GLC2400T TFT Color Data Sheet

GLC2400T TFT Color Data Sheet
Pro-face Graphic Logic Controllers
GLC2400T - TFT Color
7.4" Color HMI with distributed I/O and industrial
network connectivity support
The GLC2400 is a powerful integrated HMI/PLC one box solution. This combination
streamlines machine design by capitalizing on integrating information, display and control
in one unit while reducing overall system costs. Unit includes bar code reader support, a
sound output for audio machine feedback and printer output for report generation.
The GLC2000 family features powerful logic control algorithms including timers, counters,
logical operations, mathematical, bit manipulation etc for precise machine control and
monitoring. Additionally, expanded communications to popular industrial network interfaces
are supported with optional communication modules listed in the specifications.
GLC2400-TC41-24V
FEATURES
• 7.4 inch touch screen
• TFT 256 Color LCD
• 640 x 480 resolution
• RS-232/422 Com Ports
• Ethernet Port (10 baseT)
• CompactFlash™ Port
• Sound Output
• 2CH Flex Network Master Interface
• Optional Communication Module Interface
INFORMATION
COMMUNICATION
Powerful
secured
data
collection
and sharing
Versatile interfaces support flexible and
expanding control system needs
Easy data
transfer by
CF card.
To connect various controllers
Various HMI software solutions available to
match your needs:
• Advanced featured Graphics Editor for drawing
•
•
•
•
objects, animation, creating pre-configured
operator objects, scripting, etc.
Recipes Trending, Data Logging, Alarm/Event
Management, Security, etc.
Software application connectivity via OPC, DDE,
SQL, DLL, SMTP Email
Data sharing via Ethernet, Internet, or
CompactFlash™
Web-enabled browser features (optional Pro-Server)
Serial devices, such as single or
two-dimensional bar code readers
Industrial Network Connectivity (optional)
PROFIBUS (Slave or Master)
CANopen (Slave)
DeviceNet (Slave or Master)
Modbus Plus
CONTROL - DISTRIBUTED I/O MODULES FOR UP TO 1008 POINTS
GLC control features include: timers, counters, logical operations, mathematical, bit manipulation, etc.
Mix and match any combination of analog and discrete I/O modules to meet your application needs.
Flex Network
Module Types:
•
•
8, 16, 32 and 64-Point Discrete
Hi-Speed Counter
•
•
4 Ch. and 2 Ch. Analog In or Out
Single-Axis Positioning
(400m Max)
Please Note: Refer to the Flex Network datasheets for specifications on I/O modules.
Page 1
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
GLC2400T SPECIFICATIONS
FUNCTIONAL SPECIFICATIONS
Model
Type
Colors
Backlight
Display
Resolution
Effective Display Area (mm)
Brightness Control
Application
Memory
Data Backup
Program Area
Control
Memory Variable Area
Serial (COM 1) Interface
Exp. Serial (COM 2) Interface
Network Interface
Interfaces Tool Connector Port
CF Card Interface
Expansion Interface
Sound
Flex Network Interface
GLC2400-TC41-24V
TFT Color LCD
256 colors, No blink/64 colors, 3-speed blink (Color switching is done via software)
CCFL (Service life: 50,000 hrs. or more at 25°C and 24 hrs. operation) User replaceable
640 x 480 pixels
W149.8mm [5.90in.] x H184.5mm [4.42in.]
4 levels of adjustment available via touch panel
4MB FLASH FEPROM (Approx. 1280 screens at 3.2KB/screen)
256KB SRAM - uses a lithium battery
128KB FLASH EPROM
32KB SRAM - uses a lithium battery
RS-232C/RS-422 configurable, 25 pin D-sub, Data Transmission Speed: 2400 to 115.2 kbps
RS-232C, 9 pin D-sub, Data Transmission Speed: 2400 to 38.4 kbps
Ethernet IEEE802.3 10BASE-T
8-pin mini Din for programming/bar code reader
1 slot (CompactFlash™)
Yes - for optional communication modules
External Speaker Connection (Terminal Block) Monaural 1CH. Sound line out output 2.7Vp-p (Rated Load: 10kOhm).
Speaker Output 70mW (Rated Load: 8 Ohm, Frequency: 1kHz). Recommended Wire: AWG#28 to #16
For connecting to Flex Network distributed I/O modules
GENERAL SPECIFICATIONS
Structural Environmental
Rated Voltage
Electrical Rated Voltage Range
Power Consumption
Ambient Operating Temp.
Storage Temperature
Operating Humidity
Storage Humidity
Vibration Resistance
Ratings
Certifications
External Dimensions
Weight
24VDC
19.2VDC to 28.8VDC
28W or less
0°C to 50°C
-20°C to 60°C
10%RH to 90%RH (non-condensing, drybulb temperature: 30°C or less)
10%RH to 90%RH (non-condensing, drybulb temperature: 30°C or less)
IEC61131-2 (JIS B 3501) compliant. When vibration is NOT continuous: 10Hz to 57Hz 0.075mm, 57Hz to 150Hz 9.8m/s2
When vibration is continuous: 10Hz to 57Hz 0.035mm, 57Hz to 150Hz 4.9m/s2 X,Y, Z direction for 10 times (80min.)
NEMA TYPE#250 Type 4 x/12 (limited to the front face after installation in a panel)
EN55011, EN61000-6-2, UL/cUL 1604, Class 1, Div 2
W215mm[8.46in.] x H170mm [6.69in.] x D60mm [2.36in.] (main unit only)
1.7kg (3.7lb) or less (main unit only)
EXTERNAL DIMENSIONS
OPTIONAL COMM. MODULES
Unit: mm [in.]
CA1-DNSALL-21
CA2-DNMALL-41
CA3-MBPALL-41
CA1-PFSALL-21
CA2-PFMALL-21
CA1-COSALL-21
QPI-ABD-201*
QPI-ABR-201*
*PSL-CONV00
DeviceNet Slave Interface module
DeviceNet Master Interface module
Modbus Plus interface module
Profibus DP Slave interface module
Profibus DP Master Interface module
CANopen Slave Interface module
Data Highway Plus interface module
AB 1771 Remote I/O interface module
Required adapter when using QPI
communication modules
ORDERING INFORMATION
ORDER NUMBER
GLC2400-TC41-24V
DESCRIPTION
7.4" Color Touch Screen HMI with control
OPTIONAL ACCESSORIES
PS400-DF00
PS400-BU00-MS
GPW-CB02
GPW-CB03
FN-xxxxx
FN-CABLE2xxx-31-MS
Screen protection sheets, qty 5
Backlight Replacement
Data transfer cable, GLC to PC 9-Pin RS232 D-Sub
Data transfer cable, GLC to PC USB
Any Flex Network distributed I/O module
Flex Network cable where xxx is 010, 050, or 200 (meters) in length
Xycom Automation, Inc.
a Pro-face America Company
734-429-4971
Fax: 734-429-1010
http://www.xycom.com
Customer Support Hotline:
734-944-0482
© 2005 Xycom Automation, Inc. Is a wholly owned subsidiary of Pro-face America, Inc. Specifications may change without notice.
Xycom Automation is a trademark of Xycom Automation. Other brand or product names are the property of their respective owners.
Page 2
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement