Performance and Capacity Guidelines

Performance and Capacity Guidelines
CompactLogix Performance and Capacity
Table of Contents
Section 1: Introduction /CompactLogix System Basics:…………………………..…3
Section 2: Glossary of Terms……………………………………………………….…12
Section 3: CompactLogix CPU Utilization (%CPU) Baseline Testing................. 15
Section 4: 1769 CompactBus I/O RPI Guidelines for the 1769-L3X Family..…... 18
Section 5: CompactBus RPI Effects on %CPU/ Program Execution……………...20
Section 6: Utilizing the Periodic Task and Minimum RPI to Obtain Fastest Possible
Screw-to-Screw Performance: ……………………………………….…................. ..24
Section 7: Periodic and Event Based Tasks………………………………………….26
Section 8: System Overhead Time Slice …………………….………………….…...29
Section 9: Limitations Imposed by Connections ...…….…………………………….36
Section 10: CompactLogix on Ethernet Overview......………..…….…………..….. 39
Section 11: CompactLogix on Ethernet: Connections and Packets Per
Second……………………………………………………………………………………44
Section 12: CompactLogix Ethernet Explicit Messaging……………………….......63
Section 13: CompactLogix on ControlNet Overview………………..…………….…81
Section 14: CompactLogix ControlNet: Explicit Messaging…………………….…..87
Section 15: Bridging Through a CompactLogix Controller………….……...…….....101
Section16: Other CompactLogix Configurations……………………...…….…...…. 103
Section17: Comparing the CompactLogix L3X, L4X, and ControlLogix…….…….104
Section 18: CompactLogix 5370 L3 and Integrated Motion on EtherNet/IP……….106
Appendix A: Table of Message Types (Connected vs Unconnected)…………. .…111
Appendix B: Flex I/O vs. Point I/O Performance Comparison…………………........112
2
CompactLogix Performance and Capacity
Section 1: Introduction/ CompactLogix System Basics
Section 1a: Introduction
The purpose of this document is to provide CompactLogix system performance and
capacity information, along with design considerations, that can be used to achieve
optimized performance from a CompactLogix system.
These recommendations may not be the best solution for all applications, but rather are
guidelines and indications of performance.
This document has had three revisions:
IASIMP-QR007A-EN-P (August 2006) covered the 1769-L3X family of CompactLogix
processors.
IASIMP-QR007B-EN-P (March 2009) added the 1769-L4X family of CompactLogix
processors.
IASIMP-QR007C-EN-P (July 2012) added the 5370 L3 family of CompactLogix
processors.
The CompactLogix family of processors are designed to provide a Logix solution for
low-end to medium applications. Typically these applications are machine-level control
applications that require limited I/O quantities and limited communications capabilities.
The 1769-L3X family consists of the 1769-L31, the 1769-L32C, the 1769-L32CR, the
1769-L32E and the 1769-L35E. The 1768-L4X family consists of the 1768-L43 and
the1768-L45. The 5370 L3 family consists of the 1769-L30ER-NSE, the 1769-L30ER,
the 1769-L30ERM, the 1769-L33ER, the 1769-L33ERM, and the 1769-L36ERM
For a comparison of the 1769-L3X, the 5370 L3, and 1768-L4X Family see Section
17.This section also compares the L4X with the ControlLogix family.
Section 1b: 1769-L3x Family Basics
The 1769-L31 has two serial ports. The 1769-L32C and 1769-L35CR have an
integrated ControlNet port and one serial port. The 1769-L32E and1769-L35E
controllers have an integrated EtherNet/IP port and one serial port.
The 1769-L3X controllers all use the 1769 CompactBus local I/O bus.
Note- the first bank of I/O must contain the controller which must be in the leftmost slot.
3
CompactLogix Performance and Capacity
The power supply distance rating of all 1769 digital and analog I/O modules is eight
modules, allowing them to be placed up to eight slots from the power supply except for
specialty modules.
Power Supply Distance Rating:
1769 Digital Modules
1769 Analog Modules
1769-HSC
1769-SM1
1769-SM2
1769-SDN
1769-ADN
1769-ASCII
8 modules
8 modules
4 modules
6 modules
4 modules
4 modules
5 modules
4 modules
4
CompactLogix Performance and Capacity
1769-L31 Controller
1769-L31 Controller Capabilities
Mix and match any combination of discrete, analog and specialty modules
Up to three banks of local 1769 I/O modules
Connect the banks with 1m or 1ft of cable
Requires one power supply for each bank
Two RS-232 serial ports can be configured for ASCII, DH-485, DF1, and modems
Supports multiple 1769-SDN DeviceNet modules
Removable CompactFlash to store programs, tag values and firmware
L31 Supports
512K Memory
Up to 16 local I/O modules with up to 32 points per digital modules and 8 points
per analog modules
5
CompactLogix Performance and Capacity
1769-L32C and L35CR Controller
1769-L32C and L35CR Controller Capabilities
Mix and match any combination of discrete, analog and specialty modules
Up to three banks of local 1769 I/O modules
Connect the banks with 1m or 1ft of cable
Requires one power supply for each bank
One RS-232 serial port can be configured for ASCII, DH-485, DF1, and Modems
Supports multiple 1769-SDN DeviceNet modules
Removable CompactFlash to store programs, tag values and firmware
L32C supports
750K Memory and a single ControlNet connector
Up to 16 local I/O modules with up to 32 points for digital modules and 8 points
for analog modules
L35CR supports
1.5M Memory and redundant ControlNet connectors
Up to 30 local I/O modules with up to 32 points for digital modules and 8 points
for analog modules
6
CompactLogix Performance and Capacity
1769-L32E and L35E Controller
1769-L32E and L35E Controller Capabilities
Mix and match any combination of discrete, analog and specialty modules
Up to three banks of local 1769 I/O modules
Connect the banks with 1m or 1ft of cable
Requires one power supply for each bank
One RS-232 serial port can be configured for ASCII, DH-485, DF1, and modems
Supports multiple 1769-SDN DeviceNet modules
Removable CompactFlash to store programs, tag values and firmware
L32E: supports:
750K Memory and a single EtherNet/IP port.
Up to 16 local I/O modules with up to 32 points for digital modules and 8 points
for analog modules
L35E supports:
1.5M Memory and a single Ethernet/IP port.
Up to 30 local I/O modules with up to 32 points for digital modules and 8 points
for analog modules,
7
CompactLogix Performance and Capacity
Section 1c:1768-L4X Family Basics
The 1768-L43 and L45 processors are a modular platform consisting of:
The same1769 CompactBus local I/O bus used by the 1769-L3X to the right of
the processor and;
An enhanced 1768 bus to the left. This bus supports up to four 1768 modules
and adds enhanced communications and motion capabilities to the L4X platform.
The following 1768 modules are available:
•
•
•
•
1768-ENBT/EWEB module provides EtherNet/IP connectivity
1768-CNB module provides ControlNet connectivity
1768-CNBR module provides redundant ControlNet connectivity
1768-M04SE SERCOS module.provides up to 4 Axis of Motion capability.
The CompactLogix 1768 power supply requires that a 1768 CompactLogix controller be
installed to power the system. The power supply sends 24V dc to the controller located
in slot 0. The controller converts the 24V dc to 5V dc and 24V dc and distributes it as
needed.
– 5V and 24V power to 1769 I/O modules on the right side of the controller
– 24V power to 1768 modules on the left side of the controller
– Never put a 1769 power supply in the 1768 system.
– Each additional 1769 I/O bank must have its own power supply. Use a
standard 1769 power supply such as 1769-PA4.
Since the 1768-L4X processors use the same 1769 CompactBus as the 1769-L3X
processors, the same rules apply when using the L4X with this bus. The power supply
distance rating of all 1769 digital and analog I/O modules is eight modules, allowing
them to be placed up to eight slots from the power supply except for specialty
modules.
Power Supply Distance Rating:
1769 Digital Modules 8 modules
1769 Analog Modules 8 modules
1769-HSC 4 modules
1769-SM1 6 modules
1769-SM2 4 modules
1769-SDN 4 modules
1769-ADN 5 modules
1769-ASCII 4 modules
8
CompactLogix Performance and Capacity
1768-L43 and L45 Controller
1768-L43 and L45 Controller Capabilities
Mix and match any combination of 1769 discrete, analog and specialty modules
Connect the banks with 1m or 1ft of cable
Requires one power supply for each 1769 bank
One RS-232 serial port can be configured for ASCII, DH-485, DF1, and modems
Supports multiple 1769-SDN DeviceNet modules
Removable compact flash to store programs, tag values and firmware
L43 supports
2M Memory
16 I/O modules with up to 32 points for digital modules and 8 points for analog
modules
Two 1768 network communication modules
4 axis SERCOS system (one SERCOS card supported)
L45 supports:
3M Memory
30 I/O modules with up to 32 points for digital modules and 8 pionts for analog
modules
Two 1768 network communication modules
8 axis SERCOS system (two SERCOS cards supported)
9
CompactLogix Performance and Capacity
A 4-axis system with Kinetix drives supports:
– execution of 4 axes per 1 ms
– velocity bandwidth > 400 Hz and current loop bandwidth > 1000 Hz
– high resolution, unlimited travel, and absolute feedback features
– two feedback ports per Kinetix drive
– optional 2094 Line Interface Module (LIM) as the incoming power source for an
entire control panel
Section 1d: CompactLogix 5370 L3 Family Basics
The L3 controllers all have a USB port and an integrated dual EtherNet/IP port with DLR
connectivity, IEEE-1588 support, and sockets.
The L3 controllers all use the 1769 CompactBus local I/O bus.
Note- the first bank of I/O must contain the controller which must be in the leftmost slot.
The power supply distance rating of all 1769 digital and analog I/O modules is eight
modules, allowing them to be placed up to eight slots from the power supply except for
specialty modules.
Power Supply Distance Rating:
1769 Digital Modules
1769 Analog Modules
1769-HSC
1769-SM1
1769-SM2
1769-SDN
1769-ADN
1769-ASCII
8 modules
8 modules
4 modules
6 modules
4 modules
4 modules
5 modules
4 modules
10
CompactLogix Performance and Capacity
1769-L36ERM Controller
L3 Controller Capabilities
Mix and match any combination of discrete, analog and specialty modules.
Up to three banks of local 1769 I/O modules.
Connect the banks with 1m or 1ft of cable.
Requires one power supply for each bank.
One USB port.
Supports multiple 1769-SDN DeviceNet modules.
Removable SecureDigital (SD) card to store programs, tag values and firmware.
Support for Integrated Motion on EtherNet/IP .
IEEE-1588 Time Synchronization
Socket Support
Choose your controller based on the number of EtherNet/IP I/O nodes it will use on the
network – no need to keep track of CIP connections.
Here is a summary of the L3 capabilities:
CompactLogix L3 5370
Overview
Memory
Local Expansion Modules
EtherNet/IP I/O Nodes
Integrated Motion on EtherNet/IP
L30ER-NSE
L30ER
L30ERM
L33ER
L33ERM
L36ERM
1MB
8
16
No
1MB
8
16
No
1MB
8
16
1-4 Axis
2MB
16
32
No
2MB
16
32
1-8Axis
3MB
30
48
1-16 Axis
11
CompactLogix Performance and Capacity
Section 2: Glossary of Terms
Summary: This section defines terms and concepts important to understand the
performance and capacity information provided in this document.
Background Task: This happens during the System Overhead Time Slice.
Communications, application messaging, I/O monitoring occur in this task.
Buffer: A register or group of registers used for temporary storage of data. Logix has
these three buffer types: Outgoing Unconnected, Incoming Unconnected and Cached.
Cached-This term applies to ladder logic message instructions or messages to HMIs.
These messages are always connected (use an available connection). Therefore, they
will use resources such as buffers, bandwidth and memory even when the message is
done or not executing. 32 cached buffers are available on both the CompactLogix
ControlNet and Ethernet network ports.
Class 1 (Implicit)- refers to any connection that uses an RPI (Requested Packet
Interval). These include I/O and produced/consumed connections. Another name for a
class 1 message is “implicit”. Implicit refers to information (source address, data type,
destination address, etc.) which is implied in the message but not contained in the
message.
Class 3 (Explicit) -refers to any connection that does not use an RPI. Class 3
connections are non time critical. Example: MSG instruction and program upload.
Another name for a class 3 message is “explicit”. Explicit messages include basic
information (source address, data type, destination address, etc.) in every message,
hence they are explicit.
Connected- A message that uses a connection to transfer data to a device. Once the
connection is established, buffers and resources will remain allocated to the message.
The connection will remain open even if the data does not change. When data does
change, data transfer rates are faster since the connection has already been
established.
Connections- A connection is a communication path. Effectively, data passes through
a connection. I/O, messaging, Produced/Consumed tags, RSLinx Connections to PCs
or HMIs all use connections. The number of connections used in a Logix product must
be considered since they take up buffers, resources and memory in both processors
and network cards.
Continuous Task- A task that runs through all its programs and routines continuously,
from top to bottom, unless interrupted by another task. A project does not require a
continuous task, however, you can only configure one per project. All CPU time not
allocated to other operations such as motion, communications and periodic or event
based tasks, is used to execute the programs within this task.
12
CompactLogix Performance and Capacity
CPU Utilization (%CPU)- The CPU utilization (%CPU) is a representation of how much
time the controller is having to perform the sum total of all its functions in the
Continuous Task, including ladder execution, task switching and communications. The
lower the CPU%, the more logic, I/O and communications can be added for processing
by the controller.
Direct Connection- A communication connection used to communicate to I/O in a
remote chassis, specifically analog modules. (Digital modules can also be configured for
direct connections, but typically are configured for rack connections to conserve the
number of connections used by the controller and network cards). Each module with a
direct connection can be configured with its own RPI.
Event Task- Is a user defined task that runs code based upon a trigger of a specific
event. When the event is triggered it interrupts any lower priority tasks, executes one
time, and returns control to the task that was interrupted, at the point it was interrupted.
The trigger for the event based task can be:
• a change of a digital input
• a new sample of analog data
• a consumed tag
• an EVENT instruction
• certain motion operations
Inhibit- Inhibiting a module causes the connection to the module to be broken, and
may result in the loss of data.
NUT -The Network Update Time is the smallest user configurable repetitive time cycle
in milliseconds at which data can be sent on a ControlNet network. The range is 2 to
100 milliseconds and is configured in RSNetWorx for ControlNet.
Periodic Task- Is a user defined task runs code at a user defined time period. When
the end of the time period defined by the user is reached, the task is triggered and
interrupts any lower priority task (either continuous, periodic, or event). All programs
within that task are executed and scanned once, from top to bottom. After this single
scan, an output update is triggered and control is returned to the task that was
interrupted, at the point it was interrupted. Up to 7 periodic tasks can be configured,
each with an interrupt priority and with independent rates.
(Execution rate range (0.1ms-2,000s, in increments of 1ms)).
Produced/Consumed- Type of data format. Each produced tag and each
consumed tag uses a connection.
With Produced/Consumed data multiple nodes can consume the same data at
the same time from a single producer, resulting in more efficient use of
bandwidth. Also, nodes can be synchronized.
13
CompactLogix Performance and Capacity
Benefits over Source/Destination methods:
•
Highly Efficient- No wasted effort delivering data to those who do not require it.
•
Accurate Data - Everyone receives the data at the same time.
•
Deterministic - Length of time to deliver data is independent of the number of
nodes
Rack Optimized Connection- A communication connection a user may choose to use
when using digital I/O in a remote chassis. A rack connection uses only one connection
to the digital I/O in the remote chassis, economizing connections. A rack connection is
available only to digital I/O. (Analog modules use direct connections.) Only one RPI
value can be set to all the modules configured to use the rack connection. (Note, if
diagnostic digital modules are placed in a Rack Optimized Connection, the diagnostic
information will be lost. Use a Direct Connection to save the diagnostic data.)
RPI- Requested Packet Interval -The requested rate of data arrival to or from a
module and a controller. The data will be sent at least this often or the connection will
fail with the Connection Not Scheduled Fault. This value is configured in the properties
for each module when added to the module configuration tree.
Scheduled Connection -allow you to send and to receive data repeatedly at a
predetermined and configured rate on ControlNet. Produced/consumed tags, and
scheduled I/O communication on ControlNet are scheduled connections
A scheduled connection stays open as long as the network, the target, and the
connection originator are alive. If either the target or originator drops off the link, then
the connection is closed and periodically retried by the connection originator.
System Overhead Time Slice-The system overhead time slice is the ratio of the
amount of time spent running the continuous task versus the amount of time running the
background task, which includes handling communication requests.
Uncached- This terms applies to ladder logic message instructions. These messages
use a connection when starting the message and then close the message when
complete, therefore freeing up resources such as buffers, bandwidth and memory.
Unconnected- A message that does not use a connection to transfer data to a device.
Unconnected messages can not be cached.
Unscheduled Connection - are used when data is being produced on demand by
the user program or HMI on ControlNet. MSG instructions and RSLinx message are
examples that use unscheduled connections.
Unscheduled connections can timeout if they are not used within the timeout interval.
Network services will use an unconnected message to close the unscheduled
connection
14
CompactLogix Performance and Capacity
Section 3: CompactLogix CPU Utilization (%CPU)- Baseline Testing
Summary: This section describes the test run to provide a baseline of CompactLogix
CPU usage that will be used as a comparison for the other tests in this document.
Since the CompactLogix controller handles multiple tasks such as I/O, network
communications and messaging, CPU utilization percentage (%CPU), will be used in
this document to measure the load on the controller and to determine the performance
and capacity of the CompactLogix system.
A baseline program was written to determine the CPU utilization percentage using a
cross section of the following instructions:
•
•
•
•
•
•
•
•
•
•
1200 discrete instruction (XIC, XIO, OTE)
50 counter instructions
50 timer instructions
50 multiple instructions
50 add instructions
100 move instructions
50 compare instructions
50 copy instructions
50 FIFO instructions (FFL)
12 JSR instructions
From this program, the CPU utilization (%CPU) was calculated. The %CPU is based on
the number of times the baseline program is executed in 1 second. As the %CPU
calculated increases the controller has to perform more operations and is spending less
time on ladder execution. A ladder program calculates the %CPU.
This identical baseline program was run on a 1769-L35E processor to test the 1769-L3X
platform, a 1768-L45 processor to test the 1768-L4X platform, and a 1769-L36ERM
processor to test the 5370 L3 platform.
1769-L35E (V20): The 1769-L35E (v20) had no I/O or traffic configured for the 1769L3E Ethernet Port , had the System Overhead Time Slice (TS) set to 20%, and had no
RS232 communications. In a CompactLogix controller inhibiting the CompactBus Local
I/O does not actually disable the scanning of the CompactBus, so inhibiting it with a
larger RPI uses less CPU than just inhibiting it alone.
15
CompactLogix Performance and Capacity
Test Results. The baseline results are as follows:
System Overhead Time Slice = 20%
Memory used
140,184 bytes
Memory Available 1,432,680 bytes
Main Task Scan Times
Max 4.21 ms
Last 2.344 m
%CPU processor used
1.0% (typical)
MaxScan = 500; CPUUsed = -6 (ie -0.6%)
1768-L45: The 1768-L45 had no I/O or traffic configured for the 1768-L45 with the
System Overhead Time Slice (TS) set to 20% and had no RS232 communications.
Test Results. The baseline results are as follows:
System Overhead Time Slice = 20%
I/O Memory used
19,084 bytes bytes
I/O Memory Available
486,772 bytes
Data and Logic Memory Used
94,676 bytes
Data and Logic Memory Available 3,051,052 bytes
Main Task Scan Times
Max
3.468ms
Last
2.462ms
%CPU processor used (typical) 0.7 %
MaxScan = 570; CPUUsed = -8 (ie -0.8%)
1769-L36ERM: The 1769-L36ERM had no I/O or traffic configured for the 1769L36ERM with the System Overhead Time Slice (TS) set to 20% and had no USB
communications.
Test Results. The baseline results are as follows:
System Overhead Time Slice = 20%
I/O Memory used
1,264 bytes
I/O Memory Available
1,047,312 bytes
Data and Logic Memory Used
111,272 bytes
Data and Logic Memory Available 3,034,456 bytes
Main Task Scan Times
Max
2.516ms
Last
1.457ms
%CPU processor used (typical) 0.0 %
MaxScan = 890; CPUUsed = -5 (ie -0.5%)
16
CompactLogix Performance and Capacity
Processor Comparison:
Proc
Type
IO Mem
Used
IO Mem
Available
Data &
Logic
Used
Data &
Logic
Available
Max
Scan
CPU
Used
SOTS
(%)
Na
Main
Task
Max
Scan
(ms)
4.21
L35e
140,184
1,432,680
Na
500
-6
20
L45
19,084
486,772
94,676
3,051,052
3.468
570
-8
20
L36ERM
1,264
1,047,312
111,272
3,034,456
2.516
890
-5
20
17
CompactLogix Performance and Capacity
Section 4: 1769 CompactBus I/O RPI Guidelines for the 1769-L3X (Pre V18 Only)
Guideline: If you are using a pre V18 1769-L3X, set the RPI for CompactLocal Bus
modules to 5ms or higher (5ms is default in v16 and V17), unless faster RPIs are
required for your application. See information below for impacts of faster RPIs.
The CompactBus local RPI (Requested Packed Interval) defines the frequency at which
the controller sends and receives all I/O data on the backplane. There is one RPI for
the entire 1769 backplane when using Pre V18 1769-L3X family processors.
(The 1769-L3x V18 and later, 1768-L4X and CompactLogix 5370 L3 families supports
independently set RPIs for each module in the local chassis – see Section 5.)
As you install modules, the minimum backplane RPI may need to be increased to
handle larger amounts of data going across the backplane
This setting can be found in the local CompactBus Properties.
This value range is (1-750ms).
Default is 2ms for V15 of RSLogix 5000 or earlier
Default is 5 ms in V16 of RSLogix 5000.
Minimum settings for the CompactBus local RPI:
These numbers are minimum (fastest) RPI settings. Depending on communications,
program processing, and I/O, a higher RPI may be needed. (See Section 5).
18
CompactLogix Performance and Capacity
*Digital and Analog (any mix):
1-4 modules can be scanned in 1.0ms
5-16 modules can be scanned in 1.5ms
17-30 modules can be scanned in 2.0ms
1769-HSC (High Speed Counter): Add 0.5ms for each used
1769-SDN (DeviceNet Scanner): Add 1.5ms per module
(*Note - Input modules defined with a “F” , ie 1769-IQ16F, at the end of the catalog
number have user selectable filters that can be configured for faster filter rates
(0.0msec- 2.0ms) and can provide faster throughput times. Those modules without the
"F" have fixed 8ms filters, this means that the module can only capture an input signal
of 8ms or more. Anything lower that the filter value will be treated as noise and ignored..
Additional Notes:
These considerations show how fast modules can be scanned. They are not an
indication of screw to screw performance.
The CompactBus Local scan is asynchronous to the program scan. Other
factors, such as program execution duration, affect I/O throughput.
You can always select an RPI that is slower than your calculated minimum RPI
The RPI rule is a conservative benchmark. An RPI set below the recommended
may result in task overruns and unpredictable I/O update behavior
Caution: When using the default RPI of 2ms (in v15 or earlier) be cautious going over 8
modules to assure that you do not slow down your program execution too much for your
particular application.(see Section 5.)
19
CompactLogix Performance and Capacity
Section 5: CompactBus RPI Effects on %CPU /Program Execution
The CPU utilization (%CPU) is a representation of the load on the processor. It takes
into account how much time the controller is having to perform its functions in the
Continuous Task, including code execution and task switching.
The lower the %CPU, the more logic, I/O and communications can be added. Too high
a %CPU, then messaging, HMI communications, uploads and downloads may be
slowed.
The %CPU increases as modules are added to the CompactBus, and slower RPI’s may
need to be considered for your particular application.
Section 5a: 1769-L3X Family (Pre V18)
Guideline: For the Pre V18 L3X Family, set the RPI greater than 5ms if you want the
CompactBus I/O to have the least affect on messaging/HMI/upload and downloads.
(Even if you are using no modules and inhibit the CompactBus, set the RPI to 5ms to
achieve the best utilization.)
The graph below shows the results of testing performed to determine the effects of RPI
on CPU Utilization for the 1769-L35CR
RPI Effects on % CPU
60
CPU Utilization
50
40
No Modules
2 Modules
4 Modules
30
8 Modules
30 modules
20
10
0
1ms
2ms
3ms
4ms
5ms
10ms
15ms
20ms
RPI
(The above chart is only for the 1769 Local CompactBus I/O only. See Baseline test used for this
document).
20
CompactLogix Performance and Capacity
Section 5b: 1769-L3X Family (V18 and Later)
Summary: For the L3X Family (V18 and Later), set the individual modules RPI greater
than 5ms if you want the CompactBus I/O to have the least affect on messaging,HMI,
uploads, and downloads.
The 1769-L3X (V18 and Later) family of processors support individual RPI’s for local
modules. The range for RPI values is 1ms – 750ms; except for the 1769-SDN and
1769-ASCII modules which are 2ms – 750ms. The default RPI value depends on the
module type.
The graph below shows the results of testing performed to determine the effects of RPI
on CPU Utilization for a 1769-L35E V19.11.
70.0%
60.0%
CPU Utilization
50.0%
2 Discrete
2 Analog
40.0%
2 Discrete, 2 Analog
5 Discrete, 3 Analog
30.0%
1 HSC
1 ASCII
20.0%
1 SDN
10.0%
0.0%
1ms
2ms
3ms
4ms
5ms
RPI
21
10ms
15ms
20ms
CompactLogix Performance and Capacity
Section 5c: 5370 L3 Family
Summary: For the 5370 L3 processor family, set the individual modules RPI greater
than 5ms if you want the CompactBus I/O to have the least affect on
messaging,HMI,uploads, and downloads
The 5370 L3 processors support individual RPI’s for local modules. The range for RPI
values is 1ms – 750ms; except for the 1769-SDN module which is 2ms – 750ms.
Default RPI value depends on the module type.
The graph below shows the results of testing performed to determine the effects of RPI
on CPU Utilization for a 1769-L36ERM.
Section 5d: 1768-L4X Family
Summary: The 1768-L4x processor %CPU is minimally affected by either the number
of 1769 CompactBus modules in the rack or the individual RPI’s selected for the
modules
The 1768-L4X processors support individual RPI’s for local modules. The range for RPI
values is 1ms – 750ms; except for 1769-SDN and 1769-ASCII modules which are 2ms
– 750ms. Default RPI value depends on the module type.
22
CompactLogix Performance and Capacity
The graph below shows the results of testing performed to determine the impact of
populating the1769 bus with modules of different types at different RPI values on
%CPU.
The results of the testing show that the 1768-L4x processor is minimally affected by
either the the number of 1769 CompactBus modules being connected or the RPI’s
selected.
23
CompactLogix Performance and Capacity
Section 6: Utilizing the Periodic Task and Minimum RPI to Obtain Fastest
Possible Screw-to-Screw Performance:
Some applications require not only a fast screw-to-screw update but also need to know
screw-to-screw repeatability also known as “Screw-to-Screw Jitter”
The CompactLogix backplane scan is asynchronous to the program execution. I/O
updates can happen anytime throughout the program scan.
Note: Your minimum screw-to-screw times will increase as you add modules to your
system
Section 6a: 1769-L3X Family
Summary: With 4 or less non-specialty modules, the system can handle a 1ms RPI
and 1ms Periodic Task. Average screw-to-screw performance is 2ms. Repeatability or
“Screw-to-Screw Jitter” is 3ms or less. Make sure you set the priority of the Periodic
task greater than 6.
The following shows the results of testing performed to determine min/ max/ typical
screw to screw time possible with 1768-L3X platform. Only the local CompactBus was
used with a 1769-IQ16F/A input module and a 1769-OB16/B output module. RPI was
set to 1ms. 100 samples were taken of an output turning on an input.
Task
Continuous
Priority
15
Throughput
Worse/Best
2.1ms / 1.0ms
Main Task Scan Time
Max/Min
2.5ms / .4ms
-Average screw-to-screw performance is 2ms
-Repeatability or “Screw-to-Screw Jitter” is 3ms or less
Caution:
It is possible to starve the update of your I/O if you set the priority of a Periodic
task higher than the Local CompactBus priority of 6. Higher priority tasks
interrupt lower tasks.
Section 6b: 1769-L4X Family
Summary: With 4 or less non-specialty modules, the system can handle a 1ms RPI.
Average screw-to-screw performance is 1.2ms. Repeatability or “Screw-to-Screw Jitter”
is 2ms or less.
The following shows the results of testing performed to determine min/ max/ typical
screw to screw time possible with 1768-L4X platform. Only the local CompactBus was
24
CompactLogix Performance and Capacity
used with a 1769-IQ16F/A input module and a 1769-OB16/B output module. RPI for
each was set to 1ms.
Task
Continuous
Throughput
Worse/Best
1.9ms / 0.4ms
Priority
15
Main Task Scan Time
Max/Min
1.9ms / .4ms
-Average screw-to-screw performance is 1.2 ms
-Repeatability or “Screw-to-Screw Jitter” is 2ms or less
The histogram chart below displays the distribution of scan time values captured during
L4X testing with 35 samples taken. Typical throughput ranged from .8 – 1.6 ms.
Frequency
Histogram
20
10
Frequency
0
0.4
0.8
1.2
1.6
2
msec
Section 6c: 5370 L3 Family
Summary: With four or less non-specialty modules, the system can handle a 1ms RPI.
Average screw-to-screw performance is 1.287ms. Repeatability or “Screw-to-Screw
Jitter” is 1ms or less.
The following shows the results of testing performed to determine min/ max/ typical
screw to screw time possible with the 5370 L3 platform. Only the local CompactBus was
used with a 1769-IQ16F/A input module and a 1769-OB16/B output module. RPI for
each module was set to 1ms.
Task
Continuous
Priority
15
Throughput
Worse/Best
1.64ms / 0.856ms
Average screw-to-screw performance is 1.287ms
Repeatability or “Screw-to-Screw Jitter” is 1ms or less
25
Main Task Scan Time
Max/Min
1.935ms/0.03ms
CompactLogix Performance and Capacity
Section 7: Periodic and Event Based Tasks
Summary: The priorities the user selects for Periodic/Event Tasks will affect both I/O
throughput (5370 L3 and L3X) and Continuous (Main) Task program scan. The user
needs to determine what is important for his application and adjust the priorities
accordingly. For applications where speed is NOT of great concern, this will not be an
issue.
Section 7a: Introduction
When a project is created in RSLogix 5000, a Continuous Task is automatically
created, called the Main Task. Only one Continuous task is supported in the software.
Optional Periodic and Event based tasks can be created by right clicking on Task and
choosing New task:
26
CompactLogix Performance and Capacity
Logix Priority Task Levels:
Priority level:
Task
1- highest
17 –lowest
Priority
Periodic Task (Ladder)
*(1-15)
Local CompactBus (I/O)
6
NetLinx Class 1 messaging** 6
Continuous Task (Ladder)
15
NetLinx Class 3 messaging** 17
Other Communications
17
Comments
Up to 7 periodic tasks can configured
I/O scan performed at RPI rate (5370 L3 and L3X)
I/O, produced/consumed data
Only one Continuous Task is supported
Explicit Messaging
* The only priorities that can be changed by the user are the priority numbers of
the Periodic tasks.
** The 1769-L3X and 5370 L3 controllers must process these message types, whereas
the1768-L4X/ ControlLogix controllers do not (they have dedicated communication
modules for this function)
The priorities the user selects for Periodic/Event Tasks will affect both I/O throughput
(5370 L3 and L3X) and Continuous (Main) Task program scan. Use of a periodic/event
task will interrupt any programs in the Continuous task, thereby affecting their program
scan.
The user needs to determine what is important for his application and adjust the
priorities accordingly. For applications where speed is NOT of great concern, this will
not be an issue.
Be sure to set the period time larger than the Periodic Tasks execution time and have a
30% null time to be able to service your communications once the task execution is
complete.
Caution:
We do not recommend going below a 1ms Periodic Task. Setting the periodic task
below 1ms may produce excessive task overlaps.
Tip: Triggering an event task from an input event:
1.
2.
3.
Create an event task with the code in it that you need to execute when the event
occurs. Set this to the highest priority.
Create a periodic task at a high priority (but less than the event task) that has just
the code in it that is needed to monitor the event.
Trigger the event task from the periodic when the event condition is met.
27
CompactLogix Performance and Capacity
Section 7b: 1769-L3X Family
Guideline: If your application requires a high amount of communications, only have a
maximum of 1 Periodic Task configured and have it’s priority set to 7 or above. This will
avoid the Periodic Task interrupting the CompactBus I/O scan running at priority level 6.
Test: Effects of Changing Priorities of Periodic Task:
Task
Periodic
Periodic
Periodic
Priority
15
6
1
I/O Throughput
Worse/Best
11.2ms / 0.9ms
11.6ms / 1.6ms
13.9ms / 4.2ms
Main Task Scan Time
Max/Min
3.7ms / 3.2ms
2.9ms / 2.3ms
2.5ms/ 2.1ms
This test was based on the 1769-L35CR baseline program. This time the Main Task, which was
Continuous, was made Periodic with a priority of 6, the same priority as the local CompactBus I/O
updates. The Main Periodic Task was run at a rate of 10 ms. Only the Local CompactBus was
used, with two modules configured (a 1769-IQ16F/A with all filters set to 0ms and a 1769-OB16/B)
both configured for rack-optimized connections at 1ms.
The priorities the user selects for Periodic/Event Tasks will affect both I/O throughput
and program scan. For high speed applications the user needs to determine what is
more important for his application, I/O throughput or program scan, and adjust the
priorities accordingly. For applications where speed is NOT of great concern, this will
not be an issue.
Section 7c: 1768-L4X Family
The L4X processors do not assign a priority to the Local CompactBus I/O task as do the
L3X processors –therefore you do not have to consider this when selecting a task
priority. Remember that your selection still impacts program scan times (as discussed in
Section 7a), however.
Section 7d: 5370 L3 Family
Guideline: If your application requires a high amount of communications, only have a
maximum of one Periodic Task configured and set it’s priority to 7 or above. This will
avoid the Periodic Task interrupting the CompactBus I/O scan running at priority level 6.
The priorities the user selects for Periodic/Event Tasks will affect both I/O throughput
and program scan. For high speed applications the user needs to determine what is
more important for his application, I/O throughput or program scan, and adjust the
priorities accordingly. For applications where speed is NOT of great concern, this will
not be an issue.
28
CompactLogix Performance and Capacity
Section 8: System Overhead Time Slice
Summary: The System Overhead Time Slice, or SOTS, is the ratio of the amount of
time spent running the continuous task versus the amount of time running the
background task, which includes handling communication requests.
Increasing the time slice will interrupt the continuous task to allow for more background
time to communicate to HMIs, perform trending, execute messaging and perform serial
port communications. Setting it too low can starve your communications to HMI,
trending, messaging and serial communications. Setting it too high can increase the
scan time of the programs in the continuous task beyond what is acceptable for the
application.
Changes made in Logix V16 that affects the way the SOTS works are also discussed.
For RSLogix5000 the default value is set to 20% and can be changes in the Properties
of the Controller on the Advanced tab.
⎛ 1 ⎞
The formula used for calculating the time slice is TS % = ⎜
⎟ × 100 , which means that
⎝ CT + 1 ⎠
⎛ 100 ⎞
CT = ⎜
⎟ − 1 , where TS% is the time slice in percent, and CT is the amount of time
⎝ TS % ⎠
spent running the continuous task.
Note this is not the time to scan the continuous task from top to bottom. Many scans of
the continuous task may occur during this time, or only a partial scan of the task may
occur. It is simply the amount of time spent executing the continuous task.
29
CompactLogix Performance and Capacity
This setting only applies to the continuous task in a project. The background task may
be further delayed due to any periodic or motions task interruptions also.
The SOTS can only preempt or interrupt the continuous task. When the SOTS
preempts the continuous task it can only perform the preemption for 1ms before it must
return to the continuous task. That is the SOTS can only run in 1ms intervals of time. If
there is no continuous task in the controller the SOTS will run in the “null” time that is
when no periodic, event, or motion tasks are running.
Changes to the %SOTS will only have an effect on the controller communications
performance if there is a continuous task present. If you have only periodic, event, or
motion tasks in the application, changes to the %SOTS will have no effect.
Examples
Example 1:
The project consists of just one continuous task. There are no periodic tasks or motion.
SOTS is set to 10%. For each 1 msec of background time, the continuous task runs for
9 ms.
Continuous
Task
CT
CT
Background
Task
BT
0
1
2
3
4
5
6
7
8
9
BT
10 11 12 13 14 15 16 17 18 19 20
Time (ms)
Figure 1
The continuous task executes for 9 of every 10 ms, and the background task executes
every 10 ms.
30
CompactLogix Performance and Capacity
Example 2:
The project consists of just one continuous task. There are no periodic tasks or
motion. SOTS is set to 20%.
Continuous
Task
CT
CT
Background
Task
CT
BT
0
1
2
3
4
CT
BT
5
6
7
8
9
BT
BT
10 11 12 13 14 15 16 17 18 19 20
Time (ms)
Figure 2
The continuous task executes for 4 of every 5 ms, and the background task executes
every 5 ms.
Example 3:
The project consists of one continuous task and a periodic task with an interval of
2 ms, and a scan time of 1 ms. SOTS is set to 10%.
Continuous
Task
2
3
4
5
6
7
8
9
1
Background
Task
BT
Periodic
Task
PT
0
1
2
PT
3
4
PT
5
6
PT
7
8
PT
9
PT
PT
PT
PT
10 11 12 13 14 15 16 17 18 19 20
Time (ms)
Figure 3
The numbers in the continuous task line are the accumulated processor time for the
continuous task at the end of the tick.
Both the continuous and background tasks are interrupted by the periodic task. The
SOTS setting still means that the continuous task has to run for a certain number of ms
before the background task can run. So, here, the background task doesn’t get run until
almost 20 ms have elapsed overall and every 20 ms after that, but that is still after just 9
ms of continuous task execution, given the 10% SOTS setting. Remember that the
TS% is a ratio between the continuous task and background task running times, not
between the absolute system time and the background task time. Therefore, as the
continuous task gets interrupted by periodic tasks, the time between background task
updates will increase.
The final kind of task that we will consider is the motion task. It has the highest priority,
so it will interrupt periodic, continuous and background tasks. The period at which the
31
CompactLogix Performance and Capacity
motion task runs is governed by the coarse update rate (CUR). As a rule of thumb,
assume about ½ ms per axis for the actual calculations. Let’s see how it affects the
previous setup.
Example 4:
The project consists of one continuous task and a periodic task with an interval of
2 ms, and a scan time of 1 ms. SOTS is set to 10%.
There are 5 axes of motion with the L4x processor, with a CUR of 5 ms, and
about 2.5 ms of calculation time (½ ms per axis * 5 axes).
CT
CT
CT
CT
Continuous
Task
Background
Task
2
1
Periodic
Task
PT
PT
Motion
Task
1
PT
MT
MT
MT
0
3
PT
2
3
4
5
6
7
8
9
10 11 12 13
PT
PT
MT
14 15 16 17 18 19 20
Time (ms)
Figure 4
From the numbers on the Periodic task above:
1. The periodic task’s first scheduled occurence at the 2 ms mark was delayed by
0.5 ms due to the motion task running. The second occurence at 4 ms ran as
scheduled.
2. The periodic task’s third scheduled occurence at the 6 ms mark was delayed
by 1.5 ms due to the motion task running. This caused the task to overlap with
the 8 ms start of the next occurrence. An overlap error will be generated and the
8 ms occurrence will be missed.
3. The periodic task’s next scheduled occurrence at 10 ms was delayed by 2.5
ms due to the motion task running. This caused the start of the task to overlap
with the 12 ms start of the next occurrence. An overlap error will be generated
and the 10 ms occurrence will be missed. The task’s occurrence at 12ms is then
delayed by an additional 0.5 ms due to the motion task running.
With motion added, by the end of our sample 20 ms run, the continuous task has only
accumulated 4 ms of run time, and the background task has not run at all!
Extrapolating, it will take about 45 ms before the background task gets to run.
32
CompactLogix Performance and Capacity
Another thing to note is that the 2 ms task does not actually run at 2 ms intervals. In
some cases it gets delayed, and in other cases it does not run at all due to an overlap
condition with the previous interval.
Note-If there is no continuous task, the time slice setting has no effect. All processor
time not used for other tasks will be used for background operations.
Changes to the System Overhead Time Slice in Logix Release V16
In the V16 release of all Logix controllers there were 2 changes made to how the
System Overhead Time Slice or SOTS works. It is important to know how these
changes will effect your application, specifically if you are migrating forward from older
firmware revisions. The first change can be seen by looking at the Advanced tab of the
Controller Properties.
The area that is circled tells the controller how to use the SOTS when it is executed.
Run Continuous Task:
This is how the SOTS worked prior to V16. When the SOTS was triggered to execute
and there was no communication or background tasks to process the controller would
return to the continuous task immediately.
33
CompactLogix Performance and Capacity
Reserve for Systems Task, eg Communications:
This is a new option added with the release of V16. With this setting active the
controller will spend the entire 1ms in the SOTS whether it has communications or
background tasks to perform, before returning back to the continuous task.
This feature is intended to be used as a design and test tool allowing a user to simulate
a communication load on the controller during design and programming before HMIs,
controller to controller messaging, etc are up and running.
The other change made in V16 was how the %SOTS value was calculated.
In V15 and earlier the %SOTS would be calculated as follows in the table below:
SOTS Setting
10%
20%
25%
33%
50%
60%
70%
80%
90%
Time Allocated to
the SOTS
1ms
1ms
1ms
1ms
1ms
1ms
1ms
1ms
1ms
Time Allocated to the
Continuous Task
9ms
4ms
3ms
2ms
1ms
< 1ms
< 1ms
< 1ms
< 1ms
In V16 the %SOTS would be calculated as follows in the table below:
SOTS Setting
10%
20%
25%
33%
50%
66%
75%
80%
90%
Time Allocated to
the SOTS
1ms
1ms
1ms
1ms
1ms
2ms
3ms
4ms
9ms
Time Allocated to the
Continuous Task
9ms
4ms
3ms
2ms
1ms
1ms
1ms
1ms
1ms
The tables show that in V16 you will actually see a benefit of setting the SOTS% to a
value greater than 50%. Earlier it is stated that the SOTS can only run in 1ms intervals
of time, but the table shows that at a setting of 90% the time allocated to the SOTS will
be 9ms. The SOTS in this case is given 9 1ms intervals of consecutive time.
Now when you put both of these changes to the SOTS together you can see drastic
changes in continuous task performance. This will be outlined in the tables below. A
simple program was created that has only a Continuous Task with a loop to create a
10ms task scantime.
34
CompactLogix Performance and Capacity
Table 1 (During unused System Overhead Time Slice, Run Continuous Task selected):
SOTS Setting
10%
20%
30%
40%
50%
60%
70%
80%
90%
Continuous Task Scan time
11.366ms
11.378ms
11.614ms
11.666ms
11.670ms
11.678ms
11.756ms
11.654ms
11.610ms
Note: This is about the same performance you would see in V15 and earlier versions.
Table 2 (During unused System Overhead Time Slice, Reserve for System Tasks, eg
Communications selected):
SOTS Setting
10%
20%
30%
40%
50%
60%
70%
80%
90%
Continuous Task Scan time
12.342ms
13.464ms
15.458ms
17.644ms
20.862ms
26.064ms
34.442ms
51.554ms
112.440ms
Note:
1. You can see the drastic effect this has on the continuous task’s scantime.
2. The values in Table 1 could approach the values seen in Table 2 if there is
enough communication occurring in the controller to consume the SOTS’s 1ms
interval of time.
35
CompactLogix Performance and Capacity
Section 9: Limitations Imposed by Connections
Summary: The CompactLogix system uses connections to establish a communication
link between two devices. This includes controllers, communication modules,
input/output modules, produced/consumed tags and messages.
You indirectly determine the number of connections that the Logix controller requires
when configuring the controller to communicate with other devices in the system. Each
module in the CompactLogix system supports a limited number of active connections.
Take these connection limits into account when designing your system.
An alternative to calculating these values manually is the EtherNet/IP Capacity Tool,
available at www.ab.com/go/iatools
Section 9a: 1769-L3x Family
Device
Total
Number of
Connections
Total Number of
Connected/Cached
Buffers
Total Number of
Unconnected/Uncached
Buffers
1769 L3x Controller
**ControlNet port
**EtherNet/IP port
100
*32
32
32
3 fixed incoming/ 10-40
expandable outgoing
32
32
*Supports any combination of scheduled,
unscheduled, cached or uncached
** Each of these connections must be
subtracted from the 100 total controller
connections
Example: To determine the total number of connections used on a CompactLogix processor use
the following:
1.
2.
3.
4.
5.
Count the number of produced tags
Count the number of consumers for each produced tag
Count the number of direct I/O connections
Count the number of rack optimized connections
Count the number of messages incoming
or outgoing
6. Count the number of programming terminals online and
the number of RSLinx packages browsing over the network
7. Count the number of HMI’s polling controller (typically 5
connections per HMI are used)
______
______
______
______
______
______
______
To get the total number of connections used in your controller, add the individual results from steps 1 thru
7
Total Connections used by CompactLogix controller
______
Note: It is not recommended to use all 32 connections on the built in Network ports.
36
CompactLogix Performance and Capacity
Section 9b:1768-L4X Family
Device
1769 L4x Controller
**1768-CNB(R) module
**1768-ENBT V1 module
**1768-ENBT V2 module
Total Number
of
Connections
250
*48
Total Number of
Connected/Cached
Buffers
Total Number of
Unconnected/Uncached
Buffers
32
3 fixed incoming / 10-40
expandable outgoing
64
128
128
128
*Supports any combination of
scheduled, unscheduled,
cached or uncached
** Each of these connections
must be subtracted from the
250 total controller
connections
Example: How to determine the total number of connections used on a network communication module
use the following:
1
Count the number of produced tags
______
2
Count the number of consumers for each produced tag ______
3
Count the number of direct I/O connections
______
4
Count the number of rack optimized connections
______
5
Count the number of messages incoming or outgoing
______
6
Count the number of programming terminals online and the
number of RSLinx packages browsing over the network ______
7
Count the number of HMI’s polling controller
(typically 5 connections per HMI are used)
______
To get the total number of connections used on a network communication module:
Add the individual results from steps 1 thru 7
Total Connections used by network communication module
______
Note: The 1768-L4X will support up to two network communication modules. Remember
not to exceed the total number of L4X controller connections. Also, it is not
recommended to use all connections available on a communication module.
37
CompactLogix Performance and Capacity
Section 9c: 5370 L3 Family
With the 5370 L3 Family of processors, you only need to consider the number of
EtherNet/IP nodes on the network when sizing your system
Processor
EtherNet/IP I/O Nodes
L30ER-NSE
16
L30ER
L30ERM
16
L33ER
L33ERM
L36ERM
32
32
48
16
The information related to connections and the 5370 L3 family is included below for
reference purposes.
Device
Total Number of
Connections
Total Number of
Cached
Connections
Total Number of
Unconnected
Buffers
5370 L3 Controller/EtherNet/IP port
256
32
10-40(10 default)
Example: How to determine the total number of connections used on a network communication module
use the following:
1.
Count the number of produced tags
______
2.
Count the number of consumers for each produced tag
______
3.
Count the number of direct I/O connections
______
4.
Count the number of rack optimized connections
______
5.
Count the number of messages incoming or outgoing
______
6.
Count the number of programming terminals online and the
number of RSLinx packages browsing over the network
______
7.
Count the number of HMI’s polling controller
(typically 5 connections per HMI are used)
______
To get the total number of connections used on a network communication module:
Add the individual results from steps 1 thru 7
Total Connections used by network communication module
______
38
CompactLogix Performance and Capacity
Section 10: CompactLogix on Ethernet Overview
Guidelines:
Performance of an Ethernet network is based upon the following:
Identifying and counting the number of connections
Calculating the packets per second for loading.
Estimating maximum input and output times
Note: You can use the EtherNet/IP Capacity Tool, available at www.ab.com /go/iatools
to size your system.
Section 10a: 1769-L3x Family
1769-L3X
•
•
•
•
•
•
•
EtherNet/IP Capacity and Performance
10/100 megabits per second, Full Duplex
Up to 4000 packets per second (Class 1, I/O, produced/consumed data)
Up to 760 packets per second (Class 3, Messaging, HMI, OPC combined)
Up to 32 CIP I/O connections
Up to 64 TCP connections
2 ms minimum RPI
512 Byte maximum packet size
EtherNet/IP Rules:
– As the packet size increases the number of packets per second
decreases.
– Producer/Consumer packets tend to be much larger than I/O packets and
may reduce the maximum packets per second
NOTE: Class 1 and Class 3 values of packets per second (PPS) listed above are
maximums. It is not possible for the 1769-L3X to handle 760 PPS of HMI traffic while
also handling 4000 PPS of I/O traffic. When the 1769-L3X is required to handle both
class 1 and class 3 traffic reference the graph listed below to determine if the requested
class 1 and 3 traffic is possible.
39
CompactLogix Performance and Capacity
Section 10b:1768-L4X Family
NOTE: 1768-L43, -L45 processors support a maximum of two 1768-ENBT cards; the
following is the capabilities of one 1768-ENBT module:
1768-ENBT EtherNet/IP Capacity and Performance
•
10/100 megabits per second, Full Duplex
•
Up to 5000 packets per second (Class 1, I/O, produced/consumed data
combined)
•
Up to 960 packets per second (Class 3, Messaging, HMI, OPC combined)
•
Up to 128 simultaneous CIP Message connections
•
Up to 128 CIP I/O connections (1768-ENBT/EWEB V2 and later)
64 CIP I/O connections (1768-ENBT V1)
•
Up to 64 TCP connections (1768-ENBT/EWEB V2 and later)
32 TCP Connections (1768-ENBT V1)
•
2 ms minimum RPI
•
512 Byte maximum packet size
EtherNet/IP Rules:
– As the packet size increases the number of packets per second
decreases.
– Producer/Consumer packets tend to be much larger than I/O packets and
may reduce the maximum packets per second
NOTE: Class 1 and Class 3 values of packets per second (PPS) listed above are
maximums. It is not possible for the 1768-ENBT to handle 960 PPS of HMI traffic while
also handling 5000 PPS of I/O traffic. When 1768-ENBT module is required to handle
both class 1 and class 3 traffic reference the graph listed below to determine if the
requested class 1 and 3 traffic is possible.
40
CompactLogix Performance and Capacity
Class 1 vs Class 3 PPS
1200
Class 3 packets
1000
0, 960
800
600
2395, 500
400
200
5000, 0
0
0
1000
2000
3000
4000
5000
6000
Class 1 packets
–
If all packets are completely full (512 bytes) the maximum packets per
second count is reduced to around 2600
–
Section 10c:5370 L3 Family
5370 L3 EtherNet/IP Capacity and Performance
•
10/100 megabits per second, Full Duplex
•
From 6000 to 10000 packets per second depending on packet size (Class 1, I/O,
produced/consumed data combined). See Section 11f for details.
•
Up to 900 packets per second (Class 3, Messaging, HMI, OPC combined)
•
Up to 256 CIP I/O connections
•
Up to 120 TCP connections
•
Max EtherNet/IP I/O Nodes:
L30ER(M) 16
L33ER(M) 32
L36ERM
48
EtherNet/IP Rules
– As the packet size increases the number of packets per second
decreases.
– Producer/Consumer packets tend to be much larger than I/O packets and
may reduce the maximum packets per second
NOTE: Class 1 and Class 3 values of packets per second(PPS) listed above are
maximums. It is not possible for the 5370 L3 to handle 900 PPS of HMI traffic while
also handling 10000 PPS of I/O traffic (See Section 11f). When 5370 L3 module is
required to handle both class 1 and class 3 traffic reference the graph listed below to
determine if the requested class 1 and 3 traffic is possible.
