AMYB-1840/5840/E840

AMYB-1840/5840/E840
Moniteur
Dimensions
SENTINEL VPT Specification
AMYB-1840 / AMYB-5840 / AMYB-E840
Top View
Side View
OPEN
MONITEUR
6.56
NAMUR
STD.
A
0.156
0.249
B
0.62**
0.53
O
P
E
N
3.98
1.13*
MONITEUR
2.72
3/4 NPT
B
* - FLAT COVER DIMENSION
** - LONG NAMUR = 1.28"
6.00
A
2.25
SQ. BOLT PATTERN
5/16-18 (4X)
General Specifications
How To Specify
Nema Rating
Housing / Cover
Indicator Cover
Seals
Fasteners
Terminal Points
Weight
Operating Temp.
Valve position transmitter shall be Moniteur model AMYB-1840/5840/E840.
Enclosure shall be aluminum with a polyurethane coating and rated Nema
4, 4x, 7, 9. Visual indicator shall have 100% display change, 360° visibility
and full set point adjustability. Indicator cover shall be free of decals or paint
and sealed with an O-ring. Enclosure shall have captive cover bolts.
Enclosure shaft shall be attached to a sintered brass housing bearing with
an internal stainless steel locking ring, environmentally protected with an Oring. The sensor type shall be P&F NJ2-V3N NAMUR type rated Intrinsically
Safe. A total of four (4) switches shall be included along with 14 terminal
points. All terminals must individually marked for identification. Terminal
strip must be angle-mounted for easier installation.
4, 4x, 7, 9
Aluminum
Ektar
BUNA-N
Stainless Steel
14
4.25 lbs.
-40° F to 175° F
RIGHT
UPPER
8
BLUE
(-)
7
SWITCH 3
BROWN
(+)
5
BLUE
(-)
4
SWITCH 2
4
2
LEFT
UPPER
RIGHT
LOWER
3
1
BROWN
(+)
2
BLUE
(-)
BLUE
(-)
1
SWITCH 1
BROWN
(+)
BROWN
(+)
LEFT
LOWER
Wiring Diagram
10
11
SWITCH 4
OPTIONAL
SOLENOID
VALVE
13 14
SOL
Agency Approvals: FM Intrinsically Safe (Sensors Only)
Class 1, Division 1 & 2, Group A, B, C & D
Class 2, Division 1 & 2, Group E, F, G
GROUND
Enclosure Rating: Explosion-Proof
Class 1, Division 1 & 2, Group C & D
Class 2, Division 1 & 2, Group E, F, G
Part Number Description
A M Y B - 5
Series
Description
Series: Sentinel
Cover
Code
A
Cover
With Moniteur
M
Moniteur
Black / Yellow
Y
Bearing
Bronze
B
Moniteur
Bearing
Shaft
8
4
0
Switch
Quantity
Conduit
Description
Code
Shaft
Standard 303 SS, 1/4” flats
Low Profile NAMUR 303 SS
Standard NAMUR 303 SS
1
5
E
Switch/Sensor Type
Pepperl & Fuchs NJ2-V3N
NAMUR Sensors - FM
approved Intrinsically Safe
8
Description
Code
Switch Quantity
4
Conduit
(2) 3/4" F NPT
0
M O N I T E U R
D E V I C E S
I N C O R P O R A T E D
3 6 C o m m e rc e R o a d , C e d a r G ro v e , N J 0 7 0 0 9 Te l . ( 9 7 3 ) 8 5 7 - 1 6 0 0 F a x ( 9 7 3 ) 8 5 7 - 7 2 8 9
w w w . m o n i t e u r d e v i c e s . c o m
Form H1-1299