Super WISE Router
®
Installation - Commissioning
2015-03-23
Superwise Ro
uter
Super WISE Router
Project Design
The Super WISE Router is well suited for use in smaller
ventilation systems in which zone control is not required,
for example a system involving one ventilation unit per
storey, or in a smaller building. Several Super WISE Routers can be subject to supervision of the same Super WISE
if it is desirable to divide room supervision into several
parts.
Commissioning
The Super WISE Router normally does not need to be
commissioned; requires only to be assigned a Modbus ID.
The Modbus ID is set to 1 on delivery, and is adjustable
via the hand-held thermostat (CONDUCTOR RU or TUNE
Control). For further information about addressing, see
the WISE Project Manual.
Installation
The Super WISE Router can be mounted directly on a wall,
in plant rooms or out in the system.
1
Super WISE Router
Connections
Normally only the power supply and communication for internal Modbus communication
between Super WISE and room products are
connected.
Connect to wiring terminals 5, 6 and 7
(Modbus loop 1) on the Super WISE as well
as 1, 2 and 3 (Modbus loop 2) on the room
products. Connect the 24 V AC supply voltage
to terminals 23 and 24; see the wiring instructions.
Connection to room product,
Wiring terminals 1, 2 and 2
Connection to the Super WISE or Router 2, 3 etc.
Wiring terminals 5, 6 and 7






24 V AC





Terminations Table
Pos. 1 Passive termination. Used when
the product is placed first or last
on the loop and there is one
termination like Position 2 at the
other end.





Pos. 2 Termination via internal pull-up
resistor to ensure correct 0 level.
One of the loop ends must be
terminated in this way.
Pos. 3 Non-terminated. This setting is
used on all units that are not
placed first or last on the loop.







Wiring diagram for the Super WISE Router
AWG24
A→5
B→6
C→7
Router for connection to the Super WISE.
2
Swegon reserves the right to alter specifications.
2015-03-23
www.swegon.com