FCQ-C TECHNICAL DATA
Indoor Units
FCQ-C8VEB
air conditioning systems
technical data
Indoor Units
FCQ-C8VEB
air conditioning systems
technical data
• Indoor Units • R-410A • FCQ-C8VEB
TABLE OF CONTENTS
FCQ-C8VEB
!
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications (50Hz) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications (60Hz) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
4
4
3
Safety device settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . 7
Dimensional drawing for standard panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Dimensional drawing for auto cleaning panel . . . . . . . . . . . . . . . . . . . . . . . . 8
Dimensional drawing with accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
7
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Wiring diagram
8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sound power spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
14
16
Air flow pattern . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
• Split Sky Air • Indoor Units
1
• Indoor Units • R-410A • FCQ-C8VEB
1
t i y n k BU S E V r A8t o 0C i o 1- ld 4Q npC- RFS•I
•
•
Features
Modern style decoration panel is available in 3 different variations:
Standard panel in white (RAL9010) with grey louvers and standard
panel in full white (RAL9010) including white louvers, auto cleaning
panel
For auto cleaning panel:
- Daikin introduces first auto cleaning cassette to European market1
- Higher efficiency and comfort from daily auto cleaning of the filter1
1
- Lower maintenance costs thanks to auto cleaning function1
- Easy removal of dust with a vacuum cleaner without opening the
unit1
360° air discharge ensures uniform air flow and temperature
distribution
•
Fresh air intake: up to 20 % (optional kit required)
•
Comfortable horizontal air discharge ensures draughtfree operation
and prevents ceiling soiling
•
23 different air flow patterns possible
•
Drain-up pump with 850 mm lift fitted as standard
Only for auto cleaning panel BYCQ140CG
Heat Pump
2 steps
2
Optional
• Split Sky Air • Indoor Units
Optional
Optional
• Indoor Units • R-410A • FCQ-C8VEB
2
Specifications
2-1 Technical Specifications
Power input 50Hz
FCQ60C8VEB
FCQ71C8VEB
Nom.
kW
0.056
0.120
Nom.
kW
0.056
0.120
Height
mm
204
Width
mm
Depth
mm
Height
mm
Width
mm
Depth
mm
Material
Unit
Packed unit
Galvanised steel plate
246
840
840
220
262
882
882
Unit
kg
19
21
23
Packed Unit
kg
24
25
28
Dimensions
Length
mm
inside: 2096, outside: 2152
mm
1.2
Nr of Rows
Fin Pitch
2
Nr of Passes
Face Area
4
6
m²
Nr of Stages
Empty Tubeplate Hole
Fin
Fan
7
9
0.267
0.357
0.446
6
8
4
Type
Cross fin coil (Multi louver fins and Hi-XSS tubes)
Type
Fan
Cooling
Turbo fan
1
High
m³/min
Low
m³/min
Heating
High
m³/min
Low
m³/min
Motor
Model
10.5
12.5
13.5
8.5
12.5
13.5
10.0
8.5
Heating
15.5
23.5
9.0
16.0
19.0
16.0
23.5
27.5
9.5
16.0
QTS48D11M
27.5
19.0
QTS48C15M
Number of steps
Cooling
10
0
Quantity
Air Flow Rate
FCQ100C8VEB FCQ125C8VEB FCQ140C8VEB
Heating
Dimensions
Heat Exchanger
FCQ50C8VEB
Cooling
Casing
Weight
FCQ35C8VEB
2
Output (high)
W
Sound Power
High
dBA
49
51
54
58
Sound Pressure
High
dBA
31
33
37
41
Low
dBA
27
High
dBA
31
Low
dBA
27
Sound Pressure
Sound Level
Sound Absorbing Insulation
Refrigerant
Type
Piping connections
Liquid (OD)
Type
Gas
Type
120
28
33
32
34
28
35
37
41
32
42
35
Foamed polyurethane
R-410A
Diameter (OD)
Drain
56
Flare connection
mm
6.35
9.52
Flare connection
Diameter (OD)
mm
Diameter (OD)
mm
9.52
Heat Insulation
12.7
15.9
VP25 (O.D. 32 / I.D. 25)
Foamed polystyrene/polyethylene
• Split Sky Air • Indoor Units
3
• Indoor Units • R-410A • FCQ-C8VEB
2
Specifications
2-1 Technical Specifications
Decoration Panel
FCQ35C8VEB
FCQ50C8VEB
FCQ60C8VEB
Model
Colour
Dimensions
mm
50
W
mm
950
mm
950
D
kg
5.5
Model
BYCQ140CW1W
Colour
Pure White (RAL 9010)
H
mm
50
W
mm
950
mm
950
D
Weight
kg
5.5
Model
BYCQ140CGW1
Colour
Dimensions
FCQ100C8VEB FCQ125C8VEB FCQ140C8VEB
Pure White (RAL 9010)
H
Weight
Dimensions
FCQ71C8VEB
BYCQ140CW1
Pure White (RAL 9010)
H
mm
130
W
mm
950
D
mm
950
Weight
kg
5.5
Air Filter
Resin net with mold resistance
Standard Accessories Item
Installation and operation manual
Drain hose
Clamp for drain hose
Washer for hanger bracket
Screws
Installation guide
Insulation for fitting
Sealing pads
Drain sealing pad
2-2 Electrical Specifications (50Hz)
Power Supply
Current
FCQ35C8VEB
4
FCQ60C8VEB
FCQ71C8VEB
FCQ100C8VEB FCQ125C8VEB FCQ140C8VEB
1~
Frequency
Hz
50
Voltage
V
220-440
-10
Voltage range
Min.
