Digital Cam Switch Unit
CamCon 1756-DICAM
for Allen Bradley ControlLogix
Note:
ControlLogix® is a registered trademark of Rockwell Automation.
Digitronic Automationsanlagen GmbH
Steinbeisstraße 3 • D - 72636 Frickenhausen • Tel. (+49)7022/40590-0 • Fax -10
Auf der Langwies 1 • D - 65510 Hünstetten-Wallbach • Tel.(+49)6126/9453-0 • Fax -42
Internet: http://www.digitronic.com • E-Mail: [email protected]
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
For your attention
This instruction manual relates to the CamCon 1756-DICAM from 10.2003 Firmware 1.9 and the
DC1756.ACD software V1.21. The company Digitronic Automationsanlagen GmbH reserves the right
to make changes which present an improvement of the quality or functionality of the device without
prior notice. The instruction manual was created with great care, although it may not be error-proof.
We would be grateful for any communication relating to any errors you may have found.
UP-date
You can also obtain this instruction manual on the Internet at http://www.digitronic.com in the latest
version as PDF file.
Qualified personnel
This device may only be started and operated by qualified staff. By qualified we mean personnel who
are entitled to handle, to earth and to lable devices, systems and power circuits in accordance with the
technology safety standards.
Liability
(1) The supplier is liable for damages caused by himself or by the owner of the rights up to the sum of
the sales price. He is not liable for loss of profits, forfeited savings, intermediate and successive
damages.
(2) The above mentioned limits to liability do not apply to insurance of named characteristics and
damages which were caused deliberately or through negligence.
Protection
The CamCon 1756-DICAM and this instruction manual are protected by copyright. All rights are
reserved. Neither the CamCon 1756-DICAM, nor this document may be copied as a whole or partially,
photocopied, reproduced, translated or transferred to electronic media of any kind or into machine
readable format without prior written permission by the company Digitronic Automationsanlagen
GmbH.
Note:
Note:
Note:
We have examined the devices of the CamCon series for year 2000 compatibility and
have not found any adverse effects on any functions.
CamCon is a registered trademark of the company Firma Digitronic
Automationsanlagen GmbH.
The devices of the CamCon series comply with the standards for electromagnetic
compatibility: EN 55011, EN 55022, EN 55024 Part 2, EN 50082 Part 2, ENV 50140,
VDE 0843 Part 2,
VDE 0843 Part 4,
VDE 0871,
VDE 0875 Part 3 ("N"),
VDE 0875 Part 11, VDE 0877 Part 2, IEC 801 Part 3, IEC 801 Part 2, IEC 801 Part 4,
IEC 801 Part 5.
(c) Copyright 1992 - 2004 / File: DC1756E.DOC
Digitronic Automationsanlagen GmbH
Auf der Langwies 1
D-65510 Hünstetten - Wallbach
Tel. (+49)6126/9453-0 Fax. (+49)6126/9453-42
Internet: http://www.digitronic.com
E-Mail: [email protected]
Note:
Hiperface® is a registered trademark of the Stegmann GmbH.
ControlLogix® is a registered trademark of Rockwell Automation.
Edition: 18.08.2004
Page: 2
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
Table of Contents
1. Introduction .......................................................................................................................................... 5
2. Operating Pinciples .............................................................................................................................. 6
2.1. Speed Compensation........................................................................................................................ 7
2.1.1. Measuring delay time for Speed Compensation ............................................................................ 9
2.1.1.1. Measuring delay time through actual differences ....................................................................... 9
2.1.1.2. Measuring delay time by means of different measuring points................................................... 9
2.1.2. Speed Compensation using off-centre pressure, e.g. brake functions ........................................ 10
2.1.3. Separate delay time for Speed Compensation of switch-ON and switch-OFF points.................. 11
2.2. Time - Cam ..................................................................................................................................... 11
3. Installation .......................................................................................................................................... 12
3.1. Dimensions ..................................................................................................................................... 13
4. Electrical connections ........................................................................................................................ 14
4.1. Power supply to CamCon ............................................................................................................... 14
4.2. Output pin layout ............................................................................................................................. 14
4.3. Pin layout of inputs (Option) ............................................................................................................ 15
4.4. Pin layout of RS422 SSI measuring system ................................................................................... 15
4.5. Pin layout at 24Volt incremental measuring system ....................................................................... 15
4.6. Pin layout for Hiperface incremental measuring system................................................................. 15
4.7. Clamping allocation of the external interface (option)..................................................................... 16
4.8. RS485 interface (only for test mode) .............................................................................................. 16
4.9. The measuring system.................................................................................................................... 17
4.9.1. SSI Measuring system input ........................................................................................................ 17
4.9.2. Parallel measuring system input .................................................................................................. 17
4.9.3. Incremental measuring system input ........................................................................................... 18
4.9.3.1. Incremental measuring system input with 5V RS422 level ....................................................... 18
4.9.3.2. Incremental measuring system input with 24V PNP level......................................................... 18
4.9.3.3. Incremental Hiperface measuring system input with SINCOS level ......................................... 19
4.9.4. Analog measuring system input ................................................................................................... 19
4.9.5. PLL measuring system input........................................................................................................ 20
4.9.6. Timer as a measuring system...................................................................................................... 20
4.9.7. RS232 as a measuring system .................................................................................................... 20
4.10. The outputs ................................................................................................................................... 21
4.11. The inputs ..................................................................................................................................... 21
4.12. Precautionary measures for welding work .................................................................................... 21
4.13. Status Displays ............................................................................................................................. 22
4.13.1. Status LED ................................................................................................................................. 22
4.13.2. Status Bits in the I - Range ........................................................................................................ 22
5. Starting............................................................................................................................................... 23
5.1. Planning the ControlLogix CPU for CamCon 1756-DICAM ............................................................ 23
5.1.1. The I - Range ............................................................................................................................... 24
5.1.2. The O - Range ............................................................................................................................. 24
5.1.3. The C - Range.............................................................................................................................. 24
6. Communication between ControlLogix 1756 CPU and CamCon 1756-DICAM................................. 25
6.1. Installation of the Software.............................................................................................................. 25
6.2. General Information on the Software .............................................................................................. 26
6.2.1. The write program DC_9_DATA_WRITE for parameter, cams or delay times ........................... 27
6.2.2. The read program DC_9_DATA_READ for Status, Parameter, Cams or Delay Times .............. 28
6.2.3. The TAGs of the "DICAM1756" Program..................................................................................... 29
6.3. The Controller TAGs of the CamCon 1756-DICAM........................................................................ 30
6.3.1. TAG "ADR"................................................................................................................................... 30
6.3.2. TAG "DC_0_CLEAR_ALL"........................................................................................................... 30
6.3.3. TAG "DC_0_EEPROM_LOCK".................................................................................................... 30
Edition: 18.08.2004
Page: 3
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
6.3.4. TAG "DC_0_HW_RESET"........................................................................................................... 30
6.3.5. TAG "DC_1_SYSTEM_CONFIG" ................................................................................................ 31
6.3.6. Special measuring system TAGs................................................................................................. 34
6.3.6.1. TAG "DC_1_SYSTEM_CONFIG_ENC_0_SSI"........................................................................ 34
6.3.6.2. TAG "DC_1_SYSTEM_CONFIG_ENC_1_PAR" ...................................................................... 34
6.3.6.3. TAG "DC_1_SYSTEM_CONFIG_ENC_2_INK" or Hiperface................................................... 35
6.3.6.4. TAG "DC_1_SYSTEM_CONFIG_ENC_3_MULTI"................................................................... 35
6.3.6.5. TAG "DC_1_SYSTEM_CONFIG_ENC_4_PLL" ....................................................................... 36
6.3.6.6. TAG "DC_1_SYSTEM_CONFIG_ENC_5_TIMER" .................................................................. 36
6.3.6.7. TAG: "DC_1_SYSTEM_CONFIG_ENC_7_AG615" ................................................................. 36
6.3.6.8. TAG: "DC_1_SYSTEM_CONFIG_ENC_8_SPEED_SIM" ........................................................ 37
6.3.6.9. TAG: "DC_1_SYSTEM_CONFIG_ENC_9_HIPER".................................................................. 37
6.3.7. TAG "DC_1_SYSTEM_CONFIG_PLC[X]"................................................................................... 38
6.3.7.1. TAG: DC_1_SYSTEM_CONFIG_PLC_OK" ............................................................................. 39
6.3.8. TAG "DC_1_SYSTEM_SET_ACTUAL_VALUE" ......................................................................... 40
6.3.9. TAG "DC_2_PRG_CAM[X].CAM[Y]" ........................................................................................... 40
6.3.9.1. TAG: DC_2_PRG_CAM_OK" ................................................................................................... 40
6.3.10. TAG "DC_2_PRG_CHANGE".................................................................................................... 41
6.3.11. TAG "DC_2_PRG_DTC[X]" ....................................................................................................... 41
6.3.11.1. TAG: DC_2_PRG_DTC_OK".................................................................................................. 41
6.3.12. TAG "DC_3_STATUS"............................................................................................................... 41
6.3.13. TAG "DC_3_STATUS_FULL".................................................................................................... 42
6.3.14. TAG "DC_4_QUIT_ERROR" ..................................................................................................... 42
6.3.15. TAG Range "DC_5_...." ............................................................................................................. 43
6.3.16. TAG Range "DC_9_...." ............................................................................................................. 43
6.4. Transferring actual value and speed into realtime .......................................................................... 44
6.4.1. Speed........................................................................................................................................... 44
6.4.2. Actual value.................................................................................................................................. 44
7. Error messages and removal of errors (FAQ) ................................................................................... 44
7.1. Problem: "Pos - Err:1". .................................................................................................................... 44
7.2. Problem: "Pos - Err:2". .................................................................................................................... 44
7.3. Problem: "Pos - Err:3". .................................................................................................................... 45
7.4. Problem: "Pos - Err:5". .................................................................................................................... 45
7.5. Problem: An "Pos-Error:" occurs during operation.......................................................................... 45
7.6. Problem: "RAM-Full" = RAM memoryis full..................................................................................... 45
7.7. Problem: The EEProm memory is full............................................................................................. 46
7.8. Problem: Outputs will not activate................................................................................................... 46
7.9. Problem: "Out - Error". .................................................................................................................... 46
7.10. Problem: Error in the EEPROM. ................................................................................................... 46
7.11. Problem: "Error ???" ..................................................................................................................... 46
7.12. Problem: "Clear...."........................................................................................................................ 47
8. Calculation EEPROM cam storage.................................................................................................... 48
9. Calculation the RAM storage-requirement for CamCon .................................................................... 49
10. Technical Data ................................................................................................................................. 50
11. Keyword register .............................................................................................................................. 51
Edition: 18.08.2004
Page: 4
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
1. Introduction
Electronic Cam Switch Units have been successfully used in industry for a long time. Experiences
collected in close liaison with users over the years have been included in the development of the
CamCon series. The result is a compact digital cam switch unit which is user friendly and reliable to a
high degree. The following characteristics testify the excellence of the CamCon:
*
Tested and reliable hardware
*
Short-circuit-proof outputs
*
Graphic liquid crystal display with 128x64 pixels in the CamCon DC50,51.
*
Large
and
clearly
visible
7-Segment
display
for
program,
position
and
speed
on
CamCon DC30,33 and 40.
*
Any number of cams per output can be programmed.
*
Up to 32000 Programs for product administration
*
Master, for example: machine cams
*
Optimising switch points when machine is in operation
*
Compensation of mechanical delay time of switch components for switch-ON and switch-OFF
points can be set in steps of 100µs separately (DTC = delay time or Speed Compensation).
*
Position - Triggert - Time - Cams
*
Power supply 24V DC +/- 20%
*
Mounting of suspension rails to EN 50022 on CamCon DC16 and 90
*
Switchboard panel standard casing 144 x 144 x 63mm to DIN 43700 on CamCon DC33,40 and 51
*
S5 Components group for S5 115U, 135U and 155U on CamCon DC115
*
S7 Components group for S7 300 on CamCon DC300
*
AB Components group for ControlLogix 1756 on CamCon 1756-DICAM
*
S5 Switch-ON via PG interface with L1 - Bus on CamCon DC16,40,50,51 and 90
*
PLC Logic Module (optional)
*
Shift register (optional)
*
OP - Functions
*
Analog outputs (optional)
Cam switch units are used wherever switching operations are periodically repeated. Digital cam switch
units are an optimum replacement of mechanical units and offer in addition many other advantages,
such as:
*
Simplification of mounting and adjustment operations
*
Repeatable adjustment facility
*
Standardised for almost all areas of application
*
Reliability
*
High switch speed
*
Speed Compensation
*
Product administration for quick format change
Edition: 18.08.2004
Page: 5
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
2. Operating Pinciples
Diagram: Principles of a Cam Switch Unit
A principle for better comprehension of the function of a Cam Switch Unit is here presented. It has 3
outputs with the following cams:
Output 1:
Output 2:
Output 3:
Cam 1:
Cam 2:
Cam 3:
Cam 1:
Cam 2:
Cam 1:
Switch-ON position
Switch-ON position
Switch-ON position
Switch-ON position
Switch-ON position
Switch-ON position
60°
95°
325°
5°
95°
30°
Switch-OFF position
Switch-OFF position
Switch-OFF position
Switch-OFF position
Switch-OFF position
Switch-OFF position
85°
145°
355°
20°
145°
85°
The positions of the output signals, here presented as three tracks, occur when the three cam disks
turn anti-clockwise past a sensor, which scans the cams on the 0°-axis.
In a mechanical cam switch unit, the switch interval, i.e. the range between switch-ON and switch-OFF
position are determined by the length of the cam. The length and the position of the cam can only be
varied marginally and this is mechanically highly demanding and time consuming. With CamCon such
adjustments can be realised in a fraction of time; in addition, there can be any number of tracks. A
measuring system which is fitted to the device reports the position to the CamCon. The CamCon
compares it with the programmed switch-ON and Switch-OFF positions of all outputs. If the position
lies in the range of a programmed switch-ON / switch-OFF position (cam), then the respective outputs
are active.
Edition: 18.08.2004
Page: 6
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
2.1. Speed Compensation
Each mechanical switch component (e.g. shield, magnetic valve) has a delay time, i.e. the time
between the start signal and the actual switching of the contacts. In processes where positioning is
executed on a moving system, this can cause problems. If such a process is driven with different
speeds, different positions are caused. To avoid this happening, new timings for the switch signals of
each speed would have to be calculated.
In order to ilustrate the complicated issues surrounding delay time or speed compensation, this will be
shown on the example of a packaging machine. In the process shown in the diagram, a glue point has
to be placed in an exactly defined spot on a moving paper track.
magnetic valve
The system has the following parameters:
CamCon
vp
vT
d
glue nozzle
-
encoder
drop
TMV paper
Speed of the paper track
Falling speed of the drop of glue
Distance between the glue nozzle and
the paper track
Delay time of the magnetic valve
paper track
Points where the glue
hits the paper at the
different speeds
.
Without speed compensation the following would happen:
As soon as the measuring system has reached a certain position, the CamCon sends a signal to the
magnetic valve. The glue nozzle opens for a short time during which a drop of glue ejects. Between the
start of the impulse and the exit of the drop time passes, which is mainly caused by the delay time of
the magnetic valve TMV.. A further delay is caused by the time which the droplet needs to pass the
distance between the glue nozzle and the surface of the paper.
This flight time is calculated as follows:
d
tFlight = v
T
In total there the delay time is tFlight+TMV. During this time the paper track moves on by a specific
distance x.
It would now be possible to move the position, where the magnetic valve is switched on, forward by a
specific amount, so that the glue droplet hits the same spot again as during standstill. In this way a
speed compensation is created which works only at a specific speed of the paper. As soon as the
speed of the device and consequently that of the paper track is, for example, doubled, the hit point of
the glue droplet is shifted by the distance x, so that, without any speed compensation, it would move
backward by double the distance (2 ⋅ x) in total.
The automatic speed compensation of the CamCon makes it now possible to drive processes with
variable speed; CamCon registers the speed of the device continuously and adjusts the cams which
determine the switch time points "On Line" depending on the speed. This has the effect that the
outputs for the switch components are switched ON or OFF earlier. The direction of the movement is
of no significance in this instance.
Edition: 18.08.2004
Page: 7
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
A small example in figures was designed to eludicate:
Supposing the drive cylinder with the measuring system has a circumference of 360mm, so that one
millimeter of the circumference corresponds to exactly one angle degree of the measuring system.
The device has the following parameters:
vdroplet
d
TMV
=
=
=
20m/s
20cm
20ms
This results in the following flight time of the droplet:
d
0,2m
tFlight =
=
10ms
vT
20m/s =
The total delay time is then Tdead, altogether = TMV + tFlight = 20ms + 10ms = 30ms
During this time the paper track moves on by the distance x = vpaper ⋅ Ttotal delay. = 1m/s ⋅ 30ms =
30mm. In order to compensate the delay time, the switch point for the magnetic valve must be moved
forward by 30°.
If the speed of the device and consequently that of the paper is doubled vpaper, then the distance x is
also doubled by the speed of the paper track. In this case the switch point must be moved by 60°.
Note:
Please take into account in these explanations that delay time is of a fixed size, which is
determined by the mechanical constants of the set and switch components and by the
dimensions of the construction and therefore does not change!
If the total delay time of 30ms was programmed into the respective output of CamCon, then the glue
droplet would always hit the right spot, regardless of the speed.
Edition: 18.08.2004
Page: 8
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
2.1.1. Measuring delay time for Speed Compensation
Several ways of measuring delay time of a relay or valve are available.
2.1.1.1. Measuring delay time through actual differences
First the switch-ON point of a valve or relay is programmed. We assume that the programmed switch
point lies at 200 degrees in this case. If the machine is driven with a speed of for example 40 rpm, a
shift occurs due to delay time. This shift is then measured and, in this example, will amount to 40
degrees.
Warning:
For the calculation of the shift the programmed delay time in the cam switch unit must be
set to zero!
The delay time of the switch component is now calculated as follows:
∆ way (in °) * 60 (sec./min.)
Delay time ( in sec. ) = speed (in rpm) * 360 (°/turn)
40 * 60
Delay time ( in sec. ) = 40 * 360 = 0.1667 sec.
The resultant delay time is then entered into the cam switch unit.
See Chapter "6.3.11. TAG "DC_2_PRG_DTC[X]"" an page 41.
2.1.1.2. Measuring delay time by means of different measuring points
First the switch point is calculated at a speed of, for example, 50 rpm. We assume that the
programmed switch point lies at 200° in this case. The second measurement is taken at a speed of 80
rpm The necessary switch point must be set to 160°, if the exact switch point is to be also achieved at
80 rpm.
Warning:
For the calculation of the two switch points the programmed delay time in the cam switch
unit must be set to zero!
The delay time of the switch component is then calculated with the following formula:
Delay time ( in sec. ) =
∆ way (in °) * 60 (sec./min.)
∆ speed (in rpm) * 360 (°/turn)
40 * 60
Delay time ( in sec. ) = 30 * 360 = 0.222 sec.
The resultant delay time is then entered into the cam switch unit.
See Chapter "6.3.11. TAG "DC_2_PRG_DTC[X]"" an page 41.
Since the entered delay time shifts the switch point, the previously programmed cam must be changed.
For the calculation of the exact switch-ON position, the difference to the speed O rpm (here using 50
rpm) must be added to the first measured switch-ON point (here 200°). The difference is calculated
with the following formula:
∆ way (in degrees) =
dead time ( in sec. ) * ∆ time (in min-1) * 360 (degrees/rotations)
60 (sec./min.)
∆ way (in degrees) =
0.222 * 50 * 360
= 66.6 degrees
60
The switch-ON point of the cam is now shifted from 200° by approx. 67° to 267°.
Edition: 18.08.2004
Page: 9
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
2.1.2. Speed Compensation using off-centre pressure, e.g. brake functions
The Speed Compensation of the CamCon Cam switch unit works using a linear function. If, for
example, the speed doubles, then the shift of the compensated cam changes and also moves forward
by twice the amount. If the ram on an eccentric press should be brought to a standstill at the exact
upper stop point, the brake action of the press under different speeds results in a quadratic function.
The Speed Compensation can therefore only find an approximation of the exact switch point for the
stopping of the press by adjusting the line of the cam lines to the brake curves in the working range of
the press.
In the graphic on the right the curved line represents the
brake point of the ram in relation to the speed.
For the calculation of the parameters to be programmed
please proceed as follows:
-
Define the working range (e.g. 20-50 rpm) and determine
two measuring points which have to be specified in the
working process (e.g. 30 and 40 rpm).
-
Now let the machine run at 30 rpm and program or
optimise a cam without Speed Compensation so that, at
switch-OFF, the ram comes to a halt in top stop. Note the
switch-ON point of the cam (e.g. 340°).
-
Now let the maching work with 40 rpm and program or
optimise one cam without Speed Compensation so that,
at switch-OFF, the ram comes to a halt in top stop. Once
again, note the switch-On point of the cam. (e.g. 332°).
-
Now calculate the delay time, taking into account the
distance and speed difference, using this formula:
Delay time ( in sec. ) =
U/min
Verlauf
Nocke 1
Nocke 2
∆ way (in °) * 60 (sec./min.)
340-332 * 60
= 40-30 * 360 =
∆ Speed (in rpm.) * 360 (°/turn)
0.133 sec.
-
The calculated delay time is now entered into the cam switch unit.
-
Since the switch-OFF point has shifted through the entered Speed Compensation, the previously
programmed cam must be changed first. For the calculation of the exact switch-ON position, the
difference to the speed 0 rpm (here 30 rpm) must be added to the first measured switch-ON point
(first measuring point here 340°) The difference is calculated with the following formula:
∆ way (in °) =
-
delay time ( in sec. ) * ∆ Speed (in rpm.) * 360 (°/turn)
0.133 * 30 * 360
=
= 23.94°
60 (sec./min.)
60
The switch-ON point of the cam has now shifted from 340° by approx. 24° to 364°.
As a result a cam with a switch-ON point of 4° and a speed compensation of 0.133 sec has been
calculated. This is entered in the cam switch unit as switch-OFF cam of the press.
Note:
If the degree of accuracy is no longer sufficient when switch-OFF is done with one cam, two
or several outputs can be switched in parallel and the cam of those is then adjusted to the
required working range. For the calculation of two switch-OFF cams divide the working
range in 5 parts with 4 measuring points and then calculate the delay time value and the
cam value with the same formula as described above. For the calculation of the first cam,
use the measuring points 1 + 2 and for the calculation of the second cam use the
measuring point 3 + 4.
Through this association of the linear cam functions to the brake functions it is now possible to switch
OFF the cam via the entire working range of the press in the top stop.
Edition: 18.08.2004
Page: 10
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
2.1.3. Separate delay time for Speed Compensation of switch-ON and switch-OFF points
For CamCon devices of Software from 3/2002 Speed Compensation is now available for separate
switch-ON and switch-OFF points. This is necessary since some valves need longer to switch OFF
than to switch ON.
Switching attitude of a cam programs from 140° to 200° with 60 min -1.
Cam with 111ms Speed compensation for switch on point and 166ms
compensation for switch off point.
Cam with 111ms Speed compensation.
Cam without Speed compensation.
For the calculation of both delay times the same formuli are used as for a normal compensation. See
Chapter "2.1.1. Measuring delay time for Speed Compensation" on page 9 for entering delay time see
Chapter "6.3.11. TAG "DC_2_PRG_DTC[X]"" on page 41.
Attention: If the switch-off-point of a Cam overtakes the switch on point at rising speed, the result will
be an non-defined signal.
2.2. Time - Cam
With nomale cam becomes with increasing plant speed switch-on time ever more briefly. If controlling
a glueing-station, the result would be an insufficent ammount of spreaded glue.
A Time - cam however has with each plant speed a firm temporal length, so that excactly the same
ammount of glue could be spread at changing speeds. The switch-on point of the Cam on a normal as
well as on a Time-Cam is appointed by a position-dependent Position value and a delay-time/speed
compensation.
Normal - cam
Time - cam
60min-1
60min-1
30min-1
30min-1
For CamCon devices of software releases after 3/2002 Time Cam is also available for devices without
PLC - Logic - Module.
For entering a Time - Cam see Chapter "6.3.11. TAG "DC_2_PRG_DTC[X]"" on page 41.
Edition: 18.08.2004
Page: 11
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
3. Installation
Note:
The component group CamCon 1756-DICAM can be plugged in and pulled out when the
power is on, but this should be avoided whenever possible.
*
All assembly work and cable connections must be carried out when power is OFF!
*
Consult the ControlLogix instruction manual.
*
Switch ControlLogix CPU to STOP and disconnect the power supply to the components base into
which you wish to insert the CamCon 1756-DICAM.
*
The power supply (5V) of all component groups on a base must not exceed the maximum current
supply. Please consult the instruction manual for the ControlLogix. The Current load of the CamCon
1756-DICAM amounts to typically 450mA.
*
Push the CamCon 1756-DICAM into the components base until the metal pin engages audibly.
*
The grounding of the CamCon 1756-DICAM is made by the grounded rack of the ControlLogix.
*
The connecting cable for the measuring system must be screened and the screening must be laid
down at both ends. For this purpose the screening of the cable should be attached to the
components base by the shortest route.
*
Wire up the CamCon 1756-DICAM in accordance with the cabling instruction in Chapter "4.
Electrical connections" on page 14. The 36-pole CLX connecting plug is not part of the delivery
package containing the CamCon 1756-DICAM (AB Order Nr.:1756-TBCH). Insert the connected
plug into the component group and lock it by pulling down the small lever next to the status display.
*
When all cables are connected, operations can start. See chapter "5. Starting" on page 23 and for
Installation of the CamCon 1756-DICAM in the programming software see chapter "5.1. Planning
the ControlLogix CPU for CamCon 1756-DICAM" on page 23.
Note:
You can order the 36-pole CLX connecting plug and a label with the pin layout complete at
Digitronic Order Nr.: DC1756/ZB!
Edition: 18.08.2004
Page: 12
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
3.1. Dimensions
The diagram shows a CamCon 1756 - DICAM.
Edition: 18.08.2004
Page: 13
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
4. Electrical connections
Before you begin with wiring, please consult the following chapters: "4.10. The outputs" on page 21,
"4.11. The inputs" on page 21 and "4.9. The measuring system" on page 17.
4.1. Power supply to CamCon
Pins
2,4,6:
+24V power supply for measuring system and internal hardware.
The CamCon 1756-DICAM is supplied with 5V (approx. 450mA current input) via the PLC bus. The
periphery of the 1756-DICAM must in addition be supplied with power since it is galvanized and thus
separated from the BUS. The functioning of the periphery (measuring system, i.e. Encoder) depends
on a power supply of +24V at pins 2, 4 or 6. These act simultaneously as the power supply for the
three output blocks which should be connected to each output block since these are not connected to
each other for reasons of better current distribution and can be switched off individually in emergency.
Warning: If the power supply to the measuring system is short-circuited (>2Amp.) or exceeds the total
supply of an output block over 6 Ampere, for example wrong polarity, a Mini - Melt - Fuse
on the circuit board blows. If is melted the CamCon must sent to repair.
4.2. Output pin layout
Pin
Pin
Pin
Pin
Pin
Pin
Pin
Pin
Pin
Pin
2:
1:
3:
5:
7:
9:
11:
13:
15:
17:
+24V power supply outputs 1 - 8
Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
0V
Pin
Pin
Pin
Pin
Pin
Pin
Pin
Pin
Pin
Pin
4:
19:
21:
23:
25:
27:
29:
31:
33:
35:
+24V power supply outputs 9 - 16
Output 9
Output 10
Output 11
Output 12
Output 13
Output 14
Output 15
Output 16
0V
Pin
Pin
Pin
Pin
Pin
Pin
Pin
Pin
Pin
Pin
6:
20:
22:
24:
26:
28:
30:
32:
34:
36:
+24V power supply outputs 17 - 24 respective inputs 1-8
Output 17
Output 18
Output 19
Output 20
Output 21
Output 22
Output 23
Output 24
0V
Note:
The pins 17, 35, 36 and 18 are linked within the device.
Edition: 18.08.2004
Page: 14
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
4.3. Pin layout of inputs (Option)
The connecting pins of the inputs 1 - 8 and the outputs 17 - 24 serve a double use. If, for example,
output 24 is set, input 1 is also active.
Attention: The power supply must be connected absolutely to terminal 6, even if the outputs 1724 are used as inputs.
Pin
Pin
Pin
Pin
Pin
Pin
Pin
Pin
Pin
20:
22:
24:
26:
28:
30:
32:
34:
36:
F
Input 8 / Output 17
Input 7 / Output 18
Input 6 / Output 19
Input 5 / Output 20
Input 4 / Output 21
Input 3 / Output 22
Input 2 / Output 23
Input 1 / Output 24
0V
4.4. Pin layout of RS422 SSI measuring system
Pin
Pin
Pin
Pin
Pin
Pin
8:
10:
12:
14:
16:
18:
+24V DC power supply for the SSI measuring system (encoder)
(RS422) Clock B or Clock (RS422) Clock A or Clock +
(RS422) Data B or Data (RS422) Data A or Data +
0V power supply for the SSI measuring systems (encoder)
4.5. Pin layout at 24Volt incremental measuring system
Pin
Pin
Pin
Pin
Pin
Pin
8:
10:
12:
14:
16:
18:
+24V DC Power supply for the incremental - measuring systems (encoder)
(24Volt) Clear 2
(24Volt) Clear 1
(24Volt) B Impulse
(24Volt) A Impulse
0V Power supply for the incremental - measuring systems (encoder)
The signals Clear 1 and Clear 2 are set to zero by default AND linked; their function can be changed
with the software. See chapter "6.3.6.3. TAG "DC_1_SYSTEM_CONFIG_ENC_2_INK"" on page 35 for
setting the necessary parameters and chapter "4.9.3. Incremental measuring system input" on page
18.
4.6. Pin layout for Hiperface incremental measuring system
Pin
Pin
Pin
Pin
Pin
Pin
8:
10:
12:
14:
16:
18:
+24V DC Power supply
REFCOS
COS (B)
REFSIN
SIN (A)
0V Power supply, i.e. reference potential of the measuring system
See chapter "6.3.6.3. TAG "DC_1_SYSTEM_CONFIG_ENC_2_INK"" on page 35 for setting the
necessary parameters.
Note:
The pins 17, 18, 35 and 36 are linked within the device.
2
Note:
Pin 8 is supplied with power via diodes through pins 2, 4, or 6.
4
6
Edition: 18.08.2004
8
Page: 15
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
4.7. Clamping allocation of the external interface (option)
If you order an external interface additional to the CamCon (option X) the number of hardware-outputs
at the device is reduced from 18 to 24 and the option hardwareinputs at the device is not more
avaiable. Therefor, you are able to connect additional in- or outputs via a CamCon DC91/IO or DC92/I
module. The extension modules are snapped upon a a carrier-rail in the switch-panel and are
connected to the CamCon IO-module via a 6 pole cable, type KK1756/IO-XX, with the 9 poe. D-Sub
male plug "external Inter. in" (max. 300m wiring distance). The data transfer takes place free of
potentials via optical couplers.
Terminal
Terminal
Terminal
Terminal
Terminal
Terminal
24:
26:
28:
30:
32:
34:
RxD
RxD
TxD
TxD
Clk
Clk
+
+
CamCon 1756-DICAM
CamCon DC91/IO o. DC92/I
external
interface
external
interface
30
28
34
32
26
24
DSUB 9 female plug:
Connection for external
modules.
e.g. DC91/IO or DC92/I
Pin 1,4,7
Pin
2
Pin
6
Pin
8
Pin
3
Pin
5
Pin
9
GND
TxD
TxD
CLK
CLK
RxD
RxD
In-
and
output-
+
+
+
-
4.8. RS485 interface (only for test mode)
Attention: The RS485 interface of the CamCon 1756 DICAM is only allowed to be used for test- or
debug-modes of the PLC - Logic - functions of the programing-software DIGISOFT 2000.
A permanent installation is not allowed i.e. can cause EMV - malfunctions at the PLC.
The flatwire-connection cable with a maximum length of 30cm and a 10 pole female-plug inserted into
the device's case at the BUS-side of the device, where it is plugged into a 10 pole poleplug. If the PLC
saubassembly-carrier is fully mounted, the cable has to be lead between two subbassemblies to the
outer side.
Cable type: KK 1756 RS485"
Note:
Pin
Pin
Pin
2
3
5
B (-)
A (+)
GND
Additional to the cable "KK1756 RS485" the levelconverter "COMUCA/USB is required.
Edition: 18.08.2004
Page: 16
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
4.9. The measuring system
The measuring system is designed to record the necessary actual values (positions) for the Cam
Switch Unit. Many different measuring system can be linked with the CamCon.
See chapter "4. Electrical connections" on page 14 and for adjustment of the measuring system to the
software of the CamCons please also consult Chapter "6.3.5. TAG "DC_1_SYSTEM_CONFIG" Value:
DINT[0]" on page 31.
Note: Please also consult the instruction manual for your measuring system.
4.9.1. SSI Measuring system input
Systems with a synchronous series interface = SSI. The SSI interface is widely used in industry for
absolute single and multi-turn angle encoder. At this interface the CamCon supplies the measuring
system with 24Volt. For the purpose of data reading the CamCon sends a stroke signal (clock) with
RS422 level to the measuring system. This answers synchronously with the data output of the position
in the grey code. The frequency of the pulse signal depends on the length of the cable to the
measuring system and can be set in the CamCon.
Note: The data record corresponds to the Stegmann SSI Standard!
Clock
Tp
Data
Tmono
= clock impulse
max. 1MHz to min. 66kHz.
(adjustable through the cable
length)
= Mono flop time 25µs
Encoder
CamCon
+24V DC
0V
Clock +
Clock -
Please note:
Use a screened dual strand connection cable. Do not place
the cable parallel to a high voltage cable. If possible, lay the
screening down on both sides.
Data +
Data -
4.9.2. Parallel measuring system input
Systems with parallel 24V data leads, e.g. single turn - angle encoder or via a transformer with parallel
data output.
In this instance a gray or binary encoded value is attached to the free inputs of the CamCon and this
will be read as actual value. Since the connection cable are quite expensive and the EMV compatibility is limited, this interface type is rarely used in industry nowadays.
Note:
Since the outputs are partly switched parallel to the inputs in CamCon DC16, DC115,
DC300 and CamCon 1756-DICAM, these must not be programmed under any
circumstances and this reduces the number of available outputs.
Warning:
Reading a binary encoded value into the CamCon is only permitted after consultation with
the Service department of the company Digitronic.
Edition: 18.08.2004
Page: 17
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
4.9.3. Incremental measuring system input
Systems with 90° phase shift signals such as turning angle encoders, glass measuring rods or flow
measuring devices.
At the present time incremental measuring inputs for the CamCon DC16/50/51/115/300 and DC1756
are available as an option. We differentiate between three signal levels:
Note:
24V PNP Signal inputs
5V RS422 Signal inputs
Hiperface Signal inputs
(Order number Option: J)
(Order number Option: I)
(Order number Option: H)
For the CamCon DC16 and DC300 only the version with 24V PNP signal is available. For
the CamCon 1756-DICAM the version with 24V PNP signal and Hiperface Signal is
available. If a different signal level is necessary, this can be converted externally with the
INCDRV converter.
In all cases the CamCon supplies the measuring system with 24Volt/DC or in CamCon DC115
optionally with 5 or 24Volt/DC. As a counting signal the measuring system gives out two impulses at a
time shifted by 90° (A + B). These are counted in the CamCon and are evaluated as position values. In
addition, for each rotation another zero impulse (Clear 1) is given out for synchronisation purposes. In
order to stop synchronisation (zero setting) of the counter, a further clear signal (Clear 2) is available
on the CamCon.
The signals Clear 1 and Clear 2 are to standard AND linked and can be
changed in their function with the software. See Chapter "6.3.6.3. TAG
"DC_1_SYSTEM_CONFIG_ENC_2_INK"" on page 35
A Imp.
B Imp.
Clear 1
4.9.3.1. Incremental measuring system input with 5V RS422 level
Clear 2
If the 5V RS422 system is used, all signals of the measuring
system input must be active, otherwise the input conditions are
undefined. If no signal is available for one of the two Clear
inputs, then this input must be switched to mass on the (+)
signal in order to switch the input to low. The inputs of the
measuring system can be activated with a maximum voltage of
5V. Please pay attention to the power supply of the angle
encoder which can be 5Volt as well as 24Volt. Only the CamCon
DC115 can at present provide a voltage of 5Volt for the supply of
the angle encoder.
4.9.3.2. Incremental measuring system input with 24V PNP level
If a 24V PNP signal is used for data input, then only the (+)
signals of the inputs may be connected. The (-) signals must
stay inactive in this case. The connection of such a measuring
system requires a change of the interal switch system and must
therefore be stated on the order form.
Note:
At the incremental input of the CamCon DC16,
DC300 and DC1756 no (-) signals are available.
Edition: 18.08.2004
Page: 18
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
4.9.3.3. Incremental Hiperface measuring system input with SINCOS level
The Hiperface measuring system is a feedback system for servo-motors of the company Stegmann.
It is a mixed system and consists of an absolute measuring system and an incremental measuring
system. The absolute measuring system sends its values via RS485 interface to the counter. The
incremental measuring system works with analog sine - and cosine interface with a resolution of 512 or
1024 impulses per revolution.
The CamCon with the Hiperface signal input
(option: H) reads only the incremental sine - and
cosine signal. The signals are converted and
counted in the CamCon into normal incremental
measuring system signals.
CamCon
Since the absolute measuring system of the
Hiperface interface is not used and no clear signals are available, the CamCon must be
initialized after each restart.
controller
SINCOS
This must be done by the preset input or the
instruction ''actual value set'' of the CamCon. See
for
this
to
chapter
6.3.5.
TAG
"DC_1_SYSTEM_CONFIG" Value: DINT[16] on
page
32
and
chapter
6.3.8.
TAG
"DC_1_SYSTEM_SET_ACTUAL_VALUE" on page 40.
Note:
The maximum number of revolutions per minute is 3000 min-1 with 512 Impulse per
revolution.
The maximum number of revolutions per minute is 1500 min-1 with 1024 Impulse per
revolution.
4.9.4. Analog measuring system input
These are systems which receive their actual value through conversion of current or voltage signal,
such as temperature or pressure sensors.
For the recording of analog signals the analog to SSI conversion module AWA/SSI in 8 and 12 bit
resolution is available for the CamCon. This module is connected to the SSI of the CamCon and is
switched ON through the selection of the analog measuring system in the menu ”Measuring system”.
Edition: 18.08.2004
Page: 19
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
4.9.5. PLL measuring system input
Systems with Phase - Lock - Loop data recording. In these systems the actual value is found through
interpolation of initiator impulses. This measuring system is applied to machines with constant speed
and with a cyclic pulse.
= Initiator impulse
= Found actual value
The Initiator can be connected to any free input of the CamCon.
Note:
For CamCon DC115 a special input is available on the 25pol. SUB-D plug.
See also chapter "6.3.6.5. TAG "DC_1_SYSTEM_CONFIG_ENC_4_PLL"" on page 36.
4.9.6. Timer as a measuring system
Systems which are controlled by elapsed time. In this case the CamCon makes a time available with a
time basis of minimum 1 ms as actual value. Through laying on of input signals it is possible to
influence the elapsed time. This measuring system is applied to machines with a fixed time scanner as
a control feature, e.g. washing machines.
See also chapter "6.3.6.6. TAG "DC_1_SYSTEM_CONFIG_ENC_5_TIMER"" on page 36.
4.9.7. RS232 as a measuring system
Systems, receiving their actual position through the RS232 interface, e.g. for a junction of a Stegmann
POMUX linear scale to a RS232 data output.
Warning
The activation of this measuring system blocks the RS232 interface for
programming. This measuring system is only reasonable with a CamCon
DC50/51.
Edition: 18.08.2004
Page: 20
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
4.10. The outputs
The CamCon 1756-DICAM has 24 short-circuit outputs. They give out 24Volt high - active signals and
are isolated from the system BUS. The +24V power supply of the output blocks 1-8, 9-16 and 17-24
are separated from each other for the purpose of current distribution; therefore each output block must
be supplied with +24Volt externally. The outputs deliver continuous power supply of 0.2 Amp. or 0.4
Amp. at 50% ED per channel. See also chapter "6.3.5. TAG "DC_1_SYSTEM_CONFIG" Value:
DINT[31]" on page 32 and chapter "6.3.5. TAG "DC_1_SYSTEM_CONFIG" Value: DINT[47]" on page
33. In addition, a mini-melt-fuse has been inserted for each output block which will blow of short-circuit
or currents over 6 amps.
If they are melted, send in the device for repairing.
Note:
The outputs 17 - 24 share the pins with the optional inputs 1 - 8.
Note:
The outputs must be set to free through PLC. See chapter "5.1.2. The O - Range"
on page 24.
Warning:
For inductive loads a flywheeling diode is required.
4.11. The inputs
The CamCon 1756-DICAM can be mounted with 8 inputs as an option. These inputs work with high
active 24Volt signals and are isolated from the system BUS.
Note:
The inputs 1 - 8 share the pins with the outputs 17 -24.
The input wiring:
The input resistance
is about 5.7 KOhm.
The inputs of the CamCon have not been covered with functions by the factory. The user would have
to do this himself in the process of setting system data of the CamCon depending on his requirements.
See chapter "6.3.5. TAG "DC_1_SYSTEM_CONFIG" Value: DINT[30]" on page 32, chapter "6.3.5.
TAG "DC_1_SYSTEM_CONFIG" Value: DINT[0]" on page 31, chapter "6.3.5. TAG
"DC_1_SYSTEM_CONFIG" Value: DINT[34]" on page 33 and chapter "6.3.5. TAG
"DC_1_SYSTEM_CONFIG" Value: DINT[16]" on page 32.
4.12. Precautionary measures for welding work
Attention: For the duration of welding operations carried out at the machine, the
connecting wires concerning the data exchange from the measuring system to
the CamCon and the power supply as well as the grounding connections and
inputs and outputs have to be separated from the CamCon.
Edition: 18.08.2004
Page: 21
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
4.13. Status Displays
The CamCon 1756-DICAM has several Status Displays. These include: 32 Output
displays (LED 0 up to 31 for Output 1 to 32) and a Status LED (OK-LED). In addition,
in the I-Range of the CamCon status information is indicated, which can be evaluated
through the ControlLogix CPU (see Chapter "4.13.2. Status Bits in the I - Range").
4.13.1. Status LED
The Status LED (OK-LED) of the CamCon 1756-DICAM indicates as follows:
GREEN light
RED blinking
GREEN blinking
ORANGE light
= Communication between CamCon and ControlLogix OK.
= Firmware UP-Date via ControlFLASH.
= ControlLogix CPU in Stop mode, i.e. the CamCon is not accessed by the
software.
= ASIC in Reset.
4.13.2. Status Bits in the I - Range
In the I-Range of the CamCon 1756-DICAM component group the following information is transferred:
INT 0,1:
INT 2:
reserved for ControlLogix intern (0 = OK, not 0 = error)
Hardware status of the CamCon.
Bit 0 =
Output error, short circuit or overload (low active).
Bit 1 =
Hardware release of CamCon outputs (low active).
Bit 2 =
Hardware reset, the IO periphery of the CamCon is in reset mode (low aktiv).
Bit 3 =
Always 0; if this Bit = 1, there is no current supply on the IO periphery of the
CamCon and die other Bits in this Byte are always 1, i.e. undefined.
Bit 4 =
Power supply Output 1 - 8 ON.
Bit 5 =
Power supply Output 9 - 16 ON.
Bit 6 =
Power supply Output 17 - 24 ON.
Bit 7 =
Power supply IO periphery and measuring system ON.
Status range for MSG commands.
Bit 8 =
CMD_OK
= Last written message successful.
Bit 9 =
CMD_IN_USE = Command is being carried out.
Bit 10 =
CMD_ERROR = Error at execution of last written message.
Bit 11-14: not in use.
Bit 15 =
EXOR_BIT
= This Bit toggles after each execution of a written
message.
INT 3,.. and all of the following contain the Output Bits of the CamCon.
Example:
32 Outputs with active real time transfer for speed (Speed analogue = yes) and position
display (Actual value output = Bin.).
INT 3
= Status outputs 1 - 16.
INT 4
= Status outputs 17 - 32.
INT 5
= Actual speed as 15 Bit values with signs
and an offset of 8000Hex, scaled to 100% value in the CamCon.
(See the calculation example in the DICAM1756 program, i.e.Chapter
"6.4. Transferring actual value and speed into realtime" on page 44.)
INT 6,7
= Actual position as 32 Bit value
Note:
In addition to the described Status Bits an output parameter of the CamCon can be set as
a safety output, i.e. as RUN - Control. (Chapter "6.3.5. TAG "DC_1_SYSTEM_CONFIG"
Value: DINT[25]" on page 32) which is switched off when an error occurs. If this is not
active, the exact error can be found by checking the status question (Chapter "6.3.12.
TAG "DC_3_STATUS"" on page 41).
Edition: 18.08.2004
Page: 22
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
5. Starting
After assembly and before the first switch-on please check the wiring of the device. See Chapter "4.
Electrical connections" on page 14.
Warning:
For inductive loads a flywheeling diode is required.
After switching on the power supply on the ControlLogix component base, the device signals
with a short flicker of the Status LED (OK-LED). This is followed by an check of the loading of the
systems (i.e. the checked total of the EPROM and the EPROM are evaluated). This takes a few
seconds. When this process is finished, the BUS is initialized.
5.1. Planning the ControlLogix CPU for CamCon 1756-DICAM
In order to plan your ControlLogix CPU open your
RSLogix
5000
Project
and
insert
into
the
"I/O Configuration" a "Generic 1756 Module" into the
relevant slot.
Input the parameters shown in the next diagram:
This value corresponds to the number of hardware outputs of the CamCon; it
must be adapted to the requirements of the device. The CamCon can
administer up to maximum 200 outputs. In addition, a further 6 Bytes are
necessary for the status display and for communication. These are described
in Chapter "4.13.2. Status Bits in the I - Range" on page 22.
If the actual value and the speed are to be translated into realtime, then 2
INT must be added for the actual value and 1 INT for the speed value. See
Chapter "6.4. Transferring actual value and speed into realtime" on page 44.
Above this value you set the number of Bits which are then sent to the
CamCon in cycles. These are used as enable Bits for the cams of the
CamCon and must be set to 1, so that the respective output can be switched
on when the cam is active.
0
Slotnummer
INT
DICAM
1
194
100
Note:
The data exchange between the CamCon 1756DICAM component group ControlLogix CPU may be
set to 0.2 for Firmware Version 1.9 or later only.
Edition: 18.08.2004
Page: 23
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
5.1.1. The I - Range
The status display lies within the input range of the CamCon 1756 - DICAM. See Chapter "4.13.2.
Status Bits in the I - Range" on page 22.
5.1.2. The O - Range
The enable Bits of the CamCon 1756 - DICAM lie in the output range. The ControlLogix PLC must set
a respective bit to free each output at a time so that this can be switched on by the Cam Switch Unit.
Bit 0 in the first INT "Local:X:O.Data[0]" is the release Bit for output 1 of the CamCon. Bit 0 in the
second INT "Local:X:O.Data[1]" is the release for output 17 of the CamCon etc..
Note:
Outputs i.e. release bits are linked to the CamCon Outputs AND (Output switch-off).
When the PLC - Logic - Module is switched on, the release bits are made available as V inputs to the PLC - Logic - Module. See the Instruction Manual of the PLC - Logic Module (Order Nr.: H-SPS/E).
5.1.3. The C - Range
The configuration range of the CamCon 1756 - DICAM is not used currently.
Edition: 18.08.2004
Page: 24
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
6. Communication between ControlLogix 1756 CPU and CamCon 1756-DICAM
Communication between the ControlLogix CPU and the CamCon 1756-DICAM takes place via the
back panel Bus. Some function components are needed and "User-Defined" Data types which are
available under Order Nr.:DC1756/HB.
NOTE:
If parameters, cams or delay times are cyclically written, then the EEPROMS data
memory is destroyed after short time. If this is however necessary for certain reasons,
then the EEPROM must lock. See Chapter "6.3.3. TAG "DC_0_EEPROM_LOCK"" on
page 30
6.1. Installation of the Software
The software RSLogix 5000 Project V8.02 is available on disk or on the internet. The project name is
"DC1756". You can read about the software version in the "DICAM1756" program characteristics (right
mouse button).
For installation the following consecutive steps must be carried out:
-
Open the desired project in a RSLogix 5000 sitting.
-
Add to the I/O configuration the CamCon 1756-DICAM with the name "DICAM" as described in
Chapter "5.1. Planning the ControlLogix CPU for CamCon 1756-DICAM".
-
Open the DC1756 project on the disk in a second RSLogix session.
-
Copy into your own project via clipboard (Copy+Paste) from the "Data Types" all "User-Defined"
projects of the DC1756.
-
Copy into your own project via clipboard (Copy+Paste) all "Controller Tags" of the DC1756 project
which begin with "DC_".
-
Change in all the Alias "Controller TAGs" "DC_5_" the Base TAGs to the slot number of your
CamCon 1756 - DICAM.
-
Change the index for the number of outputs and the type for the number of cams for each output
in the "Controller TAG" DC_2_PRG_CAM[x].
If you apply the PLC - Logic - Module of the CamCon DC1756-DICAM you also change the index
of the DC_1_SYSTEM_CONFIG_PLC[x] TAGs to the number of necessary link networks.
TIP: The programingsoftware DIGISOFT 2000 enables programing the PLC-Logic-module also
"Offline" with the PLC-Logic-module's editor. This programing can be transfered by an L5K export i.e. import to the ControlLogix. For this purpose see also the DIGISOFT 2000's manual
chapter "Export"
-
Copy the "DICAM1756" progam from the DC1756 project into the "Main-Task" of your project.
-
Enter the necessary data in the "Controller TAG" DC_1_SYSTEM_CONFIG.
-
Installation is now complete.
In the "MainProgramm" of the DC1756 project you will find a few examples of how the program can be
used.
Note:
During copying via the clipboard parts of the information related to the DC_9_MSG TAGs
are lost. Should you have to re-enter these, please see Chapter "6.2.1. The write program
DC_9_DATA_WRITE" on page 27 and Chapter "6.2.2. The read program
DC_9_DATA_READ" on page 28. There you will find the necessary parameters
described.
Edition: 18.08.2004
Page: 25
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
6.2. General Information on the Software
The data transfer between CamCon 1756-DICAM and ControlLogix is carried out through
"CIP Generic Messages".
All parameters, cams, delay times and status displays of the CamCon can be written and read. These
are divided into 256 DINTs each (0..255) in 255 data-ranges (1..255) and are predefined through
"User-Defined" TAGs in the RSLogix 5000 software.
Each TAG represents a dataset and consists initially of an address (ADR) and a stipulated number of
DINTs into which those data are placed which are to be read or written.
The address (ADR) TAG is based on the "DC_9_HEADER" and the "DC_9_CMD_BITS "UserDefined" TAG. Initially the range numbers (RANGE), the offset in the range (OFFSET) and the number
of DINTs (DATA_LEN) which are to be transferred must be entered. At the present time a maximum of
120 DINTs can be transferred with one MSG. Via the TAG "DC_9_CMD_BITS" a flag READ or WRITE
is placed on the dataset. For the status display the bits data transfer running (RUN), Data Transfer
successfully executed (OK) and Data Transfer was not successfully executed (ERROR) are stored in
the CMD_BITS.
Note:
The description of the individual TAGs and the meaning of the data can be found in Chapter
"6.3. The Controller TAGs of the CamCon 1756-DICAM" on page 30.
The dataset filled with the address and the used data can now be transferred into the subprogram
DC_9_DATA_WRITE and DC_9_DATA_READ of the DICAM1756 program. The subprogram is called
up by the programs DC_2_ALL. Here the read and write bits of the individual datasets are evaluated
and the transfer programs are called up. Each write or read access always requires initially a write and then a second write or read message respectively. The two progams WRITE and READ see to the
correct procedure and set or reset the respective bits in the dataset after successful transfer. If the
data transfer takes longer than 5 seconds, control bit DC_5_STATUS_COMM_TIMEOUT is set and
the dataset is confirmed with an error meassage and the command is repeated. An error message
through the CamCon to a dataset is signified by the Control Bit DC_5_STATUS_COMM_ERROR.
