VXZ Series Zero Differential Pressure Pilot Operated 2 Port Solenoid Valve

VXZ Series Zero Differential Pressure Pilot Operated 2 Port Solenoid Valve
Zero Differential Pressure Type Pilot Operated 2 Port Solenoid Valve
Series VXZ22/23
For Air, Water, Oil
®
VX2
VXD
VXZ
VXE
VXP
VXR
VXH
VXF
VX3
VXA
VCH첸
VDW
Solenoid valves for various fluids used in a wide variety of applications VQ
LVM
VCA
Improved
corrosion resistance
Special magnetic material adopted
Reduced power
consumption (DC spec.)
VCB
VXZ22: 8 W → 7 W
VXZ23: 11.5 W → 10.5 W
VCL
VCS
VCW
Enclosure:
IP65
Low-noise
construction
Special construction
enables to reduce the
metal noise. (DC spec.)
Flame resistance
UL94V-0 conformed
Flame resistant mold coil material
Improved
maintenance
performance
Maintenance is performed easily
due to the threaded assembly.
77
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
78
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Zero Differential Pressure Type
Pilot Operated
2 Port Solenoid Valve
Series VXZ22/23
For Air, Water, Oil
VX2
VXD
Valve
VXZ
Normally closed (N.C.)
Normally open (N.O.)
VXE
VXP
Coil: Class B, Class H
100 VAC, 200 VAC, 110 VAC,
220 VAC, 240 VAC, 230 VAC,
48 VAC, 24 VDC, 12 VDC
Body
Seal
Brass (C37), Stainless steel
NBR, FKM, EPDM
VXH
• Grommet
• Conduit
• DIN terminal
• Conduit terminal
Rated Voltage
VXF
VX3
VXA
Model
Orifice dia.
Material
VXR
Electrical Entry
Solenoid Coil
VXZ22320
VXZ22420
VXZ23520
VCH
VXZ23620
10 mmø
15 mmø
20 mmø
25 mmø
Port size
1/4 (8A)
1/2 (15A) 3/4 (20A)
(Nominal size) 3/8 (10A)
VDW
VQ
LVM
1 (25A)
VCA
VCB
VCL
Contents
VCS
VCW
For Air ······································································································ P.82
For Water ································································································· P.84
For Oil ······································································································ P.86
Construction ····························································································· P.88
Dimensions ······························································································ P.89
Replacement Parts ·················································································· P.90
79
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
7-2-10-VXZ.qxd
10.2.17 10:05 AM
Page 1
Series VXZ22/23
Common Specifications
Standard Specifications
Valve construction
Zero differential pressure type pilot operated 2 port diaphragm type
Withstand pressure (MPa)
5.0
Body material
Valve
specifications
Brass (C37), Stainless steel
Seal material
NBR, FKM, EPDM
Dusttight, Low jetproof (equivalent to IP65)∗
Enclosure
Environment
Location without corrosive or explosive gases
Vibration resistance/Impact resistance
(m/s2)
30/150 or less
AC
(Class B coil, Built-in full-wave rectifier type)
Rated
voltage
100 VAC, 200 VAC, 110 VAC, 220 VAC, 230 VAC, 240 VAC, 48 VAC
AC (Class H coil)
24 VDC, 12 VDC
DC (Class B coil only)
Coil
specifications
±10% of rated voltage
Allowable voltage fluctuation
Allowable
leakage
voltage
AC
(Class B coil, Built-in full-wave rectifier type)
10% or less of rated voltage
AC (Class H coil)
20% or less of rated voltage
DC (Class B coil only)
2% or less of rated voltage
Class B, Class H
Coil insulation type
∗ Electrical entry: Grommet with surge voltage suppressor (GS) has a rating of IP40.
Be sure to read “Specific Product Precautions.”
Solenoid Coil Specifications
AC Specification (Class H coil)
DC Specification (Class B coil only)
Model
Power consumption (W)
Temperature rise (°C) Note)
VXZ22
7
45
VXZ23
10.5
60
Apparent power (VA)
Model
VXZ22
Note) The value at ambient temperature of 20°C and when the rated voltage is
applied.
AC Specification (Class B coil, Built-in full-wave rectifier type)
Model
VXZ22
VXZ23
Apparent power (VA) Note 2) Temperature rise (°C) Note 1)
9.5
12
60
VXZ23
Frequency (Hz)
Inrush
Energized
Temperature
rise (°C) Note)
50
65
33
100
60
55
27
95
50
94
50
120
60
79
41
115
Note) The value at ambient temperature of 20°C and when the rated voltage is
applied.
65
Note 1) The value at ambient temperature of 20°C and when the rated voltage
is applied.
Note 2) There is no difference in the frequency and the inrush and energized
apparent power, since a rectifying circuit is used in the AC (Class B
coil, built-in full-wave rectifier type).
80
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Applicable Fluid Check List
Zero Differential Pressure Type Pilot Operated 2 Port Solenoid Valve Series VXZ22/23
Refer to pages 82, 84, and 86 for specifications and models.
All Options
0
2
VXZ2
1
R1
Option symbol
Fluid and application
Air
Water
Heated water
Oil
Note 2)
High corrosive spec., Oil-free
Copper-free, Fluorine-free Note 4)
Other combinations
Option
symbol
Nil
G
Nil
G
E
P
A
H
D
N
L Note 1)
J
P
B
Seal
material
NBR
NBR
EPDM
Body/
Shading
coil material Note 5)
Brass (C37)/–
Stainless steel/–
Brass (C37)/–
Stainless steel/–
Brass (C37)/Cu
Stainless steel/Ag
Brass (C37)/–
FKM
Stainless steel/–
Brass (C37)/Cu
Stainless steel/Ag
FKM
EPDM
EPDM
Guide ring and
push rod (N.O. only)
material
Stainless steel/–
PPS
VX2
Coil insulation
type Note 3)
Note
VXD
B
VXZ
B
VXE
H
VXP
B
VXR
H
VXH
B
Stainless steel/–
B
Stainless steel/Ag
H
Brass (C37)/–
B
VXF
VX3
Note 1) “L” option is the oil-free treatment.
Note 2) The dynamic viscosity of the fluid must not exceed 50 mm2/s.
The special construction of the armature adopted in the built-in full-wave rectifier type gives an improvement in OFF response by providing clearance on the
absorbed surface when it is switched ON.
Select the DC spec. or AC spec. built-in full-wave rectifier type when the dynamic viscosity is higher than water or when the OFF response is prioritized.
Note 3) Coil insulation type Class H: AC spec. only
Note 4) The nuts (non-wetted parts) are nickel-plated on the Brass (C37) material.
Note 5) There is no shading coil attached to the DC spec. or AC spec built-in full-wave rectifier type.
VXA
VCH
VDW
VQ
∗ Please contact SMC when fluids other than above are used.
LVM
VCA
VCB
VCL
VCS
VCW
81
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Series VXZ22/23
For Air
(Inert gas)
Model/Valve Specifications
N.C.
N.O.
Passage symbol
Passage symbol
2
2
1
1
Normally Closed (N.C.)
Port size
(Nominal
size)
1/4 (8A)
3/8 (10A)
1/2 (15A)
3/4 (20A)
Orifice dia.
(mmø)
10
15
20
Model
Min. operating
pressure
differential (MPa)
VXZ2230-02
VXZ2230-03
VXZ2240-04
VXZ2350-06
0
Min. operating
pressure
differential (MPa)
Port size
(Nominal
size)
Orifice dia.
(mmø)
Model
1 (25A)
25
VXZ2360-10
Max. operating pressure
differential (MPa)
AC
DC
1.0
0.7
1.0
0
Max. operating pressure
differential (MPa)
AC
DC
1.0
1.0
Flow characteristics
C
8.5
11.0
23.0
38.0
b
0.44
0.42
0.34
0.20
Cv
2.4
2.8
6.0
9.5
Flow characteristics
Effective area (mm2)
215
Max. system
pressure
(MPa)
Mass (g)
550
1.5
760
1300
Max. system
pressure
(MPa)
Mass (g)
1.5
1480
Max. system
pressure
(MPa)
Mass (g)
Note) Mass of grommet type. Add 10 g for conduit type, 30 g for DIN terminal type, 60 g for conduit terminal type respectively.
• Refer to “Glossary of Terms” on page 26 for details on the max. operating pressure differential and the max. system pressure.
Normally Open (N.O.)
Port size
(Nominal
size)
1/4 (8A)
3/8 (10A)
1/2 (15A)
3/4 (20A)
Orifice dia.
(mmø)
10
15
20
Model
Min. operating
pressure
differential (MPa)
VXZ2232-02
VXZ2232-03
VXZ2242-04
VXZ2352-06
0
Min. operating
pressure
differential (MPa)
Port size
(Nominal
size)
Orifice dia.
(mmø)
Model
1 (25A)
25
VXZ2362-10
0
Max. operating pressure
differential (MPa)
AC
DC
0.7
0.6
Max. operating pressure
differential (MPa)
AC
DC
0.7
0.6
Flow characteristics
C
8.5
11.0
23.0
38.0
b
0.44
0.42
0.34
0.20
Cv
2.4
2.8
6.0
9.5
Flow characteristics
Effective area (mm2)
215
600
1.5
850
1370
Max. system
pressure
(MPa)
Mass (g)
1.5
1550
Note) Mass of grommet type. Add 10 g for conduit type, 30 g for DIN terminal type, 60 g for conduit terminal type respectively.
• Refer to “Glossary of Terms” on page 26 for details on the max. operating pressure differential and the max. system pressure.
