- No category
advertisement
▼
Scroll to page 2
of 35
S&C Source-Transfer PMH Pad-Mounted Gear With Micro-AT® Control Outdoor Distribution (14.4 kv and 25 kv) INSTRUCTIONS For Operation This publication contains instructions for operation of fuses and Mini-Rupter® Switches in S&C Source-Transfer PMH Pad-Mounted Gear. For instructions regarding field programming and operation of the S&C Micro-AT Source-Transfer Control, refer to S&C Instruction Sheet 515-500. For operating instructions regarding the optional test-panel feature (Catalog Number Suffix “-Y5”), if furnished, refer to S&C Instruction Sheet 515-505. TABLE OF CONTENTS Section Page Number INTRODUCTION Qualified Persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 SAFETY INFORMATION Understanding Safety-Alert Messages . . . . . . . . . . . . . . . . . . . . 3 Following Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Replacement Instructions and Labels . . . . . . . . . . . . . . . . . . . . 3 SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 OPERATING DESCRIPTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 MINI-RUPTER SWITCHES Decoupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Automatic Switch Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Nonautomatic Switch Operation . . . . . . . . . . . . . . . . . . . . . . . . 11 Charging Operator (Nonelectrical) . . . . . . . . . . . . . . . . . . . . . . 11 Front Barriers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 FUSING Assembling the Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Installing the Fuse in the Mounting. . . . . . . . . . . . . . . . . . . . . . 15 Warranty Qualifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 SWITCHING WITH UNI-RUPTER Installing and Closing the Fuse . . . . . . . . . . . . . . . . . . . . . . . . . 16 A Note on Single-Pole Switching . . . . . . . . . . . . . . . . . . . . . . . . 20 Opening and Removing the Fuse. . . . . . . . . . . . . . . . . . . . . . . . 20 Supersedes Instruction Sheet 663-503 dated 9-20-93 Section S&C ELECTRIC COMPANY 23 24 25 26 27 28 28 29 29 29 30 31 33 34 c1995 INSTRUCTION SHEET s Page Number RE-FUSING How to Detect and Replace a Blown Fuse. . . . . . . . . . . . . . . . Installing the Fuse in the Mounting. . . . . . . . . . . . . . . . . . . . . . FINAL CHECKS BEFORE WALKING AWAY. . . . . . . . . . . . . . . . IF OPERATOR STALLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MAINTENANCE Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Returning Equipment to Service . . . . . . . . . . . . . . . . . . . . . . . . Enclosure Finish . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . APPENDIX A Preliminary Tryout Before Gear Is Energized—Optional . . . APPENDIX B Dielectric Testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . APPENDIX C Ratings for S&C Mini-Rupter Switches. . . . . . . . . . . . . . . . . . . Ratings for S&C Power Fuses with Uni-Rupter. . . . . . . . . . . . APPENDIX D Optional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . APPENDIX E Current-Limiting Fuses for Use in S&C PMH Pad-Mounted Gear . . . . . . . . . . . . . . . . . . . . . . . . . 663-503 Page 1 of 35 August 14, 1995 S&C Source-Transfer PMH Pad-Mounted Gear With Micro-AT® Control Outdoor Distribution (14.4 kv and 25 kv) INTRODUCTION Qualified Persons Ç WARNING The equipment covered by this publication must be installed, operated, and maintained by qualified persons who are knowledgeable in the installation, operation, and maintenance of underground electric power distribution equipment along with the associated hazards. A qualified person is one who is trained and competent in: • The skills and techniques necessary to distinguish exposed live parts from non-live parts of electrical equipment. • The skills and techniques necessary to determine the proper approach distances corresponding to the voltages to which the qualified person will be exposed. • The proper use of the special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools for working on or near exposed energized parts of electrical equipment. These instructions are intended only for such qualified persons. They are not intended to be a substitute for adequate training and experience in safety procedures for this type of equipment. Ç CAUTION The equipment in this publication must be selected for a specific application. The application must be within the ratings furnished for the equipment. Ratings for this gear are listed on a ratings label on the interior of the doors (right-hand doors only for double-door models). General Each unit of S&C Source-Transfer PMH Pad-Mounted Gear is provided with an “Installation and Operation Information Kit” located in the holder inside the PentaLatch-equipped door of the low-voltage control compartment. The information kit includes applicable instruction sheets covering installation of the gear and operation of components, plus wiring diagrams and a catalog dimensional drawing showing cable-locating and anchor-bolt dimensions. All personnel involved with installation and operation of the gear should be thoroughly familiar with the contents of the kit. These instructions are for operation of fuses and MiniRupter Switches in S&C Pad-Mounted Gear, Source-Transfer PMH Models equipped with the S&C Micro-AT Source- 663-503 Page 2 of 35 August 14, 1995 Transfer Control. For instructions regarding field programming and operation of the Micro-AT control, refer to S&C Instruction Sheet 515-500. Source-Transfer PMH Pad-Mounted Gear is a totally self-contained switching and protection package that provides fault protection and fully automatic two-way source transfer for critical loads requiring a high degree of service continuity. This gear contains the following: • Switch-operator-driven 600-ampere S&C Mini-Rupter Switches for three-pole live switching of three-phase source circuits. • Stored-energy operators to provide high-speed power operation of the Mini-Rupter Switches. The operators automatically charge when voltage is present on the associated source. • S&C Micro-AT Source-Transfer Control for programmed control of all switching functions associated with automatic source transfer. • S&C Voltage Sensors to provide three-phase sensing for automatic source transfer and control power for the Micro-AT control. The voltage sensors also provide supply power for motor charging of the stored-energy operators and capacitor charging for solenoid tripping of the operators. • Decouplers to permit exercising of the stored-energy operators without affecting the position of the MiniRupter Switches. • 200- or 400-ampere hookstick-operated S&C Power Fuses with Uni-Rupter for single-pole live switching of single-phase or three-phase load circuits. Models available offer a choice of S&C Type SML-20 or SML-4Z Power Fuses, S&C Fault Fiter® Electronic Power Fuses, or a variety of current-limiting fuses. • Penta-Latch Mechanism on each set of doors for access control. Mechanism provides automatic door latching and permits padlocking only when the door is latched closed. Doors can be opened only with a pentahead socket wrench or tool except when hexhead actuators (Catalog Number Suffix “-B1” or “-B2”) are specified. A variety of optional features are available for S&C Source-Transfer PMH Pad-Mounted Gear. The catalog number stamped on the nameplate affixed to the enclosure door is suffixed with letter-number combinations applicable to the gear furnished. Refer to Appendix D for descriptions of the optional features. INSTRUCTION SHEET S&C ELECTRIC COMPANY s SAFETY INFORMATION Understanding Safety-Alert Messages There are several types of safety-alert messages which may appear throughout this instruction sheet as well as on labels affixed to the S&C Source-Transfer PMH PadMounted Gear. Familiarize yourself with these types of messages and the importance of the various signal words, as explained below. Ç DANGER “DANGER” identifies the most serious and immediate hazards which will likely result in serious personal injury or death if instructions, including recommended precautions, are not followed. Ç WARNING “WARNING” identifies hazards or unsafe practices which can result in serious personal injury or death if instructions, including recommended precautions, are not followed. Ç CAUTION “CAUTION” identifies hazards or unsafe practices which can result in minor personal injury or product or property damage if instructions, including recommended precautions, are not followed. Following Safety Instructions Ç NOTICE Thoroughly and carefully read this instruction sheet before operating your S&C Pad-Mounted Gear. If you do not understand any portion of this instruction sheet and need assistance, contact your nearest S&C Sales Office or S&C Authorized Distributor, or call S&C Headquarters at (312) 338-1000, Monday through Friday between 8:30 AM and 5:00 PM Central Standard Time. (In Canada, call S&C Electric Canada at (416) 249-9171.) Replacement Instructions and Labels If you need additional copies of this instruction sheet, contact your nearest S&C Sales Office or S&C Authorized Distributor, or call S&C Headquarters. It is important that any missing, damaged, or faded labels on the equipment be replaced immediately. Replacement labels are available by contacting your nearest S&C Sales Office, S&C Authorized Distributor, S&C Headquarters, or S&C Canada. Ç NOTICE “NOTICE” identifies important procedures or requirements that, if not followed, can result in product or property damage if instructions are not followed. INSTRUCTION SHEET s S&C ELECTRIC COMPANY 663-503 Page 3 of 35 August 14, 1995 S&C Source-Transfer PMH Pad-Mounted Gear With Micro-AT® Control Outdoor Distribution (14.4 kv and 25 kv) SAFETY PRECAUTIONS Ç DANGER Pad-mounted gear contains high voltage. Failure to observe the precautions below will result in serious injury or death. Some of these precautions may differ from company operating procedures and rules. Where a discrepancy exists, users should follow their company’s operating procedures and rules. 1. QUALIFIED PERSONS. Access to pad-mounted gear must be restricted only to qualified persons. See “Qualified Persons” on page 2. 2. SAFETY PROCEDURES. Always follow safe operating procedures and rules. 