FDEN-C
9.
CEILING SUSPENSION TYPE
PACKAGED AIR CONDITIONER
Split system, Air cooled
cooling only type
(
FDEN208CEN-S,
FDEN208CEP,
FDEN258CEN,
FDEN308CEP,
FDEN508CES,
)
FDEN208CEP-S,
FDEN258CEN-S,
FDEN258CEP,
FDEN308CES,
FDEN508CEM
FDEN208CEN
FDEN258CEP-S
FDEN308CEN
FDEN408CES
385
FDEN-C
CONTENTS
9.1
GENERAL INFORMATION ........................................................................ 387
9.1.1
Specific features ................................................................................. 387
9.1.2
How to read the model name ............................................................. 387
9.2
SELECTION DATA..................................................................................... 388
9.2.1
Specifications ..................................................................................... 388
9.2.2
Range of usage & limitations ............................................................ 402
9.2.3
Exterior dimensions ........................................................................... 403
9.2.4
Exterior appearance ........................................................................... 411
9.2.5
Piping system ..................................................................................... 412
9.2.6
Selection chart .................................................................................... 413
9.2.7
Noise level ........................................................................................... 416
9.3
ELECTRICAL DATA................................................................................... 418
9.3.1
Electrical wiring .................................................................................. 418
9.4
OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER ............. 425
9.5
APPLICATION DATA ................................................................................. 425
9.6
MAINTENANCE DATA ............................................................................... 425
386
FDEN-C
9.1 GENERAL INFORMATION
9.1.1 Specific features
(1) Less refrigerant charge amount due to use of double phase refrigerant flow system. The total refrigerant charge amount has
been reduced by more than 50%.
(2) The indoor outdoor interconnection signal wiring has been done away with. The microcomputer chip is installed in the indoor
unit. There is no need for the unit to communicate between the outdoor and indoor units so the unit is more resistant to
electromagnetic noise thus the incidence of microcomputer malfunction has been reduced. The compressor in the outdoor
unit has its own self protection function, that reacts according to abnormal high pressure and excessive high temperature.
(3) There are only four power lines between the outdoor and indoor unit. As no signal wire is used there is no need to separate the
power line from the signal line. One cab tyre cable with 4 wires encased in one sheath is enough for conducting the wiring
work between the outdoor unit and the indoor unit. This contributes to simpler wiring work in the field.
(4) The operaion modes are only cooling and fan operation for easier control.
(5) All air supply ports have auto swing louvers. The indoor fan motor has two speeds of high and low.
(6) The controls are wireless residential split air conditioner type remote controller with 4 malfunction modes.
(7) All models have control valves protruding from the outdoor unit for faster flare connection work in the field.
(8) Simple design
With the model change, the design has been completely renewed. A simple and modern form with curves harmonizes more
with the interior. The suction grill also comes in two segments, simplifying the maintenance.
(9) Amazingly quiet operation
Due to adoption of a newly developed silent stream fan, unpleasant operation sound, such as sound made when the fan runs
against the air, has been minimized, thus achieving the trade’s lowest noise level in the weak flow mode.
(10) “Aerowing” louver
In order to make air conditioning more comfortable, an “aerowing” louver has been newly developed by applying MHI’s
advanced aerodynamics, leading to improved air directivity and air conditioning feeling. In the auto swing mode, the louver
angle is optimum from 0 (level) to 75°, thus distributing the refreshing air evenly throughout your room. By working the
remote controller, you can also set the louver angle easily. The sideways blowout angle can also be set manually up to 45°
either right or left side.
9.1.2 How to read the model name
Example: FDEN
20 8 C
EN
Applicable power source ... See the specifications
Cooling only type
Series No.
Product capacity
Model name
FDEN: Ceiling suspension type unit with
wireless remote controller
FDC: Outdoor unit
387
FDEN-C
9.2 SELECTION DATA
9.2.1 Specifications
Model FDEN208CEN-S
FDEN208CEN-S
Model
Item
FDEN208C
Nominal cooling capacity(1)
FDC208CEN3
5000
W
Power source
Operation data(3)
Cooling input
1 Phase, 220/240V, 50Hz
kW
1.77/1.86
Running current (Cooling)
A
8.2/8.0
Power factor (Cooling)
%
98/97
Inrush current (L.R.A)
A
44
Noise level(4)
Exterior dimensions
Height × Width × Depth
dB(A)
Hi:43 Lo:38
52
mm
184 × 1000 × 650
690 × 880 × 290
Net weight
Refrigerant equipment
Compressor type & Q’ty
kg
22
49
–
RM5523GNE4 × 1
–
1.6
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fines & bare tubing
Refrigerant control
Capillary tube
Motor
kW
Starting method
Capillary tube
Refrigerant
R22
Quantity
Refrigerant oil
kg
Holding charged
r
–
0.9 [Pre-charged up to the piping length of 0m]
0.7 (BARREL FREEZE 32 SAM)
High pressure control
–
Air handling equipment
Multiblade centrifugal fan × 2
Fan type & Q’ty
Motor
W
Starting method
Air flow (Standard)
CMM
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Safety equipment
Installation data
Refrigerant piping size
40 × 1
55 × 1
Line starting
Line starting
Hi:14 Lo:10
56
Unavailable
–
Polypropylene net × 2 (washable)
–
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
–
20 (Crank case heater)
Wireless remote control switch
– (Indoor unit side)
W
Room temperature control
Thermostat by electronics
–
Internal thermostat for fan motor.
Frost protection thermostat.
Internal thermostat for fan motor.
Thermostat for discharge temperature.
mm
(in)
Liquid line: φ6.35 (1/4″) Gas line: φ15.88 (5/8″)
Connecting method
Drain hose
Propeller fan × 1
Flare piping
(Connectable with VP20)
Insulation for piping
Accessories
–
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
DB
WB
Cooling
27˚C
19˚C
–
Outdoor air temperature
DB
WB
35˚C
24˚C
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V and 240V respectively.
(4) Indicates the value at mild mode.
388
Standards
ISO-T1, JIS B8616
FDEN-C
Model FDEN208CEP-S
FDEN208CEP-S
Model
Item
FDEN208C
Nominal cooling capacity(1)
FDC208CEP3
5200
W
Operation data(3)
Power source
Cooling input
1 Phase, 220V, 60Hz
kW
1.76
Running current (Cooling)
A
8.3
Power factor (Cooling)
%
96
Inrush current (L.R.A)
A
52
Noise level(4)
Exterior dimensions
Height × Width × Depth
dB(A)
Hi:44 Lo:39
52
mm
184 × 1000 × 650
690 × 880 × 290
Net weight
Refrigerant equipment
Compressor type & Q’ty
kg
22
49
–
RM5520GP4 × 1
–
1.6
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fines & bare tubing
Refrigerant control
Capillary tube
Motor
kW
Starting method
Capillary tube
Refrigerant
R22
Quantity
Refrigerant oil
kg
Holding charged
r
–
0.9 [Pre-charged up to the piping length of 0m]
0.7 (BARREL FREEZE 32 SAM)
High pressure control
–
Air handling equipment
Multiblade centrifugal fan × 2
Fan type & Q’ty
Motor
W
Starting method
Air flow (Standard)
CMM
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Safety equipment
Installation data
Refrigerant piping size
40 × 1
55 × 1
Line starting
Line starting
Hi:14 Lo:10
56
Unavailable
–
Polypropylene net × 2 (washable)
–
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
–
20 (Crank case heater)
Wireless remote control switch
– (Indoor unit side)
W
Room temperature control
Thermostat by electronics
–
Internal thermostat for fan motor.
Frost protection thermostat.
Internal thermostat for fan motor.
Thermostat for discharge temperature.
mm
(in)
Liquid line: φ6.35 (1/4″) Gas line: φ15.88 (5/8″)
Connecting method
Drain hose
Propeller fan × 1
Flare piping
(Connectable with VP20)
Insulation for piping
Accessories
–
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
DB
WB
Cooling
27˚C
19˚C
–
Outdoor air temperature
DB
WB
35˚C
24˚C
Standards
ISO-T1, JIS B8616
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V.
