NX Datasheet
[email protected]
NX safety control
Integrated safety into machine automation
• The safety controller meets Category 4, PLe
according to the ISO 13849-1 and SIL3 according to
the IEC 61508
• Flexible system lets you freely mix safety controller
and safety I/O units with standard NX I/O
• High connectivity I/O units for direct connection to a
variety of devices
• Scalable CPUs for 32 or 128 safety connections
• Up to 8 safety input points per unit
• Safety function blocks conforming with IEC 61131-3
standard programming
• PLCopen function blocks for safety
• Integration in one software, Sysmac Studio
Safety controller
Safety I/O
System configuration
Sysmac Studio
NJ-Series
Machine automation controller
NX-Series I/O
Safety Controller
Safety I/O units
Safety I/O units
ADR
ADR
Accurax G5
Servo Drive
MX2 inverter
Accurax G5
Servo Motors
NX safety control
FQ-M
vision
Accurax
Linear Motors
95
Specifications
Regulations and standards
Certification body
TÜV Rheinland*1
UL
Standards
EN ISO 13849-1: 2008 + AC: 2009
EN ISO 13849-2: 2012
IEC 61508 parts 1-7: 2010
EN 62061: 2005
EN 61131-2: 2007
EN ISO 13850: 2008
EN 60204-1: 2006 + A1: 2009 + AC: 2010
cULus: Listed (UL508) and ANSI/ISA 12.12.01
EN 61000-6-2: 2005
EN 61000-6-4: 2007
NFPA 79: 2012
ANSI RIA 15.06-1999
ANSI B11.19-2010
UL1998
IEC 61326-3-1: 2008
*1. Certification was received for applications in which OMRON FSoE devices are connected to each other.
The NX-series Safety Control Units allow you to build a safety control system that meets the following standards.
• Requirements for SIL 3 (Safety Integrity Level 3) in IEC 61508, EN 62061, Safety Standard for Safety Instrumented Systems (Functional Safety
of Electrical/Electronic/Programmable Electronic Safety-related Systems)
• Requirements for PLe (Performance Level e) and for safety category 4 in EN ISO13849-1
The NX-series Safety Control Units are also registered for C-Tick and KC compliance.
General specifications
Item
Enclosure
Grounding method
Operating environment
Installation method
Applicable standards
96
Specifications
Mounted in a panel
Ground to 100 or less
Ambient operating tempera- 0 to 55°C
ture
Ambient operating humidity 10% to 95% (with no condensation or icing)
Atmosphere
No corrosive gases
Ambient storage temperature –25 to 70°C (with no condensation or icing)
Altitude
2,000 m max.
Pollution degree
2 or less: Conforms to JIS B3502 and IEC 61131-2
Noise immunity
Compliant with IEC 61131-2
2 kV on power supply line (compliant with IEC 61000-4-4)
Insulation class
Class III (SELV)
Overvoltage category
Category II: Conforms to JIS B3502 and IEC 61131-2
EMC immunity level
Zone B
Vibration resistance
Compliant with IEC 60068-2-6
5 to 8.4 Hz, 3.5-mm amplitude, 8.4 to 150 Hz, acceleration: 9.8 m/s2 for 100 minutes each in X, Y and
Z directions (time coefficient: 10 minutes x coefficient factor 10 = total time 100 min.)
Shock resistance
Compliant with IEC 60068-2-27
147 m/s2, 3 times each in X, Y and Z directions
Insulation resistance
20 M between isolated circuits (at 100 VDC)
Dielectric strength
510 VAC for 1 min between isolated circuits, leakage current: 5 mA max.
DIN track (IEC 60715 TH35-7.5/TH35-15)
EN ISO 13849-1, 13849-2: 2008 PLe/Safety Category 4
IEC 61508: 2010 SIL 3, EN 62061: 2005 SIL CL3
UL 1988
cULus: listed (UL508), ANSI/ISA 12.12.01
EC: EN 61131-2, C-Tick, KC: KC Registration
Safety
Nomenclature
Safety controller unit
A
B
C
E
D
C
F
G
C
E
C
B
Symbol Name
A
Marker installation
location
B
NX bus connector
C
Unit hookup guide
D
E
DIN track mounting
hooks
Unit pull out tabs
F
Indicators
G
Unit specifications
Function
These are where markers are attached. OMRON
markers are attached when the unit is shipped.