3. PERSONAL PROTECTIVE EQUIPMENT. Always use suitable protective equipment such as rubber gloves, rubber mats, hard hats, safety glasses, and flash clothing in accordance with safe operating procedures and rules. 4. SAFETY LABELS. Do not remove or obscure any of the “CAUTION,” “WARNING,” or “DANGER” labels. 5. KEY INTERLOCKS. v If optional key interlocks were furnished, they must be in place. v Check the operating sequence of key interlocks to verify proper sequencing. v After the pad-mounted gear is installed, either: (1) destroy the extra set of keys or (2) make them accessible only to qualified persons. This will maintain the integrity of the key-interlock scheme. v Key interlocks are not security locks and are not substitutes for padlocks. 6. MECHANICAL CABLE INTERLOCKS. If optional mechanical cable interlocks were furnished, periodically verify that these interlocks are functional. These interlocks prevent operation of the Mini-Rupter Switch when the associated switch-compartment door is open. 7. OPENING DOORS. Do not force doors open. Forcing a door open can damage the latching mechanism. If optional key interlocks are furnished, correctly position the interlocks so the doors can be opened. 8. CLOSING AND LOCKING DOORS. v Doors must be securely closed and latched, with padlocks in place at all times unless work is being performed inside the enclosure. v Do not close a door on a fuse in the open position. The door will strike the fuse pull ring which will interfere with door closing. The door may be closed if the fuse is removed from the mounting. 9. ENERGIZED TERMINALS. Always assume that both sets of power terminals on any Mini-Rupter Switch or fuse are energized unless proved otherwise by test, by visual evidence of open-circuit conditions on both sets of terminals, or by observing that both sets of terminals are grounded. 10. BACKFEED. Mini-Rupter Switches, switch terminals, fuses, and fuse mountings (Uni-Rupter, load-side hinge, and terminals) may be energized by backfeed. 11. DE-ENERGIZING. Before touching any device that is to be inspected, replaced, serviced, or repaired in the high-voltage compartments, always disconnect Mini-Rupter Switches, fuses, and other devices such as voltage sensors from all power sources (including backfeed) and control sources, test for voltage, and properly ground. 12. TESTING. Test for voltage on both sets of power terminals of any Mini-Rupter Switch or fuse using proper high-voltage test equipment before touching any device that is to be inspected, replaced, serviced, or repaired in the high-voltage compartments. 13. GROUNDING. v Make sure that the pad-mounted gear enclosure is properly grounded to the station or facility ground. v After the gear has been completely disconnected from all sources of power and tested for voltage, install suitable grounding cables in all compartments before touching any device that is to be inspected, replaced, serviced, or repaired in the high-voltage compartments. 14. SWITCH POSITION. v Always confirm the open/close position of the Mini-Rupter Switches by visually observing the position of the switch blades. v Switches and switch terminals may be energized by backfeed. v Switches and switch terminals may be energized in any position. 15. FUSE POSITION. Fuses and fuse mountings (UniRupter, load-side hinge, and terminals) may be energized by backfeed even when the fuse is in the fully open position. CONTINUED 663-503 Page 4 of 35 August 14, 1995 ➡ INSTRUCTION SHEET S&C ELECTRIC COMPANY s SAFETY PRECAUTIONS — Continued Ç DANGER — Continued Pad-mounted gear contains high voltage. Failure to observe the precautions below will result in serious injury or death. Some of these precautions may differ from company operating procedures and rules. Where a discrepancy exists, users should follow their company’s operating procedures and rules. 16. S&C GRAPPLER. v The Grappler (Catalog Number 4423) is the S&C fuse-handling fitting supplied with each unit equipped for fuses. v The Grappler improves grip, balance, and control of fuses during handling. v Always use the S&C Grappler attached to a suitable universal pole (1¹⁄₄ diameter) to handle barriers and to install, remove, open, or close fuses. The universal pole must be at least 4 feet long (S&C Catalog Number 4451R2-E, or equal) for 14.4-kv gear or at least 6 feet long (S&C Catalog Number 4452R2-E, or equal) for 25-kv gear. 17. MAINTAINING PROPER CLEARANCE. v When working in the high-voltage compartments, always maintain proper clearance from energized components. v When handling barriers or when installing, removing, opening, or closing fuses, always use an S&C Grappler attached to a suitable universal pole (see 16 above). v Switch Side: These barriers are intended for temporary use to isolate the blades of the Mini-Rupter Switch from the main contacts while work is being performed. v Fuse Side: These barriers are intended for temporary use to isolate the fuse from the contacts of UniRupter while work is being performed. 19. CLOSING FUSES. Closing a fuse into a faulted circuit will cause a loud noise, a flash of light at the UniRupter contacts, and the fuse to blow. Closing a fuse into a faulted circuit is always a possibility. When closing a fuse, always turn your face away then use a swift, unhesitating thrust since the closing operation is completely operator dependent. With Uni-Rupter, a fuse can be closed into a fault current once or twice as specified in Appendix C, and the Uni-Rupter will remain operable and able to carry and interrupt rated current. 18. FRONT BARRIERS. v Always use an S&C Grappler attached to a suitable universal pole to handle barriers in the high-voltage compartments. v Do not leave dual-purpose front barriers in the “slide-in” position for more than one week. If the barriers are left in the “slide-in” position for an extended period of time, there is the possibility of corona discharge to the barriers. Prolonged exposure to corona discharge can damage the barriers and result in a flashover, injury, and equipment damage. OPERATING DESCRIPTION Refer to S&C Instruction Sheet 515-500 for an operating description of the Micro-AT Source-Transfer Control. Remote Indication The optional remote-indication feature (Catalog Number Suffix “-Y4”) includes isolated contacts wired to a terminal block for user’s external connection to remote indicating devices. Isolated contacts are provided for remotely monitoring the presence of source voltages; the position of the manual/automatic operation selector switch; and the status of the “ready” indicating lamp, “event” indicating lamp, and overcurrent-lockout circuit (if furnished). Remote indicating devices and their control power are to be provided by the user and installed in accordance with the manufacturer’s instructions. INSTRUCTION SHEET s S&C ELECTRIC COMPANY 663-503 Page 5 of 35 August 14, 1995 S&C Source-Transfer PMH Pad-Mounted Gear With Micro-AT® Control Outdoor Distribution (14.4 kv and 25 kv) COMPONENTS Figures 1 through 4 which follow illustrate many of the basic components and features of S&C Source-Transfer Pad-Mounted Gear. Before proceeding with the remainder of the instructions, it is recommended that these figures be reviewed to gain familiarity with the various components and locations. Operator target indicates whether stored-energy operator is in switch-open or switch-closed position and whether quick-make quick-break mechanism is charged or discharged Open/close pushbuttons Emergency-trip access cover Charging shaft Remote-control receptacle (Catalog Number Suffix “-C11”) Dual-purpose manual handle Decoupler handle Switch-position target Operation counter Operation selector Micro-AT Source-Transfer Control Terminal-block compartment Decoupler indicator Bolted cover provides access to input plug and shorting receptacle for Micro-AT control Figure 1. Low-voltage control compartment. 663-503 Page 6 of 35 August 14, 1995 INSTRUCTION SHEET S&C ELECTRIC COMPANY s COMPONENTS — Continued Left source voltage indicating lamp Automatic-transfer “ready” indicating lamp Overcurrent-lockout indicating lamp and reset key (furnished with optional overcurrentlockout feature, Catalog Number Suffix “-Y2”) Right source voltage indicating lamp Manual/automatic operation selector switch. When in “MANUAL,” prevents an automatic source transfer while permitting manual operation using open/close pushbuttons Two-line 24-character backlit liquid-crystal display (LCD) Menu keys Last and next item keys Test keys for simulating overcurrent and loss of voltage on left source Test keys for simulating overcurrent and loss of voltage on right source Keypad Figure 2. S&C Micro-AT Source-Transfer Control. INSTRUCTION SHEET s S&C ELECTRIC COMPANY 663-503 Page 7 of 35 August 14, 1995 S&C Source-Transfer PMH Pad-Mounted Gear With Micro-AT® Control Outdoor Distribution (14.4 kv and 25 kv) COMPONENTS — Continued Remote-indication wiring provided with optional remoteindication feature (Catalog Number Suffix “-Y4”), leads to a terminal block for user’s connections Supervisory control wiring (not shown) provided with optional supervisory-control feature (Catalog Number Suffix “-Y6”), also leads to a terminal block for user’s connections Voltage limiters Input plug (signal-voltage, control-voltage, and currentsensing input circuits) Input receptacle Shorting receptacle Figure 3. Access panel removed showing input plug, input receptacle, and shorting receptacle of S&C Micro-AT SourceTransfer Control. 663-503 Page 8 of 35 August 14, 1995 INSTRUCTION SHEET S&C ELECTRIC COMPANY s COMPONENTS — Continued Left-hand door retainer—rotate latch upward to open door. To secure left-hand door closed, rotate latch downward over stop mounted on outer edge of door Dual-purpose front barriers S&C Uni-Rupter Viewing window for visible verification of switch position is removable for phasing. To remove window, loosen wing-head screws and lift window off alignment bolts S&C Mini-Rupter Switch Interphase and end barriers S&C Power Fuse (Fault Fiter Electronic Power Fuse shown) S&C Voltage Sensor Ground studs Current sensors furnished for attachment to each entrance cable when optional overcurrent-lockout feature (Catalog Number Suffix “-Y2”) is included Figure 4. Switch and fuse compartments. INSTRUCTION SHEET s S&C ELECTRIC COMPANY 663-503 Page 9 of 35 August 14, 1995 S&C Source-Transfer PMH Pad-Mounted Gear With Micro-AT® Control Outdoor Distribution (14.4 kv and 25 kv) MINI-RUPTER SWITCHES Ç WARNING 1. To prevent an automatic operation when decoupling or coupling an operator to a switch, during manual charging of an operator, or when manually operating a switch, place the manual/automatic operation selector switch located on the faceplate of the Micro-AT Source-Transfer Control in “MANUAL.” 2. Do not perform any switching operations if the source-transfer control is in the lockout mode as indicated by illumination of the “LOCKOUT” lamp. See Figure 2. For such cases, see “OvercurrentLockout Condition” under the “OPERATING DESCRIPTION” in S&C Instruction Sheet 515-500. 3. If the gear is energized and paralleling of sources is not permitted, decouple both stored-energy operators (see “Decoupling” below) to avoid temporary service interruptions when manually operating the gear. Switching operations will result in temporary service interruptions if stored-energy operators are coupled. 4. Due to operating errors, the stored-energy operator’s quick-make quick-break mechanism may stall in a partially discharged state. The conditions which will cause this mechanism to stall, as well as instructions for restoring the operator to the normal latched-open condition after a stall, are listed under “IF OPERATOR STALLS . . .” on page 26. 5. Do not assume that the operator position necessarily indicates the open or closed position of the Mini-Rupter Switch. Upon completion of an opening or closing operation, check to be sure that the following conditions exist: • The operator target (see Figure 1) signals “OPERATOR IN SWITCH-OPEN POSITION” or “OPERATOR IN SWITCH-CLOSED POSITION” to indicate that the switch operator has moved through a complete operation. • The switch-position target (see Figure 1) which signals “SWITCH OPEN” or “SWITCH CLOSED,” is in agreement with the operator target. • The switch position, as verified by visual check of the switch-blade position, is in agreement with the switch-position target. A viewing window is provided in the switch compartment to allow positive visual verification of switch-blade position (see Figure 4). • The operator target (see Figure 1) signals “OPERATOR CHARGED” to indicate that the operator is ready for the next operation. 6. To prevent all electrical and mechanical operations, padlock the operation selector in the “LOCK POSITION.” This will also prevent motor charging of the stored-energy operator if system operating procedures require that the quick-make quick-break mechanism remain discharged—and source voltage is present. Decoupling Coupling Decoupling is accomplished using the decoupler handle. See Figure 5. When decoupled, the stored-energy operator may be operated without affecting the position of the associated Mini-Rupter Switch. Moreover, when decoupled, the Mini-Rupter Switch is prevented from moving by a mechanical device which locks the switch drive-shaft. To decouple the stored-energy operators, first place the manual/automatic operation selector switch on the faceplate of the S&C Micro-AT Source-Transfer Control in “MANUAL.” For each stored-energy operator, grasp the decoupler handle and press down on the coupledposition latch to release the handle. Then move the handle upward to the “DECOUPLED” position. Make sure that the handle is fully latched in the decoupled position. While an operator is decoupled, the automatictransfer “ready” indicating lamp on the faceplate of the Micro-AT control will not light—a reminder of the decoupled condition. See Figure 2. To couple the stored-energy operators, first place the manual/automatic operation selector switch on the faceplate of the Micro-AT control in ”MANUAL.” Then make sure that the stored-energy operators are in the same position (open or closed) as their associated MiniRupter Switches by observing the switch-position and operator targets. See Figure 1. If required, use the open/close pushbuttons (provided control power is available) to reposition the operator(s). For each operator, grasp the decoupler handle and press down on the decoupled-position latch to release the handle. Then move the handle downward to the “COUPLED” position. Make sure that the handle is fully latched in the coupled position. An attempt to operate a switch that is not completely coupled (or decoupled) will cause the operator mechanism to stall. 663-503 Page 10 of 35 August 14, 1995 INSTRUCTION SHEET S&C ELECTRIC COMPANY s MINI-RUPTER SWITCHES — Continued Automatic Switch Operation High-speed quick-make quick-break operation is provided by stored-energy operators which, when solenoid tripped in response to control signals from the S&C Micro-AT Source-Transfer Control, automatically open and close the Mini-Rupter Switches. After each trip operation, the operators automatically charge when voltage is present on the associated source—ready for the next operation. For automatic switch operation, the manual/automatic operation selector switch on the Micro-AT control must be in “AUTOMATIC.” See Figure 2. The Micro-AT control will not function automatically if one operator is coupled and the other is decoupled. Field programming and operation of the Micro-AT control is covered in S&C Instruction Sheet 515-500. Nonautomatic Switch Operation If Control Power Is Available: To manually operate the stored-energy operator’s quick-make quick-break mechanism—and (if coupled) to open or close a Mini-Rupter Switch—place the manual/automatic operation selector switch in “MANUAL” and press the associated open/close pushbutton. See Figure 1. After each trip operation, the quick-make quick-break mechanism automatically charges Figure 5. Decoupler handle being moved upward to decouple switch from associated switch operator. when voltage is present on the associated source. The charging operation takes approximately 25 seconds. If Control Power Is Lost and Operator Is Charged: To manually operate the stored-energy operator’s quickmake quick-break mechanism—and (if coupled) to open or close a Mini-Rupter Switch—insert the small keyed end of the dual-purpose manual handle into the groove of the tripping shaft, behind the cover labeled “EMERGENCY TRIP,” and turn in the direction indicated to effect desired operation. See Figure 6. If Control Power Is Lost and Operator Is Discharged: Manually charge the stored-energy operator’s quick-make quick-break mechanism as described under “Charging Operator (Nonelectrical)” below. Then proceed as just described under “If Control Power Is Lost and Operator Is Charged.” Charging Operator (Nonelectrical) The dual-purpose manual handle is used to manually charge the stored-energy operator’s quick-make quickbreak mechanism (required only in the event that control power has been lost). See Figure 7. Keep the chargingshaft access port open by holding the operation selector in the “CHARGING POSITION.” While the operation Figure 6. Dual-purpose manual handle inserted in groove of shaft for emergency manual switching if control power is lost. Figure 7. Dual-purpose manual handle on the charging shaft. INSTRUCTION SHEET s S&C ELECTRIC COMPANY 663-503 Page 11 of 35 August 14, 1995 S&C Source-Transfer PMH Pad-Mounted Gear With Micro-AT® Control Outdoor Distribution (14.4 kv and 25 kv) MINI-RUPTER SWITCHES — Continued selector is in the “CHARGING POSITION,” the control circuit is disconnected to prevent manual or automatic electrical operation (charging or tripping) in the event that control power is restored; and the emergency-trip port is mechanically blocked to prevent a manual mechanical trip operation. While holding the port open, insert the large notched end (with recessed bolt) of the dual-purpose manual handle and secure it to the end of the charging shaft by turning the knurled knob clockwise 8 to 9 turns until firm resistance is felt. To charge the mechanism, grasp the tubular portion of the handle and, while pivoting the handle a few degrees, push in to engage the charging shaft. At the same time, rotate the handle as far as it will go (approximately 120°) in the appropriate direction. The “OPERATOR CHARGED” target will appear in the indicator window. After the charging operation, loosen the knurled knob and remove the handle. The operation selector will springreturn to the “OPERATING POSITION.” Front Barriers Before proceeding with the instructions on handling the front barriers, refer to the “DANGER” on pages 4 and 5, and the “WARNING” on page 10. Figure 8. Dual-purpose front barrier for switch in its normal, suspended position. 663-503 Page 12 of 35 August 14, 1995 Ç DANGER When working in the high-voltage compartments, always maintain proper clearance from energized components. Failure to maintain proper clearance will result in serious injury or death. Always use an S&C Grappler (Catalog Number 4423) attached to a suitable universal pole (1 ¹⁄₄ inches in diameter) to handle barriers and to install, remove, open, or close fuses. The universal pole must be at least 4 feet long (S&C Catalog Number 4451R2-E, or equal) for 14.4-kv gear or at least 6 feet long (S&C Catalog Number 4452R2-E, or equal) for 25-kv gear. Place the dual-purpose front barrier in the “slide-in” position whenever the Mini-Rupter Switch is open. When the barrier is in the “slide-in” position, the switch blades are isolated from the main contacts. This also keeps the blades from closing if, for any reason, the Mini-Rupter Switch is operated. To insert the barrier in the “slide-in” position, use an S&C Grappler™ attached to and in line with a suitable universal pole. Figures 8 through 10 show the suggested insertion method. The Grappler prongs are pointed upward when lifting the front barrier. Figure 9. Grappler being used to lift barrier. Note that door holder is in place and adjacent door is bolted closed to reduce exposure to high voltage. INSTRUCTION SHEET S&C ELECTRIC COMPANY s MINI-RUPTER SWITCHES — Continued Ç WARNING Do not leave dual-purpose front barriers in the “slide-in” position for more than one week. These barriers are intended for temporary use to isolate the blades of the Mini-Rupter Switch from the main contacts while work is being performed. If the barriers are left in the “slidein” position for an extended period of time, there is the possibility of corona discharge to the barriers. Prolonged exposure to corona discharge can damage the barriers and result in a flashover, injury, and equipment damage. Ç NOTICE Before closing a Mini-Rupter Switch, remove the dualpurpose front barrier from the “slide-in” position. Closing a switch on the barrier will block the switch blades and result in a stalled condition. If the Mini-Rupter Switch is closed with the front barrier in the “slide-in” position, the switch blades will be blocked and the stored-energy operator will stall in a partially closed position. To correct this condition, follow the directions under “IF OPERATOR STALLS . . .” on page 26. To restore the dual-purpose front barrier to the normal suspended position, use an S&C Grappler attached to a suitable universal pole. Slowly and carefully withdraw the barrier with the Grappler prongs pointed upward (as shown in Figure 10) so that, as it clears the “slide-in” position, the holes in the barrier catch on the hooks on the gear. Then lower the barrier to its normal, suspended position. (If, for any reason, the barrier was completely removed from the enclosure, a suggested method of placing it in its normal, suspended position is shown in Figure 11. Note that the barrier is supported on the Grappler prongs and held there by engagement of the lifting ring with the Grappler cone. Place the barrier on the hooks of the gear, and lower the barrier to its suspended position.) Figure 10. Grappler, after lifting and pivoting the barrier, is used to lower it into the “slide-in” position. Also shows Grappler being used to return the barrier to its normal, suspended position. INSTRUCTION SHEET s S&C ELECTRIC COMPANY 663-503 Page 13 of 35 August 14, 1995 S&C Source-Transfer PMH Pad-Mounted Gear With Micro-AT® Control Outdoor Distribution (14.4 kv and 25 kv) MINI-RUPTER SWITCHES — Continued Figure 11. Alternate method of replacing front barrier using Grappler. Inset shows barrier being supported on Grappler prongs. 663-503 Page 14 of 35 August 14, 1995 INSTRUCTION SHEET S&C ELECTRIC COMPANY s FUSING S&C Source-Transfer PMH Pad-Mounted Gear is furnished with S&C Fuse Mountings with Uni-Rupter that accommodate S&C Type SML-20 Power Fuses, S&C Type SML-4Z Power Fuses, or S&C Fault Fiter Electronic Power Fuses. Fault Fiter Electronic Power Fuse Mountings also accommodate a variety of current-limiting fuses. Ç WARNING When selecting current-limiting fuses, the voltage rating of the fuses must conform to the recommendations in Appendix E. Failure to conform to these recommendations can result in a flashover, injury, and equipment damage. Assembling the Fuse S&C Power Fuses Install an SMU-20 Fuse Unit into each set of end fittings, an SM-4 Refill Unit into each holder, or a Fault Fiter Interrupting Module and Control Module into each holder, in accordance with the instruction sheet furnished with the fuse unit, refill unit, or interrupting module. Installing the Fuse in the Mounting Follow the instructions found under “Installing and Closing the Fuse” on pages 16 through 19. Warranty Qualifications The standard warranty contained in seller’s standard conditions of sale (as set forth in Price Sheet 150) does not apply to S&C Source-Transfer PMH Pad-Mounted Gear where fuse units, fuse-unit end fittings, holders, refill units, or switch blades of other than S&C manufacture are used in conjunction with S&C SML Mountings. Nor does it apply to S&C Source-Transfer PMH Pad-Mounted Gear where other than Fault Fiter Electronic Power Fuses, S&C Switch Blades, or the current-limiting fuses listed in Appendix E are used in conjunction with Fault Fiter Electronic Power Fuse Mountings and S&C Holders designed therefor, or when current-limiting fuses are applied other than as set forth under “Recommended Voltage Ratings” for current-limiting fuses in Appendix E. Current-Limiting Fuses S&C Holders for current-limiting fuses are designed for use in pad-mounted gear models that include mountings for Fault Fiter Electronic Power Fuses. These holders will accommodate the current-limiting fuses listed in Appendix E. For instructions on installing current-limiting fuses in current-limiting fuse holders, refer to S&C Instruction Sheet 660-500. INSTRUCTION SHEET s S&C ELECTRIC COMPANY 663-503 Page 15 of 35 August 14, 1995 S&C Source-Transfer PMH Pad-Mounted Gear With Micro-AT® Control Outdoor Distribution (14.4 kv and 25 kv) SWITCHING WITH UNI-RUPTER Installing and Closing the Fuse Before proceeding with the instructions on installing and closing the fuse,d refer to the “DANGER” on pages 4 and 5. Ç DANGER When working in the high-voltage compartments, always maintain proper clearance from energized components. Failure to maintain proper clearance will result in serious injury or death. Always use an S&C Grappler (Catalog Number 4423) attached to a suitable universal pole (1 ¹⁄₄ inches in diameter) to handle barriers and to install, remove, open, or close fuses. The universal pole must be at least 4 feet long (S&C Catalog Number 4451R2-E, or equal) for 14.4-kv gear or at least 6 feet long (S&C Catalog Number 4452R2-E, or equal) for 25-kv gear. Use an S&C Grappler attached to and in line with a suitable universal polel to perform the procedures listed below: 1. Open the appropriate fuse-compartment door and secure it with the door holder. See Figure 12. The adjacent compartment door should be closed and latched to minimize exposure to high voltage. 2. If optional inner barrier panels (Catalog Number Suffix “-G7”) are furnished, loosen the pentahead bolts and remove the panel. Door holder Then remove only the dual-purpose front barrier associated with the fuse mounting into which the fuse is to be installed. See Figure 13. Insert the barrier into the “slide-in” position using the Grappler as illustrated in Figure 14. Note that the barrier is supported on the Grappler prongs and held there by engagement of the lifting ring with the Grappler cone. Ç WARNING Do not leave dual-purpose front barriers in the “slide-in” position for more than one week. These barriers are intended for temporary use to isolate the fuse from the contacts of the Uni-Rupter while work is being performed. If the barriers are left in the “slide-in” position for an extended period of time, there is the possibility of corona discharge to the barriers. Prolonged exposure to corona discharge can damage the barriers and result in a flashover, injury, and equipment damage. d Although the operations as described in this section often refer simply to “fuses,” the procedures apply to S&C Type SML-20 and SML-4Z Power Fuses, S&C Fault Fiter Electronic Power Fuses, and current-limiting fuses used in Fault Fiter Electronic Power Fuse Mountings with UniRupter. l If the enclosure is furnished with an optional base spacer (or is attached to a higher than normal mounting pad), it may be desirable, for easier handling at the increased height, to reposition the Grappler on the universal pole at a favorable angle. S&C Grappler in storage position Storage rack for S&C SMU-20 Fuse Units or SM-4 Refill Units Figure 12. Dual-purpose front barriers for fuses in their normal, suspended positions. Note that door holder is in place. 663-503 Page 16 of 35 August 14, 1995 Figure 13. Removing or replacing dual-purpose front barrier with the S&C Grappler. INSTRUCTION SHEET S&C ELECTRIC COMPANY s SWITCHING WITH UNI-RUPTER — Continued 3. For all fuses except 25-kv Fault Fiter Electronic Power Fuses, install a fuse into its hinge as follows: (a) Position the Grappler cone in the fuse pull ring and cradle the fuse in the Grappler prongs. See inset of Figure 15. (b) Grasp the universal pole with both hands (approximately 2 feet apart), with one hand at the opposite end of the pole from the Grappler. (c) Lift the fuse and lower it into its hinge. See Figure 15. Make sure that the fuse is securely seated in the hinge; then disengage the Grappler from the fuse. See Figure 16. 4. For 25-kv Fault Fiter Electronic Power Fuses, deenergize, test, and properly ground the mounting in accordance with safe operating procedures and rules, and then install the fuse into its mounting by hand using suitable protective equipment. Ç NOTICE Do not close a door on a fuse in the open position. The door will strike the fuse pull ring which will interfere with door closing. The door may be closed if the fuse is removed from its mounting. Ç DANGER Keep the fuse away from the Uni-Rupter contacts when installing the fuse into its hinge. Touching the contacts will close the circuit which can cause a flashover and serious injury. Always place the dual-purpose front barrier in the “slide-in” position whenever a fuse is open or is being removed from or installed into its hinge. Figure 14. Inserting dual-purpose front barrier into the “slide-in” position using Grappler. Figure 15. Installing fuse using the Grappler. Inset shows close-up of Grappler in position to install the fuse. INSTRUCTION SHEET s S&C ELECTRIC COMPANY 663-503 Page 17 of 35 August 14, 1995 S&C Source-Transfer PMH Pad-Mounted Gear With Micro-AT® Control Outdoor Distribution (14.4 kv and 25 kv) SWITCHING WITH UNI-RUPTER — Continued 5. Use the Grappler to remove the dual-purpose front barrier from the “slide-in” position. See Figure 17. Ç DANGER Closing a fuse into a faulted circuit will cause a loud noise, a flash of light at the Uni-Rupter contacts, and the fuse to blow. Closing a fuse into a faulted circuit is always a possibility. When closing a fuse, always turn your face away then use a swift, unhesitating thrust since the closing operation is completely operator dependent. With Uni-Rupter, a fuse can be closed into a fault current once or twice as specified in Appendix C, and the Uni-Rupter will remain operable and able to carry and interrupt rated current. Figure 16. Fuse installed in mounting in the open position. 663-503 Page 18 of 35 August 14, 1995 6. With the Grappler prongs pointed downward, insert the longer prong into the pull ring of the fuse. See inset of Figure 18. Then with one’s face turned away, close the fuse with a swift, unhesitating thrust. See Figure 18. Remove the Grappler from the pull ring. Ç NOTICE After removing the Grappler from the pull ring, make sure that complete fuse closure was attained by pushing against the fuse with the Grappler. Failure to completely close the fuse can result in damage to the Uni-Rupter. 7. Use the Grappler to hang the dual-purpose front barrier in its normal, suspended position. See Figure 13. Also install the optional inner barrier panel, if furnished. 8. Close and latch the doors and install a padlock. Pull on the doors to verify that they are securely latched. Figure 17. Removing dual-purpose front barrier from the “slide-in” position using Grappler. INSTRUCTION SHEET S&C ELECTRIC COMPANY s SWITCHING WITH UNI-RUPTER — Continued Figure 18. Closing the fuse. Inset on right shows close-up of Grappler in position to close the fuse. Top inset shows close-up of Uni-Rupter with the fuse fully closed. INSTRUCTION SHEET s S&C ELECTRIC COMPANY 663-503 Page 19 of 35 August 14, 1995 S&C Source-Transfer PMH Pad-Mounted Gear With Micro-AT® Control Outdoor Distribution (14.4 kv and 25 kv) SWITCHING WITH UNI-RUPTER — Continued Ç WARNING A Note on Single-Pole Switching In single-pole switching of ungrounded-primary threephase transformers or banks (or single-phase transformers connected line-to-line), circuit connections or parameters may, in some cases, produce excessive overvoltages. In particular, for the following applications above 22 kv, single-pole switching by any means—including Uni-Rupter—should be performed only under the conditions stated in italics: • Switching unloaded or lightly loaded delta-connected or ungrounded-primary wye-wye connected three-phase transformers or banks (or line-to-line connected single-phase transformers), rated 150 kva or less three-phase, or 50 kva or less singlephase—or of any kva rating when combined with unloaded cables or lines—where maximum system Opening and Removing the Fuse Before proceeding with the instructions on opening and removing the fuse, refer to the “DANGER” on pages 4 and 5. operating voltage exceeds 22 kv. Single-pole switching should be performed only if each phase is carrying 5% load or more, or if the transformer or bank is temporarily grounded at the primary neutral during switching. • Switching loaded or unloaded ungrounded-primary wye-delta connected three-phase transformers or banks—alone or combined with unloaded cables or lines—where maximum system operating voltage exceeds 22 kv. Single-pole switching should be performed only if each phase is carrying 5% load or more and if the lighting-load phase is always switched open first (or switched closed last); or if the transformer or bank is temporarily grounded at the primary neutral during switching. 3. With the Grappler prongs pointed downward, insert the longer prong into the pull ring of the fuse. See Figure 19. Ç DANGER When working in the high-voltage compartments, always maintain proper clearance from energized components. Failure to maintain proper clearance will result in serious injury or death. Always use an S&C Grappler (Catalog Number 4423) attached to a suitable universal pole (1 ¹⁄₄ inches in diameter) to handle barriers and to install, remove, open, or close fuses. The universal pole must be at least 4 feet long (S&C Catalog Number 4451R2-E, or equal) for 14.4-kv gear or at least 6 feet long (S&C Catalog Number 4452R2-E, or equal) for 25-kv gear. Use an S&C Grappler attached to and in line with a suitable universal pole to perform the procedures listed below: 1. Open the appropriate fuse-compartment door and secure it with the door holder. See Figure 12. The adjacent door should be closed and latched to minimize exposure to high voltage. 2. If optional inner barrier panels (Catalog Number Suffix “-G7”) are furnished, loosen the pentahead bolts and remove the panel. Then remove only the barrier associated with the fuse to be opened, using the Grappler for this purpose. See Figure 13. 663-503 Page 20 of 35 August 14, 1995 Figure 19. Grappler, as positioned for opening stroke, with longer prong inserted in the fuse pull ring. INSTRUCTION SHEET S&C ELECTRIC COMPANY s SWITCHING WITH UNI-RUPTER — Continued 4. Pull the fuse vigorously through its full travel without hesitation at any point. See Figure 20. A downward force should be maintained on the universal pole through the fuse-opening operation to counteract any tendency the fuse may have to bounce toward the closed position. NOTE: The Uni-Rupter is designed to require a hard pull to unlatch the fuse, thus reducing the possibility of an incomplete opening operation. 5. Remove the Grappler from the fuse pull ring. Ç DANGER The fuse and fuse mounting (Uni-Rupter, load-side hinge, and terminals) may be energized by backfeed even when the fuse is in the fully open position. Always assume that both terminals of a fuse are energized unless proved otherwise by test, by visual evidence of open-circuit conditions on both terminals, or by observing that both terminals are grounded. Failure to follow these precautions can result in serious injury or death. Figure 20. Opening the fuse. Ç NOTICE Do not close a door on a fuse in the open position. The door will strike the fuse pull ring which will interfere with door closing. The door may be closed if the fuse is removed from its mounting. 6. Place the dual-purpose front barrier associated with the fuse to be removed in the “slide-in” position. Use the Grappler for this, as illustrated in Figure 21. Note that the barrier is supported on the Grappler prongs and held there by engagement of the lifting ring with the Grappler cone. Ç WARNING Do not leave dual-purpose front barriers in the “slidein” position for more than one week. These barriers are intended for temporary use to isolate the fuse from the contacts of the Uni-Rupter while work is being performed. If the barriers are left in the “slide-in” position for an extended period of time, there is the possibility of corona discharge to the barriers. Prolonged exposure to corona discharge can damage the barriers and result in a flashover, injury, and equipment damage. Figure 21. Inserting dual-purpose front barrier into the “slide-in” position using Grappler. INSTRUCTION SHEET s S&C ELECTRIC COMPANY 663-503 Page 21 of 35 August 14, 1995 S&C Source-Transfer PMH Pad-Mounted Gear With Micro-AT® Control Outdoor Distribution (14.4 kv and 25 kv) SWITCHING WITH UNI-RUPTER — Continued 7. For all fuses except 25-kv Fault Fiter Electronic Power Fuses, remove the fuse from its hinge as follows: (a) Grasp the universal pole with both hands (approximately 2 feet apart), with one hand at the opposite end of the pole from the Grappler. (b) Position the Grappler cone in the fuse pull ring and cradle the fuse in the Grappler prongs. See Figure 22. (c) Stand in a normal, upright position facing the universal pole. Move the pole forward until resistance between the Grappler and the fuse is felt (approximately 2 inches). Then remove the fuse from its hinge with a forward and upward lifting motion. See Figure 23. Ç DANGER 8. For 25-kv Fault Fiter Electronic Power Fuses, deenergize, test, and properly ground the mounting in accordance with safe operating procedures and rules, and then remove the fuse from its mounting by hand using suitable protective equipment. 9. Hang the dual-purpose front barrier in its normal, suspended position using the Grappler. See Figure 13. Also install the optional inner barrier panel, if furnished. Then close and latch the doors, and padlock securely. Pull on the doors to verify that they are securely latched. Ç WARNING Always store fuses in a clean, dry location. Do not store end fittings, holders, interruping modules, or currentlimiting fuses in the enclosure. Keep the fuse away from the Uni-Rupter contacts when removing the fuse from its hinge. Touching the contacts will close the circuit which can cause a flashover and serious injury. Always place the dual-purpose front barrier in the “slide-in” position whenever a fuse is open or is being removed from or installed into its hinge. Figure 22. Grappler positioned for fuse removal. 663-503 Page 22 of 35 August 14, 1995 Figure 23. Removing fuse using the Grappler. INSTRUCTION SHEET S&C ELECTRIC COMPANY s RE-FUSING How to Detect and Replace a Blown Fuse Open the appropriate fuse-compartment door and secure it with the door holder. Ç WARNING To minimize exposure to high voltage, close and latch the adjacent door. Also remove the dual-purpose front barrier (using the Grappler) or inner barrier panel, if furnished. Ç DANGER When working in high-voltage compartments, always maintain proper clearance from energized components. Failure to maintain proper clearance will result in serious injury or death. S&C Power Fuses From a safe distance, observe the blown-fuse target for the fuse type furnished (refer to Figure 24): • SML-20 Power Fuse or Fault Fiter Electronic Power Fuse—A red blown-fuse target projects from the top of the SML-20 Power Fuse upper end fitting or the Fault Fiter Holder when the fuse has operated . . . making it easy to check the fuse condition with the fuse in the closed position. The blown-fuse target retracts within the end fitting or holder when the blown fuse unit or interrupting module is replaced. • SML-4Z Power Fuse—A fluorescent orange target in the translucent SML-4Z Holder moves to the “BLOWN” indicator window when the fuse operates, permitting a positive visual check of fuse condition without removing the fuse from its mounting. The target fluoresces when illuminated. NOTE ON HANDLING: The current-design upper end fitting for use in SML-20 Power Fuses, and the Fault Fiter Holder employ a free-floating blown-fuse target which can move (by force of gravity) into the “BLOWN” position should the fuse be inverted during handling. Fuse condition can be verified by returning the fuse to the upright position. If the fuse is blown, the target will remain in the extended (projecting) position. Remove the blown fuse from its mounting following the instructions found under “Opening and Removing the Fuse” on pages 20 through 22. Then follow the instructions for replacing blown SMU-20 Fuse Units, SM-4 Refill Units, or Fault Fiter Interrupting Modules (as applicable) that are provided with each new fuse unit, refill unit, or interrupting module. INSTRUCTION SHEET s S&C ELECTRIC COMPANY 663-503 Page 23 of 35 August 14, 1995 S&C Source-Transfer PMH Pad-Mounted Gear With Micro-AT® Control Outdoor Distribution (14.4 kv and 25 kv) RE-FUSING — Continued Current-Limiting Fuses To find the blown fuses, remove each fuse in turn from its mounting (the target cannot be seen while the fuse is in its mounting), following the instructions found under “Opening and Removing the Fuse” on pages 20 through 22. Then inspect the fuse and check for a blown-fuse target. NOTE: Following a two- or three-phase fault at a three-phase installation, any unblown fuses that carried the fault current should also be replaced. For instructions on replacing current-limiting fuses in S&C Holders, refer to S&C Instruction Sheet 660-500. S&C Holders will accommodate the current-limiting fuses listed in Appendix E. Installing the Fuse in the Mounting Follow the instructions found under “Installing and Closing the Fuse” on pages 16 through 19. Red target projects from top of upper end fitting when fuse has operated Red target projects from top of holder when fuse has operated Fluorescent-orange target appears in “BLOWN” indicator window when fuse has operated (visible through translucent holder) SML-20 Power Fuse SML-4Z Power Fuse Fault Fiter Electronic Power Fuse Figure 24. Blown-fuse target locations for the fuse types used in PMH models of S&C Pad-Mounted Gear. 663-503 Page 24 of 35 August 14, 1995 INSTRUCTION SHEET S&C ELECTRIC COMPANY s FINAL CHECKS BEFORE WALKING AWAY . . . So that the S&C Micro-AT Source-Transfer Control is ready for automatic operation, make sure that both source voltage indicating lamps and the automatic-transfer “ready” indicating lamp are illuminated. If the “READY” lamp is not lighted, refer to the liquid-crystal display on the faceplate of the Micro-AT control. When not being used to show menu information, this display shows messages explaining why the lamp is not lighted. NOTE: A lighted “READY” lamp indicates that the status of associated components is normal, but an absence of illumination does not necessarily mean that the control is inoperative. For example, when transfer to the alternate source occurs, the lamp extinguishes but the control is ready for any subsequent programmed automatic operation required by a change in source conditions. Likewise, if the stored-energy operators are decoupled, the “READY” lamp is extinguished—and the switches will not operate—but the control is fully operative. Close and padlock the access doors to the low-voltage control compartment and high-voltage compartments. INSTRUCTION SHEET s S&C ELECTRIC COMPANY 663-503 Page 25 of 35 August 14, 1995 S&C Source-Transfer PMH Pad-Mounted Gear With Micro-AT® Control Outdoor Distribution (14.4 kv and 25 kv) IF OPERATOR STALLS . . . The stored-energy operator’s quick-make quick-break mechanism will stall in a partially discharged state if the operator is inadvertently tripped while its associated Mini-Rupter Switch is prevented from closing by any of the following conditions: • Switch not completely coupled (or decoupled) to switch operator. • Switch blocked open by mechanical cable interlock (applicable when that option, Catalog Number Suffix “-C6,” is included). • Switch blocked open by mechanical antiparalleling (applicable when that option, Catalog Number Suffix “-C7,” is included). • Switch locked open by key interlock (applicable when that option, Catalog Number Suffix “-C5,” is included). • Switch blades blocked by insertion of the dual-purpose front barrier in its “slide-in” position. To determine if the quick-make quick-break mechanism has stalled, observe the switch-position indicator target. If the words “SWITCH OPEN” on the target appear slightly off-center and one or more letters are partially hidden from view in the target opening, then the mechanism is in a stalled condition. See Figure 25. Normal Page 26 of 35 August 14, 1995 Ç WARNING To guard against handle kickback during performance of this step, do not release grip on handle until latching has occurred. 2. Place the large notched end (with recessed bolt) of the dual-purpose manual handle in the center of the decoupler. See Figure 26. (The handle’s knurled knob performs no function in this application.) While pivoting the handle, push it in to engage the reverse-drive hub. Then rotate the handle counterclockwise for the lefthand switch (clockwise for the right-hand switch) to back drive the switch and the quick-make quick-break mechanism—against the tension of the stored-energy spring—until the mechanism latches in its open position. A slight click may be heard when the mechanism latches. 3. Verify that the latched-open condition has been achieved by observing that the switch-position target reads “SWITCH OPEN” and the operator targets read “OPERATOR IN SWITCH-OPEN POSITION” and “OPERATOR CHARGED.” Stalled Figure 25. Switch-position indicator target appears slightly off-center if mechanism is stalled. 663-503 Restore the stored-energy operator to a normal latched-open condition after such an occurrence as follows: 1. Make sure that the manual/automatic operation selector switch is in “MANUAL.” Figure 26. Dual-purpose manual handle reverse-driving the Mini-Rupter Switch and operator’s quick-make quick-break mechanism to recover from a stalled condition. INSTRUCTION SHEET S&C ELECTRIC COMPANY s MAINTENANCEa Components No routine maintenance is required for the S&C Micro-AT Source-Transfer Control. However, operational testing once per year in accordance with S&C Instruction Sheet 663-590 is recommended to verify proper functioning of the system. No mechanical maintenance is required for S&C PadMounted Gear. However, occasional inspection of the gear and exercising of the Mini-Rupter Switches is recommended. In addition, inspection and cleaning—of insulators and cable terminators in particular—should be performed periodically, at intervals based on environmental conditions. Ç WARNING Before cleaning, completely de-energize, test, and ground the pad-mounted gear. Never use pressuresprayed abrasives to clean pad-mounted gear. Pressure-sprayed abrasives will damage switch and fuse components. The stored-energy operators should be given an exercising consisting of five or more operations at least once every year, unless normal operating duty provides equal or greater exercise. With the switches decoupled from the operators, exercising can be accomplished at any convenient time without requiring that the switches themselves be operated and, therefore, without requiring an interruption of service. The nominal operating life of the stored-energy operators is 1500 operations (complete close-open cycles), provided that no more than 500 of such operations are performed while decoupled. Place dual-purpose front barriers for switch and fuse compartments into the “slide-in” position. See Figures 10 and 14. This will provide physical isolation for additional security if it is necessary to work on the cables connected to the Mini-Rupter Switch or fuse. Ç DANGER When access to high-voltage compartments is required for inspection, service, or repairs, always observe the precautions below. Failure to observe these precautions will result in serious injury or death. 1. Access to pad-mounted gear must be restricted only to qualified persons. See “Qualified Persons” on page 2. 2. Always follow safe operating procedures and rules. 3. Before touching any device, alway disconnect switches, fuses, and other devices from all power sources (including backfeed) and control sources, test for voltage, and properly ground. 4. When external voltage is used to test any secondaryside wiring or devices, disconnect all voltage sensors to avoid energizing the high-voltage conductors through the voltage sensors. To disconnect the voltage sensors, transfer the input plug from the input receptacle to the shorting receptacle. See Figure 3. 5. Always assume that both sets of power terminals on any switch or fuse are energized unless proved otherwise by test, by visual evidence of open-circuit conditions on both sets of terminals, or by observing that both sets of terminals are grounded. 6. Test for voltage on both sets of power terminals of any switch or fuse using proper high-voltage test equipment. 7. After the gear has been completely disconnected from all sources of power and tested for voltage, install suitable grounding cables in all compartments. 8. For maintenance of non-S&C equipment, follow the manufacturer’s instructions. 9. Make certain the enclosure is properly grounded to the station or facility ground. Do not return equipment to service unless such grounds are properly made. NOTE: Occasionally, low-voltage components may require maintenance. The maintenance of other lowvoltage components isolated from high-voltage compartments may be performed under the safety rules for equipment rated 600 volts or less. If maintenance is to be performed on devices connected to the secondary of a voltage sensor, short-circuit the secondary connections. A separate drawing will be provided with the replacement part explaining how to properly short-circuit the secondary connections. a These recommendations may differ from company operating procedures and rules. Where a discrepancy exists, users should follow their company’s operating procedures and rules. INSTRUCTION SHEET s S&C ELECTRIC COMPANY 663-503 Page 27 of 35 August 14, 1995 S&C Source-Transfer PMH Pad-Mounted Gear With Micro-AT® Control Outdoor Distribution (14.4 kv and 25 kv) MAINTENANCE — Continued Returning Equipment to Service Enclosure Finish When returning the equipment to service, the following procedures should be observed: 1. Make sure that switch and fuse grounding means are removed and that dual-purpose front barriers are removed from the “slide-in” position before closing the associated Mini-Rupter Switch or power fuses. 2. Make certain that the Mini-Rupter Switches are in the correct position (open or closed) as dictated by system circumstances. 3. Close each door permitting access to high voltage. Make sure that the associated Penta-Latch Mechanisms are securely latched and padlocked before energizing the circuit or operating any switching device. 4. Make certain that the input plug is on the input receptacle. 5. Refer to “FINAL CHECKS BEFORE WALKING AWAY . . .” on page 25. 6. Close both low-voltage compartment doors and make sure that the associated Penta-Latch Mechanism is completely latched and padlocked. 7. Padlock all doors before leaving the installation site, even momentarily. Observe this procedure even in those cases where the gear is accessible only to qualified persons. The responsibility for ensuring that a finish protects the enclosure lies with both the manufacturer and the user. S&C Source-Transfer PMH Pad-Mounted Gear is finished with the S&C Ultradur™ Finishing System, which provides lasting protection for the enclosure. To retain this protection, the user should take periodic corrective action as follows: 1. Touch up any penetration of the finish to bare metal—such as scratches and abrasions due to shipping or vandalism—to maintain the original integrity. S&C touch-up finish and primer are available in aerosol spray cans—order by Catalog Number: 9999-058 for olive green finish, 9999-080 for light gray finish, and 9999-061 for red-oxide primer. No other finish or primer is approved. The area to be touched up should be cleaned to remove all oil and grease. Sand the area, removing any traces of rust that may be present, and make sure all edges are feathered before applying primer. 2. Provide an occasional simple washdown—such as an automobile would be given—to remove surface contaminants. Use any ordinary mild household detergent solution. In those cases where the enclosure must be refinished by the user before the finish has weathered—for example, to match other equipment—a special precaution must be taken. The entire surface must be sanded to provide a tooth to bond the new coat to the unusually tough and smooth S&C Ultradur Finish. 663-503 Page 28 of 35 August 14, 1995 INSTRUCTION SHEET S&C ELECTRIC COMPANY s APPENDIX A Preliminary Tryout Before Gear Is Energized—Optional To expedite full service once high voltage is available, the user may wish to perform a preliminary checkout of the Micro-AT Source-Transfer Control before the gear is energized. For this purpose an S&C Test Accessory, Catalog Number TA-1316, is available to permit checkout of the source-transfer operation using an external single-phase 120-volt ac source. If a preliminary checkout is to be performed, special instructions must be followed to ensure correct operation of the Micro-AT control. These instructions are set forth in S&C Instruction Sheet 515-510, furnished with the test accessory. The programming and testing described under “FIELD ADJUSTMENT AND PROGRAMMING” and “OPERATIONAL TESTING” in S&C Instruction Sheet 515-500 can be completed during the preliminary checkout. When the test accessory is used, the control power available to supply the charging motors of the storedenergy operators and to maintain the charge on the solenoid-tripping capacitors is less than that available during normal three-phase operation. As a result, the time required for the motors to charge the stored-energy operators will be longer than normal. Furthermore, it may take as long as two minutes after the stored-energy operators are charged for the solenoid-tripping capacitors to become fully charged. Therefore, wait at least two minutes after the stored-energy operators are charged before initiating a transfer operation. APPENDIX B Dielectric Testing When high-voltage dielectric tests are to be performed on S&C Source-Transfer PMH Pad-Mounted Gear, special precautions should be taken to prevent damage to the voltage sensors and voltage limiters. Refer to S&C Instruction Sheet 591-500. APPENDIX C Ratings for S&C Mini-Rupter Switches Complete ratings for Mini-Rupters as applied in S&C Source-Transfer PMH Pad-Mounted Gear are shown in the table below. In addition to the load-dropping ratings shown, Mini-Rupter is capable of interrupting transformer magnetizing currents associated with the applicable loads, as well as line-charging and cable-charging currents typical for distribution systems of these voltage ratings. For applications on systems rated higher than 7.2 kv and involving load current with high harmonic content (such as rectifier load currents), refer to the nearest S&C Sales Office. The two-time duty-cycle fault-closing ratings shown for Mini-Rupters define the ability to close the Mini-Rupter twice against a three-phase fault with asymmetrical current in at least one phase equal to the rated value, with the switch remaining operable and able to carry and interrupt rated current. RATINGS FOR S&C MINI-RUPTER SWITCHES Kv Amperes, Rms Live Switching Momentary (Asym.) 1-Second (Sym.) 22 400 22 400 14 000 22 400 22 400 14 000 Nom. Max BIL Cont. Load Splitting (Parallel or Loop Switching) Load Dropping Duty-Cycle Fault-Closing, Two-Time (Asym.) 14.4 17.0 95 600 600 600 25 29 125 600 600 400 14,000 amperes rms symmetrical, 35,000 amperes peak. INSTRUCTION SHEET s S&C ELECTRIC COMPANY 663-503 Page 29 of 35 August 14, 1995 S&C Source-Transfer PMH Pad-Mounted Gear With Micro-AT® Control Outdoor Distribution (14.4 kv and 25 kv) APPENDIX C — Continued Ratings for S&C Power Fuses with Uni-Rupter Complete ratings and capabilities of S&C Power Fuses with Uni-Rupter as applied in S&C Source-Transfer PMH Pad-Mounted Gear are shown in the table below. UniRupter is also capable of carrying and interrupting load currents up to and including the emergency peak-load capabilities of the associated SML Power Fuses, or up to 400 amperes at 14.4 kv and 200 amperes at 25 kv when used with Fault Fiter Electronic Power Fuses. In addition to the load-dropping capabilities shown, Uni-Rupter is capable of interrupting transformer magnetizing currents associated with the applicable loads, as well as line-charging and cable-charging currents typical for distribution systems of these voltage ratings. The duty-cycle fault-closing capabilities shown for S&C Power Fuses with UniRupter represent the fault-closing capabilities of the fuse with Uni-Rupter when the fuse is closed with a purposeful thrust without hesitation. Following the specified number of such closings (one or two), Uni-Rupter will remain operable and able to carry and interrupt rated current. RATINGS AND CAPABILITIES FOR S&C POWER FUSES WITH UNI-RUPTER Ratings Live Switching Capabilities, Amperes, Rms Kv Fuse Type Nom. Max 14.4 17.0 25 27 14.4 17.0 25 27 14.4 17.0 25 29 Amperes, Rms Load Dropping Duty-Cycle Fault-Closing (Asym.) Load Splitting (Parallel or Loop Switching) One-Time Two-Time BIL Max Interrupting (Sym.) 95 200E or 200K 14 000 200 200 22 400 13 000 125 200E or 200K 12 500 200 200 20 000 13 000 95 200E 12 500 200 200 20 000 13 000 125 200E 12 500f 200 200 20 000 13 000 95 400 14 000 400 400 22 400 13 000 125 200 12 500 200 200 20 000 13 000 SML-20 SML-4Z Fault Fiter f Applicable to solidly grounded-neutral systems only, with fuses con- nected by single-conductor, concentric-neutral-type cable to a transformer or transformers. Rating is 9,400 amperes rms symmetrical for all other applications. 663-503 Page 30 of 35 August 14, 1995 INSTRUCTION SHEET S&C ELECTRIC COMPANY s APPENDIX D OPTIONAL FEATURES Suffix Added to Pad-Mounted Gear Catalog Number Item Light Gray Outdoor Ultradur Finish instead of olive green Stainless-Steel Enclosure1 Hexhead Actuator for use in lieu of pentahead actuator on all Penta-Latch Mechanisms -A2 With olive green finish -A10 With light gray finish -A12 For use except when option suffix “-F2” is specified -B1d For use when option suffix “-F2” is specified -B2d Key Interlocks to prevent opening fuse-compartment doors unless both switches are locked open -C5d Mechanical Cable Interlocks to prevent operation of switch when associated switch-compartment door is open -C6d Mechanical Antiparalleling to prevent paralleling two sources -C7d Auxiliary Switches, 4-PST, one coupled to each switch -C9d Auxiliary Switches, 4-PST, one coupled to each stored-energy operator -C10d Remote-Control Receptacle for each stored-energy operator to permit open/close operations from an adjacent location using the remote-control station (not included; see “ACCESSORIES” on page 33) -C11 Mounting Provisions for a Fault Indicator in each switch compartment Note: Accommodates three-phase indicator with singlephase sensors Applicable to Models Without viewing window in door -F1 With viewing window in door -F2d Inner Barrier Panels—a panel inside the enclosure door for each compartment, secured by recessed pentahead bolt(s)23 -G7 6 inches -K1 12 inches -K2 18 inches -K3 24 inches -K4 All models Carbon steel Base Spacer, compartmented to match enclosure, increases cable-termination height 6 inches -K11 12 inches -K12 18 inches -K13 24 inches -K14 Stainless steel 6 inches -K7 12 inches -K8 18 inches -K9 24 inches -K10 Carbon steel Base Spacer, noncompartmented, increases cabletermination height 6 inches -K17 12 inches -K18 18 inches -K19 24 inches -K20 Stainless steel 1 When this optional feature is specified, the entire exterior of the 3 Meets REA’s requirements for “dead-front.” enclosure is fabricated from 11-gauge Type 304 stainless steel. d When optional feature “-B1,” “-B2,” “-C5” through “-C10,” or “-F2” is 2 Where the National Electrical Safety Code (ANSI Standard C2) ordered for use with a stainless-steel enclosure, the suffix designation is increased by 10; for example, “-B11” is specified instead of “-B1.” applies, this optional feature may be included to meet the requirements of Section 381G. INSTRUCTION SHEET s S&C ELECTRIC COMPANY 663-503 Page 31 of 35 August 14, 1995 S&C Source-Transfer PMH Pad-Mounted Gear With Micro-AT® Control Outdoor Distribution (14.4 kv and 25 kv) APPENDIX D — Continued OPTIONAL FEATURES—Continued Suffix Added to Pad-Mounted Gear Catalog Number Item Switch-Terminal Adapters—for connection of two cables (through 750 kc mil) per terminal 1 Note: Space limitations prevent use of these adapters where surge arresters are to be installed Cable Guides, one at each terminal12 -M1 In switch compartments. For conductor sizes No. 2 through 1000 kc mil -M2 In fuse compartments. For conductor sizes No. 2 through 4/0 -M3 Polymer-Housed Metal-Oxide Surge Arresters,3 base-mounted, at all switch terminals (removed for shipment) 9 kv -N6f 10 kv -N7f 12 kv -N8 15 kv -N9 18 kv -N10l 9 kv, 10 kv, or 9/10 kv Mounting Provisions for Base-Mounted Surge Arresters,4 at all switch terminals Mounting Provisions for Porcelain Cable Terminators for single-conductor UD cable, at all switch terminals Applicable to Models -P1f 12 kv -P3 15 kv -P4 18 kv -P5l Joslyn PSC for No. 6 through 2/0,d or G&W PAT for No. 4 through 250 kc mil copper or aluminum cable -U2 G&W PAT for 3/0 through 750 kc mil copper or 500 kc mil aluminum cabled -U3 Overcurrent Lockout. Prevents an automatic source transfer that would close a switch into a fault. Includes field adjustable lockout level and lockout-reset time delay, lockout-indicating lamp, manual-reset key, facilities for external reset, and six current sensors (one per phase for each switch)5678 -Y2 Remote Indication. Includes provisions for remote monitoring of presence or absence of source voltages, manual or automatic operating mode, and status of “ready” indicator, “event” indicator, and overcurrent lockout (if furnished)9 -Y4 Test panel. Permits the use of an external, adjustable three-phase source to verify, through independent measurement, the response of the control to loss-of-source, phase-unbalance, and overcurrent-lockout (if furnished) conditions0⁄ -Y5 Supervisory Control. Permits switch operation from a remote location9 -Y6 Communications Card. Permits local uploading of “events” and settings from the Micro-AT control to a userfurnished personal computer, as well as downloading of the user’s standard operating parameters¤‹ -Y8 All models 1 When optional feature “-M1” or “-M2” is specified, cable-termination 8 Current sensors must not be installed on unshielded cables or on options (suffixes “-U2” and “-U3”) cannot be accommodated. In addition, when optional features “-M1” and “-M2” are both specified, only one cable guide is provided at each switch terminal. 2 These devices extend below the base of the unit. A cable pit or optional base spacer that provides a 12-inch or greater increase in cabletermination height is required. 3 Surge arresters are base-mounted only (without isolators). 4 These provisions accommodate Ohio Brass Type PDV (metal oxide), McGraw-Edison Type AZL19C (metal oxide), General Electric Tranquell® (metal oxide), or McGraw-Edison Type ES (silicon carbide) distributionclass surge arresters. Surge arresters must be base-mounted only (without isolators). 5 The current sensors furnished cannot be used with the switch-terminal adapter option (suffix “-M1”) for applications involving two source conductors per phase. For such applications, refer to the nearest S&C Sales Office. 6 For applications where pad-mounted gear load feeders are connected to transformers with wye-grounded primary windings, refer to the nearest S&C Sales Office. 7 S&C Closed-Gap Current Sensors, Catalog Number TA-1758, are furnished. Each current sensor accommodates a single conductor up to 2¹⁄₂ inches in diameter. cables where the insulation is exposed but ungrounded (for example, where dielectric tape or heat-shrink tubing is used). These sensors are intended for application at ground potential and may be damaged by the voltage gradient between the cable insulation and ground. 9 Includes a terminal block for user’s connections. 0 If a three-phase test source is not available, limited testing may be performed using an external, adjustable single-phase source. ⁄ In instances where a three-phase test source is to be used, an S&C Voltage Limiter—Three-Phase Catalog Number TA-1741 must be furnished for the test circuit. ¤ Requires an IBM PC AT or compatible computer using Intel’s 80386 microprocessor, or higher. The computer must have a minimum of 2MB of memory, one 3.5-inch 1.44-MB floppy disk drive, and a hard disk drive with at least 2MB of free space. The computer must operate under Microsoft Windows™, Version 3.1. ‹ Requires S&C Maintenance Cable Catalog Number TA-2320 or TA-2321. See “ACCESSORIES” on page 33. d These devices extend below the base of the unit. A cable pit or optional base spacer is required. f Not applicable to 25-kv models. l Not applicable to 14.4-kv models. 663-503 Page 32 of 35 August 14, 1995 INSTRUCTION SHEET S&C ELECTRIC COMPANY s APPENDIX D — Continued ACCESSORIES Item Catalog Number S&C Test Accessory, permits preliminary checkout of source-transfer control using single-phase 120-volt ac source (before medium-voltage connections are made to the pad-mounted gear) to expedite full service once medium voltage is available. The test accessory isolates the S&C Voltage Sensor during testing and eliminates the possibility of backfeed during test procedures TA-1316 Portable Remote-Control Station with 50-foot cord, connects to one remote-control receptacle (not included; see optional feature “-C11” on page 31) to permit open/close operations from an adjacent location Maintenance Cable, for connecting Micro-AT control communications card (see optional feature “-Y8” on page 32) to user-furnished personal computer Grounding Jumpers, set of three, with eye-type clamps for installation with a standard shotgun clamp stick Shotgun Clamp Sticks for installation of grounding jumpers and for use with voltage testers 5294 For personal computers having 25-pin serial communication port TA-2320 For personal computers having 9-pin serial communication port TA-2321 3 cable length 4210 65¹⁄₂ length 9933-150 85¹⁄₂ length 9933-151 For grounding jumpers Storage Bag, heavy canvas For shotgun clamp stick 9933-149 66 length 9933-152 86 length 9933-153 Voltage Tester with audio and visual signals, includes voltage tester, batteries, adapter for shotgun clamp sticks, and storage case1 9931-072 Pentahead Socket, for ¹⁄₂-inch drive 9931-074 1 For ultimate users other than electric utilities, also specify a shotgun clamp stick of the appropriate length. INSTRUCTION SHEET s S&C ELECTRIC COMPANY 663-503 Page 33 of 35 August 14, 1995 S&C Source-Transfer PMH Pad-Mounted Gear With Micro-AT® Control Outdoor Distribution (14.4 kv and 25 kv) APPENDIX E Current-Limiting Fuses for Use in S&C PMH Pad-Mounted Gear Types Accommodated and Adapters Required S&C Holders for current-limiting fuses are designed for use in pad-mounted gear models that include mountings for Fault Fiter Electronic Power Fuses. In PMH PadMounted Gear, these holders will accommodate the single-barrel current-limiting fuses listed in the table below when the fuses are equipped with ⁵⁄₈-inch diameter mounting studs at both ends. Depending on the length and diameter of the current-limiting fuse to be used, adapters may be required in order to fit the fuse in the holder. Adapters, when required, are furnished with the S&C Holder and are signified by a suffix to the catalog number of the holder. For instructions on installing current-limiting fuses in S&C Holders, refer to S&C Instruction Sheet 660-500. CURRENT-LIMITING FUSES—Types Accommodated and S&C Holders Required For use in PMH Models Rated, Kv Current-Limiting Fuse1 Manufacturer Type Combined Technologies, Inc. Max Amperes, Rms Catalog Number4 8.3 30—112 3142-A1 Q 8.3 8.3 15.5 15.5 15.5 6—30 40—100 6—30 40—50 65—100 3142-A3 3142-A1 3142-A2 3142-A1 3142 McGraw-Edison NX® 8.3 8.3 15.5 15.5 1.5C—40C 50C—100C 1.5C—40C 1.5C—100C 3142-A3 3142-A1 3142-A2 3142 RTE® ELX 8.3 15.5 3—50 3—50 3142-A3 3142-A2 CX 8.3 15.5 3.5C—40C 4C—40C 3142-A3 3142-A2 X Limiter™ 8.3 8.3 15.5 15.5 12—40 50—140 12—40 50—100 3142-A3 3142-A1 3142-A2 3142 B 15.5 22 30—100 25—65 3143R1-A1 3143R1-A1 Q 15.5 15.5 6—30 40—100 3143R1-A3 3143R1-A1 McGraw-Edison NX® 15.5 15.5 23 1.5C—40C 50C—100C 6C—40C 3143R1-A3 3143R1-A1 3143R1-A3 RTE® ELX 15.5 23 3—50 3—40 3143R1-A3 3143R1-A3 Cooper Power Systems Westinghouse Max, Kv B Kearney 14.4 S&C Holder3 Rating2 Kearney Cooper Power Systems 25 CX 15.5 4C—40C 3143R1-A3 CXN 15.5 45C—60C 3143R1-A1 X Limiter™ 15.5 15.5 23 12—40 50—100 12—40 3143R1-A3 3143R1-A1 3143R1-A3 Westinghouse Combined Technologies, Inc. 1 The single-barrel current-limiting fuses listed in this table are to be 3 S&C Holders for use in 14.4-kv models of PMH Pad-Mounted Gear are purchased from the appropriate current-limiting fuse manufacturer. 2 The maximum voltage and maximum ampere ratings listed in this table apply when the corresponding current-limiting fuse is used. Consult the appropriate current-limiting fuse manufacturer for complete fuse ratings. rated 14.4 kv nominal, 17.0 kv maximum, and 200 amperes maximum. S&C Holders for use in 25-kv models of PMH Pad-Mounted Gear are rated 25 kv nominal, 29 kv maximum, and 200 amperes maximum. 663-503 Page 34 of 35 August 14, 1995 4 Includes adapters when required. INSTRUCTION SHEET S&C ELECTRIC COMPANY s APPENDIX E — Continued Recommended Voltage Ratings • Protection of single-phase transformers serving single- In general, current-limiting fuses should have a maximum voltage rating equal to, but not greater than 140% of, the system line-to-line voltage since, for most applications, the fuses can be exposed to full system line-to-line voltage in clearing faults. Although there may be economic or space-saving incentives for using current-limiting fuses with voltage ratings “appropriate for system line-toground voltage” (i.e., fuses with a voltage rating lower than line-to-line voltage but greater than or equal to maximum system line-to-ground voltage), S&C can only recommend such use in the following applications: phase loads. • Protection of three-phase lateral circuits fed by singleconductor shielded cable (provided each transformer on that lateral is individually fused so that the currentlimiting fuse serving the lateral will not be required to clear secondary faults). • Protection of single-phase lateral circuits fed by singleconductor shielded cable where the load is line-toground connected. INSTRUCTION SHEET s S&C ELECTRIC COMPANY 663-503 Page 35 of 35 August 14, 1995
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement