Hochiki Europe (UK) Ltd
CHQ MODULES INSTALLATION INSTRUCTIONS
Products Covered: CHQ SZM (Single Zone Monitor), CHQ-DIM (Dual Input Monitor), CHQ-
DZM (Dual Zone Module)
Introduction
The CHQ "Smart-Fix" Range of Modules consists of the following models:
CHQ-DIM(SCI)
CHQ-DIM/M(SCI) Dual Input Module
CHQ-DZM(SCI))
CHQ-DZM/DIN(SCI)
CHQ-DIM/DIN(SCI)
CHQ-DRC(SCI)
CHQ-DRC/M(SCI)
CHQ-DRC/DIN(SCI)
CHQ-DSC(SCI)
Dual Relay Controller
CHQ-MRC(SCI)
CHQ-MRC/DIN(SCI)
CHQ-SZM(SCI)
Dual Zone Monitor
Mains Relay Controller
Single Zone Monitor
CHQ-DSC/DIN(SCI) CHQ-SZM/DIN(SCI)
Note: (SCI) indicates Module incorporates a short-circuit isolator. DIN indicates Module housing is designed to fit standard “Top
Hat” DIN Rail.
Components
Standard "Smart-Fix" Modules (including (SCI) versions) are supplied as two individual components (see Fig 1 & 2). DIN versions are supplied as one unit (see Fig 3).
Fig 1 Fig 2
"Smart-Fix" CHQ Module (Back Plate inc PCB Component)
(Note: configuration of Wiring Terminal blocks differs between models)
CHQ-LID Transparent Module Lid
(Supplied with four screws and acrylic retaining washers)
Setting the Loop Address
The analogue address of the Module is set using the first 7 switches of the 8-bit DIL switch, which in the case of the
Standard CHQ is located through the cut-out section on the top of the PCB cover. On the DIN version, this switch is located on the edge of the PCB behind the clear door (see Fig 3).
The switches are numbered 1 to 8 (left to right):
SWITCH UP ON
CHQ MODULE
SWITCH DOWN OFF
SWITCH UP OFF
DIN MODULE
SWITCH DOWN ON
The switches should be set using a small-tipped screwdriver or similar.
Refer to the Address Chart (Fig 9) on page 4 for a quick reference on addresses.
(continued on page 4)
Page 1
Fig 3
DIN Rail Mountable CHQ Module
2-3-0-778/ISS8/DEC11
Hochiki Europe (UK) Ltd
Fig 4
CHQ-DIM - DUAL INPUT MONITOR
This device is a loop-powered module designed to interface to a variety of inputs, such as, door contacts, sprinkler flow/door switches and plant equipment fault contacts, this module is particularly suited to applications where a fast response is required to the input change.
Setting Contact Monitoring
Both volt free input contacts can be configured to be either N/O or N/C, by setting the
2-bit DIL switch
CHQ MODULE
SWITCH 1 UP I/P 1 Normally Closed (N/C)
SWITCH 1 DOWN I/P 1 Normally Open (N/O)
DIN MODULE
SWITCH 2 UP I/P 2 Normally Closed (N/C)
SWITCH 2 DOWN I/P 2 Normally Open (N/O)
SWITCH 1 UP I/P 1 Normally Open (N/O)
SWITCH 1 DOWN I/P 1 Normally Closed (N/C)
SWITCH 2 UP I/P 2 Normally Open (N/O)
SWITCH 2 DOWN I/P 2 Normally Closed (N/C)
LOOP CONNECTIONS: S = Cable Screen (if required), - = Loop Negative (-ve), + = Loop Positive (+ve)
Order codes
Transmission method
CHQ-DIM(SCI) / CHQ-DIM/M(SCI) / CHQ-DIM/DIN(SCI)* 1
Digital communication using ESP
Operating voltage
Quiescent current 280 A
Current consumption whilst polling 22 mA 20 %
Current consumption with inputs active 4.3 mA (Both active)* 2
Weight (g) &
Dimensions (mm)
CHQ-DIM(SCI)
CHQ-DIM/M(SCI)
327
CHQ-DIM/DIN(SCI) 113
17 - 41 VDC
Current in short-circuit
Input line resistance ON threshold <50 , OFF threshold >100 K
L157 x W127 x D35 (CHQ Module plus Lid)
D=79 (CHQ Module plus Lid plus CHQ-BACKBOX)
(add 235 to module weight when using CHQ-BACKBOX)
L108 x W119 x D24 (CHQ DIN Module)
8 mA
Colour and enclosure material
* 1 Fire alarm control panel compatibility required for these products.
CHQ Module & CHQ-BACKBOX White ABS, DIN Module Green ABS
* 2 Note: - Add 85 A per input for normally closed contact monitoring
CHQ-DZM - DUAL ZONE MONITOR
This device is an externally powered module designed to allow up to 60 conventional detectors (30 per zone) to be interfaced to Hochiki’s ESP analogue addressable system. The unit features three End Of Line (EOL) monitoring options
(see page 3 for further details).
Setting EOL Monitoring Option
Select the required EOL monitoring option using the 2-bit DIL switch.
CHQ MODULE
SWITCH 1 DOWN
SWITCH 2 DOWN
ZENER
DIN MODULE
SWITCH 1 UP
SWITCH 2 DOWN
SWITCH 1 UP
SWITCH 2 UP
ACTIVE/RESISTIVE
ZENER
SWITCH 1 DOWN
SWITCH 2 UP
ACTIVE/RESISTIVE
Fig 5
LOOP CONNECTIONS: S = Cable Screen (if required), - = Loop Negative (-ve), + = Loop Positive (+ve)
Order codes CHQ-DZM(SCI) / CHQ-DZM/DIN(SCI) Transmission method Digital communication using ESP
Operating voltage
Low Power Mode (typ)
Quiescent current (typ)
Current in short-circuit
110 A
330 A
Current consumption (external)
8 mA
17 - 41 VDC
Resistance on Zone (max)
Capacitance on Zone (max)
50 Ω
0.3 µF
(Quiescent) 2mA, (Alarm) 70mA (both zones in fire)
Maximum short-circuit current (Loop) 1 A
Output rating
Detectors per zone
Weights (g) &
Dimensions (mm)
24 VDC 8.5 mA
DCA, DFB, DFE – No limit, SLG, SLK, SLR, SIF, SIH, SIJ, DCC, DCD, DFJ – 30 max,
SPB-ET, SPC-ET or SRA-ET– Only one and no other detectors, HF-24 – Only one and no other detectors,
DRD-E – 15 max, Conventional Call Points – No limit
CHQ-DZM(SCI) 350 L=157 x W=127 x D=35 (CHQ Module plus Lid)
D=79 (CHQ Module plus Lid plus CHQ-BACKBOX)
CHQ-DZM/DIN(SCI) 130
(add 235 to module weight when using CHQ-BACKBOX)
Colour and enclosure material CHQ Module & CHQ-BACKBOX White ABS, DIN Module Green ABS
* 1 Fire alarm control panel compatibility required for these options.
Page 2 2-3-0-778/ISS8/DEC11
Hochiki Europe (UK) Ltd
Standard EOL Options for CHQ-DZM
EOL Option Type
OPTION 1
Zener End of line device
(Zone)
OPTION 2
Active End Of Line Module
(Zone)
Active End Of Line in conjunction with
Capacitor (Zone)
Part Description
TE-RH-E
Hochiki Part No 2-1-1-016
(Iz=1-mA, T=30ms, Vz=22.7 to 24.3 V)
L terminal connects to +Zone
C Terminal connects to -Zone
LCMU (6K8)
Hochiki Part No 1270070-00
(SUPPLIED SEPARATELY)
47 µF Capacitor
Hochiki Part No (2-2-7-031)
Active EOL - Line Continuity Monitoring Unit for Schottky bases (See Fig 6)
Pink lead connects to +Zone
Black lead connects to –Zone
47 µF ±20% 35 V
Fitted directly into Zone terminals (see Fig 6)
6K8 resistor (2-2-5-1015) 6K8 ± 5% 0.4 W OPTION 3
Resistive EOL (Zone)
Monitored input EOL 10 KΩ resistor (2-2-5-806) 10 KΩ ± 5% 0.4W
Fig 6
CHQ-SZM SINGLE ZONE MONITOR is a loop-powered module that provides a single fully monitored input for the connection of up to six Hochiki conventional smoke or heat detectors, OR one Hochiki beam detector, or any number of conventional call points, the unit also contains an output for remote fire indication.
Note: The end of line device
(EOL) is supplied with the unit – do NOT discard in error!
The
EOL device MUST be fitted at the last detector on the zone, note the polarity.
Fig 8
Fig 7
Order codes
Transmission method
Loop:-Operating voltage
Quiescent current
Current consumption whilst polling
Current in short-circuit
Maximum short-circuit current (Loop)
E.O.L device
Zone voltage
Zone resistance
Zone capacitance
Detectors per zone
CHQ-SZM(SCI) / CHQ-SZM/M(SCI) / CHQ-SZM/DIN(SCI) *
1
Digital communication using ESP
17 - 41 VDC
260 A
22 mA 20 %
8 mA
1 A
TE-RH-E (polarity conscious)
15.3 V - 17.1 V
50 (Max)
0.3 F (Max)
DCA, DFB, DFE – No limit, SLG, SLK, SLR, SIF, SIH, SIJ, DCC, DCD, DFJ – 6 max
SPB-ET or SRA-ET– Only one and no other detectors, HF-24 – Only one and no other detectors, DRD-E – 3 max, Conventional Call Points – No limit
Weight (g) &
Dimensions (mm)
CHQ-SZM(SCI)
CHQ-SZM/M(SCI)
328
L157 x W127 x D35 (CHQ Module plus Lid)
D79 (CHQ Module plus Lid plus CHQ-BACKBOX)
(add 235 to module weight when using CHQ-BACKBOX)
CHQ-SZM/DIN(SCI) 114
Colour and enclosure material
L108 x W119 x D24 (CHQ DIN Module)
CHQ Module & CHQ-BACKBOX White ABS, DIN Module Green ABS
* Fire alarm control panel compatibility required for these products. See AP0127 for short-circuit isolator specifications.
This module does not support any line continuity options; therefore, if Manual Call Points are to be interfaced then these should be connected first.
Page 3 2-3-0-778/ISS8/DEC11
Hochiki Europe (UK) Ltd
Installation – "Smart-Fix" Version
Set analogue address before installation (see page 1). The fixing surface should be dry and stable.
Hold the back plate up against the fixing surface and mark the
position of the four corner fixing holes.
Determine which cut-out sections along the top and bottom edges of the module require removing to accommodate the cables being used.
Remove cut-outs by scoring with a sharp knife before breaking
off with pliers or snips.
Mount the back plate using appropriate fixings (not supplied) for the fixing surface.
Terminate and connect field wiring as per the wiring diagrams on pages 2 & 3 (and the terminal block indications on the product label).
The transparent lid (CHQ-LID) is supplied with four screws and eight retaining washers.
Push the screws through one of the retaining washers and then through the holes in the lid from front to back, pushing another retaining washer onto the end inside the lid.
Screw the lid onto the back plate; do not over tighten the screws as this could damage the unit.
Note, a white plastic version of the lid is available (sold separately
– CHQ-LID(WHT)).
Installation with Back Box
Fig 9
For CHQ-DIM or CHQ-SZM installations requiring glanded cables, a module back box (CHQ-BACKBOX) is available (sold separately). This is mounted on the fixing surface; the CHQ Module is then fitted to the top of the back box and the CHQ-
LID is added creating a sealed enclosure. For further details refer to the CHQ-BACKBOX Instructions (2-3-0-800). For
CHQ-DZM installations utilising heavy-duty cabling (for example, 1.5mm
2 solid conductor) the use of the SMB-1 Box with the SMB-ADAPTOR plate and CHQ-ADAPTOR is recommended. For further details refer to the SMB-ADAPTOR Instructions
(2-3-0-1502).
Ensure any glands used (not supplied) conform to IP67, if such ingress protection is required.
Installation – DIN Version
Set analogue address before installation (see page 1) and write loop address in space provided on door label.
DIN modules should be mounted in a suitable enclosure in conjunction with an NS 35 mounting rail with the loop connections at
the bottom of the unit. Hochiki recommends the SMB-2 and SMB-3 Boxes designed specifically for this purpose.
Terminate and connect field wiring as per the wiring diagrams on pages 2 & 3 (and the terminal block indications on the product label).
Suitable anti-static precautions must be taken when handling these products.
Status LEDs
Refer to the table below for Status LED indications:
CHQ-DIM (all variants) Dual Input Module
CHQ-SZM (all variants)
CHQ-DZM (all variants)
Single Zone Monitor
Dual Zone Monitor
Green LED flashes each time the unit is polled by the fire alarm control panel and is continuously illuminated when either input is active (CHQ-DIM only). Amber LED is continually illuminated when unit detects short-circuit fault.
Protocol specified in
TI/006
CHQ-DIM/DIN(SCI) 0832-CPD-1099
CHQ-SZM/DIN(SCI) 0832-CPD-1095
Hochiki Europe (UK) Ltd
Grosvenor Road, Gillingham Business Park,
Gillingham, Kent, ME8 0SA, England
Telephone: +44(0)1634 260133
Facsimile: +44(0)1634 260132
Email: [email protected]
Web: www.hochikieurope.com
Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice. Although every effort has been made to ensure the accuracy of the information contained within this document it is not warranted or represented by Hochiki Europe (UK)
Ltd. to be a complete and up-to-date description. Please check our web site for the latest version of this document.
Page 4 2-3-0-778/ISS8/DEC11