%
Voltage range
Max.
%
10
Minimum circuit amps (MCA)
A
9.75
Maximum fuse amps (MFA)
A
10
2-3 Electrical Specifications (60Hz)
Power Supply
FCQ50C8VEB
Phase
FCQ35C8VEB
Phase
19.75
17.0
20
FCQ50C8VEB
FCQ60C8VEB
25.0
32
FCQ71C8VEB
1~
Frequency
Hz
60
Voltage
V
220
Voltage range
Min.
%
-10
Voltage range
Max.
%
10
• Split Sky Air • Indoor Units
24.7
FCQ100C8VEB FCQ125C8VEB FCQ140C8VEB
• Indoor Units • R-410A • FCQ-C8VEB
3
Safety device settings
FCQ35-140C8
Safety devices
35
50
60
71
100
125
140
PC board fuse
250V 5A
250V 5A
250V 5A
250V 5A
250V 5A
250V 5A
250V 5A
Fan motor thermal fuse
FCQ
°C
---
---
---
---
---
---
---
Fan motor thermal protector
°C
Off: 108 ±5
(On: 96 ±15)
Off: 108 ±5
(On: 96 ±15)
Off: 108 ±5
(On: 96 ±15)
Off: 108 ±5
(On: 96 ±15)
Off: 108 ±5
(On: 96 ±15)
Off: 108 ±5
(On: 96 ±15)
Off: 108 ±5
(On: 96 ±15)
Drain pump fuse
°C
145
145
145
145
145
145
145
3TW28921-3
• Split Sky Air • Indoor Units
5
• Indoor Units • R-410A • FCQ-C8VEB
4
Options
FCQ35-140C8VEB
OPTIONS
Item
Model
1
Decoration panel
2
Long life replacement filter
3
Fresh air intake kit (20% fresh air)
4
Sealing member of air discharge outlet
FCQ35
FCQ50
FCQ60
FCQ71
FCQ100
FCQ125
FCQ140
FCQH71
FCQH100
FCQH125
FCQH140
FCQH100
FCQH125
FCQH140
BYCQ140CW1 / BYCQ140CW1W *3 / BYCQ140CGW1 *5,*6
Non-woven type
KAFP551K160
Chamber type
KDDQ55C140
KDBHQ55C140
CONTROL SYSTEMS
Item
1
Model
Remote control
FCQ35
Wireless
FCQ50
FCQ60
FCQ71
FCQ100
FCQ125
H/P
BRC7F532F
C/O
BRC7F533F
FCQ140
FCQH71
BRC1D528
Wired
BRC1E51A7 *4
2-1 Wiring adaptor for electrical appendices (1)
KRP1BA57 *1
2-2 Wiring adaptor for electrical appendices (2)
KRP4AA53 *1
2-3 Wiring adaptor (hour meter)
EKRP1C11 *1
3
Remote sensor
4
Installation box for adapter PCB
KRCS01-4
5
Central remote control
DCS302CA51
6
Unified ON/OFF control
DCS301BA51
7
Electrical box with earth terminal (2 blocks)
8
Schedule timer
DST301BA51
9
Remote on/off
EKRORO2
KRP1H98
KJB212AA
3TW32359-1B
NOTES
*1.
*2.
*3.
*4.
*5.
*6.
Installation box is necessary for these adapters.
All options are supplied as kit.
The BYCQ140CW1W white insulations.
Be informed that formation of dirt on white insulations is visibly stronger and that it is consequently not advised to install the BYCQ140CW1W decoration panel in environments exposed to
concentrations of dirt.
Included languages are: English, German, French, Dutch, Spanish, Italian, Greek, Portuguese, Russian and Turkish.
To be able to control the BYCQ140CGW1 the controller BRC1E* is needed.
The BYCQ140CGW1 is not compatible with Mini-VRV, Multi and Split Non-Inverter Outdoor units.
FCQ35-140C8
Max fresh air intake volume table
The maximum intake air flow volume is following table.
If the intake air flow volume is too large, the operating sound may rise or detection of the indoor unit suction
temperature may be affected.
FCQ∼C8VEB
Max fresh air intake volume (m/min.)
35
2.5
50
2.5
60
2.7
71
3.2
100
4.3
125
4.3
140
4.3
The rise of operating sound at with fresh air intake kit
The rise sound from nominal sound pressure level (dBA)
Nominal sound
pressure level
Fresh air intake volume (m`/min)
6
4D057910
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-C8VEB
5
Dimensional drawing & centre of gravity
5-1
Dimensional drawing for standard panel
FCQ35-71C8
860-910 (Ceiling opening)
950
SEE NOTE 4
710 (Suspension position
420
300 or less
SEE NOTE 3
O.D. ø 32 /I.D. ø 26
MODEL
FCQ35
FCQ50-60
FCQ71
213
420
VIEW A
Description
ø A flare connection
ø B flare connection
VP25 (O.D. ø 32 /I.D. ø 25)
A
6.35
6.35
9.52
B
9.52
12.7
15.9
139
Drain side
Name
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Power supply entry hole
Transmission wiring entry hole
Air discharge opening
Air suction grille
Corner decoration cover
Drain hose
Knock out hole
75
950
780 (Suspension position
860-910 (Ceiling opening)
Piping side
Nr
1
2
3
4
5
6
7
8
9
10
EXTERNAL
SURFACE
LIGHT
SEE NOTE 6
840
55
55
340
840
125
165
214
35
SEE NOTE 4
SEE NOTE 4
1500mm
or more (*)
200mm
or more
1500mm
or more (*)
1500mm
or more (*)
200mm
or more
NOTES
1
2
3
OTHER UNIT
1500 or more
2000 or more
4000 or more
1500 or more
(installation space)
Hanging bolt
4 x M8~M10
35
280
330
VENTILATOR
55
130
55
175
50
40
204
10
850
Adjustable (0-675)
VIEW B
Location of the nameplates
4
- Unit body: on the control box cover.
- Decoration panel: on the panel frame at the motor side under the corner cover
5
When installing an optional accessory, refer to the installation drawings.
- For the fresh air intake kit an inspection port is necessary
Make sure the spacing between the ceiling and the cassette is no more
than 35mm. MAX ceiling opening: 910mm.
In case of using an infrared remote control, this position will be a signal
6
receiver. Refer to the drawing of the infrared remote control for more detail.
Please respect the distances as shown on the figure
1500mm
or more (*)
(*) In case a discharge opening is closed with the ‘sealing member’ option,
the distance of 1500mm can be reduced to 500mm on the closed side.
When the conditions exceed 30°C and RH 80% in the ceiling or fresh air
is inducted into the ceiling, an additional insulation is required
(polyethylene foam, thickness 10mm or more).
3TW28834-1B
FCQ(H)100-140C8
300 or less
(Ceiling opening)
(Suspension position)
Item
1
2
3
4
5
6
7
8
9
10
see note 4
see note 3
(Ceiling opening)
(Suspension position)
Piping side
Name
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Power supply entry hole
Transmission wiring entry hole
Air discharge opening
Air suction grille
Corner decoration cover
Drain hose
Knock out hole
Remark
ø9.52 (Flare connection)
ø15.90 (Flare connection)
VP25 (ODø32, IDø25)
ODø32, IDø25
Drain side
View A
View B
Please respect the distances as shown on figure below
adjustable
External Ventilator
surface
light
Other unit
1500 or more
see note 4
see note 4
(Suspension position)
Hanging bolt
1500 or more
2000 or more
4000 or more
NOTE
1
2
3
4
5
Location of the nameplates - Unit body: on the control box - Decoration panel: on the panel frame at the motor side under the corner cover
When installing an optional accessory, refer to the installation drawings
For the fresh air intake kit an inspection port is necessary
In case of using a wireles remote control, this position will be a signal receiver. Refer to the drawing of the wireless remote control for more detail.
Make sure the spacing between the ceiling and the cassette is no more than 35mm. Max cailing opening: 910mm.
When the conditions exceed 30°C and RH 80% in the ceiling or fresh air is inducted into the ceiling, an additionalinsulation is required (polyethylene foam,
thickness 10mm or more).
• Split Sky Air • Indoor Units
1500 mm
or more (*)
200 mm
or more
1500 mm
or more (*)
1500 mm
or more (*)
200 mm
or more
1500 mm
or more (*)
(*) In case a discharge opening is closed with
the “sealing member” option, the distance of
1500 mm can be reduced to 500 mm on the
closed side.
3TW28914-1C
7
• Indoor Units • R-410A • FCQ-C8VEB
5
Dimensional drawing & centre of gravity
5-2
Dimensional drawing for auto cleaning panel
)&4&9(%
a&HLOLQJRSHQLQJ
1U
6HHQRWH
6XVSHQVLRQSRVLWLRQ
RUOHVV
6XVSHQVLRQSRVLWLRQ
'UDLQVLGH
a&HLOLQJRSHQLQJ
3LSLQJVLGH
0RGHO
)&4
)&4
)&4);)4
1DPH
/LTXLGSLSHFRQQHFWLRQ
*DVSLSHFRQQHFWLRQ
'UDLQSLSHFRQQHFWLRQ
3RZHUVXSSO\HQWU\KROH
7UDQVPLVVLRQZLULQJHQWU\KROH
$LUGLVFKDUJHRSHQLQJ
$LUVXFWLRQJULOOH
&RUQHUGHFRUDWLRQFRYHU
'UDLQKRVH
.QRFNRXWKROH
$
'HVFULSWLRQ
‘$ÀDUHFRQQHFWLRQ
‘%ÀDUHFRQQHFWLRQ
932'‘,'‘
2'‘,'‘
%
9,(:$
9,(:%
3OHDVHUHVSHFWWKHGLVWDQFHVDVVKRZQRQ¿JXUHEHORZ
$GMXVWDEOHa
([WHUQDO 9HQWLODWRU
VXUIDFH
OLJKW
2WKHUXQLW
RUPRUH
RUPRUH
RUPRUH
6HHQRWH
6HHQRWH
127(6
/RFDWLRQRIWKHQDPHSODWHV
‡ 8QLWERG\RQWKHFRQWUROER[
‡ 'HFRUDWLRQSDQHORQWKHSDQHOIUDPHDWWKHPRWRUVLGHXQGHUWKH
FRUQHUFRYHU
:KHQLQVWDOOLQJDQRSWLRQDODFFHVVRU\UHIHUWRWKHLQVWDOODWLRQGUDZLQJV
‡ )RUWKHIUHVKDLULQWDNHNLWDQLQVSHFWLRQSDUWLVQHFHVVDU\
0DNHVXUHWKHVSDFLQJEHWZHHQWKHFHLOLQJDQGWKHFDVVHWWHLVQRPRUH
WKDQPP0D[FHLOLQJRSHQLQJPP
:KHQWKHFRQGLWLRQVH[FHHGƒ&DQG5+LQGHFHLOLQJRUIUHVK
DLULVLQFOXGHGLQWRWKHFHLOLQJDQDGGLWLRQDOLQVXODWLRQLVUHTXLUHG
SRO\HWK\OHQHIRDPWKLFNQHVVPPRUPRUH
'RHVQRWFRXQWIRUEXLOGLQOLJKW
6SDFHQHHGHGWRHQWHUZLWKYDFXXPFOHDQHUWXEH
.HHSWKHH[KDXVWRIGHFRUDWLRQSDQHOIUHH
RUPRUH
,QVWDOODWLRQVSDFH
+DQJLQJEROW
PPRU
PRUH
PPRU
PRUH
PPRU
PRUH
PPRU
PRUH
,QVWDOODWLRQGLUHFWLRQ
PPRU
PRUH
'XVW
RSHQLQJ
3LSLQJ
PPRU
PRUH
,QFDVHDGLVFKDUJHRSHQLQJLVFORVHGZLWKWKHµVHDOLQJPHPEHU¶RSWLRQ
WKHGLVWDQFHRIPPFDQEHUHGXFHGWRPPRQWKHFORVHGVLGH
3LSLQJ
6XFWLRQ
JULOO
7:
FCQ100-140C8VEB
860~910 (Ceiling opening)