41
CompactLogix Performance and Capacity
Class 1 vs Class 3 PPS
1000
900
800
0, 800
Class 3 packets
700
600
500
6000, 403
400
300
200
100
0
0
2000
6000
8000
9000, 0
9000
Class 1 packets
Based on test results with small (less than 100 bytes) Class 1 packets (see Section 11f) and SOTS set at 20%
Section 10c:Nominal Systems
You can use the EtherNet/IP Capacity Tool, available at www.ab.com /go/iatools to size
your system.
A Nominal 1769-L3X on Ethernet system can be composed of:
7 chassis of discrete I/O at a RPI of 20ms
7 analog modules total located in any of the chassis at a RPI of 80ms
7 drives at a RPI of 40ms
I/O cards in local chassis at a RPI of 5ms
PV+ HMI and programming terminal
A Nominal 1768-L4X on Ethernet system (with one 1768-ENBT V1) can be composed
of:
14 chassis of discrete I/O at a RPI of 20ms
14 analog modules total located in any of the chassis in 80ms
7 drives at a RPI of 40ms
I/O cards in local chassis at a RPI of 5ms
PV+ HMI and programming terminal
42
CompactLogix Performance and Capacity
A Nominal 5370 L3 on Ethernet system can be composed of:
20 chassis of discrete I/O at a RPI of 20ms
20 analog modules total located in any of the chassis in 80ms
16 PowerFlex drives at a RPI of 40ms
I/O cards in local chassis at a RPI of 5ms
PV+ HMI and programming terminal
A Nominal 5370 L3 on Ethernet system with Motion can be composed of:
8 Kinetix 350 Servo Drives with a 4ms Coarse Update Rate
14 chassis of discrete I/O at a RPI of 20ms
14 analog modules total located in any of the chassis in 80ms
7 PowerFlex drives at a RPI of 40ms
I/O cards in local chassis at a RPI of 5ms
PV+ HMI and programming terminal
43
CompactLogix Performance and Capacity
Section 11: CompactLogix on Ethernet: Connections and Packets Per Second
This section will document testing for the 1769-L3X,1768-L4X, and 5370 L3 families
to determine the maximum number of CIP connections recommended at different
values of RPI.
It also will provide examples of how Packets Per Second (PPS) and max CIP
connections can be estimated via calculation for a 1769-3X, 1768-L4X , or 5370 L3
application.
Next, it will discuss how to estimate maximum input or output times for CIP
connections.
Then, it will explain Logix V16 and later changes to the heartbeat rate for unidirectional connections and how this affects utilization resources.
Finally, there is an application example.
Section 11a: 1769-L3X Family - Connections and PPS Testing
Guideline: It is recommended that for most applications, all I/O RPI’s be set to 3ms or greater,
System Overhead Time Slice set to 30% or greater and keep the Ethernet port CPU% under
70% when only Class 1 connections are active.
There are 32 max CIP connections supported by L3x Ethernet port,
However, here is a limit to how many CIP connections the controller can have for a
given RPI. As the RPI is increased, the number connections supported also increases.
Note that digital I/O (rack optimized connection), each analog module (direct
connection) and each produced and each consumed tag each require a CIP connection.
44
CompactLogix Performance and Capacity
Test: Effects of RPI and Number Ethernet Connections for 1769-L32E
(Baseline program used with Ethernet I/O in the form of 1794-AENTs containing two discrete modules in
a rack optimized connection with a size of 2. Local Compact Bus RPI set to 3ms. All Ethernet traffic was
100Mbps full duplex.)
Test Results: Effects of RPI and Number Ethernet Connections for 1769-L32E
Typical
RPI of all
Connections
ThruPut
4-12ms
9-14ms
8-23ms
12-36ms
15-42ms
3ms
5ms
10ms
16ms
26ms
Maximum
Recommended
ENetPort
ENetPort
CPU%
84%
86%
86%
85%
CPU%
61%
64%
72%
70%
73%
#Conn
5
10
20
32
#Conn
3
7
15
23
32
It is recommended that for most applications, all I/O RPI’s be set to 3ms or greater,
System Overhead Time Slice set to 30% or greater and keep the Ethernet port CPU%
under 70% when only Class 1 connections are active.
45
CompactLogix Performance and Capacity
It is recommended to choose the number of connections where the ENet Port CPU%
stays below 70%, as measured in the 1769-L3x web page:
If you are using a Periodic task, set the priority appropriately (7-15),as not to starve the
Ethernet I/O communications , in the NetLinx Class 1 connection task.
Caution:
If the ENet Port CPU% exceeds 100%, the connection will fail with Error “(Code
16#302) Connection Request Error: Out of communication bandwidth.
Guideline:
The maximum number of packets per second for a CompactLogix L3X is 4000 pps.
Total Packets Per Second should not exceed the recommended 90% packets/second, 3600 pps
for CompactLogix L3X
However, bandwidth should be allocated as follows:
Reserve 10% of the Ethernet controller’s bandwidth to allow for processing of Class 1 messages
(I/O and Produced/Consumed tags.)
The total for Class 3 messages (messaging, HMI, upload/download) should not exceed 90% for
the EtherNet I/P interface
46
CompactLogix Performance and Capacity
Section 11b: 1769-L3X Family – Estimating PPS and Max RPI via Calculation
Summary: You can estimate your PPS values using the formula’s and rules provided
below. The results may be more conservative (i.e. resulting in higher PPS numbers)
than what is seen in a real application, but can be used as a means to qualify an application.
An alternative to calculating these values manually is the EtherNet/IP Capacity Tool, available at
www.ab.com/go/iatools.
CIP connections are typically bidirectional – they require 2 packets per RPI. Using 2
packets/RPI/connection, the number of packets/second to or from each EtherNet/IP controller
can be calculated as follows:
A. Rack Optimized: Packets/Second= (2 x connections)/RPI
B. Direct Connection: Packets/Second = (2 x connections)/RPI
C. Consumed Tag: producer and all consumers are in different chassis and are
operating at a uniform RPI):
At Consumer: Packets/Second = 2/RPI for each consumed tag
At Producer: Packets/Second = (1 + No. Connections)/RPI for each produced tag
“Binary Multiple” Rule (CompactLogix 3X Family Only): The RPI you select for a given
ethernet interface or tag translates into an actual packet interval (API) that is the “next lower”
power of 2, such as 2, 4, 8, 16, etc. that is less than or equal to the RPI you configure.
You should use this API value in place of RPI in the formulas above to calculate
Packets/Second.
Below is a table listing the API for a given RPI.
47
CompactLogix Performance and Capacity
API vs RPI Table for CompactLogix 3X EtherNet/IP Connections
RPI(ms)
API(ms)
1 through 3
2
4 through 7
4
8 through 15
8
16 through 31
16
32 through 63
32
64 through 127
64
128 through 255
128
256 through 511
256
512 through 1023
512
1024 through 536870.911
1024
Note: The Binary Multiple rule/ above table only applies to the CompactLogix L3X
family – with the CompactLogix L4X and 5370 L3 the API = the RPI selected
The table below breaks out the fastest RPI allowable for different numbers of rack
connections based on applying the “binary multiple” rule for a CompactLogix L3X
(max PPS = 4000)
Examples of calculations used to generate table:
5 connections at 3msec RPI – use 2msec API in calculation.
PPS=2/.002 msec = 1000 PPS per connection x 5 connections = 5000 PPS which
exceeds the 4000 PPS limit.
5 connections at 4 msec RPI – use 4msec API in calculation.
PPS=2/.004 msec = 500 PPS per connection x 5 connections = 2500 PPS which is
within the 4000 PPS limit.
48
CompactLogix Performance and Capacity
Table: Fastest RPI for Various RPI/ API and Rack Connections Combinations
Connections
RPI (ms)
API (ms)
PPS
Fastest RPI
5
5
5
5
5
5
5
5
5
5
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
20.0
2.0
2.0
4.0
4.0
4.0
4.0
8.0
8.0
8.0
16.0
5,000
5,000
2,500
2,500
2,500
2,500
1,250
1,250
1,250
625
Exceeds L3X PPS limit (4000)
Exceeds L3X PPS limit (4000)
5 connections at 4 ms
OK
OK
OK
OK
OK
OK
OK
10
10
10
10
10
10
10
10
10
10
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
20.0
2.0
2.0
4.0
4.0
4.0
4.0
8.0
8.0
8.0
16.0
10,000
10,000
5,000
5,000
5,000
5,000
2,500
2,500
2,500
1,250
Exceeds PPS limit
Exceeds PPS limit
Exceeds PPS limit
Exceeds PPS limit
Exceeds PPS limit
Exceeds PPS limit
10 connections at 8 ms
OK
OK
OK
20
20
20
20
20
20
20
20
20
20
30
30
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
20.0
20.0
32.0
2.0
2.0
4.0
5.0
6.0
7.0
8.0
8.0
8.0
16.0
16.0
32.0
20,000
20,000
10,000
10,000
10,000
10,000
5,000
5,000
5,000
2,500
3,750
1,875
Exceeds PPS limit
Exceeds PPS limit
Exceeds PPS limit
Exceeds PPS limit
Exceeds PPS limit
Exceeds PPS limit
Exceeds PPS limit
Exceeds PPS limit
Exceeds PPS limit
20 connections at 20 ms
Exceeds 90% Recommendation
30 connections at 32 ms
Section 11c: 1768-L4x Family - Connections and PPS Testing
There are 64 Max CIP connections supported by the 1768-ENBT V1 and 128 Max CIP
connections for the1768-ENBT V2.
However, here is a limit to how many CIP connections the controller can have for a
given RPI. As the RPI is increased, the number connections supported also increases.
Note that digital I/O (rack optimized connection), each analog module (direct
connection) and each produced and each consumed tag each require a CIP connection.
49
CompactLogix Performance and Capacity
Test: Effects of RPI and Number of ENet/IP connections for 1768-ENBT V1
(Baseline program used with Ethernet I/O in the form of 1794-AENTs containing two discrete modules in
a rack optimized connection with a size of 2. All Ethernet traffic was 100Mbps full duplex.)
Test Results: Effects of RPI and Number of Ethernet Connections for 1768-ENBT V1
with 1768-L4x
RPI of Connections
(ms)
Typical Throughput
(ms)
2
3
5
8
10
13
6.4
8
10.4
12.4
14
17.4
1768-ENBT %CPU 1768-ENBT %CPU
w/ Max Connections w/ Recommended
Connections
%CPU
#Cnxn
%CPU
#Cnxn
93
5
76
4
86
7
73
6
83
12
70
11
83
20
68
18
81
25
60
22
75
31
72
29
Notes:
1. There is a limit to how many class 1 CIP connections the 1768-L43 controller with
1768-ENBT can handle for a given RPI. The above table can help you decide if your
desired RPI’s are within acceptable limits. There are other factors that can influence
the above table such as amount of explicit or UCMM traffic, being online to the
controller, System Overhead Time Slice, Periodic Task, Ethernet packets/second
etc. you must consider these factors when applying the table recommendations.
50
CompactLogix Performance and Capacity
2. 1768-L4x supports two 1768-ENBT modules; if a limitation is found in an application
utilizing one 1768-ENBT module an additional one could be added to the system.
3. 1768-ENBT %CPU and Packets Per Second as measured on its web page should
never exceed 80% or 4500 respectively when application is limited to class 1
connections:
Caution:
When the 1768-ENBT Port CPU% = 100% or PPS are exceeded 100% the connection
will fail with Error “(Code 16#302) Connection Request Error: Out of communication
bandwidth”.
Guideline: The maximum number of PPS supported for 1768-ENBT (V1 & V2) is 5000.
Bandwidth should be allocated as follows:
Reserve 10% of the Ethernet module’s bandwidth to allow for processing of Class 3
messages (messaging, HMI, upload/download.)
The total for Class 1 messages (I/O and Produced/Consumed tags) should not exceed
90% for the EtherNet I/P interface.
51
CompactLogix Performance and Capacity
Section 11d: 1768-L4X Family – Estimating PPS and Max RPI via Calculation
Summary: You can estimate your PPS values using the formula’s and rules provided
below. The results may be more conservative (i.e. resulting in higher PPS numbers)
than what is seen in a real application, but can be used as a means to qualify an application.
An alternative to calculating these values manually is the EtherNet/IP Capacity Tool, available at
www.ab.com/go/iatools.
CIP connections are typically bidirectional – they require 2 packets per RPI. Using 2
packets/RPI/connection, the number of packets/second to or from each EtherNet/IP controller
can be calculated as follows:
A. Rack Optimized: Packets/Second= (2 x connections)/RPI
B. Direct Connection: Packets/Second = (2 x connections)/RPI
C. Consumed Tag: producer and all consumers are in different chassis and are
operating at a uniform RPI):
At Consumer: Packets/Second = 2/RPI for each consumed tag
At Producer: Packets/Second = (1 + No. Connections)/RPI for each produced tag
Unlike the 1769-L3X family, the ”Binary Multiple” rule does not apply to the L4X family.
Simply use the selected RPI in the calculation.
The table below breaks out the fastest RPI allowable for different numbers of rack
connections for a CompactLogix L4X (max PPS = 5000)
Examples of calculations used to generate table:
5 connections at 2msec RPI
PPS=2/.002 msec = 1000 PPS per connection x 5 connections = 5000 PPS which
exceeds 90% of the 5000 PPS limit.
5 connections at 3 msec RPI
PPS=2/.003 msec = 667 PPS per connection x 5 connections = 3333 PPS which is
within the 5000 PPS limit.
52
CompactLogix Performance and Capacity
Table: Packets Per Second for Various RPI and Rack Connections Combinations
Connections
RPI (ms)
PPS
Fastest RPI
5
5
5
5
5
5
5
5
5
5
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
20.0
5,000
3,333
2,500
2,000
1,667
1,429
1,250
1,111
1,000
500
Exceeds 90% Recommendation
5 connections at 3ms
OK
OK
OK
OK
OK
OK
OK
OK
10
10
10
10
10
10
10
10
10
10
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
20.0
10,000
6,667
5,000
4,000
3,333
2,857
2,500
2,222
2,000
1,000
Exceeds PPS limit
Exceeds PPS limit
Exceeds 90% Recommendation
10 connections at 5ms
OK
OK
OK
OK
OK
OK
20
20
20
20
20
20
20
20
20
20
30
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
12.0
18.0
20,000
13,333
10,000
8,000
6,667
5,714
5,000
4,444
4,000
3,333
3,333
Exceeds PPS limit
Exceeds PPS limit
Exceeds PPS limit
Exceeds PPS limit
Exceeds PPS limit
Exceeds PPS limit
Exceeds 90% Recommendation
20 connections at 9ms
OK
OK
30 connections at 18ms
Section 11e: 5370 L3 Family - Connections and PPS Testing
The 1769-L36ERM supports a maximum of 48 Ethernet/IP I/O Nodes (See Section 10c
for the other L3 processors.)
However, here is a limit to how many EtherNet/IP I/O Nodes the controller can have for
a given RPI. As the RPI is increased, the number of connections supported also
increases.
Note that digital I/O (rack optimized connection), each analog module (direct
connection) and each produced and each consumed tag each require a CIP connection.
53
CompactLogix Performance and Capacity
Test: Effects of RPI and Number of ENet/IP connections on I/O Comms Utilization for
5370 L3 (1769-L36ERM)
L36ERM I/O Comms Utilization
100.0%
Comms % Utilization
90.0%
80.0%
1 AENT
70.0%
2 AENT
60.0%
4 AENT
50.0%
6 AENT
8 AENT
40.0%
10 AENT
30.0%
12 AENT
20.0%
14 AENT
10.0%
16 AENT
0.0%
2ms
3ms
5ms
10ms
15ms
20ms
RPI
Baseline program used with Ethernet I/O in the form of 1734-AENTRs containing a 1734-IB2 module in a
rack optimized connection. All Ethernet traffic was 100Mbps full duplex.
Notes:
1. There is a limit to how many class 1 CIP connections the 5370 L3 controller can
handle for a given RPI. The above table can help you decide if your desired RPI’s
are within acceptable limits. There are other factors that can influence the above
table such as amount of explicit or UCMM traffic, being online to the controller,
System Overhead Time Slice, Periodic Task, Ethernet packets/second etc. You
must consider these factors when applying the table recommendations.
2. 5370 L3 I/O Comms % Utilization as measured on its web page should never exceed
80% when application is limited to Class 1 connections.
54
CompactLogix Performance and Capacity
Test: Effects of RPI on Throughput for 5370 L3
Throughput Response Time
55
CompactLogix Performance and Capacity
Caution:
When the 5370 L3 Port CPU% = 100% or PPS are exceeded 100% the connection will
fail with error “(Code 16#302) Connection Request Error: Out of communication
bandwidth”.
Guideline: The maximum number of PPS supported for the 5730 L3 is 10000.
Bandwidth should be allocated as follows:
Reserve 10% of the Ethernet module’s bandwidth to allow for processing of Class 3
messages (messaging, HMI, upload/download).
The total for Class 1 messages (I/O and Produced/Consumed tags) should not exceed
90% for the EtherNet I/P interface.
Section 11f: 5730 L3 Family – Estimating PPS and Max RPI via Calculation
Summary: You can estimate your PPS values using the formula’s and rules provided
below. The results may be more conservative (i.e. resulting in higher PPS numbers)
than what is seen in a real application, but can be used as a means to qualify an application.
An alternative to calculating these values manually is the EtherNet/IP Capacity Tool, available at
www.ab.com/go/iatools.
CIP connections are typically bidirectional – they require two packets per RPI. Using two
packets/RPI/connection, the number of packets/second to or from each EtherNet/IP controller
can be calculated as follows:
A. Rack Optimized: Packets/Second= (2 x connections)/RPI
B. Direct Connection: Packets/Second = (2 x connections)/RPI
C. Consumed Tag: producer and all consumers are in different chassis and are
operating at a uniform RPI):
At Consumer: Packets/Second = 2/RPI for each consumed tag
At Producer: Packets/Second = (1 + No. Connections)/RPI for each produced tag
Unlike the 1769-L3X family, the ”Binary Multiple” rule does not apply to the 5730 L3
family.
Simply use the selected RPI in the calculation.
The 5730 L3 has a maximum capacity of 6000 to 10000 packets per second depending
on packet size as shown in the following graph.
56
CompactLogix Performance and Capacity
Note: 6000 PPS for Maximum 512 bytes packet size, 10000 PPS for 1 byte packet size
An assumed packet size of 164 bytes will be used, resulting a maximum PPS for the
5370 L3 of 8706PPS. (This is the assumption used in the EtherNet/IP Capacity Tool)
The table below breaks out the fastest RPI allowable for different numbers of rack
connections for a CompactLogix 5730 L3 (Max PPS = 8706)
Examples of calculations used to generate table:
20 connections at 5ms RPI
PPS=2/.005 ms = 400 PPS per connection x 20 connections = 8000 PPS which
exceeds 90% of the 8706 PPS limit.
20 connections at 10 ms RPI
PPS=2/.010 ms = 200 PPS per connection x 20 connections = 4000 PPS which is within
the 8706 PPS limit.
57
CompactLogix Performance and Capacity
Table: Packets Per Second for Various RPI and Rack Connections Combinations
Connections
RPI (ms)
PPS
Fastest RPI
5
5
5
5
5
2.0
3.0
5.0
10.0
20.0
5,000
3,333
2,000
1,000
500
OK
OK
OK
OK
OK
10
10
10
10
10
10
2.0
3.0
4.0
5.0
10.0
20.0
10,000
6,667
5,000
4,000
2,000
1,000
Exceeds PPS limit
10 connections at 3 ms
OK
OK
OK
OK
20
20
20
20
20
20
20
4.0
5.0
6.0
7.0
8.0
10.0
20.0
10,000
8,000
6,667
5,714
5,000
4,000
2,000
Exceeds PPS limit
Exceeds 90% Recommendation
20 connections at 6ms
OK
OK
OK
OK
30
30
30
30
30
30
6.0
7.0
8.0
9.0
10.0
20.0
10,000
8,571
7,500
6,667
6,000
3,000
Exceeds PPS limit
Exceeds 90% Recommendation
30 connections at 8ms
OK
OK
OK
40
40
40
40
40
9.0
10.0
11.0
15.0
20.0
8,889
8,000
7,273
5,333
4,000
Exceeds PPS limit
Exceeds 90% Recommendation
40 connections at 11ms
OK
OK
48
48
48
48
48
11.0
12.0
13.0
15.0
20.0
8,727
8,000
7,385
6,400
4,800
Exceeds PPS limit
Exceeds 90% Recommendation
48 connections at 13ms
OK
OK
Section 11g: CompactLogix Family Comparison
Here are some comparisons between the three CompactLogix Families based on the
test results above. First, typical throughput for high speed applications/low RPI values.
RPI of Connections
2
3
5
5370 L3 Typical
Throughput (ms)
5.9
6.55
7.9
1768-L4X Typical
Throughput (ms)
6.4
8
10.4
58
1769-L3X Typical
Throughput (ms)
Not Tested
4-12
9-14
CompactLogix Performance and Capacity
Secondly, maximum recommended connections/nodes for high speed applications/low
RPI values.
RPI of Connections
2
3
5
5370 L3 Max
Recommended
Connections
7
11
16*
1768-L4X Max
Recommended
Connections
4
6
11
1769-L3X Max
Recommended
Connections
Not Tested
3
7
* Maximum Number of Connections Tested
Section 11h: Estimate maximum input or output times for CIP connections
System response is dependent on several factors. The dominant factors are RPI and
the number of Class 1 connections. To simplify, the response time of a connection can
be approximated with only the RPI. The maximum input (I/O to controller) or output
(controller to I/O) times for Class 1connections can be estimated as follows.
A. Rack Optimized:
1 RPI
B Direct Connect:
Discrete:
1 RPI
Analog (non-isolated):
2 RTS
Analog (isolated):
1 RTS
C. Produced/Consumed Tag:
1 RPI
With this approximation, the error will be less than 10% if the RPI (in milliseconds) is at
least 10 times the number of connections through the EtherNet/IP interface.
Section 11i: Changes to Heartbeat rates (V16 and later)
For those CIP connections that are not bidirectional version 16 f/w in Logix controllers
have implemented reduced heartbeat rates. This is important because all of the traffic,
including heartbeats, through our Ethernet modules contributes to the CPU utilization of
those modules. The affect of reduced heartbeats is reduced utilization resources on
Ethernet bridge modules, Logix backplane, and Logix controller. This change did not
affect the data gathered in the preceding test as Rack Connections are bidirectional.
Overview
For uni-directional connections that only send data in one direction a “heartbeat” is used
to maintain the connection but does not include customer data. Heartbeat packets are
generated for the following:
™
™
™
™
Produce tag
I/O rack connection, listen-only
I/O module input connection
I/O module input connection, listen only
59
CompactLogix Performance and Capacity
™ I/O module output, listen only
For version 15 and earlier, heartbeats were sent at the same rate, the RPI rate, as the
data. For example, if a produce tag was configured for 10ms, the heartbeat from each
tag consumer was also sent at 10ms.
However, with version 16, heartbeats are sent at a reduced rate and will
correspondingly have a timeout different from the data timeout.
In summary, each CIP connection that has a heartbeat, will have the following:
™ Data RPI
™ Data timeout
™ Heartbeat RPI
™ Heartbeat timeout
Description
You can use the provided tables that follow to view data and heartbeat packet rates.
List of RPIs, Timeouts, and Packet Rates
Note:
ƒ Each CIP connection timeout is 100 ms or more.
ƒ The nominal heartbeat timeout is 2000 ms (2 seconds).
60
CompactLogix Performance and Capacity
Bidirectional Connections
Data Packets
RPI
Per
(ms)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
50
80
100
150
200
250
300
350
375
400
450
500
550
600
650
750
Second
2000
1000
667
500
400
333
286
250
222
200
182
167
154
143
133
125
118
111
105
100
95
91
87
83
80
77
74
71
69
67
40
25
20
13
10
8
7
6
5
5
4
4
4
3
3
3
Uni-Directional Connections
Data
Data
Heartbeat Heartbeat
RPI Packets
RPI
Packets
(ms)
per sec
(ms)
per sec
Total
Packets
per
second
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
50
80
100
150
200
250
300
350
375
400
450
500
550
600
650
750
1000
500
333
250
200
167
143
125
111
100
91
83
77
71
67
63
59
56
53
50
48
45
43
42
40
38
37
36
34
33
20
13
10
7
5
4
3
3
3
3
2
2
2
2
2
1
15
31
31
62
62
62
125
125
125
125
125
125
250
250
250
250
250
250
250
250
250
250
250
250
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
500
550
600
650
750
67
32
32
16
16
16
8
8
8
8
8
8
4
4
4
4
4
4
4
4
4
4
4
4
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
1
1067
532
366
266
216
183
151
133
119
108
99
91
81
75
71
67
63
60
57
54
52
49
47
46
42
40
39
38
36
35
22
15
12
9
7
6
5
5
5
5
4
4
4
3
3
3
61
CompactLogix Performance and Capacity
Section 11j: Example Application Calculation
An alternative to calculating these values manually is the EtherNet/IP Capacity Tool,
available at www.ab.com/go/iatools
Question- An application has the following types of connections; what is the total PPS
for the 1768-ENBT handling the connections?
5 Rack optimized connections RPI = 10 ms
4 Direct connections RPI = 30 ms
10 Consumed tags RPI = 100 ms
20 Produced tags RPI = 150 ms
Answer - Total PPS = 5*(2/.01) + 4*(2/.03) + 10*(2/.1) + 20*(9) = 1000 + 267 + 200 +
180 = 1847 PPS
Utilizing the Class 1 vs Class 3 PPS graph provided in Section 10b this leaves
approximately 600 PPS available for Class 3 traffic.
Total Packets Per Second is the sum of all the packets seen by the Ethernet
bridge module should not exceed the recommended 90% packets/second, 4500
PPS for 1768-ENBT.
62
CompactLogix Performance and Capacity
Section 12: CompactLogix Ethernet Explicit Messaging
This section discusses considerations when using explicit messaging on EtherNet/IP
for the 1769-L3X,1768-L4X and 5370 L3 family of processors.
Summary: When configuring a ladder message in Logix, the user may or may not have
the availability to cache a message, depending on the type of message being
configured.
Cached and uncached messages consume a processor connection; however, cached
messaging continues to use the connection, even when the message is completed,
tying up buffers and resources. Uncached messages open a connection and then close
the connection once the message is completed, freeing up the resources and buffers.
Generally, you should use cached messaging for applications with less than 32
messages. If you have an application with more than 32 messages, you must use
uncached messages after you exceed 32, but make sure you use message
management in such a way that no more than 5 uncached messages are triggered at
any given time.
Ethernet I/O traffic is not affected by the addition of explicit messaging. However, the
number of explicit messages supported decreases as Ethernet I/O connections are
added.
Section 12a: Introduction
This section will discuss Ethernet Explicit Message capabilities of the 1769-L3x, 1768L4X and 5370 L3 CompactLogix platforms.
Three tests will be run:
1) Cached Connected Messaging: Test results will show how many are possible
and typical completion time for given number of cached connected Ethernet
messages.
2) Uncached Unconnected Messaging: Test results will show how many are
possible and typical completion time for given number of uncached unconnected
Ethernet messages.
3) Cached Connected Messaging when I/O over Ethernet/IP traffic also exists: Test
results will show how many cached connected messages are possible and
typical completion time for given number of cached connected Ethernet
Messages when I/O is also present
63
CompactLogix Performance and Capacity
Section 12b: 1769-L3X Family Explicit Ethernet Messaging Considerations
When performing only messaging across Ethernet there are Pros and Cons of adding
remote modules into the module configuration.
Pros:
•
•
•
Provides visual overview of the network
Provides status on the modules of the I/O tree
Makes it easier to use a MSG instruction by allowing you to browse to
your destination during development (see Browse button in MSG
Instruction.)
•
Creates additional traffic on the network because a “Ping” is regularly
sent to the destination module.
The traffic generated uses unconnected messaging and will use some
of the unconnected message buffers on the processor.
The “Pings” will occupy the Ethernet port’s unconnected buffers
Cons
•
•
(When using messages Instructions to devices in tree no ping occurs to that
device. Also, CompactBus local I/O does not use buffers,)
Guidelines: Place the modules in the I/O Tree but inhibit them. This will give a visual
representation of the network, allow you to browse to the destination of MSG instruction,
but will not generate any “Pings”. All inhibited modules will have a yellow information
circle indicating it is inhibited and no connection will be established to them.
64
CompactLogix Performance and Capacity
Leave the I/O tree empty and type the path into the MSG instruction manually, ie.
1,1,2,5,1,5. This will not generate any additional traffic, but the status of remote
modules will be unavailable and the user must understand the Rockwell path
convention.
1, to the backplane
o #, across the backplane to the slot number of module
o 2 (or 3 if 2 ports on the front), out the front of the module to the
network
o #, address of next module
Cached vs Uncached Messages
When configuring a ladder message in Logix, the user may or may not have the
availability to cache a message, depending on the type of message being configured.
65
CompactLogix Performance and Capacity
Both use a connection, however cached messaging continues to use the connection, even when
the message is completed, tying up buffers and resources. Uncached messages open a
connection and then close the connection once the message is completed, freeing up the
resources and buffers.
Cached message performance is faster, since the connection is already established, where as
the uncached message needs time to re-open the connection.
Cached Messaging:
The number of cached messages used has little impact on the program scan. You can expect
the time to complete a message to increase as more cached messages are executed. About 1K
of memory is used for each cached message.
Caution: As the Enet port CPU% ramps close to 100%, measured in the 1769-L32 web page, it
may create excessive time for UCMM messages to complete. UCMM messages are used to
open I/O connections. Note, all open I/O connections will continue to operate- however, when
trying to establish new I/O connections may take an excessive amount of time
UnCached Messaging:
A total of 6 uncached messages are supported simultaneously due to impact on the
Enet Port CPU%.
Uncached messaging has little effect on program scan time. Time to complete an
uncached message is about twice as slow as cached messaging.
66
CompactLogix Performance and Capacity
Test: Effects of Cached and Uncached Messaging on Program Scan and Message Completion
for 1769-L32E
Ethernet Messaging Performance
140
X
120
Tim e (m s)
100
Avg Program Scan - Cached
80
Avg MSG Completion- Cached
Avg Program Scan-Uncached
60
Avg MSG Completion- Uncached
40
20
X
0
6
12
18
24
30
Cached Messages
(Baseline test used with 1769-L32E and five 1756-L55/1756-ENBT pairs. 30 messages sent to and 30 from
CompactLogix to other controllers consisting of 100 element DINT array. No class 1 messages and outgoing
buffers set to 40.)
Test Results: Effects of Cached Messaging on Program Scan and Message Completion for 1769-L32E
Total # of
CACHED
MSG’s
Executing
L35CR
6
12
18 *
24*
30*
4
5
6
7
8
Prog
Scan
Time
(AVG)
L32E
ENet
Port
%CPU
L32E
PLC
%CPU
Typical
L32E
MSG
DN
Time
(AVG)
Memory Used in
the L32E
16-50%
70-93%
100%
100%
100%
33%
43%
45%
44%
44%
40
40
65
80
120
179,309
188,886
195,716
203,824
212,132
*Not Recommended since Enet Port CPU% increases to 100%
Test Results: Effects of UnCached Messaging on Program Scan and Message Completion for 1769L32E
Total # of
UNCACHED
MSG’s
Executing
L35CR
6
5
Prog
Scan
Time
(AVG)
L32E
ENet
Port
%CPU
L32E
PLC
%CPU
Typical
L32E
MSG
DN
Time
(AVG)
Memory Used
in the L32E
90-98%
37%
110ms
190K195K
67
CompactLogix Performance and Capacity
Effects of Mixing Ethernet I/O with Explicit Cached Messaging
Ethernet I/O traffic is not affected by the addition of explicit messaging. However, the
number of explicit messages supported decreases as Ethernet I/O connections are
added.
Caution:
With both the I/O connections and explicit traffic active you must keep the ENET port
%CPU under 100%, measured in the 1769-L32 web page.
Test: Effects of Mixing Cached Ethernet Messaging with Ethernet I/O on a 1769-L32E.
Message Performance with Addition of Ethernet I/O
120
100
80
Number of Explicit Cached MSG
AVG Enet Port %CPU
60
AVG MSG DN Time (ms)
40
20
0
2
4
6
Number of I/O Connections
(Base test used with rack optimized connections to Flex adapter with IB16 and OB16 with RPI=5ms and
messaging to five 1756-L55/1756-ENBT pairs. 30 messages sent to and 30 from CompactLogix to other
controllers consisting of 100 element DINT array.)
Test Results: Effects of Mixing Cached Ethernet Messaging with Ethernet I/O on a 1769-L32E
Number
of I/O
Conn
L32E ENet Port
%CPU
WITHOUT Explicit
MSG
2
4
6
36%
50%
75%
Approx MAX
Number of
Explicit
Cached
MSG
8
6
4
68
L32E ENet Port
%CPU WITH Explicit
MSG
Typical L32E
MSG DN Time
65-95%
90-100%
100%
30-60ms
30-60ms
50-60ms
CompactLogix Performance and Capacity
Section 12c: 1768-L4X Family Explicit Ethernet Messaging Considerations
.
Adding Modules to the I/O Tree
When no I/O is present on a 1768-ENBT module it is not necessary to populate the I/O
tree within RSLogix 5000 application. Pros and Cons exist when considering adding
modules to the I/O tree.
Pros:
Provides visual overview of the network, status on the modules of the I/O tree,
eases MSG instruction configuration by allowing browse to MSG destination
during development (see Browse button in MSG Instruction.)
Cons:
Creates additional traffic on the network because a “Ping” is regularly sent to the
destination module. The traffic generated uses unconnected messaging and will
use some of the unconnected message buffers on the processor. The “Pings”
will occupy the Ethernet port’s unconnected buffers
Guidelines: Place the modules in the I/O Tree but inhibit them. This will give a visual
representation of the network, allow you to browse to the destination of MSG instruction,
but will not generate any “Pings”. All inhibited modules will have a yellow information
circle indicating it is inhibited and no connection will be established to them.
69
CompactLogix Performance and Capacity
When the I/O tree is left empty MSG instruction paths must be entered manually, ie.
1,1,2,192.168.1.2,1,1. This does not generate additional traffic, but the status of
remote modules will be unavailable and the user must understand the Rockwell path
convention (listed below).
ƒ 1, to the backplane
ƒ #, across the backplane to the slot number of module
ƒ 2 (or 3 if 2 ports exist), out the front of the module to the network
ƒ #, address of next module
Cached vs Uncached Messages
When configuring a ladder message in Logix, the user may or may not have the
availability to cache a message, depending on the type of message being configured.
Cached and uncached messages consume a processor connection; however,
cached messaging continues to use the connection, even when the message is
completed, tying up buffers and resources. Uncached messages open a connection
and then close the connection once the message is completed, freeing up the
resources and buffers.
Cached message performance is faster, since the connection is already established,
where as the uncached message needs time to re-open the connection. Use cached
messaging when sending data often, more than once every 30 seconds uncached
when sending data less frequently.
Note: Connected cached messaging is preferred because of speed and network
efficiency; however, the user may need to choose unconnected messaging if
70
CompactLogix Performance and Capacity
application requires more than 32 messages.
Test#1 Cached Messaging:
The number of cached messages used has little impact on the Program scan. You can
expect the time to complete a message to increase as more cached messages are
executed. About 1K of memory is used for each cached message.
Caution:
• As the Enet port CPU% approaches 100%, measured in the 1768-ENBT web
page, it may create excessive time for UCMM messages to complete. UCMM
messages are used to open I/O connections. Note, all open I/O connections will
continue to operate; however, an excessive amount of time may be required to
establish new I/O connections or re-establish I/O connections that previously
existed.
• Reserve at least 10% of each Ethernet/IP module’s bandwidth to allow for
processing of explicit messages. Examples of items that create explicit message
traffic: messaging cached / uncached, HMI (PVP, FactoryTalk View, OPC, etc),
RSLogix 5000 online connections, web page activity.
• The total for implicit messaging should not exceed 90% capacity for each
Ethernet/IP module. Examples of items that create implicit message traffic:
produced / consumed tags, I/O on Ethernet/IP.
• Traffic type affects Packets Per Second (PPS) available:
– I/O traffic (Class 1)1768-ENBT 5000 PPS
– HMI/MSG traffic (Class 3) 1768-ENBT 960 PPS
Use the equation below when calculating PPS:
PPSmessaging = (2 * Number of Messages) / Fastest DN time of those messages
71
CompactLogix Performance and Capacity
Effects of Cached Messaging on Program Scan, Message
Completion time, and 1768-ENBT % CPU
120
100
Avg Program
Scan (ms)
80
Avg MSG
Completion
(ms)
1768-ENBT
%CPU
60
40
20
0
6
12
17
# of Cached messages
Test Results: Effects of Cached Messaging on Program Scan and Message completion
time.
#msgs
L43 scan
time (ms)
#ENET CIP
MSG
connections
%CPU
1768ENBT
%CPU
L43
includes 1 for
RSLogix5000
Typical
L43 DN
Typical
L6x DN
(ms)
ENBT
(ms)
I/O mem
used in
L43
Data and
Logic used
in L43
6
2.5
7
78
30
15
13
58,256
220,476
12*
2.6
13
100
34
25
23
65,800
221,564
17*
2.7
18
100
32
37
33
68,560
222,012
*Not recommended because 1768-ENBT is at 100%.
NOTES:
1.
many things can affect the Completion time of messages including processor
scantime; how messages are initiated, System Overhead Time Slice, etc. The
Completion time can vary from 15 ms with six message instructions active to 40
ms with seventeen message instructions active with all other variables held
constant within the 1768-L43 controller.
2.
Adjusting the SOTS processor setting affects results. Decreasing SOTS
increases the typical MSG execution time, the number of messages possible
without errors and 1768-ENBT %CPU. Similarly increasing the SOTS decreased
the typical MSG execution time, number of messages possible without errors and
1768- ENBT %CPU.
3.
Some form of message management should be applied when attempting more
than 20 cached messages to avoid Resource Unavailable and bandwidth
exceeded errors.
72
CompactLogix Performance and Capacity
4.
5.
Memory consumed due to messaging affects both I/O memory and Data & Logic
memory reported on memory tab of processor properties. From monitoring the
memory values reported a user can determine if too many cached messages are
active. Changing processor memory usage values with purely cached message
applications indicate too many cached messages are active. When cached
messages are initiated processor memory is reserved and this accounts for the
fluctuating processor memory when cached connections must be closed to allow
another cached connection to be established.
Each cached message will consume approximately 1k of processor Data/Logic
memory.
73
CompactLogix Performance and Capacity
Test#2 Uncached Messaging
Uncached messaging has little effect on program scan time; however, it has a
dramatic effect on the 1768-ENBT %CPU. Time to complete an uncached message
is roughly twice as slow as cached messaging.
Caution:
DO NOT run with the ENET Port %CPU at 100%.
Effects of Uncached Messaging on Program Scan, MSG
Completion, and 1768-ENBT % CPU
120
100
Avg Program Scan (ms)
80
60
Avg MSG Completion Unconnected Uncached
(ms)
40
1768-ENBT %CPU
Unconnected Uncached
20
0
6
12
18
# of Uncached MSGS
Test Results: Effects of Uncached Unconnected messaging on program scan time and
message completion time.
Unconnected Uncached
All measured values fluctuate substantially
#msgs
L43 scan
time (us)
#ENET cons
includes 1 for
RSLogix5000
%CPU
1768ENBT
%CPU L43
6
2.6
1
72
27
12
2.7
1
90
18
2.8
1
98
Typical
L43 DN
(ms)
Typical
L6x DN
(ms)
I/O mem
used in L43
max
Data and
Logic used
in L43 max
25
25
52,856
219,708
29
40
28
55,000
220,028
29
100
40
57,144
220,348
Although it is possible to configure messages as Connected Uncached these messages
consume more controller memory and take more time to complete than Unconnected
Uncached messages while consuming as much or more resources from the 1768-ENBT
based on %CPU.
74
CompactLogix Performance and Capacity
Test#3 Effects of Mixing Ethernet I/O with Explicit Cached Messaging
Ethernet I/O traffic is not affected by the addition of explicit messaging.
However, the number of explicit messages is limited by the I/O traffic.
MSG Performance with Addition of Ethernet I/O
120
100
80
# of cached MSG possible
1768-ENBT %CPU
60
AVG MSG DN Time (ms)
40
20
0
2
4
6
# of I/O connections
Test Results: Effects of Mixing Cached Ethernet Messaging with Ethernet I/O with
1768-ENBT and 1768-L43
L43 PLC Approx
1768L43
Typical Typical
Number
1768MAX
ENBT
PLC
L43 MSG
L6x
of I/O
ENBT% %CPU
w/o
Number
%CPU
%CPU DN Time
MSG
Conn
CPU
w/o
Explicit
of
w/
w/
(ms)
DN
Explicit
MSG
Explicit
Explicit Explicit
Time
MSG
Cached
MSG
MSG
(ms)
MSG
2
20
24
12
100
39
15 - 20
15 - 20
4
34
26
7
100
36
18 - 23
17 - 22
6
45
27
6
100
36
20 - 25
18 - 23
Caution: With both the I/O connections and explicit traffic active you must keep the
1768-ENBT %CPU below 100%, measured in the 1768-ENBT web page.
Data shown in results are maximums with %CPU = 100. It is possible to run
a 1768-ENBT at 100% indefinitely without issue; however, this is not
suggested. Some bandwidth should be reserved within the 1768-ENBT to
allow for application expansion and configuration communication to be
possible.
75
CompactLogix Performance and Capacity
Section 12d: 5370 L3 Family Explicit Ethernet Messaging Considerations
.
When performing only messaging across Ethernet consider the following pros and cons
of adding remote modules into the module configuration.
Pros:
•
•
•
Provides visual overview of the network
Provides status on the modules of the I/O tree
Makes it easier to use a MSG instruction by allowing you to browse to
your destination during development (see Browse button in MSG
Instruction.)
•
Each module added into the module configuration uses one
EtherNet/IP I/O node.
Creates additional traffic on the network because a “Ping” is regularly
sent to the destination module.
The traffic generated uses unconnected messaging and will use some
of the unconnected message buffers on the processor.
The “Pings” will occupy the Ethernet port’s unconnected buffers
Cons
•
•
•
When using messages Instructions to devices in tree no ping occurs to that
device. Also, CompactBus local I/O does not use buffers.
76
CompactLogix Performance and Capacity
Guidelines: If you have sufficient EtherNet/IP I/O Nodes available, you can place the
modules in the I/O Tree but inhibit them. This will give a visual representation of the
network, allow you to browse to the destination of MSG instruction, but will not generate
any “Pings”. All inhibited modules will have a yellow information circle indicating it is
inhibited and no connection will be established to them.
Leave the I/O tree empty and type the path into the MSG instruction manually, ie.
1,1,2,5,1,5. This will not generate any additional traffic, but the status of remote
modules will be unavailable and the user must understand the Rockwell path
convention.
1, to the backplane
o #, across the backplane to the slot number of module
o 2 (or 3 if 2 ports on the front), out the front of the module to the
network
o #, address of next module
Cached vs Uncached Messages
When configuring a ladder message in Logix, the user may or may not be able to cache
a message, depending on the type of message being configured.
77
CompactLogix Performance and Capacity
Both use a connection, however cached messaging continues to use the connection, even when
the message is completed, tying up buffers and resources. Uncached messages open a
connection and then close the connection once the message is completed, freeing up the
resources and buffers.
Cached message performance is faster, since the connection is already established, where as
the uncached message needs time to re-open the connection.
Cached Messaging:
The number of cached messages used has little impact on the program scan. You can expect
the time to complete a message to increase as more cached messages are executed. About 1K
of memory is used for each cached message.
Caution: As the Enet port CPU% ramps close to 100%, measured in the 1769-L36ERM web
page, it may create excessive time for UCMM messages to complete. UCMM messages are
used to open I/O connections. Note, all open I/O connections will continue to operate- however,
when trying to establish new I/O connections may take an excessive amount of time
UnCached Messaging:
A total of 6 uncached messages are supported simultaneously due to impact on the
Enet Port CPU%.
Uncached messaging has little effect on program scan time. Time to complete an
uncached message is about twice as slow as cached messaging.
78
CompactLogix Performance and Capacity
Test: Effects of Cached and Uncached Messaging on Ethernet Utilization and Message
Completion for 1769-L36ERM
Ethernet Message Performance
120
100
Uncached L36ERM ENet Port
CPU Utiil (%)
80
Uncached Message DN Times
(msec)
60
Cached L36ERM ENet Port CPU
Util (%)
40
Cached Message DN Time
20
0
6
12
18
Number of Messages
(Baseline test used with 1769-L36ERM and five 1756-L75/1756-EN2TR pairs)
Effects of Mixing Ethernet I/O with Explicit Cached Messaging
Ethernet I/O traffic is not affected by the addition of explicit messaging. However, the
number of explicit messages supported decreases as Ethernet I/O connections are
added.
Caution:
With both the I/O connections and explicit traffic active you must keep the ENET port
%CPU under 100%, measured in the 1769-L36ERM web page.
79
CompactLogix Performance and Capacity
Test: Effects of Mixing Cached Ethernet Messaging with Ethernet I/O on a 1769-L36ERM.
Base test used with rack optimized connections to 1734-AENTR Point adapters with an IB16 with a RPI=5ms
and messaging to five 1756-L75/1756-EN2TR pairs.
80
CompactLogix Performance and Capacity
Section 13: CompactLogix on ControlNet Overview
This section provides guidelines for the use of ControlNet for both the 1769-L3X and
1768-L4X family of processors.
Summary: There is a limit to how many scheduled connections the ControlNet
interfaces can handle for a given NUT/RPI combination. As the NUT is increased so is
the number of connections supported. This section can help you decide if your desired
NUT/RPI’s are within acceptable limits.
Section 13a: 1769-L3X Family
This section will determine the maximum number of connections possible at different
combinations of values for Network Update Time (NUT) / Requested Packet Interval
(RPI) for the 1769-L3X family.
The L3X ControlNet interface supports up to 32 Max connections.
Network Update Times (NUT), above 4ms, has very little effect on ControlNet Interface
CPU Utilization.
– RPI must be equal to or greater than the NUT
Test: Number of connections supported by various NUT/RPI settings on1769-L35CR
Number of ControlNet Connections
35
Number of Connections
30
25
Max# of Connections
20
Recommended #of
Connections
15
10
5
0
2ms
3ms
5ms
10ms
10ms
12ms
14ms
20ms
64ms
2ms
3ms
5ms
5ms
10ms
12ms
14ms
5ms
4ms
RPI
NUT
Baseline program with 1794-ACNR with 2 discrete modules in Rack Optimized connection with size of
2. Local CompactBus was inhibited with RPI set to 3ms.
81
CompactLogix Performance and Capacity
Test Results: Number of connections supported by various NUT/RPI settings on1769-L35CR
Maximum
Typical
RPI of
Throughput
NUT Connections CNET Port CPU%
9-15ms
2ms
2ms
78%
14-19ms
3ms
3ms
82%
14-24ms
5ms
5ms
86%
20-38ms
5ms
10ms
90%
24-44ms
10ms 10ms
88%
28-46ms
12ms 12ms
95%
32-48ms
14ms 14ms
85%
24-56ms
5ms
20ms
86%
70-129ms
4ms
64ms*
*32 max connections for ControlNet port.
#
Connections
1
2
4
9
9
12
12
16
Recommended
CNET Port
CPU%
# Connections
34%
0
60%
1
70%
3
69%
6
64%
6
68%
8
71%
10
69%
12
67%
31
There is a limit to how many scheduled connections the 1769-3X can handle for a given
NUT/RPI combination. The above table can help you decide if your desired NUT/RPI’s
are within acceptable limits. There are other factors that can influence the above table
such as amount of unscheduled traffic, being online to the controller, System Overhead
Time Slice, Periodic Task, etc. you must consider these factors when applying the table
recommendations.
It is recommended that for most typical applications the NUT be set to 4ms or greater,
the CompactBus RPI set to 5ms or greater, the System Overhead Time Slice be set at
30% or greater and you keep the ControlNet port CPU% under 70% with only
scheduled connections active.
Tip: To determine worse case throughput use:
Throughput= (2*NUT) +(2*RPI of module)+(2*Program Scan)
Note: The Local I/O is not burdened by the ControlNet connections
Section 13b: 1768-L4X Family
This section will determine the maximum number of connections possible at different
combinations of values for Network Update Time (NUT) / Requested Packet Interval
(RPI) for the CompactLogix L4X family.
Each 1768-L4X ControlNet interface (the 1768-CNB(R) module) supports up to 48 Max
connections. The 1768-L4X CompactLogix platform supports the use of up to two 1768CNB(R) modules in the same rack.
82
CompactLogix Performance and Capacity
Test Results: Number of connections supported by various NUT/RPI settings on 1768L43 with 1768-CNB(R)
Number of CNET connections vs NUT/RPI
60
Number of Connections
50
40
Maximum connections
30
Suggested Connections
20
10
0
2
3
5
10
20
10
12
14
64
2
3
5
5
5
10
12
14
4
NUT/RPI setting
NUT (ms)
2
3
5
5
5
10
12
14
4
RPI (ms) of
all
Connections
2
3
5
10
20
10
12
14
64
Typical
Throughput
(ms)
12
16
17
25
39
20
29
33
118
CNET
Port
%CPU
93
91
92
98
79
74
61
53
43
Max
#Conn
4
9
17
36
48
30
30
30
48
PLC
%CPU
5
5.6
8.1
8.8
13
10.5
10.3
10.3
13.4
CNET
Port
%CPU
71
70
71
61
41
54
53
53
42
Recommended
#Conn
2
5
13
19
20
20
20
20
48
PLC
CPU%
5
5.4
9.2
8.3
8.1
9.4
7.9
7.9
13.4
There is a limit to how many scheduled connections the 1768-CNBR can handle for a
given NUT/RPI combination. The above table can help you decide if your desired
NUT/RPI’s are within acceptable limits. There are other factors that can influence the
above table such as amount of unscheduled traffic, being online to the controller,
System Overhead Time Slice, Periodic Task, etc. you must consider these factors when
applying the table recommendations.
83
CompactLogix Performance and Capacity
13c General ControlNet Guidelines:
•
It is recommended that the 1768-CNB(R) %CPU, as measured in RSLinx, under
Module Statistics, should never go above 70% when only scheduled connections
are active.
•
To determine worse case throughput use:
Throughputworst = (2*NUT) + (2*RPI of module)+(2*Program Scan)
Note: Local I/O is not burdened by the ControlNet connections
•
If your application requires some I/O to updated faster than the typical I/O,
consider putting this I/O on the local 1769 bus. This bus offers a 1ms I/O update
RPI.
•
Always reserve some connections (2 or more) for network overhead, such and
Programming using RSLogix5000, HMI, OPC topics, and data monitoring.
•
Setup banks of all digital distributed I/O as Rack Optimized: Banks of all Digital
I/O setup as rack optimized only consume (1) connection per bank instead of (1)
connection per module
•
Verify that the ’Unscheduled bytes per second” value displayed in RSNetWorx for
ControlNet exceeds 400,000 bytes/second. If you do go below 400,000 bytes you
run the risk of unscheduled data performance issues such as PanelViews
displaying read time out errors, unscheduled messaging may become
excessively slow or error, etc. Unscheduled bytes per second is directly
associated with the Smax network parameter and the number of scheduled
connections. The higher the Smax value and more scheduled connections active
for a network configuration the lower the amount of unscheduled bytes per
second available.
•
Reduce the total number of unscheduled connections, i.e. MSG instructions by
using an array of tags or User Defined Tags rather than individual tags.
•
If sharing Produce/Consumed data between a ControlLogix and
CompactLogix. Setup the ControlLogix as the data Producer and the
CompactLogix as the Consumer when ever possible
–
Producer Controllers use (1) connection for every consumer
o ControlLogix 1756-CN2(R) supports more connections
84
CompactLogix Performance and Capacity
Section 13d: CompactLogix Nominal System
Scheduled devices on the ControlNet Network should have RPI update rates that
correspond to the type of data being transferred. Typically, Digital I/O has the fastest
update rate and analog I/O has the lowest scheduled update rate
Recommend using the following RPI’s based on the type of device used:
Analog I/O
80ms RPI
Produced / Consumed Tags
40ms RPI
PowerFlex Drives
40ms RPI
Nominal System - CompactLogix
• 16 Scheduled Connections
• 16 Unscheduled Connections
• 10 ms NUT
• < 70% CNET CPU Utilization
Scheduled Connections
...
1 scheduled connection
per Drive
( 3 total scheduled
connections)
40ms RPI
1 connection for each
produced tag (array)
1 connection for each
consumed tag (array)
( 4 total scheduled
connections)
40ms RPI
Unscheduled
Connections
Nominal System:
9 connections for I/O
3 Connections for Drives
4 Connections for P/C
--------------------------------16 scheduled connect.
16 connections remain for
unscheduled devices, i.e.
10ms RPI Digital
80ms RPI Analog
3 scheduled connections per
Bank
( 9 total scheduled
connections)
• Each Bank has 6
digital and 2 analog
module
85
- Panelview Plus
- Explicit Messages
- RSLogix 5000
CompactLogix Performance and Capacity
The Nominal System is NOT the Maximum system configuration:
Nominal System:
– Shows a typical small automation application.
– Shows a configuration that is Guaranteed to work with NO performance or
communication bandwidth issues, such as lost connections, missed
updates, or slower than expected unscheduled packet updates
– Shows a Typical Network update time (10ms) that fits a majority of
customer application needs.
– Faster Digital I/O RPI can be obtained, -by compensating one of the other
factors:
• Slow down the RPI’s on the other non-critical devices
• Substitute some scheduled connections for unscheduled
connections
This Nominal System has Room to Grow:
– Our testing showed that at 70% or better ControlNet CPU utilization for
scheduled connections – the system was extremely stable.
– 70% scheduled utilization provides enough overhead to easily handle
large amounts of unscheduled data
– Simple rule: the more scheduled connections you add the higher the RPI
should be set.
– Always try to stay within 70% ControlNet CPU utilization for the most
stable system.
CompactLogix ControlNet Controllers:
1.5 Meg
1768-L43/
1768-CNB(R)
2 Meg
1768-L45/
1768-CNB(R)
3 Meg
Local I/O Modules 16 Local I/O
30 Local I/O
16 Local I/O
30 Local I/O
Minimum Local 1 ms RPI
RPI
ControlNet Media Coaxial (BNC)
1 ms RPI
1 ms RPI
1 ms RPI
Coaxial (BNC)
Coaxial (BNC)
Coaxial (BNC)
User Memory
1769-L32C
1769-L35CR
750K
ControlNet
32 Max
32 Max
Up to 2 CNB(R): Up to 2 CNB(R):
Connections
48 Max each
48 Max each
Media
No (1 BNC)
Yes (2 BNC)
Yes w/CNBR: Yes w/CNBR:
Redundancy
(2 BNC)
(2 BNC)
Setting
Rotary Switch or Rotary Switch Rotary Switch Rotary Switch
ControlNet Node software
or software
or software
or software
Address
selectable
selectable
selectable
selectable
• The L32C and L35CR have the same processing and I/O performance. The only
differences are: Memory, Local I/O, and Redundant ControlNet Media
86
CompactLogix Performance and Capacity
Section 14: CompactLogix ControlNet Messaging
This section discusses considerations when using ControlNet messaging for both the
1769-L3X and 1768-L4X family of processors.
Section14a: 1769-L3X ControlNet Messaging Considerations
ControlNet connections can be scheduled or unscheduled.
A Scheduled connection lets you send and receive data repeatedly at a predetermined interval (RPI)
Distributed I/O, HMI, Drives, Controller to Controller (Producer/Consumer), all
use scheduled connections.
An unscheduled connection is a message transfer between a controller and a device
that is triggered by a MSG instruction.
Unscheduled messages let you send and receive data when needed
Peer to Peer messaging between controllers, Controller Programming,
HMI/RSLinx all use unscheduled connections
Note: HMI devices, like Panelview Plus or RSView SE, can be setup to use both
scheduled and unscheduled connections
Unscheduled Data
Explicit Messaging- message instructions in ladder and RSLinx communications to a
HMI or PC is unscheduled.
Note- Scheduled traffic is NEVER burdened by the addition of unscheduled traffic
When performing only messaging across ControlNet there are Pros and Cons of adding
modules into the module configuration.
Pros:
• Provides visual overview of the network
• Provides status on the modules of the I/O tree
• Makes it easier to use a MSG instruction by allowing you to browse to
your destination during development
Cons
• Creates additional traffic on the network because a “Ping” is regularly
sent to the destination module.
• The traffic generated uses unconnected messaging and will use some
of the 3 incoming and 10-40* outgoing unconnected message buffers
on the processor.
• The “Pings” will occupy the ControlNet port’s unconnected buffers
(When using messages Instructions to devices in tree no ping occurs to that
device. Also, CompactBus local I/O does not use buffers,)
87
CompactLogix Performance and Capacity
*Buffer size is increased by using CIP Generic Message Instruction. (Setting the maximum
# of buffers has been outlined in Pub 1756-UM518B-EN-P Feb 2003 pg. Appendix C-2 through C-5
DHRIO User Manual, or 1756-pm001-f-en-p June 2003.)
For every buffer increased you will consume 1200 bytes of memory.
The memory tab under controller properties provides an estimate of memory used in the
controller. In CompactLogix there is only one area of memory.
Guidelines: Place the modules in the I/O Tree but inhibit them. This will give a visual
representation of the network, allow you to browse to the destination of MSG instruction,
but will not generate any “Pings”. All inhibited modules will have a yellow information
circle indicating it is inhibited and no connection will be established to them.
Leave the I/O tree empty and type the path into the MSG instruction manually, ie.
1,1,2,5,1,5. This will not generate any additional traffic, but the status of remote
modules will be unavailable and the user must understand the Rockwell path
convention.
1, to the backplane
o #, across the backplane to the slot number of module
o 2 (or 3 if 2 ports on the front), out the front of the module to the
network
o #, address of next module
88
CompactLogix Performance and Capacity
Explicit ControlNet Messaging Performance
When configuring a ladder message in Logix, the user may or may not have the availability to
cache a message, depending on the type of message being configured.
Both use a connection, however cached messaging continues to use the connection, even when
the message is completed, tying up buffers and resources. Uncached messages open a
connection and then close the connection once the message is completed, freeing up the
resources and buffers. Cached message performance is faster, since the connection is already
established, where as the uncached message needs time to re-open the connection.
.
89
CompactLogix Performance and Capacity
Cached Messaging:
When doing cached messages, only 1 connection will be used for all messages with the
same path destination. The time to complete each cached message is low and
cached messages have little effect on the scan time.
Tip: You could expect to use a little more than 1K of memory for each cached
message.
Caution: The limit of the number of cached messages could affect the use of the
PanelView Plus with the L35CR controller. The PanelView Plus uses cached buffers.
Uncached Messaging:
Only 6 messages are supported simultaneously . The time to complete an uncached
message is about 10 times slower than a cached message.
Caution: The limit of the number of uncached messages could affect the use of the
Standard PanelViews with the L35 controllers. The Standard PanelViews use uncached
buffers.
Test: Effects of Unscheduled Messaging on ControlNet on a 1769-L35CR
Unscheduled ControlNet MSG Performance
250
Time(ms)
200
cached scan time
150
cached MSG DN Time
uncached scan time
100
uncached MSG DN time
50
0
6
12
18
24
30
Total Number of Unscheduled MSG's
(The baseline test was used with 1 1769-L35CR and 5 pairs of 1756-L55/1756-CNBR pairs. No scheduled
traffic. NUT=5ms. Number of outgoing message buffers was changed ot 40. All modules in I/O tree were
inhibited. 30 messages sent to and 30 from CompactLogix to other controllers consisting of 100 element DINT
array.)
90
CompactLogix Performance and Capacity
Test Results: Effects of Unscheduled Messaging on ControlNet on a 1769-L35CR
Total Number of
Cached MSG's
executing
6
12
18
24
30
Program Scan Time
3-9ms
3-9 ms
3-9 ms
3-10ms
4-10ms
# Cnet
Connections
used by
Controller
7
13
19
26
31
Cnet
Port
CPU%
85%
98%
99%
99%
99%
Controller
CPU%
39%
44%
43%
40%
40%
Typical
MSG
DN
Time
23
35
61
81
100
Memory
Used
155,620
160,772
168,940
177,108
185,284
Mixing Scheduled ControlNet I/O with Unscheduled Cached Messaging:
Scheduled traffic, I/O and Produced/Consumed data, is not affected by addition of
unscheduled messaging.
Additional unscheduled traffic can be added to scheduled I/O on a network if CNet
%CPU port stays below 70% with only scheduled communications first.
(You only need to consider the ControlNet Interface CPU utilization. The
CompactLogix Processor CPU utilization will NEVER be over taxed ahead of the
Interface CPU.)
The amount of unscheduled messaging is limited by the number of connections
available on the L3x processor and the amount of time needed for the message to
complete.
Caution: If the CNet Port %CPU was over 70% with scheduled traffic only, as measured
in RSLinx, under Module Statistics, then adding additional unscheduled traffic is not
likely to be successful.
Caution: A maximum of only 6 uncached messages is supported simultaneously,
adding schedule data will cause the number to go down.
91
CompactLogix Performance and Capacity
Test: Effects of adding Unscheduled cached messaging to Scheduled I/O on a 1769L35CR
Adding Unscheduled Cached MSG to Scheduled I/O
100
90
80
70
60
%CPU of CNET port w/o
unscheduled MSG
50
MAX number of unsched cached
msg
40
30
20
10
0
2
4
6
8
9
Number of Connections
(The baseline test was used with the NUT=5ms, all RPIs= 10ms, Local Backplane RPI= 3ms, System
Overhead Time Slice=30% and all scheduled connections being rack optimized to a Flex adapter with an
IB-16 and OB16 module.)
Test Results: Effects of adding Unscheduled cached messaging to Scheduled I/O on a 1769-L35CR
Number of
scheduled
Connections
2
4
6
8
9
L35 Cnet
Port %CPU
w/o
unscheduled
messages
36%
53%
69%
86%
91%
MAX number of
unscheduled
cached messages
24
24
18
2
0
L35
MSG
DN time
98
120
120
181
NA
Section14b: 1768-L4X ControlNet Messaging Considerations
This section will discuss scheduled and unscheduled Controlnet communications.
Define ControlNet Explicit Message capabilities of 1768-L4x CompactLogix platform
with test configurations.
Three test configurations:
1) Cached Connected Messaging: Test results will show how many are possible
and typical completion time for given number of cached connected ControlNet
92
CompactLogix Performance and Capacity
messages.
2) Uncached Unconnected Messaging: Test results will show how many are
possible and typical completion time for given number of uncached unconnected
ControlNet messages.
3) Cached Connected Messaging when I/O over ControlNet also exists: Test
results will show how many cached connected messages are possible and
typical completion time for given number of cached connected ControlNet
Messages when I/O is also present.
Two types of ControlNet communications:
Scheduled: send and receive data repeatedly at a predetermined interval (RPI):
Distributed I/O, HMI, Drives, Controller to Controller (Producer/Consumer), all use
scheduled connections. Scheduled traffic is GUARANTEED and is not affected by
the addition of unscheduled traffic.
Unscheduled: messages send and receive data when needed Peer to Peer
messaging between controllers with MSG instruction, Controller Programming
RSLogix 5000, HMI/RSLinx all use unscheduled connections
Note: HMI devices, like Panelview Plus or FactoryTalk View SE, can be setup to use
either scheduled or unscheduled connections or both.
When performing only messaging across ControlNet there are Pros and Cons of
adding modules into the module configuration.
Pros:
Provides visual overview of the network Provides status on the
modules of the I/O tree Makes it easier to use a MSG instruction by
allowing you to browse to your destination during development
Cons:
Network traffic increased because a “Ping” is regularly sent to the
destination module. The traffic generated uses unconnected
messaging and requires unconnected message buffers on the
processor. The “Pings” also consume the ControlNet port’s
unconnected buffers
The memory tab under controller properties provides an estimate of memory used
in the controller.
93
CompactLogix Performance and Capacity
Guidelines: Place the modules in the I/O Tree but inhibit them. This will give a visual
representation of the network, allow you to browse to the destination of MSG instruction,
but will not generate any “Pings”
94
CompactLogix Performance and Capacity
All inhibited modules will have a yellow information circle indicating it is inhibited and no
connection will be established to them.
When the I/O tree is left empty MSG instruction paths must be entered manually, ie.
1,1,2,5,1,5. This will not generate any additional traffic, but the status of remote
modules will be unavailable and the user must understand the Rockwell path
convention (listed below).
ƒ
1, to the backplane
ƒ
#, across the backplane to the slot number of module
ƒ
2 out the front of the module to the network
ƒ
#, address of next module
95
CompactLogix Performance and Capacity
Explicit ControlNet Messaging Performance
When configuring a ladder message in Logix, the user may or may not have the
availability to cache a message, depending on the type of message being
configured.
Cached and uncached messges all require a connection; however, cached messaging
reserves the connection, even when the message is completed, consuming those
processor buffers and resources. Uncached messages open a connection and then
closes the connection once the message is completed, releasing the processor buffers
and resources. Cached message performance is faster than uncached, since the
connection is already established. Uncached message needs time to re-open the
connection each time the message is executed. Cached messaging is suggested when
sending data more than once every 30 seconds and uncached messaging when
sending data less frequently. Logix processors support a maximum of 32 cached
messages. If an application requires more than 32 messages to execute a portion must
be configured as uncached to avoid exceeding the 32 maximum cached message limit.
Test#1 Cached Messaging:
When doing cached messages, only 1 connection will be used for all messages with the
same path destination. The time to complete each cached message is low and cached
messages have little effect on the scan time.
Caution: Cached messaging within the processor application may affect PanelView
96
CompactLogix Performance and Capacity
Plus communications as they also require cached buffers.
CNET cached MSG Performance SOTS = 30%
120
100
80
1768-CNBR %CPU
60
Cached DN time (ms)
40
20
0
6
12
18
24
30
# of cached MSG
Results: Effects of unscheduled ControlNet Messaging with 1768-L43 and 1768-CNBR
#msgs
L43 scan
time (us)
0
6
12
18
24
30
2.4
2.4
2.6
2.6
2.6
2.6
%CPU
1768-CNB
%CPU L43
12
69
94
100
100
100
18
30
38
41
41
42
Typical
L43 DN
(ms)
Typical
L6x DN
(ms)
na
I/O mem
used in
L43
na
10
16
22
30
32
12
14
18
22
27
53,216
58,216
65,720
73,224
80,728
88,312
Data and
Logic used
in L43
175,848
192,636
193,724
194,812
195,900
198,444
NOTES:
1. Adjusting the SOTS processor setting affects results. Decreasing SOTS increases
the typical MSG execution time, the number of messages possible without errors
and 1768-CNBR %CPU. Similarly increasing the SOTS decreased the typical MSG
execution time, number of messages possible without errors and 1768-CNBR
%CPU.
2. Some form of message management should be applied when attempting more than
20 cached messages to avoid Resource Unavailable and bandwidth exceeded
errors.
3. Memory consumed due to messaging affects both I/O memory and Data & Logic
memory reported on memory tab of processor properties. From monitoring the
memory values reported a user can determine if too many cached messages are
active. Changing processor memory usage values with purely cached message
97
CompactLogix Performance and Capacity
applications indicate too many cached messages are active. When cached
messages are initiated processor memory is reserved and this accounts for the
fluctuating processor memory when cached connections must be closed to allow
another cached connection to be established.
4. Each cached message will consume approximately 1k of processor Data/Logic
memory.
Test#2 Uncached Messaging:
It was only possible to configure six uncached messages prior to errors occurring
without message management in place. The time to complete uncached messages
is substantially slower cached messages.
Caution: Uncached messaging within the processor application may affect Standard
PanelView communication as they require uncached buffers.
Results: Effects of Uncached Unconnected CNET Messaging with 1768-L43 with one
1768-CNBR
#msgs
L43 scan
time (us)
%CPU
1768-CNB
%CPU L43
0
2.5
13
18
6
2.6
99
30
Typical
L43 DN
(ms)
Typical
L6x DN
(ms)
NA
I/O mem
used in
L43
NA
21
21
Data and
Logic used
in L43
50,712
220,612
52,856
220,932
NOTES:
1)
There was no significant affect on L43 program scan time or L43 PLC CPU%.
However the 1768-CNB(R) %CPU is dramatically impacted with unscheduled
messaging.
2)
Some form of message management should be applied when attempting more
than two uncached messages to avoid overloading the 1768-CNB as its %CPU
is significantly affected by uncached messaging.
3)
The time to complete the Unconnected Uncached messaging takes roughly
twice as long as the cached messages.
With connections opening and closing both I/O and Data & Logic processor memory
4)
usage fluctuates.
Test#3 Mixing Scheduled ControlNet I/O with Unscheduled Cached Messaging:
Scheduled traffic, I/O and Produced/Consumed data, is not affected by addition of
unscheduled messaging.
Additional unscheduled traffic can be added to scheduled I/O on a network if 1768CNB(R) %CPU port is less than 70% with only scheduled communications active.
The amount of unscheduled messaging is limited by the number of connections
available on the 1768-L43 processor and 1768-CNB(R) module as well as the
%CPU of the 1768-CNB(R) module.
98
CompactLogix Performance and Capacity
Caution: A maximum of only six uncached messages is possible without errors
simultaneously, increasing scheduled data will decrease the number possible. With I/O
connections and explicit traffic active the 1768-CNB(R) %CPU should be kept below
100%, measured in the 1768-CNB(R) module statistics available in RSWho of RSLinx.
Data shown in results are maximums with %CPU = 100. It is possible to run a 1768CNB(R) at 100% indefinitely without issue; however, this is not suggested. Some
bandwidth should be reserved within the 1768-CNB(R) to allow for application
expansion and configuration communication to be possible.
Adding Cached MSG to Scheduled I/O
120
100
1768-CNBR %CPU w/ MSGs
80
1768-CNBR %CPU w/o
MSGs
60
MSG DN time (ms)
40
Max # MSGs
20
0
6
9
18
27
Number of Scheduled I/O
Results: Effects of adding unscheduled cached messaging to ControlNet where I/O
traffic exists.
Number
Typical Typical
1768L43
Approx
1768L43
of
L43
CNBR
PLC
MAX
CNBR
%CPU
L6x
Scheduled %CPU %CPU
MSG
%CPU
Conn
DN
WITH
w/o
w/o
Number
WITH
MSG
Time
Unsched
Unsched Unsched
of
Unsched
DN
MSG
Unsched
Time
6
9
18
27
MSG
MSG
Cached
MSG
26
36
54
78
21
22
25
28
42
39
30
21
MSG
85
92
100
100
99
40
38
38
40
43
47
60
60
50
55
55
55
CompactLogix Performance and Capacity
Guidelines:
When performing explicit (unscheduled) messaging, ie. ladder MSG instructions, choose:
Cached messaging when sending data more than once every 30 sec. or when
communicating to a PanelView Plus
Uncached when sending data infrequently, or when communicating to a Standard
Panelview
Up to 30 simultaneous cached messages and 6 simultaneous uncached messages are
supported by CompactLogix.
Scheduled traffic, I/O and Produced/Consumed data, is not affected by addition
of unscheduled messaging. However, the number of explicit cached messages
decreases as the number of ControlNet I/O connections increases. (See table:
Test Results: Effects of adding Unscheduled cached messaging to Scheduled I/O on a 1769L35CR at the end of this section)
100
CompactLogix Performance and Capacity
Section 15: Bridging Through a CompactLogix Controller
The following recommendations apply to all CompactLogix processors.
However, when using the 1768-L4X in a bridging application, make sure the controller
is at V16.03 or later.
Recommended:
1) ControlNet to DeviceNet via the 1769-SDN. (For DeviceNet configuration only,
not data collection.)
2) Ethernet to DeviceNet via the 1769-SDN. (For configuration only, not data
collection.)
3) RS232 Serial or USB to DeviceNet via the 1769-SDN (For configuration only, not
data collection.)
4) USB to Ethernet with L3
NOTE: issues may exist in accessing DeviceNet network with bridged connection
when explicit messaging is present in application.
Not Recommended:
1) Serial to ControlNet
•
Bridging only recommended for simple tasks like browsing ControlNet
or monitoring a single node.
•
DO NOT configure ControlNet with RSNetworx for ControlNet by
bridging through the serial port of the CompactLogix controller.
•
DO NOT use this path to go online to other controllers
2) Serial to Ethernet
•
Bridging only recommended for simple tasks like browsing Ethernet or
monitoring a single node.
•
DO NOT use this path to go online to other controllers
3) Serial to DeviceNet
•
Bridging via this route is only recommended for simple tasks like
browsing DeviceNet or monitoring a single node via DeviceNet.
101
CompactLogix Performance and Capacity
Considerations when messaging in a bridging application
Keep these considerations in mind when developing an application that will have either
bridged messages through the CompactLogix controller or messages that originate from
the CompactLogix controller to the DeviceNet network.
•Do not send more than 4 simultaneous messages to any single module on
the backplane.
•Write code to monitor for failed message delivery and to properly handle
retries.
•The controller properly handles simultaneous messaging from message
instructions and bridging messages from an EtherNet/IP connection. For
example, RSLinx or RSNetWorx software bridging from the EtherNet/IP
network across the backplane to configure a device on a DeviceNet network.
•The 1768-L43 and 1768-L45 controllers support as many as eight
simultaneous messages to the Compact I/O subsystem and as many as four
simultaneous messages to any one module in the Compact I/O configuration.
102
CompactLogix Performance and Capacity
Section 16: Other CompactLogix Configurations:
High Speed Redundant ControlNet:
CompactLogix SCADA:
103
CompactLogix Performance and Capacity
Section 17: Comparing the CompactLogix L3X, CompactLogix L4X,
CompactLogix 5370 L3, and ControlLogix Families
Many features and capabilities are shared in the Logix family of controllers. However,
differences in hardware and firmware exist that can affect performance. This section
describes the similarities and differences between the CompactLogix L3X,
CompactLogix L4X, CompactLogix 5370 L3, and the ControlLogix (1756-L6X)
platforms.
•
Similarities of CompactLogix 5370 L3 to CompactLogix L4X
– Same “rackless” design
– Native 1769 I/O with the same rules
– Neither require a battery
– Removal and Insertion Under Power not supported
– Removable Media: Either SecureDigital or CompactFlash support
– No support for DH+ or RIO legacy networks
– Event task Module Input Data State Change trigger not supported
– Both support sockets- L3 natively and L4X with the 1768-EWEB module.
– EtherNet/IP port supports single IP address
•
Differences of CompactLogix 5370 L3 to L4X
– 5370 L3 has one processor to handle application and I/O; L4X has two
processors: one dedicated to application, the other for I/O
– 5370 L3 has built in EtherNet/IP dual port that supports DLR; L4X requires
separate 1768-ENBT module for EtherNet/IP communications;.
– 5730 L3 supports Integrated Motion on EtherNet/IP via built in EtherNet/IP
port; L4X requires 1768-M04SE module for SERCOS support.
– 5730 L3 has USB port; L4X has RS-232 port.
•
Similarities of L3X to L4X
– Same “rackless” design
– Native 1769 I/O with the same rules
– Removal and Insertion Under Power not supported
– Removable Media: Both have CompactFlash support
– No support for DH+ or RIO legacy networks
– Event task Module Input Data State Change trigger not supported
•
Differences of L3X to L4X
– L4X has two processors: one dedicated to application the other for I/O;
L3X has one processor to handle application and I/O
– More processor memory available
– Motion control support of L4X is not available in L3X platform.
– The L3X uses a battery and the L4X has a special power supply that
negates the need for a battery.
– RPI values for 1769 modules can be individually configured with the L4X;
not fixed with ‘rack connection’ as with L3X solution with CompactBus RPI
setting. Adding I/O modules at a given RPI has less of an impact on
%CPU with the L4X family than the L3X family.
104
CompactLogix Performance and Capacity
–
L3X platform handles I/O updates as a prioritized task whereas the L4x
handles them with a dedicated piece of hardware for all backplane
communications. You need to consider this when setting the priority levels
of Periodic tasks in the L3X, whereas it is not an issue in the L4X.
•
Similarities of L4X to L6X
– Separate hardware dedicated for main processing duties and backplane
communications.
– Communication module flexibility for Ethernet and ControlNet expansion
– Memory: Both have the same physical amount of SDRAM and Flash
– Removable Media: Both have CompactFlash support
– NonVolatile Memory: Both have NAND Flash to hold program/data during
power down
– I/O supports individually configured RPI values.
– Motion support available
– Motion event triggers supported for Event task
•
Differences of L4X to L6X
– The L6X uses a battery and the L4X has a special power supply that
negates the need for a battery.
– Removal and Insertion Under Power (RIUP): L4X platform does not
support this feature.
– Chassis: The L4X has a “rackless” design L6X has a chassis in which
modules reside.
– L4X does not offer DH+ or RIO connectivity
– Event task Module Input Data State Change trigger not supported
105
CompactLogix Performance and Capacity
Section 18: CompactLogix 5370 L3 and Integrated Motion on EtherNet/IP
The CompactLogix 5370 L3 based Integrated Motion on EtherNet/IP solution brings
high-performance motion control to small applications. This system includes the
CompactLogix 5370 L3 Controllers, Kinetix 350 servo drives, and I/O.
The Integrated Motion on EtherNet/IP solution simplifies the network architecture by
eliminating the need for a separate motion network, while providing a high-performance,
cost-effective solution for low-axis count machines.
Target Applications
This solution is ideal for applications with fewer than 200 I/O and up to 16 axes of
motion. Some typical applications include:
•
Indexing Tables
•
Automatic Assembly Machines
•
Packaging – Intermittent VFFS &HFFS
•
CPW – Winders, Re-winders, Slitters
•
Hoisting & Crane
•
Transfer Systems
•
Feeders
•
Case Packers & Erectors
•
Rotary Knife
•
Smart Belts
•
Packaging – Intermittent VFFS &HFFS
Integrated Motion on EtherNet/IP System Features
•
Single network architecture integrates high performance drives, I/O,
smart actuators, HMI, programming terminal, and many other
EtherNet/IP devices providing lower system cost, improved
performance, flexibility, and ease-of-use benefits.
•
Kinetix and PowerFlex drives can be used on the same network for
common configuration, programming, commissioning, diagnostics,
and drive maintenance.
106
CompactLogix Performance and Capacity
•
EtherNet/IP is open and broadly adopted with over 3 million installed
nodes, and over 1000 different products as of 2011.
•
EtherNet/IP, CIP Motion, and CIP Sync technologies are global
standards from ODVA, helping to ensure device standardization and
compatibility.
•
Support for any Ethernet topology for maximum flexibility.
•
EtherNet/IP is an agile, multidiscipline network that can be used to
control, configure, monitor and do peer interlocking for motion,
safety, process and discrete applications; it provides true enterprisewide integration.
Star Topology
A star configuration is a traditional Ethernet network layout where devices are
connected to centralized network switch, point-to-point. The star configuration is most
effective when the devices are located near a centrally located network switch.
This configuration may require more cabling for device connections compared to a
Linear or Ring configuration, but offers the advantage that if a point-to-point connection
is lost to an end device, the rest of the network remains operational.
107
CompactLogix Performance and Capacity
Linear or DLR (Ring) Topology
Linear Topology
Ring Topology
A Linear or Device Level Ring (DLR) topology differs from the traditional star, as the
devices are linked together via a two port embedded switch, instead of being connected
back to a centralized network switch.
For products like the Kinetix 350 that do not support embedded switch technology, they
can still be integrated into a Linear or Ring topology with the inclusion of an EtherNet/IP
network tap (1783-ETAP).
108
CompactLogix Performance and Capacity
The ETAP contains a single device port and two network ports to connect into a Linear
or Ring network. Both Linear and Ring topologies simplify interconnect wiring between
access layer devices.
A ring configuration offers the same benefits as a linear device but is single fault tolerant
providing network resiliency with the closure of the ring. With a linear configuration,
removing a node will essentially disconnect all downstream nodes or devices, while a
ring can withstand a single connection loss.
A ring cannot be connected directly through a network switch, but the switch can be
connected into a ring via an ETAP. This is especially important to remember when
using an unmanaged switch (ex. Stratix 2000), as they do not support loop prevention.
It is crucial to configure the Ring Supervisor before connecting your Linear topology into
a Ring topology.
For more information about applying two port embedded switch enabled products,
please refer to the EtherNet/IP Embedded Switch Technology Application Guide
(ENET-AP005).
Switch Considerations
Either a managed or unmanaged switch can be used, depending on your application
requirements.
Scale your switch selection to your application with these Rockwell Automation
switches:
• Stratix 8000 and 6000 Managed Switches
• Stratix 2000 Unmanaged Switches
When connecting machines to a high level plant network, IT networking best practices
need to be considered.
109
CompactLogix Performance and Capacity
Typical Applications
This is a typical application utilizing a hybrid Star/Linear topology. The L36ERM can
comfortably scan 2 axis per ms which will support variations such as:
4 axis @ 2ms Coarse Update Rate (Shown)
8 axis @ 4ms Coarse Update Rate
16 axis @ 8ms Coarse Update Rate
Any of these will result in approximately 50% utilization of the L36ERM EtherNet/IP port,
leaving ample bandwidth for additional standard I/O connections at default RPIs as
shown.
The exact number of I/O supported depends on the RPIs selected.
You can use the EtherNet/IP Capacity Tool, available at www.ab.com /go/iatools to size
your system or use the calculations described in Section 11f.
110
CompactLogix Performance and Capacity
Appendix A: Table of Message Types (Connected vs Unconnected)
Below is a table of all the message types that are supported and the connection type
that is uses U = unconnected C = connected
Message Type
CIP Generic
CIP Datatable Read
CIP Datatable Write
SLC Typed Read - serial
SLC Typed Read - DH+
SLC Typed Read - unsol
SLC Typed Write - serial
SLC Typed Write - DH+
SLC Typed Write - unsol
Cnet BT Read
Cnet BT write
BT Read - RIO
BT Write - RIO
PLC2 Read - serial
PLC2 Read - CIP
PLC2 Read - DH+
PLC2 Read - unsol
PLC2 Write - serial
PLC2 Write - CIP
PLC2 Write - DH+
PLC2 Write - unsol
PLC-3/5 WdRng Read - serial
PLC-3/5 WdRng Read - CIP
PLC-3/5 WdRng Read - DH+
PLC-3/5 WdRng Read - unsol
PLC-3/5 WdRng Write - serial
PLC-3/5 WdRng Write - CIP
PLC-3/5 WdRng Write - DH+
PLC-3/5 WdRng Write - unsol
PLC-3/5 Typed Read - serial
PLC-3/5 Typed Read - CIP
PLC-3/5 Typed Read - DH+
PLC-3/5 Typed Read - unsol
PLC-3/5 Typed Write - serial
PLC-3/5 Typed Write - CIP
PLC-3/5 Typed Write - DH+
PLC-3/5 Typed Write - unsol
IO Reconfig
Connection Type
U/C
C/U
C/U
U
C
U
U
C
U
C
C
C
C
U
U
C
U
U
U
C
U
U
U
C
U
U
U
C
U
U
U
C
U
U
U
C
U
U
111
CompactLogix Performance and Capacity
Appendix B:Flex I/O vs. Point I/O Performance Comparison
Objective: To determine any differences from a performance standpoint between Flex
I/O and Point I/O. The test consisted of a single Flex adapter or a single Point adapter
on ControlNet or Ethernet controlled by a CompactLogix controller. The RPI and the
number of input/output modules used was varied. The communications format was
Rack Optimized. Flex I/O used the1794-IB16 as an input card and the 1794-OB16 as an
output card. Point I/O used the1734-IB4 as an input card and the 1734-OB4E as an
output card. All modules were set at their default filter time. Each configuration used 20
samples and the low and high numbers are shown. 20 samples are not enough to be
statistically accurate but are enough samples for a general comparison.
Note: Flex and Point were compared based on the number of modules used not on
identical number of I/O points. I.E. A Flex module has 16 points per module but Point
had 4 points per module.
ControlNet
Throughput
2 mS RPI Flex I/O
Point I/O
3 mS RPI Flex I/O
Point I/O
5 mS RPI Flex I/O
Point I/O
1 Input 1 Output
Module
9.0-13.0 mS
9.5-14.5 mS
12.0-16.5 mS
10.5-22.0 mS
13.5-23.0 mS
15.5-23.5 mS
2 Input 2 Output
Modules
10.0-13.5 mS
10.0-14.0 mS
11.0-16.5 mS
11.0-16.0 mS
13.5-26.0 mS
15.0-23.0 mS
4 Input 4 Output
Modules
10.0-14.5 mS
10.5-14.5 mS
14.5-17.5 mS
11-16.5 mS
14.5-23.5 mS
14.5-27.0 mS
Ethernet
Throughput
2 mS RPI Flex I/O
Point I/O
3 mS RPI Flex I/O
Point I/O
5 mS RPI Flex I/O
Point I/O
1 Input 1 Output
Module
4.5-9.5 mS
8.0-15.5 mS
4.5-9.5 mS
8.0-13.0 mS
5.0-13.0 mS
8.5-16.5 mS
2 Input 2 Output
Modules
5.0-8.5 mS
5.5-12.2 mS
5.0-9.0 mS
7.0-13.0 mS
6.0-12.5 mS
8.5-19.0 mS
4 Input 4 Output
Modules
5.0-8.5 mS
7.5-11.5 mS
5.0-9.5 mS
8.0-11.0 mS
7.0-13.5 mS
8.0-18.0 mS
Summary: This summary is based off of general trends from the data above and not all
data points will fall into the general trend primarily because the number of samples
taken was not large.
• On both Ethernet and ControlNet for a typical number of I/O modules used the
throughput is not affected by the number of modules contained in the Flex or
Point chassis. Since Flex only supports 8 modules per chassis and Point
supports 63 no statement is made about the performance of a Point chassis with
63 modules.
• On ControlNet there is no significant performance difference between Flex and
point I/O.
112
CompactLogix Performance and Capacity
www.rockwellautomation.com
_______________________________________________________________________________________________________
Power, Control and Information Solutions Headquarters
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe/Middle East/Africa: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
Publication IASIMP-QR007C-EN-P - July 2012 148
Supersedes Publication IASIMP-QR007B-EN-P – March 2009
Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.