10. CEILING MOUNTED DUCT TYPE
PACKAGED AIR-CONDITIONER
Split system, Air cooled
Cooling only type
(
)
FDUR308CEN-A
308CES-A
408CES-A
508CES-A
357
CONTENTS
10.1 GENERAL INFORMATION ..................................................................... 359
10.1.1 Specific features ............................................................................... 359
10.1.2 How to read the model name ........................................................... 359
10.2 SELECTION DATA .................................................................................. 360
10.2.1 Specifications ................................................................................... 360
10.2.2 Range of usage & limitations .......................................................... 364
10.2.3 Exterior dimensions ......................................................................... 365
10.2.4 Exterior appearance ......................................................................... 370
10.2.5 Piping system ................................................................................... 370
10.2.6 Selection chart .................................................................................. 371
10.2.7 Characteristics of fan ....................................................................... 373
10.2.8 Noise level ......................................................................................... 374
10.3 ELECTRICAL DATA ................................................................................ 375
10.3.1 Electrical wiring ................................................................................ 375
10.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER ........... 378
10.5 APPLICATION DATA ............................................................................... 378
10.6 MAINTENANCE DATA ............................................................................ 378
358
10.1 GENERAL INFORMATION
10.1.1 Specific features
(1)
Less refrigerant charge amount due to use of double phase refrigerant flow system. The total refrigerant charge amount has been
reduced by more than 50%.
(2)
The indoor outdoor interconnection signal wiring has been done away with. The microcomputer chip is installed in the indoor unit.
There is no need for the unit to communicate between the outdoor and indoor units so the unit is more resistant to electromagnetic
noise thus the incidence of microcomputer malfunction has been reduced. The compressor in the outdoor unit has its own self
protection function, that reacts according to abnormal high pressure and excessive high temperature.
(3)
There are only five power lines between the outdoor and indoor unit, As no signal wire is used there is no need to separate the
power line from the signal line. One cabtyre cable with 4 wires encased in one sheath is enough for conducting the wiring work
between the outdoor unit and the indoor unit. This contributes to simpler wiring work in the field.
(4)
All models have service valves protruding from the outdoor unit for faster flare connection work in the field.
(5)
The position of the suction port can be changed.
The suction from the lower inlet is available by replacing the duct connecting section (at the side face) and the lower plate. (They
are changed on site.)
10.1.2 How to read the model name
Example: FDUR 30 8 C EN- A
Applicable power source ... See the specifications
Cooling only type
Series No.
Product capacity
Model name
FDUR: Ceiling mounted duct type
FDC: Outdoor unit
359
10.2 SELECTION DATA
10.2.1 Specifications
Model FDUR308CEN-A
FDUR308CEN-A
Model
Item
FDUR308-A
Nominal cooling capacity(1)
ISO-T1
ISO-T3
FDC306CEN3
7100
W
5700
ISO-T1
1 Phase, 220/240V 50Hz
Cooling input
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
kW
3.40/3.55
A
17.5/18.3
%
88/81
kW
3.60/3.80
Running current (Cooling)
A
19.0/19.8
Power factor (Cooling)
%
86/80
Inrush current (L.R.A)
A
Noise level
Exterior dimensions
Height × Width × Depth
Net weight
89
dB(A)
Hi:41 Lo:37
56
mm
295 × 850 × 650
844 × 950 × 340
kg
40
67
–
RC5532ENE1 × 1
Refrigerant equipment
Compressor type & Q’ty
–
2.24
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fins & bare tubing
Refrigerant control
–
Motor
kW
Starting method
Capillary tube
Refrigerant
R22
Quantity
Refrigerant oil
kg
–
r
–
1.3 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure control
High pressure regulator valve
Air handling equipment
Multiblade centrifugal fan × 2
Fan type & Q’ty
Motor
230 × 1
60 × 1
Line starting
Line starting
CMM
Hi:25 Lo:20
54
Pa
Standard: 50, Max 130
–
W
Starting method
Air flow (Standard)
Available static pressure
Propeller fan × 1
Fresh air intake
–
–
Air filter, Q’ty
Polypropylene net ×1(washable)
–
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
–
–
Shock & vibration absorber
Electric heater
W
Operation control
Wired remote control switch
Operation switch
Room temperature control
Safety equipment
(Optional: RCD-C-E)
– (Indoor unit side)
Thermostat by electronics
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
mm
Refrigerant piping size
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
(in)
Connecting method
Flare piping
Drain hose
(Connectable with VP25)
Insulation for piping
–
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit. Drain hose
Optional parts
Suction grille
–
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
DB
27˚C
WB
19˚C
DB
35˚C
WB
24˚C
ISO-T1, JIS B8616
Cooling
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 220 / 240V 50Hz.
360
Standards
Operation
Cooling
Model FDUR308CES-A
FDUR308CES-A
Model
Item
FDUR308-A
Nominal cooling capacity(1)
ISO-T1
ISO-T3
W
ISO-T1
kW
A
%
kW
A
%
A
dB(A)
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Available static pressure
FDC306CES3
7100/7700
5700/6000
3 Phase, 380-415V 50Hz, 380V 60Hz
3.20/3.30/3.80
6.6/6.7/7.8
74/69/74
3.40/3.50/4.05
7.1/7.2/8.3
73/68/74
43
Hi:41 Lo:37
56
mm
295 × 850 × 650
844 × 950 × 340
kg
40
67
–
RC5538ESE1 × 1
kW
–
–
Louver fins & inner grooved tubing
–
2.24
Line starting
Slitted fins & bare tubing
Capillary tube
kg
r
–
–
R22
Multiblade centrifugal fan × 2
Propeller fan × 1
CMM
230 × 1
Line starting
Hi:25 Lo:20
60 × 1
Line starting
54/56
Pa
Standard: 50, Max 130
–
W
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
W
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
1.3 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
–
Polypropylene net ×1(washable)
Rubber sleeve (for fan motor)
–
Wired remote control switch
(Optional: RCD-C-E)
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat.
mm
(in)
–
–
Rubber mount (for compressor)
–
– (Indoor unit side)
–
Internal
protector
for compressor.
Internal
thermostat
for fan motor.
Internal thermostat for fan motor.
Internal pressure relief valve for compressor.
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
Flare piping
(Connectable with VP25)
Necessary (both Liquid & Gas lines)
Mounting kit. Drain hose
Suction grille
–
–
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Cooling
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
27˚C
29˚C
19˚C
19˚C
35˚C
46˚C
24˚C
24˚C
Standards
ISO-T1, JIS B8616
ISO-T3, SASO
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 380V 50Hz/415V 50Hz/380V 60Hz.
361
Model FDUR408CES-A
FDUR408CES-A
Model
Item
FDUR408-A
Nominal cooling capacity(1)
ISO-T1
ISO-T3
W
ISO-T1
kW
A
%
kW
A
%
A
dB(A)
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Available static pressure
FDC406CES3
10200/11300
8900/9900
3 Phase, 380-415V 50Hz, 380V 60Hz
3.96/4.00/4.88
8.3/8.5/9.5
72/65/78
4.52/4.60/5.48
9.0/9.2/10.3
76/70/81
45
Hi:44 Lo:40
57
mm
350 × 1370 × 650
1250 × 950 × 340
kg
63
80
–
RC5547ESE1 × 1
kW
–
–
Louver fins & inner grooved tubing
–
2.61
Line starting
Slitted fins & bare tubing
Capillary tube
kg
r
–
–
Multiblade centrifugal fan × 2
Propeller fan × 2
CMM
280 × 1
Line starting
Hi:34 Lo:27
60 × 2
Line starting
100/110
Pa
Standard: 50, Max130
W
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
W
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
R22
1.55 (Pre-charged up to the piping length of 5m)
1.63 (SUNISO 3GS)
High pressure regulator valve
–
–
Polypropylene net ×1(washable)
Rubber sleeve (for fan motor)
–
Wired remote control switch
(Optional: RCD-C-E)
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat.
mm
(in)
–
–
Rubber mount (for compressor)
–
– (Indoor unit side)
–
Internal
protector
for compressor.
Internal
thermostat
for fan motor.
Internal thermostat for fan motor.
Internal pressure relief valve for compressor.
Liquid line: φ9.52 (3/8″) Gas line: φ19.05 (3/4″)
Flare piping
(Connectable with VP25)
Necessary (both Liquid & Gas lines)
Mounting kit. Drain hose
Suction grille
–
–
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Cooling
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
27˚C
29˚C
19˚C
19˚C
35˚C
46˚C
24˚C
24˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 380V 50Hz/415V 50Hz/380V 60Hz.
362
Standards
ISO-T1, JIS B8616
ISO-T3, SASO
Model FDUR508CES-A
FDUR508CES-A
Model
Item
FDUR508-A
Nominal cooling capacity(1)
ISO-T1
ISO-T3
W
ISO-T1
kW
A
%
kW
A
%
A
dB(A)
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Available static pressure
FDC506CES3
12500/14000
10600/11900
3 Phase, 380-415V 50Hz, 380V 60Hz
5.58/5.80/6.70
11.5/12.2/12.8
74/66/80
6.18/6.40/7.40
12.8/13.5/13.8
73/66/81
68
Hi:45 Lo:41
59
mm
350 × 1370 × 650
1250 × 950 × 340
kg
65
85
–
RC5563ESE2 × 1
kW
–
–
Louver fins & inner grooved tubing
–
3.73
Line starting
Slitted fins & bare tubing
Capillary tube
kg
r
–
–
R22
Multiblade centrifugal fan × 2
Propeller fan × 2
CMM
460 × 1
Line starting
Hi:42 Lo:33.5
60 × 2
Line starting
100/110
Pa
Standard: 50, Max 130
–
W
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
W
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
1.85 [Pre-charged up to the piping length of 5m]
2.07 (SUNISO 3GS)
High pressure regulator valve
–
Polypropylene net ×1(washable)
Rubber sleeve (for fan motor)
–
Wired remote control switch
(Optional: RCD-C-E)
Thermostat by electronics
Internal thermostat for fan motor.
Frost protection thermostat.
mm
(in)
–
–
Rubber mount (for compressor)
40 (Crank case heater)
– (Indoor unit side)
–
Internal
protector
for compressor.
Internal
thermostat
for fan motor.
Internal thermostat for fan motor.
Internal pressure relief valve for compressor.
Liquid line: φ9.52 (3/8″) Gas line: φ19.05 (3/4″)
Flare piping
(Connectable with VP25)
Necessary (both Liquid & Gas lines)
Mounting kit. Drain hose
Suction grille
–
–
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Cooling
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
27˚C
29˚C
19˚C
19˚C
35˚C
46˚C
24˚C
24˚C
Standards
ISO-T1, JIS B8616
ISO-T3, SASO
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 380V 50Hz/415V 50Hz/380V 60Hz.
363
10.2.2 Range of usage & limitations
Models
Item
All models
Indoor return air temperature
(Upper, lower limits)
Refer to the selection chart
Outdoor return air temperature
(Upper, lower limits)
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Dew point temperature: 28˚C or less, relative humidity: 80% or less
Refrigerant line (one way) length
Max. 30m
Vertical height difference between
outdoor unit and indoor unit
Max. 15m
Power source voltage
Voltage at starting
Rating ± 10%
Min. 85% of rating
Frequency of ON-OFF cycle
Max. 10 times/h
ON and OFF interval
Max. 3 minutes
364
10.2.3 Exterior dimensions
(1) Indoor unit
Model FDUR308-A
Unit : mm
Air inlet duct
(Low of suspension lug)
886 (Suspension bolts pitch)
850 (Duct for dimension)
295
18
25
245
25
475
240
420
480
35
525
80
30
45
650
18
560
(Suspension bolts pitch)
145
(Duct for dimension)
Control box
Suspension bolts
(M10 × 4pcs)
70
45
30
Liquid piping
ø9.52 (3/8”)
58
Air outlet duct
71
25
Gas piping
ø15.88 (5/8”)
Drain (Connectable
with VP25)
100
150
260
Drain (Natural drainage, VP25)
28
Space for installation and service
100
(Max.Drain up)
850
600
600
635
Drain hose(Accessories)
(Local Locality)
Air outlet
1720
Ceiling surface
Inspection hole
365
Models FDUR408-A, 508-A
Unit : mm
Air inlet duct
(Duct for dimension)
(Low of suspension lug)
Control box
Suspension bolts
(M10 × 4pcs)
173
1406 (Suspension bolts pitch)
1370 (Duct for dimension)
350
18
300
25
25
475
240
420
525
35
480
80
30
45
650
560
(Suspension bolts pitch)
18
70
25
58
45
30
Liquid piping
ø9.52 (3/8”)
77
100
Gas piping
ø19.05 (3/4”)
150
Air outlet duct
260
Drain (Connectable
with VP25)
Drain (Natural drainage, VP25)
28
Space for installation and service
100
(Max.Drain up)
1370
600
600
635
Drain hose(Accessories)
(Local Locality)
Air outlet
1720
Ceiling surface
Inspection hole
366
(2) Remote controller
Remote controller mounting dimensions
Wall
2
0.3mm , 3cores (O.D.φ5.6)
120
Wire
(Recessed)
60
46
47
7
17
LCD display
120
89
83.5
For the passage
after wiring
Electrical box
(Locally Purchased)
Remote controller outline
120
16
Allowable rang of wire thickness and length
Standard Within 0.3 mm2
0.5 mm2
0.75 mm2
1.25 mm2
2 mm2
× Within 100 m
× Within 200 m
× Within 300 m
× Within 400 m
× Within 600 m
367
(3) Outdoor unit
Models FDC306CEN3, 306CES3
Unit: mm
380
580
Anchor bolts
(M10 × 4 pcs)
Required space for maintenance and air flow
Minimum allowable space to the obstacles
Unit:mm
Installation
type
1
2
3
L1
Open
Open
500
L2
300
0
Open
L3
100
150
100
Mark
Notes
(1) Fix the unit with anchor bolts.
(2) Strong wind must not be directed to the air outlet.
(3) Free space over the unit must be larger than 1 m.
(4) The unit should not be surrounded by obstructions in all
direction.
At least one direction around the unit must be free.
368
Models FDC406CES3, 506CES3
Unit: mm
380
580
Required space for maintenance and air flow
Minimum allowable space to the obstacles
Unit:mm
Installation
type
1
2
3
L1
Open
Open
500
L2
300
0
Open
L3
150
300
150
Mark
Notes
(1) Fix the unit with anchor bolts.
(2) Strong wind must not be directed to the air outlet.
(3) Free space over the unit must be larger than 1 m.
(4) The unit should not be surrounded by obstructions in
all direction.
At least one direction around the unit must be free.
369
10.2.4 Exterior appearance
(1) Indoor unit......... Zinc steel plate
(2) Outdoor unit
Models FDC306CEN3, 306CES3
Models FDC406CES3, 506CES3
Polar white
Polar white
10.2.5 Piping system
Models FDUR308CEN-A, 308CES-A, 408CES-A, 508CES-A
Indoor unit
Outdoor unit
ø15.88
(308:
408, 508: ø19.05)
(ø9.52)
Preset point of the protective devices
Parts name
Mark
Equipped
unit
FDUR308~508
Thermistor
(for frost prevention)
ThI-R
Indoor unit
OFF 2.5˚C
ON 10˚C
370
10.2.6 Selection chart
Correct the cooling capacity in accordance with the conditions as follows. The net cooling capacity can be obtained in the following
way.
Net capacity = Capacity shown on specification × Correction factors as follows.
Outdoor air D.B.
temperature (˚CD.B.)
Coefficient of cooling capacity
in relation to temperatures
(1) Coefficient of cooling capacity in relation to temperatures
ISO-T1 Standard condition
Indoor air W.B. temperature (˚CW.B.)
Table of bypass factor
Model
FDUR 308
FDUR 408
FDUR 508
Hi
0.069
0.106
0.050
Lo
0.049
0.079
0.034
Item
Air flow
(2) Correction of cooling capacity in relation to air flow rate control (fan speed)
Coefficient: 1.00 at High, 0.95 at Low
(3) Correction of cooling capacity in relation to one way length of refrigerant piping
It is necessary to correct the cooling capacity in relation to the one way equivalent piping length between the indoor and
outdoor units.
50/60Hz
Equivalent piping length(1) m
Cooling
7.5
10
15
20
25
30
35
FDUR308
1.0
0.995
0.985/0.98
0.975/0.97
0.965/0.955
0.955/0.945
0.945/0.93
FDUR408
1.0
0.998/0.995
0.99/0.985
0.985/0.975
0.975/0.965
0.97/0.955
0.96/0.945
FDUR508
1.0
0.995/0.99
0.98/0.975
0.97/0.96
0.955/0.945
0.945/0.93
0.93/0.915
Note (1) Equivalent piping length can be obtained by calculating as follows.
308 :[φ15.88(5/8″)]: Equivalent piping length = Real piping length + (0.10 × Number or bends in piping)
408, 508 :[φ19.05(3/4″)]: Equivalent piping length = Real piping length + (0.15 × Number of bends in piping)
[Equivalent piping length < Limitation length of piping + 5m]
371
(4)
When the outdoor unit is located at a lower height than the indoor unit in cooling operation the following values should be
subtracted from the values in the above table.
Height difference between the indoor unit and
outdoor unit in the vertical height difference
5m
10m
15m
Adjustment coefficient
0.01
0.02
0.03
Piping length limitations
Model
FDUR308~508
Item
Max. one way piping length
30m
Max. vertical height difference
15m
Note (1) Values in the table indicate the one way piping length between
the indoor and outdoor units.
How to obtain the cooling capacity
Example : The net cooling capacity of the model FDUR308CEN-A with the air flow “High”, the piping length of 15m, the outdoor unit
located 5m lower than the indoor unit, indoor wet-bulb temperature at 19.0 ˚C and outdoor dry-bulb temperature 35 ˚C is
Net cooling capacity =
7100
×
FDUR308CEN-A
372
1.00
Air flow
“High”
×
(0.985 - 0.01)
×
Length 15m.
Height difference 5 m
1.0
=
6923 w
Factor by air
temperatures
10.2.7 Characteristics of fan
Model FDUR308-A
Model FDUR408-A
200
200
180
180
160
160
er
pp
120
li
Hi
gh
d-U
igh
e
spe
ee
gh
ee
dee
sp
80
w
Lo
Hi
gh
pper
rd-U
da
Stan
t
miit
lliim
weerr
--LLoow
d
d
e
e
ppee
ghh ss
H
Hiig
limit
nd
igh
29
-H
27
Lower
limit
ard
Air flow(m3/min)
0
d-
Sta
60
50
40
sp
Hig
r
owweer
dd--LLo
nddaarr
SSttaan
Upper
limit
Standard
air flow
Hi
ed-
pe
hs
100
20
20 21 22 23 24 25 26 27 28 29 30
Lower
limit
pe
Up
gh
Hi
gh
igh
-H
ard
nd
Sta
0
Hi
t
mi
r li
120
Standard
pressure
t
limi
pper
d-U
r
a
d
Stan
w
-Lo
dard
Stan
20
ow
-L
ed
60
50
40
d-
mit
er li
- Low
d
e
e
h sp
Hig
e
sp
80
Standard
pressure
sp
H
100
Static pressure (Pa)
140
t
mi
gh
Hi
Static pressure (Pa)
140
31
33 34 35
37
Standard
air flow
39
41
Upper
limit
Air flow(m3/min)
Model FDUR508-A
200
180
160
it
er
120
p
Up
lim
Hi
gh
-
gh
Hi
100
ed
spe
ee
d-
Hi
gh
gh
e
sp
80
ow
-L
ed
Standard
pressure
sp
Hi
Static pressure (Pa)
140
ow
rd-L
nda
Sta
20
imit
per l
d-Up
r
a
d
Stan
gh
Hi
dee
sp
gh
Hi
60
50
40
it
er lim
-Low
speed
h
g
i
H
0
33.5 35.5 37.5 39.5 41.5 43.5 45.5 47.5 49.5
Lower
50
42
limit
Upper
Standard
air flow
limit
Air flow(m3/min)
373
10.2.8 Noise level
Notes (1) The data are based on the following conditions.
Ambient air temperature:
Indoor unit 27˚C DB, 19˚C WB.
Outdoor unit 35˚C DB.
Indoor unit
Measured based on JIS B 8616
Outdoor unit
Measured based on JIS B 8616
Mike position as below
Mike position: at highest noise level
in position as below
Distance from front side
1m
Height
1m
Unit
1.5 m
Mike (center & low points)
(2) The data in the chart are measured in an unechonic room.
(3) The noise levels measured in the field are usually higher than the data because of reflection.
(1) Indoor unit
Models FDUR308-A
Models FDUR508-A
Models FDUR408-A
Noise level 41 dB (A) at HIGH
37 dB (A) at LOW
70
70
70
70
50
50
N50
40
40
N40
30
30
63
125
250
500
60
60
N60
50
50
N50
40
40
N40
30
30
N30
20
1000
2000
4000
20
63
125
250
500
1000
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
8000
N70
Souud Pressure Level
(standard 0.0002µ bar)
60
N60
Souud Pressure Level
(standard 0.0002µ bar)
Souud Pressure Level
(standard 0.0002µ bar)
60
0
70
70
N70
N70
N2
Noise level 45 dB (A) at HIGH
41 dB (A) at LOW
Noise level 44 dB (A) at HIGH
40 dB (A) at LOW
2000
4000
20
8000
20
63
125
Mid Octave Band Frequency (Hz)
Mid Octave Band Frequency (Hz)
N30
N2
0
250
500
1000
2000
4000
20
8000
Mid Octave Band Frequency (Hz)
(2) Outdoor unit
FDC306CEN3
Noise level 56 dB (A)
70
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
125
250
500
1000
2000
4000
20
8000
Mid octave band frequency (Hz)
Noise level 59 dB (A)
70
70
Sound pressure level
(Standard 0.0002µ bar) dB
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
63
125
250
500
1000
2000
Mid octave band frequency (Hz)
374
60
4000
70
20
8000
N70
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
63
125
250
500
1000
2000
Mid octave band frequency (Hz)
FDC506CES3
Model
70
70
N70
60
Sound pressure level
(Standard 0.0002µ bar) dB
Sound pressure level
(Standard 0.0002µ bar) dB
60
Noise level 57dB (A)
70
N70
FDC406CES3
Model
Noise level 56 dB (A)
70
63
FDC306CES3
Model
4000
Sound pressure level
(Standard 0.0002µ bar) dB
Model
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
8000
20
63
125
250
500
1000
2000
Mid octave band frequency (Hz)
4000
20
8000
5
CC
4 6
3
2
1
WH
C CM R
(49C)
S
BK
52C
OR
CnM
FM01
(49F01)
Mark
Cc
CFI
CFO
CM
CnA ~ W
DM
F
FMI
FMO
FS
NR
PC
SW1
SW2, 3
CFO
WH
Parts name
Capacitor for CM
Capacitor for FMI
Capacitor for FMO
Compressor motor
Connector
Drain motor
Fuse
Fan motor (Indoor unit)
Fan motor (Outdoor unit)
Float switch
Surge suppressor
Photo coupler
Switch (Address set)
Changeover switch
OR
CnM
OR OR
CnM
NR
Meaning of marks
WH
RD
RD
WH
WH
N
Mark
TB
Thc
Thl-A
Thl-R
TrI
Val
49C
49Fo
49FI
52C
X1~7
v
■
A
B
52C
Parts name
Terminal block ( mark)
Thermistor
Thermistor
Thermistor
Transformer
Varistor
Internal thermostat for CM
Internal thermostat for FMo
Internal thermostat for FMI
Magnetic contactor for CM
Auxiliary relay
Terminal (F)
Connector
F(3 . 15A)
BK
WH
RD
3
2
TB
1
Y / GN
RD
5
4
BR
BL
Mark
BK
BL
BR
GR
OR
RD
WH
Color mark
14
10
9
2
BK
WH
3
2
1
TB
RD
1
Y / GN
L
Y / GN
BK
RD
X6
CnF2
CnF2
PC
X5
3
BK
Color
Black
Blue
Brown
Gray
Orange
Red
White
X1
RD/WH
L
8
X3
CnF1
RD RD
X1 X4 X7
X2 X5
X7
X3 X6
Mark
Y
BK/WH
BL/WH
BR/WH
RD/WH
Y/GN
5
CnF2
CFI
CnF1
6
CnF1
(49FI)
H UH
FMI
7
X4
BK/WH
BK
TB
Y / GN
BL
BL
Y / GN
BK
WH
WH
WH
BK
BL BL BL/WH
WH
WH
BL
Y / GN
Y / GN
Y / GN
Indoor Unit
WH
Outdoor Unit
WH
BR/WH
X2
CnR
4
CnR
DM
Y
Y
Val
BK
CnW1
12V
BR CnW2
TrI
BK RD
SW2
OFF
SW3
1 2 3 4
OFF
ON
1 2 3 4
ON
SW1
CnQ
Test
220/240V
Printed circuit board
CnI
FS
CnI
13
Color
Yellow
Black/White
Blue/White
Brown/White
Red/White
Yellow/Green
BR/WH
PC
GR
GR
GR
GR
CnT
CnN CnH
CnS
CnB
Power source
1 Phase 220/240V 50Hz
RD
WH
BK
BK
BK
RD
RD
XR5
Z
Y
X
TB
BK
BK
CnS2
CnN
XR3
XR1
BK
BK
CnH2
BK BK
BK
BK
XR4
XR2
LS
Y
Z
Thc
Remote
controller
RD WH BK
X
ThI–R
ThI–A
Option
10.3 ELECTRICAL DATA
10.3.1 Electrical wiring
Model FDUR308CEN-A
375
L2
N
L3
Y / GN
5
BK
52C
NR
T2
T1 CM T3
(49C)
6
3
4
2
1
RD
OR
OR
CnM
OR OR
CnM
(49FO)
FMO
CnM
BK
Mark
CFI
CFO
CM
CnA ~ W
DM
F
FMI
FMO
FS
NR
PC
TB
SW1
CFO
WH
Parts name
Capacitor for FMI
Capacitor for FMO
Compressor motor
Connector
Drain motor
Fuse
Fan motor (Indoor unit)
Fan motor (Outdoor unit)
Float switch
Surge suppressor
Photo coupler
Terminal block ( mark)
Switch (Address set)
Meaning of marks
BK
BL
WH
BL
RD
RD
Mark
SW2, 3
Thc
ThI-A
ThI-R
TrI
Val
49C
49Fo
49FI
52C
X1~7
v
■
F(3 . 15A)
A
3
2
TB
1
Parts name
Changeover switch
Thermistor
Thermistor
Thermistor
Transformer
Varistor
Internal thermostat for CM
Internal thermostat for FMo
Internal thermostat for FMI
Magnetic contactor for CM
Auxiliary relay
Terminal (F)
Connector
B
52C
BK
BK
RD
Y / GN
TB
5
4
BR
BL
Mark
BK
BL
BR
GR
OR
RD
WH
X5
X6
CnF2
CnF2
PC
Color mark
14
10
9
2
BK
WH
3
2
1
TB
RD
1
Y / GN
L1
Y / GN
3
X1
RD/WH
L
8
X3
BK
Color
Black
Blue
Brown
Gray
Orange
Red
White
CnF1
RD RD
X1 X4 X7
X2 X5
X7
X3 X6
Mark
Y
BK/WH
BL/WH
BR/WH
RD/WH
Y/GN
5
CnF2
CFI
CnF1
6
CnF1
(49FI)
H UH
FMI
7
X4
BK/WH
BK
WH
BL
WH
Y / GN
BK
WH
WH
WH
BK
BL BL BL/WH
WH
WH
BL
Y / GN
Y / GN
Y / GN
Indoor Unit
WH
Outdoor Unit
WH
BR/WH
X2
CnR
4
CnR
DM
Y
Y
BR/WH
Val
BK
CnW1
12V
BR CnW2
TrI
BK RD
SW2
SW3
OFF
1 2 3 4
OFF
ON
1 2 3 4
ON
SW1
CnQ
Test
220/240V
Color
Yellow
Black/White
Blue/White
Brown/White
Red/White
Yellow/Green
Printed circuit board
CnI
FS
CnI
13
PC
GR
GR
GR
GR
CnT
CnN CnH
CnS
376
CnB
Power Source
3 Phase 380/415V 50Hz-380V 60Hz
RD
WH
BK
BK
BK
RD
RD
XR5
Z
Y
X
TB
BK
BK
CnS2
CnN
XR3
XR1
BK
BK
CnH2
BK BK
BK
BK
XR4
XR2
LS
Y
Z
Thc
Remote
controller
RD WH BK
X
ThI–R
ThI–A
Option
Model FDUR308CES-A
N
L3
BK
52C
NR
T2
T1 CM T3
(49C)
2
5
6
3
4
1
RD
OR
CnM1
(49FO1)
FMO1
BK
OR
CnM1
OR OR
CnM1
Mark
CFI
CFO1,2
CH
CM
CnA ~ W
DM
F
FMI
FMO1,2
FS
NR
PC
TB
SW1
BK
CFo1
Only for FDUR508
OR
OR
CnM2
OR OR
CnM2
(49FO2)
FMO1
CnM2
CnP
CH
CnP
52C
Parts name
Capacitor for FMI
Capacitor for FMO
Crankcase heater
Compressor motor
Connector
Drain motor
Fuse
Fan motor (Indoor unit)
Fan motor (Outdoor unit)
Float switch
Surge suppressor
Photo coupler
Terminal block ( mark)
Switch (Address set)
Meaning of marks
BK
BL
BL
RD
WH
Y / GN
RD
BK
L2
BK
CFo2
WH
Mark
SW2, 3
Thc
ThI-A
ThI-R
TrI
Val
49C
49Fo1,2
49FI
52C
X1~7
v
■
F(3 . 15A)
A
3
2
TB
1
Parts name
Changeover switch
Thermistor
Thermistor
Thermistor
Transformer
Varistor
Internal thermostat for CM
Internal thermostat for FMo
Internal thermostat for FMI
Magnetic contactor for CM
Auxiliary relay
Terminal (F)
Connector
B
52C
BK
BK
RD
Y / GN
RD
5
4
3
BR
BL
BK
2
Mark
BK
BL
BR
GR
OR
RD
WH
Color mark
14
10
9
WH
2
1
TB
RD
1
Y / GN
TB
Y / GN
BK
WH
BL
WH
Y / GN
BK
BK
WH
WH
X6
CnF2
CnF2
PC
X5
3
X1
RD/WH
L
8
X3
BK
Color
Black
Blue
Brown
Gray
Orange
Red
White
CnF1
RD RD
X1 X4 X7
X2 X5
X7
X3 X6
Mark
Y
BK/WH
BL/WH
BR/WH
RD/WH
Y/GN
5
CnF2
CFI
CnF1
6
CnF1
(49FI)
H UH
FMI
7
X4
BK/WH
BK
L1
Y / GN
BK
WH
WH
WH
BK
BL BL BL/WH
WH
WH
BL
Y / GN
Y / GN
Y / GN
Indoor Unit
WH
Outdoor Unit
WH
BR/WH
X2
CnR
4
CnR
DM
Y
Y
BK
CnW1
12V
BR CnW2
TrI
BK RD
SW2
SW3
OFF
1 2 3 4
OFF
ON
1 2 3 4
ON
SW1
CnQ
Test
220/240V
Printed circuit board
CnI
FS
CnI
13
Val
Color
Yellow
Black/White
Blue/White
Brown/White
Red/White
Yellow/Green
BR/WH
PC
GR
GR
GR
GR
CnT
CnN CnH
CnS
CnB
Power Source
3 Phase 380/415V 50Hz-380V 60Hz
RD
WH
BK
BK
BK
RD
RD
XR5
Z
Y
X
TB
BK
BK
CnS2
CnN
XR3
XR1
BK
BK
CnH2
BK BK
BK
BK
XR4
XR2
LS
Y
Z
Thc
Remote
controller
RD WH BK
X
ThI–R
ThI–A
Option
Models FDUR408CES-A, 508CES-A
377
10.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
Except for function relating to heating, same at the unit for FDUR heat pump type. See page 306.
10.5 APPLICATION DATA
The application data for the cooling only models are similar to those for the heat pump models. (See page 322.)
10.6 MAINTENANCE DATA
This is same as FDUR heat pump series. Refer to page 340.
378