QEID Performance Supplement

QEID Performance Supplement
Direct Drive Mixed Flow Fans
Model QEID
Sound & Air Performance Supplement
• Motor Information
• Engineering Information
• Air/Sound Performance
• Dimensional Data
SOUND
and
R
AIR
PERFORMANCE
AIR
MOVEMENT
AND CONTROL
ASSOCIATION
INTERNATIONAL, INC. ®
Greenheck Fan Corporation certifies that the
Model QEID Mixed Flow Inline fans shown herein are
licensed to bear the AMCA seal. The ratings shown
are based on tests and procedures performed
in accordance with AMCA Publication 211 and
Publication 311 and comply with the requirements
of the AMCA Certified Ratings Program.
®
January
2010
Direct Drive Model Selection
The following performance charts are for the selection of QEID mixed flow inline fans. All charts are organized
by fan size and nominal motor RPM. Within each chart, there are a series of solid black lines with corresponding
dashed lines. The solid black lines represent the fan curves for each fan and are broken down by partial wheel
widths. Minimum, maximum, and 10 percent intervals are shown. The dashed lines are brake horsepower (Bhp)
curves and are also labeled by percentage wheel width.
Example Selection: 1,700 cfm @ 2.0 inches Ps wg.
To make a selection, start by finding a size and RPM that will attain the design static pressure (Ps). Next, scan for
fan sizes and RPMs that meet the CFM requirement at the design pressure. The intersection point of the static
pressure and CFM needs to be between the minimum and maximum percent wheel width for each fan.
To determine the partial wheel width and brake horsepower, start at 2.0 inches Ps and move across the graph
until intersecting the next percent wheel width beyond the required 1,700 cfm, point A. For this example, the next
largest percent wheel width is 70. Draw a vertical line from point A that crosses the 70 percent Bhp curve. In this
case, slide vertically downward from A to point B. From point B, read the Bhp on the right vertical axis of the
chart. The Bhp for this point of operation is 0.9 Bhp. Note: If the operating point falls between two partial wheel
width curves, select the next larger wheel width at the same pressure. This will result in more CFM as compared
to the original design requirements. Wheels are available in 5% partial width increments.
A
Minimum Percent
Wheel Width
B
Maximum Percent
Wheel Width
Sound data values are provided for both the inlet and outlet of the fan and are based on 100 percent wheel
widths. Values shown in the tables are based on the design static pressure. If the design static pressure is not
listed in the table, the sound power levels need to be interpolated from the values found on either side of the
design static pressure. If the design static pressure exceeds the maximum pressure listed in the table, then the
maximum values in the table should be used.
Example: 1,700 cfm @ 2.0 inches Ps wg. with 1770 fan RPM
Since 2.0 inches Ps exceeds the maximum static pressure in the table, the sound power levels for the maximum
static pressure should be used. Sound power levels should be interpolated for pressures between those listed.
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
1170
1770
2
Ps
0.00
0.40
0.60
0.80
0.00
0.90
1.40
1.83
1
71
70
69
69
76
75
75
76
2
79
75
74
73
77
75
75
74
3
75
72
70
68
85
84
82
78
4
72
70
69
66
83
80
78
75
5
75
73
72
71
82
79
78
76
6
70
65
62
59
81
78
76
73
7
59
55
53
50
77
71
69
65
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
50
46
45
44
63
61
60
59
LWiA
78
75
74
72
87
84
83
80
RPM
1170
1770
Ps
0.00
0.40
0.60
0.80
0.00
0.90
1.40
1.83
1
82
80
79
82
85
83
84
87
2
81
78
77
76
82
80
79
79
3
75
71
69
68
83
80
78
78
4
76
73
71
70
86
82
80
78
®
5
78
76
76
75
85
82
81
78
6
71
66
64
60
81
78
76
73
7
60
56
54
51
77
71
68
64
8
48
45
44
43
62
59
58
57
LWoA
81
78
77
76
89
86
84
81
Effect of Air Density - Temperature and Elevation
Ratings in the fan performance tables and curves of this catalog are based on standard air (clean, dry air with a
density of .075 pounds per cubic foot, barometric pressure at sea level of 29.92 inches of mercury, temperature of
70°F). Selecting a fan to operate at conditions other than standard air requires an adjustment to both static pressure
and brake horsepower.
A cubic foot of air has a constant volume regardless of temperature or elevation. However, air density changes with
non-standard temperature or elevation. Therefore, when selecting a fan to operate at a non-standard air density
using standard air density tables and curves, corrections must be made to parameters affected by air density.
These parameters are static pressure and brake horsepower.
For example, a size 30-QEID mixed
flow fan is to deliver 20,000 CFM at
5.0 in. static pressure. Elevation is
3000 feet, temperature is 100°F.
