Installation Guide
Current Monitoring
TM
TM
ECM Series: H6ECM
Split-Core Current Switch,
Proof of Rotation (Flow) for ECM Systems
Product Overview
The H6ECM is a current-sensitive switching device that monitors current (amperage) in the conductor passing
through it. A change in amperage in the monitored conductor that crosses the switch threshold causes the
resistance of the FET status output to change state, similar to the action of a mechanical switch. The status output
is suitable for connection to building controllers or other appropriate data acquisition equipment operating at up to
30 volts. The product requires no external power supply to generate its output.
RoHS
Compliant
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•
•
•
•
•
•
•
•
•
Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
This equipment must only be installed and serviced by qualified electrical personnel.
Read, understand and follow the instructions before installing this product.
Turn off all power supplying equipment before working on or inside the equipment.
Product may use multiple voltage/power sources. Disconnect ALL sources before
servicing.
Use a properly rated voltage sensing device to confirm that power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION.
Current transformer secondaries must be shorted or connected to a burden at all times.
Products rated only for basic insulation must be installed on insulated conductors.
Replace all doors, covers and protective devices before powering the equipment.
Failure to follow these instructions will result in death or serious injury.
A qualified person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and installations, and has received safety
training to recognize and avoid the hazards involved.
NEC Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
Product Identification
Sensor Type
H6ECM
05
05 = 0.5A threshold (tenths of amps)
NOTICE
•
•
•
•
Electrically Commutated Motors (ECMs) are increasingly common as more energy conservation measures are
implemented. The ECM is a brushless DC motor that is supplied AC power, converts that power to DC current and
uses electronic switching to control the motor rotation. The ECM shaft speed can be reduced to save energy,
resulting in lower cost and less component wear. The H6ECM is optimized to provide meaningful proof of rotation
which verifies that the ECM motor is operating as expected.
This product is not intended for life or safety applications.
Do not install this product in hazardous or classified locations.
The installer is responsible for conformance to all applicable codes.
Mount this product inside a suitable fire and electrical enclosure.
Specifications
Sensor Power
Amperage Range
Status Output Ratings
Insulation Class
Threshold
Frequency Range
Accuracy
Temperature Range
Humidity Range
Hysteresis
Induced from the monitored conductor
0.5 to 175A continuous
N.O. 1.0A @ 30VAC/DC, not polarity sensitive
600VAC RMS (UL)
0.5A
60Hz only
±10%
-15° to 60°C (5° to 140°F)
10-90% RH non-condensing
10% typical
Off State Resistance
Open switch represents > 1MΩ
On State Resistance
Closed switch represents < 200mΩ
Terminal Block Max. Wire Size
Terminal Block Torque
24 to 14AWG (0.2 to 2.1mm2)
3.5 to 4.4 in-lbs (0.4 to 0.5N-m)
COMPLIANCE INFORMATION
Agency Approvals
UL508 open device listing
Installation Category
Cat. III, pollution degree 2
For applications requiring double or reinforced insulation, please contact the factory.
The product design provides basic insulation only.
Do not use the LED indicators as evidence of applied voltage.
Z207062-0A
Page 1 of 3
©2015 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Current Monitoring
ECM Series: H6ECM
TM
Dimensions
Removable Mounting Bracket
0.6"
(16 mm)
1.2"
(31 mm)
0.7"
(18 mm)
2.1"
(54 mm)
0.5"
(13 mm)
2.5" *
(64 mm)
2.1"
(54 mm)
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x)
Installation
1.0" *
(26 mm)
2.9"
(74 mm)
3.5"
(89 mm)
Disconnect and lock out power to the enclosure containing the conductor to be
monitored.
Insulated Conductor (line or load) ONLY
1. Locate a mounting surface for the removable mounting bracket
that will allow the monitored conductor to pass through the center
window when it is installed and that will keep the product at least 1”
(13 mm) from any uninsulated conductors. Determine cable routing
for the controller connection, allowing the wiring to reach the
mounting location.
DDC CONTROLLER
DI
2. Drill holes to mount the bracket to the chosen surface using the
included screws.
3. Wire the output connections from the sensor to the controller (solidstate contact).
4. Snap the sensor over the conductor and clip the assembly to the
mounting bracket.
5. Secure the enclosure and reconnect power.
Fan
Motor (ECM)
6. Confirm the operation of the sensor with the load running normally.
Z207062-0A
Page 2 of 3
©2015 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Current Monitoring
ECM Series: H6ECM
Operation Check
TM
1. Issue a command to the ECM to rotate at normal operation speed and confirm that the motor shaft is rotating.
2. The status output of the H6ECM series product should be CLOSED (conductivity exists between terminals).
3. Issue a command to the ECM to stop rotation and confirm that the motor shaft is not rotating.
4. The status of the H6ECM series product should be OPEN (no conductivity exists between terminals).
Troubleshooting
Z207062-0A
Page 3 of 3
Problem
Solution
No reading at controller
• Check operation (see above)
• Check for control voltage at sensor (<30V, <1A)
• Check for amperage in monitored conductor (> threshold)
• Assure that sensor core mating surfaces are clean and that the core clamp is completely closed
Status outputs incorrect
If the status outputs are not seen as described above, the ECM may have “keep alive current” greater
than the current sensor threshold. Record the actual AC supply current flow to the ECM when the motor
is not rotating (a current measurement device may be needed). This is called the “keep alive current”.
For most ECM products, this is less than 0.5A. If the current seen is greater than the threshold, contact
Veris Customer Support. A higher setpoint current monitoring switch product may be needed.
©2015 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.