Contents
Air Handling Units
300-700 m3/h
The units are available with rotating recovery
systems or with cross heat exchangers. There is
a choice between electric and water batteries.
This series consists of ventilation units with heat
recovery from 300 to 700 m3/h. The units are
supplied with bosses on the top or on the sides.
Flexit L60
Flexit L50
Flexit L40
Flexit S30
Flexit L30
Flexit S20
The chart shows
an overview of
the units’ working
ranges.
Flexit L20
Flexit L18
For the units that
are not highlighted,
please see the
“Flexit Air Handling
Units (700-5000
m3/h)” brochure.
Flexit L14
Flexit L12
Flexit S12
Flexit L7
Flexit S7
Flexit L4
Flexit S4
Flexit SL4
2000
l/s
m3/h
5000
3500
3000
2500
1000
500
2000
1500
300
1000
200
700
100
400
300
50
200
30
20
100
10
Flexit S3
General Technical Information. . . . . . . . 4
Flexit S3 RK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
General Product Description. . . . . . . . . . 10
Flexit S4 R. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Flexit L4 XW/E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Flexit SL4 R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Flexit L7 XW/E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Flexit S7 RW/E.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Flexit S3 R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3
General Technical Information
Versions
Flexit air handling units are available in the
following versions:
- horizontal unit (L). Fitted with connection
nipples at the end for installation in technical
rooms, for example.
- cabinet unit (S). Fitted with connection nipples
on the top for installation in small technical
rooms, for example.
The units meet the requirements in EU Directives
89/336/EEC and 73/23/EEC.
contamination in the extract air will always be
transferred so that it is necessary to be selective
when using this recovery technology.
The temperature efficiency is approximately
75-85%.
Outdoor air
Sealing strip
Supply air
Exhaust air
Extract air
Cleaning sector
2. Cross Exchanger
(Recuperative)
Unit type L
Unit type S
Recovery Systems
Flexit uses two different recovery technologies:
1. Rotor
2. Cross exchanger
1. Rotor (Regenerative)
Flexit uses a non-hygroscopic rotor. i.e. the rotor
does not actively emit moisture into the supply
air. This form of recovery takes place as follows:
The rotor is a wheel that has a mass of aluminium
with many ducts. This wheel rotates so that
the mass absorbs heat from the extract air and
transfers the heat to the supply air. The rotor is
driven by a belt and a motor.
Unlike the cross exchanger, the rotor technology
has no practical problem with condensation and
icing up. Therefore drainage is not required.
The internal pressure ratio in the unit is designed
so that transfer of contaminants from the extract
air to the supply air is minimal. The rotor has a
cleaning sector that functions in such a way that
the rotor mass is “cleaned” with fresh air before
it supplies its heat to the supply air. Some of the
4
The cross exchanger is a cassette that consists
of a row of aluminium plates. Recovery takes
place as follows:
The extract air and supply air exchange heat
on separate sides of the aluminium plates. The
hot extract air heats the aluminium and the
cold outdoor air then absorbs the heat. As the
air flows pass on separate sides of the plates,
the extract air and the supply air will never
be in contact with each other. On account
its properties, this form of recovery involves
minimal transfer of contaminants, which, in turn,
means that it can be used in a wide range of
applications.
Using a cross exchanger, moisture may
be condensed out of the extract air. This
condensation must be drained away.
The temperature efficiency is approximately
60-70%.
Extract air
Outdoor air
Supply air
Exhaust air
Cross exchanger
General Technical Information
Risk of Frost Using a Cross
Exchanger
When condensation is precipitated out of the
extract air at low outdoor temperatures, the
condensed water will begin to freeze in the
exchanger and after a while the exchanger will
ice up. To prevent the exchanger from icing
up, Flexit has solved this problem with the
development of the patented thermoguard
and can guarantee operation under all climatic
conditions including severe cold.
Instructions
All systems are supplied with detailed
instructions covering installation, use and
maintenance.
94108N-03
2004-02
FLEXIT S3 X/TT - A3 X/TT
S4 X/TT - A4 X/TT
S7 X/TT - A7 X/TT
Brukerveiledning
Luftbehandlingsaggregat
Skapmodeller med varmegjenvinning
Properties and Function of
the Thermoguard
=c\o`kJ*O&KK$8*O&KK
J+O&KK$8+O&KK
J.O&KK$8.O&KK
Ta vare på denne veiledningen for fremtidig bruk
9ilb\im\`c\[e`e^
DXij¡'+
=fidXk1
8[fY\8ZifYXk
=c\o`k8J#K\c\m\`\e(,#(/.'¥ia\
Kc]%-0/(''''nnn%]c\o`k%ef
The thermoguard is placed inside the cross
exchanger at the coldest point and monitors
both temperature and humidity.
There is a risk of frost when:
1. Both humidity and cold are present
2. The outdoor temperature conditions mean that
there is a risk of dry ice in the exchanger cassette.
Calculation Program
A program for air handling unit calculations with
technical data such as sound, air, power, SFP, etc.
Version 2003.12
Page 1
25.02.2004
Project data
Deicing can be guaranteed by using a preheater.
During deicing, the automatic control will reduce
the air flow rate if the preheater is not able to
maintain the temperature in the cassette.
Compared with traditional frost monitoring
systems (which switch off the supply air fan at +1°,
regardless of whether humidity is present or not),
Flexit’s solution saves a lot of energy as the unit is
not operated unnecessarily in bypass mode.
Project
Customer
Designed by
Information
Location
katalog
Flexit
Marianne
Assumptions
Version 2003.12
Atmospheric pressure
Air density
Sound duct in accordance with ISO 5136
Ambient sound in accordance with ISO 9614-2
101325
1.200
Pa
kg/m³
Type of unit
Description
Flexit S 30 X E L 230
Summer
Winter
Input
Supply air flow
Relative humidity of outdoor air
Total pressure drop of supply duct
500.0
50
250
l/s
%
Pa
500.0
10
250
l/s
%
Pa
Extract air flow
Relative humidity of extract air
Total pressure drop of extract duct
500.0
50
250
l/s
%
Pa
500.0
20
250
l/s
%
Pa
Dimensioning outdoor temperature
Extract temperature
25.0
22.0
°C
°C
-25.0
22.0
°C
°C
300
kg
Technical specification
Supply
Fans
Winter
Adjustment
Power
Current
Power factor
SFP
Temperature increase because of fan
RPM
Summer
Adjustment
Power
Current
Power factor
SFP
Temperature increase because of fan
RPM
Heat recovery
Type
Winter
Temperature before
Relative humidity before
Temperature after
Relative humidity after
Pressure drop
Temperature efficiency
Humidity efficiency
Summer
Temperature before
Relative humidity before
Temperature after
Relative humidity after
Pressure drop
Temperature efficiency
Humidity efficiency
Filter
Filter class
Flexit AS
Televeien 15
1870 Ørje
Norway
Electrical afterheater
Max. effect
Winter
Effect
Temperature before
Temperature after
Summer
Effect
Temperature before
Temperature after
15.00
0.00
0.0
0.0
0.00
0.0
0.0
Sound data, supply
Weight
+47 69 81 00 00
+47 69 81 00 80
kW
kW
°C
°C
kW
°C
°C
2k
0
0
4k
0
0
8k
0
0
Total
dB 0
dB(A)
dB 0
dB(A)
Frequency band
Extract duct, winter
Extract duct, summer
Hz
63
0
0
125 250 500 1k
0
0
0
0
0
0
0
0
2k
0
0
4k
0
0
8k
0
0
Total
dB 0
dB(A)
dB 0
dB(A)
Frequency band
Ambient, winter
Ambient, summer
Hz
63
0
0
125 250 500 1k
0
0
0
0
0
0
0
0
2k
0
0
4k
0
0
8k
0
0
Total
dB 0
dB(A)
dB 0
dB(A)
%
W
A
Sound data, ambient
kW/(m³/s)
°C
1/min
LCC Calculation
0
0
0.00
0.00
0.00
0.0
0
%
W
A
0
0
0.00
0.00
kW/(m³/s) 0.00
°C
0.0
1/min
0
%
W
A
0.0
0
0.0
0
0
0
0
°C
%
°C
%
Pa
%
%
0.0
0
0.0
0
0
0
0
°C
%
°C
%
Pa
%
%
0
0
0.0
0
0
0
0
°C
%
°C
%
Pa
%
%
0
0
0.0
0
0
0
0
°C
%
°C
%
Pa
%
%
EU7
Pa
Pa
Pa
125 250 500 1k
0
0
0
0
0
0
0
0
0
0
0.00
0.00
kW/(m³/s) 0.00
°C
0.0
1/min
0
www.flexit.no
kundeservice@flexit.no
Pa
Pa
Pa
0
0
0
63
0
0
%
W
A
kW/(m³/s)
°C
1/min
0
0
0
Pa
Pa
Pa
Hz
Sound data, extract
Extract
Pa
Pa
Pa
Frequency band
Supply duct, winter
Supply duct, summer
0
0
0.00
0.00
0.00
0.0
0
EU7
Telephone :
Telefax :
Page 2
25.02.2004
All calculations are done with 20% addition at pressure drop across filters.
Winter
Dimension pressure drop
0
Start pressure drop
0
End pressure drop
0
Summer
Dimension pressure drop
0
Start pressure drop
0
End pressure drop
0
Unit specification
Supply air flow
Extract air flow
Supply air temperature
Extract air temperature
Annual average temperature
Correct coefficient VAV, supply air
Correct coefficient VAV, extract air
Annual operating time
0.0
0.0
20.0
22.0
0.0
0.01
0.01
4000
l/s
l/s
°C
°C
°C
Price of energy
Electric
Heating
0.000
0.000
NOK/kWh
NOK/kWh
Annual price increase
Electric
Heating
Accounting rate of interest
Operating time
3
3
3
10
%
%
%
years
Degree hours
Degree hour for heat recovery
Correction for supply temperature
Correction due to freezing
Degree hours, total
0
0
0
0
°Ch
°Ch
°Ch
°Ch
LCC results
kWh
0
0
0
LCC supply air
LCC exhaust air
LCC heating
h
NOK/kWh
0.000
0.000
0.000
LCC total
Flexit AS
Televeien 15
1870 Ørje
Norway
NOK
0
0
0
0
Telephone :
Telefax :
+47 69 81 00 00
+47 69 81 00 80
www.flexit.no
kundeservice@flexit.no
Environmental Class
Extract air
Outdoor air
Temperature
sensor
The units’ chassis are produced in surfacetreated sheet steel which meets environmental
class M2, which covers indoor installation with
normal humidity impact and normal content of
air pollution.
EE Regulation
Cross exchanger
Supply air
Exhaust air
Thermoguard
Cross exchanger with thermoguard
Electrical products come under the regulation
relating to scrapped electrical and electronic
products and are, in this connection, subject to
an environmental tax. In connection with future
disposal, they can be delivered free of charge
for recycling to the nearest dealer or collection
location.
5
General Technical Information
Using a Capacity Diagram
the fan at each operating level in Watt. The power
consumption can be read off the scale to the right
of the diagram.
A diagram consists of a number of curves and
axes which allow various types of data to be read
off for the unit.
4. Sound curves (red)
These curves indicate values for the sound power
level LwA of the duct at the various operating
levels. To find the sound power level of the duct in
the various octave bands, take the value read off
in the diagram and correct it using the values in
the table below the diagram for each octave. This
produces the sound power level per octave.
1. Capacity curves (blue)
These curves indicate the total available pressure
and the air volume characteristic for the unit.
The available pressure is read off to the left of the
diagram.
The air volume is read off in m3/h at the bottom of
the diagram and in l/s at the top of the diagram.
The various curves indicate different settings on
the transformer.
5. Correction axis
Here you can read off the change in pressure when
a water battery is used for heating. This pressure
drop is deducted from the available pressure.
2. Operation curves (black)
These curves show how air flow rate and
pressure change at different operating levels.
On the same axis, you can read off the change in
pressure when an EU-5 filter is used. This pressure
increase is added to the available pressure.
3. Power consumption curves (green)
These curves indicate energy consumption for
Supply air side
Air flow rate, l/s
20
40
60
80
100
400
1
120
200
3
2
Contact resistance, Pa
300
150
77dB(A)
230V
4
200
190V
170V
150V
120V
105V
85V
60V
100
90
230V
190V
170V
150V
60V
85V
105V
120V
50
75dB(A)
70dB(A)
65dB(A)
Pa 0
0 W
5
m3/h 0
Pa
100
0
100
200
10
25
Power consumption, Watt
l/s 0
260 300
35
400
500
50
65
Correction factor for Lw
Hz
Supply air
Extract air
Radiated
6
63
5
18
-39
125
3
11
-29
250
0
-3
-28
500
-1
-1
-31
1000
-6
-16
-36
2000
-8
-20
-37
4000
-17
-27
-43
8000
-31
-40
-53
Total LwA
-29,1
General Technical Information
Example:
An air handling unit installed in a standard
ventilation room.
Air flow rate
260m3/h
Total pressure
100Pa
Sound power level in supply air duct
72dBA
Motor power
90W
Example of sound calculation using the correction table
Supply air
Hz
Read off in diagram, LwA
Correction factor
Sound power level, Lw
63
72
5
77
125
72
3
75
250
72
0
72
Data for supply air is measured in accordance
with ISO 5136, the “In-duct method”.
500
72
-1
71
1000
72
-6
66
2000
72
-8
64
4000
72
- 17
55
8000
72
- 31
41
Radiated noise is measured in accordance with
ISO 9614-2.
Bruel & Kjær measuring equipment, type 2260.
l/s 0
20
40
100
80
60
120
400
Example of a correction axis for an F5 filter:
Calculation example for F5 filter, air flow rate
260m3/h against 100Paj .
Correction for F5 filter + 30Pa, read off the
correction axis. 260m3/h is available against
130Pa. To read off the new sound power level
and motor power, move the read-off point
down 30Pa to k to compensate for reduced
resistance. The motor power is reduced from
90W to approximately 85W, and the sound is
reduced from 72dBA to 70dBA.
200
Air flow rate
260m3/h
Total pressure
130Pa
Sound power level in supply air duct
70dBA
300
Motor power
150
85W
77dB(A)
230V
100
200
190V
170V
150V
120V
105V
85V
60V
100
60V
85V
105V
120V
200
100
Pa
l/s 00
20 10
0 W
260 300
2560
40
50
70dB(A)
65dB(A)
Pa 0
m3/h 0
230V
190V 1
170V
150V
2
75dB(A)
400
35
80
100 50 120
1 - 2 = 30
500
65
400
Example of a correction axis for a water battery:
Calculation example for water battery, air flow
rate 260m3/h against 100Paj.
Correction for water battery -60Pa, read off the
correction axis. 260m3/h is available against
40Pa. To read off the new sound power level and
motor power, move the read-off point up 60Pa
to k to compensate for increased resistance.
The motor power is increased from 90W to
approximately 100W, and the sound is increased
from 72dBA to 74dBA.
200
Air flow rate
260m /h
Total pressure
40Pa
3
300
Sound power level in supply air duct
Motor power
150
74dBA
100W
77dB(A)
230V
100
200
190V
170V
150V
120V
105V
85V
60V
100
2
230V
190V
170V
150V
60V
85V
105V
120V
Pa
0
75dB(A)
1
70dB(A)
65dB(A)
Pa 0
m3/h 0
50
100
200
10
25
260 300
35
0 W
400
50
1 - 2 = -60
500
65
7
General Technical Information
Determination of Sound Pressure (LpA) from the Ventilation
Unit on the Basis of Sound Power (LwA)
10
5
1
dB
0
Diagram 1
2
-5
3
-9
-10
-15
-20
50
100
160 200
400
800
1600
romvolum (m3)
Explanation of curves
Curve 1. Technical rooms without special
silencing. Typically boiler rooms or refrigerating
machine rooms with good space and hard wall
and ceiling surfaces.
Curve 2. Typically technical rooms where the
technical installations take up a lot of space.
Partially insulated ducts/pipes or silenced
surfaces.
Curve 3. Very well silenced rooms. A lot of
installations (not much space), insulated ducts/
pipes.
The curves apply to a minimum distance of
1.5-2.0 m. The diagram is based on a diffuse
sound field. In silenced rooms (curves 2 and 3),
the sound field is not diffuse. We therefore get
distance silencing. Table 1 is used to correct for
distance. Table 2 corrects for the location of the
unit.
8
Table 1 Correction for distance
Distance, m
2-3
Distance silencing
4
5
6
8
10 12 15 20
0 -1 -2 -3 -4 -5 -6 -7 -8
Table 2 Correction for location
Location:
- in the middle of the floor 0dB
- along a wall
+3dB
- in a corner
+6dB
General Technical Information
Example:
Air flow rate
260m3/h
An air handling unit type Flexit S4 X, installed in a
standard ventilation room.
Total pressure
100Pa
Motor power
Sound power level in supply air duct 72dBA
90W
The ventilation room is 8 x 5 x 4 = 160m3.
The unit is located along one long wall. The
reference distance is 1m.
This is a technical room without special silencing
and therefore we use curve 1.
If we look, in diagram 1, at the room volume,
160m3, vertically up to curve 1, and from there to
the left axis, we can read –5dB.
The calculation is shown below:
Sound power level (LwA), from the capacity diagram for supply air
72dB
Correction for radiated sound (LwA) from the correction factor table-29,1dB
Correction for room silencing from diagram 1
-5dB
Correction for distance, table 1
0dB
Correction for location, table 2
+3dB
Sound pressure level at a 1 m distance (LpA)
40,9dBA
PS: The calculation method is based on dBA
values. You can also use it for octave bands.
The method would then produce 1-2 dB for low
values in the range 63-125 Hz and 1-2 dB for
high values in the range 2000-8000 H.
Explanation of name codes:
S
3
X
E
L
230
EC
= Fan type
= Rated voltage
230V/400V
L = Left model
S = Cabinet model/Vertical
R = Right model
L = Loft model/Horizontal E = Electrically based heating
W = Water-based heating
No. =Size
– = No heating
X = Cross heat exchanger
R = Rotating exchanger
Explanation of symbols used:
SUPPLY
AIR
EXTRACT
AIR
EXHAUST
AIR
OUTDOOR
AIR
9
General Product Description
Product Description
Flexit air handling units are designed to provide
optimal air comfort combined with low energy
consumption. The heated, used indoor air is
extracted via extraction valves from the rooms,
passes through a filter and is introduced into
the unit’s cross heat exchanger before being
conducted out of the building via a roof hat or
wall outlet.
Outdoor air is introduced via an outdoor air
intake to the unit, is filtered, passes through the
cross heat exchanger and absorbs a large part
of the heat from the extract air.
The extract air and supply air pass each other in
the exchanger cassette in completely separate
ducts without the clean air being “infected” by
the used, contaminated air. The thermostatcontrolled heating battery ensures a draughtfree supply air temperature. After the unit, the
supply air normally passes through silencers
before flowing in through the supply air valves,
fresh, clean and tempered.
Flexit air handling units are fitted with
electronic automatic control.
Area of Use, Horizontal Units
Flexit horizontal (L) air handling units are
suitable for homes for installation in the loft.
These aggregates are only supplied with cross
exchangers.
both sides. This makes it easy to position the
units in relation to duct connections (right and
left model in one). Small building dimensions
have been the aim.
Area of Use, Cabinet Units
The Flexit vertical (S) cabinet version can be
used to advantage for schools, nursery schools,
offices, shops, homes, etc. The cabinet and the
compact design mean that the units can be
used in both new and existing buildings. These
units are supplied with both cross exchangers
and rotating exchangers.
Design (S)
The units are produced in sheet steel, which
results in a robust, stable construction. The
walls are made of double-cased galvanised
sheet steel with thermal and acoustic
insulation. The connection bosses are on the
top. Externally, the units are lacquered white.
All joints are sealed to eliminate the risk of air
leakages. The units are fitted with two hinged
doors in the front which allow easy access for
inspection/service.
Heat Recovery Principle
Cross Exchanger
Design (L)
Flexit air handling units are produced in strong,
galvanised sheet steel, which produces a stable,
robust construction. The units are double-cased
with an intermediate 50 mm of rock wool, which
produces good thermal and acoustic insulation.
All joints are sealed to eliminate the risk of air
leakages. The units have inspection doors on
10
The cross exchanger is made of aluminium. The
heat exchanger is designed with secure sealing
against the various air chambers and can easily
be removed for cleaning and inspection. A unit
with a cross heat exchanger requires a drainage
system for condensation water.
General Product Description
Summer Cassette
Fans
A summer cassette is available as an accessory.
Single-suction radial fans with bent-forward
blades. The fans have a high capacity, even
with long duct sections, and have a low noise
level. The fans are driven by a ball bearingmounted outer rotor motor of the highest
quality. The motor, which is located in the fan
wheel, is cooled very well. The fans can easily
be removed for cleaning (“click” electrical
connection).
This can be used to replace the heat exchanger
during the warm part of the year.
Rotating Heat Exchanger
Flexit cabinet units can be supplied with rotating
recovery. The rotating heat exchanger is a nonhygroscopic aluminium rotor which is mounted in
a cassette. The entire cassette can be removed
from the units for service and cleaning. The rotor
wheel is mounted with maintenance-free dusttight ball bearings.
The rotor is driven in sequence with the heat
control by an electric motor via a drive belt.
Filters
The units are fitted with F7 filters on both the
intake and extract air sides. The F7 filter stops
97% of all particles greater than 0.5 my (1 my =
1/1000 mm), i.e. pollen, dust from combustion,
etc. This is a valuable property, in particular
for allergics and people with respiratory tract
problems.
The filters are located in rails and are easy to
replace.
Heating
In order to ensure that the supply air has the
correct temperature, the units are fitted with
heating. This is available in the form of electric
heating elements or water batteries.
The water batteries are controlled by a 0-10
V output which controls a 2-way or 3-way valve.
11
Flexit L4 X
Art.no.
Type
14243
L4 XE
14310
L4 XW
14043
L4 XE EC
14044
L4 XW EC
CI 50 Control Panel included in all units
(with 12 m cable).
12
L4 XE
L4 XE EC L4 XW L4 XW EC Rated voltage:
230V/50Hz
230V/50Hz
230V/50Hz
230V/50Hz
Fuse:
10 A
10 A
10 A
10 A
Rated current, total:
8,7 A
8,0 A 5,7 A
5,0 A
Rated power, total:
1 990 W
1 826 W 1 315 W
1 151 W
Rated power, electric battery:
1 650 W
1 650 W
Rated power, fans:
2 x 165 W
2 X 83 W 2 x 165 W
2 X 83 W
Rated preheating power:
975 W
975 W
975 W
975 W
Fan type:
F-wheelF-wheelF-wheelF-wheel
Fan motor control:
Transformer
EC-stepless Transformer
EC-stepless
Max. fan speed:
2 230 rpm
2 900 rpm 2 230 rpm
2 900 rpm
Automatic, standard:
CS 50
CS 50
CS 50
CS 50
Filter type (SUP/EXTR):
F7/G3
F7/G3
F7/G3
F7/G3
Filter dimensions SUP (WxHxD):
257x220x50mm
257x220x50mm
257x220x50mm
257x220x50mm
Filter dimensions EXTR (WxHxD):
257x220x20mm
257x220x20mm
257x220x20mm
257x220x20mm
Weight:
36 kg
36 kg
36 kg
36 kg
Duct connection:
Ø 160 mm
Ø 160 mm
Ø 160 mm
Ø 160 mm
Height:
675 mm
675 mm
675 mm
675 mm
Width:
1 000 mm
1 000 mm
1000 mm
1000 mm
Depth:
350 mm
350 mm
350 mm
350 mm
Flexit L4 X
Accessories
Summer Cassette
Filter Set L4 X
Art.no.
Type
Art.no.
Type
14206
L4 X
12318
F7
CI 50 Control Panel
Art.no.
09380
Closing Air Damper
w/Spring Return
Art.no.
14482
Type
Ø160
CI 50 Additional box
CI 500 Control Panel
SP450 Motion Detector
for surface mounting
Art.no.
09385
Art.no.
09390
Art.no.
09381
Type
silver
09382
white
3-way Valve
Art.no. Type
56597 KVS 1,6 3-way
Motor 3-way Valve
230V
Art.no.
56596
Combi. Unit
Art.no.
00797
Type
2xØ160mm, black
00798
2xØ160mm, white
13
Flexit L4 X
System Drawing, water heating
System Drawing, electric heating
Extract Air
Outdoor Air
Extract Air
Outdoor Air
& &
& &
&)
(28
"
"
%"
"
-
-
7"
Supply Air
M1
M2
FI2
FI1
DA1
Supply air fan
Extract air fan
Extract air filter
Supply air filter
Extract air damper
(not standard)
DA2 Supply air damper
(not standard)
HR-X Exchanger cassette
&)
&)
& &
$!
&)
(28
"
%"
"
-
$!
Exhaust Air
F10 Overheating thermostat,
manual reset
F20 Overheating thermostat
WB1 Water heating battery
EB2 Preheater
B6 Thermoguard
B1 Supply air temperature sensor
B5 Water battery temperature sensor
-
%"
Supply Air
M1
M2
FI2
FI1
HR-X
F10
F11
Exhaust Air
Supply air fan
Extract air fan
Extract air filter
Supply air filter
Exchanger cassette
Overheating thermostat
manual reset
Overheating thermostat
F20
F21
EB1
EB2
B6
B1
Overheatn.thermostat
Overheatn.thermostat
Water heating battery
Preheater
Thermoguard
Supply air temperature sensor
Dimensioned Drawing
NB! The aggregate has 2 doors so that
it can be operated from either side.
14
Flexit L4 X
Capacity Diagram L4 X (measured with F7 filter)
Air flow rate, l/s
20
40
100
80
60
120
400
200
300
150
230V
100
200
190V
170V
150V
120V
105V
85V
60V
100
Pa 0
105V
120V
50
70dB(A)
65dB(A)
0 W
100
200
300
400
500
0
-5
-15
-30
-50
-75
0
15
55
65
m3/h 0
Pa
85V
60V
230V
190V
170V
150V
77dB(A)
75dB(A)
Avtrekk
L4x
30
40
Air flow rate, m3/h
Water Battery
f5 filter
Air flow rate, l/s
Extract air side
l/s 0
20
40
100
80
60
120
200
300
150
Contact resistance, Pa
400
230V
230V
200
100
190V
170V
190V
170V
150V
120V
105V
85V
60V
100
58dB(A)
150V
55dB(A)
120V
60V
Pa 0
m3/h 0
85V
Power consumption, Watt
Contact resistance, Pa
l/s 0
Power consumption, Watt
Supply air side
50
50dB(A)
105V
45dB(A)
0 W
200
100
400
300
500
Air flow rate, m /h
3
Sound data is given at sound power level LwA in the capacity
diagrams and is corrected with the table below for the various
octave bands. Radiated noise produces Lw in the various octave
bands and total LwA. Radiated noise is calculated by taking the
noise value from the supply air table and deducting the total
value from the correction factor table.
Supply air data is measured in accordance with ISO 5136, the induct method. Radiated noise is measured in accordance with ISO
9614-2. Bruel & Kjær measuring equipment, type 2260.
Correction factor for Lw
Hz
63
125
250
500
1000
2000
4000
8000
Supply air
3
2
-2
-5
-5
-6
-13
-29
Extract air
18
14
1
-12
-14
-28
-37
-43
-47
-42
-40
-43
-44
-45
-49
-57
Radiated
Total LwA
-38,7
Blue curves: Air capacity at various capacity
settings in Volt.
Green curves: Supply air fan power consumption
at various capacity settings.
Red curves: Sound power level LwA, cf.
correction table.
Light blue correction axe: Pressure increase using an EU-5 filter.
Light green correction axe: Pressure increase
using water battery.
15
Flexit L4 X EC
Capacity Diagram L4 X EC (measured with F7 filter)
Air flow rate, l/s
Contact resistance, Pa
l/s 0
20
40
100
80
60
120
400
(''
300
.,
200
,'
Power consumption, Watt
Supply Airsside
(''
(''
100
),
/'
/'
-'
+'
-' 70dB(A)
65dB(A)
+'
60dB(A)
,,[98
Pa 0
m3/h 0
Pa
0
75dB(A)
100
200
300
400
500
$,
$(,
$*'
$,'
$.,
*'
+'
,,
-,
(,
W
0
NXk\i9Xkk\ip
=,=`ck\i
Air flow rate, m3/h
Air flow rate, l/s
Contact resistance, Pa
l/s 0
20
40
100
80
60
120
400
(''
300
.,
200
,'
(''
(''
100
/'
/'
-'
-'
Pa 0
),
-'[98
,,[98
,'[98
+'
+,[98
+'[98
+'
m3/h 0
200
100
Power consumption, Watt
Extract Airsside
0 W
400
300
500
Air flow rate, m3/h
Sound data is given at sound power level LwA in the capacity
diagrams and is corrected with the table below for the various
octave bands. Radiated noise produces Lw in the various octave
bands and total LwA. Radiated noise is calculated by taking the
noise value from the supply air table and deducting the total
value from the correction factor table.
Supply air data is measured in accordance with ISO 5136, the induct method. Radiated noise is measured in accordance with ISO
9614-2. Bruel & Kjær measuring equipment, type 2260.
Correction factor for Lw
Hz
16
63
125
250
500
1000
2000
4000
8000
Supply air
9
6
-2
-3
-4
-9
-17
-31
Extract air
-38
-33
-32
-40
-42
-43
-44
-45
Radiated
-47
-42
-40
-43
-44
-45
-49
-57
Total LwA
-34,5
Blue curves: Air capacity at various capacity
settings in Volt.
Green curves: Supply air fan power consumption
at various capacity settings.
Red curves: Sound power level LwA, cf.
correction table.
Light blue correction axe: Pressure increase using an EU-5 filter.
Light green correction axe: Pressure increase
using water battery.
17
Flexit L7 X
Art.no.
Type
14246
L7 XE
14312
L7 XW
14248
L7 XE EC
14249
L7 XWEC
CI 50 Control Panel included in all units
(with 12 m cable).
18
L7 XE
L7 XE EC L7 XW
L7 XW EC
Rated voltage:
230V/50Hz
230V/50Hz
230V/50Hz
230V/50Hz
Fuse:
16 A
16 A 10 A
16 A
Rated current, total:
10,7 A
10,2 A 6,4 A
5,9 A
Rated power, total:
2 470 W
2 350 W 1 470 W
1 350 W
Rated power, electric battery:
2 000 W
2 000 W
Rated power, fans:
2 x 230 W
2 x 170 W
2 X 230 W
2 X 170 W
Rated preheating power:
1 000 W
1 000 W
1 000 W
1 000 W
Fan type:
F-wheelF-wheelF-wheelF-wheel
Fan motor control:
Transformer
EC-stepless
Transformer
EC-stepless
Max. fan speed:
2 120 rpm
2 250 rpm
2 120 rpm
2 250 rpm
Automatic, standard:
CS 50
CS 50
CS 50
CS 50
Filter type (SUP/EXTR):
F7/G3
F7/G3
F7/G3
F7/G3
Filter dimensions SUP (WxHxD):
394x223x250mm
394x223x250mm
394x223x250mm
394x223x250mm
Filter dimensions EXTR (WxHxD):
394x223x20mm
394x223x20mm
394x223x20mm
394x223x20mm
Weight:
66 kg
66 kg
66 kg
66 kg
Duct connection:
Ø 250 mm
Ø 250 mm
Ø 250 mm
Ø 250 mm
Height:
680 mm
680 mm
680 mm
680 mm
Width:
1 170 mm
1 170 mm
1 170 mm
1 170 mm
Depth:
465 mm
465 mm
465 mm
465 mm
Flexit L7 X
Accessories
Summer Cassette
Filter Set L7 X
Art.no.
Type
Art.no.
Type
14210
L7 X
12313
F7
CI 50 Control Panel
CI 50 Additional box
CI 500 Control Panel
SP450 Motion Detector
Art.no.
09380
for surface mounting
Art.no.
09385
Art.no.
09390
Art.no.
09381
09382
Type
silver
white
Lukkespjeld
3-way Valve
Art.no. Type
Art.no. Type
56597 KVS 1,6 3-way
14481
14485
Ø200
w/Spring Return
Ø250
w/Spring Return
Motor 3-way Valve
230V
Combi. Unit
Art.no.
Type
Art.no.
56596
00797
2xØ160mm, black
00798
2xØ160mm, white
00799
2xØ200mm, white
00800 2xØ200mm, black
19
Flexit L7 X
System Drawing, water heating
System Drawing, electric heating
Outdoor Air
Extract Air
Extract Air
Outdoor Air
& &
& &
&)
(28
"
"
%"
"
-
-
7"
Supply Air
M1
M2
FI2
FI1
DA1
Supply air fan
Extract air fan
Extract air filter
Supply air filter
Extract air damper
(not standard)
DA2 Supply air damper
sensor (not standard)
HR-X Exchanger cassette
&)
&)
$!
&)
(28
& &
"
%"
"
-
$!
Exhaust Air
F10 Overheating thermostat,
manual reset
F20 Overheating thermostat
WB1 Water heating battery
EB2 Preheater
B6 Thermoguard
B1 Supply air temperature B5 Water battery temperature
sensor
-
%"
Supply Air
M1
M2
FI2
FI1
HR-X
F20
F21
Exhaust Air
Supply air fan
Extract air fan
Extract air filter
Supply air filter
Exchanger cassette
Overheatn.thermostat
Overheatn.thermostat
EB1
EB2
B6
B1
Water heating battery
Preheater
Thermoguard
Supply air temperature
sensor
F10 Overheating thermostat,
manual reset
F11 Overheating thermostat
Dimensioned Drawing
NB! The aggregate has 2 doors so that
it can be operated from either side.
20
Flexit L7 X
Capacity Diagram L7 X (measured with F7 filter)
Air flow rate, l/s
Contact resistance, Pa
l/s 0
40
200
160
120
80
500
250
400
200
230V
300
100
120V
105V
85V
60V
100
Pa
150
190V
170V
150V
200
m3/h 0
Pa
105V
85V
60V
0
Power consumption, Watt
Supply air side
230V
190V
170V
150V
120V
65dB(A) 70dB(A)
200
75dB(A)
-5
-15
0
20
35
80dB(A)
0
-25
600
-40
800
-55
50
65
85
400
0
50
W
Water Battery
f5-filter
Air flow rate, m /h
3
Air flow rate, l/s
Contact resistance, Pa
l/s 0
40
200
160
120
80
500
250
400
200
230V
300
190V
170V
150V
200
100
230V
120V
105V
85V
60V
100
Pa
150
85V
60V
0
m3/h 0
Pa
105V
120V
190V
170V
50dB(A) 55dB(A)
200
0
150V
20
60dB(A)
600
400
35
64dB(A)
50
50
Power consumption, Watt
Extract air side
0 W
800
60
F5 Filter
Air flow rate, m3/h
Sound data is given at sound power level LwA in the capacity
diagrams and is corrected with the table below for the various
octave bands. Radiated noise produces Lw in the various octave
bands and total LwA. Radiated noise is calculated by taking the
noise value from the supply air table and deducting the total
value from the correction factor table.
Supply air data is measured in accordance with ISO 5136, the induct method. Radiated noise is measured in accordance with ISO
9614-2. Bruel & Kjær measuring equipment, type 2260.
Correction factor for Lw
Hz
63
125
250
500
1000
2000
4000
8000
Supply air
3
1
2
-1
-7
-11
-18
-31
Extract air
10
8
5
-2
-11
-19
-30
-48
-55
-43
-35
-36
-33
-31
-40
-50
Radiated
Total LwA
-27,1
Blue curves: Air capacity at various capacity
settings in Volt.
Green curves: Supply air fan power consumption
at various capacity settings.
Red curves: Sound power level LwA, cf.
correction table.
Light blue correction axe: Pressure increase using an EU-5 filter.
Light green correction axe: Pressure increase
using water battery.
21
Flexit L7 X EC
Capacity Diagram L7 X EC (measured with F7 filter)
Air flow rate, l/s
Contact resistance, Pa
l/s 0
40
80
200
160
120
500
250
400
200
300
150
200
(''
100
/'
-'
+'
Pa
0
100
(''
+'
m3/h 0
Pa
Power consumption, Watt
Supply Airsside
50
/'
-'
/*[98
.,[9
8 /'[98
.'[98
-'[98 -,[98
200
-25
600
-40
800
-55
50
65
85
400
0
-5
-15
0
20
35
0
W
Water Battery
f5-filter
Air flow rate, m /h
3
Air flow rate, l/s
Contact resistance, Pa
l/s 0
40
80
160
120
200
500
250
400
200
300
150
200
100
(''
/'
100
(''
/'
-'
Pa
+'
0
Power consumption, Watt
Extract Airsside
+'
m3/h 0
-'
,'[98 ,,[98 -'[98
200
600
400
-,[98 -/[98
50
0
W
800
Air flow rate, m3/h
Sound data is given at sound power level LwA in the capacity
diagrams and is corrected with the table below for the various
octave bands. Radiated noise produces Lw in the various octave
bands and total LwA. Radiated noise is calculated by taking the
noise value from the supply air table and deducting the total
value from the correction factor table.
Supply air data is measured in accordance with ISO 5136, the induct method. Radiated noise is measured in accordance with ISO
9614-2. Bruel & Kjær measuring equipment, type 2260.
Correction factor for Lw
Hz
125
250
500
1000
2000
4000
8000
Supply air
6
1
-2
-4
-5
-7
-14
-27
Extract air
11
2
4
0
-13
-15
-28
-44
-36
-31
-33
-41
-42
-39
-41
-47
Radiated
22
63
Total LwA
-33,4
Blue curves: Air capacity at various capacity
settings in Volt.
Green curves: Supply air fan power consumption
at various capacity settings.
Red curves: Sound power level LwA, cf.
correction table.
Light blue correction axe: Pressure increase using an EU-5 filter.
Light green correction axe: Pressure increase
using water battery.
23
Flexit S3 R
Art.no.
Type
14010
S3 REL
14011
S3 RER
CI 50 Control Panel included in all units
(with 12 m cable).
24
Rated voltage:
Fuse:
Rated current, total:
Rated power, total:
Rated power, electric battery:
Rated power, fans:
Rated preheating power:
Fan type:
Fan motor control:
Max. fan speed:
Automatic, standard:
Filter type (SUP/EXTR):
Filter dimensions SUP (WxHxD):
Filter dimensions EXTR (WxHxD):
Weight:
Duct connection:
Height:
Width:
S3 R
230V/50Hz
10A
5,5A
1271W
900W
2 x 165W
F-wheel
Transformer
2230rpm
CS 50
F7/F7
285x130x50mm
285x130x50mm
38,5 kg (without kitchen hood)
Ø125mm (127mm female)
700mm (without kitchen hood)
598mm
Depth:
320mm
Flexit S3 R
Accessories
Filter Set
CI 50 Control Panel
CI 50 Additional box
CI 500 Control Panel
Art.no.
Art.no.
for for surface mounting
Art.no.
12328
09380
Art.no. Type
09381 silver
09385
09382 white
SP 450 Motion Detector
Combi. Unit
Art.no.
Art.no.
00801
09390
Type
2xØ125mm, white
00802 2xØ125mm, black
00797
2xØ160mm, black
00798
2xØ160mm, white
For external installation with S3 R mod.:
Brasserie-E, white
Brasserie-E, steel
Fondue-E
Bistro-E
Art.no. 13750
Art.no. 13751
Art.no. 13616
Art.no. 13626
Frontlist, steel
Art.no.
13663
25
Flexit S3 R
System Drawing
B1
M1
FI2
M2
EB1
F10
FI1
F20
B1
EB1
F10
F20 FI1
FI2
M1
M2
HR-R
M4
Supply air temperature sensor
Water heating battery
Overheating thermostat,
manual reset
Overheating thermostat,
automatisk reset
Supply air filter
Extract air filter
Supply Airfan
Extract air fan
Rotating heat exchanger
Rotor motor
HR-R
M4
Dimensioned Drawing (right model)
Dimensions in mm
Duct connection (right model)
kitchen
hood
26
Flexit S3 R
Capacity Diagram S3 R (measured with F7 filter)
Supply air side
c&j '
Air flow rate, l/s
)'
+'
(''
/'
-'
(-'
()'
)*'M
)''
/'
(0'M
(.'M
(,'M
()'M
(',M
/,M
-'M
(''
GX '
)*'M
(0'M
(.'M
(,'M
()'M
/*[98
(',M
/'[98
.,[98
-'M /,M
-,[98 .'[98
d*&_ '
GX
Power consumption, Watt
Contact resistance, Pa
*''
'
(''
)''
*''
$((
$)/
$,*
+,
-,
)+
'
+'
N
NXk\i9Xkk\ip
=,=`ck\i
Air flow rate, m3/h
Extract air side
Air flow rate, l/s
c&j '
)'
+'
(''
/'
-'
(-'
*''
Contact resistance, Pa
)''
/'
(0'M
(.'M
(,'M
()'M
(',M
/,M
-'M
(''
/,M
-'M
GX '
d*&_ '
GX
'
)*'M
(0'M
(.'M
(,'M
,,[98
(',M ()'M
,'[98
+,[98
+'[98
(''
)''
)+
+,
+'
'
N
Power consumption, Watt
()'
)*'M
*''
=,$]`ck\i
-,
Air flow rate, m /h
3
Sound data is given at sound power level LwA in the capacity
diagrams and is corrected with the table below for the various
octave bands. Radiated noise produces Lw in the various octave
bands and total LwA. Radiated noise is calculated by taking the
noise value from the supply air table and deducting the total
value from the correction factor table.
Supply air data is measured in accordance with ISO 5136, the induct method. Radiated noise is measured in accordance with ISO
9614-2. Bruel & Kjær measuring equipment, type 2260.
Correction factor for Lw
Hz
Supply air
Extract air
Radiated
63
125
250
500
1000
2000
4000
8000
3
2
-2
-5
-5
-6
-13
-29
18
14
1
-12
-14
-28
-37
-43
-47
-42
-40
-43
-44
-45
-49
-57
Total LwA
-38,7
Blue curves: Air capacity at various capacity
settings in Volt.
Green curves: Supply air fan power consumption
at various capacity settings.
Red curves: Sound power level LwA, cf.
correction table.
Light blue correction axe: Pressure increase using an EU-5 filter.
Light green correction axe: Pressure increase
using water battery.
27
Flexit S3 RK
Art.no.
Type
14012
S3 RKEL
14013
S3 RKER
CI 50 Control Panel included in all units
(with 12 m cable).
Kitchen hood for installation, S3 RK mod.:
28
Art.no.
Type
13756
Brasserie-KL, white
13754
Brasserie-KR, white
13757
Brasserie-KL, steel
13755
Brasserie-KR, steel
55678
Air flow rate, l/s equipment, white
55679
Air flow rate, l/s equipment, steel
Rated voltage:
Fuse:
Rated current, total:
Rated power, total:
Rated power, electric battery:
Rated power, fans:
Rated preheating power:
Fan type:
Fan motor control:
Max. fan speed:
Automatic, standard:
Filter type (SUP/EXTR):
Filter dimensions SUP (WxHxD):
Filter dimensions EXTR(WxHxD):
Weight:
Duct connection:
Duct connection:
Height:
Width:
S3 RK
230V/50Hz
10A
5,5A
1271W
900W
2 x 165W
F-wheel
Transformer
2230rpm
CS 50
F7/F7
285x130x50mm
285x130x50mm
38,5 kg (without kitchen hood)
Ø125mm (127mm female)
Ø125mm
700mm (without kitchen hood)
598mm
Depth:
320mm
Flexit S3 RK
Accessories
Filter Set
CI 50 Control Panel
CI 50 Additional box
CI 500 Control Panel
Art.no.
Art.no.
for for surface mounting
Art.no.
12328
09380
Art.no. Type
09381 silver
09385
09382 white
SP 450 Motion Detector
Combi. Unit
Art.no.
Art.no.
00801
Type
2xØ125mm, white
00802
2xØ125mm, black
00797
2xØ160mm, black
00798
2xØ160mm, white
09390
29
Flexit S3 RK
System Drawing
B1
EB1
F10
F20 FI1
FI2
M1
M2
HR-R
M4
K
DA4
B1
M1
M2
EB1
FI2
F10
FI1
F20
HR-R
Supply air temperature sensor
Water heating battery
Overheating thermostat,
manual reset
Overheating thermostat,
automatisk reset
Supply air filter
Extract air filter
Supply Airfan
Extract air fan
Rotating heat exchanger
Rotor motor
Kitchen hood
Damper, kitchen hood
¥().,o Dl]]\d‚c
M4
.*'
.''
DA4
K
Dimensioned Drawing (right model)
Dimensions in mm
,0/
,(-
)*(
/)
/+
)*(
*)'
.''
./'
.''
./'
//'
.*'
//'
.*'
(''
¥().,É
Dl]]\d‚c
¥().,É
Dl]]\d‚c
*/+
0+
Duct connection (right model)
,((
30
/+
)*(
*)' /+
,(( )*(
*)'
,((
)*(
/)
/)
(''
(''
,0/ ,0/
,(- ,()*(
0+
*/+ */+
0+
,((
kitchen
hood
Flexit S3 RK
Capacity Diagram S3 RK (measured with F7 filter)
Supply air side
c&j '
Air flow rate, l/s
)'
+'
(''
/'
-'
(-'
()'
)*'M
)''
/'
(0'M
(.'M
(,'M
()'M
(',M
/,M
-'M
(''
)*'M
(0'M
(.'M
(,'M
()'M
/*[98
(',M
/'[98
.,[98
-'M /,M
-,[98 .'[98
GX '
d*&_ '
GX
Power consumption, Watt
Contact resistance, Pa
*''
'
(''
)''
*''
$((
$)/
$,*
+,
-,
)+
'
+'
N
NXk\i9Xkk\ip
=,=`ck\i
Air flow rate, m3/h
Extract air side
Air flow rate, l/s
c&j '
)'
+'
(''
/'
-'
(-'
*''
)''
/'
(0'M
(.'M
(,'M
()'M
(',M
/,M
-'M
(''
/,M
-'M
GX '
d*&_ '
GX
)*'M
(0'M
(.'M
(,'M
,,[98
(',M ()'M
,'[98
+,[98
+'[98
(''
)+
'
)''
*''
+,
-,
+'
'
N
Power consumption, Watt
Contact resistance, Pa
()'
)*'M
=,$]`ck\i
Air flow rate, m3/h
Sound data is given at sound power level LwA in the capacity
diagrams and is corrected with the table below for the various
octave bands. Radiated noise produces Lw in the various octave
bands and total LwA. Radiated noise is calculated by taking the
noise value from the supply air table and deducting the total
value from the correction factor table.
Supply air data is measured in accordance with ISO 5136, the induct method. Radiated noise is measured in accordance with ISO
9614-2. Bruel & Kjær measuring equipment, type 2260.
Correction factor for Lw
Hz
Supply air
Extract air
Radiated
63
125
250
500
1000
2000
4000
8000
3
2
-2
-5
-5
-6
-13
-29
18
14
1
-12
-14
-28
-37
-43
-47
-42
-40
-43
-44
-45
-49
-57
Total LwA
-38,7
Blue curves: Air capacity at various capacity
settings in Volt.
Green curves: Supply air fan power consumption
at various capacity settings.
Red curves: Sound power level LwA, cf.
correction table.
Light blue correction axe: Pressure increase using an EU-5 filter.
Light green correction axe: Pressure increase
using water battery.
31
Flexit S4 R
Art.no.
Type
14160
S4 REL
14161
S4 RER
14162
S4 R L
14163
S4 R R
14164
S4 REL EC
14165
S4 RER EC
14166
S4 R L EC
14167
S4 R R EC
CI 50 Control Panel included in all units
(with 12 m cable).
S4 RE
S4 RE EC
S4 RW
S4 RW EC
Rated voltage:
230V/50Hz
230V/50Hz
230V/50Hz
230V/50Hz
Fuse:
10 A
10 A
10 A
10 A
Rated current, total:
6,8 A
6,1 A
1,6 A
0,9 A
Rated power, total:
1 581 W
1 417 W
381 W
217 W
Rated power, electric battery:
1 200 W
1 200 W
Rated power, fans:
2 x 165 W
2 x 83 W
2 x 165 W
2 x 83 W
Fan type:F-wheelF-wheelF-wheelF-wheel
32
Fan motor control:
Transformer
EC-stepless
Transformer
EC-stepless
Max. fan speed:
2 230 rpm
1 970 rpm
2 230 rpm
1 970 rpm
Automatic, standard:
CS 50
CS 50
CS 50
CS 50
Filter type (SUP/EXTR):F7/F7
F7/F7
F7/F7
F7/F7
Filter dimensions SUP (WxHxD):
468x200x70mm
468x200x70mm
468x200x70mm
468x200x70mm
Filter dimensions EXTR (WxHxD):
468x200x70mm
468x200x70mm
468x200x70mm
468x200x70mm
Weight:
85 kg
85 kg
85 kg
85 kg
Duct connection:
Ø 200 mm
Ø 200 mm
Ø 200 mm
Ø 200 mm
Height:
900 mm
900 mm
900 mm
900 mm
Width:
900 mm
900 mm
900 mm
900 mm
Depth:
550 mm
550 mm
550 mm
550 mm
Flexit S4 R
Accessories
Filter Set
CI 50 Control Panel
CI 50 Additional box
CI 500 Control Panel
Art.no.
12327
Art.no.
09380
for surface mounting
Art.no.
09385
3-way Valve
Art.no. Type
56604 KVS 1,0 3-way
56597
KVS 1,6 3-way
Closing Air Damper
w/Spring Return
Art.no.
14482
Type
Ø160
Motor 3-way Valve
230V
Art.no.
56596
Art.no.
09381
Type
silver
09382
white
Water Coil
SP450 Motion Detector
Art.no.
14466
Art.no.
09390
Type
Ø160
Combi. Unit
Art.no.
00797
Type
2xØ160mm, black
00798
2xØ160mm, white
33
Flexit S4 R
System Drawing, electric heating
System Drawing, water heating
(right model)
(right model)
Supply Air
Extract Air Exhaust Air
Outdoor Air
Supply Air
Extract Air
Exhaust Air
Outdoor Air
B1
"
FI2
FI1
B1
FI2
FI1
M2
M2
F10 F20
HR-R
HR-R
M1
M1
FI2 Extract air filter
FI1
Supply air filter
HR-R Rotating heat exchanger
B1
Supply air temperature
sensor
Dimensioned Drawing
34
EB1
M4
M4
B5
M1
M2
M4
Temperature sensor
Supply air fan
Extract air fan
Rotor motor
(left modell)
FI2 Extract air filter
FI1
Supply air filter
HR-R Rotating heat exchanger
B1
Supply air temperature
sensor
EB1 Water heating battery
F10 Overheating thermostat,
manual reset
F20 Overheating thermostat
M1 Supply air fan
M2 Extract air fan
M4 Rotor motor
Dimensions in mm
Flexit S4 R
Capacity Diagram S4 R (measured with F7 filter)
Air flow rate, l/s
Contact resistance, Pa
l/s 0
20
40
100
80
60
120
400
200
300
150
)*'M
200
Power consumption, Watt
Supply air side
100
)*'M
(0'M
(.'M
(0'M
(.'M
(,'M
()'M
(',M
/,M
-'M
100
()'M
65dB(A)
(',M
-'M /,M
60dB(A)
,,[98
Pa 0
m3/h 0
Pa
75dB(A)
(,'M
0 W
100
200
300
400
$((
$)/
$,*
$0'
(.
),
*)
0
0
50
70dB(A)
500
NXk\i9Xkk\ip
=,=`ck\i
Air flow rate, m3/h
Air flow rate, l/s
Contact resistance, Pa
c&j '
)'
+'
(''
/'
-'
()'
+''
)''
*''
(,'
)''
Power consumption, Watt
Extract air side
(''
)*'M
)*'M
(0'M
-)[98
(.'M
-'[98
(0'M
(.'M
(,'M
()'M
(',M
/,M
-'M
(''
(,'M
d*&_ '
GX
/,M (',M
+,[98
-'M
GX '
(''
'
0
()'M
,'
,,[98
,'[98
'
)''
*''
+''
(.
),
*)
N
,''
=,=`ck\i
Air flow rate, m3/h
Sound data is given at sound power level LwA in the capacity
diagrams and is corrected with the table below for the various
octave bands. Radiated noise produces Lw in the various octave
bands and total LwA. Radiated noise is calculated by taking the
noise value from the supply air table and deducting the total
value from the correction factor table.
Supply air data is measured in accordance with ISO 5136, the induct method. Radiated noise is measured in accordance with ISO
9614-2. Bruel & Kjær measuring equipment, type 2260.
Correction factor for Lw
Hz
Supply air
Extract air
Radiated
63
125
250
500
1000
2000
4000
8000
7
3
-1
-3
-6
-7
-17
-30
8
9
5
-2
-11
-21
-29
-48
-43
-31
-33
-34
-38
-38
-39
-44
Total LwA
-30,6
Blue curves: Air capacity at various capacity
settings in Volt.
Green curves: Supply air fan power consumption
at various capacity settings.
Red curves: Sound power level LwA, cf.
correction table.
Light blue correction axe: Pressure increase using an EU-5 filter.
Light green correction axe: Pressure increase
using water battery.
35
Flexit S4 R EC
Capacity Diagram S4 R EC (measured with F7 filter)
Air flow rate, l/s
Contact resistance, Pa
c&j 0
)'
+'
(''
/'
-'
+''
(''
*''
.,
Power consumption, Watt
Supply Airsside
,'
)''
(''
(''
/'
(''
.*[98
-'
.'[98
-,[98
+'
-'[98
,,[98
-'
+'
Pa '
m3/h 0
Pa
),
/'
0
100
$('
200
$),
('
(,
'
300
$,,
400
$0'
),
*'
W
NXk\i9Xkk\ip
=,=`ck\i
Air flow rate, m /h
3
Air flow rate, l/s
Contact resistance, Pa
c&j 0
)'
+'
(''
/'
-'
+''
(''
*''
.,
Power consumption, Watt
Extract Airsside
,'
)''
(''
(''
/'
/'
(''
+'
),
-'[98
-'
-'
,,[98
,'[98
+'
+,[98
+'[98
Pa '
m3/h 0
Pa
0
100
('
'
200
300
400
(,
),
*'
W
f5-filter
Air flow rate, m3/h
Sound data is given at sound power level LwA in the capacity
diagrams and is corrected with the table below for the various
octave bands. Radiated noise produces Lw in the various octave
bands and total LwA. Radiated noise is calculated by taking the
noise value from the supply air table and deducting the total
value from the correction factor table.
Supply air data is measured in accordance with ISO 5136, the induct method. Radiated noise is measured in accordance with ISO
9614-2. Bruel & Kjær measuring equipment, type 2260.
Correction factor for Lw
Hz
63
125
250
500
1000
2000
4000
8000
Supply air
10
4
-3
-4
-3
-10
-20
-34
Extract air
Radiated
36
11
11
4
-4
-8
-23
-32
-48
-43
-31
-33
-34
-38
-38
-39
-44
Total LwA
-30,6
Blue curves: Air capacity at various capacity
settings in Volt.
Green curves: Supply air fan power consumption
at various capacity settings.
Red curves: Sound power level LwA, cf.
correction table.
Light blue correction axe: Pressure increase using an EU-5 filter.
Light green correction axe: Pressure increase
using water battery.
37
Flexit SL4 R
Art.no.
Type
14020
SL4 REL
14021
SL4 RER
14022
SL4 R L
14023
SL4 R R
14024
SL4 REL EC
14025
SL4 RER EC
14026
SL4 R L EC
14027
SL4 R R EC
CI 50 Control Panel included in all units
(with 12 m cable).
Rated voltage:
SL4 RE
SL4 RE EC
SL4 RW
SL4 RW EC
230V/50Hz
230V/50Hz
230V/50Hz
230V/50Hz
Fuse:
10 A
10 A
10 A
10 A
Rated current, total:
5,5 A
4,8 A
1,6 A
0,9 A
Rated power, total:
1 271 W
1 107 W
371 W
207 W
Rated power, electric battery:
900 W
900 W
-
-
Rated power, fans:
2 x 165 W
2 X 83 W
2 x 165 W
2 X 83 W
Rated preheating power:
38
Fan type:
F-wheel
F-wheelF-wheelF-wheel
Fan motor control:
Transformer
EC-stepless
Transformer
EC-stepless
Max. fan speed:
2 230 rpm
1 970 rpm
2 230 rpm
1 970 rpm
Automatic, standard:
CS 50
CS 50
CS 50
CS 50
Filter type (SUP/EXTR):
F7/F7
F7/F7
F7/F7
F7/F7
Filter dimensions SUP (WxHxDmm):
350x185x50
350x185x50
350x185x50
350x185x50
Filter dimensions EXTR (WxHxDmm):
350x185x50
350x185x50
350x185x50
350x185x50
Weight:
48 kg
48 kg
48 kg
48 kg
Duct connection:
Ø 160 mm
Ø 160 mm
Ø 160 mm
Ø 160 mm
Duct connection, kitchen hood:
Ø 125 mm
Ø 125 mm
Ø 125 mm
Ø 125 mm
Height:
700 mm
700 mm
700 mm
700 mm
Width:
598 mm
598 mm
598 mm
598 mm
Depth:
455 mm
455 mm
455 mm
455 mm
Flexit SL4 R
Accessories
Filter Set
CI 50 Control Panel
CI 50 Additional box
CI 500 Control Panel
Art.no.
12336
Art.no.
09380
for surface mounting
Art.no.
09385
SP450 Motion Detector
Art.no.
09390
Closing Air Damper
w/Spring Return
Art.no.
14482
Type
Ø160
Water Coil
Combi. Unit
Art.no.
14466
Art.no.
00797
Type
2xØ160mm, black
00798
2xØ160mm, white
00799
2xØ200mm, white
00800
2xØ200mm, black
Type
Ø160
Art.no.
09381
Type
silver
09382
white
3-way Valve
Art.no. Type
56597 KVS 1,6 3-way
Motor 3-way Valve
230V
Art.no.
56596
For external installation with SL4 R mod.:
Brasserie-E, white
Brasserie-E, steel
Fondue-E
Bistro-E
Art.no. 13750
Art.no. 13751
Art.no. 13616
Art.no. 13626
Frontlist, steel
Art.no.
13663
39
Flexit SL4 R
System Drawing, electric heating
System Drawing, water heating
Extract Air
Supply Air
Outdoor Air Exhaust Air
B5
M1
Outdoor Air
Exhaust Air
B1
B5
K
M1
FI2
Supply Air
+
B1
"
Extract Air
K
M2
EB1
F10
F20
FI2
M2
FI1
M1
FI1
M2
FI1
FI2
HR-R
"
HR-R
HR-R
M4
M4
M2 Extract air fan
HR-R Rotating heat
exchanger
M4 Rotor motor
K
Kitchen hood
(accessories)
B1
Supply air temperature
sensor
Water heating battery
Overhetingstermostat,
manual reset
F20 Overhetingstermostat,
automatic reset
FI1
Supply air filter
107
128
598
Ø160
Dimensioned Drawing
107
598
Ø160
107
Ø160
Ø125
107
FI2 Extract air filter
M1
Supply air fan
M2 Extract air fan
HR-R Rotating heat
exchanger
M4 Rotor motor
K
Kitchen hood
(accessories)
Dimensions in mm
Shown from below
Ø160
700
128
320700
455
Ø125
455
EB1
F10
320
455
FI1
FI2
M1
Supply air temperature
sensor
Temperature sensor,
water battery
Supply air filter
Extract air filter
Supply air fan
320
B5
128
B1
M4
107
598
Ø160
107
Ø125
Ø160
Ø160
Ø160
299
299
106
106
700
320
106
Kitchen hood
320
106
299
106
299
320
106
Ø160
Ø160
320
106
106
Shown from above
Front
Ø160
Ø160
299
106
299
106
320
106
320
106
40
Flexit SL4 R
Capacity Diagram SL4 R (measured with F7 filter)
Air flow rate, l/s
Contact resistance, Pa
l/s 0
20
40
100
80
60
400
200
300
150
Power consumption, Watt
Supply air side
)*'M
100
200
(0'M
(.'M
(,'M
()'M
(',M
/,M
-'M
()'M
.,[98
(',M
.'[98
-,[98
-'[98
/,M
-'M
Pa 0
m3/h 0
Pa
100
$('
0
(,
200
$),
300
$,,
400
),
*,
+,
Air flow rate, m3/h
$0'
W
NXk\i9Xkk\ip
=,=`ck\i
Air flow rate, l/s
Extract air side
c&j 0
Contact resistance, Pa
0
)'
+'
(''
/'
-'
+''
)''
*''
(,'
Power consumption, Watt
100
)*'M
/*[98
(0'M
(.'M
50
(,'M
/'[98
)*'M
(''
)''
(0'M
(.'M
(,'M
()'M
(',M
/,M
-'M
(''
)*'M
(0'M
(.'M
(,'M
-,[98
,'
()'M
-'[98
(',M
,,[98
/,M
-'M
,'[98
+,[98
Pa '
m3/h 0
Pa
0
100
200
(,
),
'
300
400
*,
+,
W
=,=`ck\i
Air flow rate, m /h
3
Sound data is given at sound power level LwA in the capacity
diagrams and is corrected with the table below for the various
octave bands. Radiated noise produces Lw in the various octave
bands and total LwA. Radiated noise is calculated by taking the
noise value from the supply air table and deducting the total
value from the correction factor table.
Supply air data is measured in accordance with ISO 5136, the induct method. Radiated noise is measured in accordance with ISO
9614-2. Bruel & Kjær measuring equipment, type 2260.
Correction factor for Lw
Hz
Supply air
Extract air
Radiated
63
125
250
500
1000
2000
4000
8000
3
1
2
-1
-7
-11
-18
-31
10
8
5
-2
-11
-19
-30
-48
-55
-43
-35
-36
-33
-31
-40
-50
Total LwA
-27,1
Blue curves: Air capacity at various capacity
settings in Volt.
Green curves: Supply air fan power consumption
at various capacity settings.
Red curves: Sound power level LwA, cf.
correction table.
Light blue correction axe: Pressure increase using an EU-5 filter.
Light green correction axe: Pressure increase
using water battery.
41
Flexit SL4 R EC
Capacity Diagram SL4 R EC (measured with F7 filter)
Air flow rate, l/s
Contact resistance, Pa
c&j 0
)'
+'
(''
/'
-'
+''
(''
*''
.,
Power consumption, Watt
Supply Airsside
,'
)''
(''
(''
/'
(''
/'
-'
-'
.'[98
+'
-,[98
-'[98
+'
Pa '
m3/h 0
Pa
),
0
100
$('
200
$),
(,
),
..[98
.,[98
'
300
$,,
400
$0'
*,
+,
W
NXk\i9Xkk\ip
=,=`ck\i
Air flow rate, m /h
3
Air flow rate, l/s
Contact resistance, Pa
c&j 0
)'
+'
(''
/'
-'
+''
(''
*''
.,
Power consumption, Watt
Extract Airsside
,'
)''
(''
(''
/'
(''
),
/'
-'
+'
Pa '
-'[98
-'
+'
+'[98
m3/h 0
Pa
0
,,[98
,'[98
+,[98
100
(,
'
200
300
400
),
*,
+,
W
f5-filter
Air flow rate, m3/h
Sound data is given at sound power level LwA in the capacity
diagrams and is corrected with the table below for the various
octave bands. Radiated noise produces Lw in the various octave
bands and total LwA. Radiated noise is calculated by taking the
noise value from the supply air table and deducting the total
value from the correction factor table.
Supply air data is measured in accordance with ISO 5136, the induct method. Radiated noise is measured in accordance with ISO
9614-2. Bruel & Kjær measuring equipment, type 2260.
Correction factor for Lw
Hz
Supply air
Extract air
Radiated
42
63
125
250
500
1000
2000
4000
8000
9
3
-1
-2
-4
-10
-18
-31
13
9
3
-2
-10
-19
-31
-48
-48
-38
-33
-34
-30
-29
-39
-50
Total LwA
-25,5
Blue curves: Air capacity at various capacity
settings in Volt.
Green curves: Supply air fan power consumption
at various capacity settings.
Red curves: Sound power level LwA, cf.
correction table.
Light blue correction axe: Pressure increase using an EU-5 filter.
Light green correction axe: Pressure increase
using water battery.
43
Flexit S7 R
Art.no.
Type
14170
S7 REL
14171
S7 RER
14172
S7 R L
14173
S7 R R
14174
S7 REL EC
14175
S7 RER EC
14176
S7 R L EC
14177
S7 R R EC
CI 50 Control Panel included in all units
(with 12 m cable).
S7 RE
S7 RE EC
S7 RW
S7 RW EC
Rated voltage:
230V/50Hz
230V/50Hz
230V/50Hz
230V/50Hz
Fuse:
16 A
13 A
10 A
10 A
Rated current, total:
14,2 A
12,4 A
3,3 A
1,5 A
Rated power, total:
3 265 W
2 845 W
765 W
345 W
Rated power, electric battery:
2 500 W
2 500 W
Rated power, fans:
2 x 375 W
2 x 175 W
2 x 375 W
2 x 175 W
Fan type:
F-wheelF-wheelF-wheelF-wheel
Fan motor control:
Transformer
EC-stepless
Transformer
EC-stepless
Max. fan speed:
2000 rpm
2000 rpm
2000 rpm
2000 rpm
Automatic, standard:
CS 50 CS 50
CS 50
CS 50
Filter type (SUP/EXTR):
F7/F7
F7/F7
F7/F7
F7/F7
Filter dimensions SUP (WxHxD):
468x200x70mm 468x200x70mm
468x200x70mm
468x200x70mm
Filter dimensions EXTR (WxHxD):
468x200x50mm
468x200x70mm
468x200x70mm
468x200x70mm
Weight:
92 kg 92 kg
92 kg
92 kg
Duct connection:
Ø 200 mm
Ø 200 mm
Ø 200 mm
Ø 200 mm
Height:
900 mm
900 mm
900 mm
900 mm
Width:
900 mm
900 mm
900 mm
900 mm
Depth:
550 mm
550 mm
550 mm
550 mm
44
Flexit S7 R
Accessories
Filter Set
CI 50 Control Panel
CI 50 Additional box
CI 500 Control Panel
Art.no.
12327
Art.no.
09380
for surface mounting
Art.no.
09385
3-way Valve
Art.no. Type
56604 KVS 1,0 3-way
56597
KVS 1,6 3-way
Closing Air Damper
w/Spring Return
Motor 3-way Valve
230V
Art.no.
56596
Art.no.
09381
Type
silver
09382
white
Water Coil
SP450 Motion Detector
Art.no.
14467
Art.no.
09390
Type
Ø200
Combi. Unit
Art.no.
Type
Art.no.
00797
Type
2xØ160mm, black
14482
Ø160
14481
Ø200
00798
2xØ160mm, white
00799
2xØ200mm, white
00800
2xØ200mm, black
45
Flexit S7 R
System Drawing, water heating
System Drawing, electric heating
(right model)
(right model)
Supply Air
Extract Air Exhaust Air
Outdoor Air
Supply Air
Extract Air Exhaust Air
Outdoor Air
B1
"
FI2
FI1
B1
FI2
FI1
M2
M2
F10 F20
HR-R
HR-R
M1
M1
FI2 Extract air filter
FI1
Supply air filter
HR-R Rotating heat
exchanger
B1
Temperature sensor,
supply air
Dimensioned Drawing
46
EB1
M4
M4
B5
M1
M2
M4
Temperature sensor
Supply air fan
Extract air fan
Rotor motor
(left modell)
FI2 Extract air filter
FI1
Supply air filter
HR-R Rotating heat
exchanger
B1
Temperature sensor,
supply air
EB1 Water heating battery
F10 Overheating thermostat,
manual reset
F20 Overheating thermostat
M1 Supply air fan
M2 Extract air fan
M4 Rotor motor
Dimensions in mm
Flexit S7 R
Capacity Diagram S7 R (measured with F7 filter)
Air flow rate, l/s
Supply air side
l/s 0
40
80
160
120
200
Contact resistance, Pa
600
300
250
400
200
)*'M
200
Pa
150
(0'M
(.'M
(,'M
()'M
(',M
/,M
-'M
100
)*'M
(',M ()'M
-'M /,M
(,'M
)''
m3/h 0
Pa
$+
$/
0
(.
0
50
(.'M (0'M
70dB(A)
-'[98 65dB(A)
0
Power consumption, Watt
350
75dB(A) /'[98
+''
/*[98
600
0 W
800
$(+
$))
$*'
$*0
$,)
),
*)
*/
+)
+.
NXk\i9Xkk\ip
=,=`ck\i
Air flow rate, m3/h
Air flow rate, l/s
Extract air side
l/s 0
40
80
160
120
200
Contact resistance, Pa
600
300
250
200
400
200
Pa
150
)*'M
(0'M
(.'M
(,'M
()'M
(',M
/,M
-'M
100
)*'M
-'M
0
85V (',M
()'M
200
0
0
50
(.'M (0'M
-/[98
-'[98 -,[98
+,[98 ,'[98 ,,[98
m3/h 0
Pa
(,'M
(.
600
400
),
*)
*/
Power consumption, Watt
350
+)
0 W
800
+.
=,=`ck\i
Air flow rate, m3/h
Sound data is given at sound power level LwA in the capacity
diagrams and is corrected with the table below for the various
octave bands. Radiated noise produces Lw in the various octave
bands and total LwA. Radiated noise is calculated by taking the
noise value from the supply air table and deducting the total
value from the correction factor table.
Supply air data is measured in accordance with ISO 5136, the induct method. Radiated noise is measured in accordance with ISO
9614-2. Bruel & Kjær measuring equipment, type 2260.
Correction factor for Lw
Hz
Supply air
Extract air
Radiated
63
125
250
500
1000
2000
4000
8000
3
1
-4
-4
-5
-7
-19
-24
10
11
3
-4
-9
-15
-26
-41
-43
-31
-33
-34
-38
-38
-39
-44
Total LwA
-30,6
Blue curves: Air capacity at various capacity
settings in Volt.
Green curves: Supply air fan power consumption
at various capacity settings.
Red curves: Sound power level LwA, cf.
correction table.
Light blue correction axe: Pressure increase using an EU-5 filter.
Light green correction axe: Pressure increase
using water battery.
47
Flexit S7 R EC
Capacity Diagram S7 R EC (measured with F7 filter)
Air flow rate, l/s
Supply Airsside
l/s 0
40
160
120
80
600
)''
Power consumption, Watt
Contact resistance, Pa
(.,
(,'
400
(),
(''
(''
200
.,
/'
Pa
,'
-'
+'
0
-'[98 -,[98
m3/h 0
200
$('
$,
Pa
0
0
/'
-'
+'
(''
.'[98 .,[98
400
$),
$(,
),
/'[98
0
$*,
600
$+,
*,
+'
(,
),
*'
Air flow rate, m3/h
W
NXk\i9Xkk\ip
=,=`ck\i
Air flow rate, l/s
Extract Airsside
l/s 0
40
160
120
80
600
)''
Power consumption, Watt
Contact resistance, Pa
(.,
(,'
400
(),
(''
(''
200
.,
/'
-'
+'
Pa
0
,'
(''
/'
),
-+[98
+,[98 ,'[98 ,,[98 -'[98
0
-'
+'
m3/h 0
Pa
0
200
0
600
400
(,
),
W
*'
*,
+'
=,=`ck\i
Air flow rate, m /h
3
Sound data is given at sound power level LwA in the capacity
diagrams and is corrected with the table below for the various
octave bands. Radiated noise produces Lw in the various octave
bands and total LwA. Radiated noise is calculated by taking the
noise value from the supply air table and deducting the total
value from the correction factor table.
Supply air data is measured in accordance with ISO 5136, the induct method. Radiated noise is measured in accordance with ISO
9614-2. Bruel & Kjær measuring equipment, type 2260.
Correction factor for Lw
Hz
Supply air
Extract air
Radiated
48
63
125
250
500
1000
2000
4000
8000
3
1
-4
-4
-5
-7
-14
-24
10
11
-3
-4
-9
-15
-26
-41
-43
-31
-33
-34
-38
-38
-39
-44
Total LwA
-30,6
Blue curves: Air capacity at various capacity
settings in Volt.
Green curves: Supply air fan power consumption
at various capacity settings.
Red curves: Sound power level LwA, cf.
correction table.
Light blue correction axe: Pressure increase using an EU-5 filter.
Light green correction axe: Pressure increase
using water battery.