ADAPT_PARASOLa

ADAPT_PARASOLa
ADAPT Parasol
Energy-saving comfort module for Swegon’s WISE System
for demand-controlled ventilation
www.eurovent-certification.com
www.certiflash.com
ADAPT Parasol
►► Comfort modules for demand-controlled ventilation and
Swegon’s WISE system.
Primary airflow:
Up to 85 l/s
►► Energy-efficient operation since the room is ventilated,
heated and cooled exactly as called for by the load,
neither more nor less.
Pressure range:
50 to 150 Pa
Total cooling capacity:
Up to 2055 W
Heating capacity:
Water: Up to 2700 W
►► Highest possible comfort with provision for individual
control on the product or at room level.
►► Waterborne cooling energy and waterborne or electric
heat
Electric: Up to 1000 W
Size:
600 and 1200 with adapters for
a number of ceiling systems
►► Draught-free indoor climate, 4-way air distribution and
Swegon’s ADC (Anti Draught Control) provide maximum comfort and flexibility both today and for future
needs.
►► Simple installation, commissioning and maintenance.
Complete product with all components and accessories installed from the factory.
1
ADAPT Parasol
Demand-controlled indoor climate
Demand-controlled ventilation involves ventilating and
conditioning the air in a room precisely to meet our
needs – no more and no less. The potential for savings
is substantial, especially in premises where there is
considerable variation between low and high load
conditions in rooms and during times when there are few
or no occupants - which is the case in many premises.
Offices for example have in many cases an occupancy rate
of less than 50 %!
The ADAPT Parasol combines the best attributes from
two worlds – demand-controlled ventilation with all its
potential for savings combined with the comfort module’s
high capacity and performance for air conditioning rooms.
All this packaged in one compact unit is simple to install.
ADAPT Parasol comfort module
The ADAPT Parasol is based on a standard Parasol but
is equipped with functions for demand control of the
indoor climate. Available as single and two-module units:
Sizes:
600x600; 600x1200
Modules:
Supply air and cooling
Supply air, cooling and heating (water)
Supply air, cooling and heating (electric)
Installation:
Flushed mounting for false ceiling constructions
Flexibility
The easily adjustable nozzles in combination with Swegon’s ADC (Anti Draught Control) offer maximum flexibility for future changes in the room layout. All sides of
the unit can be set independently of one another and this
enables the comfort module to distribute more air or less
air to each of the four sides and discharge the air in the
preferred direction in the room.
Design
Function
The essential function of the comfort modules is closely
related to that of climate beams. The major difference
is that comfort modules distribute air in four directions
instead of two. This maximizes the area for the induction
of room air with the supply air which enables the
modules to deliver a high capacity without occupying
more ceiling space than necessary. The comfort modules
are also optimized to quickly mix the supplied air with
the room which provides better comfort in the room. In
heating applications, this technique also ensures heat is
conveyed along the ceiling in a better way.
The face plate of the ADAPT Parasol is available in three
different perforation patterns. As standard, the face plate
has round perforations arranged in a triangular pattern
however other optional patterns are available to special
order.
Draught-fee indoor climate
The ADAPT Parasol distributes air in four directions at low
air velocity. The low air velocity is created by distributing
air cooler than room temperature over a large area. The
special design of the outlet creates a turbulent flow
enabling the supply air to be quickly mixed with the room
air.
The ADAPT Parasol is available in the following coil/heat
exchanger variants:
Variant A:
Supply air and waterborne cooling
Variant B: Supply air, waterborne cooling and heating.
Variant X: Supply air, waterborne cooling and electric heating.
2
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
ADAPT Parasol
1
1
3
3
3
3
2
2
3
3
3
Figure 1. Variant A: Cooling and supply air operation
1 = Primary air
2 = Induced room air
3 = Primary air mixed with chilled room air
3
Figure 3. Variant X: Supply air and heating function with electric heating elements (also includes cooling function)
1 = Primary air
2 = Induced room air
3 = Primary air mixed with heated room air
1
3
3
ADAPT Parasol
2
3
3
Figure 2. Variant B: Heating and supply air operation (also
includes cooling operation)
1 = Primary air
2 = Induced room air
3 = Primary air mixed with heated room air
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
3
ADAPT Parasol
Compact and intelligent unit
The ADAPT Parasol is supplied as a compact and intelligent unit in which the damper and control equipment is
integrated into the product. Only the power supply and
possible connection to a main control system need to be
wired from the module.
The sensor module, which is a vital part of the product, is
a combined presence detector and a temperature sensor.
Its default location is within the face plate, however it can
also be mounted on a wall.
The package together with its intelligent control system
where numerous adaptations can be made, contribute to
making the product very flexible and future proof.
As an example, it is noteworthy that all the units can
operate as master or slave, simply adjustable by changing
a parameter together with repositioning an RJ cable. This
means that in the event an open-plan office, for example,
is divided up into office cells, the extra work involved in
adapting the product to the new operating conditions is
minimized.
Range of Application
The ADAPT Parasol is ideal as a standard application in
the following typical premises:
•
•
•
•
•
•
•
Offices and conference rooms
Classrooms
Hotels
Restaurants
Hospitals
Shops
Shopping centres
With its numerous possible settings, the functions of the
ADAPT Parasol can easily be adapted to new businesses
or changes in the design of the premises.
Simple to install
The ADAPT Parasol’s small compact units are designed to
fit the most common modular ceiling dimensions and this
makes them simple to install. The small dimensions offer
benefits in handling, especially at the building site, with
easier installation and reduced health and safety issues.
ADAPT Parasol PlusFlow
If you need both high cooling capacity and high airflows,
then the ADAPT Parasol 600/1200 PF is the right choice.
ADAPT Parasol PF installed in a conference room, for
instance, can reduce the number of installed products by
50%.
The module can handle large airflows and at the same
time has the same high cooling and heating capacity as a
standard ADAPT Parasol, of course with maintained high
level of comfort in the room.
Market-standardised modular dimensions
The products available to order have modular dimensions
to fit the standardised 600, 625 and 675 mm centre-tocentre ceiling dimensions. There are also mounting frames
for gypsum board ceilings as well as solutions for clip-in
type ceilings.
Always in stock
High capacity
With its high capacity, the ADAPT Parasol utilizes
40-50% less ceiling area for handling the cooling energy
demand in a normal office, compared with a traditional
climate beam.
The ADAPT Parasol’s standard variants with the most
common functions are available from stock to keep delivery times short.
Simple to adjust
By means of built-in nozzle regulation with numerous
possible settings, the ADAPT Parasol offers optimum comfort and can be easily adapted to meet a change in room
size or operations conducted inside the premises. The
comfort module can be set so that different air volumes
are diffused on each side and can be set for both high
and low airflows.
4
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
ADAPT Parasol
All components in the product can be installed directly
from the factory
Transformer, Accessories
Valves and
actuators
for cooling
and heating.
Accessories
Pressure sensor
Standard
Controller.
Preconfigured from the factory
Motor for damper blade.
Standard
Electrical connections
All factory-fitted components are wired to terminals.
Condensation sensor.
Standard
ADC
(-40° to +40° angle).
Can be preset from the
factory.
Sensor module with temperature and presence detector.
Standard
VOC or CO2 sensor.
Accessories
Adjustable nozzle setting on all four sides.
Preset from the factory
ADAPT Parasol
Figure 4. All components in the product can be installed directly from the factory
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
5
ADAPT Parasol
Sub-system
Super WISE
Zone
CONTROL Zone
All Year Comfort
GOLD
Master
Room
ADAPT Parasol
Master
Sensor module
x 10 pc
ADAPT Parasol
ADAPT Damper
To obtain full coverage of occupancy
detection, you can connect up to 10
sensor modules on each ADAPT Parasol
(in total on Master and possible Slave
units)
ADAPT Parasol
Slave
x 9 pc
Up to 9 ADAPT Parasol slaves can
be connected to each master.
Figure 5. ADAPT Parasol, a component of the WISE system
Component of the WISE system
The ADAPT Parasol is a component of Swegon’s WISE
System for demand-controlled ventilation.
Via the SuperWISE, a communication unit, which, via
Modbus RTU, ties all the components in the WISE system
together, ADAPT Parasol communicates with other WISE
products in the system and all the way up to the GOLD air
handling unit.
One of the advantages with the ADAPT Parasol is that
the pressure in the nozzles can be kept constant, and this
means controlled throw lengths, high capacity and maintained Coanda effect of the air regardless of the operating conditions.
A CONTROL Zone damper is used for keeping the pressure constant in the zone and in each ADAPT Parasol
module.
6
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
ADAPT Parasol
The ECOPulse function
The ADAPT Parasol has 2 basic ventilation flows, min. &
max. When the ECOPulse (standard) function has been
selected, the controller calculates the amount of time the
damper will be closed (min. flow) and open (max. flow),
to obtain the required occupancy flow.
The ECOPulse function guarantees that the module
always delivers highest possible capacity.
Example:
Max. airflow (18 l/s)
Required occupancy flow (12 l/s)
Min. flow (6 l/s)
In this example, the allocation of time at closed (min.
flow) and open (max. flow) will be approximately 50/50
as the required occupancy flow is halfway between the
min. and max.
Figure 6. Min. flow, no occupancy in the room.
The sequence consists of periods (minimum of 6 minutes)
that always begin with a period with max. flow, which is
then followed by the right number of periods with min.
flow to obtain the correct air volume over time.
Flow
l/s
Figure 7. Presence detector, a combination of min. and max. flow.
30
ADAPT Parasol
24
18
12
6
0
Time
minutes
0
6
12 18
24 30 36 42 48
When the system has operated for 48 minutes, it has
therefore fulfilled a complete sequence. Then it begins
a new sequence that lasts another 48 minutes provided
no change in demand has occurred (temperature, CO2,
precense, etc).
If we now distribute the yellow and blue airflows as a
mean value over time, we reach the required flow of 12 l/s.
Basic adjustment of nozzles
Flow
In the example above, the nozzles on the short side
can be configured so that at a certain pressure they will
deliver 6 l/s min. flow, which also is the unit’s no occupancy flow.
l/s
30
The max. flow is obtainable by adjusting the nozzles on
the long side so that the four sides together will deliver 18
l/s required max. flow.
24
18
12
6
0
Figure 8. Max. flow when the temperature or CO2 content is too high
0
6
12 18
24 30 36 42 48
Swegon reserves the right to alter specifications.
Time
minutes
You can test various variants and combinations of nozzle
settings on the sides in ProSelect to save as much air as
possible in the no occupancy mode combined with always
obtaining a sufficiently good climate in the room in the
occupancy mode.
17-06-2013
www.swegon.com
7
ADAPT Parasol
Control functions
Regardless of which ADAPT Parasol model is ordered and
how this module is configured from the beginning, you
can simply choose between the following three operating
modes by making a selection in the software:
ECOPulse
The ECOPulse function enables the ADAPT Parasol to
alternate between min. and max. mode in order to obtain
increased occupancy flow. See the more detailed description on page 7.
Variable
If the Variable function is selected, the nozzle configuration still sets the limits for min. and max. flows just as
for the ECOPulse function, but in this case the integrated
damper delivers the exact air quantity all the time.
Figure 9. Vacancy/min. flow for all the control functions
On selecting the Variable function, all airflows between
min. and max. will be delivered at lower capacity compared with the ECOPulse function.
Example: No occupancy flow approx. 5 l/s, required occupancy flow 20 l/s and max. flow 35 l/s.
In the occupancy case, the max. flow will be utilized only
if the temperature or air quantity requires this, and when
these requirements have been met, the flow will decrease
back to the required occupancy flow again.
2Step
Here, the min. and max. flows are used just as before, but
the max. flow is the same as the occupancy flow. So, if
the same nozzle setting as the one in the Variable example above is used.
No occupancy = min. flow 5 l/s.
Occupancy = max. flow = 35 l/s.
Figure 10. Occupancy/max. flow for 2Step. For the Variable control function, the long sides variably discharge air between the
min., occupancy and max. ventilation flows.
8
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
ADAPT Parasol
Depending on the status of connected sensors, the
controller adjusts the outputs from any of several possible
operating conditions.
The operating conditions based on occupancy in the
room, the status of the sensor in use or signals from a
main control system are described below.
Operating modes
There are numerous functions in the ADAPT Parasol:
•
Occupancy mode.
•
No occupancy mode.
•
Stand-by, idle mode.
•
Emergency mode.
•
•
Emergency mode
In the event of a fire alarm, the controller opens or closes
the air damper in the extract air duct, depending on how
the control system is set. In the Emergency mode, cooling and heating are switched off. Supply air is normally
switched off.
Holiday.
•
Stand-by, idle mode
When the control system registers that a window is open,
the controller switches over to the Stand-by mode. When
the window is closed, the controller switches over to the
Occupancy mode. When the controller is in the Stand-by
mode, the room temperature is kept above 10°C (frost
protection).
The Emergency mode can only be managed in control
systems that are connected to a main control system via
Modbus RTU.
Commissioning.
Summer night cooling.
No Occupancy mode
When the No occupancy mode function is active, the
system automatically switches over to the energy-save
mode. The system returns to the Occupancy mode and
normal operation when occupancy is registered again.
In the energy-save mode/No occupancy mode, the valve
actuator is controlled to regulate the chilled water flow
or hot water flow according to the status on other sensors in the room, but normally with a greater permissible
deadband from the temperature setpoint for cooling or
heating than in the occupancy mode, whilst the air is
controlled to the min. flow setting.
The function will be automatically deactivated after
approx. 6 minutes while the system is energised.
A clicking noise can be heard when the valves and dampers change over to the NC mode (normally closed) and
the normal control function is activated.
Further particulars of the commissioning mode can be
read in the description of the sensor module on page 12.
Summer night cooling
The function involves the use of cold air from outdoors
for cooling the room at night to the predefined level.
The function can only be handled in the control system
that is connected to a main control system via Modbus
RTU.
Holiday.
When the Holiday operating mode is active, the system
automatically switches over to the energy-save mode just
as in the case of No occupancy, but with scope for allowing further greater temperature differential. Controlled
from a main control system.
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
9
ADAPT Parasol
Occupancy mode
When the ADAPT Parasol receives signals via presence
detector that someone is in the room, the valve actuator
for chilled water or heating water as the case may be is
controlled according to the selected temperature setpoint
for cooling or heating associated with this operating
mode. The airflow is controlled to the preselected occupancy flow, but is influenced of course by sensors such
as condensation sensors, temperature sensors, window
contacts, air quality sensors, if required, etc.
Commissioning level
The “First open” function involves having the water
valves open while the installation work is in progress,
which simplifies filling, pressure testing and venting the
water system
ADAPT Parasol
Functions
Exercising of valves
The function involves exercising the water valves regularly
by means of automatic control equipment to prevent
them from seizing or becoming stuck. During the exercising process, all the valves wired to the controller open to
the max. setting for 6 minutes and then close. The valves
of the cooling system are exercised first; after that the
valves of the heating system are exercised.
Frost protection
The function involves starting heating operation at 10°C
to prevent the risk of damage that otherwise could occur
due to freezing.
Change over
The function involves the use of only one valve actuator
which should be wired to the cooling output terminal.
This actuator then controls both the heating water and
the chilled water, which is transported in the same pipe.
An external temp. sensor should be used and this component should take measurements on the pipe through
which water always circulates.
In winter, when heating is required, the valve opens if
the water in the pipe is warmer than the temperature set
point. If the water is colder, the valve does not open.
In summer, when cooling energy is required, the valve
opens if the water in the pipe is colder than the temperature set point.
10
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
ADAPT Parasol
Specific nozzle settings
K-factors for each side can be obtained from Tables 2-5 or
from the installation instructions on the Internet, however
the easiest way to do this is in ProSelect where you can
quickly test various variants.
To specify nozzle settings, always begin from the side where
the water pipes are located. From there, proceed in counterclockwise direction and specify side after side, see Figures 11
and 12. Units can be ordered with nozzles factory-preset (this
does not apply to units held in stock).
Nozzle setting
The unique built-in nozzle control in the ADAPT Parasol
makes it possible to individually set each one of the four
sides. Depending on the unit’s location and the room’s
primary air requirement, the primary air can be guided
in all desired directions. The direction of the airflow can
be easily optimized using the Swegon ProSelect sizing
program that can be downloaded from www.swegon.
com.
The required nozzle setting is preset from the factory, but
if required it can be simply changed at the site.
K-factor
Figure 11. Top view, sides 1-4
ADAPT Parasol 600
Figure 12. Top view, sides 1-4
ADAPT Parasol 1200
A
A
B
B
B
A
Figure 13. Example 1.
A = 2.1 l/s, B = 15.4 l/s
ADAPT Parasol
B
Each nozzle setting has a specific K-factor. A total K-factor
for the unit can be determined by adding together
the K-factors for the nozzle settings on each side. The
relevant K-factor for optimized nozzle setting can also be
obtained in ProSelect.
A
Figure 14. Example 2.
A = 5.7 l/s, B = 15.25 l/s
Example 1:
Nozzle setting LHLH produces the lowest possible No
Occupancy flow (sides 1 + 3 open). This produces a min.
flow/No Occupancy flow of 4.2 l/s and a max. flow of 35
l/s at pi = 70 pa
Example 2:
If it is instead more important to obtain the highest possible max. flow/capacity, the nozzles should be set to the
HHHH position, i.e. fully open on all sides. A higher max.
flow will then be obtained, however the No Occupancy
flow will consequently also be slightly higher.
Figure 15. Nozzle setting
These adjustments are only different settings on the
same physical product which makes the unit very flexible
and adaptable, particularly together with the integrated
software.
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
11
ADAPT Parasol
The sensor module
The sensor module consists of a presence detector and a
temperature sensor in the same unit.
This component is mounted as standard in the face plate
on the ADAPT Parasol but it can also be ordered as an
accessory for wall mounting, and in that case either
recessed in a standard electrical component box or
surface-mounted on the wall.
By pressing the appropriate buttons on the sensor
module, you can adjust the temperature in the room, set
the ADAPT Parasol to the commissioning mode and read
the alarm list.
6 light-emitting diodes indicate in the normal mode which
temperature level has been selected. If an error occurs,
the current alarm is shown as a series of flashes that are
translatable using an alarm list.
Use an RJ12 cable to connect the sensor module to the
controller.
The floor area covered by the presence detector is approx.
30 m2 if it is mounted at a height of 2.7 metres above the
floor and in parallel with the floor.
Basic setting for temperature adjustment
To lower the temperature setting,
press down the
left-hand button.
To raise the temperature setting, press
down the right-hand
button.
Each diode corresponds to a one degree increase or decrease
of the set point.
Presence detector
Diodes for temperature,
commissioning or alarm
indication
Figure 18. The CABLE CONVERTER USB-RJ12 (RS485) cable can
be used for connecting a computer to the module for e.g. entering software settings.
Function buttons
Diode-indicating function
- Green = Ok
- Flashing Green = Condensation alarm
- Yellow = Alarm
- Green/Yellow = Comfort alarm
(not acute)
Temperature sensor
Figure 16. Sensor module viewed from the front
ON
1 2
3 parallel RJ12 ports (Modbus) for connecting a controller for instance, another
sensor module or computer by means of
Cable converter USB-RJ12
Addressing the sensor module. 10 sensor modules
can be connected to each master unit, each one
must have its own unique address in order to work.
Switch for termination resistance. Set Switch 1 to the
ON position for the last sensor module in the loop.
Figure 17. Sensor module viewed from rear
12
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
ADAPT Parasol
Typical installations:
2
2
2
x4
x2
RE
RE
1
1
3
3
4
5
4
5
Figure 20. Type room 2 shows ADAPT Parasol in an office room.
Supply and extract air in balance.
1. ADAPT Parasol comfort module with supply air, cooling and
heating.
1. ADAPT Parasol comfort module with supply air and cooling.
•
Pressure sensor
•
Condensation sensor
•
Communication unit/controller
•
Damper with motor.
2. CONTROL Zone damper
3. Chilled water and heating water
•
Pressure sensor
•
Presence detector
•
Temperature sensor
•
Condensation sensor
•
Communication unit/controller
•
Damper with motor.
2. CONTROL Zone damper
4. Extract air via transfer air grille to the corridor
5. External sensor module (occupancy and temperature sensor)
3. Chilled water
4. Extract air via ADAPT Damper slave-controlled from ADAPT
Parasol
5. Grille or fully open type EXC extract air register
Operating mode
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
13
ADAPT Parasol
Figure 19. Typical room 1 shows ADAPT Parasol in an office
room. Extract air leaves the room via a transfer air grille (balance
at zone level)
ADAPT Parasol
ADC
All the comfort modules are supplied with ADC air deflectors.
ADC stands for Anti Draught Control, which enables you
to set the diffusion pattern of the air being distributed
to avoid risk of draught. A number of ADC sections with
four air deflectors per section are arranged on each side
of the unit. Each section is adjustable from a straight setting to 40° air deflection to the right or left in increments
of 10°. This offers enormous flexibility and can be easily
adjusted without affecting the sound level and the static
pressure.
-40°
0°
+40°
Figure 22. Possible settings for the ADC, Fan-shape
0°
+40°
Figure 23. Possible settings for the ADC, X-shape
Figure 21. ADC, setting range from -40° to +40° in increments
of 10°
0°
Figure 24. Possible settings for the ADC, Straight airflow setting
14
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
ADAPT Parasol
Installation
Condensation-free cooling energy
Recommended types of ceiling
The ADAPT Parasol is designed to fit in most T-Bar and
Clip-in type ceiling systems in terms of length and width.
To guarantee a quality finish in T-Bar ceiling system, we
recommend T profiled sections with a width of 24 mm.
Since the comfort modules have to be designed to operate without condensation, no drainage system is required.
To wire the electric heating elements
The wiring diagram is available from www.swegon.com.
Suspension
The ADAPT Parasol has four mounting brackets for suspension, and are installed using a threaded rod in each
mounting bracket (Figure 28). A double threaded rod
with a thread lock should be used if there is substantial
distance between the overhead slab and the unit.
The threaded rod, assembly piece SYST MS M6 (Figure
29), must be ordered separately.
Connection dimensions
Water
Without valves:
Cooling energy, plain end (Cu)
Ø 12 x 1.0 mm
Heating, plain end (Cu)
Ø 12 x 1.0 mm
With factory-fitted valves:
Cooling
Male threads, DN15 (1/2”)
Heating
Male threads, DN15 (1/2”)
Air connection piece,
standard variant
Ø 125 mm
Connection frame, variant PF
Ø 160 mm
The ADAPT Parasol with electric heating is equipped with
two thermal overheat protections. The protection, with
automatic reset, switches out the heating elements (the
zero conductor) when the temperature exceeds 60 °C.
When the temperature has dropped to 50 °C the protection closes the circuit again and reenergizes the heating
elements. If the temperature instead rises to 75 °C after
the first overheat protection has tripped, the second
manually resettable overheat protection will kick in and
will also switch off the phase conductor to the heating
element.
To reset the overheat portection the perforated face plate
should first be removed. The red reset button is situated
between the air heater and the end panel through which
the cooling water pipes are installed. After the overheat
protection has been reset, click the faceplate back into
place.
CE marking
To connect air
ADAPT Parasol is supplied as standard with an open air
connection on the right-hand side (viewed from the end
where the water is connected).
The ADAPT Parasol with electric heating is CE marked in
accordance with applicable requirements. The CE Declaration of Conformity is available at our website: www.
swegon.com.
The air connection piece is mounted on delivery for
connection ted to the primary air duct (see Figure 27).
A cover is factory-fitted to the left-hand air connection,
however handling can be easily reversed with the air connection piece fitted to the left if required.
To connect the water pipes
Connect the water pipes using push-on couplings or
clamping ring couplings if the product is ordered without
valves. Note that clamp ring couplings require support
sleeves inside the pipes.
Do not use couplings that have to be brazed for connection of the water pipes. High temperatures could damage
the unit’s existing brazed joints.
Flexible connection tubes for water are available for both
plain pipe ends as well as valves and should be ordered
separately.
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
15
ADAPT Parasol
Air
Overheat protection
ADAPT Parasol
Figure 25. Water connection with factory-fitted valves
(An ADAPT Parasol 1200 is shown in the example)
Figure 28. To suspend a two-module unit
Figure 26. Water connections without factory-fitted valves
(An ADAPT Parasol 1200 is shown in the example)
Figure 29. Assembly piece SYST MS M6-1, ceiling mount and
threaded rod
ØA
Figure 30. Controller, pressure sensor and wiring terminals are
on a mounting plate which, if required, can be folded out for
simpler access.
If the module is installed in a plasterboard ceiling, for example,
an inspection cover must be arranged to enable access to the
connection end of the ADAPT Parasol.
Figure 27. Air connection piece
Variant
ADAPT Parasol 600
ADAPT Parasol 600 PF
ADAPT Parasol 1200
ADAPT Parasol 1200 PF
16
A = Ø 125 mm
A = Ø 160 mm
A = Ø 125 mm
A = Ø 160 mm
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
ADAPT Parasol
Technical data
Recommended limit values
Pressure levels
Total cooling capacity, max.
2055 W
Working pressure, coil, max.
Heating capacity, water, max.
Heating capacity, electric, max.
2700 W
1000 W
Test pressure, coil, max.
2400 kPa *
* Applies to module without installed control equipment
Airflows
Single module unit
Two-module unit
7-34 l/s
7-85 l/s
Nozzle pressure
1600 kPa *
50-150 Pa
Recommended lowest nozzle pressure if
coil heat is used, pi70 Pa
Length
Single module unit
584; 592; 598; 617; 623; 642; 667 mm
Two-module unit
1184; 1192; 1198; 1242; 1248; 1292; 1342 mm
Recommended lowest nozzle pressure with
the face plate in the high capacity position, pi 70 Pa
Width
584; 592; 598; 617; 623; 642; 667 mm
Cooling water, min.
0.030 l/s
Heating water, min.
0.013 l/s
Height
ADAPT Parasol 600
ADAPT Parasol 600 PF
ADAPT Parasol 1200
ADAPT Parasol 1200 PF
220 mm
250 mm
220 mm
250 mm
Water flow
Ensures evacuation of any air pockets in the system.
Temperature differentials
Chilled water, temperature increase
2–5 K
Heating water, drop in temperature
4-10 K
Dimensions of the units have a tolerance of (±2) mm.
Temperature differences are always expressed in Kelvin (K).
Power consumption
Power consumed for sizing 9.8 VA transformer with factory fitted actuator.
Flow temperature
Heating water, max.
60ºC
** Chilled water must always be kept at a level that ensures
that no condensation will form.
Table 1. Weight
ADAPT Parasol
Cooling Water**
Chilled water
volume (kg)
Heating water
volume (kg)
1192-A
25.6
1.4
X
1192-B
29.7
1.4
0.9
1192-A-PF
28
1.4
X
1192-B-PF
32
1.4
0.9
1192-X1
27.4
1.4
X
1192-X2
27.7
1.4
X
592-A
15.8
1.1
X
592-B
16.3
1.1
0.2
592-A-PF
17.3
1.1
X
592-B-PF
17.8
1.1
0.2
ADAPT Parasol
Dry
weight (l)
Designations
These are examples of the most common sizes of the ADAPT
Parasol. For other variants, please refer to our ProSelect program at www.swegon.com.
Excl. sensor module 0.1 kg.
P
Capacity (W)
tl
Temperature of the primary air (°C)
tr
Temperature of the room air (°C)
tm
Mean water temperature (°C)
∆Tm
Temperature differential tr- tm (K)
∆Tl
Temperature differential tl- tr (K)
∆Tk
Temperature differential between the cooling
water inlet flow and return (K)
∆Tv
Temperature differential between the heating
water inlet flow and return (K)
v
Water velocity (m/s)
q
Flow (l/s)
p
Pressure (Pa)
∆p
Pressure drop (Pa)
Supplementary index: k = cooling energy, v = heat, l = air, i =
commissioning, corr = correction
Nozzle pressure (commissioning pressure)
pl = (ql / kpl) 2
Swegon reserves the right to alter specifications.
pl Nozzle pressure (Pa)
ql
Primary airflow (l/s)
kpl Pressure drop constant for nozzle setting, see Tables 2-5
17-06-2013
www.swegon.com
17
ADAPT Parasol
Cooling
Standard
The cooling capacities have been measured in conformance with EN 15116 Standard and have been recalculated
for a constant water flow according to Diagram 2/3.
Corrected capacity – water flow
Different water flow rates to some extent have effects on
the capacity output. By checking calculated water flow
against Diagrams 2 or 3, the capacity indicated in Tables
2-5 may need to be slightly adjusted up or down.
Pcorr = k · Pk
Calculating formulae – Cooling
Below are formulae that enable the user to calculate what
comfort module is best suited for the application. The
values for the calculations can be taken from the tables.
Pressure drop in cooling coil
∆pk = (qk / kpk) 2
∆pk Pressure drop in cooling coil (kPa)
qk
Flow of cooling water (l/s), see Diagram 1
kpk
Pressure drop constant for cooling coil, see Tables
2-5
PcorrCorrected capacity (W)
k
Correction factor
Pk
Cooling capacity of the water
Diagram 2. Corrected capacity – Water flow, ADAPT
Parasol 600
Cooling capacity of the air
Pl = 1.2 · ql · ∆Tl
Pl
Primary air cooling capacity (W)
ql
Primary airflow (l/s)
∆Tl
Temperature differential between primary air (tl)
and room air (tr) (K)
Cooling capacity of the water
Pk = 4186 · qk · ∆Tk
Pk Cooling capacity of the water (W)
qk Chilled water flow (l/s)
∆Tk Temperature differential between the cooling
water inlet flow and return (K)
Diagram 3. Corrected capacity – Water flow, ADAPT
Parasol 1200
Diagram 1. Water Flow – Cooling Capacity
18
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
ADAPT Parasol
Diagram 4. Pressure drop – Chilled water flow
ADAPT Parasol
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
19
ADAPT Parasol
Table 2. Cooling capacity of the ADAPT Parasol 600
Nozzle
pressure
50 Pa
70 Pa
90 pa
Nozzle
setting
1)
Primary
airflow
(l/s)
Sound
level in
dB(A) 2)
LLLL
7.2
<20
Cooling capacity of
primary air (W) for ∆Tl
Cooling capacity of the water (W)
Pressure drop constant, air/water
for ∆Tmk 3)
6
8
10
12
6
7
8
9
10
11
kpl
kpk
52
69
86
104
196
226
258
287
319
348
1.01
0.0200
LHLH
13.4
<20
96
129
161
193
258
300
338
380
422
464
1.89
0.0200
HHHH
19.6
20
141
188
235
282
278
324
370
415
461
502
2.77
0.0200
LLLL
8.5
<20
61
82
102
122
228
266
304
338
376
413
1.01
0.0200
LHLH
15.9
24
114
153
191
229
303
352
396
444
492
540
1.89
0.0200
HHHH
23.2
25
167
223
278
334
326
379
431
483
534
581
2.77
0.0200
LLLL
9.6
20
69
92
115
138
255
297
335
377
418
460
1.01
0.0200
LHLH
18.0
28
130
173
216
259
333
386
439
492
544
592
1.89
0.0200
HHHH
26.3
29
189
252
316
379
363
420
477
534
590
636
2.77
0.0200
Table 3. Cooling capacity of the ADAPT Parasol 600 PF
Nozzle
pressure
50 Pa
70 Pa
90 pa
Nozzle
setting
1)
Primary
airflow
(l/s)
Sound
level
in
dB(A)
2)
LLLL
22.1
Cooling capacity of
primary air (W) for ∆Tl
Cooling capacity of the water (W)
for ∆Tmk 3)
Pressure drop constant, air/water
6
8
10
12
6
7
8
9
10
11
kpl
kpk
23
212
265
318
159
214
251
285
323
360
395
3.13
0.023
LHLH
27.9
27
268
335
402
201
243
281
323
366
408
447
3.95
0.023
HHHH
33.7
27
324
404
485
243
261
306
352
393
439
485
4.76
0.023
LLLL
26.2
28
252
314
377
189
263
308
352
392
437
481
3.13
0.023
LHLH
33
31
317
396
475
238
288
337
386
436
485
534
3.95
0.023
HHHH
39.8
32
382
478
573
287
310
362
415
467
520
573
4.76
0.023
LLLL
29.7
31
285
356
428
214
301
351
395
445
494
543
3.13
0.023
LHLH
37.5
35
360
450
540
270
325
380
434
488
543
597
3.95
0.023
HHHH
45.2
36
434
542
651
325
342
400
462
520
578
636
4.76
0.023
1) For particulars on the sizing of alternative nozzle settings, use Swegon’s ProSelect sizing program available at www.swegon.com
2) Room attenuation = 4 dB
3) The specified capacities are based on operation in the high capacity mode. Operation with the face plate set to the normal position reduces the water capacity of the ADAPT Parasol 600 by about 5% and that of the ADAPT Parasol 1200 by about 10 %.
The water capacity can vary depending on installation and how the airflow deflectors are set. The primary air capacity is not
affected.
The water capacity is reduced by 5 -10% when the ADC is adjusted to ”fan-shape”.
N.B.! The total cooling capacity is the sum of the airborne and waterborne cooling capacities.
20
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
ADAPT Parasol
Table 4. Cooling capacity of the ADAPT Parasol 1200
Nozzle
setting 1)
Primary
airflow
(l/s)
Sound
level in
dB(A) 2)
6
8
10
12
6
7
8
9
10
kpl
kpk
50 Pa
LLLL
13.0
<20
94
125
156
187
383
444
504
570
630
1.84
0.0220
LHLH
29.4
22
212
282
353
423
499
580
653
733
806
4.16
0.0220
HHHH
35.6
26
256
342
427
513
520
596
678
753
827
5.04
0.0220
LLLL
15.4
20
111
148
185
222
432
500
574
641
708
1.84
0.0220
LHLH
34.8
26
251
334
418
501
557
646
733
813
899
4.16
0.0220
HHHH
42.2
29
304
405
506 608
580
663
753
842
922
5.04
0.0220
LLLL
17.5
<20
126
168
210
252
471
544
624
696
768
1.84
0.0220
LHLH
39.5
29
284
379
474
569
603
697
790
875
966
4.16
0.0220
HHHH
47.8
32
344
459
574
688
627
715
810
904
989
5.04
0.0220
70 Pa
90 pa
Cooling capacity of
primary air (W) for ∆Tl
Cooling capacity, water (W)
for ∆Tmk 3)
Pressure drop constant, air/water
Nozzle
pressure
Table 5. Cooling capacity of the ADAPT Parasol 1200 PF
Nozzle
pressure
50 pa
70 pa
Primary
airflow
Pressure drop constant, air/water
(l/s)
Sound
level in
dB(A) 2)
Cooling capacity of primary air (W) for ∆Tl
Cooling capacity, water (W)
for ∆Tmk 3)
6
8
10
12
6
7
8
9
10
kpl
kpk
LLLL
40.6
25
292
390
487
585
353
409
465
520
576
5.74
0.022
LHLH
53.8
25
387
516
646
775
393
460
522
583
644
7.61
0.022
HHHH
59.6
26
429
572
715
858
411
475
538
601
664
8.42
0.022
LLLL
48.0
30
346
461
576
691
418
484
548
613
683
5.74
0.022
LHLH
63.7
30
459
612
764
917
468
539
611
688
759
7.61
0.022
HHHH
70.4
32
507
676
845
1014
481
554
634
707
787
8.42
0.022
LLLL
54.5
33
392
523
654
785
469
541
612
690
760
5.74
0.022
LHLH
72.2
34
520
693
866
1040
521
600
685
763
848
7.61
0.022
HHHH
79.9
36
575
767
959
1151
535
615
703
791
870
8.42
0.022
ADAPT Parasol
90 pa
Nozzle
setting 1)
1) For particulars on the sizing of alternative nozzle settings, use Swegon’s ProSelect sizing program available at www.swegon.com
2) Room attenuation = 4 dB
3) The specified capacities are based on operation in the high capacity mode. Operation with the face plate set to the normal position reduces the water capacity of the ADAPT Parasol 600 by about 5% and that of the ADAPT Parasol 1200 by about 10 %.
The water capacity can vary depending on installation and how the airflow deflectors are set. The primary air capacity is not
affected.
The water capacity is reduced by 5 -10% when the ADC is adjusted to ”fan-shape”.
N.B.! The total cooling capacity is the sum of the airborne and waterborne cooling capacities.
Table 6. Cooling Capacity for natural convection
Unit (mm)
Cooling capacity (W) for temperature differential, room - water
∆Tmk (K)
6
7
8
9
10
11
12
ADAPT Parasol 600
17
21
25
29
34
39
43
ADAPT Parasol 1200
41
51
61
72
83
95
107
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
21
ADAPT Parasol
Calculation example – cooling
A cellular office having dimensions w × d × h = 2.4 × 4
× 2.7 m is to be fitted with a comfort module. The total
cooling demand is estimated to be 50 W/m2 To meet this
cooling load, an ADAPT Parasol that will generate 50 x
2.4 x 4 = 480 W is required.
Design room temperature (tr) 24°C, cooling water temperature (inlet flow/return) 14/16°C and primary air temperature (tl) 16°C produces:
∆Tk= 2 K
∆Tmk= 9 K
∆Tl = 8 K
The required primary air flow to the room (ql) has been
determined to be 16 l/s. A zone damper ensures that the
pressure in the duct should be kept at a constant 70 Pa.
The sound from the unit must not exceed 30 dB(A).
Solution
Cooling
The cooling capacity of the primary air can be calculated
using the following formula: Pl = 1.2 · ∆Tl · ql
Pl = 1.2 · 8 · 16 = 154 W
The ADAPT Parasol comfort module should therefore be
able to generate 480 – 154 = 326 W in cooling capacity
on the water side.
From Table 2 we can read that a 592 x 592 mm ADAPT
Parasol with a nozzle setting of LHLH and a primary
airflow of 16 l/s generates 444 W cooling capacity on the
water side. This is thus sufficient for meeting the cooling
energy demand in the room.
At the same time, this nozzle configuration makes it possible to save a large air volume when the module operates
in the No Occupancy mode, which in this case involves
4.6 l/s.
As an alternative, the nozzles can be set to the HHHH
settings. This then discharges more air when the room is
vacant (less savings) but an over capacity of air volume
and cooling energy to utilise if, for example, there are
often visitors to the office.
Chilled water
With the cooling capacity requirement of 326 W for the
cooling water, obtain in Diagram 1 the required water
flow. With a temperature increase of ∆Tk= 2 K, the water
flow will be 0.039 l/s.
In Diagram 2 we can read that a water flow of 0.039 l/s
does not produce a fully turbulent outflow, but that the
capacity must be corrected by a reduction factor of 0.97.
The loss of capacity can be compensated by calculating
the comfort module’s required cooling capacity as follows: Pk = 326 / 0.97 = 336 W.
A new water flow can be obtained from Diagram 1, qk =
0.040 l/s.
The pressure drop is calculated on the basis of a water
flow of 0.040 l/s and pressure drop constant kpk = 0.020,
which is taken from Table 2.
The pressure drop can now be read to be 4.0 kPa from
Diagram 4.
22
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
ADAPT Parasol
Heating
Heating function
The comfort module’s capability of quickly mixing the
primary air with the room air, makes the ADAPT Parasol
ideally suited for managing both cooling and heating.
Heating premises with air heated above room temperature discharged from the ceiling is, in other words,
an excellent alternative to traditional radiator heating
solutions. Some of the benefits achieved include lower
installation costs, simpler installation and perimeter walls
free from piping and radiators. When the ADAPT Parasol
is set to maintain a high nozzle pressure, there will be a
certain heating capacity, even with low airflow conditions
or while the module is operating during weekends, for
instance, when the flow is reduced for a longer period.
Electric heating
The ADAPT Parasol variant with electric heating utilizes
electric heating elements instead of heating water. The
tubular heating elements, situated inside the heating
water pipes of the coil, heat the circulated air that passes
through the coil. Radiant heat constitutes only a small
part of the total heating capacity
The ADAPT Parasol with electric heating is available in
two capacity variants, see the table below.
Variant
P (W)
Imax(A)
X1
500
2.2
X2
1000
4.3
ADAPT Parasol
Regardless of the type of heating system installed, it is
important to consider the operative temperature in a
room. Most people are comfortable when the operative temperature in winter is in between 20–24°C. The
optimum comfort requirements are normally met when
the room temperature is 22°C. This means that in a room
with a cold perimeter wall, the air temperature must be
higher than 22°C to compensate for the radiant cooling
energy. In new buildings with normal insulated perimeter walls and normal standards of window glazing, the
difference between the room air temperature and the
operative temperature is small. But for older buildings
with worse windows, it may be necessary to raise the air
temperature to compensate for the chilling effect. Different operating scenarios can be simulated easily using the
Swegon ProClim Web software where both the room air
temperature and operative temperature are specified.
Supplying heated air from the ceiling results in some
stratification of the air. For a supply flow temperature
of max. 40°C, the stratification is non-existent, while at
60°C it can be around 4 K in the occupied zone. This only
applies during the warming-up phase, when the room is
unused and there is no internal load. When the room is in
use, the lighting is on, a computer is running and occupants are in the room, the stratification will decrease or
disappear depending on the heating energy demand.
When heating with the ADAPT Parasol, it is advisable to
use an external temperature sensor or an extra sensor
module in the room.
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
23
ADAPT Parasol
Calculation formulae - waterborne heating
Below are formulae that enable the user to calculate what comfort module is best suited for the application. The values for the
calculations are in Tables 7-10.
The cooling or heating capacity of the air
Pl = 1.2 · ql · ∆Tl
Pl
The cooling or heating capacity of the air (W)
ql
Primary airflow (l/s)
∆Tl
Temperature differential between primary air (tl)
and room air (tr) (K)
Heating capacity of the water
P v = 4186 · qv · ∆Tv
Pv Heating capacity of the water (W)
qk Heating water flow (l/s)
∆Tv Temperature differential between the heating
water inlet flow and return (K)
Diagram 5. Water Flow – Heating Capacity
Pressure drop for heating circuit
∆pv = (qv / kpv) 2
∆pv Pressure drop in heating circuit (kPa)
qv Heating water flow (l/s), see Diagram 6
kpv Pressure drop constant for heating circuit, see Tables 7-10
Diagram 6. Pressure drop – heating water flow
24
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
ADAPT Parasol
Table 7 - Heating capacity, ADAPT Parasol 600
Nozzle
pressure
50 Pa
70 Pa
90 pa
Nozzle setting 1)
Primary air
flow (l/s)
Heating capacity, water (W) for DTmv 3)
Sound
level in
dB(A) 2)
5
10
15
20
25
30
kpl
kpv
101
202
303
401
501
601
1.01
0.0241
LLLL
7.2
<20
Pressure drop constant,
air/water
LHLH
13.4
<20
132
264
388
515
637
762
1.89
0.0241
HHHH
19.6
20
142
285
420
556
688
819
2.77
0.0241
LLLL
8.5
<20
116
235
350
466
583
698
1.01
0.0241
LHLH
15.9
24
148
297
439
585
726
867
1.89
0.0241
HHHH
23.2
25
161
320
471
626
775
924
2.77
0.0241
LLLL
9.6
20
130
257
386
514
641
769
1.01
0.0241
LHLH
18.0
28
163
323
480
635
788
943
1.89
0.0241
HHHH
26.3
29
173
347
513
677
841
1002
2.77
0.0241
Table 8 - Heating capacity, ADAPT Parasol 600 PF
Heating capacity, water (W) for DTmv
3)
Nozzle
pressure
Nozzle setting 1)
Primary air
flow (l/s)
dB(A) 2)
5
10
15
20
25
30
kpl
kpv
50 Pa
LLLL
22.1
23
108
221
339
456
575
696
3.13
0.018
LHLH
27.9
27
109
233
360
494
631
770
3.95
0.018
HHHH
33.7
27
109
239
378
521
669
820
4.76
0.018
70 Pa
Pressure drop constant,
air/water
LLLL
26.2
28
126
255
390
527
665
804
3.13
0.018
LHLH
33
31
129
269
414
562
713
867
3.95
0.018
HHHH
39.8
32
131
277
429
588
747
911
4.76
0.018
LLLL
29.7
31
137
282
429
581
731
882
3.13
0.018
LHLH
37.5
35
142
294
453
611
775
939
3.95
0.018
HHHH
45.2
36
146
306
468
635
805
977
4.76
0.018
ADAPT Parasol
90 pa
Sound
level
1) For particulars on the sizing of alternative nozzle settings, use Swegon’s ProSelect sizing program available at www.swegon.com
2) Room attenuation = 4 dB
3) The specified capacities are based on operation in the high capacity mode. Operation with the face plate set to the normal position
reduces the water capacity of the ADAPT Parasol 600 by about 5% and that of the ADAPT Parasol 1200 by about 10%.
The water capacity can vary depending on installation and how the airflow deflectors are set. The primary air capacity is not affected.
The water capacity is reduced by 5 -10% when the ADC is adjusted to ”fan-shape”.
N.B.! The total heating capacity is the sum of the airborne and waterborne heating capacities. If the primary air temperature is lower
than the room temperature, it causes negative impact on the total heating capacity.
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
25
ADAPT Parasol
Table 9 - Heating capacity, ADAPT Parasol 1200
Nozzle
pressure
50 Pa
70 Pa
90 pa
Nozzle setting 1)
Primary air
flow (l/s)
Sound
level in
dB(A) 2)
Heating capacity, water (W) for DTmv 3)
5
10
15
20
25
Pressure drop constant,
air/water
30
kpl
kpv
LLLL
13.0
<20
173
348
643
944
1117
1291
1.84
0.0273
LHLH
29.4
22
221
446
823
1207
1432
1653
4.16
0.0273
HHHH
35.6
26
227
457
850
1243
1475
1706
5.04
0.0273
LLLL
15.4
20
197
391
729
1063
1260
1453
1.84
0.0273
LHLH
34.8
26
247
494
919
1345
1592
1826
4.16
0.0273
HHHH
42.2
29
253
507
948
1384
1642
1873
5.04
0.0273
LLLL
17.5
<20
212
424
787
1156
1368
1580
1.84
0.0273
LHLH
39.5
29
263
532
990
1448
1717
1947
4.16
0.0273
HHHH
47.8
32
274
544
1019
1487
1762
1994
5.04
0.0273
Table 10. Heating capacity. ADAPT Parasol 1200 PF
Nozzle
pressure
50 Pa
70 pa
90 pa
Nozzle setting 1)
Primary air
flow (l/s)
Heating capacity. water (W) for DTmv 3)
Sound
level in
dB(A) 2)
5
10
15
20
25
30
kpl
kpv
511
743
975
1200
1422
5.74
0.027
LLLL
40.6
25
268
Pressure drop constant.
air/water
LHLH
52.0
25
305
576
843
1100
1358
1608
7.61
0.027
HHHH
59.6
26
315
599
874
1140
1406
1664
8.42
0.027
LLLL
48.0
30
315
602
882
1157
1423
1691
5.74
0.027
LHLH
63.7
30
354
677
992
1302
1607
1879
7.61
0.027
HHHH
70.4
32
369
702
1026
1344
1659
1933
8.42
0.027
LLLL
54.5
33
351
673
986
1294
1593
1868
5.74
0.027
LHLH
72.2
34
392
758
1109
1450
1792
2063
7.61
0.027
HHHH
79.9
36
402
778
1139
1501
1852
2119
8.42
0.027
1) For particulars on the sizing of alternative nozzle settings, use Swegon’s ProSelect sizing program available at www.swegon.com
2) Room attenuation = 4 dB
3) The specified capacities are based on operation in the high capacity mode. If the face plate is set to the normal position, this will
reduce the water capacity of the ADAPT Parasol 1200 PF by between 5 and 12%.
The water capacity can vary depending on the installation and how the air deflectors are set. The primary air capacity is not
affected.
The water capacity is reduced by 5 -10% when the ADC is adjusted to ”fan-shape”.
N.B.! The total heating capacity is the sum of the airborne and waterborne heating capacities. If the primary air temperature is
lower than the room temperature, it causes negative impact on the total heating capacity.
26
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
ADAPT Parasol
Calculation example - heating
In a cellular office with dimensions w × d × h = 2.4 × 4 ×
2.7 m (the same room as in the example for cooling) there
is also a heating demand of 450 W in the winter. The primary air flow should be the same as in the summer case,
16 l/s and the duct pressure is now kept constant..
Design room temperature (tr) 22 °C, heating water
temperature (supply/return) 45/39 °C and the primary air
temperature (tl) 20 °C produces:
∆Tv = 6 K
∆Tmv = 20 K
∆Tl = -2 K
Solution
Heating
The primary airflow of 16 l/s in combination with the
primary air temperature of 20 °C produces a negative
impact on the heating capacity: 1.2 x 16 x (-2) = -38 W.
The required heating capacity from the heating water
thus increases to 450 + 38 = 488 W. From Table 7 we
obtain from ΔTmv = 20 K and the primary airflow 16 l/s a
heating capacity of
P v = 585 W from a single module unit with LHLH nozzle
settings, which is sufficient for meeting the heat load.
ADAPT Parasol
Heating water
With a heating capacity requirement of 488 W and ΔTv =
6 K the necessary water flow is obtained in Diagram 5:
0.019 l/s. The pressure drop for the heating water is calculated on the basis of a water flow of 0.019 l/s and pressure drop constant kpv = 0.0241, which is taken from Table
7. The pressure drop will then be: Δpv = (qv /kpv)2 = (0.019
/ 0,0241)2 = 0.62 kPa. As an alternative, the pressure drop
can be read in Diagram 6.
Electric heating
The 488 W heating load can also be met with ADAPT
Parasol electric heating variant X1, which generates 500
W heating capacity.
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
27
ADAPT Parasol
Table 11. Cross-talk
Typical Rw-values between office rooms with ADAPT
Parasol where the partition wall extends with its top edge
against the suspended ceiling (with excellent sealing properties). Assumes that the partition wall will have at least
the same Rw-value as that given in the table.
Design
Suspended
ceiling
Rw (dB)
With
ADAPT
Parasol
Rw (dB)
Light acoustic suspended ceiling. Mineral
wool or perforated steel / aluminium coffers or screen.
28
28
Light acoustic suspended ceiling. Mineral
wool or perforated steel / aluminium coffers or screen.
The suspended ceiling is lined with 50
mm thick mineral wool*.
36
Light acoustic suspended ceiling. Mineral
wool or perforated steel/aluminium coffers or screen.
Vertical 100 mm thick mineral wool
panel as sound insulation between the
office cubicles*.
36
Perforated gypsum panels in T-section
grid system.
Acoustic insulation on the top side (25
mm thick).
36
Seal the gypsum board suspended ceiling
with insulation on top side.
45
36
36
Natural attenuation and end reflection
natural attenuation ΔL (dB) including end reflection.
Table 12. natural attenuation ΔL (dB) ADAPT Parasol
600
Octave band (Hz)
Nozzle setting
63 125 250 500 1k 2k 4k 8k
LLLL
19
20
17
16
17 16 15 15
MMMM
17
18
15
14
15 14 13 13
HHHH
15
16
13
12
13 12 11 11
Table 13. Natural attenuation ΔL (dB) ADAPT Parasol
600 PF
Octave band (Hz)
Nozzle setting
63 125 250 500 1k 2k 4k 8k
LLLL
19
20
17
16
17 16 15 15
MMMM
17
18
15
14
15 14 13 13
HHHH
15
16
13
12
13 12 11 11
Table 14. natural attenuation ΔL (dB) ADAPT Parasol
1200
*Overview: Rockwool 70 kg/m, Gullfiber 50 kg/m.
Octave band (Hz)
36
44
Nozzle setting
63 125 250 500 1k 2k 4k 8k
LLLL
18
19
16
15
16 15 14 14
MMMM
16
17
14
13
14 13 12 12
HHHH
14
15
12
11
12 11 10 10
Table 15. Natural attenuation ΔL (dB) ADAPT Parasol
1200 PF
Octave band (Hz)
28
Swegon reserves the right to alter specifications.
Nozzle setting
63 125 250 500 1k 2k 4k 8k
LLLL
19
15
11
7
7
8
13 16
MMMM
19
15
11
7
7
8
13 16
HHHH
19
15
11
7
7
8
13 16
17-06-2013
www.swegon.com
ADAPT Parasol
Dimensions,
ADAPT Parasol 600
Water connections, ADAPT Parasol 600
192,5
192,5
102,5 102,5
567
35
20
113
78
220 / 250*
50
584 / 592 / 598 / 617 / 623 / 642 / 667 +2
Figure 31. ADAPT Parasol 600, viewed from end wall
* = ADAPT Parasol 600 PF
Figure 34. ADAPT Parasol 600, water connections
B2
Värme retur/
Heating return
588
600
B1
A1
Värme tillopp/ Kyla tillopp/
Heating supply Cooling supply
A2
37
Kyla retur/
Cooling return
228
Figure 35. ADAPT Parasol 600 label
A1 = Chilled water inlet connection ø12x1.0 mm (Cu)
A2 = Chilled water return connection ø12x1.0 mm (Cu)
B1 = Heating water inlet connection ø12x1.0 mm (Cu)
B2 = Heating water return connection ø12x1.0 mm (Cu)
228
37
50
125 / 160*
Figure 32. ADAPT Parasol 600, viewed from above
* = ADAPT Parasol 600 PF
567
76
284
151
584 / 592 / 598 / 617 / 623 / 642 / 667 +2
Figure 33. ADAPT Parasol 600, side view
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
29
ADAPT Parasol
Observe the following:
For the single-module unit, it is important that the chilled
water is connected to the correct pipe connection. The
direction of water flow is necessary for obtaining full
capacity. The required direction of water flow is
marked by arrows on the end wall of the unit.
ADAPT Parasol
Dimensions,
ADAPT Parasol 1200
50
20
220 / 250*
567
584 / 592 / 598 / 617 / 623 / 642 / 667 +2
Figure 36. ADAPT Parasol 1200, viewed from end wall
* = ADAPT Parasol 1200 PF
37
228
228
37
1188
50
125 / 160*
Figure 37. ADAPT Parasol 1200, viewed from above
* = ADAPT Parasol 1200 PF
1167
284
151
1184 / 1192 / 1198 / 1242 / 1248 / 1292 / 1342 +2
Figure 38. ADAPT Parasol 1200, side view
30
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
ADAPT Parasol
Water connections, ADAPT Parasol 1200
Air connection, ADAPT Parasol 600/1200
I
192,5
192,5
H
102,5 102,5
113
78
I
Figure 39. ADAPT Parasol 1200, water connections
B2
1200
B1
Värme retur/
Heating return
Värme tillopp/
Heating supply
A1
A2
Kyla tillopp/
Cooling supply
Kyla retur/
Cooling return
I
Figure 41. Connection with bend, viewed from end wall
Mounted SYST CA xxx-90 connection piece
ADAPT Parasol 600 ADAPT Parasol 600 PF
ADAPT Parasol 1200
ADAPT Parasol 1200 PF
H = 460
H = 495
H = 460
H = 495
I = 125
I = 160
I = 125
I = 160
Figure 40. ADAPT Parasol 1200 label
A1 = Chilled water inlet conn. ø12x1.0 mm (Cu)
A2 = Chilled water return conn. ø12x1.0 mm (Cu)
B1 = Heating water inlet conn. ø12x1.0 mm (Cu)
B2 = Heating water return conn. ø12x1.0 mm (Cu)
ADAPT Parasol
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
31
ADAPT Parasol
Accessories, factory-fitted
Valve with actuator, SYST VEN115 with LUNA AT for cooling energy and heat.
Fitted and wired to the controller. See separate product datasheet at www.swegon.com.
Detect Qa Co2 sensor
Analogue carbon dioxide sensor to be fitted concealed from view above the face plate.
See separate product datasheet at www.swegon.com.
Detect VOC sensor
Modbus-connected air quality sensor to be fitted concealed from view above the face
plate.
POWER Adapt 20 VA transformer
230 V 50-60 Hz input voltage
24 V AC output voltage
20 VA capacity
IP33 rated enclosure
The factory-fitted accessories above can also be ordered as individual items of equipment.
Accessories
SYST TS-1 72 VA Transformer
Double-insulated protective transformer, 230V AC/24 V AC
See separate product datasheet at www.swegon.com.
CONDUCTOR T-TG temperature sensor
External temperature sensor. Used for example if the room temperature
is to be measured at a location other than by the sensor module or for
measuring the temperature on the main pipe in a change-over system.
External sensor module
Sensor module with temperature sensor and presence detector for wall
mounting when an extra sensor module is required in the room (1 pc is
always supplied with the ADAPT Parasol)
Available in a circular or rectangular model and is always supplied with
both mounting frame for the most common existing electrical connection
boxes as well as a protruding frame for surface mounting.
32
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
ADAPT Parasol
Cable, SYST CABLE RJ12 6-LED.
Cable for connection of an external sensor module to the controller or
between sensor modules. Available in various lengths.
Cable, CABLE CONVERTER USB-RJ12 (RS485)
Cable with built-in modem for connecting a PC to the controller.
Needed for running SWICCT or ModbusPoll, for instance.
ADAPTER RJ12-WIRE
Adapter for connecting the cable together with a RJ12 connector and
cable with multi-pin cable ends.
Can also be used as an RJ12 splitter.
Card circuit breaker, SYST SENSO
Key card holder for hotel rooms.
Flexible connection hoses, SYST FH
Flexible hoses are available with quick-fit, push-on couplings as well as
clamping ring couplings for quick and simply connection. The hoses are
also available in various lengths. Note that clamp ring couplings require
support sleeves inside the pipes.
F1 = Flexible hose with clamp ring couplings
F20 = Flexible hose with quick-fit push-on couplings
F30 = Flexible hose with quick-fit push-on couplings on one end and G20ID sleeve
nuts on the other end.
ADAPT Parasol
SYST MS M6 Assembly piece
The assembly piece is used for installation and consists of threaded rods,
ceiling mounts as well as nuts for all four suspension mounts.
4x
F1
F20
F30
SYST AR-12 push-on venting nipple
A venting nipple is available as a complement to the flexible hoses with
push-on couplings. The nipple fits directly in the push-on hose coupling
and can be fitted in an instant.
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
33
ADAPT Parasol
Connection piece, air – insertion joint, SYST AD1
SYST AD1 is used as an insertion joint between the ADAPT Parasol and
the duct system. Available in two dimensions: Ø125 and Ø160 mm.
Connection piece, air, SYST CA
duct bend, 90°
Available in two dimensions: Ø125 and Ø160 mm.
Plasterboard frame, Parasol b T-FPB
Frame for creating an attractive interface between the ADAPT Parasol and
the opening in the plasterboard ceiling.
Tool for nozzle adjustment, SYST TORX
Tool designed for easy adjustment of the nozzle plates.
Optional perforation patterns
The face plate of the unit is available with three different perforation patterns that make it easily adaptable to suit different types of ceiling components, e.g. light fittings and exhaust grilles that share the surface of a suspended ceiling.
Other patterns are of course available on special order. For further details, contact your nearest Swegon representative.
A. Face plate, standard PB
Circular holes arranged in a triangular pattern.
A.
B.
C.
B. Face plate, PD
Circular holes arranged in a square pattern with a graduated
border.
C. Face plate, PE
Square holes arranged in a square pattern with a graduated
border.
34
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
ADAPT Parasol
Ordering key
Type of ceiling
Dimensions of the face plate (mm)
Lay-in T-Bar system
600 module
1200 module
c-c 600
592x592
1192x592
c-c 600 SAS130/15
584x584
1184x584
c-c 625
617x617
1242x617
c-c 650
642x642
1292x642
c-c 675
667x667
1342x667
Clip-in / metal tile
600 module
1200 module
c-c 600
598x598
1198x598
623x623
1248x623
c-c 625
The tolerance is +±2 mm
Function
The units can be ordered in various
functional versions:
A = Cooling and supply air
B = Cooling, heating and supply air
X = Cooling, electric heating and
supply air
Factory-fitted ADC supplied as standard
Airflow variant
Single module unit:
ADAPT Parasol
ADC
ADAPT Parasol 600
ADAPT Parasol 600 PF
Two-module unit:
ADAPT Parasol 1200
ADAPT Parasol 1200 PF
(PF = PlusFlow, extra high airflow)
Software configuration
The product can be supplied with
certain software settings preconfigured from the factory. For example:
Occupancy flow and temperature set
point.
Nozzle setting
Each side can be set in three different ways: L, M or H
L = Low airflow
M = Medium airflow
H = High airflow
Colour
The units are supplied painted in
Swegon’s standard shade of white,
RAL 9010, gloss level 30 ±6%
Communication
Modbus RTU
Swegon reserves the right to alter specifications.
17-06-2013
www.swegon.com
35
ADAPT Parasol
Ordering key
Summary of accessories
Sensor module
Contractor demarcation
Swegon’s supply demarcation is at the connection points
for water and air as well as for wiring the room control
equipment (see Figures 31, 32, 33, 34, 35 and 36, 37, 38,
39, 40, 41).
• The pipework contractor connects the connections
points for water to the plain pipe ends and fills the
system, vents it and tests the pressure. If the room
control equipment is installed from the factory, connect the return pipe for chilled water and heating
water respectively to the valve. (DN ½” male threads).
• The ventilation contractor connects ducting to the air
connection spigot.
• The electrical installation contractor connects the
power (24 V) and the signal cables to the wiring terminals equipped with spring-loaded pressure connections. The maximum permissible cable cross-sectional
area is 2.5 mm2. For reliable operation we recommend
the use of cable ends with multi-pin connectors.
36
Swegon reserves the right to alter specifications.
Valve actuator
LUNA AT
Valve
SYST VEN115
CO2 sensor
DETECT Qa
Temperature sensor
CONDUCTOR T-TG
VOC sensor
DETECT VOC
Tool for nozzle adjustment
SYST TORX
Transformer
SYST TS-1, 72 VA
Transformer
POWER Aa, 20 VA
Connection piece, air –
insertion joint
SYST AD1
Connection piece, air – 90°
SYST CA
Assembly piece
SYST MS M6
Flexible connection hose, with
clamp ring couplings.
SYST FH F1
Flexible connection hose with
quick-fit couplings (push-on)
SYST FH F20
Flexible connection hose with
quick-fit coupling (push-on) in
one end and G20ID sleeve nut
in the other end.
SYST FH F30
Venting nipple, push-on
SYST AR-12
Plasterboard ceiling frame
Parasol b T-FPB
Cable (2xRJ12)
SYST CABLE RJ12 6-LED.
Cable (USB+RJ12)
CABLE CONVERTER USBRJ12 (RS485)
Adapter
ADAPTER RJ12-WIRE
Key-Card circuit breaker
SYST SENSO
Perforated face plate, (in
addition to PB standard
perforations)
PD
PE
17-06-2013
www.swegon.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement