CB 140 Manual

OPERATOR'S MANUAL

FURNACE MODEL: CB 140

MULTI-OIL FURNACES

with CB-125 BURNER

USED-OIL BURNING

APPLIANCE

#MH15393 (N)

LISTED

USED OIL-FIRED

FURNACE

I89053-A

CLEAN BURN PART # 43231 PUBLICATION DATE: 07/16/13, Rev. 13

WARNING: DO NOT assemble, install, operate, or maintain this equipment without first reading and understanding the information provided in this manual. Installation and service must be accomplished by qualified personnel. Failure to follow all safety precautions and procedures as stated in this manual may result in property damage, serious personal injury or death.

IMPORTANT FOR U.S. INSTALLATIONS: All installations must be made in accordance with state and local codes which may differ from the information provided in this manual. Save these instructions for reference.

IMPORTANT FOR CANADIAN INSTALLATIONS: These instructions have been reviewed and accepted by

Underwriters' Laboratories of Canada as being appropriate for the installation of the ULC labelled products identified herein. The use of these instructions for the installation of products NOT bearing the ULC label and

NOT identified herein may result in an unacceptable or hazardous installation.

IMPORTANT FOR CANADIAN INSTALLATIONS: The installation of this equipment is to be accomplished by qualified personnel and in accordance with the regulation of authorities having jurisdiction and CSA Standard B 139,

Installation Code for Oil Burning Equipment.

CLEAN BURN

WASTE OIL FURNACE

WARRANTY INFORMATION

Clean Burn, LLC, MANUFACTURER, hereby warrants that MANUFACTURER’s products shall be free from defect in material and workmanship under normal use according to the provisions and limitations herein set forth.

MANUFACTURER warrants the heat exchanger/combustion chamber for a period of ten (10) years or 15,000 hours,

whichever comes first), from the date of purchase by the original purchaser, as follows:

If the defect occurs within the first ten (10 years or 15,000 hours, whichever comes first), Clean Burn will replace or repair the heat exchanger/combustion chamber.

MANUFACTURER warrants all other Clean Burn component parts, including the energy retention disk, for a period of

one (1) year from the date of purchase by the original purchaser.

LIMITATIONS:

The obligation of MANUFACTURER for breach of warranty shall be limited to products manufactured by

MANUFACTURER, (1) that are installed, operated and maintained according to MANUFACTURER’s instructions furnished and/or available to the purchaser upon request; (2) that are installed according to all other applicable Federal, State and local codes or regulations; and (3) that the purchaser substantiates were defective in material and workmanship notwithstanding that they were properly installed and correctly maintained as set forth above and were not abused or misused. The

MANUFACTURER may request service records or require photos of the installation or defect.

The obligation of MANUFACTURER shall be limited to replacing or repairing the defective product, at the option of the

MANUFACTURER. MANUFACTURER shall not be responsible for any labor or costs or removal or reinstallation of its products and shall not be liable for transportation costs to and from its plant at Janesville, Wisconsin.

Use of parts for modification or repair of the product or any component part thereof not authorized or manufactured by

MANUFACTURER specifically for such product shall void this warranty.

This warranty shall not apply to any damage to or defect in any of MANUFACTURER’s products that is directly or indirectly caused by (1) force majeure, Act of God or other accident not related to an inherent product defect; or (2) abuse, misuse or neglect of such product, including any damage caused by improper assembly, installation, adjustment, service, maintenance or faulty instruction of the purchaser.

Other than as expressly set forth hereinabove, MANUFACTURER makes no other warranty, express or implied, with respect to any of MANUFACTURER’s products, including but not limited to any warranty of merchantability or fitness for a particular purpose.

And in no event shall MANUFACTURER be responsible for any incidental or consequential damages of any nature suffered by purchaser or any other person or entity caused in whole or in part by any defect in any of MANUFACTURER’s products.

Any person or entity to whom this warranty extends and who claims breach of warranty against MANUFACTURER must bring suit thereon within one year from the date of occurrence of such breach of warranty or be forever barred from any and all legal or other remedies for such breach of warranty.

MANUFACTURER is not responsible for and hereby disclaims any undertaking, representation or warranty made by any dealer, distributor or other person that is inconsistent with or in any way more expansive than the provisions of this limited warranty.

Warranty (continued)

This warranty grants specific legal rights and shall be read in conformity with applicable state law. In some jurisdictions, the applicable law mandates warranty provisions that provide greater legal rights than those provided for herein. In such case, this limited warranty shall be read to include such mandated provisions; and any provision herein that is prohibited or unenforceable in any such jurisdiction shall, as to such jurisdiction, be ineffective to the extent of such prohibition or unenforceability without invalidating the remaining provisions and without affecting the validity or enforceability of such provision in any other jurisdiction(s).

TRADEMARKS

The Clean Burn logo is a trademark of Clean Burn, LLC. All other brand or product names mentioned are the registered trademarks or trademarks of their respective owners.

COPYRIGHT

Copyright © 2013 Clean Burn, LLC. All rights reserved. No part of this publication may be reproduced, or distributed without the prior written permission of Clean Burn, LLC. 4109 Capital Circle, Janesville, WI 53546. Subject to change without notice.

TABLE OF CONTENTS

SECTION 1: INTRODUCTION .............................................................................................. 1-1

Guide to this Manual ........................................................................................................ 1-1

For Your Safety... .............................................................................................................. 1-2

Guidelines for Furnace Usage ................................................................................... 1-4

Guidelines for Used Oil Tanks ................................................................................... 1-5

Safety Labels ............................................................................................................. 1-6

SECTION 2: UNPACKING ..................................................................................................... 2-1

Removing the Shipping Crate .......................................................................................... 2-1

Unpacking and Inspecting All Components ..................................................................... 2-1

Furnace Component List ........................................................................................... 2-1

Warranty Registration ....................................................................................................... 2-2

SECTION 3: FURNACE ASSEMBLY .............. .................................................................. 3-1

Understanding Assembly .................................................................................................. 3-1

Required Tools and Materials .................................................................................... 3-1

Overview of Furnace Assembly ....................................................................................... 3-2

Installing the Observation Port ......................................................................................... 3-3

Installing the Air Outlet Louvers ...................................................................................... 3-3

Installing the Combustion Sleeve ..................................................................................... 3-5

Installing the Burner ......................................................................................................... 3-6

Checking the Burner Nozzle and Electrodes ............................................................. 3-6

Mounting the Burner on the Hinge Bracket .............................................................. 3-7

Installing the Connector Block, Oil Line Tubing, and Air Line Tubing ........................... 3-8

Installing the Connector Block on the Furnace Door ................................................ 3-8

Installing the Oil Line Tubing .................................................................................... 3-8

Installing the Air Line Tubing .................................................................................... 3-9

Locking the Burner into Firing Position .................................................................... 3-9

SECTION 4: FURNACE INSTALLATION ........................................................................... 4-1

Understanding Installation ................................................................................................ 4-1

Typical Installation Illustration .................................................................................. 4-2

Selecting a Location ......................................................................................................... 4-3

Guidelines for Selecting a Location .......................................................................... 4-3

Clearances for Installation ......................................................................................... 4-3

Mounting the Furnace ....................................................................................................... 4-4

Ceiling Mounting ....................................................................................................... 4-4

Raised Platform Mounting ......................................................................................... 4-5

Floor Mounting .......................................................................................................... 4-5

Oil Tank Installation Specifications .................................................................................. 4-7

Installing the Tank Vent and Emergency Vent ........................................................... 4-8

Installing the Metering Pump ........................................................................................... 4-9

Preparing for Installation ........................................................................................... 4-9

Standard Mounting: Vertical Positioning .................................................................. 4-9

Alternate Mounting: Horizontal Positioning .......................................................... 4-11

TABLE OF CONTENTS

SECTION 4: FURNACE INSTALLATION (continued)

Wiring the Furnace and Pump ........................................................................................ 4-12

Wiring to the Furnace .............................................................................................. 4-12

Wiring to the Metering Pump .................................................................................. 4-12

Installing the Suction Oil Line Components .................................................................. 4-13

Installing the Pressure Relief Oil Line Back to the Tank ............................................... 4-16

Installing the Pressure Oil Line Components ................................................................. 4-17

Installing the Compressed Air Line ................................................................................ 4-17

Installing the Stack ......................................................................................................... 4-18

Installing the Interior Stack ..................................................................................... 4-21

Installing the Barometric Damper ........................................................................... 4-21

Installing the Stack Safety Switch For Canadian Installations ................................ 4-22

Resetting the Stack Safety Switch ..................................................................... 4-23

Understanding the Function of the Stack Safety Switch ................................... 4-23

Installing the Stack Penetration ............................................................................... 4-24

Installing the Exterior Stack .................................................................................... 4-24

Installing the Stack Cap ........................................................................................... 4-24

Installing the Optional Draft Inducer ....................................................................... 4-24

Installing the Wall Thermostat ........................................................................................ 4-26

Replacing the Wall Thermostat Batteries................................................................. 4-26

Inspecting the Furnace Installation ................................................................................. 4-26

SECTION 5: METERING PUMP PRIMING ..................................................................5-1

Understanding Metering Pump Priming ........................................................................... 5-1

Required Tools and Materials .................................................................................... 5-1

Priming the Metering Pump ............................................................................................. 5-2

Vacuum Testing the Oil Pump .......................................................................................... 5-4

SECTION 6: STARTING AND ADJUSTING THE BURNER .......................................6-1

Understanding Burner Startup and Adjustment ................................................................ 6-1

Preparing the Burner for Startup ...................................................................................... 6-1

Starting the Burner ........................................................................................................... 6-2

Checking the Operation of the Fan/Blower Motor ........................................................... 6-4

SECTION 7: RESETTING THE OIL PRIMARY CONTROL ........................................7-1

Understanding the Oil Primary Control ........................................................................... 7-1

Using the Reset Button ..................................................................................................... 7-1

The Blower/Fan Switch .................................................................................................... 7-2

The High Temp Limit Switches ........................................................................................ 7-2

Understanding the L-200 High Temp Limit Switches ............................................... 7-2

Understanding the L-290 Auxiliary Auto Reset High Temp Limit Switch ............... 7-2

TABLE OF CONTENTS

SECTION 8: ADJUSTING THE DRAFT OVER FIRE ..................................................8-1

Understanding the Importance of Draft ............................................................................ 8-1

Checking for Correct Draft Over Fire .............................................................................. 8-1

Adjusting the Barometric Damper .................................................................................... 8-2

Solving Draft Over Fire Problems .................................................................................... 8-2

Understanding the Effect of Exhaust Fans on Draft .................................................. 8-3

Checking Draft Over Fire to Determine Severity of Backdraft ................................. 8-3

Installing a Make-up Air Louver ............................................................................... 8-5

SECTION 9: MAINTENANCE ......................................................................................9-1

Understanding Maintenance ............................................................................................. 9-1

Periodic Burner Inspection ............................................................................................... 9-1

Cleaning the Canister Filter .............................................................................................. 9-2

Servicing the Metering Pump ........................................................................................... 9-3

Cleaning the Check Valve / Screen................................................................................... 9-3

Cleaning the Tank ............................................................................................................. 9-4

Cleaning Ash from the Furnace ........................................................................................ 9-5

Annual Burner Tune-Up ................................................................................................... 9-7

End of Season Maintenance ............................................................................................. 9-7

Cleaning and Maintaining the Optional Draft Inducer ..................................................... 9-7

SECTION 10: TROUBLESHOOTING ........................................................................10-1

Flow Chart ...................................................................................................................... 10-2

Troubleshooting Tables .................................................................................................. 10-3

APPENDIX A

Detailed Furnace Specifications ...................................................................................... A-1

Burner Technical Specifications ...................................................................................... A-2

Furnace Dimensions ....................................................................................................... A-3

Burner Components ......................................................................................................... A-4

Removing the Nozzle for Cleaning .......................................................................... A-9

CB-140 Cabinet Components ........................................................................................ A-10

Metering Pump Components ......................................................................................... A-12

APPENDIX B

Wiring Diagrams ..............................................................................................................B-1

Furnace Wiring Diagram ...........................................................................................B-1

CB-125 Burner Wiring Diagram ...............................................................................B-2

Ladder Schematic ......................................................................................................B-3

Metering Pump Wiring Schematic .............................................................................B-4

CAD Cell Oil Primary Control Data Sheet ................................................................B-5

APPENDIX C

Furnace Service Record ....................................................................................................C-1

Operator's Manual: Model CB-140

SECTION 1: INTRODUCTION

Guide to this Manual

This manual contains all the information necessary to safely install and operate the Clean Burn furnace model CB-140 . Consult the Table of Contents for a detailed list of topics covered. You'll find this manual's step-by-step procedures easy to follow and understand. Should questions arise, please contact your Clean Burn dealer before starting any of the procedures in this manual.

As you follow the directions in this manual, you'll discover that assembling and operating your new furnace involves five basic activities as outlined here:

UNPACKING ..................................................................................................... (Section 2)

• OPERATION

Metering Pump Priming ........................................................................ (Section 5)

Starting and Adjusting the Burner ....................................................... (Section 6)

• Resetting the Oil Primary Control ....................................................... (Section 7)

• Adjusting the Draft ............................................................................... (Section 8)

• MAINTENANCE

The manual also contains important and detailed technical reference materials which are located at the back of the manual in the Appendixes.

Please read all sections carefully, including the important safety information found in this section before beginning any installation/operation procedures; doing so ensures your safety and the optimal performance of your Clean Burn furnace.

WARNING!

1-1

STOP

YOUR SAFETY IS AT STAKE!

DO NOT INSTALL, OPERATE OR

MAINTAIN THIS EQUIPMENT

WITHOUT FIRST READING

AND UNDERSTANDING THE

OPERATOR'S MANUAL!

Operator's Manual: Model CB-140

For Your Safety...

For your safety, Clean Burn documentation contains the following types of safety statements (listed here in order of increasing intensity). Note the safety key words printed in bold for each:

instructions are not followed.

CAUTION: A safety statement that reminds of safety practices or directs attention to unsafe practices which could result in personal injury if proper precautions are not taken.

WARNING: A strong safety statement indicating that a hazard exists which can result in injury or death if proper precautions are not taken.

DANGER! The utmost levels of safety must be observed; an extreme hazard exists which would result in high probability of death or irreparable serious personal injury if proper precautions are not taken.

In addition to observing the specific precautions listed throughout the manual, the following

general precautions apply and must be heeded to ensure proper, safe furnace operation.

DANGER! DO NOT create a fire or explosion hazard by storing or using gasoline or other flammable or explosive liquids or vapors near your furnace.

DANGER! DO NOT operate your furnace if excess oil, oil vapor or fumes have accumulated in or near your furnace. As with any oil burning furnace, improper installation, operation or maintenance may result in a fire or explosion hazard.

WARNING: DO NOT add inappropriate or hazardous materials to your used oil, such as:

• Anti-freeze

• Carburetor cleaner

• Paint thinner

• Parts washer solvents

• Gasoline

• Oil additives

• Any other inappropriate/hazardous material

WARNING: Burning chlorinated materials (chlorinated solvents and oils) is illegal, will

severely damage your heat exchanger, immediately void your warranty, and adversely affect the proper, safe operation of your furnace. Instruct your personnel to never add hazardous materials to your used oil.

1-2

Operator's Manual: Model CB-140

For Your Safety... (continued)

WARNING: Never alter or modify your furnace without prior written consent of Clean

Burn, LLC. Unauthorized modifications or alteration can adversely affect the proper, safe operation of your furnace.

WARNING: The burner which is shipped with your Clean Burn furnace is to be used only with your furnace according to the instructions provided in this manual. DO NOT use the burner for any other purpose!

WARNING: The Best Operator is a Careful Operator! By using common sense, observing general safety rules, and adhering to the precautions specific to the equipment, you, the operator, can promote safe equipment operation. Failure to use common sense,

observe general safety rules, and adhere to the precautions specific to the equipment may result in equipment damage, fire, explosion, personal injury and/or death.

WARNING: The installation, operation, and maintenance of this equipment in the U.S. must be accomplished by qualified personnel and in compliance with the specifications in the Clean Burn Operator's Manual and with all national, state, and local codes or authorities having jurisdiction over environmental control, building inspection and fuel, fire and electrical safety and the following standards:

NFPA 30 Flammable and Combustible Liquids Code

NFPA 30A Automotive and Marine Service Station Code

NFPA 31 Standard for the Installation of Oil Burning Equipment

NFPA 211 Chimneys, Fireplaces, Vents and Solid Fuel Burning Appliances

NFPA 88A Parking Structures

NFPA 88B Repair Garages

NFPA 70 National Electrical Code

The International Mechanical Code

The International Building Code

The International Fire Code

The International Fuel Gas Code

Likewise, the installation, operation, and maintenance of this equipment in Canada is to be accomplished by qualified personnel and in compliance with the specifications in the

Clean Burn Operator's Manual and in accordance with the regulation of authorities having jurisdiction and the following CSA Standards:

B139 Installation Code for Oil Burning Equipment

B140.0 General Requirements for Oil Burning Equipment

C22.1 Canadian Electrical Code, Part 1.

Failure to comply with these standards and requirements may result in equipmentdamage, fire, explosion, personal injury and/or death.

1-3

Operator's Manual: Model CB-140

For Your Safety... (continued)

Guidelines for Furnace Usage

n

This furnace is listed for commercial and/or industrial use only; it is not listed for

residential use.

n

This furnace is listed with Underwriters Laboratory and Underwriters' Laboratories

of Canada to burn the following fuels:

• #2 fuel oil

• Used crankcase oil up to 50 SAE

• Used hydraulic oil

• Used transmission fluid (U.S.)

• #4 and #5 fuel oil (U.S.) n

Make sure you comply with all EPA regulations concerning the use of your furnace.

EPA regulations require that:

• Your used oil is generated on-site. You may also accept used oil from

"do-it-yourself" oil changers.

• Hazardous wastes, such as chlorinated solvents, are NOT to be mixed

with used

• The flue gases are vented to the outdoors with an appropriate stack.

• Your used oil is recycled as fuel for "heat recovery". DO NOT operate

your furnace in warm weather just to burn oil.

Contact your Clean Burn dealer for current EPA regulations.

n

If your furnace ever requires service, call your Clean Burn dealer. DO NOT allow

untrained, unauthorized personnel to service your furnace. Make sure that your

furnace receives annual preventative maintenance to ensure optimal performance.

1-4

Operator's Manual: Model CB-140

For Your Safety... (continued)

Guidelines for Used Oil Tanks

For the safe storage of used oil and the safety of persons in the vicinity of the used oil supply tank, ensure that your tank installation adheres to the following safety guidelines:

national and local codes. Consult your

local municipal authorities for more

information as necessary.

Review and adhere to the safety

guidelines for used oil supply tanks

as stated in the WARNING shown.

• Ensure that the tank for your furnace

installation complies with all code and

safety requirements as stated here. If the

tank does not comply, DO NOT use it.

• If you do not have a copy of the tank

safety label pictured at right, please

contact your Clean Burn dealer for the

label, which is to be affixed directly on

your used oil supply tank.

WARNING

Fire and explosion hazards

To prevent serious injury or death:

ONLY place these listed substances in this used-oil supply tank:

• Used crankcase oil

• Used automatic transmission fluid

• Used hydraulic oil

• #2 fuel oil

Do NOT place flammable or corrosive substances such as gasoline, chlorinated oils, solvents, paint thinners, or any other unsafe substances in this used-oil supply tank.

Do NOT weld or allow open flame within

35 feet of this used-oil supply tank.

Tank installation MUST comply with NFPA

30 and 31 Fire Codes, including the following requirements:

• Tank must be listed to UL 80 or UL 142.

• Tank must be vented to outside.

• Emergency vent or explosion relief must be installed on tank.

• Inside fill allowed only with funnel including 1/4 turn-to-close fall valve, which must be closed after filling.

• All other openings must be plugged

• All oil lines must be constructed of copper, steel, or brass components. Do NOT use rubber or plastic tubing or piping, or any other inappropriate material.

Follow all instructions for tank installation in

Operator's Manual.

42366 Rev. 2

1-5

Operator's Manual: Model CB-140

For Your Safety... (continued)

Safety Labels

Following are the locations and descriptions of all labels on your Clean Burn furnace. The following illustrations show the location of labels on your furnace. Please note that some labels denote model number, model description, etc. while others contain important safety messages.

Each Safety Label contains an important safety message starting with a key word as discussed earlier in this section (e.g. ATTENTION, CAUTION, WARNING, DANGER). For your safety and the safe operation of your furnace, review all labels and heed all safety messages as printed on the labels.

If any labels on your Clean Burn furnace ever become worn, lost or painted over, please call your Clean

Burn dealer for free replacements.

42358

42030

42027

42318

42457

DATE

CODE

42367

42319

AIR OIL

I89083-A

CB-140 Furnace Cabinet Labels

Label Part # Description

42319 CB-140 Name Label

42367 Furnace Safety Warning Label (Multiple Messages - Fire/Shock/Burn Hazards)

42318 CB-140 UL Data Label

42358 UL Header Label

42457 Made in USA / Patent Pending Combination Label

42030 Furnace Electrical Shock Hazard Warning Label

(additional label may be included, not shown, on top near fan)

42068 Fan Entanglement Hazard Warning Label (not shown, on top near fan)

42027 Burn Hazard / Hazardous Voltage Warning Label

1-6

Operator's Manual: Model CB-140

For Your Safety... (continued)

CB-140 Furnace Cabinet Safety Labels

WARNING

Hazardous voltage.

To prevent serious injury, shut OFF main power to unit before removing cover.

Line voltage is present on most subbase terminals when power is ON.

If the furnace is not wired correctly.

fire, shock or damage could result.

ONLY a qualified electrician should wire this furnace.

ONLY use copper conductors.

42030 Rev. 2

WARNING

Burn Hazard.

Hazardous Voltage.

Burner may fire at any time.

Disconnect burner power cord before swinging open burner or clean-out door.

42027 Rev. 2

WARNING

Fire, explosion and burn hazards:

Maintain clearances from combustibles as listed on unit.

ONLY burn used crankcase oil, automatic transmission fluid, hydraulic oil, or #2 fuel oil. NEVER burn any other substances in this unit.

Hot gases and ash may be released when inspection port is opened.

Wear safety goggles and hand protection when opening inspection port.

Keep face away and open port slowly.

To avoid possible injury, death, or equipment damage, read and understand operator's manuals and all safety precautions before installing, operating, or servicing this equipment.

42367 Rev. 2

WARNING

Entanglement and cutting hazard.

Blower can start at any time.

Turn power OFF before servicing.

Do NOT operate without guard in place.

42068 Rev. 2

1-7

Operator's Manual: Model CB-140

For Your Safety... (continued)

CB-140 Furnace Cabinet Safety Labels

MODEL NO.

CB-140

NOMINAL INPUT RATING W/NO 2 FUEL OIL (BTU/HR)

LISTED FUELS

NO 2 OIL

USED CRANKCASE OIL

HYDRAULIC OIL

ATF

NO 4 OIL

NO 5 OIL

UL

INPUT

-GPH-

1.0

1.0

1.0

1.0

1.0

1.0

ULC

INPUT

-GPH-

1.0

1.0

1.0

N/A

N/A

N/A

ATOM AIR

PRESSURE

-PSIG-

14

14

14

16

14

16

140000

OIL

PRESSURE

-PSIG-

1.5

2.0

2.0

2.5

2.5

2.5

MAX. DISCHARGE

AIR TEMP (°F)

200

FLUE DRAFT

(INCHES OF W.C.)

TOP

CLEARANCE TO COMBUSTIBLE SURFACES: (INCHES)

12

CHIMNEY

18

FRONT

48

REAR

BOTTOM W/

AIR DIFFUSER

12

30

SIDE

BOTTOM W/O

AIR DIFFUSER

-0.06

12

60

FAN MOTOR HP.

OIL PUMP MOTOR HP.

BURNER MOTOR HP.

BURNER HEATER WATTS

DRAFT IND. (OPT) HP

AIR COMPRESS. (OPT) HP.

TOTAL CIRCUIT AMPACITY

MAXIMUM FUSE SIZE

POWER

1/4

1/20

1/10

280

1/10

1/3

VOLTS

120

120

120

120

120

120

AMPS

3.2

0.6

1.2

2.4

1.0

4.0

12.5

20

BURNER REQUIRES A MINIMUM AIR SOURCE OF 2 S.C.F.M. AT 25 P.S.I.

THIS APPLIANCE IS NOT TO BE USED WITH AIR FILTERS AND SHALL

INCORPORATE NO PROVISIONS FOR MOUNTING AIR FILTERS.

INSTALL AND USE ONLY IN ACCORDANCE WITH THE MFR'S INSTALLATION

AND OPERATING INSTRUCTIONS. FOR COMMERCIAL OR INDUSTRIAL USE

ONLY.

AUTHORITIES HAVING JURISDICTION SHOULD

BE CONSULTED PRIOR TO INSTALLATION.

42318 - R1

HZ

60

60

60

60

60

60

CLEAN BURN LLC

JANESVILLE, WISCONSIN (USA)

MH15393

LISTED

USED-OIL BURNING APPLIANCE USED OIL-FIRED FURNACE

USED OIL-FIRED BOILER

For use with Integral Primary Safety Control

NO.

13084

MULTI-OIL HEATING SYSTEM

INSTALL AND USE ONLY IN ACCORDANCE WITH THE

MFR’S INSTALLATION AND OPERATING INSTRUCTIONS.

FOR COMMERCIAL OR INDUSTRIAL USE ONLY.

AUTHORITIES HAVING JURISDICTION SHOULD

BE CONSULTED PRIOR TO INSTALLATION.

CERTIFIED TO ELECTRICAL AND FUEL BURNING REQUIREMENTS ONLY.

42358

1-8

Operator's Manual: Model CB-140

For Your Safety... (continued)

42000

42457

42520

42023

42519

LH SIDE VIEW

FRONT VIEW

RH SIDE VIEW

CB-125 Burner Labels

Label Part # Description

42000 Reset Warning Label

42004 Voltage / Moving Parts Warning Label

42005 Serviced-By Label

42023 Power / Pump Label

42235 Burner Warning Label

42457 Made In USA Label

42520 CB-140 Series Logo Label

42519 CB-140 Series Serial Number Plate

CB-125 Burner Safety Labels

42005

42004

42235

TOP VIEW

I89084-C

WARNING

Fire and explosion hazard.

Do NOT press reset button until you read and understand Reset

Procedures in Operator's Manual.

42000 Rev. 2

WARNING

Hazardous high voltage and moving parts hazard.

To avoid electric shock and injury from moving parts. turn power OFF before opening cover.

42004 Rev. 2

WARNING

Fire and explosion hazard.

This burner is to be installed ONLY on

Clean Burn products.

Only a qualified technician may maintain and service this burner.

42235 Rev. 2

1-9

Operator's Manual: Model CB-140

1-10

Operator's Manual: Model CB-140

SECTION 2: UNPACKING

Before assembling your furnace, you must accomplish the following activities described in this section:

• Removing the Shipping Crate

• Unpacking and Inspecting All Components

• Warranty Registration

Removing the Shipping Crate

NOTE: Remove the shipping crate prior to assembly and installation of the furnace. DO NOT use the crate as a platform for furnace installation!

1.

2.

Carefully remove the top boards of the shipping crate. Then remove the front, back, and side panels of the shipping crate.

Carefully lift the furnace off the shipping pallet with a fork lift.

ATTENTION: DO NOT attempt to slide the furnace cabinet out of the shipping crate--you may damage the furnace cabinet.

Unpacking and Inspecting All Components

Following is an itemized list of all components you should have received in your Clean Burn furnace shipment. Open all shipping containers and inspect all components according to the list. Immediately notify the freight company and your Clean Burn dealer in case of shipping damage or shortage(s). Keep all components together so you will have them as needed for furnace assembly and installation.

Furnace Component List

ONE SKID containing:

• Furnace cabinet

• Items packed inside furnace cabinet (combustion chamber):

NOTE:

• Louvers

• Furnace Accessories (items below in one box):

• Vacuum Gauge

• Check Valve and Check Valve Screen

• Wall

• Burner Oil Line and Air Line Components

• Assorted bolts/fittings for assembly/installation of furnace components

• Operator's Manual Literature Packet (includes Tank Safety Label)

ITEMS PACKED IN INDIVIDUAL BOXES:

• Burner

• Combustion Sleeve

• Metering Pump (includes Suction Oil Line Fittings Package)

NOTE: You may have received additional boxes or skids if you ordered optional accessories.

2-1

Operator's Manual: Model CB-140

Unpacking Items Packed Inside the Furnace

To unpack the items packed inside the furnace cabinet (in the combustion chamber), you will need to open the combustion chamber door.

1.

2.

3.

Remove the three nuts which hold the combustion chamber door closed. Set the nuts aside in a safe place for later re-installation after the combustion sleeve has been installed (Section 3).

Carefully swing the combustion chamber door open. Remove and inspect the components packed inside.

Leave the door unfastened (open) for assembly/installation procedures to be accomplished in the next section.

I89085

Figure 2A - Accessing the Combustion Chamber

Warranty Registration

For proper warranty registration, Clean Burn requires that you fill out the provided warranty registration card and return it within 30 days to:

CLEAN BURN WARRANTY REGISTRATION

Clean Burn, LLC.

4109 Capital Circle

Janesville, WI 53546

2-2

Operator's Manual: Model CB-140

SECTION 3: FURNACE ASSEMBLY

Understanding Assembly

Assembling your Clean Burn Furnace includes the following steps:

(1) Installing the Observation Port

(2) Installing the Louvers

(3) Installing the Combustion Sleeve

(4) Installing the Burner

(5) Installing the Connector Block, Oil Line Tubing, and Air Line Tubing

Clean Burn recommends that you review all assembly procedures before proceeding, paying careful attention to safety information statements.

Figure 3A on the following page provides a general overview of the furnace components and their proper assembly.

Required Tools and Materials

The following tools are required for furnace assembly and should be gathered before starting any procedures:

• 9/16" open-end wrench

• Medium flat-blade screwdriver

• Medium adjustable wrench

• 1/4" nut driver attachment for drill

• 5/16" nut driver attachment for drill

• Variable speed drill

3-1

Operator's Manual: Model CB-140

"ALL THREAD" RODS

BURNER

MOUNTING

BRACKET

4

4

1

OBSERVATION

PORT

2

LOUVERS CONNECTOR

BLOCK

5

I89086-A

3

COMBUSTION SLEEVE

INSTALLED IN CHAMBER

ON 2" X 2" BLOCKS

Complete assembly of the furnace according to the following list of activities as illustrated above:

(1) Installing the Observation Port

(2) Installing the Louvers

(3) Installing the Combustion Sleeve

(4) Installing the Burner

(5) Installing the Connector Block, Oil Line Tubing, and Air Line Tubing

NOTE: Corresponding procedures provided in order in this section.

Figure 3A - Overview of Furnace Assembly

3-2

Operator's Manual: Model CB-140

1.

2.

3.

4.

Installing the Observation Port

CAUTION: To prevent serious personal injury, the observation port must be correctly installed according to the following procedure. A properly installed observation port permits safe observation of the flame during furnace operation. Be sure to follow all safety procedures as outlined in this manual when observing the flame through the port.

Refer to Figure 3B.

Use a 1/4" nut driver to remove the two (2) self-tapping screws from the half-moon piece.

Position the half-moon piece and the faceplate on the observation port, and install the two self-tapping screws.

Open the port and make sure the faceplate moves and closes freely. If the faceplate hangs up, loosen the hex-head screws slightly until the faceplate closes correctly.

HALF-MOON

PIECE

FACE

PLATE

OBSERVATION

PORT

I89087

Figure 3B - Assembly of Observation Port

Installing the Air Outlet Louvers

Air Flow Discharge Installation Guidelines:

• It is very important to properly install the louvers to direct the flow of hot air away from the furnace

The air flow may be directed front, back, or to either side depending on how the louvers are installed.

• Note that each furnace is supplied with four (4) louvers which may be installed all in the same

direction OR the louvers may be split for partial air discharge out either side or front to back.

• When determining the placement of the air discharge louvers, you also need to consider the required

clearances from combustibles as stated in Section 4 of this manual.

• DO NOT restrict the flow of the hot air from the furnace by keeping the louvers completely closed, or the furnace may not operate properly.

3-3

Operator's Manual: Model CB-140

1.

2.

Installing the Air Outlet Louvers (continued)

ATTENTION: If the bottom clearance is less than 60 inches use a hot air diffuser as described under

Floor Mounting in Section 4.

3.

Refer to Figures 3C. Determine the desired air flow discharge direction. Note that each furnace is supplied with four (4) louvers.

Hold each louver against the base with the bend pointing down. Install the louvers in the desired direction(s) with the self-tapping screws provided. Holes are pre-drilled in the furnace base to accommodate installation of the louvers.

Rotate the louvers to help direct the hot air away from the furnace.

Figure 3C - Installing the Hot Air Discharge Louvers

I89088-A

CAUTION: The CB-140 are Unit Heater furnaces ONLY. DO NOT install ductwork on these furnaces.

3-4

Operator's Manual: Model CB-140

2.

3.

Installing the Combustion Sleeve

Installing the Combustion Sleeve Inside the Combustion Chamber

ATTENTION: DO NOT fire your furnace without the Combustion Sleeve in place, or poor flame retention will occur. Handle the Combustion Sleeve carefully to avoid damage.

1.

4.

Refer to Figure 3A and 3D to review the proper position of the Combustion Sleeve and 2" x 2" mounting Blocks.

Swing open the clean-out door on the front of the furnace to gain access to the combustion chamber.

Refer to Figure 3D. Place the two (2) soft fiber board blocks (2" x 2" x 8") on the bottom of the combustion chamber against the indicator tabs. The notch in the support blocks should fit over the front flue plate.

Gently set the Combustion Sleeve on top of the two Blocks. The combustion sleeve needs to seat firmly against the door insulation for proper combustion. Carefully position the Combustion

Sleeve on the blocks so that it extends out slightly beyond the door opening. The door will push the Combustion Sleeve in place as it is closed.

I89090

SUPPORT BLOCK

LOCATION INDICATOR TAB

COMBUSTION SLEEVE

TIGHT AGAINST FRONT

DOOR INSULATION

NOTCH IN SUPPORT BLOCK

OVER FRONT FLUE PLATE

Figure 3D - Installing the Combustion Sleeve

Closing the Furnace Door

1.

2.

3.

After the Combustion Sleeve has been installed, close the furnace clean-out door.

If necessary, loosen the door hinges to allow the door to seal tight.

Tighten the three (3) lock-down nuts until all are snug.

3-5

Operator's Manual: Model CB-140

Installing the Burner

Checking the Burner Nozzle and Electrodes

NOTE: The burner nozzle is factory installed. Both furnace models use a Delavan 9-5 nozzle. The nozzle size is indicated on the nozzle as shown in Figure 3E. Refer also to Appendix A at the back of the manual for additional specifications/instructions on the burner nozzle.

ATTENTION: Check the electrode settings as specified in Figure 3E. The electrode settings must be correct for your burner to operate properly.

BURNER NOZZLE

SIDE VIEW - AA

NOZZLE IS STAMPED

EITHER 9-5 OR -5 ON

FLAT OF NOZZLE HEAD

3/16" GAP BETWEEN

ELECTRODES & NOZZLE

CRITICAL DIMENSION:

NOZZLE MUST BE 1/8"

AHEAD OF THE DISK.

NOZZLE MUST NOT BE

BEHIND THE DISK.

3X

SIDE VIEW - BB

VIE

W - BB

VIE

W - AA

1/8"

SPARK

GAP

Figure 3E - Burner Nozzle and Electrode Specifications

I88340-B

3-6

Operator's Manual: Model CB-140

Installing the Burner (continued)

Mounting the Burner on the Hinge Bracket

ATTENTION: Burner tube components (e.g. electrodes and retention head) are factory set. Handle the burner with extreme care so that burner components are not damaged.

1.

2.

3.

4.

Remove the nut from the mounting flange of the furnace cabinet, and set it aside for later use.

Lift the burner into position so that it is mounted on the hinge bracket on the furnace cabinet.

Carefully swing the burner so the retention head enters the throat of the furnace.

Check the clearance between the retention head and the furnace throat. There must be at least

1/8" clearance, so the retention head is not "bumped" as you swing the burner into firing

position.

NOTE: If the retention head "bumps" the furnace throat, adjust the hinge bracket bolts as follows:

• While supporting the burner, slightly loosen the two (2) hinge bracket bolts.

• Carefully re-position the burner so it swings freely into its firing position.

• With the burner in its firing position, re-tighten the hinge bracket bolts.

3-7

Operator's Manual: Model CB-140

Installing the Connector Block, Oil Line Tubing, and Air Line Tubing

ATTENTION: DO NOT use teflon tape on any fittings. Teflon tape residues will plug vital burner components and void your warranty.

Installing the Connector Block on the Furnace Door

1.

2.

3.

Refer to Figure 3F.

Use the two (2) bolts to install the aluminum connector block onto the furnace door.

Remove and discard the red caps and plugs from the fittings and ports on the connector block. DO NOT allow any dirt/debris to enter these components during furnace assembly.

ATTENTION: The connector block includes an accumulator. The accumulator functions like a shock absorber on the oil line to prevent pressure buildup and protect vital burner components. It is important that the connector block is installed as shown so that the accumulator is in a vertical position to prevent sediment from settling in the accumulator. Never operate your furnace without the

connector block and accumulator properly installed on the furnace, or damage may occur to vital burner components.

OIL FITTING

ON BURNER

CONNECTOR BLOCK

OIL LINE

AIR OIL

SWIVEL

ASSEMBLY

Installing the Oil Line Tubing

4.

5.

6.

ATTENTION: DO NOT disassemble the compression fitting from the swivel fitting. To prevent leaks, the NPT threads of the compression fitting have been sealed with hydraulic sealant during assembly of the fittings at the factory.

1.

2.

3.

Remove and discard the red caps from the oil line tubing.

Install the oil line tubing into the swival fitting on the connector block.

Slightly bend the tubing as shown in Figure 3F, if required, to "line up" the oil line with the oil line fitting on the burner. If necessary use a wrench to rotate the oil line fitting on the burner to line up the

CONNECTOR

BLOCK

SIDE VIEW OF FURNACE

SHOWING OIL LINE INSTALLED

Figure 3F - Installation of Connector

Block and Oil Line

I89089-A tubing.

If necessary, use a tubing cutter to cut the tubing to the proper length.

Make sure that the curl in the oil line is positioned so that the burner is able to swing open.

Install the oil line tubing and tighten the nuts on the compression fittings. DO NOT overtighten these fittings to avoid damaging the ferrules.

3-8

Operator's Manual: Model CB-140

Installing the Connector Block, Oil Line Tubing, and Air Line Tubing

(continued)

Installing the Air Line Tubing

7.

8.

9.

Remove and discard the red caps from the air line tubing.

Push the air line tubing into the push fitting on the connector block until the tubing bottoms out in the fitting.

Repeat this procedure to connect the air line tubing to the air line fitting on the the burner.

Locking the Burner into Firing Position

10. Swing the burner into firing position.

11. Install and tighten the lock-down nut on the mounting plate bolt to secure the burner in its firing position.

12. Plug the burner electrical cable into the receptacle on the top of the burner housing.

13. Tighten the locking ring to secure the electrical cable.

NOTE: Be sure to properly align the plug when plugging it into the receptacle. See Fig 3G.

CONNECTOR PLUG

KEY IN PLUG

MUST ALIGN

WITH SLOT IN

RECEPTACLE

RECEPTACLE ON

TOP OF BURNER

I88641-B

Figure 3G - Detail of Burner Electric Receptacle

NOTE: Your furnace is now assembled and ready for installation. Install the furnace as soon as possible so the burner and/or fan are not "bumped" or damaged. If you must store the furnace for a period of time before installation, make sure it is located in a safe, secure area.

3-9

Operator's Manual: Model CB-140

3-10

Operator's Manual: Model CB-140

SECTION 4: FURNACE INSTALLATION

Understanding Installation

Installing your Clean Burn furnace is a multi-step process which includes:

(1) Selecting a Location

(2) Mounting the Furnace

(3) Oil Tank Specifications (review)

(4) Installing the Metering Pump

(5) Wiring the Furnace and Pump

(6) Installing the Oil Lines

(7) Installing the Compressed Air Line

(8) Installing the Stack

(9) Installing the Wall Thermostat

(10) Inspecting the Installation

Clean Burn recommends that you review all procedures before beginning installation, paying careful attention to safety information statements. Figure 4A and 4B provide a general overview of a typical furnace installation and should be reviewed closely before proceeding.

WARNING: The installation, operation, and maintenance of this equipment in the U.S. must be accomplished by qualified personnel and in compliance with the specifications in the

Clean Burn Operator's Manual and with all national, state, and local codes or authorities having jurisdiction over environmental control, building inspection and fuel, fire and electrical safety and the following standards of the National Fire Protection Association.

NFPA 30 Flammable and Combustible Liquids Code

NFPA 30A Automotive and Marine Service Station Code

NFPA 31 Standard for the Installation of Oil Burning Equipment

NFPA 211 Chimneys, Fireplaces, Vents and Solid Fuel Burning Appliances

NFPA88A Parking Structures

NFPA 88B Repair Garages

NFPA 70 National Electrical Code

Likewise, the installation, operation, and maintenance of this equipment in Canada is to be accomplished by qualified personnel and in compliance with the specifications in the Clean Burn

Operator's Manual and in accordance with the regulation of authorities having jurisdiction and the following CSA Standards:

B139 Installation Code for Oil Burning Equipment

B140.0 General Requirements for Oil Burning Equipment

C22.1 Canadian Electrical Code, Part 1

Failure to comply with these standards and requirements may result in equipment damage, fire, explosion, personal injury and/or death.

WARNING: Improper installation can adversely affect the proper, safe operation of your furnace. It is critical that your furnace installer reads and follows the instructions provided in this manual.

4-1

Operator's Manual: Model CB-140

WARNING: When installing your furnace, adhere to the minimum clearances from combustible surfaces as stated in Section

4. These clearances also provide adequate space for servicing. Failure to maintain proper clearances may result in fire, explosion, personal injury, or death.

10 FT.

1/4" HOLE FOR

SETTING DRAFT.

ADJUST BAROMETRIC

DAMPER FOR -.02" W.C.

DRAFT OVER FIRE

AIR OIL

COMPRESSED AIR LINE

PRESSURE OIL LINE

24 VOLT WALL

THERMOSTAT

ELECTRIC SERVICE

EMERGENCY

VENT VALVE

SUCTION

OIL LINE

BALL VALVE

OIL

STORAGE

TANK

INSTALL CHECK VALVE WITH

ARROW POINTING UP

MINIMUM OF 12" FROM CHECK

VALVE TO BOTTOM OF TANK

12"

CLEANOUT

WITH DRAIN

Figure 4A - Typical CB-140 Furnace Installation

4-2

VENT

CAP

I89091-A

Operator's Manual: Model CB-140

Selecting a Location

Guidelines for Selecting a Location

The location you select for your furnace must allow the following:

• Unobstructed, even heat distribution.

• Safe, easy access for servicing.

• Unobstructed passage for shop vehicles and equipment.

• Proper clearances from combustibles. Verify according to your local safety codes.

• Adequate combustion air per local codes.

• Proper stack installation.

WARNING: Adhere to the following minimum clearances from combustible surfaces and to provide adequate clearance for servicing (also refer to Figure 4B for visual reference); failure to maintain proper clearances may result in fire, explosion, personal injury or death.

I89065-A

18 "

CHIMNEY

CONNECTOR

12 "

TOP

12 "

REAR

MINIMUM CLEARANCES

CB-140 FURNACE

18 "

SIDE

48 "

FRONT

• 96 " BOTTOM - IF THERE IS POTENTIAL FOR GASOLINE FUMES

• 60 " BOTTOM - IF THERE IS NO POTENTIAL FOR GASOLINE FUMES

• 30 " BOTTOM - IF THERE IS NO POTENTIAL FOR GASOLINE FUMES

AND A HOT AIR OUTLET DIFFUSER IS USED

Figure 4B - Clearances from Combustibles

CLEARANCES FOR INSTALLATION

• TOP (of furnace) .............................. 12"

• FRONT (burner) ............................... 48"

• SIDE (with or without stack) ............. 12"

• CHIMNEY CONNECTOR ................ 18"

• REAR .............................................12"

• BOTTOM (with air diffuser) .............. 30"

• BOTTOM (without air diffuser) ......... 60"

NOTE: See Appendix A for furnace cabinet dimensions.

WARNING: Codes may require that your furnace is mounted a minimum of eight (8) feet off the ground when installing the furnace in a repair facility. Refer to NFPA-88B, Standard for Repair Garages,

Chapter 3, Hazards, Sec. 3-2.3.1.

4-3

Operator's Manual: Model CB-140

Mounting the Furnace

After selecting a safe and appropriate location for your furnace, construct the mounting system as required by the location and the following specifications.

1.

2.

3.

Ceiling Mounting

WARNING: To prevent serious personal injury, ensure that your furnace mounting system can safely bear the suspended weight of the furnace and allow safe servicing of furnace components.

Use adequately sized square tubing or angle iron bridged across sufficient structural members to safely support the furnace.

Refer to Figure 4C.

Follow the instructions as provided in the diagram.

Use a spirit level to make sure the cabinet is level side to side and front to back.

CEILING MOUNTING SYSTEM

WARNING! USE MINIMUM 2-1/2 X 2-1/2 X 1/4" ANGLE

IRON BEAMS, BRIDGED ACROSS SUFFICIENT

STRUCTURAL MEMBERS TO SAFELY

SUPPORT FURNACE

ANGLE IRON SUPPORT

BEAMS

DOUBLE

NUTS

(4) 1/2" or 5/8 "ALL THREAD"

SUPPORT RODS

INSERT SUPPORT RODS THROUGH

THE FURNACE CABINET AND

INSTALL A WASHER AND DOUBLE

NUTS ON THE BOTTOM

A NUT AND WASHER CAN BE

PLACED ABOVE THE FURNACE

CABINET TO INCREASE STABILITY

WARNING! MAKE SURE TO USE

DOUBLE NUTS ON BOTH TOP

AND BOTTOM OF THE

"ALL THREAD" RODS

AIR OIL

Figure 4C - Ceiling Mounting Installation Overview

4-4

I89092-A

1.

2.

3.

Operator's Manual: Model CB-140

Mounting the Furnace (continued)

Raised Platform Mounting

WARNING: To prevent serious personal injury, make sure the platform is designed to safely bear the weight of the furnace and allow safe servicing of furnace components. The platform must be constructed of non-combustible materials

(e.g. steel) and must be securely anchored to an adjacent wall.

Refer to Figure 4D.

Follow the instructions as provided in the diagram.

Use a spirit level to make sure the cabinet is level side to side and front to back.

AIR OIL

I89093-A

Figure 4D - Furnace Installed on

Raised Platform

1.

2.

Floor Mounting

WARNING: To prevent serious personal injury, make sure the floor can safely bear the weight of the furnace.

CAUTION: The minimum distance allowed from the floor to the base of the unit is 60 inches.

If the clearance is less than 60 inches to the base of the unit a hot air diffuser, or hood, must be used to direct the hot air away from the furnace.

CB-140 hot air diffuser Clean Burn part #90244

Refer to Figure 4E.

Use a spirit level to make sure the cabinet is level side to side and front to back.

WARNING: The support stand must be constructed of non-combustible materials (e.g. steel) and must be securely anchored to the floor.

4-5

Operator's Manual: Model CB-140

Mounting the Furnace (continued)

Floor Mounting (Continued)

AIR OIL

HOT AIR

OUTLET

DIFFUSER

I89094-A

Figure 4E - Furnace Installed on a Mezanine With a Hot Air Outlet Diffuser

4-6

Operator's Manual: Model CB-140

Oil Tank Installation Specifications

Ensure that your tank installation adheres to the following safety guidelines as stated here and in

Section 1 of this manual.

The tank safety label (shown at right) also summarizes these important specifications for tank installation and usage. If you do not have a copy of this label, please contact your Clean Burn dealer for a copy, which is to be affixed directly to your used oil supply tank.

The tank installation must meet all

national and local codes. Consult your local authorities for more information as necessary.

The tank must be listed to UL 80, UL 142, or equivalent standard.

Use a minimum 250-gallon tank. DO NOT use a 55-gallon drum as a substitute for an appropriate tank. The tank must be large enough to allow water, sludge, etc. to settle out of the used oil.

Single wall tanks should have a manual shut-

off type valve on the side of the tank to allow the water, sludge, etc. to be drained from the bottom of the tank.

All unused openings in the tank must be

plugged or capped off.

For optimal system functioning, Clean Burn

Recommends inside tank installations as shown in Figures 4A, 4F, and 4J.

Some codes require the tank to be vented to

the outside of the building using iron or steel pipe and fittings with an approved vent cap.

Carefully review the oil tank and pump installation details as shown in Figures

4A, 4F, and 4J. Pertinent information also supplied with the metering pump and oil line installation procedures (following in Sec. 4).

Ensure that the oil supply tank is properly

maintained; refer to Section 9 in this manual for related procedures.

WARNING

Fire and explosion hazards

To prevent serious injury or death:

ONLY place these listed substances in this used-oil supply tank:

• Used crankcase oil

• Used automatic transmission fluid

• Used hydraulic oil

• #2 fuel oil

Do NOT place flammable or corrosive substances such as gasoline, chlorinated oils, solvents, paint thinners, or any other unsafe substances in this used-oil supply tank.

Do NOT weld or allow open flame within

35 feet of this used-oil supply tank.

Tank installation MUST comply with NFPA

30 and 31 Fire Codes, including the following requirements:

• Tank must be listed to UL 80 or UL 142.

• Tank must be vented to outside.

• Emergency vent or explosion relief must be installed on tank.

• Inside fill allowed only with funnel including 1/4 turn-to-close fall valve, which must be closed after filling.

• All other openings must be plugged

• All oil lines must be constructed of copper, steel, or brass components. Do NOT use rubber or plastic tubing or piping, or any other inappropriate material.

Follow all instructions for tank installation in

Operator's Manual.

42366 Rev. 2

ATTENTION: For outside tank installations and/or tanks larger than 500 gallons, contact your local Clean Burn Distributor for installation recommendations and specifications.

4-7

Operator's Manual: Model CB-140

Oil Tank Installation Specifications (continued)

TANK VENT KITS AVAILABLE FROM CLEAN BURN

Example Oil Tank Install Diagram

PRESSURE

LINE

PRESSURE

RELIEF OIL

LINE BACK TO

THE TANK

MUSHROOM

CAP VENT

STEEL PIPE

(USER SUPPLIED)

FUNNEL WITH

BALL VALVE

EMERGENCY

VENT

INLE

GAU

GE

PUMP

SUCTION LINE

ASSEMBLY

CHECK

VALVE

FILTER

SCREEN

42366

OIL ST

ORA

GE T

ANK

CLEAN-OUT

(TANK DRAIN)

I88669-H

Figure 4F - Typical Metering Pump Installation with Inside Tank

Installing the Tank Vent and Emergency Vent

Some codes require that you install a tank vent (to the outside) and an emergency vent for your tank as shown in Figure 4F. Tank Vent Kits are available from Clean Burn; contact your local Clean Burn dealer to order. Be sure to check your local codes for any additional tank installation requirements, and adhere to the following installation guidelines:

• Install a length of minimum 2" steel pipe (user-supplied) terminating outside with a proper vent cap as shown in Figure 4F. Consult local codes for information and requirements concerning the proper venting of oil storage tanks.

• Install an emergency vent as shown in Figure 4F. Contact your tank manufacturer for information concerning the proper emergency vent for your tank.

4-8

Operator's Manual: Model CB-140

1.

2.

Installing the Metering Pump

Preparing for Installation

Before starting installation of the metering pump, review Figures 4G, 4H, and 4I to become familiar with the metering pump components. You will also need to accomplish the following activities:

• Verify that you have the proper metering pump for your furnace (note the specific gear motor part numbers shown in Figure 4H).

• Gather all required tools and materials as needed for installation; as indicated in the following procedures, some materials (e.g. fittings, tubing) are to be user-supplied.

• Standard mounting is vertical mounting on a wall; this pump installation is recommended.

Alternate mounting is horizontal mounting on a bracket. Be sure to carefully follow the appropriate procedures/diagrams for pump mounting.

• For optimal metering pump functioning, mount the pump at a distance from the oil tank that will comply with the following requirements:

• The suction oil line may NOT exceed 6 feet TOTAL vertical lift AND 4 feet TOTAL

horizontal lift.

Standard Mounting: Vertical Positioning

Refer to Figures 4G, 4H, and 4I. Note that the metering pump is shipped with the pump head already positioned for vertical wall mounting.

Use the appropriate type of bolts and washers (user-supplied) to securely mount the metering pump to the appropriate wall in your building at a distance from the tank that complies with the suction oil line requirements.

I88727-B

1/8" OUTLET

GA

UGE

INLE

T

RELIEF

ROTA

TION

INLET BLEEDER VALVE

Figure 4G - Vertical Mounting of the Metering Pump

4-9

Operator's Manual: Model CB-140

METERING PUMP COMPONENT DETAIL

#

10

11

12

13

14

15

16

17

7

8

5

6

9

1

2

3

4

23

24

25

26

27

18

19

20

21

22

28

29

PART # DESCRIPTION

32429

32137

32142

32062

32443

32141

32140

32139

32442

32021

32061

32445

32475

32467

32210

32336

32123

32127

32430

32446

33363 CAPACITOR - GEARMOTOR see chart GEARMOTOR

11322 MOUNT - METER PUMP

32037 1/8 NPT X 1/4 TUBE COMPRESSION FITTING

N/A

N/A

N/A

N/A

32526

1/4 COPPER OR ALUM. TUBING

3/8 OR 1/2 TUBE FLARE NUT

3/8 OR 1/2 COPPER OR ALUM. TUBING

1/8 M NPT X 3/8 OR 1/2 FLARE

MINI BALL VALVE 1/8 MNPT X 1/8 FNPT

METER PUMP

1/4" X 3" NIPPLE

1/4" STREET ELBOW

1/4" X 3/4" BRASS BUSHING

VACUUM GAUGE

CANISTER FILTER- LENZ

1/2" x 3/4" BUSHING, BRASS

1/2" X 5" NIPPLE

1/2" STREET TEE, BRASS

1/2" HEX NIPPLE

1/2" BALL VALVE

1/4" NPT x 1/4" TUBING FITTING

1/4" x 1/2" BUSHING

1/2" NPT x 1/2" TUBING FLARE ADAPTER

1/2" LONG NUT

1/2" NPT x 1/2" TUBING SLIP ADAPTER

2" x 1/2" x 1/2" NPT DUPLEX HEX BUSHING

3/4" CHECK VALVE

3/4" CHECK VALVE SCREEN

1/2" PIPE CAP 21

17

18

19

20

16

29

23

24

N I

13

SUPPLY

TO BURNER

6

7

8

10

OUT

9

11

GA

UGE

A2R

RELIEF

A-7720

ROTA

TION

14

15

RETURN

TO TANK

5

4

12

3

1

2

PACKAGED WITH

CLEAN BURN

EQUIPMENT

22

25

26

SINGLE PIECE OF

COPPER TUBING

(USER SUPPLIED)

24

23

16

27

28

PACKAGED WITH

CLEAN BURN

EQUIPMENT

Figure 4H - Metering Pump Component Detail

4-10

CLEAN BURN

MODEL

CB 140

CB-1750

CB-2500

CB-3250

CB-3500

CB-5000

CB-200-CTB

CB-350-CTB

CB-500-CTB

GEARMOTOR

PART #

33291

33353

33354

33572

33355

33356

33507

33295

33558

I89110-A

Operator's Manual: Model CB-140

1.

2.

3.

4.

5.

Installing the Metering Pump (continued)

Alternate Mounting: Horizontal Positioning

ATTENTION: If the metering pump is to be mounted horizontally or on a bracket as shown in

Figure 4I, the pump head must be rotated counterclockwise so that it is aligned in a horizontal position.

The gauge arrow on the pump head must point up, or the pump will not prime.

Refer to Figures 4H and 4I.

Remove the two pump mounting bolts. The coupling is keyed and does not have set screws.

Rotate the pump head 180 degrees to the horizontal position as shown in Figure 4I.

Reinstall and tighten the two pump mounting bolts.

Use the appropriate type of bolts and washers (user-supplied) to securely mount the metering pump to the mounting bracket, which is to be installed on the appropriate wall in your building at a distance from the tank that complies with the suction oil line requirements.

ATTENTION !

THE PUMP HEAD MUST BE POSITIONED SO THE GAUGE

ARROW POINTS UP OR THE PUMP WILL NOT PRIME

GAUGE RELIEF

A2RA-7720

INLET

ROTATION

GAUGE

A2RA-7720

INLET

RELIEF

ROTATION

GAUGE

A2RA-7720

INLET

RELIEF

ROTATION

GAUGE RELIEF

A2RA-7720

INLET

ROTATION

INLET

RECOMMENDED SETUP

PUMP IS MOUNTED

LEFT ON WALL

I88708-B

INLET

ALTERNATE MOUNTING

(NOT RECOMMENDED)

BLEED VALVE IS NOW CLOSE

TO THE WALL MAKING THE

BLEEDING DIFFICULT

INLET

NON-STANDARD SETUP

PUMP HEAD HAS BEEN

ROTATED 90° CCW FOR

HORIZONTAL MOUNTING

(THE 1/4" STREET ELBOW AND

1/4" X 3" NIPPLE CHANGE PLACES

IN THE PLUMBING SEQUENCE)

Figure 4I - Proper Positioning of Metering Pump Head

4-11

Operator's Manual: Model CB-140

Wiring the Furnace and Pump

WARNING: To avoid electrical shock, make sure that power to the furnace is turned OFF before connecting any wires. A licensed electrician should install all wiring to your furnace.

All wiring must be in accordance with the National Uniform Electrical Code and local codes.

Properly size all wires and use electrical conduit for all electrical lines.

Wiring your furnace involves the installation of two lines:

1. A dedicated electrical line to the furnace

2. A pump electrical circuit from the furnace to the metering pump

Necessary wiring specifications are provided in this section and in the Wiring Schematics located in

Appendix B at the back of the manual.

Wiring to the Furnace

1. Install a dedicated electrical circuit to the electrical junction box on the furnace.

Refer to NFPA-70 for wire size and distances.

2.

WARNING: DO NOT tie into an existing circuit, or electrical overload may occur.

Wire the furnace according to the Wiring Schematic in Appendix B. Ensure that the ground

wire is attached to the GREEN ground screw in the furnace junction box.

3.

4.

Refer to the following chart and check for correct voltage at the furnace.

ATTENTION: Incorrect voltage will severely damage the fan motor/furnace components.

DO NOT operate your furnace on any non-specification power system.

Model Voltage

CB-140 110/120

Breaker Size

20 amps*

Circuit Hertz

Dedicated 60

*NOTE: Breaker size with optional equipment is 20 amps. When installing any optional equipment (e.g. air compressor or draft inducer), you do not need to "upgrade" the breaker size.

The breaker size listed above should be sufficient. Make sure a qualified electrician properly sizes and installs this electrical circuit. Refer to NFPA-70 for wire size and distances.

DO NOT turn on main power until instructed to do so.

Wiring to the Metering Pump

1.

WARNING: DO NOT wire the pump directly into your building's electrical system. The pump must be activated (receive power) from the burner via the pump electrical circuit. DO

NOT wire the pump directly to a wall outlet so that it runs continuously; this will seriously damage your metering pump and / or furnace and may result in a fire or explosion hazard.

Install the pump electrical circuit from the furnace to the metering pump location.

2. Wire the pump circuit according to the Metering Pump Wiring Schematic in Appendix B at the back of this manual.

4-12

Operator's Manual: Model CB-140

Installing the Suction Oil Line Components

ATTENTION: It is critical that you adhere to the following specifications for suction oil line

installation (oil line from the tank to the pump). If these specifications are not met, the metering pump will not function correctly and the burner will shut down on reset. The majority of service problems with the metering pump are caused by leaks at fittings in the suction oil line; these problems are eliminated by ensuring a 100% airtight suction oil line which slants up to the pump.

• All suction oil line components must be installed as shown in Figures 4H and 4J. Suction

line size is 1/2" diameter. Proper installation allows the suction oil line to be filled with used oil during initial priming.

1.

• The suction oil line may NOT exceed 6 feet TOTAL vertical lift and 4 feet total horizontal

lift (which equals 6.0” hg maximum operating vacuum). To determine if your suction oil line will meet this specification for maximum operating vacuum, base the calculation for your installation on the following equivalents:

(1) vertical foot = 0.75” hg (vacuum)

(4) horizontal feet = 0.75” hg (vacuum)

NOTE: ALSO ADD 0.75" hg to the final sum to account for every oil filter, shut-off valve, and check valve on the suction side of the pump assembly.

Sample calculation: (6) vertical feet x 0.75" = 4.50" hg AND (4) horizontal feet = 0.75" hg

4.50" hg + 0.75" hg + 0.75" hg = 6.00 " hg vacuum

• The metering pump must be installed with a 3/4" check valve at the end of the suction oil line, or the pump will not maintain its prime.

• Use Permatex #2 non-hardening gasket sealer on every threaded fitting. DO NOT use teflon tape or teflon pipe dope compounds; the teflon can flake off and cause damage to the pump head.

• The suction oil line must be 100% airtight for proper system functioning. Use only high-quality flare fittings for the copper tubing. DO NOT use compression fittings.

DO NOT use any steel pipe unions. DO NOT use sweat copper pipe. These types of fittings cause air leaks in the suction oil line and will require re-installation.

• The suction oil line must slant up to the pump; any high spots will trap air and will not allow the pump to prime.

Assemble the suction oil line fittings (from the metering pump to the canister filter):

a. Refer to Figure 4H for a detailed look at the metering pump components and fittings.

b. Remove the plug from the 1/4" inlet port of the pump.

c. Install the 1/4" x 3" brass nipple into the 1/4" inlet port on the pump.

d. Install the 1/4" brass street elbow onto the 3" brass nipple; turn the fitting onto the nipple until it is tight and faces away from the pump mounting plate.

e. Prepare the canister filter for installation:

• Install the 3/4" x 1/4" brass hex bushing into the outlet port of the canister filter. Check the

direction of the arrow for the proper flow.

• Install the 3/4" x 1/2" brass bushing into the inlet port of the canister filter.

4-13

Operator's Manual: Model CB-140

Installing the Suction Oil Line Components (continued)

(1.) (e.)Prepare the canister filter for installation (continued):

• Remove the plug from one of the 1/8" gauge ports in the canister filter and install the vacuum gauge. Seal the threads of the gauge with Permatex #2 non-hardening gasket sealer.

• Install the 1/2" threaded pipe adapter into one side of the 1/2" ball valve.

• Install the 1/2" MPT x 1/2" flare adapter into the other side of the ball valve.

• Install this assembly into one side of the 1/2" brass tee.

• Install the assembled 1/2" tee into the 3/4" x 1/2" brass bushing, which is installed in the inlet port of the canister filter. Make sure that the 1/2" flare adapter is pointing down.

• Install the canister filter assembly onto the 1/4" brass street elbow as shown in Figure 4H.

The canister filter must be installed with the arrow pointing towards the pump (direction of oil flow).

• Install the 1/2" x 5" brass nipple into the top side of the 1/2" brass tee assembly.

• Loosely install the 1/2" brass cap onto this nipple. DO NOT tighten the cap at this time.

AIR OIL

COMPRESSED AIR LINE

PRESSURE OIL LINE

FUNNEL

WITH BALL VALVE

EMERGENCY

VENT RELIEF

BALL VALVE

RADIAL BEND MADE

WITH TUBING BENDER

SUCTION

LINE

CANISTER FILTER

IN SUCTION LINE

VENT

CAP

CLEAN-OUT

CONTINUOUS PIECE

OF COPPER TUBING

INSIDE TANK: 1/2" O.D.

INSTALL SLIP FITTING

TO HOLD TUBING

IN PLACE

CHECK VALVE

CHECK VALVE SCREEN

CHECK VALVE IS MINIMUM 12 INCHES OFF

TANK BOTTOM TO CREATE SLUDGE TRAP

1 FT.

Figure 4J - Oil Line Installation Overview

4-14

I89095-A

2.

Operator's Manual: Model CB-140

Install the suction oil line (from the the tank to the canister filter):

a. Refer to Figures 4H and 4J.

b. Prepare a piece of 1/2" O.D. copper tubing (user-supplied) which will function as the pick-up line from the tank to the canister filter. This copper tubing must have the following specifications:

• The tube must be one continuous piece of 1/2" O.D. copper tubing with no kinks or fittings.

• The tube is to slant up from the tank to the pump with no loops or high points to trap air.

c. Locate the 2" MPT x 1/2" FPT x 1/2" FPT duplex, slip-thru hex bushing (which will eventually be installed into one of the 2" openings on the tank). Note that the fitting is marked "S" for suction and

"R" for return.

d. Install the 1/2" MPT x 1/2" slip fitting into the "S" side of the 2" duplex slip-thru hex bushing e. Install the 1/4" MPT x 1/4" compression fitting into the 1/2" x 1/4" brass bushing.

f. Install the 1/2" x 1/4" brass bushing into the "R" side of the 2" duplex slip-thru hex bushing g. Measure the height of the oil tank (from the bottom of the tank, NOT the floor) to the 2" opening that you are going to use for the supply oil line. Deduct 12" (305mm) from this measurement and transfer this new measurement onto the 1/2" O.D. copper tubing.

h. Remove the locking nut and ferrel sleeve connector from the 1/2" slip fitting, and slide them over the copper tubing.

i. Slide the 1/2" O.D. copper tubing through the 1/2" slip fitting, which is installed in the "S" side of the 2" hex bushing.

j. Install the screen into one side of the 3/4" check valve (making sure the arrow is pointing away from the screen assembly).

k. Install the 3/4" x 1/2" brass bushing into the 3/4" check valve.

l. Install the 1/2" MPT x 1/2" flare adapter into the 3/4" x 1/2" brass bushing.

m. Slide the 1/2" flare nut over the end of the 1/2" copper tubing, and flare the end of the tubing

NOTE: Use a high-quality flaring tool (such as a Ridgid Flaring Tool) to ensure that all flares are made properly (i.e. so they will be 100% airtight).

n. Install the flared oil line and nut onto the assembled check valve/screen and tighten.

o. Pick up the assembled oil line, and carefully guide the end of the tubing with the check valve through the 2" tank opening.

p. Apply Permatex #2 non-hardening gasket sealer (or equivalent) to the threads of the 2" duplex slipthru tank bushing, and tighten this fitting into the tank.

q. Pull the 1/2" copper tubing back up through the slip fitting until you see the mark that you put on the tubing earlier. Holding the tubing with one hand, push the ferrel sleeve connector and locking nut down the tubing, then tighten onto the 1/2" slip fitting. The oil line is now installed in the correct position off of the bottom of the tank.

r. Carefully bend the oil line up to the canister filter; use a spring bender over the oil line while bending the tubing to prevent kinks in the oil line. Allowing for the flare nut, cut off the excess tubing s. Install the 1/2" flare nut onto the tubing, and flare the end of the tubing.

t. Install the end of the tubing with the flare nut onto the 1/2" flare adapter (on the ball valve assembly at the canister filter).

u. Install a vent from the tank to the outside of the building according to code. The tank must be properly vented to allow air to enter the tank as oil is pumped out and to safely vent fumes to the outside. See Figure 4J.

v. Install plugs in all other tank openings as required by code.

w. Inspect the installation. For proper suction oil line operation, make sure all components are installed and positioned as specified in this manual.

4-15

Operator's Manual: Model CB-140

Installing the Pressure Relief Oil Line Back to the Tank

ATTENTION: It is critical that you adhere to the following specifications for plumbing the pressure relief back to the tank.

The metering pump requires the installation of a pressure relief oil line back to the tank that you are pulling oil from as shown in Figures 4H, 4J, and 4K.

• The pressure relief will open and relieve pressure if there is a restriction in the pressure oil line, clogged nozzle, etc.

Be sure to use Permatex #2 non-hardening gasket sealer to seal every threaded fitting. DO NOT use teflon tape or teflon pipe dope compounds.

1.

2.

3.

4.

Refer to Figure 4K.

Remove the plug from the relief port on top of the metering pump head.

Install the 1/8 NPT x 1/4 tube compression fitting in the relief port on top of the metering pump head.

Install 1/4" O.D. copper tubing (user-supplied) from the pressure relief port back to the oil tank.

Refer to Figure 4J as needed.

# PART # DESCRIPTION

1 32475

2 32526

METERING PUMP HEAD (7720)

MINI BALL VALVE 1/8 MNPT X 1/8 FNPT

3 INSTALLER SUPPLIED 1/8 MNPT X 3/8 OR 1/2 FLARE

4 INSTALLER SUPPLIED 3/8 OR 1/2 COPPER OR ALUM. TUBING

5 INSTALLER SUPPLIED 3/8 OR 1/2 TUBE FLARE NUT

6 INSTALLER SUPPLIED 1/4 COPPER OR ALUM. TUBING

7 32037 1/8 MNPT X 1/4 TUBE COMP. FITTING

SUPPLY

TO BURNER

5

RETURN

TO TANK

6

4

7

3

2

1

GA

UGE

A2R

INLE

T

RELIEF

A-7720

R H R

OTATION

I89004-D

Figure 4K - Pressure Relief Oil Line Back to the Tank

4-16

Operator's Manual: Model CB-140

1.

2.

3.

Installing the Pressure Oil Line Components

ATTENTION: It is critical that you adhere to the following specifications for pressure oil line installation (oil line from the pump to the furnace); if these specifications are not met, the metering pump will not function correctly and the burner will shut down on reset.

The parameters for pressure oil line installation are:

• Length of Pressure Line

Up to 100 feet

Line Size

3/8" O.D. copper tubing

(Please note that some installations will allow for a greater pressure line length. Contact your Authorized Clean Burn Distributor for more information.)

• The pressure oil line must slant up to the burner with no loops or high points to trap air.

• Local codes may require the installation of an in-line "Fire-O-Matic" safety valve. Be sure to check all appropriate codes to ensure compliance.

Refer to Figures 4H, 4J, and 4K.

Make sure you have purchased all the necessary fittings to complete the installation correctly.

Install the fittings and components as shown in the related illustrations. Be sure to use Permatex #2 non-hardening gasket sealer to seal every threaded fitting. DO NOT use teflon tape or teflon pipe dope compounds.

Installing the Compressed Air Line

NOTE: Your air compressor system must supply air pressure to the furnace with the following minimum requirements: 50 psi and water trap or dryer. If you do not have shop air, an optional air compressor is available. Contact your local Clean Burn dealer for more information.

1.

2.

Run a compressed air line from your shop air to the connector block on the furnace. Use minimum

1/4" O.D. copper tubing or equivalent for the compressed air line.

Install an easily accessible shut-off valve in the air line so the burner can be serviced without shutting off the shop air in your service area.

3.

4.

If necessary, install a pressure regulator (additional to the burner air regulator) in the air line, and set it at 50 psi.

ATTENTION: DO NOT feed full shop air pressure to the burner or damage to burner components may occur.

Install a water trap or extractor/dryer in the air line with an automatic drain so compressed air (rather than water) is supplied to the burner.

ATTENTION: Water must not be fed to the burner, or the flame will be extinguished and the burner will shut down. Be sure to drain water from your compressor tank on a regular basis to keep water out of the air line.

4-17

Operator's Manual: Model CB-140

Installing the Stack

WARNING: Inappropriate stack materials or improper stack design/installation can adversely affect the proper, safe operation of your furnace. Contact your Clean Burn dealer to purchase the proper stack components for your furnace.

Stack designs are generally classified as follows:

(1) "Class A" stack through the ceiling of the building (refer to Figure 4L)

(2) "Class A" stack through the sidewall and up the side of the building (refer to Figure 4M)

Stack Design and Specifications

ATTENTION: The stack design must be single and dedicated for each unit (furnace) according to

the following specifications. A single stack serving more than one unit MUST be engineered/certified for that specific installation (ref. NFPA 211, 3.3.39 and 10.2.1; NFPA 31 6.5.16-18). Failure to adhere to this rule may result in less than optimal system performance.

Figures 4L and 4M illustrate recommended stack designs. Choose the stack design which is appropriate for your furnace installation and review all specifications provided in the corresponding drawing. When designing your stack, adhere to the following specifications:

• Model CB-140 requires minimum 6" I.D. stack components.

• Ensure that the vertical stack height is at least 10 feet PLUS one foot for every fitting (e.g. 45

degree, 90 degree, or T) in the stack run. If needed, increase the vertical length of the stack or install a draft inducer to obtain -.02" W.C. draft over fire. (Section 8 contains details on adjusting the draft.)

• Keep the horizontal stack run as short as possible; slant it upward at a minimum of 1/4" per foot of run.

• Keep the stack design simple. Complicated stacks (with long runs and many turns) reduce draft and result in poor burner performance. Your stack may include only one 90 degree turn. All other stack turns must be at 45 degrees or less to ensure optimal draft and burner performance

NOTE: If you plan to use an existing masonry chimney, the chimney must be lined and inside the building. Exterior masonry chimneys chill the stack gases and result in poor draft and poor burner performance.

ATTENTION: If you have an exhaust fan(s) in your shop, it is critical that you have adequate

make up air (source of fresh air to replace the stale air exhausted by the fan). When an exhaust fan is run without adequate make up air, the resultant vacuum in the building will draw combustion products back into the burner. This back draft causes poor burner performance and may damage vital burner components. Refer to Section 8 in this manual for additional information.

Stack components should be installed in the following order:

(1) Inside stack (the stack components from the furnace breach to within 18" of the ceiling, roof,

or sidewall of your building)

(2) Barometric damper

(3) "Class A" stack penetration through the ceiling, roof, or sidewall

(4) "Class A" stack on the exterior of the building

(5) "Class A" stack cap

4-18

Operator's Manual: Model CB-140

Installing the Stack (continued)

"CLASS A" STACK CAP - NON-RESTRICTIVE TYPE

TO ALLOW FREE FLOW OF THE STACK GASES

NOTE: THE LAST STACK SECTION SHALL EXTEND AT

LEAST 3' HIGHER THAN ANY RIDGE, PARAPET, WALL OR

ROOF STRUCTURE WITHIN 10' OF IT.

10'

WARNING! ENSURE PROPER

CLEARANCES BETWEEN STACK

COMPONENTS AND COMBUSTIBLES

PER ALL APPLICABLE CODES.

WARNING! MAKE SURE TO INSTALL

THE PROPER ROOF SUPPORT

SYSTEM TO SAFELY SUPPORT THE

STACK

WATERTIGHT

ROOF FLASHING

"CLASS A" KIT FOR

INSTALLING "CLASS A" STACK

THROUGH CEILING

-.02" W.C. DRAFT OVER FIRE

IS ESSENTIAL FOR PROPER

FURNACE OPERATION.

SEE SECTION 8

CLEAN OUT CAP

AIR OIL

STACK SIZE:

MIN. 6"

1/4" HOLE FOR

SETTING DRAFT.

ADJUST BAROMETRIC

DAMPER FOR -.02" W.C.

DRAFT OVER FIRE

ATTENTION:

BAROMETRIC DAMPER

MUST BE INSTALLED SO

IT IS FACING AWAY FROM

THE FAN TO PREVENT

EXHAUST GASES FROM

BEING SUCKED OUT OF THE

DAMPER OPENING

Figure 4L - Installation of "Class A" Stack Through Roof/Ceiling

I89096-A

4-19

Operator's Manual: Model CB-140

Installing the Stack (continued)

WARNING! ENSURE PROPER

CLEARANCES BETWEEN STACK

COMPONENTS AND COMBUSTIBLES

PER ALL APPLICABLE CODES.

"CLASS A" STACK CAP - NON-RESTRICTIVE TYPE

TO ALLOW FREE FLOW OF THE STACK GASES

NOTE: THE LAST STACK SECTION SHALL EXTEND AT

LEAST 3 FEET HIGHER THAN ANY RIDGE, PARAPET, WALL

OR ROOF STRUCTURE WITHIN 10 FEET OF IT.

10 FT.

-.02" W.C. DRAFT OVER FIRE

IS ESSENTIAL FOR PROPER

FURNACE OPERATION.

SEE SECTION 8

AIR OIL

WARNING! MAKE SURE TO INSTALL

THE PROPER WALL SUPPORT SYSTEM

TO SAFELY SUPPORT THE STACK

1/4" HOLE FOR

SETTING DRAFT.

ADJUST BAROMETRIC

DAMPER FOR -.02" W.C.

DRAFT OVER FIRE

"CLASS A" STACK

PENETRATION AND

CLEAN-OUT TEE

BAROMETRIC

DAMPER

SINGLE WALL STACK

MIN. 24 GAUGE

DRAFT

STACK

SIZE

MIN.

6"

I89097-A

Figure 4M - Installation of "Class A" Stack Through Sidewall

4-20

Operator's Manual: Model CB-140

Installing the Interior Stack

WARNING: Single wall stack components may be used only for those portions of the stack which are located inside your building and away from any fire/burn hazards.

1.

2.

Install the single wall stack with proper clearances from combustibles. Also ensure that the stack is located a safe distance from all shop personnel.

Install an elbow at the junction of the horizontal and vertical stack components to allow for easy cleaning of the stack.

ATTENTION: Avoid additional 90-degree turns in the stack. Each additional 90-degree turn slows down stack gases, creates back-pressure, and results in repeated burner shutdown and unnecessary service calls. All other turns in the stack should be at a 45-degree (or smaller) angle.

NOTE: IMPORTANT for Canadian Installations - Local codes may require the installation of a cleanout tee.

Installing the Barometric Damper

1.

2.

Refer to Figure 4L. Install a single wall tee (min. 24 gauge) after the 90 degree elbow in the straight vertical stack section within three to five feet of the furnace breach. For horizontal stack runs (as shown in Figure 4M), install the tee after the first straight section of pipe.

NOTE: The tee is required to support the barometric damper. You must purchase this tee when you purchase your stack materials (6" single wall tee - CB #70301).

Refer to Figure 4N. Install the barometric damper in the opening of the tee. Use a small spirit level to make sure that it is properly level.

Install two self-tapping screws as shown in Figure 4N (i.e. one on each side of the barometric damper) to 3. hold the damper in place. DO NOT install a screw at the bottom of the barometric damper, or the flapper of the damper will not operate correctly.

NOTE: Specifications for adjusting the barometric damper for proper draft over fire are provided in Section 8 of this manual.

6" CLEAN BURN BAROMETRIC DAMPER

INSTALLED IN SINGLE WALL TEE

C77007

ADJUST THIS WEIGHT TO

OBTAIN PROPER DRAFT

1

1 1 31153

No QTY PART #

Figure 4N - Installation of Barometric Damper

4-21

6" BAROMETRIC DAMPER

DESCRIPTION

Operator's Manual: Model CB-140

2.

3.

4.

6.

7.

Installing the Stack Safety Switch For Canadian Installations

NOTE: CSA Standards require that all heating equipment must be installed with a stack safety switch. If your heating equipment is being installed in Canada, follow the instructions listed below.

CAUTION: For your safety and the safe operation of your heating equipment, the stack switch must be installed by a qualified installer in accordance with the installation instructions provided here. Wiring must be accomplished in accordance with all applicable codes. Failure to adhere to these safety recommendations may result in serious personal injury and/or equipment damage.

1.

5.

Follow the instructions in the Operator’s Manual, Section 4 to install a proper stack, including the barometric damper which must be installed within 40 inches of the breach.

NOTE: The barometric damper must be installed so that it is level and the flapper moves freely.

Ensure that main power to the heating equipment is turned OFF.

Position the stack safety switch over the lip of the barometric damper as shown in Figure 4O.

Drill a 1/8” pilot hole for the mounting screw, and mount the stack safety switch using the mounting screw supplied with the switch.

NOTE: The mounting screw must not interfere with the free movement of the flapper on the barometric damper.

Install the wall thermostat according to the instructions provided in the Operator’s Manual, Section 4.

Wire the wall thermostat and stack safety switch in series as shown in Figure 4P. Install the wire so that it is secured away from any hot surfaces.

When the heating equipment installation is completed, follow the instructions in the Operator’s Manual,

Sections 5 and 6 to prime the pump and start/adjust the burner.

Follow instructions in the Operator’s Manual, Section 8 to check the draft; this is crucial for the proper, safe operation of the heating equipment.

