07/05/2010
Paxton
Ins-30010 Switch2 control unit
Technical Support
01273 811011
Technical help is available:
[email protected]
Monday - Friday from 07:00 - 19:00 (GMT)
Saturday from 09:00 - 13:00 (GMT)
Documentation on all Paxton products can be found on our website - http://www.paxton.co.uk/
Quickstart guide
This supplement is a brief guide to installing a Switch2 system. Further information is available for download at:
http://paxton.info/45 or call the communications team on: 01273 811011.
Wiring
Switch2
Data
Reader
Clock
Media Detect
0V
Inputs
Contact
Alarm
Bell
Power
12V
0V
N.C.
Door relay
Green LED
Reader or Keypad
Amber LED
Caution: For 12V d.c readers only. For correct
connection of old 5V readers, please refer
to instructions.
12V
Red LED
N.O.
COM
http://paxton.info/107
PLACE SERIAL
NUMBER
123456
LABEL HERE
Exit
Fail closed release
*
(for Paxton exit buttons
GREEN and RED wires go
to reader terminals)
Exit button
Black/0V and Exit
(push to make)
To change a reader port voltage to 5V, move the red jumper(s) located beneath the wiring label to the 5V setting.
Fail open locks
* For a fail open lock (Maglock), the 0V loop wire is connected to the “N.C.” terminal. (not the “N.O.”)
This product is not suitable for retail sale. All warranties are invalid if this product is not installed by a competent person.
Page INITIALISING A NEW SYSTEM
The first time the system is powered up the control unit will beep 3 times a second.
This indicates the unit needs programming. There are 3 programming options:
Using tokens only (CARDLOCK or PROXIMITY)
Using codes only (TOUCHLOCK)
see Section 1
see Section 2
Using tokens and PIN/codes (CARDLOCK/PROXIMITY with TOUCHLOCK)
see Section 3
The reader’s default indication has all the LED’s on. Access granted is denoted
with a single flashing Green LED, Access Denied is a single flashing Red LED.
Section 1 - CARDLOCK or PROXIMITY
Enrolling a card pack.
Present/swipe enrolment card
RD
CA
de
ON rTdY arto th ckis
TI It McaI t isccardthenis tpathlidthatise the
NC OeXn eseennt kethn,nsprines prtoesvaenckwet. d byken,
to
ern llo
rd
R olm
FU rPolm
r n, pre thlae tio retoadke eris fopa er to t ca the
tio
th us en by
la atstal eer ad
en e n
al
re
a lm
thus e in
4 ed
st validin
a
e ro/7
in
toe ns
th at
w
fo
to At
in llo
At
to
id n.en
rdat ke
. ader . caalid rd
is
fo
to al to
-v t ax
-v t ca
e
th er
re
re th
/p
en n re en
To
:/ read
tp
ke To htes
n.
2. rolm 2.
e
en er to fo:pr th toke
in
us
to ercess
e
usAc
Mor
on
xt
Pa
All tokens will now be validated.
Tokens can now be issued to users
Adding an additional Proximity card pack.
You need to be in possession of a
valid enrolment card for this system. Present this enrolment card to the reader and the Amber
LED will flash with the Green & Red LED’s off. Present the Enrolment card from the new card
pack. The reader will beep and all LED’s will be lit. The additional cards will now be valid. Repeat
this with each reader and with any additional card packs. Any valid enrolment card can be used
to add further packs. If an incorrect enrolment card is used to start the process, the Red LED will
be lit and the reader will produce a squeak sound as it rejects the card.
To bar a user:
Present/swipe user’s shadow card
The user card is now barred
A user can be re-validated by showing the enrolment card
followed by the user card or re-entered if used in Card+PIN mode.
Section 2 - TOUCHLOCK
Choose a 6 digit Programming Code and load this into the unit as follows:
DO NOT USE 123456 - The default User Code will open the door
before the Programming Code had been fully entered.
6 digit Programming
Code
6 digit Programming
Code
The default user code is now set to 1234
You can now set up the user codes and features using the programming chart.
Example: - Setting a user code to unlock the door under Normal conditions.
Enter 6 digit
Programming
Code
8
Enter user code
4-8 digits
Re-enter
user code
Hold for 3 secs
4
Normal
FACTORY RESET
1.
2.
3.
4.
5.
6.
7.
8.
9.
Disconnect power
Disconnect GREEN and MAUVE wires
Insert link wire between GREEN and MAUVE terminals
Reconnect power - unit will beep 4 times
Disconnect power
Remove link wire
Reconnect GREEN and MAUVE wires
Reconnect power - unit will beep 3 times a second
Proceed with Initialising a new system
This box can be used to write down the Programming Code for future reference.
Ensure that this information is stored in a secure place.
Page START - Enter the 6 digit Programming Code and hold down a function key
for 3 seconds. - The unit beeps and the LED flashes faster.
Continue the key sequence to set the option - The keypad returns to operating mode.
Enter user code
4-8 digits
8
Set a
user code
1
Combined Card &
Keypad modes
= Normal
OR
6
= Toggle
OR
8
= Duress
OR
2
= Delete
See Section 3
5
Door open time
(seconds)
4
Re-enter
user code
X
X
Enter time in seconds
(default = 07, max = 60)
Single or multiple
codes
2
2
One code only
OR
6
Multiple codes allowed
Silent operation
3
2
Beep on
OR
6
Silent
20 wrong keystrokes
= 60 second lockout
4
2
OFF
OR
6
ON
Exit button
7
2
Open door for
time in option 5
OR
4
Toggle door open
until pressed again or
toggle code entered
Change
Programming Code
6
Enter 6 digit
Programming Code
Data Reset (except
Programming code)
9
Enter 6 digit
Programming Code
Re-enter 6 digit
Programming Code
9
Function keys
= Hold down for 3 secs
Section 3 - CARDLOCK/PROXIMITY with TOUCHLOCK mode
(i) The KP reader must first be initialised in TOUCHLOCK mode:
(Individual Toggle function is not available)
See Section 2
(ii) Set up the required operating mode, as follows:
1
1
Enter 6 digit
Programming
Code
Hold for 3 secs
Card plus PIN
OR
2
OR
Card plus Code
3
Card or Code
(iii) Present enrolment card
Card plus Code.
Access is granted by presenting a valid token and then entering a valid user code.
Card or Code.
Access is granted by presenting a valid token or entering a valid user code.
Touchlock programming - Function 2 to enable multiple user codes, Function 8 to add user codes. (4 digits)
Card plus PIN.
A card requires a 4 digit PIN to be assigned to it before it will work, as follows:
Present
enrolment
card
RD
CA
N rdY rdto the ks
IT cad pacthi ate
TIOIM
t ca t carin sethisnt lidt this
the
va by ,
X ent this
NC Oen
. en
to sen ed
ens
, pre r pre
ck
lmpresentok
ow
R
ion de
FU roPlm
pa tok card
en foll
n, the
s er
the
lat rea
nt
r tokthi
der us
nro
atio tetal
en e tall idains
ins val
rea a
use in
me
the
a s
rol74 ed
to
the ate
te en
to At
At
enfo/ low
rd
ida d to lid sn.in
. der . ca
fol
val cartok va thi
xto r
rea
re- the re- nt
/pa de
ent
To
p:/ rea .
2. olm 2.enTo httse
en
:pre
enr r tok
use
re
Mo
Present user
card
Amber flashes
Enter PIN
Amber and
Green flash
Re-Enter PIN
LED’s flash faster
by
the tok
eress
usAcc
info to
ton
Pax
Page Technical Help
Here is the list of topics about this product that receive the most technical support enquiries.
We list them here to help you speed up the installation and trouble shooting process.
1 - How to reset the controller.Q- See Main Text
2 - Two readers on the same controller.
QSimply wire the PROXIMITY or CARDLOCK readers in parallel, colour for colour. It is possible to mix 5V
Qand 12V readers. The jumper on the Switch2 must be set to provide 5V at the Red terminal and the
Q12V reader must then be powered directly from the 12V terminal.
3. - Replacing a white labelled control unit. (pre 2004 design)
QOn a White labelled unit the Red voltage terminal output was 5V DC. The new Yellow labelled unit has
Qthis output set to 12V DC. For systems where 5V readers/keypads are to be used, readers must not be
Qconnected to yellow label controllers until the jumper setting has been changed on the controller PCB.
QNOTE: The Touchlock membrane keypad is not compatible with this control unit.
4 - Initialising with 2 keypads.
QEither Keypad can be used to initialise the controller when using K-Series Keypads. Connect all wires in
Qparallel, colour for colour. If you are using the older Touchlock/SS then you must use the master keypad
Qwhich has the yellow wire connected to yellow terminal. (The slave keypad will have the yellow wire
Qconnected to the mauve terminal.)
5 - Bell/Alarm Output.
QA 12V DC alarm sounder can be wired between the 12V and Bell terminals. This output is capable of
Qdriving a 12V bell/buzzer up to 1A. This load must be taken into consideration when selecting a suitable
Qrated power supply. If door contacts are fitted on a Switch2 system, across the Black and Contacts
Qterminals, the bell/alarm output is activated when the door is forced. On a Switch2 system using a
Qkeypad, the bell would normally activate this output. However, when using a door forced alarm, the bell
Qon a keypad will not activate the bell/buzzer connected to this output.
Specifications
Features
Min
Max
Number of Users
1
10,000
Number of Codes
Code length
50
4 digits
Number of PIN’s
Readers per interface
8 digits
3,000
1
3
1 sec
60 secs
Time zones (with additional time clock)
1
2
Access levels (Colour Zones)
1
3
Door open time
Silent operation
Yes
Can be used with fail OPEN locks
Yes
Can be used with fail CLOSED locks
Yes
Exit button input
Yes
Door Contact input
Yes
Yes
Alarm/bell output voltage
Electrical
Voltage
Min
Max
11V DC
14V DC
Current
80 mA
Relay switchable voltage
24V DC
Switchable current
Environment
Operating temperature
Waterproof
Dimensions
Control Unit
Plastic Cabinet
4A
Min
Max
-20 °C
+55 °C
NO - If used externally, it must be protected in a plastic weatherproof housing
Width
Height
Depth
71 mm
70 mm
23 mm
200 mm
200 mm
75 mm
Page ">