SDCW_EN

SDCW_EN
Swegon Home Solutions
CASA duct coils for
®
cooling the supply air
Waterborne cooling duct coils
Duct coils for installation in the supply air duct, for cooling the supply air. The lowest coil height is only 255 mm,
which permits installation in a suspended ceiling.
Swegon CASA Smart control technology for ventilation
units aims to regulate indoor air according to the settings.
The control mode and the settings can be changed from a
CASA Smart control panel.
www.swegonhomesolutions.com
HOME VENTILATION
www.swegonhomesolutions.com
Ventilation unit Swegon CASA W3/R3
SDCW 16033W LVI-no 7906555
Ventilation unit Swegon CASA W4/R5
SDCW 20033W LVI-no 7906556
Ventilation unit Swegon CASA W5/R5/W9
SDCW 250K3W LVI-no 7906557
CASA cooling coils
TECHNICAL DATA
•
•
•
•
•
•
•
•
CWK 160 and 200: Three row copper/aluminium coil,
fin spacing 2.5 mm
1024VL: Four row copper/aluminium coil, fin spacing
2.5 mm
Actuator Belimo HRYD24-SR
Temperature sensor T4 604930 cable length 3 m
Casing made of galvanized sheet steel
Stainless steel condensate tray (G½"), drain with freefall
Removable side covers, which facilitates service and
cleaning
Rubber seals in connection collars
H
Three different sized chillers for the supply air duct:
• CASA CWK 160-3-2.5 (Cu 10 mm), whose height
(255 mm) means it can be housed in a suspended
ceiling, among others, in multi-storey buildings.
• CASA CWK 200-3-2.5 ( Cu 22 mm)
• CASA 1024VL (Cu 22 mm)
• Brackets included
• Thermal insulation 10 mm
•
•
•
Maximum operating temperature of 150 degrees
Maximum operating pressure of 1.0 MPa (10 bar)
Valves are selected for the size of the chiller
3-way valve (½" int. g., kvs 0.6) Belimo R3015-P63-S1
(160 and 200 mm cooling coil)
3-way valve (½" int. g., kvs 1.0) Belimo R3015-1-S1
(250 mm cooling coil)
H+8
Included in the delivery:
• Cooling coil
• Actuator with valves
• Requisite sensors
• Instructions
D
CWK 160
H 255
B 326
D 160
1024VL
H 353
B 460
D 250
CWK 200
H 330
B 411
D 200
B
CWK 160
K 276
L 356
CWK 200
K 276
L 356
K
L
1024VL
K 411
L 440
Leave at least 40 cm service space in front of the door.
02
4-6-2015 Swegon reserves the right to make changes.
Function
Venting
TV1
M
SD1
SUPPLY AIR
OUTDOOR AIR
SUPPLY AIR DUCT
24 VDC, 2W
T1
T4
2*0,5
T3
HX
4*0,5
2*0,5
Room sensor
2*0,5
Modular cable PMK20
T8
PRTG
Control panel’s
temperature sensor
Room’s summer temperature
setting e.g. 23 degrees
The function of the duct coil is controlled from a
control panel via an adjustable room temperature
setting. Valve TV1 is controlled by the room
temperature, according to the options:
Operating release for cooling is given based on the CASA
ventilation unit's internal outdoor temperature sensor T1.
The temperature after cooling T4, can, for example, be read
on a Smart panel.
1.
The following applies to the ventilation unit and system:
• Unit equipped with a Smart control system
• Smart control panel with 20 m long modular cable
• At least one, in the outside air duct positioned shut-off
damper SD1, control signal is obtained from the circuit
board 24 VDC, max. 2 W
• Heating and/or condensation insulation of the supply
air duct coil and condensate pipe
• Venting of the pipe system
• Balancing of the pipe system/coil
By a temperature sensor comprised by a CASA
Smart control panel.
2. By a separate room temperature sensor T8
(accessory).
3. By unit's internal extract air temperature
sensor T3.
03
4-6-2015 Swegon reserves the right to make changes.
HOME VENTILATION
www.swegonhomesolutions.com
CASA cooling coils for the supply air duct:
CASA CWK 160-3-2.5 (chilled water 7/12)
l/s
40
H=255, L=356
Pressure loss for air
Output approximately 26→15
Chilled water
Pressure loss
chilled water
The air’s flow to
the coil
m3/h
Pa
kW
l/s
kPa
m/s
140
9
0.7
0.03
5.62
0.5
Airflow
55
200
15
0.9
0.04
8.65
1.23
70
250
22
1.1
0.05
11.68
1.57
CASA CWK 200-3-2.5 (chilled water 7/12)
l/s
55
H=330, L=356
Pressure loss for air
Output approximately 26→15
Chilled water
Pressure loss
chilled water
The air’s flow to
the coil
m3/h
Pa
kW
l/s
kPa
m/s
200
5
1
0.05
2.22
0.67
Airflow
70
250
8
1.3
0.06
4.11
0.85
85
300
11
1.5
0.07
5.59
1.04
100
360
15
1.7
0.08
6.96
1.22
115
410
19
1.8
0.09
8.32
1.4
Chilled water
Pressure loss
chilled water
The air’s flow to
the coil
CASA 1024 VL (chilled water 7/12)
Airflow
H=353, L=440
Pressure loss for air
Output approximately 26→15
l/s
m3/h
Pa
kW
l/s
kPa
m/s
80
290
18
1.3
0.06
10.7
0.89
100
360
26
1.6
0.08
16.6
1.11
120
430
36
2.1
0.08
18.2
1.33
140
500
46
2.4
0.08
18.2
1.56
160
580
61
3
0.14
47.8
1.78
Other sizes are available, please ask for sizing data separately