The 5.0 in. static pressure refers to
the static pressure at the operating
air density, in this case at 3000 feet,
100°F. Intuitively, we realize that
at higher than standard elevations
and temperatures, air density will be
lower than standard. Therefore, we
must determine what static pressure
at standard air density will equate
to 5.0 in. static pressure at our
operating density. Since standard air
density is greater than operating air
density in this case, we would expect
the static pressure after applying
the correction to be greater than the
original operating static pressure.
The table gives air density
correction factors for non-standard
temperatures and elevations.
Dry Air Density Correction Factor (I-P)
Multiply Standard Air Density, 0.075 lbm / ft3 by the Factor to obtain Density at Condition pb
Sea
Altitude, (Z)
ft.
-1000
1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
Level
Barometric in. Hg 31.02 29.92 28.85 27.82 26.82 25.84 24.89 23.98 23.09 22.22 21.39 20.58
Pressure
( pb ) in. wg 421.71 406.75 392.21 378.20 364.61 351.29 338.37 326.00 313.90 302.07 290.79 279.78
Temperature °F
(t)
-40
1.309
1.262
1.217
1.174
1.131
1.090
1.050
1.012
0.974
0.937
0.902
0.868
0
1.195
1.152
1.111
1.071
1.033
0.995
0.959
0.924
0.889
0.856
0.824
0.793
40
1.099
1.060
1.022
0.986
0.950
0.915
0.882
0.850
0.818
0.787
0.758
0.729
70
1.037
1.000
0.964
0.930
0.896
0.864
0.832
0.801
0.772
0.743
0.715
0.688
100
0.981
0.946
0.913
0.880
0.848
0.817
0.787
0.759
0.730
0.703
0.677
0.651
150
0.901
0.869
0.838
0.808
0.779
0.750
0.723
0.696
0.670
0.645
0.621
0.598
200
0.832
0.803
0.774
0.747
0.720
0.693
0.668
0.644
0.620
0.596
0.574
0.552
250
0.774
0.746
0.720
0.694
0.669
0.645
0.621
0.598
0.576
0.554
0.534
0.513
300
0.723
0.697
0.672
0.648
0.625
0.602
0.580
0.559
0.538
0.518
0.498
0.480
350
0.678
0.654
0.631
0.608
0.586
0.565
0.544
0.524
0.505
0.486
0.468
0.450
400
0.639
0.616
0.594
0.573
0.552
0.532
0.513
0.494
0.475
0.458
0.440
0.424
450
0.604
0.582
0.561
0.541
0.522
0.503
0.484
0.467
0.449
0.432
0.416
0.401
500
0.572
0.552
0.532
0.513
0.495
0.477
0.459
0.442
0.426
0.410
0.395
0.380
550
0.544
0.525
0.506
0.488
0.470
0.453
0.436
0.420
0.405
0.390
0.375
0.361
600
0.518
0.500
0.482
0.465
0.448
0.432
0.416
0.401
0.386
0.371
0.357
0.344
700
0.474
0.457
0.440
0.425
0.409
0.394
0.380
0.366
0.352
0.339
0.327
0.314
800
0.436
0.420
0.405
0.391
0.377
0.363
0.350
0.337
0.324
0.312
0.301
0.289
900
0.404
0.390
0.376
0.362
0.349
0.336
0.324
0.312
0.301
0.289
0.278
0.268
1000
0.376
0.363
0.350
0.337
0.325
0.313
0.302
0.291
0.280
0.269
0.259
0.250
Adapted from AMCA Standard 99-09, section 0200, Charts and Tables, with written permission from Air Movement
and Control Association International, Inc.
The example below shows the
relationship of fan performance at sea level and at 3000 ft. elevation and 100°F.
EXAMPLE
The following example shows how to properly select the fan described above:
Standard Air 70°F, Sea Level
Corrected Air 100°F, Altitude of 3000 ft.
5. Since the horsepower selected refers to standard air density,
this must be corrected to reflect actual Bhp at the lighter
operating air. Operating Bhp = standard Bhp x 0.848, or 31 x
0.848 = 26.3 Bhp. 30 HP motor would meet requirements.
25
Static Pressure (Pa x 100)
4. Refer to the fan performance table for a 30-QEID. At 20,000 CFM and 5.9 in. Ps: Fan RPM = 1770, Percent Wheel
Width = 70, Actual Volume 20,800 CFM, Bhp = 31.
70º pitch
RPM
Density 0.075
20
15
10
10
8
St
an
da
rd
Air,
177
0
Co
rre
ct
ed
A
ir, 1
7
30
RPM
70 R
PM
26 Bhp
24
ir, Bhp
Standard A
r, B
Corrected Ai
6
36
31 Bhp
hp
5.9 in. wg
18
5.0 in. wg
4
12
5
2
6
0
0
0
0
5
10
10
15
20
Volume (cfm x 1000)
20
30
Volume (m3/hr x 1000)
25
40
30
Brake Horsepower
2. Determine correction factor from chart for an elevation of 3000
feet and air temperature of 100°F. The correction factor is 0.848
3. Divide the specified operating static pressure by the correction
factor to determine the standard air density equivalent static
pressure (Corrected static pressure = 5.0 in. ÷ 0.848 = 5.9 in. Ps).
QEID-30
12
Static Pressure (in. wg)
1. Since the air volume delivered by the fan is not affected by
density, airflow remains 20,000 CFM.
0
50
If a fan is selected to operate at high temperatures, the motor must be of sufficient horsepower to handle the
increased load at any lower operating temperature where the air is more dense. Assume the air entering the 30
QEID fan at start-up is 0°F. For 0°F and 3000 feet elevation the air density correction factor is 1.033. Bhp at 0°F = 31
x 1.033 = 32, therefore, a 40 HP motor is required.
®
3
Motor Data
Greenheck QEID mixed flow fans can be supplied with any cast iron motor that is commercially available and
is appropriate for the fan size and performance required. The tables show motor frame sizes corresponding to
readily available 230/460 volt 3-phase 60 Hz motors. Consult factory (CF) for motor frame sizes on motors with
larger horsepower, 50 Hz, or different voltages. See the listed maximum and minimum motor frame size for each
fan size found on individual performance pages.
Notes:
1. Open Drip-Proof and Totally Enclosed motors have a 1.15 service factor.
2. Energy Efficient motors are in compliance with Energy Policy Act of 1992 (EPAct)
3. Premium Efficient motors meet NEMA Premium and CEE efficiency levels
690 RPM MOTORS
870 RPM MOTORS
All 690 RPM motors are build-ups. Consult factory for motor
frame sizes.
Single Speed
Explosion
Resistant
Premium
Efficient
254T
Explosion
Resistant
254T
CF
Energy
Efficient
Open
TE
254T
254T
7 1/2
256T
256T
CF
256T
256T
10
284T
284T
CF
284T
284T
15
286T
286T
CF
286T
286T
20
324T
324T
CF
324T
324T
25
326T
326T
CF
326T
326T
Open
TE
Open
TE
3/4
143T
143T
CF
143T
143T
30
364T
364T
CF
364T
364T
1
145T
145T
145T
145T
145T
40
365T
365T
CF
365T
365T
1 1/2
182T
182T
182T
182T
182T
50
404T
404T
CF
404T
404T
2
184T
184T
184T
184T
184T
60
405T
405T
CF
405T
405T
3
213T
213T
213T
213T
213T
75
444T
444T
CF
444T
444T
5
215T
215T
215T
215T
215T
100
445T
445T
CF
445T
445T
7 1/2
254T
254T
254T
254T
254T
10
256T
256T
256T
256T
256T
15
284T
284T
284T
284T
284T
20
286T
286T
286T
286T
286T
25
324T
324T
324T
324T
324T
30
326T
326T
326T
326T
326T
40
364T
364T
364T
364T
364T
50
365T
365T
365T
365T
365T
1770 RPM MOTORS
Single Speed
HP
Standard
Efficient
Explosion
Resistant
Premium
Efficient
Open
TE
Open
TE
1
143T
143T
CF
143T
143T
1 1/2
145T
145T
145T
145T
145T
60
404T
404T
404T
404T
404T
75
405T
405T
405T
405T
405T
100
444T
444T
444T
444T
444T
2
145T
145T
145T
145T
145T
445T
3
182T
182T
182T
182T
182T
184T
125
4
Standard
Efficient
HP
5
1170 RPM MOTORS
HP
Single Speed
Standard
Efficient
Open
TE
445T
445T
445T
445T
5
184T
184T
184T
184T
7 1/2
213T
213T
213T
213T
213T
10
215T
215T
215T
215T
215T
15
254T
254T
254T
254T
254T
20
256T
256T
256T
256T
256T
25
284T
284T
284T
284T
284T
30
286T
286T
286T
286T
286T
40
324T
324T
324T
324T
324T
50
326T
326T
326T
326T
326T
60
364T
364T
364T
364T
364T
75
365T
365T
365T
365T
365
®
QEID-12
Wheel Diameter
Outlet Area
Minimum Frame Size
Maximum Frame Size
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
1770
3500
Ps
0.00
0.60
1.00
1.30
0.00
2.50
4.00
5.00
1
70
71
71
83
89
80
82
86
2
71
69
69
74
78
78
80
84
3
74
72
72
74
83
82
80
84
4
75
71
69
70
87
87
84
89
5
73
71
69
69
88
86
85
87
6
73
71
69
68
87
86
85
86
7
71
65
64
63
84
82
81
82
15.00 in.
1.56 ft2
143T
184T
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
57
55
55
55
85
79
79
77
LWiA
79
76
75
74
93
91
90
92
RPM
1770
3500
Ps
0.00
0.60
1.00
1.30
0.00
2.50
4.00
5.00
1
81
79
82
98
97
92
97
98
2
76
73
71
85
87
88
90
94
3
79
75
74
78
89
86
87
90
4
77
73
70
75
91
89
91
91
5
78
76
73
75
89
88
88
87
6
75
73
70
70
89
89
90
89
7
71
66
65
65
86
86
87
84
8
57
55
55
56
85
80
80
78
LWoA
82
79
77
80
95
94
95
94
Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi, LWiA and
outlet LWo, LWoA sound power levels for full (100%) width wheels, installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the
effects of duct end correction. Ratings for outlet sound include the effects of duct end correction. The A-weighted sound power ratings shown have been
calculated per AMCA Standard 301.
®
5
QEID-15
Wheel Diameter
Outlet Area
Minimum Frame Size
Maximum Frame Size
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
1170
1770
Ps
0.00
0.40
0.60
0.80
0.00
0.90
1.40
1.83
1
71
70
69
69
76
75
75
76
2
79
75
74
73
77
75
75
74
3
75
72
70
68
85
84
82
78
4
72
70
69
66
83
80
78
75
5
75
73
72
71
82
79
78
76
6
70
65
62
59
81
78
76
73
7
59
55
53
50
77
71
69
65
18.25 in.
2.32 ft2
143T
145T
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
50
46
45
44
63
61
60
59
LWiA
78
75
74
72
87
84
83
80
RPM
1170
1770
Ps
0.00
0.40
0.60
0.80
0.00
0.90
1.40
1.83
1
82
80
79
82
85
83
84
87
2
81
78
77
76
82
80
79
79
3
75
71
69
68
83
80
78
78
4
76
73
71
70
86
82
80
78
5
78
76
76
75
85
82
81
78
6
71
66
64
60
81
78
76
73
7
60
56
54
51
77
71
68
64
8
48
45
44
43
62
59
58
57
LWoA
81
78
77
76
89
86
84
81
Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi, LWiA and
outlet LWo, LWoA sound power levels for full (100%) width wheels, installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the
effects of duct end correction. Ratings for outlet sound include the effects of duct end correction. The A-weighted sound power ratings shown have been
calculated per AMCA Standard 301.
6
®
QEID-16
Wheel Diameter
Outlet Area
Minimum Frame Size
Maximum Frame Size
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
1170
1770
Ps
0.00
0.50
0.70
0.95
0.00
1.15
1.60
2.17
1
74
74
72
73
80
79
79
80
2
82
78
77
76
80
79
78
77
3
78
75
73
71
88
87
85
81
4
75
73
71
69
86
82
81
78
5
78
76
75
74
84
82
81
78
6
72
68
65
61
84
81
79
76
7
61
58
56
53
80
74
72
68
20.00 in.
2.79 ft2
143T
145T
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
53
49
48
46
66
64
63
61
LWiA
81
78
77
75
90
87
85
82
RPM
1170
1770
Ps
0.00
0.50
0.70
0.95
0.00
1.15
1.60
2.17
1
85
82
82
85
88
86
86
90
2
84
81
79
79
85
83
82
82
3
78
74
72
71
86
82
81
81
4
79
76
74
73
89
85
83
81
5
81
79
78
78
88
85
84
81
6
74
69
66
63
84
81
79
75
7
63
59
56
54
80
74
71
67
8
51
48
47
45
65
62
61
60
LWoA
83
81
80
79
92
89
87
84
Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi, LWiA and
outlet LWo, LWoA sound power levels for full (100%) width wheels, installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the
effects of duct end correction. Ratings for outlet sound include the effects of duct end correction. The A-weighted sound power ratings shown have been
calculated per AMCA Standard 301.
®
7
QEID-18
Wheel Diameter
Outlet Area
Minimum Frame Size
Maximum Frame Size
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
1170
1770
Ps
0.00
0.70
1.00
1.35
0.00
1.60
2.30
3.10
1
75
73
72
73
80
76
74
76
2
79
76
73
72
79
74
72
74
3
79
75
73
71
89
85
82
78
4
76
73
71
69
86
83
81
78
5
73
71
70
68
84
81
79
77
6
74
70
67
64
81
78
77
75
7
64
62
60
57
83
75
72
70
22.25 in.
3.45 ft2
143T
184T
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
56
54
53
54
68
66
65
65
LWiA
80
76
75
72
90
86
84
81
RPM
1170
1770
Ps
0.00
0.70
1.00
1.35
0.00
1.60
2.30
3.10
1
82
78
78
85
90
85
85
87
2
78
76
75
77
84
79
78
80
3
78
74
73
74
90
85
82
82
4
79
76
74
74
88
84
82
81
5
77
75
74
73
88
85
83
81
6
75
71
68
65
83
80
79
76
7
66
62
60
58
84
77
73
70
8
56
53
52
52
69
66
64
64
LWoA
82
79
77
76
92
88
86
84
Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi, LWiA and
outlet LWo, LWoA sound power levels for full (100%) width wheels, installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the
effects of duct end correction. Ratings for outlet sound include the effects of duct end correction. The A-weighted sound power ratings shown have been
calculated per AMCA Standard 301.
8
®
QEID-20
Wheel Diameter
Outlet Area
Minimum Frame Size
Maximum Frame Size
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
1170
1770
Ps
0.00
0.90
1.25
1.65
0.00
2.10
2.90
3.78
1
79
76
76
77
84
80
78
80
2
83
79
77
75
82
78
76
77
3
82
78
76
74
92
88
85
81
4
79
76
74
72
89
86
84
81
5
76
74
73
71
87
84
82
80
6
77
73
70
67
84
81
80
77
7
67
64
63
60
86
78
75
72
24.50 in.
4.14 ft2
143T
215T
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
58
57
56
56
71
68
68
68
LWiA
83
79
78
75
93
89
87
84
RPM
1170
1770
Ps
0.00
0.90
1.25
1.65
0.00
2.10
2.90
3.78
1
85
81
81
88
93
88
88
90
2
81
78
77
80
86
82
81
83
3
81
77
76
77
93
87
85
85
4
82
79
77
77
91
87
85
84
5
80
78
77
76
91
88
86
84
6
78
74
71
68
86
83
81
79
7
68
65
63
60
87
80
76
73
8
58
56
55
55
72
69
67
67
LWoA
85
82
80
79
95
91
89
87
Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi, LWiA and
outlet LWo, LWoA sound power levels for full (100%) width wheels, installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the
effects of duct end correction. Ratings for outlet sound include the effects of duct end correction. The A-weighted sound power ratings shown have been
calculated per AMCA Standard 301.
®
9
QEID-22
Wheel Diameter
Outlet Area
Minimum Frame Size
Maximum Frame Size
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
1170
1770
Ps
0.00
1.10
1.60
2.10
0.00
2.50
3.70
4.81
1
75
72
71
73
83
80
79
83
2
84
81
80
78
87
82
81
83
3
83
80
79
76
92
90
89
86
4
80
78
76
74
92
89
87
84
5
78
76
75
73
90
88
86
83
6
77
72
70
69
86
83
82
79
7
74
66
64
64
87
79
77
75
27.00 in.
5.12 ft2
182T
215T
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
61
59
59
62
75
71
71
72
LWiA
84
81
79
77
95
92
90
88
RPM
1170
1770
Ps
0.00
1.10
1.60
2.10
0.00
2.50
3.70
4.81
1
81
77
76
77
88
83
82
84
2
84
80
78
78
89
84
83
85
3
83
79
78
76
94
91
90
87
4
84
82
80
77
95
92
90
88
5
81
80
79
76
93
91
90
87
6
78
74
73
70
88
85
84
81
7
75
68
66
64
88
81
78
76
8
61
59
58
59
77
72
70
70
LWoA
86
84
82
79
98
95
93
91
Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi, LWiA and
outlet LWo, LWoA sound power levels for full (100%) width wheels, installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the
effects of duct end correction. Ratings for outlet sound include the effects of duct end correction. The A-weighted sound power ratings shown have been
calculated per AMCA Standard 301.
10
®
QEID-24
Wheel Diameter
Outlet Area
Minimum Frame Size
Maximum Frame Size
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
1170
1770
Ps
0.00
1.30
2.00
2.60
0.00
3.00
4.60
5.95
1
79
75
75
77
87
83
83
86
2
88
85
83
82
90
86
84
87
3
86
84
82
80
95
93
92
89
4
83
81
79
77
95
92
91
88
5
81
79
78
76
93
91
89
86
6
80
75
74
72
89
86
85
82
7
78
69
68
67
90
82
80
78
30.00 in.
6.21 ft2
213T
256T
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
64
62
63
65
78
75
74
75
LWiA
87
84
82
81
98
95
93
91
RPM
1170
1770
Ps
0.00
1.30
2.00
2.60
0.00
3.00
4.60
5.95
1
84
81
80
80
91
86
86
88
2
87
83
82
81
92
87
86
88
3
86
83
81
79
97
95
93
91
4
87
85
83
80
98
95
94
91
5
84
83
82
79
97
94
93
90
6
81
78
76
73
92
89
87
84
7
79
71
69
67
91
84
82
79
8
65
62
61
62
80
75
74
74
LWoA
89
87
85
83
101
98
96
94
Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi, LWiA and
outlet LWo, LWoA sound power levels for full (100%) width wheels, installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the
effects of duct end correction. Ratings for outlet sound include the effects of duct end correction. The A-weighted sound power ratings shown have been
calculated per AMCA Standard 301.
®
11
QEID-27
Wheel Diameter
Outlet Area
Minimum Frame Size
Maximum Frame Size
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
1170
1770
Ps
0.00
1.60
2.30
3.10
0.00
3.65
5.25
7.09
1
82
79
78
80
90
87
86
90
2
91
88
87
85
93
89
87
90
3
90
87
85
83
99
96
95
92
4
86
84
82
80
98
95
94
91
5
84
82
81
79
96
94
92
89
6
83
78
77
75
92
89
88
85
7
81
72
71
70
93
85
83
81
33.00 in.
7.54 ft2
213T
286T
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
67
65
66
68
81
77
77
78
LWiA
90
87
85
84
101
98
96
94
RPM
1170
1770
Ps
0.00
1.60
2.30
3.10
0.00
3.65
5.25
7.09
1
87
84
82
83
94
89
89
90
2
90
86
84
84
95
90
89
91
3
4
5
89 90 87
86 88 86
84 86 85
82 83 82
100 101 100
97 98 97
96 96 96
93 94 93
6
84
80
79
76
94
91
90
87
7
82
74
72
70
94
87
84
82
8
67
65
64
65
83
78
77
77
LWoA
92
90
88
86
104
101
99
97
Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi, LWiA and
outlet LWo, LWoA sound power levels for full (100%) width wheels, installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the
effects of duct end correction. Ratings for outlet sound include the effects of duct end correction. The A-weighted sound power ratings shown have been
calculated per AMCA Standard 301.
12
®
QEID-30
Wheel Diameter
Outlet Area
Minimum Frame Size
Maximum Frame Size
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
1170
1770
Ps
0.00
1.90
2.90
3.80
0.00
4.35
6.65
8.70
1
86
82
82
84
94
90
90
93
2
94
91
90
88
97
92
91
93
3
4
93 89
90 87
88 85
86 83
102 101
99 98
98 97
95 94
5
87
85
84
82
99
97
95
92
6
86
81
80
78
95
92
91
88
7
84
75
74
73
96
88
86
84
36.50 in.
9.31 ft2
254T
326T
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
70
68
69
71
84
81
80
81
LWiA
93
90
89
87
104
101
100
97
RPM
1170
1770
Ps
0.00
1.90
2.90
3.80
0.00
4.35
6.65
8.70
1
90
87
86
86
97
92
92
94
2
93
89
88
87
98
93
92
94
3
4
5
92 93 90
89 91 89
87 89 88
85 86 85
103 104 103
101 101 100
99 100 99
97 97 96
6
87
84
82
79
98
95
93
90
7
85
77
75
73
97
90
88
85
8
71
68
67
68
86
81
80
80
LWoA
95
93
91
89
107
104
102
100
Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi, LWiA and
outlet LWo, LWoA sound power levels for full (100%) width wheels, installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the
effects of duct end correction. Ratings for outlet sound include the effects of duct end correction. The A-weighted sound power ratings shown have been
calculated per AMCA Standard 301.
®
13
QEID-33
Wheel Diameter
Outlet Area
Minimum Frame Size
Maximum Frame Size
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
1170
1770
Ps
0.00
2.25
3.45
4.50
0.00
5.15
7.90
10.30
1
85
82
81
87
92
89
88
94
2
93
92
90
90
99
97
95
98
3
4
5
95 95 91
93 92 88
91 90 87
89 88 85
104 104 102
103 102 100
101 99 98
101 98 96
6
90
85
83
81
99
96
94
92
7
89
81
77
76
99
92
90
88
40.25 in.
11.27 ft2
254T
365T
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
76
72
72
72
93
86
84
83
LWiA
97
94
92
90
107
104
102
101
RPM
1170
1770
Ps
0.00
2.25
3.45
4.50
0.00
5.15
7.90
10.30
1
89
88
88
89
96
95
95
96
2
95
94
92
92
100
99
99
99
3
98
96
95
93
105
104
103
102
4
100
98
96
94
108
106
104
102
5
6
7
95 92 90
93 89 83
91 86 80
89 84 77
107 103 100
105 100 96
103 98 93
101 96 90
8
77
73
72
72
94
88
86
84
LWoA
101
98
96
94
111
109
107
105
Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi, LWiA and
outlet LWo, LWoA sound power levels for full (100%) width wheels, installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the
effects of duct end correction. Ratings for outlet sound include the effects of duct end correction. The A-weighted sound power ratings shown have been
calculated per AMCA Standard 301.
14
®
QEID-36
Wheel Diameter
Outlet Area
Minimum Frame Size
Maximum Frame Size
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
870
1170
Ps
0.00
1.55
2.30
3.10
0.00
2.80
4.20
5.55
1
85
81
80
85
89
86
85
90
2
95
92
89
88
97
95
93
93
3
87
85
83
81
98
96
94
92
4
88
86
85
84
98
95
93
91
5
85
83
81
79
94
92
90
88
6
88
81
78
75
93
88
86
84
7
75
72
70
70
92
84
80
79
44.50 in.
13.79 ft2
254T
365T
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
68
65
65
66
79
75
75
76
LWiA
92
88
86
85
101
97
95
93
RPM
870
1170
Ps
0.00
1.55
2.30
3.10
0.00
2.80
4.20
5.55
1
86
84
83
85
92
91
91
92
2
92
92
91
91
98
97
96
95
3
4
92 96
90 96
88 94
87 91
101 103
100 101
98 99
96 97
5
89
87
85
83
98
96
94
92
6
89
83
81
78
95
92
90
87
7
79
75
72
70
93
87
83
80
8
70
66
65
66
80
76
75
75
LWoA
96
95
93
90
104
102
100
97
Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi, LWiA and
outlet LWo, LWoA sound power levels for full (100%) width wheels, installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the
effects of duct end correction. Ratings for outlet sound include the effects of duct end correction. The A-weighted sound power ratings shown have been
calculated per AMCA Standard 301.
®
15
QEID-40
Wheel Diameter
Outlet Area
Minimum Frame Size
Maximum Frame Size
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
870
1170
Ps
0.00
1.90
2.80
3.75
0.00
3.45
5.10
6.80
1
88
84
83
88
92
90
89
94
2
3
4
98 90 91
95 88 89
92 86 88
91 84 87
100 101 101
98 99 98
96 97 96
96 95 94
5
88
86
84
82
97
94
93
91
6
91
84
80
78
96
91
89
87
7
78
75
73
73
95
87
83
82
49.00 in.
16.77 ft2
284T
365T
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
71
68
68
69
82
78
78
78
LWiA
95
91
89
88
103
100
98
96
RPM
870
1170
Ps
0.00
1.90
2.80
3.75
0.00
3.45
5.10
6.80
1
89
87
86
88
95
94
94
95
2
3
4
5
95 95 99 92
95 93 98 90
94 91 97 88
94 90 94 85
101 104 106 101
100 102 104 99
98 101 102 97
98 99 100 95
6
91
86
83
81
98
95
92
90
7
82
78
75
73
96
89
86
83
8
72
69
68
69
83
79
78
78
LWoA
99
97
96
93
107
104
102
100
Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi, LWiA and
outlet LWo, LWoA sound power levels for full (100%) width wheels, installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the
effects of duct end correction. Ratings for outlet sound include the effects of duct end correction. The A-weighted sound power ratings shown have been
calculated per AMCA Standard 301.
16
®
QEID-44
Wheel Diameter
Outlet Area
Minimum Frame Size
Maximum Frame Size
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
870
1170
Ps
0.00
2.30
3.45
4.60
0.00
4.15
6.25
8.30
1
92
88
87
92
96
93
92
97
2
3
4
5
101 93 94 91
98 91 92 89
95 89 91 87
94 87 90 85
103 104 104 100
101 102 101 98
100 100 99 96
99 98 97 94
6
94
87
84
81
99
94
92
90
7
81
78
76
76
98
90
86
85
54.25 in.
20.49 ft2
324T
405T
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
74
71
71
72
85
81
81
82
LWiA
98
94
92
91
107
103
101
99
RPM
870
1170
Ps
0.00
2.30
3.45
4.60
0.00
4.15
6.25
8.30
1
92
90
89
91
98
97
97
98
2
98
98
97
97
104
103
102
101
3
98
96
94
93
107
106
104
102
4
5
6
102 95 95
102 93 89
100 91 87
97 89 84
109 104 101
107 102 98
105 100 96
103 98 93
7
85
81
78
76
99
93
89
86
8
76
72
71
72
86
82
81
81
LWoA
102
101
99
96
110
108
106
103
Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi, LWiA and
outlet LWo, LWoA sound power levels for full (100%) width wheels, installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the
effects of duct end correction. Ratings for outlet sound include the effects of duct end correction. The A-weighted sound power ratings shown have been
calculated per AMCA Standard 301.
®
17
QEID-49
Wheel Diameter
Outlet Area
Minimum Frame Size
Maximum Frame Size
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
870
1170
Ps
1
0.00 95
2.70 91
4.15 90
5.55 95
0.00 99
4.90 96
7.50 95
10.10 101
2
104
101
99
97
106
105
103
102
3
97
94
92
90
107
105
103
101
4
5
6
7
97 94 97 84
95 92 90 81
94 90 87 79
93 88 84 79
107 103 102 101
104 101 97 93
102 99 95 89
100 97 93 88
60.00 in.
24.85 ft2
364T
445T
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
77
74
74
75
88
84
84
85
LWiA
101
97
95
94
110
106
104
102
RPM
870
1170
Ps
0.00
2.70
4.15
5.55
0.00
4.90
7.50
10.10
1
95
93
92
94
101
100
100
101
2
101
101
100
100
107
106
105
104
3
101
99
97
96
110
109
107
105
4
105
105
103
100
112
110
108
106
5
6
7
98 98 88
96 92 84
94 90 81
92 87 79
107 104 102
105 101 96
103 99 92
101 96 89
8
79
75
74
75
89
85
84
84
LWoA
105
104
102
99
113
111
109
106
Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi, LWiA and
outlet LWo, LWoA sound power levels for full (100%) width wheels, installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the
effects of duct end correction. Ratings for outlet sound include the effects of duct end correction. The A-weighted sound power ratings shown have been
calculated per AMCA Standard 301.
18
®
QEID-54
Wheel Diameter
Outlet Area
Minimum Frame Size
Maximum Frame Size
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
690
870
Ps
0.00
2.10
3.20
4.20
0.00
3.35
5.10
6.70
1
96
92
91
93
98
94
93
98
2
100
97
95
93
107
104
102
100
3
95
92
91
89
99
97
95
93
4
94
92
91
89
100
98
97
96
5
93
89
87
85
97
95
93
91
6
90
85
82
80
100
93
89
87
7
79
76
75
75
87
84
82
82
66.00 in.
30.46 ft2
364T
445T
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
73
70
70
72
80
77
77
78
LWiA
97
94
92
90
104
100
98
97
RPM
690
870
Ps
0.00
2.10
3.20
4.20
0.00
3.35
5.10
6.70
1
95
93
93
94
98
96
95
97
2
99
98
97
97
104
104
103
103
3
100
99
97
95
104
102
100
99
4
5
6
101 96 92
100 93 87
98 90 85
95 88 82
108 101 100
107 99 95
106 97 92
103 94 90
7
83
79
77
76
91
87
84
82
8
73
71
70
71
81
78
77
78
LWoA
102
99
98
95
108
106
105
102
Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi, LWiA and
outlet LWo, LWoA sound power levels for full (100%) width wheels, installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the
effects of duct end correction. Ratings for outlet sound include the effects of duct end correction. The A-weighted sound power ratings shown have been
calculated per AMCA Standard 301.
®
19
QEID Dimensional Data
Size
Slip-Fit
O.D.
12
15
16
18
20
22
24
27
30
33
36
40
44
49
54
Length
Slip Fit O.D.
inches
mm
Length*
inches
mm
Weight**
lbs.
kg.
17.13
435
25.0
635
100
45
20.88
530
25.0
635
140
65
23.00
584
26.0
660
170
80
25.38
645
29.0
737
200
95
27.81
706
34.0
864
250
115
30.88
784
35.5
902
370
170
34.00
864
41.5
1054
480
220
37.44
951
45.0
1143
570
260
41.63
1057
860
390
45.75
1162
1140
520
50.56
1284
1360
620
55.75
1416
1650
750
61.63
1565
2190
995
67.75
1721
2700
1225
75.00
1905
3130
1420
Refer to
table below.
*Length of unit varies with motor frame size. See table below.
**Weight is for unit only and does not include motor.
Length — inches (millimeters)
284/6 T
324/6 T
364/5 T
Size
254/6 T
30
45.5 (1156)
50.0 (1156)
50.0 (1156)
33
46.5 (1181)
54.0 (1372)
54.0 (1372)
54.0 (1372)
36
50.5 (1283)
58.0 (1473)
58.0 (1372)
58.0 (1372)
56.5 (1435)
61.0 (1549)
61.0 (1549)
64.0 (1626)
64.0 (1626)
70.0 (1778)
49
74.5 (1892)
74.5 (1892)
80.5 (2045)
54
77.0 (1956)
77.0 (1956)
83.0 (2108)
40
44
404/5 T
444/5 T
Our Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period
of one year from the shipment date. Any units or parts which prove defective during the warranty
period will be replaced at our option when returned to our factory, transportation prepaid. Motors are
warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck
prove defective during this period, they should be returned to the nearest authorized motor service
station. Greenheck will not be responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifications without notice.
P.O. Box 410 • Schofield, WI 54476-0410 • Phone (715) 359-6171 • greenheck.com
®
Copyright © 2010 Greenheck Fan Corp. • QEID Supplement Rev 2 January 2010 PD (00.CVI.9005 R2 1-2010)