Fluid and Ambient Temperature
Valve Leakage Rate
Internal Leakage
Power source
AC/Class B coil
DC
Fluid temperature (°C)
Solenoid valve option symbol
Nil, G
–10 to 60 Note)
–10 to 60 Note)
Ambient
temperature
(°C)
–10 to 60
–10 to 60
Seal material
NBR
Leakage rate (Air)
1 cm3/min or less
External Leakage
Seal material
NBR
Leakage rate (Air)
1 cm3/min or less
Note) Dew point temperature: –10°C or less
82
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Zero Differential Pressure Type
Pilot Operated 2 Port Solenoid Valve
Series VXZ22/23
For Air
How to Order
DC
AC/Class B coil (Built-in
full-wave rectifier type)
VXZ 22 3 0
VXZ 22 3 0
02
02
5 G 1
1 G R1
VX2
Model
VXD
Orifice diameter
Refer to the table (1)
shown below for availability.
Refer to the table (1) shown
below for availability.
Bracket
Nil
Valve/Body configuration
0
2
B
Solenoid valve option
N.C. / Single unit
N.O. / Single unit
None
With bracket
∗ Bracket is not removable.
Refer to the table (2)
shown below for availability.
Suffix
Nil
Z
Built-in full-wave
rectifier type
Port size
—
Oil-free spec.
Refer to the table (1)
shown below for availability.
VXZ
VXE
VXP
VXR
Thread type
Nil
T
F
N
Rc
NPTF
G
NPT
Electrical entry
G - Grommet
GS- With grommet surge
C- Conduit
VXH
VXF
voltage suppressor
VX3
Rated voltage
1
2
3
4
5
100 VAC 50/60 Hz
200 VAC 50/60 Hz
110 VAC 50/60 Hz
220 VAC 50/60 Hz
24 VDC
6
7
8
J
12 VDC
240 VAC 50/60 Hz
48 VAC 50/60 Hz
230 VAC 50/60 Hz
∗ Refer to the table (3) shown below for availability.
T - With conduit terminal
TS - With conduit terminal and
Connector
D - DIN terminal
DS - DIN terminal with surge
surge voltage suppressor
TL - With conduit terminal
and light
TZ - With conduit
terminal, surge
voltage
suppressor and light
voltage suppressor
DL - DIN terminal with light
DZ - DIN terminal with
surge voltage
suppressor and light
DO - For DIN terminal (without
connector, gasket is included.)
∗ DIN type is available with class B only.
Refer to page 90 for ordering coil only.
∗ Refer to the table (3) for the available combinations between each electrical
option (S, L, Z) and rated voltage.
∗ Surge voltage suppressor is integrated into the AC/Class B, as a standard.
Table (1) Model/Orifice Diameter/Port Size
Normally Closed (N.C.) / Normally Open (N.O.)
Orifice symbol (Diameter)
Solenoid valve (Port size)
Model
Port no.
(Port size)
VXZ22
VXZ23
3
4
5
6
(10 mmø) (15 mmø) (20 mmø) (25 mmø)
02 (1/4)
03 (3/8)
04 (1/2)
Table (2) Solenoid Valve Option
Option
symbol
Nil
G
Seal
material
NBR
Body material
Brass (C37)
Stainless steel
Body
Note
B
—
VDW
VQ
LVM
VCA
VCB
Seal
VCL
NBR
VCS
VCW
Table (3) Rated Voltage – Electrical Option
Coil
insulation
type
VCH
Material
Brass (C37),
Stainless
steel
06 (3/4)
10 (1)
VXA
Rated voltage
Class B
S
With surge
AC/ Voltage
Voltage voltage
DC symbol
suppressor
1
100 V
2
200 V
3
110 V
AC
4
220 V
7
240 V
8
48 V
J
230 V
5
24 V
DC
6
12 V
L
With
light
Class H
Z
S
With light and With surge
surge voltage voltage
suppressor suppressor
L
Z
With
light
With light and
surge voltage
suppressor
DC spec. is not
available.
∗ Option “S”, “Z” are not available as surge voltage suppressor is integrated
into the AC/Class B, as a standard.
83
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Series VXZ22/23
For Water
Model/Valve Specifications
N.C.
N.O.
Passage symbol
Passage symbol
2
2
1
1
Normally Closed (N.C.)
Port size
(Nominal
size)
1/4 (8A)
3/8 (10A)
1/2 (15A)
3/4 (20A)
1 (25A)
Orifice dia.
(mmø)
10
15
20
25
Model
Min. operating
pressure
differential (MPa)
VXZ2230-02
VXZ2230-03
VXZ2240-04
VXZ2350-06
VXZ2360-10
Max. operating pressure
differential (MPa)
AC
DC
0.7
0
1.0
1.0
Flow characteristics
Av x 10-6m2 Cv converted
46
58
130
220
290
1.9
2.4
5.3
9.2
12.0
Max. system
pressure
(MPa)
Mass (g)
550
1.5
760
1300
1480
Note) Mass of grommet type. Add 10 g for conduit type, 30 g for DIN terminal type, 60 g for conduit terminal type respectively.
• Refer to “Glossary of Terms” on page 26 for details on the max. operating pressure differential and the max. system pressure.
Normally Open (N.O.)
Port size
(Nominal
size)
1/4 (8A)
3/8 (10A)
1/2 (15A)
3/4 (20A)
1 (25A)
Orifice dia.
(mmø)
10
15
20
25
Model
Min. operating
pressure
differential (MPa)
VXZ2232-02
VXZ2232-03
VXZ2242-04
VXZ2352-06
VXZ2362-10
0
Max. operating pressure
differential (MPa)
AC
DC
0.7
0.6
Flow characteristics
Av x 10-6m2 Cv converted
46
58
130
220
290
1.9
2.4
5.3
9.2
12.0
Max. system
pressure
(MPa)
Mass (g)
600
1.5
850
1370
1550
Note) Mass of grommet type. Add 10 g for conduit type, 30 g for DIN terminal type, 60 g for conduit terminal type respectively.
• Refer to “Glossary of Terms” on page 26 for details on the max. operating pressure differential and the max. system pressure.
Fluid and Ambient Temperature
Valve Leakage Rate
Internal Leakage
Power source
AC/Class B coil
AC/Class H coil
DC
Fluid temperature (°C)
Solenoid valve option symbol
E, P
Nil, G, L
1 to 60
—
—
1 to 99
1 to 60
—
Ambient
temperature
(°C)
–10 to 60
–10 to 60
–10 to 60
Seal material
NBR, FKM, EPDM
Leakage rate (Water)
0.1 cm3/min or less
External Leakage
Seal material
NBR, FKM, EPDM
Leakage rate (Water)
0.1 cm3/min or less
Note) With no freezing
84
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Zero Differential Pressure Type
Pilot Operated 2 Port Solenoid Valve
Series VXZ22/23
For Water
How to Order
VXZ 22 3 0
VXZ 22 3 0
VXZ 22 3 0
DC
AC/Class H coil
AC/Class B coil (Built-in
full-wave rectifier type)
02
02
02
5 G 1
1 G 1
1 G R1
VX2
VXD
Model
Refer to the table (1)
shown below for availability.
VXZ
Orifice diameter
Refer to the table (1) shown
below for availability.
Nil
Valve/Body configuration
0
2
Z
Thread type
Nil
Rc
NPTF
G
NPT
T
F
N
G - Grommet
GS- With grommet surge
100 VAC 50/60 Hz
200 VAC 50/60 Hz
110 VAC 50/60 Hz
220 VAC 50/60 Hz
24 VDC
6
7
8
J
∗ Refer to the table (3) shown below for availability.
VXA
surge voltage suppressor
Port no.
(Port size)
VXZ22
VXZ23
DL - DIN terminal with light
DZ - DIN terminal with
and light
TZ - With conduit
terminal, surge
voltage
suppressor and light
Orifice symbol (Diameter)
3
4
5
6
(10 mmø) (15 mmø) (20 mmø) (25 mmø)
Nil
G
E
P
L
06 (3/4)
10 (1)
NBR
EPDM
FKM
LVM
VCA
VCB
Material
Body
Seal
Brass (C37),
Stainless
steel
NBR
FKM
EPDM
VCL
VCS
02 (1/4)
03 (3/8)
04 (1/2)
Seal
material
VQ
surge voltage
suppressor and light
DO - For DIN terminal (without
connector, gasket is included.)
∗ Refer to the table (3) for the available combinations between each electrical
option (S, L, Z) and rated voltage.
∗ Surge voltage suppressor is integrated into the AC/Class B, as a standard.
Table (2) Solenoid Valve Option
Option
symbol
VDW
voltage suppressor
TL - With conduit terminal
∗ DIN type is available with class B only.
Table (1) Model/Orifice Diameter/Port Size
Normally Closed (N.C.) / Normally Open (N.O.)
Solenoid valve (Port size)
VCH
Connector
D - DIN terminal
DS - DIN terminal with surge
T - With conduit terminal
TS - With conduit terminal and
Refer to page 90 for ordering coil only.
Model
VX3
C- Conduit
voltage suppressor
12 VDC
240 VAC 50/60 Hz
48 VAC 50/60 Hz
230 VAC 50/60 Hz
VXH
VXF
Electrical entry
Rated voltage
1
2
3
4
5
Built-in full-wave
rectifier type
Refer to the table (1)
shown below for availability.
Select nil because the
solenoid valve option “L”
is the oil-free treatment.
VXP
VXR
Port size
—
Oil-free spec.
None
With bracket
∗ Bracket is not removable.
Refer to the table (2)
shown below for availability.
Suffix
Nil
B
Solenoid valve option
N.C. / Single unit
N.O. / Single unit
VXE
Bracket
Body/Shading
coil material∗
Brass (C37)/—
Stainless steel/—
Brass (C37)/Cu
Stainless steel/Ag
Stainless steel/—
VCW
Table (3) Rated Voltage – Electrical Option
Coil
insulation
type
Note
B
—
H
Heated water
(AC only)
B
High corrosive, Oil-free
∗ There is no shading coil attached to the AC/Class B coil and DC spec.
Rated voltage
Class B
S
surge
AC/ Voltage Voltage With
voltage
DC symbol
suppressor
1
100 V
2
200 V
3
110 V
AC
4
220 V
7
240 V
8
48 V
J
230 V
5
24 V
DC
6
12 V
L
With
light
Class H
Z
S
With light and With surge
surge voltage voltage
suppressor suppressor
L
Z
With
light
With light and
surge voltage
suppressor
DC spec. is not
available.
∗ Option “S”, “Z” are not available as surge voltage suppressor is integrated
into the AC/Class B, as a standard.
∗ Class B and H coils cannot be interchanged in order to exchange the coils.
∗ AC/Class B (with built-in full wave rectifier type) can be interchanged with DC.
85
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Series VXZ22/23
When the fluid is oil.
The dynamic viscosity of the fluid must not exceed 50
mm2/s.
The special construction of the armature adopted in the
built-in full-wave rectifier type gives an improvement in OFF
response by providing clearance on the absorbed surface
when it is switched ON.
Select the DC spec. or AC spec. built-in full-wave rectifier
type when the dynamic viscosity is higher than water or
when the OFF response is prioritized.
For Oil
Model/Valve Specifications
N.C.
N.O.
Passage symbol
Passage symbol
2
2
1
1
Normally Closed (N.C.)
Port size
(Nominal
size)
1/4 (8A)
3/8 (10A)
1/2 (15A)
3/4 (20A)
1 (25A)
Orifice dia.
(mmø)
Min. operating
pressure
differential (MPa)
Model
VXZ2230-02
VXZ2230-03
VXZ2240-04
VXZ2350-06
VXZ2360-10
10
15
20
25
Max. operating pressure
differential (MPa)
AC
DC
0.7
0
Flow characteristics
Av x 10-6m2
46
58
130
220
290
Cv converted
1.9
2.4
5.3
9.2
12.0
Max. system
pressure
(MPa)
Mass (g)
550
1.5
760
1300
1480
Note) Mass of grommet type. Add 10 g for conduit type, 30 g for DIN terminal type, 60 g for conduit terminal type respectively.
• Refer to “Glossary of Terms” on page 26 for details on the max. operating pressure differential and the max. system pressure.
Normally Open (N.O.)
Port size
(Nominal
size)
1/4 (8A)
3/8 (10A)
1/2 (15A)
3/4 (20A)
1 (25A)
Orifice dia.
(mmø)
Min. operating
pressure
differential (MPa)
Model
VXZ2232-02
VXZ2232-03
VXZ2242-04
VXZ2352-06
VXZ2362-10
10
15
20
25
0
Max. operating pressure
differential (MPa)
AC
DC
0.7
0.6
Flow characteristics
Av x 10-6m2
46
58
130
220
290
Cv converted
1.9
2.4
5.3
9.2
12.0
Max. system
pressure
(MPa)
Mass (g)
600
1.5
850
1370
1550
Note) Mass of grommet type. Add 10 g for conduit type, 30 g for DIN terminal type, 60 g for conduit terminal type respectively.
• Refer to “Glossary of Terms” on page 26 for details on the max. operating pressure differential and the max. system pressure.
Fluid and Ambient Temperature
Valve Leakage Rate
Internal Leakage
Power source
AC/Class B coil
AC/Class H coil
DC
Fluid temperature (°C)
Solenoid valve option symbol
A, H
D, N
Ambient
temperature
(°C)
–5 to 60
—
–5 to 60
—
–5 to 100
—
–10 to 60
–10 to 60
–10 to 60
Seal material
FKM
Leakage rate (Oil)
0.1 cm3/min or less
External Leakage
Seal material
FKM
Leakage rate (Oil)
0.1 cm3/min or less
Note) Dynamic viscosity: 50 mm2/s or less
86
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Zero Differential Pressure Type
Pilot Operated 2 Port Solenoid Valve
Series VXZ22/23
For Oil
How to Order
DC
AC/Class H coil
AC/Class B coil (Built-in
full-wave rectifier type)
VXZ 22 3 0
VXZ 22 3 0
VXZ 22 3 0
02
02
02
5 G 1
1 G 1
1 G R1
VX2
VXD
Model
Refer to the table (1)
shown below for availability.
Refer to the table (1) shown
below for availability.
Thread type
T
F
N
Rc
NPTF
G
NPT
Rated voltage
1
2
3
4
5
100 VAC 50/60 Hz
200 VAC 50/60 Hz
110 VAC 50/60 Hz
220 VAC 50/60 Hz
24 VDC
6
7
8
J
12 VDC
240 VAC 50/60 Hz
48 VAC 50/60 Hz
230 VAC 50/60 Hz
∗ Refer to the table (3) shown below for availability.
Refer to page 90 for ordering coil only.
Table (1) Model/Orifice Diameter/Port Size
Normally Closed (N.C.) / Normally Open (N.O.)
Orifice symbol (Diameter)
Solenoid valve (Port size)
Model
Port no.
(Port size)
VXZ22
VXZ23
3
4
5
6
(10 mmø) (15 mmø) (20 mmø) (25 mmø)
A
H
D
N
FKM
G - Grommet
GS- With grommet surge
VXA
Connector
D - DIN terminal
DS - DIN terminal with surge
T - With conduit terminal
TS - With conduit terminal and
surge voltage suppressor
VCH
VDW
voltage suppressor
TL - With conduit terminal
DL - DIN terminal with
and light
TZ - With conduit
terminal, surge
voltage
suppressor and light
light
DZ - DIN terminal with
surge voltage
suppressor and light
DO -For DIN terminal (without
connector, gasket is included.)
∗ DIN type is available with class B only.
∗ Refer to the table (3) for the available combinations between each electrical
option (S, L, Z) and rated voltage.
∗ Surge voltage suppressor is integrated into the AC/Class B, as a standard.
Material
Body
VXF
VX3
C- Conduit
voltage suppressor
Brass (C37),
Stainless
steel
06 (3/4)
10 (1)
Seal
material
Electrical entry
VXH
VQ
LVM
VCA
VCB
VCL
Seal
VCS
02 (1/4)
03 (3/8)
04 (1/2)
Table (2) Solenoid Valve Option
Option
symbol
Built-in full-wave
rectifier type
Refer to the table (1)
shown below for availability.
Nil
VXP
VXR
Port size
—
Oil-free spec.
Z
∗ Bracket is not removable.
Refer to the table (2)
shown below for availability.
Suffix
Nil
None
With bracket
B
Solenoid valve option
N.C. / Single unit
N.O. / Single unit
VXE
Bracket
Nil
Valve/Body configuration
0
2
VXZ
Orifice diameter
Body/Shading
coil material∗
Brass (C37)/—
Stainless steel/—
Brass (C37)/Cu
Stainless steel/Ag
VCW
FKM
Table (3) Rated Voltage – Electrical Option
Coil
insulation
type
B
H
∗ There is no shading coil attached to the AC/Class B coil and DC spec.
Rated voltage
Class B
S
surge
AC/ Voltage Voltage With
voltage
DC symbol
suppressor
1
100 V
2
200 V
3
110 V
AC
4
220 V
7
240 V
8
48 V
J
230 V
5
24 V
DC
6
12 V
L
With
light
Class H
Z
S
With light and With surge
voltage
surge voltage
suppressor suppressor
L
Z
With
light
With light and
surge voltage
suppressor
DC spec. is not
available.
∗ Option “S”, “Z” are not available as surge voltage suppressor is integrated
into the AC/Class B, as a standard.
∗ Class B and H coils cannot be interchanged in order to exchange the coils.
∗ AC/Class B (with built-in full wave rectifier type) can be interchanged with DC.
87
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Series VXZ22/23
For Air, Water, Oil
Construction
Normally closed (N.C.)
Body material: Brass (C37), Stainless steel
Normally open (N.O.)
Body material: Brass (C37), Stainless steel
!5
!4
!3
!2
!3
o
u
i
i
u
o
!1
y
y
t
!2
t
r
r
!1
!0
!0
w
w
q
IN
OUT
q
IN
OUT
e
e
Working principles
Working principles
<Valve opened – when there is pressure>
When the coil o is energized, the armature assembly u is attacted into
the core of the tube assembly i and the pilot valve
is opened.
When the pilot valve is opened and the pressure inside the pilot chamber
decreases, resulting in the pressure difference from the inlet pressure. Then the diaphragm assembly e is lifted and the main valve
is
opened.
<Valve opened – when there is no pressure or under low minute pressure>
The armature assembly u and the diaphragm assembly e are connected with each other with the lift spring !0. When the armature assembly
is attracted, the diaphragm assembly is pulled up and the main valve
is opened.
<Valve closed>
When the coil o is de-energized, the armature assembly u returns by
the reacting force of the return spring r and the pilot valve
is closed.
When the pilot valve is closed, the pressure inside the pilot chamber
increases, resulting that the pressure difference from the inlet pressure
is lost and the main valve
is closed.
<Valve closed>
When the coil o is energized, the armature attacted by the core of the
tube assembly i closes the pilot valve
via the push rod assembly !1.
When the pilot valve is closed, the pressure inside the pilot chamber
increases, resulting in the pressure difference from the inlet pressure is
lost and the main valve
is closed.
<Valve opened – when there is pressure>
The coil o is de-energized, the armature returns by the reacting force of
the return spring r via the push rod assembly !1 and the pilot valve
is opened.
When the pilot valve is opened, the pressure inside the chamber
decreases, resulting in the pressure difference from the inlet pressure.
Then the diaphragm assembly e is lifted and the main valve
is
opened.
<Valve opened – when there is no pressure or under low minute pressure>
The push rod assembly !1 and the diaphragm assembly e are connected with each other with the lift spring !0. When the push rod assembly
returns, the diaphragm assembly is pulled up and the main valve
is
opened.
Component Parts
Component Parts
Material
Description
No.
Material
Body material brass (C37) Body material stainless
specification
steel specification
Description
No.
Body material brass (C37) Body material stainless
specification
steel specification
1
Body
Brass (C37)
Stainless steel
1
Body
Brass (C37)
Stainless steel
2
Bonnet
Brass (C37)
Stainless steel
2
Bonnet
Brass (C37)
Stainless steel
3
Diaphragm assembly
Stainless steel (NBR, FKM, EPDM)
3
Diaphragm assembly
4
Return spring
Stainless steel
4
Return spring
5
O-ring
(NBR, FKM, EPDM)
5
O-ring
6
Nut
6
Nut
7
Armature assembly
7
Armature assembly
8
Tube assembly Note)
8
Tube assembly Note)
9
Solenoid coil
—
9
Solenoid coil
10
Lift spring
Stainless steel
10
Lift spring
11
Hexagon socket bolt
Stainless steel
11
Push rod assembly
12
Name plate
Aluminum
12
Valve assembly
13
Clip
SK
13
Name plate
Stainless steel
14
Cover
Stainless steel
15
Clip
Stainless steel
Brass (C37)
Brass (C37), Ni plated
Stainless steel
Stainless steel, Cu
Stainless steel, Ag
The materials in parentheses are the seal materials.
Note) Cu and Ag are inapplicable to the DC spec and to the AC spec with built-in fullwave rectifier.
Stainless steel (NBR, FKM, EPDM)
Stainless steel
NBR
FKM, EPDM
Brass (C37)
Brass (C37), Ni plated
Stainless steel
Stainless steel, Cu
Stainless steel, Ag
—
Stainless steel
PPS, Stainless steel, NBR Stainless steel, FKM, EPDM
Aluminum
88
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Zero Differential Pressure Type
Pilot Operated 2 Port Solenoid Valve
Series VXZ22/23
For Air, Water, Oil
Dimensions/Body Material: Brass (C37), Stainless Steel
Normally closed (N.C.): VXZ220/VXZ230
Normally open (N.O.): VXZ222/VXZ232
Grommet: G
Conduit: C
Bracket
C
M
Approx. 300
Approx. 280
E
VX2
M
Bracket
VXD
VXZ
e
a
L
d
g
L
A
VXE
VXP
f
h
IN
IN
OUT
VXR
B
OUT
F
J
H
VXH
(D)
K
VXF
b
i
2xP
Port size
VX3
VXA
DIN terminal: D
VCH
Conduit terminal: T
VDW
M
N
VQ
M
Bracket
LVM
32
Bracket
25
L
G1/2
IN
VCB
VCL
G1/2
L
31.5
44
VCA
IN
OUT
VCS
OUT
VCW
Cable
ø6 to ø12
N
(mm)
Model
N.C.
Port size
N.O.
VXZ2230
VXZ2240
VXZ2350
VXZ2360
A
P
B
C
D
E
F
H
J
K
11
14
18
21
35
35
40
40
50
63
80
90
22.5
22.5
25
25
30
37
47.5
55
20
26
32.5
35
22
29.5
36
40.5
Grommet
L
VXZ2232 1/4, 3/8 89(97)
97(104.5)
1/2
VXZ2242
111(119)
3/4
VXZ2352
118.5(125.5)
1
VXZ2362
Electrical entry (DC, AC/Class H coil)
Conduit
DIN terminal
Conduit terminal
M
81(83)
40
52 89.5(90.5)
65 103(103)
70 110.5(110.5)
L
M
22.5 73.5(75.5)
22.5
81(83)
25.5
96(96)
25.5 105.5(105.5)
L
M
43
73(75)
43 80.5(82.5)
46
95(95)
46 106.5(106.5)
N
L
49.5 73.5(75.5)
49.5
81(83)
52
96(96)
52 105.5(105.5)
61.5
61.5
64
64
M
N
95
95
98
98
64
64
66.5
66.5
( ) denotes the value for N.O.
Model
N.C.
VXZ2230
VXZ2240
VXZ2350
VXZ2360
Port size
N.O.
P
VXZ2232 1/4, 3/8
1/2
VXZ2242
3/4
VXZ2352
1
VXZ2362
a
b
d
e
52 67 14 1.6
60 75 17 2.3
68 87 22 2.6
73 92 22 2.6
∗ Coil with built-in full-wave rectifier (electrical option “R”)
( ) denotes the value for N.O.
f
g
h
i
Grommet
L
26
33
40
45.5
5.5
6.5
6.5
6.5
7.5
8.5
9
9
M
Electrical entry (AC/Class B coil)∗
Conduit
DIN terminal
L
M
L
M
72(74) 51.5 73(75) 68.5
33
77(79)
28
80(80) 51.5 81(81) 68.5
35 84.5(84.5) 33
43 99.5(99.5) 36 94.5(94.5) 54 95.5(95.5) 71
45 107(107) 36 102(102) 54 103(103) 71
N
(mm)
Conduit terminal
L
M
56.5 72(74) 103.5
56.5 80(80) 103.5
59 94.5(94.5) 106
59 102(102) 106
N
72.5
72.5
75
75
89
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Series VXZ22/23
For Air, Water, Oil
Replacement Parts
Solenoid
DC
coil assembly part no.
AC/Class B coil (Built-in full-wave rectifier)
VX02 2 N
VX02 2 N
5 G
2
3
VXZ22
VXZ23
Rated voltage Note)
5
6
Valve
Series
Series
2
3
1 GR
24 VDC
12 VDC
Note) Refer to the table (1) for the
available combinations.
VXZ22
VXZ23
Symbol Valve
Nil
N.C.
2
N.O.
Rated voltage Note)
1
2
3
4
7
8
J
Valve
Symbol Valve
Nil
N.C.
2
N.O.
100 VAC
200 VAC
110 VAC
220 VAC
240 VAC
48 VAC
230 VAC
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
Note) Refer to the table (1) for the available combinations.
Electrical entry
Electrical entry
G - Grommet
GS- With grommet surge
C- Conduit
G- Grommet
C- Conduit
Connector
D - DIN terminal
DS - DIN terminal with surge
T - With conduit terminal
TL - With conduit terminal
Connector
D - DIN terminal
DL - DIN terminal with light
DO - For DIN terminal
voltage suppressor
T - With conduit terminal
TS - With conduit terminal and
surge voltage suppressor
TL - With conduit
terminal and light
TZ - With conduit
terminal, surge
voltage suppressor
and light
voltage suppressor
and light
DL - DIN terminal with light
DZ - DIN terminal with
surge voltage
suppressor and light
DO - For DIN terminal
(without connector)
(without connector,
gasket is included.)
∗ Refer to the table (1) for the available combinations between each electrical
option and rated voltage.
∗ Refer to the table (1) for the available combinations between each electrical
option and rated voltage.
∗ The rectifier and the surge voltage suppressor are integrated as a standard.
AC/Class H coil (DIN terminal is not available.)
DIN
VX02 2 N
1 G H Z
VXZ22
VXZ23
Electrical option
L
100 VAC
200 VAC
110 VAC
220 VAC
240 VAC
48 VAC
230 VAC
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
Gasket
1
2
5
6
15
100 VAC, 110 VAC
200 VAC, 220 VAC, 230 VAC, 240 VAC
24 VDC
12 VDC
48 VAC
part no. for DIN connector
VCW20-1-29-1
Note) Refer to the table (1) for the
available combinations.
G - Grommet
GS- With grommet surge
Rated voltage
With light
∗ Refer to the table (1) for
the available combinations between each
electrical option (S, L, Z)
and rated voltage.
Rated voltage Note)
1
2
3
4
7
8
J
GDM2A
GDM2A
Without electrical option
With electrical option
Series
2
3
connector part no.
Table (1) Rated Voltage – Electrical Option
Electrical entry
C- Conduit
voltage suppressor
T - With conduit terminal
TS - With conduit terminal and
surge voltage suppressor
TL - With conduit
terminal and light
TZ - With conduit
terminal, surge
voltage suppressor
and light
∗ Refer to the table (1) for the available combinations between each electrical
option and rated voltage.
Rated voltage
Class B
S
surge
AC/ Voltage Voltage With
voltage
DC symbol
suppressor
1
100 V
2
200 V
3
110 V
AC
4
220 V
7
240 V
8
48 V
J
230 V
5
24 V
DC
6
12 V
L
With
light
Class H
Z
S
With light and With surge
voltage
surge voltage
suppressor suppressor
L
Z
With
light
With light and
surge voltage
suppressor
DC spec. is not
available.
∗ Option “S”, “Z” are not available as surge voltage suppressor is integrated into the
AC/Class B, as a standard.
∗ Replacement of solenoid coils:
• DC and AC coils cannot be interchanged in order to change the voltage.
• DC and AC (built-in full-wave rectifier type) coils can be interchanged in order to
change the voltage.
• All DC coil voltages are interchangeable.
• All AC coil voltages are interchangeable.
90
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Zero Differential Pressure Type
Pilot Operated 2 Port Solenoid Valve
Series VXZ22/23
For Air, Water, Oil
Name
plate part no.
AZ-T-
Clip
Valve model
Enter by referring to
“How to Order”
(Single Unit).
Clip
part no. (For N.C.)
Name plate
VX2
Solenoid coil assembly
For VXZ22: VX022N-10
VXD
For VXZ23: VX023N-10
VXZ
Clip
VXE
part no. (For N.O.)
For VXZ22: ETW-8
VXP
For VXZ23: ETW-9
VXR
VXH
VXF
VX3
VXA
VCH
VDW
VQ
LVM
VCA
VCB
VCL
VCS
VCW
91