Instruction Sheet 716-504 [English, 2 MB, 11/29/1993]
![Instruction Sheet 716-504 [English, 2 MB, 11/29/1993] Instruction Sheet 716-504 [English, 2 MB, 11/29/1993]](http://s1.manualzz.com/store/data/013413334_1-f336a42bb7490dea426ba668e9d57388-768x994.png)
S&C Series 2000 Circuit-Switchers
Model
2020
-
Outdoor Transmission
I
and Side-Break Power-Operated
Disconnect, 69 kv through
138 kv
INSTRUCTIONS
For Field Assembly and Installation
1
TABLE
OF
CONTENTS
I
Section
INTRODUCTION
Page Number Section Page Number
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 INSTALLATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.6
BEFORE STARTING INSTALLATION
. . . . . . . . . . . . . . . .
OPERATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.19
1
INTRODUCTION
I
0
Trip and close pushbuttons located inside operator enclosure.
The equipment covered by this publication must be selected for a specific application and it must be installed, operated, and maintained persons who by qualified are thoroughly trained and who understand any hazards that may be involved. This publication is written only for such qualified persons and is not intended to be a substitute for adequate training and experience in safety procedures for this type of equipment.
Manual trip lever, for tripping interrupters
in
the
0
Manual charging handle,
for
opening disconnect after interrupters have been manually tripped open-in the event control voltage has been lost.
0
Charged and discharged indicators for stored-energy mechanism.
Non-reset electric operation counter.
General
The following instructions are for field assembly (erec- tion) and installation of S&C Series 2000 Circuit-
Switchers Model 2020-With Vertical Interrupters and
Side-Break Power-Operated Disconnect, rated 69 kv through
138
Interrupters
Series 2000 Circuit-Switchers employ single-gap SF6 puffer-type interrupters designed to close the circuit in 6 cycles, interrupt the circuit in 6 cycles, and maintain rated dielectric strength when open. These dual-function interrupters are factory-fied to full pressure under controlled conditions and then perma- nently sealed. Field fiuing is neither necessary nor possible, thus eliminating the risk of contaminating the interrupting medium.
Operator
kv.
See Figure
1.
The interrupters are driven by
a
single, stored-energy mechanism located
at
ground level in
a
48-volt dc,
125-volt dc, or 115-volt 60-hertz operator furnished with the Circuit-Switcher. Refer to the “STANDARD
FEATURES”
table on page and also Figures 18 and 20.
This operator includes the following features:
0
Eight nonadjustable single-pole double-throw auxiliary-switch contacts which interrupters. follow t h e
0
Weatherproof, dustproof enclosure.
0
Decoupling mechanism which allows decoupling and locking of disconnect-blade power train in open position, permitting operational checkout of inter- rupters, stored-energy mechanism, and relaying equipment without closing the high-voltage circuit.
0
Two
individually adjustable auxiliary-switch contacts which follow the disconnect-blade power train and operator when coupled, operator only when decoupled. trip-free capability should the Series 2000 Circuit-
Switcher be inadvertently closed into
a
fault sensed by user-furnished relaying, the mechanism w trip immediately. To accomplish trip-free operation, the mechanism
utiljzes two
spring assemblies: one for closing, one for opening. Both springs are charged by the operator motor before the Series 2000 Circuit-
Switcher can be closed. Recharging time after
a
trip operation is approximately
5
seconds.
Supersedes lnstructlon Sheet 716-504 dated 11-29-93 @1994
S&C ELECTRIC COMPANY Chicago Page
S&C ELECTRIC CANADA LTD. Toronto
INSTRUCTION SHEET
7
16-504
1 of
23
November
29, 1993
SCLC Series 2000 Circuit-Switchers
Model
2020
Outdoor Transmission
I
and Side-Break Power-Operated
Disconnect, 69 kv through 138 kv
llNTRODUCTlON
-
I
Power Train
The operator directly drives the interrupters open and cloe&d through
a
simple, high-speed power train leading from the top of the operator, through
a
horizontal interphase linkage enclosed in a steel-sheathed box- type base, to reciprocating-action insulated operating rods which pass through the center support columns. of insulating
The operator also drives the disconnect open and closed through
a
low-speed power train which rotates the insulating support columns. The disconnect is capable of opening and closingwithout hesitation under
%-inch ice formation.
A
decoupling mechanism allows decoupling and locking of the disconnect-blade power train in the open position, permitting operational checkout of the interrupters, the stored-energy
TURES''
table on page 3. Anchor bolts are furnished when specified separately.
Usual Operating
Conditions
Series
2000
Circuit-Switchers w perform
as
intended at temperatures within the range of -40°C to +40"C,
at
altitudes of up to
5000
feet, and at wind loadings
80
miles per hour. Further,
Switchers, when installed with the recommended S&C anchor bolts and with flexible-conductor connections at all
six
terminal pads, are capable of withstanding seismic loading of 0.2
g
ground acceleration in any direction,
as as
performing
as
intended during such loading and afterward. For applications
at
tempera- at higher wind loadings,
at
higher altitudes,
or
where higher seismic withstand capabilities are required, refer to the nearest
S&C Sales Office. the high-voltage circuit.
Permanently lubricated bearings are used through- out both the high-speed and low-speed power trains.
The insulating support lubricated columns are filled with
a dielectric
filler which prevents contamina- tion from affecting the dielectric integrity
of
the column or the insulated operating rod. An aerator is utilized at the upper end of each insulating support column to eliminate water being pumped-in due to pressure differentials caused by temperature cycling.
Inspection
Schedule and
Procedures
To assure Series 2000 Circuit-Switcher's continued proper performance, it should be inspected in accord- ance with
S&Cs
recommended schedule and proce- dures contained in S&C Instruction Sheet 716-590.
Catalog Number
Description
The following table lists the basic catalog numbers and ratings of Model 2020 Series 2000 Circuit-Switchers.
Mounting
Pedestals
Series
2000
Circuit-Switchers are furnished with mounting pedestals. Refer to the
"STANDARD FEA-
furnished are stamped on the nameplate located on the door of the operator.
MODEL 2020-With Vertical Interrupters and Side-Break Power-Operated Disconnect
Rating
Kv Amperes, Rms
Nom. Max BIL
Cont.
I
69
I
,
72.5
I
350
I
1200
I
64
Mom.
000
Short Time
1-Sec.
40 000
Fault-Closing,
Duty-Cycle,
40 000
121
115 40 000 40 000
Phase
Spacing,
Inches
138 650 145 1200
0
The one-time duty-cycle fault-closing rms asymmetrical is 1.6 times the symmetrical
64,000 amperes). value listed (or
40 000 40 000
Circuii-
Switcher
Catalog
Number
397436
397736 a4 397738
102 397838 a4 397739
102 397839
7 1
INSTRUCTION SHEET
Page 2 of 23
November 29, 1993
S&C ELECTRIC COMPANY Chicago
S&C ELECTRIC CANADA LTD. Toronto
1
INTRODUCTION
-
Suffues to the basic catalog number specify operator pedestal height, control voltage, space-heater voltage, and mounting standard features table:
STANDARD FEATURES
Feature
Item
Operator Control Voltage
Mounting Pedestal Height
125 v dc
115v60hz
120 Inch inch
216
inch
240
Inch v
60
240 v
60
Operator Space-Heater Voltage
I
(Anchor bolts are specified separately.)
The basic catalog number may
also be suffixed
to
with
the following table: specify one
or
more optional features, in accordance
’
Suffix
Added
to Circuit-switcher
Catalog Number Descrfption
-A
-B
-D
-E8
-E10
-E12 144
-HZ
I
in accordance with the following
OPTIONAL FEATURES
Item
Grounding Switch, manual, three-pole, group-operated,
64,000
for current transfer at hmge end of grounding-switch blades; blades parallel to pole-unlt bases when in open position. Grounds jaw-contact terminal pads
Deletion of Trip and Close Pushbuttons located inside operator enclosure
Space Heater Thermostat for operator
Key Interlock located inslde operator enclosure. Key may be removed when interrupters are tripped-thereby
I
Suffix
Added to
Circuit-Switcher
-G2
-J
-K
-L1
Key
Interlock mounted on grounding-switch manual operating handle. Works in conjunction with Key interlock
Option Suffix “-L1” to guard against operatmg grounding switch with disconnect blades closed or with interrupt- ers closed
Position-lndicatlng Lamps (one red, one green) located inslde operator enclosure. Lamps are wired in series
-L4
”
I
-T
Includes one normally open and one normally closed contact suitable for use with remotely located indicating lamps or alarms
Duplex Receptacle with Ground-Fault Circult Interrupter and Convenlence-Light Lampholder with Switch located Inside operator enclosure
Elght Additional Nonadjustable Slngle-Pole Double-Throw Auxillary-Swltch Contacts in Operator which follow the Interrupters
Local-Remote Selector Switch. Prevents remote operation of operator when selector switch is placed in ”local”
I mode as, for example, during inspection
I
-V
-wl
-v
- I
I
S&C ELECTRIC COMPANY Chicago
S&C ELECTRIC CANADA LTD. Toronto
INSTRUCTION SHEET
Page 3 of
23
November
29, 1993
S&C Series 2000 Circuit-Switchers
Model
2020
Outdoor Transmission
I
and Side-Break Power-Operated
Disconnect, 69 kv through 138 kv
I
-
Pressure-relief device and low-gas-pressure indicator
Single-gap SF6 puffer-type interrupter
I support plate
Figure 1. Model 2020 Series 2000 Circuit-Switcher fated 138
kv.
7
1
INSTRUCTION
SHEET
Page
4 of 23
November
29, 1993
S&C
ELECTRIC
COMPANY
Chicago
S&C
ELECTRIC CANADA LTD. Toronto
I
BEFORE
STARTING INSTALLATION
Checking the Shipment
An S&C
catalog drawing will be found in a water- resistant envelope attached to the wirebound-wood
Study this drawing carefully and check the bill
of
at
hand.
The Model 2020 Series 2000 Circuit-Switcher shipment should include the following items,
as
shown
in
Figures
2
and
5:
1.
Three pole-units, each consisting of
an
insulating support column, support insulator, integral discon- nect, and channel base-all factory-assembled and adjusted.
2. A
single cross base, enclosing the high-speed inter- phase power train which drives the interrupters.
3.
Three interrupters (directly attached
to
the
cross
base for shipping purposes).
4. The appropriate number of mounting pedestals, pedestal
A
single
is
used for Circuit-Switchers rated
69
kv
(with 48-inch phase spacing); a set of
two
pedestals is used for Circuit-Switchers rated
69
kv (with
@-inch phase spacing),
115 kv,
and
138 kv.
5. A
Series 2000 Circuit-Switcher Operator.
6. A
low-speed interphase power train which drives the disconnect blades.
7. A
container of miscellaneous operating-mechanism components and hardware-all individually identified.
8. Any optional features specified, such
as
a grounding switch.
Gias-Pressure Indicator
Series
2000
Circuit-Switchers have sealed interrupters containing
gas
under pressure.
Loss
of gas pressure may result in improper interrupting action. Low gas pressure is signaled by a red target in the gas-pressure indicator
at
the terminal end of the interrupter.
DO NOT INTERMIX COMPONENTS FROM
Series
DIFFERENT INSTALCATIONS
2000
Circuit-Switchers are completely factory-assembled and thoroughly tested.
To
speed
Circuit-Switcher and its operator, it is imperative that components belonging
to a
specific Circuit-
Switcher installation
not be
intermixed with components belonging to
a
different installation.
For this reason, each Series 2000 Circuit-Switcher is serially numbered.
This
serial number appears on the individual pole-units, the cross base, the mounting pedestals, and the operator.
