Pressure Control Spring for the DP and SDP Pilot Operated Pressure Reducing Valves

Pressure Control Spring for the DP and SDP Pilot Operated Pressure Reducing Valves
IM-S10-23
1000130/3
CH Issue 3
Pressure Control Spring for the
DP and SDP Pilot Operated Pressure ReducingValves
Fitting Instructions
Warning
For the full Installation and Maintenance
Instructions, inclusive of safety information,
see the relevant documents supplied with
the product and listed below:
Valve type
IM reference
DP17, DP17E and DP17R
IM-P100-05
DP17T and DP17TE
IM-P101-04
DP27
IM-P470-03
DP143 and DP163
IM-P006-07
SDP143
IM-P004-05
DP17, DP143, DP163 and SDP143
2
1
3
4
Note:
Installation and Maintenance Instructions
are available seperately from Spirax Sarco.
5
Fitting instructions
It is not necessary to isolate the valve in
order to change the spring.
1. Release the lock-nut.
2. Turn adjustment screw anticlockwise.
Ensure there is no compression on the
pressure adjustment spring.
3. For the DP17, DP143, DP163
and SDP143:
- Slide out 'C' washer.
4. Remove cover.
1
DP27
5. For the DP17, DP143, DP163
and SDP143:
- Remove pressure adjustment spring
and top plate.
For the DP27:
- Undo the 4 off spring housing securing
nuts and remove the spring housing.
- Remove the pressure adjustment spring
and the top spring plate.
2
4
5
6. Reassemble in reverse order. Note: When
fitting the variable rate conical pressure
adjustment spring the new spring top
plate and longer adjustment screw supplied
should also be fitted.