conjunction with factory supplied discharge and/or return air connectors, the ductwork can be fastened to the connectors prior to the unit installation. The connectors will accept 90° flanged ductwork. See Figure 6.1.

figure 6.1 - discharge and/or return air connectors

UNIT

BASE

90 FLANGED

DUCTWORk

(By Installer)

BEFORE UNIT INSTALLATION

CAULk ALL MATING SURFACES

(Caulk by installer)

ROOF

CURB

RETURN

AIR CONNECTOR

DISCHARGE

AIR CONNECTOR

utility connections

Utility and control connections can be made to the unit from the bottom for roof curb-mounted units or through the fixed side panels for horizontal supply and return units. Holes can be made in fixed side panels to accommodate utility connections as specified according to the unit dimensional drawings.

Sealing of holes cut in the unit casing for utility connections should be done with care to prevent air and water leaks.

rigging instructions

Four 3/4-inch holes at the extended ends of the mounting channels are supplied to facilitate lifting the unit with eyebolts to be furnished by the installer. For either crane or helicopter lift of the equipment to the rooftop, connect sturdy steel cables with eye loops as illustrated in Figure 6.2. To prevent cable from marring the cabinet end tops, use spreader bars or an angle iron frame at least 6" longer and wider than the unit to spread the lifting cables above the unit. For stability in lifting and lowering, include a spreader piece between the two cable spreaders as illustrated in Figure 6.2.

figure 6.2 - typical rooftop furnace rigging

INSTALLER’S

CABLE AND

SPREADERS

unit installation

Follow site preparation instructions for applicable curb, sub-base, or slab sites before installation. Check Model

Identification Plate of unit with plans to be sure unit is properly located. (See pages 56 and 57). Also inspect damper motors and dampers for proper type (e.g., two-position, modulating, fresh air only, fresh and return air, etc.). Although units may look outwardly similar, their function, capacities, options, and accessories will often vary. Check dimensions.

If unit is to be installed on a factory-supplied curb:

1. Install roof curb using previous roof curb instructions (pages

4 and 5).

2. Thoroughly clean and dry the top of the curb surface.

3. Lay a bead of weather resistant caulking on top perimeter of roof curb as illustrated in Figure 4.3.

4. Orient hoisted unit to its ductwork and set it down evenly on curb.

5. Make final unit connections to the electric power supply and remote control circuits. Connect the gas lines to the unit heating compartment in accordance with the submittal drawings and architect plans. Caulk all utility line clearance holes on the unit after connections are completed.

If unit is to be installed on a separate sub-base or slab, use steps 4 and 5.

venting

1. Installation of venting must conform with local building codes, or in the absence of local codes, with the National

Fuel Gas Code, ANSI Z223.1 (NFPA 54) - Latest Edition.

In Canada, installation must be in accordance with CAN/

CGA-B149.1 for natural gas units and CAN/CGA-B149.2 for propane units.

2. For HBG/HCG/HDG/HPG units, do not operate duct furnaces without the factory supplied vent cap (shipped loose) fastened securely in place. HBP/HCP/HDP/HPP units are shipped with the power exhauster discharge cover factory installed.

3. For HBG/HCG/HDG/HPG units, do not modify or obstruct the vent cap in any manner. For HBP/HCP/HDP/HPP units, do not modify or obstruct the combustion air inlet louvers or the power exhauster discharge cover.

4. Do not add any vents other than those supplied by the manufacturer.

6

INSTALLER’S

EYE BOLTS

FACTORY-SUPPLIED

ROOF CURB

MOUNTED ON ROOF

5-572.7

unit installation

Gas connections

WARNING

1. All field gas piping must be pressure/leak tested prior to

operation. Never use an open flame. Use a soap solution

or equivalent for testing.

2. Gas pressure to appliance controls must never exceed

14" W.C. (1/2 psi).

3. To reduce the opportunity for condensation, the minimum

sea level input to the appliance, as indicated on the serial

plate, must not be less than 5% below the rated input, or

5% below the minimum rated input of dual rated units.

cAUTION

Purging of air from gas supply line should be performed as described in ANSI Z223.1 - latest edition “National Fuel Gas

Code”, or in Canada in CAN/CGA-B149 codes.

figure 7.1 - recommended sediment trap/manual shut-off valve installation

GAS

SUPPLY LINE

3"

MIN.

GAS

SUPPLY LINE

SEDIMENT

TRAP

MANUAL GAS

SHUT-OFF VALVE

PLUGGED

1/8" NPT TEST

GAGE CONNECTION

GROUND

JOINT

UNION

W/ BRASS

SEAT

TO

CONTROLS

TO

CONTROLS

IMPORTANT

PLUGGED 1/8"

NPT TEST GAGE

CONNECTION

To prevent premature heat exchanger failure, the input to the appliance, as indicated on the serial plate, must not exceed the rated input by more than 5%.

1. Installation of piping must conform with local building codes, or in the absence of local codes, with the National Fuel Gas

Code, ANSI Z223.1 (NFPA 54) - Latest Edition. In Canada, installation must be in accordance with CAN/CGA-B149.1 for natural gas units and CAN/CGA-B149.2 for propane units.

2. Piping to units should conform with local and national requirements for type and volume of gas handled, and pressure drop allowed in the line. Refer to Table 13.2 to determine the cubic feet per hour (cfh) for the type of gas and size of unit to be installed. Using this cfh value and the length of pipe necessary, determine the pipe diameter from Table 7.1. Where several units are served by the same main, the total capacity, cfh and length of main must be considered. Avoid pipe sizes smaller than 1/2". Table 7.1 allows for a 0.3" W.C. pressure drop in the supply pressure from the building main to the unit. The inlet pressure to the unit must be 6-7" W.C. for natural gas and 11-14" W.C. for propane gas. When sizing the inlet gas pipe diameter, make sure that the unit supply pressure can be met after the 0.3"

W.C. has been subtracted. If the 0.3" W.C. pressure drop is too high, refer to the Gas Engineer’s Handbook for other gas pipe capacities.

Pipe length

(feet)

GAS

SUPPLY LINE

3"

MIN.

MANUAL GAS

SHUT-OFF VALVE

SEDIMENT

TRAP

Through hole in bottom of unit.

(caulk hole to prevent water leakage.)

GROUND

JOINT

UNION

W/ BRASS

SEAT

Manual gas shut-off valve is in the “OFF” position when handle is perpendicular to pipe.

table 7.1 - Gas Pipe capacities (cu. ft. per Hour)

10

1/2”

132

3/4”

278

natural Gas

1”

520

1-1/4” 1-1/2” 2”

1050 1600 3050

3. The gas piping to the unit can enter the unit from the side of the unit or from below (curb mounted units). Drill locator dimples are located in the side and bottom of the unit for field drilling the hole for the gas pipe entry. Install a ground joint union with brass seat and a manual shut-off valve external of the unit casing, and adjacent to the unit for emergency shut-off and easy servicing of controls, including a 1/8" NPT plugged tapping accessible for test gauge connection (See Figure 7.1). Verify the manual shut-off valve is gas tight on an annual basis.

note: Some local codes may require a manual shutoff valve external to the unit casing. In this case, the gas piping must exit the unit through the side piping hole, followed by the manual shut-off valve, piped back into the unit corner post, through the unit bottom, and lead to an additional union and manual shut-off valve.

4. Provide a sediment trap before each unit in the line where low spots cannot be avoided (See Figure 7.1).

5. When Pressure/Leak testing, pressures above 14" W.C.

(1/2 psi), close the field installed shut-off valve, disconnect the appliance and its combination gas control from the gas supply line, and plug the supply line before testing. When testing pressures 14" W.C. (1/2 psi) or below, close the manual shut-off valve on the appliance before testing.

5-572.7

20

30

40

50

60

70

80

90

100

125

150

92

73

63

56

50

46

43

40

38

34

31

190

152

130

115

105

96

90

84

79

72

64

350

285

245

215

195

180

170

160

150

130

120

730

590

500

440

400

370

350

320

305

275

250

1100 2100

890

760

670

610

560

530

490

460

410

380

1650

1450

1270

1150

1050

990

930

870

780

710

Gas pipe capacities based on gas pressure up to 14" W.C. through Schedule 40 pipe with a pressure drop of 0.3" W.C. for Natural gas with a specific gravity of

0.60.

For gas pipe capacities when using Propane gas (specific gravity of 1.50), multiply the value shown for Natural gas at the applicable pipe diameter and length by 0.63.

7

unit installation

8

electrical connections

WARNING

1. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.

2. All appliances must be wired strictly in accordance with wiring

diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard to persons and property.

3. Any original factory wiring that requires replacement must be

replaced with wiring material having a temperature rating of at least 105°C.

4. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% greater than rated voltage.

cAUTION

1. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% less than the rated voltage.

1. Installation of wiring must conform with local building codes, or in the absence of local codes, with the National

Electric Code ANSI/NFPA 70 - Latest Edition. Unit must be electrically grounded in conformance to this code. In

Canada, wiring must comply with CSA C22.1, Part 1,

Electrical Code.

2. Two copies of the job specific wiring diagram are provided with each unit, one located in the duct furnace electrical junction box and one in the electrical section of the unit.

Refer to this diagram for all wiring connections.

3. The wire gauge must be sized according to the National

Electric Code or CSA code based on the power supply voltage, amp draw, and length of run. Refer to Table 8.1 for maximum wire lengths and the number of wires that can be wired to each low voltage terminal block.

table 8.1 - low voltage (24v) maximum Wire length (ft.)

Wire Gauge

model no. trans.

digit 15 va 18 Ga 16 Ga 14 Ga 12 Ga 10 Ga

1

2

40

75

162

86

216

115

315

168

360

192

495

264

3

4

150

250

43

26

58

35

84

50

96

58

132

79

maximum # Wires per terminal

5 4 3 2 1

NEC-1996, Table 310-17, Copper wire with 90°C insulation, conductors in free space (not in conduit), 86°F ambient. For other wire types, refer to the NEC or

CSA code.

4. Make sure all multi-voltage components (motors, transformers, etc.) are wired in accordance with the power supply voltage.

5. The power supply to the unit must be protected with a fused or circuit breaker disconnect switch. Refer to the Factory

Mounted Option Locations (Figure 18.1) for the factory mounted disconnect switch location and then review the unit to determine if a factory installed dead front disconnect switch was provided. Accessory field installed disconnect switches should be mounted where shown in Figure 8.2. For fusible disconnect switches, refer to the Model Identification plate for the fuse size and type.

6. The power supply must be within 5% percent of the voltage rating and each phase must be balanced within 2 percent of each other. If not, advise the utility company.

7. External electrical service connections that must be installed include:

a. Supply power (120, 208, 240, 480, or 600 volts).

b. Thermostats, remote monitoring panels, building pressure sensors, time clocks, or any other accessory control devices that may be supplied (24 volts).

8. All outdoor electrical connections must be weatherized to prevent moisture from entering the electrical compartment.

9. Refer to the unit dimensional drawings on pages 43 through

46 for the location of the drill locator dimples in the side and bottom of the unit for field drilling the hole for the electrical conduit entry.

10. All supply power electrical connections are made in the electrical section of the unit. The low voltage (thermostat and accessory control devices) can be wired to either the electrical section or the duct furnace electrical junction box.

Refer to the wiring diagram for the terminal location of all low voltage wiring.

figure 8.2 - recommended accessory field installed disconnect switch mounting locations

ELECTRIC SUPPLY

COMPONENTS MUST BE

CLEAR OF SERVICE DOORS

DISCONNECT

ALTERNATE

LOCATION

WEATHERPROOF

DISCONNECT

SWITCH, WIRING

AND CONNECTOR

BLOWER

SERVICE

DOOR

HEATER

SERVICE

DOOR

OPT.

DOWN

TURN

DOOR

ELECTRIC

SUPPLY

LEFT HAND ACCESS

UNIT SHOWN

DISCONNECT

ALTERNATE

LOCATION

evaporative cooler installation

For units equipped with an evaporative cooler (Digit 22 = 3, 4,

5, 6, A, B, C, or D), refer to Installation and Service Manual -

Evaporative Coolers (Literature 5-588).

5-572.7

unit installation

cooling coil installation

Models with a cooling section can be provided with either a factory installed direct expansion (DX) evaporator, a chilled fluid

(for use with water, ethylene glycol, or propylene glycol fluids) coil, or the coil can be field supplied and installed by others.

For units equipped with a factory installed cooling coil (Digit

23 = 1), refer to the packing slip to determine the coil type provided. The cooling section is located downstream of the duct furnace heat exchanger in a blow-through configuration, preventing condensation on the heat exchanger in the cooling mode. Thus, a stainless steel heat exchanger is not required when a cooling section is used. (However, a stainless steel heat exchanger is still recommended when the combined entering/return air to the unit is below 40°F.)

figure 9.1 - cooling section

Optional double wall construction

DX single circuit (shown) and dual circuit coils available

Optional Factory

Installed

DX or Chilled

Water coil.

The cooling section includes a full coverage, 3-way sloping

409 stainless steel drain pan to remove condensate from coil headers, thermal expansion valves, and refrigerant piping.

Insulation is standard on outdoor units and optional on indoor units and double wall construction is optional on all units. The cabinet includes two doors, a removable upper door for service access to the coil once the plumbing has been installed and a lower door which includes a factory supplied 1" stubbed drain connection to the exterior of the cabinet. Field connections for coil inlet and outlet piping can be made through the cabinet corner post or back of the unit. The cooling section duct transition includes 1-1/2" flanges for fastening the sides of the coil. The bottom duct transition is angled to remove any condensation that may be entrained in the supply air stream.

For field supplied coils, do not exceed the maximum coil dimensions listed in Literature 82-135. If the coil supplied is smaller than the listed dimensions, field supplied blank off plates are required to prevent air bypass around the coil.

The coil is supported by two 14 gauge support rails which contain mounting provisions for fastening 4", 5", 6", 7.5", 8.5", and 10" deep coils. When obtaining the specifications from a coil manufacturer, it is important to obtain the pressure drop through the coil so that the proper motor horsepower can be selected.

Right or left hand coil header access to match gas controls

Fin spacings of 6,8,10,12 or 14 fins per inch

Adjustable mounting bracket for 2,3,4 and 6 row coils

Full coverage

3-way sloping

409 stainless steel drain pan

1” stubbed drain connection

condensate drain trap installation

The condensate drain line needs to include a P-trap immediately downstream of the connection to the unit. This trap should extend at least two inches below the connection to prevent air pressure from forcing air into the unit. The trap should be primed with a water/glycol solution to prevent freezing. All points where refrigerant, water or condensate lines enter the structure should be sealed and vibration dampened.

Include shut-off valves to isolate the cooling coil from the system in order to remove the coil for service or replacement without draining the entire system. For additional guidelines, refer to the ASHRAE Fundamentals Handbook section of piping recommendations.

table 9.1 - cooling coil Performance limits

model size

75

100

125

150

175

200

225

250

300

350

400

dX - single circuit dX - dual circuit chilled Water

1891

2206

2206

2521

2521

3352

3352

3724

3724

5214

5214

3.44

4.01

4.01

4.58

4.58

6.09

6.09

6.77

6.77

9.48

9.48

1707

2048

2048

2416

2416

3165

3165

3538

3538

4996

4996

3.10

3.72

3.72

4.39

4.39

5.76

5.76

6.43

6.43

9.08

9.08

1676

2011

2011

2372

2372

3214

3214

3592

3592

5073

5073

3.05

3.66

3.66

4.31

4.31

5.84

5.84

6.53

6.53

9.22

9.22

min max coil area max coil area max coil area cfm

(sq. ft.) cfm

(sq. ft) cfm

(sq. ft.) cfm

(all units) max. cooling tons

➁ ➂

dX chilled coils Water coils

609 ➃ 9.38

741 ➄ 11.43

926

1111

1296

1481

1667

1852

2222

2593

2963

11.43

13.42

13.42

18.12

18.12

20.24

20.24

27.26

27.26

10.56

12.62

12.62

14.77

14.77

19.28

19.28

21.33

21.33

29.25

29.25

Based on 550 feet per minute (FPM) coil face velocity.

1 Ton = 12,000 Btu/Hr

Based on 95°F Entering Dry Bulb, 75° Entering Wet Bulb.

Model Size 75 CFM listed for Chilled Water - DX Single Circuit CFM minimum is 688 and DX Dual Circuit CFM min is 621.

Model Size 100 CFM listed for Chilled Water - DX Single Circuit CFM minimum is 802 and DX Dual Circuit CFM min is 745.

5-572.7

9

unit installation

General refrigerant Piping

1. All field piping must be self-supporting. Long runs of piping need to be periodically supported to prevent excess vibration that can damage the piping and joints. It is recommended to provide dampening supports at intervals of length equivalent to 15 tube diameters.

2. All field brazing and welding should be performed using

high quality materials and an inert gas purge (such as

nitrogen) to reduce oxidation of the internal surface of the coil.

3. System piping should be flexible enough to allow for thermal

expansion and contraction of the coil.

direct expansion (dX) Piping

The refrigerant lines should be insulated to prevent warming or cooling of the refrigerant. If the suction line is allowed to be cooled, liquid will condense in the line and can severely damage the compressor. If the liquid line is warmed, the refrigerant can

"flash" into a gas. This will cause erratic operation of the expansion device and impair the heat transfer ability of the cooling coil.

figure 10.1 - General dX Piping

Liquid Line

Suction Header

Distributor

Equalizer Line

Nozzle

Coil

8. Failure to obtain a high vacuum is indicative of a great deal of moisture or a small leak. Break the vacuum with a charge of dry nitrogen or other suitable gas and recheck for leaks (soapy water works well). If no leaks are found, continue vacuuming the coil until the desired vacuum is reached.

chilled fluid Piping

To prevent noise within a system, an air vent is necessary to bleed off the accumulated air in the system. The vent should be located on the top of the inlet manifold where the air collects. Air in the system will generate noise and may cause water hammer that can damage the joints of the piping and the cooling coil.

The outlet manifold should have a drain installed on the bottom of the manifold to allow for periodic flushing of the system to remove sediments and corrosion products from the cooling coil. The lines between the unit and the structure should be insulated to prevent freezing of the water. Leak test the coil and connections as outlined in the section on this page.

figure 10.2 - General chilled fluid Piping

Air F low

Expansion Valve

(By Others)

Air Vent

Gate Valve

Tee

Re turn

Vent Plug

Suction Line

Remote Sensing Bulb

Straps

Suction Connection

1. Inspect the refrigerant distributor and verify that the nozzle

is in place.

2. Connect the suction line and suction connection.

3. Install the expansion valve (By Others). Follow the

expansion valve manufacturer's recommendations for

installation to avoid damaging the valve.

4. The expansion valve remote sensing bulb should be

securely strapped to the horizontal run of the suction line

at the 3 or 9 o'clock position and insulated.

5. Connect the liquid line to the expansion valve.

6. Leak test the coil and connections as outlined in the section on this page.

7. Use a vacuum pump to evacuate the coil and any

interconnecting piping that has been open to atmosphere.

Measure the vacuum in the piping using a micron gauge

located as far from the pump as possible (the vacuum at

the pump will be greater than the rest of the system).

Evacuate the coil to 500 microns or less then close the

valve between the pump and the system. If the vacuum

holds to 500 microns or less for one minute, the system

is ready to be charged or refrigerant pumped down in

another portion of the system can be opened to the coil.

A steady rise in microns would indicate that moisture is still

present and that the coil should be further vacuumed until

the moisture has been removed.

Dirt Leg

Cap

Union

Drain Plug

leak testing the coil and connections

1. Pressurize the coil, expansion valve assembly and suction connection to 100 psig with dry nitrogen or other suitable gas.

2. The coil should be left pressurized for a minimum of

10 minutes. a. If the coil holds the pressure, the hook-up can be considered leak free.

b. If the pressure drops by 5 psig or less re-pressurize the coil and wait another 10 minutes. If the pressure drops again, there is more than likely one or more small leaks which should be located and repaired.

c. Pressure losses greater than 5 psig would indicate a larger leak that should be isolated and repaired.

3. Be sure to check valves and fittings as potential sites for leakage or bleed. If the coil itself is found to be leaking, contact your local factory representative.

10

5-572.7

start-uP Procedure

IMPORTANT

1. To prevent premature heat exchanger failure, observe

heat exchanger tubes by looking at the heat exchanger

through the field installed access openings in connecting

ductwork in model HBG/HBP or the unit access doors in

models HDG/HDP, HCG/HCP, or HPG/HPP. If the bottom of

the tubes become red while blower and duct furnace are in

operation, check to be sure the blower has been set to the

proper rpm for the application. Refer to page 15 for Blower

Adjustments.

2. Start-up and adjustment procedures should be performed

by a qualified service agency.

1. Turn off power to the unit at the disconnect switch. Check that fuses or circuit breakers are in place and sized correctly. Turn all hand gas valves to the “OFF” position.

2. Remove the duct furnace and blower exterior panels and open the electrical compartment door.

3. Check that the supply voltage matches the unit supply voltage listed on the Model Identification plate. Verify that all wiring is secure and properly protected. Trace circuits to insure that the unit has been wired according to the wiring diagram.

4. Check that all electrical and gas connections are weatherized.

5. For HBG/HCG/HDG/HPG units, check to insure that the vent cap is installed and free from instruction. For HBP/HCP/

HDP/HPP units, check to insure that the combustion air inlet louvers and the power exhauster discharge cover is free from obstructions.

6. Check to see that there are no obstructions to the intake and discharge of the unit.

7. Check the belt tension and sheave alignment. Refer to Blower

Adjustments for proper belt tension.

8. Check bearings for proper lubrication. For units provided with pillow block bearings (See Model Nomenclature), refer to

Lubrication Recommendations for lubrication requirements.

9. Check to make sure that all filters are in place and that they are installed properly according to direction of air flow.

10. Perform a visual inspection of the unit to make sure no damage has occurred during installation.

11. Turn on power to the unit at the disconnect switch. Check to insure that the voltage between duct furnace electrical box terminals 1 and 2 is 24V.

12. Check the thermostat, ignition control, gas valve, and supply fan blower motor for electrical operation. If these do not function, recheck the wiring diagram. Check to insure that none of the Control Options have tripped.

13. For units with a return air damper, the return air damper linkage needs to be adjusted. Refer to Damper Linkage Adjustment.

14. Check to make sure that the damper opens properly without binding.

15. Check the blower wheel for proper direction of rotation when compared to the air flow direction arrow on the blower housing.

Blower wheel rotation, not air movement, must be checked as some air will be delivered through the duct furnace with the blower wheel running backwards.

16. Check the blower speed (rpm). Refer to Blower Adjustments for modification.

17. Check the motor speed (rpm).

18. Check the motor voltage. On three phase systems, check to make sure all legs are in balance.

5-572.7

19. Check the motor amp draw to make sure it does not exceed the motor nameplate rating. On three phase systems, check all legs to insure system is balanced.

20. Recheck the gas supply pressure at the field installed manualshut-off valve. The inlet pressure should be 6"-7" W.C. on natural gas or 11"-14" W.C. on propane. If inlet pressure is too high, install an additional pressure regulator upstream of the combination gas control.

21. Open the field installed manual gas shut-off valve.

22. Open the manual main gas valve on the combination gas valve. Call for heat with the thermostat and allow the pilot to light. (For HBP/HCP/HDP/HPP units, on a call for heat the power exhauster relay will energize the power exhauster motor. Once the power exhauster motor reaches full speed, a centrifugal switch in the motor will close before the pilot can light.) If the pilot does not light, purge the pilot line. If air purging is required, disconnect the pilot line at outlet of pilot valve. In no case should line be purged into heat exchanger. Check the pilot flame length (See Pilot Flame Adjustment).

23. Once the pilot has been established, check to make sure that the main gas valve opens. Check the manifold gas pressure

(See Main Gas Adjustment) and flame length (See Air Shutter

Adjustment) while the supply fan blower is operating.

24. Check to insure that gas controls sequence properly (See

Control Operating Sequence). Verify if the unit has any additional control devices and set according to the instructions in the Control Options.

25. Once proper operation of the unit has been verified, remove any jumper wires that were required for testing.

26. Close the electrical compartment door.

27. Replace all exterior panels.

Refer to page 58 for the Start-up Checklist.

If the unit has a cooling coil installed, verify the following upon start-up:

General - all coils

1. Proper air distribution is vital to coil performance. Air flow anywhere on the coil face should not vary by more than

20%.

2. Air velocities should be maintained between 200 and 550 feet per minute.

3. For chilled fluid coils, fluid velocities should be maintained within the recommended values of 1 to 8 fps for Water and

1 to 6 fps for Glycol solutions.

chilled fluid coils - initial start-up

1. Open all air vents so that air is eliminated from within the coil circuitry and headers. Verify that all vents and drains are not obstructed and do discharge a stream of water.

2. Fill the coil with water then close all vents.

3. Perform an initial hydrostatic leak test of all brazed, threaded or flanged joints, valves and interconnecting piping. Recheck the coil level and correct if necessary.

When the setup is found to be leak free, discharge and discard initial water charge. It is important that all grease, oil, flux and sealing compounds present from the installation be removed.

11

start-uP Procedure

Pilot Burner adjustment

The pilot burner is orificed to burn properly with an inlet pressure of 6-7" W.C. on natural gas and 11-14" W.C. on propane gas, but final adjustment must be made after installation. If the pilot flame is too long or large, it is possible that it may cause soot and/or impinge on the heat exchanger causing a fracture. If the pilot flame is shorter than shown, it may cause poor ignition and result in the controls not opening the combination gas control. A short flame can be caused by a dirty pilot orifice. Pilot flame condition should be observed periodically to assure trouble-free operation.

to adjust the Pilot flame

1. Create a call for heat from the thermostat.

2. Remove the cap from the pilot adjustment screw. For location, see the combination gas control literature supplied with unit.

3. Adjust the pilot length by turning the screw in or out to achieve a soft steady flame 3/4" to 1" long and encompassing 3/8"-1/2" of the tip of the thermocouple or flame sensing rod (See Figure 12.1).

4. Replace the cap from the pilot adjustment screw.

figure 12.1 - correct Pilot flame

3/4" to 1"

to adjust the manifold Pressure

1. Move the field installed manual shut-off valve to the “OFF” position.

2. Remove the 1/8" pipe plug in the pipe tee and attach a water manometer of “U” tube type which is at least 12" high.

3. Move the field installed manual gas shut-off valve to the

“ON” position.

4. Create a high fire call for heat from the thermostat.

5. Determine the correct high fire manifold pressure. For natural gas 3.5” W.C., for propane gas 10” W.C. Adjust the main gas pressure regulator spring to achieve the proper manifold pressure (for location, see the combination gas control literature supplied with unit).

6. If the unit has Electronic Modulation gas controls

(determine from the Model Identification Digit 12), the low fire gas pressure needs to be adjusted. Using Figure 13.1 for item number locations, this is accomplished as follows:

a.Disconnect power.

b.Remove all wires from duct furnace terminal “43” and remove cover plate (2).

c.Turn on power at the disconnect switch.

d.Remove the maximum adjustment screw (4), spring

(5), and plunger (8). A small magnet is useful for this purpose. CAUTION - The plunger is a precision part.

Handle carefully to avoid marring or picking up grease and dirt. Do not lubricate.

e.Using minimum adjusting screw (9), adjust low fire manifold pressure to 0.56" W.C. for natural gas and 1.6"

W.C. for propane gas.

f.Replace plunger and spring retainer, spring, and maximum adjusting screw in proper order.

g.Using maximum adjustment screw (4), adjust high fire manifold pressure to 3.5" W.C. for natural gas and 10"

W.C. for propane gas.

h.Disconnect power.

i. Replace cover plate (2) and re-install all wires from duct furnace terminal “43”.

7. After adjustment, move the field installed manual shut-off valve to the “OFF” position and replace the 1/8" pipe plug.

8. After the plug is in place, move the field installed manual shut-off valve to the “ON” position and recheck pipe plugs for gas leaks with soap solution.

figure 12.2 - checking manifold Pressure with “u” tube manometer main Burner adjustment

The gas pressure regulator (integral to the combination gas control) is adjusted at the factory for average gas conditions.

It is important that gas be supplied to the duct furnace in accordance with the input rating on the serial plate. Actual input should be checked and necessary adjustments made after the duct furnace is installed. Over-firing, a result of too high an input, reduces the life of the appliance and increases maintenance. Under no circumstances should the input exceed that shown on the serial plate.

Measuring the manifold pressure is done at the tee in the manifold (See Figure 12.2).

12

5-572.7

manifold tee

start-uP Procedure

figure 13.1 - maxitrol modulating valve adjustments air shutter adjustment

Proper operation provides a soft blue flame with a well-defined inner core. A lack of primary air will reveal soft yellow-tipped flames. Excess primary air produces short, well-defined flames with a tendency to lift off the burner ports. For both natural and propane gas, the air shutters can be adjusted to control the burner flame height. The air shutters can be accessed by reaching behind the manifold tee shown in Figure 12.2. The larger models may require the removal of the manifold (see

Manifold Assembly Removal).

natural Gas flame control

Control of burner flames on duct furnaces utilizing natural gas is achieved by resetting the primary air shutters (See Figure

53.2) to either increase or decrease primary combustion air.

Prior to flame adjustment, operate duct furnace for about fifteen minutes. The main burner flame can be viewed after loosening and pushing aside the gas designation disc on the side of the burner box.

To increase primary air, loosen the air shutter set screws and move the air shutters closer to the manifold until the yellowtipped flames disappear. (See Figure 53.2 for air shutter and heat exchanger support locations.) To decrease primary air, move the air shutters away from the manifold until flames no longer lift from burner ports, but being careful not to cause yellow tipping. Retighten set screws after adjustment.

Propane Gas flame control

An optimum flame will show a slight yellow tip. Prior to flame adjustment, operate furnace for at least fifteen minutes. Loosen air shutter set screws and move the air shutters away from the manifold to reduce the primary air until the yellow flame tips appear. Then increase the primary air until yellow tips diminish and a clean blue flame with a well defined inner cone appears.

table 13.1 - manifold Pressure and Gas consumption

model size type of Gas

Btu/cu. ft.

specific Gravity

High fire manifold Pressure

inches of Water column

75

100

125

150

175

200

225

250

300

350

400

500

600

700

800

840

960

Cfh

Orifice Drill Size

Cfh

Orifice Drill Size

Cfh

Orifice Drill Size

Cfh

Orifice Drill Size

Cfh

Orifice Drill Size

Cfh

Orifice Drill Size

Cfh

Orifice Drill Size

Cfh

Orifice Drill Size

Cfh

Orifice Drill Size

Cfh

Orifice Drill Size

Cfh

Orifice Drill Size

Cfh

Orifice Drill Size

Cfh

Orifice Drill Size

Cfh

Orifice Drill Size

Cfh

Orifice Drill Size

Cfh

Orifice Drill Size

Cfh

Orifice Drill Size

Model contains 2 furnaces. Values shown are per furnace.

Model contains 3 furnaces. Values shown are per furnace.

natural

1040

0.60

3.5

72.1

20

96.1

30

120.2

25

144.2

30

168.3

27

192.3

23

216.3

20

240.4

25

288.7

20

336.5

27

384.6

23

240.4 ➀

25

288.7 ➀

20

336.5 ➀

27

384.6 ➀

23

336.5 ➁

27

384.6 ➁

23

Propane

2500

1.53

10

30.0

37

40.0

45

50.0

42

60.0

45

70.0

43

80.0

40

90.0

37

100.0

42

120.0

37

140.0

43

160.0

40

100.0 ➀

42

120.0 ➀

37

140.0 ➀

43

160.0 ➀

40

140.0 ➁

43

160.0 ➁

40

no. of orifices

1

2

2

3

3

3

3

4

4

6

6

6

6

6

6

4

4

5-572.7

13

14 start-uP Procedure

Blower adjustments

If blower fan speed changes are required, adjust motor sheave as follows:

1. Refer to page 34 to determine correct blower speed according to job requirements, then proceed with steps 2 through 8.

2. Loosen motor base and take belt off of motor sheave.

3. Loosen set screw on outer side of adjustable motor sheave.

figure 14.1 - motor sheave adjustment

Toward Motor

Set Screw

Adjustable Half of Sheave

4. Turn outer side of motor sheave clockwise until motor sheave is fully closed.

5. From fully closed position, turn outer side of motor sheave counterclockwise until the proper number of turns open are achieved.

6. Retighten motor sheave set screw, replace belt and retighten motor base. Motor base should be shifted for proper belt tension which is 3/4" deflection with about 5 lbs. of force.

figure 14.2 - Belt tension adjustment lubrication recommendations

The blower can be provided with either spider or pillow block bearings. Spider bearings are permanently lubricated and do not require lubrication. Pillow block bearings are shipped greased from the factory but will require lubrication. The bearings should be checked and lubricated before each heating season but a more frequent lubrication schedule may be required based on the environment in which the unit is installed, and the frequency of the equipment operation. Shell Alvania #2 lubricant is recommended.

damper linkage adjustment

If the unit is provided with a return air damper, to prevent shipping damage, the return air damper linkage is disconnected and the damper closed. Before operating the unit, the fresh and return air dampers must be connected. This is accomplished by the following:

1. The damper actuator should be de-energized and the fresh air damper in a fully closed position.

2. Open the return air damper in a fully open position.

3. Slide the connecting rod into the ball joint on the blade arm with the return air damper fully open. See Figure 14.3.

4. Tighten the 5/16" hex head screw on the ball joint.

figure 14.3 - damper linkage adjustment

Connecting

Rod

Ball

Joint

Blade Arm

Damper

Blade

3/4" deflection with 5 lbs. of force

7. Recheck blower rpm after adjustment.

note: Do not fire unit until blower adjustment has been made or unit may cycle on high limit control.

8. Check motor amps. Do not exceed nameplate amps shown on motor nameplate.

5-572.7

PaGe intentionally left BlanK

5-572.7

15

start-uP Procedure

control operating sequence

All weatherproof units are supplied with intermittent pilot ignition systems. These systems are offered with 100% shut-off with continuous retry for operation on natural gas and 100% shut-off with lockout for units operating on propane gas. On all systems, both the main burner and pilot burner are turned off

100% when the thermostat is satisfied.

For natural gas units, the ignition controller is 100% shut-off with continuous retry. On a call for heat, the system will attempt to light the pilot for 70 seconds. If the pilot is not sensed for any reason, the ignition control will wait for approximately six minutes with the combination gas control closed and no spark.

After six minutes, the cycle will begin again. After three cycles, some ignition controllers lockout for approximately one hour before the cycle begins again. This will continue indefinitely until the pilot flame is sensed or power is interrupted to the system.

For propane gas units, the ignition controller is 100% shutoff with lockout. On a call for heat, the system will attempt to light the pilot for 70 seconds. If the pilot is not sensed for any reason, the ignition control will lockout, the pilot gas valve shut off and the sparking discontinued. The system will not attempt to relight until power has been interrupted to the controls and the controls are reset via the thermostat.

note: Factory Installed Options (see page 18) could change the listed sequence of operation based on their function. The descriptions given are for the basic unit.

single-stage Gas controls

Utilizes a single-stage combination gas control, an ignition control, and a single-stage low voltage thermostat.

1. The thermostat calls for heat.➀

2. The pilot valve opens and the spark ignitor sparks in an attempt to light the pilot.

3. Once the pilot is lit, the flame sensor proves the pilot and stops the spark ignitor from sparking.

4. The main gas valve is opened and the main burner is lit to

100% full fire.

5. The time delay relay starts the blower after 30 to 45 seconds.

6. The unit continues to operate until the thermostat is satisfied, at which time both the main and pilot valves close 100%.

7. The time delay relay stops the blower after 30 to 45 seconds.

two-stage Gas controls

9. The unit continues to operate until the low stage thermostat is satisfied, at which time both the main and pilot valves close 100%.

10. The time delay relay stops the blower after 30 to 45 seconds.

electronic modulating Gas controls single furnace - model sizes 75-400

Utilizes an electronic modulating/regulating gas control, combination gas valve, an ignition control, modulating amplifier, and either a modulating room thermostat or modulating duct thermostat with remote temperature set point adjuster. The thermostat controls can modulate the gas flow between 40% through 100% full fire.

When the thermostat is satisfied, the amplifier cuts power to the combination gas valve which prevents gas flow to both the main and pilot burners.

When duct sensing is utilized, a room override thermostat can be added. When calling for heat, the room override thermostat provides full fire operation until the space temperature is satisfied.

Control is then returned to the duct sensing control. In this situation, either the duct sensor or the room override thermostat can call for heat.

1. The thermostat calls for heat. ➀

2. The pilot valve opens and the spark ignitor sparks in an attempt to light the pilot.

3. Once the pilot is lit, the flame sensor proves the pilot and stops the spark ignitor from sparking.

4. The main gas valve is opened and the main burner is lit to

100% full fire.

5. The time delay relay starts the blower after 30 to 45 seconds.

6. The modulating gas valve can be controlled by either an electronic modulating room or duct thermostat. The thermostat can modulate the firing rate between 40% through 100% full fire. The call for heat is created by a resistance signal (8000 to 12000 ohms) in the thermostat.

The amplifier converts this resistance into a DC voltage

(0 to 12 volts DC with 0 volts high fire and 12 volts low fire). The output voltage is applied to the modulating gas valve to control the gas flow to the main burner. As the temperature drops, the voltage drops causing the modulating valve to open further. If the discharge air temperature increases, the voltage increases causing the modulating valve to close allowing less gas flow to the main burner. For further information regarding the operation of the electronic modulating system, consult the literature provided with the unit.

7. The unit continues to operate in this manner until the thermostat is satisfied, at which time both the main and pilot valves close 100%.

8. The time delay relay stops the blower after 30 to 45 seconds.

Utilizes a two-stage combination gas control, an ignition control, and a two-stage low voltage thermostat. The unit fires at 50% fire on low stage and 100% fire on high stage.

1. The thermostat calls for low stage heat.➀

2. The pilot valve opens and the spark ignitor sparks in an attempt to light the pilot.

3. Once the pilot is lit, the flame sensor proves the pilot and stops the spark ignitor from sparking.

4. The main gas valve is opened and the main burner is lit to

50% fire.

5. The time delay relay starts the blower after 30 to 45 seconds.

6. If the temperature at the thermostat continues to fall, the thermostat will call for high stage heat.

7. The main gas valve is opened completely and the main burner is lit to 100% full fire.

8. The unit continues to operate until the high stage of the thermostat is satisfied, at which time the main valve closes to 50% fire.

electronic modulating Gas controls two & three furnaces - model sizes 500-960

One Master furnace is provided with up to two Slave furnaces that utilize electronic modulating/regulating gas controls, combination gas valves, ignition controls, one multiple furnace modulating amplifier, and either a modulating room thermostat or modulating duct thermostat with remote temperature adjustment. The thermostat controls can modulate the gas flow of all the furnaces between 40% through 100% full fire. The amplifier sends a signal to all of the gas valves so that they modulate at the same percentage. When the thermostat is satisfied, the amplifier cuts power to the combination gas valves which prevents gas flow to both the main and pilot burners.

For Models HBP/HCP/HDP/HPP after the thermostat calls for heat, the power exhauster relay is energized starting the power exhauster motor. Once the motor has reached full speed, the power exhauster centrifugal switch closes energizing the gas control circuit.

16

5-572.7

start-uP Procedure

When duct sensing is utilized, a room override thermostat can be added. When calling for heat, the room override thermostat provides full fire operation until the space temperature is satisfied. Control is then returned to the duct sensing control.

In this situation, either the duct sensor or the room override thermostat can call for heat.

The sequence of operation for Electronic Modulating Gas

Controls - Two & Three Furnaces is the same as Electronic

Modulating Gas Controls - Single Furnace.

electronic modulating Gas controls -

Building management control

(0-10vdc or 4-20 ma signal)

Utilizes an electronic modulating/regulating gas control, combination gas valve, an ignition control, modulating signal conditioner, and an inverted (0 Vdc or 4mA being high fire and

10 Vdc or 20 mA being low fire) 0-10Vdc or 4-20 mA input signal provided by a Building Management System (BMS).

The signal conditioner can modulate the gas flow between

40% through 100% full fire. When the BMS thermostat (field supplied) is satisfied, the BMS heat contact (field supplied) opens to cut power to the combination gas valve which prevents gas flow to both the main and pilot burners.

1. The BMS thermostat (field supplied) calls for heat and closes the BMS heat contact (field supplied). ➀

2. The pilot valve opens and the spark ignitor sparks in an attempt to light the pilot.

3. Once the pilot is lit, the flame sensor proves the pilot and stops the spark ignitor from sparking.

4. The main gas valve is opened and the main burner is lit to

100% full fire.

5. The time delay relay starts the blower after 30 to 45 seconds.

6. The modulating gas valve is controlled the BMS thermostat. The thermostat can modulate the firing rate between 40% through 100% full fire by modulating the input signal between either 0-10Vdc or 4-20 mA (The signal conditioner can accept a 0-10 Vdc signal when all the dip switches are in the “OFF” position and 4-20 mA signal when all the dip switches are in the “ON” position).

The signal conditioner converts the input signal into a DC voltage (0 to 12 volts DC with 0 volts high fire and 12 volts low fire). The output voltage is applied to the modulating gas valve to control the gas flow to the main burner. As the temperature drops, the voltage drops causing the modulating valve to open further.

If the discharge air temperature increases, the voltage increases causing the modulating valve to close allowing less gas flow to the main burner. For further information regarding the operation of the electronic modulating system, consult the literature provided with the unit.

7. The unit continues to operate in this manner until the thermostat is satisfied, at which time the BMS heat contact opens resulting in both the main and pilot valves closing

100%. (If the unit was not provided with a time delay relay, the blower stops at this time.)

8. The time delay relay stops the blower after 30 to 45 seconds.

variable air movement applications

Units may be supplied with variable frequency drives for applications where variable air volume is required. The minimum air flow may be varied between 30 and 100% of the full speed air flow depending on the controls selection of the unit. Due to the extra restrictions of the controller all selections must be performed with the AccuSpec configuration software.

Within AccuSpec, three variable frequency drive speed control changeover options are variable:

1. Two speed which may be controlled by a manual high/low switch which may be factory mounted on the control panel or shipped loose for field installation or by exhaust fan interlocks.

2. Floating building pressure sensing which utilizes a photohelic pressure controller to adjust the building pressure by varying the amount of makeup air supplied to the space.

3. Building management control which allows for an external signal of 0-10VDC of 4-20mA to adjust the unit airflow.

Additionally, when the unit is equipped with a two-speed motor, the allowable minimum CFM of the HFG/HFP duct furnace can be 66% of the minimum listed CFM in Table 26.1 if the unit is applied as follows:

1. The unit is provided with 2-stage, mechanical modulation, or electronic modulating gas controls. (see Model

Identification).

2. The unit is provided with a factory installed discharge air controller.

3. The system does not include a room thermostat.

The factory installed discharge air thermostat will prevent the unit from firing above the allowable 100°F rise when the unit is at or above the minimum CFM by monitoring the discharge air and going to low fire. A room thermostat, because it is located remote from the unit, could cause the unit to over-fire.

For Models HBP/HCP/HDP/HPP after the thermostat calls for heat, the power exhauster relay is energized starting the power exhauster motor. Once the motor has reached full speed, the power exhauster centrifugal switch closes energizing the gas control circuit.

5-572.7

17

oPtions - factory installed

figure 18.1 - factory mounted option locations

1. Discharge Thermostat

2. Low Gas Pressure Switch

3. High Gas Pressure Switch

4. Power Exhauster

5. Timed Freeze Protection

6. Ignition Controller

7. Combustion Air/Exhaust Cap

8. Control Relay

9. Time Delay Relay

10. Furnace Low Voltage Terminal Strip

11. Power Exhauster Relay

12. Furnace Supply Power Terminal Strip

13. Control Step Down Transformer

14. Control Relay

15. Blower Low Voltage Terminal Strip

16. Dead Front Disconnect Switch

17. Step Down Transformer Fuses

18. Step Down Transformer

19. Factory Installed Minimum Positioner

20. Extended Grease Line Zerk Fittings

21. Extended Grease Lines

22. Return Air Fire Stat

23. Blower Housing

24. Pillow Block Bearings

25. Blower Motor

26. Filters

27. Fresh Air Damper

28. Enthalpy Sensor

29. Rainhood and Birdscreen

30. Direct Drive Damper Actuator

31. Enthalpy Controller

32. Damper to Damper Linkage

33. Return Air Damper

34. Proportional Temp Controller Sensor

35. Motor and Blower Vibration Isolation

36. Blower Support

37. Convenience Outlet

38. Blower Door Switch

39. Dirty Filter Switch

40. Motor Starter/VFD Control

41. Mild Temperature Thermostat

42. Proportional Temp Controller

43. Warm-Up Stat

All units include the standard (STD) features. The unit must be reviewed to determine the optional (OPT) features that may have been supplied with the unit.

(1) discharge thermostat – (oPt)

The discharge thermostat is factory installed in the discharge air stream of the unit. For additional information, refer to the thermostat vendor literature provided in the literature packet with the unit.

note: Model Sizes 500-960 contain multiple furnaces so multiple thermostats/sensors may be included.

figure 18.2 - two-stage capillary type thermostat

44. Blower Supply Power Terminal Strip

45. Service Switches

46. Electronic Modulating Amplifier

47. Electronic Modulating Gas Valve

48. Air Flow Proving Switch

49. High Limit Switch

50. Supply Air Fire Stat

51. Main Gas Valve

52. Burner Box

53. Direct Drive Damper Actuator

54. Discharge Damper

The thermostat(s) provided can be one of the following: a) Two-stage Capillary Type Thermostat – The thermostat includes a thermostat body that is factory installed below the unit junction box. The thermostat body contains the discharge air set point adjuster that must be field set.

b)

Two-stage Electronic Thermostat - Includes a factory installed discharge air sensor. The thermostat body is field installed remotely and includes the discharge air set point adjuster that must be field set. Refer to Literature

5-577.

figure 18.3 - two-stage electronic thermostat

Right

Setpoint

Adjuster

R B

R B

W

W

Left

Duct Furnace

Electrical

Duct

Furnace

Electrical

Control

Box

Thermostat body

(Shown with cover removed)

Duct

Furnace

Electrical

Control

Box

18

5-572.7

oPtions - factory installed

c) Electronic Modulating Discharge Air Thermostat – Includes a factory installed mixing tube and discharge air sensor. The set point adjuster is field installed remotely and must be field set. Refer to Literature 5-578.

figure 19.1 - electronic modulating discharge air thermostat

Discharge Air

Sensor Terminals

Duct Furnace

Electrical

Duct

Furnace

Electrical

Control

Box exhauster motor centrifugal switch that closes when the motor reaches full speed. The unit door includes a factory installed power exhauster discharge cover and inlet combustion louvers.

For information about venting, refer to the Installation – Venting section.

(5) timed freeze Protection – (oPt)

The timed freeze protection system is factory installed in the duct furnace electrical junction box with the sensor (30°-75°F adjustable) factory installed in the discharge air stream. On initial start-up, the timed delay in the system allows the unit to go through the normal ignition sequence. The timed delay is an automatic reset switch and adjustable for 1-10 minutes. In the event that the unit fails to fire after this period, the discharge air sensor will sense the cold air and will shut down the entire unit.

figure 19.3 - timed freeze Protection module

1

2

3

(2) low Gas Pressure switch – (oPt)

The low gas pressure switch is factory installed in the duct furnace above the gas train. The switch monitors the gas pressure upstream of all the gas controls and shuts off the electric supply to the ignition controller and combination gas valve if low gas pressure is experienced. This will shut off all gas flow to the burner. The switch has an automatic reset so that if the gas pressure is interrupted and then is returned, the switch will automatically allow the unit to operate when gas conditions are returned to the allowable range of the pressure switch. The pressure switch range is 2" to 14" W.C. and should be set to insure that the minimum inlet gas pressure is available (6" W.C. for natural gas, 11" W.C. for propane gas).

figure 19.2 - low or High Gas Pressure switch

NC

NO

C

Reset Switch

(3) High Gas Pressure switch – (oPt)

The high gas pressure switch is factory installed in the duct furnace above the gas train. The switch monitors the gas pressure downstream of all the gas controls and shuts off the electric supply to the ignition controller and combination gas valve if high gas pressure is experienced right before the manifold. This will shut off all gas flow to the burner. The switch has a manual reset so that if the gas pressure is too high, a service person must check the unit to make sure that none of the gas controls have been damaged by the high gas pressure and then reset the switch to allow the unit to operate when gas conditions are returned to the allowable range of the pressure switch. The pressure switch range is 2" to 16" W.C. and should be set to insure that the maximum manifold gas pressure is not exceeded (3.5" W.C. for natural gas, 10" W.C. for propane gas).

(4) Power exhauster – (std on HBP/HcP/HdP/HPP units)

The power exhauster is factory installed in the duct furnace section. On a call for heat, the power exhauster creates a combustion draft through the duct furnace prior to the pilot being energized. The draft is proven through the power

5-572.7

(6) ignition controller – (std)

The ignition controller is factory installed in the duct furnace electrical junction box with the spark ignitor and sensor located on the burner. All units are supplied with intermittent pilot ignition systems. For natural gas units, the ignition controller is 100% shut-off with continuous retry. For propane gas units, the ignition controller is 100% shut-off with lockout. Please see the section titled "Control Operating Sequence" in the "Start-Up Procedure" section for operational details.

(7) combustion air/exhaust cap – (std on HBG/HcG/HdG/

HPG units)

The combustion air/exhaust cap is shipped loose in a separate carton for field installation. For information about venting, refer to the Installation – Venting section. For information about installation of the cap, refer to Literature 5-573 – Vent Cap

Installation & Submittal Data which is provided with the cap.

(8) control relay – (oPt)

The control relay is factory installed in the duct furnace electrical junction box. The relay has a 24v coil with double-pole, double throw (DPDT) contacts rated for a maximum of 30 amps @

115V/1Ph. Refer to the unit wiring diagram for the function of the switching operation of the relay.

19

oPtions - factory installed

(9) time delay relay – (std)

The time delay relay is factory installed in the duct furnace electrical junction box. The time delay relay allows the gas controls to operate for approximately 30 seconds before the blower starts. This allows the heat exchanger a warm up period so that the initial delivered air coming out of the ductwork is not cool. The time delay relay also keeps the motor running for approximately 30 seconds after the call for heat has been satisfied to remove the residual heat from the heat exchanger. For single phase units below 2 Hp, the time delay relay controls the motor directly. For single phase units 2 Hp and greater and all three phase units, the time delay relay controls the motor starter.

(10) furnace low voltage terminal strip – (std)

The furnace low voltage terminal strip is located in the duct furnace electrical junction box. The terminal strip is labeled to match the electrical wiring diagram provided with the unit.

Low voltage labeling ranges from terminal numbers 1 to 79. All field wiring connections should be made to the top side of the terminals to prevent miswiring by modifying the factory wiring which is made to the bottom of the terminal strip.

(16) dead front disconnect switch – (oPt)

WARNING

When the dead front disconnect switch is in the “OFF” position, supply power remains energized at the blower supply power terminal strip and the top of the dead front disconnect switch. When providing service on or near these terminals, building supply power to the unit should be de-energized.

figure 20.1 - dead front disconnect switch assembly

Handle opening instruction table

Supply Power Terminals

(See Warning)

(11) Power exhaust relay – (std on HBP/HcP/HdP/HPP units)

The control relay is factory installed in the duct furnace electrical junction box. The relay has a 24v coil with single-pole single throw (SPST) contacts. On a call for heat, the relay coil is energized resulting in the contacts energizing the power exhauster motor.

(12) furnace supply Power terminal strip – (std)

The furnace supply power terminal strip is located in the duct furnace electrical junction box. The terminal strip is labeled to match the electrical wiring diagram provided with the unit.

Supply power labeling ranges from terminal numbers 80 to 99.

All field wiring connections should be made to the bottom side of the terminals to prevent miswiring by modifying the factory wiring which is made to the top of the terminal strip.

Pinch handle latch

& handle together when opening and closing door

To override turn shaft 90° C.W.

(with door open)

Blower Electrical Section

Stand-off Panel

The dead front disconnect switch is factory installed in the electrical section. The disconnect switch is designed so that it must be turned “OFF” before entry to the electrical control cabinet can be obtained (See Figure 20.1). When in the “OFF” position, power is disconnected to all unit wiring electrically following the switch (See Warning). For servicing the unit, the disconnect switch can be manually overridden by using a wrench and turning the disconnect switch shaft 90° clockwise

Fusible and circuit breaker switches available. For fusible switches, Class “J” time delay fuses must be field provided matching the fuse size listed on the Model Identification plate.

(13) control step down transformer – (std)

The control step down transformer is located in the duct furnace electrical junction box. The transformer is used to step down the supply power (115V, 208V, 230V, 460V, 575V) to 24V. This transformer is used to control the gas controls, damper actuator, motor starter, etc. Refer to the unit model number to determine the volt- amp (VA) capacity of the duct furnace. The 15th digit indicates the VA (See Model

Nomenclature).

(14) control relay – (oPt)

The control relay is factory installed in the electrical section.

The relay has a 24v coil with double-pole, double throw

(DPDT) contacts. Refer to the unit wiring diagram for the function of the switching operation of the relay. The two normally open and two normally closed contacts are rated for a maximum of 30 amps @ 115V/1Ph.

(

17) step down transformer fuses – (oPt)

The transformer fuses are factory installed in the electrical section.

The fuses are included to protect the transformer. Fuses included.

(18) step down transformer – (oPt)

The step down transformer is factory installed in the eletrical section. The transformer is required for power exhausted units

(Digit 2 = P) with a supply voltage of 460V/3Ph and 575V/3Ph and all units that have an evaporative cooler (Digit 22 = 3,4,5, or 6).

For all units with an evaporative cooler, when the supply power voltage is 208V/1Ph or 208V/3Ph, the transformer is provided to step down the voltage from 208V to 115V. In this case, the evaporative cooler pump motor operates at 115V.

For power exhausted units and all units with an evaporative cooler, when the supply power voltage is 460V/3Ph or

575V/3Ph, the transformer is provided to step down from supply power voltage to 115V. In this case, the evaporative cooler pump motor operates at 115V.

(15) Blower low voltage terminal strip – (std)

The blower low voltage terminal strip is located in the electrical section. The terminal strip is labeled to match the electrical wiring diagram provided with the unit. Low voltage labeling ranges from terminal numbers 1 to 79. All field wiring connections should be made to the right side of the terminals to prevent miswiring by modifying the factory wiring which is made to the left side of the terminal strip.

20

(19) factory installed minimum Positioner – (oPt)

The factory installed minimum positioner is installed in the electrical section and is used with a modulating damper actuator to set the minimum percentage of outside air. The minimum positioner dial is manually set between 0 to 100% resulting in a 2 to 10 VDC signal being sent to the damper actuator. When used in conjunction with the Proportional Temp Controller, the positioner sets the minimum outside air percentage and the Proportional Temp Controller then modulates between the minimum position and 100% outside air.

5-572.7

oPtions - factory installed figure 21.1 - minimum Positioner

80

60

Belimo

%

40

20 is factory installed in the blower section. The fresh air damper is used an outside air shut-off damper so ultra low leak,

Class II leakage resistance (less than 10 CFM/ft2 at 1" W.C.) dampers with self-compensating stainless steel side seals and santoprene and galvanized steel blade seals are used.

(28) enthalpy sensor – (oPt)

An enthalpy sensor is provided with Air Control option GJ

(Digits 20 & 21) and factory installed on the rear of unit in the inlet air stream. The enthalpy sensor senses and combines the temperature and humidity of the outdoor air to provide the 4-20 mA input signal to the Enthalpy Controller. The enthalpy sensor is used in conjunction with the Enthalpy Controller (Item 31) and a mixed air temperature sensor (not shown).

(29) rainhood and Birdscreen – (oPt)

The rainhood and birdscreen is shipped loose for field installation at the back of the blower section. For installation instructions, refer to Literature 5-589 supplied with the rainhood and birdscreen.

(

(21) extended Grease lines – (oPt)

The extended grease lines are factory installed in the blower section from the Extended Grease Line Zerk Fittings (20) to the

Pillow Block Bearings. The grease lines allow the pillow block bearings to be lubricated without requiring the service personnel to remove both blower doors to access the bearings. The grease lines will require filling at the time of first lubrication.

22) return air fire stat – (oPt)

The return air fire stat is factory installed in the electrical section with the sensor in the return air stream. In case of elevated temperatures in the return air stream, the manual reset switch shuts down the entire unit. If the limit temperature is exceeded, a service person must inspect the unit for the cause of the high discharge temperature, take corrective action, and then reset the switch.

(30) direct drive damper actuator – (oPt)

The direct drive damper actuator is factory installed in the blower section on the side of the fresh air damper. The actuator controls the position of the fresh air damper. The return air damper, if provided, is controlled by the damper linkage between the two dampers. All damper actuators are low voltage

(24V). For Right Hand units (Digit 9 = R), during operation the actuator should rotate in the counterclockwise direction when viewed from the service side of the unit. For Left Hand units (Digit 9 = L), during operation the actuator should rotate in the clockwise direction when viewed from the service side of the unit. Three different types of dampers actuators can be provided: Two-position, Modulating, and Floating.

( 23) Blower Housing – (std)

The blower housing is factory installed in the blower section.

The blower housing contains a double width, double inlet

(DWDI) blower wheel so both sides of the blower must be free from obstructions for proper operation. For Right Hand units

(Digit 9 = R), during operation the blower wheel should rotate in the clockwise direction when viewed from the service side of the unit. For Left Hand units (Digit 9 = L), during operation the blower wheel should rotate in the counterclockwise direction when viewed from the service side of the unit. If necessary, interchange supply power wiring to reverse blower rotation.

Two-position Damper Actuator: A two-position damper actuator is provided with Air Control options DA, EA, EQ, and FA (Digits

20 & 21). The two-position damper actuator provides open/ closed operation of the fresh air damper. When the damper is energized, the fresh air damper is opened to 100% outside air in 75 seconds (For units with a two-position damper limiter, the outside air percentage would be the set by the damper limiter.

See Two-Position Damper Limiter below). All two-position damper actuators are spring return, so when the damper is de-energized, the fresh air damper will spring closed. All twoposition dampers include auxiliary switches (one normally open and one normally closed) that reverse when the damper actuator is at 85° rotation (adjustable).

Two-Position Damper Limiter: The two-position damper limiter is factory set to prevent the outside air damper from opening

100%. The outside air percentage and the actuator end switch is set based on the unit order.

(24) Pillow Block Bearings – (oPt)

The blower bearings are factory installed in the blower section.

The blower can be provided with either spider or pillow block bearings. Spider bearings are permanently lubricated and do not require lubrication. Pillow block bearings are shipped non-greased from the factory and require lubrication before start-up. For lubrication recommendations, see Lubrication

Recommendations.

(25) Blower motor – (std)

The blower motor is factory installed in the blower section. The blower motor can be provided in a variety of supply voltages, frame types, and motor horsepowers. Refer to the model nomenclature to determine the type of motor provided. The blower motor is supplied with an adjustable sheave that can be used to increase/decrease the blower RPM. For instructions on changing the blower RPM, refer to Blower Adjustments.

(26) filters – (oPt)

When filters are supplied with the unit, a rack and the filters are factory installed in the blower section. The unit can be supplied with 1" or 2" permanent filters, 2" FARR® Aeropleat or 2" FARR® 30/30 filters. For filter replacement, refer to

Maintainance.

(27) fresh air damper – (oPt)

When a fresh air damper is supplied with the unit, the damper

5-572.7

Field adjustment of the two-position damper limiter is accomplished by the following:

1. Determine the amount of damper rotation required

(Percentage of outside air).

2. Locate the angle of rotation limiter on the actuator so that its edge lines up with the degree graduation on the actuator face which corresponds with the required rotation. (See Figure

22.1 which is shown at 50% rotation limit.)

3. Find the appropriate cross-hair location through the slot of the limiter. This is the screw mounting location.

4. Pierce through the label material to allow easy fastening of the retaining screw.

5. Position the limiter back to the desired position, making sure the locating “teeth” on the limiter are engaged into the locating holes on the actuator.

6. Fasten the limiter to the actuator using the self tapping screw provided.

7. Test the damper rotation either manually with the manual crank or apply power and if required, a control signal.

Re-adjust if necessary.

21

oPtions - factory installed figure 22.1 - two-position damper actuator and limiter

L

R

Adjustable end switch set to angle of rotation

Actuator clamp at

50% rotation limit

Modulating Damper Actuator: A modulating damper actuator is provided with Air Control options GA, GB, GC, GD, GE,

GF, GG, GH, GJ, Gk, GM, and GN (Digits 20 & 21). The modulating damper actuator provides incremental operation of the fresh air damper (The return air damper is controlled by the fresh air damper position). Full 90° rotation of the modulating actuator requires 150 seconds. All modulating damper actuators operate using a 0-10 Vdc input signal (Air Control GB utilizes a resistor to convert from a 4-20 mA to 0-10 Vdc) from a damper controller. All modulating damper actuators are spring return, so when the damper is de-energized, the fresh air damper will spring closed.

Floating Damper Actuator: A floating damper actuator is provided with Air Control option HP (Digits 20 & 21). The floating damper actuator provides forward and reversing damper operation in response to contact closures from the space pressure controller. When the space pressure is above the desired set point, a high pressure contact on the space pressure controller energizes the damper to drive the fresh air damper closed. When the space pressure is below the desired set point, a low pressure contact on the space pressure controller energizes the damper to drive the fresh air damper open. When the space pressure is between the high and low set points, the damper “floats” at the fresh air percentage that satisfied the space pressure controller. Full 90° rotation of the floating actuator requires 150 seconds. For additional information on the space pressure controller, refer to Literature

5-585.

COOLING MODE

When the space thermostat calls for cooling, the system operates as follows:

Outdoor Air Enthalpy is Below Changeover Set Point

1. The outdoor air damper is proportioned open (and the return

air damper is proportioned closed) to maintain between 50°F

and 56°F at the mixed temperature air sensor.

2. During economizer operation, mechanical cooling is operated

by the second stage of the cooling on the space thermostat.

Outdoor Air Enthalpy is Above Changeover Set Point

1. The outdoor air damper is closed to its minimum position.

2. A call for cooling from the space thermostat brings on

mechanical cooling.

The enthalpy controller is used in conjunction with the Enthalpy

Sensor (Item 28) and a mixed air temperature sensor (not shown). The mixed air temperature sensor is factory installed in the blower section to sense the combined temperature of the fresh and return air streams. The sensor is non-adjustable and when in the free cooling mode, modulates the dampers to maintain between 50°F and 56°F at the sensor.

The enthalpy controller contains a minimum position adjustment and an enthalpy changeover set point that must be field set.

figure 22.2 - enthalpy controller

The damper actuator is designed to “float” and therefore it is not spring return. When the unit is de-energized under normal operation, the fresh air damper is closed by a relay contact closure which electrically drives the damper closed. If the supply power to the unit is interrupted before the damper actuator can drive closed, the fresh air damper will remain open. The damper can be manually closed through the use of the manual override switch on the floating damper actuator.

Minimum Position Adjustment:

The minimum position adjustment keeps the outdoor air damper from closing completely during system operation to provide ventilation in both the heating and cooling modes.

To set the minimum position adjustment:

1. Disconnect mixed air sensor from terminals T and T1 on the

enthalpy controller.

2. Make sure the factory installed jumper is in place across terminals P and P1.

3. Connect 24 Vac across terminals TR and TR1.

4. Adjust the minimum position adjustor with a screwdriver for

the desired minimum position.

(

31) enthalpy controller – (oPt)

An enthalpy controller is provided with Air Control option GJ

(Digits 20 & 21) and factory installed in the blower section.

The purpose of the enthalpy controller is to use outside air for cooling, whenever possible, to reduce compressor operation of the mechanical cooling system. The economizer functions as a true first stage of cooling and provides maximum fuel economy during the cooling cycle.

Outdoor Enthalpy Changeover Set Point

The outdoor enthalpy changeover set point returns the outdoor air damper to the minimum position when the enthalpy rises above its set point. Enthalpy set point scale markings, located on the enthalpy controller, are A, B, C, and D. See Figure 23.1 for the corresponding control point. The factory installed 620ohm jumper placed across terminals S

R

and + is required for proper operation and should not be removed. Refer to suppliers literature supplied with the unit for additional information.

HEATING and VENTILATING MODE

When the space thermostat calls for heat or it is in the fan

ON position without a call for cooling (ventilation mode), the economizer is automatically locked out. It holds the outdoor air damper at the minimum position setting.

22

(32) damper to damper linkage – (oPt)

Units with fresh and return air dampers include a damper actuator that controls the fresh air damper. The return air damper position is controlled by the fresh air damper through the connecting rod. For adjustment, refer to Damper Linkage

Adjustment.

5-572.7

oPtions - factory installed figure 23.1 - enthalpy changeover set Point control Points

The convenience outlet is factory installed in the blower section for providing power for 115V service equipment (trouble light, power tools, etc.). The 115V ground fault circuit interrupter

(GFCI) is rated for 15 amps and includes test and reset switches. A separate field supplied 115V/1Ph power supply must be routed through the electrical section wall into the back of the convenience outlet junction box.

(38) Blower door switch – (oPt)

The blower door switch is factory installed inside the blower section door on the access side of the unit. When the blower section door is removed, the momentary switch is released and interrupts power to the low voltage circuit. For single phase units 1-1/2 Hp and less, the door switch de-energizes a relay that controls blower motor operation. For three phase units and single phase units 2 Hp and greater, the door switch deenergizes the motor starter that controls blower motor operation.

For servicing, the switch is equipped with an override position that can be manually pulled out to override the switch. See

Figure 23.2

figure 23.2 - Blower door switch with manual override

(

33) return air damper – (oPt)

When a return air damper is supplied with the unit, the damper is factory installed in the blower section. The return air damper is used as a air balancing damper so low leak, Class III leakage resistance (less than 40 CFM/ft2 at 1" W.C.) dampers with selfcompensating stainless steel side seals and santoprene blade seals are used.

(34) Proportional temperature controller sensor – (oPt)

A proportional temperature controller sensor is provided with Air

Control options GF, GG, GH, Gk, GM, or GN (Digits 20 & 21) and factory installed in the blower section. The sensor provides the mixed air temperature signal to the A350P Proportional

Temperature Controller which is mounted in the electrical section.

(

35) motor and Blower vibration isolation – (oPt)

The motor vibration isolation is factory installed in the blower section below the blower support bracket. The four (4)

13/32" neoprene vibration mount grommet provides isolation of the blower housing and motor from the blower support channels. The blower vibration isolation is factory installed in the blower section between blower discharge and the blower duct connection. The blower duct connection is not rigidly mechanically fastened and the 1/4'' thick gasketing around the duct transition provides vibration isolation.

(36) Blower support – (std)

The blower supports are factory installed in the blower section.

The blower supports are used to rigidly support the weight of the blower and motor during operation and shipping.

(37) convenience outlet – (oPt)

WARNING

Do not perform service on the convenience outlet without

disconnecting its power supply. The convenience outlet power

supply is separate from main power supply to the unit. When

the main disconnect switch is de-energized, the convenience

outlet power supply remains energized.

COM

NC NO

(

39) dirty filter switch – (oPt)

The dirty filter pressure switch is factory installed in the electrical section. The dirty filter pressure switch monitors the pressure differential between the two sides of the filters. When the filters become dirty, the differential pressure increases and trips the pressure switch which energizes a light on the remote monitoring panel. The pressure differential switch must be field set because setting the switch requires the blower to be in operation and the ductwork to be installed.

setting the dirty filter switch

The range of the dirty filter pressure switch is adjustable between 0.17" to 5.0" W.C.

1. Ensure that the unit filters are clean. Clean or replace if necessary.

2. Connect the leads of a continuity tester to the NO and C terminals of the dirty filter pressure switch. See Figure 24.1

3. Set the thermostat so that there is a call for heat. This should fire the burner and the blower should start.

4. Turn the set screw of the pressure switch clockwise until it stops. This will set the pressure at 5.0" W.C. and the continuity tester should be sensing an open circuit.

5. Begin turning the screw counterclockwise until the continuity tester senses a closed circuit. This determines the base pressure of the system.

6. Turn the screw clockwise until the continuity tester senses an open circuit and then one additional full turn (This is approximately 0.25" W.C.) This will allow for the increase in static pressure due to dirty filters.

5-572.7

23

oPtions - factory installed figure 24.1 - dirty filter Pressure switch and air flow

Proving switch

Positive pressure connector

Negative pressure connector

Pressure adjustment set screw set to the desired mild temperature condition (typically set at

60°F or 5°-10°F below duct or room thermostat).

(42) Proportional temperature controller – (oPt)

A proportional temperature controller is provided with Air

Control options GF, GG, GH, Gk, GM, or GN (Digits 20 & 21) and factory installed in the electrical section. The controller compares the mixed air temperature set point and the mixed air temperature from the Proportional Temperature Controller

Sensor. The controller sends a 2-10 Vdc signal to the modulating damper actuator in order to maintain the set point.

The controller includes a set point dial that must be field set to the desired mixed air temperature (typically 55°F).

figure 24.3 - Proportional temperature controller

(40) motor starter – (oPt)

The motor starter is factory installed in the electrical section. A motor starter is required for all three phase motors and single phase motors 2 Hp and greater. The motor starter current set point dial is factory set to the motor full load amp draw listed on the motor nameplate.

The overload module of the motor starter is designed to trip to protect the motor from exceeding the nameplate amps. If the motor exceeds the amp draw on the current set point dial, the trip condition is indicated by a red color in the trip indicator window. The motor starter can be placed in the automatic or manual reset positions. Automatic reset is accomplished by depressing the “RESET” button and turning the button 1/4 turn.

When in the automatic reset position, if the overload module trips, the module will reset itself once the overload relay has cooled. In the manual reset position, if the overload module trips, the “RESET” button must be depressed before the blower can operate.

The contractor module includes one (1) normally open auxiliary contact. The contact rating is 10 amps.

If the factory installed motor starter option was not ordered with a unit that has a three phase motor or single phase motor 2 Hp or greater, a motor starter must be field supplied and installed.

figure 24.2 - motor starter

A1

1 L1 3 L2 5 L3

A2

13 NO

VOLTS

2 4 6 8 10

ON

A350 P

4 8 12 16 25

MILLIAMPS

JOHNSON

CONTROLS

Set Point

Dial

Contactor

Module

Current

Set Point

Dial

2

T1

4

T2

6

T3

14

NO

A2

Trip

Indicator

Window

Reset

(43) Warm-up stat – (oPt)

A warm-up stat is provided with Air Control options Gk, GM, or

GN (Digits 20 & 21) and factory installed in the electrical section with the sensor in the return air stream. The warm-up thermostat monitors the return air temperature to the unit and prevents the fresh air dampers from opening until the temperature of the return air has reached the desired set point (typically 65°F or

5°F below the room temperature).

(44) Blower supply Power terminal strip – (std)

The blower supply power terminal strip is located in the electrical section. The terminal strip is labeled to match the electrical wiring diagram provided with the unit. Supply power labeling ranges from terminal numbers 80 to 99. All field wiring connections should be made to the bottom side of the terminals to prevent miswiring by modifying the factory wiring which is made to the top of the terminal strip.

Overload

Module

2

98

NO

T1

97

4

T2

H

95

NC

6

96

T3

E

T

E

S

(40) variable frequency drive – (oPt)

The VFD controller adjusts the motor RPM to vary the unit airflow. The minimum air flow may be varied between 30 and 100% of the full speed airflow depending on the controls selection of the unit. The control changeover options are two speed, floating building pressure sensing, and building management control.

(45) service switches – (oPt)

The service switches are factory installed in the electrical section. The service switches allow for service personnel to independently test operation of the damper, blower, and furnace without using jumper wires. The switches override the remote monitoring panel and/or thermostats to energize each component directly. All switches need to be reset to the “OFF” position after testing otherwise the components will remain energized (See Figure 25.1).

(41) mild temperature thermostat – (oPt)

The mild temperature thermostat is factory installed in the electrical section. The mild temperature thermostat is designed to lockout the burner during mild weather conditions which prevents the burner from cycling. The thermostat must be field

24

5-572.7

(46) electronic modulation amplifier – (oPt)

An electronic modulation amplifier is provided factory installed in the duct furnace electrical junction box when the unit is equipped with Electronic Modulating Gas Controls (Digit 12 =

4 or 5). The amplifier processes the thermostat temperature and set point signals to modulate the firing rate between 40% to 100% full fire. For additional information, refer to Control

Operating Sequence.

oPtions - factory installed figure 25.1 - service switches

(52) Burner Box – (std)

The burner box is located in the duct furnace section and contains the burner and pilot assembly. The burner box includes an access panel for removal of the burner for inspection and servicing.

(47) electronic modulating Gas valve – (oPt)

An electronic modulating gas valve is provided factory installed in the duct furnace gas train when the unit is equipped with

Electronic Modulating Gas Controls (Digit 12 = 4, 5, 6, 7, or 8).

The gas valve modulates the firing rate between 40% to 100% full fire based on the input signal from the Electronic Modulation

Amplifier or Signal Conditioner. For additional information, refer to Control Operating Sequence.

(48) air flow Proving switch – (oPt)

The air flow proving switch is factory installed in the duct furnace electrical junction box. The air flow proving switch monitors the pressure differential between the duct furnace and the atmosphere. The purpose of the air flow proving switch is to cut power to the gas controls if a positive pressure is not measured by the switch. This could be caused by a lack of air movement through the heat exchanger (Refer to Figure 24.1).

(53) direct drive damper actuator – (oPt)

The direct drive damper actuator is factory installed in the downturn plenum section. The actuator controls the position of the supply air damper and can only be used on 100% make-up air units. All damper actuators are low voltage (24V). For Right

Hand units (Digit 9 = R), during operation the actuator should rotate in the counterclockwise direction when viewed from the service side of the unit. For Left Hand units (Digit 9 = L), during operation the actuator should rotate in the clockwise direction when viewed from the service side of the unit. When the damper is energized, the fresh air damper is opened to 100% outside air in 75 seconds. All two-position damper actuators are spring return, so when the damper is de-energized, the fresh air damper will spring closed. All two-position dampers include auxiliary switches (one normally open and one normally closed) that reverse when the damper actuator is at 85° rotation (adjustable).

NOTE: The air flow proving switch will prevent any heat exchanger warm-up because the gas controls can not be energized until air flow is proven.

(54) discharge damper – (oPt)

When a discharge air damper is supplied with the unit, the damper is factory installed in the downturn plenum section. The discharge air damper is used an outside air shut-off damper so ultra low leak, Class II leakage resistance (less than 10 CFM/ft2 at 1" W.C.) dampers with self-compensating stainless steel side seals and santoprene and galvanized steel blade seals are used.

setting the air flow Proving switch

The range of the air flow proving switch is adjustable between

0.17" to 5.0" W.C.

1. Set the thermostat so that there is a call for heat. This should start the blower and then the burner ignition sequence.

2. Turn the set screw of the pressure switch clockwise until it stops. This will set the pressure at 5.0" W.C.

3. Turn the screw counter-clockwise until the gas controls light and then one additional full turn. (This is approximately

0.25" W.C.) This will allow for dirty filters or any other slight static pressure increases in the system.

(not shown) circuit analyzer – (oPt)

The circuit analyzer is factory installed on the door of the electrical section. The circuit analyzer is used to quickly assist service personnel in troubleshooting by monitoring the unit firing sequence and vital operating steps. Lights will come on as a point of electrical operation is passed and proven. If any light is not lit, that is the point where failure occurred.

(49) High limit switch

Automatic – (STD)

The automatic reset high limit switch is factory installed in the duct furnace electrical junction box. If the limit temperature is exceeded, the gas controls are de-energized until the switch is cooled.

figure 25.2 - circuit analyzer

Circuit analyzer tagging will vary based on the unit ordered.

Circuit analyzer shown is for reference only.

Manual – (OPT)

The manual reset high limit switch is factory installed in place of the standard automatic reset high limit switch located in the duct furnace electrical junction box. In case of a failure of the blower motor, blockage of the inlet air, etc., the manual reset switch prevents the unit from cycling on the high limit. If the limit temperature is exceeded, a service person must inspect the unit for the cause of the high discharge temperature, take corrective action, and then reset the switch.

(50) supply air fire stat – (oPt)

The supply air fire stat is factory installed in the duct furnace electrical junction box with the sensor in the discharge air stream.

In case of elevated temperatures in the supply air stream, the manual reset switch shuts down the entire unit. If the limit temperature is exceeded, a service person must inspect the unit for the cause of the high discharge temperature, take corrective action, and then reset the switch.

(51) main Gas valve – (std)

The main gas valve is factory installed in the duct furnace gas train. The main gas valve provides the pilot, regulator, main gas, and manual shutoff functions. For additional information, see the supplier literature included with the unit.

5-572.7

25

General Performance data

table 26.1

General Performance data - models With Blower

model size (digits 4-6)

Btu/Hr input

Btu/Hr output

Blower style (digit 16 letter)

max. temp. rise (°f)

min. temp. rise (°f)

max. cfm

min. cfm

75 100 125 150 175

75000 75000 100000 100000 125000 125000 150000 150000 175000 175000

60000 60000 80000 80000 100000 100000 120000 120000 140000 140000

A or B C or D

100 100

C or D E or F

100 85

C or D

100

E or F

100

C or D E or F

100 100

C or D E or F

100 100

28 20

1980 2778

556 556

21

3450

741

20

3704

875

27

3450

926

20

4630

926

33

3350

1111

20

5556

1111

39

3350

1296

23

5556

1296

model size (digits 4-6)

Btu/Hr input

Btu/Hr output

Blower style (digit 16 letter)

max. temp. rise (°f)

min. temp. rise (°f)

max. cfm

min. cfm

200 225 250

200000 200000 200000 225000 225000 225000 250000 250000 250000

160000 160000 160000 180000 180000 180000 200000 200000 200000

C or D E or F G or H C or D E or F G or H E or F G or H I, J, or k

100 85

44 28

3400 5250

1481 1750

85

23

6500

1750

100

49

3400

1667

95

32

5250

1750

95

26

6500

1750

100

31

100

26

6000 7250

1852 1852

96

20

9259

1925

model size (digits 4-6)

Btu/Hr input

Btu/Hr output

Blower style (digit 16 letter)

max. temp. rise (°f)

min. temp. rise (°f)

max. cfm

min. cfm

300 350 400

300000 300000 300000 350000 350000 350000 400000 400000 400000

240000 240000 240000 280000 280000 280000 320000 320000 320000

E or F G or H I, J, or k E or F G or H I, J, or k E or F G or H I, J, or k

100 100 100 100 100 100 100 100 100

37 31

6000 7250

2222 2222

20

2222

45

11111 5700

2593

37

7000

2593

22

12000

2593

52

5700

2963

42

7000

2963

25

12000

2963

model size (digits 4-6)

Btu/Hr input

Btu/Hr output

Blower style (digit 16 letter)

max. temp. rise (°f)

min. temp. rise (°f)

max. cfm

min. cfm

500 600 700

500,000 500,000 500,000 600,000 600,000 600,000 700,000 700,000 700,000

400,000 400,000 400,000 480,000 480,000 480,000 560,000 560,000 560,000

G or H I, J, or k

120 120

L

120

G or H I, J, or k

120 120

L

120

G or H I, J, or k

120 120

L

120

53 40

7000 9259

3086 3086

40

9259

3086

63

7000

3704

40

11111

3704

40

11111

3704

76

6850

4321

40

12963

4321

40

12963

4321

model size (digits 4-6)

Btu/Hr input

Btu/Hr output

Blower style (digit 16 letter)

max. temp. rise (°f)

min. temp. rise (°f)

max. cfm

min. cfm

800 840 960

800,000 800,000 800,000 1,050,000 1,050,000 1,200,000 1,200,000

640,000 640,000 640,000 840,000 840,000 960,000 960,000

G or H I, J, or k L I, J, or k L I, J, or k L

120

87

6850

4938

120

46

13000

4938

120

41

14500

4938

120

60

13000

6481

120

60

13000

6481

120

68

13000

7407

120

63

14000

7407

Ratings are shown for elevations up to 2000 ft. For higher elevations the input rating should be reduced at the rate of 4% for each 1000 feet above sea level.

For Canada, in elevations between 2000 and 4500 feet, the unit must be derated to 90% of the rating listed above.

For Variable Air Movement Applications, see page 17.

26

5-572.7

General Performance data

table 27.1

air temperature rise

Btu/Hr

input output 20 max

25 30 35 air temperature rise through unit (°f)

40 45 50 55 60 cfm

65 70 75 80 85 90 95 100 min

75,000 60,000 2778 2222 1852 1587 1389 1235 1111 1010

926 855 794 741 694 654 617 585 556

100,000 80,000 3704 2963 2469 2116 1852 1646 1481 1347 1235 1140 1058 988 926 871 823 780 741

125,000 100,000 4630 3704 3086 2646 2315 2058 1852 1684 1543 1425 1323 1235 1157 1089 1029 975

926

150,000 120,000 5556 4444 3704 3175 2778 2469 2222 2020 1852 1709 1587 1481 1389 1307 1235 1170 1111

175,000 140,000

- 5185 4321 3704 3241 2881 2593 2357 2160 1994 1852 1728 1620 1525 1440 1365 1296

200,000 160,000 - 5926 4938 4233 3704 3292 2963 2694 2469 2279 2116 1975 1852 1743 1646 1559 1481

225,000 180,000

- 6667 5556 4762 4167 3704 3333 3030 2778 2564 2381 2222 2083 1961 1852 1754 1667

250,000 200,000 9259 7407 6173 5291 4630 4115 3704 3367 3086 2849 2646 2469 2315 2179 2058 1949 1852

300,000 240,000 11111 8889 7407 6349 5556 4938 4444 4040 3704 3419 3175 2963 2778 2614 2469 2339 2222

350,000 280,000 - 10370 8642 7407 6481 5761 5185 4714 4321 3989 3704 3457 3241 3050 2881 2729 2593

400,000 320,000

- 11852 9877 8466 7407 6584 5926 5387 4938 4558 4233 3951 3704 3486 3292 3119 2963

Btu/Hr

input output 40 max

45 50 55 60 air temperature rise through unit (°f)

65 70 75 80 cfm

85 90 95 100 105 110 115 120 min

500,000 400,000 9259 8230 7407 6734 6173 5698 5291 4938 4630 4357 4115 3899 3704 3527 3367 3221 3086

600,000 480,000 11111 9877 8889 8081 7407 6838 6349 5926 5556 5229 4938 4678 4444 4233 4040 3865 3704

700,000 560,000 12963 11523 10370 9428 8642 7977 7407 6914 6481 6100 5761 5458 5185 4938 4714 4509 4321

800,000 640,000 14500 13000 11852 10774 9877 9117 8466 7901 7407 6972 6584 6238 5926 5644 5387 5153 4938

1,050,000 840,000

-

1,200,000 960,000

-

-

-

-

-

-

-

12963 11966 11111 10370 9722 9150 8642 8187 7778 7407 7071 6763 6481

- 13675 12698 11852 11111 10458 9877 9357 8889 8466 8081 7729 7407

Ratings are shown for elevations up to 2000 ft. For higher elevations the input rating should be reduced at the rate of 4% for each 1000 feet above sea level. For

Canada, in elevations between 2000 and 4500 feet, the unit must be derated to 90% of the rating listed above.

For Variable Air Movement Applications, see page 17.

air temperature limits

The maximum allowable discharge air temperature is 150°F. The maximum allowable air temperature rise per furnace for Low Air

Temperature Rise Units is 60°F. All system units are designed for a maximum allowable total static pressure of 3.0" W.C.

5-572.7

27

unit selection

selection Procedure

In order to properly select an indirect-fired heating, ventilating, cooling or make-up air unit, it is necessary to have the following basic information.

1. required air handling capacity (cfm).

The air capacity of the unit is usually determined by the ventilation air requirements, exhaust load of the building, infiltration losses, or the air turns/changes of the space.

2. outdoor and indoor design temperature.

The outdoor design temperature is determined by using the ASHRAE Guide design temperatures for the city where the equipment is to be installed. For heating and ventilating units, the desired room temperature would be used as the indoor design temperature. In the case of 100% make-up air units, the discharge air temperature should be at least equal to the temperature of the air being exhausted.

3. required heating output capacity (Btu/Hr).

The heating output capacity of the unit is determined by using the formula:

BTU/HR = CFM x Temp. Rise (°F) x 1.08

4. external static pressure to unit.

The external static pressure (E.S.P.) is determined using the ASHRAE Guide for duct losses, or may be provided by the design engineer.

5. unit configuration with options and accessories

(rainhood, filters, dampers, or evaporative cooler).

The unit configuration is determined by the location where the unit is to be installed. The critical options and accessories are those that add internal static pressure

(I.S.P.) to the unit. Once these items are determined, the pressure drop curves would be used to calculate the total pressure drop (T.S.P.)

Total Static Pressure = Internal + External Static Pressure

6. Heat exchanger material.

The heat exchanger type is determined by the application.

The standard heat exchanger material is aluminized steel. A 409 stainless steel heat exchanger and burner is recommended when the unit is installed downstream of a cooling coil or evaporative cooler, and when the combined entering/return air to the unit is below 40°F.

7. type of fuel.

Either natural or propane gas determined by the design engineer.

8. Gas control staging method.

Either single stage, two stage, mechanical modulation, or electronic modulation determined by the design engineer.

9. main power supply voltage to unit.

10. altitude at which unit is to be installed.

With this information a basic unit can be selected as shown in the following example.

selection example conditions

Select an indirect-fired, 100% make-up air unit to meet the following conditions:

1. CFM at sea level = 5,000 cfm

2. Outdoor design temp. = 10°F

Indoor design temp. = 70°F

3. Heating output capacity =

5000 cfm x (70°F -10°F) x 1.08 = 324,000 Btu/Hr

4. External Static Pressure = 0.65

5. The Gravity Vented unit with the controls on the Right

Hand Side is to be provided with the following:

2" Permanent Filters, a Rainhood with Fresh Air Damper,

and a Downturn.

6. Heat exchanger and burner = 409 Stainless Steel.

7. Gas Type = Natural

8. Gas Controls = Electronic Modulating with Duct Sensing.

9. Supply Voltage: 460V/60Hz/3Ph

10. Altitude: 1000 feet

With the information listed above, the basic model, using the

Model Nomenclature shown on page 59, can be selected as shown in the following example:

1. determine the model configuration and venting:

The Model Configuration is determined by the required sections of the unit (Blower and Downturn) and the venting style (Gravity) that are obtained from item #5. Using the

Model Nomenclature on page 59, the Model Configuration and Venting = HDG.

2. determine the furnace input rating (mBH):

Using the Heating output capacity, the Furnace Input

Rating is determined from Table 27.1. The closest model to 324,000 Btu/Hr output has an Btu/Hr Input rating of

400,000 Btu/Hr so the Furnace Input Rating = 400.

3. determine the Heat exchanger/Burner/drip Pan material:

From item #2 listed above, the Heat Exchanger and Burner required are 409 Stainless Steel. Because the Drip Pan material is not specified, the standard Aluminized Steel drip pan will be used. Thus, the Heat Exchanger/Burner/Drip

Pan Material = S.

4. determine the development sequence:

From item #8 listed above, the modulating gas controls result in the Development Sequence = M.

5. determine the access side:

From item #5 listed above, the Right Hand Gas controls result in the Access Side = R.

6. determine the air temperature rise:

From item #2 listed above, the Air Temperature Rise is

60°F (70°F - 10°F). However, using the output capacity of the HDG400 @ 5000 cfm, the resulting temperature rise is

59.3°F (320,000/(5000 x 1.08). Since the rise is less than

60°F, the Air Temperature Rise = L.

7. determine the Gas type:

From item #7 listed above, the Natural Gas results in the

Gas Type = N.

8. determine the Gas valve:

From item #8 listed above, the Electronic Modulating with

Duct Sensing results in the Gas Valve = 4.

9. determine the additional safety switches:

Since no additional safety switches were specified, the

Additional Safety Switches = 0.

28

5-572.7

unit selection

10. determine the supply voltage:

From item #9 listed above, the 460V/60Hz/3Ph results in the Supply Voltage = F.

11. determine the transformer:

With the selected Unit Type = HDG, the Transformer = 2.

12. determine the Blower size and Bearing type:

Using Table 27.1, the Model Size 400 has three available blowers for which the performance tables are shown on page 32. Since all of the blower performance tables can provide the required 5000 cfm, the total static pressure for each blower performance curve must be determined.

A) The Pressure Drop of an option or accessory is determined by entering the right of the table at the desired cfm and reading across the table until the cfm intersects the desired item. For this example, in table

30.1 the 2” Permanent Filter is used. At the point of intersection, read across the table to the right and read the pressure drop, in inches of water column for the filters. For this example, the pressure drop is 0.06” W.C.

This method is used to determine the pressure drop for the other options and accessories. As a result:

For the Model Size 400 with Digit 16 = E,F,G, or H:

2” Permanent Filters:

Rainhood:

Downturn:

0.06” W.C.

0.11” W.C.

0.07” W.C.

Internal Static Pressure Drops 0.24” W.C.

The Total Static Pressure for the system is determined by Internal Static + External Static = Total Static Pressure

For this example 0.24” + 0.65” = 0.89” W.C. T.S.P.

From page 30, for the Model Size 400 with Digit 16 = I, J, or k:

2” Permanent Filters:

Rainhood:

0.04” W.C.

0.11” W.C.

Downturn: 0.07” W.C.

Internal Static Pressure Drops 0.22” W.C.

The Total Static Pressure for the system is determined by Internal Static + External Static = Total Static Pressure

For this example 0.22” + 0.65” = 0.87” W.C. T.S.P.

B) Using the total static pressure (T.S.P.) calculated in step

12a, use blower performance tables for the Model Size

400 (Tables 32.1).

Using Table 32.1, enter the table at the required 5000 cfm for E.F. blowers, and follow the cfm line to the right until it intersects with the T.S.P. line of 0.75” W.C. which is shown at the top of the table. At the point of intersection of these two columns, read the required horsepower and blower rpm. Repeat this process for

1.00” T.S.P and iterate to determine the BHP and rpm for 0.89” W.C. For this example the horsepower is 5 and the blower rpm is 1280.

IMPORTANT

When selecting the required motor horsepower, the horsepower must always be read off the curve to the right of the data point determined from the intersection point of the cfm and T.S.P. lines.

Following this procedure for G,H blowers (Using 5000 cfm and 0.89” W.C. T.S.P), the horsepower is 5 hp and

920 rpm. Following this procedure for I,J,k blowers

(Using 5000 cfm and 0.87” W.C. T.S.P), the horsepower is 3 hp and 700 rpm. Although I,J,H blowers results in a

3 hp motor, this blower requires the use of the extended cabinet length. As a result, for purposes of this selection example G,H blowers will be used.

Since the Bearing Type was not specified, the standard spider bearings will be used. Thus, using Table 32.1 with spider bearings, the Blower Size and Bearing Type = G.

13. determine the motor Horsepower:

The motor horsepower determined in step 12 was a 3 Hp.

Since the supply voltage is 460V/60Hz/3Ph, a motor starter will need to be provided either with the unit or by others.

For purposes of this selection, a motor starter by others will be used so the Motor Horsepower = G.

14. determine the motor type:

The motor type was not specified so for purposes of this selection the standard open drip proof motor will be used so the Motor Type = 1.

15. determine the sheave arrangement:

To establish the Sheave Arrangement, the motor frame size must be determined. The Motor Data tables on pages 38 to

42 contain the motor frame size.

A) Using the Supply Voltage (460V/60Hz/3Ph), enter the correct Motor Data table (Table 41.1). Using Model

Nomenclature Digits 17 and 18 (G1) determined in steps

13 and 14, find the motor frame size (182T).

B) Using the Motor Frame Size enter the Sheave Selection table for the selected blower determined by step 13

(Table 35.2). Using the rpm calculated in step 12 (920 rpm), select the sheave range that contains the required rpm. Find the intersection with the Motor Frame Size to determine the Sheave Selection. For this example with a

182T frame with 920 rpm, from Table 35.2, the Sheave

Arrangement = I.

16. determine the air control:

The Air Control option is selected based on the required damper configuration. The available damper selections are detailed on page 21. For this selection, a 100% fresh air unit without return air was required so the Air Control = DA.

17. determine the evaporative cooler:

An evaporative cooler was not specified so for purposes of this selection the Evaporative Cooler = 0.

18. determine the cooling coil:

A cooling coil cabinet was not specified so for purposes of this selection the Cooling Coil = 0.

Based on the previous steps, the model number for the base unit is the following:

HDG400SMRLN40F2GG1IDA00

Once the basic model has been determined, the additional options and accessories outlined on page 18 to 25 can be added to the unit.

5-572.7

29

oPtion & accessory Pressure droP data

table 30.1 - option & accessory Pressure drop tables (in ''W.c.)

all units evap cooler, 6" media

Weatherproof unit only evap cooler, 12" media

unit size

75

100/125

150/175

200/225

250/300

500/600

350/400

700/800

840/960 digit 16 a,B,c,d c,d,e,f c,d,e,f c,d,e,f,G,H e,f,G,H i,J,K,l e,f,G,H i,J,K,l

0.11

0.15

0.20

0.25

0.33

0.38

0.02

0.02

0.13

0.19

0.26

0.32

0.01

0.03

0.05

0.08

0.03

0.04

0.05

0.11

0.14

0.16

0.18

0.02

0.03

0.04

0.06

0.08

0.10

0.23

0.02

0.02

0.04

0.05

0.06

0.08

0.10

0.04

0.05

0.07

0.09

0.12

0.14

0.17

0.20

0.24

0.06

0.07

0.08

0.10

0.11

0.01

0.02

0.03

0.02

0.03

0.04

0.06

0.08

0.11

0.13

0.16

0.19

0.21

0.04

0.06

0.08

0.11

0.13

0.16

0.20

0.21

0.01

0.01

0.01

0.02

0.02

0.03

0.04

0.04

0.05

0.07

0.09

0.02

0.02

0.15

0.19

0.24

0.30

0.38

0.43

0.04

0.05

0.18

0.25

0.34

0.41

0.03

0.05

0.08

0.11

0.06

0.07

0.09

0.16

0.19

0.22

0.25

0.05

0.05

0.07

0.10

0.12

0.15

0.30

0.03

0.04

0.05

0.07

0.09

0.11

0.13

0.05

0.07

0.10

0.12

0.15

0.18

0.22

0.26

0.30

0.10

0.12

0.14

0.16

0.18

0.02

0.02

0.04

0.03

0.04

0.06

0.09

0.11

0.14

0.18

0.21

0.25

0.27

0.05

0.07

0.10

0.13

0.16

0.20

0.25

0.26

0.02

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.10

0.11

0.15

0.02

0.03

0.16

0.21

0.27

0.33

0.42

0.47

0.04

0.05

0.22

0.31

0.42

0.51

0.03

0.05

0.09

0.12

0.06

0.08

0.10

0.18

0.21

0.25

0.28

0.05

0.06

0.09

0.11

0.15

0.18

0.38

0.03

0.04

0.06

0.08

0.10

0.12

0.15

0.06

0.08

0.11

0.13

0.16

0.19

0.23

0.27

0.31

0.12

0.14

0.17

0.19

0.22

0.02

0.03

0.04

0.04

0.05

0.08

0.11

0.15

0.18

0.23

0.27

0.32

0.34

0.07

0.10

0.14

0.19

0.24

0.30

0.37

0.39

0.03

0.03

0.04

0.05

0.06

0.07

0.09

0.10

0.11

0.13

0.16

0.02

0.04

0.10

0.14

0.18

0.23

0.30

0.03

0.04

0.15

0.22

0.30

0.01

0.03

0.04

0.07

0.05

0.06

0.08

0.21

0.25

0.30

0.02

0.03

0.04

0.06

0.09

0.11

0.02

0.03

0.05

0.08

0.10

0.13

0.17

0.06

0.09

0.12

0.16

0.20

0.25

0.31

0.10

0.12

0.15

0.17

0.20

0.02

0.02

0.04

0.01

0.03

0.04

0.07

0.10

0.14

0.18

0.23

0.28

0.30

0.04

0.08

0.12

0.17

0.23

0.30

0.01

0.01

0.02

0.03

0.04

0.06

0.08

0.10

0.12

0.16

0.23

0.01

0.02

0.26

0.34

0.41

0.50

0.64

0.10

0.13

0.35

0.48

0.63

0.05

0.10

0.15

0.20

0.16

0.19

0.23

0.47

0.55

0.63

0.10

0.11

0.15

0.19

0.24

0.29

0.08

0.12

0.17

0.22

0.27

0.33

0.40

0.19

0.25

0.31

0.38

0.46

0.54

0.64

0.27

0.31

0.36

0.40

0.45

0.08

0.09

0.14

0.07

0.10

0.15

0.20

0.27

0.34

0.41

0.50

0.59

0.63

0.14

0.21

0.30

0.40

0.51

0.63

0.05

0.05

0.08

0.11

0.14

0.17

0.21

0.25

0.30

0.37

0.51

0.06

0.08

cfm

4500 0.10

5500 0.14

6500 0.19

7250 0.23

1925 0.02

3000 0.03

4000 0.05

5000 0.08

6000 0.11

7000 0.15

8000 0.19

9000 0.24

10400 0.32

11111 0.36

2593 0.02

3000 0.02

3500 0.03

4000 0.03

4500 0.04

5556 0.19

1481 0.01

2000 0.01

2500 0.02

3000 0.03

3500 0.03

4000 0.05

4500 0.06

5000 0.07

5500 0.09

6000 0.11

6500 0.13

1852 0.03

2000 0.03

2500 0.04

3000 0.05

3500 0.07

4000 0.08

556 0.01

600 0.01

800 0.02

1000 0.02

1200 0.03

1400 0.03

1600 0.04

1800 0.04

2000 0.05

2300 0.06

2778 0.08

741 0.01

1000 0.02

1500 0.03

2000 0.05

2500 0.07

3000 0.09

3500 0.11

4000 0.14

4500 0.17

4630 0.17

1111 0.01

1500 0.02

2000 0.03

2500 0.05

3000 0.06

3500 0.08

4000 0.11

4500 0.13

5000 0.16

5200 0.17

5000 0.05

5500 0.06

6000 0.06

6500 0.07

7000 0.08

2593 0.02

3000 0.02

4000 0.03

5000 0.04

6000 0.06

7000 0.07

8000 0.09

9000 0.11

10000 0.13

11050 0.15

12000 0.18

13000 0.20

0.46

0.61

0.77

0.95

1.23

0.16

0.20

0.64

0.91

1.23

0.08

0.15

0.23

0.34

0.25

0.32

0.39

0.89

1.05

1.23

0.15

0.17

0.24

0.32

0.41

0.52

0.12

0.19

0.27

0.36

0.47

0.60

0.73

0.31

0.42

0.55

0.70

0.86

1.04

1.24

0.47

0.55

0.64

0.74

0.85

0.11

0.14

0.22

0.09

0.15

0.24

0.34

0.46

0.61

0.77

0.95

1.15

1.23

0.23

0.36

0.53

0.73

0.97

1.23

0.07

0.07

0.12

0.17

0.22

0.29

0.36

0.44

0.53

0.68

0.96

0.08

0.12

0.28

0.38

0.49

0.62

0.83

0.95

0.07

0.10

0.42

0.62

0.86

1.07

0.03

0.07

0.13

0.20

0.13

0.18

0.22

0.62

0.75

0.89

1.04

0.07

0.09

0.13

0.19

0.26

0.33

0.98

0.06

0.10

0.16

0.23

0.31

0.40

0.51

0.17

0.24

0.33

0.43

0.54

0.66

0.81

0.95

1.11

0.28

0.33

0.40

0.47

0.54

0.05

0.06

0.11

0.04

0.07

0.13

0.20

0.29

0.39

0.51

0.65

0.80

0.86

0.11

0.20

0.31

0.45

0.61

0.80

1.01

1.07

0.03

0.03

0.05

0.08

0.11

0.15

0.19

0.23

0.29

0.37

0.54

0.03

0.05

0.18

0.25

0.33

0.42

0.57

0.66

0.02

0.03

0.10

0.15

0.21

0.27

0.02

0.04

0.08

0.12

0.04

0.05

0.06

0.18

0.21

0.26

0.30

0.02

0.02

0.03

0.04

0.06

0.08

0.26

0.02

0.03

0.04

0.06

0.09

0.11

0.14

0.07

0.10

0.14

0.19

0.24

0.30

0.36

0.43

0.51

0.07

0.09

0.10

0.12

0.14

0.02

0.03

0.05

0.02

0.02

0.04

0.05

0.07

0.10

0.13

0.17

0.21

0.23

0.02

0.04

0.07

0.11

0.15

0.19

0.25

0.26

0.00

0.00

0.01

0.01

0.02

0.03

0.04

0.05

0.06

0.08

0.12

0.00

0.01

0.28

0.35

0.42

0.51

0.64

0.71

0.03

0.04

0.19

0.25

0.31

0.37

0.07

0.12

0.16

0.22

0.05

0.07

0.09

0.27

0.32

0.38

0.45

0.07

0.08

0.09

0.12

0.14

0.16

0.33

0.03

0.05

0.08

0.10

0.14

0.18

0.22

0.11

0.17

0.23

0.30

0.38

0.48

0.58

0.69

0.81

0.11

0.14

0.17

0.20

0.23

0.03

0.04

0.07

0.02

0.03

0.05

0.08

0.10

0.14

0.18

0.22

0.27

0.29

0.07

0.10

0.13

0.16

0.19

0.22

0.25

0.26

0.01

0.01

0.02

0.03

0.03

0.04

0.06

0.07

0.08

0.11

0.15

0.03

0.05

0.16

0.21

0.28

0.35

0.47

0.53

0.01

0.01

0.09

0.13

0.18

0.23

0.02

0.04

0.07

0.11

0.01

0.01

0.02

0.10

0.12

0.14

0.16

0.02

0.02

0.03

0.04

0.06

0.07

0.13

0.01

0.01

0.02

0.04

0.05

0.06

0.08

0.02

0.04

0.05

0.08

0.10

0.14

0.17

0.21

0.26

0.02

0.03

0.04

0.04

0.05

0.01

0.01

0.01

0.01

0.01

0.02

0.02

0.04

0.05

0.06

0.08

0.10

0.11

0.02

0.03

0.04

0.05

0.07

0.09

0.11

0.11

0.00

0.01

0.01

0.01

0.01

0.02

0.02

0.03

0.03

0.04

0.06

0.01

0.01

0.02

0.02

0.03

0.05

0.07

0.09

0.11

0.14

0.17

0.22

0.32

0.02

0.03

0.07

0.13

0.20

0.29

0.39

0.51

0.68

0.03

0.05

0.09

0.13

0.19

0.26

0.34

0.42

0.52

0.57

0.04

0.07

0.11

0.15

0.21

0.27

0.34

0.42

0.50

0.60

0.02

0.05

0.08

0.13

0.18

0.25

0.32

0.40

0.54

0.05

0.06

0.09

0.13

0.17

0.22

0.28

0.41

0.57

0.05

0.06

0.09

0.11

0.14

0.18

0.21

0.26

0.30

0.35

0.03

0.04

0.07

0.11

0.16

0.21

0.27

0.12

0.18

0.24

0.32

0.34

0.42

0.40

0.50

0.51 0.61

0.60

0.70

11050 Max CFM for Evap

0.20

0.24

0.29

0.34

0.39

0.03

0.04

0.08

0.20

0.27

0.35

0.45

0.60

0.05

0.07

0.29

0.43

0.60

0.02

0.05

0.09

0.14

0.10

0.13

0.16

0.42

0.50

0.60

0.05

0.06

0.09

0.13

0.17

0.23

0.04

0.07

0.10

0.15

0.20

0.27

0.34

0.03

0.05

0.09

0.14

0.20

0.27

0.35

0.45

0.55

0.60

0.08

0.15

0.23

0.34

0.46

0.60

0.02

0.02

0.04

0.06

0.08

0.11

0.15

0.19

0.23

0.31

0.45

0.02

0.04

Accessory / Option static pressure losses are approximate values only. Please consult the Accuspec selection software for static pressure losses at other than listed CFM.

30

5-572.7

BloWer Performance data

21°F/25°F

100°F/113°F

89°F/100°F

85°F/95°F

74°F/83°F

66°F/74°F

59°F/67°F

54°F/61°F

49°F/56°F

85°F/95°F

74°F/83°F

59°F/67°F

49°F/56°F

42°F/48°F

37°F/42°F

86°F/100°F

79°F/93°F

62°F/72°F

51°F/59°F

43°F/50°F

37°F/43°F

86°F/100°F

79°F/93°F

62°F/72°F

51°F/59°F

43°F/50°F

37°F/43°F

33°F/38°F

29°F/34°F

26°F/31°F

24°F/28°F

33°F/37°F

30°F/33°F

85°F/95°F

74°F/83°F

59°F/67°F

49°F/56°F

42°F/48°F

37°F/42°F

33°F/37°F

30°F/33°F

27°F/30°F

25°F/28°F

80°F/100°F

62°F/77°F

53°F/66°F

41°F/51°F

34°F/42°F

28°F/36°F

25°F/31°F

41°F/51°F

34°F/42°F

28°F/36°F

25°F/31°F

22°F/27°F

20°F/25°F

- / 23°F

- / 20°F

100°F/117°F

69°F / -

56°F / -

46°F / -

40°F / -

35°F / -

31°F / -

69°F / -

56°F / -

46°F / -

40°F / -

35°F / -

31°F / -

28°F / -

24°F / -

20°F / -

100°F / -

1296 0.27 793

1400 0.32 832

1800 0.59 994

2200 1.00 1166

2600 1.58 1344

3000 2.35 1526

1296 - -

1400 0.17 474

1800 0.28 526

2200 0.44 588

2600 0.67 657

3000 0.96 729

3400 1.35 804

3800 1.82 880

4200 2.40 959

4700 3.30 1058

5200 4.40 1158

1481 0.36 871

1667 0.48 943

1750 0.54 975

2000 0.76 1077

2250 1.04 1181

2500 1.38 1288

2750 1.79 1396

3000 2.28 1506

1750 0.29 594

2000 0.40 642

2500 0.68 746

3000 1.09 857

3500 1.66 972

4000 2.40 1091

4500 3.34 1211

5000 4.52 1332

1750 0.20 425

2000 0.26 449

2500 0.42 507

3000 0.65 571

3500 0.97 639

4000 1.38 710

4500 1.90 783

5000 2.54 858

5500 3.32 933

6000 4.25 1009

800 0.18 801

1000 0.29 917

1200 0.45 1042

1400 0.66 1173

1600 0.93 1308

1800 1.28 1445

800 -

1000 -

-

-

1200 0.19 705

1400 0.27 770

1600 0.37 839

1800 0.49 912

2000 0.65 987

2300 0.94 1104

2778 1.59 1296

741 - -

926 0.13 670

1200 0.22 758

1400 0.30 828

1800 0.55 982

2200 0.93 1145

2600 1.45 1315

3000 2.16 1489

1800 0.28 497

2200 0.43 553

2600 0.63 614

3000 0.91 680

3400 1.26 748

3704 1.58 802

4100 2.09 873

4630 2.93 969

1111 0.19 727

table 31.1 - unit Performance tables

① ②

air digit temp. unit size 16 rise cfm

75 a,B

100°F / -

0.25

556 0.09 679 0.15

0.50

BHP rPm BHP rPm BHP

871 0.22

0.75 1.00 total static Pressure, ''W.c.

1.25 rPm BHP rPm BHP rPm

1031 0.29 1170 0.37 1296

.

1.50 2.00 2.50 3.00

BHP rPm BHP rPm BHP rPm BHP rPm

0.45 1411 0.63 1617 0.81 1800 1.01 1968

79°F / 700 0.14 747 0.21 924 0.29 1074 0.37 1206 0.46 1327 0.55 1438 0.75 1638 0.95 1818 1.17 1982

75

100/125 c,d

start 125

100/125

end 100 c,d e,f

150/175 c,d

start 175

150/175 e,f

200/225 c,d

start 225

200/225 e,f

200/225 G,H

1.67

2.19

2.88

3.75

4.82

-

-

-

-

0.99

1.17

1.26

1.57

1.94

2.37

2.88

-

1.14

1.28

1.38

1.69

2.10

2.60

3.23

3.98

4.87

-

-

1.27

1.59

1.98

2.47

3.04

3.73

4.76

0.83

0.91

1.30

1.84

2.54

-

-

-

1.33

1.63

2.01

2.47

2.88

3.49

4.48

0.70

0.56

0.74

0.89

1.27

1.79

2.46

-

-

0.65

0.77

0.92

1.09

1.30

1.67

2.44

0.47

-

-

-

-

0.64

0.83

1.08

1.38

1108

1176

1255

1345

1441

-

-

-

-

1366

1411

1433

1502

1577

1658

1743

-

1042

1058

851

877

914

958

1008

1064

1123

-

952

972

1004

1044

1092

1146

1204

1281

1293

1313

1410

1529

1664

-

-

-

942

965

997

1038

1072

1122

1194

1262

1236

1282

1323

1422

1537

1666

-

-

1250

1273

1304

1343

1388

1465

1606

1212

-

-

-

-

1354

1419

1499

1589

1.45

1.95

2.61

3.46

4.51

-

-

-

-

0.85

1.03

1.11

1.40

1.75

2.17

2.66

-

0.94

1.08

1.16

1.45

1.84

2.34

2.94

3.67

4.54

-

0.85

1.09

1.39

1.76

2.23

2.79

3.45

4.46

0.71

0.78

1.15

1.66

2.34

-

-

-

1.12

1.41

1.77

2.21

2.60

3.20

4.16

0.59

0.47

0.62

0.76

1.12

1.61

2.25

-

-

0.54

0.66

0.80

0.96

1.16

1.52

2.26

0.38

-

-

-

-

0.54

0.72

0.94

1.23

1025

1101

1188

1284

1385

-

-

754

-

1259

1309

1332

1407

1488

1573

1663

1756

944

966

774

807

850

899

955

1014

1077

-

859

887

925

972

1025

1083

1145

1227

1184

1208

1316

1444

1589

1743

-

-

855

885

1731

970

1008

1062

1140

1148

1121

1173

1218

1325

1449

1585

1731

837

1131

1161

1199

1244

1295

1380

1532

1093

1237

1310

1397

1495

1601

-

-

1112

1.23

1.72

2.36

3.18

4.21

-

-

0.74

-

0.73

0.88

0.96

1.24

1.57

1.97

2.44

2.98

0.75

0.88

0.94

1.23

1.60

2.08

2.66

3.37

4.22

-

0.70

0.91

1.19

1.55

2.00

2.53

3.18

4.16

0.59

0.66

1.00

1.49

2.14

3.00

-

-

0.93

1.20

1.54

1.96

2.34

2.91

3.84

0.48

0.38

0.52

0.64

0.98

1.44

2.05

2.84

0.72

0.44

0.55

0.68

0.84

1.03

1.37

2.09

0.30

0.44

0.60

0.82

1.08

1.42

-

-

0.36

938

1024

1119

1221

1329

-

653

662

-

1144

1198

1224

1306

1393

1484

1579

1677

838

866

692

732

782

839

899

963

1030

1099

760

796

842

895

955

1018

1085

1172

1066

1093

1216

1356

1510

1673

734

737

762

800

847

899

942

1001

1085

1023

993

1052

1103

1220

1354

1500

1654

735

1003

1041

1087

1139

1197

1292

1456

962

1109

1192

1289

1395

1509

-

960

975

845

942

1047

1157

1270

1387

546

562

1212

1016

1078

1106

1197

1291

1389

1490

1593

723

759

603

654

713

776

842

911

982

1054

650

697

753

815

881

951

1023

1116

937

970

1109

1264

1429

1600

609

615

662

710

766

825

873

938

1028

884

846

916

975

1108

1254

1410

1573

622

862

912

968

1030

1095

1200

1377

808

966

1062

1171

1288

1412

1539

795

822

1.04

1.50

2.12

2.91

3.91

-

0.48

0.56

-

0.60

0.75

0.82

1.08

1.39

1.77

2.22

2.75

0.58

0.71

0.75

1.02

1.38

1.83

2.40

3.08

3.91

4.89

0.55

0.75

1.01

1.35

1.77

2.29

2.92

3.87

0.47

0.54

0.86

1.32

1.95

2.78

0.37

0.40

0.75

1.00

1.32

1.72

2.08

2.63

3.53

0.38

0.29

0.41

0.53

0.83

1.27

1.85

2.61

0.56

0.35

0.45

0.57

0.72

0.90

1.22

1.92

0.23

0.35

0.50

0.69

0.94

1.25

-

0.21

0.28

0.85

1.29

1.88

2.65

3.62

4.82

0.33

0.40

4.71

0.48

0.61

0.68

0.92

1.21

1.57

2.00

2.51

0.43

0.54

0.58

0.83

1.17

1.60

2.14

2.81

3.61

4.57

0.41

0.59

0.83

1.15

1.55

2.05

2.66

3.58

0.37

0.42

0.72

1.16

1.76

2.57

0.25

0.28

0.58

0.81

1.11

1.48

1.83

2.35

3.23

0.28

0.21

0.31

0.41

0.69

1.10

1.65

2.39

0.41

0.27

36.00

0.47

0.60

0.77

1.08

1.75

0.15

0.26

0.39

0.57

0.80

1.09

1.46

0.15

0.20

1188

1248

1320

1404

1495

-

-

-

-

1465

1507

1527

1592

1663

1739

1820

-

1134

1146

925

944

975

1014

1061

1112

1168

-

-

1052

1078

1114

1157

1206

1260

1333

1395

1412

1500

1610

1737

-

-

-

1025

1042

1068

1104

1135

1180

1247

1369

1342

1384

1422

1513

1621

1744

-

-

1361

1377

1403

1437

1477

1547

1679

1320

-

-

-

-

1462

1522

1595

1680

-

-

-

-

2.15

2.71

3.43

4.35

-

1.26

1.47

1.57

1.91

2.31

2.78

-

-

1.58

1.74

-

2.21

2.64

3.18

3.84

4.62

-

-

-

1.67

2.02

2.45

2.96

3.58

4.30

-

1.09

1.18

1.62

2.20

2.95

-

-

-

-

-

2.51

3.01

3.45

4.10

-

0.94

0.77

0.97

1.15

1.58

2.15

1.35

-

-

-

1.00

1.17

1.36

1.59

1.98

2.80

0.60

-

-

-

-

0.84

1.07

1.35

-

-

-

-

-

1337

1384

1455

1518

-

1646

1682

1700

1758

1822

1892

-

-

1303

1309

-

1071

1093

1123

1161

1206

-

-

-

1201

1218

1245

1280

1322

1369

-

1582

1596

1667

1762

1877

-

-

-

-

-

1202

1229

1254

1291

-

1563

1532

1568

1600

1681

1778

1638

-

-

-

1572

1589

1613

1645

1703

1818

1514

-

-

-

-

1658

1709

1773

-

-

-

-

-

2.67

3.27

4.03

4.98

-

1.54

1.77

1.88

2.26

2.69

-

-

-

2.07

2.23

-

-

3.23

3.80

4.48

-

-

-

-

-

2.47

2.94

3.49

4.14

4.90

-

-

-

-

-

1.37

1.47

1.95

2.57

-

-

3.04

3.58

4.04

4.74

-

1.21

0.99

1.22

1.42

1.90

2.52

-

-

-

-

-

1.44

1.65

1.89

2.31

-

0.86

-

-

-

-

1.06

1.32

-

-

-

-

-

-

1475

1511

1563

1628

-

1808

1842

1857

1910

1969

-

-

-

1458

1458

-

-

1202

1226

1258

-

-

-

-

-

1348

1368

1396

1431

1472

-

-

-

-

-

1752

1763

1823

1906

-

-

1328

1347

1367

1398

-

1738

1702

1733

1762

1834

1923

-

-

-

-

-

1760

1777

1802

1850

-

1686

-

-

-

-

1832

1879

-

-

-

-

-

-

3.24

3.86

-

-

-

1.84

2.09

2.21

2.62

-

-

-

-

2.60

2.78

-

-

-

-

-

-

3.86

4.46

-

-

2.96

3.45

4.03

4.72

-

-

-

-

-

-

1.66

1.78

2.29

2.96

-

-

3.60

4.17

4.67

-

-

1.48

1.22

1.48

1.70

2.23

2.90

-

-

-

-

-

1.72

1.94

2.20

2.65

-

1.07

-

-

-

-

1.30

-

-

-

-

-

-

-

1604

1632

-

-

-

1958

1988

2003

2051

-

-

-

-

1600

1595

-

-

-

-

-

-

1307

1324

-

-

1469

1483

1505

1535

-

-

-

-

-

-

1909

1917

1967

2041

-

-

1446

1459

1474

-

-

1899

1856

1884

1910

1976

2057

-

-

-

-

-

1920

1931

1950

1990

-

1840

-

-

-

-

1996

-

-

-

Total static pressure should include external static pressure and accessory / option static pressure from Table 30.1. Unit internal resistance has been included in the unit performance tables.

Brake Horsepower and RPM values are approximate values only. Please consult the AccuSpec selection software for values at other than listed CFM / static pressures.

5-572.7

BloWer Performance data

table 32.1 - unit Performance tables

① ②

digit unit size 16

250/300 e,f

air temp. rise

100°F / 120°F

start 300

83°F / 100°F

74°F / 89°F

0.25 0.50 0.75 cfm BHP rPm BHP rPm BHP rPm

1852

m

0.26

2222 0.39

532

582

0.39

0.54

665

703

0.54

0.70

782

810

250/300 G,H start 300

250/300

74°F / 89°F

62°F / 74°F

53°F / 63°F

46°F / 56°F

41°F / 49°F

37°F / 44°F

34°F / 40°F

31°F / 37°F

28°F / 34°F

i, J, K

46°F / 56°F

37°F / 44°F

end 250

350/400 e,f start 400

350/400 start 400

350/400 start 400

G,H i,J,K

62°F / 74°F

53°F / 63°F

46°F / 56°F

41°F / 49°F

37°F / 44°F

34°F / 40°F

100°F / 120°F

83°F / 100°F

31°F / 37°F

26°F / 32°F

23°F / 28°F

20°F / 24°F

- / 22°F

- / 20°F

100°F / -

96°F / -

87°F / 100°F

74°F / 85°F

65°F / 74°F

58°F / 66°F

52°F / 59°F

47°F / 54°F

100°F / -

87°F / 100°F

74°F / 85°F

65°F / 74°F

58°F / 66°F

52°F / 59°F

47°F / 54°F

43°F / 49°F

40°F / 46°F

100°F / -

87°F / 100°F

65°F / 74°F

52°F / 59°F

43°F / 49°F

37°F / 42°F

32°F / 37°F

29°F / 33°F

26°F / 30°F

24°F / 27°F

23°F / 26°F

2500 0.51

3000 0.80

3500 1.19

4000 1.69

625

706

793

882

4500 2.34 974

5000 3.14 1067

5500 4.11 1161

1852 - -

2222 0.28 424

2500 0.35

3000 0.53

3500 0.76

4000 1.07

4500 1.45

5000 1.92

5500 2.50

6000 3.16

447

492

542

594

649

706

767

822

0.52

0.72

0.98

1.31

1.72

2.22

2.81

3.52

0.68

0.99

1.41

1.94

736

803

878

958

2.62 1043

3.44 1130

4.44 1219

0.34 519

0.43 537

6500 3.96

4000 -

5000 -

6000 1.94

881

-

-

559

4.34

0.97

1.51

2.29

934

507

560

620

7000 2.93

8000 4.24

9259 6.40

10000 7.97

632

707

804

862

3.33

4.69

6.91

8.52

686

755

846

901

11111 10.79 949 11.40 985

2593 0.61

2700 0.67

2963 0.85

3500 1.30

668

686

730

826

4000 1.86 918

4500 2.57 1012

5000 3.44 1109

5500 4.50 1206

2593 0.43 479

2963 0.57

3500 0.85

4000 1.19

4500 1.61

5000 2.22

5500 2.77

6000 3.53

6500 4.42

2593

2963

-

-

4000 -

5000 1.37

6000 2.20

7000 3.34

8000 4.84

9000 6.75

10000 9.13

-

-

-

515

588

665

744

824

906

516

574

631

690

767

813

876

939

-

-

1.07

1.69

2.58

3.77

5.33

7.29

9.72

0.79

1.09

1.45

1.91

2.46

3.12

3.91

4.82

0.80

0.87

1.06

1.54

781

796

834

917

2.13 1000

2.87 1087

3.78 1177

4.87 1269

0.62 585

-

-

533

590

654

723

796

871

948

614

662

710

762

817

874

933

992

553

588

878

673

721

771

824

878

0.77

0.89

1.37

2.04

2.97

4.22

5.83

7.85

10.33

1.02

1.35

1.74

2.22

2.80

3.49

4.30

-

1.01

1.08

1.28

1.80

2.42

3.18

4.12

-

0.84

0.71

0.93

1.21

1.57

2.00

2.52

3.14

3.87

0.85

1.19

1.64

2.20

2.90

3.76

4.78

0.49

0.61

4.72

1.25

1.84

2.66

984

583

626

679

3.75

5.16

7.45

9.09

738

802

887

939

12.03 1020

702

742

784

830

880

933

987

-

561

571

609

658

715

778

845

917

990

882

895

928

1002

1078

1158

1242

-

679

646

674

707

746

789

834

882

933

836

893

959

1032

1109

1191

1275

623

634

11000 12.01 988 12.66 1027 13.32 1065

11500 13.66 12.09 14.34 1067 - -

total static Pressure, ''W.c.

1.00 1.25

.

1.50

BHP rPm BHP rPm BHP rPm BHP

0.69 887 0.85 985 1.03 1074 1.39

0.87 909 1.05 1000 1.24 1085 1.64

2.00 2.50 3.00

rPm BHP rPm BHP rPm

1239 1.79 1387 2.21 1523

1242 2.06 1385 2.52 1517

1.22

1.30

1.52

2.07

2.71

3.51

4.47

-

1.09

-

1.56

2.19

3.06

4.19

5.64

7.99

9.67

12.66

0.90

1.15

1.45

1.83

2.29

2.84

3.49

4.24

1.04

1.40

1.87

2.46

3.19

4.08

-

0.66

0.79

1.04

1.18

1.69

2.41

3.39

4.68

6.34

8.41

10.95

1.28

1.63

2.04

2.55

3.15

3.87

4.70

-

14.00

-

975

986

1015

1081

1151

1226

1305

-

764

-

654

688

734

-

1.89

2.56

3.46

788

847

927

977

4.64

6.14

8.55

10.27

1054 13.31

1.45

1.53

1.76

2.34

3.01

3.84

4.84

-

1.35

730

752

780

814

852

894

938

984

930

978

1036

1102

1174

1250

-

713

721

1.11

1.38

1.71

2.11

2.59

3.16

3.83

4.61

1.23

1.62

2.12

2.73

3.49

4.40

-

0.85

0.99

782

815

853

895

940

989

1040

-

639

646

679

721

1.34

1.49

2.03

2.79

772

830

893

960

3.82

5.16

6.87

8.99

1030 11.58

1.56

1.93

2.36

2.89

3.52

4.25

-

-

1103 14.68

- -

806

824

848

878

912

950

991

1035

1016

1058

1109

1170

1236

1308

-

795

800

1.33

1.62

1.97

2.39

2.90

3.50

4.19

5.00

1.43

1.84

2.36

3.01

3.79

4.73

-

1.05

1.20

1061

1071

1097

1157

1221

1291

1366

-

841

-

719

748

787

-

2.24

2.95

3.89

-

781

804

838

-

-

3.77

4.79

836

891

5.11

6.65

882

933

6.09

7.72

966 9.12 1004 10.30

1014 10.87 1050 12.12

1087 13.97 1121 -

1.69

1.78

2.02

2.62

3.32

4.18

-

-

1.64

1142

1151

1174

1228

1288

1353

-

-

1142

2.19

2.29

2.56

3.22

3.97

4.88

-

-

2.26

877

892

912

939

969

1004

1042

1084

1099

1133

1179

1234

1296

1364

-

870

872

1.81

2.13

2.52

2.99

3.54

4.18

4.93

-

1.85

2.31

2.88

3.58

4.41

-

-

1.47

1.65

856

885

918

956

998

1042

-

-

1.86

2.25

2.70

3.25

3.90

4.66

-

-

926

951

980

1014

1053

1095

-

-

709

715

742

779

1.66

1.81

2.40

3.19

774

779

802

835

2.36

2.54

3.18

4.05

826

879

938

1002

4.26

5.65

7.41

9.58

877

927

982

1043

5.20

6.68

8.53

10.80

1069 12.22 1107 13.54

1139

-

-

-

-

-

2.50

2.93

3.41

4.00

4.70

-

-

-

-

-

1290

1297

1316

1362

1414

1472

-

-

1046

-

-

908

935

971

1015

1079

1120

-

1006

1016

1031

1052

1077

1107

1140

-

1250

1275

1312

1358

1412

-

-

1005

1005

891

894

910

937

973

1016

1066

1121

1180

1053

1072

1096

1124

1157

-

-

-

-

-

2.73

2.84

3.13

3.84

4.65

-

-

-

2.94

-

-

4.67

5.75

-

-

1005

1025

7.13

8.83

1055

1093

11.52 1150

13.41 1187

- -

1425

1431

1446

1486

1531

-

-

-

1165

2.32

2.68

3.11

3.62

4.22

4.90

-

-

2.30

2.81

3.42

4.17

-

-

-

1.94

2.14

1123

1129

1140

1156

1177

1202

-

-

1389

1406

1435

1474

-

-

-

1126

1123

-

-

-

-

3.20

3.66

4.19

4.81

3.14

3.34

4.04

4.98

995

997

1009

1030

6.21

7.77

1061

1099

9.70 1144

12.07 1194

14.90 1249

-

-

-

-

-

-

1170

1183

1202

1226

-

-

3.30

3.42

3.74

4.50

-

-

-

-

3.68

-

-

-

6.77

-

-

-

1110

8.22 1134

10.00 1167

12.79 1218

14.74 1252

- -

1550

1555

1568

1602

-

-

-

-

1275

2.87

3.27

3.74

4.28

4.92

-

-

-

2.78

3.33

3.99

4.78

-

-

-

2.44

2.67

1230

1232

1240

1253

1270

-

-

-

1517

1529

1552

1584

-

-

-

1237

1231

-

-

-

-

3.96

4.45

-

-

4.00

4.20

4.96

5.96

1090

1091

1099

1117

7.26

8.90

1144

1178

10.92 1219

13.37 1265

- -

-

-

-

-

-

-

1277

1287

-

-

-

-

Total static pressure should include external static pressure and accessory / option static pressure from Table 30.1. Unit internal resistance has been included in the unit performance tables.

Brake Horsepower and RPM values are approximate values only. Please consult the AccuSpec selection software for values at other than listed CFM / static pressures.

32

5-572.7

BloWer Performance data

table 33.1 - unit Performance tables

① ②

unit size

500/600

start 600

500/600

start 600

end 500

500/600

start 500

700/800

start 800

700/800

start 800

700/800

end 700

840/960

end 840

840/960

end 840 digit 16

G or H i, J, K l

G or H i, J, K l i, J, K l air total static Pressure inches "W.c.

temp 0.25 0.50 0.75 1.00 1.25 1.50 2.00 2.50 3.00

rise cfm BHP rPm BHP rPm BHP rPm BHP rPm BHP rPm BHP rPm BHP rPm BHP rPm BHP rPm

120°F / -

106°F / -

3086 0.62 529 0.82 620 1.03 703 1.26 779 1.50 849 1.75 916 2.28 1038 2.84 1149 3.44 1252

3500 0.84 575 1.06 658 1.30 736 1.54 807 1.80 874 2.07 937 2.63 1054 3.23 1162 3.86 1262

100°F / 120°F 3704 0.97 598 1.20 678 1.45 753 1.70 822 1.97 887 2.25 949 2.83 1064 3.44 1170 4.09 1268

93°F / 111°F 4000 1.18 633 1.43 709 1.69 779 1.96 846 2.24 908 2.53 968 3.14 1080 3.78 1183 4.45 1279

82°F / 99°F

74°F / 89°F

4500 1.61 693 1.88 762 2.17 827 2.46 889 2.77 948 3.09 1001 3.74 1110 4.43 1208

5000 2.13 755 2.43 818 2.75 878 3.07 936 3.40 991 3.74 1044 4.44 1145 - -

-

- -

-

67°F / 81°F

62°F / 74°F

57°F / 68°F

120°F / -

5500

6000

2.77 818 3.10

3.53 882 3.89

876 3.44 932 3.79 986 4.15 1038 4.51 1088

936 4.25 988 4.63 1038

6500 4.41 946 4.80 996 - - - -

3086 0.46 401 0.69 496 0.95 580 1.23 657

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

100°F / 120°F 3704 0.69 443 0.95 527 1.23 604 1.54 675 - - - -

93°F / 111°F 4000 0.82 464 1.09 544 1.39 618 1.71 686 2.05 749 2.42 810

74°F / 89°F

62°F / 74°F

-

-

-

-

-

-

-

-

-

-

-

-

5000 1.43 542 1.75 609 2.09 673 2.46 733 2.84 790 3.24 844 4.09 946 5.01 1041 - -

6000 2.31 624 2.68 682 3.07 738 3.48 791 3.91 842 4.35 891 5.29 984 6.28 1072 7.33 1155

53°F / 63°F

46°F / 56°F

41°F / 49°F

- / 44°F

7000

8000

9000

3.51 709 3.94

5.09 797 5.57

7.11 885 7.65

760 4.38 809 4.84 857 5.31

842 6.07 886 6.58 928 7.10

903

970

5.80 947 6.82

7.64 1010 8.75

1032 7.90 1113 9.03 1191

1089 9.92 1163 11.13 1235

926 8.20 965 8.76 1001 9.33 1042 9.92 1079 11.13 1151 12.38 1220 13.69 1287

10000 9.62 975 10.21 1012 10.81 1048 11.43 1083 12.05 1118 12.69 1152 14.00 1218 15.35 1283 - -

- / 43°F

- / 40°F

- / 40°F

62°F / 74°F

53°F / 63°F

46°F / 56°F

41°F / 49°F

- / 44°F

10400 10.77 1011 11.38 1046 12.01 1081 12.64 1115 13.29 1149 13.95 1182 15.30 1247 -

11000 12.66 1065 13.31 1099 13.97 1132 14.64 1164 15.32 1197 16.01 1228 17.42 1290 -

11111 13.04 1075 13.69 1109 14.36 1141 15.03 1174 15.72 1205 16.41 1237 17.83 1298 -

6000 1.69 512 1.97 565 2.26 615 2.57 664 2.89 710 3.23 755 - - -

-

-

-

-

-

-

-

-

7000 2.57 580 2.89 626 3.22 671 3.56 714 3.92 756 4.29 797 5.06 874 - -

8000 3.73 650 4.09 691 4.46 731 4.84 770 5.23 808 5.64 845 6.47 916 7.35 984

-

-

-

-

9000 5.21 721 5.60 758 6.01 795 6.43 830 6.86 864 7.30 898 8.21 964 9.16 1027 10.14 1088

10000 7.04 793 7.48 827 7.93 860 8.39 892 8.85 924 9.33 955 10.31 1016 11.33 1074 12.38 1131

-

-

-

-

- / 43°F

- / 40°F

- / 40°F

120°F / -

10400 7.88 823 8.34 855 8.80 887 9.28 918 9.76 949 10.25 979 11.26 1038 12.31 1095 13.38 1150

11000 9.27 866 9.75 897 10.24 927 10.74 957 11.24 986 11.76 1015 12.81 1071 13.90 1126 - -

11111 9.54 874 10.03 905 10.52 935 11.02 964 11.53 993 12.05 1022 13.12 1078 14.21 1132

4321 1.51 685 1.80 760 2.11 830 2.43 896 2.77 958 3.13 1018 3.88 1131 4.69 1236

-

- -

-

115°F / - 4500 1.68 708 1.98 780 2.30 847 2.63 912 2.98 973 3.34 1032 4.11 1142 4.94 1245

105°F / 120°F 4938 2.15 763 2.48 89 2.82 893 3.17 953 3.54 1011 3.93 1066 4.74 1172 - -

104°F / 119°F 5000 2.23 770 2.55 836 2.90 899 3.26 959 3.63 1016 4.02 1072 4.83 1176 -

94°F / 108°F 5500 2.89 834 3.25 895 3.62 953 4.00 1009 4.40 1063 4.81 1116 - - -

-

-

-

-

-

-

-

-

-

-

86°F / 99°F

80°F / 91°F

6000

6500

3.68 900 4.06

4.61 965 -

956 4.46 1010 4.87 1062

- - - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

120°F / - 4321 0.87 443 1.14 421 1.42 591 1.72 657 2.04 717 2.37 774 3.08 879 3.84 974 4.65 1063

104°F / 119°F 5000 1.26 488 1.55 558 1.87 623 2.20 683 2.54 740 2.90 794 3.66 894 4.47 985 5.33 1071

86°F / 99°F

65°F / 74°F

6000

8000

2.02 558 2.36

4.44 707 4.89

619 2.73 677 3.10 731 3.49

755 5.35 801 5.82 845 6.30

782

888

3.89 832

6.79 930

4.73

7.81

924 5.62 1010 6.55 1091

1009 8.87 1085 9.96 1156

58°F / 66°F 9000 6.19 784 6.69 827 7.20 869 7.72 909 8.25 949 8.79 987 9.90 1061 11.04 1131 12.23 1199

52°F / 59°F 10000 8.36 861 8.91 901 9.47 939 10.04 976 10.62 1012 11.21 1048 12.42 1117 13.66 1183 14.93 1246

47°F / 54°F 11000 11.00 940 11.60 976 12.22 1011 12.84 1045 13.47 1079 14.11 1112 15.41 1176 16.74 1238

43°F / 49°F 12000 14.16 1019 14.81 1052 15.48 1085 16.15 1117 16.83 1148 17.52 1179 18.92 1239 - -

-

-

-

-

40°F / 46°F 13000 17.88 1098 18.59 1129 19.30 1159 -

65°F / 74°F 8000 3.26 566 3.60

- -

611 3.95 654 4.31 696 4.67

-

736

- -

5.05 774

-

5.84

- - -

848 6.66 918

- -

7.51 984

58°F / 66°F 9000 4.54 626 4.92 667 5.30 706 5.70 744 6.10 780 6.52 816 7.37 885 8.25 950 9.17 1012

52°F / 59°F 10000 6.13 687 6.54 724 6.97 760 7.40 794 7.85 828 8.30 861 9.22 925 10.17 987 11.15 1046

47°F / 54°F 11000 8.06 749 8.52 782 8.98 815 9.45 847 9.93 879 10.42 910 11.41 969 12.43 1027 13.48 1083

47°F / 54°F 11050 8.17 752 8.62 785 9.09 818 9.56 850 10.04 881 10.53 912 11.53 972 12.56 1029 13.61 1084

43°F / 49°F 12000 10.37 811 10.86 842 11.37 872 11.88 902 12.40 931 12.92 960 13.99 1016 15.08 1070 16.20 1123

40°F / 46°F 13000 13.09 873 13.63 902 14.17 930 14.72 958 15.27 986 15.83 1013 16.98 1065 18.14 1116 19.33 1166

- / 42°F

- / 41°F

14000 16.26 936 16.83 963 17.41 989 18.00 1015 18.59 1041 19.19 1066

14500 18.02 968 18.61 994 19.21 1019 19.82 1045 - - - -

-

-

-

-

-

-

-

-

-

- -

-

120°F / -

111°F / -

6481

7000

2.72 630 3.09

3.36 672 3.76

685 3.48 736 3.88 785 4.30

723 4.17 772 4.60 818 5.04

832

863

4.72 876

5.49 905

5.60

6.42

960 6.52 1038 7.48 1112

986 7.38 1061 8.39 1133

105°F / 120°F 7407 3.93 705 4.35 754 4.79 800 5.23 845 5.69 888 6.16 929 7.13 1007 8.13 1081 9.17 1151

97°F / 111°F 8000 4.87 754 5.33 799 5.90 843 6.27 885 6.76 926 7.26 965 8.28 1040 9.33 1111 10.43 1179

86°F / 99°F 9000 6.80 837 7.31 878 7.83 918 8.36 956 8.90 994 9.44 1030 10.56 1100 11.71 1166 12.90 1230

78°F / 89°F 10000 9.20 921 9.76 958 10.33 995 10.91 1030 11.50 1065 12.10 1099 13.32 1164 14.56 1226 - -

70°F / 80°F 11050 12.28 1010 12.89 1044 13.52 1078 14.16 1110 14.80 1142 15.45 1173 16.77 1234 -

65°F / 74°F 12000 15.60 1091 16.27 1123 16.95 1154 17.63 1184 18.32 1214 19.02 1243 - - -

-

-

-

- -

-

62°F / 71°F 12500 17.58 1134 18.27 1164 18.97 1194 19.69 1224 -

60°F / 68°F 13000 19.71 1177 - - - - - - -

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

86°F / 99°F 9000 5.01 675 5.40 715 5.80 753 6.21 789 6.62 825 7.05 859 7.91 925 8.81 988 9.73 1048

78°F / 89°F 10000 6.78 742 7.21 778 7.64 812 8.09 846 8.54 879 9.00 911 9.95 973 10.91 1032 11.91 1088

70°F / 80°F 11050 9.04 812 9.51 845 9.99 877 10.48 908 10.97 939 11.47 968 12.50 1026 13.54 1081 14.61 1135

65°F / 74°F 12000 11.48 876 12.00 907 12.51 937 13.04 966 13.57 994 14.11 1022 15.20 1076 16.32 1129 17.46 1179

60°F / 68°F 13000 14.50 945 15.05 973 15.62 1000 16.18 1028 16.75 1054 17.33 1081 18.50 1132 19.70 1181

- / 63°F 14000 18.02 1013 18.61 1039 19.21 1065 19.82 1091 - - - - - - - -

-

- -

-

Total static pressure should include external static pressure and accessory / option static pressure from Table 30.1. Unit internal resistance has been included in the unit performance tables.

Brake Horsepower and RPM values are approximate values only. Please consult the AccuSpec selection software for values at other than listed CFM / static pressures.

5-572.7

33

BloWer sHeave assemBly data

adjusting the Blower drive setting

Based on the Sheave Arrangement, Tables 34.1 through 35.5 give the Sheave Assembly numbers used on units that include a blower. The Sheave Arrangement is Digit 19 and is found on the unit Model Identification Plate. The Sheave Assembly describes the motor and blower sheave size and bore as well as the belt provided.

To determine how many turns open the motor sheave should be set for:

1. Follow the Selection Procedure found on pages 28 and 29 to determine what blower rpm is required to meet the job specifications.

2. Locate the unit Model Identification Plate and note Digit 16 and Digit 19 of the model number. Digit 16 is the Blower

Size and Type and Digit 19 is the Sheave Arrangement.

3. Once the Blower Size and Type (Digit 16) is known, enter the proper Sheave Arrangement table.

4. Use the Sheave Arrangement (Digit 19) to determine the

Sheave Assembly provided.

5. Use Table 36.1 and the Sheave Assembly number to determine the required turns open to achieve the desired blower rpm.

6. Set the motor sheave as described in Blower Adjustments.

figure 34.1 - Blower section

EXTENDED

GREASE

LINES

ADJUSTABLE

MOTOR

SHEAVE

MOTOR

FILTER

RACk

EXTENDED

GREASE LINE

ZERk FITTINGS

1/4" PERIMETER

GASkETED

BLOWER

CONNECTION

CONVENIENCE

OUTLET

BLOWER DOOR

SAFETY SWITCH

BOTTOM

SUPPORTED

BLOWER AND

MOTOR

DIRECT

DRIVE

DAMPER

ACTUATOR

Blower sheave assembly numbers table 34.1 - digit 16 = a or B (9-7 Blower units)

motor frame size

48

56

143 or 145

656-1001 978-1265 rPm range

1150-1561 1526-1858 1763-2147

Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly

A 3H35125B1

B

3H35125B2

C

D

E

3H35125B3

3H35125B4

3H35125B5

F

G

3H35125B6

3H35125B7

H

I

3H35125B8

3H35125B9

J k

3H35125B10

3H35125B11

table 34.2 - digit 16 = c or d (9-9 Blower units)

motor frame size

48

56

143 or 145

182 or 184

656-1001 978-1265 rPm range

1150-1561 1526-1858 1763-2147

Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly

A

B

3H35126B1

3H35126B2

C

3H35126B3

D

3H35126B4

F

3H35126B6

E 3H35126B5 G 3H35126B7

I

J

3H35126B9

L

3H35126B12

3H35126B10 M

3H35126B13

H

3H35126B8

k

3H35126B11

N

3H35126B14

34

5-572.7

BloWer sHeave assemBly data

Blower sheave assembly numbers (con’t) table 35.1 - digit 16 = e or f (12-12 Blower units)

motor frame size

48

56

143 to 145

182 or 184

213 or 215

468-715 644-874 rPm range

863-1078 1029-1332 1150-1438 1327-1659

Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly

A

3H35127B1

B 3H35127B2 C

D

E

3H35127B3

3H35127B4

3H35127B5

F

G

H

3H35127B6

3H35127B7

3H35127B8

Q

I

J

3H35127B10

M

3H35127B13

O

3H35127B15

k

3H35127B17

3H35127B9

3H35127B11

L

3H35127B12

N

3H35127B14

P

3H35127B16

table 35.2 - digit 16 = G or H (15-15 Blower units)

motor frame size

48

56

143 to 145

182 or 184

213 or 215

410-625

rPm range

568-771 767-958 934-1136 1136-1380

Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly

A 3H35128B1

B 3H35128B2

C

3H35128B3

D 3H35128B4 G

3H35128B7

O

3H35128B15

E 3H35128B5 H 3H35128B8

F 3H35128B6 I 3H35128B9

J k

L

3H35128B10

3H35128B11

3H35128B12

M

N

3H35128B13

3H35128B14

table 35.3 - digit 16 = i or J (18-18 Blower units under 15 Hp motor)

motor frame size

56

143 or 145

182 to 184

213 or 215

254

256

491-649 586-744 rPm range

682-821 821-1009 995-1161 1101-1285

Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly

A

B

C

3H35129B1

3H35129B2

3H35129B3

D 3H35129B4

E

3H35129B5

H

F

G

3H35129B6

3H35129B7

I

J

3H35129B8

3H35129B9

3H35129B10 k

3H35129B11

O

3H35129B15

L

3H35129B12

P

3H35129B16

S

3H35129B19

M

3H35129B13

Q

3H35129B17

T

3H35129B20

N

3H35129B14

R

3H35129B18

U

3H35129B21

table 35.4 – digit 16 = K (18-18 Blower units with 15 Hp motor & up)

motor frame size

254

256

284

286

826-1009

rPm range

995-1161 1101-1285 1232-1438

Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly

A

3H35130B1

C

3H35130B3

E

3H35130B5

B

3H35130B2

D

3H35130B4

F

3H35130B6

G

3H35130B13

I 3H35130B15 k 3H35130B17 M

3H35130B19

H

3H35130B14

J

3H35130B16

L

3H35130B18

N

3H35130B20

table 35.5 - digit 16 = l (20-18 Blower units)

rPm range

motor frame size

491-649 626-765 765-901 901-1059 995-1161 1101-1285

Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly Digit 19 Sheave Assembly

143 or 145

182 to 184

213 or 215

254

256

284

286

A

B

3H36622B1

3H36622B2

C 3H36622B3

D 3H36622B4

E

F

3H36622B5

G

H

3H36622B6

3H36622B7

3H36622B8

L

3H36622B12

M

3H36622B13

R

3H36622B18

N

3H36622B14

S

3H36622B19

W

3H36622B23

I

3H36622B9

O

3H36622B15

T

3H36622B20

X

3H36622B24

J 3H36622B10 P 3H36622B16 U 3H36622B21 Y

3H36622B25

k

3H36622B11

Q

3H36622B17

V

3H36622B22

Z

3H36622B26

5-572.7

35

BloWer sHeave assemBly data

table 36.1 - Blower sheave assembly settings

sheave assembly

3H35125B1-2

3H35125B3-5

3H35125B6-7

0 0.5

1001 966

1

932

1.5

897

turns open

2 2.5

3

Blower rPm

863 828 794

3.5

759

4

725

4.5

690

5

656

1265 1236 1208 1179 1150 1121 1093 1064 1035 1006 978

1561 1520 1479 1438 1396 1355 1314 1273 1232 1191 1150

3H35125B8-9 1858 1825 1791 1758 1725 1692 1659 1625 1592 1559 1526

3H35125B10-11 2147 2108 2070 2032 1993 1955 1917 1878 1840 1802 1763

3H35126B1-2 1001 966 932 897 863 828 794 759 725 690 656

3H35126B3-5

3H35126B6-8

1265 1236 1208 1179 1150 1121 1093 1064 1035 1006 978

1561 1520 1479 1438 1396 1355 1314 1273 1232 1191 1150

3H35126B9-11 1858 1825 1791 1758 1725 1692 1659 1625 1592 1559 1526

3H35126B12-14 2147 2108 2070 2032 1993 1955 1917 1878 1840 1802 1763

3H35127B1-2

3H35127B3-5

3H35127B6-8

715

874

690

851

665

828

641

805

616

782

1078 1057 1035 1013 992

591

759

970

567

736

949

542

713

927

518

690

906

493

667

884

468

644

863

3H35127B9-11 1332 1301 1271 1241 1211 1180 1150 1120 1089 1059 1029

3H35127B12-14 1438 1409 1380 1351 1323 1294 1265 1236 1208 1179 1150

3H35127B15-16 1659 1625 1592 1559 1526 1493 1460 1426 1393 1360 1327

3H35127B17

3H35128B1-3

3H35128B4-6

3H35128B7-9

1332 1301 1271 1241 1211 1180 1150 1120 1089 1059 1029

625

771

958

604

751

939

582

731

920

561

710

901

539

690

882

518

670

863

496

649

843

474

629

824

453

609

805

431

589

786

410

568

767

3H35128B10-12 1136 1116 1096 1076 1055 1035 1015 994 974 954 934

3H35128B13-14 1380 1355 1331 1306 1281 1257 1232 1208 1183 1158 1136

3H35128B15 1136 1116 1096 1076 1055 1035 1015 994 974 954 934

3H35129B1-3

3H35129B4-7

3H35129B8-10

649

744

821

633

728

807

617

712

793

601

696

779

586

681

765

570

665

751

554

649

737

538

633

723

522

617

709

506

601

696

491

586

682

3H35129B11-14 1009 991 973 954 936 918 899 881 863 844 821

3H35129B15-18 1161 1144 1128 1111 1095 1078 1062 1045 1028 1012 995

3H35129B19-21 1285 1266 1248 1230 1211 1193 1174 1156 1138 1119 1101

3H35130B1-2 1009 991 973 954 936 918 899 881 863 844 826

3H35130B3-4

3H35130B5-6

3H35130B13-14

1161 1144 1128 1111 1095 1078 1062 1045 1028 1012 995

1285 1266 1248 1230 1211 1193 1174 1156 1138 1119 1101

974 960 946 932 918 904 890 876 863 849 835

3H35130B15-16 1161 1144 1128 1111 1095 1078 1062 1045 1028 1012 995

3H35130B17-18 1285 1266 1248 1230 1211 1193 1174 1156 1138 1119 1101

3H35130B19-20 1438 1417 1396 1376 1355 1335 1314 1294 1273 1253 1232

3H36622B1-2

3H36622B3-5

649 633 617 601 586 570 554 538 522 506 491

765 751 737 723 709 696 682 668 654 640 626

3H36622B6-11 901 888 875 863 850 837 824 811 798 785 765

3H36622B12-17 1059 1044 1029 1014 999 984 968 953 938 923 901

3H36622B18-22 1161 1144 1128 1111 1095 1078 1062 1045 1028 1012 995

3H36622B23-26 1285 1266 1248 1230 1211 1193 1174 1156 1138 1119 1101

36

5-572.7

BloWer sHeave assemBly data

table 37.1 - Blower sheave assembly settings

sheave assembly

3H35127B9

3H35127B10

3H35127B11

3H35127B12

3H35127B13

3H35127B14

3H35127B15

3H35127B16

3H35127B17

3H35128B1

3H35128B2

3H35128B3

3H35128B4

3H35128B5

3H35128B6

3H35128B7

3H35128B8

3H35128B9

3H35128B10

3H35128B11

3H35128B12

3H35128B13

3H35128B14

3H35128B15

3H35126B8

3H35126B9

3H35126B10

3H35126B11

3H35126B12

3H35126B13

3H35126B14

3H35127B1

3H35127B2

3H35127B3

3H35127B4

3H35127B5

3H35127B6

3H35127B7

3H35127B8

3H35125B1

3H35125B2

3H35125B3

3H35125B4

3H35125B5

3H35125B6

3H35125B7

3H35125B8

3H35125B9

3H35125B10

3H35125B11

3H35126B1

3H35126B2

3H35126B3

3H35126B4

3H35126B5

3H35126B6

3H35126B7

8.5

8

7

6.5

9

9

9

8.5

8.5

5.7

8

8

8

8.5

8.5

8.5

6

6.2

5.2

5.7

5.7

5.7

6.7

6

7.5

8

8

8

7

7

7.5

7.5

4.2

5.2

5.2

5.2

4.5

4.5

4.5

6

6

4.2

4.2

4.5

5

5

6

Blower sheave

Pitch diameter Bore

5

5

0.75

0.75

6

6

0.75

0.75

6

4.2

4.2

5.2

5.2

4.5

0.75

0.75

0.75

0.75

0.75

0.75

0.75

0.75

0.75

0.75

0.75

0.75

0.75

0.75

0.75

0.75

0.75

0.75

0.75

0.75

0.75

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

5.6

5.2

5.6

5.2

5

5

5

5.6

5.6

4.4

2.9

2.9

2.9

3.8

3.8

3.8

5

5.2

5

5.6

4.4

4.4

5.2

5

3.8

5

5

5

2.9

2.9

3.8

3.8

3.8

5.6

5.6

5.6

5.6

5.6

5.6

4.4

4.4

3.8

3.8

5.6

2.9

2.9

4.4

motor sheave

Pitch diameter Bore

2.9

2.9

0.5

0.625

4.4

4.4

0.5

0.625

4.4

3.8

3.8

5.6

5.6

5.6

0.875

0.625

0.875

0.625

0.875

0.625

1.125

0.625

0.875

1.125

0.625

0.875

1.125

0.875

0.5

0.625

0.5

0.625

0.875

0.625

0.875

0.625

0.875

1.125

0.875

1.125

1.375

1.125

1.375

0.625

0.625

0.5

0.625

0.875

0.625

0.875

1.125

0.875

1.125

1.375

0.875

1.125

1.375

1.125

1.375

0.5

0.625

0.625

0.875

1.125

0.625

0.875

1.125

Browning

Belt no.

A43

A47

A48

A48

A50

A50

A52

A43

A45

A49

A45

A47

A49

A45

A48

A53

A52

A54

A53

A54

A54

A52

A52

A53

A42

A43

A46

A45

A47

A48

A48

A50

A36

A38

A38

A40

A37

A37

A39

A34

A33

A34

A37

A38

A38

A34

A34

A30

A31

A34

A35

A35

A31

A31

A35

A35

A34

5-572.7

8.9

12.4

8.9

10.4

11.4

11.4

13.4

9.4

8.4

8.4

10.9

10.9

8.9

9.4

12.4

12.4

10.4

10.4

9.4

9.4

9.4

9.4

10.4

10.4

9.4

11.4

10.4

10.4

10.4

10.4

10.4

9.4

9.4

9.4

9.4

13.4

8.4

9.4

9.4

9.4

11.4

9.4

10.4

10.4

10.4

10.4

9.4

9.4

12.4

12.4

12.4

8.9

9.4

9.4

Blower sheave

Pitch diameter Bore

10.9

1

10.9

10.9

10.9

10.9

10.9

12.4

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1.44

1

1.44

1.44

1.44

1.44

1.44

6

6

7

4.1

5.5

4.7

5.5

7

7

7

4.1

4.1

4.1

7

7

7

7

7

7

7

5.5

5.5

7

7

7

7

7

7

7

7

7

7

7

7

7

7

5.3

5.9

6

6

7

7

7

7

5.5

7

7

7

5.9

5.9

5.9

5.3

5.5

5.5

motor sheave

Pitch diameter Bore

4.1

0.625

4.1

4.1

4.7

4.7

4.7

5.5

0.875

1.125

0.625

0.875

1.125

1.375

1.625

1.125

1.375

1.625

1.625

1.375

1.625

0.875

1.125

1.375

1.125

1.375

1.625

1.875

1.375

1.625

1.625

1.875

1.875

1.875

1.125

1.375

1.625

1.625

1.875

1.625

1.625

1.875

1.875

1.125

1.375

1.125

1.375

1.625

1.625

1.875

1.875

1.875

1.875

0.875

1.125

0.875

1.625

1.875

1.875

1.875

1.875

1.875

1.625

1.625

1.625

1.625

1.625

1.625

sheave assembly

3H35129B21

3H35130B1

3H35130B2

3H35130B3

3H35130B4

3H35130B5

3H35130B6

3H35130B13

3H35130B14

3H35130B15

3H35130B16

3H35130B17

3H35130B18

3H35130B19

3H35130B20

3H36622B1

3H36622B2

3H36622B3

3H36622B4

3H36622B5

3H36622B6

3H36622B7

3H36622B8

3H36622B9

3H36622B10

3H36622B11

3H36622B12

3H36622B13

3H36622B14

3H36622B15

3H36622B16

3H36622B17

3H36622B18

3H36622B19

3H36622B20

3H36622B21

3H36622B22

3H36622B23

3H36622B24

3H36622B25

3H36622B26

3H35129B1

3H35129B2

3H35129B3

3H35129B4

3H35129B5

3H35129B6

3H35129B7

3H35129B8

3H35129B9

3H35129B10

3H35129B11

3H35129B12

3H35129B13

3H35129B14

3H35129B15

3H35129B16

3H35129B17

3H35129B18

3H35129B19

3H35129B20

Browning

Belt no.

B77

Qty (2) B74

Qty (2) B74

Qty (2) B78

Qty (2) B78

Qty (2) B77

Qty (2) B77

Qty (2) B82

Qty (2) B82

Qty (2) B79

Qty (2) B79

Qty (2) B77

Qty (2) B77

Qty (2) B75

Qty (2) B75

B75

BX73

B72

B70

BX78

B74

BX75

Qty (2) BX82

Qty (2) BX82

Qty (2) B86

Qty (2) B86

B71

BX74

Qty (2) BX79

Qty (2) BX79

Qty (2) B83

Qty (2) B83

B77

Qty (2) B82

Qty (2) B82

Qty (2) B81

Qty (2) B81

Qty (2) B80

Qty (2) B80

Qty (2) B80

Qty (2) B80

BX75

B73

B72

B78

B78

B70

B77

BX77

BX75

BX75

BX68

BX68

BX75

B71

B71

B70

BX71

BX71

BX71

BX71

37

electrical data

total unit amp draw

The total unit amp draw is a combination of the motor, the control step down transformer, the power exhauster motor, and the evaporative cooler pump motor (or step down transformer for 208V/1Ph, 208V/3Ph, 460V/3Ph, or 575V/3Ph units) where applicable.

The control step down transformer includes damper actuators, ignition controllers, gas valves, control relays, amplifiers, and motor starters.

Motor Amp Draw (Tables 38.1 to 42.1) =

Control Step Down Transformer Amp Draw (Table 38.1) =

Power Exhauster Motor Amp Draw (Table 38.1) =

Evaporative Cooler Amp Draw (Table 38.2) =

+ ____________

Total Amp Draw =

table 38.1 - control step down transformer amp draws

digit 14 control step down transformer amp draw

Power exhauster amp draw

supply voltage

0 digit 15 - transformer

1 2 3 4 75-175 200-400 model size

500-800 840-960 a

115/60/1

0 0.35 0.65

1.3

2.17

1.4

2.00/2.40

4.00/4.80

6.00/7.20

B 208/60/1

0 0.19 0.36 0.72

1.2

0.7

1.10/1.40

2.20/2.80

3.30/4.20

c 230/60/1

0 0.17 0.33 0.65 1.09 0.66/0.60

0.95/1.30

1.90/2.60

2.85/3.90

d

G

208/60/3

0 0.19 0.36 0.72

1.2

0.7

1.10/1.40

2.20/2.80

3.30/4.20

e 230/60/3

0 0.17 0.33 0.65 1.09 0.66/0.60

0.95/1.3

1.90/2.60

2.85/3.90

f

460/60/3

0 0.09 0.16 0.33 0.54

0.30➁ 0.54②/0.65➂ 1.08③/1.3➃ 1.63④/2.0➄

575/60/3

0 0.07 0.13 0.26 0.43

0.24➁ 0.43②/0.52➂ 0.87③/1.1➃ 1.30④/1.6➄

table 38.2 - evaporative cooler amp draws (digit 22 = 3, 4, 5 or 6)

model size

Blower a type (digit 16) (115/60/1)

digit 14 (supply voltage)

B

(208/60/1) c

(230/60/1) d

(208/60/3)

all

All 1.00 1.20 0.50 1.20

When 2 amp draws are listed, the first is for Outdoor units and the second is for Indoor Power Vented & Separated Combustion units.

Amp draw is for a 250 VA transformer.

Amp draw is for a 500 VA transformer.

Amp draw is for a 750 VA transformer.

Amp draw is for a 1000 VA transformer.

Only include amp draw for gravity vented models. For power vented models, the step down transformer amp draw is included in the

Power Exhauster Motor Amp Draw. Amp draw is for 250 VA step down transformer.

e

(230/60/3)

0.50

f

(460/60/3)

0.54

G

(575/60/3)

0.43

table 38.3 - motor data for digit 14 = a - 115v/60Hz/1Ph table 38.4 - motor data for digit 14 = B - 208v/60Hz/1Ph

digits

17&18

a1

a5

B1

B5

c1

c5

d1

d5

e1

e5

f1 or r1

f5 or r5

G1 or s1

G5 or s5

motor

1/3 ➂

1/3 ➂ TENV 48 5.0 1.00

1/2 ➂ ODP 56 9.0 1.25

1/2 ➂ TEFC 56 8.0 1.15

3/4 ➂ ODP 56 11.0 1.25

3/4 ➂ TE

1 ➂ ODP 56 13.4 1.15

1 ➂ TE

1 1/2 ➂ ODP 56 18.0 1.15

1 1/2 ➂ TE

2 ODP 145T 21.0 1.15

2 TE 182T 20.0 1.15

3 ODP 184T 34.0 1.15

3

motor frame amp. service Weight efficiency

size (HP) type size draw factor (lbs)

ODP

TE

56 6.6

56 11.0 1.15

56 13.4 1.15

56 15.2 1.15

184T 32.0

1.35

1.00

37

40

45

49

54

81

83

25

25

23

28

25

30

32

(%)

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

digits motor motor frame amp. service Weight efficiency

17&18

size (HP) type size draw factor (lbs) (%)

a1

B1

B5

c1

c5

d1

d5

e1

e5

f1 or r1

f5 or r5

H1 or t1

H5 or t5

1/3 ➂

5

ODP

TE

56 3.0

184T 22.8

1.35

1/2 ➂ ODP 56 4.1 1.25

1/2 ➂ TEFC 56 4.0 1.15

3/4 ➂ ODP 56 5.5 1.25

3/4 ➂ TE 56 5.4 1.15

1 ➂ ODP 56 6.8 1.15

1 ➂ TE 56 6.8 1.15

1 1/2 ➂ ODP 56 9.3 1.15

1 1/2 ➂ TE 56 8.2 1.15

2 ODP 145T 11.3 1.15

2 TE 182T 10.8 1.15

5 ODP 184T 23.0 1.15

1.00

Refer to page 42 for Motor Type abbreviations.

Motors manufacturers do not rate single-phase motors for efficiency.

Single phase motors, 1-1/2HP and smaller, feature integral thermal overload protection. 2HP and larger require external protection. The optional motor starter for those sizes provides overcurrent protection.

40

45

49

54

87

86

25

23

28

25

30

32

37

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

38

5-572.7

motor data

table 39.1 - motor data for digit 14 = c - 230v/60Hz/1Ph

digits

17&18

a1

a5

B1

B5

c1

c5

d1

d5

e1

e5

f1 or r1

f5 or r5

G1 or s1

G5 or s5

H1 or t1

H5 or t5

motor size (HP)

1/3 ➂

1/3 ➂

1/2 ➂

1/2 ➂

3/4 ➂

3/4 ➂

1 ➂

1 ➂

1 1/2 ➂

1 1/2 ➂

2

2

3

3

5

5

motor

type

ODP

TENV

ODP

TEFC

ODP

TE

ODP

TE

ODP

TE

ODP

TE

ODP

TE

ODP

TE

frame size

56

56

56

56

56

145T

182T

184T

56

48

56

56

56

184T

184T

184T

amp. draw

3.3

2.5

4.5

4.0

5.5

5.5

6.7

6.7

9.0

7.6

10.5

10.0

17.0

16.0

22.0

20.2

service factor

1.35

1.00

1.25

1.15

1.25

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.00

1.15

1.00

Weight

(lbs)

45

49

54

81

30

32

37

40

25

25

23

28

25

83

87

86

efficiency

(%)

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Refer to page 42 for Motor Type abbreviations.

Motors manufacturers do not rate single-phase motors for efficiency.

Single phase motors, 1-1/2HP and smaller, feature integral thermal overload protection. 2HP and larger require external protection. The optional motor starter for those sizes provides overcurrent protection.

table 39.2 - motor data for digit 14 = d - 208v/60Hz/3Ph

motor

digits size motor frame amp. service Weight efficiency

17&18 (HP)

type

size draw factor (lbs) ( %)

a1 or l1 1/3

a5 or l5 1/3

B1 or m1 1/2

B5 or m5 1/2

c1 or n1 3/4

c5 or n5 3/4

d1 or P1

d2 or P2

1

1

ODP

TE

ODP

TEFC

ODP

56

48

56

56

56

1.5

1.2

2.1

2.1

2.7

1.35

1.00

1.25

1.15

1.25

TEFC

ODP

56 2.7

143T 3.1

1.15

1.15

ODP HE 143T 3.2 1.15

d3 or P3

1 ODP 18/9 143T 3.5/1.5 1.15

17 N/A

d4 or P4

1 ODP 18/12 145T 3.4/2.0 1.15

d5 or P5

1

d6 or P6

1

TEFC 56 3.5

TE HE 143T 3.5

1.15

1.15

d7 or P7

1 TEFC 18/9 143T 3.5/1.5 1.00

d8 or P8 1 TEFC 18/12 145T 3.2/1.8 1.00

e1 or Q1 1 1/2 ODP

ODP

1.15

1.00 e2 or Q2 1 1/2

145T 5.9

145T 4.8

e3 or Q3 1 1/2 ODP 18/9 145T 5.0/2.1 1.15

e4 or Q4 1 1/2 ODP 18/12 145T 5.0/2.9 1.15

e5 or Q5 1 1/2 TEFC 56 4.8

e6 or Q6 1 1/2 TE HE 145T 4.9

1.15

1.15

e7 or Q7 1 1/2 TEFC 18/9 145T 4.3/1.9 1.00

e8 or Q8 1 1/2 TEFC 18/12 145T 5.0/2.9 1.00

f1 or r1 2

f2 or r2 2

ODP

ODP

145T 7.2

145T 5.8

1.15

1.00

f3 or r3 2 ODP 18/9 145T 6.2/2.6 1.15

f4 or r4 2 ODP 18/12 182T 6.5/3.5 1.15

f5 or r5 2

f6 or r6 2

TE 145T 7.0

TE HE 145T 6.5

1.15

1.15

f7 or r7 2 TEFC 18/9 145T 6.4/2.5 1.00

f8 or r8 2 TE 18/12 182T 6.4/3.9 1.15

G1 or s1 3

G2 or s2 3

ODP

ODP HE

182T 10.0

182T 8.9

1.15

1.15

G3 or s3 3 ODP 18/9 182T 10.1/4.1 1.15

G4 or s4 3 ODP 18/12 184T 9.3/4.9 1.15

G5 or s5

3 TE 182T 10.0 1.15

TE HE 182T 9.4-9.1 1.15

G6 or s6

3

G7 or s7

3 TE 18/9 182T 9.3/3.5 1.00

G8 or s8

3 TE 18/12 184T 9.2/5.4 1.15

83

92

87.5%

88.5%

64 84.0 / 70.0%

84 84.0 / 82.0%

H1 or t1

5

H2 or t2

5

ODP 184T 16.0 1.15

ODP HE 182T 15.7 1.15

76

94

84.0%

89.5%

H3 or t3

5 ODP 18/9 184T 16.0/6.2 1.15 81 85.0 / 77.0%

H4 or t4

5 ODP 18/12 215T 16.0/9.7 1.15 117 86.0 / 78.0%

H5 or t5

5

H6 or t6

5

TE 184T 14.2 1.15

TE HE 184T 15.0 1.15

90

99

87.5%

88.5%

H7 or t7

5 TE 18/9 184T 15.0/5.3 1.00 85 85.0 / 85.0%

H8 or t8 5 TE 18/12 213T 15.0/8.5 1.15 107 85.0 / 80.0%

i1 or W1 7 1/2 ODP 213T 26.9 1.15 106 81.5%

15

18

18

21

N/A

N/A

N/A

N/A

30

40

N/A

82.5%

30 84.0%

26 76.0 / 59.0%

42 74.0 / 60.0%

28

68

N/A

84.5%

29 76.0 / 58.0%

31 74.0 / 60.0%

43

35

80.0%

89.5%

29 80.0 / 65.0%

49 80.0 / 71.0%

33 N/A

84.0% 62

38 83.0 / 71.0%

38 80.0 / 72.0%

43

74

82.0%

89.5%

33 81.0 / 67.0%

78 81.0 / NA%

52

66

84.0%

86.5%

41 84.0 / 70.0%

65 84.0 / 77.0%

78

83

81.5%

89.5%

66 82.0 / 72.0%

79 81.0 / 75.0%

motor

digits size motor frame amp. service Weight efficiency

17&18 (HP) type

size draw factor (lbs) (%)

i2 or W2 7 1/2 ODP HE 213T

22.3 1.15

i3 or W3 7 1/2 ODP 18/9 213T 23.0/9.3

1.15

i4 or W4 7 1/2 ODP 18/12 215T 22.0/12.3 1.15

i5 or W5 7 1/2

TE 213T 24.0

i6 or W6 7 1/2

TE HE 213T 22.0

1.15

1.15

i7 or W7 7 1/2 TE 18/9

213T 21.0/8.8 1.15

i8 or W8 7 1/2 TE 18/12 215T 21.8/12.0 1.15

J1 or X1 10

J2 or X2 10

J5 or X5 10

J6 or X6 10

ODP

TE

215T 32.6

ODP HE 215T 29.0

215T 29.0

TE HE 215T 27.6

1.15

1.15

J4 or X4 10 ODP 18/12 256T 27.0/14.5 1.15

1.15

1.15

141 91.7%

108 85.0 / 72.0%

167 89.0 / 85.0%

126

158

89.5%

90.2%

106 87.0 / 75.0%

124 86.0 / 80.0%

120

126

196 88.0 / 80.0%

130

200

84.0%

91.7%

J3 or X3 10 ODP 18/9 215T 27.7/11.2 1.15 118 88.0 / 77.0%

87.5%

90.2%

J7 or X7 10 TE 18/9 215T 29.0/11.5 1.15 118 87.0 / 77.0%

J8 or X8 10 TE 18/12 254T 30.0/17.0 1.15 212 88.0 / 80.0%

K1 or y1 15 ODP 254T 45.6

K2 or y2 15 ODP HE 254T 43.4

K5 or y5 15

K6 or y6 15

TE

TE HE

254T 42.0

254T 40.3

1.15

1.15

K3 or y3 15 ODP 18/9 256T 42.5/16.5 1.15 244 90.2 / 84.0%

1.15

1.15

147

220

250

259

87.5%

93.0%

91.0%

91.7%

K7 or y7 15 TE 18/9 256T 44.0/16.0 1.15 218 88.0 / 82.0%

K8 or y8 15 TE 18/12 256T 42.0/23.0 1.15 219 88.0 / 84.0%

v1 or Z1 20 ODP 256T 61.6

v2 or Z2 20 ODP HE 256T 57.0

1.15

1.15

200

250

87.5%

93.6%

v3 or Z3 20 ODP 18/9 284T 56.0/21.0 1.15 221 90.2 / 82.5%

v4 or Z4 20 ODP 18/12 286T 54.0/28.0 1.15 270 89.0 / 86.0%

v6 or Z6 20 TE HE 256T 54.0 1.15 290 91.7%

v7 or Z7 20 TE 18/9 284T 59.0/20.0 1.15 346 89.0 / 88.0%

Motors have no thermal overload.

Refer to page 42 for Motor Type abbreviations

.

39

5-572.7

motor data

table 40.1 - motor data for digit 14 = e - 230v/60Hz/3Ph

motor

digits size motor frame amp. service Weight efficiency

17&18 (HP)

type

size draw factor (lbs) (%)

a1 or l1 1/3

a5 or l5 1/3

B1 or m1 1/2

B5 or m5 1/2

c1 or n1 3/4

c5 or n5 3/4

d1 or P1 1

d2 or P2 1

ODP

TE

ODP

TEFC

56

48

56

56

1.6

1.2

2.2

2.2

ODP

TEFC

56

56

2.8

2.8

ODP 143T 3.1

ODP HE 143T 3.2

1.35

1.00

1.25

1.15

1.25

1.15

1.15

1.15

17

15

18

18

21

30

36

30

26 76.0 / 59.0%

42 74.0 / 60.0%

28

68

N/A

N/A

N/A

N/A

N/A

N/A

82.5%

84.0%

d3 or P3

1 ODP 18/9 143T 3.4/1.6 1.15

d4 or P4

1 ODP 18/12 145T 3.4/2.2 1.15

d5 or P5

d6 or P6

1

1

TEFC 56 3.6

TE HE 143T 3.0

1.15

1.15

N/A

85.5%

d7 or P7 1 TEFC 18/9 143T 3.4/1.6 1.00 29 76.0 / 58.0%

d8 or P8 1 TEFC 18/12 145T 3.4/2.2 1.00

e1 or Q1 1 1/2

e2 or Q2 1 1/2

ODP

ODP

145T 4.4

145T 5.6

1.15

1.00

e3 or Q3 1 1/2 ODP 18/9 145T 4.8/2.7 1.15

e4 or Q4 1 1/2 ODP 18/12 145T 4.9/2.8 1.15

e5 or Q5 1 1/2 TEFC 56 4.8

e6 or Q6 1 1/2 TE HE 145T 5.0

1.15

1.15

e7 or Q7 1 1/2 TEFC 18/9 145T 4.0/1.7 1.00

e8 or Q8 1 1/2 TEFC 18/12 145T 4.9/2.8 1.00

f1 or r1 2

f2 or r2 2

ODP

ODP

145T 5.8

145T 5.8

1.15

1.00

f3 or r3 2 ODP 18/9 145T 6.4/2.7 1.15

f4 or r4

2 ODP 18/12 182T 6.3/3.5 1.15

TE 145T 5.8

TE HE 145T 6.0

1.15

1.15

31 74.0 / 60.0%

42

35

84.0%

89.5%

29 80.0 / 65.0%

49 80.0 / 71.0%

33

62

N/A

86.5%

38 83.0 / 71.0%

38 80.0 / 72.0%

43 84.0%

89.5%

f5 or r5

2

f6 or r6 2

f8 or r8 2 TE 18/12 182T 6.4/4.2 1.15

G1 or s1 3 ODP 182T 9.4

ODP HE 182T 8.6

74

33 81.0 / 67.0%

78 81.0 / NA%

52

64

84.0%

85.5%

f7 or r7 2 TEFC 18/9 145T 6.4/2.6 1.00 41 84.0 / 70.0%

G2 or s2 3

1.15

1.15

G3 or s3 3

ODP 18/9 182T 11.6/4.4 1.15

G4 or s4 3 ODP 18/12 184T 8.5/4.6 1.15

G5 or s5 3 TE 182T 8.2

TE HE 182T 8.0

65 84.0 / 77.0%

81

74

86.5%

89.5%

66 82.0 / 72.0%

79 81.0 / 75.0%

83

G6 or s6 3

G7 or s7 3

1.15

1.15

TE 18/9 182T 10.0/3.6 1.00

G8 or s8 3

TE 18/12 184T 8.8/5.5 1.15

110

87.5%

89.5%

64 84.0 / 70.0%

84 84.0 / 82.0%

H1 or t1

5

H2 or t2 5

ODP 184T 14.0 1.15

ODP HE 184T 13.6 1.15

87

94

87.5%

89.5%

H3 or t3 5 ODP 18/9 184T 17.7/6.2 1.15 81 85.0 / 77.0%

H4 or t4 5 ODP 18/12 215T 15.5/10.2 1.15 117 86.0 / 78.0%

H5 or t5 5

H6 or t6

5

TE 184T 13.0 1.15 90

TE HE 184T 13.0 1.15 117

87.5%

90.2%

H7 or t7

5 TE 18/9 184T 16.0/5.3 1.00 85 85.0 / 85.0%

H8 or t8 5 TE 18/12 213T 14.0/8.8 1.15 107 85.0 / 80.0%

motor

digits size motor frame amp. service Weight efficiency

17&18 (HP) type

size draw factor (lbs) (%)

i1 or W1 7 1/2

ODP 213T 19.6 1.15 121

i2 or W2 7 1/2 ODP HE 213T

19.4 1.15 160

88.5%

91.7%

i3 or W3 7 1/2 ODP 18/9 213T 22.5/8.2 1.15 108 85.0 / 72.0%

i4 or W4 7 1/2 ODP 18/12 215T 19.5/12.3 1.15 167 89.0 / 85.0%

i5 or W5 7 1/2 TE 213T 20.0 1.15 126

i6 or W6 7 1/2 TE HE

213T 19.2 1.15 194

89.5%

91.7%

i7 or W7 7 1/2 TE 18/9 213T 21.0/8.8 1.15

106 87.0 / 75.0%

i8 or W8 7 1/2 TE 18/12 215T 20.0/12.4 1.15 124 86.0 / 80.0%

J1 or X1 10 ODP 215T 26.8 1.15 138

J2 or X2 10 ODP HE 215T 25.2 1.15 220

89.5%

91.7%

J3 or X3 10 ODP 18/9 215T 32.4/11.6 1.15 118 88.0 / 77.0%

J4 or X4 10 ODP 18/12 256T 24.0/13.0 1.15

196 88.0 / 80.0%

J5 or X5 10

TE 215T 26.0 1.00 138

J6 or X6 10 TE HE 215T 25.0 1.15 213

89.5%

90.2%

J7 or X7 10 TE 18/9 215T 29.0/11.5 1.15 118 87.0 / 77.0%

J8 or X8 10 TE 18/12 254T 28.0/17.5 1.15 212 88.0 / 80.0%

K1 or y1 15 ODP 254T 38.6 1.15 215

K2 or y2 15

ODP HE 254T 37.8 1.15 217

91.0%

93.0%

K3 or y3 15 ODP 18/9 256T 40.0/17.0 1.15

244 90.2 / 84.0%

K5 or y5 15 TE 254T 40.0 1.15 250

K6 or y6 15 TE HE 254T 38.0 1.15 322

91.0%

92.4%

K7 or y7 15 TE 18/9 256T 39.0/15.0 1.15 218 88.0 / 82.0%

K8 or y8 15 TE 18/12 256T 38.0/22.0 1.15

219 88.0 / 84.0%

v1 or Z1 20

ODP 256T 50.0 1.15 233

v2 or Z2 20 ODP HE 256T 49.0 1.15 250

91.0%

93.6%

v3 or Z3 20 ODP 18/9 284T 51.0/21.5 1.15 221 90.2 / 82.5%

v4 or Z4 20 ODP 18/12 286T 48.0/26.0 1.15 270 89.0 / 86.0%

v5 or Z5 20

v6 or Z6 20

TEFC

TE HE

256T

256T

51.0

48.2

1.15

1.15

287

368

91.0%

93.0%

v7 or Z7 20

TE 18/9 284T 52.0/18.0 1.15 346 89.0 / 88.0%

Motors have no thermal overload.

Refer to page 42 for Motor Type abbreviations.

40

5-572.7

motor data

table 41.1 - motor data for digit 14 = f - 460v/60Hz/3Ph

motor

digits size motor frame amp. service Weight efficiency

17&18 (HP)

type

size draw factor (lbs) (% )

a1 or l1 1/3

a3 or l3 1/3

B1 or m1 1/2

B5 or m5 1/2

c1 or n1 3/4

c5 or n5 3/4

d1 or P1 1

ODP

TE

ODP

TEFC

ODP

TEFC

ODP

56

48

56

56

56

0.8

0.6

1.1

1.1

1.4

1.35

1.00

1.25

1.15

1.25

56 1.4 1.15

143T 1.6 1.15

d2 or P2 1 ODP HE 143T 1.5 1.15

d3 or P3

1 ODP 18/9 143T 1.8/0.8 1.15

d4 or P4 1 ODP 18/12 145T 1.7/1.1 1.15

d5 or P5 1

d6 or P6

1

e1 or Q1 1 1/2

e2 or Q2 1 1/2

TEFC

ODP

ODP

e5 or Q5 1 1/2 TEFC

56

145T

145T

1.8

2.2

2.4

1.15

TE HE 143T 1.5 1.15

d7 or P7 1 TEFC 18/9 143T 1.8/0.8 1.00

d8 or P8 1 TEFC 18/12 145T 1.7/1.1 1.00

1.15

1.00

e3 or Q3 1 1/2 ODP 18/9 145T 2.3/1.0 1.15

e4 or Q4 1 1/2 ODP 18/12 145T 2.4/1.4 1.15

56 2.4 1.15

17

15

18

18

21

30

36

30

N/A

N/A

N/A

N/A

N/A

N/A

82.5%

84.0%

26 76.0 / 59.0%

39 74.0 / 60.0%

28 N/A

68 85.5%

28 73.0 / 58.0%

31 74.0 / 60.0%

42

35

84.0%

89.5%

29 80.0 / 65.0%

32 75.0 / 71.0%

33 N/A

e6 or Q6 1 1/2 TE HE 145T 2.5 1.15

e7 or Q7 1 1/2 TEFC 18/9 145T 2.0/0.9 1.00

e8 or Q8 1 1/2 TEFC 18/12 145T 2.5/1.4 1.00

f1 or r1 2

f2 or r2

f5 or r5

f6 or r6

f7 or r7 2 TEFC 18/9 145T 3.2/1.3 1.00

f8 or r8

2 TE 18/12 182T 3.1/1.9 1.15

G1 or s1 3 ODP 182T 4.5 1.15

G2 or s2 3 ODP HE 182T 4.3 1.15

G3 or s3

3 ODP 18/9 182T 4.5/1.8 1.15

G4 or s4 3 ODP 18/12 184T 4.6/2.7 1.15

G5 or s5

2

2

2

3

G6 or s6

3

G7 or s7 3

ODP

ODP

TE

TE HE

TE

TE HE

145T

145T

145T

182T 4.1 1.15

182T

2.9

2.9

3.0

4.0

1.15

145T 2.9 1.00

f3 or r3 2 ODP 18/9 145T 3.0/1.3 1.15

f4 or r4 2 ODP 18/12 182T 3.0/2.0 1.15

1.15

1.15

1.15

TE 18/9 182T 4.6/1.7 1.15

62 86.5%

39 83.0 / 71.0%

37 80.0 / 72.0%

43 84.0%

74 89.5%

33 79.0 / 62.0%

61 80.0 / 70.0%

52

64

42 84.0 / 70.0%

68 81.0 / 77.0%

81

74

110

84.0%

85.5%

86.5%

89.5%

60 80.0 / 66.0%

71 82.5 / NA%

83 87.5%

89.5%

65 84.0 / 70.0%

G8 or s8 3 TE 18/12 184T 4.3/2.6 1.15

H1 or t1

5

H2 or t2 5

ODP 184T

ODP HE 184T

7.0

6.8

1.15

1.15

73 82.5 / 75.5%

87

94

87.5%

89.5%

H3 or t3 5 ODP 18/9 184T 9.1/3.2 1.15 94 84.0 / 73.0%

H4 or t4

5 ODP 18/12 215T 7.1/4.8 1.15 117 78.0 / 71.0%

H5 or t5 5 TE 184T 6.5 1.15 90 87.5%

motor

digits size motor frame amp. service Weight efficiency

17&18 (HP) type

size draw factor (lbs) (%)

H6 or t6 5

H7 or t7 5

TE HE 184T 6.5 1.15

TE 18/9 184T 7.0/2.5 1.15

117 90.2%

H8 or t8 5

TE 18/12 213T 6.9/4.1 1.15 107 85.0 / 75.5%

9.8

83 86.0 / 83.0%

1.15 121 88.5% i1 or W1 7 1/2 ODP 213T

i2 or W2 7 1/2 ODP HE 213T

9.7 1.15 160 91.7%

i3 or W3 7 1/2 ODP 18/9 213T 11.8/4.2

1.15 125 85.0 / 72.0%

i4 or W4 7 1/2 ODP 18/12 215T 10.0/6.0 1.15 131 87.0 / 80.0%

i5 or W5 7 1/2

TE

i6 or W6 7 1/2 TE HE

213T

213T

10.0

9.6

1.15 126

1.15 194

i7 or W7 7 1/2 TE 18/9 213T 10.0/4.1 1.15

89.5%

91.7%

83 84.0 / 74.0%

i8 or W8 7 1/2 TE 18/12 215T 10.3/5.6 1.15 128 85.0 / 80.0%

J1 or X1 10

ODP 215T 13.4

J2 or X2 10 ODP HE 215T 12.6

1.15

1.15

138

220

89.5%

91.7%

J3 or X3 10 ODP 18/9 215T 15.0/5.3 1.15 116 83.0 / 71.0%

J4 or X4 10 ODP 18/12 256T 12.0/6.3

1.15 192 87.0 / 82.0%

J5 or X5 10 TE 215T 13.0 1.00 138 89.5%

J6 or X6 10 TE HE 215T 12.5 1.15 213 90.2%

J7 or X7 10

TE 18/9 215T 13.0/5.4 1.15 107 86.5 / 77.0%

J8 or X8 10 TE 18/12 254T 13.5/7.5 1.15 222 87.0 / 82.0%

K1 or y1 15

K2 or y2 15

ODP 254T 19.3

ODP HE 254T 18.9

1.15 215

1.15 217

91.0%

93.0%

K3 or y3 15 ODP 18/9 256T 19.3/7.8 1.15 203 88.5 / 81.5%

K4 or y4 15 ODP 18/12 256T 18.0/9.5 1.15 298 86.0 / 81.0%

K5 or y5 15

TE 254T 20.0

K6 or y6 15 TE HE 254T 19.0

1.15

1.15

250

322

91.0%

92.4%

K7 or y7 15 TE 18/9 256T 19.5/7.5 1.15 218 88.0 / 82.0%

K8 or y8 15 TE 18/12 256T 19.5/11.0 1.15

223 88.0 / 84.0%

v1 or Z1 20 ODP 256T 25.0 1.15 233 91.0%

v2 or Z2 20 ODP HE 256T 24.5 1.15 250 93.6%

v3 or Z3 20 ODP 18/9 256T 25.2/10.0 1.15

208 89.5 / 82.5%

v4 or Z4 20 ODP 18/12 286T 24.0/13.0 1.15 270 90.0 / 84.0%

v5 or Z5 20

v6 or Z6 20

TEFC 256T 25.5

TE HE 256T 24.1

1.15 287

1.15 368

91.0%

93.0%

v7 or Z7 20 TE 18/9 284T 26.0/8.7 1.15 331 89.0 / 88.0%

v8 or Z8 20 TE 18/12 284T 24.7/14.0 1.15 361 90.0 / 86.0%

Motors have no thermal overload.

Refer to page 42 for Motor Type abbreviations.

5-572.7

41

motor data

table 42.1 - motor data for digit 14 = G - 575v/60Hz/3Ph

digits

17&18

G6 or s6

H1 or t1

H5 or t5

H6 or t6

i1 or W1

i5 or W5

i6 or W6

J1 or X1

J5 or X5

J6 or X6

K1 or y1

K5 or y5

K6 or y6

v1 or Z1

v5 or Z5

v6 or Z6

a5 or l5

B1 or m1

B5 or m5

c1 or n1

c5 or n5

d1 or P1

d5 or P5

d6 or P6

e1 or Q1

e5 or Q5

e6 or Q6

f1 or r1

f5 or r5

f6 or r6

G1 or s1

G5 or s5

motor size (HP)

15

20

20

20

10

10

15

15

3

5

5

5

7 1/2

7 1/2

7 1/2

10

1 1/2

1 1/2

1/12

2

2

2

3

3

1/3

1/2

1/2

3/4

3/4

1

1

1

Motors have no thermal overload

Motor Type Abbreviations

ODP

ODP HE

Open Drip Proof

Open Drip Proof, High Efficiency

ODP 18/9

ODP 18/12

TE

TEFC

Open Drip Proof, 2-speed 1800/900 RPM

Open Drip Proof, 2-speed 1800/1200 RPM

Totally Enclosed

Totally Enclosed, Fan Cooled

TE HE

TE 18/9

TE 18/12

TENV

Totally Enclosed, High Efficiency

Totally Enclosed, 2-speed 1800/900 RPM

Totally Enclosed, 2-speed 1800/1200 RPM

Totally Enclosed, Non-Ventilating

motor

type

TE HE

ODP

TEFC

TE HE

ODP

TEFC

TE HE

ODP

TE

TE HE

ODP

TE

TE HE

ODP

TEFC

TE HE

TEFC

ODP

TEFC

ODP

TEFC

ODP

TEFC

TE HE

ODP

TEFC

TE HE

ODP

TEFC

TE HE

ODP

TEFC

frame size

215T

215T

254T

254T

254T

256T

256T

256T

182T

184T

184T

184T

213T

213T

213T

215T

145T

145T

145T

145T

145T

145T

182T

182T

56

56

56

56

56

143T

56

143T

amp. draw

10.4

9.6

15.4

16.0

15.2

20.8

20.4

19.5

3.2

5.2

5.2

5.2

7.8

8.0

7.6

10.3

1.8

2.0

1.7

2.3

2.3

2.4

3.4

3.4

0.6

0.9

0.9

0.9

1.1

1.1

1.5

1.2

service factor

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.15

1.25

1.15

1.25

1.15

1.15

1.15

1.15

efficiency

(%)

89.5%

90.2%

91.0%

91.0%

92.4%

91.0%

91.0%

93.0%

89.5%

87.5%

87.5%

89.5%

88.5%

89.0%

90.2%

89.5%

84.0%

84.0%

85.5%

84.0%

84.0%

86.5%

86.5%

87.5%

N/A

N/A

N/A

N/A

N/A

82.5%

77.0%

85.5%

Weight

(lbs)

154

200

184

250

326

255

287

368

100

91

89

117

113

142

192

123

65

66

72

98

48

72

66

50

33

41

28

68

16

25

24

28

42

5-572.7

dimensions - unit

figure 43.1 - HBG/HBP outdoor Blower Package unit dimensions

Y

33.50

B

C

33.50

B

C

48.00

D

(Max.)

2.00

Qty (4) Drill Locator

Dimples for Field

Drilled Electrical

Conduit Entry Holes

(spaced 2.0" apart)

34.25

2.32

Optional Rainhood

& Birdscreen

9.50

1.45

E (Height)

X

F (Width)

(Inside)

9.00

R

1.72

3.00

1.45

10.26

A

24.00

(Inside)

9.21

Fresh Air

Duct Connection

1

2

4.29

16.73

24.94

2.03

24.00

4.35

(Inside)

Return Air Duct Connection

1

2

S

500 - 800 model shown figure 43.2 - HdG/HdP outdoor downturn Package unit dimensions

Downturn

Duct

Connection

4.27

Q

4.16

2.56

3

1.50

5.29

6.28

P/2

P Over Roof

1 k Inside

24.00

(Inside)

N

4

9.21

2

6.28

1.50

3.00

5.29

29.32

D

(Max.)

24.53

33.50

B

C

R

1.72

3.00

1.45

10.26

Z

33.50

B

C

9.50

1.45

24.00

(Inside)

1

2

4.29

16.73

24.94

1

2

T

500 - 800 model shown

48.00

2.00

Qty (4) Drill Locator

Dimples for Field

Drilled Electrical

Conduit Entry Holes

(spaced 2.0" apart)

34.00

2.32

24.00

(Inside)

Optional Rainhood

& Birdscreen

Q

4.16

A

2.56

P/2

P Over Roof k Inside

9.21

Fresh Air

Duct Connection

2.03

24.00

(Inside) 4.35

Return Air Duct Connection

3

1.50

5.29

6.28

1

4

24.00

(Inside)

9.21

N

2

6.28

1.50

5.29

3.00

table 43.1 - HBG/HBP/HdG/HdP outdoor unit dimensions (all dimensions in inches)

model Blower type Qty. of

size (digit 16) furnaces a

B c d

e

75

100/125

All

All

150/175

200/225

All

All

250/300 E, F, G, or H

350/400 E, F, G, or H

500/600

G or H

700/800

G or H

1

1

1

1

1

1

2

2

f K dimensions n P

Q r

s t y Z

Gas conn.

33.75 19.22 8.62 14.07 18.98 15.18 20.02 39.23 32.06 10.75 7.00 84.41 108.39 81.49 110.82 1/2

33.75 19.22 8.62 14.07 18.98 17.69 20.02 39.23 34.56 10.75 7.00 84.41 108.39 81.49 110.82 1/2

33.75 19.22 8.62 14.07 18.98 21.94 23.99 39.23 38.82 10.75 7.00 84.41 108.39 81.49 110.82 1/2

37.75 19.22 8.62 14.07 22.98 24.06 23.99 43.23 40.94 11.58 9.90 84.41 108.39 81.49 110.82 1/2

37.75 21.31 10.62 15.05 22.98 27.09 29.96 43.23 44.05 11.58 9.90 84.41 108.39 81.49 110.82 3/4

37.75 24.64 12.62 18.25 22.98 38.60 41.90 43.23 55.57 11.58 9.90 84.41 108.39 81.49 110.82 3/4

37.75 21.31 10.62 15.05 22.98 27.09 29.96 43.23 44.05 11.58 9.90 117.53 146.77 114.94 144.12 3/4

37.75 24.64 12.62 18.25 22.98 38.60 41.90 43.23 55.57 11.58 9.90 117.53 146.77 114.94 144.12 3/4

For Right Hand Access Units - Location of drill locator dimples for field drilled gas connection entry holes - one side of unit and one on bottom.

For Left Hand Access Units - Location of drill locator dimples for field drilled gas connection entry holes - one side of unit and one on bottom.

For Right Hand Access Units - Location of drill locator dimples for field drilled electrical connection, entry holes identical as side electrical connections.

For Left Hand Access Units - Location of drill locator dimples for field drilled electrical connection, entry holes identical as side electrical connections.

For Gravity Vented Models, the combustion air/vent cap is required so only dimensions B, C and D apply. For Power Vented Models, the power exhauster discharge cover and inlet louvers are included so only dimensions Q and R apply.

5-572.7

43

dimensions - unit

figure 44.1 - HBG/HBP outdoor Blower Package unit dimensions with Blower type i, J, K, or l

E

B

C

Y

47.27

36.58

P/2

P Over Roof

41.62

D

(Max.)

2.00

6.56

29.74

Qty (4) Drill Locator

Dimples for Field

Conduit Entry Holes

(spaced 2.0" apart)

34.00

2.32

Optional Rainhood

& Birdscreen

22.98 (Height)

X

9.00

R

1.72

3.00

1.45

10.26

9.50

1.45

34.00

37.85

24.00

(Inside)

Q

4.16

2.56

k Inside

9.21

1

1

2

1

4.29

16.73

24.94

2.03

S

2

500 - 800 model shown

Return Air

Duct Connection

24.00

(Inside)

4.35

3

1.50

5.29

6.28

2

figure 44.2 - HdG/HdP outdoor downturn Package unit dimensions with Blower type i, J, K, or l

4

24.00

(Inside)

43.23

9.21

3.00

1.50

5.29

6.28

Duct

Connection

4.27

29.32

24.53

1

Z

E

B

C

47.27

2.00

6.56

29.74

Qty (4) Drill Locator

Dimples for Field

Drilled Electrical

(spaced 2.0" apart)

34.00

9.50

1.45

R

1.72

3.00

1.45

10.26

2

1

4.29

16.73

24.94

2

T

500 - 800 model shown

2.03

36.58

34.00

Return Air

Duct Connection

24.00

(Inside)

37.85

2.32

9.21

4.35

Optional Rainhood

& Birdscreen

Fresh Air

Duct Connection

Q

4.16

2.56

3

1.50

5.29

6.28

1

P/2

P Over Roof

41.62

➅ k Inside

2

4

9.21

3.00

1.50

5.29

6.28

43.23

table 44.1 - HBG/HPG/HdG/HdP outdoor unit dimensions with Blower i, J, K, or l (all dimensions in inches)

model Blower type Qty. of

size

(digit 16) furnaces B c d

250/300

I, J, or k

350/400

I, J, or k

500/600 I, J, k, or L

700/800 I, J, k, or L

840/960 I, J, k, or L

1

1

2

2

3

e f K dimensions

P

Q r

s t y Z

21.31 10.62 15.05 33.50 27.09 29.96 44.05 11.58 9.90 120.00 141.34 117.34 141.34

24.64 12.62 18.25 33.50 38.60 41.90 55.57 11.58 9.90 120.00 141.34 117.34 141.34

21.31 10.62 15.05 67.00 27.09 29.96 44.05 11.58 9.90 153.12 182.36 150.74 180.00

24.64 12.62 18.25 67.00 38.60 41.90 55.57 11.58 9.90 153.12 182.36 150.74 180.00

24.64 12.62 18.25 100.50 38.60 41.90 55.57 11.58 9.90 186.52 215.77 184.14 213.40

Gas conn.

3/4

3/4

3/4

3/4

3/4

For Right Hand Access Units - Location of drill locator dimples for field drilled gas connection entry holes - one side of unit and one on bottom.

For Left Hand Access Units - Location of drill locator dimples for field drilled gas connection entry holes - one side of unit and one on bottom.

For Right Hand Access Units - Location of drill locator dimples for field drilled electrical connection, entry holes identical as side electrical connections.

For Left Hand Access Units - Location of drill locator dimples for field drilled electrical connection, entry holes identical as side electrical connections.

For Gravity Vented Models, the combustion air/vent cap is required so only dimensions B, C and D apply. For Power Vented Models, the power exhauster discharge cover and inlet louvers are included so only dimensions Q and R apply.

Applies to units with Digit 16 = L only.

44

5-572.7

dimensions - unit

figure 45.1 - HcG/HcP outdoor cooling Package unit dimensions

Outlet Air

Duct

Connection

J (Height)

X

H (Width)

(Inside)

7.65

G

24.00

D (Max.)

19.23

1.45

33.50

B

C

105.49

48.00

2.00

Qty (4) Drill Locator

Dimples for Field

Drilled Electrical

Conduit Entry Holes

(spaced 2.0" apart)

34.25

9.50

1.45

R

3.00

1.72

10.26

2.03

A

4.29

16.75

24.94

108.39

24.00

(Inside)

Return Air

Duct Connection

4.35

2.20

24.00

(Inside)

9.21

Optional Rainhood

& Birdscreen

Fresh Air

Duct Connection

Q

4.16

2.56

5.29

1.50

6.28

P/2

P Over Roof k Inside

24.00

(Inside)

9.21

6.28

1.50

3.00

5.29

N

figure 45.2 - HPG/HPP outdoor Packaged unit dimensions

Downturn

Duct

Connection

4.27

29.32

24.53

24.00

134.82

C

D (Max.)

G

19.23

1.45

9.50

1.45

R

3.00

1.72

10.26

2.03

4.29

16.75

24.94

137.63

48.00

2.00

Qty (4) Drill Locator

Dimples for Field

Drilled Electrical

Conduit Entry Holes

(spaced 2.0" apart)

34.25

2.20

Return Air

Duct Connection

Optional Rainhood

& Birdscreen

Q

4.16

2.56

A

24.00

(Inside)

9.21

Fresh Air

Duct Connection

4.35

5.29

1.50

6.28

P/2

P Over Roof k Inside

24.00

(Inside)

9.21

N

6.28

1.50

3.00

5.29

table 45.1 - HcG/HcP/HPG/HPP outdoor unit dimensions (all dimensions in inches)

model Blower type

size (digit 16) a

B c d

G dimensions

H J K n P

Gas

Q r conn.

75

100/125

All

All

33.75 19.22 8.62 14.07 28.75 18.00 25.00 20.02 39.23 32.06 10.75 7.00 1/2

33.75 19.22 8.62 14.07 28.75 21.00 25.00 20.02 39.23 34.56 10.75 7.00 1/2

150/175

200/225

All

All

33.75 19.22 8.62 14.07 28.75 24.00 25.00 23.99 39.23 38.82 10.75 7.00

37.75 19.22 8.62 14.07 32.75 27.00 28.00 23.99 43.23 40.94 11.58 9.90

1/2

1/2

250/300 E, F, G, or H 37.75 21.31 10.62 15.05 32.75 30.00 28.00 29.96 43.23 44.05 11.58 9.90

3/4

350/400 E, F, G, or H 37.75 24.64 12.62 18.25 32.75 42.00 28.00 41.90 43.23 55.57 11.58 9.90 3/4

For Right Hand Access Units - Location of drill locator dimples for field drilled gas connection entry holes - one side of unit and one on bottom.

For Left Hand Access Units - Location of drill locator dimples for field drilled gas connection entry holes - one side of unit and one on bottom.

For Right Hand Access Units - Location of drill locator dimples for field drilled electrical connection, entry holes identical as side electrical connections.

For Left Hand Access Units - Location of drill locator dimples for field drilled electrical connection, entry holes identical as side electrical connections.

For Gravity Vented Models, the combustion air/vent cap is required so only dimensions B, C and D apply. For Power Vented Models, the power exhauster discharge cover and inlet louvers are included so only dimensions Q and R apply.

5-572.7

45

dimensions - unit

figure 46.1 - HcG/HcP outdoor cooling Package unit dimensions with Blower type i, J, or K

24.00

33.50

B

C

D (Max.)

Outlet Air

Duct

Connection

19.23

28.00 (Height)

X

H (Width)

(Inside)

32.68

1.45

7.65

9.50

R

3.00

1.72

10.26

1.45

2.00

141.34

47.27

Qty (4) Drill Locator

Dimples for Field

Drilled Electrical

Conduit Entry Holes

(spaced 2.0" apart)

34.00

4.29

16.73

24.94

36.58

2.03

Return Air

Duct Connection

143.98

24.00

(Inside)

34.00

2.32

37.85

24.00

(Inside)

Optional Rainhood

& Birdscreen

Q

4.16

2.56

9.21

4.35

Fresh Air

Duct Connection

1.50

5.29

6.28

P/2

P Over Roof k Inside

24.00

(Inside)

9.21

N

6.28

1.50

3.00

5.29

figure 46.2 - HPG/HPP outdoor Packaged unit dimensions with Blower type i, J or K

Downturn

Duct

Connection

4.27

29.32

24.53

24.00

(Inside)

24.00

33.50

B

C

170.66

D (Max.)

19.23

32.68

1.45

9.50

R

3.00

1.72

10.26

1.45

2.00

4.29

16.73

24.94

173.22

47.27

Qty (4) Drill Locator

Dimples for Field

Drilled Electrical

Conduit Entry Holes

(spaced 2.0" apart)

34.00

2.03

Return Air

Duct Connection

36.58

34.00

2.32

37.85

24.00

(Inside)

Optional Rainhood

& Birdscreen

Q

4.16

24.00

(Inside)

9.21

Fresh Air

Duct Connection

4.35

1.50

5.29

2.56

6.28

P/2

P Over Roof k Inside 24.00

(Inside)

N

9.21

6.28

1.50

3.00

5.29

table 46.1 - HcG/HcP/HPG/HPP outdoor unit dimensions (all dimensions in inches)

model Blower type

size (digit 16)

B c d

f dimensions

H K n

Gas

P

Q r conn.

250/300

I, J, or k 21.31 10.62 15.05 27.09 30.00 29.96 43.23 44.05 11.58 9.90 3/4

350/400

I, J, or k 24.64 12.62 18.25 38.60 42.00 41.90 43.23 55.57 11.58 9.90 3/4

For Right Hand Access Units - Location of drill locator dimples for field drilled gas connection entry holes - one side of unit and one on bottom.

For Left Hand Access Units - Location of drill locator dimples for field drilled gas connection entry holes - one side of unit and one on bottom.

For Right Hand Access Units - Location of drill locator dimples for field drilled electrical connection, entry holes identical as side electrical connections.

For Left Hand Access Units - Location of drill locator dimples for field drilled electrical connection, entry holes identical as side electrical connections.

For Gravity Vented Models, the combustion air/vent cap is required so only dimensions B, C and D apply. For Power Vented Models, the power exhauster discharge cover and inlet louvers are included so only dimensions Q and R apply.

46

5-572.7

dimensions - unit Base

figure 47.1 - unit Base dimensions

A

C

To end of Unit

F

G

M M

B

J

E

Inside

M

6.28

6.28

Drill Locator Dimple for Field Drilled Gas

Connection Entry Hole

Left Hand Access Units

Drill Locator Dimple for Field Drilled Gas

Connection Entry

Hole Right Hand

Access Units

E

Inside

M

4.29

24.00

Inside

Supply Air Opening Return Air Opening

24.00

Inside

H

4.35

table 47.1 - HBG/HBP & HdG/HdP outdoor unit Base rail dimensions (all dimensions in inches)

model size

75

100/125

150/175

200/225

250/300

250/300

350/400

350/400

500/600

500/600

700/800

700/800

840/960

Blower type

(digit 16)

HBG/HBP a c

HdG/HdP a c

dimensions

B

All

All

All

All

84.41 81.49 113.63 110.82 34.85

84.41 81.49 113.63 110.82 37.36

84.41 81.49 113.63 110.82 41.61

84.41 81.49 113.63 110.82 43.71

E,F,G, or H 84.41 81.49 113.63 110.82 46.75

I, J, or k 120.00 117.34 149.22 146.66 46.75

E,F,G, or H 84.41 81.49 113.63 110.82 58.27

I, J, or k 120.00 117.34 149.22 146.66 58.27

G or H 117.53 114.94 146.77 144.12 46.75

I, J, k, or L 153.12 150.74 182.36 180.00 46.75

G or H 117.53 114.94 146.77 144.12 58.27

I, J, k, or L 153.12 150.74 182.36 180.00 58.27

I, J, k, or L 186.52 184.14 215.77 213.40 58.27

e

HBG/HBP/HdG/HdP

f G

19.52

19.52

23.49

23.49

78.66 53.72

78.66 53.72

78.66 53.72

78.66 53.72

29.46 78.66 53.72

29.46 114.23 84.29

41.40 78.66 53.72

41.40 114.23 82.29

29.46 78.66 53.72

29.46 114.23 82.29

41.40 78.66 53.72

41.40 114.23 82.29

41.40 114.23 82.29

H

1.53

1.53

1.53

1.53

1.53

1.28

1.53

1.28

1.53

1.28

1.53

1.28

1.28

J

32.00

34.50

38.75

40.85

43.89

43.89

55.41

55.41

43.89

43.89

55.41

55.41

55.41

table 47.2 - HcG/HcP & HPG/HPP outdoor unit Base rail dimensions (all dimensions in inches)

model size

75

100/125

150/175

200/225

250/300

250/300

350/400

350/400

Blower type

(digit 16)

HcG/HcP a c

HPG/HPP a c

dimensions

B e

HcG/HcP/HPG/HPP f G

All

All

All

All

108.39 105.49 137.63 134.82 34.85 19.52 78.66 53.72

108.39 105.49 137.63 134.82 37.36 19.52 78.66 53.72

108.39 105.49 137.63 134.82 41.61 23.49 78.66 53.72

108.39 105.49 137.63 134.82 43.71 23.49 78.66 53.72

E,F,G, or H 108.39 105.49 137.63 134.82 46.75 29.46 78.66 53.72

I, J, or k 143.98 141.34 173.22 170.66 46.75 29.46 114.23 82.29

E,F,G, or H 108.39 105.49 137.63 134.82 58.27 41.40 78.66 53.72

I, J, or k 143.98 141.34 173.22 170.66 58.27 41.40 114.23 82.29

H

1.53

1.53

1.53

1.53

1.53

1.28

1.53

1.28

Gas connection for 1st furnace. For Models 500-800 add 33.5” for second furnace gas connection.

For Model 840-960 add 33.50” and 67.00” for second and third furnace gas connections.

J m

32.00 6.23

34.50 7.49

38.75 7.63

40.85 8.69

43.89 7.21

43.89 7.21

55.41 7.00

55.41 7.00

m

6.23

7.49

7.63

8.69

7.21

7.21

7.00

7.00

7.21

7.21

7.00

7.00

7.00

5-572.7

47

dimensions - roof curBs

figure 48.1 - roof curb dimensions

Discharge Air Opening is for HDG/HDP/HPG/HPP models only

1.75

TYP

1.68

24.00 INSIDE

OPENING

1.00

TYP

H

AIR OPENI

D

5.53

2.97

TY

P

GAS LINE CONN.

(RH ASSY ONLY)

ELECT. BOTT

PAN CONN.

H

G

3 SP

2.00 = 6.

B INSIDE

A

OUT

SID

E

C

44.16

5.53

24.9

4

J

GAS LINE CONN.

(LH ASSY ONLY)

24.00 INSIDE

OPENING

E

F

INSID

OUTSIDE

E

1.79

model size

75

100/125

150/175

200/225

250/300

250/300

350/400

350/400

500/600

500/600

700/800

700/800

840/960

table 48.1 - HBG/HBP & HdG/HdP roof curb dimensions (all dimensions in inches)

(digit 16)

Blower type a

HBG/HBP

B c d

dimensions a

HdG/HdP

B c d e

HBG/HBP/HdG/HdP f G H

J

All

All

All

All

88.77 76.77

88.77 76.77

88.77 76.77

88.77 76.77

E,F,G, or H 88.77 76.77

I, J, or k 124.61 112.61

E,F,G, or H 88.77 76.77

I, J, or k 124.61 112.61

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

117.98 105.98

117.98 105.98

117.98 105.98

117.98 105.98

117.98 105.98

117.98 105.98

-

-

-

-

-

-

-

-

-

-

-

153.83 141.63 105.98 35.85

-

153.83 141.63 105.98 35.85

39.33

41.84

46.18

48.22

51.25

51.25

62.76

62.76

27.33

29.84

34.18

36.22

39.25

39.25

50.76

50.76

3.97 19.52 74.84

5.22 19.52 74.84

5.41 23.49 74.84

6.43 23.49 74.84

4.96 29.46 74.84

4.96 29.46 110.41

4.74 41.40 74.84

4.74 41.40 110.41

G or H 121.89 109.89 - - 151.10 139.10 105.98 33.12 51.25 39.25 4.96 29.46 74.84

I, J, k, or L 157.74 145.74 105.98 39.76 186.98 174.98 105.98 69.00 51.25 39.25 4.96 29.46 110.41

G or H 121.89 109.89 - - 151.10 139.10 105.98 33.12 62.76 50.76 4.74 41.40 74.84

I, J, k, or L 157.74 145.74 105.98 39.76 186.98 174.98 105.98 69.00 62.76 50.76 4.74 41.40 110.41

I, J, k, or L 191.14 179.14 105.98 73.16 220.39 208.39 105.98 102.41 62.76 50.76 4.74 41.40 110.41

table 48.2 - HcG/HcP & HPG/HPP roof curb dimensions (all dimensions in inches)

model size

75

100/125

150/175

200/225

250/300

250/300

350/400

350/400

(digit 16)

Blower type a

HcG/HcP

B c d

dimensions a

HPG/HPP

B c d e

HcG/HcP/HPG/HPP f G H J

All

All

All

All

112.74 100.74

112.74 100.74

112.74 100.74

112.74 100.74

-

-

-

-

-

-

-

-

141.98 129.98 100.74 29.24 39.33 27.33 3.97 19.52 74.84

141.98 129.98 100.74 29.24 41.84 29.84 5.22 19.52 74.84

141.98 129.98 100.74 29.24 46.18 34.18 5.41 23.49 74.84

141.98 129.98 100.74 29.24 48.22 36.22 6.43 23.49 74.84

E,F,G, or H 112.74 100.74 - - 141.98 129.98 100.74 29.24 51.25 39.25 4.96 29.46 74.84

I, J, or k 148.59 136.59 105.98 30.61 177.83 165.83 105.98 59.85 51.25 39.25 4.96 29.46 110.41

E,F,G, or H 112.74 100.74 - - 141.98 129.98 100.74 29.24 62.76 50.76 4.74 41.40 74.84

I, J, or k 148.59 136.59 105.98 30.61 177.83 165.83 105.98 59.85 62.76 50.76 4.74 41.40 110.41

Gas connection for 1st furnace. For Models 500-800 add 33.5” for second furnace gas connection.

For Model 840-960 add 33.50” and 67.00” for second and third furnace gas connections.

48

5-572.7

dimensions - coolinG coils

figure 49.1 - dX coil drawing

(All dimensions in inches)

Airflow Direction

rows 2 3 4 6

W 7.5 6 7.5 10

TOP VIEW

L

1.5

1.5

W

Coil for Right Hand Units

(Digit 9 = R)

Headers on opposite side for Left Hand Units

H

S

FRONT VIEW

1.5

FL

FH

Distributor Inlet (Liquid

Line) Connection(s)

(Second Inlet on Dual

Circuit Coils)

SIDE VIEW

Airflow

Direction

Suction Line Connections in direction of airflow

(Second Inlet on Dual Circuit Coils)

I

table 49.1 - dX coil dimensions

model cooling

size mBH

75

100/125

All

All

dX - single circuit dX - dual circuit fH

H s fl i l

suction liquid

line (Qty) line (Qty) fl i l

suction liquid

line (Qty) line (Qty)

27.5 30.5 1.5 18 25 21 (1) 1.625 (1) 1.375 16.25 26.5 19.25 (2) 1.625 (2) 0.875

27.5 30.5 1.5 21 28 24 (1) 1.625 (1) 1.375 19.5 29.75 22.5 (2) 1.625 (2) 0.875

150/175

200/225

250/300

350/400

All

Below 185

MBH

185 MBH

& Up

Below 185

MBH

185 MBH

& Up

Below 185

MBH

185 MBH

& Up

27.5 30.5 1.5 24 31 27 (1) 1.625 (1) 1.375 23 33.25 26.0 (2) 1.625 (2) 0.875

32.5 34.5 0.5 27 34 30 (1) 1.625 (1) 1.375

32.5 34.5 0.5 27 34.5 30 (1) 2.125 (1) 1.375

32.5 34.5 0.5 30 37 33 (1) 1.625 (1) 1.375

32.5 34.5 0.5 30 37.5 33 (1) 2.125 (1) 1.375

32.5 34.5 0.5 42 49 45 (1) 1.625 (1) 1.375

32.5 34.5 0.5 42 49.5 45 (1) 2.125 (1) 1.375

25.5 35.75 28.5 (2) 1.625 (2) 0.875

28.5 38.75 31.5 (2) 1.625 (2) 0.875

40.25 50.5 43.25 (2) 1.625 (2) 0.875

figure 49.2 - chilled Water coil drawing

(All dimensions in inches)

Airflow Direction

rows 4 6

W 7.5 10

TOP VIEW

1.5

L

1.5

1.8

W

Coil for Right Hand Units (Digit

9 = R)

Headers on opposite side for

Left Hand Units

H

S

FRONT VIEW

FL

FH

2.25

Return Water Line

Connection turned 90˚ in direction of airflow

Airflow

Direction

SIDE VIEW

V 2.25

Supply Water Line

Connection turned 90˚ in direction of airflow

I

1.8

table 49.2 - chilled Water coil dimensions

model size fH

75

100/125

150/175

200/225

250/300

350/400

27

27

27

33

33

33

H

30

30

30

34.5

34.5

34.5

s

1.5

1.5

1.5

0.5

0.5

0.5

v

1.5

1.5

1.5

1

1

1

fl i l

16.25 25.50 19.25 1.50 MPT

19.50 28.75 22.50 1.50 MPT

23.00 32.25 26.00 1.50 MPT

25.50 34.75 28.50 1.50 MPT

28.50 37.75 31.50 1.50 MPT

40.25 49.50 43.25 1.50 MPT

5-572.7

supply line return line

1.50 MPT

1.50 MPT

1.50 MPT

1.50 MPT

1.50 MPT

1.50 MPT

49

dimensions - rainHood, remote Panel & evaPorative cooler

figure 50.1 - rainhood and Birdscreen dimensions

1.09

31.19

.75

42.66 Approx.

44.56

1.14

32.71

A

1.14

table 50.1 - rainhood and Birdscreen dimensions (all dimensions in inches)

rainhood & Birdscreen model size a

75

100/125

29.43

31.94

150/175

200/225

250/300

350/400

38.24

38.24

41.34

52.85

500/600

700/800

840/960

41.34

52.85

52.85

figure 50.3 - remote Panel dimensions figure 50.2 - evaporative cooling module

Top View

J-Box

1.25

Pump

C

1.50

W/2 -1.50

3.00

W

Optional 1"

Pre-Filter

Rack

5.57

1.50

4.50

1.25

Side View

Blower

Section

36.00

3.53

A 3.53

notes:

1. Holes visable on right side are also on left side in the same location.

2. Holes on top are also on the back in the same location horizontally,

1" down vertically.

B

2.56

3.38

2.13

25.50

6" or 12"

Media

1/2" NPT Water Inlet

4.50

3.00

.25

Leveling Legs

H

table 50.3 - remote Panel dimensions

(all dimensions in inches)

remote Panel type

Light and Switch Panels Only

Light and Switch Panels with Single Stage

Thermostat or Electronic Set Point Adjustor

Light and Switch Panels with

Two Stage Thermostat

a

7.06

B

-

c

2.81

10.60 3.53 4.58

13.09 6.03 5.82

table 50.2 - evaporative cooler dimensional, Performance, and Weight data (all dimensions in inches)

model size

75

100/125

150/175

200/225

250/300

250/300

350/400

350/400

500/600

500/600

700/800

700/800

840/960

Blower type

(digit 16)

All

All

All

All

E,F,G, or H

I, J, or k

E,F,G, or H

I, J, or k

G or H

I, J, k or L

G or H

I, J, k or L

I, J, k or L

H

34 30

34 30

34 36

38 36

38 39

56 39

38 51

47 51

38 39

56 39

38 51

47 51

47 51

maximum media face

W cooling cfm area (ft2) at max cfm

6" media

face velocity (digit 23 = 3, 5, a, or c) (digit 23 = 4, 6, B, or d)

(ft/min) dry

Weight operating

Weight

12" media

dry

Weight operating

Weight

2778

4000

5200

6000

6500

10400

8500

11050

6500

10400

8500

11050

11050

4.0

5.0

6.5

7.5

8.1

13.0

10.6

13.8

8.1

13.0

10.6

13.8

13.8

695

800

800

800

800

800

800

800

800

800

800

800

800

149

154

159

164

171

200

211

225

171

200

211

225

225

273

280

313

318

338

371

433

450

338

371

433

450

450

154

159

169

174

182

214

228

244

182

214

228

244

244

363

404

473

496

285

295

336

341

363

404

473

496

496

All weights in pounds.

50

5-572.7

WeiGHts

table 51.1 - HBG/HBP Blower Package unit operating Weights

model Blower type

size

HBG HBP

(digit 16) unit vent cap unit motor

75

100/125

All

All

429

464

16

16

439

474

150/175

200/225

All

All

501

573

250/300 E,F,G, or H 611

250/300 I, J, or k 860

16

16

26

26

511

588

626

875

350/400 E,F,G, or H 723

350/400 I, J, or k 922

35

35

500/600 G or H 929 52

500/600 I, J, k, or L 1178 52

700/800 G or H 1123 70

700/800 I, J, k, or L 1322 70

840/960 I, J, k, or L 1722 105

738

1019

959

1208

1153

1352

1767

12

17

8

15

12

17

17

filters dampers dampers double Wall fresh air f & ra (all sections) rainhood

6

6

26

26

46

46

38

38

65

67

6

6

8

15

29

29

33

33

52

52

60

60

43

46

46

93

70

72

83

83

38

38

33

33

38

38

38

70

70

60

60

70

70

70

53

96

46

93

53

96

96

90

90

83

83

90

90

90

evap

table 51.2 - HcG/HcP cooling Package unit operating Weights

model Blower type HcG HcP

size (digit 16) unit vent cap unit

75

100/125

All

All

536

574

150/175

200/225

All

All

616

699

250/300 E,F,G, or H 741

16

16

16

16

26

250/300

I, J, or k 990

350/400 E,F,G, or H 872

26

35

350/400

I, J, or k 1071 35

546

584

626

714

756

1005

887

1168

motor filters dampers dampers double Wall fresh air f & ra (all sections) rainhood

8

15

12

17

6

6

6

6

26

26

29

29

33

33

38

38

46

46

52

52

60

60

70

70

72

72

77

85

87

134

101

144

83

83

90

90

65

67

70

72

table 51.3 - HdG/HdP outdoor w/ downturn Package operating Weights

model Blower type

size

HdG

(digit 16) unit vent cap

HdP unit

75 All 530 16 540

motor fresh air f & ra (all sections)

6 26 46 73

rainhood

65

100/125

150/175

All

All

568

611

200/225 All 692

250/300 E,F,G, or H 732

250/300 I, J, or k 981

350/400 E,F,G, or H 861

26

35

350/400 I, J, or k 1060 35

500/600 G or H 1050 52

16

16

16

26

500/600 I, J, k, or L 1299 52

700/800 G or H 1261 70

700/800 I, J, k, or L 1460 70

840/960 I, J, k, or L 1860 105

578

621

707

747

996

876

1057

1080

1329

1291

1490

1905

15

12

17

8

6

6

6

8

15

12

17

17

33

38

38

33

26

29

29

33

33

38

38

38

60

70

70

60

46

52

52

60

60

70

70

70

135

102

145

88

73

78

86

88

135

102

145

145

83

90

90

83

67

70

72

83

83

90

90

90

table 51.4 - HPG/HPP outdoor Packaged operating Weights

model Blower type

size

HPG

(digit 16) unit vent cap

HPP unit motor filters dampers dampers double Wall fresh air f & ra (all sections)

75

100/125

All

All

637

678

16

16

150/175

200/225

All

All

726

818

250/300 E,F,G, or H 862

16

16

26

250/300

I, J, or k 1111 26

350/400 E,F,G, or H 1010

35

350/400

I, J, or k 1209 35

647

688

736

833

877

1126

1025

1306

6

6

6

6

8

15

12

17

26

26

29

29

33

33

38

38

46

46

52

52

60

60

70

70

107

107

112

125

129

176

150

193

All weights in pounds.

rainhood

83

83

90

90

65

67

70

72

evap evap

5-572.7

51

maintenance

All heating equipment should be serviced before each heating season to assure proper operations. The following items may be required to have more frequent service schedule based on the environment in which the unit is installed, and the frequency of the equipment operation.

Blower assembly

The blower assembly includes the bearings, drive sheaves and belts.

Blower bearings should be checked and lubricated based on the blower manufacturer’s recommendations. Bearings should also be checked for any unusual wear and replaced if needed.

Drive sheaves should be checked at the same time the bearings are inspected. Check to make sure the sheaves are in alignment and are securely fastened to the blower and motor shafts.

Belt tension should be rechecked shortly after the unit has been installed to check for belt stretching. After the initial startup, monthly checks are recommended.

filters

If the unit is supplied with a dirty filter switch and light, clean or replace the filters any time the dirty filter light comes on.

Units which do not have a dirty filter warning light should have the filters checked monthly. Clean or replace if necessary. In dirty atmospheres, filter maintenance may be required more often.

figure 52.1 - filter replacement arrangement for Blower size (digit 16) a, B, c, d, e, f, G and H

FILTER SPACER

B

B

C

75

C

B

B

B

B

B

100/125

B

A

150/175

FILTER SPACER

A

duct furnace

When providing annual maintenance for the duct furnace, keep the unit free from dust, dirt, grease and foreign matter. Pay particular attention to:

1. For HBG/HCG/HDG/HPG units, the combustion air intake and exhaust vent cap louvered openings. For HBP/HCP/

HDP/HPP units, the power exhauster discharge opening and the combustion air inlet louvers.

2. The burner ports and pilot burner orifices (avoid the use of hard, sharp instruments capable of damaging surfaces for cleaning these ports). To check the burner port and pilot burner orifice, see Burner and Pilot Assembly Removal.

3. The air shutters and main burner orifices (avoid the use of hard, sharp instruments capable of damaging surfaces for cleaning these orifices). To check the air shutters and main burner orifices, see for Manifold Assembly Removal.

The heat exchanger should be checked annually for cracks and discoloration of the tubes. If a crack is detected, the heat exchanger should be replaced before the unit is put back into service. If the tubes are dark gray, airflow across the heat exchanger should be checked to insure that a blockage has not occurred or the blower is operating properly.

electrical Wiring

The electrical wiring should be checked annually for loose connections or deteriorated insulation.

Gas Piping & controls

The gas valves and piping should be checked annually for general cleanliness and tightness.

The gas controls should be checked to insure that the unit is operating properly.

manifold assembly removal

1. Shut off gas and electric supply.

2. Remove the side access panel.

3. Disconnect gas manifold at ground union joint.

4. Remove the two screws holding the manifold to the heat exchanger support.

5. Slide the manifold through the manifold bracket.

6. Clean the orifices and adjust the air shutters as necessary.

7. Follow steps 3-6 in reverse to install the manifold assembly.

8. Turn on the electric and gas supply.

9. Check the ground union joint for leaks with a soap solution.

Tighten if necessary.

10. Install the side access panel.

A A A

A A

C

A A A A

A

A

C

A

200/225

250/300

500/600

350/400

700/800

A = 20" X 25" FILTER

B = 16" X 25" FILTER

C = 15" X 25" FILTER

Filter Spacer to be inserted on non-access side of unit

figure 52.2 - filter replacement arrangement for Blower size (digit 16) i, J, K, and l a a a

NON-ACCESS

SIDE

FILTER

SPACER

a d a

NON-ACCESS

SIDE

FILTER

SPACER

a

figure 52.1 - manifold assembly removal

SERIAL

PLATE

ELECTRICAL

JUNCTION

BOX

GROUND

UNION

JOINT

52 a c

250/300

500/600

c a a c

A = 20'' x 25''

B = 16'' x 25''

C = 20'' x 16''

D = 15'' X 25''

a

B d

350/400

700/800

840/960

B a

5-572.7

BURNER SIDE

ACCESS PANEL

MANIFOLD

HEAT EXCHANGER

SUPPORT

maintenance

Burner and Pilot assembly removal to remove the burner

1. Shut off gas and electric supply.

2. Remove the side access panel.

3. Disconnect the pilot supply line from the gas valve.

4. Disconnect the ignition cable from the ignition controller

(located in the electrical junction box). Feed the cable through the bushing in the bottom of the electrical junction box.

5. Remove the screws holding the burner side access panel.

Attached to the panel are the burner retaining pins that align the burner.

6. Slide the burner assembly out. The pilot is attached to the burner assembly.

7. Examine the burner and pilot assembly for cleanliness and/or obstructions as necessary (see Duct Furnace for cleaning instructions).

8. Replace the burner assembly in reverse order. In replacing the burner, be certain that the rear burner slots are located properly on the burner retaining pins. Do not force the burner side access panel, it will not fit if the burner is not properly aligned.

9. Reconnect the ignition cable and pilot gas supply line.

10. Install the side access panel.

11. Turn on the electric and gas supply.

figure 53.1 - Burner and Pilot assembly removal coil maintenance

(for units supplied with a dX or chilled Water coil)

1. Filters should be inspected on a regular basis and changed as needed. Maintaining clean filters is a cost- effective way to help maintain maximum coil performance and service life.

2. Periodic inspection of the coil for signs of corrosion and for leaks is recommended. For DX coils, Small leaks can be detected using a Halide torch. Repair and replacement of the coil and the connecting piping, valves, etc., should be performed as needed by a qualified individual(s).

3. Should the coil surface need cleaning, caution should be exercised in selecting the cleaning solution as well as the cleaning equipment. Improper selection can result in damage to the coil and/or health hazards. Clean the coil from the leaving air-side so that foreign material will be washed out of the coil rather than pushed further in. Be sure to carefully read and follow the cleaning fluid manufacturer's recommendations before using any cleaning fluid.

4. For DX coils, the use of filter-dryers in the system piping is recommended along with a sight glass that has a moisture indicator. Replace the filter dryer(s) as needed.

5. For chilled fluid coils,

A) Maintain the circulated fluid free of sediment, corrosive

products and biological contaminants. Periodic testing

of the fluid followed by any necessary corrective

measures along with maintaining adequate fluid

velocities and proper filtering of the fluid will help to

satisfy this goal.

B) Automatic air vents must be utilized to remove

accumulated air.

C) Freeze Protection - During the winter, chilled water coils

need to be protected against freezing. The two

predominant protective measures are 1) Blowing-out

the coils with air or 2) Flushing coils with inhibited

glycol. It is recommended to use inhibited glycol

designed for HVAC applications for corrosion

protection. Select an inhibited glycol solution that will

protect the coil from the lowest possible temperatures

that can occur at the particular coil's locality.

PILOT

ASSEMBLY

IGNITION

CABLE

PILOT

SUPPLY

LINE

HEAT

EXCHANGER

SUPPORT

AIR SHUTTERS

(NOT SHOWN)

ARE LOCATED

ON THE

MANIFOLD

5-572.7

53

service & trouBlesHootinG

WARNING

When servicing or repairing this equipment, use only factory-approved service replacement parts. A complete replacement parts list may be obtained by contacting Modine

Manufacturing Company. Refer to the rating plate on the unit for complete unit model number, serial number, and company address. Any substitution of parts or controls not approved by the factory will be at the owner’s risk.

cAUTION

Do not reuse any mechanical or electrical component which has been wet. Such component must be replaced.

IMPORTANT

To check most of the Possible Remedies in the troubleshooting guide listed in Table 54.1, refer to the applicable sections of the manual.

table 54.1 - troubleshooting

trouble

Pilot does not light

main burners do not light (Pilot is lit) lifting flames (see figure 55.1) yellow tipping

(With propane gas, some yellow tipping is always present.)

Possible cause

1. Main gas is off.

2. Power supply is off.

3. Air in gas line.

4. Dirt in pilot orifice.

5. Gas pressure out of proper range.

6. Pilot valve does not open.

a. Defective ignition controller.

b. Defective gas valve.

7. No Spark at ignitor.

a. Loose wire connections.

b. Pilot sensor is grounded.

c. Defective ignition controller.

8. Safety device has cut power.

1. Defective valve.

2. Loose wiring.

3. Defective pilot sensor

4. Defective ignition controller.

5. Improper thermostat wiring.

1. Too much primary air.

2. Main pressure set too high.

3. Orifice too large.

1. Insufficient primary air.

2. Dirty orifice.

3. Misaligned orifice.

Possible remedy

1. Open manual gas valve.

2. Turn on main power.

3. Purge gas line.

4. Check for plugged pilot orifice and clean with compressed air if necessary.

5. Adjust to a maximum of 14" W.C.

Minimum for Natural Gas - 6" W.C.

Minimum for Propane Gas - 11" W.C.

6. Check wiring for 24 volts to valve. a. Replace ignition controller. b. Replace gas valve.

7.

a. Check all ignition controller wiring.

b. Replace sensor if cracked or worn c. Replace ignition controller.

8. Check all safety devices (High limit, air flow proving switch, power exhauster centrifugal switch - HFP Models Only, gas pressure switches, etc.) Determine and correct problem. Reset if necessary.

1. Replace valve.

2. Check wiring to gas valve.

3. Replace pilot sensor.

4. Replace ignition controller.

5. Verify wiring compared to wiring diagram.

1. Reduce primary air.

2. Adjust to a maximum of 14" W.C.

3. Check orifice size with those listed on the serial plate.

1. Increase primary air.

2. Check orifices and clean with compressed air if necessary.

3. Check manifold, replace if necessary.

flashback floating flames (see figure 55.2)

54

1. Too much primary air.

2. Main pressure set too high.

3. Orifice too large.

1. Insufficient primary air.

2. Main pressure set too high.

3. Orifice too large.

4. Blocked vent cap.

5-572.7

1. Reduce primary air.

2. Adjust to a maximum of 14" W.C.

3. Check orifice size with those listed on the serial plate.

1. Increase primary air.

2. Adjust to a maximum of 14" W.C.

3. Check orifice size with those listed on the serial plate.

4. Clean louvers in vent cap.

service & trouBlesHootinG trouble flame rollout (see figure 55.3) not enough Heat too much Heat

Power exhauster motor will not start

(HfP models only)

Possible cause

1. Main pressure set too high.

2. Orifice too large.

3. Blocked vent cap.

1. Unit cycling on high limit. ➀ a. Obstructions/leaks in duct system.

b. Main pressure set too high.

c. Blower motor not energized.

d. Loose belt e. Blower speed too low.

f. Blocked/damaged venting system.

g. Air distribution baffle removed (high

temperature rise units only).

h. Defective high limit switch.

2. Main pressure set too low.

3. Too much outside air.

4. Thermostat malfunction.

5. Gas controls wired incorrectly.

6. Unit undersized.

1. Thermostat malfunction.

2. Gas controls do not shut-off. a. Gas controls wired incorrectly.

b. Short circuit.

3. Main gas pressure set too high.

4. Defective gas valve.

1. Power supply is off.

2. No 24V power to thermostat.

3. Thermostat malfunction.

4. Defective power exhauster relay.

5. Defective power exhauster motor.

Possible remedy

1. Adjust to a maximum of 14" W.C.

2. Check orifice size with those listed on the serial plate.

3. Clean louvers in vent cap.

1.

a. Clean/correct duct system.

b. Adjust to a maximum of 14" W.C. c. Check/correct to insure blower motor

operates within 45 seconds of when

gas controls are energized.

d. Adjust belt tension.

e. Check/correct blower drive settings for

proper rpm.

f. Check/correct venting system.

g. Replace air distribution baffle.

h. Replace high limit switch.

2. Adjust main gas pressure.

Minimum for Natural Gas — 6" W.C.

Minimum for Propane Gas — 11" W.C.

3. Adjust outside air damper to decrease outside air percentage (if possible).

4. Check/replace thermostat.

5. Check unit wiring against the wiring diagram.

6. Check design conditions. If unit is undersized, an additional unit(s) or other heat source must be added.

1. Check/replace thermostat.

2.

a. Check unit wiring against the wiring

diagram.

b. Check for loose or worn wires.

3. Adjust to a maximum of 14" W.C.

4. Replace gas valve.

1. Turn on main power.

2. Check control transformer.

3. Check/replace thermostat.

4. Replace power exhauster relay.

5. Replace power exhauster motor.

automatic reset High limit

The duct furnace comes standard with an automatic reset high limit switch that will shut-off the gas should the discharge air

49 temperature become excessive. See Figure 18.1, indicator for the location of either the standard automatic or optional manual reset high limit switch. The switch should operate only when something is seriously wrong with the unit operation.

Anytime the switch operates, correct the difficulty immediately or serious damage may result. If the switch cuts off the gas supply during normal operation, refer to the “Not Enough Heat” section of Service & Troubleshooting.

figure 55.1

lifting flame condition figure 55.2

floating flame condition figure 55.3

flame rollout appearance

5-572.7

55

model desiGnations

model identification

Modine weatherproof duct furnace/make-up air units contain an AGA/CGA and ETL/ETL Canada certified weatherproof duct furnace. This duct furnace is combined with either a blower section, or a blower and/or cooling and/or downturn sections to make a complete make-up air or heating/ventilating/cooling unit that is ETL/ETL Canada certified. For this reason, two identification plates are used on these models. The

serial

Plate is used to identify the duct furnace and its components.

The model identification Plate is used to identify the complete model, including blower, cooling, and/or downturn sections.

ordering

When servicing, repairing or replacing parts on these units, locate the model identification plate of the unit and always give the complete Model Number and Serial Number from the model identification plate. The model identification plate is located on the door of the electrical control box (See Figure 56.1). The part number for some common replacement parts are listed on the serial plate (See Figure 56.2) and the model identification plate

(See Figure 57.1). For a complete description of the model number, see Model Identification.

figure 56.1 - serial Plate and model id Plate locations

SERIAL

PLATE

MODEL

IDENTIFICATION

PLATE

figure 56.2 - serial Plate

56

Modine Manufacturing Company

1221 magnolia avenue

Buena vista, va, 24416; Phone: 540-261-2166

TYPE OF GAS

TYPE DE GAZ

TEMPERATURE RISE RANGE

ELEVATION DE TEMPERATURE

natural

20-100

outdoor Gas-fired duct furnace/ for industrial/commercial use cHaudiere a` GaZ a` conduit Pour eXterieur/

Pour usaGe industriel/commercial

MADE IN U.S.A

.

aPProvals

MODEL NUMBER

NUMERO DE MODELE

SERIAL NUMBER

NUMERO DE SERIE

0917093610-0123

0 to 2000 ft.

0 et 610 m.

(in canada)

2000 to 4500 ft.

610 et 1370 m.

INPUT BTU/HR

DEBIT CALORIFIQUE

BTU/HEURE

200000

180000

MIN.

CFM

1481

PHASE

1

OUTPUT BTU/HR

RENDEMENT

BTU/HEURE

160000

144000

MAX.

CFM

7407

AMPS

0.35

ORIFICE SIZE

DIM. DE L’INJECTEUR

23 26

*

MIN. VARIABLE

SPEED CFM

1111

common rePlacement Parts

for parts ordering, contact the parts wholesaler or the manufacturer’s representative serving your area. When inquiring about parts, always provide model number, serial number, description and part number. When ordering parts, provide part number listed.

for service, contact your local qualified installation and service contractor or appropriate utility company.

60

comBustiBle materials and service clearances materiauX comBustiBles et dÉGaGements d ‘ entretien

Air flow / Air courant

5H73205-1 Comb. Gas Control

5H73696- Ignition Control

3H34347-3 Pilot Assy. kit

5H74976-1 limit Control

5H74977-1 Transfomer

5H74818-1 Wiring Diagram

3H35628-6 Burner kit

3H35616-6 Heat Exch. kit

MIN. INPUT BTU/HR

DEBIT CALORIFIQUE

MIN. BTU/HEURE

160000

MIN. INLET PRESS. FOR PURPOSE

OF INPUT ADJUSTMENT

PRESSION D’ ALIMENTATION

EN GAZ MIN. ADMISE

MANIFOLD PRESSURE

PRESSION A LA TUBULURE

D’ ALIMENTATION

MAXIMUM EXTERNAL

STATIC PRESSURE

PRESSION STATIQUE

EXTERIEUR MAXIMUM

VOLTS

air tHrouGHPut deBit d’air

6

3.5

3

115

Top View/

Vue de dessus

IN. W.C.

PO.C.D’E

DESIGN COMPLIES WITH DUCT FURNACE STANDARD:

IN. W.C.

PO.C.D’E

IN. W.C.

PO.C.D’E

ANS Z83.8 - 96

CGA 2.8 - M86

DESIGN CONFORMS TO: UL STD 1995

CERTIFIED TO: CAN/CSA C22.2 NO. 236

APPROVED FOR USE IN CA BY THE CEC WHEN EQUIPPED WITH IPI

APPROVED FOR USE IN MASSACHUSETTS

ACCEPTED BY CITY OF NEW YORk:

MEA

135-99-E

9900100

General

1. FOR OUTDOOR INSTALLATIONS ONLY.

2. MINIMUM AMBIENT TEMPERATURE -40 F.

3. FOR INSTALLATION DOWN STREAM OF REFRIGERATION SYSTEMS.

4. INSTALL ON THE POSITIVE PRESSURE SIDE OF AIR CIRCULATING BLOWER.

5. FOR UNITS WITH MANUAL RESET HIGH LIMIT SWITCH, RESET BUTTON IS LOCATED IN ELECTRICAL

JUNCTION BOX.

6. (IN USA) FOR INSTALLATIONS ABOVE 2000 FEET, DERATE 4 PERCENT FOR EACH 1000 FEET

OF ELEVATION ABOVE SEA LEVEL.

liGHtinG instructions

1. OPEN ALL GAS VALVES. TURN ON POWER.

2. SET THERMOSTAT TO DESIRED SETTING.

sHut doWn instructions

1

.

TURN OFF POWER & CLOSE ALL GAS VALVES.

REFER TO INSTALLATION AND SERVICE MANUAL FOR MORE INSTRUCTIONS

*

for units WitH tWo staGe, mecHanical modulation, or electronic modulatinG Gas controls, a factory discHarGe air controller and no room tHermostat included.

Access

Side/

C™t dÕacc s

Non-Access side/ Non-

C™t dÕ acc ss

GÉnÉral

1 SEULEMENT POUR L’INSTALLATION EXTERIEURE

3. POUR L’INSTALLATION QUE SUIVE LES SYSTEMS REFRIGERANTS.

^ TÉ DE LA PRESSION POSITIVE DU VENTILATEUR.

1

2

Minimum clearance to combustibles is 0.0” from bottom of unit mounting rail or 3” from bottom of sheet metal casing. / Le dégagement minimum du combustible est 0.0” du bas de la barre qui support l’élément ou 3” du bas de l’enveloppe de to^le.

HFP - Minimum clearance to combustibles is 1.0” from rooftop. / HFP Les dimensions minima de positionnement par rapport aux matériaux combustibles est de 1.0 po depuis le dessus de l’appareil.

MODEL

SIZE

75

100/125

150/175

200/225

250/300

350/400

FRONT &

REAR (B)

HFG

0”

0”

3”

4”

5”

11”

CLEARANCE TO

COMBUSTIBLE

MATERIALS

FRONT &

REAR (B)

HFP

4”

5”

11”

3”

3”

3”

SIDE C

HFG/HFP

0”

0”

0”

0”

0”

0”

SIDE A

HFG HFP

0”

0”

0”

0”

0”

0”

3”

3”

3”

3”

3”

3”

5. POUR APPAREILS AVEC INTERRUPTEUR REMIS MANUEL HAUT-LIMITE, REMISE EST SITUÉE

*

DANS LA BOI^TE JUNCTION ÉLECTRIQUE. POUR REMETTRE PRESSER LE BOUTON.

instructions d’allumaGe

1. DUVRIR TOUTES LES ROBINETS A GAZ. DONNER LE COURANT.

2. REGLER LE THERMOSTAT SUR LA POSITION DESIREE.

instructions de fer meture

1. COUPER LE COURANT ET FERMER TOUTES LES ROBINETS A GAZ.

REFERREZ AU MANUAL D’INSTALLATION ET

DE SERVICE POUR PLUS D’ INSTRUCTIONS

Pour aPPareils avec deuX PHases modulation mÉcHaniQue, ou aPPareils de contro et tHermostat de cHamBre nÕest Pas inclus.

^le de GaZ ÉlectriQues modulÉs, un air contro^leur dÉcHarGe installÉ a` la manufacture,

RECOMMENDED

SERVICE

CLEARANCE

ACCESS

SIDE

(A)

18”

20”

25”

27”

30”

41”

NON-

ACCESS

SIDE (C)

6”

6”

6”

6”

6”

6”

dimension du modele

75

100/125

150/175

200/225

250/300

350/400

avant & arriere

(B)

HfG

4”

5”

11”

0”

0”

3”

DEGAGEMENT DU

MATERIAL

COMBUSTIBLE

avant & arriere

(B)

HfP

3”

3”

3”

4”

5”

11”

cote c

HfG/HfP

0”

0”

0”

0”

0”

0”

COTE A

HFG

0”

0”

0”

0”

0”

0”

HFP

3”

3”

3”

3”

3”

3”

DEGAGEMENT

DE SERVICE

RECOMMENDE

cote d’acces

(a)

18”

20”

25”

27”

30”

41”

cote nonacces (c)

6”

6”

6”

6”

6”

6”

5H74930B Rev F

5-572.7

model desiGnations

figure 57.1 - model identification Plate

HBG 75AFRHN10A1AA1AAA1A

01101010199-0002

115/208-230

115 60

1

60

1

8.47

6.6/3.0-3.3

9F20218

5H71790-

10.00

Modine Manufacturing Company

1500 DeKoven Ave., Racine, WI 53403

Phone: 800.828.4328

5H63081-20

5H58064-3

5H76183-31

figure 57.2 - HfG/HfP serial number designations

s 09 17 09 36

serial numBer PrefiX

<blank> if standard

"S" if Special Product Order

series identity numBer control suPPlier

01-Robertshaw 09-White Rodgers

05-Honeywell 17-United Technologies

08-Fenwal

Gas valve suPPlier

01-Robertshaw 09-White Rodgers

05-Honeywell

10 0123 10000

sPo numBer

<blank> if standard

##### if Special Product Order

seQuential numBer

Varies - 0000 TO 9999

Each unit in a week has a unique number

year

Produced

WeeK

Produced

figure 57.3 - HBG/HBP/HcG/HcP/HdG/HdP/HPG/HPP

serial number designations

serial number designations

motor vendor code

01 – Century

15 – Marathon etc.

fan or BloWer vendor code

10 – Lau

20 – Morrison etc.

series identity numBer

Identifies which series of controls were furnished on the unit.

01 10 201 01 02-1000

seQuence numBer year of manufacture

01 – 2001

02 – 2002 etc.

WeeK of manufacture

01 – 1st week of year

26 – 26th week of year

Serial number format subject to change. When contacting the factory for replacement parts, always have the actual serial number ready from the unit(s).

5-572.7

57

start-uP cHecKlist indirect Gas-fired HeatinG eQuiPment

Job Name:

Address:

City & State:

Start-Up Check List “ALL ITEMS MUST BE CHECkED”

Date:

Model No.:

Order No.:

Serial No.:

1. All shipping straps, braces, tie downs removed?

2. Unit installed level and secure?

3. Gas burner properly located and aligned?

4. Blower and motor alignment okay?

5. Bearings aligned and tight on shaft/bearing supports?

6. Electrical connections checked and secure?

7. Gas piping checked and tightened if necessary?

8. Any visible damage to unit?

Describe: ______________________________________________

If damaged, was the damage repaired?

9. Air inlet and discharge checked for obstructions?

10. Bearings checked for proper lubrication?

11. Filters in place and correct to direction of air flow?

12. Belt tension checked?

13. Electric supply to unit: ______ Volts, ______ Hz, ______ Phase

14. Gas supply to unit: ______ Natural, ______ Propane

15. Gas supply pressure to unit: ______ " W.C., ______ PSIG

16. Inlet and/or discharge dampers operating correctly?

17. Blower rotation correct?

18. Blower speed: Hi Speed ______ RPM, Lo Speed ______ RPM

19. Motor speed: Hi Speed ______ RPM, Lo Speed ______ RPM

20. Is unit noisy? Excessive vibration?

21. Motor voltage: L1 ______ V, L2 ______ V, L3 ______ V

22. Motor amps: L1 ______ Amp, L2 ______ Amp, L3 ______ Amp

23. High temperature limit control continuity checked?

24. Burner light off

Low Fire: Does entire burner light off?

Hi Fire: Burner pressure reading? ______ " W.C.

Is flame clean and stable?

Does flame modulate in response to temperature control(s)?

25. Gas input checked?

Input at maximum firing rate: __________ Btu/Hr

____ Yes

____ Yes

____ Yes

____ Yes

____ Yes

____ Yes ___ No

____ Yes ___ No

____ Yes

____ Yes

____ Yes

____ Yes

____ Yes

____ Yes

____ Yes

____ Yes

____ Yes

___ No

___ No

___ No

___ No

___ No

___ No

___ No

____ Yes ___ No

____ Yes ___ No

____ Yes ___ No

___ No

___ No

___ No

___ No

___ No

___ No

___ No

____ Yes ___ No

____ Yes ___ No

Input at minimum firing rate: -__________ Btu/Hr

26. Gas piping checked for and free of leaks? ____ Yes ___ No

27. Has wiring been verified to match the unit wiring diagram? ____ Yes ___ No

28. Have all the modes of the sequence of operation been verified and tested? ____ Yes ___ No

29. What optional and/or accessory control devices have been set?

Device: _______________ Setting: ___________ (°F/psi/Inches W.C./etc.) ____ Yes ___ No

Device: _______________ Setting: ___________ (°F/psi/Inches W.C./etc.) ____ Yes ___ No

Device: _______________ Setting: ___________ (°F/psi/Inches W.C./etc.) ____ Yes ___ No

Customer/Owner instructed in operation and maintenance of unit? ____ Yes ___ No

Name of Person(s) Instructed: ______________________________________________________________

Comments: ____________________________________________________________________________

____________________________________________________________________________

Start-Up Company Name: _______________________________ Phone: __________________________

Signature: _______________________________________________________ Date: ________________

58

5-572.7

model nomenclature for system units

Weatherproof model nomenclature

1 2 3

PT UC V

3 - venting (v)

4 5 6

MBH

1 - Product type (Pt)

H - Outdoor HVAC Unit

2 - unit configuration (uc)

B - Blower Package - Furnace & Blower

C - Cooling Package - Furnace, Blower, & Cooling Cabinet

D - Downturn Package - Furnace, Blower, & Downturn

P - Packaged Unit - Furnace, Blower, Cooling Cabinet, & Downturn

G - Gravity P - Power

4,5,6 - furnace input rating (mBH) (output on 840 & 960)

100 - 100,000 Btu/Hr Input

175 - 175,000 Btu/Hr Input

250 - 250,000 Btu/Hr Input

400 - 400,000 Btu/Hr Input

7

HE

8 9 10 11 12 13 14 15

DS AS ATR GT GV SS SV TR

500 - 500,000 Btu/Hr Input

600 - 600,000 Btu/Hr Input

840 - 1,050,000 Btu/Hr Input

960 - 1,200,000 Btu/Hr Input

7 - Heat exchanger/Burner/drip Pan material (He)

A - Aluminized Steel

S - 409 Stainless Steel Heat Exchanger/Burner

T - 409 Stainless Steel Heat Exchanger/Burner/Drip Pan

8 - development sequence designation (ds)

F - Single Stage M - 2-stage or Modulating

9 - access side (as)

R - Right Hand L - Left hand

16 - Blower size & Bearing type (BB)

A - 9-7 Spider Bearings

B - 9-7 Pillow Block Bearings

C - 9-9 Spider Bearings

D - 9-9 Pillow Block Bearings

E - 12-12 Spider Bearings

18 - motor type (mt)

1 - ODP

2 - ODP - High Eff.

3 - ODP, 1800/900 RPM

4 - ODP, 1800/1200 RPM

16

BB

17

HP

18

MT

5 - TE

19 20 21 22 23

SA

6 - TE - High Eff.

AC

7 - TE, 1800/900 RPM

8 - TE, 1800/1200 RPM

EC CC

F - 12-12 Pillow Block Bearings L - 20-18 Pillow Block Bearings

17 - motor Horsepower (HP)

A - 1/3 Hp

B - 1/2 Hp

C - 3/4 Hp

D - 1 Hp

E - 1-1/2 Hp

F - 2 Hp

G - 3 Hp

H - 5 Hp

I - 7-1/2 Hp

J - 10 Hp k - 15 Hp

V - 20 Hp

G - 15-15 Spider Bearings

H - 15-15 Pillow Block Bearings

I - 18-18 Spider Bearings under 15 Hp

J - 18-18 Pillow Block Bearings under 15 Hp k - 18-18 Pillow Block Bearings for 15 Hp & up

L - 1/3 Hp with Motor Starter

M - 1/2 Hp with Motor Starter

N - 3/4 Hp with Motor Starter

P - 1 Hp with Motor Starter

Q - 1-1/2 Hp with Motor Starter

R - 2 Hp Hp with Motor Starter

S - 3 Hp with Motor Starter

T - 5 Hp with Motor Starter

W - 7-1/2 Hp with Motor Starter

X - 10 Hp with Motor Starter

Y - 15 Hp with Motor Starter

Z - 20 Hp with Motor Starter

10 - air temperature rise (atr)

H - High 60°-100°F

L - Low 20°-60°F

11 - Gas type (Gt)

N - Natural with ignition controller

P - Propane with ignition controller

12 - Gas valve (Gv)

1 - Single Stage

2 - Two Stage

4 - Electronic Modulation

6 - Electronic Modulation Slave

7 - Electronic Modulation 0-10 Vdc

External Input

5 - Electronic Modulation Master 8 - Electronic Modulation 4-20 mA

External Input

13 - additional safety switches (ss)

0 - No Switches (Standard)

1 - Low Gas Pressure Switch (Premium)

2 - High Gas Pressure Switch (Premium)

3 - High and Low Gas Pressure Switch (Premium)

14 - supply voltage (sv)

A - 115/60/1

B - 208/60/1

C - 230/60/1

D - 208/60/3

15 - transformer (tr)

1 - 40 VA

2 - 75 VA

3 - 150 VA

E - 230/60/3

F - 460/60/3

G - 575/60/3

4 - 250 VA

0 - None

19 - sheave arrangement (sa)

A - (See Sheave Tables)

20,21 - air control (ac)

AA - RA Opening

BA - FA Opening

CA - FA & RA Openings

DA - FA Dampers w/ 2 pos motor (No RA)

EA - FA & RA Dampers w/ 2 pos motor

EQ - ASHRAE Cycle I - (“EA” with Warm-up Stat)

FA - FA Damper & RA Opening w/ 2 pos motor

GA - FA & RA Mod motor w/ 0-10 Vdc External Input

GB - FA & RA Mod motor w/ 4-20 mA External Input

GC - FA & RA Mod motor w/ Minimum Position

GD - FA & RA Mod motor w/ Remote Position (On Remote Panel)

GE - FA & RA Mod motor w/ 3 pos. damper (100% RA, Variable, 100% OA)

GF - FA & RA Mod motor w/ A350P Proportional Temp Controller

GG - FA & RA Mod motor w/ Minimum Position & Prop. Temp Controller

GH - FA & RA Mod motor w/ Remote Position & Prop. Temp Controller

GJ - FA & RA Mod motor w/ FA Enthalpy Controller

Gk - ASHRAE Cycle II - (“GG” with Warm-up Stat)

GM - ASHRAE Cycle II - (“GH” with Warm-up Stat)

GN - ASHRAE Cycle III - (“GF” with Warm-up Stat)

HP - FA & RA Floating motor w/ Space Pressure Controller

JA - Manual FA & RA Dampers kA - Manual FA Damper with Return Air Opening

22 - evaporative cooling (ec)

3 - 6" CELdek Media

4 - 12" CELdek Media

5 - 6" GLASdek Media

6 - 12" GLASdek Media

A - 6" CELdek Media, Stainless Steel Casing

B - 12" CELdek Media, Stainless Steel Casing

C - 6" GLASdek Media, Stainless Steel Casing

D - 12" GLASdek Media, Stainless Steel Casing

0 - None

23 - cooling coil (cc)

0 - None 1 - Factory Installed Coil

5-572.7

59

commercial Warranty

Seller warrants its products to be free from defects in material and workmanship, EXCLUSIVE, HOWEVER, of failures attributable to the use of materials substituted under emergency conditions for materials normally employed. This warranty covers replacement of any parts furnished from the factory of Seller, but does not cover labor of any kind and materials not furnished by Seller, or any charges for any such labor or materials, whether such labor, materials or charges thereon are due to replacement of parts, adjustments, repairs, or any other work done. This warranty does not apply to any equipment which shall have been repaired or altered outside the factory of

Seller in any way so as, in the judgment of Seller, to affect its stability, nor which has been subjected to misuse, negligence, or operating conditions in excess of those for which such equipment was designed. This warranty does not cover the effects of physical or chemical properties of water or steam or other liquids or gases used in the equipment.

BUYER AGREES THAT SELLER’S WARRANTY OF ITS PRODUCTS TO

BE FREE FROM DEFECT IN MATERIAL AND WORkMANSHIP, AS LIMITED

HEREIN, SHALL BE IN LIEU OF AND EXCLUSIVE OF ALL OTHER

WARRANTIES, EITHER EXPRESS OR IMPLIED, WHETHER ARISING

FROM LAW, COURSE OF DEALING, USAGE OF TRADE, OR OTHERWISE,

tHere are no otHer Warranties, includinG Warranty of mercHantaBility or fitness for PurPose, WHicH eXtend

Beyond tHe Product descriPtion confirmed By Buyer and seller as of tHe date of final aGreement.

This warranty is void if the input to the product exceeds the rated input as indicated on the product serial plate by more than 5% on gas-fired and oil-fired units, or if the product in the judgment of SELLER has been installed in a corrosive atmosphere, or subjected to corrosive fluids or gases, been subjected to misuse, negligence, accident, excessive thermal shock, excessive humidity, physical damage, impact, abrasion, unauthorized alterations, or operation contrary to SELLER’S printed instructions, or if the serial number has been altered, defaced or removed.

BUYER’S REMEDY FOR BREACH OF WARRANTY, EXCLUSIVE OF ALL

OTHER REMEDIES PROVIDED BY LAW, IS LIMITED TO REPAIR OR

REPLACEMENT AT THE FACTORY OF SELLER, ANY COMPONENT WHICH

component

Applicable Models

SHALL, WITHIN THE APPLICABLE WARRANTY PERIOD DEFINED HEREIN

AND UPON PRIOR WRITTEN APPROVAL, BE RETURNED TO SELLER

WITH TRANSPORTATION CHARGES PREPAID AND WHICH THE

EXAMINATION OF SELLER SHALL DISCLOSE TO HAVE BEEN DEFECTIVE;

EXCEPT THAT WHEN THE PRODUCT IS TO BE USED BY BUYER AS A

COMPONENT PART OF EQUIPMENT MANUFACTURED BY BUYER,

BUYER’S REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE

LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER. FOR

GAS-FIRED PRODUCTS INSTALLED IN HIGH HUMIDITY APPLICATIONS

AND UTILIZING STAINLESS STEEL HEAT EXCHANGERS, BUYER’S

REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO TEN

YEARS FROM DATE OF SHIPMENT FROM SELLER.

These warranties are issued only to the original owner-user and cannot be transferred or assigned. No provision is made in these warranties for any labor allowance or field labor participation. Seller will not honor any expenses incurred in its behalf with regard to repairs to any of Seller’s products. No credit shall be issued for any defective part returned without proper written authorization (including, but not limited to, model number, serial number, date of failure, etc.) and freight prepaid.

OPTIONAL SUPPLEMENTAL WARRANTY

Provided a supplemental warranty has been purchased, Seller extends the warranty herein for an additional four (4) years on certain compressors.

Provided a supplemental warranty has been purchased, Seller extends the warranty herein for an additional four (4) years or nine (9) years on certain heat exchangers.

EXCLUSION OF CONSUMABLES & CONDITIONS BEYOND

SELLER’S CONTROL

The above referenced warranty shall not be applicable to any of the following items: refrigerant gas, belts, filters, fuses and other items consumed or worn out by normal wear and tear or conditions beyond Seller’s control, including

(without limitation as to generality) polluted or contaminated or foreign matter contained in the air or water utilized for heat exchanger (condenser) cooling or if the failure of the part is caused by improper air or water supply, or improper or incorrect sizing of power supply.

“aPPlicaBle Warranty Period”

Heat exchangers

Gas-Fired Units except PSH/BSH

TEN YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN

TEN YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN TEN YEARS

FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN ONE

HUNDRED TWENTY-SIX MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER

OCCURS FIRST

Heat exchangers

Low Intensity Infrared Units

compressors

Condensing Units for Cassettes

Burners

Low Intensity Infrared Units

other

Components excluding Heat Exchangers,

Coils, Condensers, Burners, Sheet Metal

FIVE YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN

FIVE YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN FIVE YEARS

FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN SIXTY-SIX

MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST

TWO YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN

TWO YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN

THIRTY MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST

Heat exchangers/coils

Indoor and Outdoor Duct Furnaces and

System Units, PSH/BSH, Steam/Hot Water Units,

Oil-Fired Units, Electric Units, Cassettes,

Vertical Unit Ventilators

compressors

Vertical Unit Ventilators

Burners

High Intensity Infrared Units

sheet metal Parts

All Products

ONE YEAR FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN

ONE YEAR FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN

EIGHTEEN MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST

As Modine Manufacturing Company has a continuous product improvement program, it reserves the right to change design and specifications without notice.

© Modine Manufacturing Company 2010