TUNEAdapt5

TUNEAdapt5
TUNE Adapt
User guide Version: 5
TUNE Adapt
1
TUNE Adapt
Figure 9. To open the sensor module, use a screw driver, be careful when reinstalling the module to avoid damaging the positioning pins.
TUNE Adapt
Description
TUNE Adapt is a hand-held terminal for setting and viewing the readings of all ADAPT products. TUNE Adapt is
powered by the product it is connected to. Tune Adapt
is supplied as standard with display in four languages:
Swedish, English, French and Danish. The compatibility of
the various versions of the ADAPT controller is as follows:
hand-held micro terminals of later version cannot read
older versions of ADAPT controllers, hand-held micro
terminals of older version can always read the newer
ADAPT controllers, however the newer variables will then
be lacking in the hand-held micro terminal. The hand-held
terminal must not be confused with the terminal that is
supplied with the GOLD air handling unit, it has different
software.
Keypad functions
The arrow keys are used for advancing up and down
in the menus. To change to an underlying menu press
“enter”  . In the menus for entering settings, you must
immediately press ”enter” again to come to the image
where you can change the variables. All the variables that
can be changed will then be highlighted.
The +/- keys are used for increasing or decreasing the
values. The values are changed immediately in the ADAPT
products, without having to press ”enter”.
Figure 10. TUNE Adapt can be connected to the air diffuser using
the RJ12 contact on the circuit card.
Press X to return to the previous menu.
The display can shown only four lines with text. In the
descriptions that follow, the menus below are displayed in
a fainter tone. The menus appear more distinctly as you
press the arrow “down" key.
There is a small red LED to the side of the ”enter” key.
When it shines/flashes, the ADAPT product, to which it
is connected, is being 0 calibrated. Wait a minute or two
and reconnect TUNE Adapt.
Figure 11. TUNE Adapt can be connected directly to the single
contact on the side in the duct dampers.
2
Swegon reserves the right to alter specifications.
20100112
www.swegon.com
TUNE Adapt
The display screen
The uppermost line always shows the Swegon headline,
on later versions the program version for the ADAPT
products is shown as well.
The line with highlighted text is the selected line you can
advance to by pressing the  ”enter button”.
The pile to the right indicates whether there are more
menu lines below that you can access by navigating
downward. The black field at the lower edge shows that
there are menu lines below. The contrary applies if there
is a black field at the upper edge.
Tune Adapt menu structures
Descriptions of the menus
The input menu for start up. The image shows all the
functions that are available from the start menu. Press
enter to advance to the menu selected.
* S W E G O N
T U N E A D A P T *
USER MENU
LANGUAGE
ADVANCED MENU
TEST MENU
SAVE / LOAD *MENU
USER MENU *
AIRFLOW
000l/s
ROOM TEMP
00.0g
SUPPLY AIR TEMP
00.0g
0000ppm
CAC LEVEL
CAC CO2 EQUV
00%
0000ppm
COOLING
000%
HEATING
000%
VALVE POS
000%
OCC TIME
00000h
RUN TIME
00000h
SOFTWARE
SERIAL NUMBER
Supply air temp
Shows the value of the built-in temperature sensor. In certain
applications such as ADAPT Damper if the extract air, the
temperature cannot be shown, the value -1 is then given.
CO2 in room
If DETECT Quality is connected and Application type is set
to 2 the carbon dioxide value in the room is shown.
CAC
If Clean Air Control is enabled, the air quality value and
the corresponding recalculated CO2 value in ppm are
shown here. Good air quality corresponds here to a CAC
value that is lower than 35%.
Cooling (Cooling load)
Shows the value of the cooling load 0-100%, 0% corresponds to vacancy or the occupancy flow, 100% corresponds to the max. flow.
Heating (Heating load)
The heating load in % is shown here if the controller is
set for heating control. Heating control is time proportional which means that the valve is open only during that
part of the time cycle to which the heat load corresponds,
example: heating load 50%, the valve is open 50% of
350 s = 175 s. and then closed for 175 s.
ALARM MENU
CO2 IN ROOM
Room temp
Shows the room temperature in °C regardless of whether
the temperature is measured by the built-in sensor or
a connected DETECT Temp. In certain applications, for
example ADAPT Damper for supply air, the room temperature cannot be shown. The value -1 is given in this case.
In ADAPT Damper, the extract air temperature can be one
or two degrees higher than the representative room temperature. This should be taken into consideration when
selecting the set points for the temperature settings.
0000
00000
Valve pos (Valve pos, later than version 3)
The value of the valve output is shown here, which most
often is equal to the heating load. If the cold down draught
protection function is enabled, the heating load can be 0%
while the valve output can be 20% for instance.
Occ time (Time occupied)
The controller has a time counter which automatically
counts the time during which the premises is occupied.
The function can for instance be used for analysis of the
cleaning interval, etc.
Run time (Total runtime)
The controller has a built-in operating time counter which is
enabled as soon as the controller is powered. The counter
automatically resets after 32767 hours, approx. 3.7 years.
Software
Current version of the software.
Serial number
The product serial number.
Swegon reserves the right to alter specifications.
20100112
www.swegon.com
3
TUNE Adapt
* SW EG ON T U N E A D A P T *
USER MENU
A L AR M ME N U
L AN G U A GE
Airflow
The current airflow in l/s and the estimated set-point is
shown here.
TUNE Adapt
Alarm menu
These menus show the value 1 if something is abnormal
in the ADAPT product. At the same time, the diode in the
sensor module shines red.
* SWEGON TUNE A V5 *
USER MENU
ALARM MENU
LANGUAGE
* ALARM MENU *
ADVANCED MENU
ALARM
TESTFUNCTION
MENU
STROKE
SAVE DAMPER
/ LOAD MENU
MOTOR
0
0
PRESSURE SENSOR
0
ROOM TEMP
0
SUPPLY TEMP
0
WRONG SET POINT
0
COMFORT ALARM
0
TEMPERATURE
0
AIR QUALITY
0
Damper stroke
ALARM SETTINGS
When the controller is started up, a stroke check is carried
60
out. If thisSET
checkTIME
fails, an alarm is initiated.
RESET TIME
1
Motor
MAX
TEMPis DEV
If the control
function
not operating so that the2 motor
200 of
can steer MAX
to the CO2
desiredDEV
position within the length
damper stroke detected, an alarm is initiated.
Pressure sensor
If the pressure sensor transmits unreasonable values or if
communication to this sensor ceases, an alarm is initiated.
Room Temp
Refers to failure of the built-in temperature sensor normally fitted inside the sensor module.
Supply Temp
Refers to failure of the built-in temperature sensor normally
fitted in the supply airflow path inside the air diffuser.
Wrong set point
An alarm is initiated if the heating set point and cooling
set point cross one another. The heating load must always
be lower than the cooling set point.
4
Swegon reserves the right to alter specifications.
CAC Sensor error
Indicates that the built-in sensor is faulty or is missing.
Comfort alarm
Activates the comfort control system and initiates an
alarm if the temperature or CO2 value deviates more than
the preset limit values during a period longer than the
preset period (60 min.). If the cause of the alarm is remedied, the alarm value is cleared after the preset period (5
min.).
Language menu
Used for changing the language in TUNE Adapt.
* SWEGON TUNE A V5 *
USER MENU
ALARM MENU
LANGUAGE
ADVANCED MENU
TEST MENU
SAVE / LOAD* LANGUAGE
MENU
MENU *
ENGLISH
SVENSKA
SUOMI
DANSK
Language menu
As standard, TUNE Adapt is supplied with text in four languages: English, Swedish, Finnish and Danish. Scroll down
to the language desired and press enter.
Other language combinations are the following:
English, Swedish, Russian and Polish
or
English, Swedish, German and French
These variants must however be ordered separately.
20100112
www.swegon.com
TUNE Adapt
Advanced menu
Heat temp unocc (Heating temperature, unoccupied)
The same function as for the occupancy temperature
All the setting values can be changed in these menus.
Calc setp (Calculated set-point)
The estimated value for control is shown here. When the
room temperature is between the heating and cooling set
point, the room temperature is shown in this variable. If
the room temperature is above the set point for cooling
control, the set point is shown (for example 23.0°)
* SWEGON TUNE A V5 *
ALARM MENU
LANGUAGE
ADVANCED MENU
TEST MENU
SAVE / LOAD MENU
When you select the ADVANCED MENU, a warning is
shown to remind you to be especially cautious; changing data in these menus could compromise the regulator
function.
* ADVANCED MENU *
External input
The external input level 0-100% corresponds to the input
function when an external control is used, see the Application Menu.
TEMP MENU
FLOW MENU
PRESENCE (INT)
COMMUNICATION
Nightcool (Night-time cooling)
Set point for night-time cooling. This set point applies
when the night-time cooling function is enabled from a
main control system and it leads to boosting the airflow
until the flow reaches its preset max. airflow rate.
APPLICATION MENU
* TEMPERATURE MENU *
COOL TEMP OCC
23°
HEAT TEMP OCC
21°
COOL TEMP UNOCC
25°
HEAT TEMP UNOCC
20°
CALC SETP
Morning heat
This function is not enabled in the controller, (will be
introduced in a later version).
21.0°
ROOM TEMP DEV
0.0°
EXTERNAL INPUT
100%
NIGHTCOOL
18°
MORNING HEAT
25°
HEAT VALVE TIME
Example:
Cooling set point 23°: if the room temperature is 22.5°
the value 0,0 is shown on the nonconforming temperature line. Now if TUNE Temp knob is turned down as
much as possible for reduced room temperature, the cooling set point will be 20° and the value 2.5° will then be
shown. This means that it is 2.5° too warm in the room
and the cooling control function will start.
Heat valve time (protected variable)
This time is the normal time it takes for a thermal actuator to open completely from the cold position. The time is
used for the time proportional opening when the heating
load is <100%.
350sec
Cool temp occ (Cooling temperature, occupied)
The temperature at which cooling control begins. If the
system has sufficient capacity, this will be the maximum
room temperature in the cooling mode.
If the ADAPT controller is to control electric heating via
semi-conductor relay the time should be set to max.
60 sec. The variable can only be changed via a special
Modbus tool of Modbus Poll type.
Heat temp occ (Heating temperature, occupied)
The temperature at which heating control begins. This will
be the room’s lowest temperature if the ADAPT product
steers heating control. If this does not take place, the
value is insignificant.
Cool temp unocc (Cooling temperature, unoccupied)
The same function as for the occupancy temperature.
Swegon reserves the right to alter specifications.
20100112
www.swegon.com
5
TUNE Adapt
Temperature menu
In order to be able to change a value, it must be highlighted by pressing enter on the first menu line. In the
image, this value is: COOL TEMP OCC.
Room temp dev (Room temperature deviation)
The difference is shown here between the actual values
and the preset set points for cooling/heating for occupancy or vacancy. When the room temperature is in the
dead band, the value 0 is shown. If TUNE Temp is used
for set point displacement, the change can be read in this
menu only.
TUNE Adapt
Airflow
In order to be able to change a value, you must highlight
it by pressing enter on the first menu line. In the image,
this is: OCCUPANCY.
Slave output
Shows the slave output flow level: 0% is minimum or
vacancy flow, 100% corresponds to the maximum airflow.
* ADVANCED MENU *
TEMPERATURE
AIRFLOW
OCCUPANCY (INT)
COMMUNICATION
* AIR FLOW *
APPLICATION MENU
OCCUPANCY
MIN
10l/s
MAX
40l/s
UNOCCUPIED
MIN
5l/s
PRESSURE SENSOR
FLOW PRESS
45.2Pa
PRESS 0-CAL.
00.0Pa
DAMPER POS
Damper pos (Damper position)
The current damper blade position can be read here.
When commissioning, make sure that this value is at least
85% open for the design room in the zone.
100%
SLAVE OUTPUT
0%
CO2
Under this menu, set the limit values for the proportional
airflow control function in relation to the CO2 value. Control starts from the minimum set point and proportionally
increases to 100% airflow for the maximum set point.
ppm per Volt
This is the interpretive value of the input signal from the
CO2 sensor. This is normally 200 ppm/V.
CAC MIN.
The lower limit where the airflow increase starts for ventilation to remove impurities.
CAC MAX.
The upper limit where the airflow has reached its max.
value.
CO2
MIN SET
MAX SET
800ppm
1000ppm
PPM PER VOLT
200
CAC SET POINTS
CAC MIN SET
25%
CAC MAX SET
35%
Occupancy min/max
The airflows to be used for the relevant room can be set
here. If the product is marked with a “default” in the
designation, then it is a product from stock with standard
settings that probably are not applicable to the current
installation.
Unoccupied
The airflow for vacancy of occupants
Pressure sensor
The current flow pressure can be read here. This pressure
is almost identical to the static pressure drop across the
air diffuser.
Zero calibration can be carried out, however this requires
that you are sure that there is no airflow. It will not help
to force the damper to close. 0-calibration has been carried out at the factory prior to delivery and should not
normally need to be changed.
6
Swegon reserves the right to alter specifications.
20100112
www.swegon.com
TUNE Adapt
Occupancy (INT)
Communication
In order to be able to change a value, you must highlight
it by pressing enter on the first menu line. In the image,
this is: Occupancy.
In order to be able to change a value, it must be highlighted by pressing enter on the first menu line. In the
image, this is: Modbus address.
* ADVANCED MENU *
* ADVANCED MENU *
TEMPERATURE
AIRFLOW
AIRFLOW
OCCUPANCY (INT)
OCCUPANCY (INT)
COMMUNICATION
* OCCUPANCY (INT) *
APPLICATION MENU
OCC SENSOR LEV
0000
COMMUNICATION
OCC STATUS
0
OCC STAT+DELAY
0
DELAY OFF
20m
DELAY ON
00s
APPLICATION MENU
* COMMUNICATION *
MODBUS ADDRESS
BAUDRATE
PARITY
000
38.4k
NONE
STOP BITS
Occ status
Shows the momentary status from the built-in presence
detector 1=occupancy. The value returns to 0 after 1
minute if no new occupancy has been detected.
Modbus address
The address can be set to a value between 1-248.
Baud rate
The communication speed can be set to three levels: 9.6k
- 19.2k - 38.4k.
Parity
The parity check can be set to: Even/Uneven/None.
Occ stat + delay
The occupancy situation including the delay. This value
applies to the entire system of master/slave air diffusers
that are interconnected.
Stop bits
Can be set either to 1 or 0.
Delay off
The time until the controller switches over to vacancy if
no new occupancy has been detected.
Delay on
The switch on delay time must always be 0 if the lighting
is to be controlled. Otherwise the value can appropriately
be 30 s.
Swegon reserves the right to alter specifications.
20100112
www.swegon.com
7
TUNE Adapt
Occ sensor lev (Occupancy sensor level)
Indicates the signal level from the built-in presence sensor.
The limit value for detecting occupancy is 250.
1
TUNE Adapt
Application menu
In order to be able to change a value, it must be highlighted by pressing enter on the first menu line. In the
image, this is: APPLICATION.
* ADVANCED MENU *
0 = ADAPT supply air diffuser
1 = ADAPT Exhaust and Damper for extract air
2 = ADAPT Damper for supply air
OCCUPANCY (INT)
COMMUNICATION
APPLICATION MENU
* APPLICATION MENU *
APPLICATION
0
LED FUNCTION
TEMP SENSOR USE
TYPE
0
HEATING
PRESENT
COOL PROTECTION
ACTIVE LEVEL
20%
COOL LIMIT
50%
VALVE EXERCISE
TIME INTERVAL
Temperature sensor use (from Software Version 5)
How the built-in temperature sensors should be used is
adjusted with this variable. This function is programmed
from the factory. If “default” ADAPT Damper is supplied
directly from stock, you will have to change this variable if
the damper is to be adjusted for use as a slave.
5days
CAC USE
NOT PRESENT
VENT BOOST
ON
BOOST DELAY
BOOST TIME
72h
5m
CAC/CO2 AT UNOCC
NOT ACTIVE
Application
Select the application that fits the description. The application describes how the external control input on the
master air diffuser should be used. The slave air diffuser
should always have the value 3.
0 = Temperature control (ADAPT) 1 = External control with 0-10 V DC signal
2 = Temp. control (ADAPT) + CO2 (DETECT Q 0)
3 = Slave controller 4 = Set point switch, TUNE Temp
5 = External temp. sensor, DETECT Temp
Heat valve control (Software later than Version 4)
If the ADAPT controller is to be used for controlling the
radiators, this function must be enabled, however it
cannot be combined with two-phase cooling. In the Ver.
3 ADAPT, change-over can only take place in Modbus via
variable 0x0006.
Cold down draught protection (Software later than
Version 3)
This function applies only from Program Version 4. The
controller can also control heating if there is no heating load. This function is used for reducing cold down
draughts by the windows. The heating control feature will
be enabled to the preset level, for example 20%, until the
cooling load has reached 50%.
Valve exercise (Software later than Version 4)
This function applies only from Program Version 4. During
the summer half of the year, the valves may need to be
exercised so that they will not jam. The exercising feature
can be enabled by setting the time between these occasions to >0. The time is expressed in 24-hour periods
Exercising takes place by enabling the valve output for 10
minutes. The function is enabled as standard.
CAC Use
Activation of the built-in air quality sensor in ADAPT
Damper on the extract air duct.
Ventilation boost function
Enables the function for forcing the airflow for a shorter
time (5 minutes) when the ventilation system has operated in the vacant room mode longer than the preset
time (72 hours).
CAC/CO2-function for vacancy
Provision for enabling the CAC/CO2 function even when
the ventilation system is operating in the room vacancy
mode.
LED function
Here you can choose whether the LED should be out or
used for indicating the functions, see the Alarm Menu.
8
Swegon reserves the right to alter specifications.
20100112
www.swegon.com
TUNE Adapt
Test menu
These menu functions are used for commissioning and
performance checks. When you select the TEST MENU, a
warning is shown to remind you to be especially cautious;
changing any data in these menus could cause the control
system to stop operating.
* SWEGON TUNE ADAPT *
Valve test
If activated the valve opens during 10 minutes. Serves to
check the valve operation and to override the “first-stop”
function of the valve.
LANGUAGE
ADVANCED MENU
TEST MENU
Night cooling
This function is used to test the night cooling function, do
not forget to set USE to “OFF” when the test is completed.
SAVE / LOAD MENU
* TEST MENU *
MAN FLOW OPTION
MAX AIRFLOW
AIRFLOW
MASTER
SLAVE REVERSED
TEST POS%
DAMPER POS MAN
OFF
TUNE Adapt
Morning boost
This function is used to test the morning heat function,
do not forget to set USE to “OFF” when the test is completed.
000l/s
EMERGENCY
CONTROL
Occupancy
The occupancy function can be forced here to AUTO or
MAN. UNOCCUPIED or OCCUPANCY should be set in the
manual mode. If the ADAPT Damper in the master version
lacks a built-in presence detector, this value should be set
to continuous OCCUPANCY if DETECT Occupancy is not
connected.
CLOSE
OFF
OFF
100%
OCCUPANCY
OCC AUTO/MAN
OCC ACTION
AUTO
UNOCC
NIGHTCOOL
AUTO/MAN
Save/Load menu
AUTO
These menu functions are used for transferring data from
one air diffuser to another.
MORNING BOOST
AUTO/MAN
AUTO
* SAVE/LOAD MENU *
Man flow option (Commissioning mode)
This function is used during the commissioning and
performance check phase. All the products are supplied
preset for maximum flow. The LED shines orange. During
the commissioning phase, this mode should be reset to
MIN FLOW – VACANCY FLOW – and DISABLED. The LED
shines orange for minimum and vacancy flows.
Emergency
This menu can be used for testing the emergency function. It is also possible to set whether the event should
be ”Close” or ”Open” as well as reversed function on
the slave air diffusers. Set the Open or Close event in the
master air diffuser. The reversed function for the slave air
diffusers can only be set if TUNE Adapt is connected to
each respective slave air diffuser.
Do not forget to set USE to “OFF” when the test is completed.
Test mode
The damper position can be manually steered with this
function to a fixed value within 0-100%. Do not forget to
reset the test mode to “OFF”.
UPLOAD FROM ADAPT
SAVE TO ADAPT
SAVE TO PC
Upload from ADAPT
Connect the first air diffuser and select UPLOAD FROM
ADAPT.
Save to ADAPT
Connect to the next air diffuser whose variables should
be updated and select SAVE TO ADAPT. Caution; when
saving to a new ADAPT unit data from the previous unit is
carried over. Therefore a new 0-calibration of the pressure
sensor must be performed. Data must only be transfered
between units of the same type and dimensions.
Save to PC
The save to PC function requires special equipment that
can only be handled by Swegon specialists.
When the test mode is enabled, the LED shines orange.
Swegon reserves the right to alter specifications.
20100112
www.swegon.com
9
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement