IC693CBL303

IC693CBL303
This Datasheet is for the
IC693CBL303
Hand-Hand Programmer and Converter (IC690ACC900) Cable
http://www.cimtecautomation.com/parts/p-14592-ic693cbl303.aspx
Provides the wiring diagrams and installation guidelines for this GE Series 90-30
module.
For further information, please contact Qualitrol Technical Support at
1-800-784-9385
[email protected]
10
IC693CBL303
Hand-Hand Programmer and Converter (IC690ACC900) Cable
Function of cable
The Hand-Held Programmer cable provides the connections that allow the Hand-Held
Programmer and the Programmable Logic Controller to communicate. This cable also
provides the power connections for the HHP, and a signal which indicates to the PLC
that the HHP is attached to the PLC serial port. It can also be used to connect the
RS-485 serial port on the PLC to the RS-422/RS-485 to RS-232 converter (IC690ACC900).
Cable Specifications
The prewired cable (IC693CBL303) is 6 feet (2 meters) long. If a different length cable is
required for connection to the converter, refer to the information below for specifications
and wiring information.
This information is essential if you intend to build your own cable. The recommended
cable types for this cable are listed below and depend on the length of the cable.
Specifications for IC693CBL303 Prewired cable
Item
Description
Connectors
Same connector is on
both ends
15-pin male, D-Subminiature Type, Canon DA15S (solder pot)
Hood
AMP 207470-1 connector shell
Hardware kit
AMP 207871-1 Kit includes 2 metric screws and 2 screw clips
Cable Type
Belden 9508:
AWG #24 (.22 mm2)
CableLength
6 feet (2 meters)
Wire Types for Custom Cables
Cable Length
Wire Size
30 feet (10m)
>30 (10m) feet to
980 feet (300m)
22 (.36 mm2)
22 (.36 mm2)
1.
2.
10-34
Catalog Number
Belden 9309
Same as for 30 feet. In addition, the+5 VDC logic power source for the
converter cannot be supplied by the PLC. It must be provided by an
external power supply connected to the +5V and SG pins at the converter
end of the connector. The +5V pin at the PLC connector must not be connected to the cable. The +5V and SG connections from the power supply
must be isolated from its own power line ground connection. Be sure that
there is no connection between the external supply and the PLC except the
SG cable connection.
Catalog numbers are provided as suggestions only. Any cable having the same electrical characteristics is
acceptable. It is strongly recommended that you use stranded wire. Since it is sometimes hard to find a
cable with the desired number of twisted pairs (the Belden 9309 has an extra pair), you may end up with a
cable with extra pairs.
A greater cable length between the PLC and the converter increases the possibility of noise coupling into
the data and converter logic power circuits within the cable. The cable should be as short as possible in
noisy environments. In extreme cases, additional noise protection measures, such as double-shielded
cables, may be required.
Series 90-30 PLC Installation and Hardware Manual – October 1999
GFK-0356P
10
Wiring Diagram
The following wiring diagram applies to the IC693CBL303 cable and to custom-built
cables.
RS–422
TWISTED SHIELDED PAIRS
RS–232/RS–485
CONVERTER
(IC690ACC900)
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
25–PI
FEMALE
RS–232 PORT
Î
Î
Î
Î
Î
Î
Î
Î
Î
Î
PIN
NOTE:
SHLD
1
1
SHLD
ATTCH
DCD (A)
DCD (B)
RT
RD (A’)
4
2
3
9
10
4
2
3
ATTCH
DCD (A)
DCD (B)
RD (B’)
11
12
13
9
SD (A)
SD (B)
RT
RD (A’)
RD (B’)
SD (A)
SD (B)
12
13
10
11
+5V
5
5
0V
7
6
14
7
15
0V
CTS (A’)
8
CTS (B’)
15
6
14
RTS (A)
RTS (B)
RTS (A)
RTS (B)
CTS (A’)
CTS (B’)
15–PIN
FEMALE
RS–485 PORT
a44750
PIN
8
15–PIN
MALE
+5V
15–PIN
MALE
ÎÎÎ
ÎÎ
Î
ÎÎ
ÎÎ
Î
Î
ÎÎ
ÎÎÎ
Î
Î
Î
Î
ÎÎÎ
SERIES
90 PLC
RS–422
PORT
15–PIN
FEMALE
PINS 9 AND 10 ARE JUMPERED AT BOTH ENDS OF CABLE TO CONNECT TERMINATING
RESISTORS FOR THE RD SIGNAL WHICH IS INSIDE THE PLC POWER SUPPLY.
Figure 10-23. Wiring Connections for IC693CBL303 and Custom-Built Cables
Connecting the Cable
H
Attach the 15-pin male D connector to the serial port connector on the PLC power
supply.
H
Attach the D connector on the other end to the mating connector on the HHP.
These connections are shown in the following figure.
a47062
HAND–HELD
PROGRAMMER
ÎÎÎÎÎÎÎÎÎÎÎ
ÎÎÎÎÎÎÎÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
Î
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
Î
Î
ÎÎ
ÎÎ
ÎÎ
ÎÎ
Î
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
Î
Î
Î
ÎÎÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎÎÎ
ÎÎÎ
ÎÎ
ÎÎÎ
ÎÎÎÎ
SERIES 90–30
CABLE
(IC693CBL303)
C
P
U
Figure 10-24. Hand-Held Programmer Cable Connection to a Series 90-30 PLC
GFK-0356P
Chapter 10 Cables
10-35