(4) Indicates the value at mild mode.
389
FDEN-C
Model FDEN258CEN-S
FDEN258CEN-S
Model
Item
FDEN258C
Nominal cooling capacity(1)
FDC258CEN3
5700
W
Power source
Operation data(3)
Cooling input
1 Phase, 220/240V, 50Hz
kW
2.04/2.15
Running current (Cooling)
A
9.4/9.4
Power factor (Cooling)
%
99/95
Inrush current (L.R.A)
A
51
Noise level(4)
Exterior dimensions
Height × Width × Depth
dB(A)
Hi:44 Lo:39
52
mm
184 × 1260 × 650
845 × 880 × 340
Net weight
Refrigerant equipment
Compressor type & Q’ty
kg
27
55
–
RM5526GNE4 × 1
–
1.9
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fines & bare tubing
Refrigerant control
Capillary tube
Motor
kW
Starting method
Capillary tube
Refrigerant
R22
Quantity
Refrigerant oil
kg
Holding charged
r
–
1.05 [Pre-charged up to the piping length of 5m]
0.7 (BARREL FREEZE 32 SAM)
High pressure control
–
Air handling equipment
Multiblade centrifugal fan × 4
Fan type & Q’ty
Motor
W
Starting method
Air flow (Standard)
CMM
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Safety equipment(4)
Installation data
Refrigerant piping size
25 × 2
55 × 1
Line starting
Line starting
Hi:16 Lo:10.5
56
Unavailable
–
Polypropylene net × 2 (washable)
–
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
–
20 (Cank case heater)
Wireless remote control switch
– (Indoor unit side)
kW
Room temperature control
Thermostat by electronics
–
Internal thermostat for fan motor.
Frost protection thermostat.
Internal thermostat for fan motor.
Thermostat for discharge temperature.
mm
(in)
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
Connecting method
Drain hose
Propeller fan × 1
Flare piping
(Connectable with VP20)
Insulation for piping
Accessories
–
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
DB
WB
Cooling
27˚C
19˚C
–
Outdoor air temperature
DB
WB
35˚C
24˚C
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V and 240V respectively.
(4) Indicates the value at mild mode.
390
Standards
ISO-T1, JIS B8616
FDEN-C
Model FDEN258CEP-S
FDEN258CEP-S
Model
Item
FDEN258C
Nominal cooling capacity(1)
FDC258CEP3
6200
W
Operation data(3)
Power source
Cooling input
1 Phase, 220V, 60Hz
kW
2.77
Running current (Cooling)
A
12.8
Power factor (Cooling)
%
98
Inrush current (L.R.A)
A
71
Noise level(4)
Exterior dimensions
Height × Width × Depth
dB(A)
Hi:45 Lo:40
52
mm
184 × 1260 × 650
845 × 880 × 340
Net weight
Refrigerant equipment
Compressor type & Q’ty
kg
27
55
–
RM5526GP4 × 1
–
1.9
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fines & bare tubing
Refrigerant control
Capillary tube
Motor
kW
Starting method
Capillary tube
Refrigerant
R22
Quantity
Refrigerant oil
kg
Holding charged
r
–
1.31 [Pre-charged up to the piping length of 5m]
0.7 (BARREL FREEZE 32 SAM)
High pressure control
–
Air handling equipment
Multiblade centrifugal fan × 4
Fan type & Q’ty
Motor
W
Starting method
Air flow (Standard)
CMM
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Safety equipment
Installation data
Refrigerant piping size
25 × 2
55 × 1
Line starting
Line starting
Hi:16 Lo:10.5
56
Unavailable
–
Polypropylene net × 2 (washable)
–
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
–
20 (Cank case heater)
Wireless remote control switch
– (Indoor unit side)
W
Room temperature control
Thermostat by electronics
–
Internal thermostat for fan motor.
Frost protection thermostat.
Internal thermostat for fan motor.
Thermostat for discharge temperature.
mm
(in)
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
Connecting method
Drain hose
Propeller fan × 1
Flare piping
(Connectable with VP20)
Insulation for piping
Accessories
–
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
DB
WB
Cooling
27˚C
19˚C
–
Outdoor air temperature
DB
WB
35˚C
24˚C
Standards
ISO-T1, JIS B8616
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V.
(4) Indicates the value at mild mode.
391
FDEN-C
Model FDEN208CEN
FDEN208CEN
Model
Item
FDEN208C
Nominal cooling capacity(1)
ISO-T1
ISO-T3
ISO-T1
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC206CEN3
5000
4100
1 Phase, 220/240V, 50Hz
2.08/2.11
9.9/9.7
96/91
2.34/2.36
11.0/10.8
97/91
47
W
kW
A
%
kW
A
%
A
dB(A)
Hi:43 Lo:38
59
mm
184 × 1000 × 650
615 × 850 × 290 + 30
kg
22
55
–
RC5520ENE1 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
1.49
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
R22
W
CMM
W
0.9 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
Multiblade centrifugal fan × 2
Propeller fan × 1
40 × 1
Line starting
Hi:14 Lo:10
Unavailable
Polypropylene net × 2 (washable)
Rubber sleeve (for fan motor)
–
55 × 1
Line starting
42
–
–
Rubber mount (for compressor)
–
Wireless remote control switch
Thermostat by electronics
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
Liquid line: φ6.35 (1/4″) Gas line: φ15.88 (5/8″)
Flare piping
(Connectable with VP20)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
–
–
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
WB
19˚C
DB
35˚C
WB
24˚C
ISO-T1, JIS B8616
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V and 240V respectively.
(4) Indicates the value at mild mode.
392
Standards
DB
27˚C
FDEN-C
Model FDEN208CEP
FDEN208CEP
Model
Item
FDEN208C
Nominal cooling capacity(1)
ISO-T1
ISO-T3
ISO-T1
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC206CEP
5200
4500
1 Phase, 220V, 60Hz
2.06
9.6
98
2.32
10.9
97
50
W
kW
A
%
kW
A
%
A
dB(A)
Hi:44 Lo:39
59
mm
184 × 1000 × 650
615 × 850 × 290 + 30
kg
22
44
–
RC5520EPE1 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
1.31
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
R22
W
CMM
W
1.15 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
Multiblade centrifugal fan × 2
Propeller fan × 1
40× 1
Line starting
Hi:14 Lo:10
Unavailable
Polypropylene net × 2 (washable)
Rubber sleeve (for fan motor)
–
55 × 1
Line starting
44
–
–
Rubber mount (for compressor)
–
Wireless remote control switch
Thermostat by electronics
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
Liquid line: φ6.35 (1/4″) Gas line: φ15.88 (5/8″)
Flare piping
(Connectable with VP20)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
–
–
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
Standards
DB
27˚C
WB
19˚C
DB
35˚C
WB
24˚C
ISO-T1, JIS B8616
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V.
(4) Indicates the value at mild mode.
393
FDEN-C
Model FDEN258CEN
FDEN258CEN
Model
Item
FDEN258C
Nominal cooling capacity(1)
ISO-T1
ISO-T3
ISO-T1
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC256CEN3
5900
4900
1 Phase, 220/240V, 50Hz
2.58/2.62
12.6/13.2
93/83
2.76/2.80
13.4/14.0
94/83
64
W
kW
A
%
kW
A
%
A
dB(A)
Hi:44 Lo:37
59
mm
184 × 1260 × 650
615 × 850 × 290 + 30
kg
27
55
–
RC5527ENE1 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
1.87
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
R22
W
CMM
W
1.35 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
Multiblade centrifugal fan × 4
Propeller fan × 1
25× 2
Line starting
Hi:16 Lo:10.5
Unavailable
Polypropylene net × 2 (washable)
Rubber sleeve (for fan motor)
–
55 × 1
Line starting
42
–
–
Rubber mount (for compressor)
–
Wireless remote control switch
Thermostat by electronics
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
Flare piping
(Connectable with VP20)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
–
–
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
WB
19˚C
DB
35˚C
WB
24˚C
ISO-T1, JIS B8616
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V and 240V respectively.
(4) Indicates the value at mild mode.
394
Standards
DB
27˚C
FDEN-C
Model FDEN258CEP
FDEN258CEP
Model
Item
FDEN258C
Nominal cooling capacity(1)
ISO-T1
ISO-T3
ISO-T1
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC256CEP3
6200
5200
1 Phase, 220V, 60Hz
2.68
12.4
98
3.06
14.4
97
66
W
kW
A
%
kW
A
%
A
dB(A)
Hi:45 Lo:40
59
mm
184 × 1260 × 650
615 × 850 × 290 + 30
kg
27
56
–
RC5528EPE1 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
1.68
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
R22
W
CMM
W
1.35 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
Multiblade centrifugal fan × 4
Propeller fan × 1
25 × 2
Line starting
Hi:16 Lo:10.5
Unavailable
Polypropylene net × 2 (washable)
Rubber sleeve (for fan motor)
–
55 × 1
Line starting
44
–
–
Rubber mount (for compressor)
–
Wireless remote control switch
Thermostat by electronics
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
Flare piping
(Connectable with VP20)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
–
–
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
Standards
DB
27˚C
WB
19˚C
DB
35˚C
WB
24˚C
ISO-T1, JIS B8616
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V.
(4) Indicates the value at mild mode.
395
FDEN-C
Model FDEN308CEN
FDEN308CEN
Model
Item
FDEN308C
Nominal cooling capacity(1)
ISO-T1
ISO-T3
ISO-T1
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC306CEN3
7100
5700
1 Phase, 220/240V, 50Hz
3.08/3.12
15.6/16.3
90/80
3.27/3.31
16.6/17.3
90/80
89
W
kW
A
%
kW
A
%
A
dB(A)
Hi:45 Lo:39
56
mm
184 × 1260 × 650
844 × 950 × 340
kg
27
67
–
RC5532ENE1 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
2.24
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
R22
W
CMM
W
1.3 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
Multiblade centrifugal fan × 4
Propeller fan × 1
35× 2
Line starting
Hi:16.5 Lo:11.5
Unavailable
Polypropylene net × 2 (washable)
Rubber sleeve (for fan motor)
–
60 × 1
Line starting
54
–
–
Rubber mount (for compressor)
–
Wireless remote control switch
Thermostat by electronics
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
Flare piping
(Connectable with VP20)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
–
–
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
WB
19˚C
DB
35˚C
WB
24˚C
ISO-T1, JIS B8616
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V and 240V respectively.
(4) Indicates the value at mild mode.
396
Standards
DB
27˚C
FDEN-C
Model FDEN308CEP
FDEN308CEP
Model
Item
FDEN308C
Nominal cooling capacity(1)
ISO-T1
ISO-T3
ISO-T1
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC306CEP3
7100
5700
1 Phase, 220V, 60Hz
3.05
14.2
98
3.28
15.3
97
78
W
kW
A
%
kW
A
%
A
dB(A)
Hi:46 Lo:40
59
mm
184 × 1260 × 650
844 × 950 × 340
kg
27
67
–
RC5533EPE1 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
1.87
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
R22
W
CMM
W
1.3 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
Multiblade centrifugal fan × 4
Propeller fan × 1
35 × 2
Line starting
Hi:16.5 Lo:11.5
Unavailable
Polypropylene net × 2 (washable)
Rubber sleeve (for fan motor)
–
60 × 1
Line starting
56
–
–
Rubber mount (for compressor)
–
Wireless remote control switch
Thermostat by electronics
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
Flare piping
(Connectable with VP20)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
–
–
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
Standards
DB
27˚C
WB
19˚C
DB
35˚C
WB
24˚C
ISO-T1, JIS B8616
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V.
(4) Indicates the value at mild mode.
397
FDEN-C
Model FDEN308CES
FDEN308CES
Model
Item
FDEN308C
Nominal cooling capacity(1)
ISO-T1
ISO-T3
W
ISO-T1
kW
A
%
kW
A
%
A
dB(A)
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC306CES3
7100/7700
5700/6000
3 Phase, 380-415V 50Hz or 380V 50Hz/415V 50Hz, 380V 60Hz
2.84/2.85/3.37
5.3/5.3/6.1
81/75/84
3.03/3.04/3.60
5.7/5.7/6.6
81/74/83
43
Hi:45/46 Lo:39/40
59
mm
184 × 1260 × 650
844 × 950 × 340
kg
27
67
–
RC5538ESE1 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
2.24
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
R22
W
CMM
W
1.3 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
Multiblade centrifugal fan × 4
Propeller fan × 1
35 × 2
Line starting
Hi:16.5 Lo:11.5
Unavailable
Polypropylene net × 2 (washable)
Rubber sleeve (for fan motor)
–
60 × 1
Line starting
54/56
–
–
Rubber mount (for compressor)
–
Wireless remote control switch
Thermostat by electronics
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
Flare piping
(Connectable with VP20)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
–
–
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
27˚C
29˚C
19˚C
19˚C
35˚C
46˚C
24˚C
24˚C
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 380/415V 50Hz and 380V 60Hz respectively.
(4) Indicates the value at mild mode.
398
Standards
ISO-T1, JIS B8616
ISO-T3, SASO
FDEN-C
Model FDEN408CES
FDEN408CES
Model
Item
FDEN408C
Nominal cooling capacity(1)
ISO-T1
ISO-T3
W
ISO-T1
kW
A
%
kW
A
%
A
dB(A)
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC406CES3
10200/11300
8900/9900
3 Phase, 380-415V 50Hz or 380V 50Hz/415V 50Hz, 380V 60Hz
3.74/3.74/4.61
7.3/7.3/8.6
78/71/81
4.08/4.08/5.11
7.9/7.9/9.3
78/72/83
45
Hi:49/50 Lo:43/43
57
mm
239 × 1260 × 650
1250 × 950 × 340
kg
34
80
–
RC5547ESE1 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
2.61
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
R22
W
CMM
W
1.55 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
Multiblade centrifugal fan × 3
Propeller fan × 2
35 + 55
Line starting
Hi:26 Lo:19
Unavailable
Polypropylene net × 3 (washable)
Rubber sleeve (for fan motor)
–
60 × 2
Line starting
100/110
–
–
Rubber mount (for compressor)
–
Wireless remote control switch
Thermostat by electronics
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
Liquid line: φ9.52 (3/8″) Gas line: φ19.05 (3/4″)
Flare piping
(Connectable with VP20)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
–
–
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
27˚C
29˚C
19˚C
19˚C
35˚C
46˚C
24˚C
24˚C
Standards
ISO-T1, JIS B8616
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 380/ 415V 50Hz and 380V 60Hz respectively.
(4) Indicates the value at mild mode.
399
FDEN-C
Model FDEN508CES
FDEN508CES
Model
Item
FDEN508C
Nominal cooling capacity(1)
ISO-T1
ISO-T3
W
kW
A
%
kW
A
%
A
dB(A)
ISO-T3 ISO-T1
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC506CES3
12500/14000
10600/11900
3 Phase, 380-415V 50Hz or 380V 50Hz/415V 50Hz, 380V 60Hz
4.82/4.82/5.78
9.8/9.8/10.8
75/68/81
5.37/5.37/6.38
11.1/11.1/11.8
74/67/82
68
Hi:50/51 Lo:44/45
59
mm
239 × 1470 × 650
1250 × 950 × 340
kg
40
85
–
RC5563ESE2 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
3.73
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
R22
W
CMM
W
1.85 [Pre-charged up to the piping length of 5m]
2.07 (SUNISO 3GS)
High pressure regulator valve
Multiblade centrifugal fan × 4
Propeller fan × 2
55 × 2
Line starting
Hi:28 Lo:20
Unavailable
Polypropylene net × 3 (washable)
Rubber sleeve (for fan motor)
–
60 × 2
Line starting
100/110
–
–
Rubber mount (for compressor)
40 (Crank case heater)
Wireless remote control switch
Thermostat by electronics
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
Liquid line: φ9.52 (3/8″) Gas line: φ19.05 (3/4″)
Flare piping
(Connectable with VP20)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
–
–
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
WB
19˚C
DB
35˚C
WB
24˚C
ISO-T1, JIS B8616
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 380/415V 50Hz and 380V 60Hz respectively.
(4) Indicates the value at mild mode.
400
Standards
DB
27˚C
FDEN-C
Model FDEN508CEM
FDEN508CEM
Model
Item
FDEN508C
Nominal cooling capacity(1)
ISO-T1
ISO-T3
W
ISO-T1
kW
A
%
kW
A
%
A
dB(A)
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC506CEM3
12500/14000
11900
3 Phase, 230V 50Hz, 220V 60Hz
4.59/5.51
14.8/16.2
78/89
6.03
17.5
90
108
Hi:50/51 Lo:44/45
59
mm
239 × 1470 × 650
1250 × 950 × 340
kg
40
85
–
RC5559EME2 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
3.36
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
R22
W
CMM
W
1.8 [Pre-charged up to the piping length of 5m]
2.07 (SUNISO 3GS)
High pressure regulator valve
Maltiblade centrifugal fan × 4
Propeller fan × 2
55 × 2
Line starting
Hi:28 Lo:20
Unavailable
Polypropylene net × 3 (washable)
Rubber sleeve (for fan motor)
–
60 × 2
Line starting
100/110
–
–
Rubber mount (for compressor)
40 (Crank case heater)
Wireless remote control switch
Thermostat by electronics
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
Liquid line: φ9.52 (3/8″) Gas line: φ19.05 (3/4″)
Flare piping
(Connectable with VP20)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
–
–
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
Standards
DB
27˚C
WB
19˚C
DB
35˚C
WB
24˚C
ISO-T1, JIS B8616
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 230V,50Hz and 220V,60Hz respectively.
(4) Indicates the value at mild mode.
401
FDEN-C
9.2.2 Range of usage & limitations
Models
Item
FDEN208, 258 (FDC208, 258 type)
FDEN208~508 (FDC206~506 type)
Indoor return air temperature
(Upper, lower limits)
Refer to the selection chart
Outdoor air temperature
(Upper, lower limits)
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Power source voltage
Max. 30m
Max. 20 m (Outdoor unit is higher)
Max. 15 m (Outdoor unit is lower)
Rating ± 10%
Voltage at starting
Min. 85% of rating
Frequency of ON-OFF cycle
Max. 10 times/h
ON and OFF interval
Max. 3 minutes
402
Max. 15m
) 50
(
20
30
35
10
1160 [900]
5mm
or more
20
55
11
Left exit
Left exit
(piping
& wiring )
Rear exit
75
drain
(piping
& wiring ) ( piping )
18
70
(piping
& wiring )
)
34
45
80
195
195
225
248
135
(Liq.)
(Gas)
(Drain)
75
18
Drain piping
connection
Drain piping connection
18 75
Liquid piping
Gas piping
Note (1) The slope of drain piping inside the unit is able to take
incline of 10 mm.
650
570
275
Holes for suspension bolt
(12 x 17 x 4 pcs.)
605
5
208: ø6.35 (1/4˝)
Liquid piping 258, 308: ø9.52 (3/8˝)
Gas piping ø15.88 (5/8")
30 Drain (Connectable with VP20)
Indication board
37
Right exit
(
Top exit
ref. piping
& wiring
Note (1) The [ ] value dimension for models FDEN208C.
150mm
or more
Obstacles
100mm
or more
20
30
Air outlet grille
(Automatic louver)
10
50
Piping & wiring draw out holes
Air inlet grille
Air filter
1200 [940]
1260 [1000]
(Holes for suspension bolt)
Space for installation & servicing
30
Drain
Side panel
)
The brackets face interior
When the unit is suspended
beneath the ceiling
(
7
15
Holes for
suspension bolts
(12 × 17 × 4 pcs.)
34
184
150
15
94
1244 [984]
46
(Holes for suspension bolt)
10
The brackets face out
When the unit is half
recessed above the ceiling
300mm
or more
20 70
46
135
290
31
20
15
FDEN-C
9.2.3 Exterior dimensions
(1) Indoor unit
Models FDEN208C, 258C, 308C
Unit: mm
403
Side panel
35
10
5mm
min
(
)
Right exit
piping
& wiring
Note (1) The [ ] value dimension for models FDEN408C
150mm
min
)
34
80
66
Gas piping ø19.05 (3/4")
30
(
)(
(
)
Left exit
piping
& wiring
Rear exit Left exit
piping
drain
& wiring
piping
)
Drain (Connectable with VP20)
55
29 Liquid piping ø9.52 (3/8")
Indication board
(Automatic louver)
Piping & wiring draw out holes
Top exit
ref. piping
& wiring
(
30
20
(12 × 17 × 4pcs.)
Air outlet grille
10
50
174
650
570
196
225
266
135
5
(Liq.)
(Gas)
(Drain)
75
18
Drain piping
Connection
Drain hole connection
18 75
Liquid piping
Gas piping
Note (1) The slope of drain piping inside the unit is able to take
incline of 10 mm.
275
584
94
Holes for suspension bolts
(12 × 17 × 4pcs.)
Models FDEN408C, 508C
Obstacles
100mm
min
Ceiling suspension installation
Air inlet grille
Air filter
1410 [1200]
1470 [1260]
(Holes for suspension bolt)
1370 [1160]
Space for installation & servicing
30
Drain
30
20
the unit is sus( When
pended beneath the ceiling )
The brackets face interior
50
239
the unit is half
( When
recessed above the ceiling )
Holes for
suspension bolts
15
135
89
150
15
46
1451 [1244]
37
(Holes for suspension bolt)
20 70
15
300mm
min
7
290
31
20
10
404
46
The brackets face out
FDEN-C
Unit: mm
FDEN-C
(2) Remote controller
(a) Wireless remote controller
Unit: mm
COOL DRY FAN
FAN HI LO
FILTER
°C
ON AM
PM
TEMP
ON/OFF
161.5
MODE
OFF AM
PM
60
20.5
(b) Indication board of indoor unit
Remote controller
signal receiver
405
FDEN-C
(3) Outdoor unit
Models FDC208CEN3, 208CEP3
Unit: mm
40
53
40
Liquid piping:ø6.35 (1/4")
(Flare connecting)
Gas piping:ø15.88 (5/8")
(Flare connecting)
95
Liquid piping:ø6.35 (1/4")
(Flare connecting)
Terminal block
Gas piping:ø15.88 (5/8")
(Flare connecting)
A
351
311
40
50
Opening for piping and
electric wiring
50
50
Opening for piping
and electric wiring
195
10
195
110
690
110
Opening for electric wiring
15
50
27
50
880
150
70
15
103
50
40
35
290
35
Opening for piping
and electric wiring
55
15
330
150
15
Electric wiring
Opening for
electric wiring
Holes for anchor bolt
(M10 ⳯ 4 pcs.)
580
150
55
50
335
260
15
Holes for drain
(ø20 ⳯ 3 pcs.)
15
50
40
VIEW A
Minimum allowable space to the obstacles
Unit:mm
Required space for maintenance and air flow
L3
L2
Air inlet
L4
Air
inlet
L1
( Maintenance
)
space
406
Air outlet
Installation
type
1
2
L1
Open
Open
500
L2
300
5
Open
L3
100
150
100
L4
5
5
5
Mark
3
Notes
(1) Avoid the location where four sides are entirely
surrounded by walls.
(2) Fix the unit by anchor bolts without fail.
Restrict the protrusion length of anchor bolt to
15 mm and under.
(3) When strong wind blows against the unit, direct
the discharge port at a right angle to the wind
direction.
(4) Secure the space of 1 m and over at the top of
unit.
(5) Make the height of obstruction wall in front of
discharge port lower than the height of unit.
FDEN-C
Models FDC258CEN3, 258CEP3
Unit: mm
Liquid piping: ø9.52 (3/8")
(Flare connecting)
53
40
Gas piping: ø15.88 (5/8")
(Flare connecting)
40
95
Terminal block
Liquid piping: ø9.52 (3/8")
(Flare connecting)
110
195
50
50
10
195
460
110
845
Gas piping: ø15.88 (5/8")
(Flare connecting)
Opening for
electric wiring
Opening for
electric wiring
Opening for piping
and electric wiring
50
40
50
27
15
Opening for piping
and electric wiring
50
880
15
35
103
70
Opening for piping
and electric wiring
40
50
222
50
47
340
35
55
380
15
Electric wiring
150
15
150
Holes for anchor bolt
(M10 ⫻ 4 pcs.)
580
150
15
50
15
50
Holes for drain
(ø9.52 ⫻ 3pcs.)
310
VIEW A
Required space for maintenance and air flow
Minimum allowable space to the obstacles
Unit:mm
L3
L2
Installation
type
Air inlet
L4
Air
inlet
L1
Maintenance
space
Air outlet
1
2
3
L1
Open
Open
500
L2
300
5
Open
L3
100
150
100
L4
5
5
5
Mark
Notes
(1) Avoid the location where four sides are entirely
surrounded by walls.
(2) Fix the unit by anchor bolts without fail. Restrict
the protrusion length of anchor bolt to 15 mm
and under.
(3) When strong wind blows against the unit, direct the discharge port at a right angle to the
wind direction.
(4) Secure the space of 1 m and over at the top of
unit.
(5) Make the height of obstruction wall in front of
discharge port lower than the height of unit.
407
FDEN-C
Models FDC206CEN3, 206CEP3, 256CEN3, 256CEP3
Unit: mm
30
Anchor bolts
(M10 × 4pcs.)
19
30
307
19
170
345
510
25
170
33
850
30
290
615
Terminal block
Gas piping: ø15.88 (5/8")
(Flare connecting)
65 105
Liquid piping: 206 type · ø6.35 (1/4") 256 type · ø9.52 (3/8")
(Flare connecting)
206 type: 125
256 type: 145
35
128
Opening for
electric wiring
15
87
Required space for maintenance and air flow
Minimum allowable space to the obstacles
Unit:mm
Air inlet L3
L2
500 mm
Air
inlet
Air outlet
L1
Maintenance space
Installation
type
Obstacles
Mark
1
2
L1
Open
100
L2
100
Open
L3
100
500
Notes
(1) Fix the unit with anchor bolts.
(2) Strong wind must not be directed to
the air outlet.
(3) Free space over the unit must be
larger than 1 m.
(4) The unit should not be surrounded by
obstructions in all direction.
At least one direction around the unit
must be free.
408
FDEN-C
Models FDC306CEN3, 306CEP3, 306CES3
Unit: mm
Anchor bolts
(M10 × 4 pcs.)
Required space for maintenance and air flow
L2
Air inlet
Unit:mm
L3
Installation
type
500
Obstacles
Air
inlet
Air outlet
Minimum allowable space to the obstacles
L1 Maintenance
space
1
2
3
L1
Open
Open
500
L2
300
0
Open
L3
100
150
100
Mark
Notes
(1) Fix the unit with anchor bolts.
(2) Strong wind must not be directed to the air
outlet.
(3) Free space over the unit must be larger than
1 m.
(4) The unit should not be surrounded by
obstructions in all direction.
At least one direction around the unit must be
free.
409
FDEN-C
Models FDC406CES3, 506CES3, 506CEM3
Unit: mm
Required space for maintenance and air flow
Minimum allowable space to the obstacles
Unit:mm
Installation
type
1
2
3
L1
Open
Open
500
L2
300
0
Open
L3
150
300
150
Mark
Notes
(1) Fix the unit with anchor bolts.
(2) Strong wind must not be directed to the air
outlet.
(3) Free space over the unit must be larger than
1 m.
(4) The unit should not be surrounded by obstructions in all direction.
At least one direction around the unit must be
free.
410
FDEN-C
9.2.4 Exterior appearance
(1) Indoor unit
Gray
(Vertical lins)
Ceramic white
(Front panel)
Gray
(Frame)
(2) Outdoor unit
Models FDC208CEN3, 208CEP3
Ceramic white
(Side panel)
Ceramic white
(Air inlet louver)
Ceramic white
(Front panel)
Models FDC258CEN3, 258CEP3
Polar white
Models FDC206CEN3, 206CEP3
256CEN3, 256CEP3
Polar white
Polar white
Models FDC306CEN3, 306CEP3
306CES3
Models FDC406CES3, 506CES3
506CEM3
Polar white
Polar white
411
FDEN-C
9.2.5 Piping system
Models FDEN208CEN-S, 208CEP-S, 258CEN-S, 258CEP-S
Check joint
Service valve
Indoor unit
Outdoor unit
(Flare connecting)
Gas line
(φ15.88)
Thermistor
(Th1–A)
Thermostat
(23Td)
Heat
exchanger
Thermistor
(Th1–R)
Heat
exchanger
Compressor
Solenoid
valve
SV
Accumulator
(
Liquid line
208:φ6.35
258:φ9.52
)
Check joint
Capillary tube
Stralner
Service valve
(Flare connecting)
Models FDEN208CEN, 208CEP, 258CEN, 258CEP, 308CEN, 308CEP, 308CES, 408CES, 508CES, 508CEM
Indoor unit
Outdoor unit
ø15.88
(208~308:
408, 508: ø19.05)
ø6.35
(208:
258~508: ø9.52)
Preset point of the protective devices
Part name
Thermistor
(for frost prevention)
412
Mark
Equipped
unit
All models
ThI-R
Indoor unit
OFF 2.5°C
ON 10°C
FDEN-C
9.2.6 Selection chart
Correct the cooling capacity in accordance with the conditions as follows. The net cooling capacity can be obtained in the
following way.
Net capacity = Capacity shown on specification × Correction factors as follows.
(1) Coefficient of cooling capacity in relation to temperatures
Coefficient of cooling capacity
in relation to temperature (˚CD.B.)
(a) Only case of ISO-T1 models
Cooling
Cooling operation
Outdoor air D.B.
temperature (˚CD.B.)
Applicable range
ISO-T1 Standard condition
Indoor air W.B. temperature (˚CW.B.)
413
FDEN-C
Cooling operation
Outdoor air D.B.
temperature (˚CD.B.)
Coefficient of cooling capacity
in relation to temperature (˚CD.B.)
Only case of ISO-T3 and SASO models
ISO-T1 Standard condition
Indoor air W.B. temperature (˚CW.B.)
Table of bypass factor
Model
Item
Air flow
Hi
Lo
FDEN208 type
FDEN258 type
FDEN308 type
FDEN408·508 type
0.031
0.016
0.030
0.013
0.036
0.018
0.018
0.010
(2) Correction of cooling capacity in relation to air flow rate control (fan speed)
Coefficient: 1.00 at High, 0.95 at Low
414
FDEN-C
(3) Correction of cooling capacity in relation to one way length of refrigerant piping
It is necessary to correct the cooling capacity in relation to the one way equivalent piping length between the indoor
and outdoor units.
(50/60Hz)
Cooling
Equivalent piping length(1)
5
10
15
20
FDEN208 type
1.0
0.995
0.995/0.99
0.99/0.985
FDEN258 type
1.0
0.995
0.99
0.985
0.98
FDEN308 type
1.0
0.99
0.98/0.975
0.97/0.965
FDEN408 type
1.0
0.995/0.99
0.985/0.98
0.98/0.97
FDEN508 type
1.0
0.99/0.985
0.975/0.97 0.965/0.955
m
25
30
35
0.985/0.98 0.985/0.975
0.98/0.97
0.975
0.97
0.96/0.95
0.95/0.94
0.94/0.925
0.97/0.96
0.965/0.95 0.955/0.94
0.95/0.94
0.94/0.925 0.925/0.91
Note (1) Equivalent piping length can be obtained by calculating as follows.
208, 258, 308 series [φ15.88(5/8″)]: Equivalent piping length = Real piping length + (0.10 × Number or bends in piping)
408, 508, series [φ19.05(3/4″)]: Equivalent piping length = Real piping length + (0.15 × Number of bends in piping)
[Equivalent piping length < Limitation length of piping + 5m]
(4) When the outdoor unit is located at a lower height than the indoor unit in cooling operation, the following
values should be subtracted from the values in the above table.
Height difference between the indoor unit and
outdoor unit in the vertical height difference
5m
10m
15m
Adjustment coefficient
0.01
0.02
0.03
Piping length limitations
Model
FDEN208, 258 (FDC208, 258 type)
Item
Max. one way piping length
FDEN208 ~ 508 (FDC206~506 type)
30m
20m (Outdoor unit is higher)
15m
Max. vertical height difference
15m (Outdoor unit is lower)
Note (1) Values in the table indicate the one way piping length between the indoor and outdoor units.
How to obtain the cooling capacity
Example : The net cooling capacity of the model FDEN308CEN with the air flow “High”, the piping length of 15m, the outdoor unit
located 5m lower than the indoor unit, indoor wet-bulb temperature at 19.0 ˚C and outdoor dry-bulb temperature 35 ˚C is
Net cooling capacity
= 7100 ×
1.00 ×
(0.98 - 0.01) ×
1.0
=
6887 w
FDEN308CEN
Air flow
“High”
Length 15m.
Height difference 5 m
Factor by air
temperatures
415
FDEN-C
9.2.7 Noise level
Notes (1) The data are based on the following conditions.
Ambient air temperature:
Indoor unit 27˚C DB, 19˚C WB.
Outdoor unit 35˚C DB.
Indoor unit
Measured based on JIS B 8616
Outdoor unit
Measured based on JIS B 8616
Mike position: at highest noise level
in position as below
Distance from front side
1m
Height
1m
Mike position as below
1m
Unit
1m
Mike (front & at low point)
(1) Indoor unit
Model FDEN208C (50Hz)
Model FDEN208C (60Hz)
Noise level 43 dB (A) at HIGH
38 dB (A) at LOW
70
50
N50
40
40
N40
30
30
N30
N2
0
20
250
500
1000
2000
20
8000
4000
60
N60
50
50
N50
40
40
N40
30
30
N2
N30
0
20
63
125
Mid octave band frequency (Hz)
250
500
1000
2000
Model FDEN258C (60Hz)
70
50
50
N50
40
40
N40
30
30
N30
20
1000
2000
4000
Sound pressure level
(Standard 0.0002µ bar) dB
Sound pressure level
(Standard 0.0002µ bar) dB
60
N60
500
20
8000
60
N60
50
50
N50
40
40
N40
30
30
N2
N30
0
20
63
125
250
500
1000
2000
60
N60
50
50
N50
40
40
N40
30
30
N30
1000
2000
Mid octave band frequency (Hz)
416
4000
1000
2000
60
60
N60
50
50
N50
40
40
N40
30
30
N2
N30
0
20
20
8000
63
125
250
500
1000
2000
20
8000
50
Noise level 50 dB (A) at HIGH
44 dB (A) at LOW
70
70
60
60
50
N50
40
40
N40
30
30
N30
20
63
125
250
500
1000
2000
Mid octave band frequency (Hz)
20
8000
Model FDEN508C (50Hz)
N60
0
4000
Mid octave band frequency (Hz)
60
N2
20
8000
4000
70
70
N70
N70
Sound pressure level
(Standard 0.0002µ bar) dB
Sound pressure level
(Standard 0.0002µ bar) dB
60
500
4000
70
70
250
500
70
Noise level 50 dB (A) at HIGH
43 dB (A) at LOW
N70
20
250
N70
Model FDEN408C (60Hz)
70
125
125
Noise level 46 dB (A) at HIGH
40 dB (A) at LOW
60
Noise level 49 dB (A) at HIGH
43 dB (A) at LOW
63
30
N30
N2
0
Mid octave band frequency (Hz)
Model FDEN408C (50Hz)
0
30
63
70
Mid octave band frequency (Hz)
N2
40
N40
N70
60
250
40
Model FDEN308C (60Hz)
70
N70
125
50
N50
Noise level 45 dB (A) at HIGH
39 dB (A) at LOW
Noise level 45 dB (A) at HIGH
40 dB (A) at LOW
63
50
Mid octave band frequency (Hz)
Model FDEN308C (50Hz)
70
N2
0
N60
20
20
8000
4000
60
60
Mid octave band frequency (Hz)
Sound pressure level
(Standard 0.0002µ bar) dB
125
60
N70
4000
20
8000
Sound pressure level
(Standard 0.0002µ bar) dB
63
Sound pressure level
(Standard 0.0002µ bar) dB
Sound pressure level
(Standard 0.0002µ bar) dB
60
N60
50
70
70
N70
N70
60
Noise level 44 dB (A) at HIGH
39 dB (A) at LOW
Noise level 44 dB (A) at HIGH
39 dB (A) at LOW
70
70
Sound pressure level
(Standard 0.0002µ bar) dB
70
Model FDEN258C (50Hz)
60
N60
50
50
N50
40
40
N40
30
30
N2
N30
0
20
63
125
250
500
1000
2000
Mid octave band frequency (Hz)
4000
20
8000
FDEN-C
(2) Outdoor unit
Model FDEN508C (60Hz)
Model FDC208CEN3
Noise level 51 dB (A) at HIGH
45 dB (A) at LOW
Noise level 52 dB (A)
70
70
60
60
N60
50
50
N50
40
40
N40
30
30
N30
20
125
250
500
1000
2000
50
N50
40
40
N40
30
30
N2
N30
0
20
20
8000
4000
50
63
125
250
500
1000
2000
Model FDC206CEN3
Noise level 59 dB (A)
70
N60
50
50
N50
40
40
N40
30
30
N30
20
500
1000
2000
70
20
8000
4000
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
63
125
250
500
1000
Noise level 52 dB (A)
2000
50
N50
40
N40
30
30
N30
20
250
500
1000
2000
4000
Sound pressure level
(Standard 0.0002µ bar) dB
Sound pressure level
(Standard 0.0002µ bar) dB
60
40
60
N60
50
50
N50
40
40
N40
30
30
63
N30
0
125
250
500
1000
2000
50
50
N50
40
40
N40
30
30
N30
20
4000
Sound pressure level
(Standard 0.0002µ bar) dB
Sound pressure level
(Standard 0.0002µ bar) dB
60
2000
60
50
50
N50
40
40
N40
30
30
N30
N2
0
63
2000
125
250
500
1000
4000
20
8000
70
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
63
125
250
500
1000
2000
4000
20
8000
70
70
2000
4000
20
8000
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
63
125
250
500
1000
2000
4000
20
8000
Mid octave band frequency (Hz)
Models FDC506CES3, 506CEM3
Noise level 59 dB (A)
70
70
70
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
2000
Mid octave band frequency (Hz)
4000
20
8000
Sound pressure level
(Standard 0.0002µ bar) dB
Sound pressure level
(Standard 0.0002µ bar) dB
1000
N70
N60
N70
1000
500
Noise level 59 dB (A)
60
Noise level 57 dB (A)
500
250
Mid octave band frequency (Hz)
Mid octave band frequency (Hz)
70
250
125
70
20
8000
20
20
8000
Model FDC406CES3
125
30
N30
N2
0
63
70
Mid octave band frequency (Hz)
63
30
N70
N60
1000
40
N40
Noise level 59 dB (A)
60
500
4000
70
70
250
40
Model FDC306CES3
N70
125
50
N50
Mid octave band frequency (Hz)
Noise level 56 dB (A)
63
50
N70
Model FDC306CEP3
0
60
N60
Noise level 59 dB (A)
20
20
8000
Model FDC306CEN3
N2
60
Mid octave band frequency (Hz)
60
N2
20
8000
4000
20
70
Mid octave band frequency (Hz)
70
2000
N70
N60
50
1000
70
Noise level 59 dB (A)
60
500
Model FDC256CEP3
N70
125
20
8000
4000
70
70
250
70
60
Model FDC256CEN3
70
63
125
Mid octave band frequency (Hz)
Model FDC258CEP3
0
30
N30
N2
0
N70
60
Mid octave band frequency (Hz)
N2
30
63
N70
60
250
40
N40
Noise level 52 dB (A)
70
Sound pressure level
(Standard 0.0002µ bar) dB
Sound pressure level
(Standard 0.0002µ bar) dB
60
125
40
Model FDC258CEN3
N70
63
50
N50
Noise level 59 dB (A)
70
0
50
Mid octave band frequency (Hz)
Model FDC206CEP3
N2
60
N60
20
20
8000
4000
60
Mid octave band frequency (Hz)
Mid octave band frequency (Hz)
Sound pressure level
(Standard 0.0002µ bar) dB
63
60
N60
Sound pressure level
(Standard 0.0002µ bar) dB
0
70
N70
Sound pressure level
(Standard 0.0002µ bar) dB
N2
Sound pressure level
(Standard 0.0002µ bar) dB
Sound pressure level
(Standard 0.0002µ bar) dB
60
Noise level 52 dB (A)
70
70
N70
N70
Sound pressure level
(Standard 0.0002µ bar) dB
70
Model FDC208CEP3
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
63
125
250
500
1000
2000
Mid octave band frequency (Hz)
4000
20
8000
417
Y/GN
WH
U
R
2 Cc
51C
1
R
52C
W BK
T
RD
CnM
Mark
Cc
CFI
CFO
CH
CM
CnA~W
F
FMI
FMO
LED1
LED2
LM
SV
SW
BL
23Td
SV
CnM
CnM
OR OR
FMo
CFo
(49Fo)
OR OR
CnP
CH
CnP
52C
RD
BR
Parts name
Capacitor for CM
Capacitor for FMI
Capacitor for FMO
Crankcase heater
Compressor motor
Connector
Fuse
Fan motor (Indoor unit)
Fan motor (Outdoor unit)
Indication lamp (Green-Run)
Indication lamp (Yellow-Check)
Louver motor
Solenoid coil (for control)
Back up switch (ON/OFF)
Meaning of marks
CM
C S
V
S
BK
BK
BL
N
WH
BR BR
BR
52C
WH
NR
Mark
TB
ThI-A
ThI-R
TrI
VaI
23Td
49FI
49FO
51C
52C
X1~6
NR
Y/GN
BK
WH
RD
3
2
3
2
TB2 TB
1
1
Y/GN
BK
WH
RD
Parts name
Terminal block ( mark)
Thermistor
Thermistor
Transformer
Varistor
Thermostat
Internal thermostat for FMI
Internal thermostat for FMO
Overcurrent relay for CM
Magnetic contactor for CM
Auxiliary relay
Terminal (F)
Surge suppressor
Connector
F (3.15A)
Outdoor unit
WH
BK
RD
RD
RD
WH
WH
BL
BK
BK
9
2
1
X5
X4
X3
FMI1
(49FI)
L H
Mark
BK
BL
BR
GR
OR
RD
WH
Y/GN
Color mark
5
X1
CnJ
CnJ
3
LM
Color
Black
Blue
Brown
Gray
Orange
Red
White
Yellow/Green
CnF2
OR
OR
CF11
X5
X3
CnF2
7 6
X4
X2
X1
Indoor unit
BR
RD
BK
RD
Y/GN
WH WH WH
OR
OR
WH
WH
4
X2
CnQ
Test
SW3
1 2 3 4
BK
CnW1
12V
BR
CnW2
TrI
RD
Printed wiring board
10
8
Val
BK
220/240V
TB1
RD
L
WH
WH
GR
WH
CnT
CnH
418
CnL
Power Source
FDEN208CEN-S
1 Phase 220/240V 50Hz
FDEN208CEP-S
1 Phase 220V 60Hz
(8)
BK
BK
(8)
Receiver
amp
ThI-R
Wireless
remote
controller
SW
LED2
Option
XR5
ThI-A
XR3
XR1
BK
BK
CnB2
LED1
CnL
CnH2
CnN
RD
RD
BK
BK
XR4
XR2
FDEN-C
9.3 ELECTRICAL DATA
9.3.1 Electrical wiring
Models FDEN208CEN-S, 208CEP-S
Y/GN
2
FMo
(49Fo)
Mark
Cc
CFI, 1, 2
CFO
CH
CM
CnA~W
F
FMI1, 2
FMO
LED1
LED2
LM
SV
SW
BL
CFo
SV
CnP
CH
CnP
52C
RD
Parts name
Capacitor for CM
Capacitor for FMI
Capacitor for FMO
Crankcase heater
Compressor motor
Connector
Fuse
Fan motor (Indoor unit)
Fan motor (Outdoor unit)
Indication lamp (Green-Run)
Indication lamp (Yellow-Check)
Louver motor
Solenoid coil (for control)
Back up switch (ON/OFF)
CnM
OR OR
CnM
OR OR
CnM
52C
W BK
T
RD
Meaning of marks
CM
R
V
S
S
Cc
WH
4
C
51C
U
R
23Td
BK
BL BK
WH
WH
BR
BR BR
WH
NR
Mark
TB
ThI-A
ThI-R
TrI
VaI
23Td
49FO
49FI,1,2
51C
52C
X1~5
BR
F (3.15A)
NR
TB2 TB RD
1
1
WH
WH
2
2
BK
BK
3
3
Y/GN
Y/GN
RD
Parts name
Terminal block ( mark)
Thermistor
Thermistor
Transformer
Varistor
Thermostat
Internal thermostat for FMO
Internal thermostat for FMI
Overcurrent relay for CM
Magnetic contactor for CM
Auxiliary relay
Terminal (F)
Surge suppressor
Connector
52C
WH
BK
RD
RD
RD
BL
1
WH
BK
BK
9
2
1
X5
(49FI2)
FMI2
L H
CnF3
CF12
Mark
BK
BL
BR
GR
OR
RD
WH
Y/GN
Color mark
CnF3
OR
OR
X4
(49FI1)
FMI1
L H
OR
OR
Color
Black
Blue
Brown
Gray
Orange
Red
White
Yellow/Green
5
CF11
X5
X3
CnF2
X4
X2
X1
CnF2
7 6
X3
Indoor unit
RD
RD
Y/GN
BR
CnJ
LM
CnJ
3
X1
4
X2
CnQ
BK
CnW1
12V
SW3
1 2 3 4
Test
BR
CnW2
TrI
RD
Printed wiring board
10
8
Val
BK
220/240V
Outdoor unit
Y/GN
BK
WH WH
RD
BK
RD RD
BK BK
WH WH WH
OR
OR
WH
WH
TB RD
L
WH
N
WH
WH
GR
WH
CnT
CnH
CnL
Power Source
FDEN258CEN-S
1 Phase 220/240V 50Hz
FDEN258CEP-S
1 Phase 220V 60Hz
(8)
Wireless
remote
controller
SW
LED2
ThI-R
XR5
ThI-A
XR3
XR1
Receiver
amp
CnB2
LED1
CnL
BK
(8)
BK
RD
RD
CnN
CnH2
BK
BK
BK
BK
XR4
XR2
Option
FDEN-C
Models FDEN258CEN-S, 258CEP-S
419
420
Mark
Cc
CFI
CFO
CM
CnA~W
F
FMI
FMO
LED1
LED2
LM
SW
TB
Parts name
Capacitor for CM
Capacitor for FMI
Capacitor for FMO
Compressor motor
Connector
Fuse
Fan motor (Indoor unit)
Fan motor (Outdoor unit)
Indication lamp (Green-Run)
Indication lamp (Yellow-Check)
Louver motor
Back up switch (ON/OFF)
Terminal block ( mark)
Meaning of marks
Only for
FDEN208CEN
NR
Mark
ThI-A
ThI-R
TrI
VaI
49FI
49C
49FO
52C
X1~5
Thermistor
Thermistor
Transformer
Varistor
Internal thermostat for FMI
Internal thermostat for CM
Internal thermostat for FMO
Magnetic contactor for CM
Auxiliary relay
Terminal (F)
Surge suppressor
Connector
Parts name
Outdoor unit
Mark
BK
BL
BR
GR
OR
RD
WH
Y/GN
Color mark
Color
Black
Blue
Brown
Gray
Orange
Red
White
Yellow/Green
Indoor unit
BK
12V
BR
CnW2
TrI
RD
BK
CnW1
220/240V
Power Source
FDEN208CEN
1 Phase 220/240V 50Hz
FDEN208CEP
1 Phase 220V 60Hz
XR1
Receiver
amp
ThI-A
XR5
XR3
Wireless
remote
controller
SW
LED2
LED1
CnL
CnH2
XR4
XR2
Option
FDEN-C
Models FDEN208CEN, 208CEP
CnT
Mark
Cc
CFI, 1,2
CFO
CM
CnA~W
F
FMI 1,2
FMO
LED1
LED2
LM
SW
TB
Parts name
Capacitor for CM
Capacitor for FMI
Capacitor for FMO
Compressor motor
Connector
Fuse
Fan motor (Indoor unit)
Fan motor (Outdoor unit)
Indication lamp (Green-Run)
Indication lamp (Yellow-Check)
Louver motor
Back up switch (ON/OFF)
Terminal block ( mark)
Meaning of marks
NR
Mark
ThI-A
ThI-R
TrI
VaI
49C
49FO
49FI,1,2
52C
X1~5
Only for
FDEN258CEN, 308CEN
Thermistor
Thermistor
Transformer
Varistor
Internal thermostat for CM
Internal thermostat for FMO
Internal thermostat for FMI
Magnetic contactor for CM
Auxiliary relay
Terminal (F)
Surge suppressor
Connector
Parts name
Outdoor unit
Mark
BK
BL
BR
GR
OR
RD
WH
Y/GN
Color mark
Color
Black
Blue
Brown
Gray
Orange
Red
White
Yellow/Green
Indoor unit
BK
12V
BR
CnW2
TrI
RD
BK
CnW1
220/240V
Power Source
FDEN258CEN, 308CEN
1 Phase 220/240V 50Hz
FDEN258CEP, 308CEP
1 Phase 220V 60Hz
Receiver
amp
XR5
XR3
XR1
Wireless
remote
controller
SW
LED2
LED1
CnL
XR4
XR2
Option
FDEN-C
Models FDEN258CEN, 258CEP, 308CEN, 308CEP
421
CnT
422
Mark
CFI, 1,2
CFO
CM
CnA~W
F
FMI 1,2
FMO
LED1
LED2
LM
SW
TB
Parts name
Capacitor for FMI
Capacitor for FMO
Compressor motor
Connector
Fuse
Fan motor (Indoor unit)
Fan motor (Outdoor unit)
Indication lamp (Green-Run)
Indication lamp (Yellow-Check)
Louver motor
Back up switch (ON/OFF)
Terminal block ( mark)
Meaning of marks
NR
Mark
ThI-A
ThI-R
TrI
VaI
49C
49FO
49FI,1,2
52C
X1~5
Thermistor
Thermistor
Transformer
Varistor
Internal thermostat for CM
Internal thermostat for FMO
Internal thermostat for FMI
Magnetic contactor for CM
Auxiliary relay
Terminal (F)
Surge suppressor
Connector
Parts name
Outdoor unit
Mark
BK
BL
BR
GR
OR
RD
WH
Y/GN
Color mark
Color
Black
Blue
Brown
Gray
Orange
Red
White
Yellow/Green
Indoor unit
BK
12V
BR
CnW2
TrI
RD
BK
CnW1
220/240V
Power Source
3 Phase 380-415V 50Hz/380V 60Hz
Receiver
amp
XR5
XR3
XR1
Wireless
remote
controller
SW
LED2
LED1
CnL
XR4
XR2
Option
FDEN-C
Model FDEN308CES
CnT
Mark
CFI, 1,2
CFO1,2
CH
CM
CnA~W
F
FMI, 1,2
FMO1,2
LED1
LED2
LM
SW
TB
Parts name
Capacitor for FMI
Capacitor for FMO
Crankcase heater
Compressor motor
Connector
Fuse
Fan motor (Indoor unit)
Fan motor (Outdoor unit)
Indication lamp (Green-Run)
Indication lamp (Yellow-Check)
Louver motor
Back up switch (ON/OFF)
Terminal block ( mark)
Meaning of marks
NR
Mark
ThI-A
ThI-R
TrI
VaI
49C
49FO1,2
49FI,1,2
52C
X1~5
Thermistor
Thermistor
Transformer
Varistor
Internal thermostat for CM
Internal thermostat for FMO
Internal thermostat for FMI
Magnetic contactor for CM
Auxiliary relay
Terminal (F)
Surge suppressor
Connector
Parts name
Outdoor unit
Mark
BK
BL
BR
GR
OR
RD
WH
Y/GN
Color mark
Color
Black
Blue
Brown
Gray
Orange
Red
White
Yellow/Green
Indoor unit
BK
12V
BR
CnW2
TrI
RD
BK
CnW1
220/240V
Power Source
3 Phase 380-415V 50Hz/380V 60Hz
Receiver
amp
XR5
XR3
XR1
Wireless
remote
controller
SW
LED2
LED1
CnL
XR4
XR2
Option
FDEN-C
Models FDEN408CES, 508CES
423
CnT
424
Mark
CFI, 1,2
CFO1,2
CH
CM
CnA~W
F
FMI, 1,2
FMO1,2
LED1
LED2
LM
SW
Parts name
Capacitor for FMI
Capacitor for FMO
Crankcase heater
Compressor motor
Connector
Fuse
Fan motor (Indoor unit)
Fan motor (Outdoor unit)
Indication lamp (Green-Run)
Indication lamp (Yellow-Check)
Louver motor
Back up switch (ON/OFF)
Meaning of marks
CnM1
Mark
TB
ThI-A
ThI-R
TrI
VaI
49C
49FI,1,2
49FO1,2
52C
X1~5
CnM2
Parts name
Terminal block ( mark)
Thermistor
Thermistor
Transformer
Varistor
Internal thermostat for CM
Internal thermostat for FMI
Internal thermostat for FMO
Magnetic contactor for CM
Auxiliary relay
Terminal (F)
Connector
Outdoor unit
Mark
BK
BL
BR
GR
OR
RD
WH
Y/GN
Color mark
CnF3
Color
Black
Blue
Brown
Gray
Orange
Red
White
Yellow/Green
Indoor unit
BK
12V
BR
CnW2
TrI
RD
BK
CnW1
220/240V
Power Source
3 Phase 230V 50Hz/220V 60Hz
Receiver
amp
XR5
XR3
XR1
Wireless
remote
controller
SW
LED2
LED1
CnL
XR4
XR2
Option
FDEN-C
Model FDEN508CEM
CnT
FDEN-C
9.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
Except for function relating to heating, same as the unit for FDT(N) heat pump type. See page 241.
9.5 APPLICATION DATA
The application data for the cooling only models are similar to those for the heat pump models. (See page 380.)
9.6 MAINTENANCE DATA
Same as the cooling /heating equipment for FDT(N) heat pump type. Refer to page 271.