It is further important that components from different installations not be intermixed in that S&C
maintains an
historical record-by serial number- of every circuit-Switcher produced.
This
lists
information pertinent to each installation, such
as
application, date of shipment, and any service performed by S&C factory service specialists.
This
record is invaluable when questions arise relative
to
modifications or replacements.
Please complde and
m a i l
the Circuit-Switcher registration card
{enclosed in a vinyl envelope
located inside the operator) a m
the
Circuit-
Switcher has been installed. The information
requested on
this
card
is
vital to
ensure prompt notifkation i n
the
event fkld nwdifiatitms are needed.
S&C ELECTRIC
S&C ELECTRIC
CANADA LTD.
COMPANY Chicago Page
Toronto
INSTRUCTION SHEET
7
1
5 of
23
November 29, 1993
SBC Series 2000 Circuit-Switchers
Model
2020
-
Outdoor Transmission
I
and Side-Break Power-Operated
Disconnect, 69 kv through
138
kv
1
INSTALLATION
Do
not remove the containers from the interrupters,
or the wirebound-wood
wrappers
from the insu- lating support columns, until the installation has been completed.
BOLTED
AND
PINNED CONNECTIONS
A
typical bolted connection for field assembly requires
a flat
washer under the cap screw and hex nuts are specified, it is essential that the threads of the associated cap screws be lubricated with
a
general-purpose grease, to facilitate tightening.
All
pins used in the field assembly should also be lubricated to facilitate insertion.
step 1
Cut the steel straps which bind the mounting pedestals and support arms to the cross base and the straps which bind the container of miscellaneous operating- mechanism components and hardware.
Also
remove the wood bracing between the pole-unit terminal pads.
See Figure
2.
step
2
Install the mounting pedestals. See Figure
3.
Make certain that the grounding
pad
on each mounting pedestal is properly positioned for this particular installation.
Adjust the lower set
of
anchor-bolt nuts at each
The
upper set of anchor-bolt nuts should
be
only loosely attached
at
this time.
Pole-unit
Figure 2. Typical shipment of Model 2020 Series
2000
Circuit-Switcher. Operator is skid; see Figure 5.
7
1
INSTRUCTION
SHEET
Page 6 of 23
November
29, 1993
S&C ELECTRIC COMPANY
S&C ELECTRIC CANADA LTD.
Chicago
Toronto
1 INSTALLATION - Continued
step 3
Attach the support arms to the mounting pedestals as shown on the catalog drawing using W-11 X 1W hex-head galvanized steel cap screws and flat washers furnished. Torque the cap screws to 160 foot-pounds.
Also attach the covers to the tops of the mounting pedestals as shown on the catalog drawing using
W-13 X 2” hex-head galvanized steel cap screws, flat washers, and self-locking hex nuts furnished.A Securely tighten the cap screws.
step 4
Attach the lifting angles to the cross base using
M”-13 X 1%” hex-head galvanized steel cap screws furnished. See Figure 4. Securely tighten the cap screws.
Then attach four suitable lifting slings to the lifting angles. Unbolt the base from the shipping skids and lift the base-with interrupters attached-atop the support arm gussets,* as shown on the catalog drawing.
Avoid sudden starts and stops. Verify that the switchposition indicator on the base is visible on the desired side (this is also the side on which the operator door will open).
A Not applicable to 69.kv Circuit-Switchers with 48.inch phase spacing.
* On 69-kv Circuit-Switchers with 48-inch phase spacing, support arm gussets are not used; the cross base is attached atop the mounting pedestal using %“-11 X 2W hex-head gahranized steel cap screws, flat washers, and self-lockiug hex nuts.
I
Two nuts and two flat washers
Figure 3. Pedestal mounting detail.
Interrupter lifting bracket
Protective cover at le-unit mounting position. See Step
Interrupter shipping bracket and clamps
Figure 4. Hoisting the cross base.
1 Lifting angle A
‘3
S&C ELECTRIC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto
INSTRUCTION SHEET
7 l&504
Page.7 of 23
November 29, 1993
S&C Series 2000 Circuit-Switchers
Outdoor Transmission
I
Model 2020 - With Vertical Interrupters and Side-Break Power-Operated
Disconnect, 69 kv through 138 kv
1 INSTALLATION - Continued
Loose&
bolt
step 5
the cross base to the support arms* using the W’-13 X 2” hex-head galvanized steel cap screws, flat washers, and self-locking hex nuts furnished.
Then-using a level-verity that the cross base is horizontal, both lengthwise and side-to-side; adjust the lower set of anchor-bolt nuts at the pedestals to achieve this condition. If necessary, loosen the W-11 X 1W’ hex-head galvanized steel cap screws which attach the support arms to the mounting pedestals, reposition the support arms, and retighten the cap screws.
Securely
bolt
Step 6
the cross base to the support arms. Shims are furnished and should be installed as necessary between the cross base and the support arms, to compensate for any irregularities greater than ‘/s inch between the mating surfaces.
ste!p 7
Refer to the catalog drawing and attach the support brace to the support arms, using the spacers,
W”-13 X 2” hex-head galvanized steel cap screws, flat washers, and self-locking hex nuts furnished. Securely tighten the associated cap screws.
step 8
Check the lower set of anchor-bolt nuts at each mounting pedestal to verify that all nuts are in contact with the bottom of the pedestal. Hand-tighten these anchor-bolt nuts as necessary. Then securely tighten the upper set of anchor-bolt nuts at each mounting pedestal.
* On 69-kv Circuit-Switchers with 48.inch phase spacing, support arm gussets are not used; the cross base is attached atop the mounting pedestal using W-11 X 2%” hex-head gahranized steel cap screws, flat washers, and self-locking hex nuts.
I
4
I
Stored-energy housing
I
Figure 5. Raising operator upon base skid.
7
1
e-504
INSTRUCTION SHEET
Page 8 of 23
November 29, 1993
S&C ELECTRIC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Tomnto
INSTALLATION - Continued
Step 9
Loosen the %“-13 X 1%” galvanized steel cap screws, flat washers, and nuts which are used to attach the bottom plates and lifting angles to the underside of
the
cross base. Remove the plates and place them and their hardware aside on a clean surface. Discard the lifting angles.
Also remove the ?&inch stainless-steel pm and cotter pin from the interphase drive lever enclosed in the cross base. See Figure 12. Retain these pins for re-use in
Step 21.
step 10
Wrap a lifting sling around the stored-energy housing of the operator, as shown in Figure 5 (left). Now carefully raise the operator to the upright position so that it rests on its base skid, as shown in Figure 5 (right).
Donot?-emDue
the lifling sling around the stored-energy housing, as the operator is top-heavy and must be adequately supported until it is attached to the Circuit-
Stitcher. Remove the skid and bracing which runs the length of the operator, stored-energy housing, and operator support tube. Also remove the protective cover atop the operator support tube, as well as
the
protective covers on the operator enclosure louvers.
I
step 11
Reposition the lifting sling around the front of the stored-energy housing and wrap another lifting sling around the back of the stored-energy housing, as shown in Figure 6. Make certain that the operator door faces the same way as the switch-position indicator on the cross base. Then carefully hoist the operator into place.
Be cart&l not to damage the uni-ball coupling on the operator connecting link during hoisting and attachment of the
operator. Attach the operator support tube mounting plate to the underside of the cross base using four Y/--13X 1%” hex-head galvanized steel cap screws, flat washers, and self-locking hex nuts. Tighten all four screws securely.
Holes for W--13X 1%” hex-head galvanized steel cap screws, flat washers, and self-locking nuts
Operator support tube
/
Uni-ball coupling
’ Operator support tube mounting plate
‘Stored-energy housing
Figure 8. Hoisting operator into position.
a S&c ELECTRIC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto
INSTRUCTION SHEET
7 161504
Pageg of 23
November 29, 1993
S&C Series 2000 Circuit-Switchers
Outdoor Transmission
I
INSTALLATION - Continued
step12
Attach the operator support angle to the appropriate mounting pedestal using two %“-I1 X 14” hex-head galvanized steel cap screws, four flat washers, and two self-locking hex nuts. Refer to the catalog drawing. Then attach the operator support plate to the angle on the side of the operator enclosure and to the operator support angle on the mounting pedestal using four
M”-13 X 1 w” hex-head galvanized steel cap screws, flat washers, and self-locking hex nuts furnished. Securely
tighten
the screws. See Figure 1. On Circuit-Switchers utilizing two or three mounting pedestals, insert the hole plugs furnished into all unused holes in the pedestals.
9
step13
Attach four suitable lifting slings to the channel base of the pole-unit that will be mounted at the center of the cross base-marked “Pole 2”-as shown in Figure 7.
(“Pole 2” is positioned
outboard
on the shipping skid
Model 2020 - With Vertical Interrupters and Side-Break Power-Operated
Disconnect, 69 kv through 138 kv for ease in handling.) Attach an additional sling around the support insulator as shown in Figure 7; this sling is required to maintain stability during lifting.
Make cert&n that the rigging does not stress the disconnect. Unbolt the base from the skid. Raise the pole-unit a few feet, then remove the two W-13 X 1%” hex-head galvanized steel cap screws, flat washers, and hex nuts which attach the shipping bracket to the bottom of the pole-unit channel base. Discard the shipping bracket and associated hardware.
Remove the %-inch silicon-bronze pm and cotter pin from the insulated operating rod. Retain these pins for re-use in Step 18(f).
Remove the protective cover on the cross base at the pole-unit mounting position. See Figure 4. Now continue to raise the pole-unit to its mounting position at the center of the cross base, as shown on the catalog drawing. Carefully guide the pole-unit to avoid damag-
I
Shipping bracket for insulated
Figure 7. Hoisting the pole-unit.
.’
7
l&504 INSTRUCTION SHEET
Page IQ of 23
November 29, 1993
S&C ELECTRIC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto
I
INSTALLATION
- ing the insulated operating rod.
Do not attempt to
lifi
the
pole-unit by the disconnect.
Attach the pole-unit channel base to the cross base, using
%"-13
X 13h" hex-head galvanized steel cap screws, flat washers, and self-locking hex nuts furnished. Next, attach the pole-unit channel base to
%"-13
X
1
%" hex-head galva- nized steel cap screws,
flat
washers, and self-locking hex nuts furnished. Securely tighten all these cap screws.
Step
14
Repeat Step 13 for the two outboard pole-units- marked "Pole
1"
and "Pole
3."
Step
15
For 69-kv Circuit-Switchers with 48-inch phase spacing:
Relevel the support brace to the same
as
the cross base. If necessary, loosen the cap screws used to attach the
outboard
pole-unit channel bases tighten the cap screws.
Step
16
Attach
a
lifting sling to the lifting bracket on one of the interrupters. See Figure
4.
clamps and associated %-inch galvanized steel hard- ware which fasten the interrupter shipping bracket to the cross base. Then carefully
lift
the interrupter somewhat higher than the top of the transition box
of
its associated insulating support column.
Now
remove the four
%"-13
stainless-steel hex nuts and
Belleville washers used to attach the interrupter shipping bracket to the threaded studs on the interrupter. Discard the shipping bracket but retain
in
Step 18(e).
I
Step
17
for attachment to insulating support column
as
follows:
(a)
Remove and discard the two
#10-32
screws which connect the operating-rod holding bracket (marked with
a
black/yellow striped label) for shipment. See
Figure
8
(left). Note: The operating rod is under pressure; when the
two
screws are removed, the holding bracket may move about % inch.
(b) Pull the holding bracket to move the operating rod to its fully open position.
See
Figure 8 (rght).
( c )
Remove the connecting pin used to attach the holding bracket to the coupling. Retain the connecting pin for re-use in Step 18(g), but discard the holding bracket.
I
Operating-rod holding bracket
/y
striped label)
Operating rod in shipping position
Figure 8.
Preparing interrupter lor attachment to Insulating support column.
Operating rod in fully open position
S&C ELECTRIC COMPANY Chicago
S&C ELECTRIC CANADA LTD. Toronto
INSTRUCTION SHEET
7 1 &504
Page
11 01 23
November
29,
1993
S&C Series 2000 Circuit-Switchers
Outdoor Transmission
I
Model 2020 - With Vertical Interrupters and Side-Break Power-Operated
Disconnect, 69 kv through 138 kv
INSTALLATION - Continued
,W-13 stainless-steel studs, Beiieviiie washers, and stainless- / . hI’ [email protected] hex nuts , i*
‘rl
Shipping cover A
Transition box
Access cover
(removed)
/
5
E
I’ i
Figure 9. Attaching interrupter to insulating support column.
Step18
Attach the interrupter to its insulating support column as follows. See Figure 9.
(a) Remove and discard the shipping cover atop the transition box.
(b) Thoroughly wire-brush the top of the transition box and the mating surface on the interrupter, and immediately apply a liberal coating of [email protected]
A (available from Burndy Corporation) or other suitable aluminum connector compound to the brushed surfaces.
(c) Remove the four
5/16”-18
X %” hex-head stainlesssteel cap screws used to attach the access cover to the side of the transition box. Remove the cover and place it and the hardware on a clean surface.
Also remove the cloth bag containing hardware which will be used for connecting the interrupter coupling to the operating rod link in Step 18(g).
(d)Mah ce.rt&n that t2&
positioning mark on the bottom of
the
interrupter is aligmed with the positioning mark an the top of th& transition box.
Then carefully lower the interrupter on top of the transition box. Note that one of the W-13 stainlesssteel studs on the interrupter is longer than the other three, to aid in assembly.
(e) Reattach a %-inch Belleville washer and a %“--13 stainless-steel hex nut, as retained from Step 16, to each of the four studs. Tighten each nut securely.
(f) Attach the insulated operating rod end links to the interphase drive linkage lever in the cross base, using the %-inch silicon-bronze pin and cotter pm retained from Step 13. See Figure 10. The insulated operating rod may be moved up or down, as required, to make the connection.
(g) Insert the connecting pin retained from Step 17(c) into the coupling and operating rod link. See
Figure 11.
It will be necessary to loosen the
5/,,5”-18 X 2’/O” hex-head stainless-steel screw indicated in Figure 11 and withdraw it app?-oximately
‘/s
inch, so that the UmneCting pin can be inserted. Do not remmx the screw at this time.
(h)Insert the pin retaining clip as indicated in
Figure 11.
Make sure that the
clip is positioned US
Shown.
(i) Now remove and discard the
5/16”-i8 X 2%”
hexhead stainless-steel screw, stop bracket (marked with a black/yellow striped label), and spacer
(marked with a black/yellow striped label)
ihS-
trated in Figure 11.
I
7
l&504 INSTRUCTION SHEET
Page 12 of 23
November 29, 7993
S&C ELECTRIC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto
INSTALLATION - Continued
step 19
Remove the interrupter lifting bracket and associated
M-inch stainless-steel hardware from atop the interrupter. Discard the lifting bracket but retain the hardware. Thoroughly wire-brush the indicator end casting where the upper terminal pad is to be attached, as well as the mating surface on the upper terminal pad, and immediately apply a liberal coating of
Penetrox A or other suitable aluminum connector compound to the brushed surfaces. Then attach the upper terminal pad using three %“-13 X 1%” hex-head stainless-steel cap screws and Belleville washers.
step 20
Repeat Steps 16 through 19 for the other two interrupters.
step 21
Attach the uni-ball coupling on the operator connecting link to the interphase drive lever in the cross base, using the %-inch stainless-steel pin and cotter pin retained from Step 9. See Figure 12. An adjustable locking rod
(marked with a black/yellow striped label) is furnished, factory-connected to the interphase drive lever; turn the associated %“-20 locknuts as required to raise or lower the interphase drive lever and thus facilitate insertion of the stainless-steel pin.
step 22
Remove the lower 5/4”--20 locknut which retains the adjustable locking rod. Then remove and discard the adjustable locking rod and locknuts.
Step 23
Open the disconnect blade on each pole-unit. With the disconnect-blade corona-ball contact clear of its jawcontact fingers as indicated in Figure 13 (top), check that the blade centerline has not shifted up or down by more than % inch-as measured to the centerline of the jaw contact. See Figure 13 (bottom). If any blade centerline has shifted by more than l/4 inch, loosen the leveling-screw locknuts located under the associated jaw-contact support insulator. See Figure 14. Adjust the locknuts as necessary to shift the jaw-contact centerline to correspond to that of the blade centerline, f’/4 inch. Then tighten the locknuts.
Connecting pin
Spacer (marked with a black/yellow striped label)
Figure.10. Attaching insulated operating rod to interphase drive.
stainless-steel screw
Pin retaining
I clip
Operiting rod link
(ma’rked with a black/yellow striped label)
Figure 11. Connecting interrrupter to operating rod link.
m S&C ELECTRIC COMPANY
l
Chicago rm S&C ELECTRIC CANADA LTD.
l
Toronto
INSTRUCTION SHEET
7 161504
Page 13 of 23
November 29. 1993
S&C Series
2000 Circuit-Switchers
Model
2020
-
Outdoor Transmission
I
and Side-Break Power-Operated
Disconnect,
69
kv through 138 kv
I
INSTALLATION
- using
a
%-inch stainless-steel pin and cotter furnished. See Figure 16. pin
I
step
24
Close the disconnect blade on each pole-unit. The
disconnect-blade corona-ball contact must be centered on its
jawcontact fingers and the blade must
touch its
stop
as
indicated i n
FXgure 15 (top].
Connect the pole-unit insulating support column drive lever using
a
%-inch stainless-steel pin, two galvanized steel spacers, and
two
stainless-steel
“X”
washers furnished. to the two outboard pole-unit insulating support column drive levers. be connected to an outboard pole-unit insulating support column drive lever, loosen the appropriate locknut at the adjustable coupling and rotate the affected interphase pipe section
so
that the can be made; then tighten the locknut. See Figure
16.
Step
26
Attach the ‘%”-shaped clevis at the lower end of the vertical-operating-pipe assembly to the take-off shaft on the rear
of
the operator, using a %-inch stainless- steel pin and stainless-steel
“X”
washer furnished. See
Figure 16 (inset). Then attach the straight clevis at the upper end of the vertical-operating-pipe assembly
cross
base, using a %-inch stainless-steel pin and cotter pin furnished. See Figure 16. If necessary, loosen the locknuts
at
the top and pipe and rotate the pipe
so
that the connection can be made; then tighten the locknuts.
Step
25
Attach the clevis end the longer
of
the interphase drive link to
of
the bell-crank
arms
on the cross base,
Step
27
Check
for
proper blade closure
at
the
center
pole-unit- marked “Pole
2.“
With
a
pull-out force of approximately
15
(top), blade deflection should be no more than W inch.
(marked with a black/yellow striped label) Interphase drive lever
Adjustable locking rod
Uni-ball coupllng
%“
stainless-steel pin and coner pin
%““20
locknut
Operator connecting link
7 1
INSTRUCTION SHEET
Page
14 of 23
November
29,
7993
S&C
ELECTRIC COMPANY Chicago
S&C ELECTRIC CANADA LTD. Toronto
1
INSTALLATION
- of the vertical operating pipe and rotate the pipe
counterclockwise
(as
blade travel; then tighten the locknuts. See Figure
16
(inset).
Step 28
Check
for
proper blade closure
at
the
two
outboard
pole-units-marked "Pole 1" and "Pole
3."
With
a
pull- out force of approximately
40
pounds applied at the position indicated
in
Figure
15
(top), blade deflection should be no more than
% inch.
If
necessary, loosen the four
%"-13
X
1%"
screws which attach the blade clamp to the transition box and rotate the blade
mnterclockwise (as
- the cap scre;Y's. See Figure
17.
I
step 29
Use the manual charging handle furnished with the operator
to
check functioning
of
the low-speed power train,
as
follows. Refer
to
Rgure
19.
(a) Open the access shutter and place the manual
(b) Rotate the shaft,
clockwise
only,
until
a firm
resistance
is
felt. At this point, the should be open approximately
90
degrees.
If
the
open
this extent, operating pipe and rotate the pipe
clockwise (as
tlghten the locknuts.
( c )
Remove the manual charging handle from the manual charging shaft.
I
Disconnect-blade corona-ball contact
Jaw-contact
I ,
c of disconnect blade assembly
Figure
13.
Checking alignment of disconnect blade and jaw contact.
S&C ELECTRIC COMPANY Chicago
S&C ELECTRIC
CANADA LTD. Toronto
INSTRUCTION SHEET
7
1
Page 15 of 23
November
29,1993
S&C Series 2000 Circuit-Switchers
Outdoor Transmission
Model 2020 - With Vertical Interrupters and Side-Break Power-Operated
Disconnect, 69 kv through 138 kv
INSTALLATION - Continued
step 30
Attach the high-voltage conductors to their respective
Circuit-Switcher terminal pads using flexibleconductor connections. Observe the terminal-pad loading limits specified on the catalog drawing.
Conductors must be de-energized and grounded in accordance with standard system operating practice.
I
Use the following procedure for attachment:
(a) Thoroughly wire-brush the current-transfer surfaces of each connector and immediately apply a liberal coating of Penetrox A or other suitable aluminum connector compound to the brushed surfaces.
(b) Wire-brush each Circuit-Switcher terminal pad and apply a coating of Penetrox A. Then bolt the connectors to the terminal pads.
(c) Prepare the conductors using established procedures and clamp them in their respective connectors.
Step 31
Remove the container from each interrupter as follows:
(a) Remove and discard the ?~‘a”---16 zinc-plated serrated hex nuts which run the length of the container.
(b
) Remove and discard the two %“-16 X 1” and two
%“-16 X %” zinc-plated hex-head cap screws and flat washers which attach the two container-halves to the
coupling end casting
of the interrupter.
cc
) Remove and discard the two %“-16 X 1” and one
%“-16 X %” zinc-plated hex-head cap screws and flat washers which attach one of the containerhalves to the
indicator end casting
of the interrupter. Don’t remove the remaining 3/e”-16 X 7/s” cap screw-it’s needed to temporarily retain the other container-half.
(d) Pry the container-halves apart with a screwdriver.
One of the container-halves can now be removed and discarded-slotted holes are provided so that a rope or lifting sling can be attached and the container more conveniently lowered to the ground.
(e) Now remove and discard the remaining
3/e”-16 X ?‘a” hex-head cap screw and flat washer which attach the other container-half. Then discard this container-half.
(f) Finally, remove and discard the foam-core inner liner wrapped around the interrupter.
74 6.504 INSTRUCTION SHEET
Page 16 of 23
November 29,1993
Step 32
Remove and discard the wirebound-wood wrapper from each insulating support column.
step 33
Perform the following set-up procedure on the operator.
See Figure 18.
(a) To avoid accidentally energizing the operator after the external connections have been completed, open the control-source disconnect switch.
(b
Loosen the clamps on the inside of the side access door, open the side access door, and remove the blocking from the motor contactors.
cc
Mark the conduit-entrance location for the controlcircuit wiring on the conduit-entrance plate in the bottom of the operator enclosure. Then remove the plate and cut out the necessary opening. Apply the sealing compound furnished, replace the plate, and make up the entrance fittings. Verify that the entrance fittings are properly sealed to prevent water ingress.
(d) Connect the external control-circuit wiring (including the space-heater source leads) to the terminal blocks at the bottom of the enclosure, in accordance with the wiring diagram furnished. Observe correct polarity on dc-control-voltage models. 7bip-circuit
conductors and motor-and-closing
circuit
wnductars must be adequately sized
indicated
for
on the wiring diagram.
the ampacities
support insulator 6’:’
Figure 14. Adjusting leveling-screw locknuts.
S&C ELECTRIC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto
q
-
1
INSTALLATION
-
Unauthorized changes should not be made in the wiring
of
the operator. Should
a
control-circuit revision appear desirable, it should be made only on the authority
of a
revised wiring diagram which has been approved by both the user and S&C
Electric Company.
Do
not apply control time!
at
this
Blade stop
Disconnect-blade
7
JawJcontact fingers t
40-pound Maximum pull-out force
\ allowable deflection: 'h inch
See
Steps 27 and 28
Top View
of disconnect blade and jaw-contact assembly
step
34
Check the
following
. . . failure to do
so
can result in damage to the Circuit-Switcher when operated!
each
transition
box:
The operating-rod holding bracket, stop bracket, and spacer have been removed from the interrupter (see Figures 8 and
ll),
and
The interrupter coupling has been connected to its insulated operating rod link (see Fig- ure
11).
(b)
In
the
m s
base:
0
Each insulated operating rod has been connected to the interphase drive (see Fig- ure lo),
The interphase drive lever has been connected to the operator uni-ball coupling (see Rgure
12),
and
0
The adjustable locking rod attached to the interphase drive lever has been removed (see
Figure
12).
(c) All
ouler
pinned
tun" and all bolted
con128ctio12s
have been securely tightened.
(d)At
the
operator:
0
Blocking has been removed from the motor contactors, and
0
Correct polarity has been observed on dc- control-voltage models.
I
Side View
e
~
Figure 15. Checking engagement of disconnect-blade corona-ball contact in jaw-contact fingers.
7 1
M w
Page 17 of
23
November 29, 1993
S&C ELECTRIC COMPANY Chicago
S&C ELECTRIC CANADA LTD. Toronto
S&C Series 2000 Circuit-Switchers
Outdoor Transmission
I
Model 2020 - With Vertical Interrupters and Side-Break Power-Operated
Disconnect, 69 kv through 138 kv
INSTALLATION - Continued
Step 35
Replace the access cover on the side of each transition box and securely tighten the associated %“-18 X %” hex-head stainless-steel cap screws.
Step 36
Replace the bottom plates to the underside of the cross base and securely tighten the associated M”-13 X 1%” galvanized steel cap screws, flat washers, and nuts.
Step 37
Insert the motor-and-closing circuit fuseholder. Then close the control-source disconnect switch.
Locknut
70” stainlesssteel pin and “x” washer
I
Take-off shaft l/a” stainless-steel pin, galvanized steel spacers, and stainless-steel
“X” washers
5/8” stainless-steel pin
- Vertical-
Locknut l/2” stainless-steel drive lever
_ .
Figure 18. Connecting interphase pipe assembly and vertical-operating-pipe assembly. Attachment of interpnase drive link to interphase pipe assembly is different on Circuit-Switchers rated 89 kv (with 48-inch phase spacing); refer to the catalog drawing.
7
1 &SW INSTRUCTION SHEET
Page 18 of 23
November 29, 1993
. S&C ELECTRIC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto
q
-
I
INSTALLATION
-
Step 38
Press the “CL0SE”A pushbutton. The motor-driven cam
in
the stored-energy mechanism will immediately
start
retracting. Simultaneously, the take-off shaft
at
the
rear
of the operator w turn to pipe assembly, closing the disconnect. When the disconnect has completely closed, the closing latch will release, discharging the closing spring. This action closes the interrupters. The switch-position indicator on the cross base w move to the “CLOSED” position.
Further, if the position-indicating lamp option has been specified, the red lamp w light.
Step
39
When the Circuit-Switcher is ready to be placed in service, the motor-and-closing circuit fuses can-at the user’s option-be replaced with the slugs furnished.
This
practice is recommended for increased reliability because low-voltage fuses can be damaged by the repeated inrush current experienced during normal
Circuit-Switcher opening and closing operations and can thus sneak out, leaving the Circuit-Switcher inoperable.
Bejiie replacing these fuses
slugs, make certain that the control-source battery
is
adequately protected to prevent discharge, using
fuses
or circuit breakers located at the battery bus.
step 40
Please complete and mail
the
Circuit-Switcher regis- tration card!
The information requested on this card is vital to ensure prompt notification in the event field modifications are needed.
A ’hip and close pushbuttons are not included on operators specified with Catalog Number
Suffix
‘J.” In such instances, momentarily jumper terminals 1 and 3 to close the Circuit-Switcher.
Blade clamp
7
=
at outboard pole-unit
to attain
I
1
.
lOPERATlON
Electrical Operation
Refer to Figure 18.
To open the Circuit-Switcher,
press the “ T R I P pushbutton.* The opening latch in the stored-energy mechanism will release, discharging the opening spring. and closing pistons in the mechanism downward,
as
denoted by movement of the indicator to the “DIS-
CHARGED” window. The switch-position indicator on
3
if the position-indicating lamp option
“-M”)
w light.
‘The motor-driven cam in the stored-energy mech- anism will immediately
start
rising, thereby charging both the opening and closing springs; when the opening spring latches, the indicator w again be visible
at
the
“CHARGED” window. Simultaneously, the take-off shaft
*
n i p and close pushbuttons on operators specified with Catalog Number Suffm ‘-J.” Refer to the ‘Manual Operation” section.
S&C ELECTRIC COMPANY Chicago
S&C ELECTRIC CANADA LTD. Toronto
INSTRUCTION SHEET
7
1&5O4
Page 19 of
23
November
29,1993
S&C Series 2000 Circuit-Switchers
Outdoor Transmission
I
Model 2020 - With Vertical Interrupters and Side-Break Power-Operated
Disconnect, 69 kv through 138 kv
OPERATION - Continued
Eight nonadjustable single-pole doublethrow auxiliary-switch contacts
(not visible in photo) which follow the interrupters
Key interlock
(Catalog Number Suffix “-Ll”)
Side access door for user’s external connections
(to terminal blocks at bottom of enclosure)
Instruction indicating lamps
Duplex receptacle with ground-fault circuit interrupter and conveniencelight lampholder with switch
Non-reset electric fuses
Access shutter handle
operator when coupled, operator only when decoupled
Figure 18. Interior of operator.
Space-heater fuses
716-504
Page 20 of 23
November 29, 1993
INSTRUCTION SHEET
Motor-andclosing circuit fuseholder
Control-source disconnect switch
S&C ELECTRIC COMPANY
l
Chicago s&C ELECTRIC CANADA LTD.
l
Toronto
OPERATION - Continued at the rear of the operator housing will turn to drive the interphase pipe assembly, opening the disconnect.
To
close the
Circuit-Switcher, press the “CLOSE” pushbutton.* The motor-driven cam in the storedenergy mechanism will immediately start retracting.
Simultaneously, the take-off shaft at the rear of the operator housing will turn to drive the interphase pipe assembly, closing the disconnect. When the disconnect has completely closed, the closing latch will release, discharging the closing spring. This action closes the interrupters. The switch-position indicator on the cross base will move to the “CLOSED” position. Further, if the position-indicating lamp option has been specified, the red lamp will light.
The Circuit-Switcher may also be electrically operated via remotely located control switches. No instruc-
* Trip and close pushbuttons are not included on operators specified with Catalog Number Suffix “-J.” Refer to the “Manual Operation” section.
Coupled
Vertlcal-operatlng-
4H pipe assembly
(In open pmtion)
Decoupling handle
Figure 19. Using manual charging handle to recharge opening and closing springs, and open disconnect.
w S&C ELECTRIC COMPANY
l
Chicago
S&C ELECTRIC CANADA LTD.
l
Toronto
Decoupled
Figure 20. Decoupling the disconnect-blade power train.
INSTRUCTION SHEET
7
1
e-504
Page 21 of 23
November 29, 7993
1
SBC Series 2000 Circuit-Switchers
Model
2020
Outdoor Transmission
I
and Side-Break Power-Operated
Disconnect, 69 kv through 138 kv
I
- tions are included for such operation because control schemesvarywith different installations. With any given installation, however, it may be possible and desirable to effect such operation.
Manual Operation
Refer to Figure 18.
To open
ULe
Circuit-Switcher,
lever counterclockwise. The opening latch in the stored- energy mechanism will release, discharging the opening spring. This action trips the interrupters and forces the opening and closing pistons in the mechanism downward,
as
denoted by movement of the indicator to the “DISCHARGED” window. The switch-position indicator on the cross base will move to the “OPEN” position. Further,
if
the position-indicating lamp option has been specified-and operator control voltage is available-the green lamp w light.
The motor-driven cam in the stored-energy mech- anism w immediately start rising-if operator control voltage is available-thereby charging both the opening and closing springs; when the opening spring latches, the indicator will again be visible at the “CHARGED“ window. Simultaneously, the take-off shaft at the rear
of
the operator pipe assembly, opening the disconnect.
If
operator control driven cam in the stored-energy mechanism will charge the opening and closing springs-and the take-off shaft will turn to pipe assembly, opening the disconnect-when control voltage returns.
If
desired, the opening and closing springs can be charged and the disconnect opened after the interrupters have been tripped, using the manual charging handle furnished. Refer to Figure 19. Use the following procedure:
(a) Open the access shutter and place the manual charging handle on the manual operating shaft.
clockwisemly,
until the disconnect opens fully and the mechanism reaches its open stop.
Manual closing of the Circuit-Switcher cannot be performed.
Decoupling
The disconnect-blade power train may be decoupled in the open position, permitting the interrupters to be tripped and closed for inspection purposes.
To
decouple,
open the Circuit-Switcher electrically
or
manually. Then disengage the decoupling handle on the rear of the operator by pivoting it outward. See
Figure 20 (bottom). The disconnect-blade power train
I
7
ern5O4
Page 22 of 23
November 29, 1993
S&C ELECTRIC COMPANY Chicago
S&C ELECTRIC CANADA LTD. Toronto
1 OPERATION - Continued may now be padlocked open. In addition, the interrupters may now be closed and re-tripped as desired, either electrically or manually.
To rtwmplq
open the Circuit-Switcher electrically or manually. Then engage the decoupling handle on the rear of the operator by pivoting it inward. See Figure 20
(top). The disconnect-blade power train may now be padlocked coupled.
Adjusting Auxiliary-Switch Contacts
Two individually adjustable auxiliary-switch contacts are furnished in the operator. These contacts follow the position of the disconnect-blade power train and operator when the power train is coupled, and the position of the operator when the power train is decoupled.
Each auxiliary-switch contact is operated by a camactuated roller. A contact is closed if its roller is disengaged from a cam and, conversely, a contact is open if its roller is engaged by a cam. The cams are individually adjustable in 4.5-degree increments.
Adjustment of the cams is accomplished as follows:
(a) Push the cam toward its adjacent spring until the cam is separated from the teeth of the inner gear.
See Figure 2 1.
(b) Rotate the cam to advance or retard engagement with its roller.
(c) Release the cam,
making
sure that the teeth are in mesh with the inner gear.
I
Cam
Figure 21. Adjustment of cams on auxluary swucn.
S&C ELECTRIC CANADA LTD.
l
Toronto
INSTRUCTION SHEET
7
1
e-504
Page 23 of 23
November 29, 1993
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
Related manuals
advertisement