advertisement
Copy of marking plate:
Page 2 of 82 Report No.: 11009010 001
Summary of testing:
● The maximum normal load condition of unit as below:
1) For unit consist power supply with DC/AC inverter board type PTB-1725:
- for plastic enclosure shape type C: Operation with full brightness, max. contrast of the LCD backlight circuit, max. volume of speaker and dummy load of 2.5W for four USB ports (series A receptacle).
- for plastic enclosure shape type A: Operation with full brightness, max. contrast of the LCD backlight circuit and max. volume of speaker.
2) For unit consist power supply with DC/AC inverter board type PTB-1806:
For plastic enclosure shape type B: Operation with full brightness, max. contrast of the LCD backlight circuit and max. volume of speaker.
● The ambient was specified as 40°C by manufacture.
● This unit complied with stability test (sub-clause 4.1) for each enclosure shape (type A, B, C).
● The USB ports (for unit with plastic enclosure shape type C and consist with power supply with DC/AC inverter board type PTB-1725), output (+20.5Vdc output) of power supply with DC/AC inverter board (type
PTB-1806) and main board output (type A: P308 output connector to key control board and P306 output connector to speaker; type B: P307 output connector to key control baord and P310 output connector to speaker) were complied with the limited power source (sub-clause 2.5).
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 3 of 82
Particulars: test item vs. test requirements
Equipment mobility .......................................: Movable equipment
Operating condition .......................................:
Continuous
Mains supply tolerance (%) ...........................:
+10% / -10%
Tested for IT power systems ........................:
Yes (Norway)
IT testing, phase-phase voltage (V) .............:
IT, 230V for Norway
Class of equipment .......................................:
Class I
Mass of equipment (kg).................................: max. 5.9
Protection against ingress of water ..............: IPX0
Test case verdicts
Test case does not apply to the test object ..: N/A
Test item does meet the requirement ..........: P(ass)
Test item does not meet the requirement ....: F(ail)
Testing
Date of receipt of test item ...........................: Nov., 2006
Date(s) of performance of test .....................: Nov., 2006
General remarks
Report No.: 11009010 001
”This report is not valid as a CB Test Report unless appended by an approved CB Testing
Laboratory and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02”.
The test result presented in this report relate only to the object(s) tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory.
”(see Enclosure #)" refers to additional information appended to the report.
"(see appended table)" refers to a table appended to the report.
Throughout this report a point is used as the decimal separator.
Comments:
Summary of compliance with National Differences (for explanation of codes see below):
AR, AT, AU, BE, CH, DE, DK, FI, FR, GB, GR, HU, IL, IN, IT, KR, MY, NL, NO, PL, SE, SG, SI
AR=Argentina, AT=Austria, AU=Australia, BE=Belgium, CA=Canada, CH=Switzerland, CN=China,
DE=Germany, DK=Denmark, FI=Finland, FR=France, GB=United Kingdom, GR=Greece, HU=Hungary,
IL=Israel, IN=India, IT=Italy, KE=Kenya, KR=Korea, MY=Malaysia, NL=The Netherlands, NO=Norway,
PL=Poland, SE=Sweden, SG=Singapore, SI=Slovenia, SK=Slovakia, US=United States of America.
For National Differences see end of this test report.
Factories:
1) Lite-On Computer Technology (Dong Guan) Co., Ltd.
N. San Heng Rd., Heng Jiao Ind. Zone, Xi Chen Zone, Shi Jie Town, Dongguan, Guangdong, P.R. China
2) Dongguan shijie yuanli electronics factory
Heng Jiao Ind. Zone, Shi Jie Town, Dong Guan City, Guang Dong Province, P.R. China
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Definition of variables:
Variable:
X
Range of variable:
Can be 0-9, A-Z or blank
Page 4 of 82
Content:
Report No.:
Marketing purpose, no technical differences.
11009010 001
General product information:
The equipment model AL2002W XXXX (X can be 0-9, A-Z or blank, trade mark: “acer”) is a 20” LCD Monitor for the use in information technology equipment.
This equipment consists of following critical components:
- TFT LCD panel module
- Metal enclosure (inside the plastic enclosure, covering the switching power supply with DC/AC inverter board and function control board)
- Building-in type switching power supply with DC/AC inverter board (refer to appended table 1.5.1 for source details)
- Secondary function control board (as main board, SELV circuit; with one DVI and D-sub port)
- Plastic enclosure
- Key control board (as SELV circuits)
For unit construction deviation details, refer to below information
1). Plastic enclosure shape type A consist with following parts:
- Switching power supply with DC/AC inverter board type PTB-1725
- Metal enclosure shape type A
- Main board type A
2). Plastic enclosure shape type B consist with following parts:
- Switching power supply with DC/AC inverter board type PTB-1806
- Metal enclosure shape type B
- Main board type B
3). Plastic enclosure shape type C consist with following parts:
- Switching power supply with DC/AC inverter board type PTB-1725
- Metal enclosure shape type A
- Main board type B
- USB board
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 5 of 82 Report No.: 11009010 001
Clause
1
1.5
1.5.1
1.5.2
IEC 60950-1 / EN 60950-1
Requirement – Test
GENERAL
Components
General
Comply with IEC 60950 or relevant component standard
Evaluation and testing of components
Result – Remark
See below.
(see appended table 1.5.1)
Components, which are certified to IEC and/or national standards, are used correctly within their ratings or had been evaluated during this approval.
Verdict
P
P
P
P
P
1.5.3
1.5.4
Thermal controls
Transformers
No thermal controls provided.
Transformer used is suitable for the intended application and complies with the relevant requirements of the standard and particularly with those of
Annex C.
N/A
P
1.5.5 Interconnecting cables Interconnection cable provided with the equipment is carrying signals on energy level below
240VA.
P
1.5.6
1.5.7
1.5.7.1
1.5.7.2
1.5.7.3
1.5.7.4
1.5.8
Besides for the insulation materials there are not other requirements for the interconnection cables.
Capacitors in primary circuits ...............................: Between lines: X2 sub-class capacitor according to IEC
60384-14:1993 with 21 days damp heat test.
Between Line/Neutral to earth:
Y2 or Y1 sub-class capacitor according to IEC 60384-
14:1993.
Double insulation or reinforced insulation bridged by components
General
No such components used.
See above.
Bridging capacitors
Bridging resistors
TRF No.:IECEN60950_1B
See above.
See above.
Accessible parts See above.
Components in equipment for IT power systems Y1 or Y2 subclass capacitors according to IEC 60384-14:1993 provided between phase and earth are rated 250Vac min.
P
N/A
N/A
N/A
N/A
N/A
P
TRF originator: SGS Fimko
1.7
1.7.1
1.7.2
1.7.3
1.7.4
1.7.5
Clause
1.6
1.6.1
1.6.2
1.6.3
1.6.4
Page 6 of 82 Report No.: 11009010 001
IEC 60950-1 / EN 60950-1
Requirement – Test
Power interface
AC power distribution systems
Result – Remark
Input current
Voltage limit of hand-held equipment
TN power system considered.
IT power system for Norway.
(see appended table 1.6.2)
This appliance is not a handheld equipment.
Neutral conductor The neutral is not identified in the equipment. Basic insulation for rated voltage between earthed parts and primary phases.
Verdict
P
P
P
N/A
P
Marking and instructions
Power rating See below.
Rated voltage(s) or voltage range(s) (V) .............: 100-240V~
Symbol for nature of supply, for d.c. only .............: AC mains only.
Rated frequency or rated frequency range (Hz) ..: 50/60Hz
Rated current (mA or A) ......................................: 1.5A
Manufacturer’s name or trademark or identification Acer mark .....................................................................:
Type/model or type reference...............................: AL2002W XXXX (X can be 0-9,
A-Z or blank)
P
P
P
N/A
P
P
P
P
Symbol for Class II equipment only .....................: Class I equipment.
Other symbols ......................................................: Other symbols do not give rise to misunderstanding.
Certification marks ...............................................: See copy of the marking plates for the safety marks.
Safety instructions User’s manual provided.
Short duty cycles Equipment is designed for continuous operation.
Supply voltage adjustment ...................................: Full range circuit design.
Methods and means of adjustment; reference to installation instructions .........................................:
No such supply voltage adjustment.
Power outlets on the equipment ..........................: No standard power outlets provided.
N/A
P
N/A
P
N/A
N/A
N/A
N/A
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Clause
1.7.6
1.7.7
1.7.7.1
1.7.7.2
1.7.7.3
1.7.8
1.7.8.1
1.7.8.2
1.7.8.3
1.7.8.4
1.7.9
1.7.10
1.7.11
1.7.12
Page 7 of 82 Report No.: 11009010 001
IEC 60950-1 / EN 60950-1
Requirement – Test Result – Remark
Fuse identification (marking, special fusing characteristics, cross-reference) ............................:
Fuse marking label adjacent to the fuse holder on PCB:
F801 T3.15AH 250V
CAUTION: FOR CONTINUED
PROTECTION AGAINST A RISK OF
FIRE REPLACE ONLY WITH SAME
TYPE AND RATINGS OF FUSE.
Wiring terminals See below.
Protective earthing and bonding terminals ..........: Appliance inlet is provided. The symbol 60417-1-IEC-5019 was located on PCB.
Terminal for a.c. mains supply conductors The equipment is provided with appliance inlet, which is for connection of a detachable type power supply cord.
Terminals for d.c. mains supply conductors No such conductors.
Controls and indicators See below.
Identification, location and marking .....................: The marking and indication of the stand-by switch is located that indication of function is clearly.
Colours ...............................................................: The colours of the Power LED indicator are as follows:
- Green for ON condition
- Amber for stand-by condition
Symbols according to IEC 60417 .........................: Marking according 60417-1-
IEC- 5009 (line half inside circle) for stand-by switch.
Verdict
P
P
P
N/A
N/A
P
P
P
P
Markings using figures ........................................: No indicators for different positions of control.
Isolation of multiple power sources .....................: Single power source only.
IT power distribution systems For Norway compliance has to be evaluated during the national approved.
Thermostats and other regulating devices Neither thermostats nor other regulating devices provided.
Language(s) .........................................................: User’s manual provided in
English and German. Marking label provided in English.
Versions in other languages will be provided during national approval.
N/A
N/A
N/A
N/A
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 8 of 82 Report No.: 11009010 001
Clause
1.7.13
1.7.14
1.7.15
1.7.16
1.7.17
2
2.1
2.1.1
2.1.1.1
2.1.1.2
2.1.1.3
2.1.1.4
Requirement – Test
Durability
IEC 60950-1 / EN 60950-1
Result – Remark
The marking plate was subjected to the permanence of marking test. The marking plate was rubbed with cloth soaked with water for 15 s and then again for 15 s with the cloth soaked with petroleum spirit.
After this test there was no damage to the marking. The marking on the label did not fade. There was no curling of the marking.
Removable parts
Replaceable batteries
No removable parts provided.
No batteries provided.
Language(s)..........................................................:
Operator access with a tool ..................................: There are no any operator accessible areas with a tool defined.
Equipment for restricted access locations ............: No restricted access locations.
PROTECTION FROM HAZARDS
Protection from electric shock and energy hazards
Protection in operator access areas No hazards (electrical shock or energy hazards) in operator accessible areas.
Access to energized parts See sub clause 2.1.1
Test by inspection ................................................: No access with test finger to any parts with only basic insulation to ELV or hazardous voltage. Any hazardous parts accessible are unlikely.
Test with test finger ..............................................: See above.
Test with test pin ..................................................: See above.
Test with test probe .............................................: No TNV circuit.
Battery compartments .........................................: No battery compartments provided.
Access to ELV wiring No ELV wiring in operator access area.
Working voltage (Vpeak or Vrms); minimum distance (mm) through insulation
Access to hazardous voltage circuit wiring No hazardous voltage circuit in operator access area.
Verdict
P
N/A
N/A
N/A
N/A
P
P
P
P
P
P
P
N/A
N/A
N/A
N/A
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 9 of 82 Report No.: 11009010 001
Clause
2.1.1.5
2.1.1.6
2.1.1.7
2.1.2
2.1.3
Requirement – Test Result – Remark
Energy hazards ....................................................: Energy does not exceed 240 VA between any two points at accessible parts.
Verdict
P
Manual controls
IEC 60950-1 / EN 60950-1
No conductive shafts of operating knobs and handles.
N/A
P Discharge of capacitors in equipment No risk of electric shock.
Time-constant (s); measured voltage (V) .............: (See appended table)
Protection in service access areas No maintenance works in operation mode necessary.
Protection in restricted access locations The unit is not limited to be used in restricted access locations.
N/A
N/A
2.2
2.2.1
2.2.2
2.2.3
2.2.3.1
2.2.3.2
2.2.3.3
2.2.4
SELV circuits
General requirements See below.
Voltages under normal conditions (V) ..................: Between any conductor of the
SELV circuits, 42.4Vpeak or
60Vd.c. are not exceeded.
Result see appended table
2.2.2.
Voltages under fault conditions (V).......................: Single fault did not cause excessive voltage in SELV circuits. The limits of 71Vpeak and 120Vd.c. were not exceed.
Furthermore, the SELV limits
(see sub clause 2.2.2) were not exceeded for longer than 0.2 seconds. Results see appended tables 2.2.2 and
2.2.3.
Separation by double insulation or reinforced insulation (method 1)
Separation by earthed screen (method 2)
Method 1 used.
Method 2 used.
Protection by earthing of the SELV circuit
(method 3)
Connection of SELV circuits to other circuits........: See sub clause 2.2.2, 2.2.3. and 2.4.
2.3
2.3.1
2.3.2
TNV circuits
Limits
Type of TNV circuits .............................................:
Separation from other circuits and from accessible parts
TRF No.:IECEN60950_1B
P
P
P
P
P
P
N/A
P
N/A
N/A
N/A
TRF originator: SGS Fimko
Clause
2.3.3
2.3.4
2.3.5
2.4
2.4.1
2.4.2
2.4.3
Page 10 of 82
Connection of TNV circuits to other circuits
Insulation employed ..............................................:
Test for operating voltages generated externally
Report No.: 11009010 001
IEC 60950-1 / EN 60950-1
Requirement – Test
Insulation employed ..............................................:
Result – Remark
Separation from hazardous voltages
Insulation employed ..............................................:
Limited current circuits
General requirements
Limit values
Considered for output of
DC/AC inverter.
See appended table 2.4.2.
Frequency (Hz) .....................................................: See appended table 2.4.2.
Measured current (mA).........................................: The peak drop voltage was measured with an oscilloscope at a 2kΩ non-inductive resistor.
Results see appended table
2.4.2.
Measured voltage (V) ...........................................: 1) 1.36kV (for power supply with
DC/AC inverter board type PTB-
1725)
2) 3.34kV (for power supply with
DC/AC inverter board type PTB-
1725)
Measured capacitance (µF) ..................................: 1) 22pF (for power supply with
DC/AC inverter board type PTB-
1725)
2) 10pF (for power supply with
DC/AC inverter board type PTB-
1725)
Connection of limited current circuits to other circuits
Complies.
Verdict
N/A
N/A
N/A
P
P
P
P
2.5 Limited power sources
For power supply with DC/AC inverter board type PTB-1806: +20.5Vdc output of power supply with DC/AC inverter board and P310/P307 output connectors of main board type B were complied with L.P.S test.
For main board types A, which consist with power supply with DC/AC inverter board type PTB-1725, P308/P306 output connectors were complied with L.P.S test.
For USB ports, which consist with power supply with DC/AC inverter board type
PTB-1725, also were complied with L.P.S test.
Inherently limited output
Impedance limited output
TRF No.:IECEN60950_1B
P
N/A
N/A
TRF originator: SGS Fimko
2.6.3
2.6.3.1
2.6.3.2
2.6.3.3
2.6
2.6.1
Clause
Page 11 of 82 Report No.: 11009010 001
IEC 60950-1 / EN 60950-1
Requirement – Test
Overcurrent protective device limited output
Result – Remark
Regulating network limited output under normal operating and single fault condition
For USB ports, +20.5Vdc output of power supply with
DC/AC inverter board (type
PTB-1806), P308/P306 output connector (main board type A) and P310/P307 output connector (main board type B) were complied. See appended table for test result.
Regulating network limited output under normal operating conditions and overcurrent protective device limited output under single fault condition
Output voltage (V), output current (A), apparent power (VA)............................................................:
Results see appended table
2.5.
Current rating of overcurrent protective device (A)
Verdict
N/A
P
N/A
2.6.2
Provisions for earthing and bonding
Protective earthing Appliance inlet (with PE pin) reliable connection to PCB and also with screw to metal enclosure.
One protective bonding conductor (green/yellow wire) connected to the approved appliance inlet (hooked and soldered) and to the PCB via solder pin and soldered.
Functional earthing Secondary functional earthing is separated to primary by double or reinforce insulation or by basic insulation and protective earthing. No green/yellow wire used for functional earthing.
See below. Protective earthing and protective bonding conductors
General No power supply cord provided.
See sub clause 2.6.3.4.
Size of protective earthing conductors
Rated current (A), cross-sectional area (mm
2
),
AWG .....................................................................:
No power cord provided.
Size of protective bonding conductors Evaluation by test. Rated current below 16A.
P
P
P
P
P
N/A
N/A
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Clause
2.6.3.4
2.6.3.5
2.6.4
2.6.4.1
2.6.4.2
2.6.4.3
2.6.5
2.6.5.1
2.6.5.2
2.6.5.3
2.6.5.4
2.6.5.5
2.6.5.6
Page 12 of 82 Report No.: 11009010 001
IEC 60950-1 / EN 60950-1
Requirement – Test
Rated current (A), cross-sectional area (mm
2
),
AWG .....................................................................:
Result – Remark
Resistance (Ω) of earthing conductors and their terminations, test current (A) ................................:
(Refer to appended table
2.6.3.4).
Colour of insulation ...............................................: The insulation of the protective bonding conductor is green/yellow wire.
Terminals See below.
Verdict
P
P
P
General
Integrity of protective earthing
See sub clause 2.6.1.
Protective earthing and bonding terminals The earth terminal of appliance inlet is considered as the protective earthing terminal and was evaluated by sub clause
2.6.3.4.
Rated current (A), type and nominal thread diameter (mm) ......................................................:
Evaluation by test. Rated current below 16A.
Separation of the protective earthing conductor from protective bonding conductors
Only protective earthing conductor used in this equipment.
See below.
Interconnection of equipment
Components in protective earthing conductors and protective bonding conductors
Disconnection of protective earth
This unit has it's own earthing connection. Any other units connected via the output shall be provided SELV only.
No switch or overcurrent protective device in protective earthing or bonding conductor.
Appliance inlet provided as disconnection device.
Parts that can be removed by an operator
N/A
P
P
P
P
P Plug or inlet, the earth connection is made before and broken after the hazardous voltage. No other operator removable parts provided.
P
P
Parts removed during servicing P It is not necessary to disconnect the earth connection except for the removing of the earthed part itself.
Corrosion resistance All safety earthing connections in compliance with Annex J.
P
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Clause
2.6.5.7
2.6.5.8
Page 13 of 82 Report No.: 11009010 001
IEC 60950-1 / EN 60950-1
Requirement – Test
Screws for protective bonding
Result – Remark
Only ISO thread screw used in metal chassis for protective bonding. Metal thickness at least twice the pitch of the screw.
No self-tapping or spaced thread screws.
Reliance on telecommunication network or cable distribution system
No TNV circuits provided.
Verdict
N/A
N/A
2.7
2.7.1
2.7.2
2.7.3
2.7.4
2.7.5
2.7.6
2.8
2.8.1
2.8.2
2.8.3
2.8.4
2.8.5
2.8.6
2.8.7
2.8.7.1
Overcurrent and earth fault protection in primary circuits
Basic requirements Equipment relies on or circuit breaker of the wall outlet installation protection of the building installation in regard to
L to N short circuit and earth fault. Over current protection is provided by one built-in fuse.
Instructions when protection relies on building installation
Faults not covered in 5.3
Pluggable equipment type A.
The protection devices are well dimensioned and mounted.
Short-circuit backup protection Pluggable equipment type A, the building installation is considered as providing short circuit backup protection.
Number and location of protective devices ..........: One built-in fuse provided on the mains conductor.
Protection by several devices One fuse provided.
Warning to service personnel ...............................: No service work necessary.
Safety interlocks
General principles
Protection requirements
Inadvertent reactivation
Fail-safe operation
Moving parts
Overriding
Switches and relays
Contact gaps (mm) ..............................................:
TRF No.:IECEN60950_1B
P
P
N/A
P
P
P
N/A
N/A
TRF originator: SGS Fimko
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Page 14 of 82 Report No.: 11009010 001
Clause
2.8.7.2
2.8.7.3
Requirement – Test
Overload test
Endurance test
IEC 60950-1 / EN 60950-1
Result – Remark
2.8.7.4
2.8.8
Electric strength test
Mechanical actuators
2.9
2.9.1
Electrical insulation
Properties of insulating materials
Humidity conditioning
Natural rubber, asbestos or hygroscopic materials are not used.
Carried out for 120 hrs.
Humidity (%) ........................................................: 95% R.H.
2.9.2
2.9.3
Temperature (°C) .................................................: 40°C
Grade of insulation Adequate levels of safety insulation were provided and maintained to comply with the requirements of this standard.
2.10
2.10.1
2.10.2
Clearances, creepage distances and distances through insulation
General See below.
Determination of working voltage The rms and the peak voltages were measured for the unit.
The unit was connected to a
240V TN power system.
Results see appended table
2.10.2.
2.10.3 Clearances See below, Annex G was not considered.
2.10.3.1
2.10.3.2
General
Clearances in primary circuits
2.10.3.3 Clearances in secondary circuits
Annex F and minimum clearances considered.
(see appended table 2.10.3 and 2.10.4)
Sub clause 5.3.4 considered.
2.10.3.4
2.10.4
Measurement of transient voltage levels Normal transient voltage considered (overvoltage category II for primary circuits).
Creepage distances (see appended table 2.10.3 and 2.10.4)
CTI tests ...............................................................: CTI rating for all materials of min. 100, see appended table
C.2 for details.
Verdict
N/A
N/A
N/A
N/A
P
P
P
P
P
P
P
P
P
P
N/A
N/A
P
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 15 of 82 Report No.: 11009010 001
Clause
2.10.5
Requirement – Test
Solid insulation
IEC 60950-1 / EN 60950-1
Result – Remark
See below.
2.10.5.1 Minimum distance through insulation (see appended table 2.10.5)
Verdict
P
P
2.10.5.2 Thin sheet material The thin sheet materials of polyester tape used in transformer T801.
Number of layers (pcs) .........................................: 3 layers.
Electric strength test
2.10.5.3 Printed boards
(see appended table 5.2)
P
N/A
N/A
Distance through insulation
Electric strength test for thin sheet insulating material
Number of layers (pcs) .........................................:
2.10.5.4 Wound components
2.10.6
Number of layers (pcs) .........................................:
Two wires in contact inside wound component; angle between 45° and 90° ..................................:
Coated printed boards
2.10.6.1 General
No coated printed boards.
2.10.6.2
2.10.6.3
Sample preparation and preliminary inspection
Thermal cycling
2.10.6.4 Thermal ageing (°C) .............................................:
2.10.6.5 Electric strength test
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A 2.10.6.6 Abrasion resistance test
Electric strength test
2.10.7
2.10.8
2.10.9
2.10.10
Enclosed and sealed parts ...................................: No hermetically sealed components.
Temperature T1=T2 + Tma – Tamb +10K (°C)....:
Spacings filled by insulating compound................: Certified photo-couplers used.
No other components applied for.
Electric strength test
Component external terminations
Insulation with varying dimensions
See appended table 2.10.3 and
2.10.4.
No reduction of distances considered.
N/A
N/A
P
P
N/A
3 WIRING, CONNECTIONS AND SUPPLY P
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 16 of 82 Report No.: 11009010 001
Clause
3.1
3.1.1
3.1.2
3.1.3
3.1.4
3.1.5
3.1.6
3.1.7
3.1.8
3.1.9
3.1.10
3.2
3.2.1
3.2.1.1
3.2.1.2
3.2.2
3.2.3
IEC 60950-1 / EN 60950-1
Requirement – Test
General
Current rating and overcurrent protection
Result – Remark
Protection against mechanical damage
All internal wires are UL recognized wiring, which is
PVC insulated, rated VW-1, min. 80°C, 300V. Internal wiring gauge is suitable for current intended to be carried.
Wires do not touch sharp edges and heatsinks, which could damage the insulation.
Securing of internal wiring
Insulation of conductors
Internal wires are secured by solder, cable tie or other mechenical connect so that a loosening of the terminal connection is unlikely.
The insulation of the individual conductors is suitable for the application and the working voltage. For the insulation material see 3.1.1.
Beads and ceramic insulators Not used.
Screws for electrical contact pressure No electrical contact pressure by screwed connection.
Insulating materials in electrical connections
Self-tapping and spaced thread screws
All current carrying connections made by metal to metal.
No self-tapping or spaced thread screws used.
Termination of conductors All conductors are reliably secured by solder-pin or glued or other mechanical fixing means.
10 N pull test
Sleeving on wiring
Complied.
No sleeving used as supplementary insulation function.
Connection to an a.c. mains supply or a d.c. mains supply
Means of connection ............................................: See below.
Connection to an a.c. mains supply Appliance inlet used.
Connection to a d.c. mains supply
Multiple supply connections
Permanently connected equipment
Only AC mains supply.
Only one mains connection.
Not permanently connected equipment.
Verdict
P
P
P
P
P
N/A
N/A
P
N/A
P
P
N/A
P
P
P
N/A
N/A
N/A
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Clause
3.2.4
3.2.5
3.2.5.1
3.2.5.2
3.2.6
3.2.7
3.2.8
3.2.9
Page 17 of 82 Report No.: 11009010 001
IEC 60950-1 / EN 60950-1
Requirement – Test
Number of conductors, diameter (mm) of cable and conduits ........................................................:
Result – Remark
Appliance inlets
Power supply cords
The appliance inlet complies with IEC 60320-1. The power cord can be inserted without difficulties and does not support the unit.
Not provided.
AC power supply cords Not provided.
Verdict
P
N/A
N/A
Type ......................................................................:
Rated current (A), cross-sectional area (mm
2
),
AWG .....................................................................:
DC power supply cords Not connect to DC mains.
N/A
N/A Cord anchorages and strain relief
Mass of equipment (kg), pull (N) ........................:
No non-detachable power supply cords provided.
Longitudinal displacement (mm) ..........................:
P Protection against mechanical damage
Cord guards
D (mm); test mass (g) ..........................................:
No parts under this unit likely to damage the power supply cords. Enclosure without sharp edges.
No cord guard provided. N/A
Radius of curvature of cord (mm).........................:
Supply wiring space Not permanently connected and without non-detachable power supply cord.
N/A
3.3
3.3.1
3.3.2
3.3.3
3.3.4
3.3.5
Wiring terminals for connection of external conductors
Neither permanently connected nor non-detachable equipment.
Wiring terminals
Connection of non-detachable power supply cords
Screw terminals
Conductor sizes to be connected
Rated current (A), cord/cable type, cross-sectional area (mm2) ...........................................................:
Wiring terminal sizes
Rated current (A), type and nominal thread diameter (mm) .....................................................:
TRF No.:IECEN60950_1B
N/A
N/A
N/A
N/A
N/A
N/A
TRF originator: SGS Fimko
3.4.5
3.4.6
3.4.7
3.4.8
3.4.9
3.4.10
Clause
3.3.6
3.3.7
3.3.8
3.4
3.4.1
3.4.2
3.4.3
3.4.4
3.4.11
3.5
3.5.1
3.5.2
3.5.3
4
4.1
Page 18 of 82 Report No.: 11009010 001
Requirement – Test
Wiring terminals design
Grouping of wiring terminals
Stranded wire
IEC 60950-1 / EN 60950-1
Result – Remark Verdict
N/A
N/A
N/A
Disconnection from the mains supply
General requirement
Disconnect devices
Permanently connected equipment
Parts which remain energized
Switches in flexible cords
Single-phase equipment and d.c. equipment
Three-phase equipment
See below.
Appliance inlet used as disconnect divice.
Not permanently connected equipment.
When the power cord is removed from the inlet no remaining parts with hazardous voltage in the equipment.
No power supply cords provided.
Both poles are disconnected simultaneously.
Single-phase equipment.
Switches as disconnect devices See sub clause 3.4.2.
Plugs as disconnect devices See sub clause 3.4.2.
Interconnected equipment Interconnection of the power supply to the other PCBs in the equipment by secondary output cable only.
Multiple power sources Only one supply connection provided.
Interconnection of equipment
General requirements
ELV circuits as interconnection circuits
See below.
Types of interconnection circuits ..........................: Interconnection circuits of
SELV through the connector.
No ELV interconnection.
PHYSICAL REQUIREMENTS
Stability
P
P
P
N/A
P
N/A
P
N/A
N/A
N/A
N/A
N/A
P
P
P
N/A
P
P
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Clause
Page 19 of 82 Report No.: 11009010 001
Requirement – Test
Angle of 10°
IEC 60950-1 / EN 60950-1
Result – Remark
The equipment does not overbalance when tilted to 10 degrees (for all type of base stand).
Test: force (N).......................................................: Equipment is not a floor standing unit.
Verdict
P
N/A
4.2
4.2.1
4.2.2
4.2.3
4.2.4
4.2.5
4.2.6
4.2.7
4.2.8
4.2.9
4.2.10
Mechanical strength
General See below. After the tests, the equipment complies with the requirements of sub-clauses
2.1.1, 2.6.1 and 2.10.
Steady force test, 10 N
Steady force test, 30 N
10N applied to components other than parts serving as an enclosure.
Steady force test, 250 N 250N applied to internal metal enclosure at top, side, bottom and rear. No energy or other hazards.
Impact test No hazard as result from steel ball impact test for plastic enclosure.
See above. Fall test
Swing test See above.
Drop test
Stress relief test After the test at temperature of
70.4°C for plastic enclosure, no shrinkage, distortion or loosening of any enclosure part was noticeable on the equipment for all plastic enclosure materials.
Cathode ray tubes
Picture tube separately certified ...........................:
No CRT provided.
High pressure lamps No high pressure lamps provided.
Wall or ceiling mounted equipment; force (N) .....: Equipment is not a wall or ceiling mounted equipment.
4.3
4.3.1
Design and construction
Edges and corners
TRF No.:IECEN60950_1B
The edges and corners are rounded and smoothed.
P
P
P
N/A
P
P
P
P
N/A
P
N/A
N/A
N/A
N/A
P
P
TRF originator: SGS Fimko
Page 20 of 82 Report No.: 11009010 001
Clause
4.3.2
4.3.3
4.3.4
4.3.5
4.3.6
4.3.7
4.3.8
IEC 60950-1 / EN 60950-1
Requirement – Test Result – Remark
Handles and manual controls; force (N) ...............: None, which could cause hazards.
Adjustable controls No safety relevant adjustable controls provided.
Securing of parts
Heating elements in earthed equipment
Batteries
Electrical and mechanical connections can be expected to withstand usual mechanical stress. No loosening of clearance or creepage impairing distances likely to occur.
Connection of plugs and sockets No mismatch of connectors, plugs or socket possible.
Direct plug-in equipment
Dimensions (mm) of mains plug for direct plug-in :
Not direct plug-in type.
Torque and pull test of mains plug for direct plug-in; torque (Nm); pull (N) ................................:
No heating elements.
No batteries provided.
4.3.9
4.3.10
4.3.11
Oil and grease
Dust, powders, liquids and gases
Containers for liquids or gases
No oil or grease inside the equipment.
Equipment intended use not considered to be exposed to these.
No container for liquid or gas.
4.3.12 Flammable liquids.................................................: No flammable liquid.
Quantity of liquid (l) ...............................................:
4.3.13
Flash point (°C).....................................................:
Radiation; type of radiation ..................................: See below.
4.3.13.1 General No radiation is generated inside the equipment. The energy of the indicator LED is far below the limit for Class 1 LED products.
4.3.13.2 Ionizing radiation
Measured radiation (pA/kg) .................................:
Measured high-voltage (kV) ................................:
Measured focus voltage (kV) ...............................:
CRT markings .....................................................:
4.3.13.3 Effect of ultraviolet (UV) radiation on materials
Verdict
N/A
N/A
P
P
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
P
P
N/A
N/A
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 21 of 82 Report No.: 11009010 001
Clause
IEC 60950-1 / EN 60950-1
Requirement – Test
Part, property, retention after test, flammability classification ........................................................:
Result – Remark
4.3.13.4 Human exposure to ultraviolet (UV) radiation ......:
Verdict
N/A
N/A
4.3.13.5 Laser (including LEDs) No ionizing radiation or laser or flammable liquids presents. LED power is far below LED Class 1 limit.
Laser class ...........................................................: See above.
4.3.13.6 Other types ..........................................................: Not used.
4.4 Protection against hazardous moving parts
P
N/A
N/A
4.4.1
4.4.2
General
Protection in operator access areas
N/A
N/A
4.4.3 Protection in restricted access locations N/A
4.4.4 N/A
4.5
4.5.1
4.5.2
Protection in service access areas
Thermal requirements
Maximum temperatures (see appended table 4.5.1)
Normal load condition per Annex L.......................: Considered.
Resistance to abnormal heat Phenolic materials used in where parts at hazardous voltage are directly mounted on. Phenolic is accepted without further testing. Others see appended table.
P
P
P
P
4.6
4.6.1
P
P
4.6.2
4.6.3
4.6.4
4.6.5
Openings in enclosures
Top and side openings See below.
Dimensions (mm) ................................................: (see appended table)
Bottoms of fire enclosures See below.
Construction of the bottom ...................................: (see appended table)
Doors or covers in fire enclosures No doors or covers provided.
Openings in transportable equipment Equipment not transportable type.
Adhesives for constructional purposes
Conditioning temperature (°C)/time (weeks) ........:
No adhesives used.
P
N/A
N/A
N/A
4.7 Resistance to fire P
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 22 of 82 Report No.: 11009010 001
Clause
4.7.1
4.7.2
4.7.2.1
4.7.2.2
4.7.3
4.7.3.1
4.7.3.2
4.7.3.3
4.7.3.4
4.7.3.5
4.7.3.6
IEC 60950-1 / EN 60950-1
Requirement – Test Result – Remark
Reducing the risk of ignition and spread of flame See below.
Method 1, selection and application of components wiring and materials
Method 2, application of all of simulated fault condition tests
Conditions for a fire enclosure
Materials with suitable flammability classes are used.
Not used.
Parts requiring a fire enclosure
See below.
Fire enclosure is required if at least one of the following is provided:
● components in primary
Parts not requiring a fire enclosure
● components in secondary
(not supplied by LPS)
● insulated wiring
Fire enclosure is required.
Key control board and speaker were supplied by limited power source and components were mounted on V-1 PCB which outside the metal enclosure.
Materials
General PCB rated accordingly. For details see table 1.5.1.
Materials for fire enclosures Internal metal enclosure was considered as fire enclosure.
Materials for components and other parts outside fire enclosures
The other part (base stand) outside of fire enclosure used material rated HB or better.
Materials for components and other parts inside fire enclosures
Internal components except small parts are V-2 or better.
Materials for air filter assemblies No air filters provided.
Materials used in high-voltage components No high voltage components provided.
Verdict
P
P
N/A
P
P
P
P
P
P
P
P
N/A
N/A
5
5.1
5.1.1
5.1.2
5.1.3
5.1.4
ELECTRICAL REQUIREMENTS AND SIMULATED ABNORMAL CONDITIONS
Touch current and protective conductor current
General
Equipment under test (EUT)
See sub-clauses 5.1.2 to 5.1.6.
EUT has only one mains connection.
Test circuit
Application of measuring instrument
Equipment of figure 5A used.
See appended table 5.1.6.
TRF No.:IECEN60950_1B
P
P
P
P
P
P
TRF originator: SGS Fimko
5.1.6
5.1.7
5.1.8
5.1.8.2
5.2
5.2.1
5.2.2
5.3
5.3.1
5.3.2
5.3.3
Clause
5.1.5
5.1.8.1
Page 23 of 82 Report No.: 11009010 001
Requirement – Test
Test procedure
IEC 60950-1 / EN 60950-1
Result – Remark
The touch current was measured from mains to metal enclosure, output connector and plastic enclosures with metal foil.
Verdict
P
Test measurements See appended table 5.1.6.
Test voltage (V) ...................................................: See above.
P
Measured touch current (mA) ..............................: See above.
Max. allowed touch current (mA) .........................: See above.
Measured protective conductor current (mA) ......:
Max. allowed protective conductor current (mA) .:
Equipment with touch current exceeding 3.5 mA : Touch current does not exceed
3.5mA.
Touch currents to and from telecommunication networks and cable distribution systems and from telecommunication networks
No TNV circuit connection.
Limitation of the touch current to a telecommunication network and a cable distribution system
Test voltage (V) ...................................................:
N/A
N/A
N/A
Measured touch current (mA) ..............................:
Max. allowed touch current (mA) .........................:
Summation of touch currents from telecommunication networks ................................:
No TNV circuit connection.
N/A
Electric strength
General
Test procedure
Abnormal operating and fault conditions
Protection against overload and abnormal operation
Motors
Transformers
TRF No.:IECEN60950_1B
(see appended table 5.2)
(see appended table 5.2)
See below.
No motors used.
With the overload and shorted output of the transformer, no high temperature of the transformer was recorded.
Results of the overload and short-circuit tests see appended table 5.3 and Annex C.
P
P
P
P
P
N/A
P
TRF originator: SGS Fimko
Page 24 of 82 Report No.: 11009010 001
Clause
5.3.4
5.3.5
5.3.6
5.3.7
5.3.8
IEC 60950-1 / EN 60950-1
Requirement – Test Result – Remark
Functional insulation .............................................: Method c). Test results see appended table 5.3.
Electromechanical components No electromechanical component provided.
Simulation of faults Ventilation blocked: Results see appended table.
Short and open circuit test for power supply board. Result see appended table.
Verdict
P
N/A
P
Unattended equipment N/A
Compliance criteria for abnormal operating and fault conditions
None of the listed components was provided.
No fire occurs. No molten metal was emitted. Electric strength tests primary to secondary and primary to earth were passed.
P
6
6.1
6.1.1
6.1.2
6.1.2.1
6.1.2.2
6.2
6.2.1
6.2.2
6.2.2.1
6.2.2.2
6.2.2.3
6.3
CONNECTION TO TELECOMMUNICATION NETWORKS
Protection of telecommunication network service persons, and users of other equipment connected to the network, from hazards in the equipment
Protection from hazardous voltages
Separation of the telecommunication network from earth
Requirements
Test voltage (V) ...................................................:
Current in the test circuit (mA) ............................:
Exclusions.............................................................:
Protection of equipment users from overvoltages on telecommunication networks
Separation requirements
Electric strength test procedure
Impulse test
Steady-state test
Compliance criteria
Protection of the telecommunication wiring system from overheating
Max. output current (A) .........................................:
Current limiting method ........................................:
CONNECTION TO CABLE DISTRIBUTION SYSTEMS 7
TRF No.:IECEN60950_1B
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
TRF originator: SGS Fimko
A.2.1
A.2.2
A.2.3
A.2.4
A.2.5
A.2.6
A
A.1
A.1.1
A.1.2
A.1.3
A.1.4
A.1.5
A.1.6
A.2
7.2
7.3
7.3.1
7.3.2
7.3.3
Clause
7.1
Page 25 of 82 Report No.: 11009010 001
Requirement – Test
IEC 60950-1 / EN 60950-1
Result – Remark
Protection of cable distribution system service persons, and users of other equipment connected to the system, from hazardous voltages in the equipment
Protection of equipment users from overvoltages on the cable distribution system
Insulation between primary circuits and cable distribution systems
General
Voltage surge test
Impulse test
ANNEX A, TESTS FOR RESISTANCE TO HEAT AND FIRE
Flammability test for fire enclosures of movable equipment having a total mass exceeding 18 kg, and of stationary equipment (see 4.7.3.2)
Samples................................................................:
Wall thickness (mm) .............................................:
Conditioning of samples; temperature (°C) ..........:
Mounting of samples ............................................:
Test flame (see IEC 60695-11-3)
Flame A, B, C or D ...............................................:
Test procedure
Compliance criteria
Sample 1 burning time (s) ....................................:
Sample 2 burning time (s) ....................................:
Sample 3 burning time (s) ....................................:
Flammability test for fire enclosures of movable equipment having a total mass not exceeding 18 kg, and for material and components located inside fire enclosures
(see 4.7.3.2 and 4.7.3.4)
Samples, material .................................................:
Wall thickness (mm) .............................................:
Conditioning of samples
Mounting of samples ...........................................:
Test flame (see IEC 60695-11-4)
Flame A, B or C ...................................................:
Test procedure
Compliance criteria
Verdict
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
B.7
B.7.1
B.7.2
B.7.3
B.8
B.9
B.10
B.2
B.3
B.4
B.5
B.1
B.6
Clause
A.2.7
A.3
A.3.1
A.3.2
A.3.3
B
Page 26 of 82 Report No.: 11009010 001
IEC 60950-1 / EN 60950-1
Requirement – Test
Sample 1 burning time (s) ....................................:
Result – Remark
Sample 2 burning time (s) ....................................:
Sample 3 burning time (s) ....................................:
Alternative test acc. to IEC 60695-2-2, cl. 4 and 8
Sample 1 burning time (s) ....................................:
Sample 2 burning time (s) ....................................:
Sample 3 burning time (s) ....................................:
Hot flaming oil test (see 4.6.2)
Mounting of samples
Test procedure
Compliance criterion
ANNEX B, MOTOR TESTS UNDER ABNORMAL CONDITIONS (see 4.7.2.2 and
5.3.2)
General requirements
Position ................................................................:
Manufacturer ........................................................:
Type .....................................................................:
Rated values .......................................................:
Test conditions
Maximum temperatures
Running overload test
Locked-rotor overload test
Test duration (days) .............................................:
Electric strength test: test voltage (V) ..................:
Running overload test for d.c. motors in secondary circuits
Locked-rotor overload test for d.c. motors in secondary circuits
Test procedure
Alternative test procedure; test time (h)................:
Electric strength test
Test for motors with capacitors
Test for three-phase motors
Test for series motors
Operating voltage (V) ...........................................:
Verdict
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Clause
Page 27 of 82 Report No.: 11009010 001
IEC 60950-1 / EN 60950-1
Requirement – Test
ANNEX C, TRANSFORMERS (see 1.5.4 and 5.3.3)
Result – Remark
Position ................................................................: T801
Manufacturer ........................................................: (see appended table C.2)
Type .....................................................................: (see appended table C.2)
Rated values .......................................................: Class B
Method of protection .............................................: By the circuit design.
Overload test (see appended table 5.3)
Insulation (see appended table C.2)
Protection from displacement of windings ............: By additional insulation tape.
Verdict
C
C.1
C.2
D
D.1
D.2
G
G.1
G.2
G.2.1
G.2.2
G.3
G.4
G.5
G.6
E
F
H
ANNEX D, MEASURING INSTRUMENTS FOR TOUCH-CURRENT TESTS
(see 5.1.4)
Measuring instrument
Alternative measuring instrument
See sub clause 5.1.3 and 5.1.4
ANNEX E, TEMPERATURE RISE OF A WINDING (see 1.4.13)
ANNEX F, MEASUREMENT OF CLEARANCES AND CREEPAGE DISTANCES
(see 2.10)
Summary of the procedure for determining minimum clearances
ANNEX G, ALTERNATIVE METHOD FOR DETERMINING MINIMUM
CLEARANCES
Determination of mains transient voltage (V) .......:
AC mains supply
DC mains supply
Determination of telecommunication network transient voltage (V)..............................................:
Determination of required withstand voltage (V)...:
Measurement of transient levels (V).....................:
Determination of minimum clearances .................:
ANNEX H, IONIZING RADIATION (see 4.3.13)
TRF No.:IECEN60950_1B
P
P
N/A
N/A
P
N/A
TRF originator: SGS Fimko
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
P
P
P
P
Page 28 of 82 Report No.: 11009010 001
L.1
L.2
L.3
L.4
L.5
L.6
L.7
M
M.1
M.2
M.3
M.3.1
M.3.1.1
M.3.1.2
M.3.1.3
M.3.1.4
M.3.2
M.3.2.1
Clause
J
K
K.1
K.2
K.3
K.4
K.5
K.6
L
IEC 60950-1 / EN 60950-1
Requirement – Test Result – Remark
ANNEX J, TABLE OF ELECTROCHEMICAL POTENTIALS (see 2.6.5.6)
Metal used ...........................................................: Complied.
ANNEX K, THERMAL CONTROLS (see 1.5.3 and 5.3.7)
Making and breaking capacity
Thermostat reliability; operating voltage (V) .........:
Thermostat endurance test; operating voltage
(V) .......................................................................:
Temperature limiter endurance; operating voltage
(V) ........................................................................:
Thermal cut-out reliability
Stability of operation
ANNEX L, NORMAL LOAD CONDITIONS FOR SOME TYPES OF ELECTRICAL
BUSINESS EQUIPMENT (see 1.2.2.1 and 4.5.1)
Typewriters
Adding machines and cash registers
Erasers
Pencil sharpeners
Duplicators and copy machines
Motor-operated files
Other business equipment See sub clause 1.6.2.
ANNEX M, CRITERIA FOR TELEPHONE RINGING SIGNALS (see 2.3.1)
Introduction
Method A
Method B
Ringing signal
Frequency (Hz) ....................................................:
Voltage (V) ...........................................................:
Cadence; time (s), voltage (V) .............................:
Single fault current (mA) .......................................:
Tripping device and monitoring voltage ................:
Conditions for use of a tripping device or a monitoring voltage
Tripping device
Verdict
P
N/A
N/A
N/A
N/A
N/A
N/A
N/A
P
N/A
N/A
N/A
N/A
N/A
N/A
N/A
P
N/A
N/A
N/A
N/A
N/A
N/A
N/A
M.3.2.2
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Clause
M.3.2.3
N
N.1
N.2
P
Q
R
R.1
R.2
S
S.1
S.2
S.3
Page 29 of 82 Report No.: 11009010 001
IEC 60950-1 / EN 60950-1
Requirement – Test
Monitoring voltage (V)...........................................:
Result – Remark
ANNEX N, IMPULSE TEST GENERATORS (see 2.10.3.4, 6.2.2.1, 7.3.2 and clause G.5)
ITU-T impulse test generators
IEC 60065 impulse test generator
ANNEX P, NORMATIVE REFERENCES
ANNEX Q, BIBLIOGRAPHY
ANNEX R, EXAMPLES OF REQUIREMENTS FOR QUALITY CONTROL
PROGRAMMES
Minimum separation distances for unpopulated coated printed boards (see 2.10.6)
Reduced clearances (see 2.10.3)
ANNEX S, PROCEDURE FOR IMPULSE TESTING (see 6.2.2.3)
Test equipment
Test procedure
Examples of waveforms during impulse testing
ANNEX T, GUIDANCE ON PROTECTION AGAINST INGRESS OF WATER
(see 1.1.2)
Verdict
N/A
N/A
N/A
N/A
P
P
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
T
U
V
V.1
V.2
V.3
V.4
ANNEX U, INSULATED WINDING WIRES FOR USE WITHOUT INTERLEAVED
INSULATION (see 2.10.5.4)
ANNEX V, AC POWER DISTRIBUTION SYSTEMS (see 1.6.1)
Introduction See below.
TN power distribution systems
TT power systems
IT power systems
TRF No.:IECEN60950_1B
Single-phase TN power system considered and used for testing.
Not considered.
IT power system for Norway.
N/A
P
P
P
N/A
P
TRF originator: SGS Fimko
Y
Y.1
Y.2
Y.3
Y.4
Clause
W
W.1
W.1.2
W.2
W.2.1
W.2.2
W.2.3
X
X.1
X.2
Requirement – Test
ANNEX W, SUMMATION OF TOUCH CURRENTS
Touch current from electronic circuits
Earthed circuits
Interconnection of several equipments
Isolation
Common return, isolated from earth
Common return, connected to protective earth
ANNEX X, MAXIMUM HEATING EFFECT IN TRANSFORMER TESTS
(see clause C.1)
Determination of maximum input current
Overload test procedure
ANNEX Y, ULTRAVIOLET LIGHT CONDITIONING TEST (see 4.3.13.3)
Test apparatus .....................................................:
Mounting of test samples .....................................:
Carbon-arc light-exposure apparatus ..................:
Xenon-arc light exposure apparatus ....................:
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 31 of 82 Report No.: 11009010 001
IEC 60950-1 / EN 60950-1
Clause Requirement – Test Result – Remark
CENELEC COMMON MODIFICATIONS [C],
SPECIAL NATIONAL CONDITIONS [S] AND A-DEVIATIONS (NATIONAL DEVIATIONS) [A]
(EN 60950-1:2001, Annex ZB and Annex ZC)
Deleted. General C: Delete all the "country" notes in the reference document according to the following list:
1.1.5 Note 2
1.7.2 Note 4
1.5.8 Note 2 1.6.1 Note
1.7.12 Note 2 2.6 Note
2.2.3 Note 2.2.4
2.3.3 Note 1, 2 2.3.4
Note 2.3.2
Note 2,3 2.7.1
Note 2, 7, 8
Note
2.10.3.1 Note 4
3.2.5.1 Note 2
4.7.3.1 Note 2
6.2.2
7
Note
Note 4
3.2.1.1 Note
4.3.6
3.2.3 Note 1, 2
Note 1,2 4.7.2.2 Note
6.1.2.1 Note 6.1.2.2 Note
6.2.2.1 Note 2 6.2.2.2 Note
7.1 Note
G2.1 Note 1, 2 Annex H Note 2
1.2.4.1 S (DK): Certain types of Class I appliances (see
3.2.1.1) may be provided with a plug not establishing earthing conditions when inserted into Danish socket-outlets.
No power supply cord provided.
Verdict
P
P
N/A
1.5.1 No such switches used. N/A
1.5.8
A (SE, Ordinance 1990:944 and
CH, Ordinance on environmentally hazardous substances SR 814.013, Annex 3.2, Mercury):
Add NOTE – Switches containing mercury such as thermostats, relays and level controllers are not allowed.
S (NO): Due to the IT power system used (see annex V, Fig. V.7), capacitors are required to be rated for the applicable line-to-line voltage
(230 V).
Considered. P
1.7.2 S (FI, NO, SE): CLASS I PLUGGABLE EQUIPMENT
TYPE A intended for connection to other equipment or a network shall, if safety relies on connection to protective earth or if surge suppressors are connected between the network terminals and accessible parts, have a marking stating that the equipment must be connected to an earthed mains socket-outlet.
The marking text in the applicable countries shall be as follows:
Should be evaluated during national approval.
FI: "Laite on liitettävä suojamaadoituskoskettimilla varustettuun pistorasiaan"
See above.
N/A
N/A
NO: "Apparatet må tilkoples jordet stikkontakt" See above.
SE: "Apparaten skall anslutas till jordat uttag" See above.
A (DK, Heavy Current Regulations): Supply cords of class I equipment, which is delivered without a plug, must be provided with a visible tag with the following text:
Vigtigt!
Lederen med grøn/gul isolation må kun tilsluttes en klemme mærket
See above.
N/A
N/A
N/A
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 32 of 82 Report No.: 11009010 001
Clause
1.7.5
1.7.5
1.7.12
1.7.15
Requirement – Test
IEC 60950-1 / EN 60950-1
Result – Remark
eller
If essential for the safety of the equipment, the tag must in addition be provided with a diagram which shows the connection of the other conductors, or be provided with the following text:
"For tilslutning af de øvrige ledere, se medfølgende instalationsvejledning."
S (DK): Socket-outlets for providing power to other equipment shall be in accordance with the
Heavy Current Regulations, Section 107-2-D1,
Standard Sheet DK 1-3a, DK 1-5a or DK 1-7a, when used on Class I equipment. For stationary equipment the socket-outlet shall be in accordance with Standard Sheet DK 1-1b or DK 1-5a.
A (DK, Heavy Current Regulations):
CLASS II EQUIPMENT shall not be fitted with socketoutlets for providing power to other equipment.
No socket-outlets provided.
Class I equipment.
A (DE, Gesetz über technische Arbeitsmittel
(Gerätesicherheitsgesetz) [Law on technical labour equipment {Equipment safety law}], of 23 rd
October 1992, Article 3, 3 rd
paragraph, 2 nd sentence, together with the "Allgemeine
Verwaltungsvorschrift zur Durchführung des
Zweiten Abschnitts des Gerätesicherheitsgesetzes" [General administrative regulation on the execution of the Second Section of the
Equipment safety law], of 10 th
January 1996, article 2, 4 th
paragraph item 2):
Directions for use with rules to prevent certain hazards for (among others) maintenance of the technical labour equipment, also for imported technical labour equipment shall be written in the
German language.
NOTE: Of this requirement, rules for use even only by service personnel are not exempted.
German user’s manual provided.
A (CH, Ordinance on environmentally hazardous substances SR 814.013):
Annex 4.10 of SR 814.013 applies for batteries.
No battries provided.
A (DE, Regulation on protection against hazards by X-ray, of 8 th
January 1987, Article 5 [Operation of X-ray emission source], clauses 1 to 4): a) A licence is required by those who operate an
X-ray emission source. b) A licence in accordance with Cl. 1 is not required by those who operate an X-ray emission source on which the electron acceleration voltage does not exceed 20 kV if
1) the local dose rate at a distance of 0,1 m from the surface does not exceed 1 µSv/h and
This national difference was deleted by A11 of EN 60950-1.
Verdict
N/A
N/A
P
N/A
N/A
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 33 of 82 Report No.: 11009010 001
Clause
2.2.4
2.3.2
2.3.3 and
2.3.4
2.6.3.3
IEC 60950-1 / EN 60950-1
Requirement – Test
2) it is adequately indicated on the X-ray emission source that i) X-rays are generated and ii) the electron acceleration voltage must not exceed the maximum value stipulated by the manufacturer or importer. c) A licence in accordance with Cl. 1 is also not required by persons who operate an X-ray emission source on which the electron acceleration voltage exceeds 20 kV if
1) the X-ray emission source has been granted a type approval and
2) it is adequately indicated on the X-ray emission source that i) X-rays are generated ii) the device stipulated by the manufacturer or importer guarantees that the maximum permissible local dose rate in accordance with the type approval is not exceeded and iii) the electron acceleration voltage must not exceed the maximum value stipulated by the manufacturer or importer. d) Furthermore, a licence in accordance with
Cl. 1 is also not required by persons who operate
X-ray emission sources on which the electron acceleration voltage does not exceed 30 kV if
1) the X-rays are generated only by intrinsically safe CRTs complying with Enclosure III, No. 6,
2) the values stipulated in accordance with
Enclosure III, No. 6.2 are limited by technical measures and specified in the device and
3) it is adequately indicated on the X-ray emission source that the X-rays generated are adequately screened by the intrinsically safe CRT.
Result – Remark
No TNV circuits. S (NO): Requirements according to this annex,
1.7.2 and 6.1.2.1 apply.
S (NO): Requirements according to this annex,
6.1.2.1 apply.
No TNV circuits.
S (NO): Requirements according to this annex,
1.7.2 and 6.1.2.1 apply.
S (GB): The current rating of the circuit shall be taken as 13 A, not 16 A.
No TNV circuits.
Considered.
2.7.1 C: Replace the subclause as follows:
Basic requirements
To protect against excessive current, shortcircuits and earth faults in PRIMARY CIRCUITS , protective devices shall be included either as
TRF No.:IECEN60950_1B
Replaced.
Verdict
N/A
N/A
N/A
N/A
P
TRF originator: SGS Fimko
Page 34 of 82 Report No.: 11009010 001
Clause
IEC 60950-1 / EN 60950-1
Requirement – Test integral parts of the equipment or as parts of the building installation, subject to the following, a), b) and c): a) except as detailed in b) and c), protective devices necessary to comply with the requirements of 5.3 shall be included as parts of the equipment;
Result – Remark b) for components in series with the mains input to the equipment such as the supply cord, appliance coupler, r.f.i. filter and switch, shortcircuit and earth fault protection may be provided by protective devices in the building installation; c) it is permitted for PLUGGABLE EQUIPMENT TYPE B or PERMANENTLY CONNECTED EQUIPMENT , to rely on dedicated overcurrent and short-circuit protection in the building installation, provided that the means of protection, e.g. fuses or circuit breakers, is fully specified in the installation instructions.
If reliance is placed on protection in the building installation, the installation instructions shall so state, except that for PLUGGABLE EQUIPMENT TYPE
A the building installation shall be regarded as providing protection in accordance with the rating of the wall socket outlet.
S (GB): To protect against excessive currents and short-circuits in the PRIMARY CIRCUIT OF
DIRECT PLUG IN EQUIPMENT , protective device shall be included as integral parts of the DIRECT PLUG -
IN EQUIPMENT .
Equipment is not direct plug-in equipment.
2.7.2
2.10.2
C: Void.
C: Replace in the first line "(see also 1.4.7)" by
"(see also 1.4.8)".
2.10.3.1 S (NO): Due to the IT power distribution system used (see annex V, Fig. V.7), the A .
C . MAINS
SUPPLY
voltage is considered to be equal to the line-to-line voltage and will remain at 230 V in case of a single earth fault
Declared.
Replaced.
Considered.
Verdict
N/A
N/A
P
P
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 35 of 82 Report No.: 11009010 001
Clause
3.2.1.1
IEC 60950-1 / EN 60950-1
Requirement – Test
S (CH): Supply cords of equipment having a
RATED CURRENT not exceeding 10 A shall be provided with a plug complying with SEV 1011 or
IEC 60884-1 and one of the following dimension sheets:
SEV 6532-2.1991, Plug type 15, 3P+N+PE 250/400 V, 10 A
SEV 6533-2.1991, Plug type 11, L+N 250 V, 10 A
SEV 6534-2.1991, Plug type 12, L+N+PE 250 V, 10 A
In general, EN 60309 applies for plugs for currents exceeding 10 A. However, a 16 A plug and socket-outlet system is being introduced in
Switzerland, the plugs of which are according to the following dimension sheets, published in
February 1998:
SEV 5932-2.1998, Plug type 25, 3L+N+PE 230/400 V, 16 A
SEV 5933-2.1998, Plug type 21, L+N 250 V, 16 A
SEV 5934-2.1998, Plug type 23, L+N+PE 250 V, 16 A
Result – Remark
No power supply cord provided.
Verdict
N/A
S (DK): Supply cords of single-phase equipment having a rated current not exceeding 13 A shall be provided with a plug according to the Heavy
Current Regulations, Section 107-2-D1.
CLASS I EQUIPMENT provided with socket-outlets with earth contacts or which are intended to be used in locations where protection against indirect contact is required according to the wiring rules shall be provided with a plug in accordance with standard sheet DK 2-1a or DK 2-5a.
If ply-phase equipment and single-phase equipment having a RATED CURRENT exceeding
13 A is provided with a supply cord with a plug, this plug shall be in accordance with the Heavy
Current Regulations, Section 107-2-D1 or
EN 60309-2.
No power supply cord provided. N/A
S (ES): Supply cords of single-phase equipment having a rated current not exceeding 10 A shall be provided with a plug according to
UNE 20315:1994.
Supply cords of single-phase equipment having a rated current not exceeding 2,5 A shall be provided with a plug according to
UNE-EN 50075:1993.
No power supply cord provided.
CLASS I EQUIPMENT provided with socket-outlets with earth contacts or which are intended to be used in locations where protection against indirect contact is required according to the wiring rules, shall be provided with a plug in accordance with standard UNE 20315:1994.
If poly-phase equipment is provided with a supply cord with a plug, this plug shall be in accordance with UNE-EN 60309-2.
TRF No.:IECEN60950_1B
N/A
TRF originator: SGS Fimko
Clause
3.2.3
3.2.5.1
3.2.5.1
3.3.4
Page 36 of 82 Report No.: 11009010 001
IEC 60950-1 / EN 60950-1
Requirement – Test
S (GB): Apparatus which is fitted with a flexible cable or cord and is designed to be connected to a mains socket conforming to BS 1363 by means of that flexible cable or cord and plug, shall be fitted with a 'standard plug' in accordance with
Statutory Instrument 1768:1994 – The Plugs and
Socket etc. (Safety) Regulations 1994, unless exempted by those regulations.
NOTE – 'Standard plug' is defined in SI 1768:1994 and essentially means an approved plug conforming to BS 1363 or an approved conversion plug.
S (IE): Apparatus which is fitted with a flexible cable or cord and is designed to be connected to a mains socket conforming to I.S. 411 by means of that flexible cable or cord and plug, shall be fitted with a 13 A plug in accordance with
Statutory Instrument 525:1997 – National
Standards Authority of Ireland (section 28) (13 A
Plugs and Conversion Adaptors for Domestic
Use) Regulations 1997.
Result – Remark
No power supply cord provided.
Verdict
N/A
No power supply cord provided. N/A
C: Delete Note 1 and in Table 3A, delete the conduit sizes in parentheses.
C: Replace
"60245 IEC 53" by "H05 RR-F";
"60227 IEC 52" by "H03 VV-F or H03 VVH2-F";
"60227 IEC 53" by "H05 VV-F or H05 VVH2-F2".
In Table 3B, replace the first four lines by the following:
Up to and including 6
Over 6 up to and including 10 (0,75)
2)
0,75
1,0
Over 10 up to and including 16 (1,0)
3)
1,5
1)
In the Conditions applicable to Table 3B delete the words "in some countries" in condition
1)
.
In Note 1, applicable to Table 3B, delete the second sentence.
S (GB): A power supply cord with conductor of
1,25 mm
2
is allowed for equipment with a rated current over 10 A and up to and including 13 A.
C: In table 3D, delete the fourth line: conductor sizes for 10 to 13 A, and replace with the following:
"Over 10 up to and including 16 1,5 to 2,5 1,5 to 4"
Delete the fifth line: conductor sizes for 13 to
16 A.
Deleted.
Replaced.
No power supply cord provided.
Deleted.
N/A
N/A
N/A
N/A
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 37 of 82 Report No.: 11009010 001
Clause
3.3.4
4.3.6
IEC 60950-1 / EN 60950-1
Requirement – Test
S (GB): The range of conductor sizes of flexible cords to be accepted by terminals for equipment with a RATED CURRENT of over 10 A up to and including 13 A is:
- 1,25 mm
2
to 1,5 mm
2
nominal cross-sectional area.
Result – Remark
No power supply cord provided.
Verdict
N/A
S (GB): The torque test is performed using a socket outlet complying with BS 1363 and the plug part of DIRECT PLUG IN EQUIPMENT shall be assessed to BS 1363: Part 1, 12.1, 12.2, 12.3,
12.9, 12.11, 12.12, 12.16 and 12.17, except that the test of 12.17 is performed at not less than
125 °C.
EUT is not direct plug-in type.
S (IE): DIRECT PLUG IN EQUIPMENT is known as plug similar devices. Such devices shall comply with Statutory Instrument 526:1997 – National
Standards Authority of Ireland (Section 28)
(Electrical plugs, plug similar devices and sockets for domestic use) Regulations, 1997.
See above.
N/A
N/A
4.3.13.6 C: Add the following note:
NOTE Attention is drawn to 1999/519/EC: Council
Recommendation on the limitation of exposure of the general public to electromagnetic fields 0 Hz to 300 GHz. Standards taking into account this recommendation are currently under development.
Added.
6.1.2.1 S (FI, NO, SE): Add the following text between the first and second paragraph:
If this insulation is solid, including insulation forming part of a component, it shall at least consist of either
- two layers of thin sheet material, each of which shall pass the electric strength test below, or
- one layer having a distance through insulation of at least 0,4 mm, which shall pass the electric strength test below.
If this insulation forms part of a semiconductor component (e.g. an optocoupler), there is no distance through insulation requirement for the insulation consisting of an insulating compound completely filling the casing, so that CLEARANCES
AND CREEPAGE DISTANCES do not exist, if the component passes the electric strength test in accordance with the compliance clause below and in addition
- passes the tests and inspection criteria of 2.10.8 with an electric strength test of 1,5 kV multiplied by 1,6 (the electric strength test of 2.10.7 shall be performed using 1,5 kV), and
- is subject to ROUTINGE TESTING for electric
No TNV circuits provided.
N/A
N/A
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 38 of 82 Report No.: 11009010 001
Clause
6.1.2.2
7.1
G.2.1
Requirement – Test
IEC 60950-1 / EN 60950-1
Result – Remark strength during manufacturing, using a test voltage of 1,5 kV.
It is permitted to bridge this insulation with a capacitor complying with EN 132400:1994, subclass Y2.
A capacitor classified Y3 according to
EN 132400:1994, may bridge this insulation under the following conditions:
- the insulation requirements are satisfied by having a capacitor classified Y3 as defined by
EN 132400, which in addition to the Y3 testing, is tested with an impulse test of 2,5 kV defined in
EN 60950:2000, 6.2.2.1;
- the additional testing shall be performed on all the test specimens as described in EN 132400;
- the impulse test of 2,5 kV is to be performed before the endurance test in EN 132400, in the sequence of tests as described in EN 132400.
S (FI, NO, SE): The exclusions are applicable for
PERMANENTLY CONNECTED EQUIPMENT and
PLUGGABLE EQUIPMENT TYPE B and equipment intended to be used in a RESTRICTED ACCESS
LOCATION where equipotential bonding has been applied, e.g. in a telecommunication centre, and which has provision for a permanently connected
PROTECTIVE EARTHING CONDUCTOR and is provided with instructions for the installation of that conductor by a service person.
No TNV circuits provided.
S (FI, NO, SE): Requirements according to this annex, 6.1.2.1 and 6.1.2.2 apply with the term
TELECOMMUNICATION NETWORK in 6.1.2 being replaced by the term CABLE DISTRIBUTION SYSTEM .
No TNV circuit or cable distribution system provided.
S (NO): Due to the IT power distribution system used (see annex V, Fig. V.7), the A .
C . MAINS
SUPPLY voltage is considered to be equal to the line-to-line voltage, and will remain at 230 V in case of a single earth fault.
Considered.
Annex H C: Replace the last paragraph of this annex by:
At any point 10 cm from the surface of the operator access area, the dose rate shall not exceed 1 µSv/h (0,1 mR/h) (see note). Account is taken of the background level.
Replaced.
Replace the notes as follows:
NOTE These values appear in Directive 96/29/Euratom.
Delete Note 2.
Annex P C: Replace the text of this annex by:
See annex ZA.
TRF No.:IECEN60950_1B
Replaced.
Verdict
N/A
N/A
N/A
N/A
P
TRF originator: SGS Fimko
Page 39 of 82 Report No.: 11009010 001
IEC 60950-1 / EN 60950-1
Clause Requirement – Test Result – Remark
Annex Q C: Replace the title of IEC 61032 by "Protection of persons and equipment by enclosures – Probes for verification".
Add the following notes for the standards indicated:
IEC 60127 NOTE Harmonized as EN 60127 (Series) (not modified)
IEC 60269-2-1 NOTE Harmonized as HD 630.2.1 S4:2000 (modified)
IEC 60529 NOTE Harmonized as EN 60529:1991 (not modified)
IEC 61032 NOTE Harmonized as EN 61032:1998 (not modified)
IEC 61140 NOTE Harmonized as EN 61140:2001 (not modified)
ITU-T Recommendation K.31
NOTE in Europe, the suggested document is EN 50083-1.
Verdict
P
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 40 of 82 Report No.: 11009010 001
IEC 60950-1 / EN 60950-1
Clause Requirement – Test Result – Remark
Annex ZA C: NORMATIVE REFERENCES TO INTERNATIONAL PUBLICATIONS WITH
THEIR RELEVANT EUROPEAN PUBLICATIONS
This European Standard incorporates, by dated or undated reference, provisions from other publications. These normative references are cited at the appropriate places in the text and the publications are listed hereafter. For dated references, subsequent amendments to or revisions of any of these publications apply to this
European Standard only when incorporated in it by amendment or revision. For undated references, the latest edition of the publication referred to applies
(including amendments).
NOTE When an international publication has been modified by common modifications, indicated by
(mod), the relevant EN/HD applies.
IEC 60050-151
EN 60065:1998 + corr. June 1999
EN 60073:1996
HD 566 S1:1990
HD 214 S2:1980
HD 611.4.1.S1:1992
HD 21
HD 22
1)
2)
Series
Series
IEC 60050-195
IEC 60065 (mod):1998
IEC 60073:1996
IEC 60085:1984
IEC 60112:1979
IEC 60216-4-1:1990
EN 60309 Series
EN 60317-43:1997
EN 60320 Series
HD 384.3 S2:1995
HD 384.4.41 S2:1996
EN 132400:1994
4)
IEC 60227 (mod) Series
IEC 60245 (mod) Series
IEC 60309 Series
IEC 60317-43:1997
IEC 60320 (mod) Series
IEC 60364-3 (mod):1993
IEC 60364-4-41 (mod):1992
3)
IEC 60384-14:1993
+ A2:1998 + A3:1998 + A4:2001
EN 60417-1 IEC 60417-1
HD 625.1 S1:1996 + corr. Nov. 1996 IEC 60664-1 (mod):1992
EN 60695-2-2:1994
EN 60695-2-11:2001
IEC 60695-2-2:1991
IEC 60695-2-11:2000
IEC 60695-2-20:1995
IEC 60695-10-2:1995
IEC 60695-11-3:2000
IEC 60695-11-4:2000
EN 60695-11-10:1999
EN 60695-11-20:1999
EN 60730-1:2000
EN 60825-1:1994 + corr. Febr. 1995 +
A11:1996 + corr. July 1997
EN 60825-2:2000
EN 60851-3:1996
EN 60851-5:1996
IEC 60695-11-10:1999
IEC 60695-11-20:1999
IEC 60730-1:1999 (mod)
IEC 60825-1:1993
IEC 60825-2:2000
IEC 60825-9:1999
IEC 60851-3:1996
IEC 60825-5:1996
EN 60851-6:1996
EN 60990:1999
EN 61965:2001
EN ISO 178:1996
EN ISO 179 Series
EN ISO 180:2000
IEC 60851-6:1996
IEC 60885-1:1987
IEC 60990:1999
IEC 61058-1:2000
IEC 61965:2000
ISO 178:1993
ISO 179 Series
ISO 180:1993
Verdict
P
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Clause
Page 41 of 82 Report No.: 11009010 001
IEC 60950-1 / EN 60950-1
Requirement – Test Result – Remark
EN ISO 527 Series
EN ISO 4892 Series
EN ISO 8256:1996
EN ISO 9773:1998
ISO 261:1998
ISO 262:1998
ISO 527 Series
ISO 386:1984
ISO 4892 Series
ISO 7000:1989
ISO 8256:1990
ISO 9772:1994
ISO 9773:1998
ITU-T:1988 Recommendation K.17
ITU-T:2000 Recommendation K.21
1) The HD 21 series is related to, but not directly equivalent with the IEC 60227 series
2) The HD 22 series is related to, but not directly equivalent with the IEC 60245 series
3) IEC 60364-4-41:1992 is superseded by IEC 60364-4-41:2001
4) EN 132400, Sectional Specification: Fixed capacitors for electromagnetic interference suppression and connection to the supply mains (Assessment level D), and its amendments are related to, but not directly equivalent to IEC 60384-14
Verdict
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
1.5.1 TABLE: list of critical components
Object/part no. Manufacturer/ trademark
Type/model
Page 42 of 82
Technical data
Report No.:
Standard
11009010 001
P
Mark(s) of conformity
1.
LCD Monitor unit
Switching Power
Supply with
DC/AC inverter board
Lite-on
Switching Power
Supply with
DC/AC inverter board
LCD Panel
Base stand
Lite-on
ChungHwa
AUO
--
Metal enclosure --
PTB-1725 I/P: 100-240Vac,
50/60Hz, 1.3-
0.9A;
O/P: 5.1Vdc /
3.48A,
20.68Vdc/
1.74A,
12.08Vdc/ 1.03A
(for power supply)
--
I/p: 20.68Vdc,
1.74A; o/p: 2400Vrms,
8.0mA (for
DC/AC inverter)
PTB-1806 I/P: 100-240Vac,
50/60Hz, 1.5A;
O/P: 5.32Vdc /
1.9A, 22.64Vdc/
1.32A (for power supply)
--
I/p: 22.64Vdc,
1.32A; o/p: 2400Vrms,
7.0mA (for
DC/AC inverter)
CLAA201WA03 20.1”, TFT type,
1680X1050
--
M201EW02
--
--
HF-380
20.1”, TFT type,
1680X1050
--
Plastic material
HB min. cover with metal
UL 94
Metal, Thickness min 0.81 mm
--
HB, thickness
1.8mm min
UL 94
Tested in apparatus
Tested in apparatus
--
--
UL
--
UL Plastic
Enclosure
LG Chemical
Mylar sheet between Power supply board component side and metal enclosure
-- -- V-2 or better, cover area
170mm by
210mm
UL 94 UL
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Report No.: 11009010 001
Speakers
(Two provided)
(Optional)
P.C.B.
-- -- Each 4Ω, 2W max.
--
-- -- V-1, 105°C min UL 94
Power supply with DC/AC inverter board: PTB-1725
Appliance Inlet
(P801)
Solteam
Inalways
ST-01 10A, 250Vac
0707-1, 0711-2 10A, 250Vac
IEC 60320-1
IEC 60320-1
Fuse (F801)
Duoling
Littelfuse
CDJ-3
215
Page 43 of 82
10A, 250Vac
T3.15AH,
250Vac
IEC 60320-1
IEC 60127-1
IEC 60127-2
--
UL
VDE, S, D, N, FI,
UL, CSA, SEV
VDE, S, D, N, FI,
UL, CSA, SEV
VDE, S, D, N, FI,
UL, CSA, SEV
VDE, S, UL
X Capacitor
(C803, C806)
(optional)
Bel
Hua Jung
Matsushita
5HT
MKP
T3.15AH,
250Vac
Max. 0.47 µF,
250Vac
IEC 60127-1
IEC 60127-2
IEC 60384-14/
1993
VDE, S, UL
VDE, SEV, UL,
CSA, FI
Pilkor
Teapo
Iskra
ECQ-UV,
ECQUL
PCX2 337
XG-VS
Max. 0.47 µF,
250Vac
Max. 0.47 µF,
250Vac
Max. 0.47 µF,
250Vac
IEC 60384-14/
1993
IEC 60384-14/
1993
IEC 60384-14/
1993
VDE, SEV, S, N,
D, FI, UL, CSA
VDE, SEV, S, N,
D, FI, UL
VDE, SEV, S, N,
D, FI, UL,
CSA
VDE, UL, CUL
Europtronic
Matsushita
KNB1560 Max. 0.47 µF,
250Vac
MPX Max. 0.47 µF,
250Vac
TS, RS, NS-A 470-4700pF,
250Vac
IEC 60384-14/
1993
IEC 60384-14/
1993
IEC 60384-14/
1993
VDE, UL, CUL
VDE, UL,
CSA, FI
Y-Capacitor
(C802, C808,
C805, C836,
C838, C839)
(Y1 or Y2 type)
(optional)
Pan Overseas AC, AH
Success
Success
TDK
SF, SE
SB
CD
470-4700pF,
250Vac
470-4700pF,
250Vac
470-4700pF,
250Vac
470-4700pF,
250Vac
IEC 60384-14/
1993
IEC 60384-14/
1993
IEC 60384-14/
1993
IEC 60384-14/
1993
VDE, FI, UL,
CSA
VDE, FI, UL,
CSA
VDE, FI, UL,
CSA
VDE, FI, UL,
CSA
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 44 of 82 Report No.: 11009010 001
Murata KX, KD
Ripple Capacitor
(C801)
Dongguan South
Hongming
F
-- Electrolytic can type
Carbon type
470-4700pF,
250Vac
470-4700pF,
250Vac
100-150µF,
400Vmin.,
105°C
1MΩ, 1/4 W Bleeder Resistor
(R802)
--
Thermistor
(R801)
--
Bridge Diode
(D813, D814,
D815, D816)
Current sense resistor (R813)
--
--
Switching
Transistor
(Q801)
Power
Transformer
(T801)
--
L.S.E
NTC type
--
--
--
600V, 2A
0.24Ω, 2W
600V, 7.5A
--
10 Ω, 5A at 25°C --
--
--
--
Line Filter
(T802)
Line Filter
(T803)
DC/AC Inverter
Transformer
(T101, T102)
LSE
LSE
LSE
LSE
LSE
613106142X (X:
0-9 for marketing purpose)
Class B
613800440X (X:
0-9 for marketing purpose)
130°C
613800000X (X:
0-9 for marketing purpose)
130°C
613800440X (X:
0-9 for marketing purpose)
130°C
613800000X (X:
0-9 for marketing purpose)
130°C
613102220X (X:
0-9 for marketing purpose)
130°C
IEC 60384-14/
1993
IEC 60384-14/
1993
--
VDE, FI, UL,
CSA
VDE, FI, UL,
CSA
--
--
--
--
--
--
Applicable parts in IEC 60950-1 and according to
IEC 60085
Tested with this appliance
-- --
--
--
--
--
--
--
--
--
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Optocoupler
(I802)
LITEON
LITEON
LITEON
NEC
NEC
NEC
QT
Sharp
Sharp
Toshiba
Toshiba
Page 45 of 82 Report No.: 11009010 001
LTV-817
LTV-816
Di = 0.4 mm,
In = 4.0 mm,
Ex = 8.0 mm,
Min.100°C
Di = 0.6 mm,
In = 4.6 mm,
Ex = 7.4 mm,
Min.100°C
LTV-713 series Di = 0.4 mm,
In = 2.0 mm,
Ex = 8.0 mm,
Min.100°C
PS 2561 Di = 0.4 mm,
In = 4.0 mm,
Ex = 7.0 mm,
Min.100°C
PS2581
PS2561A-1 series
Di = 0.4 mm,
In = 4.0 mm,
Ex = 8.0 mm,
Min.100°C
Di = 0.4 mm,
In = 4.0 mm,
Ex = 7.0 mm,
Min.100°C
H11A817A
H11A817B
H11A817C
PC123
PC817
TLP621
TLP721
DIN EN 60747-
5-2: 2003,
IEC 60950-1
DIN EN 60747-
5-2: 2003,
IEC 60950-1
DIN EN 60747-
5-2: 2003,
IEC 60950-1
DIN EN 60747-
5-2: 2003,
IEC 60950-1
DIN EN 60747-
5-2: 2003,
IEC 60950-1
DIN EN 60747-
5-2: 2003,
IEC 60950-1
Di=0.4 mm, exter creepage
= 7.0 mm, thermal cycling,
AC 3000V.
DIN EN 60747-
5-2: 2003,
IEC 60950-1
Di = 0.7 mm,
In = 5.0 mm,
Ex = 8.0 mm,
Min.100°C
Di = 0.4 mm,
In = 5 mm,
Ex = 6.4 mm,
Min.100°C
DIN EN 60747-
5-2: 2003,
IEC 60950-1
DIN EN 60747-
5-2: 2003,
IEC 60950-1
Di=0.8 mm, exter creepage
DIN EN 60747-
5-2: 2003,
= 8.0 mm,
Thermal cycling,
IEC 60950-1
AC 3000V.
Di = 0.8 mm,
In = 4.0 mm,
Ex = 8.0 mm,
Min.100°C
DIN EN 60747-
5-2: 2003,
IEC 60950-1
VDE, FI
VDE, FI
VDE, FI
VDE, FI
VDE, FI
VDE, FI
VDE, FI
VDE, FI
VDE, FI
VDE, FI
VDE, FI
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Toshiba
Vishay
Vishay
TLP421 series Di=0.4 mm, exter creepage
DIN EN 60747-
5-2: 2003,
= 8.0 mm,
Thermal cycling,
IEC 60950-1
AC 3000V.
TCET1100
TCET1102
TCET1103
TCET1107
TCET1108
TCET1109
Di = 0.6 mm,
In = 4.2 mm,
Ex = 8.1 mm,
Min.100°C
DIN EN 60747-
5-2: 2003,
IEC 60950-1
TCET1103G
TCET1107G
TCET1108G
TCET1109G
Di = 0.7 mm,
In = 4.2 mm,
Ex = 8.1 mm,
Min.100°C
DIN EN 60747-
5-2: 2003,
IEC 60950-1
Power supply with DC/AC inverter board: PTB-1806
Appliance Inlet
(P801)
Solteam ST-01 10A, 250Vac
Inalways 0707-1, 0711-2 10A, 250Vac
IEC 60320-1
IEC 60320-1
Fuse (F801)
Duoling
Littelfuse
CDJ-3
215
Page 46 of 82
10A, 250Vac
Report No.: 11009010 001
IEC 60320-1
VDE, FI
VDE, FI
VDE, FI
VDE, S, D, N, FI,
UL, CSA, SEV
VDE, S, D, N, FI,
UL, CSA, SEV
VDE, S, D, N, FI,
UL, CSA, SEV
VDE, S, UL
X Capacitor
(C801, C819)
(optional)
Bel
Hua Jung
Matsushita
5HT
MKP
T3.15AH,
250Vac
T3.15AH,
250Vac
Max. 0.47 µF,
250Vac
IEC 60127-1
IEC 60127-2
IEC 60127-1
IEC 60127-2
IEC 60384-14/
1993
VDE, S, UL
VDE, SEV, FI,
UL, CSA
Y-Capacitor
(C808, C820,
C825)
(Y1 or Y2 type)
(optional)
Pilkor
Teapo
Iskra
Europtronic
Matsushita
Pan Overseas
ECQ-UV,
ECQUL
PCX2 337
XG-VS
KNB1560
AC, AH
Max. 0.47 µF,
250Vac
Max. 0.47 µF,
250Vac
Max. 0.47 µF,
250Vac
Max. 0.47 µF,
250Vac
MPX Max. 0.47 µF,
250Vac
TS, RS, NS-A 470-4700pF,
250Vac
470-4700pF,
250Vac
IEC 60384-14/
1993
IEC 60384-14/
1993
IEC 60384-14/
1993
IEC 60384-14/
1993
IEC 60384-14/
1993
IEC 60384-14/
1993
IEC 60384-14/
1993
VDE, SEV, S, N,
D, FI, UL, CSA
VDE, SEV, S, N,
D, FI, UL
VDE, SEV, S, N,
D, FI, UL, CSA
VDE, UL, cUL
VDE, UL, cUL
VDE, UL,
CSA, FI
VDE, FI, UL,
CSA
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 47 of 82 Report No.: 11009010 001
Success
Success
TDK
Murata
SF, SE
SB
CD
KX, KD
Ripple Capacitor
(C805)
Dongguan South
Hongming
F
-- Electrolytic can type
Carbon type
470-4700pF,
250Vac
470-4700pF,
250Vac
470-4700pF,
250Vac
470-4700pF,
250Vac
470-4700pF,
250Vac
100-150µF,
400Vmin.,
105°C
1MΩ, 1/4 W Bleeder Resistor
(R801)
--
-- Thermistor
(R802)
Bridge Diode
(D807, D808,
D805, D812)
--
-- Current sense resistor (R811)
Switching
Transistor
(Q803)
Power
Transformer
(T801)
--
L.S.E
NTC type
--
--
--
6131053702P
600V, 2A
0.39Ω, 2W
600V, 7A
Class B
--
10 Ω, 3A at 25°C --
--
--
--
LI TAI 6131053702P60 Class B
6138003611P 130°C
IEC 60384-14/
1993
IEC 60384-14/
1993
IEC 60384-14/
1993
IEC 60384-14/
1993
IEC 60384-14/
1993
--
VDE, FI, UL,
CSA
VDE, FI, UL,
CSA
VDE, FI, UL,
CSA
VDE, FI, UL,
CSA
VDE, FI, UL,
CSA
--
--
--
--
--
--
Applicable parts in IEC 60950-1 and according to
IEC 60085
Tested with this appliance
Applicable parts in IEC 60950-1 and according to
IEC 60085
Tested with this appliance
-- -- Line Filter
(T802)
DC/AC Inverter
Transformer
(T101, T102)
Optocoupler
(I802)
DGBullWill
LSE
Darfon
LITEON
6138003601P 130°C
6131020002P00 130°C
LTV-817 Di = 0.4 mm,
In = 4.0 mm,
Ex = 8.0 mm,
Min.100°C
--
--
DIN EN 60747-
5-2: 2003,
IEC 60950-1
--
--
VDE, FI
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
LITEON
LITEON
NEC
NEC
NEC
QT
Sharp
Sharp
Toshiba
Toshiba
Toshiba
TRF No.:IECEN60950_1B
Page 48 of 82 Report No.: 11009010 001
LTV-816 Di = 0.6 mm,
In = 4.6 mm,
Ex = 7.4 mm,
Min.100°C
LTV-713 series Di = 0.4 mm,
In = 2.0 mm,
Ex = 8.0 mm,
Min.100°C
PS 2561
PS2581
Di = 0.4 mm,
In = 4.0 mm,
Ex = 7.0 mm,
Min.100°C
Di = 0.4 mm,
In = 4.0 mm,
Ex = 8.0 mm,
Min.100°C
DIN EN 60747-
5-2: 2003,
IEC 60950-1
DIN EN 60747-
5-2: 2003,
IEC 60950-1
DIN EN 60747-
5-2: 2003,
IEC 60950-1
DIN EN 60747-
5-2: 2003,
IEC 60950-1
PS2561A-1 series
H11A817A
H11A817B
H11A817C
PC123
Di = 0.4 mm,
In = 4.0 mm,
Ex = 7.0 mm,
Min.100°C
DIN EN 60747-
5-2: 2003,
IEC 60950-1
Di=0.4 mm, exter creepage
= 7.0 mm, thermal cycling,
AC 3000V.
DIN EN 60747-
5-2: 2003,
IEC 60950-1
Di = 0.7 mm,
In = 5.0 mm,
Ex = 8.0 mm,
Min.100°C
DIN EN 60747-
5-2: 2003,
IEC 60950-1
PC817
TLP621
TLP721
Di = 0.4 mm,
In = 5 mm,
Ex = 6.4 mm,
Min.100°C
DIN EN 60747-
5-2: 2003,
IEC 60950-1
Di=0.8 mm, exter creepage
DIN EN 60747-
5-2: 2003,
= 8.0 mm,
Thermal cycling,
IEC 60950-1
AC 3000V.
Di = 0.8 mm,
In = 4.0 mm,
Ex = 8.0 mm,
Min.100°C
DIN EN 60747-
5-2: 2003,
IEC 60950-1
TLP421 series Di=0.4 mm, exter creepage
DIN EN 60747-
5-2: 2003,
= 8.0 mm,
Thermal cycling,
AC 3000V.
IEC 60950-1
VDE, FI
VDE, FI
VDE, FI
VDE, FI
VDE, FI
VDE, FI
VDE, FI
VDE, FI
VDE, FI
VDE, FI
VDE, FI
TRF originator: SGS Fimko
Page 49 of 82 Report No.: 11009010 001
Vishay TCET1100
TCET1102
TCET1103
TCET1107
TCET1108
TCET1109
Di = 0.6 mm,
In = 4.2 mm,
Ex = 8.1 mm,
Min.100°C
DIN EN 60747-
5-2: 2003,
IEC 60950-1
VDE, FI
Vishay TCET1103G
TCET1107G
TCET1108G
TCET1109G
Di = 0.7 mm,
In = 4.2 mm,
Ex = 8.1 mm,
Min.100°C
DIN EN 60747-
5-2: 2003,
IEC 60950-1
VDE, FI
Note(s):
1. An asterisk indicates a mark that assures the agreed level of surveillance.
2. In Optocoupler technical data column, where “Di” means distance through insulation, “In” means internal creepage distance, “Ex” means external creepage distance.
1.6.2 TABLE: electrical data (in normal conditions)
Fuse # Irated (A) U(V)/F(Hz) P (W) I (A)
Power supply with DC/AC inverter board: PTB-1725
F801 -- 90/50 59.0 1.1
Ifuse (A)
1.1
Condition/status
P
Maximum normal load conditions
F801
F801
F801
F801
--
1.5
1.5
1.5
90/60
100/50
100/60
240/50
59.0
57.5
57.5
55.6
1.1
1.0
1.0
0.54
1.1
1.0
1.0
0.54
Maximum normal load conditions
Maximum normal load conditions
Maximum normal load conditions
Maximum normal load conditions
F801
F801
F801
F801
F801
1.5
--
--
--
--
240/60
254/50
254/60
264/50
264/60
55.6
55.6
55.6
55.2
55.2
0.54
0.51
0.51
0.49
0.49
0.54
0.51
0.51
0.49
0.49
Maximum normal load conditions
Maximum normal load conditions
Maximum normal load conditions
Maximum normal load conditions
Maximum normal load conditions
Power supply with DC/AC inverter board: PTB-1806
F801
F801
--
--
90/50
90/60
47.0
47.0
0.89
0.90
F801
F801
F801
F801
F801
F801
1.5
1.5
1.5
1.5
--
--
100/50
100/60
240/50
240/60
254/50
254/60
47.0
47.0
46.0
46.0
46.0
46.0
0.81
0.83
0.42
0.42
0.40
0.40
0.89
0.90
0.81
0.83
0.42
0.42
0.40
0.40
Maximum normal load conditions
Maximum normal load conditions
Maximum normal load conditions
Maximum normal load conditions
Maximum normal load conditions
Maximum normal load conditions
Maximum normal load conditions
Maximum normal load conditions
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 50 of 82
F801
F801
--
--
264/50
264/60
46.0
46.0
0.39
0.39
0.39
0.39
Power supply with DC/AC inverter board: PTB-1725 with USB ports
F801
F801
--
--
90/50
90/60
67.5
67.3
1.23
1.24
1.23
1.24
F801
F801
F801
F801
F801
F801
F801
1.5
1.5
1.5
1.5
--
--
--
100/50
100/60
240/50
240/60
254/50
254/60
264/50
F801
Note(s):
2.1.1.5
-- 264/60 64.0
TABLE: max. V, A, VA test
Voltage (rated)
(V)
Note(s):
2.1.1.7
Current (rated)
(A)
TABLE: discharge test
66.5
66.4
64.0
64.0
64.0
64.0
64.0
1.12
1.13
0.57
0.56
0.54
0.54
0.53
0.53
Voltage (max.)
(V)
Condition
τ
calculated
(s)
τ
measured
(s)
Power supply with DC/AC inverter board: PTB-1725
Line to Neutral 0.94 0.18 t u→ 0V
(s)
--
1.12
1.13
0.57
0.56
0.54
0.54
0.53
0.53
Maximum normal load conditions
Maximum normal load conditions
Maximum normal load conditions
Maximum normal load conditions
Maximum normal load conditions
Maximum normal load conditions
Maximum normal load conditions
Maximum normal load conditions
Maximum normal load conditions
Maximum normal load conditions
Maximum normal load conditions
Comments
Report No.: 11009010 001
Maximum normal load conditions
Current (max.)
(A)
N/A
VA (max.)
(VA)
P
Vpk=354V, 37% of Vpk=131V, after 1 sec voltage drop to 0V
Power supply with DC/AC inverter board: PTB-1806
Line to Neutral 0.94 0.77 -- Vpk=368V, 37% of Vpk=136V, after 1 sec voltage drop to 104V
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 51 of 82
Note(s):
For Power supply with DC/AC inverter board: PTB-1725:
Overall capacity: 0.94µF (C803=C806=0.47µF)
Discharge resistor: 1MΩ (R802=1MΩ)
For Power supply with DC/AC inverter board: PTB-1806:
Overall capacity: 0.94µF(C801=C819=0.47µF)
Discharge resistor: 1MΩ (R801=1MΩ)
2.2.2
Transformer
TABLE: Hazardous voltage measurement
Location max. Voltage
V peak V d.c.
Power supply with DC/AC inverter board: PTB-1725
Report No.: 11009010 001
Voltage Limitation
Component
P
T801
T801
T801
Pin 9, 10 – Pin 8
Pin 13 – Pin 8
After D805
Pin 11 – Pin 8
26.0
101
22.8
66
16.8
9.0
32.6
13.7
20.9
9.9
--
--
D805
--
D807 After D807
Power supply with DC/AC inverter board: PTB-1806
T801 Pin 7, 8 – Pin 6 31.4 -- --
T801 Pin 10 – Pin 6
After D809
Note(s): Input Voltage is 240Vac, 60Hz
121.0
--
--
26.4
--
D809
2.2.3
Location
TABLE: SEL voltage measurement
Voltage measured (V)
Power supply with DC/AC inverter board: PTB-1725
+12V output 0
Comments
+5V output 0
When D807 short, the o/p-voltage did not exceed 42.4Vpk.
When D805 short, the o/p-voltage did not exceed 42.4Vpk.
P
Power supply with DC/AC inverter board: PTB-1806
+20.5V output 0 When D809 short, the o/p-voltage did not exceed 42.4Vpk.
Note(s): Input Voltage is 240Vac, 60Hz
2.4.2 TABLE: limited current circuit measurement
TRF No.:IECEN60950_1B
P
TRF originator: SGS Fimko
Page 52 of 82 Report No.: 11009010 001
Location Voltage
(V)
Current
(mA)
Freq.
(kHz)
Limit
(mA)
Comments
Power supply with DC/AC inverter board: PTB-1725
With normal condition
P103 pin 1 – P103 pin 2
P103 pin 1 – Earth
P103 pin 2 – Earth
T101 pin 9 – Earth
44
0
21.2
0
Single fault condition (D133 shorted)
P103 pin 1 – P103 pin 2 42.2
P103 pin 1 – Earth 0
22
0
10.6
0
21.1
0
47
--
46
--
46
--
32.9
--
32.2
--
--
Unit shut down, no hazards
32.2 --
-- Unit shut down, no hazards
--
Unit shut down, no hazards
47
--
32.9 --
-- Unit shut down, no hazards
P103 pin 2 – Earth
T101 pin 9 – Earth
20.8
0
Single fault condition (R151 shorted)
P103 pin 1 – P103 pin 2 41.2
P103 pin 1 – Earth
P103 pin 2 – Earth
T101 pin 9 – Earth
0
7.4
0
10.4
0
Single fault condition (Q110 pin 1 to pin 2 shorted)
P103 pin 1 – P103 pin 2 0 0
P103 pin 1 – Earth
P103 pin 2 – Earth
0
0
0
0
T101 pin 9 – Earth 0
Single fault condition (C181 shorted)
P103 pin 1 – P103 pin 2
P103 pin 1 – Earth
P103 pin 2 – Earth 0
0
0
20.6
0
3.7
0
0
0
0
0
0
T101 pin 9 – Earth 0
Single fault condition (C185 shorted)
P103 pin 1 – P103 pin 2
P103 pin 1 – Earth
0
0
P103 pin 2 – Earth
T101 pin 9 – Earth
Single fault condition (C106 shorted)
P103 pin 1 – P103 pin 2 0
0
0
0
0
0
0
0
47
--
47
--
--
--
--
--
--
--
--
--
--
--
--
--
--
32.9
--
32.9 --
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
P103 pin 1 – Earth
P103 pin 2 – Earth
T101 pin 9 – Earth
Single fault condition (D136 shorted)
P103 pin 1 – P103 pin 2 52
P103 pin 1 – Earth
P103 pin 2 – Earth
0
4.2
T101 pin 9 – Earth 0
0
0
0
TRF No.:IECEN60950_1B
0
0
0
26
0
2.1
0
Page 53 of 82
--
--
--
47
--
51
--
--
--
--
Report No.: 11009010 001
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
32.9 --
-- Unit shut down, no hazards
35.7 --
-- Unit shut down, no hazards
Power supply with DC/AC inverter board: PTB-1806
Normal condition
P101 pin1 to pin2
P101 pin1 to Earth
P101 pin2 to Earth
38.8
0
2.2
P102 pin1 to pin2
P102 pin1 to Earth
42.4
42.0
P102 pin2 to Earth
Single fault condition (D103 short)
0.4
P101 pin1 to pin2
P101 pin1 to Earth
P101 pin2 to Earth
P102 pin1 to pin2
P102 pin1 to Earth
0
0
0
0
0
P102 pin2 to Earth
Single fault condition (C115 short)
0
P101 pin1 to pin2
P101 pin1 to Earth
38.7
0
P101 pin2 to Earth
P102 pin1 to pin2
P102 pin1 to Earth 42.1
P102 pin2 to Earth
Single fault condition (R115 short)
0.4
P101 pin1 to pin2
P101 pin1 to Earth
P101 pin2 to Earth
P102 pin1 to pin2
2.2
41.9
39.0
0
2.2
42.1
19.4
0
1.1
21.2
21.0
0.2
0
0
0
0
0
0
19.4
0
1.1
21.0
21.1
0.2
19.5
0
1.1
21.1
47
--
47
47
47
1
--
--
--
--
--
--
47
--
46
47
47
1
47
--
47
47
32.9
--
32.9 --
32.9 --
32.9 --
0.7 --
--
--
--
--
--
--
--
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
32.9 --
--
32.2 --
32.9 --
32.9
0.7
32.2
--
Unit shut down, no hazards
--
--
--
Unit shut down, no hazards
32.9 --
32.9 --
TRF originator: SGS Fimko
P102 pin1 to Earth
P102 pin2 to Earth
Single fault condition (C117 short)
41.9
0.4
P101 pin1 to pin2 0
P101 pin1 to Earth
P101 pin2 to Earth
P102 pin1 to pin2
P102 pin1 to Earth
P102 pin2 to Earth
0
0
0
0
0
Single fault condition (C132 short)
P101 pin1 to pin2 0
P101 pin1 to Earth
P101 pin2 to Earth
P102 pin1 to pin2
0
0
0
P102 pin1 to Earth
P102 pin2 to Earth
0
0
Single fault condition (C133 short)
P101 pin1 to pin2
P101 pin1 to Earth
38.4
0
20.1
0.2
0
0
0
0
0
0
0
0
0
0
0
0
Page 54 of 82
47
1
--
--
--
--
--
--
--
--
--
--
--
--
32.9
0.7
--
--
--
--
--
--
--
--
--
--
--
--
Report No.:
--
--
11009010 001
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
Unit shut down, no hazards
19.2
0
47
--
32.9 --
-- Unit shut down, no hazards
P101 pin2 to Earth
P102 pin1 to pin2
P102 pin1 to Earth
P102 pin2 to Earth
2.2
42.1
42.3
0.4
1.1
21.1
21.2
0.2
47
47
47
1
Note(s): Output measured with a 2kΩ non-inductive resistor as load.
2.5 TABLE: limited power source measurement
Limits
32.9 --
32.9 --
32.9 --
0.7 --
Measured
P
Verdict
For main board type A, output connector P308 (to key control board), from pin 1 to earth
According to Table 2B (normal condition), Uoc=5.5V current (in A) apparent power (in VA)
8
Uoc*5 (27.5)
According to Table 2B (R813 shorted in single fault condition), Uoc=5.5V
0.02
0.06
Pass
Pass current (in A) apparent power (in VA)
8
Uoc*5 (27.5)
0.02
0.06
Pass
Pass
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 55 of 82
According to Table 2B (R817 shorted in single fault condition), Uoc=5.5V current (in A) apparent power (in VA)
8
Uoc*5 (27.5)
Report No.:
0.02
0.06
According to Table 2B (I805 pin1-4 shorted in single fault condition), Uoc=5.5V current (in A) 8 0.02 apparent power (in VA) Uoc*5 (27.5) 0.06
11009010 001
Pass
Pass
Pass
Pass
According to Table 2B (I802 pin1-2 shorted in single fault condition), Uoc=5.5V current (in A) 8 0.02 apparent power (in VA) Uoc*5 (27.5) 0.06
Pass
Pass
For main board type A, output connector P308 (to key control board), from pin 4 to earth
According to Table 2B (normal condition), Uoc=5.2V current (in A) apparent power (in VA)
8
Uoc*5 (26)
According to Table 2B (R813 shorted in single fault condition), Uoc=5.2V
0.02
0.06
Pass
Pass
Pass
Pass current (in A) apparent power (in VA)
8
Uoc*5 (26)
According to Table 2B (R817 shorted in single fault condition), Uoc=5.2V current (in A) 8
0.02
0.06
0.02 apparent power (in VA) Uoc*5 (26) 0.06
According to Table 2B (I805 pin1-4 shorted in single fault condition), Uoc=5.2V current (in A) 8 0.02
Pass
Pass
Pass
Pass apparent power (in VA) Uoc*5 (26) 0.06
According to Table 2B (I802 pin1-2 shorted in single fault condition), Uoc=5.2V current (in A) 8 0.02 apparent power (in VA) Uoc*5 (26) 0.06
Pass
Pass
For main board type A, output connector P306 (to speaker), from pin 2,3,4,5 to earth
According to Table 2B (normal condition), Uoc=2.8V current (in A) apparent power (in VA)
8
Uoc*5 (14)
0.02
0.05
Pass
Pass
According to Table 2B (R813 shorted in single fault condition), Uoc=2.8V current (in A) 8 apparent power (in VA) Uoc*5 (14)
According to Table 2B (R817 shorted in single fault condition), Uoc=2.8V current (in A) 8 apparent power (in VA)
TRF No.:IECEN60950_1B
Uoc*5 (14)
0.02
0.05
0.02
0.05
Pass
Pass
Pass
Pass
TRF originator: SGS Fimko
Page 56 of 82
According to Table 2B (I805 pin1-4 shorted in single fault condition), Uoc=2.8V
Report No.: 11009010 001 current (in A) apparent power (in VA)
8
Uoc*5 (14)
0.02
0.05
According to Table 2B (I802 pin1-2 shorted in single fault condition), Uoc=2.8V current (in A) 8 0.02 apparent power (in VA) Uoc*5 (14) 0.05
Pass
Pass
Pass
Pass
Power supply with DC/AC inverter board: PTB-1806
For +20.5Vdc output of power supply with DC/AC inverter board (output to DC/AC inverter)
According to Table 2B in normal condition, U
OC
=25V current (in A) 8 apparent power (in VA) 100
3
53.5
According to Table 2B in fault condition with D811 short, U
OC
=22.41V current (in A) 8 apparent power (in VA) 100
According to Table 2B in fault condition with R811 short, U
OC
=
1) current (in A) apparent power (in VA)
8
5 * Uoc =
1)
According to Table 2B in fault condition with I802 pin1 open, U
OC
=
1) current (in A) apparent power (in VA)
8
5 * Uoc =
1)
According to Table 2B in fault condition with I802 pin1-pin2 short, U
OC
=
1) current (in A) apparent power (in VA)
8
5 * Uoc =
1)
According to Table 2B in fault condition with I802 pin4 open, U
OC
=
1) current (in A) apparent power (in VA)
8
5 * Uoc =
1)
According to Table 2B in fault condition with I802 pin3-pin4 short, U
OC
=
1) current (in A) apparent power (in VA)
8
5 * Uoc =
1)
1.39
29.54
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass current (in A)
For P310 connector (on main board type B, output to speaker)
According to Table 2B in normal condition, pin 1 to earth U
OC
=2.67V
8 2.5 apparent power (in VA) 5 * Uoc = 13.35 3.8
According to Table 2B in normal condition, pin 2 to earth U
OC
=2.67V current (in A)
TRF No.:IECEN60950_1B
8 2.5
Pass
Pass
Pass
TRF originator: SGS Fimko
Page 57 of 82 apparent power (in VA) 5 * Uoc = 13.35
According to Table 2B in normal condition, pin 3 to earth U
OC
=2.67V current (in A) 8
Report No.:
3.8
11009010 001
Pass apparent power (in VA) 5 * Uoc = 13.35
According to Table 2B in normal condition, pin 4 to earth U
OC
=2.67V current (in A) 8
2.4
3.8
2.4
Pass
Pass apparent power (in VA) 5 * Uoc = 13.35 3.8 Pass
According to Table 2B in fault condition with condition: R811 short/I802 pin1 open/I802 pin1-pin2 short/ I802 pin4 open/I802 pin3-pin4 short, U
OC
=
1) current (in A) 8
1)
Pass apparent power (in VA) 5 * Uoc =
1) 1)
Pass
For P307 connector (on main board type B, output to key control board)
According to Table 2B in normal condition, pin 1 to earth U
OC
=
1) current (in A) 8
1) apparent power (in VA) 5 * Uoc =
1)
According to Table 2B in normal condition, pin 2 to earth U
OC
=
1)
1) current (in A) apparent power (in VA)
8
5 * Uoc =
1)
1)
1)
Pass
Pass
Pass
Pass
Pass
According to Table 2B in normal condition, pin 3 to earth U
OC
=1.98V current (in A) 8 apparent power (in VA) 5 * Uoc = 3.96
According to Table 2B in normal condition, pin 4 to earth U
OC
=2.66V current (in A) 8 apparent power (in VA) 5 * Uoc = 13.3
0.02
0.04
Pass
Pass
0.01
0.03
Pass
Pass
According to Table 2B in normal condition, pin 5 to earth U
OC
=2.66V current (in A) 8 0.01 Pass apparent power (in VA) 5 * Uoc = 13.3 0.03 Pass
According to Table 2B in fault condition with condition: R811 short/I802 pin1 open/I802 pin1-pin2 short/ I802 pin4 open/I802 pin3-pin4 short, U
OC
=
1) current (in A) 8
1)
Pass apparent power (in VA) 5 * Uoc =
1) 1)
Pass
For USB ports
According to Table 2B in normal condition, U
OC
=5.1V current (in A) 8 apparent power (in VA) 5 * Uoc = 25.5
0.9
4.19
Pass
Pass
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 58 of 82 Report No.: 11009010 001
According to Table 2B in fault condition with condition: I603 pin5-pin7 short, U
OC
=5.1V current (in A) 8 0.95 Pass apparent power (in VA) 5 * Uoc = 25.5 4.17 Pass
Note(s):
1)
2)
Unit shut down.
Input Voltage is 240Vac, 60Hz
2.6.3.4 TABLE: ground continue test P
Location Resistance measured (mΩ) Comments
Unit with Power supply with DC/AC inverter board: PTB-1725
7 Test current at 25A, for 1 min. The PE pin of AC inlet to the signal cable
The PE pin of AC inlet to the signal cable
7 Test current at 40A, for 2 min.
The PE pin of AC inlet to the earth trace of C802
The PE pin of AC inlet to the earth trace of C802
13
13
Test current at 25A, for 1 min.
Test current at 40A, for 2 min.
AC inlet earth pin to metal enclosure
Unit with Power supply with DC/AC inverter board: PTB-1806
15.9 25A, 1min
16.7 40A, 2min AC inlet earth pin to C825 earthed trace
AC inlet earth pin to C825 earthed trace
13.6 25A, 1min
17.0 40A, 2min AC inlet earth pin to C808 earthed trace
AC inlet earth pin to C808 earthed trace
15.1 25A, 1min
Note(s):
2.10.2
Location
Table: working voltage measurement
RMS voltage (V) Peak voltage (V) Comments
P
T801 pin 1 to pin 8
T801 pin 1 to pin 9, 10
T801 pin 1 to pin 11
TRF No.:IECEN60950_1B
Power supply with DC/AC inverter board: PTB-1725
273 588 Max. Vpeak and Vrms of T801
269
261
580
580
TRF originator: SGS Fimko
Page 59 of 82 Report No.: 11009010 001
T801 pin 1 to pin 12
T801 pin 1 to pin 13
T801 pin 4 to pin 8
T801 pin 4 to pin 9, 10
T801 pin 4 to pin 11
T801 pin 4 to pin 12
T801 pin 4 to pin 13
T801 pin 6 to pin 8
237
256
214
216
217
165
222
620
576
388
396
428
288
464
420
396
376
312
388
372
376
T801 pin 6 to pin 9, 10
T801 pin 6 to pin 11
T801 pin 6 to pin 12
T801 pin 6 to pin 13
T801 pin 7 to pin 8
T801 pin 7 to pin 9, 10
T801 pin 7 to pin 11
T801 pin 7 to pin 12
T801 pin 7 to pin 13
215
216
213
167
213
214
212
I802 pin 1 – pin 3
I802 pin 1 – pin 4
I802 pin 2 – pin 3
I802 pin 2 – pin 4
T801 pin 1 to pin 6
T801 pin 1 to pin 7, 8
T801 pin 1 to pin 9
T801 pin 1 to pin 10
T801 pin 3 to pin 6
T801 pin 3 to pin 7, 8
T801 pin 3 to pin 9
T801 pin 3 to pin 10
T801 pin 4 to pin 6
T801 pin 4 to pin 7, 8
T801 pin 4 to pin 9
T801 pin 4 to pin 10
T801 pin 5 to pin 6
TRF No.:IECEN60950_1B
214
165
214
216
216
388
268
392
376
376
216
216
376
376
Power supply with DC/AC inverter board: PTB-1806
273
268
524
532
Highest Vrms of T801
Highest Vpk of T801
261 524
252
217
217
217
220
217
215
214
214
213
516
376
396
436
472
428
416
388
396
372
TRF originator: SGS Fimko
Page 60 of 82
T801 pin 5 to pin 7, 8
T801 pin 5 to pin 9
T801 pin 5 to pin 10
C808 primary to secondary
I802 pin 1 to pin 3
I802 pin 1 to pin 4
213
215
217
213
216
216
376
388
396
372
376
376
I802 pin 2 to pin 3
I802 pin 2 to pin 4
Note(s): Input Voltage is 240Vac, 60Hz
216
216
376
376
2.10.3 and
2.10.4
TABLE: clearance and creepage distance measurements
Clearance cl and creepage distance dcr at/of:
Up
(V)
U r.m.s.
(V)
Required cl (mm)
Report No.: cl
(mm)
Primary components (with
10N) to earthed metal enclosure
Power supply with DC/AC inverter board: PTB-1725
420 250 2.0 2.5
T803 to metal stud of earthed metal enclosure
5.0
420 250 2.0 See below Primary traces to earthed trace of SPS
Near C803
Near T802
2.5
2.5
Under C802
Under C808
3.3
2.5
Near C806
D815 trace to earthed trace
2.7
2.8
2.0 Line/neutral trace to earthed trace
Primary traces to secondary trace of SPS
420 250 4.0 See below
Under I802
Under C805
Under C836
Under T801
Between fuse two ends
1).
588
420
273
250
4.6
1.5
4.5
7.5
7.6
7.6
6.0
Required dcr (mm)
2.5
2.5
5.0
5.8
2.5
11009010 001
P dcr
(mm)
2.5
5.0
See below
See below
5.0
7.5
7.6
7.6
6.0
2.5
2.5
3.3
2.5
2.7
2.8
2.5
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Primary trace before fuse
1).
420
Page 61 of 82
250 1.5 2.9
Report No.:
2.5
11009010 001
2.9 trace of SPS
Under C820
Under C825
Near C819
Line/neutral trace to earthed trace
Power supply with DC/AC inverter board: PTB-1806
420 250 2.0 See above
6.8
6.8
6.7
4.0
2.5 See above
6.8
6.8
6.7
4.7
420 250 4.0 See above 5.0 See above trace of SPS
Under I802
Under C808
Under T801
Between fuse two ends
1).
Primary trace before fuse
1).
532
420
420
273
250
4.4
1.5
5.0
7.3
6.9
7.2
2.5
5.8
2.5
2.5
6.1
7.3
6.9
7.2
4. 0 250 1.5
Note(s):
1. Functional insulation, see clause 5.3.4 a).
2. Other functional insulation according to sub-clause 5.3.4 c).
For Power supply with DC/AC inverter board: PTB-1725
- There is one cut slot (1.2mm x 11.1mm) between Line/Neutral trace and earthed trace of AC inlet.
- There is one cut slot (1.4mm x 7.9mm) under I802 primary and secondary race.
- Glued components: C836, C805, C801.
- There is a mylar sheet (170mm x 210mm min.) between component side of power supply with DC/AC inverter board and metal enclosure type A.
For Power supply with DC/AC inverter board: PTB-1806
- There are two L type slots (1.2mm x 8.5mm x 7.1mm) between Line/Neutral trace.
- There is one cut slot (1.6mm x 7.9mm) under I802 primary and secondary race.
- Glued component: C805.
- There is a mylar sheet (170mm x 210mm min.) between component side of power supply with DC/AC inverter board and metal enclosure type B.
2.10.5 TABLE: distance through insulation measurements
Distance through insulation di at/of:
Photo coupler (reinforced insulation)
U r.m.s.
(V)
250
Test voltage
(V)
3000
Required di
(mm)
0.4
P di
(mm)
1)
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
P
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
T801 core (class B)
C808 body
I802 body
PCB near R808
T101 coil (DC/AC inverter)
T101 core (DC/AC inverter)
PCB near I306 (main board)
Plastic enclosure inside
Plastic enclosure outside
LCD Panel
Ambient
Ambient during test
Page 63 of 82
88.0
77.5
71.8
91.3
78.2
77.8
78.1
60.4
56.1
50.1
40.0
26.5
Report No.:
89.2
75.6
70.3
71.8
77.9
77.7
77.9
60.1
56.1
50.1
40.0
26.4
11009010 001
Power supply with DC/AC inverter board: PTB-1725 with USB port
Appliance Inlet near line pin 51.5 50.6
C803 body
T802 coil
64.2
81.5
58.5
63.8
T803 coil
C801 body
T801 coil (class B)
87.1
78.4
98.6
65.9
67.4
100.7
T801 core (class B)
I802 body
PCB under R801
T102 coil
T102 core
PCB near I306 (main board)
Plastic enclosure inside
97.6
72.5
104.4
105.9
102.1
69.0
58.4
100.0
69.8
80.1
104.7
101.8
68.5
57.9
Plastic enclosure outside
LCD Panel
Ambient
Ambient during test
Temperature T of winding:
Note(s):
R
1
(Ω)
54.6
51.4
40.0
26.3
R
2
(Ω)
54.1
51.6
40.0
26.3
T
(°C) allowed
T max
(°C)
110
100
105
130
130
105
--
95
--
--
--
70
85
130
130
85
110 insulation class
110
85
100
105
130
130
105
--
95
--
--
--
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 64 of 82 Report No.: 11009010 001
1. The temperatures were measured under the worse case normal mode defined in 1.2.2.1 and as described in sub-clause 1.6.2 at voltages as described above.
2. With a specified ambient temperature of 40°C.
3. The maximum temperatures are calculated as follows:
Winding components (with safety isolation):
- Class B → Tmax = 120 °C - 10 °C = 110°C
4.5.2 TABLE: ball pressure test of thermoplastic parts P
Part allowed impression diameter (mm) .................. : ≤ 2 mm
Test temperature
(°C)
Power supply with DC/AC inverter board: PTB-1725
125 Bobbin of T802 and T803 / Nan Ya, type 1403G3 (0.75mm)
Power supply with DC/AC inverter board: PTB-1806
E I Dupont, type FR530L+ of transformer T801 125
Impression diameter
(mm)
1.2
1.5
Note(s):
4.6.1, 4.6.2 Table: enclosure openings
Location
Internal metal enclosure type A
Top
Rear (left and right side)
Left Side
Right Side
Bottom
2)
Size (mm) Comments
P
∅4.5mm Numerous circle openings, cover area 25mm x 315mm.
∅4.5mm Numerous circle openings, cover area 145mm x 55mm (left side) and 145mm x 55mm (right side).
∅4.5mm Numerous circle openings at an area 23mm
35mm.
∅4.5mm Numerous circle openings at an area 23mm
35mm.
Ø1.8mm, Numerous circle openings at an area 312mm
Central to central: 5.0mm,
Thickness: 0.81mm x 35mm.
External plastic enclosure type A
Top
Rear
Side
3.6mm x 40mm Numerous rectangle openings cover area
40mm 340mm.
N/A No openings.
N/A No openings.
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 65 of 82 Report No.: 11009010 001
Bottom 3.9mm x 25mm Numerous rectangle openings cover area
25mm x 130mm and 25mm x 33mm (two blocks).
Internal metal enclosure type B
Top ∅4.5mm Numerous circle openings, cover area
34.5mm x 315mm.
Rear (left and right side)
Left Side
2)
∅4.5mm Numerous circle openings, cover area 145mm x 55.5mm.
∅4.5mm Numerous circle openings at an area 25mm
35mm.
Right Side
Bottom
∅4.5mm Numerous circle openings at an area 25mm
35mm.
Ø1.8mm, Numerous circle openings at an area 230mm
Central to central: 5.0mm,
Thickness: 0.81mm x 27mm and 25mm x 27mm.
External plastic enclosure type B
Top 2.6mm x 40mm Numerous rectangle openings cover area
40mm 340mm.
Rear
Side
Bottom
N/A No openings.
N/A No openings.
3.6m x 25.6mm Numerous rectangle openings cover area
25.6mm x 130mm and 25.6mm x 31mm (two blocks).
Note(s):
1) The internal metal enclosure was considered as fire enclosure.
2) According to user’s manual, the unit can’t adjust downward, therefore the rear opening considered as
side opening to prevent subjects drop into fire enclosure.
3) The construction of alternative plastic enclosure type C is similar to enclosure shape type A except USB part.
4.7
Part
Table: resistance to fire
Manufacturer of material Type of material
Note(s): Internal metal enclosure was considered as fire enclosure.
5.1.6 TABLE: touch current measurement
Condition L→ terminal A
(mA)
N → terminal A
(mA)
Power supply with DC/AC inverter board: PTB-1725
Limit
(mA)
Comments
Thickness
(mm)
N/A
Flammability class
P
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 66 of 82
System ON (Fuse in)
System ON (Fuse out)
System ON (Fuse in)
1.7
0.02
0.01
1.7
3.4
0.01
Power supply with DC/AC inverter board: PTB-1806
System ON (Fuse in)
System ON (Fuse in)
0.19
0.19
0.20
0.20
3.5
3.5
0.25
3.5
3.5
Report No.:
To metal enclosure/output connector, switch “e” opened.
To metal enclosure/output connector, switch “e” opened.
To plastic enclosure with metal foil, switch “e” opened.
11009010 001
To metal enclosure, switch “e” opened.
To earthed output connector, switch
“e” opened.
System ON (Fuse in)
0.01 0.01 0.25 To plastic enclosure with metal foil, switch “e” closed.
Note(s):
Input voltage:
Input frequency:
264V
60Hz
Overall capacity:
C802=C805=C808=C836=C838=C839=4700pF (Power supply with DC/AC inverter board: PTB-1725);
C808=C820=C825=4700pF (Power supply with DC/AC inverter board: PTB-1806)
5.2 TABLE: electric strength tests and impulse tests
Test voltage applied between: Test voltage (V)
Power supply with DC/AC inverter board: PTB-1725
P
Breakdown
Unit: primary and secondary
Unit: primary and Earth
T801: primary and secondary
DC 4242
DC 2651
AC 3000
No
No
No
T801: primary and core
T801: secondary and core
2 layers of insulation tape
Mylar sheet
AC 1875
AC 1875
AC 3000
AC 1500
Power supply with DC/AC inverter board: PTB-1806
No
No
No
No
Unit: primary and secondary
Unit: primary and earth
T801: primary and secondary
T801: primary and core
T801: secondary and core
Two layers of insulation tape of T801
Mylar sheet
DC 4242
DC 2550
AC 3000
AC 1803
AC 1803
AC 3000
AC 1500
No
No
No
No
No
No
No
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 67 of 82 Report No.: 11009010 001
Note(s):
5.3 TABLE: fault condition tests P ambient temperature (°C) ...................................... : 25°C, if not otherwise stated model/type of power supply ................................... : See below manufacturer of power supply ............................... : See append table 1.5.1
rated markings of power supply ............................. : See append table 1.5.1
No.
1
2
Component no.
T801 pin 11 to pin 13
T801 pin 11 to pin 10
Fault Test voltage (V)
Test time
Fuse no.
Fuse current (A)
Result
Power supply with DC/AC inverter board: PTB-1725 s-c 240 10 min F801 0.08-0.14 Unit shut down, no components damaged, no hazards s-c 240 10 min F801 0.08-0.15 Unit shut down, no components damaged, no hazards
3
4
5
6
7
8
9
T801 pin 9 to pin
8
T801 pin 1 to pin
4
T801 pin 6 to pin
7
D805
D812
D807
C815
10 C812
11 C823 s-c s-c s-c s-c s-c s-c s-c s-c s-c
240
240
240
240
240
240
240
240
240
10 min F801 0.08-0.15 No display, no components damaged, no hazards
10 min F801 0.08-0.2 Unit shut down, no components damaged, no hazards
10 min F801 0.08 Unit shut down, no components damaged, no hazards
1 sec F801 0.08-0.12 No display, no components damaged, no hazards
10 min F801 0.08-0.12 Unit shut down, no components damaged, no hazards
10 min F801 0.08-0.13 Unit shut down, no components damaged, no hazards
10 min F801 0.08-0.14 Unit shut down, no components damaged, no hazards
10 min F801 0.08-0.14 Unit shut down, no components damaged, no hazards
10 min F801 0.08-0.12 Unit shut down, no components damaged, no hazards
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 68 of 82 Report No.: 11009010 001
12 I802 pin 4
13 I802 pin 1 to pin
2
14 I802 pin 3 to pin
4
15 Q801 pin G to pin
D
16 Q801 pin G to pin
S
17 Q801 pin D to pin
S
18 C801
19 D802
20 D813
21 T801 pin 13 to pin 8 (after D805)
22 T801 pin 11 to pin 8 (after D807)
23 T801 pin 10 to pin 8(after D812)
24 D808
25 C805
26 Q803 (D-S)
27 Q803 (D-G)
28 R811
29 I802 pin 3 to pin
4 o-c s-c s-c s-c s-c s-c s-c s-c s-c o-l o-l o-l
240
240
240
240
240
240
240
240
240
240
240
240
10 min F801 0.08 No display, no components damaged, no hazards
10 min F801
10 min F801 0.08-0.12 No display, no components damaged, no hazards
1 sec F801 0.02 Unit shut down, no components damaged, no hazards
10 min F801
0.08 No display, no components damaged, no hazards
1 sec F801
0.2 No display, no components damaged, no hazards
0.2 No display, no components damaged, no hazards
1 sec F801
1 sec F801
10 min F801
-- F801 damaged, no hazards.
-- F801 damaged, no hazards.
6.5 hrs
7.5 hrs
7.0 hrs
F801
F801
F801
0.02 No display, no components damaged, no hazards
-- Overload to 5.0A, no components damaged, T801 coil = 148°C, T801 core =
111°C, ambient = 25°C, no hazards.
-- Overload to 6.0A, no components damaged, T801 coil = 136°C, T801 core =
126°C, ambient = 25°C, no hazards.
-- Overload to 8.0A, no components damaged, T801 coil = 138°C, T801 core =
130°C, ambient = 22°C, no hazards.
Power supply with DC/AC inverter board: PTB-1806 s-c s-c s-c
240
240
240
1 sec
1 sec
30 min
F801
F801
F801
-- F801 opened, no hazards.
-- F801 opened, no hazards. s-c 240 30 min F801
0.04 Unit shutdown, I801 and
R813 damaged, no hazards.
0.04 Unit shutdown, I801 damaged, no hazards. s-c s-c
240
240
30 min F801
30 min F801
0.04 Unit shutdown, I801 damaged, no hazards.
0.05 Unit shutdown, Internal protection operated (I801), no hazards.
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
30 I802 pin 1 to pin
2
31 I802 pin 4 s-c o-c
240
Page 69 of 82
30 min F801
240 30 min F801
240 30 min F801
240 30 min F801
32 I802 pin 1
33 D809 o-c s-c
34 D810 s-c
35 T801 pin 4 to pin
5 s-c
36 T801 pin 10 to pin 6
37 T801 pin 8,7 to pin 6 s-c s-c
38 T801 pin 1 to pin
3 s-c
39 T801 pin 10 to pin 8,7 s-c
40 I801 pin 3 to pin
2
41 +20.5Vdc output s-c s-c
42 +5Vdc ouptut s-c
43 T801 pin 7,8 to pin 6 (after D810) o-l
240
240
240
240
240
240
240
240
240
240
30 min
30 min
30 min
30 min
30 min
30 min
30 min
30 min
30 min
7 hrs
F801
F801
F801
F801
F801
F801
F801
F801
F801
F801
Report No.: 11009010 001
0.05 Unit shutdown, Internal protection operated (I801), no hazards.
0.04 Unit shutdown, Internal protection operated (I801), no hazards.
0.05 Unit shutdown, Internal protection operated (I801), no hazards.
0.04 Unit shutdown, Internal protection operated (I801), no hazards.
0.06 Unit shutdown, Internal protection operated (I801), no hazards.
0.05 Unit shutdown, Internal protection operated (I801), no hazards.
0.05 Unit shutdown, Internal protection operated (I801), no hazards.
0.06 Unit shutdown, Internal protection operated (I801), no hazards.
0.07 Unit shutdown, no components damaged, no hazards.
0.1 Unit shutdown, no components damaged, no hazards.
0.08 I801 and I802 damaged, no hazards.
0.04 Unit shutdown, Internal protection operated (I801), no hazards.
0.04 Unit shutdown, Internal protection operated (I801), no hazards.
0.67 When overloaded to 5.8A unit shutdown. Temp was stable at 5.4A. Max. temp of
T801 coil=79.8ºC, T801 core=71.2ºC, I802 body=39.7ºC,
Ambient=26.3ºC, no hazard.
Complied sub clause 5.3.8.
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 70 of 82 Report No.: 11009010 001
44 T801 pin 10 to pin 6 (after D809) o-l 240 15.5 hrs F801 0.66 When overloaded to 2.8A unit shutdown. Temp was stable at 2.6A. Max. Temp of
T801 coil=74.4ºC, T801 core=67.2ºC, I802 body=37.6ºC,
Ambient=27.8ºC, no hazard.
Complied sub clause 5.3.8.
45 Ventilation openings (plastic enclosure type A)
46 Ventilation opening (plastic enclosure type B)
Blocke d blocke d
240
240
3 hrs
1 hr 20 min
F801
F801
0.65 Temp. was stabled. T801 coil=64.5°C, T801 core=46.6°C, T101 coil=78.6°C, T102 coil=83.2°C, ambient=21.8°C, no hazards.
0.42 Temperatures were stabled.
Max. temp. of T801 coil=84.8°C, T801 core=79.4°C, I802 body=61.3°C, ambient=26.1°C.
47 Ventilation opening (plastic enclosure type A with USB port blocke d
240 1 hr 50 min
F801 0.57 Temperatures were stabled.
Max. temp. of T801 coil=94.1°C, T801 core=93.6°C, I802 body=64.6°C, ambient=26.4°C.
Note(s):
1). In fault column, where s-c=short-circuited, o-c=open-circuited, o-l = overload.
2). For fuse opened conditions were tested with each source of fuse.
3). Temp. limited of transformer (class B) according to table C.1 is 175°C -(40°C -25°C)=160°C.
C.2 Safety isolation transformer P
Type:
Construction details:
Transformer part name: T801 of Power supply with DC/AC inverter board: PTB-1725
Manufacturer: See appended table 1.5.1
See appended table 1.5.1
588V
4.0mm+0.6mm
Recurring peak voltage
Required clearance for reinforced insulation
(from table 2H and 2J)
Effective voltage rms
Required creepage distance for reinforced insulation
(from table 2L with linear interpolation)
TRF No.:IECEN60950_1B
273V
5.8
TRF originator: SGS Fimko
Measured min. creepage distance
Location prim-sec
Page 71 of 82
6.4
Report No.: 11009010 001 inside (mm)
6.4 outside (mm)
prim-core
sec-core prim-prim
Measured min. clearances
Location prim-sec
3.2
3.2
--
6.4 inside (mm)
3.2
3.2
-- outside (mm)
6.4
prim-core
sec-core prim-prim
3.2
3.2
--
Construction:
Concentric windings on ETD-34 (3C90/TP4/PC40) type core (horizontal orientation), three layers insulation tape between primary and secondary windings. Three layers of insulation tape are wrapped on external core surface. Core is considered as floating part. Distance tape is 3.2mm on both sides of transformer bobbin.
Winding ends additionally fixed with tape, outer winding is primary. Tubing on all winding exit ends are leaded above the distance tape.
Pin numbers
Prim.
3.2
3.2
--
6-7, 1-3-4
Sec.
Bobbin
Material
13-11-10, 9-8
Phenolic, Chang Chun, T375J, V-0, 150°C min. 0.8mm Thickness
Electric strength test
With 3000 V a.c. after humidity treatment
Result
C.2 Safety isolation transformer
Pass
P
Construction details:
Transformer part name: T801 of power supply with DC/AC inverter board: PTB-1806
Manufacturer: See appended table 1.5.1
Type: See appended table 1.5.1
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 72 of 82 Report No.: 11009010 001
Remark: All sources of T801 are identical except for model name and manufacture.
Recurring peak voltage
Required clearance for reinforced insulation
(from table 2H and 2J)
532
4.4mm
Effective voltage rms
Required creepage distance for reinforced insulation
(from table 2L with linear interpolation)
Measured min. creepage distance
Location prim-sec prim-core sec-core prim-prim
273
5.8mm
6.4
3.0
3.2
-- inside (mm) outside (mm)
22.0 (pin to pin);
6.0 (winding to pin)
5.8 (pin to core)
5.8 (pin to core)
--
Measured min. clearances
Location prim-sec prim-core sec-core prim-prim
6.4
3.0
3.2
-- inside (mm) outside (mm)
22.0 (pin to pin);
6.0 (winding to pin)
5.8 (pin to core)
5.8 (pin to core)
--
Construction:
Concentric windings on bobbin (horizontal type core). Three layers insulation tape around outer winding
(consider as primary). Three layers insulation tape between primary winding and secondary winding. The core is considered as floating part. Distance tape of bobbin: 3.0mm min. on primary side winding (N1, N5); 3.2mm min. on primary side winding (N6) and all secondary side winding; 3.5mm min. on primary side winding (N2,
N3, N4). The bottom side of bobbin (near primary or secondary pin) is further cover with one layer insulation tape. Side of core near primary or secondary pin is further cover with two layers of insulation tape. Tubing on all winding exit ends are leaded above the distance tape. Pin 2 cut off.
Pin numbers
Prim.
Sec.
Bobbin
Material
1-2-3, 4-5
10-9-8, 7-6
EI Dupont, FR530L+, V-0, 155°C
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Thickness
Electric strength test
With 3000 V a.c. after humidity treatment
Result
Page 73 of 82 min. 0.8mm
Pass
Report No.: 11009010 001
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Clause Requirement − Test
Page 74 of 82
National Differences
Report No.:
Result – Remark
11009010 001
Verdict
TRF No.:IECEN60950_1B TRF originator: SGS Fimko
Page 75 of 82
National Differences
Report No.:
Clause Requirement − Test Result – Remark
APPENDIX Australian National Differences according to CB Bulletin No. 110A, June 2006
(AS/NZS 60950.1:2003)
11009010 001
Verdict
P
(IEC Publication 60950-1:2001)
EXPLANATION FOR ABBREVIATIONS
P=Pass, F=Fail, N/A=Not applicable. Placed in the column to the right.
1.2
Annex ZZ Variations
Between the definitions for "Person, service" and
"Range, rated frequency" insert the following:
Inserted. N/A
Potential ignition source 1.2.12.201
1.2.12.15 After the definition of 1.2.12.15, add the following: Added.
1.2.12.201 Potential ignition source:
Possible fault which can start a fire if the opencircuit voltage measured across an interruption or faulty contact exceeds a value of 50 V (peak) a.c. or d.c. and the product of the peak value of this voltage and the measured r.m.s. current under normal operating conditions exceeds 15 VA.
Such a faulty contact or interruption in an electrical connection includes those which may occur in conductive patterns on printed boards.
NOTE 201: An electronic protection circuit may be used to prevent such a fault from becoming a potential ignition source.
NOTE 202: This definition is from AS/NZS
60065:2003.
1.5.1 Add the following to the end of first paragraph:
"or the relevant Australian/New Zealand
Standard."
Added.
1.5.2
2.1
3.2.3
3.2.5
Add the following to the end of first and third dash items:
Added.
"or the relevant Australian/New Zealand
Standard."
Delete the Note.
Delete Note 2.
Modify Table 3B as follows:
Deleted.
Deleted.
Modified.
Rated current of equipment A
Over 0.2 up to and including 3
Nominal crosssectional area mm
2
0.5
1)
AWG or kcmil
(cross-sectional area in mm
2
) see note 2
18 [0.8]
N/A
N/A
N/A
N/A
N/A
N/A
Australian National Differences according to CB Bulletin No. 110A, June 2006
Page 76 of 82
National Differences
Report No.:
Result – Remark
11009010 001
Verdict Clause Requirement − Test
Over 3 up to and including 7.5
Over 7.5 up to and including 10
Over 10 up to and including 16
0.75
(0.75)
(1.0)
2)
3)
1.00
1.5
16 [1.3]
16 [1.3]
14 [2]
4.3.6
Replace footnote 1) with the following:
1)
This nominal cross-sectional area is only allowed for Class II appliances if the length of the power supply cord, measured between the point where the cord, or cord guard, enters the appliances, and the entry to the plug does not exceed 2 m (0.5 mm² three-core supply flexible cords are not permitted; see AS/NZS 3191).
Delete Note 1.
Replace paragraph three with:
Equipment with a plug portion, suitable for insertion into a 10 A 3-pin flat-pin socket-outlet complying with AS/NZS 3112, shall comply with the requirements in AS/NZS 3112 for equipment with integral pins for insertion into socket-outlets.
Replaced.
4.3.13.5 Add the following to the end of the first paragraph: Added.
", or AS/NZS 2211.1"
4.7 Add the following paragraph:
For alternative tests refer to clause 4.7.201.
See below.
4.7.201 Add the following after clause 4.7.3.6:
4.7.201 Resistance to fire - Alternative tests
Added.
However, equipment under test and materials and components in compliance with requirements of
IEC 60950-1. Alternative test methods were not considered.
4.7.201.1 General
Parts of non-metallic material shall be resistant to ignition and spread of fire.
This requirement does not apply to decorative trims, knobs and other parts unlikely to be ignited or to propagate flames originating from inside the apparatus, or the following:
See above.
(a) Components that are contained in an enclosure having a flammability category of
FV-0 according to AS/NSZ 4695.707 and having openings only for the connecting wires filling the openings completely, and for the
Australian National Differences according to CB Bulletin No. 110A, June 2006
N/A
N/A
N/A
N/A
N/A
Page 77 of 82
National Differences
Report No.:
Result – Remark
11009010 001
Verdict Clause Requirement − Test ventilation not exceeding 1 mm in width regardless of the length.
(b) The following parts which would contribute negligible fuel to a fire:
- small mechanical parts, the mass of which does not exceed 4 g, such as mounting parts, gears, cams, belts and bearings;
- small electrical components, such as capacitors with a volume not exceeding
1750 mm
3
, integrated circuits, transistors and optocoupler packages, if these components are mounted on material flammability category FV-1 or better according to AS/NZS
4695.707
NOTE - In considering how to minimize propagation of fire and what “small parts” are, account should be taken of the cumulative effect of small parts adjacent to each other for the possible effect of propagating fire from one part to another.
Compliance is checked by tests of 4.7.201.2,
4.7.201.3, 4.7.201.4 and 4.7.201.5.
For the base materials of printed boards, compliance is checked by the test of 4.7.201.5.
The tests shall be carried out on parts of nonmetallic material, which have been removed from the apparatus. When the glow-wire test is carried out, the parts shall be placed in the same orientation, as they would be in normal use.
These tests are not carried out on internal wiring.
4.7.201.2 Parts of non-metallic material are subjected to glow wire test of AS/NZS 4695.2.11, which is carried out at 550 °C.
Parts for which the glow-wire test cannot be carried out, such as those made of soft or foamy material, shall meet the requirements specified in
ISO 9772 for category FH-3 material. The glowwire test shall be not carried out on parts of materials classified at least FH-3 according to
ISO 9772 provided that the sample was not thicker than the relevant part.
See above.
4.7.201.3 Testing of insulating materials
Parts of insulating materials supporting potential ignition sources shall be subject to the glow-wire test of AN/NZS 4695.2.11, which is carried out at
750 °C.
The test shall be also carried out on other parts of
See above.
Australian National Differences according to CB Bulletin No. 110A, June 2006
N/A
N/A
Page 78 of 82
National Differences
Report No.:
Result – Remark
11009010 001
Verdict Clause Requirement − Test insulating material which are within a distance of
3 mm of the connection.
NOTE - Contacts in components such as switch contacts are considered to be connections.
For parts, which withstand the glow-wire test but produce a flame, other parts above the connection within the envelope of a vertical cylinder having a diameter of 20 mm and a height of 50 mm shall be subjected to the needle-flame test. However, parts shielded by a barrier which meets the needle-flame test shall not be tested.
The needle-flame test shall be made in accordance with AS/NZS 4695.2.2 with the following modifications:
5 Severities
Replace with:
The duration of application of the test flame shall be 30 s ± 1 s.
8 Test procedure
8.2 Modification:
Replace the first sentence with:
The specimen shall be arranged so that the flame can be applied to a vertical or horizontal edge as shown in the examples of figure 1.
8.4 Modification:
The first paragraph does not apply.
Addition:
If possible, the flame shall be applied at least
10 mm from a corner.
8.5 Replacement:
The test shall be made on one specimen. If the specimen does not withstand the test, the test may be repeated on two further specimens, both of which shall then withstand the test.
10 Evaluation of test results
Replace with:
The duration of burning (t b
) shall not exceed 30 s.
However, for printed circuit boards, it shall not exceed 15 s.
The needle-flame test shall not be carried out on parts of material classified as V-0 or V-1
Australian National Differences according to CB Bulletin No. 110A, June 2006
Page 79 of 82
National Differences
Report No.:
Result – Remark
11009010 001
Verdict Clause Requirement − Test according to IEC 60695-11-10, provided that the sample tested was not thicker than the relevant part.
4.7.201.4 Testing in the event of non-extinguishing material See above.
If parts, other than enclosures, do not withstand the glow-wire tests of 4.7.201.3, by failure to extinguish within 30 s after the removal of the glow-wire tip, the needle-flame test detailed in
4.7.201.3 is made on all parts of non-metallic material which are within a distance of 50 mm or which are likely to be impinged upon by flame during the tests of 4.7.201.3. Parts shielded by a separate barrier which meets the needle-flame test need not to be tested.
NOTE 1 - If the enclosure does not withstand the glow-wire test the equipment is considered to have failed to meet the requirement of clause
4.7.201 without the need for consequential testing.
NOTE 2 - If other parts do not withstand the glowwire test due to ignition of the tissue paper and if this indicates that burring or glowing particles can fall onto an external surface underneath the equipment, the equipment is considered to have failed to meet the requirement of clause 4.7.201 without the need for consequential testing.
NOTE 3 - Parts likely to be impinged upon by the flame are considered to be those within the envelope of a vertical cylinder having a radius of
10 mm and a height equal to the height of the flame, positioned above the point of the material supporting in contact with or in close proximity to connections.
N/A
4.7.201.5 Testing of printed boards
The base material of printed boards is subjected to needle-flame test to Clause 4.7.201.3. The flame is applied to the edge of the board where the heat sink effect is lowest when the board is positioned as in normal use. The flame shall not be applied to an edge, consisting of broken perforations, unless the edge is less than 3 mm for a potential ignition source.
The test is not carried out if the –
- Printed board does not carry any potential ignition source;
For PCB material refer to table
1.5.1 of IEC 60950-1 test report.
- Base material of printed boards, on which the available apparent power at a connection exceeds 15 VA operating at a voltage exceeding 50 V and equal or less than 400 V
Australian National Differences according to CB Bulletin No. 110A, June 2006
N/A
Clause
6.2.2
6.2.2.1
Page 80 of 82
National Differences
Report No.:
Result – Remark
11009010 001
Verdict Requirement − Test
(peak) a.c. or d.c. under normal operating conditions, is of flammability category FV-1 or better according to AS/NZS 4695.707, or the printed boards are protected by an enclosure meeting the flammability category FV-0 according to AS/NZS 4695.707, or made of metal, having openings only for connecting wires which fill the opening completely, or
- Base material of printed boards, on which the available apparatus power at a connection exceeds 15 VA operating at a voltage exceeding 400 V (peak) a.c. or d.c. under normal operating conditions, and base material printed boards supporting spark gaps which provide protection against overvoltages, is of flammability category FV-0 according to
AS/NSZ 4695.707 or the printed boards are contained in a metal enclosure, having openings only for connecting wires fill the openings completely.
Compliance is determined using the smallest thickness of the material.
NOTE - Available apparent power is the maximum apparent power, which can be drawn from the supplying circuit through a resistive load whose value is chosen to maximise the apparent power for more than 2 min when the circuit supplied is disconnected.
Add the following after the first paragraph:
In Australia (this variation does not apply in New
Zealand), compliance with 6.2.2 is checked by the tests of both 6.2.2.1 and 6.2.2.2.
No TNV circuit.
Delete the note.
Delete Note 2. No TNV circuit.
Add the following after the first paragraph:
In Australia (this variation does not apply in New
Zealand), the electrical separation is subjected to
10 impulses of alternating polarity, using the impulse test generator of annex N for 10/700 µs impulses. The interval between successive impulses is 60 s and the initial voltage, Uc, is:
- for 6.2.1 a):
7.0 kV for hand-held telephones and for
headsets and 2.5 kV for other equipment; and
- for 6.2.1b) and 6.2.1c):
1.5 kV.
N/A
N/A
Australian National Differences according to CB Bulletin No. 110A, June 2006
Page 81 of 82
National Differences
Report No.:
Result – Remark
11009010 001
Verdict Clause Requirement − Test
6.2.2.2
NOTE 201 - The 7 kV impulse simulates lightning surges on typical rural and semi-rural network lines.
NOTE 202 – The 2.5 kV impulse for 6.2.1a) was chosen to ensure adequacy of the insulation concerned and does not necessarily simulate likely overvoltages.
Delete the note.
Add the following after the second paragraph:
No TNV circuit.
In Australia (this variation does not apply in New
Zealand), the a.c. test voltage is:
- for 6.2.1a):
- for 6.2.1b) and 6.2.1c):
3 kV; and
1.5 kV.
NOTE 201 – Where there are capacitors across the insulation under test, it is recommended that d.c. test voltages are used.
NOTE 202 – The 3 kV and 1.5 kV values have been determined considering the low frequency induced voltages from the power supply distribution system.
Annex P Add the following Normative References to Annex
P:
Added.
IEC 60065, Audio, Video and similar electronic apparatus - Safety requirements
AS/NZS 3112, Approval and test specification -
Plugs and socket-outlets
AS/NZS 3191, Approval and test specification -
Electric flexible cords
AS/NZS 4695.707, Fire hazard testing of electrotechnical products - Methods of test for the determination of the flammability of solid electrical insulating materials when exposed to an igniting source
N/A
N/A
Australian National Differences according to CB Bulletin No. 110A, June 2006
Page 82 of 82
National Differences
Report No.:
Clause Requirement − Test Result – Remark
APPENDIX Korean National Differences according to CB Bulletin No. 110A, June 2006
(K60950)
(IEC Publication 60950-1:2001)
11009010 001
Verdict
P
EXPLANATION FOR ABBREVIATIONS
P=Pass, F=Fail, N/A=Not applicable. Placed in the column to the right.
1.5.101 Addition:
Plugs for the connection of the apparatus to the supply mains shall comply with the Korean requirement (KSC 8305).
No power supply cords provided.
7 Addition: EMC
The apparatus shall comply with the relevant
CISPR standards.
Compliance shall be evaluated during national approval.
N/A
N/A
Korean National Differences according to CB Bulletin No. 110A, June 2006
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project