R3-PA16 TOTALIZED PULSE INPUT MODULE BEFORE USE .... COMPONENT IDENTIFICATION

R3-PA16 TOTALIZED PULSE INPUT MODULE BEFORE USE .... COMPONENT IDENTIFICATION
R3-PA16
INSTRUCTION MANUAL
TOTALIZED PULSE INPUT MODULE
MODEL
(Pi 16 points)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
the contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
Totalized pulse input module ..................................... (1)
COMPONENT IDENTIFICATION
■FRONT VIEW
RUN LED
ERR LED
■ MODEL NO.
Check that model No. described on the specification label is
exactly what you ordered.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
11
12
13
14
15
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, including installation, connection and basic
maintenance procedures.
POINTS OF CAUTION
R3-PA16
16
17
18
19
20
Status Indicator LED
1
2
3
4
5
6
7
8
9
10
■SIDE VIEW
■ CONFORMITY WITH EC DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel configurations, connected devices and connected wires may
affect the protection level of this unit when it is integrated in
a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.
■ HOT INSERTION/REMOVAL OF MODULES
Removing or replacing modules does not affect other modules
on the same backplane. It is possible to replace them without
removing the power supply. However, replacing multiple
modules at once may greatly change line voltage levels. We
recommend that you replace them one by one.
■ ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH in
order to ensure adequate life span and operation.
■ WIRING
• Do not install cables (power supply, input and output) close
to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises
are present. Do not install them in the same duct.
SW3
4
3
2
1
Count
Reset Input
ON
Count
Reset
Set the Count Reset SW to OFF to start counting.
■STATUS INDICATOR LED
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with the excitation abnormality;
Green in normal operating conditions.
Input status indicator: Red LED; turns on with the inputs
supplied.
INSTALLATION
Use the Installation Base (model: R3-BSx).
■ AND ....
• The unit is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data sheet.
P. 1 / 2
EM-8389 Rev.5
R3-PA16
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■ DIMENSIONS mm (inch)
27.5 (1.08)
109 (4.29)
POSITIONING
GUIDE
12
13
14
15
16
17
18
19
20
1
20–M3
SCREW
2
3
4
5
6
6.2
(.24)
130 (5.12)
11
7
8
9
10
TERMINAL
COVER
■ CONNECTION DIAGRAM
WIRING INSTRUCTIONS
■R3-PA16x/A
Pi 1 1
Pi 2 2
Pi 2 2
Pi 3 3
Pi 3 3
Pi 4 4
Pi 4 4
Pi 5 5
Pi 5 5
Pi 6 6
Pi 6 6
Pi 7 7
Pi 7 7
Pi 8 8
Pi 8 8
Pi 9 11
Pi 9 11
Pi 10 12
Pi 10 12
Pi 11 13
Pi 11 13
Pi 12 14
Pi 12 14
Pi 13 15
Pi 13 15
Pi 14 16
Pi 14 16
Pi 15 17
Pi 15 17
Pi 16 18
BUS A
BUS B*
INTERNAL
POWER
■ SOLDERLESS TERMINAL mm (inch)
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solderless
terminals with insulation sleeve do not fit. Applicable wire
size: 0.3 – 0.5 mm2
3 (.12) max.
4 min.
(.16)
3.2 (.13) dia.
6 max.
(.24)
Pi 1 1
BUS CONNECTOR
■R3-PA16x
12 (.47) max.
Pi 16 18
COM(+)
9
9
+24V
**
19
10
19
0V
20
10
0V
20
* For dual redundant communication.
**DO NOT use the terminals No. 9 and 19.
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System's sole liability, and purchaser's exclusive remedies,
under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To
submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]
P. 2 / 2
EM-8389 Rev.5