Product data sheet 3RT1024-1AP00 CONTACTOR, AC-3 5.5 KW/400 V, AC 230 V,

Product data sheet 3RT1024-1AP00 CONTACTOR, AC-3 5.5 KW/400 V, AC 230 V,
Product data sheet
3RT1024-1AP00
CONTACTOR, AC-3 5.5 KW/400 V, AC 230 V,
50 HZ, 3-POLE, SIZE S0, SCREW CONNECTION
General technical data:
product brand name
SIRIUS
Size of the contactor
S0
Protection class IP / on the front
IP20
Degree of pollution
3
Installation altitude / at a height over sea level / maximum
m
2,000
Ambient temperature / during operating
°C
-25 … +60
Mechanical operating cycles as operating time
• of the contactor / typical
10,000,000
• of the contactor with added auxiliary switch block / typical
10,000,000
• of the contactor with added electronics-compatible auxiliary
switch block / typical
5,000,000
Main circuit:
Number of NC contacts / for main contacts
0
Number of NO contacts / for main contacts
3
Operating current
• at AC-1 / at 400 V
• at 40 °C ambient temperature / rated value
A
40
• at AC-3 / at 400 V / rated value
A
12
• at AC-4 / at 400 V / rated value
A
12.5
3RT1024-1AP00
Page 1/ 5
07/14/2014
subject to modifications
© Copyright Siemens AG 2014
• with 1 current path / at DC-1
• at 24 V / rated value
A
35
• at 110 V / rated value
A
4.5
• at 24 V / rated value
A
35
• at 110 V / rated value
A
35
• at 24 V / rated value
A
35
• at 110 V / rated value
A
35
• at 24 V / rated value
A
20
• at 110 V / rated value
A
2.5
• at 24 V / rated value
A
35
• at 110 V / rated value
A
15
• at 24 V / rated value
A
35
• at 110 V / rated value
A
35
• at AC-2 / at 400 V / rated value
kW
5.5
• at AC-3 / at 400 V / rated value
kW
5.5
• at AC-4 / at 400 V / rated value
W
5,500
• with 2 current paths in series / at DC-1
• with 3 current paths in series / at DC-1
• with 1 current path / at DC-3 / at DC-5
• with 2 current paths in series / at DC-3 / at DC-5
• with 3 current paths in series / at DC-3 / at DC-5
Service power
Control circuit:
Voltage type / of control feed voltage
AC
Operating range factor control supply voltage rated value / of
the magnet coil
• at 50 Hz
• for AC
0.8 … 1.1
Apparent pull-in power / of the solenoid / for AC
V·A
61
Apparent holding power / of the solenoid / for AC
V·A
7.8
Inductive power factor / with the pull-in power of the coil
0.82
Inductive power factor / with the pull-in power of the coil
0.24
Auxiliary circuit:
Contact reliability / of the auxiliary contacts
1 faulty switching per 100 million (17 V, 1 mA)
Number of NC contacts / for auxiliary contacts / instantaneous
switching
0
Number of NO contacts / for auxiliary contacts / instantaneous
switching
0
Short-circuit:
3RT1024-1AP00
Page 2/ 5
07/14/2014
subject to modifications
© Copyright Siemens AG 2014
Design of the fuse link
• for short-circuit protection of the auxiliary switch / required
fuse gL/gG: 10 A
• for short-circuit protection of the main circuit
• with type of assignment 1 / required
fuse gL/gG: 63 A
• at type of coordination 2 / required
fuse gL/gG: 25 A
Installation/mounting/dimensions:
Mounting type
screw and snap-on mounting onto 35 mm standard
mounting rail according to DIN EN 50022
series installation
Yes
Width
mm
45
Height
mm
85
Depth
mm
91
Distance, to be maintained, to earthed part / sidewards
mm
6
Connection type:
Design of the electrical connection
• for main current circuit
screw-type terminals
• for auxiliary and control current circuit
screw-type terminals
Type of the connectable conductor cross-section
• for main contacts
• solid
2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), max. 2x 10 mm²
• finely stranded
• with conductor end processing
2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
• for AWG conductors / for main contacts
2x (20 ... 16), 2x (18 ... 14), 1x 12
• for auxiliary contacts
• solid
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x
(0.75 ... 4 mm²)
• finely stranded
• with conductor end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
• for AWG conductors / for auxiliary contacts
2x (20 ... 16), 2x (18 ... 14), 1x 12
Certificates/approvals:
3RT1024-1AP00
Page 3/ 5
07/14/2014
subject to modifications
© Copyright Siemens AG 2014
General Product Approval
Functional Safety /
Safety of
Machinery
Declaration of
Conformity
Type Examination
Test Certificates
Special Test
Certificate
Type Test
Certificates/Test
Report
Shipping Approval
other
Confirmation
other
Environmental
Confirmations
Further information:
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/industrial-controls/catalogs
Industry Mall (Online ordering system)
http://www.siemens.com/industrial-controls/mall
Cax online generator:
http://www.siemens.com/cax
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
http://support.automation.siemens.com/WW/view/en/3RT1024-1AP00/all
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3RT1024-1AP00
3RT1024-1AP00
Page 4/ 5
07/14/2014
subject to modifications
© Copyright Siemens AG 2014
last change:
3RT1024-1AP00
Page 5/ 5
Jul 7, 2014
07/14/2014
subject to modifications
© Copyright Siemens AG 2014
Was this manual useful for you? yes no