November 30, 2009
Boiler Outdoor Reset and its Effect on Condensing Boiler
Efficiencies (Part 3) By Brad Notter with edit by Norm Hall
Let’s continue to examine the reset example we started last week. Using the
reset schedule below as our example, we know our supply water temperature
will be 120° at an outdoor temperature of 40° and the return water would be at
110°or even lower.
As the boiler return water is lowered below 140 degrees, condensing starts to
occur and in a condensing boiler, the efficiency is increased.
This increase in efficiency is due to the capture of the latent (hidden heat) of the
flue gas turning into condensate. For every pound of condensate made by the
boiler, 970 BTUs are recovered. In our example above of 110 degree return
water, the efficiency of the boiler operating at 100% input is increased from 86%
to 89%. For a 2 million BTU boiler operating at 100 percent input, the 3%
increase is equal to 60,000 BTU from 7.75 gallons of condensate.
If we couple the higher efficiency due to temperature with the higher efficiency
due to turndown (see Oct 26th & Nov 2nd MMM), we have the increased
efficiency of the AERCO boiler.
As the boiler modulates to a lower input firing rate, the efficiency is increased
due to the fact the heat transfer surface of the boiler does not change and that
surface can capture more of the heat from the burner. If the boiler is operating at
5% input, the efficiency is increased from 86.5% to 92.5%.
(continue on page 2)
Disclaimer: R. L. Deppmann and it’s affiliates can not be held liable for issues caused by use of the information on this page. While the information comes from many
years of experience and can be a valuable tool, it may not take into account special circumstances in your system and we therefore can not take responsibility for actions
that result from this information. Please feel free to contact us if you do have any questions.
20929 Bridge Street, Southfield, MI 48033
4121 Brockton Drive SE, Grand Rapids, MI 49512
6200 Baron Drive, Bridgeport, MI 48722
6910 Treeline Drive, Suite A, Brecksville, OH 44141
Serving the industry since 1927
Phone: (800) 589-6120 - Fax: (248) 354-3710
www.deppmann.com
Matching the heat generated by a heating plant to the heat lost by the building is
now a reality, not just something we have to dream about anymore. By
implementing AERCO condensing modulating boilers the high turndown ratio
and the full capability of outdoor reset the will definitely save you or your
customer some green and is “green” at the same time.
Thank you for using products sold by
R. L. Deppmann Company in Michigan and Ohio!
.
Disclaimer: R. L. Deppmann and it’s affiliates can not be held liable for issues caused by use of the information on this page. While the information comes from many
years of experience and can be a valuable tool, it may not take into account special circumstances in your system and we therefore can not take responsibility for actions