Overview:

Altronix LPS3C24X220 Linear Power Supply/Charger is specifically designed to provide the power needed by the most demanding security and access control applications. It converts a 220VAC 60Hz input to a 2.5 amp 24VDC continuous power-limited output.

Fig. 1

Specifications:

Input:

• 220VAC 50/60Hz 0.5 amp.

Output:

• 24VDC output.

• 2.5 amp continuous supply current.

• Filtered and electronically regulated output.

• Short circuit and thermal overload protection.

Battery Backup:

• Built-in charger for sealed lead acid or gel type batteries.

• Maximum charge current 500mA.

• Automatic switch over to stand-by battery when

AC fails (zero voltage drop).

• Fused battery protection (circuit breaker available).

• Battery leads included.

Visual Indicators:

• AC/DC power LED indicator.

Enclosure:

• Enclosure dimensions (H x W x D approximate):

15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm).

• Combination knockouts are 1/2” and 3/4”.

• Accommodates up to two (2) 12VDC/12AH batteries.

AC DC

24V Open

ALTRONIX CORP. "LPS3 POWER SUPPLY"

XFMR

Black

Lead

Red

Lead

Input 220VAC

50/60Hz

0.7 amp

Installation Instructions:

The LPS3C24X220 should be installed in accordance with The National Electrical Code and all applicable Local Regulations.

1. Mount LPS3C24X220 in the desired location.

2. Connect AC power to the black and red flying leads of the transformer (Fig. 1).

Use 18 AWG or larger for all power connections (Battery, DC output).

3. Measure output voltage before connecting devices. This helps avoiding potential damage.

Keep power-limited wiring separate from non power-limited wiring (220VAC 50/60Hz Input, Battery Wires).

Minimum 0.25” spacing must be provided.

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment.

There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.

4. Connect devices to be powered to the terminals marked [- DC +] (Fig. 1).

5. Connect battery to the terminals marked [- BAT +] (Fig. 1) as marked on the unit (battery leads included).

Note: When batteries are not used, a loss of AC will result in loss of output voltage.

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level

(see power supply voltage output specifications chart).

Battery Test: Under normal load conditions, check that the battery is fully charged, check specified voltage both at battery terminal and at the board terminals marked - BAT + to ensure that there is no break in the battery connection wires.

Note: Maximum charging current under discharge is 500mA.

Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.

Terminal Identification:

Terminal Legend

AC/AC

- BAT +

- DC +

Function/Description

Low voltage AC input (28VAC 100VA).

Stand-by battery connections.

24VDC @ 2.5 amp continuous output.

LED Diagnostics:

Red (DC)

ON

ON

OFF

OFF

Green (AC) Power Supply Status

ON

OFF

ON

OFF

Normal operating condition.

Loss of AC. Stand-by battery is supplying power.

No DC output.

Loss of AC. Discharged or missing stand-by battery. No DC output.

Enclosure Dimensions (H x W x D approximate):

15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)

1.5”

(38.1mm)

4.615”

(117.22mm)

4.615”

(117.22mm)

1.5”

(38.1mm)

1.75”

(44.45mm)

1.5”

(38.1mm)

1.25”

(31.75mm)

4.5”

(114.3mm)

0.91”

(23.114mm)

1.1”

(27.94mm)

12.23”

(310.64mm)

1.375”

(34.925mm)

1.125”

(28.575mm)

1.1”

(27.94mm)

0.91”

(23.114mm)

4.5”

(114.3mm)

1.25”

(31.75mm)

1.5”

(38.1mm)

2.0”

(50.8mm)

2.0”

(50.8mm)

5.0”

(127.0mm)

1.25”

(31.75mm)

15.5”

(393.7mm)

1.1”

(27.94mm)

0.79”

(20.06mm)

1.5”

(38.1mm)

4.615”

(117.22mm)

4.615”

(117.22mm)

Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.

140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 website: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.

IILPS3C24X220 - Rev. 121703 G15N

1.5”

(38.1mm)

1.75”

(44.45mm)

1.25”

(31.75mm)

5.0”

(127.0mm)

MEMBER

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement