Gentex AVS44 Synchronization Module
July 28, 1998
G-122
Gentex AVS44
Synchronization Control Module
for the GOT/GOS Series Horn & Horn/Strobe
Section: Audio/Visual Devices
GENERAL
California
State Fire
Marshal
7300-0569:121
MEA
The Gentex AVS44 Synchronization Control Module is
designed to provide an easy way to synchronize multiple
horns as well as strobe light flashes using only two wires in
those rare instances where a synchronized flash is required.
The control module has the ability to synchronize multiple horn signals with: a Code 3 temporal pattern at 800
Hz or 2400 Hz; the 800/1000 Hz alternating tone; the chime
— and the ability to silence the horn while allowing the
strobes to continue flashing.
285-91-E Vol. XII
S5405
By incorporating the control module as shown in the wiring
diagrams (page 2), the control module will control power to
the horns to produce synchronized operation. When using
Z-Series strobes or horn/strobes in parallel mode, synchronization may also be attained without using a control module if the fire alarm control panel is capable of providing
pulsed power with a minimum power-off time of 10 mS and
a maximum power-off time of 20 mS and with a repetition
rate of 1 second (see figure 2, page 2). In parallel mode,
the horn cannot be silenced while maintaining strobe operation.
FEATURES
• Option to silence the horn while strobes continue to flash.
• Synchronize horn and strobe using only two wires.
• Operates GOS “Z” horn/strobe.
• Module is rated for 3 Amps at 24 VDC.
• Easy to install.
• Synchronizes to 1 Hz flash rate.
• Dimensions: 3.321" (84.3534 mm) high x 2.896"
(73.5584 mm) wide x 1.190" (30.2260 mm) deep.
ORDERING INFORMATION
MODEL
NUMBER
AVS44
OPERATING
VOLTAGE
INRUSH
(mA)
PEAK (mA)
DC (mA)
FWR (mA)
CANDELA
21 VDC
—
—
7 mA
—
—
—
24 VDC
—
—
8 mA
—
30 VDC
—
—
9 mA
—
—
21 VFWR
—
—
—
7 mA
—
24 VFWR
—
—
—
8 mA
—
30 VFWR
—
—
—
9 mA
—
STROBE
Gentex
GOS-4-15/75Z*
RATED
CURRENT
21 VDC
420 mA
440 mA
144 mA
—
15*
24 VDC
490 mA
680 mA
130 mA
—
15*
30 VDC
620 mA
580 mA
116 mA
—
15*
21 VFWR
550 mA
920 mA
—
172 mA
15*
24 VFWR
640 mA
920 mA
—
155 mA
15*
30 VFWR
700 mA
640 mA
—
138 mA
15*
* Rated 75 Cd per UL 1638, Fire Protective Visual Signaling Appliances.
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications or
anticipate all requirements. All specifications are subject to change without notice. For
more information, contact Fire•Lite. Phone: (203) 484-7161 FAX: (203) 484-7118
12 Clintonville Road, Northford, Connecticut
06472
ISO-9001
Engineering and Manufacturing
Quality System Certified to
International Standard ISO-9001
Made in the U.S.A.
DF-51933 — Page 1 of 2
WIRING DIAGRAMS
WIRING NOTE:
Do NOT loop wires under terminals.
Use in-and-out wiring method.
WIRING FIGURE 1: For INDEPENDENT
synchronized (Z-Series) strobes and
temporal horn.
Fig. 1
WIRING FIGURE 2: For synchronized temporal horn ONLY,
or PARALLEL horn/strobe operation.
Fig. 2
NOTE ON JUMPERS:
When using the AVS44 control module, J5 and
J6 on the GOS must be in the top position.
These jumpers are in the top position when
shipped from the factory.
SEE DIAGRAM AT RIGHT.
Fig. 3
Page 2 of 2 — DF-51933