Nr
1
2
3
4
5
6
7
8
9
10
See note 3
710 (Suspension position)
300 or less
780 (Suspension position)
Drain side
860~910 (Ceiling opening)
Piping side
Name
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Power supply entry hole
Transmission wiring entry hole
Air discharge opening
Air suction grille
Corner decoration cover
Drain hose
Knock out hole
VIEW A
Description
Ø9.52 flare connection
Ø15.90 flare connection
VP25 (O.D.Ø32, I.D. Ø25)
O.D.Ø32, I.D. Ø26
VIEW B
Please respect the distances as shown on figure below
Adjustable (0~675)
6.
External
surface
light (*1)
Ventilator
Other unit
256
1500 or more
2000 or more
Hanging bolt
See note 3
See note 3
NOTES
1.
2.
3.
4.
Location of the nameplates:
5.
• Unit body: on the control box.
• Decoration panel: on the panel frame at the motor side under the
corner cover
When installing an optional accessory, refer to the installation drawings.
• For the fresh air intake kit an inspection part is necessary
Make sure the spacing between the ceiling and the cassette is no more
than 35mm. Max. ceiling opening: 910mm
When the conditions exceed 30°C and RH 80% in de ceiling or fresh
air is included into the ceiling, an additional insulation is required
(polyethylene foam, thickness 10mm or more).
1500 or more
(Installation space)
4000 or more
(*1) Does not count for build in light
(*2) Space needed to enter with vacuum-cleaner tube.
(*3) Keep the exhaust of decoration panel free.
1500mm or
more (*4)
200mm or
more (*4)
1500mm or
more (*4)
1500mm or
more (*4)
Installation direction
200mm or
more (*4)
Piping
Dust
opening
Piping
1500mm or
more (*4)
(*4) In case a discharge opening is closed with the ‘sealing member’ option,
the distance of 1500mm can be reduced to 500 mm on the closed side.
Suction
grill
3TW32524-1
8
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-C8VEB
5
Dimensional drawing & centre of gravity
5-3
Dimensional drawing with accessories
FCQ35,50,60,71C8
Service acces panel:
450 x 450 mm or more
(Refer to note 1)
Ventilation resistance in chamber (note 6)
Nr
1
2
3
4
5
Name
Description
Indoor unit
Decoration panel
Suction chamber
Connecting chamber (Right)
Connecting chamber (Left)
Service acces panel:
450 x 450 mm or more
(Refer to note 1)
Static pressure of chamber (Pa)
Installation service access panel
note 3
Pipe connection side
Inlet
T-tube
Field supply
Air flow rate (m3/min)
Drain connection side
View A
note 3
455 (Ceiling opening panel)
Connecting chamber mounting space
NOTES
1
2
3
4
(*) In case a discharge opening is closed with the ‘sealing member’ option, the distance of 1500 mm can be reduced to 500 mm on the closed side
When installing this kit, inspection hatch is necessary.
(It is necessary when servicing.) Either one of
inspection hatches must be installed.
Field construction.
The corner air outlet of this part must be shut.
In case of mounting a duct fan, make sure to use a wiring adapter for
electrical appendices and link with the indoor unit fan.
1
2
The intake air flow rate is recommended to be 20%
or less of the H speed air flow rate.
If the intake air flow rate is too large, the operating
sound may rise or detection of the indoor unit suction temperature may be affected.
It indicates the distance between the T-tube inlet and the
indoor unit inlet when the T-tube is connected.
3D057035
FCQ100,125,140C8
Service acces panel:
450 x 450 mm or more
(Refer to note 1)
Ventilation resistance in chamber (note 6)
Nr
1
2
3
4
5
Name
Description
Indoor unit
Decoration panel
Suction chamber
Connecting chamber (Right)
Connecting chamber (Left)
Service acces panel:
450 x 450 mm or more
(Refer to note 1)
Static pressure of chamber (Pa)
Installation service access panel
note 3
306
Pipe connection side
Inlet
Air flow rate (m3/min)
T-tube
Field supply
Drain connection side
View A
note 3
455 (Ceiling opening panel)
Connecting chamber mounting space
A
NOTES
1
2
3
4
(*) In case a discharge opening is closed with the ‘sealing member’ option, the distance of 1500 mm can be reduced to 500 mm on the closed side.
When installing this kit, inspection hatch is necessary.
(It is necessary when servicing.) Either one of
inspection hatches must be installed.
Field construction.
The corner air outlet of this part must be shut.
In case of mounting a duct fan, make sure to use a wiring adapter for
electrical appendices and link with the indoor unit fan.
1
2
The intake air flow rate is recommended to be 20%
or less of the H speed air flow rate.
If the intake air flow rate is too large, the operating
sound may rise or detection of the indoor unit suction temperature may be affected.
It indicates the distance between the T-tube inlet and the
indoor unit inlet when the T-tube is connected.
3D057034
• Split Sky Air • Indoor Units
9
• Indoor Units • R-410A • FCQ-C8VEB
5
Dimensional drawing & centre of gravity
5-4
Centre of gravity
FCQ35-140C8
Remote control dimensions
Receiver installation procedure
Transmitting part
Receiver
Pipe connection side
Drain connection side
Decoration panel
Remote controller holder installation
procedure (installation to wall surface)
Receiver detail
Liquid crystal
remote control
(wireless)
Remote control holder
Wireless remote control kit for each decoration panel
Wireless remote control kit
BRC7F532F BRC7F533F
Decoration panel
BYCQ140CW1
3D056851
10
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-C8VEB
5
Dimensional drawing & centre of gravity
5-4
Centre of gravity
FCQ35-140C8
Models
FCQ35~71
FCQ100~140
A
202
246
B
60
90
C
409
411
D
358
411
4TW28839-2
• Split Sky Air • Indoor Units
11
• Indoor Units • R-410A • FCQ-C8VEB
6
Piping diagram
FCQ35-140C8
Heat exchanger
Fan
Liquid pipe connection port
Refrigerant flow
Cooling
Heating
Gas pipe connection port
Refrigerant pipe connection port diameters
Model
Gas
FCQ35C8
Ø9.52
FCQ50C8
Ø12.70
FCQ60C8
FCQ71C8
FCQ100C8
Ø15.90
FCQ125C8
FCQ140C8
Liquid
Ø6.35
Ø6.35
Ø9.52
3TW28925-1A
12
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-C8VEB
7
Wiring diagram
7-1
Wiring diagram
FCQ35-140C8VEB
In case of simultaneous operation system
35~140-Class
Indoor unit
(slave)
Indoor unit
(slave)
To outdoor unit
To outdoor unit
Indoor unit
(master)
35~60 CLASS
35~60 CLASS
Norm. emg.
Remote control
Receiver display unit
Central remote control
(note1)
Control box
Wired remote
control
Exept for self
cleaning panel
(note 5)
100~140 CLASS
35~71 CLASS
Indoor unit
Printed circuit board
Printed circuit board (Humidity sensor unit)
Light emitting diode (Service monitor green)
Magnetic relay (M1P)
Motor (Indoor fan)
Motor (Drain pump)
Motor (Swing flap)
Power supply circuit
Thermistor (Air)
Thermistor (Coil)
Signal receiver circuit
Float switch
Selector switch (Emergency)
Signal transmission circuit
Terminal strip
Terminal strip
Ferrite core
A1P
A2P
HAP
KPR
M1F
M1P
M1S
PS
R1T
R2T
RC
S1L
SS1
TC
X1M
X2M
Z1C
: Terminal strip
: Connector
: Field wiring
A3P
A4P
BS1
H1P
H2P
H3P
H4P
SS1
SS2
indoor
Receiver display unit (attached to wireless remote controller)
Printed circuit board
Printed circuit board
Push button (On/off)
Light emitting diode (On-red)
Light emitting diode (Timer-green)
Light emitting diode (Filter sign-red)
Light emitting diode (Defrost - orange)
Selector switch (Main/sub)
Selector switch (Wireless address set)
X24A
X33A
X35A
X70A
Connector for optional parts
Connector (Wireless remote control)
Connector (Adapter for wiring)
Connector (Group control adapter)
Connector (Self cleaning panel)
R1T
SS1
Wired remote control
Thermistor (Air)
Selector switch (Main/sub)
Colors:
RED Red
BLK Black
WHT White
YLW
GRN
ORG
Yellow
Green
Orange
BRN
GRY
BLU
Brown
Grey
Blue
3TW32356-1
NOTES
1.
In case of using a central remote control, connect it to the unit in accordance with th attached installation manual.
2.
X24A, X33A and X335A are connected when the optional accessories are being used.
3.
Remote control model varies according to the combination system, confirm engineering data and catalogs, etc. before connecting.
4.
Confirm the method of setting the selector switch (SS1, SS2) by installation manual and engineering data, etc.
5.
In case of self cleaning panel follow the self cleaning panel installation instruction.
• Split Sky Air • Indoor Units
13
• Indoor Units • R-410A • FCQ-C8VEB
8
Sound data
8-1
Sound pressure spectrum
Octave band sound pressure level dB(0dB=0.0002 μ bar)
FCQ50C8
Octave band sound pressure level dB(0dB=0.0002 μ bar)
FCQ35C8
Hi
Approximate
threshold hearing
for continuous
noise
Hi
Approximate
threshold hearing
for continuous
noise
Low
Octave band center frequency (Hz)
Low
Octave band center frequency (Hz)
4D056856
NOTES
Scale
Over All (dB):
(B, G, N is already rectified)
Operating conditons:
•
•
•
•
A
C
NOTES
Mode
Hi
31.0
37.0
Low
27.0
33.0
Power source: 220~240V 50Hz/220V 60Hz
Cooling: return air temperature: 27°C DB, 19°C WB - outdoor temperature: 35°C DB, 24°C WB
Heating: return air temperature: 20°C DB, 15°C WB - outdoor temperature: 7°C DB, 6°C WB
4 direction discharge
Power level (dB): Hi 49
Measuring place: Anechoic chamber
Location of microphone
Scale
Over All (dB):
(B, G, N is already rectified)
Operating conditons:
•
•
•
•
A
C
1.5m
1.5m
0.3m
Drain up
Mic. position
Mic. position
FCQ71C8
Octave band sound pressure level dB(0dB=0.0002 μbar)
FCQ60C8
Octave band sound pressure level dB(0dB=0.0002 μ bar)
Note: Operation noise differs with operation and ambient conditions.
Hi
Approximate
threshold hearing
for continuous
noise
Hi (cooling)
Hi (Heating)
Scale
Over All (dB):
(B, G, N is already rectified)
Operating conditons:
A
C
Mode
Hi
33.0
39.0
Low
28.0
34.0
Power source: 220-240V 50Hz/220V 60Hz
Cooling: return air temperature: 27°C DB, 19°C WB - outdoor temperature: 35°C DB, 24°C WB
Heating: return air temperature: 20°C DB, 15°C WB - outdoor temperature: 7°C DB, 6°C WB
4 direction discharge
Scale
Over All (dB):
(B, G, N is already rectified)
•
•
•
•
Power level (dB):
Measuring place: Anechoic chamber
Location of microphone
Hi
Cooling Heating
51
52
Drain up
1.5m
Mic. position
Mic. position
Note: Operation noise differs with operation and ambient conditions.
• Split Sky Air • Indoor Units
4D056859
Power source: 220~240V 50Hz/220V 60Hz
Cooling: return air temperature: 27°C DB, 19°C WB - outdoor temperature: 35°C DB, 24°C WB
Heating: return air temperature: 20°C DB, 15°C WB - outdoor temperature: 7°C DB, 6°C WB
4 direction discharge
1.5m
Drain up
A
C
Mode
Hi
Low
Cooling Heating Cooling Heating
28.0
33.0
34.0
34.0
39.0
40.0
Operating conditons:
0.3m
Power level (dB): Hi 51
Measuring place: Anechoic chamber
Location of microphone
0.3m
(Cooling/Heating)
Octave band center frequency (Hz)
4D056858
NOTES
Low
Approximate
threshold hearing
for continuous
noise
Low
Octave band center frequency (Hz)
14
Low
27.0
33.0
Power source: 220~240V 50Hz/220V 60Hz
Cooling: return air temperature: 27°C DB, 19°C WB - outdoor temperature: 35°C DB, 24°C WB
Heating: return air temperature: 20°C DB, 15°C WB - outdoor temperature: 7°C DB, 6°C WB
4 direction discharge
Note: Operation noise differs with operation and ambient conditions.
•
•
•
•
Mode
Hi
31.0
37.0
Power level (dB): Hi 49
Measuring place: Anechoic chamber
Location of microphone
Drain up
0.3m
4D056857
Note: Operation noise differs with operation and ambient conditions.
• Indoor Units • R-410A • FCQ-C8VEB
8
Sound data
8-1
Sound pressure spectrum
Octave band sound pressure level dB(0dB=0.0002 μ bar)
FCQ125C8
Octave band sound pressure level dB(0dB=0.0002 μ bar)
FCQ100C8
Hi
Approximate
threshold hearing
for continuous
noise
Hi
(Cooling)
Low
Approximate
threshold hearing
for continuous
noise
Low
Octave band center frequency (Hz)
Octave band center frequency (Hz)
4D056860
NOTES
Scale
Over All (dB):
(B, G, N is already rectified)
Operating conditons:
•
•
•
•
A
C
NOTES
Mode
Hi
37.0
43.0
Low
32.0
38.0
Power source: 220~240V 50Hz/220V 60Hz
Cooling: return air temperature: 27°C DB, 19°C WB - outdoor temperature: 35°C DB, 24°C WB
Heating: return air temperature: 20°C DB, 15°C WB - outdoor temperature: 7°C DB, 6°C WB
4 direction discharge
Power level (dB): Hi 54
Measuring place: Anechoic chamber
Location of microphone
Scale
Over All (dB):
(B, G, N is already rectified)
Operating conditons:
•
•
•
•
A
C
Mode
Hi
41.0
47.0
Low
35.0
41.0
Power source: 220~240V 50Hz/220V 60Hz
Cooling: return air temperature: 27°C DB, 19°C WB - outdoor temperature: 35°C DB, 24°C WB
Heating: return air temperature: 20°C DB, 15°C WB - outdoor temperature: 7°C DB, 6°C WB
4 direction discharge
Power level (dB): Hi 58
Measuring place: Anechoic chamber
Location of microphone
Drain up
1.5m
1.5m
0.3m
Drain up
0.3m
4D056861
Mic. position
Mic. position
Note: Operation noise differs with operation and ambient conditions.
Note: Operation noise differs with operation and ambient conditions.
Octave band sound pressure level dB(0dB=0.0002 μ bar)
FCQ140C8
Hi (Heating)
Low
(Heating/
cooling)
Approximate
threshold hearing
for continuous
noise
Hi
(cooling)
Octave band center frequency (Hz)
Scale
Over All (dB):
(B, G, N is already rectified)
A
C
Mode
Hi
Low
Cooling Heating Cooling Heating
35.0
41.0
42.0
41.0
47.0
48.0
4D056862
Operating conditons:
•
•
•
•
Power source: 220~240V 50Hz/220V 60Hz
Cooling: return air temperature: 27°C DB, 19°C WB - outdoor temperature: 35°C DB, 24°C WB
Heating: return air temperature: 20°C DB, 15°C WB - outdoor temperature: 7°C DB, 6°C WB
4 direction discharge
Power level (dB):
Measuring place: Anechoic chamber
Location of microphone
Hi
Cooling Heating
58
59
1.5m
0.3m
Drain up
Mic. position
Note: Operation noise differs with operation and ambient conditions.
• Split Sky Air • Indoor Units
15
• Indoor Units • R-410A • FCQ-C8VEB
8
Sound data
8-2
Sound power spectrum
Sound operation level (dB)
FCQ60C8
Sound operation level (dB)
FCQ35-50C8
Octave band center frequency (Hz)
Octave band center frequency (Hz)
4TW28927-1
4TW28947-1
NOTES
1
2
3
4
5
NOTES
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound operation level (A-scale according to IEC).
Reference acoustic intensity 0dB = 10E-6μW/m2
Curve for FCQ35-50C8VEB in cooling mode.
1
2
3
4
5
FCQ100C8
Sound operation level (dB)
Sound operation level (dB)
FCQ71C8
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound operation level (A-scale according to IEC).
Reference acoustic intensity 0dB = 10E-6μW/m2
Curve for FCQ60C8VEB in cooling mode.
Octave band center frequency (Hz)
Octave band center frequency (Hz)
4TW28957-1
4TW28967-1
NOTES
1
2
3
4
5
16
NOTES
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound operation level (A-scale according to IEC).
Reference acoustic intensity 0dB = 10E-6μW/m2
Curve for FCQ71C8VEB in cooling mode.
• Split Sky Air • Indoor Units
1
2
3
4
5
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound operation level (A-scale according to IEC).
Reference acoustic intensity 0dB = 10E-6μW/m2
Curve for FCQ100C8VEB in cooling mode.
• Indoor Units • R-410A • FCQ-C8VEB
8
Sound data
8-2
Sound power spectrum
Sound operation level (dB)
FCQ140C8
Sound operation level (dB)
FCQ125C8
Octave band center frequency (Hz)
Octave band center frequency (Hz)
4TW28977-1
4TW28987-1
NOTES
1
2
3
4
5
NOTES
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound operation level (A-scale according to IEC).
Reference acoustic intensity 0dB = 10E-6μW/m2
Curve for FCQ125C8VEB in cooling mode.
• Split Sky Air • Indoor Units
1
2
3
4
5
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound operation level (A-scale according to IEC).
Reference acoustic intensity 0dB = 10E-6μW/m2
Curve for FCQ140C8VEB in cooling mode.
17
• Indoor Units • R-410A • FCQ-C8VEB
9
Air flow pattern
FCQ35C8
Cooling air velocity distribution
All round air discharge, air flow direction: horizontal
2.7m
2.0m/s
2m
1.5m/s
1.0m/s
0.5m/s
1m
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
Cooling air temperature distribution
All round air discharge, air flow direction: horizontal
2.7m
20°C
2m
22°C
24°C
26°C
1m
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
4D057199
18
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-C8VEB
9
Air flow pattern
FCQ50C8
Cooling air velocity distribution
All round air discharge, air flow direction: horizontal
2.7m
2.0m/s
2m
1.5m/s
1.0m/s
0.5m/s
1m
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
Cooling air temperature distribution
All round air discharge, air flow direction: horizontal
2.7m
20°C
22°C
2m
24°C
26°C
1m
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
4D057201
• Split Sky Air • Indoor Units
19
• Indoor Units • R-410A • FCQ-C8VEB
9
Air flow pattern
FCQ60C8
Cooling air velocity distribution
All round air discharge, air flow direction: horizontal
2.7m
2.0m/s
2m
1.5m/s
1.0m/s
0.5m/s
1m
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
Cooling air temperature distribution
All round air discharge, air flow direction: horizontal
2.7m
20°C
22°C
2m
24°C
26°C
1m
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
4D057203
20
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-C8VEB
9
Air flow pattern
FCQ71C8
Cooling air velocity distribution
All round air discharge, air flow direction: horizontal
2.7m
2.0m/s
2m
1.5m/s
1.0m/s
0.5m/s
1m
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
Cooling air temperature distribution
All round air discharge, air flow direction: horizontal
2.7m
20°C
22°C
2m
24°C
26°C
1m
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
4D057205
• Split Sky Air • Indoor Units
21
• Indoor Units • R-410A • FCQ-C8VEB
9
Air flow pattern
FCQ100C8
Cooling air velocity distribution
All round air discharge, air flow direction: horizontal
3.2m
3m
2.0m/s
1.5m/s
1.0m/s
0.5m/s
2m
1m
4m
3m
2m
1m
0m
1m
2m
3m
0m
4m
Cooling air temperature distribution
All round air discharge, air flow direction: horizontal
3.2m
3m
20°C
22°C
24°C
26°C
2m
1m
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
4D057207
22
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-C8VEB
9
Air flow pattern
FCQ125C8
Cooling air velocity distribution
All round air discharge, air flow direction: horizontal
3.2m
3m
2.0m/s
1.5m/s
1.0m/s
0.5m/s
2m
1m
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
Cooling air temperature distribution
All round air discharge, air flow direction: horizontal
3.2m
3m
20°C
22°C
24°C
26°C
2m
1m
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
4D057209
• Split Sky Air • Indoor Units
23
• Indoor Units • R-410A • FCQ-C8VEB
9
Air flow pattern
FCQ140C8
Cooling air velocity distribution
All round air discharge, air flow direction: horizontal
3.2m
3m
2.0m/s
1.5m/s
1.0m/s
0.5m/s
2m
1m
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
Cooling air temperature distribution
All round air discharge, air flow direction: horizontal
3.2m
3m
20°C
22°C
24°C
26°C
2m
1m
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
4D057211
24
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-C8VEB
9
Air flow pattern
FCQ35C8
Heating air velocity distribution
All round air discharge, air flow direction: horizontal
2.7m
2m
2.0m/s
1.5m/s
1m
1.0m/s
0.5m/s
0.25m/s
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
Heating air temperature distribution
All round air discharge, air flow direction: horizontal
2.7m
2m
28°C
27°C
26°C
25°C
24°C
1m
23°C
22°C
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
4D057198
• Split Sky Air • Indoor Units
25
• Indoor Units • R-410A • FCQ-C8VEB
9
Air flow pattern
FCQ50C8
Heating air velocity distribution
All round air discharge, air flow direction: horizontal
2.7m
2m
2.0m/s
1.5m/s
1m
1.0m/s
0.5m/s
0.25m/s
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
Heating air temperature distribution
All round air discharge, air flow direction: horizontal
2.7m
2m
28°C
27°C
26°C
25°C
24°C
23°C
1m
22°C
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
4D057200
26
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-C8VEB
9
Air flow pattern
FCQ60C8
Heating air velocity distribution
All round air discharge, air flow direction: horizontal
2.7m
2m
2.0m/s
1.5m/s
1m
1.0m/s
0.5m/s
0.25m/s
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
Heating air temperature distribution
All round air discharge, air flow direction: horizontal
2.7m
2m
28°C
27°C
26°C
25°C
24°C
23°C
22°C
1m
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
4D057202
• Split Sky Air • Indoor Units
27
• Indoor Units • R-410A • FCQ-C8VEB
9
Air flow pattern
FCQ71C8
Heating air velocity distribution
All round air discharge, air flow direction: horizontal
2.7m
2m
2.0m/s
1.5m/s
1m
1.0m/s
0.5m/s
0.25m/s
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
Heating air temperature distribution
All round air discharge, air flow direction: horizontal
2.7m
2m
28°C
27°C
26°C
25°C
24°C
23°C
22°C
1m
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
4D057204
28
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-C8VEB
9
Air flow pattern
FCQ100C8
Heating air velocity distribution
All round air discharge, air flow direction: horizontal
3.2m
3m
2m
2.0m/s
1.5m/s
1.0m/s
1m
0.5m/s
0.25m/s
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
Heating air temperature distribution
All round air discharge, air flow direction: horizontal
3.2m
3m
2m
28°C
27°C
26°C
25°C
1m
24°C
23°C
22°C
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
4D057206
• Split Sky Air • Indoor Units
29
• Indoor Units • R-410A • FCQ-C8VEB
9
Air flow pattern
FCQ125C8
Heating air velocity distribution
All round air discharge, air flow direction: horizontal
3.2m
3m
2m
2.0m/s
1.5m/s
1.0m/s
1m
0.5m/s
0.25m/s
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
Heating air temperature distribution
All round air discharge, air flow direction: horizontal
3.2m
3m
2m
28°C
27°C
26°C
25°C
1m
24°C
23°C
22°C
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
4D057208
30
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FCQ-C8VEB
9
Air flow pattern
FCQ140C8
Heating air velocity distribution
All round air discharge, air flow direction: horizontal
3.2m
3m
2m
2.0m/s
1.5m/s
1.0m/s
1m
0.5m/s
0.25m/s
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
Heating air temperature distribution
All round air discharge, air flow direction: horizontal
3.2m
3m
2m
28°C
27°C
26°C
25°C
1m
24°C
23°C
22°C
0m
4m
3m
2m
1m
0m
1m
2m
3m
4m
4D057210
• Split Sky Air • Indoor Units
31
Daikin Europe N.V. is approved by LRQA for its Quality
Management System in accordance with the ISO9001
standard. ISO9001 pertains to quality assurance regarding
design, development, manufacturing as well as to services
related to the product.
The present publication is drawn up by way of information only and does not
constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has
compiled the content of this publication to the best of its knowledge. No
express or implied warranty is given for the completeness, accuracy,
reliability or fitness for particular purpose of its content and the products and
services presented therein. Specifications are subject to change without
prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or
indirect damage, in the broadest sense, arising from or related to the use
and/or interpretation of this publication. All content is copyrighted by Daikin
Europe N.V..
ISO14001 assures an effective environmental
management system in order to help protect human health
and the environment from the potential impact of our
activities, products and services and to assist in
maintaining and improving the quality of the environment.
Naamloze Vennootschap
Zandvoordestraat 300
B-8400 Oostende, Belgium
www.daikin.eu
BE 0412 120 336
RPR Oostende
Daikin Europe N.V. is participating in the EUROVENT
Certification Programme. Products are as listed in the
EUROVENT Directory of Certified Products.
Copyright Daikin
Daikin units comply with the European regulations that
guarantee the safety of the product.
Prepared in Belgium by Lannoo (www.lannooprint.be), a company whose concern for
the environmont is set in the EMAS and ISO 14001 systems.
Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B- 8400 Oostende
Daikin’s unique position as a manufacturer of air
conditioning
equipment,
compressors
and
refrigerants has led to its close involvement in
environmental issues. For several years Daikin has
had the intension to become a leader in the provision
of products that have limited impact on the
environment. This challenge demands the eco design
and development of a wide range of products and an
energy management system, resulting in energy
conservation and a reduction of waste.