E31 CT Adapter Board Kit

E31 CT Adapter Board Kit
INSTALLATION GUIDE
POWER MONITORING
TM
E31CTDB
E31CTDB
Adapter Boards for
E31 Panelboard Monitoring System
quick install
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
1. Disconnect and lock out power. Use a properly rated voltage sensing device to
confirm power is off.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•
•
•
•
•
Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
This equipment must only be installed and serviced by qualified electrical personnel.
Read, understand and follow the instructions before installing this product.
Turn off all power supplying equipment before working on or inside the equipment.
Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
2. Mount the adapter boards in the electrical enclosure using either DIN Rail or
SNAPTRACK.
3. Connect adapter boards to the main board via ribbon cable (sold separately).
4. Connect current transducers to the adapter boards (sold separately).
5. Secure wires using strain relief cable ties.
dimensions
1.00”
(26 mm)
Failure to follow these instructions will result in death or serious injury.
NOTICE
•
•
•
•
This product is not intended for life or safety applications.
Do not install this product in hazardous or classified locations.
The installer is responsible for conformance to all applicable codes.
Mount this product inside a suitable fire and electrical enclosure.
1.5”
(37 mm)
2.75”
(70 mm)
1.00”
(26 mm)
4.6”
(117 mm)
0.73”
(19 mm)
FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found
to comply with the limits for a class B digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a residential environment. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used
in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area may cause harmful interference in which case the
user will be required to correct the interference at his own expense.
Modifications to this product without the express authorization of
Veris Industries nullify this statement.
Product Identification
E31CTDB
Adapter Boards for E31
Z205768-0B
PAGE 1
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
07121
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
INSTALLATION GUIDE
E31CTDB
TM
Installation
B. SNAPTRACK: Secure the SNAPTRACK to the mounting surface. Click the
adapter board into place (Figure 3).
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
Figure 3
1. Disconnect power to the electrical panel and lock it out. Use a properly rated
voltage sensing device to confirm power is off.
Figure 1A:
Side-by-side
panel orientation
Panel 1
Panel 2
3. Connect adapter boards to the main board using
ribbon cable (Figure 4). Ribbon cables are keyed to
ensure proper installation.
Main Circuit Board
4. Connect current sensors to the terminals on the
adapter boards (Figure 4).
Adapter Boards
Figure 1B:
Vertical panel
orientation
Note: Flat and round ribbon cable are available
from Veris. See Recommended Accessories
(page 10)
Note: Align ribbon cable key
with connector keyhole.
Figure 4
Panel 1
A
A
Panel 1
B
B
Main Circuit Board
Adapter boards
Panel 2
Note: Current
sensor orientation
does NOT affect
meter accuracy.
Panel 2
Voltage taps are
shared by both panels
5. Plastic cable ties are included with the product for strain relief. Insert the strain
relief device into one of the available holes on the adapter board (Figure 5A).
Gather all current sensor wires connected to that adapter board and secure the
cable tie around them (Figure 5B).
2. Mount the adapter boards in the enclosure using either DIN rail or SNAPTRACK.
A. DIN Rail: Use the supplied screws to secure the plastic DIN clip to the
adapter board. Affix the clip to the DIN rail (Figure 2).
Figure 5
(A)
(B)
Figure 2
DIN Option 1: Vertical Mount
DIN Option 1: Horizontal Mount
Z205768-0B
PAGE 2
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
07121
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
INSTALLATION GUIDE
E31CTDB
TM
Safety
6. The adapter boards are silk screened with two rows of numbers. For applications
that require odd/even branch circuit numbering, use the row designated ODD or
EVEN. For applications that require sequential numbering, use the number row
marked SEQ (Figure 6).
Figure 6
BLACK
WHITE
41 1
39 2
37 3
35 4
33 5
31 6
29 7
27 8
25 9
23 10
21 11
19 12
17 13
15 14
13 15
11 16
9 17
7 18
19
20
21
SEQ
5
3
1
ODD
Adapter Board A numbering:
ODD
SEQ
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41
21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
If Veris E31 products are used in installations with circuits higher than the product
ratings, the circuits must be kept segregated per UL508A Sec. 17.5.
Note: 277/480VAC Wye connected (center grounded) power systems operate
within the 300VAC line to neutral safety rating of the E3x series, and the
operational voltage limit (single-phase connection) as the line to neutral
voltage is 277VAC in such power systems. Corner-grounded delta 480VAC
systems would not qualify, as the actual line to earth voltage is 480VAC on
each leg, exceeding the E3x ratings.
Note: E31 internal circuitry (cables and CTs) are not circuits as defined by
UL508A, as they do not extend beyond the E31 itself without further safety/
fire isolation.
UL listed under standard 508 as an “open type device.”
Maximum ambient air temperature for use is 60°C.
Installation category: CAT III
BLACK
WHITE
42 42
40 41
38 40
36 39
34 38
32 37
30 36
28 35
26 34
24 33
22 32
20 31
24
23
22
18 30
16 29
14 28
6
4
2
SEQ
12 27
10 26
8 24
EVEN
E31CTDB adapter boards, their connections to CTs, and the E31 main board must be
installed in an appropriate electrical and fire enclosure per local regulations.
Adapter Board B numbering:
For use in a Pollution Degree 2 or better environment only.
EVEN
SEQ
A Pollution Degree 2 environment must control conductive pollution and the
possibility of condensation or high humidity. Consideration must be given to the
enclosure, the correct use of ventilation, thermal properties of the equipment and the
relationship with the environment.
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
Recommended Accessories
Part ID
Description
CBL008
Flat ribbon cable, 50 x 28 AWG, 1.5 ft. (0.45 m)
CBL016
Flat ribbon cable, 50 x 28 AWG, 4 ft. (1.2 m)
CBL017
Flat ribbon cable, 50 x 28 AWG, 5 ft. (1.5 m)
CBL018
Flat ribbon cable, 50 x 28 AWG, 6 ft. (1.8 m)
CBL019
Flat ribbon cable, 50 x 28 AWG, 8 ft. (2.4 m)
CBL020
Flat ribbon cable, 50 x 28 AWG, 10 ft. (3.0 m)
CBL021
Flat ribbon cable, 50 x 28 AWG, 20 ft. (6.1 m)
CBL022
Round ribbon cable, 50 x 28 AWG, 4 ft. (1.2 m)
CBL023
Round ribbon cable, 50 x 28 AWG, 10 ft. (3 m)
CBL024
Round ribbon cable, 50 x 28 AWG, 20 ft. (6 m)
CBL025
Flat ribbon cable, 50 x 28 AWG, 2 m
CBL026
Flat ribbon cable, 50 x 28 AWG, 4 m
CBL027
Flat ribbon cable, 50 x 28 AWG, 6 m
E31CT0
Six-pack 50 A CT, 6 ft. (1.8 m) lead
E31CT0R20
Six-pack 50 A CT, 20 ft. (6 m) lead
E31CT1
Six-pack 100 A CT, 6 ft. (1.8 m) lead
E31CT1R20
Six-pack 100 A CT, 20 ft. (6 m) lead
E31CT2
Six-pack 100 A CT, 4 ft. (1.2 m) lead
E31CTDB
2 E31 Adapter boards
AE001
E3x MCB Cover
AV01
Veris DIN Rail
Z205768-0B
PAGE 3
If the equipment is used in a manner not specified by the manufacturer, the
protection provided by the device may be impaired.
IEC/EN 61010-1
This symbol indicates an electrical shock hazard exists.
Documentation must be consulted where this symbol is used on the
product.
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
07121
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
INSTALLATION GUIDE
E31CTDB
TM
CHINA RoHS COMPLIANCE INFORMATION (EFUP TABLE)
产品中有毒有害物质或元素的名称及含量Substances
部件名称
铅 (Pb) 汞 (Hg)
电子线路板
X
O
镉 (Cd)
六价铬 (Cr(VI))
多溴联苯(PBB)
多溴二苯醚(PBDE)
O
O
O
O
O = 表示该有毒有害物质在该部件所有均质材料中的含量均在 SJ/T11363-2006 标准规定的限量要求以下.
X = 表示该有毒有害物质至少在该部件的某一均质材料中的含量超出SJ/T11363-2006标准规定的限量要求.
Z000057-0A
Z205768-0B
PAGE 4
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]