Further subprograms in the DICAM1756 program are:
DC_1_MAIN:
DICAM1756 main program,
calls up DC_0_INIT once,
calls up the subprogram DC_2_ALL,
calculates the actual realtime speed, ,
checks the status,
and carries out an error reset every 5 seconds when an error
message has been reported.
DC_0_INIT:
Initializing of all general data and of the datasets,
calling up the subprogram "DC_0_INIT_LOOP" with a FOR
loop. In case of a change of cam and delay time tables the
number of loops is also changed.
Subprogram of DC_0_INIT.
DC_0_INIT_LOOP:
DC_2_ALL:
DC_2_ALL_CAM_LOOP:
DC_2_ALL_PLC_LOOP:
DC_2_ALL_TZK_LOOP:
Here the read and write Bits of the individual datasets are
evaluated and the transfer programs are called up. In case of a
change of cam and delay time tables the number of loops is
also changed.
Subprogram of DC_2_ALL.
Subprogram of DC_2_ALL.
Subprogram of DC_2_ALL.
Edition: 18.08.2004
Page: 26
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
6.2.1. The write program DC_9_DATA_WRITE for parameter, cams or delay times
In order to write a parameter, a cam or a delay time, the CamCon must first be informed of the target
range by means of a write-message. This always consists of 3 DINTs (12 bytes) and is transferred
through the "Service Code:" = 10, the "Class name:" = 4 and the "Instance name:" = 100 with a length
of 12 bytes to the CamCon 1756-DICAM (Communication / Path = DICAM).
DC_9_MSG_BUFFER_TMP.ADR
The construction of the source range, in the example "DC_9_MSG_BUFFER_TMP", consists of 3
DINTs, whereby the first DINT covers the target range (1..255), the second DINT the Offset in the
target range (0..255) and the third DINT the number of DINTs which are to be written.
The message must only be set when the bit "CMD_IN_USE" (See Chapter "4.13.2. Status Bits in the I Range") is not acitve. The "DN" Bit of the message itself as well as the bits "CMD_OK" or, in the case
of an error the Bit "CMD_ERROR" confirms the MSG. At the end of writing the first message the
"EXOR_BIT" toggles its place and the "CMD_IN_USE" Bit goes back to 0. If the MSG was successful,
then the actual data range with the parameters i.e. cams or delay times can be sent.
The second message must contain exactly as many
DINTs as previously stipulated. It is transferred through
the "Service Code:" = 10, the "Class name:" = 4 and the
"Instance name:" = 101 with the respective length =
number of DINTs * 4 (this is adapted during the program
runtime i.e. calculated) to the CamCon 1756-DICAM
(Communication / Path = DICAM).
DC_9_MSG_BUFFER_TMP.DATA
The second message must not be stopped when the bit
"CMD_IN_USE" is active. The "DN" bit of the message
itself as well as the bits "CMD_OK" or "CMD_ERROR"
also confirm the MSG. In this case it is possible that the
"DN" of the message is already active, but the bits
"CMD_OK" or "CMD_ERROR" are not yet set. At the end of writing the second message the
"EXOR_BIT" once again changes its place, the "CMD_IN_USE" bit goes back to 0 and the command
has now either been carried out successfully or has been processed with an error.
Note:
Since the bits in the I - Range can be asynchronous to the program run, it is possible that
the PLC Program cannot recognise the bit "CMD_IN_USE". Only through evaluating the
"EXOR_BIT" will it be discernible whether a write - MSG has arrived and is finished.
Note:
If the data transfer takes longer than 5 seconds, a Control Bit
DC_5_STATUS_COMM_TIMEOUT is set, the dataset is confirmed with an error
message and the command is repeated. An error message through the CamCon to a
dataset is signified by the Control Bit DC_5_STATUS_COMM_ERROR.
Edition: 18.08.2004
Page: 27
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
6.2.2. The read program DC_9_DATA_READ for Status, Parameter, Cams or Delay Times
In order to read the status, a parameter, a cam or a delay time, the CamCon 1756-DICAM must first be
informed of the source range through a write message. This always consists of 3 DINTs (12 bytes) and
is transferred through the "Service Code:" = 10, the "Class name:" = 4 and the "Instance name:" = 100
with a length of 12 bytes to the CamCon 1756-DICAM (Communication / Path = DICAM).
The construction of the source range, in the example
"DC_9_MSG_BUFFER_TMP", consists of 3 DINTs,
whereby the first DINT covers the source range (1..255),
the second DINT the Offset in the source range (0..255)
and the 3. DINT the number of DINTs which are to be
read.
DC_9_MSG_BUFFER_TMP.ADR.RANGE
The message can only be set when the bit
"CMD_IN_USE" (see Chapter "4.13.2. Status Bits in the
I - Range") is not active. The "DN" bit of the message
itself as well as the bits "CMD_OK" or, in the case of an
error the bit "CMD_ERROR", confirm this MSG. At the
end of writing the first message the EXOR_BIT toggles
its place and the "CMD_IN_USE" Bit goes back to 0. If the MSG was successful, then the actual data
range with the status, the parameters i.e. cams or delay times can be read.
The second message in the "Destination" range must be
allocated exactly as many DINTs as previously
stipulated. It reads through the "Service Code:" = e, the
"Class name:" = 4 and the "Instance name:" = 101 the
CamCon 1756-DICAM data.
Note:
In this case the length must always be
specified as 0, since the lengths was already
fixed by the first message.
DC_9_MSG_BUFFER_TMP.DATA
The second message must only be set when the bit
"CMD_IN_USE" is not active. The "DN" bit of the
message itself as well as the bits "CMD_OK" or
"CMD_ERROR" also confirm the MSG. The read command has now been carried out successfully or
has been processed with an error.
Note:
Since the Bits in the I-Range run asynchronous to the program, it is possible that the PLC
program cannot recognise the Bit "CMD_IN_USE". Only through evaluating the
"EXOR_BITs” will it be discernible whether a write - MSG has arrived and is finished.
Note:
If the data transfer takes longer than 5 seconds, a Control Bit
DC_5_STATUS_COMM_TIMEOUT is set, the dataset is confirmed with an error
message and the command is repeated. An error message through the CamCon to a
dataset is signified by the Control Bit DC_5_STATUS_COMM_ERROR.
Edition: 18.08.2004
Page: 28
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
6.2.3. The TAGs of the "DICAM1756" Program
Type
Name
Data
DINT
NMB_CAM_OUTPUTS
1..62
DINT
NMB_OUTPUTS
1..200
DINT
NMB_PLC_LOGIC
1..896
DINT
NMB_DTC_OUTPUTS
1..200
BOOL
BOOL
BOOL
BOOL
DC_5_STATUS_COM
M_RANGE
BOOL
BOOL
BOOL
DINT
DC_9_MSG_BUFFER
DINT
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
INT
TIMER
TIMER
TIMER
DINT
OUTERROR
CMD_ERROR
CMD_IN_USE
CMD_OK
DICAM_I_KOM
DICAM_I_KOM.0
DICAM_I_KOM.10
DICAM_I_KOM.9
DICAM_I_KOM.8
local:X:I.Data[2]
EXOR_BIT
EXOR_BIT_SAVE
HARDWARE_RESET
HELP
MSG_BUFFER_TMP_2
MSG_STATUS
OUTPUT_ENABLE
POWER_SUP_ENCODER
POWER_SUP_IO
POWER_SUP_OUT_17_24
POWER_SUP_OUT_1_8
POWER_SUP_OUT_9_16
SPEED_HELP
STATUS_R_TIMER
TIMEOUT_R
TIMEOUT_W
LOOP_PLC
DICAM_I_KOM.15
0..1
DICAM_I_KOM.2
0..1000
0..2
DICAM_I_KOM.1
DICAM_I_KOM.7
DICAM_I_KOM.3
DICAM_I_KOM.6
DICAM_I_KOM.4
DICAM_I_KOM.5
-32767..+32767
every 5 seconds
maximum 5 seconds
maximum 5 seconds
0..NMB_PLC_LOGIC
DINT
LOOP_PLC_CHK
-1..NMB_PLC_LOGIC
DINT
LOOP_CAM
0..NMB_OUTPUTS
DINT
LOOP_CAM_CHK
-1..NMB_OUTPUTS
DINT
LOOP_DTC
DINT
LOOP_DTC_CHK
0..
NMB_DTC_OUTPUTS
-1..
NMB_DTC_OUTPUTS
Description
Number of components (cams per output) from the cam table
(for the creation of automatic parameters for the FOR - loops)
Number of components (outputs) from the cam table
(for the creation of automatic parameters for the FOR - loops)
Number of components from the PLC - Logic - Module table
(for the creation of automatic parameters for the FOR - loops)
Number of components (cams with DTC) from the delay time table
(for the creation of automatic parameters for the FOR - loops)
Hardware Bit of the CamCon for recognition of output errors.
Error during execution of write message.
Command in progress
Last write message successfully done
Alias for controller TAG "DC_5_STATUS_COMM_RANGE".
This Bit toggles after execution of a write message
Save variable for EXOR Bit.
Hardware reset bit of the CamCon.
Run variable
2. MSG Bufffer for changing position of data in the subprogram
Status of MSG transfer / 0 = No MSG / 1 = 1.MSG run / 2 = 2.MSG run.
Hardware bit of the CamCon for output release
Power supply IO periphery and measuring system available
must always be 0, if 1 then all other Bits in this are Byte 1 i.e. undefined
Power supply Output 17 - 24 available
Power supply Output 1 - 8 available
Power supply Output 9 - 16 available
Help variable for calculating realtime speed
Timer for cyclic reading of the status question
Data transfer, read Timeout Timer
Data transfer, write Timeout Timer
Loop counter for the controller TAG: DC_1_SYSTEM_KONFIG_SPS[]
for DICAM SPS - Logic - module programing.
Counter for the elements of the TAG: DC_1_SYSTEM_KONFIG_SPS[] with se
OK Bit. If this value equals the NMB_PLC_LOGICthe controller
TAG: DC_1_SYSTEM_KONFIG_SPS_OK is set to1.
Loop-counter for controller TAG: DC_2_PRG_CAM[]
for Cam programingerung.
Counter for the TAG's elements: DC_2_PRG_CAM[] with set OK Bit.
If this value equals ANZ_OUTPUTS
the controller's TAG: DC_2_PRG_CAM_OK is set to 1.
Loop-counter for controlleTAG: DC_2_PRG_DTC[]
for delay-time programingg.
Counter for the TAG's elements: DC_2_PRG_DTC[] with se OK Bit.
If this value equals ANZ_DTC_OUTPUTS
the controller'sr TAG: DC_2_PRG_DTC_OK is set to 1.
Edition: 18.08.2004
Page: 29
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
6.3. The Controller TAGs of the CamCon 1756-DICAM
The Controller TAGs described here are derived from the predefined "User-Defined" TAGs.
6.3.1. TAG "ADR"
The ADR TAG of the individual datasets always consists of the data range, the offset, the data length
and the control bits. Via the range and the offset the function, i.e. the parameters, cams or delay time
values are selected. If more validators are necessary, it is then stipulated via the data length how much
is to be read or written. Data transfer is released and monitored by the control bits.
Type
Name
DC_9_HEADER
DINT[0]
DINT[1]
DINT[2]
DC_9_CMD_BITS
DC_9_CMD_BIT
ADR
RANGE
OFFSET
DATA_LEN
CMD
WRITE
DC_9_CMD_BIT
DC_9_CMD_BIT
DC_9_CMD_BIT
RUN
OK
ERROR
DC_9_CMD_BIT
READ
Description
Address consists of:
Data range number
Offset in the data range
Length of transferred data
Command bits consist of:
Dataset to be written
Note: Not ev99ery dataset can be written
Dataset transfer in progress
Dataset transfer completed and OK
Dataset transfer completed with Error or Timeout
In a Timeout; the DC1756DICAM Program attempts to send the dataset again
Dataset to be read
Note: Not every dataset can be read
For simpler presentation purposes, the following tag description will always show one line with the
range, Offset and the length. The bits WRITE, RUN and READ must always be 0 in this definition. In
case a data transfer is interrupted by a power cut of the CPU, these must be set to 0 during
initialisation (See Program DC_0_INIT).
6.3.2. TAG "DC_0_CLEAR_ALL"
Type
DC_9_HEADER
DINT[0]
Name
Data
ADR
DATA
205,1,1
-1
Description
Address
If this dataset is transferred, the CamCon is completely erased
Note: write only is possible
6.3.3. TAG "DC_0_EEPROM_LOCK"
Type
DC_9_HEADER
DINT[0]
Name
Data
ADR
EEProm_Lock
205,4,1
0..1
Description
Adresse
0 = EEProm not blocked
1 = EEProm blocked, no write to the EEProm
Warning: The EEProm must be blocked, if data is written frequently (cycllic) to the
component group; otherwise the EEProm memory is destroyed. Changes on cams,
parameters etc. which are written after the memory has been blocked are lost after
switching OFF and ON.
6.3.4. TAG "DC_0_HW_RESET"
Type
DC_9_HEADER
DINT[0]
Name
ADR
DATA
Data
205,2,1
-1
Description
Adresse
When this dataset is transferred, a Hardware Reset is released on the CamCon.
This corresponds to switching operating power OFF and ON.
Note: write only is possible
Edition: 18.08.2004
Page: 30
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
6.3.5. TAG "DC_1_SYSTEM_CONFIG"
With the transfer of this TAG the parameters of the CamCon 1756-DICAM are complete.
Type
DC_9_HEADER
DINT[0]
Name
Data
ADR
Measuring_system_type
203,0,66
-1, 0..20
DINT[1]
Special_measuring_system_
type
0..7
DINT[2]
SMS_Parameter_1
DINT[3]
SMS_Parameter_2
DINT[4]
SMS_Parameter_3
DINT[5]
SMS_Parameter_4
DINT[6]
SMS_Parameter_5
DINT[7]
SMS_Parameter_6
DINT[8]
Value_hysteresis
0..125
DINT[9]
Speed_maximum
0..9999
alue
Description
Adresse
Here you select your measuring system.
0 = 256 SSI Single turn Grey
1 = 360 SSI Single turn Grey
2 = 512 SSI Single turn Grey
3 = 1000 SSI Single turn Grey
4 = 1024 SSI Single turn Grey
5 = 2048 SSI Single turn Grey
6 = 4096 SSI Single turn Grey
7 = 8192 SSI Single turn Grey
8 = AWA/SSI 8 Bit
9 = AWA/SSI 12Bit
10 = 4096x4096 SSI Multiturn 4096Imp.= 1 Turn
11 = 4096x4096 SSI Multiturn 4096Imp.= 2 Turn
12 = 4096x4096 SSI Multiturn 4096Imp.= 4 Turn
13 = 4096x4096 SSI Multiturn 4096Imp.= 8 Turn
14 = 4096x4096 SSI Multiturn 4096Imp.= 16 Turn
15 = 4096x4096 SSI Multiturn 8192Imp.= 2 Turn
16 = 4096x4096 SSI Multiturn 8192Imp.= 4 Turn
17 = 4096x4096 SSI Multiturn 8192Imp.= 8 Turn
18 = 4096x4096 SSI Multiturn 8192Imp.= 16 Turn
19 = 4096x4096 SSI Multiturn 8192Imp.= 32 Turn
20 = 4096x4096 SSI Multiturn 8192Imp.= 64 Turn
or select a specific one
-1 = Special measuring system
Special measuring system type
0 = SSI - Measuring system
1 = Parallel - Measuring system
2 = Incremental - i.e. Hiperface - Measuring system.
3 = Multiturn - Measuring system
4 = PLL - Measuring system
5 = Timer - Measuring system
6 = RS232 - Measuring system
7 = AG615 at 360° - Measuring system
Special measuring system depends on Parameter 1.
See Chapter "6.3.6. Special measuring system TAGs"
Special measuring system depends on Parameter 2.
See Chapter "6.3.6. Special measuring system TAGs"
Special measuring system depends on Parameter 3.
See Chapter "6.3.6. Special measuring system TAGs"
Special measuring system depends on Parameter 4.
See Chapter "6.3.6. Special measuring system TAGs"
Special measuring system depends on Parameter 5.
See Chapter "6.3.6. Special measuring system TAGs"
Special measuring system depends on Parameter 6.
See Chapter "6.3.6. Special measuring system TAGs"
The value hysteresis
This value is necessary to suppress fluttering of the outputs during unsteady value
gathering. The exact value can only be obtained by trial and error, but it has to be as small
as possible or always 0. Hysteresis can be set between 0 and maximum 1/4 of the total
resolution but it must not exceed maximum of 125 Impulses.
Maximum speed for measuring system control (Impulses per cycle)
The value to be entered is calculated from the actual cycle time of the CamCon, from the
physical resolution of the measuring systems and the speed of the machine.
Example: Cycle time = 0.5ms / resolution = 360 / speed of the machine = 180 min -1.
Value =
Resolution * machine speed
* cycle time + safety reserve
60 * 1000
360 * 180
* 0.5 + 5 = 5.54 ≈ 6
60 * 1000
DINT[10]
Transmission_multiplier
-99999...
99999
DINT[11]
Transmission_divider
1..99999
The result is rounded up and entered. If the CamCon now registers an actual value jump of
more than 6 impulses, an error message "Pos-Err:5" is created. If a zero is entered, the
control is switched off. The Resolution must be entered as a physical value (no transmission
factor).
The multiplier for electronic transmission serves for measuring range transformation. The
physical measuring range, for example of a rotational angle encoder, is transformed into a
new and for the user effectively visible measuring range (actual value).
Note:
The counting direction of the measuring systems is marked by the prefix.
Divider for electronic transmission
Example:
In the event of a full turn of the rotational angle encoder with 360 steps per rotation, a
machine drives around 1000mm.
If the display of the position is no longer supposed to be in angle degrees but in mm, the
motor must be set to the factor 1000 / 360 with the effect that the display will no longer
change in one-step increments, since the resolution is not influenced.
If you select, for example 100 / 360, the actual value is calculated down to a process range
of up to 100. The position display is then given in cm, whereby moving the decimal point is
not possible.
Edition: 18.08.2004
Page: 31
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
DINT[12]
Measuring_system_moveme
nt
0..1
DINT[13]
Starting_point_line_measuri
ng_system
-9999999...
9999999
DINT[14]
Offset_measuring_system
minimum...
maximum
possible
actual value
DINT[15]
Preset_value_measuring
system
DINT[16]
Preset_input_measuring_sys
tem
DINT[17]
Zero_power_fixed_preset
minimum..
maximum
possible
actual value
0..
Number_cam_
Inputs
0..1
DINT[18]
Speed_factor
1..999999999
DINT[19]
Max_speed_value
2..999999999
DINT[20]
Speed_display_accuracy
1..999
DINT[21]
DINT[22]
DINT[23]
Switchover_mode_display
Input_switchover_display
Cable_length
0
0
0..1000
DINT[24]
Cycle_time
0..10000
DINT[25]
Safety_output
0..
Number_cam_
Outputs
DINT[26]
Send_actual_realtime_value
0..2
DINT[27]
Turning_direction_output
0..
Number_cam_
Outputs
DINT[28]
Hold_output
DINT[29]
Speed_hysteresis
DINT[30]
Number_cam_inputs
0..
Number_cam_
Outputs
0..
Max_speed_val
ue
0..200
(only multiples
of 8)
DINT[31]
Number_cam_outputs
24..200
(only multiples
of 8)
Digital Cam Switch Unit
CamCon 1756-DICAM
Measuring system type
0 = Rotational (for example: eccentric presses, packaging machine)
1 = Linear (for example: toggle press, positioning)
Warning: If during linear path measuring the value is outside the stipulated range, the
CamCon switches off with the error message "Pos-Err 3".
Start value for linear measuring system
Here you state the required start value of the process range. You can also set a negative
value.
Offset for measuring system
The Offset is deducted from the physical actual value and thus gives you the option of
moving the zero point.
Note: If you have selected a linear movement and the turning direction is set to minus, then
the offset must be of a value smaller than zero (for example -359).
Setting a preset value for an actual value in the measuring system when a positive limit on
the CamCon preset input is found. By setting the preset value to zero you can create an
external zero signal, in order to, for example, synchronise the position of the machine with
the acual value of the CamCon.
Preset Input for measuring system
0 = Preset OFF
The actual value can be changed with a positive limit on the CamCon Preset Input.
Preset fixed zero power
0 = zero power not fixed
1 = zero power fixed
Warning: At a value of 1the EEProm can be destroyed by cyclical writing!
Note: This parameter also affects the setting of the actual value. See Chapter "6.3.8. TAG
"DC_1_SYSTEM_SET_ACTUAL_VALUE"" on page 40.
Speed factor
The speed is measured by increments i.e. impulses per second which the measuring system
gives out after calculation through the electronic gear (USER resolution). But, if you want to
display the speed, for example in U/min. or in items per minute or status, you willhave to set
a conversion factor. With a Speed factor of 100000 the speed value shows
User resolution / second.
Factor for U/min = 60 / User resolution * 100000.
Example: 16666 = at 360° User resolution or 732 = at 8129 Imp User resolution
100% - Speed value
This value served the adaptation of the speed display and must always be set to 10%
greater than the maximum expected speed of the device.
Accuracy or damping of the speed indicator 100 = 1.00%
Oscillation of the speed indicator can be limited to a maximum value. This is achieved by
damping through a low pass, which results in a smoothing of the display, i.e. a kind of middle
value is created. The smaller the entered value, the smoother the speed display will be.
This value has no function in the CamCon 1756-DICAM.
This value has no function in the CamCon 1756-DICAM.
Cable length between the SSI - measuring system and the CamCon and between the
external input/output extension and the CamCon in meters. This value is necessary, since
the cable lengths determines the maximum possible speed of serial data transfer. The
greater the entered cable length, the slower the data communication and the greater the
cycle time (Default = 30 meters).
The expected cycle time in µs, i.e. actual cycle time when this value is read.
The expected cycle time is for example necessary when a measuring system is connected to
it, which allows only one reading of the data within a specific time.
Safety Output i.e. Run-Control
In order to have the option of controlling the CamCon in situations such as short circuits on
output channels or errors in path measuring, a rotary cam can be programmed for a single
output. This output is only switched off when an error occurs and serves as a safety output.
In the case of a program change the safety output is temporarily set back. See also DINT[36]
on page DINT[36] on page 33. "0" means that no safety output has been programmed.
Output of actual realtime value on the I-range
0 = No actual realtime output
1 = Output actual value in grey code
2 = Output actual value in binary code
Always set CamCon 1756-DICAM to 2.
Rotational direction output
This switches over when the speed hysteresis is exceeded. When the direction of the
movement is positive, output is switched on and if it is negative, it is switched off. "0" means
that no rotational direction output has been programmed.
No movement output
This output switches on when the actual speed exceeds the set hysteresis value. "0" means
that no standstill output was programmed.
Speed hysteresis
For the rotational direction output and the standstill output the speed hysteresis must be set.
This value is necessary for defining a switch threshold at which the switch-over takes place.
Number of cam-switch inputs
When the "PLC - Logic - Option" is switched off, the number of hardware inputs must be
entered at the CamCon. If the option inputs is built into the device, 8 or otherwise 0 must be
entered.
Note:
The option X = "external Interface" and the connected extension device require that the
number of inputs correspond exactly to the number of electrical inputs, since the short-circuit
recognition of the CamCon reacts to the number of inputs.
Number of cam-switch outputs
When the "PLC - Logic- Option" is switched off, the number of hardware outputs must be
entered at the CamCon (24). In addition it is possible to make up to 200 cam outputs
available via the back plane bus of the ControlLogix.
Note:
The option X = "external Interface" with the connected extension devices require that the
number of outputs correspond exactly to the number of electrical outputs.
Edition: 18.08.2004
Page: 32
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
DINT[32]
Number_outputs_with_DTC
DINT[33]
DINT[34]
Input_keyboard_lock
Number_Input_for_external_
progam_selection
Strob_Input_of_external_pro
gram_selection
Program_selection_mode
DINT[35]
DINT[36]
DINT[37]
Actual_value_progam_select
ion_mode_2
DINT[38]
DINT[39]
Number_of_analog_outputs
Realtime_speed_output
DINT[40]
Number_internal_analog_out
put
Offset_int_analog_output_1
Offset_int_analog_output_2
Factor_int_analog_output_1
Factor_int_analog_output _2
Plc_logic_module_status
DINT[41]
DINT[42]
DINT[43]
DINT[44]
DINT[45]
DINT[46]
Number_hardware_inputs
Digital Cam Switch Unit
CamCon 1756-DICAM
0..
Number_cam_
outputs
(only multiples
of 8)
0
0
This value has no function in the CamCon 1756-DICAM and must always be 0.
This value has no function in the CamCon 1756-DICAM and must always be 0.
0
This value has no function in the CamCon 1756-DICAM and must always be 0.
0..2
Program selection mode 0 =slow, 1 = direct, 2 = by actual value
slow: The selected program is constructed cam by cam. This kind of program change does
not require any additional RAM storage, but during program switching at full speed
complications on the machine can occur. In this case, the safety output of the CamCon is
temporarily switched off.
direct: In a buffer store the selected program is constructed cam by cam and then quickly
changed. This kind of program change needs double storage space for the cam construction
and the outputs are never undefined. The safety output of the CamCon is not switched off in
this case.
by actual value: In a buffer the selected program is constructed cam by cam. You must wait
until the machine passes a specific actual value and then execute a sudden program
change. This kind of program change also needs double storage space for the cam
construction and the outputs are never undefined. The safety output of the CamCon is not
switched off in this case.
Change-over point when the program select mode is set to 2.
minimum..
maximum
possible
actual value
0
0..1
0
This value has at present no function in the CamCon 1756-DICAM and must always be 0.
Realtime speed output
0 = no realtime speed output
1 = realtime speed output switched on
This value has no function in the CamCon 1756-DICAM.
0
0
0
0
0..2
This value has no function in the CamCon 1756-DICAM.
This value has no function in the CamCon 1756-DICAM.
This value has no function in the CamCon 1756-DICAM.
This value has no function in the CamCon 1756-DICAM.
Plc - Logic - Module / 0 = OFF / 1 = ON/ 2 = ON / remanend
DINT[53]
Master_program
0..200
(only
of 8)
0..200
(only
of 8)
0..248
(only
of 8)
0..248
(only
of 8)
0..200
(only
of 8)
0..248
(only
of 8)
0..248
(only
of 8)
0..1
DINT[54]
Master_program_number
0..32767
DINT[55]
Master_output_1_32
Bits 0-31
DINT[56]
DINT[57]
DINT[58]
DINT[59]
DINT[60]
DINT[61]
DINT[62]
DINT[63]
Master_output_33_64
Master_output_65_96
Master_output_97_128
Master_output_129_160
Master_output_161_192
Master_output_193_224
Master_output_225_248
DC300_interrupt
DINT[47]
Number_hardware_outputs
DINT[48]
Number_plc_register
DINT[49]
DINT[50]
DINT[51]
DINT[52]
Number_plc_x_register
Number_plc_timer_
counter
Number_plc_v_inputs
Number_plc_s_inputs
Number of outputs with Speed Compensation
Here you enter the number of Speed Compensating cam outputs which are available to the
CamCon. The number of outputs should not exceed the absolutely necessary maximum,
otherwise you waste storage space and cycle time unnecessarily.
multiples
multiples
multiples
multiples
multiples
multiples
multiples
etc.
"
"
"
"
"
"
0
Warning: Before you switch on the Plc - Logic - Module, it is essential that you read the
instruction manual of the Plc - Logic - Module. You can access this instruction manual at the
address "http://www.digitronic.com" as a PDF file.
Number of Hardware Inputs
Note:
This value is only applied if the Plc - Logic - Module is switched on.
Number of Hardware Outputs = I - Range of ControlLogix
Note:
This value is only applied if the Plc - Logic - Module is switched on.
Number of "PLC - Logic - Module" register
Note:
This value is only applied if the Plc - Logic - Module is switched on.
Number of "PLC - Logic - Module" X - register
Note:
This value is only applied if the Plc - Logic - Module is switched on.
Number of "PLC - Logic - Module" Timer/Counter
Note:
This value is only applied if the Plc - Logic - Module is switched on.
Number of "PLC - Logic - Module" V - Inputs = 0 - Range of ControlLogix
Note:
This value is only applied if the Plc - Logic - Module is switched on.
Number of "PLC - Logic - Module" S - Inputs
Note:
This value is only applied if the Plc - Logic - Module is switched on.
Master - Program / 0 = OFF / 1 = ON
This gives you the option of defining program or related product cams. These are necessary
if, for example, you process several products with your machine which have only few product
related differences in the cam program. It is a way of saving considerable cam storage space
(EEProm), since the cams which are not product dependent need not be repeatedly
programmed.
Master Program Number
Enter the Master Program Number under which the Master cams are to be stored.
Master Program Output 1 - 32, Radix := Binary
Here it is defined as bit example which cam output is a Master Output.
Output 33 - 64
etc.
"
"
"
"
"
This value has no function in CamCon 1756-DICAM.
Edition: 18.08.2004
Page: 33
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]hvssystem.com
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
DINT[64]
Number_plc_shift_register
0..200
(only multiples
of 8)
DINT[65]
Max_shift_size
0..999999
Note:
Number of shift registers in the Plc - Logic - Module
Attention:
If a shift register is defined, the variable "speed max" is set to 16, for the reason that in
a cycle of the DICAM a maximum of 16 Bits of the shift register can be shifted. See
also chapter 6.3.5. TAG "DC_1_SYSTEM_CONFIG" Value: DINT[9].
Note:
This value is rounded up and only then applied when the Plc - Logic - Module is switched on
Maximum length of a shift register in the Plc - Logic -Module.
Note:
This value is rounded up and only then applied when the Plc - Logic - Module is switched on.
You will find the minimum/maximum possible actual value in Chapter "6.3.13. TAG "DC_3_STATUS_FULL"
Value: DINT[27]" and Chapter "6.3.13. TAG "DC_3_STATUS_FULL" Value: DINT[28]" on page 42.
6.3.6. Special measuring system TAGs
A special measuring system is necessary if you cannot connect or use any of the predefined SSI measuring systems to the CamCon.
6.3.6.1. TAG "DC_1_SYSTEM_CONFIG_ENC_0_SSI"
Type
Name
Data
DINT[0]
DINT[1]
DINT[2]
REC
TYP
BIT
-1
0
2..25
DINT[3]
LSB
2..25
DINT[4]
CAPP
0..65536
DINT[5]
ERROR
14
25 / 26
DINT[6]
DINT[7]
RES1
RES2
0
0
Description
Always -1 = recognition of special measuring system
Type 0 = SSI Measuring system
Measuring system resolution in bits
Enter the number of the used data bits of the SSI - measuring system. Resolution of, for example 1000
Impulses, this corresponds to 10 bits.
Position of the LSB (Offset) in the delivered encoder value from which the evaluation is to be started.
For a 1000 Impulse SSI - measuring system the position of the LSB is on position 10. For more accurate
information please consult the instruction manual for your measuring system.
Capping for encoders which have no binary resolution.
At 1000 Impulses this would be ( 1024 - 1000 ) / 2 = 12.
Bit position of the SSI - Error bit
Standard rotating angle encoders of the Stegmann company use the bit position 14. At this SSI - Position
it is necessary to transfer a 0.
Reserve 1
Reserve 2
Copy this data range to the beginning of the data range tag "DC_1_SYSTEM_CONFIG" with the ”COP”
command or enter the value directly in the DC_1_SYSTEM_CONFIG TAG. After the transfer of this
dataset the SSI - special measuring system is set.
Note:
Consider also chapter "4.9.1. SSI Measuring system input" on page 17.
6.3.6.2. TAG "DC_1_SYSTEM_CONFIG_ENC_1_PAR"
Type
Name
Data
DINT[0]
DINT[1]
DINT[2]
REC
TYP
RESOLUTION
-1
1
2..65536
DINT[3]
INPUT
DINT[4]
MODE
0...
Number_cam_o
utputs resolution
in
bits
0..1
DINT[5]
DINT[6]
DINT[7]
RES1
RES2
RES3
0
0
0
Description
always -1 = Recognition of the special measuring system
Type 1 = parallel measuring system
Measuring system resolution
Please state the resolution of the parallel measuring systems (for example 500 Impulses)
Input number from which evaluation is to be started
This is the input of the lowest value bits (LSB).
At a resolution of 500 impulses 9 bits of resolution are needed. The CamCon calculates from the
position of the LSBs automatically the position of the remaining inputs, that is in ascending order.
Please make sure that you are not going outside the input range of the CamCon.
Coding of parallel measuring systems
0 = Gray code
1 = Binary code
Warning:
The parallel binary code should only be used in exceptional circumstances. Please contact your
customer service.
Reserve 1
Reserve 2
Reserve 3
Copy this data range to the beginning of the data range tag "DC_1_SYSTEM_CONFIG" with the ”COP”
command or enter the value directly in the DC_1_SYSTEM_CONFIG TAG. After the transfer of this
dataset the parallel special measuring system is set.
Note:
Consider also chapter "4.9.2. Parallel measuring system input" on page 17.
Edition: 18.08.2004
Page: 34
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
6.3.6.3. TAG "DC_1_SYSTEM_CONFIG_ENC_2_INK" or Hiperface
Type
Name
Data
Description
DINT[0]
DINT[1]
DINT[2]
REC
TYP
RESOLUTION
-1
2
2..131072
DINT[3]
DIV
0..11
DINT[4]
MODE
0..7
always -1 = Recognition for special measuring system
Type 2 = INK or Hiperface Measuring system
Measuring system resolution
Enter the maximum necessary impulse number. This value is then the maximum resoluton which the
CamCon will evaluate. If more impulses are counted than set for the resolution, then the CamCon
begins to count from zero again. But, if the movement system was set to "linear" (TAG = Measuring
system_movement), then the CamCon switches to "Clear...." or "Pos-Err: 3". In this case the
resolution must be made greater or the actual value must be reset by means of a Clear or Preset
signal.
Divisor of impulses, 0 = *4, 1 = *2, 2 = *1, 3 = /2, 4 = /3.....
The divider divides or multiplies the incoming impulses of the measuring systems with this value. The
following dividers can be entered: "*4", "*2", "*1", "/2", "/4", "/8", "/16", "/32", "/64", "/128", "/256", "/512".
If the divisor is set to "*4" = 0, this means that a measuring system with 500 impulses resolution makes
available 2000 impulses to the device (quadrupling).
Clear Modes, 0=C1&C2, 1=/C1&C2...... 7=C2 neg. edge or C1
Here you set the function of the additional inputs C1 and C2. You can select from 8 possible function
types:
"C1 & C2"
If Input C1 is high and C2 is high, the counter is set to zero.
"/C1 & C2"
If Input C1 is low and C2 is high, the counter is set to zero.
"C1 & /C2"
If Input C1 is high and C2 is low, the counter is set to zero.
"/C1 & /C2"
If Input C1 is low and C2 is low, the counter is set to zero.
"C1 : W"
If Input C1 is high, the counter is set to zero.
If Input C2 is high, impulses are no longer counted (Wait).
"/C1 : W"
If Input C1 is low, the counter is set to zero.
If Input C2 is high, impulses are no longer counted (Wait).
"C1 or áC2" The counter is set to zero, if Input C1 is high if or if the signal changes an Input C2 from
low to high.
"C1 or âC2". The counter is set to zero, if Input C1 is high or if the signal changes an Input C2 from
high to low.
DINT[5]
DINT[6]
DINT[7]
RES1
RES2
RES3
0
0
0
Reserve 1
Reserve 2
Reserve 3
Copy this data range to the beginning of the data range tag "DC_1_SYSTEM_CONFIG" with the ”COP”
command or enter the value directly in the ”DC_1_SYSTEM_CONFIG” tag. After the transfer of this
dataset the incremental special measuring system is set.
Note:
Consider also chapter "4.9.3. Incremental measuring system input" on page 18.
6.3.6.4. TAG "DC_1_SYSTEM_CONFIG_ENC_3_MULTI"
Type
Name
Data
DINT[0]
DINT[1]
REC
TYP
-1
3
DINT[2]
RESOLUTION
2..65536
DINT[3]
DINT[4]
DINT[5]
DINT[6]
DINT[7]
TURN
DIV
RES1
RES2
RES3
1..999
1..999
0
0
0
Description
always -1 = Recognition for special measuring system
Type 3 = Multi-turn measuring system for AAG626 or AAG66107
This measuring system is needed, if you have to drive a multi-turn angle encoder with non-binary
number revolutions.
Measuring system resolution
Example 1:
You have a turntable with a gear ration of 3 to 1, whereby the angle encoder makes three turns and the
turntable one turn. These three revolutions correspond now to 360 impulses (360 Degrees). The
following entries are necessary to achieve this:
Resolution = 360 / Turn = 3 / Div = 1.
Example 2: You have a turntable with a gear ratio of 12.5 to 1, whereby the angle encoder makes 12.5
turns and the turntable one turn. These 12.5 revolutions now correspond to 3600 impulses (360.0
Degrees). The following entries are necessary to achieve this:
Resolution = 3600 7 Turn = 25 / Div = 2.
Warning:
This measuring system works only in connection with a multi-turn angle encoder with 4096 x 4096
impulses resolution (Type: AAG66107 or AAG626) and must not be through more than 512 revolutions
of the angle encoder without power supply.
Number of turns of the encoder
Divider for uneven turns or 1
Reserve 1
Reserve 2
Reserve 3
Copy this data range to the beginning of the data range tag "DC_1_SYSTEM_CONFIG" with the ”COP”
command or enter the value directly in the ”DC_1_SYSTEM_CONFIG” tag. After the transfer of this
dataset the multi-turn special measuring system is set.
Edition: 18.08.2004
Page: 35
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
6.3.6.5. TAG "DC_1_SYSTEM_CONFIG_ENC_4_PLL"
Type
Name
Data
DINT[0]
DINT[1]
REC
TYP
-1
4
DINT[2]
DINT[3]
IMPULSES
NUMBER_
IMPULSE
ERROR
IMPULS_
INPUT
2..8192
1..8192
DINT[4]
DINT[5]
DINT[6]
CLEAR_INPUT
DINT[7]
ERROR_
OUTPUT
0..8192
1..
Number_cam_i
nputs
0..
Number_cam_i
nputs
0..
Number_cam_o
utputs
Description
always -1 = Recognition for special measuring system
Type 4 = PLL - Measuring system
The PLL measuring system (Phase - Lock - Loop) calculates the path from time Interpolation of a
single measuring impulse. For example: If you have fixed an initiator to your turntable and you would
like to calculate the actual position at constant speed without attaching a further measuring system,
then the PLL measuring system is the right choice.
Impulses per input signal
Number of input impulses for one revolution
Error window
Impulse - Input
Clear - Input
Error - Output
Copy this data range to the beginning of the data range tag "DC_1_SYSTEM_CONFIG" with the ”COP”
command or enter the value directly in the ”DC_1_SYSTEM_CONFIG” tag. After the transfer of this
dataset the PLL special measuring system is set.
Note:
Consider also chapter "4.9.5. PLL measuring system input" on page 20.
6.3.6.6. TAG "DC_1_SYSTEM_CONFIG_ENC_5_TIMER"
Type
Name
Data
DINT[0]
DINT[1]
DINT[2]
REC
TYP
RESOLUTION
-1
5
2..65536
DINT[3]
DINT[4]
TIME
STOP_INPUT
DINT[5]
CLEAR_INPUT
1..10000
0Number_cam_i
nputs
0Number_cam_i
nputs
DINT[6]
DINT[7]
RES1
RES2
Description
always -1 = Recognition for special measuring system
Type 5 = Timer Measuring system
Measuring system resolution
The timer path simulation makes it possible to create paths or actual time values without measuring
system, that is on a time basis. In that case, the Cam Switch Unit behaves in a similar way as a
washing machine control system.
Time per step in ms
Stop - Input (release)
A high signal at this input lets the timer run, a low signal at this input stops the timer. If you do not
want to have a stop input, simply insert "0".
Clear - Input
A high signal at this input leaves the timer at "0". If you do not want a Clear - Input, simply insert "0".
Reserve 1
Reserve 2
Copy this data range to the beginning of the data range tag "DC_1_SYSTEM_CONFIG" with the ”COP”
command or enter the value directly in the DC_1_SYSTEM_CONFIG TAG. After the transfer of this
dataset the timer special measuring system is set.
Note:
Consider also chapter "4.9.6. Timer as a measuring system" on page 20.
6.3.6.7. TAG: "DC_1_SYSTEM_CONFIG_ENC_7_AG615"
Type
Name
Data
DINT[0]
DINT[1]
REC
TYP
-1
7
DINT[2]
DINT[3]
DINT[6]
DINT[6]
DINT[6]
DINT[7]
RESOLUTION
TURNS
RES1
RES2
RES3
RES4
2..8192
1..999
Description
alwaysr -1 = Recognition for special measuring system
Type 7 = Measuringsystem AG615
This SSI Speciale measuring system makes a Multi-Turn i.e. Use measuring sytem of an AAG6158192 Single - Turn measuring system. As a result, one gets severally revolutions at the DICAM per a
single Turn of the AG615.
Resolution of the measuring system per Turn
Number of Turns per revolution of the measuring system
Reserve 1
Reserve 2
Reserve 3
Reserve 4
Copy this data range using the "Copy" command at the beginning of the data-range of the TAG
"DC_1_SYSTEM_CONFIG" or directly enter the values into the TAG: DC_1_SYSTEM_CONFIG. After
the transmission of this data-record, the AG615 is set.
Edition: 18.08.2004
Page: 36
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
6.3.6.8. TAG: "DC_1_SYSTEM_CONFIG_ENC_8_SPEED_SIM"
Type
Name
Data
DINT[0]
DINT[1]
REC
TYP
-1
8
DINT[2]
DINT[3]
DINT[4]
RESOLUTION
INC_SECOND
HALT_INPUT
DINT[5]
CLEAR_INPUT
2..65536
1..10000
0Number
of_NSW_inputs
0Number
of_NSW_inputs
DINT[6]
DINT[7]
RES1
RES2
Description
recognition for special measuring systems
Type 8 = measuring system simulator
This measuring system simulator enables creating way- or actual time-values without needing a
measuring system (on the base of time). On the contrary to the Timer-measuring system a higher
speed is possible.
measuring system resolution
Speed in Impulses i.e. Increments per second.
Halt - input (enableling).
A high Signal at this input sets the simulator to go, a low signal at this input stops the simulator. If
you do not want a Halt input, simple enter a 0 here.
Clear - input
A high signal at this input sets the timer to "0". If you do not want a Clear - input, simply enter a "0"
here.
Reserve 1
Reserve 2
This datarange can be copied directly to the beginning of the data-range of the TAG
"DC_1_SYSTEM_CONFIG" by using the "copy" command or directly enter the values into the TAG:
DC_1_SYSTEM_CONFIG. After a transmission of this data record the simulator - special measuring
system.
6.3.6.9. TAG: "DC_1_SYSTEM_CONFIG_ENC_9_HIPER"
Type
Name
Data
DINT[0]
DINT[1]
REC
TYP
-1
9
DINT[2]
DINT[3]
DINT[4]
MUL
DIV
RESOLUTION
1..9999
1..4095
2..131072
DINT[5]
MODE
0..7
DINT[6]
DINT[7]
RES1
RES2
Description
always 1 as Recognition for special measure systems
Type 9 = HIPER - measure systems with Roll - Over - Function
This special measuringh system is used if the DICAM is equiped with a HIPER - Face - or
Incremental - measuring system-input and an odd translation of the gear would cause an adding
measuring error..
Multipliertfor the HIPER - gear.
Divisor for the HIPER - gear.
Enter here the maximum required number of impulses. This values is the resolution to which the
CamCon is evaluated. If more impulses than the set resolution value are counted, the Camcon restarts counting at 0. If the moving system was set to "linear" (TAG = measuring system_moving),
the CamCon switches to "Clear" respective "Err: 3", a case in which the resolution has to be set to a
greater value or the actual value has to be reset by creating a Clear- or Preset-signal.
Clear Modes, 0=C1&C2, 1=/C1&C2...... 7=C2 neg. edge or C1
Set the aditional input's C1 and C2 functions here. You can choose between 8 possible types of
functions :
"C1 & C2"
If input C1 is high and C2 high, the counter is set to 0.
"/C1 & C2"
If input C1 is low and C2 high, the counter is set to 0.
"C1 & /C2"
If input C1 is high and C2 low, the counter is set to 0.
"/C1 & /C2"
If input C1 is low and C2 low, the counter is set to 0.
"C1 : W"
If input C1 is high, the counter is set to 0.
If input C2 is high, no more impulses will be countedt (Wait).
"/C1 : W"
If input C1 is low, the counter is set to 0.If input C2 is high ist, no more impulses will
be countedt (Wait).
"C1 or áC2" The counter is set to 0, if input C1 is high or the signal at the input C2 changes from
low to high.
"C1 or âC2". The counter is set to 0, if input C1 is high or the signal at the input C2 changes from
high to low.
Reserve 1
Reserve 2
Copy this data range, using the "COP" command to the begining of the datarange of the TAG
"DC_1_SYSTEM_CONFIG" or transfer the values directly into the TAG: DC_1_SYSTEM_CONFIG.
After the transmission of this data record, the HIPER - special measuring system.
Note:
Please also regard chapter "4.9.3.3. Incremental Hiperface measuring system input with
SINCOS level" on page 19.
Edition: 18.08.2004
Page: 37
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
6.3.7. TAG "DC_1_SYSTEM_CONFIG_PLC[X]"
The company Digitronic Automationsanlagen GmbH has been known for a long time within the industry
as a supplier and developer of electronic cam-switch mechanisms. Long-standing experience gained in
a close working relationship with the users with regard to linking PLC control systems and cam-switch
mechanism have been taken into account in the development of the CamCon PLC Logic Module. The
result is a PLC Software which works in the CamCon parallel to the cam-switch mechanism. The input
and outputs of the cam-switch mechanism are linked without external logic and without requiring
hardware, such as locking mechanisms, timers, Set - Reset functions, counters, markers and therefore
work within the same cycle time as the cam-switch mechanism. This combination guarantees the best
way of exploiting the Speed Compensation of the cam-switch mechanism and of the logic of the PLC,
without loss of switching speed through slower external switching components (for example relays,
units of time, central PLC control with high cycle times).
The tags DC_1_SYSTEM_CONFIG_PLC[X] provide the programming of the PLC - Logic - Module of
the CamCon 1756-DICAM. Before you switch on and program the PLC - Logic - Module, it is essential
that you consult the user instruction manual for the PLC - Logic - Modules. You can access this
instruction manual in the Internet at http://www.digitronic.com as a PDF file.
Type
Name
Data
DC_1_SYSTEM_CONFIG_PLC[X]
Index X
DC_9_HEADER
ADR
1..
2*200 + 2*248
216,0,36
DINT[0]
TYP_OPMX
0..1015
DINT[1]
DINT[2]
DINT[3]
DINT[4]
DINT[5]
DINT[6]
DINT[7]
DINT[8]
DINT[9]
DINT[10]
DINT[11]
DINT[12]
DINT[13]
DINT[14]
DINT[15]
DINT[16]
DINT[17]
DINT[18]
DINT[19]
DINT[20]
DINT[21]
DINT[22]
DINT[23]
DINT[24]
DINT[25]
DINT[26]
DINT[27]
DINT[28]
DINT[29]
DINT[30]
DINT[31]
DINT[32]
DINT[33]
DINT[34]
DINT[35]
FUNK
VALUE_1
VALUE_2
VALUE_3
VALUE_4
R0_S0
R0_S1
R0_S2
R0_S3
R0_S4
R0_S5
R1_S0
R1_S1
R1_S2
R1_S3
R1_S4
R1_S5
R2_S0
R2_S1
R2_S2
R2_S3
R2_S4
R2_S5
R3_S0
R3_S1
R3_S2
R3_S3
R3_S4
R3_S5
R4_S0
R4_S1
R4_S2
R4_S3
R4_S4
R4_S5
0..9
0..999999
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
0..65536
Description
Array for PLC - Logic - Module, one component for each network
Address
Note: at the present time only write is possible
Type in the PLC - Logic - Module
Range O = 0
Range P = 256
Range M = 512
Range X = 768
+ Number
Function 0 = Standard, 1=SR-FlipFlop, 2=Data-FlipFlop...
Preset value for Timer, Counter, signal number or length of shift register
Reset field or DTC Value 1 (ON) for shift register
DTC Value 2 (OFF) for shift register
Shift register Mode 0 = standard, DTC, 1 = DTC ON / OFF, 2 = time cam
1. Path symbol 0
2. Path symbol 0
3. Path symbol 0
4. Path symbol 0
5. Path symbol 0
6. Path symbol 0
1. Path symbol 1
2. Path symbol 1
3. Path symbol 1
4. Path symbol 1
5. Path symbol 1
6. Path symbol 1
1. Path symbol 2
2. Path symbol 2
3. Path symbol 2
4. Path symbol 2
5. Path symbol 2
6. Path symbol 2
1. Path symbol 3
2. Path symbol 3
3. Path symbol 3
4. Path symbol 3
5. Path symbol 3
6. Path symbol 3
1. Path symbol 4
2. Path symbol 4
3. Path symbol 4
4. Path symbol 4
5. Path symbol 4
6. Path symbol 4
For the output ranges O and P up to 200 and for the register ranges M and X up to 248 Logic networks can be programmed. You can develop the required Logic OFFLINE with the DIGISOFT 2000
Program V2.03 or later. This program is able to print out the necessary data, which have to be entered
into this TAG, as decimal numbers.
You can then enter these data into the respective tag and transfer these to the CamCon.
! TIP:
With the DIGISOFT 2000 Version 2.16 or later, an L5K - file can be created, that can be
imported into the RSLogix 5000 Program. This requires the English handling components.
Edition: 18.08.2004
Page: 38
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
Example:
In this example output 2 can only be switched on, if
input S006 (ControlLogix in RUN) is active, cam output
2 and the V002 - input (ControlLogix O - Range) are
active or the V008 - input (ControlLogix O - Range) is
active.
If you enter the following numbers into a TAG of the
array and send the dataset to the CamCon, the
network will be programmed and the program will be
executed immediately.
TAG:
TAG:
TAG:
TAG:
TAG:
TAG:
Type_OPMX
Function
Value1
Value2
Value3
Value4
TAG:
R0_S0..4
TAG: R1_S0..4 R2_S0..4
R3_S0..4
R4_S0..4
6.3.7.1. TAG: DC_1_SYSTEM_CONFIG_PLC_OK"
This TAG is set by the DICAM1756 - program, if in all
DC_1_SYSTEM_CONFIG_PLC[X]'s elements, the Bit "ADR.CMD.OK" is set.
of
the
TAG:
Now you are able to detect if all elements of the PLC-Logic-program have been written without any
errors into the CamCon 1756 DICAM.
Edition: 18.08.2004
Page: 39
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
6.3.8. TAG "DC_1_SYSTEM_SET_ACTUAL_VALUE"
Type
DC_9_HEADER
DINT[0]
Name
ADR
ACTUAL_VALUE
Data
Description
201,0,1
minimum..
maximum
possible
actual value
Adress
Set actual value
If this dataset is transferred, then on the CamCon the actual value is set to the transmitted value..
This is identical with the preset function. See Chapter "6.3.5. TAG "DC_1_SYSTEM_CONFIG"
Value: DINT[16]" on page 32.
Note: If an incremental or Hiperface input is used as measuring system, then the error message
"Pos-Err:3" or "Clear.." can be confirmed through this dataset and the CamCon started.
Warning:
The setting of the actual value can be stored in the EEProm at zero current. See Chapter "6.3.5.
TAG "DC_1_SYSTEM_CONFIG" Value: DINT[17]" on page 32. This is not meaningful however with
an incremental - and/or a Hiperface input.
6.3.9. TAG "DC_2_PRG_CAM[X].CAM[Y]"
Type
Name
Data
DC_2_PRG_CAM[X]
Index X
DC_9_HEADER
ADR
8..
Number_ca
m_outputs
XXX,1,YYY
DC_2_PRG_CAM_CAM CAM[Y]
Index Y (z.B. = 3)
1..62
DC_2_PRG_CAM_CAM
DINT[0]
Index
ON
0
minimum..
maximumpossible
actual value
DINT[1]
OFF
DC_2_PRG_CAM_CAM
DINT[0]
Index
ON
DINT[1]
OFF
DC_2_PRG_CAM_CAM
DINT[0]
Index
ON
DINT[1]
OFF
minimum..
maximumpossible
actual value
1
minimum..
maximumpossible
actual value
minimum..
maximumpossible
actual value
2
minimum..
maximumpossible
actual value
minimum..
maximumpossible
actual value
Description
Array cam outputs, one component for each output
Address, XXX = 1..200 = Output 1..200, YYY = 2..124 maximum 62 cams
Array for cams, one component for each output
XXX = Index + 1
YYY = Number of components from DC_2_PRG_CAM_CAM * 2, z.B. 3 * 2 = 6
Array for cams - one component for each cam DC_2_PRG_CAM_CAM for example
3.
Maximum 62 cams can be transferred
Cam 1
Switch-on point for cam 1
For
minimum
possible
actual
value
see
Chapter
"6.3.13.
TAG
"DC_3_STATUS_FULL" Value: DINT[27]" on page 42.
For
maximum
possible
actual
value
see
Chapter
"6.3.13.
TAG
"DC_3_STATUS_FULL" Value: DINT[28]" on page 42.
Switch-off point for cam 1
Cam 2
Switch-on point for cam 2
Switch-off point for cam 2
Cam 3
Switch-on point for cam 3
Switch-off point for cam 3
If one of these datasets is transferred, all previously programmed cams on this output are erased and
replaced by new cam values. If during the transfer the error Bit "DC_5_STATUS_COMM_ERROR" is
set, please check for free storage space in the EEProm. See Chapter "6.3.13. TAG
"DC_3_STATUS_FULL" Value: DINT[20]" on page 42.
Note:
Programming is always performed in the actually running program (online) or in the
product program. That means a changed cam becomes active instantly.
6.3.9.1. TAG: DC_2_PRG_CAM_OK"
This TAG is set by the DICAM1756 - program, if in all elements of the TAG: DC_2_PRG_CAM[X] the
Bit "ADR.CMD.OK" is set.
By this you are able to detect if all elements i.e. Cams have correctly been entered into the CamCon
1756-DICAM.
Edition: 18.08.2004
Page: 40
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
6.3.10. TAG "DC_2_PRG_CHANGE"
Type
DC_9_HEADER
DINT[0]
Name
ADR
Program_number
Data
201,2,1
0..32767
Description
Adress
Actual program number or product number when reading
If this dataset is written, the program number or product number is set to the sent value. See also
Chapter "DINT[36]" on page 33.
6.3.11. TAG "DC_2_PRG_DTC[X]"
Type
Name
Data
Description
DC_2_PRG_DTC[X]
Index X
DC_9_HEADER
ADR
8..
Number_out
puts_with_D
TC
XXX,251,3
DINT[0]
DTC_TYP
0..2
DINT[1]
DTC1
DINT[2]
DTC2
0..
maximum
possible
DTC
0..
maximum
possible
DTC or
switch time
Array for delay time values, one component for each output
Address, XXX = 1..200 = delay time for output 1..200
XXX = Index + 1
Configuration of Speed Compensation
0 = Standard or Speed Compensation for switch-on and switch-off points equal.
1 = Speed Compensation for switch-on and switch-off different
2 = The output is set to time - cam
Notes about the effects of Speed Compensation can be found in Chapter "2.1. Speed
Compensation" on page 7
Value 1
Type = 0 = Delay time value for switch-on and switch-off points in 100µs
Type = 1 = Delay time value for switch-on points in 100µs
Type = 2 = Delay time value for switch-on points on time - cam in 100µs
Value 2
With Type = 0 = not used
With Type = 1 = delay time value switch-on and switch-off points in 100µs
With Type = 2 = switch-on time in 100µs.
The switch-on time applies to all switch points (cams) on the cam path (output).
If one of these datasets is transferred, all previously programmed cams on this output are erased and
replaced by new cam values. If during the transfer the error bit "DC_5_STATUS_COMM_ERROR" is
set, please check for free storage space in the EEProm. See Chapter "6.3.13. TAG
"DC_3_STATUS_FULL" Value: DINT[20]" on page 42.
Note:
Programming is always performed online or in the product program. That means a
changed delay time becomes active instantly.
6.3.11.1. TAG: DC_2_PRG_DTC_OK"
This TAG is set by the DICAM1756 - program, if in all elements of the TAG: DC_2_PRG_DTC[X] the
Bit "ADR.CMD.OK" is set.
By this you are able to detect that all elements i.e. delay times have been entered correctly into the
CamCon 1756-DICAM.
6.3.12. TAG "DC_3_STATUS"
Type
DC_9_HEADER
DINT[0]
Name
ADR
Status
Data
201,34,1
0..8, 255
Description
Adress
This dataset should be read in cycles. An error message will be shown adjacent to
the CamCon. Note: reading only possible
0 = Status OK no error message
1 = Pos Error 1
2 = Pos Error 2
3 = Pos Error 3
4 = Output Error
5 = Pos Error 5
6 = EEProm write overload
7 = not defined
8 = RAM FULL
255 = EE-Prom Error
See Chapter "7. Error messages and removal of errors (FAQ)" on page 44.
Note: If a safety output parameters ( RUN - Control ) has been created, then read is
not necessary as long as this is active. See Chapter "6.3.5. TAG
"DC_1_SYSTEM_CONFIG" Value: DINT[25]" on page 32
Note:
In the DICAM1756 - program this TAG is read every 5 seconds, if the safety output i.e. the
Run-controll-Bit are not active. If a value unequal 0 or an error-message is detected as
status the preogram tries to acknowledge this error-message by the writing of the TAG:
"DC_4_QUIT_ERROR" automatically.
Edition: 18.08.2004
Page: 41
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
6.3.13. TAG "DC_3_STATUS_FULL"
Type
Name
Data
DC_9_HEADER
ADR
201,0,37
DINT[0]
Actual_value
DINT[1]
Speed
DINT[2]
DINT[3]
DINT[4]
DINT[5]
DINT[6]
DINT[7]
DINT[8]
DINT[9]
DINT[10]
DINT[11]
DINT[12]
DINT[13]
DINT[14]
DINT[15]
DINT[16]
DINT[17]
DINT[18]
DINT[19]
Programm_numbe
r
Analog_value_1
Analog_value_2
Analog_value_3
Analog_value_4
Analog_value_5
Analog_value_6
Analog_value_7
Analog_value_8
Analog_value_9
Analog_value_10
Analog_value_11
Analog_value_12
Analog_value_13
Analog_value_14
HW_Plc
CPU_68332
Temp
minimum..
maximum-possible
actual value
minimum..
maximum-possible
Speed.
0..32767
DINT[20]
Free_cams
0..ca.10000
DINT[21]
DINT[22]
Use_cams
DTC_max
0..ca.10000
0..10000
DINT[23]
Ram_size
1048576
DINT[24]
Ram_free
DINT[25]
EEProm_ser
DINT[26]
DINT[27]
EEProm_par
Min_actual_value
0..
1048576
8,16,32,48,64,128
KByte
0
-999999..
+999999
DINT[28]
Max_actual_value
-999999..
+999999
DINT[29]
Prog_max
32768
DINT[30]
DINT[31]
DINT[32]
DINT[33]
Use_DTC
Firmware_Z_1_4
Firmware_Z_5_8
Firmware_Z_9_12
0..10000
'18.0'
'3.20'
'02$00§00'
DINT[34]
DINT[35]
Status
EE_write_Counter
0..8, 255
0..
2.000 Million
DINT[36]
CPU_Type
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
-20..+80
Description
Address
This dataset should be read when the system configuration is changed. In this the minimum and
maximum possible actual value is entered.
Note: This dataset can only be read.
Current actual value
Current speed
Current program number
Analog value on analog cam ...
"
"
"
"
"
"
"
"
"
"
"
"
"
This value is always 0 in CamCon 1756-DICAM
This value is always 0 in CamCon 1756-DICAM
Current temperature in the device
Warning:
The permitted temperature range lies between 0 and +50°. Outside this range error functions can
occur.
Number of cams or delay times for Speed Compensation which can still be stored
Delay times for separate switch-on and switch-off points require double storage space.
Number of programmed cams
Maximum possible Speed Compensation in ms.
Warning:
Delay times must not be longer than this value
Size of built-in RAM storage
Currently: 1048576 Byte
Size of free Ram storage in bytes
Size of the EEProm
8,16,32,48,64,128 Kbyte
This value is always 0 in CamCon 1756-DICAM
Minimum possible actual value.
Warning:
Each cam value or parameter value must not be smaller than this value.
Maximum possible actual value.
Warning:
Each cam value or parameter value must not be equal to or greater than this value..
Maximum number of programs (products) which can be administered
Note:
The number of programmable cams depends on the size of EEProm storage capacity.
Number of programmed delay times for Speed Compensation
Firmware data character 1..4",
Firmware data character 5..8",
Firmware data character 9..12",
e.g.: '18.03.2002'
See Chapter "6.3.12. TAG "DC_3_STATUS"" on page 41.
EEProm write counter
Warning:
If a value greater than 1 Million is reached here, there is the danger of loss of data.
Coldfire CPU Type
Currently Type 1
6.3.14. TAG "DC_4_QUIT_ERROR"
Type
DC_9_HEADER
DINT[0]
Note:
Name
ADR
DATA
Data
205,3,1
-1
Description
Adress
If this dataset is transferred, an error message "Pos-Err: 1,2,3,5", "Output-Error"
adjacent to the CamCon must be confirmed.
Note: write only possible
Using the DICAM1756 - program the TAG "DC_3_STATUS" is read every 5 seconds, if
the
safety output
i.e.
the
Run
controll
Bit
is
not
active.
If an error message is detected, the program tries by writing this TAG, to acknowledge
them automatically.
Edition: 18.08.2004
Page: 42
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
6.3.15. TAG Range "DC_5_...."
Type
Name
Data
Description
INT
DC_5_OUTPUT_ENABLE_1_16
local:X:0.Data[0]
Alias for the O - Range in which the enable for output 1 - 16 must be entered.
INT
INT
INT
DINT
DC_5_OUTPUT_ENABLE_17_32
DC_5_OUTPUT_ENABLE_33_48
DC_5_OUTPUT_ENABLE_49_64
DC_5_PRG_ACTUAL
local:X:0.Data[1]
local:X:0.Data[2]
local:X:0.Data[3]
0..32767
INT
BOOL
DC_5_STATUS_COMM_RANGE
DC_5_STATUS_COMM_ERROR:
local:X:I.Data[2]
0..1
BOOL
DC_5_STATUS_COMM_TIMEOUT
0..1
INT
INT
INT
DC_5_STATUS_OUTPUT_1_16
DC_5_STATUS_OUTPUT_17_32
DC_5_STATUS_Realtime_Actual_valu
e
local:X:I.Data[3]
local:X:I.Data[4]
local:X:I.Data[6]
Alias for the O - Range in which the enable for output 17 - 32 must be entered.
Alias for the O - Range in which the enable for output 33 - 48 must be entered.
Alias for the O - Range in which the enable for output 49 - 64 must be entered.
Program number to be introduced. If this and the value in TAG
"DC_2_PRG_CHANGE" is different, a program change is created.
Alias for the I - Range in which the Status Bits of the CamCon lie.
Bit which is set when an error has occurred during data transfer. This must be
monitored by the user program and reset.
Bit which is set when a timeout has occurred during data transfer. The dataset is resent. This bit is reset as soon as the data transfer has been successful.
Alias for the I - Range in which the bits for Output 1 - 16 lie.
Alias for the I - Range in which die bits for Output 17 - 32 lie.
Alias for the I - Range in which the current actual value of the CamCon in realtime
lies.
DINT
INT
DC_5_STATUS_Realtime_Speed
DC_5_STATUS_Realtime_Speed_Help
-32767..+32767
local:X:I.Data[5]
Note:
This variables position changes correspponding to the number of
adjusted outputs.
Current speed in realtime
Alias for the I - Range in which the current speed of the CamCon in realtime lies.
Note:
BOOL
DC_5_STATUS_RUN_CONTROLL
shows:
DC_5_STATUS_OUTPUT_17_32.15
DC_5_STATUS_V0_OUTPUT
shows:
DC_5_STATUS_OUTPUT_17_32.13
DC_5_STATUS_VR_OUTPUT
shows:
DC_5_STATUS_OUTPUT_17_32.14
BOOL
BOOL
This variables position changes correspponding to the number of
adjusted outputs.
0..1
This will be re-calculated and will then lie in DC_5_STATUS_Realtime_Speed.
Alias for the I - Range in which the bits for the safety output (RUN_CONTROL) lie.
0..1
Alias for the I - Range in which the bits for the idling output lies.
0..1
Alias for the I - Range in which the bits for the turning direction output lie.
6.3.16. TAG Range "DC_9_...."
Type
Name
Data
MESSAGE
MESSAGE
DC_9_MSG_BUFFER
DC_9_MSG_ADR_R:
DC_9_MSG_ADR_W:
DC_9_MSG_BUFFER_TMP:
-
MESSAGE
MESSAGE
DC_9_MSG_DATA_R:
DC_9_MSG_DATA_W:
-
Description
"CIP Generic Messages" TAG for addresses write when reading.
"CIP Generic Messages" TAG for adresses write when writing.
Temporary messages buffer for reading and writing
consists of 1 * DC_9_HEADER and 126 * DINTs.
This will be used for each write or read message as send or receive buffer.
"CIP Generic Messages" TAG for data reading
"CIP Generic Messages" TAG for data writing.
Edition: 18.08.2004
Page: 43
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected].com
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
6.4. Transferring actual value and speed into realtime
The CamCon 1756-DICAM cam-switch unit is able to provide the actual value and the speed value of
the ControlLogix as an input word in realtime.
6.4.1. Speed
The realtime speed output is switched ON or OFF. See Chapter 6.3.5. TAG
"DC_1_SYSTEM_CONFIG" Value: DINT[39]. If realtime transfer is switched on, a 16 bit wide value is
entered after the last CamCon output in the I - Range of the ControlLogix. From the transferred value
the scaling of the CamCon must be calculated. First a value of 32768 must be subtracted (SUB) and
the intermediate result INT (SPEED_HELP) must be stored. This value is then recalculated to result in
the actual speed value by use of a CPT command and the 100% speed value (Chapter "6.3.5. TAG
"DC_1_SYSTEM_CONFIG" Value: DINT[19]" on page 32).
Current speed (DINT) = SPEED_HELP * DINT[19] / 32768
6.4.2. Actual value
The realtime actual value output is switched ON or OFF. See Chapter 6.3.5. TAG
"DC_1_SYSTEM_CONFIG" Value: DINT[26]. If the realtime transfer is switched on (DINT[26] = 2), a
32 bit wide value will be entered behind the last CamCon output or, if switched on, behind the realtime
speed value in the I-Range of the ControlLogix. This value can be used further immediately without
recalculation. If the maximum actual value is larger than 32767 or smaller than -32767, then a
conversion of the 2 INTs from the I - Range to a DINT must be made.
7. Error messages and removal of errors (FAQ)
The error messages appear on the standard display or in CamCon DC16, 90, 115, 300 and 1756DICAM without a display of their own through the status LED or status bits. See also Chapter 6.3.12.
TAG "DC_3_STATUS" on page 41.
7.1. Problem: "Pos - Err:1".
Possible causes:
The measuring system has not been correctly connected.
Solution:
Please check the wiring to the measuring system. Please consult the instruction manual to the
measuring system.
If the error is eliminated, the error-message can be deleted by Absetzen der Error Quittierung
7.2. Problem: "Pos - Err:2".
Possible causes:
The measuring system is faulty or not connected.
The setting of the error bits in the special measuring system setting is not correct.
Solution:
Check the wiring to the measuring system.
Check the inputs of the measuring system resolution.
Consult the instruction manual of your measuring system.
If the error is eliminated, the error-message can be deleted by Absetzen der Error Quittierung
Edition: 18.08.2004
Page: 44
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
7.3. Problem: "Pos - Err:3".
Possible causes:
The resolution of the connected measuring system is not in accord with the input resolution. The
measuring system is faulty. The actual value is outside the range which was entered in the menu path
setting for linear systems. See Chapter "6.3.5. TAG "DC_1_SYSTEM_CONFIG" Value: DINT[12]" on
page 32. If an incremental measuring system is set, then this report is an alternative for the message
"Clear...".
Solution:
Check the input of the measuring system setting and the cable length setting.
Consult the instruction manual of your measuring system.
Consult Chapter "Problem: Clear...".
If the error is eliminated, the error-message can be deleted by Absetzen der Error Quittierung
7.4. Problem: "Pos - Err:5".
Possible causes:
The measuring system control is activated. The CamCon has registered a large unacceptable actual
value jump. The measuring system is possibly faulty.
Solution:
Check the input of the measuring system setting and of the setting of the cable length or increase the
permitted actual value jump. Consult Chapter "6.3.5. TAG "DC_1_SYSTEM_CONFIG" Value: DINT[9]"
on page 31. Consult the instruction manual of your measuring system.
If the error is eliminated, the error-message can be deleted by Absetzen der Error Quittierung
7.5. Problem: An "Pos-Error:" occurs during operation.
The monitor displays "Pos-Err:1", "Pos-Err:2", "Pos-Err:3" or "Pos-Err:5".
Possible causes:
The connection cable of the measuring system or the measuring system itself is defective. A cable
without screening or without dual strand was used. The laying of a connection cable in the vicinity of a
strong electromagnetic source of interference (e.g. high voltage cable, motor cable) can lead to an pos
error.
Solution:
Check the wiring to the measuring system. Replace the measuring system.
Take measures for screening.
Lay the connection lead in another location.
Consult the instruction manual of your measuring system.
If the error is eliminated, the error-message can be deleted by Absetzen der Error Quittierung
7.6. Problem: "RAM-Full" = RAM memoryis full.
Possible causes:
The resolution of the measuring system is too large.
The number of outputs is too high.
The number of Speed Compensated outputs is too high.
Solution:
Check the input of the measuring system setting.
Reduce the measuring system resolution.
Reduce the number of Speed Compensated outputs.
Please contact your customer service representative if you require a RAM memory extension.
Edition: 18.08.2004
Page: 45
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
7.7. Problem: The EEProm memory is full.
Cause:
Too little memory space available in the EEPROM for the storage process.
Solution:
Please contact your customer service representative if you require an EEProm storage extension.
Also consult Chapter "8. Calculation EEPROM cam storage on page 48.
7.8. Problem: Outputs will not activate
Possible causes:
An error message is active. The outputs are not connected to power supply. A programed Cam is to
short or gets to short by increasing rotation speed. The enable - Input is not set.
Solution:
Check the error message.Program a longer Cam. A Cam with delay-time/speed-compensation must at
least have the length of two steps.
Enable Outputs at the enable-Input, see also chapter 6.3.15. TAG Range "DC_5_...." Enable_1_64 on
page 43
Enable the outputs through the ControlLogix PLC.
Send the device in to be repaired.
7.9. Problem: "Out - Error".
Possible causes:
Your outputs are overloaded or short-circuited. Check the wiring and the connection output as well as
possible inductive loads which have no zero setting or are driven by a cancellation component.
The number of set inputs is not correct.
Power failure at an external interface module (e.g. DC91/IO or DC16/IO).
Solution:
See chapter "4.10. The outputs" on page 21.
See chapter "6.3.5. TAG "DC_1_SYSTEM_CONFIG" Value: DINT[30]" on page 32.
See chapter "6.3.5. TAG "DC_1_SYSTEM_CONFIG" Value: DINT[47]" on page 33.
If the error is eliminated, the error-message can be deleted by Absetzen der Error Quittierung
Here the attempt to reset outputs is done
Warning:
Wires crossing behind the outputs, if the cables leading towards the switchOFF of the outputs are in an awkward position, can lead to a switch-OFF of the
outputs, since in an open situation a potential is built up which, when the
contacts are closed, is led back into the outputs.
In inductive loads the outputs must be organised with a flywheeling diode. Protection or
induction in the switch cabinet in the immediate vicinity of the device or due to their wiring
have an effect on the device or its wiring and must be organised with cancellation
components.
7.10. Problem: Error in the EEPROM.
Possible causes:
The data of the EEPROM was changed or destroyed by interference.
One of the existing data carriers (EEPROM or EPROM) was renewed or is defective.
The power supply was switched OFF during alteration of the data.
Solution:
Transfer the DC_0_CLEAR_ALL instruction. All data will be erased and must be re-entered.
Should these errors occur repeatedly, please contact your customer service.
7.11. Problem: "Error ???"
Possible causes:
An unpredictable error has occurred.
Solution:
Please contact your customer service.
Edition: 18.08.2004
Page: 46
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
7.12. Problem: "Clear...."
Cause:
The CamCon is waiting for the arrival of the Clear signal in an incremental measuring system.
Solution:
Set the Clear signal ON or activate an actual value Preset. The result is the immediate release of the
Cam Switch Unit.
Note:
The incremental measuring system is only available as an option for CamCon DC16,
DC50/51, DC115, DC300 and CamCon 1756-DICAM.
See chapter "6.3.6.3. TAG "DC_1_SYSTEM_CONFIG_ENC_2_INK"" on page 35.
Edition: 18.08.2004
Page: 47
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
8. Calculation EEPROM cam storage
In the CamCon you have the opportunity to extend the EEPROM Cam storage. The storage space
required for programming is influenced by the following factors:
1. Basic requirement
2. Per cam
3. Per set delay time for Speed Compensation
4. Per name for an output
5. Per set key / code
6. For a special measuring system
7. For direct or ”actual” program selection
8. Per set program name
9. Per line of the OP function
= 256 Bytes
= 12 Bytes
= 12 Bytes
= 24 Bytes
= 66 Bytes
= 66 Bytes
= 12 Bytes
= 48 Bytes
= 72 Bytes
The value is generated by the CamCon with the following formula:
Storage requirements in Bytes
Example 1:
=
+
+
+
+
+
+
+
+
Basic needs
Number of cams * 12
Number of delay times for Speed Compensation * 12
Number of output names * 24
Number of user keys * 66
66 when the special measuring system is available.
12 when "on Pos" program selection is set.
48 * number of set program names.
72 * number of set lines of the OP function.
The Cam Switch Unit is supposed to have 8 Programs each with 16 cams and Speed
Compensation for 16 outputs.
Storage requirement in Bytes = 256 Bytes + ( 8 Programs * 16 * 12 Bytes ) + ( 16 * 12 Bytes )
Storage requirement = 1984 Bytes
Example 2:
The Cam Switch Unit is supposed to have 20 programs each with 16 cams and 16
delay times for Speed Compensation.
Storage requirement in Bytes
=
+
+
+
+
256 Bytes
( 20 Programs * 16 * 12 Bytes )
( 16 TZK * 12 Bytes )
( 16 Output names * 24 Bytes )
( 1 User keys * 66 Bytes )
Storage requirement = 4738 Bytes
Warning:
Through alterations in the storage structure of the CamCon software, the extent to
which storage capacity is used up can differ from software version to software version!
Edition: 18.08.2004
Page: 48
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
9. Calculation the RAM storage-requirement for CamCon
The required RAM-main storage (not similar to the constand value - Camstorage or the EEPROM)
depends on 7 factors:
1. Standard consumption
2. Number of outputs
3. Cycle time
4. Actual value/measuring system
resolution
5. Maximal Speed-compensation
6. Mode of program selection
(approximately 100000 Byte)
( 8 to 200 in steps of 8 outputs).
(displayed in miliseconds).
(displayed in impulses)
( 0 to 9999.9 in steps of 100 microseconds).
(the double ammount of storage is required ).
( See also chapter "6.3.5. TAG
"DC_1_SYSTEM_CONFIG" Value: DINT[36]" on page
33).
( EE-Prom - storage size in Byte for Cache ).
7. Size of the EE-Prom storage
The RAM - storage requirement is calculated by the following formula:
storage requirement in Bytes =
standard consumption +
Number of outputs * IActual value resolution.* ( 2 If program Mode not slow )
+
8
max. delay-time * 4
+ EE-Prom size
cycletime
Example 1:
The camswitch with a resolution of 360°, an EE-Promstorage of 32kByte, 16 outputs, a
speed-compensation of 1000ms and a cycletime of 250µs needs:
Storage requirement in Bytes = 100000 +
16 * 360
1000 * 4
+ 0.250 + 32768
8
Storage requirement in Bytes = 100000 + 720 + 16000 + 32768
Storage requirement in Bytes = 149488 = ca. 150kByte
Example 2:
The camswitch with a resolution of 8192°, an EE-Promstorage of 48kByte, 64 outputs,
a speed-compensation of 500ms and a cycletime of 250µs, needs:
64 * 8182
500 * 4
+ 0.250 + 49152
8
Storage requirement in Bytes = 100000 + 65536 + 8000 + 49152
Storage requirement in Bytes = 100000 +
Storage requirement in Bytes = 222688 = ca. 220kByte
Note:
If the required RAM - storage requirement greater than the CamCons total ammount of
storage, you need to reduce the measuring system's resolution.
Attention: Changings in the storage-structure of the CamCon software the storage requirement can
alternate at different software-versions!
Edition: 18.08.2004
Page: 49
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
10. Technical Data
Application...........................................................ControlLogix 1756 PLC
Display.................................................................32 * Status LED for each Output, 1 * Status LED
Interfaces ............................................................ControlLogix 1756 back plane bus,
optional RS485 but only for testing purposes.
Number of outputs ..............................................24, electrolytically separated for ControlLogix
(extendable to 200 through external Interface Option
X).
Number of inputs.................................................no/ optional 8, electrolytically separated for
ControlLogix, of these Input 1 - 8
are linked with output 17 - 24 (extendable to 200
through external Interface Option X).
Number of programmable cams .........................1200 or optional 4000, 10000 cams
Data saving/storage ............................................EEPROM (16K, 48K or 128K)
Number of programs ...........................................32768
cycle time, (switchover speed) ............................from 70µs this is adjusted to requirements (optimised).
Speed or Delay Time Compensation (DTC) .......can be set individually for each output, depending on
measuring system and storage space.
Setting range of the DTC ....................................0 up to maximum 9999.9ms, depending on measuring
system and storage space.
Accuracy of the DTC ...........................................+0 up to -1 step
Measuring system - Input....................................synchronous serial (SSI) grey coded, optional
incremental data input, PLL data input, time related
data input or pure incremental Hiperface input.
Resolution of the measuring systems ................can be set in 360 steps (Standard), otherwise
depending on measuring system and storage space.
Measuring system (SSI)......................................AAG60007, AAG612-2048, AAG612-4096,
AAG612-8192, AAG615, AAG626 oder AAG66107.
Measuring system (incremental).........................ADG60/24/500.
Cut-off frequency of incremental input ................approx. 100kHz
Input level of incremental input ...........................24V PNP.
Number of revolutions of the Hiperface input......max. 3000 min -1 with 512 Impulse revolution,
max. 1500 min -1 with 1024 Impulse revolution.
Zero point correction of the measuring system...is programmed in CamCon
Turning direction of the measuring system .........is programmed in CamCon
Length of the connecting cable
between measuring system and CamCon ..........at SSI up to maximum 300m (optional up to1000m)
Power supply.......................................................24V DC ±20 %
Measuring system - power supply.......................with 24V DC via the power supply of the outputs (24V
on pin 2,5 or 6).
Current intake from the back plane.....................type 450mA
Current intake periphery......................................type 100mA without measuring system and outputs
Output .................................................................24V DC, switching to plus
Output current .....................................................0,2Amp. for each output or 0.4amp. for each output at
50% on switch time, short-circuit proof
Programming ......................................................via back plane bus with "Messages" and "UserDefined".
Connections for:
Power supply, measuring system
and cam outputs .................................................via screw-pin, 36 poles
AB Order Nr.: 1756-TBCH (not contained in the
delivery range of the CamCon 1756-DICAM).
Assembly.............................................................see Chapter "3. Installation" on page 12.
Type of protection ...............................................IP20
Working/operational temperature .......................0°C ... + 55° C
Weight.................................................................approx. 350g without connection plug
Edition: 18.08.2004
Page: 50
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
11. Keyword register
Actual value, realtime............................................................................................................................. 44
Analog measuring system input ............................................................................................................. 19
brake functions....................................................................................................................................... 10
C - Range............................................................................................................................................... 24
CE ............................................................................................................................................................ 2
centre pressure ...................................................................................................................................... 10
Clear....................................................................................................................................................... 47
Communication, ControlLogix <-> CamCon 1756 - DICAM .................................................................. 25
Connections, electrical ........................................................................................................................... 14
ControlLogix programm ......................................................................................................................... 25
Delay time .............................................................................................................................................. 41
Delay time compensation, Effects............................................................................................................ 7
delay time for Speed Compensation, separate for switch-ON and switch-OFF points .......................... 11
Delay time, Calculation ............................................................................................................................ 9
Edition, ControlLogix software ............................................................................................................... 25
EEPROM cam storage, Calculation....................................................................................................... 48
EEProm storage is full ........................................................................................................................... 46
EEPROM, Error...................................................................................................................................... 46
Error messages...................................................................................................................................... 44
Export, L5K ............................................................................................................................................ 25
External interface ................................................................................................................................... 16
Hiperface.............................................................................................................................. 19; 35; 37; 40
I - Range .......................................................................................................................................... 22; 24
Import, L5K............................................................................................................................................. 25
Incremental measuring system input ..................................................................................................... 18
Input wiring............................................................................................................................................. 21
Inputs, general ....................................................................................................................................... 21
Installation .............................................................................................................................................. 12
Installation instructions........................................................................................................................... 12
Installation, ControlLogix app. software ................................................................................................. 25
L5K................................................................................................................................................... 25; 38
Maximum possible actual value ............................................................................................................. 42
Measuring system, General information ................................................................................................ 17
Message, parameter, cams and delay times ......................................................................................... 27
Message, Status, Parameter, Cam and Delay Times............................................................................ 28
millenium .................................................................................................................................................. 2
Minimum possible actual value .............................................................................................................. 42
No contact to unit XX ............................................................................................................................. 44
O - Range............................................................................................................................................... 24
Out - Error .............................................................................................................................................. 46
Outputs, general..................................................................................................................................... 21
Parallel measuring system input ............................................................................................................ 17
PDF - File ................................................................................................................................................. 2
pin layout, Hiperface incremental measuring system ............................................................................ 15
pin layout, incremental measuring system ............................................................................................. 15
pin layout, inputs .................................................................................................................................... 15
pin layout, output .................................................................................................................................... 14
Edition: 18.08.2004
Page: 51
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
pin layout, SSI measuring system .......................................................................................................... 15
Planning the ControlLogix CPU ............................................................................................................. 23
PLL measuring system input.................................................................................................................. 20
Pos - Err 1 .............................................................................................................................................. 44
Pos - Err 2 .............................................................................................................................................. 44
Pos - Err 3 .............................................................................................................................................. 45
Pos - Err 5 .............................................................................................................................................. 45
Power supply to CamCon ...................................................................................................................... 14
RAM, storage requirement, calculation.................................................................................................. 49
RAM-Full ................................................................................................................................................ 45
realtime .................................................................................................................................................. 44
RS232 as a measuring system .............................................................................................................. 20
RS485 .................................................................................................................................................... 16
Speed Compensation............................................................................................................................. 41
Speed Compensation, Effects ................................................................................................................. 7
Speed, realtime ...................................................................................................................................... 44
SSI measuring system input .................................................................................................................. 17
Starting................................................................................................................................................... 23
Status bits .............................................................................................................................................. 22
Status Displays ...................................................................................................................................... 22
Status LED ............................................................................................................................................. 22
Table of Contents..................................................................................................................................... 3
TAG
ADR .................................................................................................................................................. 30
DC_0_CLEAR_ALL .......................................................................................................................... 30
DC_0_EEPROM_LOCK ................................................................................................................... 30
DC_0_HW_RESET........................................................................................................................... 30
DC_1_SYSTEM_CONFIG ................................................................................................................ 31
DC_1_SYSTEM_CONFIG_ENC_0_SSI........................................................................................... 34
DC_1_SYSTEM_CONFIG_ENC_1_PAR ......................................................................................... 34
DC_1_SYSTEM_CONFIG_ENC_2_INK .......................................................................................... 35
DC_1_SYSTEM_CONFIG_ENC_3_MULTI...................................................................................... 35
DC_1_SYSTEM_CONFIG_ENC_4_PLL .......................................................................................... 36
DC_1_SYSTEM_CONFIG_ENC_5_TIMER ..................................................................................... 36
DC_1_SYSTEM_CONFIG_ENC_7_AG615 ..................................................................................... 36
DC_1_SYSTEM_CONFIG_ENC_8_SPEED_SIM............................................................................ 37
DC_1_SYSTEM_CONFIG_ENC_9_HIPER ..................................................................................... 37
DC_1_SYSTEM_CONFIG_PLC[X]................................................................................................... 38
DC_1_SYSTEM_CONFIG_PLC_OK................................................................................................ 39
DC_1_SYSTEM_SET_ACTUAL_VALUE ......................................................................................... 40
DC_2_PRG_CAM[X].CAM[Y] ........................................................................................................... 40
DC_2_PRG_CAM_OK...................................................................................................................... 40
DC_2_PRG_CHANGE...................................................................................................................... 41
DC_2_PRG_DTC[X] ......................................................................................................................... 41
DC_2_PRG_DTC_OK ...................................................................................................................... 41
DC_3_STATUS................................................................................................................................. 41
DC_3_STATUS_FULL...................................................................................................................... 42
DC_4_QUIT_ERROR ....................................................................................................................... 42
DC_5_............................................................................................................................................... 43
DC_9_............................................................................................................................................... 43
program TAGs of DICAM1756.......................................................................................................... 29
Special measuring system TAGs...................................................................................................... 34
Technical Data ....................................................................................................................................... 50
Time -Cam ............................................................................................................................................. 11
time cam ................................................................................................................................................ 41
Timer as a measuring system................................................................................................................ 20
Edition: 18.08.2004
Page: 52
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Digital Cam Switch Unit
CamCon 1756-DICAM
UP - Date ................................................................................................................................................. 2
User-Defined, TAGs............................................................................................................................... 26
Welding operations, Safety precautions ................................................................................................ 21
Y2K .......................................................................................................................................................... 2
Edition: 18.08.2004
Page: 53
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com