User manual | Eaton 9135 UPS

Add to my manuals
4 Pages

advertisement

User manual | Eaton 9135 UPS | Manualzz

Powerware series

Eaton 9135 UPS

Product snapshot

Power rating: 5 kVA/3.5 kW; 6 kVA/4.2 kW

Voltage: 230V nominal,

200–250 Vac range

Frequency: 50/60 Hz (auto-sensing)

Configuration: Rackmount (3U) or tower

Advanced power protection for:

• Medium-density data centers

• Banking and security systems

• Manufacturing process control

• Retail point-of-sale systems

• Telecommunications/VoIP equipment.

Features

• Provides clean, continuous power to protect critical equipment and applications from power-related downtime, data loss and corruption, and process interruption

• Saves valuable rack space by delivering 5000 - 6000 VA/4200W in only 3U

• Offers deployment versatility through rack and tower installation options with rail kits and pedestals provided

• Increases availability with hot-swappable batteries and power module

• Offers extended battery runtime options to power essential systems for more than an hour during an outage

• Simplifies UPS monitoring and management with a bright LCD user interface, intuitive LanSafe® & NetWatch software

• Provides two-year limited warranty

The Eaton® 9135 UPS,

Powerware® series, resolves utility power problems and supplies continuous, conditioned power. You get clean power for valuable IT and networking equipment, battery backup to gracefully handle utility outages, and on-demand visibility into UPS status from anywhere.

Under normal power conditions, the UPS can operate in high-efficiency mode at up to

97 percent efficiency. In double conversion mode, the UPS operates at up to 91 percent efficiency.

Get more usable power for less cost

The 9135 provides exactly the level of power protection needed under the conditions of the moment—optimizing for both efficiency and performance.

The more efficient the UPS, the lower your utility and cooling bills.

Double-conversion design for superior reliability and protection

In double conversion mode, the

9135 is constantly monitoring power conditions—regulating both voltage and frequency.

Even when presented with the most severe power problems, this UPS’s output remains within two percent of nominal voltage.

Rack model and EBM installation

Hot swappable batteries

Load segments

ConnectUPS-MS Network Management Card web interface

With a wide range of acceptable input voltages, this UPS does not depend on batteries to smooth out power fluctuations. Batteries are conserved for those times when utility power is highly unstable or completely out. If an outage occurs, the 9135 transfers to battery with no break in power, making this an ideal UPS for equipment sensitive to voltage fluctuations.

More power in less space

High power density. The 9135 increases power density, delivering

5000 - 6000 VA/4200W in only 3U of rack space, freeing more rack space for IT and telecom equipments. Rail kits and tower pedestals are included with every 9135 for flexible installation.

This UPS is even more user-friendly than its predecessors offering greater distribution capabilities, with eight IEC 10A & two IEC 16A outlets to power multiple pieces of equipment without a PDU.

You can combine the 9135 with an Eaton enclosure PDU (ePDU™) to power an entire rack of equipment from a single power cord input. ePDU outlets can be monitored, switched, sequenced and managed individually, providing maximum flexibility in distributing power from the 9135.

Maximum availability for critical systems

Battery runtime for minutes or hours. During a power outage, internal batteries in the 9135 keep loads running long enough to gracefully shut down systems. Add up to four external battery modules (EBMs) to deliver more than an hour of extended runtime at full load—or hours under lighter loads. Each EBM occupies only

3U of rack space. These battery modules are hot-swappable and can be replaced at any time without interrupting UPS operation and load protection.

Maximum battery runtime for critical equipments. LanSafe power management software enables independent control of load segments. With this feature, you can manage scheduled shutdowns and sequential startups of protected loads. During a power outage, you could shut down power to less essential loads to extend battery backup time for more critical devices.

When the load segments feature is used with optional

ConnectUPS-MS connectivity cards, users can remotely re-boot locked-up network equipment. Simply access the ConnectUPS-MS card over the network, and toggle the password-protected load segment controller to get your network back online.

Service without downtime. The 9135 features hot-swappable components and an automatic internal bypass. The UPS automatically switches to an alternate power path within the unit if it senses a trouble condition with an internal component. Users can even remove and replace the battery and power modules without powering down the UPS or interrupting power to loads.

2 EATON CORPORATION Eaton 9135 UPS

Visibility, control and management from anywhere

Local UPS status at a glance. An intuitive LCD interface provides detailed information and menu-driven functions for UPS management. The entire display rotates for the best orientation, whether the UPS is used vertically as a tower unit or horizontally in a rack.

The blue, backlit LCD screen displays four lines of alphanumeric information. LEDs clearly display UPS status:

Load Protected

Downgraded Operation

Load Not Protected

UPS ON/OFF button

Choice of connectivity options. Connectivity options are available for almost any networking environment. The standard unit comes with USB and RS-232 serial communication ports and a DB-9 dry contact port. You can customize your UPS by adding MS-slot interface options for other types of communications, such as:

A direct connection to the Ethernet network and the Internet, with the ability to monitor and manage the UPS from a standard Web browser

Serial connection for monitoring and graceful shutdown of up to five servers running various operations systems

Serial connection for simple alarm notification via isolated contacts to signal a change of state in UPS operation (typical in

IBM® eServer® iSeries applications)

Unified management for power protection. The 9135 comes complete with the Eaton Software Suite CD, including SNMPcompatible LanSafe power management software. LanSafe provides control and visibility over multiple UPSs, using an intuitive, graphical interface. From a central vantage point anywhere within the reach of a network connection, you can:

• Establish prioritized shutdown of network devices and client/ server applications

Test all network-connected UPSs from one node

Stay informed of power problems via email broadcasts

LCD rotatable display

Web/SNMP card with ModBus

Web/SNMP card

Relay/serial interface card

MODELS

Catalog number

Rack Tower Models

PW9135G5000-XL3UEU

PW9135G6000-XL3UEU

Extended Battery Modules

PW9135N6000-EBM3U

Style number

103006721-6591

103006722-6591

103006723-6591

Rating

(VA/Watts)

5000/3500

6000/4200

NA

BATTERY BACKUP TIMES (IN MINUTES)

Loads (VA/Watts)

1000/700

2000/1400

3000/2100

Standards Internal Batteries

36

13

10

4000/2800

5000/3500

6000/4200*

7

5

4

* Runtimes available for the 6 kVA model only.

Input plug

Hardwired

Hardwired

NA

+1 EBM

132

52

40

29

22

18

Output receptacles

Hardwired + (2) C19, (8) C13

Hardwired + (2) C19, (8) C13

NA

2 EBMs

232

95

74

53

41

33

Dimensions H x W x D, mm

130 x 444 x 741

130 x 444 x 741

130 x 444 x 650

+3 EBMs

332

140

110

80

62

50

Weight, kg

57

57

77.5

+4 EBMs

433

184

146

107

83

68 www.eaton.com/powerware 3

Technical specifications

General

User interface

LEDs

Topology

Diagnostics

UPS bypass

Dimensions

Rail kit

Electrical Input

Nominal voltage

Graphical LCD with blue backlight and text in

English, French, German, Portuguese, Italian and

Spanish

Four status-indicating LEDs

Double-conversion

Full system self-test

Automatic bypass

See models selection guide

Included with all units

Voltage range

Power draw of UPS

(full load)

230V

220V-240V user selectable

156–280 Vac (output PF 0.7)

5000VA: 21.7A @230V

6000VA: 26A @230V

35A Recommended inputbreaker rating

Frequency

Frequency range

50/60 Hz autoselect

40–70 Hz

Electrical Output

Power factor

On utility voltage

0.7

±2% of nominal regulation

±2% of nominal regulation On battery voltage

Efficiency >97% in high-efficiency mode; 91% in normal mode

Frequency regulation ±3% Hz online

Load crest factor 3 to 1

Battery

Internal battery type 5.5Ah, sealed, lead-acid; maintenance free

Externa battery modules

Up to four per 9135, rail kits included for rack mounting

EBM battery type

Battery runtime

Battery recharge time

5.5 Ah, sealed, lead-acid; maintenance free

Four (4) minutes with internal batteries @100% load (0.7 PF)

For additional details, see battery runtime chart

Six (6) hours to recover 90 percent of nominal backup time after 100 percent RCD load discharge

Battery replacement Hot-swappable internal and external batteries

Start-on-battery Allows start of UPS without utility input

In the interests of continual product improvement all specifications are subject to change without notice.

Communications

Serial port

USB port

Relay output

Software

Optional communication cards

RS-232 standard, RS-232 cable provided

HID standard, for communicating with Windows XP/

Vista

DB-9 Dry Contact-common alarm standard

LanSafe & NetWatch monitoring and management software

ConnectUPS-MS Network Management Card for direct control and monitoring in SNMP-based networks

ConnectUPS-MS Card with ModBus RTU interface

Serial Management Card-MS for integration to industrial environment and building management systems, remote shutdown for IBM AS/400 systems

Environmental

Safety markings

EMC

Audible noise

Ambient operating

CE, GS

IEC/EN 62 040-2 class A

Max 46 dB

0˚C to +40˚C

Storage temperature -20˚C to +40˚C with batteries and

-25˚C to +55˚C without batteries

Relative humidity 5–90% non-condensing

Heat dissipation (BTUs/hr)

Operating mode Efficiency

Normal

Battery

91%

86%

High efficiency 97%

5 kVA

1150

1650

370

6 kVA

1350

1960

450

Eaton, Powerware, ABM, LanSafe and

PowerChain Management are trade names, trademarks, and/or service marks of Eaton

Corporation or its subsidiaries and affiliates.

All other trademarks are the property of their respective owners.

© 2008 Eaton Corporation

All Rights Reserved

Printed in Finland

1018085 rev A

October 2008

BELGIUM

Tel: +32 (0) 2 348 44 10

[email protected]

Tel: +32 15 44 55 00

[email protected]

CZECH

Tel: +420 272 760 365

[email protected]

DENMARK

Tel: +45 3686 7910

[email protected]

FINLAND

Tel: +358 9 452 661

[email protected]

FRANCE

Tel: +33 1 60 12 74 00 [email protected]

GERMANY

Tel: +49 7841 6040 [email protected]

ITALY

Tel: +39 02 95542 309 [email protected]

MOROCCO

Tel: +212 22 95 77 40

Fax: +212 22 95 77 41

NORWAY

Tel: +47 23 03 65 50

[email protected]

POLAND

Tel: +48 22 331 85 24 [email protected]

PORTUGAL

Tel: +351 21 421 74 30

Fax: +351 21 421 74 29

THE NETHERLANDS

Tel: +31 (0) 78 652 16 80 [email protected]

RUSSIA

Tel: +7 495 981 37 70

[email protected]

SLOVAKIA

Tel: +421 2 4463 7046

[email protected]

SPAIN

Tel: +34 93 475 32 03 [email protected]

SWEDEN

Tel: +46 8 598 940 00 [email protected]

UAE

Tel: +971 4 881 19 33

Fax: +971 4 881 1939

UNITED KINGDOM

Tel: +44 1753-608 700 [email protected]