Hochiki CHQ-DIM2(SCI) Instructions

Add to my manuals
4 Pages

advertisement

Hochiki CHQ-DIM2(SCI) Instructions | Manualzz

Hochiki Europe (UK) Ltd

CHQ MODULES INSTALLATION INSTRUCTIONS

Products Covered: CHQ SZM (Single Zone Monitor), CHQ-DIM (Dual Input Monitor), CHQ-

DZM (Dual Zone Module)

Introduction

The CHQ "Smart-Fix" Range of Modules consists of the following models:

CHQ-DIM(SCI)

CHQ-DIM/M(SCI) Dual Input Module

CHQ-DZM(SCI))

CHQ-DZM/DIN(SCI)

CHQ-DIM/DIN(SCI)

CHQ-DRC(SCI)

CHQ-DRC/M(SCI)

CHQ-DRC/DIN(SCI)

CHQ-DSC(SCI)

Dual Relay Controller

CHQ-MRC(SCI)

CHQ-MRC/DIN(SCI)

CHQ-SZM(SCI)

Dual Zone Monitor

Mains Relay Controller

Single Zone Monitor

CHQ-DSC/DIN(SCI) CHQ-SZM/DIN(SCI)

Note: (SCI) indicates Module incorporates a short-circuit isolator. DIN indicates Module housing is designed to fit standard “Top

Hat” DIN Rail.

Components

Standard "Smart-Fix" Modules (including (SCI) versions) are supplied as two individual components (see Fig 1 & 2). DIN versions are supplied as one unit (see Fig 3).

Fig 1 Fig 2

"Smart-Fix" CHQ Module (Back Plate inc PCB Component)

(Note: configuration of Wiring Terminal blocks differs between models)

CHQ-LID Transparent Module Lid

(Supplied with four screws and acrylic retaining washers)

Setting the Loop Address

The analogue address of the Module is set using the first 7 switches of the 8-bit DIL switch, which in the case of the

Standard CHQ is located through the cut-out section on the top of the PCB cover. On the DIN version, this switch is located on the edge of the PCB behind the clear door (see Fig 3).

The switches are numbered 1 to 8 (left to right):

SWITCH UP ON

CHQ MODULE

SWITCH DOWN OFF

SWITCH UP OFF

DIN MODULE

SWITCH DOWN ON

The switches should be set using a small-tipped screwdriver or similar.

Refer to the Address Chart (Fig 9) on page 4 for a quick reference on addresses.

(continued on page 4)

Page 1

Fig 3

DIN Rail Mountable CHQ Module

2-3-0-778/ISS8/DEC11

Hochiki Europe (UK) Ltd

Fig 4

CHQ-DIM - DUAL INPUT MONITOR

This device is a loop-powered module designed to interface to a variety of inputs, such as, door contacts, sprinkler flow/door switches and plant equipment fault contacts, this module is particularly suited to applications where a fast response is required to the input change.

Setting Contact Monitoring

Both volt free input contacts can be configured to be either N/O or N/C, by setting the

2-bit DIL switch

CHQ MODULE

SWITCH 1 UP I/P 1 Normally Closed (N/C)

SWITCH 1 DOWN I/P 1 Normally Open (N/O)

DIN MODULE

SWITCH 2 UP I/P 2 Normally Closed (N/C)

SWITCH 2 DOWN I/P 2 Normally Open (N/O)

SWITCH 1 UP I/P 1 Normally Open (N/O)

SWITCH 1 DOWN I/P 1 Normally Closed (N/C)

SWITCH 2 UP I/P 2 Normally Open (N/O)

SWITCH 2 DOWN I/P 2 Normally Closed (N/C)

LOOP CONNECTIONS: S = Cable Screen (if required), - = Loop Negative (-ve), + = Loop Positive (+ve)

Order codes

Transmission method

CHQ-DIM(SCI) / CHQ-DIM/M(SCI) / CHQ-DIM/DIN(SCI)* 1

Digital communication using ESP

Operating voltage

Quiescent current 280 A

Current consumption whilst polling 22 mA  20 %

Current consumption with inputs active 4.3 mA (Both active)* 2

Weight (g) &

Dimensions (mm)

CHQ-DIM(SCI)

CHQ-DIM/M(SCI)

327

CHQ-DIM/DIN(SCI) 113

17 - 41 VDC

Current in short-circuit

Input line resistance ON threshold <50 , OFF threshold >100 K

L157 x W127 x D35 (CHQ Module plus Lid)

D=79 (CHQ Module plus Lid plus CHQ-BACKBOX)

(add 235 to module weight when using CHQ-BACKBOX)

L108 x W119 x D24 (CHQ DIN Module)

8 mA

Colour and enclosure material

* 1 Fire alarm control panel compatibility required for these products.

CHQ Module & CHQ-BACKBOX White ABS, DIN Module Green ABS

* 2 Note: - Add 85 A per input for normally closed contact monitoring

CHQ-DZM - DUAL ZONE MONITOR

This device is an externally powered module designed to allow up to 60 conventional detectors (30 per zone) to be interfaced to Hochiki’s ESP analogue addressable system. The unit features three End Of Line (EOL) monitoring options

(see page 3 for further details).

Setting EOL Monitoring Option

Select the required EOL monitoring option using the 2-bit DIL switch.

CHQ MODULE

SWITCH 1 DOWN

SWITCH 2 DOWN

ZENER

DIN MODULE

SWITCH 1 UP

SWITCH 2 DOWN

SWITCH 1 UP

SWITCH 2 UP

ACTIVE/RESISTIVE

ZENER

SWITCH 1 DOWN

SWITCH 2 UP

ACTIVE/RESISTIVE

Fig 5

LOOP CONNECTIONS: S = Cable Screen (if required), - = Loop Negative (-ve), + = Loop Positive (+ve)

Order codes CHQ-DZM(SCI) / CHQ-DZM/DIN(SCI) Transmission method Digital communication using ESP

Operating voltage

Low Power Mode (typ)

Quiescent current (typ)

Current in short-circuit

110 A

330 A

Current consumption (external)

8 mA

17 - 41 VDC

Resistance on Zone (max)

Capacitance on Zone (max)

50 Ω

0.3 µF

(Quiescent) 2mA, (Alarm) 70mA (both zones in fire)

Maximum short-circuit current (Loop) 1 A

Output rating

Detectors per zone

Weights (g) &

Dimensions (mm)

24 VDC 8.5 mA

DCA, DFB, DFE – No limit, SLG, SLK, SLR, SIF, SIH, SIJ, DCC, DCD, DFJ – 30 max,

SPB-ET, SPC-ET or SRA-ET– Only one and no other detectors, HF-24 – Only one and no other detectors,

DRD-E – 15 max, Conventional Call Points – No limit

CHQ-DZM(SCI) 350 L=157 x W=127 x D=35 (CHQ Module plus Lid)

D=79 (CHQ Module plus Lid plus CHQ-BACKBOX)

CHQ-DZM/DIN(SCI) 130

(add 235 to module weight when using CHQ-BACKBOX)

Colour and enclosure material CHQ Module & CHQ-BACKBOX White ABS, DIN Module Green ABS

* 1 Fire alarm control panel compatibility required for these options.

Page 2 2-3-0-778/ISS8/DEC11

Hochiki Europe (UK) Ltd

Standard EOL Options for CHQ-DZM

EOL Option Type

OPTION 1

Zener End of line device

(Zone)

OPTION 2

Active End Of Line Module

(Zone)

Active End Of Line in conjunction with

Capacitor (Zone)

Part Description

TE-RH-E

Hochiki Part No 2-1-1-016

(Iz=1-mA, T=30ms, Vz=22.7 to 24.3 V)

L terminal connects to +Zone

C Terminal connects to -Zone

LCMU (6K8)

Hochiki Part No 1270070-00

(SUPPLIED SEPARATELY)

47 µF Capacitor

Hochiki Part No (2-2-7-031)

Active EOL - Line Continuity Monitoring Unit for Schottky bases (See Fig 6)

Pink lead connects to +Zone

Black lead connects to –Zone

47 µF ±20% 35 V

Fitted directly into Zone terminals (see Fig 6)

6K8 resistor (2-2-5-1015) 6K8 ± 5% 0.4 W OPTION 3

Resistive EOL (Zone)

Monitored input EOL 10 KΩ resistor (2-2-5-806) 10 KΩ ± 5% 0.4W

Fig 6

CHQ-SZM SINGLE ZONE MONITOR is a loop-powered module that provides a single fully monitored input for the connection of up to six Hochiki conventional smoke or heat detectors, OR one Hochiki beam detector, or any number of conventional call points, the unit also contains an output for remote fire indication.

Note: The end of line device

(EOL) is supplied with the unit – do NOT discard in error!

The

EOL device MUST be fitted at the last detector on the zone, note the polarity.

Fig 8

Fig 7

Order codes

Transmission method

Loop:-Operating voltage

Quiescent current

Current consumption whilst polling

Current in short-circuit

Maximum short-circuit current (Loop)

E.O.L device

Zone voltage

Zone resistance

Zone capacitance

Detectors per zone

CHQ-SZM(SCI) / CHQ-SZM/M(SCI) / CHQ-SZM/DIN(SCI) *

1

Digital communication using ESP

17 - 41 VDC

260 A

22 mA  20 %

8 mA

1 A

TE-RH-E (polarity conscious)

15.3 V - 17.1 V

50  (Max)

0.3 F (Max)

DCA, DFB, DFE – No limit, SLG, SLK, SLR, SIF, SIH, SIJ, DCC, DCD, DFJ – 6 max

SPB-ET or SRA-ET– Only one and no other detectors, HF-24 – Only one and no other detectors, DRD-E – 3 max, Conventional Call Points – No limit

Weight (g) &

Dimensions (mm)

CHQ-SZM(SCI)

CHQ-SZM/M(SCI)

328

L157 x W127 x D35 (CHQ Module plus Lid)

D79 (CHQ Module plus Lid plus CHQ-BACKBOX)

(add 235 to module weight when using CHQ-BACKBOX)

CHQ-SZM/DIN(SCI) 114

Colour and enclosure material

L108 x W119 x D24 (CHQ DIN Module)

CHQ Module & CHQ-BACKBOX White ABS, DIN Module Green ABS

* Fire alarm control panel compatibility required for these products. See AP0127 for short-circuit isolator specifications.

This module does not support any line continuity options; therefore, if Manual Call Points are to be interfaced then these should be connected first.

Page 3 2-3-0-778/ISS8/DEC11

Hochiki Europe (UK) Ltd

Installation – "Smart-Fix" Version

Set analogue address before installation (see page 1). The fixing surface should be dry and stable.

Hold the back plate up against the fixing surface and mark the

 position of the four corner fixing holes.

Determine which cut-out sections along the top and bottom edges of the module require removing to accommodate the cables being used.

Remove cut-outs by scoring with a sharp knife before breaking

 off with pliers or snips.

Mount the back plate using appropriate fixings (not supplied) for the fixing surface.

Terminate and connect field wiring as per the wiring diagrams on pages 2 & 3 (and the terminal block indications on the product label).

The transparent lid (CHQ-LID) is supplied with four screws and eight retaining washers.

 Push the screws through one of the retaining washers and then through the holes in the lid from front to back, pushing another retaining washer onto the end inside the lid.

Screw the lid onto the back plate; do not over tighten the screws as this could damage the unit.

Note, a white plastic version of the lid is available (sold separately

– CHQ-LID(WHT)).

Installation with Back Box

Fig 9

For CHQ-DIM or CHQ-SZM installations requiring glanded cables, a module back box (CHQ-BACKBOX) is available (sold separately). This is mounted on the fixing surface; the CHQ Module is then fitted to the top of the back box and the CHQ-

LID is added creating a sealed enclosure. For further details refer to the CHQ-BACKBOX Instructions (2-3-0-800). For

CHQ-DZM installations utilising heavy-duty cabling (for example, 1.5mm

2 solid conductor) the use of the SMB-1 Box with the SMB-ADAPTOR plate and CHQ-ADAPTOR is recommended. For further details refer to the SMB-ADAPTOR Instructions

(2-3-0-1502).

Ensure any glands used (not supplied) conform to IP67, if such ingress protection is required.

Installation – DIN Version

Set analogue address before installation (see page 1) and write loop address in space provided on door label.

 DIN modules should be mounted in a suitable enclosure in conjunction with an NS 35 mounting rail with the loop connections at

 the bottom of the unit. Hochiki recommends the SMB-2 and SMB-3 Boxes designed specifically for this purpose.

Terminate and connect field wiring as per the wiring diagrams on pages 2 & 3 (and the terminal block indications on the product label).

Suitable anti-static precautions must be taken when handling these products.

Status LEDs

Refer to the table below for Status LED indications:

CHQ-DIM (all variants) Dual Input Module

CHQ-SZM (all variants)

CHQ-DZM (all variants)

Single Zone Monitor

Dual Zone Monitor

Green LED flashes each time the unit is polled by the fire alarm control panel and is continuously illuminated when either input is active (CHQ-DIM only). Amber LED is continually illuminated when unit detects short-circuit fault.

Protocol specified in

TI/006

CHQ-DIM/DIN(SCI) 0832-CPD-1099

CHQ-SZM/DIN(SCI) 0832-CPD-1095

Hochiki Europe (UK) Ltd

Grosvenor Road, Gillingham Business Park,

Gillingham, Kent, ME8 0SA, England

Telephone: +44(0)1634 260133

Facsimile: +44(0)1634 260132

Email: [email protected]

Web: www.hochikieurope.com

Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice. Although every effort has been made to ensure the accuracy of the information contained within this document it is not warranted or represented by Hochiki Europe (UK)

Ltd. to be a complete and up-to-date description. Please check our web site for the latest version of this document.

Page 4 2-3-0-778/ISS8/DEC11