Below you will find brief information for Air Cooled Water Chiller SyScroll 85-135 Air. This air-cooled water chiller is designed for cooling and heating applications, and it utilizes R410A refrigerant. It features a tandem scroll compressor, plate heat exchanger, and a ventilating unit with quiet fans. These units are available in two acoustic options, standard and super low noise. It is important to note that the standard version can be supplied with a pressure actuated stepless type fan speed controller for low ambient operation (-14 °C) while the Super Low Noise version is supplied with this as standard. The SyScroll units are equipped with safety features such as high pressure switch, low pressure switch, water flow switch and more. They also offer control features such as chilled and hot water temperature regulation, evaporator antifreeze protection and heat pump defrost control. With a wide range of operating limits and capacity steps, the SyScroll 85-135 Air can be easily integrated into a variety of HVAC systems.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

SyScroll 85-135 Air Engineering Data Manual | Manualzz

Chiller | Close Control | Water terminals

SyScroll 85-135 Air

NEW

Air Cooled Water Chillers

Cooling Only, Heat Pump

Engineering Data Manual

84 to 132 kW 88 to 135 kW

SyScroll 85-135 Air |

3

Key point

General

SyScroll Air have been designed and optimized to work with R410A refrigerant . As near azeotropic mixture it behaves like a homogeneous substance (reduced service problems in case of leakage or re-charge) with negligible temperature glide.

Units with high seasonal performances ( ESEER up to

4.4

).

With except for the fans, all the versions keep the same configuration of the base units (same structure, electrical board, compressors and coils).

Easy upgrade of the units in stock or on the field .

Electronic expansion devices on all units: superheating value controlled by microprocessor, simple and accessible refrigeration system especially for heat pump versions with reduction of brazing points and than possible leakage.

New Microchannel coils for Cooling only version.

Compressors box (less sound proofing) always installed

- additional compressors jackets only for S version (easy upgrade of the units in stock) .

High Temperature Version (HT) developed for high ambient temperature but also providing high seasonal efficiency (ESEER higher than and high operation limits with inverter fans (electronic brushless type motor).

Special version (HPF) for high external static pressure

(max. 120 Pa) with inverter fans (electronic brushless type motor).

New microprocessor : 4 times greater RAM memory compared with previous version, flash memory card and compressors envelope curves put inside, 3 times faster than previous control.

Hydro kits with or without buffer tank (205 l from 85 to

105 size, 320 l from 120 to 135 size).

One or two water pumps are available: standard pressure (100 kPa) or high pressure (200 kPa).

For service operation, special valves dedicated to R410A are supplied on the refrigerant system. These valves, of

5/16” flare SAE type, are mounted on the liquid line, discharge, suction line and on the gauges manifold of the unit.

4

|

SyScroll 85-135 Air

Specifications

SY SCROLL

SIZES Air

CO

HP

RE

BC

-

HT

HPF

-

S

CO = Cooling Only; HP = Heat Pump; RE = Remote Evaporator; BC = Brine for Process Cooling.

General

The new SyScroll Air units have been designed to operate with HFC 410A refrigerant. Both compressors and heat exchangers (plate heat exchanger and coils) have been optimized for this refrigerant.

They consist of a single refrigerant circuit equipped with a tandem complete with high efficiency and low vibration level Scroll compressors, a single circuit plate heat exchanger and a ventilating unit comprising V-shape coils and quiet fans; each of them is located in an externally mounted nozzle profile housing generating low sound level.

Syscroll Air CO units are available in 5 sizes , with a nominal capacity range from 84 to 132 kW .

SyScroll Air HP units are available in 5 sizes , with a nominal capacity range from 79 to 125 kW in cooling mode and from 85 to 133 kW in heating mode.

HPF (High Pressure Fans) version : It has same equipment as Basic version, except that the units are equipped with special inverter fans (same as those used on HT version, but with a different regulation) driven by EC motors with integrated electronic inverter . HPF version provides external static pressure up to 120 Pa . This version can be supplied with BLN acoustic option only.

In addition, partial heat recovery option is available:

Desuperheater : All the versions can be supplied with plate type heat exchangers fitted, one on each refrigerant circuit, on the compressor discharge line to recover about 20 % of the total heat rejected to the condensers.

Conformity with directives

The following applies to all the sizes and versions:

Machine Directive: 2006/42/EC

Electromagnetic Compatibility Directive: 2004/108/EC

Pressure Equipment Directive: 97/23/EC

SyScroll Air (Standard) version can be supplied with 2 acoustic options :

Basic Low Noise (-) : The units are equipped with delta connected fans implying a standard rpm. The chillers are not supplied with fan speed controller, but fitted with compressors box to reduce the noise emissions.

Super Low Noise (S) : The units are equipped with star connected fans , fitted with a speed controller which allows the units to operate with a very low rpm. The chillers are supplied with compressors box and soundproof jackets on compressors reducing significantly the noise emissions.

To increase their field of applications, the SyScroll Air ranges are available in 2 additional versions :

HT (High Temperature) version : It has same equipment as Basic version, but the units are fitted with special inverter fans and motors to ensure low energy consumption and to operate on a wider envelope. The HT version can be supplied with BLN acoustic option only.

Cabinet and structure

The unit cabinet and structure are made of heavy gauge galvanized steel coated with polyester powder based painting (RAL 7040). All parts of the structure are fastened totally with non-corrosive screws and bolts.

Compressors

Each unit is equipped with two compressors arranged in tandem.

Compressors are of hermetic scroll type and fitted with an electronic control system ensuring protection against high temperature and excessive load.

All compressors have direct-on-line starting and are mounted on rubber vibration isolators in order to minimize noise and vibration transmission.

SyScroll 85-135 Air |

5

Evaporator

Evaporators is of a brazed stainless steel plate type heat exchanger.

It is insulated with a 19 mm thick closed cell polyethylene foam material and is fitted with a film type electric heater on the external surface to prevent the unit from freezing at a low temperature (down to -18 °C) when the unit is off.

Water connections are of a Male GAS Threaded type

(2”1/2 diameter).

Heat pump units (HP) are provided with 4-way reversing valve, suction accumulator and liquid receiver on the liquid line.

The functional diagram of each circuit is shown in the section “Refrigerant flow diagram”.

Electrical board

Metal case, externally arranged at one end of the unit.

Case for the board with IP44 protection rating, complete with grille for natural air ventilation of the box.

Condenser coils

The condenser coils are made of seamless copper tubes, arranged in staggered rows, mechanically expanded into corrugated aluminum fins.

For Cooling only version (CO version) condenser coils are of microchannel type, made of 100% aluminium (fins, tubes and headers) with the exception of pipe couplings which are in copper.

Condenser fans

For each size, all versions keep the same number of fans.

Large diameter, direct drive axial type fans with asynchronous three-phase motors are used in all acoustic versions (S version) of SyScroll 85-135 Air.

Special inverter fans with electronic brushless type motors are used in SyScroll 85-135 Air HT and HPF.

On high pressure fans of HPF units, the external static pressure (≤ 120 Pa) can be adjusted on site to match the customer demand directly from the electronic control panel of the unit.

Fans are equipped with externally mounted nozzle profile housing which generates low sound levels.

Control and safety devices

Each unit is fitted with the following devices:

Safety:

Power disconnect switch with an emergency stop func

tion.

HP switch, set to 40.5 bar, automatic and manual reset to be reinitialized from the control panel.

Water flow switch on the evaporator, protect the unit

against low water flow operation.

Antifreeze temperature sensor (set to +4 °C) on the

evaporator.

Safety valve on discharge line, set to 45 bar.

Control:

HP and LP transducers.

Evaporator water inlet temperature sensor.

Evaporator water outlet temperature sensor (with an antifreeze function).

Suction temperature sensor (in case of EEV option).

Ambient air temperature sensor.

Coil temperature sensor.

Fan speed control

The speed of fans is controlled in order to operate at a low ambient temperature.

On units with standard axial fans, the accessory fan speed control, supplied as standard on S version, is of a pressure actuated stepless type with an electronic controller.

The pressure actuated stepless type fan speed controller can be supplied as optional on - version. It allows the units to operate in cooling mode at ambient temperature down to -14 °C.

On HT and HPF units with electronic axial fans, the pressure actuated stepless type fan speed control is supplied as standard, because these electronic fans are already equipped with an integrated fan speed control (fan speed range: 50 to 1200 rpm; ambient temperature limit: -18 °C

(in cooling mode only).

Refrigerant circuits

All the units are composed a single refrigerant circuit.

Each refrigerant circuit is equipped with liquid line and discharge line shutoff valves, filter-drier with solid core, sight glass and thermostatic expansion valve (electronic expansion valve can be supplied as an option) .

Electronic control

Units are supplied with the new microprocessor-based electronic control and management system ensuring the following functions:

Management of the operation of compressors:

Power on/off

Anticycle management

Tandem unloading for high pressure or high compressor pressure ratio (integrated inside the curves of compressor operating limits).

Chilled and hot water temperature regulation (control option on inlet water temperature RWT (P+I type) or outlet water temperature LWT (neutral band type) of the evaporator.

Control of superheating on suction line (in case of EEV option).

Evaporator antifreeze protection.

Heat pump defrost control for automatic operation.

Management of high and low pressure alarms.

Management of the electronic expansion valves by means of EXV controller allowing optimized functions: cooling, heating, start-up and defrost (in case of EEV option).

6

|

SyScroll 85-135 Air

Management of external interlocks.

Management of the remote control:

Unit power on/off

Summary alarm signals

Remote signalling, by dry contacts:

Voltage presence

Compressors in operation

General Alarm

Management of the hydro kit: start-up of pump, antifreeze heater of external tank.

The unit controller can also clearly show all control parameters of the machine on the liquid crystal display, such as:

Display of superheating value (in case of EEV option).

Display of the temperature at the evaporator inlet and outlet.

Display of the ambient air temperature.

Display of discharge pressure and suction pressure.

Display of the set point.

Display of the various alarm and operation status:

Low / High pressure

Evaporator antifreeze

Flow switch signal for lack of water

Control of the compressor operating hours

Compressors in operation

Pump in operation and operating hours

Thermal protection of compressors

Thermal protection of fans

Faulty sensors

Standard equipment

Set point timer/clock card.

Pressure actuated fan speed control.

Back light display.

Digital pressure and temperature reading kit.

High ambient pressure control.

Sequence phase control.

Control circuit transformer 400 V/230 V.

Data logger.

Power supply without neutral.

Hour meter.

Main switch.

Refrigerant R410A.

PED approval.

Evaporator antifreeze electric heater.

Compressor jacket (standard on S version).

Compressor box.

Water flow switch.

Optional hydro kits

On board mounted inside and remote hydrokits are available as optional. The on board hydro kits can be supplied with or without buffer tank while remote hydro kits (supplied loose for field installation) are always provided with internal tank.

On board hydro kit without buffer tank has the following components:

Single or double pump with low static pressure (100 kPa) or high static pressure (200 kPa),

Expansion tank (18 litres for all models),

Water filter option (supplied loose),

Shut-off valves,

Safety valve,

Automatic air vent valve,

Thermal insulation for pipes and water pump(s),

The on board hydro kit with buffer tank has the following components:

Single or double pump with low static pressure (100 kPa) or high static pressure (200 kPa),

Buffer tank (205 l from 85 to 105 size, 320 l from 120 to 135 size),

Expansion tank (18 litres for all models),

Water filter option (supplied loose),

Shut-off valves,

Safety valve,

Automatic air vent valve,

Thermal insulation for pipes and water pump(s),

Electrical box,

Antifreeze electric heater inside buffer tank (electric heater for pipes is not supplied).

Factory installed options

ModBus protocol kit for BMS.

Lonwork protocol kit for BMS.

Bacnet protocol kit for BMS.

Compressors soft starter.

Pressure actuated stepless fan speed controller for low ambient operation (-14 °C).

Double set point.

Power factor correction capacitors.

Compressors overload protection.

GSM.

HP & LP manometers.

Ecoating for Microchannel and AL/CU. Blue fins treatment for AL/CU.

Condenser coils with copper fins.

Coil grilles.

Chiller grilles.

Desuperheater.

On board hydro kits 1P/2P with/witout tank.

Field-installed accessories

Remote ON/OFF control.

Remote keyboard panel.

Master and slaves control, up to 4 units max.

Spring anti-vibration.

Water filter.

Remote hydro kits with buffer tank, 1 or 2 low or high pressure pump(s), relevant accessories and with or without antifreeze heater:

300 litres: sizes 85-105.

500 litres: sizes 120-135.

SyScroll 85-135 Air |

7

Accessories & Options

SyScroll Air

Set point timer/Clock card

Back light display

Digital pressures and temperatures reading Kit

High pressure control on capacity

Sequence phases control

Control circuit transformer 400V/230V

Data logger

Power supply without neutral

Hour meter

Main switch

Flow switch

Antifreeze electric heater kit

Compressor Jacket

Remote On/Off control

Remote keyboard panel

Electronic expansion valves

Modbus protocol kit for BMS

Lonwork protocol kit for BMS

Bacnet protocol kit for BMS

Interface Kit ethernet/webctrl pcos

(Modbus & Bacnet already included)

Softstarter for compressor

Low ambient kit (-14°C)

(pressostatic stepless fan speed control)

Double set point

Power factor corrector capacitors

Overload protection for compressors

Delivery

Std

Std

Std

Std

Std

Std

Std

Std

Std

Std

Std

Std

Std SLN

Accessory

Accessory

Option

Option

Abbreviation Description & Befenit

CLK

PHC

To schedule 4 different interval time with different active water T setpoint.

User Display panel mounted. Suggested for outdoor installation.

Pressure Transducers & Sensors to show the Discharge and

Suction pressure and temperature during running condition.

Functions able to protect multistage circuit from High discharge pressure values. Circuit is partloaded whenever the Discharge pressure is too high to prevent HP tripping.

It allows to check the correct sense R-S-T of electric supply phases for 400/3/50 units.

TRF

DL

3PH

FS

EEH

CJ

Voltage transformer to provide correctly the separated voltage to the auxiliary line.

Record continuously the essential thermodynamic operating parameters, during the last hours. This facilitates debug and service activity on field.

Unit to be supplied with 400/3/50. No need of Neutral cable.

Total running hours recorded for each compressors and for total unit. Also record of total scroll compressors starts.

Front operated switch-disconnector with direct mounted handle to cut the power Supply Line according CE standards.

Prevents the operation of the unit if the circulating chilled fluid is insufficient. It is recommended to install a flow switch to ensure the correct operation of the unit.

Electrical Heater protects the plate exchanger.

Jacket for each compressors in order to reduce the sound of its.

It enables the operator to power on the unit when it is in standby mode, to display alarms and switch over cooling–heat pump. Maximum lenght: 50mt.

EEV

MBS

Makes it possible to control the unit through the remote terminal, up to a maximum distance of 400mt of telephone cable.

It is the device able to control the refrigerant flow on suction line trough a stepper motor in order to keep the superheat as constant as possible.

It permits the integration of the unit with BMS with Modbus protocol trough RS485 port.

Option LON

It permits the integration of the unit with BMS with Lonwork

Network.

Option

Option

Option

Option

Option

Option

Option

BAC

SS

FSC

DSP

PFC

CP

It permits the integration of the unit with BMS with Bacnet protocol trough RS485 port.

It permits the integration of the unit with BMS with Modbus or

Bacnet protocol trough Ethernet port (TCP/IP).

An electronic device that automatically starts up the compressors gradually. The starting current can be reduced by up to 40% of the direct on line value.

Electronic speed controllers are designed to control the speed of fan motors in Air Cooled Chiller and Heatpump. Fan Speed controlled by Condensing Pressure in cool mode or by Air Temp in heat mode. Using variable fan speed controllers offers following benefits in commercial refrigeration or air-conditioning applications High

Efficiency, Low Noise level, Low air temperature in cool mode and

High air temperature in heat mode.

Can manage two different applications (set point) selected by remote dry contact Circuit 1 and Circuit 2.

On/Off or Part Load by remote Dry contact.

The purpose of the power factor corrector capacitor is to minimize the input current distortion and make the current in phase with the voltage. Target is to keep Power Factor about 0.90 in any running condition.

The compressor is equipped with an amperometrical protection

(overload protection) wired under the compressor contactor; this protection operates: a) if compressor’s temperature is too high. b) if current’s absorption is too high.

8

|

SyScroll 85-135 Air

Accessories & Options (continued)

SyScroll Air

Sequencer for up to 4 chillers installation

Master and slave up to 4 chillers installation:

CHILLERNET

GSM

Automatic circuit breaker

Mechanical gauges kit (HP and LP manometers)

E-coating MCHX

Copper Fins

Coil Guards

Chiller grilles

Desuperheater

Water pressure switch

Water filter

Delivery

Accessory

Abbreviation Description & Befenit

SEQ

It can easily pilot up to 4 units, chiller or heat pumps, belonging to the same family, fitted in parallel, 50 metres apart maximum.

Accessory

Option

Option

Option

Option

Option

Option

Option

Option

Accessory

Accessory

GSM

ACB

KM

CU/CU

CG

KG

D

It is a network of chillers. They are hydraulically connected in parallel on the same installation. They are intended to work together as a single machine whose capacity equals the total amount of capacities. Up to 4 chillers of the same family can be connected together.

One of these chillers is called MASTER, the others are SLAVE. The

MASTER chiller will control all the other chillers.

Makes it possible to check the working mode or the switching on/ off of the unit via SMS. In case of any alarms, the unit sends an

SMS to the user.

ACB is an automatically operated electrical switch designed to protect an electrical circuit from damage caused by overload or short circuit. Providing Magnetic and Thermal protection to Fan and

Compressor motors.

Pressure gauges that display the operating pressure in the high and low pressure sections of the refrigerant circuit.

It is a treatment fo MCHX coil for medium level of pollution and for marine atmosphere.

The package heat exchanger finned coils in Cu/Cu can be used in places with a concentrations in the air of saline and highly aggressive agents: Not suitable in presence of sulphur-based agents.

Grilles to protect the coils.

Grilles to protect unit avoiding possible intrusion into the unit.

Additional exchanger in order to recover 20% of capacity for

Domestic Hot Water application.

Mechanical water pressure switch to be mounted on the field installation on installation water piping to prevent very low Water

Pressure.

Filter to remove impurities from the water supply.

Accessories are loosed and to install in the field. Options are mounted in factory.

SyScroll 85-135 Air |

9

EN 14511

Starting 2012 Campaign Eurovent Certification Company took decision to start certify only performances declared in according severe European Standard EN14511.

BEFORE 2012: GROSS PERFORMANCES

Before this date all capacity performances are declared, measured and certified by Eurovent, as GROSS performances.

COOLING or HEATING CAPACITY was rated without taking in account the negative contribution of the heat exchanger Pressure Drop or the positive contribution of the Head Available prevalence in example.

OWER INPUT was rated as pure sum of all power input contribution from all motors fitted on the unit. Without taking in account the correction due to power spent to win the exchanger Pressure Drop in example.

AFTER 2012: NET PERFORMANCES

After this date all data are certified according EN14511. Mainly consequences in example on Water chiller or heatpump are:

COOLING or HEATING CAPACITY is now rated taking in account the negative contribution of the heat exchanger Pressure

Drop or the positive contribution of the Head Available prevalence in example. In case of Water to Water unit, in example, both exchanger Pressure Drop values are taken in account in the formula.

POWER INPUT is now rated as all power input contribution from all motors fitted on the unit taking in account also the correction due to power spent to win the exchanger Pressure Drop in example.

As an important consequence of these new rules setted by Eurovent is that EER, COP and ESEER are also affected by these correction. All efficiency index are now calculated, measured and certified according new rules setted by Eurovent according EN14511.

Air to water unit (non ducted outdoor):

Ph

Pc

Pe

Ph

Pc

Pe m

(1) m

(1) m

(1)

Indoor pump is an integral part

ECC 2011 (gross) EN14511

Ph m

– q wi

Δp pi e,wi

Pc m

+ q wi

Δp pi e,wi

Pe m

– q wi

Δp pi e,wi

(1) Measured with the indoor pump not running.

ECC 2011 (gross)

Ph

Pc

Pe

Indoor pump is not an integral part

m m m

EN14511

Ph m

+ q wi

(–Δp

η pi i,wi

)

Pc m

– q wi

(–Δp pi i,wi

)

Pe m

+ q wi

(–Δp

η pi i,wi

)

Where:

Ph = NET heating capacity.

Pc = NET cooling capacity.

Pe = electrical power input.

Ph m

Pc m q

η wi

Δ pi,wi pi

= is the gross heat capacity, expressed in Watts.

= is the gross cool capacity, expressed in Watts.

= is the nominal liquid flow rate.

Δ pe,wi

= is the measured available external static pressure.

= is the measured internal static pressure difference.

= is the efficiency of the pump.

Reference: Guidelines for the declaration of performances according to EN14511 (available a copy upon request for

Systemair customer).

10

|

SyScroll 85-135 Air

Refrigerant Flow Diagram - SyScroll 85-135 Air CO

2

7

G

5

AT

A only size 120-135

A M

1

OIL EQUAL.

BT

B

6

D

5

8

3

4

MECHANICAL EXPANSION VALVE

(STANDARD)

F

FS

E

SUCTION

LINE

BT

UNIT

CONTROL

EXV

CONTROL

3

4

ELECTRONIC EXPANSION VALVE

(OPTIONAL)

COMPONENTS

1

2

3

4

5

6

7

8

Compressor tandem scroll type

Air cooled condenser

Filter drier

Electronic/mechanical expansion valve

Globe valve

Plate heat exchanger

Desuperheater (optional)

Solenoid valve

SAFETY/CONTROL DEVICES

E

F

G

M

A High pressure switch (40.5 bar)

AT High pressure transducer

B Low pressure switch (1.5 bar)

BT Low pressure transducer

FS Water flow switch

D Air temperature sensor

Outlet water temperature sensor

Inlet water temperature sensor

PED pressure relief valve (45 bar)

Discharge temperature sensor

Pipe connection with Shrader valve

SyScroll 85-135 Air |

11

Refrigerant Flow Diagram - SyScroll 85-135 Air HP

2

12

8

AT only size 120-135

A A M

ON

1

OIL EQUAL.

G

5

D

14

H BT

B

5

G

3

14

13

7

10

S

9

4

14

MECHANICAL EXPANSION VALVE

(STANDARD)

N

14

F

11

FS

E

14

5

BT

B

G

9

EXV

CONTROL

N

UNIT

CONTROL

14

7

10

3

4

14

ELECTRONIC EXPANSION VALVE

(OPTIONAL)

14

COMPONENTS

1

2

3

4

5

Compressor tandem scroll type

Air cooled heat exchanger

Filter drier

Electronic/mechanical expansion valve

Globe valve

Liquid receiver 7

8

9

Four-way valve

Suction accumulator

10 Sight glass

11 Plate heat exchanger

12 Desuperheater (optional)

13 Solenoid valve

14 Check valve

SAFETY/CONTROL DEVICES

A High pressure switch (40.5 bar)

AT High pressure transducer

B Low pressure switch (1.5 bar)

BT Low pressure transducer

FS

D

E

F

G

H

M

S

Water flow switch

Air temperature sensor

Outlet water temperature sensor

Inlet water temperature sensor

PED pressure relief valve (45 bar)

Defrost temperature sensor

Discharge temperature sensor

5/16” valve connection (service only)

Pipe connection with Shrader valve

12

|

SyScroll 85-135 Air

Refrigerant Flow Diagram - SyScroll 85-135 Air RE

2

D

G

3

AT

A only size 120-135

A M

1

OIL EQUAL.

BT B

3

3

COMPONENTS

1

2

3

Compressor tandem scroll type

Air cooled condenser

Globe valve

SAFETY/CONTROL DEVICES

D

G

M

A High pressure switch (40.5 bar)

AT High pressure transducer

B Low pressure switch (1.5 bar)

BT Low pressure transducer

Air temperature sensor

PED pressure relief valve (45 bar)

Discharge temperature sensor

Pipe connection with Shrader valve

Refrigerant Flow Diagram - SyScroll 85-135 Air BC

2

D

G

5

AT

A only size 120-135

A M

1

OIL EQUAL.

7

BT

B

6

5

UNIT

CONTROL

EXV

CONTROL

3

4

F

FS

E

SyScroll 85-135 Air |

13

COMPONENTS

1

2

3

4

5

6

7

Compressor tandem scroll type

Air cooled heat exchanger

Filter drier

Electronic/mechanical expansion valve

Globe valve

Plate heat exchanger

Suction accumulator

SAFETY/CONTROL DEVICES

A High pressure switch (40.5 bar)

AT High pressure transducer

B Low pressure switch (1.5 bar)

BT Low pressure transducer

FS

D

E

F

G

M

Water flow switch

Air temperature sensor

Outlet water temperature sensor

Inlet water temperature sensor

PED pressure relief valve (45 bar)

Discharge temperature sensor

Pipe connection with Shrader valve

14

|

SyScroll 85-135 Air

Operating Limits - SyScroll Air CO - Cooling Mode

Operating limits

SyScroll Air CO

Chilled liquid

Liquid outlet temperature

Water

Water with glycol

*

Temperature spread

Maximum operating pressure

Ambient air

Air entering temperature cooling

External static pressure

-

S

HT-HPF

Standard fans

High pressure fans

Recommended system chilled water volume

2

Minimum capacity step

Power supply voltage

3

°C

°C

°C

Pa

°C

°C

K bar

Pa l

%

V

Min

85

510

50

Max Min

95 105

570

43

Max Min Max

+6 to +18

-10 to +6

3 to 7

6

+10 to +45

-14 to +42

-16 to +47

Min

0

<120

630

50

400 V / 3 Ø / 50 Hz (nominal)

120

720

44

Max Min

135

*

For Liquid outlet temperature <0 °C provide Brine Version.

1

Total unit flow rate and pressure drop are given for std unit. Caution: Minimum flow rates may only be used with brine solutions after reprogramming unit parameters.

2

Table shows minimum water / brine volume of system (about 5 lt/kW).

3

Voltage 400V +/- 10%.

810

50

Max

STD version

50

45

40

35

30

25

20

15

10

Brine Version(*)+

Water+Glycol

Water+

Glycol

Water

5

0

-5

-10

Brine Version (*)+

Water+Glycol+FSC

Water+

Glycol+FSC

Water+FSC

-15

-20

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

LWT (°C)

HT version

35

30

25

20

15

10

5

0

55

50

45

40

Brine Version(*)+

Water+Glycol

Water+

Glycol

Water

-5

-10

-15

-20

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

LWT (°C)

SLN version

50

45

40

35

30

25

20

15

10

5

0

Brine Version(*)+

Water+Glycol

Water+

Glycol

Water

-5

-10

-15

-20

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

LWT (°C)

SyScroll 85-135 Air |

15

Operating Limits - SyScroll Air HP - Cooling Mode

Operating limits

SyScroll Air HP

Chilled liquid

Liquid outlet temperature

Water

Water with glycol

*

Temperature spread

Maximum operating pressure

Ambient air

Air entering temperature cooling

External static pressure

-

S

HT-HPF

Standard fans

High pressure fans

Recommended system chilled water volume

2

Minimum capacity step

Power supply voltage

3

°C

°C

°C

Pa

°C

°C

K bar

Pa l

%

V

Min

85

510

50

Max Min

95 105

570

43

Max Min Max

+6 to +18

-10 to +6

3 to 7

6

+5 to +42

-14 to +40

-18 to +44

Min

0

<120

630

50

400 V / 3 Ø / 50 Hz (nominal)

120

720

44

Max Min

135

*

For Liquid outlet temperature <0 °C provide Brine Version.

1

Total unit flow rate and pressure drop are given for std unit. Caution: Minimum flow rates may only be used with brine solutions after reprogramming unit parameters.

2

Table shows minimum water / brine volume of system (about 5 lt/kW).

3

Voltage 400V +/- 10%.

810

50

Max

STD version

50

45

40

35

30

25

20

15

10

Brine Version(*)+

Water+Glycol

Water+

Glycol

Water

5

0

-5

-10

Brine Version (*)+

Water+Glycol+FSC

Water+

Glycol+FSC

Water+FSC

-15

-20

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

LWT (°C)

HT version

35

30

25

20

15

10

5

0

55

50

45

40

Brine Version(*)+

Water+Glycol

Water+

Glycol

Water

-5

-10

-15

-20

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

LWT (°C)

SLN version

50

45

40

35

30

25

20

15

10

5

0

Brine Version(*)+

Water+Glycol

Water+

Glycol

Water

-5

-10

-15

-20

-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18

LWT (°C)

16

|

SyScroll 85-135 Air

Operating Limits - SyScroll Air HP - Heating Mode

Operating limits

SyScroll Air HP

Heat pump liquid

Liquid outlet temperature

Water

Temperature spread

Maximum operating pressure

-

Air entering Full

Load Operation heating

S

HT

Ambient air

External static pressure

Recommended system chilled water volume

2

Minimum capacity step

Power supply voltage

3

Standard fans

High pressure fans

°C

°C

Pa

Pa

°C

K bar

°C

% l

V

Min

85

510

50

Max Min

95 105

570

43

Max Min Max

+20 to +52

3 to 7

6

-10 to +20

-10 to +20

-12 to +20

0

Min

<120

630

50

400 V / 3 Ø / 50 Hz (nominal)

120

720

44

Max Min

135

1

Total unit flow rate and pressure drop are given for std unit. Caution: Minimum flow rates may only be used with brine solutions after reprogramming unit parameters.

2

Table shows minimum water / brine volume of system (about 3 lt/kW).

3

Voltage 400V +/- 10%.

810

50

Max

10

5

0

-5

25

20

15

-10

HT Version

-15

-20

15 20 25 30 35 40 45 50 55 60

LWT (°C)

SyScroll 85-135 Air |

17

Operating Limits - SyScroll Air RE

Operating limits

SyScroll Air RE

Ambient air

Air entering temperature cooling

External static pressure

Minimum capacity step

Power supply voltage

1

1

Voltage 400V +/- 10%.

-

S

HT-HPF

Standard fans

High pressure fans Pa

%

V

°C

°C

°C

Pa

Min

85

Max

50

Min

95

43

105

Max Min Max

+10 to +45

-10 to +43

-12 to +47

Min

0

<120

50

400 V / 3 Ø / 50 Hz (nominal)

120

44

Max Min

135

Max

50

BLN version

50

45

40

35

30

25

20

15

10

5

0

-5

-10

-15

-20

-17 -12 -7

HT-HPF version

50

45

40

35

30

25

20

15

10

5

0

-5

-10

-15

-20

-17 -12 -7

FSC

-2

SST (°C)

3

-2

SST (°C)

3

8 13

8 13

S version

50

45

40

35

30

25

20

15

10

5

0

-5

-10

-15

-20

-17 -12 -7 -2

SST (°C)

3 8 13

18

|

SyScroll 85-135 Air

Correction Factors

Fouling factors

Fouling factor

(m

2

.°C/kW)

0.044

0.088

0.176

0.352

EVAPORATOR

Cooling capacity factor

1.000

0.987

0.964

0.915

Altitude factors

Altitude (m)

0

600

1200

1800

2400

Power input factor

1.000

0.995

0.985

0.962

Cooling capacity factor

1.000

0.987

0.973

0.958

0.943

Fouling factor

(m

2

.°C/kW)

0.044

0.088

0.176

0.352

CONDENSER

Cooling capacity factor

1.000

0.987

0.955

0.910

Power input factor

1.000

1.023

1.068

1.135

Power input factor

1.000

1.010

1.020

1.029

1.038

System Water Volume

The minimum system water volume is calculated using the minimum compressor running time (1.5 minute for scroll compressor) and the lower capacity step (only one compressor running among the four compressors installed):

V= P x t

(n x 25 x ΔT)

Where V : Water volume (litre)

P n

: Unit total cooling capacity (W)

: Number of compressor steps t : Compressor minimum running time (minute)

ΔT : Evaporator temperature difference (°C)

With t = 1.5 minute, ΔT = 5 °C and n = 2, the minimum system water volume is about V = 6 litres/kW .

SyScroll 85-135 Air |

19

Physical Data - SyScroll Air CO _ - (STD-HT-HPF)

Standard, High Temperature and High Pressure Fan versions

Model

Nominal cooling capacity

Input power

EER

1

EER 75%

EER 50%

EER 25%

1

Energy Efficiency Class

1 kW kW

85

84,2

27,2

3,09

B

3,56

4,15

4,22

95

93,2

31,5

2,96

B

3,58

4,74

4,94

105

104,6

37,7

2,77

C

3,39

4,33

4,45

120

118,6

42,0

2,82

C

3,49

4,30

4,39

ESEER

EER

EER

*

ESEER

**

*

ESEER

**

3,66 4,11 3,81 3,90 3,90

Number of refrigerant circuits 1 1 1 1 1

Total capacity steps

Compressor

% 50-100 43-100 50-100 44-100 50-100

Number / Type

N° of loading stages

Evaporator

Number / Type

Water flow

Pressure drop

Water volume

Antifreeze Heater m

3

/h kPa

W l

3,94

3,18

4,03

2,80

0/100

14,5

26

7

4,35

3,04

4,43

2,73

0/100

16,0

32

7

4,00

2,76

3,96

2,58

2 / Scroll

0/100

1 / Plate

18,0

28

8

130

4,01

2,84

4,03

2,72

0/100

20,4

22

11

4,03

2,80

4,00

2,68

0/100

22,7

19

13

135

132,1

47,6

2,78

C

3,38

4,38

4,50

Air cooled condenser

Number of coils

Total coil face area per coil

Fans

Number of fans

Nominal speed

Total airflow

Total input power

Total input power

*

Total input power

**

External static pressure

Water Connections (Evaporator)

Type

Inlet Diameter / Outlet Diameter

Water Connections (Desuperheater)

Type

Inlet Diameter / Outlet Diameter

Weight m rpm m

3

/h kW kW kW

Pa

2 inch inch

690

34.000

2,4

1,6

3,0

2,4

690

34.000

2,4

1,6

3,0

2

2

900

44.000

3,4

3,0

5,2

0 or 120 Pa

**

Male GAS Threaded

2”1/2 / 2”1/2

Male GAS Threaded

1” / 1”

900

44.000

3,4

3,0

5,2

3,1

900

44.000

3,4

3,0

5,2

Shipping

Operating

Additional weight

HT-HPF versions

Desuperheater versions

Dimensions

Length

Width

Height

Acoustical data

Sound power level

2

Sound pressure level at 10 m

3 kg kg kg kg mm mm mm dB(A) dB(A)

708

715

20

12

84

52

779

786

20

12

3.000

84

52

858

867

20

13

1.100

2.250

88

56

908

919

20

13

88

56

3.500

946

959

20

13

88

56

1

Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.

2 Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744.

3

Sound pressure levels refer to ISO Standard 3744, parallelepiped shape.

*

High Temperature Units (HT) with inverter fans.

**

HPF Units with high static pressure fans.

20

|

SyScroll 85-135 Air

Physical Data - SyScroll Air CO_S - (STD)

Standard version

Model

Nominal cooling capacity

Input power

EER

1

Water flow

1

Energy Efficiency Class

EER 75%

EER 50%

EER 25%

Pressure drop

Water volume

Antifreeze Heater

1 kW kW

95

89,3

32,8

2,72

C

3,56

4,72

4,90

105

101,4

38,6

2,63

D

3,36

4,32

4,43

120

113,5

43,0

2,64

D

3,55

4,29

4,45

ESEER 3,91 4,32 3,98 4,03 4,00

Number of refrigerant circuits 1 1 1 1 1

Total capacity steps

Compressor

% 50-100 43-100 50-100 44-100 50-100

Number / Type

N° of loading stages

Evaporator

Number / Type m

3

/h kPa

W l

85

81,1

28,0

2,90

C

3,52

4,13

4,19

0/100

13,9

23

7

0/100

15,4

28

7

2 / Scroll

0/100

1 / Plate

17,4

25

8

130

0/100

19,5

20

11

0/100

21,7

17

13

135

126,0

49,6

2,54

D

3,35

4,37

4,46

Air cooled condenser

Number of coils

Total coil face area per coil

Fans

Number of fans

Nominal speed

Total airflow

Total input power rpm m

3 m

2

/h kW

550

25.000

1,8

2,4

550

25.000

1,8

2

2

690

34.000

2,4

690

36.000

2,4

3,1

690

36.000

2,4

Water Connections (Evaporator)

Type

Inlet Diameter / Outlet Diameter

Water Connections (Desuperheater)

Type

Inlet Diameter / Outlet Diameter

Weight

Shipping

Operating

Additional weight

HT-HPF versions

Desuperheater versions

Dimensions

Length

Width

Height

Acoustical data

Sound power level

2

Sound pressure level at 10 m

3 inch inch kg kg kg kg mm mm mm dB(A) dB(A)

708

715

20

12

82

50

779

786

20

12

3.000

82

50

Male GAS Threaded

2”1/2 / 2”1/2

Male GAS Threaded

1” / 1”

858

867

20

13

1.100

2.250

85

53

908

919

20

13

85

53

3.500

946

959

20

13

85

53

1

Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.

2

Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744.

3

Sound pressure levels refer to ISO Standard 3744, parallelepiped shape.

SyScroll 85-135 Air |

21

Physical Data - SyScroll Air HP _ - (STD-HT-HPF)

Standard, High Temperature and High Pressure Fan versions

Model

Nominal cooling capacity

Input power

EER

1

1

Energy Efficiency Class

EER 75%

EER 50%

EER 25%

1 kW kW

85

79,0

27,6

2,86

C

3,21

4,43

3,81

95

87,0

32,0

2,72

C

3,48

4,60

4,79

105

98,0

39,0

2,51

D

3,18

4,06

4,17

120

113,8

42,0

2,71

C

3,46

4,27

4,36

135

125,0

47,0

2,66

D

3,36

4,35

4,48

ESEER

EER

*

/ EER

**

ESEER

*

/ ESEER

**

3,84

2,93 / 2,59

4,02 / 3,49

85,0

4,22

2,77 / 2,48

4,38 / 3,93

96,0

3,75

2,51 / 2,29

3,89 / 3,62

107,0

3,98

2,74 / 2,45

4,17 / 3,85

120,0

4,00

2,68 / 2,40

4,18 / 3,89

132,6 Nominal heating capacity

Input power

COP

2

2

Energy Efficiency Class

2 kW kW 27,1

3,14

B

3,23 / 2,86

30,8

3,12

B

3,21 / 2,88

38,0

2,82

C

2,85 / 2,70

42,5

2,82

C

2,58 / 2,69

47,2

2,81

C

2,83 / 2,67 COP

*

/ COP

**

Number of refrigerant circuits 1 1 1 1 1

Total capacity steps % 50-100 43-100 50-100 44-100 50-100

Compressor

Number / Type

N° of loading stages

Evaporator

Number / Type

Water flow cooling

1

Water pressure drop cooling

1

Water flow heat pump

2

Water pressure drop heat pump

2 m

3

/h kPa m

3

/h kPa

W l

0/100

13,6

24

14,6

28

7

0/100

15,0

29

16,5

33

7

2 / Scroll

0/100

1 / Plate

16,9

25

18,4

30

8

130

0/100

19,6

21

20,6

22

11

0/100

21,5

17

22,8

18

13 Water volume

Antifreeze Heater

Air cooled condenser

Number of coils

Total coil face area per coil

Fans

Number of fans

Nominal speed

Total airflow

Total input power

Total input power

*

/ Total input power

**

External static pressure

Water Connections (Evaporator)

Type / Inlet Diameter / Outlet Diameter

Water Connections (Desuperheater) m rpm m

3

/h kW kW

Pa

2 inch

690

34.700

2,4

1,6 / 3,0

2,4

690

34.700

2,4

1,6 / 3,0

2

2

900

42.000

3,4

3,0 / 5,2

0 or 120 Pa

**

900

43.200

Male GAS Threaded / 2”1/2 / 2”1/2

3,4

3,0 / 5,2

3,1

900

43.200

3,4

3,0 / 5,2

Type / Inlet Diameter / Outlet Diameter

Weight

Shipping

Operating

Additional weight

HT-HPF versions

Desuperheater versions

Dimensions

Length

Width

Height

Acoustical data

Sound power level

2

Sound pressure level at 10 m

3 inch kg kg kg kg mm mm mm dB(A) dB(A)

839

860

20

12

84

52

906

932

20

12

84

52

Male GAS Threaded / 2”1/2 / 2”1/2

3.000

1.043

1.064

20

13

1.100

2.250

88

56

1.159

1.170

20

13

88

56

3.500

1.208

1.214

20

13

88

56

1

Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.

2

Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744.

3

Sound pressure levels refer to ISO Standard 3744, parallelepiped shape.

* High Temperature Units (HT) with inverter fans.

**

HPF Units with high static pressure fans.

22

|

SyScroll 85-135 Air

Physical Data - SyScroll Air HP_S (STD)

Standard version

Model

Nominal cooling capacity

Input power

EER

1

1

Energy Efficiency Class

EER 75%

EER 50%

EER 25%

1 m

3 kW kW

85

76,0

28,3

2,68

D

3,37

3,94

4,01

95

83,3

33,3

2,50

E

3,39

4,47

4,66

105

95,0

40,0

2,37

E

3,13

3,98

4,11

2

690

34.700

2,4

120

111,4

42,6

2,62

D

3,26

4,01

4,09

ESEER

Nominal heating capacity

Input power

COP

2

2

2

Energy Efficiency Class B B C C C

Number of refrigerant circuits 1 1 1 1 1

Total capacity steps

Compressor

% 50-100 43-100 50-100 44-100 50-100

Number / Type

N° of loading stages

Evaporator

Number / Type

Water flow cooling

Water volume

Antifreeze Heater

1

Water pressure drop cooling

Water flow heat pump

Air cooled condenser

Number of coils

2

1

Water pressure drop heat pump

2 m m kW kW

3

3

/h kPa

/h kPa

W l

3,73

82,6

26,4

3,13

0/100

13,1

22

14,2

26

7

4,10

93,1

30,1

3,09

0/100

14,3

26

16,0

32

7

3,68

105,1

37,0

2,84

2 / Scroll

0/100

1 / Plate

16,3

24

18,1

29

8

130

2

3,74

117,8

41,5

2,84

0/100

19,2

20

20,3

21

11

3,88

129,4

46,2

2,80

0/100

20,9

17

22,3

17

13

Total coil face area per coil

Fans

Number of fans

Nominal speed

Total airflow

Total input power

Water Connections (Evaporator)

Type m

2 rpm

/h kW inch

550

26.200

1,8

2,4

550

26.200

1,8

Male GAS Threaded

2”1/2 / 2”1/2

690

35.800

2,4

3,1

135

121,8

48,0

2,54

D

3,26

4,22

4,34

690

35.800

2,4

Inlet Diameter / Outlet Diameter

Water Connections (Desuperheater)

Type

Inlet Diameter / Outlet Diameter

Weight

Shipping

Operating

Additional weight inch kg kg

853

860

926

932

Male GAS Threaded

1” / 1”

1.056

1.064

1.160

1.170

1.201

1.214

HT-HPF versions

Desuperheater versions

Dimensions

Length

Width

Height

Acoustical data

Sound power level

3

Sound pressure level at 10 m

4 kg kg mm mm mm dB(A) dB(A)

20

12

82

50

20

12

3.000

82

50

20

13

1.100

2.250

85

53

20

13

85

53

3.500

20

13

85

53

1

Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.

2

Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.

3

Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744.

4

Sound pressure levels refer to ISO Standard 3744, parallelepiped shape.

SyScroll 85-135 Air |

23

Physical Data - SyScroll Air RE

Remote Evaporator

Model

SyScroll Air RE_ - (STD)

Nominal cooling capacity

1

Input power

2

Refrigerant In connections

Refrigerant Out connections

SyScroll Air RE_ - (S)

Nominal cooling capacity

1

Input power

2

Refrigerant In connections

Refrigerant Out connections

Weight

Shipping

Additional weight

HT/HPF versions

Dimensions

Length

Width

Height kW kW inch inch kW kW inch inch kg kg mm mm mm

85

94,3

24,8

1 5/8”

7/8”

90,2

26,3

1 5/8”

7/8”

625

20

95

105,0

29,2

1 5/8”

7/8”

99,8

31,3

1 5/8”

7/8”

697

20

3.000

105

116,4

34,6

2 1/8”

1 1/8”

112,4

36,7

2 1/8”

1 1/8”

765

20

1.100

2.250

120

130,5

39,8

2 1/8”

1 1/8”

125,2

42,5

2 1/8”

1 1/8”

817

20

3.500

135

142,4

45,1

2 1/8”

1 1/8”

135,7

48,4

2 1/8”

1 1/8”

840

20

1

Data refers to 7°C evaporating temperature and 35°C condenser air temperature.

2 Input power (only compressors).

N.B. For additional technical data regarding compressors, fan motors and noise, please refer to correspondant CO unit.

24

|

SyScroll 85-135 Air

Electrical Data

Compressors @ 400 V/3 Ph/50 Hz

Model

85

95

105

120

135

Power input nominal Cond.

compressor kW

12,3

12,3

12,3

15,9

17,4

17,4

17,4

21,1

21,1

21,1

Nom. Cond.

current compressor

A

23,3

23,3

23,3

27,8

28,2

28,2

28,2

33,6

33,6

33,6

Power input max. Cond.

compressor kW

17,0

17,0

17,0

22,6

26,0

26,0

26,0

32,0

32,0

32,0

Max. running current compressor FLA

Starting current compressor LRA

40

44

44

44

A

34

34

34

53

53

53

225

210

210

210

A

174

174

174

210

210

210

Nominal power factor Unit fuse size Cable section kW

0,76

0,76

0,76

0,82

0,89

0,89

0,89

0,91

0,91

0,91

A

100

100

125

125

160 mm

50

50

70

70

70

2

Fans @ 400 V/3 Ph/50 Hz

Units _

Size

85

95

105

120

135

Number

2

2

2

2

2

Units S

Units HT/HPF

Size

85

95

105

120

135

Size

85

95

105

120

135

Number

2

2

2

2

2

Number

2

2

2

2

2

Nominal power per fan (kW) Δ

1,2

1,2

2,1

2,1

2,1

Max. running current per fan (A) Δ

2,2

2,2

4,1

4,1

4,1

Total fan power

(kW) Δ

2,3

2,3

4,2

4,2

4,2

Total max. fan current

(A) Δ

4,4

4,4

8,2

8,2

8,2

Nominal power per fan (kW) Δ

1,2

1,2

1,2

1,2

1,2

Max. running current per fan (A) Δ

2,2

2,2

2,2

2,2

2,2

Total fan power

(kW) Δ

2,3

2,3

2,3

2,3

2,3

Total max. fan current

(A) Δ

4,4

4,4

4,4

4,4

4,4

Nominal power per fan (kW) Δ

3,1

3,1

3,1

3,1

3,1

Max. running current per fan (A) Δ

4,8

4,8

4,8

4,8

4,8

Total fan power

(kW) Δ

6,2

6,2

6,2

6,2

6,2

Total max. fan current

(A) Δ

9,6

9,6

9,6

9,6

9,6

SyScroll 85-135 Air |

25

Units @ 400 V/3 Ph/50 Hz

- Version

Current input (A)

Power input (kW)

Nominal

Maximum

Nominal

Maximum

Max Start-up current

S Version

Current input (A)

Power input (kW)

Max Start-up current

Nominal

Maximum

Nominal

Maximum

HT/HPF Version

Current input (A)

Power input (kW)

Max Start-up current

Nominal

Maximum

Nominal

Maximum

Pump data

Model

85

95

105

120

135 kW kW

A

A

A

A

A kW kW

A kW kW

A

A

A

85

27

36

51

72

212

85

27

36

51

72

212

85

31

40

56

78

218

Nominal power kW

1,99

1,99

1,99

2,45

2,45

Low Pressure

Max. running current

A

3,41

3,41

3,41

4,53

4,53

95

30

42

55

78

263

95

30

42

55

78

263

95

34

46

61

84

269

105

39

56

65

96

262

105

37

54

61

92

258

105

41

58

66

98

264

120

43

62

70

105

262

120

41

60

66

101

258

120

45

64

71

107

264

Nominal power kW

3,26

3,26

3,26

3,00

3,00

High Pressure

Max. running current

A

5,86

5,86

5,86

6,14

6,14

135

46

68

75

114

271

135

45

66

72

110

267

135

48

70

77

116

273

26

|

SyScroll 85-135 Air

Electrical Data

Units with std pressure pump @ 400 V/3 Ph/50 Hz

- Version

Current input (A)

Power input (kW)

Max Start-up current

Nominal

Maximum

Nominal

Maximum

A

A kW kW

A

85

29

38

54

76

216

S Version

Current input (A)

Power input (kW)

Max Start-up current

Nominal

Maximum

Nominal

Maximum

HT/HPF Version

Current input (A)

Power input (kW)

Max Start-up current

Nominal

Maximum

Nominal

Maximum

A

A kW kW

A

A

A kW kW

A

85

33

42

60

81

221

85

29

38

54

76

216

Units with high pressure pump @ 400 V/3 Ph/50 Hz

- Version

Current input (A)

Power input (kW)

Max Start-up current

Nominal

Maximum

Nominal

Maximum kW kW

A

A

A

85

30

39

57

78

218

S Version

Current input (A)

Power input (kW)

Max Start-up current

Nominal

Maximum

Nominal

Maximum kW kW

A

A

A

85

30

39

57

78

218

HT/HPF Version

Current input (A)

Power input (kW)

Max Start-up current

Nominal

Maximum

Nominal

Maximum

A

A kW kW

A

85

34

43

62

83

223

95

36

48

64

87

272

95

32

44

59

82

267

95

32

44

59

82

267

120

47

67

76

111

268

120

43

63

71

106

263

120

45

65

75

110

267

105

43

60

69

101

267

105

39

56

64

96

262

105

41

58

68

100

266

135

51

73

81

120

277

135

47

69

76

115

272

135

49

71

80

119

276

95

34

45

61

84

269

95

34

45

61

84

269

95

38

49

67

89

274

120

46

65

76

111

268

120

44

63

72

108

265

120

48

67

78

113

270

105

42

59

70

102

268

105

40

58

67

98

264

105

44

61

72

103

269

135

49

71

82

120

277

135

48

69

78

117

274

135

51

73

83

122

279

SyScroll 85-135 Air |

27

Fan Data - HPF Version

SyScroll 85-135 Air HPF

Model

85-105

120-135

Fan Static Pressure (Pa)

120

40

60

80

100

40

60

80

100

120

Sound data - SyScroll Air

Model

- Version

85

95

105

120

135

S Version

85

95

105

120

135

HT-HPF Version

**

85

95

105

120

135

94

94

94

94

94

81

81

84

84

84

125

83

83

87

87

87

95

95

95

95

95

82

82

85

85

85

250

84

84

88

88

88

Fan RPM

870

910

950

990

1.030

1.000

1.030

1.070

1.100

1.130

Parameter in Service Level:

Max Speed (Vdc)

9,3

9,1

9,3

9,6

9,8

8,1

8,4

8,7

9,0

10,0

93

93

93

93

93

80

80

83

83

83

500

82

82

86

86

86

77

77

80

80

80

79

79

83

83

83

Frequency (Hz)

1000 2000

74

74

78

78

78

90

90

90

90

90

85

85

85

85

85

72

72

75

75

75

73

73

73

73

73

60

60

63

63

63

8000

62

62

66

66

66

79

79

79

79

79

66

66

69

69

69

4000

68

68

72

72

72

Sound

Power dB(A)

82

82

85

85

85

84

84

88

88

88

95

95

95

95

95

Sound

Pressure dB(A)

*

50

50

53

53

53

52

52

56

56

56

63

63

63

63

63

*

Sound pressure level at 10 m. Values refers to ISO Standard 3744 with parallepiped shape.

**

Sound data valid in max air flow rate condition.

28

|

SyScroll 85-135 Air

Cooling Capacities - SyScroll Air CO _ - (STD-HT-HPF)

Model

85

95

105

120

135

LWT

°C

Cool

98,6

104,9

111,4

118,2

125,3

132,6

144,0

110,9 kW

88,5

94,1

100,0

106,0

112,4

118,9

129,2

117,8

124,9

132,2

139,7

147,5

159,3

124,6

132,5

140,6

148,9

157,6

166,6

180,4

140,9

149,8

159,0

168,5

178,5

188,7

204,7

5

7

15

18

11

13

7

9

13

15

18

5

9

11

5

7

18

5

7

9

11

13

15

7

9

18

5

9

11

13

15

11

13

15

18

25

Input

Power

*

22,9

23,4

23,8

24,3

24,8

25,3

26,1

26,6 kW

19,9

20,2

20,6

20,9

21,2

21,5

22,0

26,9

27,2

27,6

27,9

28,2

28,7

30,8

31,2

31,6

32,1

32,6

33,1

34,0

34,4

35,0

35,6

36,2

37,0

37,7

38,9

Cool

93,5

99,5

105,7

112,2

118,9

125,8

136,6

105,3 kW

84,2

89,6

95,1

100,9

106,9

113,2

122,9

111,7

118,3

125,2

132,2

139,4

150,4

117,9

125,3

132,9

140,8

148,9

157,3

170,3

132,9

141,3

150,0

159,0

168,4

178,0

193,1

30

Condensing Air Temperature °C

32

Input

Power

*

Cool

25,2

25,6

26,1

26,7

27,2

27,8

28,7

29,9 kW

21,9

22,3

22,7

23,1

23,5

23,9

24,5

30,2

30,6

30,9

31,2

31,6

32,1

34,5

35,0

35,5

36,0

36,5

37,1

37,9

38,6

39,2

39,8

40,5

41,3

42,1

43,3

91,4

97,3

103,4

109,7

116,2

123,0

133,6

102,9 kW

82,4

87,7

93,1

98,8

104,6

110,7

120,2

109,2

115,7

122,3

129,1

136,1

146,7

115,1

122,3

129,7

137,4

145,3

153,5

166,1

129,6

137,8

146,3

155,1

164,2

173,6

188,3

Input

Power

*

26,1

26,6

27,1

27,7

28,2

28,8

29,7

31,3 kW

22,8

23,2

23,6

24,0

24,4

24,8

25,5

31,7

32,0

32,4

32,7

33,1

33,6

36,2

36,7

37,1

37,7

38,2

38,8

39,7

40,4

41,0

41,7

42,4

43,2

44,0

45,3

35

Input

Power

*

27,7

28,2

28,7

29,3

29,9

30,5

31,4

33,6 kW

24,1

24,5

24,9

25,4

25,8

26,3

27,0

33,9

34,3

34,7

35,1

35,4

36,0

38,8

39,3

39,8

40,3

40,9

41,5

42,4

43,3

44,0

44,7

45,4

46,2

47,0

48,3

Cool

88,1

93,8

99,7

105,8

112,2

118,7

128,9

99,2 kW

79,6

84,7

89,9

95,4

101,1

107,0

116,1

105,3

111,5

117,9

124,4

131,0

141,3

110,8

117,7

124,8

132,2

139,8

147,6

159,7

124,5

132,3

140,5

149,0

157,7

166,8

180,9

*

Only Compressors.

SyScroll 85-135 Air |

29

Model

LWT

°C

85

95

105

120

135

5

7

15

18

11

13

7

9

13

15

18

5

9

11

5

7

18

5

7

9

11

13

15

7

9

18

5

9

11

13

15

11

13

15

18

38

Input

Power

*

29,4

29,9

30,4

31,0

31,6

32,2

33,2

36,0 kW

25,5

25,9

26,3

26,8

27,3

27,7

28,5

36,4

36,8

37,2

37,6

38,0

38,6

41,6

42,2

42,7

43,2

43,8

44,4

45,4

46,5

47,2

47,8

48,6

49,4

50,2

51,5

Cool

84,8

90,3

96,0

101,9

108,0

114,3

124,1

95,3 kW

76,7

81,5

86,6

91,9

97,4

103,0

111,9

101,1

107,1

113,3

119,5

125,9

135,7

106,2

112,8

119,7

126,8

134,1

141,6

153,2

119,2

126,7

134,5

142,6

151,0

159,7

173,2

Cool

82,5

87,8

93,4

99,1

105,1

111,3

120,8

92,5 kW

74,6

79,4

84,3

89,5

94,8

100,3

108,9

98,2

104,1

110,1

116,2

122,4

131,9

103,0

109,5

116,1

123,1

130,2

137,5

148,8

115,4

122,8

130,4

138,2

146,4

154,8

168,0

40

Condensing Air Temperature °C

42

Input

Power

*

Cool

30,6

31,1

31,7

32,2

32,8

33,5

34,5

37,7 kW

26,5

26,9

27,3

27,8

28,3

28,8

29,5

38,2

38,6

39,0

39,4

39,8

40,4

43,7

44,2

44,7

45,3

45,9

46,5

47,4

48,8

49,4

50,1

50,8

51,6

52,5

53,8

80,2

85,4

90,8

96,3

102,2

108,2

117,5

89,6 kW

72,5

77,1

82,0

87,0

92,2

97,6

105,9

95,2

101,0

106,8

112,7

118,8

128,0

99,7

106,0

112,5

119,2

126,1

133,2

144,2

111,6

118,7

126,1

133,7

141,6

149,8

Input

Power

*

31,9

32,4

32,9

33,5

34,1

34,8

35,8

39,5 kW

27,5

27,9

28,4

28,8

29,3

29,8

30,6

40,0

40,4

40,9

41,3

41,7

42,3

45,8

46,3

46,9

47,4

48,0

48,6

49,6

51,1

51,8

52,5

53,2

54,0

54,9

45

Input

Power

*

33,9

34,4

35,0

35,6

36,2

36,9

37,9

42,4 kW

29,2

29,6

30,0

30,5

31,0

31,5

32,2

42,9

43,4

43,8

44,3

44,8

45,4

49,1

49,7

50,3

50,8

51,5

52,1

53,1

54,9

55,6

56,3

57,0

57,8

58,6

Cool

76,5

81,5

86,7

92,1

97,6

103,4

112,3

85,0 kW

69,2

73,6

78,3

83,1

88,1

93,2

101,3

90,5

96,0

101,6

107,4

113,2

122,0

94,4

100,5

106,8

113,2

119,9

126,7

137,1

105,6

112,4

119,4

126,7

134,3

142,1

*

Only Compressors.

HT Version

30

|

SyScroll 85-135 Air

Cooling Capacities - SyScroll Air CO S - (STD)

Model

85

95

105

120

135

LWT

°C

Cool

95,2

101,1

107,2

113,5

120,0

126,7

137,1

108,3 kW

86,0

91,3

96,8

102,5

108,4

114,5

124,0

114,9

121,6

128,5

135,5

142,7

153,7

121,7

129,2

136,9

144,8

153,0

161,4

174,3

134,9

143,2

151,7

160,5

169,6

179,0

193,4

5

7

15

18

11

13

7

9

13

15

18

5

9

11

5

7

18

5

7

9

11

13

15

7

9

18

5

9

11

13

15

11

13

15

18

25

Input

Power

*

24,4

24,9

25,5

26,1

26,8

27,4

28,5

28,1 kW

21,1

21,5

22,0

22,4

22,9

23,3

24,1

28,5

28,9

29,3

29,7

30,1

30,8

32,4

32,9

33,5

34,0

34,7

35,3

36,3

36,7

37,5

38,2

39,1

39,9

40,9

42,4

Cool

90,0

95,6

101,4

107,4

113,5

119,9

129,7

102,6 kW

81,6

86,6

91,9

97,2

102,8

108,6

117,5

108,7

115,0

121,4

128,0

134,6

144,8

114,9

121,9

129,1

136,5

144,2

152,0

164,1

126,9

134,7

142,7

150,9

159,5

168,2

181,8

30

Condensing Air Temperature °C

32

Input

Power

*

Cool

26,8

27,4

28,0

28,6

29,3

30,0

31,2

31,5 kW

23,2

23,6

24,1

24,6

25,1

25,7

26,5

31,9

32,4

32,8

33,3

33,7

34,4

36,3

36,9

37,5

38,1

38,8

39,4

40,5

41,2

41,9

42,8

43,6

44,5

45,5

47,1

87,9

93,4

99,0

104,8

110,9

117,0

126,6

100,1 kW

79,7

84,7

89,7

95,0

100,5

106,1

114,8

106,1

112,2

118,5

124,9

131,3

141,2

112,0

118,8

125,9

133,1

140,5

148,2

159,9

123,6

131,1

138,9

146,9

155,2

163,8

177,0

Input

Power

*

27,8

28,4

29,0

29,7

30,4

31,1

32,3

33,0 kW

24,0

24,5

25,0

25,5

26,1

26,6

27,4

33,4

33,9

34,4

34,8

35,3

36,0

38,0

38,6

39,2

39,9

40,5

41,2

42,3

43,1

43,9

44,7

45,6

46,5

47,5

49,1

35

Input

Power

*

29,5

30,1

30,8

31,4

32,1

32,9

34,1

35,4 kW

25,4

25,9

26,4

26,9

27,5

28,1

28,9

35,8

36,3

36,8

37,3

37,8

38,5

40,8

41,4

42,0

42,7

43,4

44,1

45,2

46,2

47,0

47,9

48,8

49,7

50,7

52,4

Cool

84,6

89,9

95,3

100,9

106,7

112,7

121,8

96,3 kW

76,8

81,6

86,5

91,6

96,8

102,2

110,6

102,1

107,9

114,0

120,1

126,3

135,7

107,6

114,1

120,9

127,8

134,9

142,3

153,5

118,4

125,6

133,0

140,7

148,7

156,9

169,5

*

Only Compressors.

SyScroll 85-135 Air |

31

Model

LWT

°C

85

95

105

120

135

5

7

15

18

11

13

7

9

13

15

18

5

9

11

5

7

18

5

7

9

11

13

15

7

9

18

5

9

11

13

15

11

13

15

18

38

Input

Power

*

31,3

31,9

32,6

33,3

34,0

34,8

36,0

37,9 kW

26,9

27,4

27,9

28,4

29,0

29,6

30,5

38,4

38,9

39,5

40,0

40,5

41,3

43,7

44,4

45,0

45,7

46,4

47,1

48,3

49,6

50,4

51,2

52,1

53,1

54,1

Cool

81,2

86,2

91,5

96,9

102,4

108,1

117,0

92,2 kW

73,8

78,4

83,1

88,0

93,0

98,2

106,2

97,8

103,5

109,2

115,1

121,1

130,1

102,8

109,1

115,6

122,3

129,1

136,2

146,9

112,9

119,8

126,9

134,3

141,9

149,7

Condensing Air Temperature °C

40

Cool

Input

Power

*

78,8

83,7

88,8

94,1

99,5

105,0

113,6

89,3 kW

71,7

76,1

80,7

85,5

90,4

95,4

103,2

94,8

100,3

106,0

111,7

117,5

126,2

99,5

105,7

112,0

118,5

125,1

131,9

142,4

109,1

115,8

122,7

129,9

137,2

144,8

32,6

33,2

33,9

34,6

35,3

36,1

37,3

39,7 kW

27,9

28,4

28,9

29,5

30,0

30,6

31,6

40,2

40,8

41,3

41,9

42,4

43,2

45,8

46,5

47,1

47,8

48,6

49,3

50,5

52,0

52,8

53,6

54,5

55,5

56,5

76,4

86,3

96,1

105,2

Cool kW

69,5

42

Input

Power

* kW

29,0

34,0

41,6

48,0

54,5

*

Only Compressors.

32

|

SyScroll 85-135 Air

Cooling Capacities - SyScroll Air HP _ - (STD-HT-HPF)

Model

85

95

105

120

135

LWT

°C

Cool

92,4

98,2

104,2

110,4

116,9

123,5

133,8

104,1 kW

83,3

88,5

93,9

99,5

105,3

111,3

120,7

110,4

116,9

123,5

130,3

137,3

147,9

121,5

129,1

136,9

145,0

153,4

162,0

175,3

133,4

141,7

150,3

159,2

168,5

178,0

192,7

5

7

15

18

11

13

7

9

13

15

18

5

9

11

5

7

18

5

7

9

11

13

15

7

9

18

5

9

11

13

15

11

13

15

18

25

Input

Power

*

23,7

24,2

24,7

25,3

25,8

26,4

27,4

27,7 kW

20,3

20,7

21,1

21,5

21,9

22,3

22,9

28,1

28,5

28,9

29,3

29,7

30,3

30,1

30,6

31,1

31,6

32,1

32,6

33,5

33,8

34,4

35,1

35,8

36,5

37,3

38,6

Cool

87,5

93,0

98,7

104,6

110,7

116,9

126,7

98,6 kW

79,1

84,1

89,2

94,5

100,0

105,7

114,5

104,5

110,5

116,7

123,1

129,5

139,4

115,0

122,1

129,4

137,0

144,9

152,9

165,4

125,8

133,6

141,7

150,1

158,8

167,7

181,6

30

Condensing Air Temperature °C

32

Input

Power

*

Cool

26,0

26,5

27,1

27,7

28,3

29,0

30,0

31,1 kW

22,3

22,7

23,2

23,6

24,1

24,6

25,3

31,5

31,9

32,4

32,8

33,2

33,9

33,8

34,3

34,8

35,3

35,9

36,5

37,4

37,9

38,5

39,2

40,0

40,8

41,6

43,0

85,4

90,8

96,4

102,1

108,1

114,2

123,8

96,2 kW

77,4

82,2

87,2

92,4

97,7

103,3

111,9

102,0

107,9

113,9

120,1

126,4

136,0

112,2

119,2

126,3

133,7

141,4

149,2

161,3

122,7

130,3

138,2

146,3

154,8

163,5

177,0

Input

Power

*

27,0

27,6

28,1

28,7

29,4

30,0

31,1

32,6 kW

23,2

23,6

24,1

24,5

25,0

25,5

26,3

33,0

33,4

33,9

34,3

34,8

35,5

35,4

35,9

36,4

37,0

37,6

38,2

39,1

39,7

40,3

41,0

41,8

42,6

43,5

44,8

35

Input

Power

*

28,6

29,2

29,8

30,4

31,1

31,8

32,8

34,9 kW

24,5

24,9

25,4

25,9

26,4

26,9

27,7

35,4

35,8

36,3

36,8

37,3

38,0

38,0

38,5

39,1

39,6

40,2

40,8

41,8

42,5

43,2

43,9

44,7

45,5

46,4

47,8

Cool

82,3

87,5

92,8

98,4

104,1

110,1

119,2

92,6 kW

74,6

79,2

84,1

89,1

94,3

99,6

107,9

98,1

103,8

109,6

115,5

121,5

130,7

107,9

114,6

121,5

128,6

135,9

143,5

155,1

117,7

125,0

132,6

140,4

148,5

156,9

169,9

*

Only Compressors.

SyScroll 85-135 Air |

33

Model

LWT

°C

85

95

105

120

135

5

7

15

18

11

13

7

9

13

15

18

5

9

11

5

7

18

5

7

9

11

13

15

7

9

18

5

9

11

13

15

11

13

15

18

38

Input

Power

*

30,4

31,0

31,6

32,2

32,9

33,6

34,7

37,4 kW

25,9

26,4

26,9

27,4

27,9

28,4

29,2

37,9

38,4

38,9

39,4

39,9

40,7

40,8

41,3

41,9

42,4

43,1

43,7

44,7

45,6

46,3

47,1

47,8

48,7

49,6

51,0

Cool

79,0

84,0

89,2

94,5

100,1

105,8

114,6

88,7 kW

71,7

76,2

80,8

85,6

90,6

95,8

103,8

94,0

99,5

105,1

110,8

116,5

125,3

103,4

109,9

116,5

123,3

130,3

137,6

148,7

112,6

119,6

126,8

134,3

142,1

150,1

162,5

Condensing Air Temperature °C

40

Cool

Input

Power

*

76,8

81,6

86,7

91,9

97,3

102,8

111,4

85,9 kW

69,7

74,1

78,6

83,3

88,1

93,1

100,9

91,2

96,5

101,9

107,5

113,1

121,6

100,3

106,6

113,0

119,7

126,5

133,5

144,3

109,0

115,8

122,8

130,1

137,6

145,4

157,5

31,6

32,2

32,8

33,5

34,2

34,9

36,0

39,2 kW

26,9

27,4

27,9

28,4

28,9

29,4

30,3

39,7

40,3

40,8

41,3

41,8

42,6

42,7

43,3

43,9

44,5

45,1

45,7

46,7

47,8

48,5

49,3

50,1

50,9

51,8

53,2

74,5

79,2

84,1

83,0

88,2

93,4

97,0

103,1

109,4

105,3

111,8

118,7

Cool kW

67,6

71,9

76,3

42

Input

Power

* kW

28,0

28,4

28,9

33,0

33,5

34,2

41,1

41,6

42,2

44,8

45,4

45,9

50,2

50,9

51,6

*

Only Compressors.

HT Version

34

|

SyScroll 85-135 Air

Heating Capacities - SyScroll Air HP _ - (STD-HT-HPF)

Model

85

95

105

120

135

LWT

°C

40

45

50

30

45

50

30

35

50

30

35

40

30

35

40

45

30

35

40

45

35

40

45

50

50

Heat kW

61,5

61,2

61,0

69,1

68,9

68,9

77,4

77,7

77,6

86,0

86,4

86,8

94,8

95,3

96,2

-7

Input

Power

* kW

17,2

19,0

21,1

19,8

21,9

24,4

24,2

27,1

30,4

27,1

30,5

34,3

30,2

34,1

38,6

Heat kW

64,8

64,4

64,1

63,8

81,2

81,5

81,5

81,1

90,2

90,7

91,0

91,2

72,8

72,5

72,3

99,2

99,8

100,6

-5

Ambient Air Temperature °C

-3

Input

Power

* kW

17,3

19,1

21,2

23,7

Heat kW

68,3

67,8

67,2

66,9

Input

Power

* kW

17,5

19,3

21,3

23,8

20,0

22,0

24,4

24,2

27,2

30,4

34,1

27,1

30,5

34,3

38,7

30,2

34,1

38,6

76,7

76,3

76,0

75,8

85,2

85,5

85,6

85,1

94,8

95,1

95,4

95,6

104,6

104,7

105,3

106,2

20,1

22,1

24,5

27,3

24,2

27,2

30,5

34,1

27,1

30,5

34,4

38,7

30,2

34,1

38,6

43,7

0

Input

Power

*

24,7

27,4

30,6

24,2

27,2

30,5

34,2

38,3 kW

17,7

19,5

21,5

23,9

26,6

20,3

22,3

27,1

30,5

34,4

38,7

43,6

30,3

34,1

38,5

43,6

Heat

81,8

81,4

81,3

91,4

91,7

91,8

91,5

90,8 kW

73,8

73,2

72,5

72,0

71,5

82,8

82,2

101,9

102,0

102,2

102,3

102,1

111,9

112,1

112,5

113,1

*

Only Compressors.

SyScroll 85-135 Air |

35

Model

LWT

°C

85

95

105

120

135

40

45

50

30

45

50

30

35

50

30

35

40

30

35

40

45

30

35

40

45

35

40

45

50

50

5

Input

Power

*

25,0

27,7

30,8

24,2

27,2

30,6

34,3

38,5 kW

18,0

19,8

21,8

24,1

26,7

20,6

22,6

27,2

30,6

34,4

38,7

43,6

30,4

34,2

38,5

43,5

49,2

Heat

91,9

91,3

90,8

102,5

102,6

102,5

102,2

101,6 kW

83,3

82,5

81,7

80,8

79,8

93,5

92,7

114,4

114,2

114,0

113,8

113,5

126,4

125,5

125,4

125,5

125,7

Heat

96,7

95,8

95,0

108,1

108,0

107,5

107,0

106,3 kW

87,8

86,9

85,9

84,8

83,7

99,0

98,0

120,8

120,5

120,0

119,2

118,6

132,7

132,2

132,0

131,8

131,2

7

Ambient Air Temperature °C

10

Input

Power

*

25,1

27,8

30,9

24,2

27,2

30,6

34,3

38,5 kW

18,1

20,0

22,0

24,3

26,8

20,7

22,8

27,2

30,6

34,4

38,7

43,6

30,4

34,2

38,6

43,5

49,1

Heat

103,7

102,6

101,6

115,6

115,1

114,7

114,1

113,4 kW

94,3

93,4

92,2

91,0

89,6

106,1

104,9

129,6

128,5

127,9

127,2

126,4

142,7

141,8

140,8

140,1

139,5

Input

Power

*

25,3

28,0

31,1

24,2

27,2

30,6

34,3

38,5 kW

18,3

20,2

22,2

24,5

27,0

20,9

23,0

27,2

30,6

34,4

38,7

43,6

30,5

34,3

38,6

43,5

49,1

15

Input

Power

*

25,7

28,4

31,4

24,1

27,1

30,5

34,3

38,5 kW

18,5

20,5

22,6

24,9

27,4

21,2

23,3

27,2

30,6

34,4

38,7

43,5

30,5

34,3

38,6

43,5

49,0

Heat

117,2

115,6

114,1

131,1

129,4

128,2

127,2

126,2 kW

106,8

105,6

104,1

102,5

100,8

121,0

118,8

147,0

145,4

143,4

142,3

141,0

161,7

160,2

158,8

156,9

155,5

*

Only Compressors.

36

|

SyScroll 85-135 Air

Cool

89,2

94,6

100,2

106,0

111,9

118,0

127,4

101,9 kW

80,9

85,8

90,9

96,1

101,5

107,1

115,7

107,9

114,0

120,2

126,6

133,0

142,8

119,8

127,1

134,6

142,3

150,3

158,4

171,0

131,0

139,0

147,2

155,6

164,4

173,3

187,1

Cooling Capacities - SyScroll Air HP S - (STD)

Model

85

95

105

120

135

LWT

°C

15

18

5

7

11

13

7

9

13

15

18

5

9

11

5

7

18

5

7

9

11

13

15

7

9

18

5

9

11

13

15

11

13

15

18

25

Input

Power

*

25,2

25,8

26,4

27,1

27,8

28,5

29,7

29,3 kW

21,5

21,9

22,4

22,9

23,5

24,0

24,8

29,8

30,3

30,8

31,3

31,8

32,6

31,3

31,9

32,5

33,1

33,7

34,3

35,4

35,3

36,0

36,8

37,6

38,5

39,5

41,0

Condensing Air Temperature °C

30

Cool

Input

Power

*

84,2

89,3

94,6

100,0

105,6

111,3

120,2

96,2 kW

76,6

81,2

86,0

90,9

96,0

101,3

109,4

101,8

107,5

113,3

119,2

125,2

134,2

113,1

119,9

126,9

134,2

141,6

149,2

161,0

123,2

130,6

138,3

146,3

154,4

162,8

175,8

27,6

28,3

29,0

29,7

30,4

31,2

32,5

32,8 kW

23,5

24,0

24,6

25,1

25,7

26,3

27,2

33,4

33,9

34,5

35,0

35,6

36,5

35,2

35,7

36,3

37,0

37,7

38,3

39,4

39,5

40,3

41,1

42,0

43,0

43,9

45,5

32

Input

Power

*

28,7

29,4

30,1

30,8

31,6

32,4

33,6

34,4 kW

24,4

24,9

25,5

26,0

26,6

27,2

28,1

34,9

35,5

36,1

36,7

37,3

38,1

36,8

37,4

38,0

38,7

39,4

40,1

41,2

41,4

42,2

43,0

43,9

44,9

45,9

47,5

Cool

82,1

87,1

92,2

97,5

103,0

108,6

117,2

93,7 kW

74,8

79,3

83,9

88,8

93,7

98,8

106,7

99,2

104,7

110,4

116,1

121,9

130,7

110,2

116,9

123,7

130,8

138,0

145,4

156,8

120,0

127,2

134,6

142,4

150,3

158,5

171,1

*

Only Compressors.

SyScroll 85-135 Air |

37

Model

LWT

°C

85

95

105

120

135

5

7

15

18

11

13

7

9

13

15

18

5

9

11

5

7

18

5

7

9

11

13

15

7

9

18

5

9

11

13

15

11

13

15

18

35

Input

Power

*

30,4

31,1

31,8

32,6

33,4

34,2

35,5

36,8 kW

25,8

26,3

26,9

27,5

28,1

28,7

29,6

37,4

38,0

38,6

39,2

39,9

40,8

39,5

40,1

40,7

41,4

42,1

42,9

44,0

44,4

45,2

46,0

47,0

47,9

48,9

50,6

Cool

78,9

83,7

88,6

93,7

99,0

104,3

112,6

89,9 kW

71,9

76,3

80,8

85,4

90,2

95,1

102,6

95,1

100,5

105,9

111,4

116,9

125,3

105,8

112,2

118,8

125,5

132,5

139,6

150,5

114,9

121,8

128,9

136,3

143,9

151,7

163,8

Condensing Air Temperature °C

38

Cool

Input

Power

*

75,6

80,2

84,9

89,8

94,8

99,9

107,8

85,7 kW

68,9

73,1

77,4

81,9

86,5

91,1

98,4

90,8

95,9

101,2

106,4

111,8

119,8

101,1

107,3

113,6

120,1

126,7

133,5

144,0

109,5

116,1

122,9

130,0

137,2

144,7

156,2

32,3

33,0

33,7

34,5

35,3

36,1

37,5

39,4 kW

27,3

27,8

28,4

29,0

29,6

30,2

31,2

40,1

40,7

41,4

42,0

42,7

43,7

42,3

43,0

43,7

44,3

45,1

45,8

47,0

47,6

48,4

49,3

50,2

51,2

52,2

53,9

73,3

82,8

97,9

105,8

Cool kW

66,9

40

Input

Power

* kW

28,3

33,7

41,3

44,4

49,9

*

Only Compressors.

38

|

SyScroll 85-135 Air

Heating Capacities - SyScroll Air HP S - (STD)

Model

85

95

105

120

135

LWT

°C

40

45

50

30

45

50

30

35

50

30

35

40

30

35

40

45

30

35

40

45

35

40

45

50

50

Heat kW

59,5

59,2

59,2

66,8

66,7

-

75,8

76,2

76,0

84,1

84,7

85,0

92,4

93,3

94,4

-7

Input

Power

* kW

17,1

18,9

21,1

19,8

21,9

-

24,2

27,1

30,4

27,0

30,5

34,3

30,1

34,0

38,6

Heat kW

62,6

62,3

62,2

70,1

69,9

70,0

-5

Ambient Air Temperature °C

-3

Input

Power

* kW

17,2

19,0

21,2

Heat kW

66,0

65,6

65,3

65,2

Input

Power

* kW

17,4

19,2

21,2

23,7

19,9

22,0

24,5

74,0

73,7

73,5

20,0

22,1

24,5

79,3

79,7

79,8

88,0

88,5

89,0

96,6

97,4

98,4

24,2

27,1

30,4

27,1

30,5

34,3

30,2

34,1

38,6

83,4

83,7

83,7

83,5

92,7

93,1

93,3

93,6

101,8

102,4

103,2

104,1

24,2

27,2

30,5

34,1

27,1

30,5

34,4

38,7

30,2

34,1

38,5

43,7

0

24,2

27,2

30,5

34,2

27,1

30,5

34,4

38,7

Input

Power

* kW

17,6

19,3

21,4

23,8

26,5

20,2

22,3

24,7

27,5

30,3

34,1

38,5

43,6

89,2

89,6

89,7

89,6

99,2

99,5

99,8

100,1

Heat kW

71,0

70,6

70,3

69,9

69,6

79,5

79,1

78,9

78,8

109,2

109,2

109,9

110,7

*

Only Compressors.

SyScroll 85-135 Air |

39

Model

LWT

°C

85

95

105

120

135

40

45

50

30

45

50

30

35

50

30

35

40

30

35

40

45

30

35

40

45

35

40

45

50

50

5

Input

Power

*

25,0

27,7

30,8

24,2

27,2

30,6

34,3

38,5 kW

17,9

19,7

21,7

24,0

26,7

20,5

22,6

27,2

30,6

34,4

38,7

43,6

30,3

34,2

38,5

43,5

49,2

Heat

88,5

88,1

87,9

100,4

100,1

100,1

100,0

99,6 kW

80,2

79,6

78,9

78,3

77,7

90,1

89,5

111,8

111,5

111,3

111,3

111,2

122,8

122,7

122,8

122,6

123,1

Heat

93,4

92,8

92,3

105,2

105,3

105,3

105,1

104,3 kW

84,7

84,1

83,3

82,4

81,3

94,7

94,0

117,4

117,2

117,1

116,9

116,5

128,8

128,5

128,5

128,6

128,9

7

Ambient Air Temperature °C

10

Input

Power

*

25,1

27,8

30,9

24,2

27,2

30,6

34,3

38,5 kW

18,0

19,9

21,9

24,2

26,7

20,7

22,7

27,2

30,6

34,4

38,7

43,6

30,4

34,2

38,5

43,5

49,1

Heat

100,2

99,1

98,3

113,0

112,7

112,3

111,7

111,1 kW

91,2

90,1

89,1

88,1

87,0

102,1

101,1

126,2

125,7

125,2

124,3

123,8

138,5

138,0

137,5

137,2

136,5

Input

Power

*

25,3

28,0

31,1

24,2

27,2

30,6

34,3

38,6 kW

18,2

20,1

22,1

24,3

26,9

20,9

22,9

27,2

30,6

34,4

38,7

43,6

30,4

34,2

38,6

43,5

49,1

15

Input

Power

*

25,7

28,4

31,4

24,2

27,2

30,5

34,3

38,5 kW

18,4

20,4

22,5

24,7

27,2

21,2

23,3

27,2

30,6

34,4

38,7

43,5

30,5

34,3

38,6

43,5

49,0

Heat

113,3

112,1

110,3

127,5

126,7

125,9

124,8

123,7 kW

103,4

102,4

100,7

99,2

97,7

115,9

114,6

142,8

141,7

140,7

139,5

138,0

156,6

155,6

154,6

153,6

152,7

*

Only Compressors.

40

|

SyScroll 85-135 Air

Condensing unit - SyScroll Air RE _ - (STD-HT-HPF)

Model

85

95

105

120

135

LWT

°C

15

18

5

7

11

13

7

9

13

15

18

5

9

11

5

7

18

5

7

9

11

13

15

7

9

18

5

9

11

13

15

11

13

15

18

25

Input

Power

*

23,0

23,4

23,9

24,3

24,8

25,3

26,2

26,6 kW

19,5

19,8

20,1

20,5

20,8

21,1

21,6

26,9

27,2

27,6

27,9

28,2

28,7

30,4

30,8

31,3

31,7

32,2

32,7

33,5

34,3

34,8

35,4

36,1

36,8

37,5

38,7

Cool

98,6

104,9

111,5

118,3

125,3

132,6

143,9

110,4 kW

88,1

93,7

99,6

105,6

111,9

118,4

128,6

117,3

124,4

131,7

139,1

146,8

158,5

123,7

131,6

139,7

148,1

156,8

165,7

179,6

135,6

144,2

153,2

162,4

172,0

181,9

197,3

Cool

93,1

99,1

105,4

111,8

118,5

125,3

136,1

104,3 kW

83,5

88,9

94,4

100,1

106,1

112,2

121,9

110,8

117,4

124,2

131,1

138,2

149,1

116,6

124,0

131,6

139,5

147,6

156,0

168,9

127,4

135,5

143,9

152,6

161,6

170,9

185,4

30

Input

Power

*

Condensing Air Temperature °C

35

Cool

Input

Power

*

25,2

25,6

26,1

26,7

27,2

27,8

28,6

29,8 kW

21,5

21,8

22,2

22,6

23,0

23,4

24,0

30,2

30,5

30,9

31,2

31,5

32,1

34,1

34,6

35,0

35,5

36,0

36,5

37,4

38,4

39,0

39,6

40,3

41,1

41,8

43,1

87,4

93,0

98,9

105,0

111,3

117,7

127,8

97,9 kW

78,6

83,6

88,8

94,3

99,9

105,7

114,7

103,9

110,1

116,4

122,9

129,4

139,5

109,1

116,0

123,1

130,5

138,1

145,9

157,9

118,8

126,4

134,2

142,4

150,8

159,4

173,0

27,7

28,2

28,7

29,2

29,8

30,4

31,4

33,5 kW

23,5

23,9

24,4

24,8

25,2

25,7

26,3

33,9

34,2

34,6

35,0

35,4

35,9

38,3

38,8

39,3

39,8

40,3

40,9

41,7

43,1

43,7

44,4

45,1

45,9

46,7

47,9

Cool

81,3

86,6

92,2

97,8

103,7

109,8

119,3

90,8 kW

73,2

78,0

82,9

88,0

93,2

98,7

107,2

96,5

102,3

108,2

114,3

120,4

129,7

101,0

107,4

114,1

121,0

128,1

135,3

146,5

109,6

116,6

123,9

131,5

139,3

147,4

159,9

40

Input

Power

*

30,5

31,0

31,6

32,1

32,7

33,4

34,4

37,6 kW

25,9

26,3

26,7

27,1

27,6

28,1

28,8

38,0

38,5

38,9

39,3

39,7

40,3

43,1

43,6

44,1

44,6

45,2

45,8

46,7

48,5

49,1

49,8

50,5

51,3

52,1

53,4

75,0

79,9

85,1

90,4

95,9

82,9

88,3

93,8

99,4

105,0

92,1

98,2

104,4

110,8

117,4

99,6

106,1

112,9

119,8

127,1

Cool kW

67,5

72,0

76,5

81,3

86,2

45

Input

Power

* kW

28,4

28,8

29,3

29,7

30,2

48,5

49,0

49,5

50,1

50,7

54,6

55,2

55,9

56,6

57,4

42,2

42,7

43,2

43,7

44,1

33,8

34,3

34,8

35,4

36,0

*

Only Compressors.

HT Version

SyScroll 85-135 Air |

41

Cool

95,0

100,9

107,0

113,2

119,7

126,3

136,6

107,7 kW

85,4

90,7

96,2

101,9

107,7

113,7

123,1

114,2

120,9

127,7

134,7

141,8

152,6

120,1

127,5

135,2

143,0

151,1

159,3

172,1

131,1

139,1

147,4

156,0

164,9

174,0

188,0

Condensing unit - SyScroll Air RE S - (STD)

Model

85

95

105

120

135

LWT

°C

5

7

15

18

11

13

7

9

13

15

18

5

9

11

5

7

18

5

7

9

11

13

15

7

9

18

5

9

11

13

15

11

13

15

18

25

Input

Power

*

24,4

24,9

25,5

26,1

26,8

27,4

28,5

28,0 kW

20,7

21,1

21,5

21,9

22,4

22,8

23,5

28,4

28,8

29,3

29,7

30,1

30,7

32,3

32,8

33,4

33,9

34,5

35,2

36,2

36,5

37,2

38,0

38,8

39,7

40,6

42,1

Cool

89,4

95,0

100,7

106,7

112,7

119,0

128,7

101,5 kW

80,7

85,7

90,9

96,2

101,7

107,4

116,2

107,6

113,8

120,2

126,7

133,3

143,3

112,9

119,9

127,0

134,3

141,9

149,6

161,4

122,8

130,3

138,1

146,1

154,4

162,9

176,1

30

Condensing Air Temperature °C

35

Input

Power

*

Cool

26,7

27,3

27,9

28,6

29,3

30,0

31,1

31,4 kW

22,6

23,1

23,6

24,1

24,6

25,1

25,9

31,9

32,3

32,7

33,2

33,6

34,3

36,2

36,7

37,3

37,9

38,6

39,2

40,3

40,9

41,7

42,5

43,3

44,2

45,2

46,7

118,4

125,2

132,2

139,4

150,5

114,0

121,0

128,2

135,7

143,4

151,3

163,5

83,6

88,8

94,2

99,8

105,5

111,4

120,4

94,9 kW

75,6

80,4

85,2

90,2

95,4

100,7

108,9

100,6

106,4

112,4

118,4

124,5

133,8

105,2

111,7

Input

Power

*

41,8

42,5

43,1

43,8

44,9

45,9

46,7

47,5

48,4

49,3

50,3

51,9

29,4

30,0

30,7

31,3

32,0

32,8

33,9

35,3 kW

24,8

25,3

25,8

26,3

26,8

27,4

28,2

35,7

36,2

36,7

37,2

37,7

38,4

40,6

41,2

40

Input

Power

*

32,5

33,1

33,7

34,4

35,2

35,9

37,1

39,5 kW

27,2

27,7

28,2

28,7

29,3

29,8

30,7

40,1

40,6

41,2

41,7

42,2

43,0

45,6

46,2

46,9

47,6

48,3

49,0

50,1

51,6

52,4

53,2

54,1

55,0

56,0

57,6

Cool

77,5

82,4

87,4

92,6

97,9

103,4

111,8

87,5 kW

70,2

74,6

79,1

83,8

88,6

93,6

101,3

92,9

98,4

104,0

109,6

115,3

124,0

96,9

102,9

109,1

115,5

122,0

128,7

139,0

104,5

111,0

117,7

124,6

131,7

139,0

150,3

(*) Only Compressors.

42

|

SyScroll 85-135 Air

Evaporator Water Pressure Drop Curves

SySroll Air CO

50

40

30

20

10

0,5

50

40

30

20

10

2,5

SyScroll HP

85

95

105

120

135

5

Water flow rate (l/s)

7,50

50

40

30

20

85

95

105

10

120

135

2,5

Desuperheater pressure drop

5

Water flow rate (l/s)

7,50

85

95

105

120

135

Water flow rate (l/s)

1,50

10

10

2 2,50

SyScroll 85-135 Air |

43

Water pump curves 1 or 2 pump available static pressure (1P/2P-SP)

275

250

225

200

175

150

125

100

75

50

25

0

3,0 3,5 4,0 4,5 5,0

85-95

5,5 6,0 6,5

Water flow rate (l/s)

7,0

105-120

7,5 8,0

135

8,5 9,0

Water pump curves 1 or 2 pump available static pressure (1P/2P-HP)

350

225

200

175

150

125

325

300

275

250

135

100

75

50

25

85-95

0

105-120

2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5 7,0 7,5 8,0 8,5 9,0 9,5 10,0 10,5 11,0 11,5 12,0

Water flow rate (l/s)

44

|

SyScroll 85-135 Air

Dimensions SyScroll 85-105 Air

Front view

I

M

I

M

N

O

N

O

218

218

A

E

=

D

B =

178

C

=

Back view

178

C

L

L

F

G

F

G

650

650

1095

1095

70

70

NOTES

A B C D E Water connection 2” 1/2 Gas M

F

G

I

L

M

Electrical auxiliary lines

Electrical power supply

Gauge kit (Accessory)

Main switch

Control keypad / display

OPTIONAL

N

O

Desuperheater water inlet ø 1” GAS M

Desuperheater water outlet ø 1” GAS M

P1, P2, P3, P4 Anti-vibration mount position

45

45

P1

552

P1

552

P2

P2

Side view

1385

1600

2905

B

B

A

1600

Top view

P4 4x 17

P4 4x 17

155

155

650

E

C-D

E

90

C-D

90

650

970

1800

971

P3

971

P3

970

1800

619

553

619

553

Hydraulic option

STD

1P

2P

1PT

2PT

Water in

D

C

A

C

D

Water out

B

E

B

B

E

SyScroll 85-135 Air |

45

Dimensions SyScroll 120-135 Air

Front view

N

O

N

O

218

218

=

A

E

E

B

D

B

=

178

178

C

C

F

G

F

G

653

653

M

M

I

I

L

L

P2

P2

1095

1095

70

70

45

45

P1

552

P1

552

NOTES

A B C D E Water connection 2” 1/2 Gas M

F

G

I

L

M

Electrical auxiliary lines

Electrical power supply

Gauge kit (Accessory)

Main switch

Control keypad / display

OPTIONAL

N

O

Desuperheater water inlet ø 1” GAS M

Desuperheater water outlet ø 1” GAS M

P1, P2, P3, P4 Anti-vibration mount position

Side view

1985

A

B

A

1985

B

2200

3505

2200

P4 4x 17

P4 4x 17

155

155

E

653

653

90

970

2400

1214

1214

P3

P3

732

553

732

553

Hydraulic option

STD

1P

2P

1PT

2PT

Water in

D

C

A

C

D

Water out

B

E

B

B

E

46

|

SyScroll 85-135 Air

Space requirements

1 MT.

3 MT

.

0,8 MT

.

1 MT

.

1,2

MT.

Systemair srl

Via XXV Aprile, 29

20825 Barlassina (MB)

Italy

Tel. +39 0362 680 1

Fax +39 0362 680 693 [email protected]

www.systemair.com

Systemair · May 2014 · EDM SyScroll 85-135 Air-S-1GB/05.14 • E34013 As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos.

advertisement

Key Features

  • Air cooled water chiller
  • Cooling or heating operation
  • Tandem scroll compressor
  • Plate heat exchanger
  • Quiet fans
  • 2 acoustic options: standard and super low noise
  • Electronic control and management system
  • Safety features
  • Control features
  • Wide range of operating limits

Frequently Answers and Questions

What refrigerant does the SyScroll 85-135 Air use?
This model uses R410A refrigerant.
What types of compressors are used in the SyScroll 85-135 Air?
It features two tandem scroll compressors.
What are the acoustic options available for the SyScroll 85-135 Air?
The SyScroll 85-135 Air is available in two acoustic options: Standard and Super Low Noise (S).
What type of heat exchanger does the SyScroll 85-135 Air use?
It incorporates a plate heat exchanger.
What is the maximum operating pressure for the SyScroll 85-135 Air?
The maximum operating pressure is 6 bar.
What are the minimum and maximum ambient air temperatures for the SyScroll 85-135 Air?
The minimum ambient air temperature is -14 °C for the standard version and -18 °C for the High Temperature version. The maximum ambient air temperature is 45 °C.
What are some of the safety features of the SyScroll 85-135 Air?
Safety features include a high pressure switch, low pressure switch, water flow switch, and more.
What are some of the control features of the SyScroll 85-135 Air?
Control features include chilled and hot water temperature regulation, evaporator antifreeze protection, and heat pump defrost control. The unit also has an electronic control and management system.

Related manuals