I88964

Figure 4O - Stack Safety Switch Installed on the Barometric Damper

4-22

Operator's Manual: Model CB-140

Resetting the Stack Safety Switch

WARNING: BURN HAZARD! To prevent serious personal injury, be sure to allow ample time, at least

30 minutes, for the stack, barometric damper, and switch to cool down before attempting to access and service these components. It is crucial to identify the cause of the stack obstruction (e.g. heavy snowfall) and correct it before resetting the stack safety switch and re-starting the burner. DO NOT operate the heating equip-

ment with an obstructed stack; failure to correct an obstructed stack may result in fire, explosion, and/or burn hazards causing serious personal injury or death.

NOTE: In locations where heavy snowfall occurs, it is critical that the stack remain unobstructed by snow. For safe heating equipment operation, be sure to keep the area surrounding the stack clear of snow.

1.

2.

3.

Before resetting the stack safety switch, check the stack to make sure it is clear of any obstructions.

Remove the cover from the stack safety switch, and push the small button in the middle of the switch.

Pushing the stack safety switch reset button will re-establish the thermostat circuit, and the burner will start (assuming the wall thermostat is calling for heat).

Understanding the Function of the Stack Safety Switch

The Stack Safety Switch monitors the temperature at the barometric damper on the stack and is designed to detect the obstruction of the free flow of stack gases from the heating equipment and shut down the burner. Obstruction of the stack results in the “spillage” of stack gases from the barometric damper, which heats up the switch.

The switch then opens, disconnecting the thermostat circuit to the burner, and the burner shuts off.

Stack Safety Switch Specifications

Switching Voltage

Switch OPEN Temperature

Switch Type

24 volts

180 degrees F

L180, normally closed, manual reset

WALL

THERMOSTAT

OIL

PRIMARY

STACK

SAFETY

SWITCH

(MOUNTED ON

BAROMETRIC DAMPER)

I88965

Figure 4P - Stack Safety Switch Wiring Diagram

4-23

Operator's Manual: Model CB-140

Installing the Stack Penetration

WARNING: When running the stack through your ceiling, roof, or sidewall, you must use Class A/UL

103 HT double-wall insulated all-fuel stack components with a stainless steel liner. DO NOT run single-wall stack through your ceiling, roof or sidewall. NEVER locate a stack joint inside walls or in a joist spacer.

Ensure proper clearances from combustibles per all applicable codes.

1.

2.

Refer to Figure 4L / 4M as needed.

Follow the installation instructions provided by the stack manufacturer.

Installing the Exterior Stack

ATTENTION: All exterior stack pieces must be Class A/UL103 HT double-wall insulated all-fuel stack components with a stainless steel liner.

• DO NOT use Class B or BW Vent/double-wall stack components (for gas fired appliances only).

• DO NOT use Type L Vent/double-wall stack components (for approved fuel oil appliances only).

• DO NOT use black stack pipe (for solid fuel burning appliances only).

• DO NOT use single-wall stack for your exterior stack. Single-wall exterior stack chills the stack gases and results in poor draft and poor burner performance.

1.

2.

1.

2.

3.

Refer to Figure 4L / 4M as needed.

Follow the installation instructions provided by the stack manufacturer.

Install water-tight roof flashing around the penetration of the exterior stack.

NOTE: Clean Burn recommends the use of "Dektite" roof flashing (or equivalent) which ensures a water-tight seal when installed properly. Contact your local Clean Burn dealer for details.

Installing the Stack Cap

NOTE: Proper installation of a "Class A" stack cap ensures the free flow of stack gases which is essential for optimal burner performance.

Refer to Figure 4L / 4M as needed. Your stack cap should be classified as: "Class A" non-restrictive, allfuel type.

Install the stack cap according to the manufacturer's instructions.

Installing the Optional Draft Inducer

ATTENTION: The draft inducer, Field brand model DI-2, is optional equipment and may be installed to ensure proper draft. The Field brand draft inducer has been tested for use on Clean Burn furnaces. DO NOT use other models or brands of draft inducers.

Understanding the Importance of the Draft Inducer

The draft inducer is designed to aid in the removal of the natural draft created by the appliance to vent the combustion gases to the outside of the building. As the paddle wheel turns, a negative pressure is maintained within the stack so that the combustion gases can leave the furnace and travel out of the stack. (See Figure 4Q.) Proper

sizing, installation, and adjustment of the draft inducer are critical for optimal draft inducer operation.

4-24

Operator's Manual: Model CB-140

Installing the Optional Draft Inducer (continued)

NOTE: Lubricate the motor as recommended by the

Draft Inducer manufacturer.

NOTE: INSTALL THE DRAFT INDUCER IN

THE LAST SECTION OF VERTICAL STACK

TO POSITION THE DRAFT INDUCER AWAY

FROM THE FURNACE BREECH SO THE

MOTOR DOES NOT OVERHEAT. THIS ALSO

REDUCES ASH ACCUMULATION IN THE

DRAFT INDUCER.

"CLASS A" STACK

OPTIONAL

DRAFT

INDUCER

DO NOT MOUNT THE

DRAFT INDUCER IN

THE HORIZONTAL

STACK NEAR THE

FURNACE BREECH.

DRAFT

ADJUSTMENT

PLATE

24 GA. INTERIOR ST

CHECK FOR

-.02" W.C. DRAFT

OVER FIRE

CLEAN-OUT CAP

INSTALLED ON L.H.

FURNACE BREECH

SERVICEMAN ADJUSTS

BAROMETRIC DAMPER TO

OBTAIN -.02" W. C. DRAFT

OVER FIRE

AIR OIL

I89098-A

Figure 4Q - Installation of the Optional Draft Inducer

WARNING: Turn OFF the main power to the furnace before proceeding with the installation of the draft inducer.

ATTENTION: It is very important to install the draft inducer on a vertical section of stack to isolate the inducer from excessive heat and ash buildup. Never install the draft inducer on a horizontal section of stack close to the furnace breach where heat and ash will damage the inducer motor.

4-25

Operator's Manual: Model CB-140

Installing the Optional Draft Inducer (continued)

1.

2.

Refer to Figure 4Q. Follow the instructions included with the draft inducer to mount the draft inducer on the section of single-wall vertical stack.

Position the draft plate all the way out so that it does not reduce the draft produced by the draft inducer Follow instructions in Section 8 (Adjusting the Draft Over Fire) to set the proper draft.

Wiring the Draft Inducer for Normal Operation*

1.

*(No exhaust fans in the building. Read pages 8-3 to 8-6 if exhaust fans are present.)

Wire the draft inducer according to the Furnace Wiring Diagram provided in Appendix B at the back of this manual.

Installing the Wall Thermostat

1.

2.

3.

4.

5.

6.

Select a location for the thermostat on an interior wall away from any hot or cold drafts.

Remove the top cover from the thermostat by pushing gently on the latch at the top center of the body.

(Hold the thermostat base in one hand, and grasp the body with the other hand; push in on the latch with

your thumb, and pull the cover away from the base.)

ATTENTION: DO NOT use a screwdriver to pry the cover off the base, or damage may occur.

Remove the green paper insert and the black plastic battery isolator from the battery section of the thermostat.

Refer to the Burner Wiring Diagram in Appendix B at the back of this manual. Run two wire,

18-gauge (minimum) thermostat cable from the terminals on the back of the thermostat base to the T/T terminals of the primary control on the burner. ATTENTION: NEVER jump between T/T terminals on the primary control without removing one of the wires. Failure to remove one of the wires will burn out the heat anticipator on the thermostat and will cause the thermostat to fail.

Mount the thermostat base 60" to 66" from the floor using the hardware provided.

Reassemble the thermostat body onto the base. (Align the hinges at the bottom of the cover with

the slots at the bottom of the base, and swing the cover up into place.)

Replacing the Wall Thermostat Batteries

1.

2.

3.

Proper battery level is indicated by the room temperature being displayed on the LCD screen.

When the battery level becomes low, a battery icon along with the word "REPLACE" will be displayed in the lower left corner of the LCD screen. Replace the batteries to ensure proper operation, following the previous instructions on the thermostat disassembly procedure.

If the batteries are not replaced, the display will slowly become dim and not display any information. The thermostat will eventually not function. If this happens, replace the batteries immediately.

Inspecting the Furnace Installation

Following completion of all installation activities described in this chapter, the furnace should be inspected by qualified personnel before firing. This ensures that your installation meets all applicable national and local codes and allows for any deficiencies to be corrected before furnace startup. Improper installation may void

your warranty.

4-26

Operator's Manual: Model CB-140

SECTION 5: METERING PUMP PRIMING

Understanding Metering Pump Priming

Preparing your Clean Burn furnace for operation begins with priming the metering pump. The procedures in this section must be performed in sequence without interruption to properly prime the pump.

Required Tools and Materials

The following tools and materials are required for oil pump priming and should be gathered before starting any procedures:

• 3/8" open-end wrench

• 5/8" open-end wrench

• Rags

• Two containers (minimum one-gallon)

• Permatex #2 non-hardening gasket sealer

• Adjustable Wrench

• Pipe Wrench

5-1

Operator's Manual: Model CB-140

6.

7.

4.

5.

1.

2.

3.

Priming the Metering Pump

ATTENTION: The priming process must be done precisely as described in this procedure to ensure that all

air is thoroughly bled from the system. Failure to bleed all air from the system will result in repeated burner shutdowns on reset.

Refer to Figure 5A.

Remove the 1/4" NPT plug from the side of the pump head, and set it aside.

Remove the 1/2" brass cap from the 1/2" brass nipple. Place a funnel in the opening. Slowly pour used oil into the funnel until oil comes out of the side of the pump head; this will fill the oil line, canister filter, and pump head with oil.

ATTENTION: NEVER run the pump head dry (i.e. without oil in the pump head); doing so will severely damage the pump.

Apply Permatex #2 non-hardening gasket sealer to the threads of the plug (removed from the pump head).

Re-install the plug and tighten.

Apply Permatex #2 non-hardening gasket sealer to the threads of the 1/2" brass nipple. Re-install the 1/2" brass cap on the brass nipple and tighten.

Open the bleeder valve on the pump two to three (2-3) full turns, and position a container to catch oil which will flow from the bleeder during pump priming.

Close the mini ball valve at the outlet port of the pump head.

ATTENTION: Verify that the relief oil line is installed back to the tank before closing the mini ball valve. Closing the mini ball valve will cause the internal pump relief valve to open.

TO BURNER

1/2" BRASS

CAP

1/2" BRASS

NIPPLE

RETURN TO TANK

MINI BALL

VALVE

1/4" PLUG

PUMP

GEARMOTOR

BALL VALVE

BLEEDER VALVE

VACUUM GAUGE

CANISTER

FILTER

TO TANK

SUCTION

LINE

Figure 5A - Priming the Metering Pump

5-2

I88756-C

Operator's Manual: Model CB-140

Priming the Metering Pump (continued)

8. Activating the Pump

NOTE: The CB-140 furnace features a priming switch which is mounted on the right-hand side of the electrical junction box on the front of the furnace cabinet. The priming switch has two positions:

• PRIME (switch is in the UP position): This is used only for pump priming. When the switch is in the UP position, the pump circuit is activated for priming. The pump will continue to run as long as the switch is in this position. The oil primary control circuit is de-activated so the burner cannot run while the switch is in the UP position.

• BURNER (switch is in the DOWN position): This is used for normal burner operation. When the switch is in the DOWN position, the burner controls the operation of the pump. The pump will only run while the burner is running.

a. Refer to Figure 5B to locate the priming switch.

b. Turn the priming switch to the prime (UP) position. The pump should immediately start running.

OIL PUMP

PRIMING

SWITCH

I89099-A

Figure 5B - Locating the Pump Priming Switch

5-3

Operator's Manual: Model CB-140

Priming the Metering Pump (continued)

9. Run the pump until a solid stream of oil flows from the pump bleeder. This will bleed all air out of the suction line, oil filter and pump head.

ATTENTION: For the metering pump to operate correctly, it is very important that the system is entirely full of oil and all air is bled out. The burner will shut down if there is any air in the system

10. Open the mini ball valve at the outlet port of the pump head to allow the pressure oil line to be filled

11. Close and tighten the bleeder on the pump.

12. Turn the priming switch to the burner (DOWN) position so that the pump stops running.

13. Disconnect the pressure oil line from the burner and position a container to catch oil which will flow from the pressure oil line during pump priming.

14. Turn the priming switch to the prime (UP) position. The pump should start running immediately .

15. Run the oil pump until the proper flow of oil has been established, and the oil line has been completely flushed out.

16. Turn the priming switch to the burner (DOWN) position so that the pump stops running.

17. Re-connect the oil line to the burner.

2.

3.

Vacuum Testing the Oil Pump

Vacuum testing the oil pump is a very accurate way to determine the following:

• The condition of the pump -- the ability of the pump to pull a vacuum and suck oil from the tank.

• The condition of the fittings, gaskets and seals from the ball valve to the pump -- these components must all be airtight to avoid suction leaks.

The following procedure provides instructions for vacuum testing the pump and canister filter on systems equipped with a ball valve.

ATTENTION: For the pump to pull and hold vacuum, it is critical that all fittings are airtight. If any of these fittings are loose, the pump may not pull a vacuum or may lose the vacuum rapidly. It is also critical that all fittings in the suction line, including fittings on the canister filter, are 100% airtight.

1.

4.

Follow the instructions to prime the pump (previous procedure).

NOTE: The pump will not pull a vacuum if the pump is dry. There must be oil in the gears of the pump before the pump can pull a vacuum.

With the pump running, open the bleeder two to three full turns, and make sure that oil is flowing from the bleeder. DO NOT close the bleeder yet.

Refer to Figure 5A. Close the ball valve at the inlet to the canister filter. Observe the vacuum gauge.

NOTE: The ball valve must have a stainless steel ball and should be pressure tested by the manufacturer to ensure that it does not leak. If the ball valve leaks, the vacuum test will not be accurate.

The vacuum should increase within 30 seconds to 15 inches of vacuum. When the vacuum gauge reads

15 inches of vacuum, first close and tighten the bleeder, then turn the pump off and close the mini ball valve at the outlet port of the pump. Observe the vacuum gauge.

NOTE: If the pump will not pull at least 15 inches of vacuum, there is a very serious suction leak, or the pump is damaged

5-4

Operator's Manual: Model CB-140

Vacuum Testing the Oil Pump (continued)

5. If there are no suction leaks, the system will hold vacuum.

NOTE: It is acceptable for the vacuum to drop one to five inches within one minute as the seal in the pump seats. The vacuum should then hold steady for 15 minutes.

ATTENTION: If the vacuum drops more than one to five inches within the first minute, there is one or more

leaks somewhere between the pump and the ball valve. Do the following:

6.

• Wipe your finger along the cylinder at the shaft of the pump. If there is oil here, the pump seal is damaged. Replace the pump.

• Disassemble and clean all the fittings from the pump to the ball valve. Properly seal all fittings with

Permatex #2 non-hardening gasket sealer or equivalent. Check the condition of the o-ring on the canister filter and tighten the four canister filter bolts in a crisscross pattern.

• Repeat the procedure to vacuum test the system to ensure that the system is air tight.

Follow the instructions to prime the metering pump after a vacuum test has been performed.

5-5

Operator's Manual: Model CB-140

5-6

Operator's Manual: Model CB-140

SECTION 6: STARTING AND ADJUSTING THE BURNER

Understanding Burner Startup and Adjustment

Starting and adjusting the burner involves a series of separate procedures which must be accomplished in sequence without interruption. Review all the procedures before attempting burner startup and adjustment, paying careful attention to safety information statements.

Preparing the Burner for Startup

1. Turn the switch on the wall thermostat OFF.

NOTE: If your thermostat does not have an OFF setting, disconnect one thermostat wire so the burner will not run.

2. Turn the main power to the furnace ON.

3. Wait at least 15 minutes until the preheater block is thoroughly warmed up. (Feel the back of the burner box to make sure the preheater is sufficiently warm. The proving switch on the preheater block will not allow the burner to start until the block is hot.)

NOTE: The preheater block will remain warm as long as power is supplied to the burner.

If the main power supply is ever turned OFF, you must wait at least 15 minutes until the preheater block is thoroughly warm before starting the burner.

ELECTRICAL

BOX COVER

4. Refer to Figure 6A to locate the air regulator. Loosen the locking nuts on the air regulator.

5. Turn the adjustment knobs on the air regulator counterclockwise until 1/2" of the threads on the knob are exposed. DO NOT back the knob all the way out.

AIR

REGULATOR

AIR

GAUGE

COMBUSTION

AIR BAND

I88584-C

NOTE: The air gauge will not show any pressure until the burner starts.

Before starting the burner for the first time, it is very important to turn the air regulator completely OFF as described.

FIGURE 6A - Component Detail of the CB-125 Burner

6-1

Operator's Manual: Model CB-140

Preparing the Burner for Startup (continued)

6.

Initial Adjustment of the Combustion Air Band:

WARNING: The combustion air band must be properly adjusted to ensure that the burner ignites and burns correctly. DO NOT attempt to start the burner with the combustion air band wide open or completely closed. The burner may not ignite correctly. Failure to heed this warning may result in a fire or explosion hazard.

• Refer to Figure 6A to locate the combustion air band.

• Rotate the combustion air band to adjust it to the appropriate initial slot opening as listed in the following Initial Adjustment Charts. Use a ruler to accurately set the combustion air band gap.

IMPORTANT NOTE: This initial setting of the combustion air band will allow you to start the burner.

You will fine tune the combustion air band further as described later in these instructions.

ATTENTION: The settings shown in the charts below are only initial adjustments. Final

adjustments must be done by inspecting the flame length according to the illustration provided on the following page.

NOTE: The oil pressure is automatically adjusted by the metering pump.

Initial Adjustments for the CB-140 Furnace

Maximum Input = 140,000 BTUH @ 1.0 GPH with CB-125 Burner

Oil Type Oil PSI / Flame Length

#2 Fuel Oil check flame length

#4 Fuel Oil check flame length

Used Crankcase Oil check flame length

ATF

Used Hydraulic Oil

check flame length

check flame length

Air PSI

14-18

14-18

14-18

14-18

14-18

Air Band Nozzle

1/2"

1/2"

1/2"

1/2"

1/2"

9-5

9-5

9-5

9-5

9-5

Starting the Burner

1.

2.

3.

Turn the switch on the wall thermostat to HEAT and adjust the thermostat setting above room temperature to start the burner.

Adjusting the Air Regulator:

As soon as the burner starts running, turn the knob on the air regulator clockwise to achieve proper operating air pressure. Refer to the Initial Adjustment Charts.

NOTE: If the safety reset on the primary control is activated and the burner stops running, see

Section 7 for further instructions on restarting your burner.

Observing the Flame Length:

Visually inspect the flame length through the observation port. Refer to Figure 6B for an illustration of the desired flame length. The flame should extend no more than one-half of the way down the combustion chamber.

WARNING: The observation port gets hot as the burner fires. To avoid personal injury, always wear heavy work gloves and safety glasses when opening the port and viewing the flame.

6-2

Operator's Manual: Model CB-140

Starting the Burner (continued)

Correct Maximum Flame Adjustment

(Proper Oil and Air Pressure with correct supply of Combustion Air):

• Flame goes half of the way down the combustion chamber

• Flame does not touch back or walls of combustion chamber.

Incorrect Flame Adjustment

(Not Enough Combustion Air):

• Flame must not touch back or walls of combustion chamber

• Increase combustion air by opening the air band on the side of the burner.

Incorrect Flame Adjustment

(Air Pressure Too High):

• Ensure proper air pressure setting.

NOTE: Increasing combustion air will shorten the flame; decreasing the combustion air will lengthen the flame.

FIGURE 6B - Flame Length Adjustment

I89100

4.

5.

6.

Check the flame length after the burner has fired for 15 minutes.

Tighten the locking nuts on the air regulator.

Fine Tuning the Combustion Air Band:

NOTE: The initial setting of the combustion air band may require additional adjustment.

• Refer to Figure 6A to identify the combustion air band location on the burner.

• Observe the flame. The flame should be yellow-white with sharp tips and no "sparkles."

• If the flame is orange in color or the flame length is too long, the oil you are burning requires MORE combustion air. OPEN the air band 1/8" to 1/4", and re-check the flame for the proper characteristics.

• Re-check the flame after ten minutes. You should see a yellow-white flame with sharp tips and no "sparkles", and the flame should extend half of the way down the combustion chamber.

6-3

Operator's Manual: Model CB-140

Starting the Burner (continued)

7.

Checking for a Smokeless Burn:

Check for a smokeless burn by observing the stack while the burner is running. If you see any smoke, repeat the previous steps for setting the combustion air band and adjusting the air regulator. After adjusting the combustion air band, re-check the flame length.

NOTE: Check for a smokeless burn periodically (as you do the flame length). Immediately readjust the burner if you ever see smoke coming from the stack. Smoke indicates improper combustion air adjustment.

NOTE: When using instruments to adjust the burner for a smokeless burn, the following readings should be achieved:

• Draft over fire should be -.02 inch w.c.

• Adjust for a smoke spot of a trace to 2

• Adjust for a CO

2

reading of 9% to 11% or an O

• Cad cell reading below 500 ohms

2

reading of 7% to 8%

Checking the Operation of the Fan Motor

NOTE: It is important to verify that the fan motor operates correctly to ensure that the fan switch is properly cycling the fan motor as described below. Also refer to Appendix A at the back of the manual for additional pertinent information.

1.

2.

3.

4.

Start the burner and adjust it as described previously in this section.

The fan motor will not start until the burner has been running for 3 to 5 minutes to heat up the combustion chamber and heat exchanger. At this point, the fan switch will activate the fan motor.

Once the fan motor has activated, turn the burner off by turning the wall thermostat to OFF.

With the burner off, the fan motor should continue to run for 5 to 10 minutes until the combustion chamber is cooled down. The fan switch will then shut off the motor.

WARNING: If the fan motor does not operate as described, immediately shut down your furnace to avoid potential equipment damage and/or fire hazard. Contact your Clean Burn dealer immediately.

6-4

Operator's Manual: Model CB-140

SECTION 7: RESETTING THE OIL PRIMARY CONTROL

( See Appendix B for additional information )

Understanding the Oil Primary Control

NOTE: The CB-125 primary controller (CB Part #33400) is a recycle type control, which features interrupted ignition operation.

The oil primary control will go into safety lockout and shut the burner off when it detects flame-out during burner operation. The oil primary control will then wait approximately one to two minutes and attempt to re-ignite the burner (recycle mode). If the burner does not re-ignite, the control will shut the burner off on safety. The following procedure explains what should be done when this occurs. It is very

important that you follow these instructions precisely when resetting the safety on the primary control and restarting the burner.

1.

2.

3.

4.

Using the Reset Button

DANGER! DO NOT push the reset button more than once! DO NOT push the reset button if oil mist is present in the combustion chamber or when the combustion chamber is hot! DO NOT operate your furnace if excess oil, oil vapor or fumes have accumulated in or near your furnace. As with any oil burning furnace, improper operation may result in a fire or explosion hazard.

5.

Refer to Figure 7A.

Check the combustion chamber for fuel mist by shining a flashlight through the observation port.

If you see fog (fuel mist) in the chamber, DO NOT push the reset button.

If the combustion chamber is hot, allow the furnace to cool for at least 30 minutes. DO NOT push the reset button.

When you are sure all mist has been cleared from the chamber and the combustion chamber is cool, depress the red button on the primary control for 2 seconds, then release. Reset the control

ONCE ONLY.

If the burner will not restart, call your Clean Burn dealer immediately.

AMB GRN RED

AMBER LED

GREEN LED

RED LED

CAD CELL

WIRES

WIRES RUN UNDER

SMALL CENTER GAP

WARNING

Fire and explosion hazard.

Do NOT press reset button until you read and understand Reset

Procedures in Operator's Manual.

42000 Rev. 2

RESET BUTTON

C77008

ATTENTION: Never touch a jumper wire from an "F" terminal to a "T" terminal on the oil primary control. This will severely damage your primary control. Make sure the plastic barrier strip is in place between the "F" and "T" terminals as shown in

Figure 7A.

FIGURE 7A - Oil Primary Control

7-1

Operator's Manual: Model CB-140

The Blower/Fan Switch

The CB-140 furnace features an F-180 blower/fan switch (normally open) which is surface mounted at the front of the combustion chamber (see Figure 7B). The blower/fan switch senses the temperature of the combustion chamber as the burner is firing. When the combustion chamber reaches the proper temperature, the blower/fan switch closes and sends power to the fan motor to turn ON the fan. When the wall thermostat is satisfied and the burner shuts off, the fan continues to run until the switch senses that the combustion chamber has cooled down. The switch then opens and shuts off the fan motor.

The Hi-Temp Limit Switches

These furnaces also feature two high temperature limit switches which are mounted on a bracket at the front of the combustion chamber as shown in Figure 7B. The switches sense the build-up of heat within the combustion chamber and are designed to protect the furnace from damage due to overheating. The limit switches are wired in series, and both are auto-resetting.

Understanding the Function of the L-200 Hi-Temp Limit Switch

If the temperature of the combustion chamber is too hot, the L-200 hi-temp limit switch opens and shuts off power to the primary control on the burner, and the burner shuts off. The fan continues to run to cool down the furnace. After the combustion chamber has cooled down, the L-200 hi-temp limit switch will automatically reset and allow the burner to restart.

ATTENTION: If the L-200 hi-temp limit switch is opening repeatedly, the burner MUST be readjusted

according to the instructions in Section 6 to correct the overheating problem, or serious damage to the furnace may occur.

The L-200 hi-temp limit switch will open and shut down the burner if any of the following conditions exists:

• The furnace is over firing. Review the directions in Section 6 to properly adjust the burner

• Ductwork is installed on the furnace. The CB-140 furnace is not designed for ductwork applications.

Understanding the Function of the L-290 Auxiliary Auto-Reset Hi-Temp Limit Switch

The L-290 auxiliary auto-reset high temperature limit switch is a back-up safety switch for the L-200 hi-temp limit switch.

Both the L-200 and L-290 auxiliary hi-temp limit switches will open and shut down the burner if:

• The fan has stopped running for any reason during furnace operation, the heat in the furnace will cause the limit switches to open. Ensure that the fan is functioning properly.

ATTENTION: It is very important to determine the reason for the opening of the limit switches and

take steps to correct the cause; failure to do so may result in serious overheating and damage to the heat exchanger of the furnace. Additionally, if the burner is rapidly cycling on/off, contact your Clean

Burn Distributor immediately; failure to address this situation may result in serious damage to the furnace.

7-2

Operator's Manual: Model CB-140

The Hi-Temp Limit Switches (continued)

CLEAN-OUT

BREECH

CLEAN-OUT CAP

RED & TAN WIRE LINKS THE 2

SWITCHES IN SERIES

(33390) L-200

HI LIMIT NC

AUTO RESET

RED & TAN WIRE

TO BURNER

RED & TAN WIRE

FROM TERMINAL

BLOCK

BLACK AND TAN WIRE

TO TERMINAL BLOCK

33288 L-290 HI LIMIT AUXILIARY

SWITCH (AUTO RESET)

(33230) F-180

SURFACE MOUNT

FAN SWITCH

Figure 7B - Locating the Hi-Temp Limit Switches

7-3

I89101-A

Operator's Manual: Model CB-140

7-4

Operator's Manual: Model CB-140

SECTION 8: ADJUSTING THE DRAFT OVER FIRE

Understanding the Importance of Draft

Draft in the furnace is created as the hot combustion gases rise up the stack, creating a negative pressure inside the stack and the furnace. This negative pressure is measured as inches of water column (W.C.) of draft. A proper draft over fire of -.02 to -.04 w.c. is essential so that all combustion products travel away from the burner, down the combustion chamber, through the furnace flue tubes and up the stack.

Checking for Correct Draft Over Fire

WARNING: Correct draft over fire is

essential for the proper and safe operation of your furnace.

Your furnace is equipped with an observation/draft reading port to check draft over fire. Qualified

service personel with proper equipment must check/adjust your furnace for proper draft.

Contact your Clean Burn dealer for this service.

1.

2.

Insert the probe of the draft gauge instrument into the draft reading port in the observation port as shown in Figure 8A.

NOTE: Follow the directions with the draft gauge to use your specific type of gauge.

Note the draft over fire reading on the draft gauge. ATTENTION: The draft reading should be in the -.02 to -.04 w.c. range.

Poor draft (i.e. -.01 to +.08) results in back pressure in the furnace and poor burner performance. Too much draft over fire (i.e.

greater than -.04) sucks the heat from the furnace and results in abnormally high stack temperature.

Figure 8A - Checking for Proper

Draft Over Fire

I88257

8-1

Operator's Manual: Model CB-140

Adjusting the Barometric Damper

2.

3.

4.

NOTE: If the draft over fire is not in the -.02 to -.04 w.c. range, it is necessary to adjust the barometric damper.

1.

5.

Before starting the burner, turn the weight on the flapper COUNTERCLOCKWISE until the flapper remains closed. This will provide maximum draft for the furnace.

Follow the directions in Section 6 to start and adjust the burner.

With the burner running, check the draft over fire with a draft gauge.

As shown in Figure 8B, adjust the weight on the flapper to obtain a consistent -.02 w.c. draft over fire. Turn the weight

COUNTERCLOCKWISE to increase draft

(i.e. draft increases as the flapper closes).

Turn the weight CLOCKWISE to decrease draft (i.e. draft decreases as the flapper opens).

Tighten the locking nut to securely hold the weight in position.

ADJUST THIS WEIGHT

TO OBTAIN PROPER

DRAFT OVERFIRE

I88572

Figure 8B - Adjustment of Barometric Damper

Solving Draft Over Fire Problems

WARNING! If you cannot achieve proper draft over fire, do not operate your furnace!

Contact your Clean Burn dealer for assistance.

ATTENTION: Backdraft must be resolved or your furnace will not operate correctly!

Under backdraft conditions, draft over fire readings will show positive pressure in the combustion chamber. Backdraft means that oil spray, combustion products, and heat are blown back against the

burner. Backdraft results in oil-fouled retention heads and electrodes. Severe backdraft will force heat back against the burner and result in heat damage to the cad cell and transformer.

• Backdraft is caused by the following conditions:

• Poor draft caused by improper stack design. (See Section 4.)

• Poor draft caused by improper adjustment of the barometric damper. (See Above)

• Incorrect combustion air band setting on the burner. (See Section 6.)

• Furnace flues are plugged with ash. (See Section 9.)

• Exhaust fans in your building are sucking gases down the stack. (See following pages)

8-2

Operator's Manual: Model CB-140

Understanding the Effect of Exhaust Fans on Draft

Any type of exhaust fan, paint booth, or exhaust system in a building will create negative pressure in the building unless there is a source of make-up air (i.e. fresh air which enters the building and replaces the air removed by the exhaust fans.) Refer to Figure 8C on the following page.

If there is insufficient make-up air, the exhaust fan will suck air and combustion gases down the furnace stack and create backdraft in the furnace. Even if the exhaust fan is on another level of the building or in another room away from the furnace, the exhaust fan will still create backdraft at the furnace.

1.

2.

3.

4.

Checking Draft Over Fire to Determine Severity of Backdraft

The following procedure is an accurate method of determining how much backdraft is created by the exhaust fans. Once this is determined, you can select the correct method for resolving the backdraft.

Refer to Figure 8C on the following page as needed.

Turn off ALL exhaust fans and close ALL doors and windows in the building (any open door or window will allow make-up air to enter the building and will negate the test).

Start the furnace and adjust the barometric damper so that the draft over fire is -.02 w.c.

Check the draft over fire again. Now have someone start the exhaust fans.

Note how much the draft over fire has changed.

ATTENTION: If the draft over fire changed towards positive, it is mandatory that make-up air is provided to the building or severe damage to the furnace and burner will occur (voiding the warranty). If the draft over fire remained constant at -.02 w.c., there is sufficient make-up air entering the building, and the exhaust fan is not adversely affecting the draft.

8-3

SPECIAL NOTE TO

SERVICE PERSONNEL

Operator's Manual: Model CB-140

BACKDRAFT

EXHUST FAN CREATES BACKDRAFT IN STACK

AND SUCKS COMBUSTION GASES DOWN THE

STACK AND BACK INTO THE FURNACE

TO ARRIVE AT PROPER DRAFT

MEASUREMENTS BE SURE THAT ALL

FANS WITHIN THE BUILDING ARE

RUNNING WHILE ADJUSTING THE

DRAFT TO FINAL LEVELS!

BACKDRAFT

CREATED BY

EXHAUST FAN

64.1626

OIL SPRAY AND HEAT IS FORCED

BACK AGAINST THE BURNER AND

RESULTS IN OIL FOULED

ELECTRODES AND RETENTION

HEAD. SEVERE BACKDRAFT WILL

HEAT AND DAMAGE THE CAD CELL

AND THE TRANSFORMER.

PROPER DRAFT

DRAFT OVERFIRE OF -.02 TO -.04

W.C. MEANS COMBUSTION GASES

ARE FLOWING AWAY FROM THE

BURNER,THROUGH THE FURNACE

FLUES AND UP THE STACK

RISING HOT

COMBUSTION

GASES PRODUCE

PROPER DRAFT

SERVICEMAN ADJUST BAROMETRIC

DAMPER TO OBTAIN -.04 TO -.06

W.C. DRAFT AT STACK

Corresponding Draft Over Fire measurement should be -.02 to

-.04 WC

Figure 8C - Proper Draft vs. Backdraft

8-4

COMBUSTION AIR

TO BURNER

I89103-A

Operator's Manual: Model CB-140

Installing a Make-up Air Louver

Exhaust Fans and Make-up Air Louvers

When exhaust fans are operated in tight buildings, there is little or no source of fresh air to replace the air removed from the building by the exhaust fan. This results in negative pressure (vacuum) in the building which creates severe backdraft problems at the furnace.

Properly sized make-up air louvers are designed to allow adequate fresh air to enter the building during operation of the exhaust fans. The louvers automatically open under the vacuum created by the exhaust fans. The louvers open just enough to provide the correct CFM of fresh air. The louvers automatically close when the exhaust fans are turned off.

Sizing the Make-up Air Louver

IMPORTANT NOTE: When using louvers and grills, and the actual free area of the louver or grill is not known, it is understood that wooden louvers/grills will have a free area of 25%, while metal louvers/ grills will have a free area of 75%. ("Free area" translates into the actual space allowing air to flow through.)

Procedure 1:

a. Determine the CFM rating of the exhaust fan. This information should be stamped on a label on the exhaust fan. Make sure to add up the total CFM if more than one exhaust fan exists in the building.

b. Select the correct size of make-up air louver to provide the required CFM of fresh air.

If you cannot determine the CFM rating of the exhaust fan, use the following procedure.

Procedure 2:

a. Count the total number of exhaust fans in the building.

b. Close all of the doors and windows in the building except for one overhead garage door.

c. Start the furnace and allow it to run for 15 minutes to bring it up to temperature.

d. Set the draft-over-fire for -.02" to -.04" W.C. e. Turn ON all of the exhaust fans in the building.

f. Now close the opened overhead garage door slowly, just until the draft gauge moves down into a positive (+) draft reading; as soon as it reaches this point, STOP the door at that position.

g. Slowly open the door back up, just until the draft reading comes back up to the -.02" to -.04 W.C.

h. Measure the size of the door opening, rounding this measurement off to the next largest even foot

Example of Calculations for Sizing Make-up Air Louver

Measured door opening: 12' wide x 9" high

• Round off to 12' wide x 1' high

• Convert to square feet (in this case, equals 12 square feet)

• Multiply by 1.1 correction factor (12 sq. ft. x 1.1 = 13.20 sq. ft.)

• Multiply by free area factor (13.20 sq. ft. x 1.25 = 16.50 sq. ft.)

• Refer to sizing chart (following page) - required grill size would be (1) 54" square grill

8-5

Operator's Manual: Model CB-140

Installing a Make-up Air Louver (continued)

Calculated Opening Size

(Square Feet)

From 0.000 to 0.569

From 0.570 to 0.900

From 0.901 to 1.556

From 1.557 to 2.070

From 2.071 to 2.574

From 2.575 to 3.408

From 3.409 to 5.133

From 5.134 to 7.696

From 7.697 to 9.883

From 9.884 to 13.299

From 13.300 to 16.683

From 13.684 to 21.152

Required Louver / Grill Size

(Inches)

10 x 10

12 x 12

16 x 16

18 x 18

20 x 20

24 x 24

30 x 30

36 x 36

42 x 42

48 x 48

54 x 54

60 x 60

2.

3.

Installing the Make-up Air Louver

All louvers and grills, regardless of the material from which they are made, must be FIXED in the

OPEN position OR be interlocked with the appliance so that they will open automatically during the operation of the appliance. The interlock must be placed on the driven member.

NOTE: It is very important to follow these instructions carefully to ensure proper performance of the louver.

1. The louver must not be close to the furnace. The fresh air should travel at least 40 to 50 feet before reaching the furnace, so the air warms up. The furnace will not heat well if it is receiving cold return air.

The louver must be high in the sidewall of the building so the cold fresh air does not blow across the floor level and chill the service personnel.

The louver should be installed in the opposite wall from the location of the exhaust fan. This will quickly vent diesel exhaust from the top of the building and reduce the amount of run time for the exhaust fan.

8-6

Operator's Manual: Model CB-140

SECTION 9: MAINTENANCE

Understanding Maintenance

Servicing your Clean Burn furnace in a timely manner is very important to keep your furnace running in peak condition. Just as an automobile requires periodic maintenance such as oil changes, engine tuneups, etc. your Clean Burn furnace also requires regularly scheduled service.

WARNING: Failure to maintain and/or improper servicing by unqualified personnel may

adversely affect the proper, safe operation of your furnace, may reduce the service life of your furnace, and may void your warranty.

The following chart summarizes all the service intervals which are required to maintain your furnace.

Service instructions/procedures for these activities are included in this chapter.

Activity Interval

Periodic Burner Inspection

Cleaning the canister filter

Monthly

Before vacuum gauge reads 10" HG of vacuum

Servicing the metering pump

Cleaning the check valve/screen

Cleaning water/sludge out of tank

Cleaning out ash

Annual burner tune-up

At least once a year

At least once a year

At least once a year

800 - 1000 hours as indicated on the hour meter*

At least once a year

*It is very important to clean ash from the furnace on schedule. Normal use of the furnace requires clean-out at least twice during the heating season. Heavy, around-the-clock usage requires more frequent clean-out. For instance, one month of continual running of the furnace is 720 hours (24 hours x

30 days = 720 hours).

NOTE: IMPORTANT! Record all maintenance activities in the Maintenance Record provided in

Appendix C.

Periodic Burner Inspection

Following initial start up of the burner, you should inspect the operation of the burner periodically-ideally on a monthly basis. Doing so ensures that the system is functioning efficiently and safely.

• Visually inspect the flame length through the observation port; the flame should extend no more than one-half of the way down the combustion chamber.

• If the flame is diminishing or displays wide variations, clean the canister filter and check valve/screen

(procedures provided in this section).

• If the flame is firing too strongly (i.e. flame touches back and/or side walls of the combustion chamber), check the air pressure setting (see following guideline).

CAUTION

WHEN OPENING INSPECTION PORT

PORT MAY BE HOT

PROTECT HANDS

WEAR SAFETY GOGGLES

KEEP FACE AWAY

OPEN PORT SLOWLY

9-1

Operator's Manual: Model CB-140

Periodic Burner Inspection (continued)

• Check the air pressure by observing the air gauge; proper air pressure settings are provided in

Section 6. DO NOT over fire the burner; doing so on a continual basis will damage the furnace.

• Check the combustion air band setting for the proper opening and clean away any dust/debris as necessary. Note that the air band should NEVER be set fully open or closed.

• Check the draft over fire reading as specified in Section 8.

Cleaning the Canister Filter

ATTENTION: Never operate your furnace with more than 10" HG of vacuum on the suction side of the pump. High vacuum separates air from the oil and results in erratic burner operation.

5.

6.

7.

8.

9.

1.

2.

3.

4.

The following protective gear should be worn when cleaning the filter:

• Rubber gloves

• Safety goggles

Close the ball valve adjacent to the filter.

Position a container under the filter.

Unscrew the four bolts to drain the oil from the canister.

Remove the canister bowl.

Clean the screen and the bowl in a parts washer.

Referring to Figure 9A, examine the filter components as you reassemble them.

Check the condition of the O-rings. Replace any that are cracked or worn.

Ensure that the canister filter is 100% airtight by firmly tightening the four bolts.

After the pump head screen is serviced as well (page 9-4) open the ball valve and refer to

Sections 5 and 6 for instructions on priming the pump and starting the burner.

TO BURNER

RETURN BACK

TO TANK

USE A RATCHET WRENCH WITH A 6" EXTENSION

AND 3/16" "ALLEN" SOCKET TO REMOVE THE

FOUR "ALLEN" SCREWS

Figure 9A - Canister Filter Component Detail

9-2

I88259-C

Operator's Manual: Model CB-140

Servicing the Metering Pump

1.

2.

3.

4.

5.

6.

Refer to Figure 9B.

Remove the pump head cover (part 1).

Remove the screen (part 2) and wash it.

Remove and discard the used gasket (part 3).

Install a new gasket (Clean Burn Part #32422).

Replace the screen and pump head cover.

3

2

1

GA

UGE

A2R

RELIEF

A - 7720

INLE

T

ROTA

TION

PART No 32422

PART No 32423

I88332-A

Figure 9B - Servicing the Metering Pump

Cleaning the Check Valve And Check Valve Screen

This procedure applies to furnace installations with inside and outside tanks. The following protective gear should be worn when cleaning the check valve/screen:

• Rubber gloves

• Safety goggles

1. Refer to Figure 9C. Remove the one-piece suction oil line from the tank.

2. Remove the check valve and screen. Clean these components in a parts washer.

3. Check the operation of the check valve. The valve must seat so it is airtight to hold pump prime.

4. Re-assemble and re-install the components. Apply Permatex #2 non-hardening gasket sealer or equivalent to the threaded fittings. Firmly tighten all connections so the suction line is 100% airtight.

5. Follow pump priming instructions in Section 5 to re-establish prime.

9-3

TO BURNER

EMERGENCY

VENT

FUNNEL WITH

BALL VALVE

Operator's Manual: Model CB-140

METERING PUMP

SUCTION

OIL LINE

VENT

CAP

CLEANOUT

OIL STORAGE TANK

CHECK VALVE

CHECK VALVE SCREEN

12"

I88670-F

Figure 9C - Check Valve Detail

Cleaning the Tank

DO NOT allow water, sludge, or other debris to accumulate in your oil supply tank to the point that noncombustible or harmful materials are drawn into the pump or burner.

Drain water and sludge from the bottom of your tank at least once a year, and more frequently with water accumulation.

NOTE: If your used oil tank has not been cleaned on a regular basis, a considerable amount of sludge, etc. may have accumulated on the bottom of the tank. Under these circumstances, it is advisable for you to hire your used oil hauler to pump the tank. Make sure the tank is pumped to the bottom to remove all sludge, etc. from the tank (your used oil hauler may charge an additional fee for this type of service).

The best time to pump the used oil tank is at the end of the heating season when the tank is low. This allows sufficient time to refill the tank with used oil (generated by your company over the summer months) so that you have adequate fuel for the heating season.

9-4

Operator's Manual: Model CB-140

Cleaning Ash from the Furnace

NOTE: The maintenance interval for cleaning ash from the furnace is 800 to 1000 hours of operation as indicated on the hour meter on the pump (refer to the servicing intervals at the beginning of this chapter). Be sure to clean the ash from your furnace at least twice during the heating season. Your

furnace may require more frequent clean out of the ash due to contaminants in the oil or heavy use.

As ash accumulates, furnace heat output declines, and the stack temperature rises. 1/8" of ash has the insulating capacity of one inch of fiberglass insulation and reduces heat transfer significantly. Never

allow more than 1/4" of ash to accumulate in the combustion chamber, heat exchanger flues, or stack.

CAUTION: Be aware that used oils may contain heavy metallic compounds or foreign materials. When burned, these compounds are deposited within the furnace, necessitating careful cleaning. The following protective gear should be worn when cleaning the ash:

• Respirator for fine particles (a dust mask is not acceptable)

• Rubber gloves • Safety goggles • Protective clothing

CAUTION: Make sure you use a sturdy ladder or scaffolding for safe access to ceiling-hung furnaces. When cleaning the furnace, static electricity may build up in the shop vac hose. If this occurs, use #12 copper wire wrapped around the hose with the other end connected to the furnace (or other ground source) to eliminate the static.

CLEAN-OUT

DOOR

CLEAN-OUT

BREECH

CLEAN-OUT CAP

I89104

COMBUSTION

CHAMBER

COMBUSTION SLEEVE

WITH SUPPORT BLOCKS

Figure 9D - Accessing the Combustion Chamber for Cleaning

9-5

Operator's Manual: Model CB-140

Cleaning the Ash (continued)

1.

2.

3.

Ensure that power has been turned OFF, and all "hot" components have been allowed to cool sufficiently.

(Allow at least one hour for the Combustion Sleeve to cool.)

Clean the ash from the stack components: a. Brush accumulated ash from the stack cap.

b. Lightly tap the stack components to loosen the ash.

c. Allow ash and dust to settle in the elbow on the stack.

NOTE: It is not necessary to remove the stack to clean it. You will vacuum ash from the stack elbow as you clean out the back of the furnace as described below.

d. Remove the clean-out cap from the unused furnace breach.

e. Thoroughly vacuum out the back of the furnace, including the stack elbow, through the clean-out breach. A long wand on the hose of your shop vac is helpful in reaching all the way through the back of the furnace to the stack elbow.

Clean the ash from the combustion chamber (see Figure 9D): a. Bleed down pressure on the air and oil lines by slightly loosening the fittings at the bottom of the connector block.

NOTE: Turn off the shut-off on the air pressure line.

b. With air and oil pressure completely bled off, disconnect the air and oil pressure lines from the bottom of the connector block.

NOTE: Cover the lines to keep dirt from entering the air / oil supply.

c. Remove the lock-down nuts on the clean-out door.

d. Carefully swing open the clean-out door to expose the heat exchanger flues and the combustion chamber. Carefully remove the Combustion Sleeve with a long handle or pipe. Lightly vacuum the

Combustion Sleeve.

e. Check the color of the ash--it should be light gray or tan.

ATTENTION: White ash indicates excessive air pressure. Black ash or soot indicates lack of combustion air. If these conditions exist, call your Clean Burn dealer. DO NOT over fire your furnace by turning up the compressed air. Overfiring will damage the combustion chamber and heat exchanger and will void your warranty.

f. Vacuum the ash from the combustion chamber and the flues.

ATTENTION: When cleaning the combustion chamber, ensure that you do not gouge or damage the refractory material on the inside of the clean-out door.

NOTE: Avoid "packing" the ash in the tubes by first vacuuming the flues before pushing the flue brush down the flues. DO NOT bump or bend burner components while cleaning the combustion chamber.

g. Use a flue brush to thoroughly clean the flues.

h. Thoroughly vacuum any remaining ash residue from the flues. Make sure the back (at the breach) is still clean.

i. Check the flues for rust.

ATTENTION: The presence of rust in the flues indicates that chlorinated materials are being burned. Burning chlorinated materials will severely damage your heat exchanger and void your warranty. Contact your Clean Burn dealer for instructions to test your oil for chlorine contamination before firing your furnace.

j. Inspect the inside of the clean-out door. Make sure the refractory material on the inside of the cleanout door is in good condition and the clean-out door seals tightly when closed. If the door does not seal tightly, replace any damaged components.

9-6

Operator's Manual: Model CB-140

Cleaning the Ash (continued)

k. Re-install the furnace components: Swing the clean-out door shut; install and tighten the lock-down nuts so that the door seals properly. Re-install the air and oil lines on the bottom of the connector block.

NOTE: You may need to bleed air from the oil line before starting the burner. See Section 5 for the pertinent instructions.

Annual Burner Tune-up

Your Clean Burn furnace requires annual periodic maintenance. The burner requires an annual tune-up

(similar to an automotive tune-up) to keep it running in peak condition. The burner tune-up should be

performed by a qualified Clean Burn service technician who has the necessary parts and expertise.

Contact your local Clean Burn dealer to schedule the annual periodic maintenance which is usually

(preferably) performed during warm weather to prepare the furnace for the next heating season. Various levels of service are provided to fit your particular need.

End of Season Maintenance

ATTENTION: Turn main power to your furnace OFF at the end of the heating season. EPA regulations allow your used oil to be burned only for "heat recovery." DO NOT operate your furnace during warm weather just to burn oil, or severe damage to the combustion chamber/heat exchanger may occur.

Contact your local Clean Burn dealer to schedule your annual burner tune-up. Allow only trained, authorized service personnel to service your burner.

1.

2.

3.

4.

Cleaning and Maintaining the Optional Draft Inducer

The Draft Inducer will require periodic maintenance to ensure that the fan blades do not accumulate excessive ash which can create vibration, noise, and motor wear.

Ensure that power has been turned OFF, and all "hot" components have been allowed to cool sufficiently.

Disconnect the wires from the draft inducer and remove it from the stack penetration.

Clean the fan blades with a scraper and wire brush.

Oil the draft inducer motor according to the manufacturer's recommendations.

9-7

Operator's Manual: Model CB-140

9-8

Operator's Manual: Model CB-140

SECTION 10: TROUBLESHOOTING

The following charts and tables are provided for reference in troubleshooting any difficulties encountered in furnace operation and adjustment.

• The Flow Chart outlines the proper sequence of events in furnace operation -- use this chart to help diagnose where a problem may be occurring.

• More specific troubleshooting information is provided in the Troubleshooting Tables following the flow charts. Each table lists a Problem, Possible Cause, and Possible Action(s) to fix the problem.

10-1

Operator's Manual: Model CB-140

Oil primary control checks for 2000+ ohms from cad cell indicating dark in the combustion chamber (NO FLAME) Oil primary control relay closes. Burner ignition sequence begins.

Oil primary control receives <500 ohm signal from cad cell indicating proper ignition.

Flame is established and igniter shuts of Burner continues to run until the wall thermostat is satisfied.

Primary control relay opens and the burner shuts of

FLOW CHART CB 140 115 V / 60 Hz

Pump circuit opens oil solenoid.

Pump circuit starts oil pump.

Pump circuit starts hour meter

When block temperature reaches 120 °F , the F120 proving switch closes and sends power to the oil primary control.

F120 proving switch remains closed and oil primary control has power

Fan switch sends power to Fan motor and fan starts.

Air sensing switch closes as it receives more than 10 psi of air pressure.

Air sensing switch receives power from centrifugal switch.

Preheater thermostat cycles 250 watt block heater element and maintains the block temperature.

Air regulator adjusted to proper psi of air pressure.

Combustion air band adjusted for proper combustion air

Centrifugal switch closes and sends power to air sensing switch.

Fan switch senses ON temperature (180 °F) and Fan switch closes.

Fan switch senses OFF temperature (160 °F) and Fan switch opens.

Main power ON sending power to both high limit switches.

Burner cable plugged in.

Green indicator light ON.

14,000 volt igniter starts, providing spark at electrode gap.

Air solenoid opens.

Burner motor starts and reaches full rpm.

10-2

Fan switch on combustion chamber senses temperature rise as the burner fires.

Fan continues to run to drive latent heat from the heat exchanger

Operator's Manual: Model CB-140

PROBLEM

Burner won't run at all and green power light is NOT ON

POSSIBLE CAUSE(S)

1. Circuit breaker / main switch open

2. Fuse / breaker blown

3. Burner cable is damaged or not plugged in properly.

POSSIBLE ACTION(S)

1. Close circuit breaker / switch.

2. Electrician should check out electrical system

3. Check burner cable.

Burner won't run at all and green power light is ON

1. Oil primary control has shut down on safety reset.

2. Wall thermostat is not operating

3. heater block is not heating up

4. F-120 proving switch has not closed.

5. Oil primary control terminals are not wired correctly

6. Oil primary control is damaged.

7. The L290 or L-290 limit switches have opened.

1. Follow the directions in Section 7 to reset the oil primary control.

2. Check the wall thermostat and thermostat cable.

3. Feel the heater block; it should be at least 120 ºF. If the heater block is NOT HOT: (a) wait 15 minutes for the heater block to heat up and re-check, and (b) check the block heater thermostat and block heater element. Refer to the wiring diagram and ladder schematic in appendix B.

4. If the block is HOT: (a) check the red wire going to the F-120 proving switch in slot #13, of the terminal block for power. refer to the wiring diagram and ladder schematic in Appendix B to troubleshoot the circuit that provides power to the proving switch. (b) if there is power at #13 going to the proving switch check for power at the red wire in slot #4 on the terminal block. If there is

NO power at #4, replace the F-120 proving switch.

5. Check the oil primary control:

(a) Check that the "F" terminals are NOT jumped. (b) check that the two yellow cad cell wires are connected to the "F" terminals.

(c) Check that the two thermostat wires are connected to the "T" terminals.

6. Replace oil primary control: (a)

Check voltage - it must be 115 volts.

7. Test the switch for power. Note that power should be indicated on both sides of the switch. See section 7.

10-3

Operator's Manual: Model CB-140

PROBLEM

Burner ignites but will not stay running and burner shuts off on reset within 15 seconds.

POSSIBLE CAUSE(S)

1. There is a fuel delivery problem.

2. The cad cell is dirty.

3. Cad cell wires are loose

4. Cad cell / cad cell wires are damaged

5. The primary control is not receiving the proper ohm signal from the cad cell.

Burner ignites and runs properly, but the burner shuts off on reset periodically (e.g. the burner goes off on reset during the night and requires resetting in the morning).

1. There is air in the suction oil line due to leaks at the fittings

2. There is air trapped in a high point in the pressure oil line.

POSSIBLE ACTION(S)

1. Follow the procedures listed in the next problem

2. clean and check the condition of the cad cell and cad cell wires.

3. check that the yellow wires are connected properly at the "F" terminals on the oil primary control.

4. Replace the cad cell and cad cell wires. If the cad cell is heat damaged: (a) clean your furnace, including the combustion chamger, flues and stack. Refer to instructions in section 9. (b)

Check for backdraft caused by exhaused fans in your building.

Follow instructions in Section 8.

5. Disconnect the yellow wires from the "F" terminals. Start the burner and check the ohm reading from the cad cell. You have 10 seconds to perform this test before the burner shuts off on reset. Refer to

Section 7 to reset the oil primary control. If the ohm reading is above 500 ohms: (a) check the position of the cad cell; the cad cell must "look" straight through the central hole in the retention head. (b) Check the position of the retention head according to

Appendix A.

1. Follow the procedures in Section 5 to vacuum test the pump. Reinstall and properly seal the suction line fittings to eliminate air leaks.

2. Bleed the air out of the pressure oil line.

10-4

Operator's Manual: Model CB-140

PROBLEM

Burner ignites and Burner shuts off on reset sometime later during the day or night.

POSSIBLE CAUSE(S)

1. There is air in the fuel supply.

2. The primary control is not receiving the proper ohm signal from the cad cell.

3. There is insufficient air pressure.

4. The heater block is cold.

5. The electrodes are fouled.

POSSIBLE ACTION(S)

1. Prime the pump. If the pump will not prime or there is air in the oil stream from the pump bleeder, follow the steps in the next problem (“Pump will not prime.”)

2. Check for proper ohm signal.

Follow the procedures in the previous problem (top, page 10-4)

3. Follow the instructions in Section to adjust the air regulator for proper air pressure. DO NOT turn the air compressor off while the furnace is operating. If you turn the air compressor off at night, turn the wall thermostat to OFF so the burner will not run.

4. DO NOT shut off power to the furnace overnight, or the heater block will cool down, and the burner will not re-start the next morning. To turn the furnace “off” overnight, turn the wall thermostat to OFF. The heater block will stay hot.

5. If oil residues have built up on the electrodes and retention head, follow the instructions in Section 8 to check for proper draft overfire.

Clean the electrodes and retention head as shown in Appendix A.

10-5

PROBLEM

Pump will not prime and Pump motor is running.

Operator's Manual: Model CB-140

POSSIBLE CAUSE(S)

1. There is a leak(s) in the suction line.

2. The pump is not installed so it will

4. The pump seal is damaged. fill with oil during the priming process.

3. The pump gears are dry.

5. The ball valve is closed.

6. The canister filter is dirty.

7. The check valve is dirty.

8. The pump is damaged or worn out.

POSSIBLE ACTION(S)

1. Follow the specifications in Section

4 to make sure the suction line is installed properly and that all fittings are 100% airtight.

2. Make sure the pump head is filled with oil prior to starting the pump.

See Section 5.

3. Follow the procedure in Section

5 to fill the oil line and prime the pump.

4. With the pump not running, wipe your finger along the bottom of the cylinder at the pump shaft. If there is oil at the pump shaft, the seal is damaged. Replace the pump, or replace the seal

NOTE: Some oils will expand as they warm up. Because there is a check valve in the suction line, the expanding oil may build up pressure and damage the oil seal.

Install a mini-accumulator in the

1/8” port of the canister filter to prevent the pressure build-up.

5. Open the ball valve on the suction line.

6. Refer to Section 9 to clean the canister filter.

7. Refer to Section 9 to clean the check valve.

8. Replace the pump.

10-6

PROBLEM

Pump will not prime and Pump motor is

NOT running.

Fan motor runs all the time.

Fan motor will not run.

Operator's Manual: Model CB-140

POSSIBLE CAUSE(S)

1. There is NO power on the pump circuit from the burner.

2. The pump motor has shut off on thermal overload.

1. Fan motor circuit is wired incorrectly.

1. The fanmotor is not wired correctly.

2. The Blower / Fan switch is defective

3. The fan motor has overheated and shut down on thermal reset.

POSSIBLE ACTION(S)

1. Start the burner and adjust the air pressure regulator to 15 PSI. (a)

Refer to the wiring diagram and ladder schematic in Appendix B to troubleshoot the pump circuit from the burner to the pump. (b)

With the burner running, check for power at the wires on the air pressure switch. If there is NO power at the air pressure switch, replace the burner motor. If there is power at the air pressure switch, replace the air pressure switch.

2. (a) The pump motor is too hot: the internal thermal protection switch shut the motor off. Wait for the motor to cool down; the thermal switch will automatically reset. Check voltage and amperage draw of the pump motor. Call your dealer if the problem persists.

(b) The coupling is not adjusted properly, keeping the shafts of the motor and pump from turning freely. Re-position the coupling so that both shafts turn freely. (c) The shaft on the motor or oil pump will not turn freely. If you can’t turn the shafts, replace the faulty part(s).

1. Refer to wiring diagram and ladder schematic in Appendix B to troubleshoot the fan motor circuit.

1. Check the fan motor wiring. Refer to the wiring diagram and ladder schematic in Appendix B. Follow the directions in Section 6 to test for proper fan operation. If the fan does not operate, shut OFF power to the furnace and call your Clean

Burn dealer for service.

2. Replace the Blower / Fan switch.

3. The fan motor is too hot : the internal thermal protection switch shut the motor off. Wait for the motor to cool down; the thermal switch will automatically reset.

Check voltage and amperage draw of the fan motor. Call your dealer if the problem persists.

10-7

Operator's Manual: Model CB-140

10-8

Operator's Manual: Model CB-140

APPENDIX A

Detailed Furnace Specifications

FURNACE MODEL

BTUH Input

Listed Fuels:

CB-140

140,000*

@ 1.0 GPH

#2 Fuel Oil

#4 and #5 Fuel Oils (U.S.)

Used Crankcase Oil

Used ATF (U.S.)

Used Hydraulic Oil

47.25 x 32 x 20 Cabinet Dimensions

(LxWxH) inches

Furnace Dimensions w/ fan, Burner, and Louvers

(LxWxH) inches

Approximate Weight

(complete furnace system – uncrated)

Mounting (NFPA-31)

61.25 x 32 x 31.5

220 lbs.

Electrical Requirements

(VAC @ 60 Hz)

Circuit Breaker

1. Ceiling hung

2. Raised platform

3. Bench Tank Kit

115

20 amps

Wall Thermostat 24 volt

Oil Pump

Oil Pump Motor

Pump Motor Rotation

Canister Filter

Stack Size

Fan Motor HP

Blower/Fan Switch

Hi-Temp Limit Switch

Auxiliary Hi-Temp Switch

Approx. Air Compressor

Requirements

Suntec

A2RA-7720

Bison Gear Motor

1/20 HP

CCW shaft end

Lenz

DH 750-100

6”

1/4 HP

F180

L200

L290 (Auto-Reset)

2.5 CFM

@ 30 PSI

* Nominal values; actual values may vary depending on installation.

A-1

Operator's Manual: Model CB-140

Burner Technical Specifications

Burner

Ignition Transformer

Nozzle

Burner Motor

Burner Motor Rotation

Compressed Air Requirements

Oil Primary Control

Heater Element in Preheater Block

Air Pressure Switch

Preheater Temperature Switch

CB-125

Carlin Transformer 14,000 Volts

Delavan 9-5

1/10 HP 3200 RPM with centrifugal switch

CCW shaft end

2.5 CFM @ 30 psi

Carlin Oil Primary

280 Watts

MPL 808

L-150

A-2

CB-140 Dimensions

9.5"

20"

47.25"

Operator's Manual: Model CB-140

10.38

26"

32"

39.25" 6.62"

MOUNTING HOLE DIMENSIONS

28"

29.5"

I89105-A

A-3

Burner Components

24

Operator's Manual: Model CB-140

1

2

19

23

22

21

6

20

3

4

5

6

7

8

18

17

16 15 14

13

I89137

11

12

10

9

FIGURE A1 - Burner Component Detail

A-4

Operator's Manual: Model CB-140

Burner Components (continued)

ITEM# DESCRIPTION

1 26136

2 26135

COVER

COVER 125

TERMINAL 3 33247

4 14088

5 11308 RETENTION

6 26078 LID

BLOCK

CONNECTOR

HEAD

7 11633

8 33400

TAB

HOUSING

PRIMARY

9 33175 BLOWER

SEC, WIR

10 26044

MOTOR

MOTOR

11 31113

12 12159

13 26141

14 33297

FAN

BLOWER

COVER

HOUR

MOTER

15 33168

16 33169

METER,

AMBER

GREEN

17 11359

18 26103

AIR

AIR

19 13183

20 33105

OUTER

HEATER

SNAP

21 33116 CAD

22 26056

23 31284

24 33189

CELL

CAD

HINGE

BRACKET

1.5 4.25

ELECTRIC

A-5

Operator's Manual: Model CB-140

Burner Components (continued)

28

27

26

25

29

40

39

38

41

34

33

32

31

30

37

36

35

42

45

46 47 48

49

1

43

44

22

2

3

5

6

5

4

24

23

22

21

5

20

19

5

18

17

16

15

14

13

12

11

10

9

7

8

I89136

FIGURE A2 - Preheater Block Assembly Component Detail

A-6

Operator's Manual: Model CB-140

Burner Components (continued)

ITEM# PART# DESCRIPTION

1 32000

2 34436

3 26134

4 26140 GUIDE

5 32199 1/16

TEMPATURE

NPT

PROVING

L-150

SWITCH

NUT

9 33319

10

11

COIL

12

WASHER

33317

13

14

FLUXPLATE

PLUNGER

33315

15

PLUNGER

16

BODY

33313

17

18

MANIFOLD

SOLENOID

33311

19

SOLENOID

20

AIR

33298

21

22

23

24

140

32505

32042

32007

25

26

32202

1/8X 2 1/2 RND BRS NIPPLE

ST EL 90 1/8F 1/8M NPT

PLUG,HEX

SQ.

PIPE

27

28

FEMALE ELBOW (3/8 OIL LINE)

1/8

SQ. OIL GAUGE, 0-15 PSI 29

30

32178

POPPET

32222

32223

32305

VALVE

RING

32225

POPPET

DIAPHRAGM

32226

36 32227

37

38

39

40

41

42

43

44

33310

45

46

32201

34070

34326

47

33183

49

FEMALE ELBOW (3/8 OIL LINE)

SET SCREW 1/4 X 1/4

A-7

Operator's Manual: Model CB-140

Burner Components (continued)

BURNER NOZZLE

SIDE VIEW - AA

NOZZLE IS STAMPED

EITHER 9-5 OR -5 ON

FLAT OF NOZZLE HEAD

3/16" GAP BETWEEN

ELECTRODES & NOZZLE

CRITICAL DIMENSION:

NOZZLE MUST BE 1/8"

AHEAD OF THE DISK.

NOZZLE MUST NOT BE

BEHIND THE DISK.

3X

SIDE VIEW - BB

VIE

W - BB

VIE

W - AA

1/8"

SPARK

GAP

FIGURE A3 - Burner Electrode Component Detail

I88340-B

A-8

Operator's Manual: Model CB-140

Burner Components (continued)

HEAD

DISTRIBUTOR

Nozzle

CB-125 Delavan 9-5

STEM

NOZZLE SIZE IS

STAMPED ON

FLAT OF

NOZZLE HEAD

ORIFICE

O-RING

I88378

Removing the Nozzle for Cleaning:

1.

2.

3.

4.

Remove the lock-down nut on the mounting flange bolt.

Disconnect power from the burner.

Carefully swing the burner open to its maintenance position.

Remove the nozzle from the nozzle adapter with a 5/8" socket.

Cleaning the Nozzle:

1.

2.

3.

6.

7.

4.

5.

8.

9.

Unscrew the stem from the nozzle head.

Spray WD-40 or equivalent through the orifice to thoroughly remove any blockage.

ATTENTION: DO NOT damage or deform the nozzle orifice; DO NOT use a torch tip cleaner or other inappropriate device to clean the orifice. If the blockage is a "tarry" material or a hard, black material, call your Clean Burn dealer for service.

Flush all components with WD-40 to remove oil residues.

Reassemble the nozzle components. When tightening the stem, just barely "snug" it down.

DO NOT overtighten.

Check the O-ring on the nozzle stem. Replace the O-ring if it is in the least bit cut or deformed.

Lubricate the O-ring on the nozzle stem with a couple of drops of new motor oil, then re install the nozzle.

Check the electrodes for proper gap and clearances.

Re-install the burner and adjust for optimal performance as described in Section 6.

NOTE: If the nozzle plugs within a few days after cleaning, call your Clean Burn Dealer for service.

FIGURE A4 - Cleaning the Nozzle

A-9

CB-140 Cabinet Components

Operator's Manual: Model CB-140

34

33

CB-140

35

32

31

30

29

DETAIL A

22

33

34

36

28

27

26

23

25

21

20

37

38

B

24

48

11

42

41

40

39

DETAIL B

45

46

47

44

43

1

2

19

18

17

11

16

A

15

14

13

12

11

10

9

7

8 (OPTIONAL)

6

5

4

3

I89107-A

A-10

Operator's Manual: Model CB-140

CB-140 Cabinet Components (continued)

ITEM #

1 29212

2

3

PART #

29210

70479

BREECH

5 23093

6

7 29149

8

9

10

11

12

13

14

15

16

17

34191

90244

21185

34119

34118

34095

21056

11582

34120

11583

DESCRIPTION

SHROUD REAR 140

DUCT CAP 6" 24 GA GALV

6"

CB-125

140

3X33.75

3/8-16 X 3/4 CARRIAGE BOLT

AIR DISCHARGE HOOD 140 A

COMBUSTION SLEEVE & FEET 140 A

3/8-16 X 3 HHCS GR-2 ZINC

5/16-18 X 3/4 HEX WASHER HEAD

3/8-16 STOVER L/N

HINGE BRACKET GALV

HINGE BRKT 3DEG BURNER WA - USE W 11583 MOUNT

A

5/16-18 X 2 3/4 CARR BOLT SS

21076

BURNER MOUNT 3 DEG WA - USE WITH 11582 BRACJET

PORT

22

23

24

11325

CAP

INSPECTION

20

21 31275

12314

33336

25

26

33273

33286

27

33486

INSULATINO DOOR 140

SLEC PRIME SW BOX A

CONNECTOR 90 DEG SNAP-TITE (3/8 FLEX CONDUIT)

SWITCH DPDT ON-ON

28

29

30

31

32

33

34

35

36

37

38

21183

34051

32039

13188

32304

32303

13187

E-BOX FOR PRIME SWITCH

E-BOX

5/16-18 X 1 1/2 HHCS ZINC

CONNECTOR

ADAPT 1/4 OD X 1/8 P

AIR LINE 125 A

NUT LONG 3/8 COMP

SLEEVE 3/8 COMPRESSION

32245

12057

OIL LINE 125 A

SWIVEL 1/4 NPTM, 1/4 NPTF

29090

FLEX CONDUIT RW 3/8 X 23 1/2

SWITCH

39

40

41

42

43

33390

44

45

46

47

48

33288

29064

33230

29067

33586

140

31125

31274

21057

11589

COVER

AUXIL HI LIMIT-AUTO RESET 290

MOUNT FAN START SWITCH

FAN - TEMP SWITCH

BRACKET TEMP HI LIMIT

ASSEMBLY

MOTOR - 1/4 HP FAN

FAN

FAN 3-BLADE 20 IN DIA 20 DEG PITCH

HINGE BRACKET GALV

CB 140 FURNACE WA

A-11

Metering Pump Components

Operator's Manual: Model CB-140

29

17

18

19

20

16

13

N I

SUPPLY

TO BURNER

6

7

8

RETURN

TO TANK

5

4

10

9

GAUGE

INLET

RELIEF

ROT

ATIO

N

11

3

30

31

2

12

OUT

GAUGE

A2RA

INLET

R.H. ROT

ATION

14

PACKAGED WITH

CLEAN BURN

EQUIPMENT

15

1

21

22

23

24

25

26

SINGLE PIECE OF

COPPER TUBING

(USER SUPPLIED)

24

23

16

27

PACKAGED WITH

CLEAN BURN

EQUIPMENT

28

I89112-A

A-12

Operator's Manual: Model CB-140

32430

32446

32429

32137

32142

32062

32443

32141

32140

32139

32442

32021

32061

32445

32423

32422

PART #

33363

33291

11322

32037

N/A

N/A

N/A

N/A

32526

32475

32467

32210

32336

32123

32127

Metering Pump Components (continued)

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

ITEM #

1

2

3

4

5

6

7

8

9

10

11

DESCRIPTION

CAPACITOR

GEAR MOTOR CB-140

MOUNT METER PUMP A

1/8 NPT X 1/4 TUBE COMPRESSION FITTING

1/4 COPPER OR ALUMINUM TUBING

3/8 OR 1/2 TUBE FLARE NUT

3/8 0R 1/2 COPPER OR ALUMINUM TUBING

1/8 M NPT X 3/8 OR 1/2 FLARE

MINI BALL VALVE 1/8 MNPT X 1/8 FNPT

PUMP-METERED OIL

NIPPLE 1/4 NPT X 3 ROUND BRASS

ST EL 90 1/4F-1/4M NPT

BUSHING 3/4 X 1/4 BR.

GAUGE (LENZ)

CANISTER FILTER

BUSHING 3/4" X 1/2"

NIPPLE 1/2 X 5"-BRASS

TEE 1/2" BRANCH

EXTERNAL PIPE ADAPTER

BALL VALVE 1/2 NPT

MALE CONNECTOR 1/4 TUBE

BUSHING 1/4 X 1/2" BRASS

FLARED TUB.TO PIPE STRAIGHT

LONG NUT 1/2

TUBE TO PIPE MALE STRAIGHT

BUSHING DUPLEX SLIP THRU

CHECK VALVE

CHECK VALVE SCREEN 3/4"

PIPE CAP 1/2"-BRASS

SCREEN PUMP (M PUMP)

GASKET COVER (M PUMP)

33297

21182

HOUR METER (60 Hz)

MTR PUMP COVER FOR HOUR METER

A-13

Operator's Manual: Model CB-140

A-14

Wiring Diagrams

Operator's Manual: Model CB-140

APPENDIX B

PRIME PUMP RUN BURNER

BLK

WHITE

4 5

Wht HT

Wht HT

Red /

Red /

HIGH LIMIT

HIGH LIMIT

B-1

Operator's Manual: Model CB-140

Wiring Diagrams (continued)

WHITE

BLACK

TER

TER

140 W HEA

140 W HEA

FIGURE B2 - CB-125 Burner Wiring Diagram

B-2

BLACK

BROWN

WHITE

Operator's Manual: Model CB-140

OPTIONAL SERVICE

DISCONNECT SWITCH

MODEL CB-140

HOT NEUTRAL

FAN SWITCH

(METAL SURFACE: 33230)

D P D T

TOGGLE SWITCH

ON FURNACE CABINET

TOGGLE DOWN : BURNER

TOGGLE UP : PRIME

HI LIMIT TEMP SWITCH N/C

(ON METAL SURFACE:33390)

SECONDARY TEMP SWITCH N/C

PRIME BURNER

(ON METAL SURFACE:33288)

FAN MOTOR

M 1

OIL PUMP MOTOR

M 2

DRAFT INDUCER

MOTOR (OPTIONAL)

GRN

WHT

RD

BK

A

C

E

F

U

R

N

- CONNECTION TO

CUSTOMER POWER

WHT

GRN

BK

RD

PROVING SWITCH

120°

AIR COMPRESSOR (OPTIONAL)

WALL

THERMOSTAT

CAD

CELL

BK F

OR

BL

F T

OIL

PRIMARY

CONTROL

T

WHT

IGNITION TRANSF.

SPARK GAP

AIR SOL.

BURNER MOTOR

M 3

OIL SOL.

AIR PRESSURE

CENTRIFUGAL SWITCH

B

U

R

N

E

R

BLOCK TEMP. SWITCH

150°

250 WATTS BLOCK HEATER

POWER ON

G

I44125

FIGURE B3 - Ladder Schematic for CB-140 with CB-125 Burner (120 Volts / 60 Hz)

B-3

Operator's Manual: Model CB-140

Wiring Diagrams (continued)

ENCLOSED J-BOX

GRN

BLUE

GROUND

HOUR

METER

RED

BLK

L 2 (WHT)

L 1 (BLK)

BLK

BLK

* 115 V 60 HZ POWER FROM OIL PUMP CIRCUIT

SEE FURNACE SCHEMATIC

Figure B4 - Metering Pump Wiring Schematic

I42533

*

B-4

Operator's Manual: Model CB-140

Understanding the Oil Primary Control

Model 40200 / 42230 Cad Cell Oil Primary Control Data Sheet

Model 40200/ 42230 CAD Cell Oil

Primary Control Data Sheet

• Oil pump bleed assist up to 1 min.

C77009

• Thermostat/aquastat compatible

• Serviceman Reset Protection

Latch-up after 3 consecutive lockouts

• Diagnostic LED’s

• 15-second TFI/ 30-second TFI

• Improved SMC Technology zero bleed voltage during standby

• Works well with generators

Insensitive to frequency changes

• Flame Stabilize

Power input (from limit circuit)

Motor load

Ignitor load

Operating temperature limits

120 VAC, 60 HZ, 10 VA

10 FLA/ 60 LRA

120 VAC, 60 HZ, 500 VA

+32°F to +140°F

Storage temperature limits

-40°F to +185°F

Thermostat anticipator current 0.1 A, AC

Cad cell resistance

R < 1500 OHMS

Agencies

UL recognized (US & Canada)

Installing and wiring

Warning

1. Always disconnect power source before wiring to avoid electrical shock or damage to the control. All wiring must comply with applicable codes and ordinances.

2. Thermostat terminals (T–T) provide a current source. Never apply external power to these terminals under any circumstances.

Mounting

• The control may be mounted on a 4” x 4” junction box in any convenient location on the burner, furnace or wall. The location must not exceed the ambient

temperature limit, 140°F.

Wiring

• Wiring must comply with local and national electrical codes, and with the wiring diagram.

L2 L2 L2

Field checks

1. Safety timing (TFI) test — Remove one cad cell wire (F-F). Start burner.

The control should lockout within the TFI time limit. Replace cad cell wire.

2.

Flame failure test

LIMIT IN

120V, 60 HZ

as described on the reverse side of this Data sheet. The control should recycle (restart after 65 seconds).

3. If control does not operate as described, check the wiring.

LINE

HEAT-

ER

MOTOR

10FLA

60LRA

IGNITOR

500VA

VALVE

Start-up & operation

Model 40200/42230 diagnostic LED’s contains oil or oil vapor.

– Amber OFF

– Green OFF

– Amber ON

– Green ON

– Amber FLASHING

– Green FLASHING

– Red OFF – Red ON – Red FLASHING

The amber LED

every 3 to 4 seconds & green LED will be on or blinking.

Power ON Open all manual oil line valves. Close the line switch.

Self-test 1 The control performs a “boot-up” test to verify internal operation each time power is applied to the black wire. The amber LED turns on and the test continues for about 5 seconds. If the test fails, the control turns the amber LED off and repeats this test sequence until successful.

Stand-by (No call for heat) If Self-test 1 is successful, amber LED turns off and control waits for heat call.

Call for heat Set thermostat and limit to call for heat. Thermostat circuit must be closed and power coming to black wire from limit circuit.

Burner on After the self-test, amber LED turns off. The ignitor starts, followed 2 seconds later by the motor.

B-5

Operator's Manual: Model CB-140

Understanding the Oil Primary Control (continued)

Model 40200 / 42230 Cad Cell Oil Primary Control Data Sheet

Start-up & operation continued...

C77010

Pump Prime To enter pump prime: 1. Start a CFH cycle. During Pre-Ignition or Pre-Purge, press Reset until motor turns off (10 seconds), then in Pump Prime, release Reset button.

Optional Pump Prime notes: 1) If lost, press Reset for 1 second and release, then if the control is not in Pump Prime, restart the se-

Reset button is pressed.

TFI

Run The burn

Lockout lockout occurs. The control turns the red LED on

To Reset

Latch-up constant, and closes the alarm contact.

Push in and hold reset button for 2 seconds, then release.

If the control locks out 3 times during a single call for heat, latch-up occurs. The control turns on both the amber and red LED’s constant. You must use the special procedure below to reset the control after latch-up.

repeated burner lockouts must be corrected before returning the burner to normal operation.

Flame failure

the control will restart (releasing the button before the LED’s turn off will cause the control to remain in latch-up).

The 40200 & 42230 controls will retain lockout or latch-up if power is interrupted.

Recycle: Control waits for 65 seconds (with f .

Stand-by Control remains in stand-by mode until limit circuit sends power to the black wire and thermostat circuit closes (call for heat).

Service & Troubleshooting

Burner (control) will not come on

No power to control

• Check limit circuit to the control (at least 102

VAC

).

• Check all electrical connections.

Control is in lockout

• Red LED will be on. Press the reset button for 2 seconds.

CAD cell seeing light

• Green LED on, and amber LED blinking 1 second on, 4 seconds off. Remove one yellow lead from FF terminals. If the amber LED

If the amber LED goes OFF, the control is OK, and;

• light is leaking into the burner housing,

OR

• CAD cell is defective,

OR

• there is a problem with the CAD cell wiring or holder.

• If appliance was recently shut down, CAD cell may see residual hot spots in chamber.

To troubleshoot:

• Attach multimeter to monitor CAD cell resistance. Dark

resistance should be over 50K ohms, and room light resis-

Replace cell if necessary, or reinstall and close the burner housing.

• Check for stray light by measuring the CAD cell resistance

looking into the inactive combustion chamber. It should read at least 50

KOHMS

.

Other no start problems

If the CAD cell is OK, and the amber LED still blinks 1 second on, 4 seconds off, the other possible failures include:

• on, 1/2 second off, 1 second on, 3 seconds off, then repeats).

Check line voltage.

• Internal fault: CAD cell, and line voltage OK, the issue may be an internal fault . Replace the control.

Check for:

• CAD cell is defective. Replace.

• check for proper air band setting and draft.

Control locks out at end of TFI ( red LED on)

Check for:

• Shorted electrodes- inspect for cracked porcelain and replace as needed.

• Poor spark- check electrode spacing and condition per burner manual. Replace or realign if necessary.

• Nozzle clogged- replace nozzle.

• Ignitor module defective- replace if no spark.

• CAD cell defective

• Oil valve (if used) stuck in closed position.

• Check wiring connections.

-

B-6

Operator's Manual: Model CB-140

APPENDIX C

Furnace Service Record

Furnace Purchased: Date __________ From (name/phone)________________________________

Furnace Installed: Date __________ By (name/phone)__________________________________

Furnace Inspected: Date __________ By (name/phone)__________________________________

Note: Refer to Section 9 for Maintenance Instructions

Draft Readings Service Record

(Date / Draft) (Date / Initials of Technician)

Burner Stack Canister Metering Check Valve Chamber Stack Oil Tank A.P.M.*

Filter Pump and Screen & Flues

*A.P.M. is Annual Preventative Maintenance on the Burner (Burner Tune-up)

C-1

Operator's Manual: Model CB-140

C-2

Was this manual useful for you? yes no
Thank you for your participation!