Highbay Fluorescent - Eight Lamp Flat Profile Design HFC1 Series Specification Sheet

Highbay Fluorescent - Eight Lamp Flat Profile Design HFC1 Series Specification Sheet
Specification Sheet
HFC1 Series
Highbay Fluorescent
4/9/2014
Project:
Highbay Fluorescent - Eight Lamp
Flat Profile Design
Catalog#:
Approved by:
Description
HFC1 series high-bay fluorescent fixture is a great
energy saving alternative to traditional HID highbay fixtures. This fixture operates eight lamps
and as a standard feature comes equipped with
Howard ballasts.
Benefits
•
•
•
•
•
•
Applications
Warehouse
Manufacturing
Facility
Gymnasium
Cafeteria
Auditorium
•
•
•
Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Easy access to wiring compartment & ballast
Access plate provides access to electrical wiring with-out the
need to open the fixture
Knock-outs for easy electrical wiring and assembly
Factory Installed Occupancy Sensor option
Factory Installed Emergency ballast option
Lamp Installation option available
Multiple power cord set options, (voltage, length, gage)
Pendant mount kit provides a top J-box to simplify HID
retrofit installations. Can be used with a hook or rigid conduit
and fasteners (Fixture must be specified with “J” option)
Door and lens kit options available
Choice of 86% Standard Specular Aluminum Reflector,
95% Specular Enhanced Aluminum Reflector or 91% White
Reflector
Heavy Duty pre-painted steel construction
Factory Installed Wireguard option
Custom configurations available
Can be easily mounted by a single person
Suspended or Pendant mounting insures a quick painless
install
Chain and V-Clip Hanging option
Wire cable hanging option.
UL Listed for Damp Locations
•
Energy Saving Compared to HID systems
Exceptional Color Rendering
High System Efficacy
Long Lamp Life
Instant On/Re-strike Capability
Howard Ballast and Howard Lamp as a
system is covered by Howard Industries
Warranty
Quality Lamp holders
Computer Designed Reflectors
System Tested, Designed, Approved, and
Manufactured by Howard Industries in
Mendenhall Mississippi.
Compliant with Safety and performance
standards.
Cable hanging
Holes for “V” clip
& chain hanging
Factory Installed Option J
Pendant Mount Kit (PMK2)
installs from the outside: no
need to open the fixture
Access plate
5.5”
”
48
19
.87
5”
Pendant Mount lances included only if
Factory Installed Option “J” is selected.
Specifications subject to change without notice.
Howard Lighting Products | 580 Eastview Drive | Laurel, MS 39443
(toll free) 800.956.3456 | (direct) 601.422.0033 | (fax) 601.422.1652
www.HowardLightingProducts.com
Highbay Fluorescent
Specification Sheet
HFC1 Series
Highbay Fluorescent - Eight Lamp
Flat Profile Design
Project:
Catalog#:
Approved by:
Ordering Information
Model
Family
HFC1
HFC1
Reflector
No. of
Lamps
E
E: Enhanced
Specular
Aluminum (95%)
Lamp Type/
Wattage(1)
CRI/CCT
Ballast
32
A
SE
8
8
A: Specular
Aluminum (86%)
W: White
reflective (91%)
T8 Lamps
28: F28T8
32: F32T8
T5 Lamps
28:F28T5
54: F54T5HO
CRI
CCT
A: No Lamps
B: 75 3000
C: 75 3500
D: 75 4100
E: 75 5000
F: 85 3000
G: 85 3500
H: 85 4100
I: 85 5000
J: 85 6500
K: 85 3000
L: 85 3500
M: 85 4100
N: 85 5000
LE: LBF High Eff(2)
X
X
X
X
X
X
X
X
Yes
Yes
Yes
Yes
X
X
X
X
PS: PRS T5
P8: PRS T8(2)
X
X
X
X
X
Standard Ballast Factor High Efficiency Instant Start T8 Ballast
HE
High Ballast Factor High Efficiency Instant Start T8 Ballast
LE
Low Ballast Factor High Efficiency Instant Start T8 Ballast
PS
Program Rapid Start T5 Ballast
P8
Program Rapid Start High Efficiency T8 Ballast
(consult customer service
for other corset options)
Cordset Options
T
B
A
OCJ
01
0
000: No FIOs
A: Occ Sensor(4)
B: Emergency Ballast(5)
C: Door W/Lens &
Safety Cable(6)
D: Door W/Lens(6)
G: Wireguard
I: Special Wiring
Instructions
J: J-box config.(7)
T: Toggle switch bilevel lighting control(8)
00: Standard Disconnect
01: 6’ SJT 18/3, no plug
02: 10’ SJT 18/3, no plug
03: 6’ SJT 18/3 L5-15, twist lock 120v
04: 10’ SJT 18/3 L5-15twist lock 120v
05: 6’ SJT 18/3 5-15non twist lock 120v
06: 10’ SJT 18/3 5-15non twist lock 120v
07: 6’ SJT 18/3 L7-15 twist lock 277v
08: 10’ SJT 18/3 L7-15 twist lock 277v
09: 6’ SJT 7-15 non twist lock 277v
10: 10’ SJT 7-15 non twist lock 277v
11: 16/3, no plug spec len
12: 16/4, no plug spec len
16: 16’ SJT 18/3 7-15, non twist lock 277v
17: 18/3, no plug spec len
18: 6’ STW L8-20, twist lock 480v
19: 10’ STW L8-20, twist lock 480v
20: 16’ SJT 18/3 L5-15, twist lock 120v
21: 16’ SJT 18/3 L5-15, twist lock 277v
Factory Installed
Options
MV
(2)
High
T8 T5 SE: SBF High Eff
Lumen
HE: HBF High Eff(2)
(1) Lamp installation available.
(2) High Efficiency ballasts are CEE Listed.
(3) Step-down autotransformer. Allows hook-up of standard MV ballast to 480v.
(4) Occupancy Sensors should be used with programmed rapid start ballasts for maximum lamp life.
Standard Occupancy Sensor requires neutral wired fixtures (ex. -120v or -277v).
For phase-to-phase voltage applications (240v) advise Customer Service at time of request.
(5) Please specify Emergency Ballast (120-277v only) lumen requirements at time of request. (6) Standard acrylic prismatic, pattern 12, 0.100” thick. Call for options.
(7) Unless otherwise specified, fixture will include field installed J-box. Supply wires will exit the center of the fixture, not the
access plate. J-box can be installed without entering the fixture.
(8) Allows for separate control of two ballasts through simple “toggling” of a standard wall switch.
Recommend use of programmed rapid start ballast with this control.
SE
Input Volts
MV: 120-277v
HV: 347-480v
(T5HO)
AX: 480-277(3)
Sample Ordering Number:
HFC1 E 8 32 A SE MV 000 01 I
HFC1 Series Highbay Fluorescent
Enhanced Specular Aluminum Reflector
8-lamps (none installed)
F32T8 Standard Ballast Factor High Efficiency Ballast
Multi-volt (120-277v)
No Factory Installed Options
6’ SJT 18/3 cord, no plug
Single Packaging
Specifications subject to change without notice.
Howard Lighting Products | 580 Eastview Drive | Laurel, MS 39443
(toll free) 800.956.3456 | (direct) 601.422.0033 | (fax) 601.422.1652
www.HowardLightingProducts.com
Pack.
I
I: Single
B: Bulk
Specification Sheet
HFC1 Series
4/9/2014
Project:
Catalog#:
Highbay Fluorescent
Field Installed Options Ordering
Approved by:
HFC1-WG
Wire Guard
HFA-WCH
Wire Cable Hanging Kit
(2 pcs per kit)
HF-2CV (2 foot)
HF-3CV (3 foot)
Hanging Chain & V-clips
HF-SK1
Stabilizer Kit
(Hub, color and wire cable)
HF-PMK2
Pendant Mount Kit
with 1.0” diameter through hole
Energy Cost Estimator
Hours
burned
per year
Cost per
kWh$
Existing System
New System
400W MH Highbay
HFC1E832ASE
High Eff Standard BF
Fluorescent Highbay
4368
Number
of Fixtures
0.12
Energy Cost
Estimation
1
Number of
Fixtures
1
Watts per
Fixture
(existing
system)
458
Watts per
Fixture
(new
system)
216
Energy
used
per year
(existing
system)
$240
Energy
used per
year (new
system)
$113
Energy saving per
year (per fixture)
$250
53% Annual Savings
$200
$150
$100
$127.00
$50
$0
$240
$113
Existing System
New System
Specifications subject to change without notice.
Howard Lighting Products | 580 Eastview Drive | Laurel, MS 39443
(toll free) 800.956.3456 | (direct) 601.422.0033 | (fax) 601.422.1652
www.HowardLightingProducts.com
Specification Sheet
HFC1 Series
4/9/2014
Project:
Catalog#:
Highbay Fluorescent
Photometric Data - 8 Lamp T5 (HFC1E854)
Approved by:
Candela Polar Plot
Luminaire Efficiencies*
Reflector Type
Enhanced Specular
Specular
White
T8
84%
79%
74%
T5
89%
83%
79%
*Luminaire efficiency is the ratio of light output emitted by the luminaire to the
light output emitted by its lamps.
Zonal Lumen Summary
Zone
Lumens
%Lamp
%Fix
0-30
9399.78
23.50
28.20
0-40
15444.29
38.60
46.30
0-60
26593.54
66.50
79.70
0-90
33369.54
83.40
100.00
0-180
33369.54
83.40
100.00
Luminance Data (cd/Sq.m)
HFC1E854
Test Report: HFC1E854APSMV.ies
Maximum Candela = 12262.25
Located at Horizontal Angle = 90, Vertical Angle = .5
#1 = Vertical Plane Through Horizontal Angles (90-270) Through Max Cd.
#2 = Vertical Plane Through Horizontal Angles (45-225)
#3 = Horizontal Cone Through Vertical Angle (.5) (Through Max. Cd.)
Angle In
Degrees
Average
0-deg
Average
45-deg
Average
90-deg
45
19857
19935
17294
55
18756
16751
16506
65
16843
15832
16872
75
12850
14889
16174
85
4551
10082
7282
Coefficients of Utilization - Zonal Cavity Method
Effective Floor Cavity Reflectance 0.20
RC
RW
80
70
50
70
30
10
70
50
50
30
10
50
30
30
10
50
30
10
10
50
30
0
10
0
0
99
99
99
99
97
97
97
97
93
93
93
89
89
89
85
85
85
83
1
91
87
83
80
89
85
82
79
81
79
76
78
76
74
75
73
72
70
2
83
76
70
65
80
74
69
65
71
67
63
69
65
62
66
63
60
59
3
75
67
60
55
73
65
59
54
63
58
53
61
56
52
58
55
51
49
4
69
59
52
46
67
58
51
46
56
50
45
54
49
45
52
48
44
42
5
64
53
45
40
62
52
45
40
50
44
39
49
43
39
47
42
38
37
6
59
48
40
35
57
47
40
35
45
39
34
44
38
34
43
38
34
32
7
54
43
36
31
53
43
36
31
41
35
31
40
34
30
39
34
30
28
8
51
39
32
28
49
39
32
27
38
32
27
37
31
27
36
31
27
25
9
47
36
29
25
46
36
29
25
35
29
25
34
28
24
33
28
24
23
10
44
33
27
23
43
33
27
22
32
26
22
31
26
22
31
26
22
21
Specifications subject to change without notice.
Howard Lighting Products | 580 Eastview Drive | Laurel, MS 39443
(toll free) 800.956.3456 | (direct) 601.422.0033 | (fax) 601.422.1652
www.HowardLightingProducts.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement