Variable Speed Induced-Combustion Deluxe 4-Way Multipoise Furnace Installation, Start-up, Operating, and
Add to my manuals58 Pages
advertisement
Variable Speed
Induced-Combustion Deluxe
4-Way Multipoise Furnace
Cancels: II 315A-70-4 II 315A-70-5
4-06
Installation, Start-up, Operating, and
Service and Maintenance Instructions
Series 120/C
NOTE: Read the entire instruction manual before starting the
installation.
This symbol
→ indicates a change since the last issue.
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1-2006©, with permission of National Fire Protection Association, Quincy, MA 02269 and American
Gas Association, Washington DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI on the referenced subject, which is represented only by the standard in its entirety.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS .....................................................2
INTRODUCTION ..........................................................................2
CODES AND STANDARDS........................................................4
Safety.........................................................................................4
General Installation...................................................................4
Combustion and Ventilation Air ..............................................4
Duct Systems ............................................................................4
Acoustical Lining and Fibrous Glass Duct..............................4
Gas Piping and Gas Pipe Pressure Testing..............................4
Electrical Connections ..............................................................4
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
PROCEDURE ................................................................................4
LOCATION....................................................................................5
General ......................................................................................5
Location Relative to Cooling Equipment ................................7
AIR FOR COMBUSTION AND VENTILATION ......................7
INSTALLATION .........................................................................10
Upflow Installation .................................................................10
Bottom Return Air Inlet ....................................................10
Side Return Air Inlet.........................................................10
Leveling Legs (If Desired)................................................10
Downflow Installation ............................................................10
Bottom Return Air Inlet ....................................................11
Horizontal Installation ............................................................11
Suspended Furnace Support ..............................................11
Platform Furnace Support .................................................11
Roll-Out Protection............................................................11
Bottom Return Air Inlet ....................................................14
Side Return Air Inlet.........................................................14
Filter Arrangement..................................................................12
Air Ducts.................................................................................12
General Requirements .......................................................12
Ductwork Acoustical Treatment .......................................13
Supply Air Connections ....................................................13
Return Air Connections.....................................................15
Gas Piping...............................................................................18
Electrical Connections ............................................................19
115-V Wiring.....................................................................19
J-Box Relocation ...............................................................20
Electrical Connection to J-Box .........................................19
Power Cord Installation.....................................................20
BX Cable Installation ........................................................21
24-V Wiring.......................................................................21
Accessories ........................................................................21
Venting ....................................................................................21
General Venting Requirements .........................................24
Masonry Chimney Requirements......................................29
Appliance Application Requirements ...............................29
Additional Venting Requirements.....................................30
Sidewall Venting ...............................................................33
START-UP, ADJUSTMENT, AND SAFETY CHECK ............33
General ....................................................................................33
Start-Up Procedures ...............................................................35
Adjustments ...........................................................................36
Check Safety Controls ............................................................43
Checklist..................................................................................43
SERVICE AND MAINTENANCE PROCEDURES..................43
Introduction .............................................................................46
General...............................................................................46
Electrical Controls and Wiring .........................................46
Care and Maintenance ............................................................47
Cleaning and/or Replacing Air Filter ...............................47
Blower Motor and Wheel..................................................48
Cleaning Heat Exchanger..................................................49
Sequence of Operation............................................................50
Wiring Diagrams.....................................................................54
Troubleshooting ......................................................................54
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 6a 8a
PC 101 Printed in U.S.A.
Pg 1 4-06
SAFETY CONSIDERATIONS
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous operation, serious injury, death, or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified service agency must use only factory-authorized and listed kits or accessories when modifying this product.
FURNACE RELIABILITY HAZARD
Improper installation or misapplication of furnace may require excessive servicing or cause premature component failure.
Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in literature, on tags, and on labels attached to or shipped with furnace and other safety precautions that may apply.
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We require these instructions as a minimum for a safe installation.
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces.
Wear safety glasses and work gloves. Have fire extinguisher available during start-up and adjustment procedures and service calls.
This is the safety-alert symbol . When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which
could result in personal injury or death. CAUTION is used to
identify hazards which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
1. Use only with type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as specified in the “Location” section of these instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in “Air for Combustion and Ventilation” section.
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the “Venting” section of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in the “Gas
Piping” section.
6. Always install furnace to operate within the furnace’s intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified in the “Start-Up, Adjustments, and Safety Check” section.
See furnace rating plate.
→
7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. See “Air Ducts” section.
8. A gas-fired furnace for installation in a residential garage must be installed as specified in the warning box in the “Location” section.
9. The furnace may be used for construction heat provided that the furnace installation and operation complies with the first
CAUTION in the LOCATION section of these instructions.
10. These Multipoise Gas-Fired Furnaces are CSA (formerly
A.G.A. and C.G.A.) design-certified for use with natural and propane gases (see furnace rating plate) and for installation in alcoves, attics, basements, closets, utility rooms, crawlspaces, and garages. The furnace is factory-shipped for use with natural gas. A CSA (A.G.A. and C.G.A.) listed gas conversion kit is required to convert furnace for use with propane gas.
11. See Fig. 1 for required clearances to combustible construction.
12. Maintain a 1-in. clearance from combustible materials to supply air ductwork for a distance of 36 inches horizontally from the furnace. See NFPA 90B or local code for further requirements.
13. These furnaces SHALL NOT be installed directly on carpeting, tile, or any other combustible material other than wood flooring. In downflow installations, factory accessory floor base MUST be used when installed on combustible materials and wood flooring. Special base is not required when this furnace is installed on manufacturer’s Coil Assembly Part No.
CD5 or CK5, or when Coil Box Part No. KCAKC is used. See
Fig. 1 for clearance to combustible construction information.
INTRODUCTION
The Series 120/C 4–way multipoise Category I fan-assisted furnace is CSA (formerly A.G.A. and C.G.A.) design-certified. A
Category I fan-assisted furnace is an appliance equipped with an integral mechanical means to either draw or force products of combustion through the combustion chamber and/or heat exchanger. The furnace is factory-shipped for use with natural gas.
This furnace is not approved for installation in mobile homes, recreational vehicles, or outdoors.
2
†
INSTALLATION
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
DISTANCE MINIMALE EN POUCES AUX CONSTRUCTIONS COMBUSTIBLES
This forced air furnace is equipped for use with natural gas at altitudes 0-10,000 ft (0-3,050m).
An accessory kit, supplied by the manufacturer, shall be used to convert to propane gas use or may be required for some natural gas applications.
This furnace is for indoor installation in a building constructed on site.
This furnace may be installed on combustible flooring in alcove or closet at minimum clearance as indicated by the diagram from combusitble material.
This furnace may be used with a Type B-1 Vent and may be vented in common with other gas fired appliances.
Cette fournaise à air pulsé est équipée pour utilisation avec gaz naturel et altitudes comprises entre 0-3,050m (0-10,000 pi).
Utiliser une trousse de conversion, fournie par le fabricant, pour passer au gaz propane ou pour certaines installations au gaz naturel.
Cette fournaise est prévue pour être installée dans un bâtiment construit sur place.
Cette fournaise peut être installée sur un plancher combustible dans une alcôve ou dans un garde-robe en respectant le minimum d'espace libre des matériaux combustibles, tel qu
´ indiqué sur le diagramme.
Cette fournaise peut être utilisée avec un conduit d
´
évacuation de Type B-1 ou connectée au conduit ommun d 'autres appareils à gaz.
This furnace is approved for UPFLOW, DOWNFLOW, and
HORIZONTAL installations.
Cette fournaise est approuvée pour l 'installation HORIZONTALE et la circulation d 'air VERS LE HAUT et VERS LE BAS.
Clearance arrows do not change with furnace orientation.
0"
A
R
B
A
R I
C
È
R
K
E
*
0"
S I
D E
É
C
Ô T
†
1"
Les fléches de dégagement ne change pas avec l 'orientation de la fournaise.
*
0"
E
D
S I
F
U
F O
R N
U
R N
F R
A
A
V
E
I
ON
A
E
T
N
T
C
Ô T
A
F
R
V
O
A
N
N
T
T
3"
Ø
EN
S
E
TR
R V
E
T
È
I
I
C
E
E
N 24"
MIN
0"
Clearance in inches
Dégagement (po).
Vent Clearance to combustibles:
For Single Wall vents 6 inches (6 po).
For Type B-1 vent type 1 inch (1 po).
Dégagement de l
´
évent avec combustibles:
Pour conduit d´évacuation à paroi simple 6 po (6 inches).
Pour conduit d´évacuation de Type B-1 1 po (1 inch).
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
DOWNFLOW POSITIONS:
Installation on non-combusibible floors only.
For Installation on combustible flooring only when installed on special base, Part No. KGASB0201ALL,
Coil Assembly, Part No. CD5 or CK5, or Coil Casing, Part No. KCAKC.
Ø
*
18 inches front clearance required for alcove.
Indicates supply or return sides when furnace is in the horizontal position. Line contact only permissible between lines formed by intersections of the Top and two Sides of the furnace jacket, and building joists, studs or framing.
Ø
*
†
DÉGAGEMENT MINIMUM EN POUCES AVEC ÉLÉMENTS
DE CONSTRUCTION COMBUSTIBLES
POUR LA POSITION COURANT DESCENDANT:
Pour l
´ installation sur plancher non combustible seulement.
Pour l
´ installation sur un plancher combustible seulement quand on utilise la base spéciale, pièce nº KGASB0201ALL, l
´ ensemble serpentin, pièce nº CD5 ou CK5, ou le carter de serpentin, pièce nº KCAKC.
Dans une alcôve, on doit maintenir un dégagement à l
´ avant de 18 po (450mm).
La poistion indiquée concerne le côté d
´ entrée ou de retour quand la fournaise est dans la position horizontale.
Le contact n
´ est permis qu
´ entre les lignes formées par les intersections du dessus et des deux côtés de la cherrise de la fournaise et les solives, montant sous cadre de charpente.
327590-101 REV. C
Fig. 1—Clearances to Combustibles
3
Fig. 2—Return Air Temperature
80
60
A04036
This furnace is designed for minimum continuous return-air temperature of 60°F db or intermittent operation down to 55°F db such as when used with a night setback thermostat. Return-air temperature must not exceed 80°F db. Failure to follow these return-air temperature limits may affect reliability of heat exchangers, motors, and controls. (See Fig. 2.)
For accessory installation details, refer to the applicable instruction literature.
NOTE: Remove all shipping brackets and materials before oper-
ating the furnace.
CODES AND STANDARDS
Follow all national and local codes and standards in addition to
these instructions. The installation must comply with regulations
of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes listed below and all authorities having jurisdiction.
In the United States and Canada, follow all codes and standards for the following:
Step 1—Safety
• US: National Fuel Gas Code (NFGC) NFPA 54–2002/ANSI
Z223.1–2002 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B
• CANADA: CSA B149.1-00 National Standard of Canada
Natural Gas and Propane Installation Code (NSCNGPIC)
Step 2—General Installation
• US: Current edition of the NFGC and the NFPA 90B. For copies, contact the National Fire Protection Association Inc.,
Batterymarch Park, Quincy, MA 02269; (www.NFPA.org) or for only the NFGC, contact the American Gas Association, 400
N. Capitol Street, N.W., Washington, DC 20001
(www.AGA.org.)
• CANADA: NSCNGPIC. For a copy, contact Standard Sales,
CSA International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario, M9W 1R3 Canada
Step 3—Combustion and Ventilation Air
• US: Section 8.3 of the NFGC, Air for Combustion and
Ventilation
• CANADA: Part 7 of NSCNGPIC, Venting Systems and Air
Supply for Appliances
4
Step 4—Duct Systems
• US and CANADA: Air Conditioning Contractors Association
(ACCA) Manual D, Sheet Metal and Air Conditioning Contractors National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning Engineers
(ASHRAE) 2001 Fundamentals Handbook Chapter 34 or 2000
HVAC Systems and Equipment Handbook Chapters 9 and 16.
Step 5—Acoustical Lining and Fibrous Glass Duct
• US and CANADA: current edition of SMACNA and NFPA
90B as tested by UL Standard 181 for Class I Rigid Air Ducts
Step 6—Gas Piping and Gas Pipe Pressure Testing
• US: NFGC; chapters 5, 6, 7, and 12 and National Plumbing
Codes
• CANADA: NSCNGPIC Parts 3, 4, and 5, and Appendices A,
B, E and H.
Step 7—Electrical Connections
• US: National Electrical Code (NEC) ANSI/NFPA 70–2002
• CANADA: Canadian Electrical Code CSA C22.1
Step 8—Venting
• US: NFGC; chapters 10 and 13
• CANADA: NSCNGPIC Part 7 and Appendix C
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
PROCEDURE
FURNACE RELIABILITY HAZARD
Improper installation or service of furnace may cause premature furnace component failure.
Electrostatic discharge can affect electronic components.
Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.
1. Disconnect all power to the furnace. Multiple disconnects may be required. DO NOT TOUCH THE CONTROL OR ANY
WIRE CONNECTED TO THE CONTROL PRIOR TO DIS-
CHARGING YOUR BODY’S ELECTROSTATIC CHARGE
TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing to recharge your body with static electricity (for example; DO
NOT move or shuffle your feet, do not touch ungrounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body with static electricity), firmly touch a clean, unpainted metal surface of the furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungrounded) furnaces.
6. Before removing a new control from its container, discharge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 4 before bringing the control or yourself in contact with the furnace. Put all used and new controls into containers before touching ungrounded objects.
28-7/8"
26-1/8"
(FLUE COLLAR)
7/8" DIA
ACCESSORY
5-15/16"
25-1/4"
22-9/16"
JUNCTION BOX
LOCATION
F
A
D
13/16"
4-13/16"
2-7/16"
1-5/16"
1-1/8"
8-9/16"
AIRFLOW
19"
OUTLET
1/2" DIA. K.O.THERMOSTAT
WIRE ENTRY
1-3/4" DIA.RIGHT HAND
GAS ENTRY
13/16"
11/16"
7-3/4"
9-5/8"
11-1/2"
1/2" DIA THERMOSTAT
WIRE ENTRY
3-15/16"
LEFT HAND GAS
ENTRY
7/8" DIA. K.O. WIRE ENTRY
33-5/16"
24-7/8"
ALTERNATE
JUNCTION BOX
LOCATIONS (TYP)
VENT OUTLET
5 PLACES (TYP)
14-7/8"
7/8" DIA. ACCESSORY
7/8" DIA. ACCESSORY
5-1/2"
11/16"
21-5/8"
BOTTOM INLET
24"
CASING
1-11/16"
5-1/2"
E 11/16"
3-3/4"
1-1/2"
22-1/16"
SIDE INLET
1-1/4"
1"
NOTES:
1. Two additional 7/8-in. diameter holes are located in the top plate.
2. Minimum return-air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent diameters.
a. For 800 CFM-16-in. round or 14 1/2 x 12-in. rectangle.
b. For 1200 CFM-20-in. round or 14 1/2 x 19 1/2-in. rectangle.
c. For 1600 CFM-22-in. round or 14 1/2 x 22 1/16-in. rectangle.
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets, a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
Fig. 3—Dimensional Drawing
A04037
Table 1—Dimensions (IN.)
FURNACE SIZE
070-12/036070
090-16/048090
110-20/060110
A
CABINET WIDTH
(IN.)
14-3/16
17-1/2
21
D
SUPPLY-AIR
WIDTH
(IN.)
12-9/16
15-7/8
19-3/8
E
RETURN-AIR
WIDTH
(IN.)
12-11/16
16
19-1/2
F
C.L. TOP AND
BOTTOM FLUE COLLAR
(IN.)
9-5/16
11-9/16
13-5/16
135-22/066135
155-22/066155
24-1/2
24-1/2
22-7/8
22-7/8
23
23
15-1/16
15-1/16
* 5” or 6” vent connector may be required in some cases.
†5
″ or larger vent is required. Use a 4-5 or 4-6 inch vent adapter between furnace and vent connector.
FLUE COLLAR*
(IN.)
4
4
4
4†
4†
SHIP WT. (LB)
127
151
163
177
183
FILTER MEDIA
CABINET SIZE
(IN.)
16
16
20
24
24
7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage.
LOCATION
GENERAL
This multipoise furnace is shipped in packaged configuration.
Some assembly and modifications are required when used in any of the four applications shown in Fig. 4.
NOTE: For high-altitude installations, the high-altitude conver-
sion kit MUST be installed at or above 5500 ft above sea level.
Obtain high-altitude conversion kit from your area authorized distributor.
This furnace must:
• be installed so the electrical components are protected from water.
•
not be installed directly on any combustible material other than
wood flooring (refer to SAFETY CONSIDERATIONS).
• be located close to the chimney or vent and attached to an air distribution system. Refer to Air Ducts section.
• be provided ample space for servicing and cleaning. Always comply with minimum fire protection clearances shown on the furnace clearance to combustible construction label.
5
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
AIR CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
THE BLOWER IS
LOCATED ABOVE THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD
THE BLOWER IS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT.
A02097
Fig. 4—Multipoise Orientations
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death and unit component damage.
Corrosive or contaminated air may cause failure of parts containing flue gas, which could leak into the living space.
Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products. Do not install furnace in a corrosive or contaminated atmosphere. Make sure all combustion and circulating air requirements are met, in addition to all local codes and ordinances.
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as perchloroethylene)
• Printing inks, paint removers, varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes dryers
• Masonry acid washing materials
All fuel-burning equipment must be supplied with air for fuel combustion. Sufficient air must be provided to avoid negative pressure in the equipment room or space. A positive seal must be made between the furnace cabinet and the return-air duct to prevent pulling air from the burner area and from draft safeguard opening.
The following types of furnace installations may require OUT-
DOOR AIR for combustion due to chemical exposures:
• Commercial buildings
• Buildings with indoor pools
• Laundry rooms
• Hobby or craft rooms, and
• Chemical storage areas
If air is exposed to the following substances, it should not be used for combustion air, and outdoor air may be required for combustion:
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine based swimming pool chemicals
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
When the furnace is installed in a residential garage, the burners and ignition sources must be located at least 18 in.
above the floor. The furnace must be located or protected to avoid damage by vehicles. When the furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, the furnace must be installed in accordance with the NFGC or NSCNGPIC. (See Fig. 5.)
6
18-IN. MINIMUM
TO BURNERS
Fig. 5—Installation in a Garage
A93044
FIRE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect return-air ducts to the back of the furnace. (See Fig. 6.)
LOCATION RELATIVE TO COOLING EQUIPMENT
The cooling coil must be installed parallel with, or on the downstream side of the unit to avoid condensation in the heat exchangers. When installed parallel with the furnace, dampers or other flow control must prevent chilled air from entering the furnace. If the dampers are manually operated, they must be equipped with means to prevent operation of either unit unless the damper is in the full-heat or full-cool position.
PERSONAL INJURY AND/OR PROPERTY DAMAGE
HAZARD
Improper use or installation of this furnace may cause premature furnace component failure.
This gas furnace may be used for heating buildings under construction provided that:
-The furnace is permanently installed with all electrical wiring, piping, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
-The furnace is controlled by a thermostat. It may not be
″hot wired
″ to provide heat continuously to the structure without thermostatic control.
-Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
-The temperature of the return air to the furnace is maintained between 55°F (13°C) and 80°F (27°C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions.
-The air temperature rise is within the rated rise range on the furnace rating plate, and the gas input rate has been set to the nameplate value.
-The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy.
-The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed.
-Verify proper furnace operating conditions including ignition, gas input rate, air temperature rise, and venting according to these installation instructions.
Fig. 6—Prohibit Installation on Back
A02054
7
AIR FOR COMBUSTION AND VENTILATION
Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with:
•
U.S. Installations: Section 8.3 of the NFGC, Air for Combus-
tion and Ventilation and applicable provisions of the local building codes.
•
Canadian Installations: Part 7 of the NSCNGPIC, Venting
Systems and Air Supply for Appliances and all authorities having jurisdiction.
FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace damage.
Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products.
Table 2–Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors
FURNACE
INPUT
(BTUH)
44,000
66,000
88,000
110,000
132,000
154,000
TWO HORIZONTAL DUCTS
(1 SQ. IN./2,000 BTUH) (1,100 SQ. MM/KW)
Free Area of
Opening and Duct
(Sq. In.)
Round Duct
(in. Dia)
22
33
6
7
44
55
66
77
8
9
10
10
SINGLE DUCT OR OPENING
(1 SQ. IN./3,000 BTUH) (734 SQ. MM/KW)
Free Area of
Opening and Duct
(sq In.)
Round Duct
(in. Dia)
14.7
22
5
6
29.3
36.7
44
51.3
7
7
8
9
TWO OPENINGS OR VERTICAL DUCTS
(1 SQ. IN./4,000 BTUH) (550 SQ. MM/KW)
Free Area of
Opening and Duct
(Sq In.)
Round Duct
(In. Dia)
11
16.5
4
5
22
27.5
33
38.5
6
6
7
8
EXAMPLES: Determining Free Area
FURNACE
110,000
66,000
88,000
+
+
+
WATER HEATER
30,000
40,000
30,000
=
=
=
TOTAL INPUT
(140,000 divided by 4,000)
(106,000 divided by 3,000)
(118,000 divided by 2,000)
=
=
=
35.0 Sq. In. for each two Vertical Ducts or Openings
35.3 Sq. In. for a Single Duct or Opening
59.0 Sq. In. for each of two Horizontal Ducts
ACH
0.60
0.50
0.40
0.30
0.20
0.10
0.00
NP = Not Permitted
1,050
1,260
1,575
2,100
3,150
6,300
NP
Table 3–Minimum Space Volumes for 100% Combustion, Ventilation, and
Dilution from Indoors
OTHER THAN FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
30 40 50
1,400
1,680
2,100
2,800
4,200
8,400
NP
1,750
2,100
2,625
3,500
5,250
10,500
NP
44 66
Space Volume (ft
3
)
FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
88 110 132
1,100
1,320
1,650
1,650
1,980
2,475
2,200
2,640
3,300
2,750
3,300
4,125
3,300
3,960
4,950
2,200
3,300
6,600
NP
3,300
4,950
9,900
NP
4,400
6,600
13,200
NP
5,500
8,250
16,500
NP
6,600
9,900
19,800
NP
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a
NEGATIVE PRESSURE CONDITION at the furnace.
Make-up air MUST be provided for the ventilation devices, in addition to that required by the furnace. Refer to the Carbon
Monoxide Poisoning Hazard warning in the venting section of these instructions to determine if an adequate amount of make-up air is available.
The requirements for combustion and ventilation air depend upon whether or not the furnace is located in a space having a volume of at least 50 cubic feet per 1,000 Btuh input rating for all gas appliances installed in the space.
• Spaces having less than 50 cubic feet per 1,000 Btuh require the OUTDOOR COMBUSTION AIR METHOD.
• Spaces having at least 50 cubic feet per 1,000 Btuh may use the
INDOOR COMBUSTION AIR, STANDARD or KNOWN-
AIR INFILTRATION METHOD.
Outdoor Combustion Air Method
1. Provide the space with sufficient air for proper combustion, ventilation, and dilution of flue gases using permanent hori-
8
154
3,850
4,620
5,775
7,700
11,550
23,100
NP zontal or vertical duct(s) or opening(s) directly communicating with the outdoors or spaces that freely communicate with the outdoors.
2. Fig. 7 illustrates how to provide TWO OUTDOOR OPEN-
INGS, one inlet and one outlet combustion and ventilation air opening, to the outdoors.
a. One opening MUST commence within 12
″ (300 mm) of the ceiling and the second opening MUST commence within 12
″ (300 mm) of the floor.
b. Size openings and ducts per Fig. 7 and Table 2.
c. TWO HORIZONTAL DUCTS require 1 square inch of free area per 2,000 Btuh (1,100 mm
2
/kW) of combined input for all gas appliances in the space per Fig. 7 and Table
2.
d. TWO OPENINGS OR VERTICAL DUCTS require 1 square inch of free area per 4,000 Btuh (550 mm
2
/kW) for combined input of all gas appliances in the space per Fig.
7 and Table 2.
3. ONE OUTDOOR OPENING requires: a. 1 square inch of free area per 3,000 Btuh (734 mm
2
/kW) for combined input of all gas appliances in the space per
Table 2 and b. Not less than the sum of the areas of all vent connectors in the space.
DUCTS
TO
OUTDOORS
1 SQ IN.
PER 4000
BTUH*
CIRCULATING AIR
DUCTS
VENT THROUGH ROOF
12
″ MAX
1 SQ IN.
PER 2000
BTUH*
B
D
VENT
THROUGH
ROOF
F
12
″
MAX
1 SQ IN.
PER
4000
BTUH*
DUCTS
TO
OUTDOORS
1 SQ IN.
PER 2000
BTUH*
12
″ MAX
A
E
G
C
12
″ MAX
1 SQ IN.
PER
4000
BTUH*
12
″
MAX
CIRCULATING AIR DUCTS
DUCT
TO
OUTDOORS
1 SQ IN.
PER 4000
BTUH*
*Minimum dimensions of 3 in.
NOTE:
Use any of the following combinations of openings:
A & B C & D D & E F & G
A03174
Fig. 7—Air for Combustion, Ventilation, and
Dilution for Outdoors
The opening shall commence within 12
″ (300 mm) of the ceiling.
Appliances in the space shall have clearances of at least 1
″ (25 mm) from the sides and back and 6
″ (150 mm) from the front. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
Indoor Combustion Air© NFPA & AGA
Standard and Known-Air-Infiltration Rate Methods
Indoor air is permitted for combustion, ventilation, and dilution,
if the Standard or Known-Air-Infiltration Method is used.
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in death and/or personal injury.
Many homes require air to be supplied from outdoors for furnace combustion, ventilation, and dilution of flue gases.
The furnace combustion air supply must be provided in accordance with this instruction manual.
The Standard Method:
1. The space has no less volume than 50 cubic feet per 1,000
Btuh of the maximum input ratings for all gas appliances installed in the space and
2. The air infiltration rate is not known to be less than 0.40 air changes per hour (ACH).
The Known Air Infiltration Rate Method shall be used, if the infiltration rate is known to be:
9
INTERIOR
HEATED
SPACE
12" MAX
1 SQ IN.
PER 1000
BTUH* IN DOOR
OR WALL
UNCONFINED
SPACE
6" MIN
(FRONT)
†
1 SQ IN.
PER 1000
BTUH* IN DOOR
OR WALL
12" MAX
CIRCULATING AIR DUCTS
* Minimum opening size is 100 sq in. with
minimum dimensions of 3 in.
† Minimum of 3 in. . when type-B1 vent is used.
A03175
Fig. 8—Air for Combustion, Ventilation, and
Dilution from Indoors
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the number of
ACH and shall be determined per Table 3 or Equations 1 and 2.
Determine the minimum required volume for each appliance in the space and add the volumes together to get the total minimum required volume for the space.
Table 3-Minimum Space Volumes were determined by using the
following equations from the National Fuel Gas Code ANSI
Z223.1-2002/NFPA 54-2002,8.3.2.2:
1. For other than fan-assisted appliances, such as a draft hood-equipped water heater:
Volume
Other
= 21ft
3
ACH
I other
1000 Btu/hr
A04002
2. For fan-assisted appliances such as this furnace:
Volume
Fan
= 15ft
3
ACH
I fan
1000 Btu/hr
A04003
If:
I other
= combined input of all other than fan-assisted appli-
ances in Btu/hr
I fan
= combined input of all fan-assisted appliances in Btu/hr
ACH = air changes per hour (ACH shall not exceed 0.60.)
The following requirements apply to the Standard Method and to the Known Air Infiltration Rate Method.
1. Adjoining rooms can be considered part of a space if: a. There are no closable doors between rooms.
b. Combining spaces on same floor level. Each opening shall have free area of at least 1 in.
2
/1,000 Btuh (2,000 mm
2
/kW) of the total input rating of all gas appliances in the space, but not less than 100 in.
2
(0.06 m
2
). One opening shall commence within 12
″ (300 mm) of the ceiling and the second opening shall commence within 12
″ (300 mm) of the floor. The minimum dimension of air openings shall be at least 3 in. (80 mm). (See Fig. 8.) c. Combining space on different floor levels. The volumes of spaces on different floor levels shall be considered as communicating spaces if connected by one or more permanent openings in doors or floors having free area of at least
2 in.
2
/1,000 Btuh (4,400 mm
2
/kW) of total input rating of all gas appliances.
2. An attic or crawlspace may be considered a space that freely communicates with the outdoors provided there are adequate permanent ventilation openings directly to outdoors having free area of at least 1-in.
2
/4,000 Btuh of total input rating for all gas appliances in the space.
3. In spaces that use the Indoor Combustion Air Method, infiltration should be adequate to provide air for combustion, permanent ventilation and dilution of flue gases. However, in buildings with unusually tight construction, additional air
MUST be provided using the methods described in the
Outdoor Combustion Air Method section.
Unusually tight construction is defined as
Construction with: a. Walls and ceilings exposed to the outdoors have a continuous, sealed vapor barrier. Openings are gasketed or sealed and b. Doors and openable windows are weatherstripped and c. Other openings are caulked or sealed. These include joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, etc.
Combination of Indoor and Outdoor Air
1. Indoor openings shall comply with the Indoor Combustion
Air Method below and,
2. Outdoor openings shall be located as required in the Outdoor
Combustion Air Method mentioned previously and,
3. Outdoor openings shall be sized as follows: a. Calculate the Ratio of all Indoor Space volume divided by required volume for Indoor Combustion Air Method below.
b. Outdoor opening size reduction Factor is 1 minus the
Ratio in a. above.
c. Minimum size of Outdoor openings shall be the size required in Outdoor Combustion Air Method above multiplied by reduction Factor in b. above. The minimum dimension of air openings shall be not less than 3 in. (80 mm).
INSTALLATION
UPFLOW INSTALLATION
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return-air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom filler panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return-air opening. This panel MUST be in place when only side return air is used.
NOTE: Side return-air openings can be used in UPFLOW and
most HORIZONTAL configurations. Do not use side return-air openings in DOWNFLOW configuration.
Leveling Legs (If Desired)
In upflow position with side return inlet(s), leveling legs may be used. (See Fig. 10.) Install field-supplied, 5/16 X 1-1/2 in. (max) corrosion-resistant machine bolts, washers and nuts.
NOTE: Bottom closure must be used when leveling legs are used.
It may be necessary to remove and reinstall bottom closure panel to install leveling legs. To remove bottom closure panel, see Item
1 in Bottom Return Air Inlet section in Step 1 above.
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each bottom corner of furnace. (See Fig. 10.)
2. For each leg, install nut on bolt and then install bolt with nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer if desired.)
4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.
5. Reinstall bottom closure panel if removed.
10
Fig. 9—Removing Bottom Closure Panel
A02098
DOWNFLOW INSTALLATION
NOTE: For downflow applications, this furnace is approved for
use on combustible flooring when any one of the following 3 accessories are used:
5
⁄
16
″
HORIZONTAL INSTALLATION
5
⁄
16
″
1 3
⁄
4
″
5
⁄
16
″
1
3
⁄
4
″
1
3
⁄
4
″
1 3
⁄
4
″
5
⁄
16
″
Fig. 10—Leveling Legs
A02071
• Special Base, KGASB
• Cased Coil Assembly Part No. CD5 or CK5
• Coil Box Part No. KCAKC
1. Determine application being installed from Table 4.
2. Construct hole in floor per Table 4 and Fig. 11.
3. Construct plenum to dimensions specified in Table 4 and Fig.
11.
4. If downflow subbase, KGASB is used, install as shown in Fig.
12. If Coil Assembly Part No. CD5 or CK5 or Coil Box Part
No. KCAKC is used, install as shown in Fig. 13.
NOTE: It is recommended that the perforated supply-air duct
flanges be completely folded over or removed from furnace when installing the furnace on a factory-supplied cased coil or coil box.
To remove the supply-air duct flange, use wide duct pliers or hand seamers to bend flange back and forth until it breaks off. Be careful of sharp edges. (See Fig. 14.)
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return-air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom filler panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
11
FIRE, EXPLOSION, AND CARBON MONOXIDE POI-
SONING HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect return-air ducts to the back of the furnace.
The furnace can be installed horizontally in an attic or crawlspace on either the left-hand (LH) or right-hand (RH) side. The furnace can be hung from floor joists, rafters or trusses or installed on a non-combustible platform, blocks, bricks or pad.
Suspended Furnace Support
The furnace may be supported under each end with threaded rod, angle iron or metal plumber’s strap as shown. (See Fig. 15 and 16.)
Secure angle iron to bottom of furnace as shown. Heavy-gauge sheet metal straps (plumber’s straps) may be used to suspend the furnace from each bottom corner. To prevent screws from pulling out, use 2 #8 x ¾-in. screws into the side and 2 #8 x ¾-in. screws in the bottom of the furnace casing for each strap. (See Fig. 15 and
16.)
If the screws are attached to ONLY the furnace sides and not the bottom, the straps must be vertical against the furnace sides and not pull away from the furnace sides, so that the strap attachment screws are not in tension (are loaded in shear) for reliable support.
Platform Furnace Support
Construct working platform at location where all required furnace clearances are met. (See Fig. 2 and 17.) For furnaces with 1-in.
clearance requirement on side, set furnace on non-combustible blocks, bricks or angle iron. For crawlspace installations, if the furnace is not suspended from the floor joists, the ground underneath furnace must be level and the furnace set on blocks or bricks.
Roll-Out Protection
Provide a minimum 17-3/4
″ X 22″ piece of sheet metal for flame roll-out protection in front of burner area for furnaces closer than
12 inches above the combustible deck or suspended furnaces closer than 12 inches to joists. The sheet metal MUST extend underneath the furnace casing by 1 in. with the door removed.
The bottom closure panel on furnaces of widths 17-1/2 in. and larger may be used for flame roll-out protection when bottom of furnace is used for return air connection. See Fig. 17 for proper orientation of roll-out shield.
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return-air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following:
1. Tilt or raise furnace and remove 2 screws holding bottom filler panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom return-air opening. This panel MUST be in place when side return air inlet(s) are used without a bottom return air inlet.
B
A
PLENUM
OPENING
D
FLOOR
C
OPENING
FURNACE
(OR COIL CASING
WHEN USED)
COMBUSTIBLE
FLOORING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
A96283
Fig. 11—Floor and Plenum Opening Dimensions
A96285
Fig. 12—Furnace, Plenum, and Subbase Installed on a Combustible Floor
FURNACE
CD5 OR CK5
COIL ASSEMBLY
OR KCAKC
COIL BOX
COMBUSTIBLE
FLOORING
SHEET METAL
PLENUM
FLOOR
OPENING
FILTER ARRANGEMENT
A04140
Fig. 13—Furnace, Plenum, and Coil Assembly or Coil
Box Installed on a Combustible Floor
Not all horizontal furnaces are approved for side return air connections (See Fig. 20.)
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, or death.
Never operate a furnace without a filter or with filter access door removed.
There are no provisions for an internal filter rack in these furnaces.
An external filter rack is required.
12
A04140
This furnace is shipped with a factory-supplied Media Filter
Cabinet. The Media Filter Cabinet uses either a factory-supplied standard 1-inch filter or 4-inch wide Media Filter which can be purchased separately.
Refer to the instructions supplied with Media Cabinet for assembly and installation options.
AIR DUCTS
General Requirements
The duct system should be designed and sized according to accepted national standards such as those published by: Air
Conditioning Contractors Association (ACCA), Sheet Metal and
Air Conditioning Contractors National Association (SMACNA) or
American Society of Heating, Refrigerating and Air Conditioning
Engineers (ASHRAE) or consult The Air Systems Design Guide-
lines reference tables available from your local distributor. The
FURNACE
CASING
WIDTH
14–3/16
17–1/2
21
24-1/2
Table 4—Opening Dimensions (In.)
APPLICATION
PLENUM OPENING
A B
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on combustible flooring (KGASB
subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box (KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on combustible flooring (KGASB
subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box (KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on combustible flooring (KGASB
subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box (KGASB subbase not required)
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on Combustible flooring (KGASB
subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box (KGASB subbase not required)
12-11/16
12-9/16
11-13/16
12-5/16
16
15-7/8
15-1/8
15-1/2
19-1/2
19-3/8
18-5/8
19
23
22-7/8
22-1/8
22-1/2
21-5/8
19
19
19
21-5/8
19
19
19
21-5/8
19
19
19
21-1/8
19
19
19
20-1/8
20
20-1/4
20
23-5/8
23-1/2
23-3/4
23-1/2
FLOOR OPENING
C D
13-5/16 22-1/4
13-3/16
13-7/16
19-5/8
20-5/8
13-5/16 20
16-5/8
16-1/2
16-3/4
16-1/2
22-1/4
19-5/8
20-5/8
20
22-1/4
19-5/8
20-5/8
20
22-1/4
19-5/8
20-5/8
20 duct system should be sized to handle the required system design
CFM at the design external static pressure. The furnace airflow rates are provided in Table 5-Air Delivery-CFM (With Filter).
When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
Secure ductwork with proper fasteners for type of ductwork used.
Seal supply- and return-duct connections to furnace with code approved tape or duct sealer.
NOTE: Flexible connections should be used between ductwork
and furnace to prevent transmission of vibration.
Ductwork passing through unconditioned space should be insulated to enhance system performance. When air conditioning is used, a vapor barrier is recommended.
Maintain a 1-in. clearance from combustible materials to supply air ductwork for a distance of 36 in. horizontally from the furnace. See
NFPA 90B or local code for further requirements.
Ductwork Acoustical Treatment
NOTE: Metal duct systems that do not have a 90 degree elbow
and 10 ft of main duct to the first branch take-off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest
13 edition of SMACNA construction standard on fibrous glass ducts.
Both acoustical lining and fibrous ductwork shall comply with
NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
Supply Air Connections
For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the air stream. The cover attachment shall prevent leaks.
Upflow and Horizontal Furnaces
Connect supply-air duct to flanges on furnace supply-air outlet.
Bend flange upward to 90° with wide duct pliers. (See Fig. 14.)
The supply-air duct must be connected to ONLY the furnace supply-outlet-air duct flanges or air conditioning coil casing (when used). DO NOT cut main furnace casing side to attach supply air duct, humidifier, or other accessories. All accessories MUST be connected to duct external to furnace main casing.
NOTE: For horizontal applications, the top most flange may be
bent past 90 degrees to allow the evaporator coil to hang on the flange temporarily while the remaining attachment and sealing of the coil are performed.
Downflow Furnaces
UPFLOW
90˚
PREFERRED
D OWNFLOW
PREFERRED
HORIZONTAL
90˚
PREFERRED
120˚
MIN
PREFERRED
120˚
MIN
PREFERRED
120˚
MIN
PREFERRED
PERMITTED PERMITTED PERMITTED
Fig. 14—Duct Flanges
1
/
4
" THREADED ROD
4 REQ.
A02329
OUTER DOOR
ASSEMBLY
8" MIN FOR DOOR
REMOVAL
SECURE ANGLE
IRON TO BOTTOM
OF FURNACE WITH
3 #8 x 3
/
4
" SCREWS
TYPICAL FOR 2 SUPPORTS
1" SQUARE, 1 1
/
4
" x 1 1
/
4
" x 1
/
4
" ANGLE IRON
OR UNI-STRUT MAY BE USED
(2) HEX NUTS, (2) WASHERS & (2) LOCK WASHERS
REQ. PER ROD
Fig. 15—Horizontal Unit Suspension
14
A02345
METHOD 2
USE (4) #8 x 3/4 SHEET
METAL SCREWS FOR EACH
STRAP. THE STRAPS
SHOULD BE VERTICAL
AGAINST THE FURNACE
SIDES AND NOT PULL AWAY
FROM THE FURNACE
SIDES.
METHOD 1
FOLD ALL STRAPS UNDER
FURNACE AND SECURE WTH
(4) #8 x 3/4 SHEET METAL SCREWS
(2 SCREWS IN SIDE AND 2 SCREWS
IN BOTTOM).
A03176
Fig. 16—Horizontal Suspension with Straps
LINE CONTACT ONLY PERMISSIBLE BETWEEN
LINES FORMED BY INTERSECTIONS OF
THE TOP AND TWO SIDES OF THE FURNACE
JACKET AND BUILDING JOISTS,
STUDS, OR FRAMING.
GAS
ENTRY
TYPE-B
VENT
17
4
3
3
/
4
″ OVER ALL
/
4
″ UNDER DOOR
1
″ UNDER FURNACE
EXTEND OUT 12
″ OUT
FROM FACE OF DOOR
6″ MIN*
30-IN. MIN
WORK AREA
* WHEN USED WITH
SINGLE WALL VENT
CONNECTIONS
17
3
/
4
″
SHEET
METAL
22
″
EQUIPMENT MANUAL
SHUT-OFF GAS VALVE
SEDIMENT
TRAP
UNION
Fig. 17—Typical Attic Installation
A03177
Connect supply-air duct to supply-air outlet on furnace. Bend flange inward past 90° with wide duct pliers (See Fig. 14.) The supply-air duct must be connected to ONLY the furnace supply outlet or air conditioning coil casing (when used). When installed on combustible material, supply-air duct must be connected to
ONLY the accessory subbase, KGASB0201ALL, or a factory approved air conditioning coil casing. DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other accessories. All accessories MUST be connected to duct external to furnace casing.
Return Air Connections
15
FIRE HAZARD
A failure to follow this warning could cause personal injury, death and/or property damage.
Never connect return-air ducts to the back of the furnace.
Follow instructions below.
Downflow Furnaces
Fig. 18—Upflow Return Air Configurations and Restrictions
A02075
Fig. 19—Downflow Return Air Configurations and Restrictions
A02163
Fig. 20—Horizontal Return Air Configurations and Restrictions
16
A02162
Table 5—Air Delivery - CFM (With Filter)*
FURNACE
SIZE
Operating Mode
036070
†† Low Heat
††
High Heat
1-1/2 Tons Cooling
CFM Airflow
Setting
735 (615)†
1180 (1060)†
525
700
875
1050
1225
1400
985 (825)†
1210 (1090)†
525
700
875
1050
1225
1400
1600
External Static
Pressure Range
0 – 0.5
0 – 1.0
0 – 0.5‡
0 – 0.5‡
0 – 1.0‡
0 – 1.0‡
0 – 1.0
0 – 1.0
0.1 0.2
EXTERNAL STATIC PRESSURE (In. wc)**
0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
735 735 735 735 725
1160 1165 1175 1180 1180 1180 1180 1180 1180 1175
525
700
525
700
525
700
525
695
510
685
875 875 875 875 875 875 865 855 845 840
1050 1050 1050 1050 1050 1050 1050 1050 1045 1035
1205 1215 1225 1225 1225 1225 1225 1225 1225 1210
1395 1400 1400 1400 1400 1400 1400 1385 1360 1310
0 – 1.0
0 – 1.0
0 – 0.5‡
0 – 0.5‡
0 – 1.0‡
0 – 1.0‡
0 – 1.0‡
0 – 1.0
0 – 1.0
950 970 985 985 985 985 985 985 985 980
1190 1205 1210 1210 1210 1210 1210 1210 1210 1200
525
690
525
695
525
700
525
700
500
690
830 855 875 875 875 875 870 865 850 820
1005 1025 1040 1050 1050 1050 1050 1050 1050 1050
1205 1220 1215 1225 1225 1225 1225 1225 1225 1220
1370 1385 1395 1400 1400 1400 1400 1400 1400 1380
1565 1580 1585 1595 1600 1600 1560 1520 1480 1430
††
††
††
Low Heat
High Heat
2 Tons Cooling
2-1/2 Tons Cooling
3 Tons Cooling
3-1/2 Tons Cooling
4 Tons Cooling
5 Tons Cooling
1320 (1110)†
1475 (1330)†
700
875
1050
1225
1400
1750
0 – 1.0
0 – 1.0
0 – 0.5‡
0 – 0.5‡
0 – 0.5‡
0 – 1.0‡
0 – 1.0‡
0 – 1.0‡
1275 1295 1315 1320 1320 1320 1320 1320 1320 1315
1460 1465 1475 1475 1475 1475 1475 1475 1465 1465
700
860
700
875
700
865
685
855
660
840
1050 1050 1045 1050 1050
1185 1195 1215 1225 1225 1225 1225 1225 1225 1225
1385 1395 1400 1400 1400 1400 1400 1400 1400 1400
1710 1730 1745 1745 1750 1750 1750 1750 1745 1740
††
066135
††
††
††
066155
††
††
6 Tons Cooling
Maximum
Low Heat
High Heat
2 Tons Cooling
2-1/2 Tons Cooling
3 Tons Cooling
3-1/2 Tons Cooling
4 Tons Cooling
5 Tons Cooling
6 Tons Cooling
Maximum
Low Heat
High Heat
2 Tons Cooling
2-1/2 Tons Cooling
3 Tons Cooling
3-1/2 Tons Cooling
4 Tons Cooling
5 Tons Cooling
2100
2200
1700 (1430)†
1915 (1725)†
700
875
1050
1225
1400
1750
2100
2200
1715 (1440)†
1970 (1775)†
700
875
1050
1225
1400
1750
0 – 1.0
0 – 1.0
0 – 1.0
0 – 1.0
0 – 0.5‡
0 – 0.5‡
0 – 0.5‡
0 – 1.0‡
0 – 1.0‡
0 – 1.0‡
0 – 1.0
0 – 1.0
0 – 1.0
0 – 1.0
0 – 0.5‡
0 – 0.5‡
0 – 0.5‡
0 – 1.0‡
0 – 1.0‡
0 – 1.0‡
2090
2200
700
870
1010
1155
1395
1740
2075
2180
2100
2200
700
870
1030
1180
1400
1750
2085
2195
2100
2200
700
865
1050
1200
1400
1750
2090
2200
2100
2190
700
865
1050
1210
1400
1750
2100
2200
2095 2085
2185 2175
665
865
1050
1220 1225
1400 1400
1735 1740
2100 2100
2200 2200
2065
2155
1225
1400
1735
2090
2185
2045
2130
1225
1390
1730
2080
2165
2020
2085
1225
1375
1715
2055
2140
1990
2015
1700 1700 1700 1700 1700 1695 1700 1695 1685 1670
1900 1905 1915 1915 1915 1915 1915 1915 1915 1915
1225
1355
1700
2025
2095
1715 1715 1715 1715 1715 1705 1710 1705 1705 1695
1955 1965 1965 1970 1970 1970 1970 1970 1970 1960
700
865
1015
1160
1385
1745
700
875
1020
1185
1400
1750
700
875
1035
1215
1400
1750
700
865
1045
1225
1400
1750
680
865
1050
1225 1225
1400 1400
1745 1740
1225
1395
1745
1225
1395
1745
1225
1380
1740
1225
1360
1735
6 Tons Cooling
Maximum
2100
2200
0 – 1.0
0 – 1.0
2055 2070 2080 2085 2095 2100 2100 2100 2090 2065
2175 2190 2200 2200 2200 2200 2200 2200 2180 2160
* Actual external static pressure (ESP) can be determined by using the fan laws (CFM is proportional to ESP); such as a system with heating airflow of 1180 CFM at 0.5 ESP would operate at cooling airflow of 1050 CFM at 0.4 ESP and low-heating airflow of 735 CFM at 0.19 ESP.
** A filter is required for each return-air connection to the furnace. Airflow performance includes 1" washable filter media such as contained in factory-authorized accessory filter rack. To determine airflow performance without this filter, assume an additional 0.1" available external static pressure.
† "Comfort mode" airflow values are shown in (parenthesis). "Comfort mode" airflow is selected when the low-heat rise adjustment switch (SW1-3) is OFF and the comfort/efficiency switch (SW1-4) is ON. Furnaces are shipped in this configuration.
‡ Ductwork must be sized for the highest airflow, which is high-heating CFM and is greater than cooling CFM in this case.
Note also that heating ESP will be higher than cooling ESP for this system.
†† Operation within the blank areas of the chart is not recommended because high-heat airflow will be above 1.0 ESP.
*** All airflows on 110 size furnace are 5% less on side return only installations.
A04016
17
The return-air duct must be connected to return-air opening
(bottom inlet) as shown in Fig. 3. DO NOT cut into casing sides
(left or right). Side opening is permitted for only upflow and certain horizontal furnaces. Bypass humidifier connections should be made at ductwork or coil casing sides exterior to furnace. (See
Fig. 19.)
Upflow and Horizontal Furnaces
The return-air duct must be connected to bottom, sides (left or right), or a combination of bottom and side(s) of main furnace casing as shown in Fig. 3. Bypass humidifier may be attached into unused return air side of the furnace casing. (See Fig. 18 and 20.)
Not all horizontal furnace models are approved for side return air connections. (See Fig. 20.)
GAS PIPING
Table 6—Maximum Capacity of Pipe*
NOMINAL
IRON
PIPE
SIZE
(IN.)
1/2
3/4
1
1-1/4
1-1/2
INTERNAL
DIAMETER
(IN.)
0.622
0.824
1.049
1.380
1.610
10
175
360
680
1400
2100
LENGTH OF PIPE (FT)
20
120
250
465
950
1460
30
97
200
375
770
1180
40
82
170
320
660
990
50
73
151
285
580
900
* Cubic ft of natural gas per hr for gas pressures of 0.5 psig (14–in. wc) or less and a pressure drop of 0.5–in wc (based on a 0.60 specific gravity gas).
Ref: Table 12.2 ANSI Z223-2002/NFPA 54-2002.
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.
FIRE OR EXPLOSION HAZARD
A failure to follow this warning could result in personal injury, death, and/or property damage.
If local codes allow the use of a flexible gas appliance connector, always use a new listed connector. Do not use a connector which has previously served another gas appliance.
Black iron pipe shall be installed at the furnace gas control valve and extend a minimum of 2 in. outside the furnace.
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Use proper length of pipe to avoid stress on gas control manifold and a gas leak.
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Gas valve inlet and/or inlet pipe must remain capped until gas supply line is permanently installed to protect the valve from moisture and debris. Also, install a sediment trap in the gas supply piping at the inlet to the gas valve.
Gas piping must be installed in accordance with national and local codes. Refer to current edition of NFGC in the U.S. and the
NSCNGPIC in Canada.
Installations must be made in accordance with all authorities having jurisdiction. If possible, the gas supply line should be a separate line running directly from meter to furnace.
NOTE: In the state of Massachusetts:
1. Gas supply connections MUST be performed by a licensed plumber or gas fitter.
2. When flexible connectors are used, the maximum length shall not exceed 36 inches (915 mm).
3. When lever handle type manual equipment shutoff valves are used, they shall be T-handle valves.
4. The use of copper tubing for gas piping is NOT approved by the state of Massachusetts.
Refer to Table 6 for recommended gas pipe sizing. Risers must be used to connect to furnace and to meter. Support all gas piping with appropriate straps, hangers, etc. Use a minimum of 1 hanger every 6 ft. Joint compound (pipe dope) should be applied sparingly and only to male threads of joints. Pipe dope must be resistant to the action of propane gas.
18
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in furnace damage.
Connect gas pipe to furnace using a backup wrench to avoid damaging gas controls and burner misalignment.
An accessible manual equipment shutoff valve MUST be installed external to furnace casing and within 6 ft of furnace. A 1/8-in. NPT plugged tapping, accessible for test gauge connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual equipment shutoff valve.
NOTE: The furnace gas control valve inlet pressure tap connec-
tion is suitable to use as test gauge connection providing test pressure DOES NOT exceed maximum 0.5 psig (14-in. wc) stated on gas control valve. (See Fig. 53.)
Some installations require gas entry on right side of furnace (as viewed in upflow). (See Fig. 21a and 21b.)
Install a sediment trap in riser leading to furnace as shown in Fig
21c. Connect a capped nipple into lower end of tee. Capped nipple should extend below level of furnace gas controls. Place a ground joint union between furnace gas control valve and exterior manual equipment gas shutoff valve.
A 1/8-in. NPT plugged tapping, accessible for test gauge connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual equipment shutoff valve.
Piping should be pressure and leak tested in accordance with
NFGC in the United States or NSCNGPIC in Canada, local, and national plumbing and gas codes before the furnace has been connected. After all connections have been made, purge lines and check for leakage at furnace prior to operating furnace.
If pressure exceeds 0.5 psig (14-in. wc), gas supply pipe must be disconnected from furnace and capped before and during supply pipe pressure test. If test pressure is equal to or less than 0.5 psig
(14-in. wc), turn off electric shutoff switch located on furnace gas
A05028
Fig. 21a—Right Side Gas Entry Example 1
90
° Elbow
ELECTRICAL CONNECTIONS
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Blower access panel door switch opens 115-v power to control. No component operation can occur. Do not bypass or close switch with panel removed.
See Fig. 24 for field wiring diagram showing typical field 115-v wiring. Check all factory and field electrical connections for tightness.
Field-supplied wiring shall conform with the limitations of 63°F
(33°C) rise.
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
The cabinet MUST have an uninterrupted or unbroken ground according to NEC ANSI/NFPA 70-2002 and Canadian Electrical Code CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire, conduit approved for electrical ground or a listed, grounded power cord (where permitted by local code) when installed in accordance with existing electrical codes.
Refer to the power cord manufacturer’s ratings for proper wire gauge. Do not use gas piping as an electrical ground.
2" Nipple
Street Elbow
Gas Valve
A02327
Fig. 21b—Right Side Gas Entry Example 2
GAS
SUPPLY
MANUAL
SHUTOFF
VALVE
(REQUIRED
SEDIMENT
TRAP
UNION
Fig. 21c—Typical Gas Pipe Arrangement
A02035
FURNACE MAY NOT OPERATE
Failure to follow this caution may result in intermitent furnace operation.
Furnace control must be grounded for proper operation or else control will lock out. Control must remain grounded through green/yellow wire routed to gas valve and manifold bracket screw.
115-V WIRING
Verify that the voltage, frequency, and phase correspond to that specified on unit rating plate. Also, check to be sure that service provided by utility is sufficient to handle load imposed by this equipment. Refer to rating plate or Table 7 for equipment electrical specifications.
U.S. Installations: Make all electrical connections in accordance
with National Electrical Code (NEC) ANSI/NFPA 70-2002 and any local codes or ordinances that might apply.
Canadian Installations: Make all electrical connections in accor-
dance with Canadian Electrical Code CSA C22.1 or authorities having jurisdiction.
control valve and accessible manual equipment shutoff valve before and during supply pipe pressure test. After all connections have been made, purge lines and check for leakage at furnace prior to operating furnace.
The gas supply pressure shall be within the maximum and minimum inlet supply pressures marked on the rating plate with the furnace burners ON and OFF.
19
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire.
Use a separate, fused branch electrical circuit with a properly sized fuse or circuit breaker for this furnace. See Table 7 for wire size and fuse specifications. A readily accessible means of electrical disconnect must be located within sight of the furnace.
Table 7—Electrical Data
FURNACE SIZE
VOLTS-
HERTZ-
PHASE
070-12/036070
115-60-1
090-16/048090
115-60-1
110-20/060110
115-60-1
135-22/066135
115-60-1
155-22/066155
115-60-1
OPERATING
VOLTAGE RANGE
Maximum* Minimum*
127 104
127
127
127
127
104
104
104
104
MAXIMUM
UNIT AMPS
9.0
9.6
15.1
14.9
15.0
UNIT
AMPACITY#
11.99
12.56
19.33
19.13
19.23
MAXIMUM
WIRE LENGTH (FT)‡
30
29
29
30
29
MAXIMUM
FUSE OR CKT BKR
AMPS†
15
15
20
20
20
MINIMUM
WIRE GAUGE
14
14
12
12
12
* Permissible limits of the voltage range at which the unit operates satisfactorily.
# Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier, etc.) full load amps.
† Time-delay type is recommended.
‡ Length shown is as measured 1 way along wire path between furnace and service panel for maximum 2 percent voltage drop.
NOTE: Proper polarity must be maintained for 115-v wiring. If
polarity is incorrect, control LED status indicator light will flash rapidly and furnace will NOT operate.
J-BOX RELOCATION
NOTE: If factory location of J-Box is acceptable, go to next
section (ELECTRICAL CONNECTION to J-Box).
NOTE: On 14
″ wide casing models, the J-Box shall not be relocated to other side of furnace casing when the vent pipe is routed within the casing.
1. Remove and save two screws holding J-Box. (See Fig. 22.)
NOTE: The J-Box cover need not be removed from the J-Box in
order to move the J-Box. Do NOT remove green ground screw inside J-Box. The ground screw is not threaded into the casing flange and can be lifted out of the clearance hole in casing while swinging the front edge of the J-Box outboard of the casing.
2. Cut wire tie on loop in furnace wires attached to J-Box.
3. Move J-Box to desired location.
4. Fasten J-Box to casing with the two screws removed in Step
1.
5. Route J-Box wires within furnace away from sharp edges, rotating parts and hot surfaces.
ELECTRICAL CONNECTION TO J-BOX
Field-Supplied Electrical Box on Furnace J-Box Bracket
See Fig. 24.
1. Remove cover from furnace J-Box.
2. Attach electrical box to furnace J-Box bracket with at least two field-supplied screws through holes in electrical box into holes in bracket. Use blunt-nose screws that will not pierce wire insulation.
3. Route furnace power wires through holes in electrical box and
J-Box bracket, and make field-wire connections in electrical box. Use best practices (NEC in U.S. and CSA C22.1 in
Canada) for wire bushings, strain relief, etc.
4. Route and secure field ground wire to green ground screw on
J-Box bracket.
5. Connect line voltage leads as shown in Fig. 24.
6. Reinstall cover to J-Box. Do not pinch wires between cover and bracket.
Electrical Box on Furnace Casing Side
See Fig. 23.
Fig. 22—Relocating J-Box
TWO
A02099
20
FIRE OR ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
If field-supplied manual disconnect switch is to be mounted on furnace casing side, select a location where a drill or fastener cannot damage electrical or gas components.
1. Select and remove a hole knockout in the casing where the electrical box is to be installed.
NOTE: Check that duct on side of furnace will not interfere with
installed electrical box.
2. Remove the desired electrical box hole knockout and position the hole in the electrical box over the hole in the furnace casing.
3. Fasten the electrical box to casing by driving two fieldsupplied screws from inside electrical box into casing steel.
4. Remove and save two screws holding J-Box. (See Fig. 22.)
5. Pull furnace power wires out of 1/2-inch diameter hole in
J-Box. Do not loosen wires from strain-relief wire-tie on outside of J-Box.
6. Route furnace power wires through holes in casing and electrical box and into electrical box.
7. Pull field power wires into electrical box.
8. Remove cover from furnace J-Box.
9. Route field ground wire through holes in electrical box and casing, and into furnace J-Box.
Fig. 23—Field-Supplied Electrical Box on
Furnace Casing
A03221
10. Reattach furnace J-Box to furnace casing with screws removed in Step 4.
11. Secure field ground wire to J-Box green ground screw.
12. Complete electrical box wiring and installation. Connect line voltage leads as shown in Fig. 24. Use best practices (NEC in
U.S. and CSA C22.1 in Canada) for wire bushings, strain relief, etc.
13. Reinstall cover to J-Box. Do not pinch wires between cover and bracket.
POWER CORD INSTALLATION IN FURNACE J-BOX
NOTE: Power cords must be able to handle the electrical require-
ments listed in Table 7. Refer to power cord manufacturer’s listings.
1. Remove cover from J-Box.
2. Route listed power cord through 7/8-inch diameter hole in
J-Box.
3. Secure power cord to J-Box bracket with a strain relief bushing or a connector approved for the type of cord used.
4. Secure field ground wire to green ground screw on J-Box bracket.
5. Connect line voltage leads as shown in Fig. 24.
6. Reinstall cover to J-Box. Do not pinch wires between cover and bracket.
BX CABLE INSTALLATION IN FURNACE J-BOX
1. Remove cover from J-Box.
2. Route BX cable into 7/8-inch diameter hole in J-Box.
3. Secure BX cable to J-Box bracket with connectors approved for the type of cable used.
4. Secure field ground wire to green ground screw on J-Box bracket.
5. Connect line voltage leads as shown in Fig. 24.
6. Reinstall cover to J-Box. Do not pinch wires between cover and bracket.
24-V WIRING
Make field 24-v connections at the 24-v terminal strip. (See Fig.
25.) Connect terminal Y/Y2 as shown in Fig. 26-33 for proper cooling operation. Use only AWG No. 18, color-coded, copper thermostat wire.
The 24-v circuit contains an automotive-type, 3-amp fuse located on the control. Any direct shorts during installation, service, or maintenance could cause this fuse to blow. If fuse replacement is required, use ONLY a 3-amp fuse of identical size.
ACCESSORIES
1. Electronic Air Cleaner (EAC)
Connect an accessory Electronic Air Cleaner (if used) using
1/4-in female quick connect terminals to the two male 1/4-in quick-connect terminals on the control board marked EAC-1 and EAC-2. The terminals are rated for 115VAC, 1.0 amps maximum and are energized during blower motor operation.
(See Fig. 25.)
2. Humidifier (HUM)
Connect an accessory 24 VAC, 0.5 amp maximum humidifer
(if used) to the 1/4-in male quick-connect HUM terminal and
C
OM
-24V screw terminal on the control board thermostat strip.
The HUM terminal is energized when blower is energized in heating. (See Fig. 25.)
NOTE: DO NOT connect furnace control HUM terminal to HUM
(humidifier) terminal on Thermidistat, Zone Controller or similiar device. See Thermidistat™, Zone Controller, thermostat, or controller manufacturer’s instructions for proper connection.
VENTING
The furnace shall be connected to a listed factory built chimney or vent, or a clay-tile lined masonry or concrete chimney. Venting into an unlined masonry chimney or concrete chimney is prohibited.
When an existing Category I furnace is removed or replaced, the original venting system, may no longer be sized to properly vent the attached appliances. An improperly sized Category I venting system could cause the formation of condensate in the furnace and vent, leakage of condensate and combustion products, and spillage of combustion products into the living space.
21
FIELD 24-VOLT WIRING
FIELD 115-, 208/230-, 460-VOLT WIRING
FACTORY 24-VOLT WIRING
FACTORY 115-VOLT WIRING
FIVE
WIRE
THREE-WIRE
HEATING-
ONLY
NOTE 2
W C Y R G
1-STAGE
THERMOSTAT
TERMINALS
FIELD-SUPPLIED
FUSED DISCONNECT
208/230- OR
460-VOLT
THREE
PHASE
BLK BLK
W2
COM
WHT WHT
W/W1
GND
115-VOLT FIELD-
SUPPLIED
FUSED
DISCONNECT
JUNCTION
BOX
CONTROL
BOX
Y/Y2
R
G
24-VOLT
TERMINAL
BLOCK
FURNACE
NOTE 1
NOTES: 1.
2.
3.
CONDENSING
UNIT
GND
208/230-
VOLT
SINGLE
PHASE
Connect Y/Y2-terminal as shown for proper operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use same type or equivalent wire.
Fig. 24—Field Wiring Diagram
A95236
22
MODEL PLUG
CONNECTOR
SW1 SETUP
SWITCHES AND
BLOWER OFF-
DELAY
AIR CONDITIONING
(A/C) AIRFLOW
SETUP SWITCHES
COMMUNICATION
CONNECTOR
CONTINUOUS FAN
(CF) AIRFLOW
SETUP SWITCHES
FUTURE
APPLICATIONS
24-V THERMOSTAT
TERMINALS
HUMIDIFIER
TERMINAL (24-VAC
0.5 AMP MAX.
ACRDJ – AIR
CONDITIONING
RELAY DISABLE
JUMPER
FLASH
UPGRADE
CONNECTOR
(FACTORY
ONLY)
STATUS AND COMM
LED LIGHTS
3-AMP FUSE
TRANSFORMER 24-VAC
CONNECTIONS
PL3 – ECM BLOWER
HARNESS
CONNECTOR
115-VAC (L2) NEUTRAL
CONNECTIONS
PL1 – LOW VOLTAGE MAIN
HARNESS CONNECTOR
EAC-1 TERMINAL
(115-VAC 1.0 AMP MAX.)
115-VAC (L1) LINE
VOLTAGE CONNECTIONS
PL2 – HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
A02018
Fig. 25—Variable Speed Furnace Control for ECM Blower Motor
23
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI
Z223.1-2002/NFPA 54 or the CSA B149.1, Natural Gas and Propane Installation Code and these instructions.
Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies, which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1-
2002/NFPA 54 and/or CSA B149.1, Natural Gas and
Propane Installation Code.
9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning appliance to their previous conditions of use.
Vent system or vent connectors may need to be resized. Vent systems or vent connectors must be sized to approach minimum size as determined using appropriate table found in the NFGC or
NSCNGPIC.
GENERAL VENTING REQUIREMENTS
Follow all safety codes for proper vent sizing and installation requirements, including local building codes, the National Fuel
Gas Code ANSI Z223.1-2002/NFPA 54-2002 (NFGC), Parts 10 and 13 in the United States or the National Standard of Canada,
Natural Gas and Propane Installation Code CSA-B149.1-00
(NSCNGPIC) Section 7 and Appendix C in Canada, the local building codes, and furnace and vent manufacturers’ instructions.
These furnaces are design-certified as Category I furnaces in accordance with ANSI Z21.47-2003/CSA 2.3-2003 and operate with a non-positive vent static pressure to minimize the potential for vent gas leakage. Category I furnaces operate with a flue loss not less than 17 percent to minimize the potential for condensation in the venting system. These furnaces are approved for common venting and multi-story venting with other fan assisted or draft hood equipped appliances in accordance with the NFCG or the
NSCNGPIC, the local building codes, and furnace and vent manufacturers’ instructions.
24
A00275
Fig. 26—Two-Stage Furnace with Single-Speed
Air Conditioner
The following information and warning must be considered in addition to the requirements defined in the NFGC or the NSCNG-
PIC.
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Do not bypass the draft safeguard switch, as an unsafe condition could exist which must be corrected.
1. If a vent (common or dedicated) becomes blocked, the furnace will be shut off by the draft safeguard switch located on the vent elbow.
2. Two-stage furnaces require Type B vent connectors outside the casing in all configurations. Single wall vent connector may be used inside the furnace casing with the transition to
Type B vent outside the furnace casing. Size the connector so that the FAN-Min vent connector capacity is equal to or lower than the low fire rate of the furnace and the FAN-Max vent connector capacity is equal to or higher than the furnace high fire rate.
3. Do not vent this Category I furnace into a single wall dedicated or common vent. The dedicated or common vent is considered to be the vertical portion of the vent system that terminates outdoors.
4. Vent connectors serving Category I furnaces shall not be connected into any portion of a mechanical draft system operating under positive pressure.
5. In the US: Do not vent this appliance with any solid fuel burning appliance.
In Canada: Check with the authority having jurisdiction for approval on use with solid fuel burning appliance.
See notes 2, 5, 8, 10, 11 and 12 on the page following these figures
A03179
Fig. 27—Two-Stage Furnace with Two-Speed
Air Conditioner
See notes 1, 2, 4, 6, 7, 9, 10, 11, and 15 on the page following these figures
A03180
Fig. 28—Two-Stage Furnace with Single-Speed
Heat Pump (Dual Fuel)
See notes 1, 2, 3, 4, 6, 8, 9, 10, 12, 13 and 15 on the page following these figures
Fig. 29—Two-Stage Furnace with Two-Speed Heat Pump (Dual Fuel)
25
A03178
See notes 1, 2, 4, 11, 14, 15, and 16 on the page following these figures
A03181
Fig. 30—Dual Fuel Thermostat with Two-Stage
Furnace and Single-Speed Heat Pump
See notes 2, 11, and 12 on the page following these figures
A03183
Fig. 32—Two-Stage Thermostat with Two-Stage
Furnace and Two-Speed Air Conditioner
1
See notes 1 and 2 on the page following these figures
A03184
Fig. 33—Single-Stage Thermostat with
Two-Stage Furnace and Two-Speed Air Conditioner
See notes 1, 2, 3, 4, 12, 13, 14, 15, and 17 on the page following these figures
A03182
Fig. 31—Dual Fuel Thermostat with Two-Stage
Furnace and Two-Speed Heat Pump
26
NOTES FOR FIGURES 26-33
1. Heat pump MUST have a high pressure switch for dual fuel applications.
2. Refer to outdoor equipment Installation Instructions for additional information and setup procedure.
3. If the heat pump date code is 1501E or earlier, select the
″ZONE″ position on the two-speed heat pump control. Heat pumps having date codes 1601E and later do not have or require a
″ZONE″ selection.
4. Outdoor Air Temperature Sensor must be attached in all dual fuel applications.
5. Dip switch No. 1 on Thermidistat should be set in OFF position for air conditioner installations. This is factory default.
6. Dip switch No. 1 on Thermidistat should be set in ON position for heat pump installations.
7. Dip switch No. 2 on Thermidistat should be set in OFF position for single-speed compressor operation. This is factory default.
8. Dip switch No. 2 on Thermidistat should be set in ON position for two-speed compressor operation.
9. Configuration Option No. 10 “Dual Fuel Selection” must be turned ON in all dual fuel applications.
10. NO connection should be made to the furnace HUM terminal when using a Thermidistat.
11. Optional connection: If wire is connected, dip switch SW1-2 on furnace control should be set in ON position to allow
Thermidistat/Thermostat to control furnace staging.
12. Optional connection: If wire is connected, ACRDJ jumper on furnace control should be removed to allow Thermidistat/Thermostat to control outdoor unit staging.
13. Furnace must control its own high-stage heating operation via furnace control algorithm.
14. The RVS Sensing terminal “L” should not be connected. This is internally used to sense defrost operation.
15. DO NOT SELECT the “FURNACE INTERFACE” or “BALANCE POINT” option on the two-speed heat pump control board. This is controlled internally by the Thermidistat/Dual Fuel Thermostat.
16. Dip switch D on Dual Fuel Thermostat should be set in OFF position for single-speed compressor operation. This is factory default.
17. Dip switch D on Dual Fuel Thermostat should be set in ON position for two-speed compressor operation.
27
CHIMNEY INSPECTION CHART
For additional requirements refer to the National Fuel Gas Code NFPA 54/ANSI Z223.1 and ANSI/NFPA 211
Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances in the U.S.A. or to the Canadian
installation Code CSA-B149.1 in Canada.
Crown condition:
Missing mortar or brick?
No
Yes
Rebuild crown.
Is chimney property lined with clay tile liner?
No
Yes
Is liner and top seal in good condition?
Yes
No
Repair liner or top seal or reline chimney as necessary.
Reline
Repair
Debris in cleanout?
Mortar, tile, metal vent, fuel oil residue?
Yes
No
Remove metal vent or liner.
Mortar or tile debris?
No
Yes
Remove mortar and tile debris
Clay tile misalignment, missing sections, gaps?
Yes
No
Condensate drainage at bottom of chimney?
No
Chimney exposed to outdoors below roof line?
No
Yes
Yes
No
Is chimney lined with properly
Consult
Part B of chimney adapter venting instructions for application suitability.
Suitable sized, listed liner or
Type-B vent?
Yes
Yes
Not Suitable
Install chimney adapter per instructions.
Not Suitable
Is chimney to be dedicated to a single furnace?
No
Line chimney with property sized, listed flexible metal liner or Type-B vent per
NFGC or NSCNGPIC Vent
Sizing Tables and liner or vent manufacturer’s
Installation instructions.
Consult
Part C of chimney adapter venting instructions for application suitability
Suitable
Install chimney adapter per instructions.
Chimney is acceptable for use.
Fig. 34—Chimney Inspection Chart
28
A03206
6. Category I furnaces must be vented vertically or nearly vertically unless equipped with a listed mechanical venter. See
SIDEWALL VENTING section.
7. Do not vent this appliance into an unlined masonry chimney.
Refer to Chimney Inspection Chart, Fig. 34.
MASONRY CHIMNEY REQUIREMENTS
NOTE: These furnaces are CSA design-certified for use in
exterior tile-lined masonry chimneys with a factory accessory
Chimney Adapter Kit. Refer to the furnace rating plate for correct kit usage. The Chimney Adapter Kits are for use with ONLY furnaces having a Chimney Adapter Kit number marked on the furnace rating plate.
If a clay tile-lined masonry chimney is being used and it is exposed to the outdoors below the roof line, relining might be required.
Chimneys shall conform to the Standard for Chimneys, Fireplaces,
Vents, and Soild Fuel Burning Appliances ANSI/NFPA 211-2003 in the United States and to a Provincial or Territorial Building
Code in Canada (in its absence, the National Building Code of
Canada) and must be in good condition.
U.S.A.-Refer to Sections 13.1.9 and 13.2.20 of the NFGC or the
authority having jurisdiction to determine whether relining is required. If relining is required, use a properly sized listed metal liner, Type-B vent, or a listed alternative venting design.
NOTE: See the NFGC 13.1.9 and 13.2.20 regarding alternative
venting design and the exception, which cover installations such as our Chimney Adapter Kits KGACA02014FC and
KGACA02015FC, which are listed for use with these furnaces.
The Chimney Adapter Kit is a listed alternative venting system for these furnaces. See the kit instructions for complete details.
Canada (and U.S.A.)-This furnace is permitted to be vented into
a clay tile-lined masonry chimney that is exposed to the outdoors below the roof line, provided:
1. Vent connector is Type-B double-wall, and
2. This furnace is common vented with at least 1 draft hoodequipped appliance, and
3. The combined appliance input rating is less than the maximum capacity given in Table A, and
4. The input rating of each space heating appliance is greater than the minimum input rating given in Table B for the local
99% Winter Design Temperature. Chimneys having internal areas greater than 38 square inches require furnace input ratings greater than the input ratings of these furnaces. See footnote at bottom of Table B, and
5. The authority having jurisdiction approves.
If all of these conditions cannot be met, an alternative venting design shall be used, such as the listed chimney adapter kit with a furnace listed for use with the kit, a listed chimney-lining system, or a Type-B common vent.
Inspections before the sale and at the time of installation will determine the acceptability of the chimney or the need for repair and/or (re)lining. Refer to the Fig. 34 to perform a chimney inspection. If the inspection of a previously used tile-lined chimney: a. Shows signs of vent gas condensation, the chimney should be relined in accordance with local codes and the authority having jurisdiction. The chimney should be relined with a listed metal liner, Type-B vent, or a listed chimney adapter kit shall be used to reduce condensation. If a condensate drain is required by local code, refer to the NFGC, Section
10.9 for additional information on condensate drains.
29 b. Indicates the chimney exceeds the maximum permissible size in the tables, the chimney should be rebuilt or relined to conform to the requirements of the equipment being installed and the authority having jurisdiction.
A chimney without a clay tile liner, which is otherwise in good condition, shall be rebuilt to conform to ANSI/NFPA 211 or be lined with a UL listed (ULC listed in Canada) metal liner or UL listed Type-B vent. Relining with a listed metal liner or Type-B vent is considered to be a vent-in-a-chase.
If a metal liner or Type-B vent is used to line a chimney, no other appliance shall be vented into the annular space between the chimney and the metal liner.
Exterior Masonry Chimney FAN + NAT
Installations with Type-B Double-Wall Vent
Connectors
©NFPA & AGA
Table A—Combined Appliance Maximum Input
Rating in Thousands of BTU per Hour
VENT HEIGHT (FT)
6
8
10
15
20
30
80
84
NR
NR
NR
INTERNAL AREA OF CHIMNEY
(SQ. IN.)
12
74
19
119
28
178
38
257
130
138
152
NR
NR
193
207
233
250
NR
279
299
334
368
404
APPLIANCE APPLICATION REQUIREMENTS
Appliance operation has a significant impact on the performance of the venting system. If the appliances are sized, installed, adjusted, and operated properly, the venting system and/or the appliances should not suffer from condensation and corrosion. The venting system and all appliances shall be installed in accordance with applicable listings, standards, and codes.
The furnace should be sized to provide 100 percent of the design heating load requirement plus any margin that occurs because of furnace model size capacity increments. Heating load estimates can be made using approved methods available from Air Conditioning Contractors of America (Manual J); American Society of
Heating, Refrigerating, and Air-Conditioning Engineers; or other approved engineering methods. Excessive oversizing of the furnace could cause the furnace and/or vent to fail prematurely.
When a metal vent or metal liner is used, the vent must be in good condition and be installed in accordance with the vent manufacturer’s instructions.
To prevent condensation in the furnace and vent system, the following precautions must be observed:
1. The return-air temperature must be at least 60°F db except for brief periods of time during warm-up from setback at no lower than 55°F db or during initial start-up from a standby condition.
2. Adjust the gas input rate per the installation instructions. Low gas input rate causes low vent gas temperatures, causing condensation and corrosion in the furnace and/or venting system. Derating is permitted only for altitudes above 2000 ft.
3. Adjust the air temperature rise to the midpoint of the rise range or slightly above. Low air temperature rise can cause low vent gas temperature and potential for condensation problems.
4. Set the thermostat heat anticipator or cycle rate to reduce short cycling.
Table B—Minimum Alowable Input Rating of
Space-Heating Appliance in
Thousands of BTU per Hour
VENT
HEIGHT (FT)
12
INTERNAL AREA OF CHIMNEY
(SQ. IN.)
19 28 38
Local 99% Winter Design
Temperature: 17 to 26 degrees F*
6
8
10
15
20
30
6
8
10
15
20
0
52
NR
NR
NR
NR
55
74
90
NR
NR
Local 99% Winter Design
Temperature: 5 to 16 degrees F*
NR
NR
NR
NR
NR
NR
78
94
111
NR
NR
99
111
125
167
212
NR
121
135
149
193
NR
141
154
169
212
258
362
166
182
198
247
293
377 30
6
8
10
15
NR NR
Local 99% Winter Design
Temperature: -10 to 4 degrees F*
NR
NR
NR
NR
NR
NR
NR
NR
NR
20
30
NR
NR
NR
NR
NR
NR
Local 99% Winter Design
Temperature: -11 degrees F or lower*
145
159
175
NR
196
213
231
283
333
NR
3 screws that secure vent elbow to furnace, rotate furnace vent elbow to position desired, re-install screws. The factory-supplied vent elbow does NOT count as part of the number of vent connector elbows.
The vent connector can exit the door through one of 5 locations on the door.
1. Attach the single wall vent connector to the furnace vent elbow, and fasten the vent connector to the vent elbow with at least two field-supplied, corrosion-resistant, sheet metal screws located 180° apart.
NOTE: An accessory flue extension KGAFE0112UPH is avail-
able to extend from the furnace elbow to outside the furnace casing. If flue extension is used, fasten the flue extension to the vent elbow with at least two field-supplied, corrosion-resistant, sheet metal screws located 180° apart. Fasten the vent connector to the flue extension with at least two field-supplied, corrosionresistant sheet metal screws located 180° apart.
2. Vent the furnace with the appropriate connector as shown in
Fig 35-47.
Not recommended for any vent configuration
*The 99% Winter Design Dry-Bulb (db) temperatures are found in the 1993
ASHRAE Fundamentals Handbook, Chapter 24, Table 1 (United States) and
2 (Canada), or use the 99.6% heating db temperatures found in the 1997 or
2001 ASHRAE Fundamentals Handbook, Climatic Design Information chapter, Table 1A (United States) and 2A (Canada).
Air for combustion must not be contaminated by halogen compounds which include chlorides, fluorides, bromides, and iodides.
These compounds are found in many common home products such as detergent, paint, glue, aerosol spray, bleach, cleaning solvent, salt, and air freshener, and can cause corrosion of furnaces and vents. Avoid using such products in the combustion-air supply.
Furnace use during construction of the building could cause the furnace to be exposed to halogen compounds, causing premature failure of the furnace or venting system due to corrosion.
Vent dampers on any appliance connected to the common vent can cause condensation and corrosion in the venting system. Do not use vent dampers on appliances common vented with this furnace.
ADDITIONAL VENTING REQUIREMENTS
A 4
″ round vent elbow is supplied with the furnace. A 5-inch or 6inch vent connector may be required for some model furnaces. A field-supplied 4-inch to 5-inch or 4-inch to 6-inch sheet metal increaser fitting is required when 5-inch or 6-inch vent connector is used. See Fig. 35-47, Venting Orientation for approved vent configurations.
NOTE: Vent connector length for connector sizing starts at
furnace vent elbow. The 4-inch vent elbow is shipped for upflow configuration and may be rotated for other positions. Remove the
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces.
3. Orient the door to determine the correct location of the door knockout to be removed.
4. Use aviation-type tin snips to remove the correct U-shaped knockout in door.
NOTE:
A number of techniques can be used to remove these knockouts as seen in Fig. 48 through 52. The knockout in the bottom of the door is unique due to its flanging and is not easily removed by first cutting the two tie points at the edge of the door, using aviation-type tin snips. (See Fig. 48.) A sharp blow to the rounded end of the knockout (See Fig. 49.) will separate more tie points and allow the knockout to be pulled loose. (See Fig. 50.)
Remove any burrs and sharp edges.
For the rectangular J-box knockout, use tin snips along the door edge and use a sharp blow with a hammer to remove the knockout.
Remove any burrs and sharp edges.
For the knockouts in the other locations on the door (top and sides), tin snips can also be used along the door edges; however, the preferred method is to use a hammer and screwdriver to strike a sharp blow (See Fig. 51.) directly to the knockout tie points or use a hammer in the upper left corner of the desired knockout. (See
Fig. 52.) Remove any burrs and sharp edges.
NOTE: If a knockout does not come out after two sharp blows,
pull and snip as needed to remove the knockout. Additional blows may cause damage to the door.
30
BURN HAZARD
Failure to follow this caution may result in personal injury.
Hot vent pipe is within reach of small children when installed in downflow position.
See the following instruction.
An accessory Vent Guard Kit, KGAVG0101DFG is REQUIRED for downflow applications for use where the vent exits through the lower portion of the furnace casing door. Refer to the Vent Guard
Kit Instructions for complete details.
SEE NOTES: 1,2,4,7,8,9 on the page following these figures
Fig. 35—Upflow Application-Vent Elbow Up
A03208
SEE NOTES: 1,2,4,5,7,8,9 on the page following these figures
A03211
Fig. 38—Downflow Application-Vent Elbow Up
SEE NOTES: 1,2,3,4,7,8,9 on the pages following these figures
A03209
Fig. 36—Upflow Application-Vent Elbow Right
SEE NOTES: 1,2,4,5,6,7,8,9,10 on the page following these figures
Fig. 39—Downflow Application-
Vent Elbow Left then Up
A03207
SEE NOTES:1,2,3,4,5,7,8,9 on the page following these figures
Fig. 37—Downflow Application-
Vent Elbow Up then Left
A03210
31
SEE NOTES:1,2,3,4,5,7,8,9 on the page following these figures.
Fig. 40—Downflow Application-
Vent Elbow Up then Right
A03212
SEE NOTES: 1,2,4,7,8,9 on the page following these figures
A03213
Fig. 41—Horizontal Left Application-Vent Elbow Left
SEE NOTES: 1,2,4,5,7,8,9 on the page following these figures
A03215
Fig. 43—Horizontal Left Application-Vent Elbow Up
SEE NOTES: 1,2,4,5,7,8,9 on the page following these figures
Fig. 42—Horizontal Left Application-
Vent Elbow Right then Up
A03214
SEE NOTES: 1,2,4,5,7,8,9 on the page following these figures
A03216
Fig. 44—Horizontal Left Application-Vent Elbow Right
SEE NOTES: 1,2,4,7,8,9 on the page following these figures
Fig. 45—Horizontal Right Application-
Vent Elbow Right
A03218
SEE NOTES: 1,2,4,5,7,8,9 on the page following these figures
Fig. 46—Horizontal Right Application-
Vent Elbow Left then Up
A03219
SEE NOTES: 1,2,4,5,7,8,9
Fig. 47—Horizontal Right Application-Vent Elbow Left
32
A02068
Caution!! For the following applications, use the minimum vertical heights as specified below
For all other applications, follow exclusively the National Fuel Gas Code
FURNACE ORIENTATION VENT ORIENTATION FURNACE INPUT(BTU/HR)
MINIMUM
VENT DIAMETER (IN.)*
Downflow
Vent elbow left, then up
Fig. 37
154,000
132,000
110,000(036/-12 only)
Horizontal Left
Horizontal Left
Vent elbow right, then up
Fig. 40
Vent Elbow up
Fig. 41
154,000
132,000
154,000
132,000
Horizontal Left
Downflow
Downflow
Vent elbow right
Fig. 42
Vent elbow up then left
Fig. 35
Vent elbow up, then right
Fig. 38
154,000
110,000
(036/-12 only)
110,000
(036/-12 only)
NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC.
*4 in. inside casing or vent guard
**Including 4 in. vent section(s)
5
5
5
5
5
5
MINIMUM VERTICAL VENT HEIGHT (FT)**
12
7
7
7
10
10
Venting Notes for Fig. 35-47
1. For common vent, vent connector sizing and vent material:
United States--use the NFGC
Canada--use the NSCNGPIC
2. Immediately increase to 5-inch or 6-inch vent connector outside furnace casing when 5-inch vent connector is required, refer to Note 1 above.
3. Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace, except when
KGAVG0101DFG, Downflow Vent Guard Kit, is used in the downflow position.
4. Type-B vent where required, refer to Note 1 above.
5. Four-inch single-wall (26 ga. min.) vent must be used inside furnace casing and when the KGAVG0101DFG Downflow Vent Guard Kit is used external to the furnace.
6. Accessory Downflow Vent Guard Kit, KGAVG0101DFG required in downflow installations with lower vent configuration.
7. Chimney Adapter Kit may be required for exterior masonry chimney applications. Refer to Chimney Adapter Kit, KGACA02014FC or
KGACA02015FC, for sizing and complete application details.
8. Secure vent connector to furnace elbow with (2) corrosion-resistant sheet metal screws, spaced approximately 180° apart.
9. Secure all other single wall vent connector joints with (3) corrosion resistant screws spaced approximately 120° apart. Secure Type-B vent connectors per vent connector manufacturer’s recommendations.
10. The total height of the vent and connector shall be at least seven feet for the 154,000 Btuh gas input rate model when installed in a downflow application with furnace elbow turned to left side with the connector elbow outside furnace casing pointing upward. (See Fig.
39.)
The horizontal portion of the venting system shall slope upwards not less than 1/4-in. per linear ft (21 mm/m) from the furnace to the vent and shall be rigidly supported every 5 ft or less with metal hangers or straps to ensure there is no movement after installation.
SIDEWALL VENTING
This furnace is not approved for direct sidewall horizontal venting.
In the U.S.: Per section 10.3.4 of the NFGC, any listed mechanical
venter may be used, when approved by the authority having jurisdiction.
In Canada: Per section 7.24.2 of the NSCNGPIC, any listed
mechanical venter may be used, when approved by the authority having jurisdiction.
Select the listed mechanical venter to match the Btuh input of the furnace being vented. Follow all manufacturer’s installation requirements for venting and termination included with the listed mechanical venter.
33
START-UP, ADJUSTMENT, AND SAFETY CHECK
Step 1—General
FIRE HAZARD
Failure to follow this warning could result in personal injury, death or property damage.
This furnace is equipped with manual reset limit switches in the gas control area. The switches open and shut off power to the gas valve, if a flame rollout or overheating condition occurs in the gas control area. DO NOT bypass the switches.
Correct problem before resetting the switches.
1. Maintain 115-v wiring and ground. Improper polarity will result in rapid flashing LED and no furnace operation.
2. Make thermostat wire connections at the 24-v terminal block on the furnace control. Failure to make proper connections
Fig. 48—Using Tin Snips to Cut Tie Points
A04127
Fig. 49—Rounded End of Knockout
A04128
A04130
Fig. 51—Hammer and Screwdriver Used for
Knockout
Fig. 52—Remove Knockout with Hammer
A04131
A04129
Fig. 50—Knockout Pulled Loose
will result in improper operation. (See Fig. 24.)
3. Gas supply pressure to the furnace must be greater than 4.5-in.
wc (0.16 psig ) but not exceed 14-in. wc (0.5 psig).
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces.
4. Check all manual-reset switches for continuity.
34
5. Replace blower compartment door. Door must be in place to operate furnace.
6. Setup switch descriptions
The variable speed furnace control has DIP switches to select thermostat staging, blower off delay timings, air flow selection and other operational or service related functions. (See Fig.
25, 57 and Table 8.)
ON/OFF SWITCH
1/2˝ NPT INLET
INLET
PRESSURE TAP
MANIFOLD
PRESSURE TAP
1/2˝ NPT OUTLET
A04167
Fig. 53—Redundant Automatic Gas Control Valve
BURNER
ORIFICE
Fig. 54—Orifice Hole
THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)
HOOK-AROUND
AMMETER
A93059
R Y W G
10 TURNS
REGULATOR COVER SCREW
PLASTIC ADJUST SCREW
REGULATOR SPRING
HIGH STAGE GAS
PRESSURE REGULATOR
ADJUSTMENT
LOW STAGE
GAS PRESSURE
REGULATOR ADJUSTMENT
Step 2—Start-Up Procedures
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could cause personal injury, death or property damage.
Never purge a line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition for the purpose of checking leakage. Use a soap-and-water solution to check for leakage.
1. Purge gas lines after all connections have been made.
2. Check gas lines for leaks.
FROM UNIT 24-V
CONTROL TERMINALS
EXAMPLE:
5.0 AMPS ON AMMETER
10 TURNS AROUND JAWS
=
0.5 AMPS FOR THERMOSTAT
ANTICIPATOR SETTING
Fig. 55—Amp Draw Check With Ammeter
A96316
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, or death.
Blower access door switch opens 115-v power to control. No component operation can occur unless switch is closed.
Caution must be taken when manually closing this switch for service purposes.
3. To Begin Component Self-Test:
Remove Blower Access Door. Disconnect the thermostat R lead from furnace control board. Manually close blower door switch. Turn Setup DIP switch SW1-6 ON. (See Fig. 25, 57 and Table 8.)
NOTE: The furnace control allows all components, except the gas
valve, to be run for short period of time. This feature helps diagnose a system problem in case of a component failure.
Component test feature will not operate if any thermostat signal is present at the control.
Refer to service label attached to furnace or See Fig. 56.
Component test sequence is as follows: a. Inducer motor starts on high-speed and continues to run until Step d. of component test sequence.
b. Hot surface igniter is energized for 15 sec., then off.
c. Blower motor operates for 15 sec.
d. Inducer motor goes to low-speed for 10 sec., then stops.
e. After component test is completed, one or more status codes (11, 25, or 41) will flash. See component test section of service label (Fig. 56) in furnace for explanation of status codes.
NOTE: To repeat component test, turn setup switch SW1-6 OFF,
then back ON.
4. Turn setup DIP switch SW1-6 OFF. Reconnect R lead to furnace control board, release blower door switch and reinstall blower access door.
5. Operate furnace per instruction on inner door.
6. Verify furnace shut down by lowering thermostat setting below room temperature.
7. Verify furnace restarts by raising thermostat setting above room temperature.
35
SETUP
SWITCH NO.
SW1-1
SW1-2
SW1-3
SW1-4
SW1-5
SW1-6
SW1-7
SW1-8
SWITCH
NAME
Low Heat
Rise Adjust
Table 8—Furnace Setup Switch Description
Status Code Recovery
Adaptive Heat Mode
Comfort/Efficiency Adjustment
CFM per ton adjust
Component Self-Test
Blower OFF delay
Blower OFF delay
NORMAL
POSITION
OFF
OFF
OFF
ON
OFF
OFF
ON or OFF
ON or OFF
DESCRIPTION
OF USE
Turn ON to retrieve up to 7 stored status codes for troubleshooting assistance when R thermostat lead is disconnected.
Allows 2-stage operation with a single stage thermostat.
Turn ON when using 2 stage thermostat to allow Low Heat operation when R to W/W1 closes and High Heat operation when R to
W/W1 and W2 close.
Turn ON to increase Low Heat airflow by 18 percent. This compensates for increased return air temperature caused with bypass humidifier.
Turn ON to decrease Low Heat airflow by 16 percent and High Heat airflow 10 percent for maximum comfort.
Turn ON for 400 CFM per ton. Turn OFF for 350 CFM per ton.
Turn ON to initiate Component Self-Test for troubleshooting assistance when R thermostat lead is disconnected.
Turn OFF when Self-Test is completed.
Control blower Off Delay time. Used in conjunction with SW1-8. See
Table 10.
Control blower Off Delay time. Used in conjunction with SW1-7. See
Table 10.
SERVICE
LED CODE STATUS
CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2.
CONTINUOUS ON - Control has 24VAC power.
RAPID FLA SHING - Line voltage (115VAC) polarity reversed.
If status code recall is needed disconnect the "R" thermostat lead, reset power, and put setup switch "SW1-1" in the ON position. To clear the status code history put setup switch "SW1-1" in the ON position and jumper thermostat terminals "R",
"W/W1", and "Y/Y2" simultaneously until status code #11 is flashed.
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES.
11 NO PREVIOUS CODE - Stored status codes are erased automatically after 72 hours or as specified above.
12 BL OWER ON AFTER POWER UP (115 VAC or 24 VAC) -Blower runs for 90 seconds, if unit is powered up during a call for heat (R-W/W1 closed) or
(R-W/W1 opens) during blower on-delay period.
13 LIMIT CIRCUIT LOCKOUT - Lockout occurs if a limit, draft safeguard, flame rollout, or blocked vent switch (if used) is open longer than 3 minutes or 10 successive limit trips occurred during high-heat. Control will auto reset after three hours. Refer to status code #33.
14 IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to status code #34.
15 BL OWER MOTOR LOCKOUT - Indicates the blower failed to reach 250 RPM or the blower failed to communicate within 30 seconds after being turned ON in two successive heating cycles. Control will auto reset after 3 hours.
Refer to status code #41.
21 GAS HEATING LOCKOUT - Control will NOT auto reset. Check for:
- Mis-wired gas valve -Defective control (valve relay)
22 ABNO RMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is de-energized. Inducer will run until fault is cleared. Check for:
- Leaky gas valve - Stuck-open gas valve
23 PRESSURE SWITCH DID NOT OPEN Check for:
- Obstructed pressure tubing - Pressure switch stuck closed
24 SECONDARY VOLTAGE FUSE IS OPEN Check for: - Short circuit in secondary voltage (24VAC) wiring.
25 INVAL ID MODEL SELECTION OR SETUP ERROR - Indicates either the model plug is missing or incorrect or, setup switch "SW1-1" or "SW1-6" is positioned improperly. If code flashes 4 times on power-up control is defaulting to model selection stored in memory.Check for: -Thermostat call with SW1-1, SW1-6 or
32 Cont in ued: Check for:
33
- Defective inducer motor
- Defective pressure switch
- Low inducer voltage (115 VAC)
- Low inducer voltage (115 VAC)
- Disconnected or obstructed pressure tubing
LIMIT CIRCUIT FAULT - Indicates a limit, draft safeguard, flame rollout, or blocked vent switch (if used) is open or the furnace is operating in high-heat only mode due to 2 successive low heat limit trips. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts off. Flame rollout switch and BVSS require manual reset. Check for: - Loose blower wheel
- Restricted vent - Proper vent sizing - Excessive wind
- Dirty filter or restricted duct system - Defective switch or connections
- Inadequate combustion air supply (Flame Roll-out Switch open)
34 IGNITION PROVING FAILURE - Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for:
- Oxide buildup on flame sensor (clean with fine steel wool)
- Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal)
- Manual valve shut-off - Low inlet gas pressure - Control ground continuity
- Gas valve defective or turned off
- Inadequate combustion air supply
- Low inlet gas pressure (if LGPS used)
- Inadequate flame carryover or rough ignition
- Green/Yellow wire MUST be connected to furnace sheet metal
41 BL OWER MOTOR FAUL T - Indicates the blower failed to reach 250 RPM or the blower failed to communicate within the prescribed times limits. Thirty both SW1-1 & SW1-6 ON. - Board date code 2103 or later required to recognize model seconds after being turned ON or ten seconds during steady-state operation.
43 LOW-HEAT PRESSURE SWITCH OPEN WHILE HIGH-HEAT PRESSURE
SWITCH IS CLOSED - Check for: - Mis-wired pressure switches
31 HIGH-HEAT PRESSURE SWITCH OR RELAY DID NOT CLOSE OR
REOPENED - Control relay may be defective. Refer to status code #32.
32 LOW-HEAT PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than five minutes, inducer shuts off for 15 minutes before retry. If opens during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Excessive wind - Restricted vent - Proper vent sizing
- Low-heat pressure switch stuck open - Low inlet gas pressure (if LGPS used)
- Disconnected or obstructed pressure tubing
45 CONTROL CIRCUITRY LOCKOUT Auto-reset after one hour lockout due to;
- Gas valve relay stuck open - Flame sense circuit failure - Software check error
Reset power to clear lockout. Replace control if status code repeats.
COMPONENT TEST
To initiate the component test sequence, shut
OFF the room thermostat or disconnect the "R" thermostat lead. Reset power and then put setup switch "SW1-6" in the ON position to start the component test sequence. Once initiated the furnace control will turn the inducer ON at highheat speed. The inducer motor will run for the entire test. The hot surface igniter and blower motor will be turned ON for 15 seconds each.
When the blower is turned OFF the inducer will be switched to low-speed for 10 seconds. When the component test is completed one or more of the following codes will flash.
CODE
- Flame sensor must not be grounded
DESCRIPTION
11 Indicates the blower motor tested
OK. Visual check of inducer motor
and hot surface igniter required.
25 SETUP ERROR - Same as code 25 above.
41 BL OWER MOTOR FAUL T - Indicates
To repeat component test turn setup switch
"SW1-6" OFF and then back ON. After component test is completed put setup switch "SW1-6" in the lead.
blower motor failed test. Check
blower, wiring, and furnace control.
OFF position and reconnect the "R" thermostat
328787-101 REV. A
A04015
Fig. 56—Service Label
Step 3—Adjustments
FIRE HAZARD
Failure to follow this warning could result in injury, death and/or property damage.
DO NOT bottom out gas valve regulator adjusting screw.
This can result in unregulated manifold pressure and result in excess overfire and heat exchanger failures.
36
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace life.
DO NOT redrill orifices. Improper drilling (burrs, out-ofround holes, etc.) can cause excessive burner noise and misdirection of burner flames. This can result in flame impingement of heat exchangers, causing failures. (See Fig.
54.)
Furnace gas input rate on rating plate is for installations at altitudes up to 2000 ft. Furnace input rate must be within ±2 percent of furnace rating plate input. For altitudes above 5500 ft., a fieldsupplied high altitude pressure switch is required.
1. Determine the correct gas input rate.
In the U.S.A.:
The input rating for altitudes above 2,000 ft. must be reduced by 4 percent for each 1,000 ft. above sea level.
For installations below 2000 ft., refer to the unit rating plate.
For installations above 2000 ft., multiply the input on the rating plate by the de-rate multiplier in Table 9 for the correct
10 16
1 7
ACRDJ
7 8 7 8 7 8 7 8
OFF OFF OFF OFF
PRINTED CIRCIUT BOARD
YEL
RED
GRN
YEL
BLU
TRAN
LO HI HSI VS
RED
GRN
YEL
BLU
PL12
OFF
1 2 3
OFF
1 2 3
OFF
1 2 3
OFF
1 2 3
OFF
1 2 3
OFF
1 2 3
OFF
1 2 3
OFF
1 2 3
-1 EAC
SW4
OAT
PRINTED CIRCIUT BOARD
J ACRD
HUM
-1 SEC
-2 EAC
-AMP
-2 SEC
SE 3 FU
SW1
PL4
37
. A R EV 1 -10 328782
Table 9–Altitude Derate Multiplier for U.S.A.
ALTITUDE
(FT)
0–2000
2001–3000
3001–4000
4001–5000
5001–6000
6001–7000
7001–8000
8001–9000
9001–10,000
PERCENT
OF DERATE
0
8–12
12–16
16–20
20–24
24–28
28–32
32–36
36–40
DERATE MULTIPLIER
FACTOR*
1.00
0.90
0.86
0.82
0.78
0.74
0.70
0.66
0.62
* Derate multiplier factors are based on midpoint altitude for altitude range.
input rate.
In Canada:
The input rating for altitudes from 2,000 to 4,500 ft above sea level must be derated 10 percent by an authorized Gas
Conversion Station or Dealer.
To determine correct input rate for altitude, see example and use 0.90 as derate multiplier factor.
EXAMPLE:
88,000 BTUH INPUT FURNACE INSTALLED AT 4300 FT.
Derate
Furnace Input Rate
X Multiplier =
at Sea Level
88,000
X
Factor
0.90
=
Furnace Input Rate at Installation
Altitude
79,200
2. Determine the correct orifice and manifold pressure adjustment. All models in all positions except Low NOx models in downflow and horizontal positions use Table 12 (22,000 Btuh per burner.) Low NOx models in downflow or horizontal positions must use Table 13 (21,000 Btuh per burner.)
See input listed on rating plate.
a. Obtain average yearly gas heat value (at installed altitude) from local gas supplier.
b. Obtain average yearly gas specific gravity from local gas supplier.
c. Find installation altitude in Table 12 or 13.
d. Find closest natural gas heat value and specific gravity in
Table 12 or 13.
e. Follow heat value and specific gravity lines to point of intersection to find orifice size and low-and high-heat manifold pressure settings for proper operation.
f. Check and verify burner orifice size in furnace. NEVER
ASSUME ORIFICE SIZE. ALWAYS CHECK AND
VERIFY.
g. Replace orifice with correct size, if required by Table 12 or
13. Use only factory-supplied orifices. See EXAMPLE 2.
Table 10—Blower Off Delay Setup Switch
DESIRED HEATING MODE
BLOWER OFF DELAY (SEC.)
SETUP SWITCH (SW-7 AND -8) POSITION
90
120
150
180
SW1-7
OFF
ON
OFF
ON
SW1-8
OFF
OFF
ON
ON
38
EXAMPLE 2: (0–2000 ft altitude)
For 22,000 Btuh per burner application use Table 12.
Heating value = 1000 Btu/cu ft
Specific gravity = 0.62
Therefore: Orifice No. 43*
Manifold pressure: 3.7-in. wc for high-heat
1.6-in. wc for low-heat
* Furnace is shipped with No. 43 orifices. In this example all main burner orifices are the correct size and do not need to be changed to obtain proper input rate.
3. Adjust manifold pressure to obtain low fire input rate. (See
Fig. 53.) a. Turn gas valve ON/OFF switch to OFF.
b. Remove manifold pressure tap plug from gas valve.
c. Connect a water column manometer or similar device to manifold pressure tap.
d. Turn gas valve ON/OFF switch to ON.
e. Move setup SW1–2 on furnace control to ON position to lock furnace in low-heat operation. (See Table 8 and Fig.
25.) f. Manually close blower door switch.
g. Jumper R and W/W1 thermostat connections on control to start furnace. (See Fig. 25.) h. Remove regulator adjustment cap from low heat gas valve pressure regulator (See Fig. 53.) and turn low-heat adjusting screw (3/16 or smaller flat-tipped screwdriver) counterclockwise (out) to decrease input rate or clockwise (in) to increase input rate.
NOTE: DO NOT set low-heat manifold pressure less than 1.4-in
wc or more than 1.7-in. wc for natural gas. If manifold pressure is outside this range, change main burner orifices.
i. Install low-heat regulator adjustment cap.
j. Leave manometer or similar device connected and proceed to Step 4.
NOTE: If orifice hole appears damaged or it is suspected to have
been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr-free and squarely aligned orifice hole is essential for proper flame characteristics.
4. Verify natural gas low-heat input rate by clocking meter.
NOTE: Gas valve regulator adjustment caps must be in place for
proper input to be clocked.
a. Turn off all other gas appliances and pilots served by the meter.
b. Run furnace for 3 minutes in low-heat operation.
c. Measure time (in sec) for gas meter to complete 1 revolution and note reading. The 2 or 5 cubic feet dial provides a more accurate measurement of gas flow.
d. Refer to Table 11 for cubic ft of gas per hr.
e. Multiply gas rate cu ft/hr by heating value (Btu/cu ft) to obtain input.
If clocked rate does not match required input from Step 1, increase manifold pressure to increase input or decrease manifold pressure to decrease input. Repeat steps b through e until correct low-heat input is achieved. Re-install lowheat regulator seal cap on gas valve.
5. Set low heat temperature rise.
The furnace must operate within the temperature rise ranges
specified on the furnace rating plate. Do not exceed temperature rise ranges specified on furnace rating plate for high-and low-fire. Determine the temperature rise as follows:
NOTE: Blower access door must be installed when taking tem-
perature rise reading. Leaving blower access door off will result in incorrect temperature measurements.
a. Verify unit is running in low-heat per Step 4. Place thermometers in return and supply ducts as close to furnace as possible. Be sure thermometers do not see radiant heat from heat exchangers. Radiant heat affects temperature rise readings. This practice is particularly important with straight-run ducts.
b. When thermometer readings stabilize, subtract return-air temperature from supply-air temperature to determine air temperature rise.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect 115-v electrical power before changing speed tap.
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in shorten furnace life. Set air temperature rise within limits specified on the rating plate to prevent reduced life of furnace components.
Operation is within a few degrees of the mid-point of rise range when setup switch SW1-4 is OFF.
When setup switch SW1-4 is ON, operation will be near the high end of the rise range for improved comfort.
This furnace is capable of automatically providing proper airflow to maintain the temperature rise within the range specified on unit rating plate.
NOTE: If the temperature rise is outside this range, first check:
1.) Gas input for low heat operation.
2.) Derate for altitude if applicable.
3.) Return and supply ducts for excessive restrictions causing static pressures greater than 0.50-in. wc.
4.) Ensure low-heat rise adjust switch SW1-3 is in ON position when bypass humidifier is used. Refer to Table
8 and Fig. 25 and 57.
5.) Make sure proper model plug is installed.
6. Adjust Manifold Pressure to Obtain High Heat Rate a. Remove high heat regulator adjustment cap from gas valve pressure regulator.
b. Jumper R, W/W1 and W2 thermostat connections on control to run furnace in high heat. (See Fig. 25 and 57.) c. Turn high-heat adjusting screw (3/16 or smaller flat-tipped screwdriver)) counterclockwise (out) to decrease input rate or clockwise (in) to increase rate.
d. Re-install high-heat adjustment caps.
NOTE: DO NOT set high-heat manifold pressure less than 3.2-in.
wc or more than 3.8-in. wc for natural gas. If manifold pressure is outside this range, change main burner orifices.
7. Verify natural gas high heat input rate by clocking meter.
NOTE: Gas valve regulator adjustment caps must be in place for
proper input to be clocked.
a. Turn off all other gas appliances and pilots served by the meter.
39
Table 11—GAS RATE (CU FT/HR)
SECONDS
FOR 1
REVOLUTION
36
37
38
39
32
33
34
35
40
41
42
43
44
45
46
47
48
49
25
26
27
28
21
22
23
24
29
30
31
14
15
16
17
10
11
12
13
18
19
20
100
97
95
92
113
109
106
103
90
88
86
84
82
80
78
76
75
73
144
138
133
129
171
164
157
150
124
120
116
SIZE OF TEST DIAL
1
Cu Ft
2
Cu Ft
5
Cu Ft
257
240
225
212
360
327
300
277
200
189
180
720 1800
655 1636
600 1500
555 1385
514 1286
480 1200
450 1125
424 1059
400
379
360
1000
947
900
200
195
189
185
225
218
212
206
180
176
172
167
164
160
157
153
150
147
288
277
267
257
343
327
313
300
248
240
232
500
486
474
462
563
545
529
514
450
439
429
419
409
400
391
383
375
367
720
692
667
643
857
818
783
750
621
600
581
SECONDS
FOR 1
REVOLUTION
39
38
38
37
43
42
41
40
36
35
35
34
33
33
32
31
30
51
50
48
47
58
56
54
53
46
45
44
SIZE OF TEST DIAL
1
Cu Ft
2
Cu Ft
5
Cu Ft
67
65
64
63
72
71
69
68
62
61
60
144
141
138
136
133
131
129
126
124
122
120
333
327
321
316
360
355
346
340
310
305
300
78
76
75
74
86
84
82
80
72
71
69
68
67
65
64
62
60
103
100
97
95
116
112
109
106
92
90
88
196
192
188
184
214
209
205
200
180
178
173
170
167
164
161
155
150
257
250
243
237
290
281
273
265
231
225
220
92
94
96
98
84
86
88
90
100
102
104
106
108
110
112
116
120
70
72
74
76
62
64
66
68
78
80
82
54
55
56
57
50
51
52
53
58
59
60 b. Run for 3 minutes in high-heat operation.
c. Measure time (in sec) for gas meter to complete 1 revolution and note reading.
d. Refer to Table 11 for cubic ft of gas per hr.
e. Multiply gas rate cu ft/hr by heating value (Btu/cu ft) to obtain input.
NOTE: Using the 2 cu. ft. or 5 cu. ft. gas meter dial provides
greater accuracy in verifying gas input rate.
If clocked rate does not match required input from Step 1, increase manifold pressure to increase input or decrease manifold pressure to decrease input. Repeat steps b through e until correct high heat input is achieved. Re-install high-heat regulator seal cap on gas valve.
8. Set high heat temperature rise.
Jumper R to W/W1 and W2 to check high-gas-heat temperature rise. Do not exceed temperature rise ranges specified on furnace rating plate for high heat. The furnace must operate within the temperature rise ranges specified on the furnace rating plate.
Determine the air temperature rise as follows:
NOTE: Blower access door must be installed when taking tem-
perature rise reading. Leaving blower access door off will result in incorrect temperature measurements.
a. Verify the unit is operating in high heat per Step 6. Place thermometers in return and supply ducts as close to furnace as possible. Be sure thermometers do not see radiant heat from heat exchangers. Radiant heat affects temperature rise readings. This practice is particularly important with straight-run ducts.
b. When thermometer readings stabilize, subtract return-air temperature from supply-air temperature to determine air temperature rise.
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in shorten furnace life. Set air temperature rise within limits specified on the rating plate to prevent reduced life of furnace components.
Operation is within a few degrees of the mid-point of rise range when setup switch SW1-4 is OFF.
When setup switch SW1-4 is ON, operation will be near the high end of the rise range for improved comfort.
This furnace is capable of automatically providing proper airflow to maintain the temperature rise within the range specified on unit rating plate.
NOTE: If the temperature rise is outside this range, first check:
1.) Gas input for low-and high-heat operation.
2.) Derate for altitude if applicable.
3.) Return and supply ducts for excessive restrictions causing static pressures greater than 0.50-in. wc.
4.) Make sure proper model plug is installed.
c. Remove thermostat jumpers and release blower access door switch.
d. Repeat Steps a through c as required to adjust for proper rise.
e. When correct high heat input rate and temperature rise is achieved, turn gas valve ON/OFF switch to OFF.
f. Release blower access door switch.
g. Remove manometer or similar device from gas valve.
h. Re-install manifold pressure tap plug in gas valve. (See
Fig. 53.)
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage. Reinstall manifold pressure tap plug in gas valve to prevent gas leak.
i. Remove thermostat jumper wire from furnace control board.
j. Turn gas valve ON/OFF switch to ON.
k. Proceed to Step 9,
″Set Blower Off Delay″ before installing blower access door.
40
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace life. Recheck temperature rise.It must be within limits specified on the rating plate. Recommended operation is at the mid-point of rise range or slightly above.
9. Set Blower Off Delay a. Remove blower access door if installed.
b. Turn Dip switch SW-7 or SW-8 ON or OFF for desired blower off delay. (See Table 10 and Fig. 25 and 57.)
10. Set thermostat heat anticipator.
a. Mechanical thermostat—Set thermostat heat anticipator to match the amp draw of the electrical components in the
R-W/W1 circuit. Accurate amp draw readings can be obtained at the wires normally connected to thermostat subbase terminals, R and W. The thermostat anticipator should NOT be in the circuit while measuring current.
(1.) Set SW1-2 switch on furnace control board to ON.
(2.) Remove thermostat from subbase or from wall.
(3.) Connect an amp meter as shown in Fig. 55 across the
R and W subbase terminals or R and W wires at wall.
(4.) Record amp draw across terminals when furnace is in low heat and after blower starts.
(5.) Set heat anticipator on thermostat per thermostat instructions and install on subbase or wall.
(6.) Turn SW1-2 switch OFF.
(7.) Install blower access door.
b. Electronic thermostat: Set cycle rate for 3 cycles per hr.
11. Set Airflow for Air Conditioning -Single Stage and High
Stage Cooling
The ECM blower can be adjusted for a range of airflows for
Low Speed or High Speed cooling. See Table 5-Air Delivery
- CFM (With Filter ). Depending on the model size, the cooling airflow can be adjusted from 1½ tons nominal cooling to 3 ½, to 4 or to 6 tons of nominal cooling based on 350 cfm ton.
The cooling airflow is adjusted by turning Setup switches
SW2-1, SW2-2 and SW2-3 either ON or OFF. Select the required airflow from Fig. 61. Fig. 61 is based on 350 CFM per ton. For airflow at 400 CFM per ton, turn Setup SW1-5
ON (See Table 8 and Fig. 25 and 57.)
NOTE: 6 ton airflow will truncate at 2200 cfm on applicable
models. For a complete explanation of cooling airflow, refer to the section titled
″Sequence of Operation.″
12. Set Airflow For Continuous Fan/Low Speed Cooling Airflow
The ECM blower motor can be adjusted for continuous fan speeds different than heating or cooling fan speed. See Table
5 - Air Delivery - CFM (With Filter). Select the required continuous fan airflow from Fig. 61.
The continuous fan speed is also the fan speed for low speed cooling when furnace is used with a 2-speed cooling unit.
Adjust the Continuous Fan CFM to match the airflow required for low speed cooling. Select the required airflow from Fig.
61. For airflow at 400 CFM per ton, turn Setup SW1-5 ON
(See Fig. 61.) The airflow selected for low speed cooling will also be the airflow used for continuous fan.
The continuous fan speed can be further adjusted at the thermostat using the
″Comfort Fan″ select function. Changing the continuous fan speed at the thermostat DOES NOT change the low speed cooling airflow selected at the control board.
TABLE 12—Orifice Size and Manifold Pressure for Gas Input Rate
(Tabulated Data Based On 22,000 Btuh High-Heat/14,500 Btuh for Low-Heat Per Burner,
Derated 4 Percent For Each 1000 Ft Above Sea Level)
ALTITUDE
RANGE
(FT)
0 to
2000
ALTITUDE
RANGE
(FT)
U.S.A.
Altitudes
2001 to
3000 or
Canada
Altitudes
2001 to
4500
ALTITUDE
RANGE
(FT)
3001 to
4000
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
775
800
825
850
875
900
925
950
AVG GAS
HEAT VALUE
(BTU/CU FT)
4001 to
5000
750
775
800
825
850
875
900
925
* Orifice numbers 43 are factory installed
900
925
950
975
1000
1025
1050
1075
1100
800
825
850
875
900
925
950
975
1000
43
43
44
44
44
Orifice no.
42
42
43
43
0.58
Manifold
Pressure
3.5/1.5
3.3/1.4
3.8/1.7
3.6/1.6
3.5/1.5
3.3/1.4
3.6/1.6
3.4/1.5
3.3/1.4
Orifice no.
42
42
43
43
43
44
44
44
45
0.58
Manifold
Pressure
3.4/1.5
3.2/1.4
3.7/1.6
3.5/1.5
3.3/1.4
3.5/1.5
3.4/1.5
3.2/1.4
3.7/1.6
Orifice no.
42
43
43
43
44
44
45
46
0.58
Manifold
Pressure
3.2/1.4
3.6/1.6
3.4/1.5
3.2/1.4
3.5/1.5
3.3/1.4
3.8/1.6
3.8/1.6
Orifice no.
43
43
43
44
44
45
46
46
0.58
Manifold
Pressure
3.6/1.6
3.4/1.5
3.2/1.4
3.4/1.5
3.2/1.4
3.7/1.6
3.7/1.6
3.5/1.5
SPECIFIC GRAVITY OF NATURAL GAS
0.60
0.62
Orifice no.
Manifold
Pressure
Orifice no.
Manifold
Pressure
42
42
42
43
3.6/1.6
3.4/1.5
3.3/1.4
3.8/1.6
42
42
42
42
3.7/1.6
3.5/1.5
3.4/1.5
3.2/1.4
43
43
43
44
3.6/1.6
3.4/1.5
3.2/1.4
3.5/1.5
43
43
43
43
3.7/1.6
3.5/1.5
3.4/1.5
3.2/1.4
44 3.4/1.5
44 3.5/1.5
SPECIFIC GRAVITY OF NATURAL GAS
0.60
0.62
Orifice no.
42
42
43
43
43
43
44
44
Manifold
Pressure
3.5/1.5
3.3/1.4
3.8/1.6
3.6/1.6
3.4/1.5
3.2/1.4
3.5/1.5
3.3/1.4
Orifice no.
42
42
42
43
43
43
44
44
Manifold
Pressure
3.6/1.6
3.4/1.5
3.2/1.4
3.7/1.6
3.5/1.5
3.3/1.4
3.6/1.6
3.4/1.5
45 3.8/1.7
44 3.2/1.4
SPECIFIC GRAVITY OF NATURAL GAS
Orifice no.
42
43
0.60
Manifold
Pressure
3.3/1.4
3.8/1.6
Orifice no.
42
42
0.62
Manifold
Pressure
3.4/1.5
3.2/1.4
43
43
44
3.5/1.5
3.3/1.4
3.6/1.6
43
43
43
3.7/1.6
3.4/1.5
3.3/1.4
44
44
Orifice no.
43
3.4/1.5
3.2/1.4
44
44
Orifice no.
42
3.5/1.5
3.3/1.5
45 3.7/1.6
45 3.8/1.7
SPECIFIC GRAVITY OF NATURAL GAS
0.60
Manifold
Pressure
0.62
Manifold
Pressure
43
43
3.8/1.6
3.5/1.5
3.3/1.4
43
43
3.2/1.4
3.6/1.6
3.4/1.5
44
44
45
46
46
3.6/1.5
3.4/1.5
3.8/1.7
3.8/1.7
3.6/1.6
43
44
44
45
46
3.2/1.4
3.5/1.5
3.3/1.4
3.7/1.6
3.7/1.6
Orifice no.
41
42
42
42
43
43
43
43
43
0.64
Manifold
Pressure
3.5/1.5
3.7/1.6
3.5/1.5
3.3/1.4
3.8/1.7
3.6/1.6
3.5/1.5
3.3/1.4
3.2/1.4
Orifice no.
42
42
42
43
43
43
43
44
44
0.64
Manifold
Pressure
3.7/1.6
3.5/1.5
3.3/1.4
3.8/1.7
3.6/1.6
3.4/1.5
3.2/1.4
3.5/1.5
3.4/1.5
Orifice no.
42
42
43
43
43
43
44
44
0.64
Manifold
Pressure
3.5/1.5
3.3/1.4
3.8/1.6
3.6/1.5
3.4/1.5
3.2/1.4
3.4/1.5
3.3/1.4
Orifice no.
42
43
43
43
44
44
44
46
0.64
Manifold
Pressure
3.3/1.4
3.8/1.6
3.5/1.5
3.3/1.4
3.6/1.6
3.4/1.5
3.2/1.4
3.8/1.7
41
ALTITUDE
RANGE
(FT)
ALTITUDE
RANGE
(FT)
5001 to
6000
ALTITUDE
RANGE
(FT)
6001 to
7000
7001 to
8000
650
675
700
725
750
775
800
825
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
8001 to
9000
625
650
675
700
725
750
775
* Orifice numbers 43 are factory installed
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
725
750
775
800
825
850
875
900
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
675
700
725
750
775
800
825
850
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
TABLE 12—Orifice Size and Manifold Pressure for Gas Input Rate
(Tabulated Data Based On 22,000 Btuh High-Heat/14,500 Btuh for Low-Heat Per Burner,
Derated 4 Percent For Each 1000 Ft Above Sea Level)(Continued)
Orifice
No.
43
43
44
44
46
46
47
47
0.58
Manifold
Pressure
3.4/1.5
3.2/1.4
3.4/1.5
3.2/1.4
3.8/1.7
3.6/1.6
3.8/1.7
3.6/1.6
Orifice
No.
43
44
44
45
46
46
47
47
0.58
Manifold
Pressure
3.4/1.5
3.6/1.6
3.4/1.5
3.8/1.7
3.7/1.6
3.5/1.5
3.7/1.6
3.5/1.5
Orifice
No.
44
44
45
46
46
47
47
48
0.58
Mainifold
Pressure
3.6/1.6
3.3/1.5
3.8/1.6
3.7/1.6
3.4/1.5
3.6/1.6
3.4/1.5
3.7/1.6
Orifice
No.
44
45
46
47
47
48
48
0.58
Manifold
Pressure
3.3/1.5
3.7/1.6
3.6/1.6
3.8/1.7
3.6/1.6
3.8/1.7
3.6/1.5
SPECIFIC GRAVITY OF NATURAL GAS
0.60
0.62
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
43
43
44
44
45
46
3.5/1.5
3.3/1.4
3.5/1.5
3.3/1.4
3.8/1.6
3.7/1.6
43
43
43
44
44
46
3.6/1.6
3.4/1.5
3.2/1.4
3.4/1.5
3.2/1.4
3.8/1.7
46
47
3.5/1.5
3.8/1.6
46
46
3.6/1.6
3.4/1.5
SPECIFIC GRAVITY OF NATURAL GAS
0.60
0.62
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
43
43
44
44
3.5/1.5
3.3/1.4
3.5/1.5
3.3/1.4
43
43
44
44
3.6/1.6
3.4/1.5
3.6/1.6
3.4/1.5
46
47
47
48
43
44
44
46
45
46
46
47
3.7/1.6
3.6/1.6
3.4/1.5
3.6/1.6
45
46
46
47
3.8/1.7
3.8/1.6
3.5/1.5
3.8/1.6
SPECIFIC GRAVITY OF NATURAL GAS
0.60
0.62
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
3.2/1.4
3.5/1.5
3.2/1.4
3.8/1.7
3.6/1.5
3.8/1.6
3.5/1.5
3.8/1.6
43
44
44
45
46
46
47
47
3.4/1.5
3.6/1.6
3.3/1.4
3.7/1.6
3.7/1.6
3.4/1.5
3.7/1.6
3.4/1.5
SPECIFIC GRAVITY OF NATURAL GAS
0.60
0.62
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
44
44
46
46
47
47
48
3.5/1.5
3.2/1.4
3.8/1.6
3.5/1.5
3.7/1.6
3.5/1.5
3.7/1.6
44
44
45
46
47
47
48
3.6/1.6
3.3/1.4
3.7/1.6
3.6/1.6
3.8/1.7
3.6/1.6
3.8/1.7
Orifice
No.
43
43
43
44
44
45
46
46
0.64
Manifold
Pressure
3.7/1.6
3.5/1.5
3.3/1.4
3.5/1.5
3.3/1.4
3.8/1.6
3.7/1.6
3.5/1.5
Orifice
No.
43
43
43
44
44
45
46
46
0.64
Manifold
Pressure
3.7/1.6
3.5/1.5
3.2/1.4
3.5/1.5
3.2/1.4
3.7/1.6
3.6/1.6
3.4/1.5
Orifice
No.
43
43
44
44
46
46
47
47
0.64
Manifold
Pressure
3.5/1.5
3.2/1.4
3.4/1.5
3.2/1.4
3.8/1.6
3.6/1.5
3.8/1.6
3.6/1.5
Orifice
No.
43
44
45
46
46
47
47
0.64
Manifold
Pressure
3.2/1.4
3.4/1.5
3.8/1.7
3.7/1.6
3.5/1.5
3.7/1.6
3.5/1.5
42
TABLE 12—Orifice Size and Manifold Pressure for Gas Input Rate
(Tabulated Data Based On 22,000 Btuh High-Heat/14,500 Btuh for Low-Heat Per Burner,
Derated 4 Percent For Each 1000 Ft Above Sea Level)(Continued)
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
9001 to
10,000
600
625
650
675
700
725
* Orifice numbers 43 are factory installed
Orifice
No.
45
46
47
47
48
48
0.58
Manifold
Pressure
3.7/1.6
3.6/1.6
3.8/1.6
3.5/1.5
3.7/1.6
3.5/1.5
SPECIFIC GRAVITY OF NATURAL GAS
0.60
0.62
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
45
46
46
47
48
48
3.8/1.7
3.7/1.6
3.4/1.5
3.6/1.6
3.8/1.7
3.6/1.6
44
46
46
47
47
48
3.3/1.4
3.8/1.7
3.6/1.5
3.7/1.6
3.5/1.5
3.7/1.6
Orifice
No.
44
45
46
46
47
48
0.64
Manifold
Pressure
3.4/1.5
3.8/1.6
3.7/1.6
3.4/1.5
3.6/1.6
3.8/1.7
Step 4—Check Safety Controls
The flame sensor, gas valve, and pressure switch were all checked in the Start-up procedure section as part of normal operation.
1. Check Main Limit Switch
This control shuts off combustion system and energizes air-circulating blower motor, if furnace overheats. By using this method to check limit control, it can be established that limit is functioning properly and will operate if there is a restricted return-air supply or motor failure. If limit control does not function during this test, cause must be determined and corrected.
a. Run furnace for at least 5 minutes.
b. Gradually block off return air with a piece of cardboard or sheet metal until the limit trips.
c. Unblock return air to permit normal circulation.
d. Burners will re-light when furnace cools down.
2. Check draft safeguard switch.
The purpose of this control is to cause the safe shutdown of the furnace during certain blocked vent conditions.
a. Verify vent pipe is cool to the touch.
b. Disconnect power to furnace and remove vent connector from furnace vent elbow.
c. Restore power to furnace and set room thermostat above room temperature.
d. After normal start-up, allow furnace to operate for 2 minutes, then block vent elbow in furnace 80 percent of vent area with a piece of flat sheet metal.
e. Furnace should cycle off within 2 minutes. If gas does not shut off within 2 minutes, determine reason draft safeguard switch did not function properly and correct condition.
f. Remove blockage from furnace vent elbow.
g. Switch will auto-reset when it cools.
h. Re-install vent connector.
NOTE: Should switch remain open longer than 3 minutes,
furnace control board will lockout the furnace for 3 hours. To reset furnace control board, turn thermostat below room temperature or from HEAT to OFF and turn 115-v power OFF, then back ON.
3. Check Pressure Switch(es)
This control proves operation of the draft inducer blower.
a. Turn off 115-v power to furnace.
b. Disconnect inducer motor lead wires from wire harness.
c. Turn on 115-v power to furnace.
43 d. Set thermostat to
″call for heat″ and wait 1 minute. When pressure switch is functioning properly, hot surface igniter should NOT glow and control diagnostic light flashes a status code 32. If hot surface igniter glows when inducer motor is disconnected, shut down furnace immediately.
e. Determine reason pressure switch did not function properly and correct condition.
f. Turn off 115-v power to furnace.
g. Reconnect inducer motor wires, replace outer door, and turn on 115-v power.
h. Blower will run for 90 seconds before beginning the call for heat again.
i. Furnace should ignite normally.
Step 5—Checklist
1. Put away tools and instruments. Clean up debris.
2. Verify that switches SW1-1 and SW1-6 are OFF and other setup switches are set as desired. Verify that switches SW1-7 and SW1-8 for the blower OFF DELAY are set as desired per
Table 10.
3. Verify that blower and burner access doors are properly installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer’s instructions.
6. Review User’s Guide with owner.
7. Attach literature packet to furnace.
SERVICE AND MAINTENANCE PROCEDURES
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
The ability to properly perform maintenance on this equipment requires certain knowledge, mechanical skills, tools, and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment other than those procedures recommended in the User’s Manual.
TABLE 13–Orifice Size and Manifold Pressure for Gas Input Rate (Tabulated Data Based On 21,000 Btuh
High-Heat/14,500 Btuh for Low-Heat Per Burner,
Derated 4 Percent For Each 1000 Ft Above Sea Level)
ALTITUDE
RANGE
(FT)
0 to
2000
ALTITUDE
RANGE
(FT)
U.S.A.
Altitudes
2001 to
3000 or
Canada
Altitudes
2001 to
4500
ALTITUDE
RANGE
(FT)
3001 to
4000
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
900
925
950
975
1000
1025
1050
1075
1100
AVG GAS
HEAT VALUE
(BTU/CU FT)
800
825
850
875
900
925
950
975
1000
AVG GAS
HEAT VALUE
(BTU/CU FT)
775
800
825
850
875
900
925
950
AVG GAS
HEAT VALUE
(BTU/CU FT)
4001 to
5000
750
775
800
825
850
875
900
925
* Orifice numbers 43 are factory installed
44
44
44
45
46
Orifice no.
42
43
43
43
0.58
Manifold
Pressure
3.2/1.5
3.7/1.8
3.5/1.7
3.3/1.6
3.6/1.7
3.4/1.6
3.3/1.6
3.8/1.8
3.8/1.8
Orifice no.
43
43
43
43
44
44
45
46
46
0.58
Manifold
Pressure
3.8/1.8
3.5/1.7
3.3/1.6
3.2/1.5
3.4/1.6
3.2/1.5
3.7/1.8
3.7/1.8
3.5/1.7
Orifice no.
43
43
44
44
45
46
46
46
0.58
Manifold
Pressure
3.5/1.7
3.3/1.6
3.6/1.7
3.4/1.6
3.8/1.8
3.8/1.8
3.6/1.7
3.4/1.6
Orifice no.
43
44
44
45
46
46
47
47
0.58
Manifold
Pressure
3.3/1.6
3.6/1.7
3.3/1.6
3.8/1.8
3.8/1.8
3.5/1.7
3.8/1.8
3.6/1.7
SPECIFIC GRAVITY OF NATURAL GAS
0.60
0.62
Orifice no.
Manifold
Pressure
Orifice no.
Manifold
Pressure
42
43
43
43
3.3/1.6
3.8/1.8
3.6/1.7
3.4/1.6
42
42
43
43
3.4/1.6
3.2/1.5
3.7/1.8
3.5/1.7
43
44
44
44
3.3/1.6
3.6/1.7
3.4/1.6
3.2/1.5
43
43
44
44
3.4/1.6
3.2/1.5
3.5/1.7
3.3/1.6
45 3.7/1.8
44 3.2/1.5
SPECIFIC GRAVITY OF NATURAL GAS
0.60
0.62
Orifice no.
42
43
43
43
44
44
45
Manifold
Pressure
3.2/1.5
3.7/1.7
3.5/1.6
3.3/1.6
3.5/1.7
3.3/1.6
3.8/1.8
Orifice no.
42
43
43
43
43
44
44
Manifold
Pressure
3.3/1.6
3.8/1.8
3.6/1.7
3.4/1.6
3.2/1.5
3.5/1.6
3.3/1.6
46
46
3.8/1.8
3.6/1.7
45
46
3.8/1.8
3.8/1.8
SPECIFIC GRAVITY OF NATURAL GAS
0.60
0.62
Orifice no.
Manifold
Pressure
Orifice no.
Manifold
Pressure
43
43
43
44
3.7/1.7
3.4/1.6
3.2/1.5
3.5/1.7
43
43
43
44
3.8/1.8
3.5/1.7
3.3/1.6
3.6/1.7
44
44
45
46
46
47
44
45
46
46
3.3/1.6
3.8/1.8
3.7/1.8
3.5/1.7
44
44
45
46
3.4/1.6
3.2/1.5
3.7/1.8
3.7/1.7
SPECIFIC GRAVITY OF NATURAL GAS
Orifice no.
43
43
0.60
Manifold
Pressure
3.4/1.6
3.2/1.5
Orifice no.
43
43
0.62
Manifold
Pressure
3.5/1.7
3.3/1.6
3.4/1.6
3.2/1.5
3.7/1.8
3.7/1.7
3.5/1.7
3.7/1.8
44
44
45
46
46
47
3.6/1.7
3.4/1.6
3.8/1.8
3.8/1.8
3.6/1.7
3.8/1.8
43
43
43
44
44
Orifice no.
42
42
43
43
0.64
Manifold
Pressure
3.5/1.7
3.3/1.6
3.8/1.8
3.7/1.7
3.5/1.7
3.3/1.6
3.2/1.5
3.4/1.6
3.3/1.6
Orifice no.
42
42
43
43
43
44
44
44
45
0.64
Manifold
Pressure
3.4/1.6
3.2/1.5
3.7/1.8
3.5/1.7
3.3/1.6
3.6/1.7
3.4/1.6
3.2/1.5
3.7/1.8
Orifice no.
42
43
43
43
44
44
45
46
0.64
Manifold
Pressure
3.2/1.5
3.7/1.7
3.4/1.6
3.2/1.5
3.5/1.7
3.3/1.6
3.8/1.8
3.8/1.8
Orifice no.
43
43
43
44
44
45
46
46
0.64
Manifold
Pressure
3.6/1.7
3.4/1.6
3.2/1.5
3.5/1.6
3.3/1.6
3.7/1.8
3.7/1.8
3.5/1.7
44
ALTITUDE
RANGE
(FT)
ALTITUDE
RANGE
(FT)
5001 to
6000
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
725
750
775
800
825
850
875
900
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
ALTITUDE
RANGE
(FT)
6001 to
7000
ALTITUDE
RANGE
(FT)
7001 to
8000
675
700
725
750
775
800
825
850
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
650
675
700
725
750
775
800
825
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
8001 to
9000
625
650
675
700
725
750
775
* Orifice numbers 43 are factory installed
TABLE 13–Orifice Size and Manifold Pressure for Gas Input Rate (Tabulated Data Based On 21,000 Btuh
High-Heat/14,500 Btuh for Low-Heat Per Burner,
Derated 4 Percent For Each 1000 Ft Above Sea Level)(Continued)
Orifice
No.
44
44
45
46
46
47
47
48
0.58
Manifold
Pressure
3.5/1.7
3.3/1.6
3.7/1.8
3.7/1.8
3.5/1.7
3.7/1.8
3.5/1.7
3.8/1.8
Orifice
No.
44
44
45
46
46
47
47
48
0.58
Manifold
Pressure
3.5/1.7
3.3/1.6
3.7/1.8
3.6/1.7
3.4/1.6
3.6/1.7
3.4/1.6
3.7/1.7
Orifice
No.
44
45
46
47
47
48
48
48
0.58
Manifold
Pressure
3.3/1.6
3.7/1.8
3.6/1.7
3.8/1.8
3.5/1.7
3.8/1.8
3.6/1.7
3.3/1.6
Orifice
No.
45
46
47
47
48
48
49
0.58
Manifold
Pressure
3.7/1.8
3.6/1.7
3.8/1.8
3.5/1.7
3.7/1.8
3.5/1.7
3.8/1.8
SPECIFIC GRAVITY OF NATURAL GAS
0.60
0.62
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
43
44
44
46
3.2/1.5
3.4/1.6
3.2/1.5
3.8/1.8
43
44
44
45
3.3/1.6
3.5/1.7
3.3/1.6
3.8/1.8
46
47
47
47
3.6/1.7
3.8/1.8
3.6/1.7
3.4/1.6
46
46
47
47
3.7/1.8
3.5/1.7
3.7/1.8
3.5/1.7
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
43
44
0.60
Manifold
Pressure
3.2/1.5
3.4/1.6
Orifice
No.
43
44
0.62
Manifold
Pressure
3.3/1.6
3.5/1.7
45
46
46
47
3.8/1.8
3.8/1.8
3.5/1.7
3.8/1.8
44
45
46
46
3.3/1.6
3.7/1.8
3.6/1.7
3.4/1.6
47 3.5/1.7
47 3.6/1.7
48 3.8/1.8
47 3.4/1.6
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
44
45
46
46
0.60
Manifold
Pressure
3.4/1.6
3.8/1.8
3.7/1.8
3.5/1.7
Orifice
No.
44
44
46
46
0.62
Manifold
Pressure
3.5/1.7
3.3/1.6
3.8/1.8
3.6/1.7
47
47
48
3.7/1.8
3.4/1.6
3.7/1.8
47
47
48
3.8/1.8
3.6/1.7
3.8/1.8
48 3.5/1.6
48 3.6/1.7
SPECIFIC GRAVITY OF NATURAL GAS
Orifice
No.
45
46
0.60
Manifold
Pressure
3.8/1.8
3.7/1.8
Orifice
No.
44
46
0.62
Manifold
Pressure
3.3/1.6
3.8/1.8
46
47
48
48
48
3.4/1.6
3.6/1.7
3.8/1.8
3.6/1.7
3.4/1.6
46
47
47
48
48
3.5/1.7
3.7/1.8
3.5/1.7
3.7/1.8
3.5/1.7
Orifice
No.
43
43
44
44
46
46
46
47
0.64
Manifold
Pressure
3.4/1.6
3.2/1.5
3.4/1.6
3.2/1.5
3.8/1.8
3.6/1.7
3.4/1.6
3.7/1.7
Orifice
No.
43
43
44
45
46
46
47
47
0.64
Manifold
Pressure
3.4/1.6
3.2/1.5
3.4/1.6
3.8/1.8
3.8/1.8
3.5/1.7
3.8/1.8
3.5/1.7
Orifice
No.
43
44
45
46
46
47
47
48
0.64
Manifold
Pressure
3.2/1.5
3.4/1.6
3.8/1.8
3.7/1.8
3.5/1.6
3.7/1.7
3.4/1.6
3.7/1.8
Orifice
No.
44
45
46
46
47
48
48
0.64
Manifold
Pressure
3.4/1.6
3.8/1.8
3.7/1.7
3.4/1.6
3.6/1.7
3.8/1.8
3.6/1.7
45
TABLE 13–Orifice Size and Manifold Pressure for Gas Input Rate (Tabulated Data Based On 21,000 Btuh
High-Heat/14,500 Btuh for Low-Heat Per Burner,
Derated 4 Percent For Each 1000 Ft Above Sea Level)(Continued)
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
AT ALTITUDE
(BTU/CU FT)
9001 to
10,000
600
625
650
675
700
725
* Orifice numbers 43 are factory installed
Orifice
No.
46
47
47
48
48
49
0.58
Manifold
Pressure
3.6/1.7
3.7/1.8
3.4/1.6
3.6/1.7
3.4/1.6
3.7/1.8
SPECIFIC GRAVITY OF NATURAL GAS
0.60
0.62
Orifice
No.
Manifold
Pressure
Orifice
No.
Manifold
Pressure
46
47
47
48
48
49
3.7/1.8
3.8/1.8
3.6/1.7
3.8/1.8
3.5/1.7
3.8/1.8
46
46
47
47
48
48
3.8/1.8
3.5/1.7
3.7/1.8
3.4/1.6
3.6/1.7
3.4/1.6
Orifice
No.
45
46
47
47
48
48
0.64
Manifold
Pressure
3.7/1.8
3.6/1.7
3.8/1.8
3.5/1.7
3.7/1.8
3.5/1.7
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow this warning could result in personal injury or death, or property damage.
Before servicing, disconnect all electrical power to furnace.
Verify proper operation after servicing.
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in improper furnace operation or failure of furnace.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Step 1—Introduction
GENERAL
These instructions are written as if the furnace is installed in an upflow application. An upflow furnace application is where the blower is located below the combustion and controls section of the furnace, and conditioned air is discharged upward. Since this furnace can be installed in any of the 4 positions shown in Fig. 4, you must revise your orientation to component location accordingly.
ELECTRICAL CONTROLS AND WIRING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
There may be more than 1 electrical supply to the furnace.
Check accessories and cooling unit for additional electrical supplies that must be shut off during furnace servicing.
The electrical ground and polarity for 115-v wiring must be properly maintained. Refer to Fig. 24 for field wiring information and to Fig. 57 for furnace wiring information.
NOTE: If the polarity is not correct, the STATUS LED on the
control will flash rapidly and prevent the furnace from heating.
The control system also requires an earth ground for proper operation of the control and flame-sensing electrode.
The 24-v circuit contains an automotive-type, 3-amp fuse located on the control. (See Fig. 25.) Any shorts of the 24-v wiring during
46 installation, service, or maintenance will cause this fuse to blow. If fuse replacement is required, use ONLY a 3-amp fuse. The control
LED will display status code 24 when fuse needs to be replaced.
Proper instrumentation is required to service electrical controls.
The control in this furnace is equipped with a Status Code LED
(Light-Emitting Diode) to aid in installation, servicing, and troubleshooting. It can be viewed through the sight glass in blower access door. The amber furnace control LED is either ON continuously, rapid flashing, or a code composed of 2 digits. The first digit is the number of short flashes, the second digit is the number of long flashes.
For an explanation of status codes, refer to service label located on blower access door or Fig. 56, and the troubleshooting guide which can be obtained from your distributor.
See Fig. 62, a brief Troubleshooting Guide.
For 2-Stage Variable Speed ECM Controls the stored status codes will NOT be erased from the control memory, when 115- or 24-v power is interrupted. The control will store up to the last 7 Status
Codes in order of occurence.
1. To retrieve status codes, proceed with the following:
NOTE: NO thermostat signal may be present at control, and all
blower-OFF delays must be completed.
a. Leave 115-v power to furnace turned on.
b. Remove outer access door.
c. Look into blower access door sight glass for current amber
LED status. Removing blower access door will open blower access door switch and terminate 115-v power to control so that status code is not displayed.
d. Remove blower access door.
NOTE: The Status Codes cannot be retrieved by disconnecting
the limit switch or draft safeguard switch. To retrieve Status
Codes, follow the procedure below.
2. Turn Setup Switch, SW1-1 “ON.”
3. Manually close blower access door switch.
4. Control will flash up to 7 Status Codes.
5. The last Status Code, or 8th Code, will be Code 11.
6. Turn SW1-1 “OFF.”
7. A continuously-lit Amber LED will appear and indicates proper operation.
8. Release blower access door switch, install blower access door and replace outer door or refer to the SERVICE label on the front of the blower access door for more information.
Component Self-Test
Component Test can ONLY be initiated by performing the following:
1. Remove outer access door.
2. Remove blower access door.
3. Remove the wire from the “R” terminal of the control board.
4. Turn Setup Switch, SW-1-6 “ON.”
5. Manually close blower access door switch.
Blower access door switch opens 115-v power to control. No component operation can occur unless switch is closed. Caution must be taken when manually closing this switch for service purposes.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, or death.
Blower access door switch opens 115-v power to furnace control. No component operation can occur unless switch is closed. Exercise caution to avoid electrical shock from exposed electrical components when manually closing this switch for service purposes.
6. Component Test sequence will function as follows: a. Inducer motor starts on high-speed and continues to run until Step (d.) of component test sequence.
b. Hot surface igniter is energized for 15 sec, then deenergized.
c. Blower operates for 10 sec, then turns off.
d. Inducer motor goes to low-speed for 10 seconds, then turns off.
e. After component test is completed, one or more status codes (11, 25, or 41) will flash. See component test section of service label for explanation of status codes.
NOTE: To repeat component test, turn setup switch SW1-6 OFF
then back ON.
f. Turn setup switch SW1-6 OFF.
7. RELEASE BLOWER ACCESS DOOR SWITCH, reattach wire to “R” terminal on furnace control board, replace blower access door, and replace outer access door.
Step 2—Care and Maintenance
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Never store anything on, near, or in contact with the furnace, such as:
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners, or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds, plastic or plastic containers, gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids, or other volatile fluids.
3. Paint thinners and other painting compounds, paper bags, or other paper products.
Exposure to these materials could lead to corrosion of the heat exchangers.
For continuing high performance and to minimize possible furnace failure, periodic maintenance must be performed on this furnace.
47
Consult your local dealer about proper frequency of maintenance and the availability of a maintenance contract.
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Turn off the gas and electrical supplies to the furnace before performing any maintenance or service. Follow the operating instructions on the label attached to the furnace.
CARBON MONOXIDE POISONING AND FIRE
HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Never operate furnace without a filter or with filter access door removed.
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces.
The minimum maintenance on this furnace is as follows:
1. Check and clean air filter each month or more frequently if required. Replace if torn.
2. Check blower motor and wheel for cleanliness each heating and cooling season. Clean as necessary.
3. Check electrical connections for tightness and controls for proper operation each heating season. Service as necessary.
4. Inspect burner compartment before each heating season for rust, corrosion, soot or excessive dust. If necessary, have furnace and burner serviced by a qualified service agency.
5. Inspect the vent pipe/vent system before each heating season for rust, corrosion, water leakage, sagging pipes or broken fittings. Have vent pipes/vent system serviced by a qualified service agency.
6. Inspect any accessories attached to the furnace such as a humidifier or electronic air cleaner. Perform any service or maintenance to the accessories as recommended in the accessory instructions.
CLEANING AND/OR REPLACING AIR FILTER
The air filter arrangement will vary depending on the application.
NOTE: If the filter has an airflow direction arrow, the arrow must
point towards the blower.
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces.
Media cabinet filter procedures:
NOTE: Media cabinet is included with variable speed furnace.
1. Turn off electrical supply to furnace before removing filter access door.
Table 14—Filter Size Information (In.)
FURNACE
CASING WIDTH
14-1/2
17-1/2
21
24
* Recommended
FILTER SIZE
Side Return Bottom Return
16 X 25 X 1
16 X 25 X 1
16 X 25 X 1
16 X 25 X 1
14 X 25 X 1
16 X 25 X 1
20 X 25 X 1
24 X 25 X 1
FILTER
TYPE
Cleanable*
Cleanable*
Cleanable*
Cleanable*
2. Remove filter cabinet door.
3. Slide filter out of cabinet.
4. If equipped with permanent, washable 1-inch filter, clean filter by spraying cold tap water through filter in opposite direction of airflow. Rinse filter and let dry. Oiling or coating of the filter is not recommended. See Table 14 for size information.
5. If equipped with factory-specified disposable media filter, replace only with media filter having the same part number and size. For expandable replacement media, refer to the instructions included with the replacement media. If equipped with accessory KGAFR0301ALL external filter rack, See
Table 14.
6. Slide filter into cabinet.
7. Replace filter cabinet door.
8. Turn on electrical supply to furnace.
BLOWER MOTOR AND WHEEL
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Blower access door switch opens 115-v power to control. No component operation can occur unless switch is closed.
Caution must be taken when manually closing this switch for service purposes.
NOTE: The blower wheel should not be dropped or bent as
balance will be affected.
The following steps should be performed by a qualified service agency.
To ensure long life and high efficiency, clean accumulated dirt and grease from blower wheel and motor annually.
The inducer and blower motors are pre-lubricated and require no additional lubrication. These motors can be identified by the absence of oil ports on each end of the motor.
Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
2. Loosen the thumbscrew on outer door and then remove outer door.
3. For downflow or horizontal furnaces having vent pipes within the furnace that pass in front of the blower access door: a. Disconnect vent connector from furnace vent elbow.
b. Disconnect and remove short piece of vent pipe from within furnace.
4. Remove 2 screws from blower access door and remove blower access door.
5. Disconnect blower leads from furnace control. Record wire color and location for reassembly. All other factory wires can be left connected, but field thermostat connections may need to be disconnected depending on their length and routing.
48
6. Remove 2 screws holding control box to blower shelf.
7. Hang control box from front of furnace casing and away from blower compartment.
8. Remove 2 screws holding blower assembly to blower deck and slide blower assembly out of furnace.
9. Clean blower wheel and motor using a vacuum with soft brush attachment. Blower wheel blades may be cleaned with a small paint or flux brush. Do not remove or disturb balance weights
(clips) on blower wheel blades.
10. Vacuum any loose dust from blower housing, wheel and motor.
11. If a greasy residue is present on blower wheel, remove wheel from the blower housing and wash it with an appropriate degreaser. To remove wheel:
NOTE: Before disassembly, mark blower mounting arms, motor,
and blower housing so motor and each arm is positioned at the same location during reassembly.
a. Disconnect ground wire attached to blower housing.
b. Remove screws securing cutoff plate and remove cutoff plate from housing.
c. Loosen set screw holding blower wheel on motor shaft
(160+/-20 in.-lb. when assembling).
d. Remove bolts holding motor to blower housing and slide motor out of wheel (40+/-10 in.-lb. when reassembling).
e. Remove blower wheel from housing.
f. Clean wheel and housing.
12. Reassemble motor and blower by reversing steps 11e, through
11a. Be sure to reattach ground wire to the blower housing.
13. Verify that blower wheel is centered in blower housing and set screw contacts the flat portion of the motor shaft. Loosen set screw on blower wheel and reposition if necessary.
14. Spin the blower wheel by hand to verify that the wheel does not rub on the housing.
15. Reinstall blower assembly in furnace.
16. Reinstall control box assembly in furnace.
NOTE: Refer to Fig. 57 if leads were not identified before
disconnection.
17. Reconnect blower leads to furnace control. Refer to furnace wiring diagram, and connect thermostat leads if previously disconnected.
18. To check blower for proper rotation: a. Turn on electrical supply.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, or death.
Blower access door switch opens 115-v power to furnace control. No component operation can occur unless switch is closed. Exercise caution to avoid electrical shock from exposed electrical components when manually closing this switch for service purposes.
b. Manually close blower access door switch.
NOTE: If R-W/W1 thermostat terminals are jumpered at the time
blower access door switch is closed, blower will run for 90 sec before beginning a heating cycle.
c. Perform component self-test as shown at the bottom of the
SERVICE label, located on the front of blower access door.
d. Verify blower is rotating in the correct direction
19. If furnace is operating properly, RELEASE BLOWER AC-
CESS DOOR SWITCH. Remove any jumpers or reconnect any disconnected thermostat leads. Replace blower access door.
20. Downflow or horizontal furnaces with vent pipe through furnace only: a. Install and connect short piece of vent pipe inside furnace to existing vent.
b. Connect vent connector to vent elbow.
21. Turn on gas supply and cycle furnace through one complete heating and cooling cycle. Verify the furnace temperature rise as shown in Adjustments Section. Adjust temperature rise as shown in Adjustments Section. If outdoor temperature is below 70°F, turn off circuit breaker to outdoor unit before running furnace in the cooling cycle. Turn outdoor circuit breaker on after completing cooling cycle.
CLEANING HEAT EXCHANGER
The following steps should be performed by a qualified service agency:
NOTE: If the heat exchangers get a heavy accumulation of soot
and carbon, they should be replaced rather than trying to clean them thoroughly. A build-up of soot and carbon indicates that a problem exists which needs to be corrected, such as improper adjustment of manifold pressure, insufficient or poor quality combustion air, incorrect size or damaged manifold orifice(s), improper gas, or a restricted heat exchanger. Action must be taken to correct the problem.
If it becomes necessary to clean the heat exchangers because of dust or corrosion, proceed as follows:
1. Turn OFF gas and electrical power to furnace.
2. Remove outer access door.
3. Disconnect vent connector from furnace vent elbow.
4. For downflow or horizontal furnace having an internal vent pipe, remove internal vent pipe within the casing.
5. Disconnect wires to the following components. Mark wires to aid in reconnection (be careful when disconnecting wires from switches because damage may occur): a. Draft safeguard switch.
b. Inducer motor.
c. Pressure switches.
d. Limit overtemperature switch.
e. Gas valve.
f. Hot surface igniter.
g. Flame-sensing electrode h. Flame rollout switches.
6. Remove screws that fasten the collector box assembly to the cell panel. Be careful not to damage the collector box. Inducer assembly and elbow need not be removed from collector box.
7. Disconnect gas line from gas manifold.
8. Remove the 4 screws that attach the burner assembly to the cell panel. The gas valve and individual burners need not be removed from support assembly. Remove NOx baffles, if installed.
NOTE: Be very careful when removing burner assembly to avoid
breaking igniter. See Fig. 58 and 59 for correct igniter location.
9. Using field-provided 25-caliber rifle cleaning brush, 36 in.
long, 1/4
″ diameter steel spring cable, a variable speed,
49
9/32˝
5/16˝
Fig. 58—Igniter Position-Side View
A05025
1-7/8”
A05026
Fig. 59—Igniter Position-Top View
reversible electric drill, and vacuum cleaner, clean cells as follows: a. Remove metal screw fitting from wire brush to allow insertion into cable.
b. Insert the twisted wire end of brush into end of spring cable, and crimp tight with crimping tool or crimp by striking with ball-peen hammer. TIGHTNESS IS VERY
IMPORTANT.
NOTE: The materials needed in item 9 can usually be purchased
at local hardware stores.
(1.) Attach variable-speed, reversible drill to the end of spring cable (end opposite brush).
(2.) Insert brush end of cable into the outlet opening of cell and slowly rotate with drill. DO NOT force cable.
Gradually insert cable into upper pass of cell. (See Fig.
60.)
(3.) Work cable in and out of cell 3 or 4 times to obtain sufficient cleaning. DO NOT pull cable with great force. Reverse drill and gradually work cable out.
(4.) Insert brush end of cable in burner inlet opening of cell, and proceed to clean 2 lower passes of cell in same manner as upper pass.
(5.) Repeat foregoing procedures until each cell in furnace has been cleaned.
(6.) Using vacuum cleaner, remove residue from each cell.
(7.) Using vacuum cleaner with soft brush attachment, clean burner assembly.
(8.) Clean flame sensor with fine steel wool.
(9.) Install NOx baffles (if removed).
Fig. 60—Cleaning Heat Exchanger Cell
A91252
(10.) Reinstall burner assembly. Center burners in cell openings.
10. Remove old sealant from cell panel and collector box flange.
11. Spray releasing agent on the heat exchanger cell panel where collector box assembly contacts cell panel.
NOTE: A releasing agent such as cooking spray or equivalent
(must not contain corn or canola oil, aromatic or halogenated hydrocarbons or inadequate seal may occur) and RTV sealant
(G.E. 162, 6702, or Dow-Corning 738) are needed before starting installation. DO NOT substitute any other type of RTV sealant.
G.E. 162 (P771-9003) is available through RCD in 3-oz tubes.
12. Apply new sealant to flange of collector box and attach to cell panel using existing screws, making sure all screws are secure.
13. Reconnect wires to the following components (Use connection diagram on wiring label, if wires were not marked for reconnection locations.): a. Draft safeguard switch.
b. Inducer motor.
c. Pressure switches.
d. Limit overtemperature switch.
e. Gas valve.
f. Hot surface igniter.
g. Flame-sensing electrode.
h. Flame rollout switches.
14. Reinstall internal vent pipe, if applicable.
15. Reinstall vent connector on furnace vent elbow. Securely fasten vent connector to vent elbow with 2 field-supplied, corrosion-resistant, sheet metal screws located 180° apart.
16. Replace blower access door only if it was removed.
17. Set thermostat above room temperature and check furnace for proper operation.
18. Verify blower airflow and speed changes between heating and cooling.
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
Never use a match or other open flame to check for gas leaks.
Use a soap-and-water solution.
19. Check for gas leaks.
50
Step 3—Sequence of Operation
NOTE: Furnace control must be grounded for proper operation or
else control will lock out. Control is grounded through green/yellow wire routed to gas valve and burner box screw.
Using the schematic diagram in Fig. 57, follow the sequence of operation through the different modes. Read and follow the wiring diagram very carefully.
NOTE: If a power interruption occurs during a call for heat
(W/W1 or W/W1-and-W2), the control will start a 90-second blower-only ON period two seconds after power is restored, if the thermostat is still calling for gas heating. The amber LED light will flash code 12 during the 90-second period, after which the LED will be ON continuous, as long as no faults are detected. After the
90-second period, the furnace will respond to the thermostat normally.
The blower door must be installed for power to be conducted through the blower door interlock switch ILK to the furnace control CPU, transformer TRAN, inducer motor IDM, blower motor BLWM, hot-surface igniter HSI, and gas valve GV.
1. Two-Stage Heating (Adaptive Mode) with Single-Stage
Thermostat
See Fig. 24 or 33 for thermostat connections
NOTE: The low-heat only switch SW1-2 selects either the
low-heat only operation mode when ON, (see item 2. below) or the adaptive heating mode when OFF in response to a call for heat.
(See Table 8.) When the W2 thermostat terminal is energized it will always cause high-heat operation when the R-to-W circuit is closed, regardless of the setting of the low-heat only switch.
This furnace can operate as a two-stage furnace with a single-stage thermostat because the furnace control CPU includes a programmed adaptive sequence of controlled operation, which selects low-heat or high-heat operation. This selection is based upon the stored history of the length of previous gas-heating periods of the single-stage thermostat.
The furnace will start up in either low- or high-heat. If the furnace starts up in low-heat, the control CPU determines the low-heat on-time (from 0 to 16 minutes) which is permitted before switching to high-heat.
If the power is interrupted, the stored history is erased and the control CPU will select low-heat for up to 16 minutes and then switch to high-heat, as long as the thermostat continues to call for heat. Subsequent selection is based on stored history of the thermostat cycle times.
The wall thermostat
″calls for heat″, closing the R-to-W circuit.
The furnace control performs a self-check, verifies the low-heat and high-heat pressure switch contacts LPS and HPS are open, and starts the inducer motor IDM in high-speed.
a. Inducer Prepurge Period
(1.) If the furnace control CPU selects low-heat operation the inducer motor IDM comes up to speed, the low-heat pressure switch LPS closes, and the furnace control CPU begins a 15-second prepurge period. If the low-heat pressure switch LPS fails to remain closed the inducer motor IDM will remain running at high-speed. After the low-heat pressure switch recloses the furnace control CPU will begin a 15-second prepurge period, and continue to run the inducer motor
IDM at high-speed.
(2.) If the furnace control CPU selects high-heat operation, the inducer motor IDM remains running at high-speed, and the high-heat pressure switch relay HPSR is de-energized to close the NC contact. When sufficient pressure is available the high-heat pressure switch
Cooling Tonnage vs. Airflow (CFM)
AIR CONDITIONING
TONS (12,000 BTU/HR)
1-1/2
2
2-1/2
3
AIRFLOW
(CFM)
525
700
875
1050
3-1/2
4
5
6
1225
1400
1750
2100
X-INDICATES AN ALLOWABLE SELECTION.
070 MODEL
X
2
X
X
X
1
X
1
090 MODEL
X
X
2
X
X
X
1
X
1
AIR CONDITIONING (A/C) OR CONTINUOUS-FAN (CF) AIRFLOW SELECTION CHART
BASED ON 350 CFM/TON
SW1-5 ON
SWITCH SW3 POSITIONS
MODEL
SIZE
070
090
DEF
DEF
110,135,155 DEF
525
2
525
700
700
700
2
875
2
875
875
1050
1050
1
1050
1225
1225
1225
1400
1225
1400
1
1750
1
1225
1400
2100
110, 135,
& 155 MODELS
X
X
2
X
X
X
X
X
1
BASED ON 400 CFM/TON
SW1-5 ON
SWITCH SW3 POSITIONS
MODEL
SIZE
070
090
110,135,155
DEF 600
2
800 1000 1200
1
DEF 600 800
DEF 800 1000
2
2
1000 1200
1400 1400 1400
1400 1600
1
1200 1400 1600 2000
1
1600
2200
1.DEFAULT A/C AIRFLOW WHEN A/C SWITCHES ARE IN OFF POSITION (FACTORY SETTING)
2.DEFAULT CONT. FAN AIRFLOW WHEN CF SWITCHES ARE IN OFF POSITION (FACTORY SETTING)
3. SWITCH POSITIONS ARE ALSO SHOWN ON FURNACE WIRING DIAGRAM
Fig. 61—Cooling (A/C) or Continuous-Fan (CF) Airflow Selection Chart
HPS closes, and the high-heat gas valve solenoid
GV-HI is energized. The furnace control CPU begins a 15-second prepurge period after the low-heat pressure switch LPS closes. If the high-heat pressure switch HPS fails to close and the low-heat pressure switch LPS closes, the furnace will operate at low-heat gas flow rate until the high-heat pressure switch closes for a maximum of 2 minutes after ignition.
b. Igniter Warm-Up -At the end of the prepurge period, the
Hot-Surface Igniter HSI is energized for a 17-second igniter warm-up period.
c. Trial-For-Ignition Sequence -When the igniter warm-up period is completed the main gas valve relay contact GVR closes to energize the gas valve solenoid GV-M. The gas valve solenoid GV-M permits gas flow to the burners where it is ignited by the HSI. Five seconds after the GVR closes, a 2-second flame proving period begins. The HSI igniter will remain energized until the flame is sensed or until the 2-second flame proving period begins.
If the furnace control CPU selects high-heat operation, the high-heat gas valve solenoid GV-HI is also energized.
d. Flame-Proving - When the burner flame is proved at the flame-proving sensor electrode FSE, the inducer motor
IDM switches to low-speed unless the furnace is operating in high-heat, and the furnace control CPU begins the blower-ON delay period and continues to hold the gas valve GV-M open. If the burner flame is not proved within
A03220 two seconds, the control CPU will close the gas valve
GV-M, and the control CPU will repeat the ignition sequence for up to three more Trials-For-Ignition before going to Ignition-Lockout. Lockout will be reset automatically after three hours, by momentarily interrupting
115 vac power to the furnace, or by interrupting 24 vac power at SEC1 or SEC2 to the furnace control CPU (not at
W/W1, G, R, etc.).
If flame is proved when flame should not be present, the furnace control CPU will lock out of Gas-Heating mode and operate the inducer motor IDM on high speed until flame is no longer proved.
e. Blower-On delay - If the burner flame is proven the blower-ON delays for low-heat and high-heat are as follows:
Low-heat - 45 seconds after the gas valve GV-M is opened
the blower motor BLWM is turned ON at low-heat airflow.
High-heat - 25 seconds after the gas valve GV-M is
opened the BLWM is turned ON at high-heat airflow.
Simultaneously, the humidifier terminal HUM and electronic air cleaner terminal EAC-1 are energized and remain energized throughout the heating cycle.
f. Switching from Low- to High-Heat - If the furnace control CPU switches from low-heat to high-heat, the furnace control CPU will switch the inducer motor IDM speed from low to high. The high-heat pressure switch relay
HPSR is de-energized to close the NC contact. When
51
sufficient pressure is available the high-heat pressure switch HPS closes, and the high-heat gas valve solenoid
GV-HI is energized. The blower motor BLWM will transition to high-heat airflow five seconds after the furnace control CPU switches from low-heat to high-heat.
g. Switching from High- to Low-Heat -The furnace control
CPU will not switch from high-heat to low-heat while the thermostat R-to-W circuit is closed when using a singlestage thermostat.
h. Blower-Off Delay - When the thermostat is satisfied, the R to W circuit is opened, de-energizing the gas valve GV-M, stopping gas flow to the burners, and de-energizing the humidifier terminal HUM. The inducer motor IDM will remain energized for a 5-second post-purge period. The blower motor BLWM and air cleaner terminal EAC-1 will remain energized at low-heat airflow or transition to low-heat airflow for 90, 120, 150, or 180 seconds (depending on selection at blower-OFF delay switches). The furnace control CPU is factory-set for a 120-second blower-OFF delay.
2. Two-Stage Thermostat and Two-Stage Heating
See Fig. 32 for thermostat connections.
NOTE: In this mode the low-heat only switch SW1-2 must be ON
to select the low-heat only operation mode in response to closing the thermostat R-to-W1 circuit. Closing the thermostat R-to-
W1-and-W2 circuits always causes high-heat operation, regardless of the setting of the low-heat only switch.
The wall thermostat
″calls for heat″, closing the R-to-W1 circuit for low-heat or closing the R-to-W1-and-W2 circuits for high-heat.
The furnace control performs a self-check, verifies the low-heat and high-heat pressure switch contacts LPS and HPS are open, and starts the inducer motor IDM in high-speed.
The start up and shut down functions and delays described in item
1. above apply to the 2-stage heating mode as well, except for switching from low- to high-Heat and vice versa.
a. Switching from Low- to High-Heat - If the thermostat Rto-W1 circuit is closed and the R-to-W2 circuit closes, the furnace control CPU will switch the inducer motor IDM speed from low to high. The high-heat pressure switch relay HPSR is de-energized to close the NC contact. When sufficient pressure is available the high-heat pressure switch HPS closes, and the high-heat gas valve solenoid
GV-HI is energized. The blower motor BLWM will transition to high-heat airflow five seconds after the R-to-W2 circuit closes.
b. Switching from High- to Low-Heat -If the thermostat Rto-W2 circuit opens, and the R-to-W1 circuit remains closed, the furnace control CPU will switch the inducer motor IDM speed from high to low. The high-heat pressure switch relay HPSR is energized to open the NC contact and de-energize the high-heat gas valve solenoid GV-HI. When the inducer motor IDM reduces pressure sufficiently, the high-heat pressure switch HPS will open. The gas valve solenoid GV-M will remain energized as long as the low-heat pressure switch LPS remains closed. The blower motor BLWM will transition to low-heat airflow five seconds after the R-to-W2 circuit opens.
3. Cooling mode
The thermostat
″calls for cooling″.
a. Single-Speed Cooling-
See Fig. 24 for thermostat connections
The thermostat closes the R-to-G-and-Y circuits. The R-to-
Y circuit starts the outdoor unit, and the R-to-G-and-Y/Y2 circuits start the furnace blower motor BLWM on cooling
52 airflow. Cooling airflow is based on the A/C selection shown in Fig. 61. The electronic air cleaner terminal
EAC-1 is energized with 115 vac when the blower motor
BLWM is operating.
When the thermostat is satisfied, the R-to-G-and-Y circuits are opened. The outdoor unit will stop, and the furnace blower motor BLWM will continue operating at cooling airflow for an additional 90 seconds. Jumper Y/Y2 to
DHUM to reduce the cooling off-delay to 5 seconds. (See
Fig. 25.) b. Single-Stage
Thermostat and Two-Speed Cooling
(Adaptive Mode) -
See Fig. 33 for thermostat connections
This furnace can operate a two-speed cooling unit with a single-stage thermostat because the furnace control CPU includes a programmed adaptive sequence of controlled operation, which selects low-cooling or high-cooling operation. This selection is based upon the stored history of the length of previous cooling period of the single-stage thermostat.
NOTE: The air conditioning relay disable jumper ACRDJ must
be connected to enable the adaptive cooling mode in response to a call for cooling. (See Fig. 25.) When ACRDJ is in place the furnace control CPU can turn on the air conditioning relay ACR to energize the Y/Y2 terminal and switch the outdoor unit to high-cooling.
The furnace control CPU can start up the cooling unit in either low- or high-cooling. If starting up in low-cooling, the furnace control CPU determines the low-cooling on-time (from 0 to 20 minutes) which is permitted before switching to high-cooling.
If the power is interrupted, the stored history is erased and the furnace control CPU will select low-cooling for up to 20 minutes and then energize the air conditioning relay ACR to energize the
Y/Y2 terminal and switch the outdoor unit to high-cooling, as long as the thermostat continues to call for cooling. Subsequent selection is based on stored history of the thermostat cycle times.
The wall thermostat
″calls for cooling″, closing the R-to-G-and-Y circuits. The R-to-Y1 circuit starts the outdoor unit on low-cooling speed, and the R-to-G-and-Y1 circuits starts the furnace blower motor BLWM at low-cooling airflow which is the true on-board
CF selection as shown in Fig. 61.
If the furnace control CPU switches from low-cooling to highcooling, the furnace control CPU will energize the air conditioning relay ACR. When the air conditioning relay ACR is energized the
R-to-Y1-and-Y2 circuits switch the outdoor unit to high-cooling speed, and the R-to-G-and-Y1-and-Y/Y2 circuits transition the furnace blower motor BLWM to high-cooling airflow. Highcooling airflow is based on the A/C selection shown in Fig. 61.
NOTE: When transitioning from low-cooling to high-cooling the
outdoor unit compressor will shut down for 1 minute while the furnace blower motor BLWM transitions to run at high-cooling airflow.
The electronic air cleaner terminal EAC-1 is energized with 115 vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R-to-G-and-Y circuit are opened. The outdoor unit stops, and the furnace blower BLWM and electronic air cleaner terminal EAC-1 will remain energized for an additional 90 seconds. Jumper Y1 to DHUM to reduce the cooling off-delay to 5 seconds. (See Fig. 25.) c. Two-Stage Thermostat and Two-Speed Cooling
See Fig. 32 for thermostat connections
NOTE: The air conditioning relay disable jumper ACRDJ must
be disconnected to allow thermostat control of the outdoor unit staging. (See Fig. 25.)
The thermostat closes the R-to-G-and-Y1 circuits for low-cooling or closes the R-to-G-and-Y1-and-Y2 circuits for high-cooling. The
R-to-Y1 circuit starts the outdoor unit on low-cooling speed, and the R-to-G-and-Y1 circuit starts the furnace blower motor BLWM at low-cooling airflow which is the true on-board CF (continuous fan) selection as shown in Fig. 61. The R-to-Y1-and-Y2 circuits start the outdoor unit on high-cooling speed, and the R-to-
G-and-Y/Y2 circuits start the furnace blower motor BLWM at high-cooling airflow. High-cooling airflow is based on the A/C (air conditioning) selection shown in Fig. 61.
The electronic air cleaner terminal EAC-1 is energized with 115 vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R-to-G-and-Y1 or R-to-
G-and-Y1-and-Y2 circuits are opened. The outdoor unit stops, and the furnace blower BLWM and electronic air cleaner terminal
EAC-1 will remain energized for an additional 90 seconds. Jumper
Y1 to DHUM to reduce the cooling off-delay to 5 seconds. (See
Fig. 25.)
4. Thermidistat Mode
See Fig. 26-29 for thermostat connections
The dehumidification output, DHUM on the Thermidistat should be connected to the furnace control thermostat terminal
DHUM. When there is a dehumidify demand, the DHUM input is activated, which means 24 vac signal is removed from the DHUM input terminal. In other words, the DHUM input logic is reversed. The DHUM input is turned ON when no dehumidify demand exists. Once 24 vac is detected by the furnace control on the DHUM input, the furnace control operates in Thermidistat mode. If the DHUM input is low for more than 48 hours, the furnace control reverts back to non-Thermidistat mode.
The cooling operation described in item 3. above also applies to operation with a Thermidistat. The exceptions are listed below: a. Low cooling-When the R-to-G-and-Y1 circuit is closed and there is a demand for dehumidification, the furnace blower motor BLWM will drop the blower airflow to 86 percent of low-cooling airflow which is the true on-board
CF (continuous fan) selection as shown in Fig. 61.
b. High cooling-When the R-to-G-and Y/Y2 circuit is closed and there is a demand for dehumidification, the furnace blower motor BLWM will drop the blower airflow to 86 percent of high-cooling airflow. High-cooling airflow is based on the A/C (air conditioning) selection shown in Fig.
61.
c. Cooling off-delay-When the
″call for cooling″ is satisfied and there is a demand for dehumidification, the cooling blower-off delay is decreased from 90 seconds to 5 seconds.
5. Super-Dehumidify Mode
Super-Dehumidify mode can only be entered if the furnace control is in the Thermidistat mode and there is a demand for dehumidification. The cooling operation described in item 3.
above also applies to operation with a Thermidistat. The exceptions are listed below: a. When the R-to-Y1 circuit is closed, R-to-G circuit is open, and there is a demand for dehumidification, the furnace blower motor BLWM will drop the blower airflow to 65 percent of low-cooling airflow for a maximum of 10 minutes each cooling cycle or until the R-to-G circuit closes or the demand for dehumidification is satisfied.
Low-cooling airflow is the true on-board CF (continuous fan) selection as shown in Fig. 61.
b. When the R-to-Y/Y2 circuit is closed, R-to-G circuit is open, and there is a demand for dehumidification, the furnace blower motor BLWM will drop the blower airflow to 65 percent of high-cooling airflow for a maximum of 10 minutes each cooling cycle or until the R-to-G circuit closes or the demand for dehumidification is satisfied.
High-cooling airflow is based on the A/C (air conditioning) selection shown in Fig. 61.
c. When the
″call for cooling″ is satisfied and there is a demand for dehumidification, the cooling blower-off delay is decreased from 90 seconds to 5 seconds.
6. Continuous Blower Mode
When the R-to-G circuit is closed by the thermostat, the blower motor BLWM will operate at continuous blower airflow. Continuous blower airflow selection is initially based on the CF (continuous fan) selection shown in Fig. 61. Factory default is shown in Fig. 61. Terminal EAC-1 is energized as long as the blower motor BLWM is energized.
During a call for heat, the furnace control CPU will transition the blower motor BLWM to continuous blower airflow, low-heat airflow, or the midrange airflow, whichever is lowest. The blower motor BLWM will remain ON until the main burners ignite then shut OFF and remain OFF for the blower-ON delay (45 seconds in low-heat, and 25 seconds in high-heat), allowing the furnace heat exchangers to heat up more quickly, then restarts at the end of the blower-ON delay period at low-heat or high-heat airflow, respectively.
The blower motor BLWM will revert to continuous-blower airflow after the heating cycle is completed. In high-heat, the furnace control CPU will drop the blower motor BLWM to low-heat airflow during the selected blower-OFF delay period before transitioning to continuous-blower airflow.
When the thermostat
″calls for low-cooling″, the blower motor
BLWM will switch to operate at low-cooling airflow. When the thermostat is satisfied, the blower motor BLWM will operate an additional 90 seconds at low-cooling airflow before transitioning back to continuous-blower airflow.
When the thermostat
″calls for high-cooling″, the blower motor BLWM will operate at high cooling airflow. When the thermostat is satisfied, the blower motor BLWM will operate an additional 90 seconds at high-cooling airflow before transitioning back to continuous-blower airflow.
When the R-to-G circuit is opened, the blower motor BLWM will continue operating for an additional 5 seconds, if no other function requires blower motor BLWM operation.
Continuous Blower Speed Selection from Thermostat -To
select different continuous-blower airflows from the room thermostat, momentarily turn off the FAN switch or pushbutton on the room thermostat for 1-3 seconds after the blower motor BLWM is operating. The furnace control CPU will shift the continuous-blower airflow from the factory setting to the next highest CF selection airflow as shown in Fig. 61.
Momentarily turning off the FAN switch again at the thermostat will shift the continuous-blower airflow up one more increment. If you repeat this procedure enough you will eventually shift the continuous-blower airflow to the lowest
CF selection as shown in Table 1. The selection can be changed as many times as desired and is stored in the memory to be automatically used following a power interruption.
NOTE: If the blower-off delay is set to the maximum, the
adjustable continuous-fan feature is locked (i.e., fan speed cannot be changed from its current setting).
53
7. Heat pump
See Fig. 28-31 for thermostat connections.
When installed with a heat pump, the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles. Whenever W/W1 is energized along with Y1 or Y/Y2, the furnace control CPU will transition to or bring on the blower motor BLWM at cooling airflow, low-heat airflow, or the midrange airflow, whichever is lowest. The blower motor BLWM will remain on until the main burners ignite then shut OFF and remain OFF for 25 seconds before coming back on at heating airflow.
When the W/W1 input signal disappears, the furnace control begins a normal inducer post-purge period while changing the blower airflow. If Y/Y2 input is still energized the furnace control CPU will transition the blower motor BLWM airflow to cooling airflow. If Y/Y2 input signal disappears and the Y1 input is still energized the furnace control CPU will transition the blower motor BLWM to low-cooling airflow. If both the
Y1 and Y/Y2 signals disappear at the same time, the blower motor BLWM will remain on at low-heat airflow for the selected blower-OFF delay period. At the end of the blower-
OFF delay, the blower motor BLWM will shut OFF unless G is still energized, in which case the blower motor BLWM will operate at continuous blower airflow.
8. Component test
The furnace features a component test system to help diagnose a system problem in the case of a component failure. To initiate the component test procedure, ensure that there are no thermostat inputs to the control and all time delays have expired. Turn on setup switch SW1-6. (See Fig. 25.)
NOTE: The component test feature will not operate if the control
is receiving any thermostat signals or until all time delays have expired.
The component test sequence is as follows: a. The furnace control CPU turns the inducer motor ON at high-heat speed and keeps it ON through step c.
b. After waiting 10 seconds the furnace control CPU turns the hot surface igniter ON for 15 seconds, then OFF.
c. The furnace control CPU then turns the blower motor
BLWM on at midrange airflow for 15 seconds, then OFF.
d. After shutting the blower motor OFF the furnace control
CPU switches the inducer to low-heat speed for 10 seconds, then OFF.
NOTE: The EAC terminals are energized when the blower is
operating.
After the component test is completed, 1 or more status codes (11,
25, or 41) will flash. See component test section or Service Label
(Fig. 56.) for explanation of status codes.
NOTE: To repeat component test, turn setup switch SW1-6 to
OFF and then back ON.
Step 4—Wiring Diagram
Refer to wiring diagram Fig. 57.
Step 5—Troubleshooting
Refer to the service label. (See Fig. 56—Service Label.)
The Troubleshooting Guide (See Fig. 62.) can be a useful tool in isolating furnace operation problems. Beginning with the word
“Start,” answer each question and follow the appropriate arrow to the next item.
The Guide will help to identify the problem or failed component.
After replacing any component, verify correct operation sequence.
A more detailed Troubleshooting Guide is available from your distributor.
54
55
Copyright 2006 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 6a 8a
PC 101 Printed in U.S.A.
Pg 56 4-06
57
Copyright 2006 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 6a 8a
PC 101 Printed in U.S.A.
Pg 58 4-06
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project