ME-AGS-WB* wiring diagram –
For Westerbeke (8.0- 15.0 BEG Gas Generators)
Input DC Voltage
jumper - set to
monitored battery
bank voltage
(on 24V setting)
Dip-switch
configuration
(5-Wire Mode*)
ON
These 5 adjustments
are not active when a
ME-RC Remote
Control with revision
1.5 or higher is used.
They are set using
displays under the
AGS button on the
remote control.
12/24/48V
4.0
1 2 3 4
* ME-AGS-WB with revision
5 amp
fuse
TB1
ON Switch
(N.C.)
1
5
amp
fuse
2
85
Battery
Bank
(monitored
for gen
turn on)
30
4
Start Switch
(N.O.)
5
86
87
87A
Stop Switch
(N.O.)
TB2
3
Gen Run Signal
(input to pin 2 must
be 10 to 40 DC volts
only while generator
is running);
can be the generator
hour-meter or a
12vdc pilot/run light
85
30
0123
5
Gen
Hour Meter
86
87
87A
Westerbeke BEG
Generator
Relays used are SPDT 30 Amp, 12 VDC coil relays
[shown in the non-energized (N.C.) position]
ME-AGS-WB Relay Timing Information
GEN AND POWER I/O
Relay 1
(terminals 5 & 6)
Relay 3
(terminals 1 & 8)
Stop
Start
Delay
Delay
Relay 2
(terminals 6 & 7)
Start
RUN TIME
HOURS
Stop
ON
Stop Time
10 Sec.
Start Delay Time
14 Sec.
Start Time
10 Sec.
Preheat Delay Time
4 Sec.
ON Time
25 Sec.
Next Retry Time
2 Min.
Total Start Attempts
4
Magnum Energy, Inc. provides this diagram to assist in the installation of the Auto-Generator Start controller.
Since the use of this diagram and the conditions or methods of installation, operation and use are beyond the
control of Magnum Energy, Inc., we do not assume responsibility and expressly disclaim liability for loss,
damage or expense arising out of the installation, operation and use of this unit.
3-3-2008