You can also attach commercially available
markers.
This is the NX-series bus connector. It is used to
connect an NX-series safety I/O unit or other NX
unit.
This guide is used to connect the unit to another
unit.
These hooks are used for installation on a DIN
track.
Place your fingers on these tabs to pull out the
unit.
The indicators show the current operating status of
the NX unit and signal I/O status.
The number of indicators depend on the NX unit.
The specifications of the NX unit are given here.
Safety controller unit
Item
Model
Name
Maximum number of safety I/O points
Program capacity
Number of safety master connections
External connection terminals
Unit power consumption
I/O power supply system
I/O current consumption
Current capacity of I/O power supply terminal
I/O refreshing method
Dimensions
Weight
NX safety control
Specifications
NX-SL3300
Safety CPU unit
256 points
512 KB
32
None
0.90 W max.
Not supplied
No consumption
No I/O power supply terminals
Free-run refreshing
30(W) x 100(H) x 71(D)
75 g max.
NX-SL3500
1024 points
2048 KB
128
97
Safety I/O unit
Safety input unit
Item
Model
Name
Number of safety inputs
Number of test outputs
Internal I/O common
Rated input voltage
OMRON special safety input devices
Number of safety slave connections
Safety input current
Safety input ON voltage
Safety input OFF voltage/OFF current
Test output type
Rated current of test outputs
Residual ON voltage of test outputs
Leakage current of test outputs
Dielectric strength
Insulation resistance
Isolation method
Unit power consumption
I/O power supply system
I/O current consumption
Current capacity of I/O power supply terminal
I/O refreshing method
Terminal block type
Dimensions
Weight
Maximum cable length
Protective functions
Specifications
NX-SIH400
NX-SID800
Advanced safety input unit
Safety input unit
4 points
8 points
2 points
Sinking (PNP)
24 VDC
Can be connected
Cannot be connected
1
4.5 mA
3.0 mA
11 VDC min.
15 VDC min.
5 VDC max., 1 mA max.
Sourcing outputs (PNP)
25 mA max.
50 mA max.
1.2 V max.
0.1 mA max.
510 VAC for 1 min between isolated circuits, leakage current: 5 mA max.
20 M min. between isolated circuits (at 100 VDC)
Photocoupler isolation
0.70 W max.
0.75 W max.
Power supplied through the NX bus
20 mA max.
No applicable terminals
Free-run refreshing
Screwless push-in terminals
Screwless push-in terminals
8 terminals (A + B)
16 terminals (A + B)
12(W) × 100(H) × 71(D)
70 g max.
Devices with mechanical contacts: 400 m, other devices: 100 m
Overvoltage protection circuit and ground fault detection (test outputs)
Circuit layout
Terminal wiring
NX-SIH400
NX-SIH400
NX-SIH400
Safety Input Unit
T0 and T1
Internal circuits
A1
Terminal block
Si0 to Si3
Left-side NX
bus connector
I/O power supply +
I/O power supply +
I/O power supply 
I/O power supply 
Right-side NX
bus connector
B1
Si0
Si1
T0
T1
Si2
Si3
T0
T1
A8
Safety Switch
B8
NX-SID800
NX-SID800
NX-SID800
Safety Input Unit
A1
Terminal block
Si0 to Si7
Left-side NX
bus connector
Internal circuits
T0 and T1
I/O power supply +
I/O power supply +
I/O power supply 
I/O power supply 
Right-side NX
bus connector
A8
98
B1
Si0
Safety Switch
Si1
T0
T1
Si2
Si3
T0
T1
Si4
Si5
T0
T1
Si6
Si7
T0
T1
B8
Safety
Safety output unit
Item
Model
Name
Number of safety outputs
Internal I/O common
Maximum load current
Rated voltage
Number of safety slave connections
Safety output ON residual voltage
Safety output OFF residual voltage
Safety output leakage current
Dielectric strength
Insulation resistance
Isolation method
Unit power consumption
I/O power supply system
I/O current consumption
Current capacity of I/O power supply terminal
I/O refreshing method
Terminal block type
Dimensions
Weight
Maximum cable length
Protective functions
Specifications
NX-SOH200
NX-SOD400
High-current safety output unit
Safety output unit
2 points
4 points
Sourcing outputs (PNP)
2.0 A/point, 4.0 A/unit at 40ºC, 2.5 A/unit at 55ºC 0.5 A/point and 2.0 A/unit
The maximum load current depends on the
installation orientation and ambient temperature.
24 VDC
1
1.2 V max.
2 V max.
0.1 mA max.
510 VAC for 1 min between isolated circuits, leakage current: 5 mA max.
20 M min. between isolated circuits (at 100 VDC)
Photocoupler isolation
0.70 W max.
0.75 W max.
Power supplied through the NX bus
40 mA max.
60 mA max.
IOG: 2 A max./terminal
IOG (A3 and B3): 2 A max./terminal,
IOG (A7 and B7): 0.5 A max./terminal
Free-run refreshing
Screwless push-in terminals
8 terminals (A + B)
12(W) × 100(H) × 71(D)
65 g max.
100 m
Overvoltage protection circuit and ground fault detection
Circuit layout
Terminal wiring
NX-SOH200
NX-SOH200
NX-SOH200
Safety
Output Unit
Internal circuits
A1
Left-side NX
bus connector
So0 and So1
B1
So0
So1
IOG
IOG
NC
NC
NC
NC
Terminal block
L
L
L
L
IOG
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
Right-side NX
bus connector
A8
B8
NX-SOD400
NX-SOD400
NX-SOD400
Safety
Output Unit
Internal circuits
A1
Left-side NX
bus connector
NX safety control
So0 to So3
B1
So0
So1
IOG
IOG
So2
So3
IOG
IOG
Terminal block
IOG
I/O power supply +
I/O power supply +
I/O power supply −
I/O power supply −
Right-side NX
bus connector
A8
B8
99
Dimensions
EtherCAT coupler unit
NX-ECC201/ECC202
48.1
46
1.5
104.5
100
1.5
65.2
71
80
Safety controller unit
NX-SL3300/SL3500
30
100
71
Safety I/O unit
End cover unit (included with the EtherCAT coupler unit)
12 mm width
NX-END01
14.1
12.0
12
100
1.5
1.5
104.5
1.5
65.2
100
71
1.5
71
80.1
100
Safety
Ordering information
EtherCAT coupler unit
Type
EtherCAT
communication coupler
(firmware version 1.1 or
higher)
Signal type
EtherCAT slave
Specifications
Up to 63 I/O units
Max. 1024 bytes in + 1024 bytes out
Supports distributed clock
Channels
2
2
Max. I/O power supply
4.0 A
10.0 A
Width
46 mm
46 mm
Model
NX-ECC201
NX-ECC202
Program capacity
512 KB
2048 KB
Width
30 mm
30 mm
Model
NX-SL3300
NX-SL3500
Test outputs
2 points
2 points
Width
12 mm
12 mm
Model
NX-SIH400
NX-SID800
Width
12 mm
12 mm
Model
NX-SOH200
NX-SOD400
Width
12 mm
Model
NX-END01
Safety controller unit
Type
Safety CPU
Safety master connections
32
128
Safety I/O points
256 points max.
1024 points max.
Safety I/O unit
Safety input unit
Type
Safety input
Signal type
PNP type
Safety slave connections Safety inputs
1
4 points
8 points
Signal type
PNP type
Safety slave connections
1
Safety output unit
Type
Safety output
Safety outputs
2 points
4 points
System unit
Type
End cover
Specifications
Included with communication coupler
Accessories
Name
Terminal block coding pins
Terminal block
Specifications
For 10 units (Terminal block: 30 pins, unit: 30 pins)
Replacement front connector with 8 wiring terminals (A + B)
Replacement front connector with 16 wiring terminals (A + B)
Model
NX-AUX02
NX-TBA082
NX-TBA162
Computer software
Name
Sysmac Studio version 1.08 or higher*1
Model
[email protected]@@
*1. Please contact your OMRON representative for compatibility between the Sysmac Studio version 1.07 or lower and NX I/O units.
101
.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat.No.SysCat_I183E-EN-02
102
In the interest of product improvement, specifications are subject to change without notice.