Socomec Delphys MX
DELPHYS MX
Three-phase UPS
from 250 to 900 kVA
the Mega Power protection up to 5.4 MVA
The solution for
> Industry
> Telecommunications
> Processes
Attestations
DEFYS 176 A
B U R E A U
VERITAS
DELPHYS MX series is
attested by Bureau Veritas.
Advantages
Lower Total Cost of Ownership
Flexible architecture
• Minimized running costs, by:
- very high efficiency of up to 93.5%
(VFI mode, including the transformer),
- ‘Energy saver’ automatically adapts the
number of running units to the real load,
- free-cooling compatible.
• Reduced footprint.
• Exceptional high power density (the most
compact unit of its class): 500 kVA in less
1.6 meters (width) per unit including the
bypass.
• PFC “clean input” rectifier (without filters) with
a lasting high input power factor whatever the
operating conditions.
• Intelligent built-in battery monitoring system
interacts with “charging mode” to prolong
battery lifetime.
• Leading power factor load compatible
without derating.
• Parallel system with modular units.
• Powerful central bypass for power extension
or redundancy.
• Tier 3 and Tier 4 compatible.
• Designed for optimal use with STS in
downstream network.
High reliability and availability
• Internal fault-tolerant architecture with internal
redundancies and fan failure localisation.
• Intelligent embedded battery monitoring with
failed block localisation and preventative
remote alarm.
• Able to withstand an output short-circuit and
overload.
• Reliable and robust paralleling mode.
• Multisystem automatic cross
synchronisation (ACS) for an optimized use
with STS.
• Output isolation transformer to reduce the
influence of N-GND (Neutral Line-to-Ground)
voltage and load harmonic current on UPS
inverter.
30
Catalogue 2013
User-friendly operation
• A control panel with graphic display for more
ergonomic operation.
• An array of “com-slot” plug-in
communication interfaces, for upgrading
your operating requirements.
• Reduced MTTR thanks to extractible power
bridges or fans on “cassette”.
• Front accessibility for all components.
Simplified communication
• Easy remote monitoring via web browser or
via customer’s supervision systems (web,
intranet, extranet…).
• Very open connectivity (MODBUS/JBUS,
JBUS tunnelling, LAN).
Parallel systems
• To fulfil the most demanding needs for
power supply availability, flexibility and the
installation to be upgraded.
• Modular parallel up to 6 units, development
without constraint.
• Centralized bypass for progressive
development.
• Twin channel architecture with Static
Transfer Systems.
Flywheel
COMPATIBLE
DELPHYS MX
from 250 to 900 kVA
Three-phase UPS
Standard electrical features
Electrical options
Communication options
• Backfeed protection: detection circuit.
• Standard interface:
- 3 inputs (emergency stop, generating set,
battery protection),
- 4 outputs (general alarm, back-up, bypass,
preventative maintenance needs).
• EBS (Expert Battery System).
• BHC INTERACTIVE.
• EBS (Expert Battery System).
• FLYWHEEL compatible.
• ACS synchronisation system.
• Redundant electronic power supplies.
Standard communication
features
• Reinforced IP protection degree.
• Ventilation filters.
• Redundant ventilation with failure detection.
• Top entry connection.
• GTS (Graphic Touch Screen).
• ADC interface (configurable voltage-free
contacts).
• RS232, RS422, RS485 serial port
JBUS/MODBUS or PROFIBUS.
• MODBUS TCP interface (JBUS/MODBUS
tunneling).
• BACnet/IP interface.
• NET VISION: professional WEB/SNMP
interface for UPS monitoring and shutdown
management of several operating systems.
• Alarm notification via SMS.
• Multilanguage graphic display.
• Slots for 7 communication cards.
Mechanical options
Remote monitoring service
• Remote mobile and web-based surveillance
service connected 24/7 to your local
Socomec Service Centre.
Technical data
DCG 129013
DELPHYS MX
Sn [kVA]
Pn [kW]
Input / output
Parallel configuration
INPUT
Rated voltage(1)
Voltage tolerance
Rated frequency
Frequency tolerance
Power factor / THDI
OUTPUT
Rated voltage
Voltage tolerance
Rated frequency
Frequency tolerance
Total output voltage distortion - linear load
Total output voltage distortion - non-linear load
(lEC 62043-3)
Short-circuit current
Overload
Crest factor
Power factor without derating
BYPASS
Rated voltage
Voltage tolerance
Rated frequency
Frequency tolerance
EFFICIENCY
Online mode
Eco Mode
ENVIRONMENT
Operating ambient temperature
Relative humidity
Maximum altitude
Acoustic level at 1 m (ISO 3746)(2)
UPS CABINET
Dimensions W x D x H
Weight
Degree of protection
Colours
STANDARDS
Safety
EMC
Performance
Product declaration
250
225
300
270
400
360
500
450
800
720
900
800
3/3
up to 6 units
380 V - 400 V - 415 V
340 to 460 V
360 to 460 V
50/60 Hz
± 5 Hz
0.93 / < 4.5%
0.94 / < 5%
380 V - 400 V - 415 V
< 1 % (static load), ± 2 % in 5 ms (dynamic load conditions from 0 to 100 %)
50/60 Hz
± 0.2%
< 2%
< 4%
< 3%
Up to 4,4 In
150% for 1 minute, 125% for 10 minutes
3:1
0.9 lagging to 0.9 leading
380 V - 400 V - 415 V
± 10%
50/60 Hz
± 2% (configurable for GenSet compatibility)
up to 93.5%
98%
from 0 °C up to +35 °C (from 15 °C to 25 °C for maximum battery life)
0 % - 95 % without condensation
1000 m without derating (max. 3000 m)
≤ 70 dBA
≤ 72 dBA
2500 kg
1600 x 995 x 1930 mm
2800 kg
3300 kg
≤ 75 dBA
3200 x 995 x 2210 mm
5900 kg
IP20
RAL 9006
IEC 62040-1; EN 62040-1; IEC 60950-1
IEC 62040-2; EN 62040-2
IEC 62040-3
CE
(1) DELPHYS MX 250-500: others on demand. - (2) As per power range.
www.socomec.com
Non contractual document.
© 2013, Socomec SA. All rights reserved.
Catalogue 2013
31
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement