Wise11 WiseMP11 ZERO CURRENT AND ZERO VOLTAGE CROSSING AUTOMATIC VOLTAGE

Wise11 WiseMP11 ZERO CURRENT AND ZERO VOLTAGE CROSSING AUTOMATIC VOLTAGE
Wise11
ZERO CURRENT AND ZERO VOLTAGE
CROSSING AUTOMATIC VOLTAGE
STABILIZER
WiseMP11
Non-linear load
Load L
Microprocessor Control
●
Zero current and zero voltage crossing
●
Input voltage is 220 Vac (L-N) +15% -20% for Wise11
and +15% -17.5% for Wise MP11
●
Single Phase 2 Wires Input / Output
Load C
●
Output voltage is 220 Vac (L-N) ± 5% for Wise11 and
and ± 2.5% for Wise MP11
●
Crest factor ratio 3:1
●
LED and digital meter on LCD display
●
Surge, spike, sag and brownout protection
●
EMI/RFI and power line noise protection
●
Overload and short circuit protection
●
Over voltage and under voltage protection
●
Analog Output Volt meter and Amp meter
●
RS-232 for PC communication and remote monitoring (option)
Tap change at
zero current and
zero voltage
I
Tap change at
zero current
I
Tap change at
zero current
I
ZERO CURRENT AND ZERO VOLTAGE CROSSING AUTOMATIC VOLTAGE STABILIZER (LED and LCD DISPLAY)
The most reliable topology of Automatic Voltage Stabilizer for full protect electrical equipment such as factory automation
equipment, medical and scientific equipment, communication equipments, industrial instruments etc.
Wise11 and Wise MP11
ZERO CURRENT AND ZERO VOTAGE CROSSING AUTOMATIC VOLTAGE STABILIZER
SPECIFICATIONS
Wise 0811
MODEL
Wise1011
Wise1511
Wise2011
Wise2511
Wise3011
Wise4011
Wise5011
WiseMP0811 WiseMP1011 WiseMP1511 WiseMP2011 WiseMP2511 WiseMP3011 WiseMP4011 WiseMP5011
RATED POWER
Pf. = 1
SYSTEM
Topology
8 kVA
10 kVA
8 kW
10 kW
15 kVA
20 kVA
25 kVA
30 kVA
40 kVA
50 kVA
15 kW
20 kW
25 kW
30 kW
40 kW
50 kW
Single phase stabilizer with microprocessor controlled
Number of TAP change
4 Taps for Wise xx11
8 Taps for Wise MPxx11
Crossing Technique
INPUT
Zero current and zero voltage crossing
Voltage
220 Vac -20% +15% for Wise xx11
220 Vac -17.5% +15% for Wise MPxx11
OUTPUT
Frequency
50 / 60 Hz ± 6% (auto sensing)
Wave form
Pure sine wave
Voltage
220 Vac ± 5% for Wise xx11
220 Vac ± 2.5% for Wise MPxx11
Frequency
Synchronize with input
Wave form
Pure sine wave (sinusoidal)
Total harmonic distortion
Less than 0.2% THD
Overload capability
100% for continuos load
100% for continuous load
150% for 1 min.
150% for 1 min.
1000% for 1 cycle
Crest factor ratio
3:1
EFFICIENCY
AC to AC (at full load)
SYSTEM
Overload
Automatic shutdown with manual restart or auto restart (selectable)
Over/under voltage
Automatic shutdown with manual restart or auto restart (selectable)
PROTECTION
More than 96%
Short circuit
Circuit breaker
Surge energy dissipation
400 joules (40 kA)
Surge clamping voltage
710 Vp
Power dissipation
100 kHz - 80 MHz
Attenuation
More than 36 dBA
MANUAL
Maintenance bypass
CONTROLS
switch
INDICATOR
5,500,000 W within 100 microsec.
EMI / RFI dissipation
yes
Front panel LED's
AVR, Alarm
LCD Display
Input voltage, input frequency, output voltage, output current, %load, system status
Analog Meter
Output voltage, output current
AUDIBLE ALARM
Overload, over voltage, under voltage
ACOUSTIC NOISE At 1 metre
ENVIRONMENT
Less than 50 dBA
Temperature
0°C to 45°C
Humidity
PHYSICAL
0 - 95% (non-condensing)
W x H x D (cm.)
40 x 90 x 65
TBA
DIMENSIONS
WEIGHT
Approximate in kg.
90
96
101
TBA
Continuous product development is our commitment. In that manner, the above specifications may be changed without prior notice.