DS DALI RM en
luxCONTROL lighting control system
comfortDIM
DALI RM
DALI control module for 1 relays
Product description
•Control of one standard contactor
•5-year guarantee
È
Wiring diagrams and installation examples, page 4
Data sheet 10/15-CO050-3
Subject to change without notice.
www.tridonic.com
1
luxCONTROL lighting control system
comfortDIM
DALI RM
DALI control module for 1 relays
Ambient temperature ta
0 ... +50 °C
Type of protection
IP20
11
Technical data
41
30
30
3
3
Ordering data
Type
Article number
Packaging, carton
Weight per pc.
DALI-RM
24034702
1 pc(s).
0.087 kg
Specific technical data
Type
Inputs
Output, relay
DALI control input
Current draw
Number of DALI
addresses
Max. switching
voltage AC
Max. switching
voltage DC
Type of contact
Min. contact load
1
12 mA from DALI
1
250 V
35 V
1 changeover
1.2 W
DALI-RM
Data sheet 10/15-CO050-3
Subject to change without notice.
www.tridonic.com
2
luxCONTROL lighting control system
comfortDIM
DALI standard
The DALI RM is designed to control control gear
with DALI standard IEC 60929 (DALI V0) .
Glow-wire test
according to EN 60598-1 passed.
Functional description:
• Compact relay module for controlling a standard
contactor via DALI.
•Loads that do not have a DALI input can therefore
be integrated in the DALI circuit. The loads can be
switched on and off via DALI.
•“masterCONFIGURATOR” software is available free
of charge at www.tridonic.com for programming
the switch-on and switch-off points.
“MIN LEVEL”: Sets switch off level
“MAX LEVEL”: Sets switch on level
Factory preset:
“MIN LEVEL” = 0 → OFF
“MAX LEVEL” = 100 → ON
Installation:
•Loads must not be connected directly to the DALI
RM. The load must always be switched via an
external contactor.
•The maximum load that can be connected to the
DALI RM is the load of a contactor coil.
•When selecting the correct contactor please check
the inrush currents of the switched loads. Electronic ballasts may have very high inrush currents.
Check with the contactor manufacturer.
•If DC contactor coils are controlled they must
be equipped with an appropriate free-wheeling
diode.
•This is not a separate unit, it is intended for
installation.
•DALI is not SELV. The installation instructions for
low voltage therefore apply.
DALI
DALI RM
N.O.
N.C.
COM
Circuit diagram
Data sheet 10/15-CO050-3
Subject to change without notice.
www.tridonic.com
3
luxCONTROL lighting control system
comfortDIM
Switching of 12/24 VDC contactor coils
L
N
+
-
230V
24V
F1
DALI
PS
PCA EXCEL one4all
PCA EXCEL one4all
DALI RM
LAST
DALI
DALI
GC
DALI
SC
DALI
USB
Switching of 230 VAC contactor coils
L
N
230V
F1
DALI
PS
PCA EXCEL one4all
PCA EXCEL one4all
DALI RM
LAST
DALI
DALI
GC
DALI
SC
DALI
USB
Data sheet 10/15-CO050-3