Installation equipment cabinet for smoke funct. TBLZ-1-48-1 GOLD/COMPACT 1. General

Installation equipment cabinet for smoke funct. TBLZ-1-48-1 GOLD/COMPACT 1. General
GB.TBLZ481.120614
Installation equipment cabinet for smoke funct. TBLZ-1-48-1
GOLD/COMPACT
1. General
Equipment cubicle for smoke function consists of a control unit installed in a box with transparent cover.
There are necessary terminals for external connection.
The equipment cubicle is equipped with knockout grommets.
2. Range of Application
The equipment cubicle is used together with smoke detectors TBLZ-2-49-a. In the event of an error indication the
unit is designed to control dampers and stop the unit and
give an alarm. Connected damper actuators must be suitable for a 230 V supply.
3. Function control unit smoke
The control unit is designed to meet the requirements set
to provide reliable fire protection together with our smoke
detectors. Equipped with relay contactors for controlling
dampers and fans. Besides smoke alarms, the control unit
is equipped with a service alarm and error alarm relays.
In the event of a smoke alarm, a red LED lights and the
alarm relays trip at the same time.
In the event of a service alarm on the smoke detector,
the LED for the service alarm flashes quickly for 1 minute.
Then the service alarm relay is active and the LED lights
continuously. If the service alarm on the detector resets,
the relay trips and the LED starts to flash slowly: Alarm
memory.
Short-circuits and open-circuits cause fault relays and
alarm relays to activate at the same time as the respective
LED lights (open-circuit, approx. 10 seconds delay). If a
short-circuit or open-circuit recurs, the relays trip and the
respective LED starts to flash slowly: Alarm memory.
Exercising the relays: keep the reset button depressed for
5 seconds.
4. Installation
Use the four screws to mount the equipment cabinet on
the wall, unit or similar.
5. Technical Data
Supply voltage
230VAC, 50-60Hz
Power consumption
(control unit)
1.8VA
Degree of protection
IP 65
Ambient temperature
0-50°C
Dimensions (WxHxD)
175 x 125 x 100mm
Weight
740g
Specifications are subject to alteration without notice.
www.swegon.com
1
GB.TBLZ481.120614
6. Electrical Connections
The electrical connections are to be wired by a qualified
electrician in accordance with local electrical safety regulations.
Smoke function
GOLD RX/PX/CX/SD
Smoke detector terminal
Terminal
Terminals on the control
unit
25
26
54
Ext. fire alarm
55
Ext. alarm 2
52
53
GOLD LP/COMPACT
Terminals in electrical
equipment cubicle
201
202
Terminals on the control
5
unit
*
Terminal block
6
**
7
8
*Should be selected for ext. fire alarm in the micro
terminal.
**Should be selected for ext. alarm in the micro
terminal.
Function:
In the event of smoke detector B7
deploying in the duct the alarm is forwarded to GOLD/COMPACT, external
fire alarm. Damper actuator MG7 is
controlled via control unit B6.
When the smoke detectors become
dirty a service alarm occurs in control
unit B6 and is forwarded to GOLD/
COMPACT via the external alarm 2.
The alarm is reset on control unit B6 or
hand terminal P1.
2
www.swegon.com
2,2
MG7:
MG7:
Damper
actuator
Damper
actuator
In the event of more smoke
damper actuators being connected, these must be connected
in parallel in the terminal block.
B7:
Smoke detector
B7:
Smoke detector
In the event of more smoke detectors being connected, these
must be connected in series (
terminating resistor only installed
on the last smoke detector).
Specifications are subject to alteration without notice.