Systemair SyScroll 85-135 Air Air Cooled Water Chiller Engineering Data Manual
Below you will find brief information for Air Cooled Water Chiller SyScroll 85-135 Air. This air-cooled water chiller is designed for cooling and heating applications, and it utilizes R410A refrigerant. It features a tandem scroll compressor, plate heat exchanger, and a ventilating unit with quiet fans. These units are available in two acoustic options, standard and super low noise. It is important to note that the standard version can be supplied with a pressure actuated stepless type fan speed controller for low ambient operation (-14 °C) while the Super Low Noise version is supplied with this as standard. The SyScroll units are equipped with safety features such as high pressure switch, low pressure switch, water flow switch and more. They also offer control features such as chilled and hot water temperature regulation, evaporator antifreeze protection and heat pump defrost control. With a wide range of operating limits and capacity steps, the SyScroll 85-135 Air can be easily integrated into a variety of HVAC systems.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
Chiller | Close Control | Water terminals
SyScroll 85-135 Air
NEW
Air Cooled Water Chillers
Cooling Only, Heat Pump
Engineering Data Manual
84 to 132 kW 88 to 135 kW
SyScroll 85-135 Air |
3
Key point
General
SyScroll Air have been designed and optimized to work with R410A refrigerant . As near azeotropic mixture it behaves like a homogeneous substance (reduced service problems in case of leakage or re-charge) with negligible temperature glide.
Units with high seasonal performances ( ESEER up to
4.4
).
With except for the fans, all the versions keep the same configuration of the base units (same structure, electrical board, compressors and coils).
Easy upgrade of the units in stock or on the field .
Electronic expansion devices on all units: superheating value controlled by microprocessor, simple and accessible refrigeration system especially for heat pump versions with reduction of brazing points and than possible leakage.
New Microchannel coils for Cooling only version.
Compressors box (less sound proofing) always installed
- additional compressors jackets only for S version (easy upgrade of the units in stock) .
High Temperature Version (HT) developed for high ambient temperature but also providing high seasonal efficiency (ESEER higher than and high operation limits with inverter fans (electronic brushless type motor).
Special version (HPF) for high external static pressure
(max. 120 Pa) with inverter fans (electronic brushless type motor).
New microprocessor : 4 times greater RAM memory compared with previous version, flash memory card and compressors envelope curves put inside, 3 times faster than previous control.
Hydro kits with or without buffer tank (205 l from 85 to
105 size, 320 l from 120 to 135 size).
One or two water pumps are available: standard pressure (100 kPa) or high pressure (200 kPa).
For service operation, special valves dedicated to R410A are supplied on the refrigerant system. These valves, of
5/16” flare SAE type, are mounted on the liquid line, discharge, suction line and on the gauges manifold of the unit.
4
|
SyScroll 85-135 Air
Specifications
SY SCROLL
SIZES Air
CO
HP
RE
BC
-
HT
HPF
-
S
CO = Cooling Only; HP = Heat Pump; RE = Remote Evaporator; BC = Brine for Process Cooling.
General
The new SyScroll Air units have been designed to operate with HFC 410A refrigerant. Both compressors and heat exchangers (plate heat exchanger and coils) have been optimized for this refrigerant.
They consist of a single refrigerant circuit equipped with a tandem complete with high efficiency and low vibration level Scroll compressors, a single circuit plate heat exchanger and a ventilating unit comprising V-shape coils and quiet fans; each of them is located in an externally mounted nozzle profile housing generating low sound level.
Syscroll Air CO units are available in 5 sizes , with a nominal capacity range from 84 to 132 kW .
SyScroll Air HP units are available in 5 sizes , with a nominal capacity range from 79 to 125 kW in cooling mode and from 85 to 133 kW in heating mode.
HPF (High Pressure Fans) version : It has same equipment as Basic version, except that the units are equipped with special inverter fans (same as those used on HT version, but with a different regulation) driven by EC motors with integrated electronic inverter . HPF version provides external static pressure up to 120 Pa . This version can be supplied with BLN acoustic option only.
In addition, partial heat recovery option is available:
Desuperheater : All the versions can be supplied with plate type heat exchangers fitted, one on each refrigerant circuit, on the compressor discharge line to recover about 20 % of the total heat rejected to the condensers.
Conformity with directives
The following applies to all the sizes and versions:
Machine Directive: 2006/42/EC
Electromagnetic Compatibility Directive: 2004/108/EC
Pressure Equipment Directive: 97/23/EC
SyScroll Air (Standard) version can be supplied with 2 acoustic options :
Basic Low Noise (-) : The units are equipped with delta connected fans implying a standard rpm. The chillers are not supplied with fan speed controller, but fitted with compressors box to reduce the noise emissions.
Super Low Noise (S) : The units are equipped with star connected fans , fitted with a speed controller which allows the units to operate with a very low rpm. The chillers are supplied with compressors box and soundproof jackets on compressors reducing significantly the noise emissions.
To increase their field of applications, the SyScroll Air ranges are available in 2 additional versions :
HT (High Temperature) version : It has same equipment as Basic version, but the units are fitted with special inverter fans and motors to ensure low energy consumption and to operate on a wider envelope. The HT version can be supplied with BLN acoustic option only.
Cabinet and structure
The unit cabinet and structure are made of heavy gauge galvanized steel coated with polyester powder based painting (RAL 7040). All parts of the structure are fastened totally with non-corrosive screws and bolts.
Compressors
Each unit is equipped with two compressors arranged in tandem.
Compressors are of hermetic scroll type and fitted with an electronic control system ensuring protection against high temperature and excessive load.
All compressors have direct-on-line starting and are mounted on rubber vibration isolators in order to minimize noise and vibration transmission.
SyScroll 85-135 Air |
5
Evaporator
Evaporators is of a brazed stainless steel plate type heat exchanger.
It is insulated with a 19 mm thick closed cell polyethylene foam material and is fitted with a film type electric heater on the external surface to prevent the unit from freezing at a low temperature (down to -18 °C) when the unit is off.
Water connections are of a Male GAS Threaded type
(2”1/2 diameter).
Heat pump units (HP) are provided with 4-way reversing valve, suction accumulator and liquid receiver on the liquid line.
The functional diagram of each circuit is shown in the section “Refrigerant flow diagram”.
Electrical board
Metal case, externally arranged at one end of the unit.
Case for the board with IP44 protection rating, complete with grille for natural air ventilation of the box.
Condenser coils
The condenser coils are made of seamless copper tubes, arranged in staggered rows, mechanically expanded into corrugated aluminum fins.
For Cooling only version (CO version) condenser coils are of microchannel type, made of 100% aluminium (fins, tubes and headers) with the exception of pipe couplings which are in copper.
Condenser fans
For each size, all versions keep the same number of fans.
Large diameter, direct drive axial type fans with asynchronous three-phase motors are used in all acoustic versions (S version) of SyScroll 85-135 Air.
Special inverter fans with electronic brushless type motors are used in SyScroll 85-135 Air HT and HPF.
On high pressure fans of HPF units, the external static pressure (≤ 120 Pa) can be adjusted on site to match the customer demand directly from the electronic control panel of the unit.
Fans are equipped with externally mounted nozzle profile housing which generates low sound levels.
Control and safety devices
Each unit is fitted with the following devices:
Safety:
Power disconnect switch with an emergency stop func
tion.
HP switch, set to 40.5 bar, automatic and manual reset to be reinitialized from the control panel.
Water flow switch on the evaporator, protect the unit
against low water flow operation.
Antifreeze temperature sensor (set to +4 °C) on the
evaporator.
Safety valve on discharge line, set to 45 bar.
Control:
HP and LP transducers.
Evaporator water inlet temperature sensor.
Evaporator water outlet temperature sensor (with an antifreeze function).
Suction temperature sensor (in case of EEV option).
Ambient air temperature sensor.
Coil temperature sensor.
Fan speed control
The speed of fans is controlled in order to operate at a low ambient temperature.
On units with standard axial fans, the accessory fan speed control, supplied as standard on S version, is of a pressure actuated stepless type with an electronic controller.
The pressure actuated stepless type fan speed controller can be supplied as optional on - version. It allows the units to operate in cooling mode at ambient temperature down to -14 °C.
On HT and HPF units with electronic axial fans, the pressure actuated stepless type fan speed control is supplied as standard, because these electronic fans are already equipped with an integrated fan speed control (fan speed range: 50 to 1200 rpm; ambient temperature limit: -18 °C
(in cooling mode only).
Refrigerant circuits
All the units are composed a single refrigerant circuit.
Each refrigerant circuit is equipped with liquid line and discharge line shutoff valves, filter-drier with solid core, sight glass and thermostatic expansion valve (electronic expansion valve can be supplied as an option) .
Electronic control
Units are supplied with the new microprocessor-based electronic control and management system ensuring the following functions:
Management of the operation of compressors:
Power on/off
Anticycle management
Tandem unloading for high pressure or high compressor pressure ratio (integrated inside the curves of compressor operating limits).
Chilled and hot water temperature regulation (control option on inlet water temperature RWT (P+I type) or outlet water temperature LWT (neutral band type) of the evaporator.
Control of superheating on suction line (in case of EEV option).
Evaporator antifreeze protection.
Heat pump defrost control for automatic operation.
Management of high and low pressure alarms.
Management of the electronic expansion valves by means of EXV controller allowing optimized functions: cooling, heating, start-up and defrost (in case of EEV option).
6
|
SyScroll 85-135 Air
Management of external interlocks.
Management of the remote control:
Unit power on/off
Summary alarm signals
Remote signalling, by dry contacts:
Voltage presence
Compressors in operation
General Alarm
Management of the hydro kit: start-up of pump, antifreeze heater of external tank.
The unit controller can also clearly show all control parameters of the machine on the liquid crystal display, such as:
Display of superheating value (in case of EEV option).
Display of the temperature at the evaporator inlet and outlet.
Display of the ambient air temperature.
Display of discharge pressure and suction pressure.
Display of the set point.
Display of the various alarm and operation status:
Low / High pressure
Evaporator antifreeze
Flow switch signal for lack of water
Control of the compressor operating hours
Compressors in operation
Pump in operation and operating hours
Thermal protection of compressors
Thermal protection of fans
Faulty sensors
Standard equipment
Set point timer/clock card.
Pressure actuated fan speed control.
Back light display.
Digital pressure and temperature reading kit.
High ambient pressure control.
Sequence phase control.
Control circuit transformer 400 V/230 V.
Data logger.
Power supply without neutral.
Hour meter.
Main switch.
Refrigerant R410A.
PED approval.
Evaporator antifreeze electric heater.
Compressor jacket (standard on S version).
Compressor box.
Water flow switch.
Optional hydro kits
On board mounted inside and remote hydrokits are available as optional. The on board hydro kits can be supplied with or without buffer tank while remote hydro kits (supplied loose for field installation) are always provided with internal tank.
On board hydro kit without buffer tank has the following components:
Single or double pump with low static pressure (100 kPa) or high static pressure (200 kPa),
Expansion tank (18 litres for all models),
Water filter option (supplied loose),
Shut-off valves,
Safety valve,
Automatic air vent valve,
Thermal insulation for pipes and water pump(s),
The on board hydro kit with buffer tank has the following components:
Single or double pump with low static pressure (100 kPa) or high static pressure (200 kPa),
Buffer tank (205 l from 85 to 105 size, 320 l from 120 to 135 size),
Expansion tank (18 litres for all models),
Water filter option (supplied loose),
Shut-off valves,
Safety valve,
Automatic air vent valve,
Thermal insulation for pipes and water pump(s),
Electrical box,
Antifreeze electric heater inside buffer tank (electric heater for pipes is not supplied).
Factory installed options
ModBus protocol kit for BMS.
Lonwork protocol kit for BMS.
Bacnet protocol kit for BMS.
Compressors soft starter.
Pressure actuated stepless fan speed controller for low ambient operation (-14 °C).
Double set point.
Power factor correction capacitors.
Compressors overload protection.
GSM.
HP & LP manometers.
Ecoating for Microchannel and AL/CU. Blue fins treatment for AL/CU.
Condenser coils with copper fins.
Coil grilles.
Chiller grilles.
Desuperheater.
On board hydro kits 1P/2P with/witout tank.
Field-installed accessories
Remote ON/OFF control.
Remote keyboard panel.
Master and slaves control, up to 4 units max.
Spring anti-vibration.
Water filter.
Remote hydro kits with buffer tank, 1 or 2 low or high pressure pump(s), relevant accessories and with or without antifreeze heater:
300 litres: sizes 85-105.
500 litres: sizes 120-135.
SyScroll 85-135 Air |
7
Accessories & Options
SyScroll Air
Set point timer/Clock card
Back light display
Digital pressures and temperatures reading Kit
High pressure control on capacity
Sequence phases control
Control circuit transformer 400V/230V
Data logger
Power supply without neutral
Hour meter
Main switch
Flow switch
Antifreeze electric heater kit
Compressor Jacket
Remote On/Off control
Remote keyboard panel
Electronic expansion valves
Modbus protocol kit for BMS
Lonwork protocol kit for BMS
Bacnet protocol kit for BMS
Interface Kit ethernet/webctrl pcos
(Modbus & Bacnet already included)
Softstarter for compressor
Low ambient kit (-14°C)
(pressostatic stepless fan speed control)
Double set point
Power factor corrector capacitors
Overload protection for compressors
Delivery
Std
Std
Std
Std
Std
Std
Std
Std
Std
Std
Std
Std
Std SLN
Accessory
Accessory
Option
Option
Abbreviation Description & Befenit
CLK
PHC
To schedule 4 different interval time with different active water T setpoint.
User Display panel mounted. Suggested for outdoor installation.
Pressure Transducers & Sensors to show the Discharge and
Suction pressure and temperature during running condition.
Functions able to protect multistage circuit from High discharge pressure values. Circuit is partloaded whenever the Discharge pressure is too high to prevent HP tripping.
It allows to check the correct sense R-S-T of electric supply phases for 400/3/50 units.
TRF
DL
3PH
FS
EEH
CJ
Voltage transformer to provide correctly the separated voltage to the auxiliary line.
Record continuously the essential thermodynamic operating parameters, during the last hours. This facilitates debug and service activity on field.
Unit to be supplied with 400/3/50. No need of Neutral cable.
Total running hours recorded for each compressors and for total unit. Also record of total scroll compressors starts.
Front operated switch-disconnector with direct mounted handle to cut the power Supply Line according CE standards.
Prevents the operation of the unit if the circulating chilled fluid is insufficient. It is recommended to install a flow switch to ensure the correct operation of the unit.
Electrical Heater protects the plate exchanger.
Jacket for each compressors in order to reduce the sound of its.
It enables the operator to power on the unit when it is in standby mode, to display alarms and switch over cooling–heat pump. Maximum lenght: 50mt.
EEV
MBS
Makes it possible to control the unit through the remote terminal, up to a maximum distance of 400mt of telephone cable.
It is the device able to control the refrigerant flow on suction line trough a stepper motor in order to keep the superheat as constant as possible.
It permits the integration of the unit with BMS with Modbus protocol trough RS485 port.
Option LON
It permits the integration of the unit with BMS with Lonwork
Network.
Option
Option
Option
Option
Option
Option
Option
BAC
SS
FSC
DSP
PFC
CP
It permits the integration of the unit with BMS with Bacnet protocol trough RS485 port.
It permits the integration of the unit with BMS with Modbus or
Bacnet protocol trough Ethernet port (TCP/IP).
An electronic device that automatically starts up the compressors gradually. The starting current can be reduced by up to 40% of the direct on line value.
Electronic speed controllers are designed to control the speed of fan motors in Air Cooled Chiller and Heatpump. Fan Speed controlled by Condensing Pressure in cool mode or by Air Temp in heat mode. Using variable fan speed controllers offers following benefits in commercial refrigeration or air-conditioning applications High
Efficiency, Low Noise level, Low air temperature in cool mode and
High air temperature in heat mode.
Can manage two different applications (set point) selected by remote dry contact Circuit 1 and Circuit 2.
On/Off or Part Load by remote Dry contact.
The purpose of the power factor corrector capacitor is to minimize the input current distortion and make the current in phase with the voltage. Target is to keep Power Factor about 0.90 in any running condition.
The compressor is equipped with an amperometrical protection
(overload protection) wired under the compressor contactor; this protection operates: a) if compressor’s temperature is too high. b) if current’s absorption is too high.
8
|
SyScroll 85-135 Air
Accessories & Options (continued)
SyScroll Air
Sequencer for up to 4 chillers installation
Master and slave up to 4 chillers installation:
CHILLERNET
GSM
Automatic circuit breaker
Mechanical gauges kit (HP and LP manometers)
E-coating MCHX
Copper Fins
Coil Guards
Chiller grilles
Desuperheater
Water pressure switch
Water filter
Delivery
Accessory
Abbreviation Description & Befenit
SEQ
It can easily pilot up to 4 units, chiller or heat pumps, belonging to the same family, fitted in parallel, 50 metres apart maximum.
Accessory
Option
Option
Option
Option
Option
Option
Option
Option
Accessory
Accessory
GSM
ACB
KM
CU/CU
CG
KG
D
It is a network of chillers. They are hydraulically connected in parallel on the same installation. They are intended to work together as a single machine whose capacity equals the total amount of capacities. Up to 4 chillers of the same family can be connected together.
One of these chillers is called MASTER, the others are SLAVE. The
MASTER chiller will control all the other chillers.
Makes it possible to check the working mode or the switching on/ off of the unit via SMS. In case of any alarms, the unit sends an
SMS to the user.
ACB is an automatically operated electrical switch designed to protect an electrical circuit from damage caused by overload or short circuit. Providing Magnetic and Thermal protection to Fan and
Compressor motors.
Pressure gauges that display the operating pressure in the high and low pressure sections of the refrigerant circuit.
It is a treatment fo MCHX coil for medium level of pollution and for marine atmosphere.
The package heat exchanger finned coils in Cu/Cu can be used in places with a concentrations in the air of saline and highly aggressive agents: Not suitable in presence of sulphur-based agents.
Grilles to protect the coils.
Grilles to protect unit avoiding possible intrusion into the unit.
Additional exchanger in order to recover 20% of capacity for
Domestic Hot Water application.
Mechanical water pressure switch to be mounted on the field installation on installation water piping to prevent very low Water
Pressure.
Filter to remove impurities from the water supply.
Accessories are loosed and to install in the field. Options are mounted in factory.
SyScroll 85-135 Air |
9
EN 14511
Starting 2012 Campaign Eurovent Certification Company took decision to start certify only performances declared in according severe European Standard EN14511.
BEFORE 2012: GROSS PERFORMANCES
Before this date all capacity performances are declared, measured and certified by Eurovent, as GROSS performances.
COOLING or HEATING CAPACITY was rated without taking in account the negative contribution of the heat exchanger Pressure Drop or the positive contribution of the Head Available prevalence in example.
OWER INPUT was rated as pure sum of all power input contribution from all motors fitted on the unit. Without taking in account the correction due to power spent to win the exchanger Pressure Drop in example.
AFTER 2012: NET PERFORMANCES
After this date all data are certified according EN14511. Mainly consequences in example on Water chiller or heatpump are:
COOLING or HEATING CAPACITY is now rated taking in account the negative contribution of the heat exchanger Pressure
Drop or the positive contribution of the Head Available prevalence in example. In case of Water to Water unit, in example, both exchanger Pressure Drop values are taken in account in the formula.
POWER INPUT is now rated as all power input contribution from all motors fitted on the unit taking in account also the correction due to power spent to win the exchanger Pressure Drop in example.
As an important consequence of these new rules setted by Eurovent is that EER, COP and ESEER are also affected by these correction. All efficiency index are now calculated, measured and certified according new rules setted by Eurovent according EN14511.
Air to water unit (non ducted outdoor):
Ph
Pc
Pe
Ph
Pc
Pe m
(1) m
(1) m
(1)
Indoor pump is an integral part
ECC 2011 (gross) EN14511
Ph m
– q wi
Δp pi e,wi
Pc m
+ q wi
Δp pi e,wi
Pe m
– q wi
Δp pi e,wi
(1) Measured with the indoor pump not running.
ECC 2011 (gross)
Ph
Pc
Pe
Indoor pump is not an integral part
m m m
EN14511
Ph m
+ q wi
(–Δp
η pi i,wi
)
Pc m
– q wi
(–Δp pi i,wi
)
Pe m
+ q wi
(–Δp
η pi i,wi
)
Where:
Ph = NET heating capacity.
Pc = NET cooling capacity.
Pe = electrical power input.
Ph m
Pc m q
η wi
Δ pi,wi pi
= is the gross heat capacity, expressed in Watts.
= is the gross cool capacity, expressed in Watts.
= is the nominal liquid flow rate.
Δ pe,wi
= is the measured available external static pressure.
= is the measured internal static pressure difference.
= is the efficiency of the pump.
Reference: Guidelines for the declaration of performances according to EN14511 (available a copy upon request for
Systemair customer).
10
|
SyScroll 85-135 Air
Refrigerant Flow Diagram - SyScroll 85-135 Air CO
2
7
G
5
AT
A only size 120-135
A M
1
OIL EQUAL.
BT
B
6
D
5
8
3
4
MECHANICAL EXPANSION VALVE
(STANDARD)
F
FS
E
SUCTION
LINE
BT
UNIT
CONTROL
EXV
CONTROL
3
4
ELECTRONIC EXPANSION VALVE
(OPTIONAL)
COMPONENTS
1
2
3
4
5
6
7
8
Compressor tandem scroll type
Air cooled condenser
Filter drier
Electronic/mechanical expansion valve
Globe valve
Plate heat exchanger
Desuperheater (optional)
Solenoid valve
SAFETY/CONTROL DEVICES
E
F
G
M
↓
A High pressure switch (40.5 bar)
AT High pressure transducer
B Low pressure switch (1.5 bar)
BT Low pressure transducer
FS Water flow switch
D Air temperature sensor
Outlet water temperature sensor
Inlet water temperature sensor
PED pressure relief valve (45 bar)
Discharge temperature sensor
Pipe connection with Shrader valve
SyScroll 85-135 Air |
11
Refrigerant Flow Diagram - SyScroll 85-135 Air HP
2
12
8
AT only size 120-135
A A M
ON
1
OIL EQUAL.
G
5
D
14
H BT
B
5
G
3
14
13
7
10
S
9
4
14
MECHANICAL EXPANSION VALVE
(STANDARD)
N
14
F
11
FS
E
14
5
BT
B
G
9
EXV
CONTROL
N
UNIT
CONTROL
14
7
10
3
4
14
ELECTRONIC EXPANSION VALVE
(OPTIONAL)
14
COMPONENTS
1
2
3
4
5
Compressor tandem scroll type
Air cooled heat exchanger
Filter drier
Electronic/mechanical expansion valve
Globe valve
Liquid receiver 7
8
9
Four-way valve
Suction accumulator
10 Sight glass
11 Plate heat exchanger
12 Desuperheater (optional)
13 Solenoid valve
14 Check valve
SAFETY/CONTROL DEVICES
A High pressure switch (40.5 bar)
AT High pressure transducer
B Low pressure switch (1.5 bar)
BT Low pressure transducer
FS
D
E
F
G
H
M
S
↓
Water flow switch
Air temperature sensor
Outlet water temperature sensor
Inlet water temperature sensor
PED pressure relief valve (45 bar)
Defrost temperature sensor
Discharge temperature sensor
5/16” valve connection (service only)
Pipe connection with Shrader valve
12
|
SyScroll 85-135 Air
Refrigerant Flow Diagram - SyScroll 85-135 Air RE
2
D
G
3
AT
A only size 120-135
A M
1
OIL EQUAL.
BT B
3
3
COMPONENTS
1
2
3
Compressor tandem scroll type
Air cooled condenser
Globe valve
SAFETY/CONTROL DEVICES
D
G
M
↓
A High pressure switch (40.5 bar)
AT High pressure transducer
B Low pressure switch (1.5 bar)
BT Low pressure transducer
Air temperature sensor
PED pressure relief valve (45 bar)
Discharge temperature sensor
Pipe connection with Shrader valve
Refrigerant Flow Diagram - SyScroll 85-135 Air BC
2
D
G
5
AT
A only size 120-135
A M
1
OIL EQUAL.
7
BT
B
6
5
UNIT
CONTROL
EXV
CONTROL
3
4
F
FS
E
SyScroll 85-135 Air |
13
COMPONENTS
1
2
3
4
5
6
7
Compressor tandem scroll type
Air cooled heat exchanger
Filter drier
Electronic/mechanical expansion valve
Globe valve
Plate heat exchanger
Suction accumulator
SAFETY/CONTROL DEVICES
A High pressure switch (40.5 bar)
AT High pressure transducer
B Low pressure switch (1.5 bar)
BT Low pressure transducer
FS
D
E
F
G
M
↓
Water flow switch
Air temperature sensor
Outlet water temperature sensor
Inlet water temperature sensor
PED pressure relief valve (45 bar)
Discharge temperature sensor
Pipe connection with Shrader valve
14
|
SyScroll 85-135 Air
Operating Limits - SyScroll Air CO - Cooling Mode
Operating limits
SyScroll Air CO
Chilled liquid
Liquid outlet temperature
Water
Water with glycol
*
Temperature spread
Maximum operating pressure
Ambient air
Air entering temperature cooling
External static pressure
-
S
HT-HPF
Standard fans
High pressure fans
Recommended system chilled water volume
2
Minimum capacity step
Power supply voltage
3
°C
°C
°C
Pa
°C
°C
K bar
Pa l
%
V
Min
85
510
50
Max Min
95 105
570
43
Max Min Max
+6 to +18
-10 to +6
3 to 7
6
+10 to +45
-14 to +42
-16 to +47
Min
0
<120
630
50
400 V / 3 Ø / 50 Hz (nominal)
120
720
44
Max Min
135
*
For Liquid outlet temperature <0 °C provide Brine Version.
1
Total unit flow rate and pressure drop are given for std unit. Caution: Minimum flow rates may only be used with brine solutions after reprogramming unit parameters.
2
Table shows minimum water / brine volume of system (about 5 lt/kW).
3
Voltage 400V +/- 10%.
810
50
Max
STD version
50
45
40
35
30
25
20
15
10
Brine Version(*)+
Water+Glycol
Water+
Glycol
Water
5
0
-5
-10
Brine Version (*)+
Water+Glycol+FSC
Water+
Glycol+FSC
Water+FSC
-15
-20
-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18
LWT (°C)
HT version
35
30
25
20
15
10
5
0
55
50
45
40
Brine Version(*)+
Water+Glycol
Water+
Glycol
Water
-5
-10
-15
-20
-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18
LWT (°C)
SLN version
50
45
40
35
30
25
20
15
10
5
0
Brine Version(*)+
Water+Glycol
Water+
Glycol
Water
-5
-10
-15
-20
-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18
LWT (°C)
SyScroll 85-135 Air |
15
Operating Limits - SyScroll Air HP - Cooling Mode
Operating limits
SyScroll Air HP
Chilled liquid
Liquid outlet temperature
Water
Water with glycol
*
Temperature spread
Maximum operating pressure
Ambient air
Air entering temperature cooling
External static pressure
-
S
HT-HPF
Standard fans
High pressure fans
Recommended system chilled water volume
2
Minimum capacity step
Power supply voltage
3
°C
°C
°C
Pa
°C
°C
K bar
Pa l
%
V
Min
85
510
50
Max Min
95 105
570
43
Max Min Max
+6 to +18
-10 to +6
3 to 7
6
+5 to +42
-14 to +40
-18 to +44
Min
0
<120
630
50
400 V / 3 Ø / 50 Hz (nominal)
120
720
44
Max Min
135
*
For Liquid outlet temperature <0 °C provide Brine Version.
1
Total unit flow rate and pressure drop are given for std unit. Caution: Minimum flow rates may only be used with brine solutions after reprogramming unit parameters.
2
Table shows minimum water / brine volume of system (about 5 lt/kW).
3
Voltage 400V +/- 10%.
810
50
Max
STD version
50
45
40
35
30
25
20
15
10
Brine Version(*)+
Water+Glycol
Water+
Glycol
Water
5
0
-5
-10
Brine Version (*)+
Water+Glycol+FSC
Water+
Glycol+FSC
Water+FSC
-15
-20
-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18
LWT (°C)
HT version
35
30
25
20
15
10
5
0
55
50
45
40
Brine Version(*)+
Water+Glycol
Water+
Glycol
Water
-5
-10
-15
-20
-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18
LWT (°C)
SLN version
50
45
40
35
30
25
20
15
10
5
0
Brine Version(*)+
Water+Glycol
Water+
Glycol
Water
-5
-10
-15
-20
-12 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18
LWT (°C)
16
|
SyScroll 85-135 Air
Operating Limits - SyScroll Air HP - Heating Mode
Operating limits
SyScroll Air HP
Heat pump liquid
Liquid outlet temperature
Water
Temperature spread
Maximum operating pressure
-
Air entering Full
Load Operation heating
S
HT
Ambient air
External static pressure
Recommended system chilled water volume
2
Minimum capacity step
Power supply voltage
3
Standard fans
High pressure fans
°C
°C
Pa
Pa
°C
K bar
°C
% l
V
Min
85
510
50
Max Min
95 105
570
43
Max Min Max
+20 to +52
3 to 7
6
-10 to +20
-10 to +20
-12 to +20
0
Min
<120
630
50
400 V / 3 Ø / 50 Hz (nominal)
120
720
44
Max Min
135
1
Total unit flow rate and pressure drop are given for std unit. Caution: Minimum flow rates may only be used with brine solutions after reprogramming unit parameters.
2
Table shows minimum water / brine volume of system (about 3 lt/kW).
3
Voltage 400V +/- 10%.
810
50
Max
10
5
0
-5
25
20
15
-10
HT Version
-15
-20
15 20 25 30 35 40 45 50 55 60
LWT (°C)
SyScroll 85-135 Air |
17
Operating Limits - SyScroll Air RE
Operating limits
SyScroll Air RE
Ambient air
Air entering temperature cooling
External static pressure
Minimum capacity step
Power supply voltage
1
1
Voltage 400V +/- 10%.
-
S
HT-HPF
Standard fans
High pressure fans Pa
%
V
°C
°C
°C
Pa
Min
85
Max
50
Min
95
43
105
Max Min Max
+10 to +45
-10 to +43
-12 to +47
Min
0
<120
50
400 V / 3 Ø / 50 Hz (nominal)
120
44
Max Min
135
Max
50
BLN version
50
45
40
35
30
25
20
15
10
5
0
-5
-10
-15
-20
-17 -12 -7
HT-HPF version
50
45
40
35
30
25
20
15
10
5
0
-5
-10
-15
-20
-17 -12 -7
FSC
-2
SST (°C)
3
-2
SST (°C)
3
8 13
8 13
S version
50
45
40
35
30
25
20
15
10
5
0
-5
-10
-15
-20
-17 -12 -7 -2
SST (°C)
3 8 13
18
|
SyScroll 85-135 Air
Correction Factors
Fouling factors
Fouling factor
(m
2
.°C/kW)
0.044
0.088
0.176
0.352
EVAPORATOR
Cooling capacity factor
1.000
0.987
0.964
0.915
Altitude factors
Altitude (m)
0
600
1200
1800
2400
Power input factor
1.000
0.995
0.985
0.962
Cooling capacity factor
1.000
0.987
0.973
0.958
0.943
Fouling factor
(m
2
.°C/kW)
0.044
0.088
0.176
0.352
CONDENSER
Cooling capacity factor
1.000
0.987
0.955
0.910
Power input factor
1.000
1.023
1.068
1.135
Power input factor
1.000
1.010
1.020
1.029
1.038
System Water Volume
The minimum system water volume is calculated using the minimum compressor running time (1.5 minute for scroll compressor) and the lower capacity step (only one compressor running among the four compressors installed):
V= P x t
(n x 25 x ΔT)
Where V : Water volume (litre)
P n
: Unit total cooling capacity (W)
: Number of compressor steps t : Compressor minimum running time (minute)
ΔT : Evaporator temperature difference (°C)
With t = 1.5 minute, ΔT = 5 °C and n = 2, the minimum system water volume is about V = 6 litres/kW .
SyScroll 85-135 Air |
19
Physical Data - SyScroll Air CO _ - (STD-HT-HPF)
Standard, High Temperature and High Pressure Fan versions
Model
Nominal cooling capacity
Input power
EER
1
EER 75%
EER 50%
EER 25%
1
Energy Efficiency Class
1 kW kW
85
84,2
27,2
3,09
B
3,56
4,15
4,22
95
93,2
31,5
2,96
B
3,58
4,74
4,94
105
104,6
37,7
2,77
C
3,39
4,33
4,45
120
118,6
42,0
2,82
C
3,49
4,30
4,39
ESEER
EER
EER
*
ESEER
**
*
ESEER
**
3,66 4,11 3,81 3,90 3,90
Number of refrigerant circuits 1 1 1 1 1
Total capacity steps
Compressor
% 50-100 43-100 50-100 44-100 50-100
Number / Type
N° of loading stages
Evaporator
Number / Type
Water flow
Pressure drop
Water volume
Antifreeze Heater m
3
/h kPa
W l
3,94
3,18
4,03
2,80
0/100
14,5
26
7
4,35
3,04
4,43
2,73
0/100
16,0
32
7
4,00
2,76
3,96
2,58
2 / Scroll
0/100
1 / Plate
18,0
28
8
130
4,01
2,84
4,03
2,72
0/100
20,4
22
11
4,03
2,80
4,00
2,68
0/100
22,7
19
13
135
132,1
47,6
2,78
C
3,38
4,38
4,50
Air cooled condenser
Number of coils
Total coil face area per coil
Fans
Number of fans
Nominal speed
Total airflow
Total input power
Total input power
*
Total input power
**
External static pressure
Water Connections (Evaporator)
Type
Inlet Diameter / Outlet Diameter
Water Connections (Desuperheater)
Type
Inlet Diameter / Outlet Diameter
Weight m rpm m
3
/h kW kW kW
Pa
2 inch inch
690
34.000
2,4
1,6
3,0
2,4
690
34.000
2,4
1,6
3,0
2
2
900
44.000
3,4
3,0
5,2
0 or 120 Pa
**
Male GAS Threaded
2”1/2 / 2”1/2
Male GAS Threaded
1” / 1”
900
44.000
3,4
3,0
5,2
3,1
900
44.000
3,4
3,0
5,2
Shipping
Operating
Additional weight
HT-HPF versions
Desuperheater versions
Dimensions
Length
Width
Height
Acoustical data
Sound power level
2
Sound pressure level at 10 m
3 kg kg kg kg mm mm mm dB(A) dB(A)
708
715
20
12
84
52
779
786
20
12
3.000
84
52
858
867
20
13
1.100
2.250
88
56
908
919
20
13
88
56
3.500
946
959
20
13
88
56
1
Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.
2 Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744.
3
Sound pressure levels refer to ISO Standard 3744, parallelepiped shape.
*
High Temperature Units (HT) with inverter fans.
**
HPF Units with high static pressure fans.
20
|
SyScroll 85-135 Air
Physical Data - SyScroll Air CO_S - (STD)
Standard version
Model
Nominal cooling capacity
Input power
EER
1
Water flow
1
Energy Efficiency Class
EER 75%
EER 50%
EER 25%
Pressure drop
Water volume
Antifreeze Heater
1 kW kW
95
89,3
32,8
2,72
C
3,56
4,72
4,90
105
101,4
38,6
2,63
D
3,36
4,32
4,43
120
113,5
43,0
2,64
D
3,55
4,29
4,45
ESEER 3,91 4,32 3,98 4,03 4,00
Number of refrigerant circuits 1 1 1 1 1
Total capacity steps
Compressor
% 50-100 43-100 50-100 44-100 50-100
Number / Type
N° of loading stages
Evaporator
Number / Type m
3
/h kPa
W l
85
81,1
28,0
2,90
C
3,52
4,13
4,19
0/100
13,9
23
7
0/100
15,4
28
7
2 / Scroll
0/100
1 / Plate
17,4
25
8
130
0/100
19,5
20
11
0/100
21,7
17
13
135
126,0
49,6
2,54
D
3,35
4,37
4,46
Air cooled condenser
Number of coils
Total coil face area per coil
Fans
Number of fans
Nominal speed
Total airflow
Total input power rpm m
3 m
2
/h kW
550
25.000
1,8
2,4
550
25.000
1,8
2
2
690
34.000
2,4
690
36.000
2,4
3,1
690
36.000
2,4
Water Connections (Evaporator)
Type
Inlet Diameter / Outlet Diameter
Water Connections (Desuperheater)
Type
Inlet Diameter / Outlet Diameter
Weight
Shipping
Operating
Additional weight
HT-HPF versions
Desuperheater versions
Dimensions
Length
Width
Height
Acoustical data
Sound power level
2
Sound pressure level at 10 m
3 inch inch kg kg kg kg mm mm mm dB(A) dB(A)
708
715
20
12
82
50
779
786
20
12
3.000
82
50
Male GAS Threaded
2”1/2 / 2”1/2
Male GAS Threaded
1” / 1”
858
867
20
13
1.100
2.250
85
53
908
919
20
13
85
53
3.500
946
959
20
13
85
53
1
Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.
2
Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744.
3
Sound pressure levels refer to ISO Standard 3744, parallelepiped shape.
SyScroll 85-135 Air |
21
Physical Data - SyScroll Air HP _ - (STD-HT-HPF)
Standard, High Temperature and High Pressure Fan versions
Model
Nominal cooling capacity
Input power
EER
1
1
Energy Efficiency Class
EER 75%
EER 50%
EER 25%
1 kW kW
85
79,0
27,6
2,86
C
3,21
4,43
3,81
95
87,0
32,0
2,72
C
3,48
4,60
4,79
105
98,0
39,0
2,51
D
3,18
4,06
4,17
120
113,8
42,0
2,71
C
3,46
4,27
4,36
135
125,0
47,0
2,66
D
3,36
4,35
4,48
ESEER
EER
*
/ EER
**
ESEER
*
/ ESEER
**
3,84
2,93 / 2,59
4,02 / 3,49
85,0
4,22
2,77 / 2,48
4,38 / 3,93
96,0
3,75
2,51 / 2,29
3,89 / 3,62
107,0
3,98
2,74 / 2,45
4,17 / 3,85
120,0
4,00
2,68 / 2,40
4,18 / 3,89
132,6 Nominal heating capacity
Input power
COP
2
2
Energy Efficiency Class
2 kW kW 27,1
3,14
B
3,23 / 2,86
30,8
3,12
B
3,21 / 2,88
38,0
2,82
C
2,85 / 2,70
42,5
2,82
C
2,58 / 2,69
47,2
2,81
C
2,83 / 2,67 COP
*
/ COP
**
Number of refrigerant circuits 1 1 1 1 1
Total capacity steps % 50-100 43-100 50-100 44-100 50-100
Compressor
Number / Type
N° of loading stages
Evaporator
Number / Type
Water flow cooling
1
Water pressure drop cooling
1
Water flow heat pump
2
Water pressure drop heat pump
2 m
3
/h kPa m
3
/h kPa
W l
0/100
13,6
24
14,6
28
7
0/100
15,0
29
16,5
33
7
2 / Scroll
0/100
1 / Plate
16,9
25
18,4
30
8
130
0/100
19,6
21
20,6
22
11
0/100
21,5
17
22,8
18
13 Water volume
Antifreeze Heater
Air cooled condenser
Number of coils
Total coil face area per coil
Fans
Number of fans
Nominal speed
Total airflow
Total input power
Total input power
*
/ Total input power
**
External static pressure
Water Connections (Evaporator)
Type / Inlet Diameter / Outlet Diameter
Water Connections (Desuperheater) m rpm m
3
/h kW kW
Pa
2 inch
690
34.700
2,4
1,6 / 3,0
2,4
690
34.700
2,4
1,6 / 3,0
2
2
900
42.000
3,4
3,0 / 5,2
0 or 120 Pa
**
900
43.200
Male GAS Threaded / 2”1/2 / 2”1/2
3,4
3,0 / 5,2
3,1
900
43.200
3,4
3,0 / 5,2
Type / Inlet Diameter / Outlet Diameter
Weight
Shipping
Operating
Additional weight
HT-HPF versions
Desuperheater versions
Dimensions
Length
Width
Height
Acoustical data
Sound power level
2
Sound pressure level at 10 m
3 inch kg kg kg kg mm mm mm dB(A) dB(A)
839
860
20
12
84
52
906
932
20
12
84
52
Male GAS Threaded / 2”1/2 / 2”1/2
3.000
1.043
1.064
20
13
1.100
2.250
88
56
1.159
1.170
20
13
88
56
3.500
1.208
1.214
20
13
88
56
1
Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.
2
Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744.
3
Sound pressure levels refer to ISO Standard 3744, parallelepiped shape.
* High Temperature Units (HT) with inverter fans.
**
HPF Units with high static pressure fans.
22
|
SyScroll 85-135 Air
Physical Data - SyScroll Air HP_S (STD)
Standard version
Model
Nominal cooling capacity
Input power
EER
1
1
Energy Efficiency Class
EER 75%
EER 50%
EER 25%
1 m
3 kW kW
85
76,0
28,3
2,68
D
3,37
3,94
4,01
95
83,3
33,3
2,50
E
3,39
4,47
4,66
105
95,0
40,0
2,37
E
3,13
3,98
4,11
2
690
34.700
2,4
120
111,4
42,6
2,62
D
3,26
4,01
4,09
ESEER
Nominal heating capacity
Input power
COP
2
2
2
Energy Efficiency Class B B C C C
Number of refrigerant circuits 1 1 1 1 1
Total capacity steps
Compressor
% 50-100 43-100 50-100 44-100 50-100
Number / Type
N° of loading stages
Evaporator
Number / Type
Water flow cooling
Water volume
Antifreeze Heater
1
Water pressure drop cooling
Water flow heat pump
Air cooled condenser
Number of coils
2
1
Water pressure drop heat pump
2 m m kW kW
3
3
/h kPa
/h kPa
W l
3,73
82,6
26,4
3,13
0/100
13,1
22
14,2
26
7
4,10
93,1
30,1
3,09
0/100
14,3
26
16,0
32
7
3,68
105,1
37,0
2,84
2 / Scroll
0/100
1 / Plate
16,3
24
18,1
29
8
130
2
3,74
117,8
41,5
2,84
0/100
19,2
20
20,3
21
11
3,88
129,4
46,2
2,80
0/100
20,9
17
22,3
17
13
Total coil face area per coil
Fans
Number of fans
Nominal speed
Total airflow
Total input power
Water Connections (Evaporator)
Type m
2 rpm
/h kW inch
550
26.200
1,8
2,4
550
26.200
1,8
Male GAS Threaded
2”1/2 / 2”1/2
690
35.800
2,4
3,1
135
121,8
48,0
2,54
D
3,26
4,22
4,34
690
35.800
2,4
Inlet Diameter / Outlet Diameter
Water Connections (Desuperheater)
Type
Inlet Diameter / Outlet Diameter
Weight
Shipping
Operating
Additional weight inch kg kg
853
860
926
932
Male GAS Threaded
1” / 1”
1.056
1.064
1.160
1.170
1.201
1.214
HT-HPF versions
Desuperheater versions
Dimensions
Length
Width
Height
Acoustical data
Sound power level
3
Sound pressure level at 10 m
4 kg kg mm mm mm dB(A) dB(A)
20
12
82
50
20
12
3.000
82
50
20
13
1.100
2.250
85
53
20
13
85
53
3.500
20
13
85
53
1
Data refers to 7°C leaving chilled water temperature and 35°C condenser air temperature, according EN14511 standard.
2
Data refers to 45°C leaving warm water temperature and 7°C ambient coil air temperature with 87% R.H., according EN14511 standard.
3
Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744.
4
Sound pressure levels refer to ISO Standard 3744, parallelepiped shape.
SyScroll 85-135 Air |
23
Physical Data - SyScroll Air RE
Remote Evaporator
Model
SyScroll Air RE_ - (STD)
Nominal cooling capacity
1
Input power
2
Refrigerant In connections
Refrigerant Out connections
SyScroll Air RE_ - (S)
Nominal cooling capacity
1
Input power
2
Refrigerant In connections
Refrigerant Out connections
Weight
Shipping
Additional weight
HT/HPF versions
Dimensions
Length
Width
Height kW kW inch inch kW kW inch inch kg kg mm mm mm
85
94,3
24,8
1 5/8”
7/8”
90,2
26,3
1 5/8”
7/8”
625
20
95
105,0
29,2
1 5/8”
7/8”
99,8
31,3
1 5/8”
7/8”
697
20
3.000
105
116,4
34,6
2 1/8”
1 1/8”
112,4
36,7
2 1/8”
1 1/8”
765
20
1.100
2.250
120
130,5
39,8
2 1/8”
1 1/8”
125,2
42,5
2 1/8”
1 1/8”
817
20
3.500
135
142,4
45,1
2 1/8”
1 1/8”
135,7
48,4
2 1/8”
1 1/8”
840
20
1
Data refers to 7°C evaporating temperature and 35°C condenser air temperature.
2 Input power (only compressors).
N.B. For additional technical data regarding compressors, fan motors and noise, please refer to correspondant CO unit.
24
|
SyScroll 85-135 Air
Electrical Data
Compressors @ 400 V/3 Ph/50 Hz
Model
85
95
105
120
135
Power input nominal Cond.
compressor kW
12,3
12,3
12,3
15,9
17,4
17,4
17,4
21,1
21,1
21,1
Nom. Cond.
current compressor
A
23,3
23,3
23,3
27,8
28,2
28,2
28,2
33,6
33,6
33,6
Power input max. Cond.
compressor kW
17,0
17,0
17,0
22,6
26,0
26,0
26,0
32,0
32,0
32,0
Max. running current compressor FLA
Starting current compressor LRA
40
44
44
44
A
34
34
34
53
53
53
225
210
210
210
A
174
174
174
210
210
210
Nominal power factor Unit fuse size Cable section kW
0,76
0,76
0,76
0,82
0,89
0,89
0,89
0,91
0,91
0,91
A
100
100
125
125
160 mm
50
50
70
70
70
2
Fans @ 400 V/3 Ph/50 Hz
Units _
Size
85
95
105
120
135
Number
2
2
2
2
2
Units S
Units HT/HPF
Size
85
95
105
120
135
Size
85
95
105
120
135
Number
2
2
2
2
2
Number
2
2
2
2
2
Nominal power per fan (kW) Δ
1,2
1,2
2,1
2,1
2,1
Max. running current per fan (A) Δ
2,2
2,2
4,1
4,1
4,1
Total fan power
(kW) Δ
2,3
2,3
4,2
4,2
4,2
Total max. fan current
(A) Δ
4,4
4,4
8,2
8,2
8,2
Nominal power per fan (kW) Δ
1,2
1,2
1,2
1,2
1,2
Max. running current per fan (A) Δ
2,2
2,2
2,2
2,2
2,2
Total fan power
(kW) Δ
2,3
2,3
2,3
2,3
2,3
Total max. fan current
(A) Δ
4,4
4,4
4,4
4,4
4,4
Nominal power per fan (kW) Δ
3,1
3,1
3,1
3,1
3,1
Max. running current per fan (A) Δ
4,8
4,8
4,8
4,8
4,8
Total fan power
(kW) Δ
6,2
6,2
6,2
6,2
6,2
Total max. fan current
(A) Δ
9,6
9,6
9,6
9,6
9,6
SyScroll 85-135 Air |
25
Units @ 400 V/3 Ph/50 Hz
- Version
Current input (A)
Power input (kW)
Nominal
Maximum
Nominal
Maximum
Max Start-up current
S Version
Current input (A)
Power input (kW)
Max Start-up current
Nominal
Maximum
Nominal
Maximum
HT/HPF Version
Current input (A)
Power input (kW)
Max Start-up current
Nominal
Maximum
Nominal
Maximum
Pump data
Model
85
95
105
120
135 kW kW
A
A
A
A
A kW kW
A kW kW
A
A
A
85
27
36
51
72
212
85
27
36
51
72
212
85
31
40
56
78
218
Nominal power kW
1,99
1,99
1,99
2,45
2,45
Low Pressure
Max. running current
A
3,41
3,41
3,41
4,53
4,53
95
30
42
55
78
263
95
30
42
55
78
263
95
34
46
61
84
269
105
39
56
65
96
262
105
37
54
61
92
258
105
41
58
66
98
264
120
43
62
70
105
262
120
41
60
66
101
258
120
45
64
71
107
264
Nominal power kW
3,26
3,26
3,26
3,00
3,00
High Pressure
Max. running current
A
5,86
5,86
5,86
6,14
6,14
135
46
68
75
114
271
135
45
66
72
110
267
135
48
70
77
116
273
26
|
SyScroll 85-135 Air
Electrical Data
Units with std pressure pump @ 400 V/3 Ph/50 Hz
- Version
Current input (A)
Power input (kW)
Max Start-up current
Nominal
Maximum
Nominal
Maximum
A
A kW kW
A
85
29
38
54
76
216
S Version
Current input (A)
Power input (kW)
Max Start-up current
Nominal
Maximum
Nominal
Maximum
HT/HPF Version
Current input (A)
Power input (kW)
Max Start-up current
Nominal
Maximum
Nominal
Maximum
A
A kW kW
A
A
A kW kW
A
85
33
42
60
81
221
85
29
38
54
76
216
Units with high pressure pump @ 400 V/3 Ph/50 Hz
- Version
Current input (A)
Power input (kW)
Max Start-up current
Nominal
Maximum
Nominal
Maximum kW kW
A
A
A
85
30
39
57
78
218
S Version
Current input (A)
Power input (kW)
Max Start-up current
Nominal
Maximum
Nominal
Maximum kW kW
A
A
A
85
30
39
57
78
218
HT/HPF Version
Current input (A)
Power input (kW)
Max Start-up current
Nominal
Maximum
Nominal
Maximum
A
A kW kW
A
85
34
43
62
83
223
95
36
48
64
87
272
95
32
44
59
82
267
95
32
44
59
82
267
120
47
67
76
111
268
120
43
63
71
106
263
120
45
65
75
110
267
105
43
60
69
101
267
105
39
56
64
96
262
105
41
58
68
100
266
135
51
73
81
120
277
135
47
69
76
115
272
135
49
71
80
119
276
95
34
45
61
84
269
95
34
45
61
84
269
95
38
49
67
89
274
120
46
65
76
111
268
120
44
63
72
108
265
120
48
67
78
113
270
105
42
59
70
102
268
105
40
58
67
98
264
105
44
61
72
103
269
135
49
71
82
120
277
135
48
69
78
117
274
135
51
73
83
122
279
SyScroll 85-135 Air |
27
Fan Data - HPF Version
SyScroll 85-135 Air HPF
Model
85-105
120-135
Fan Static Pressure (Pa)
120
40
60
80
100
40
60
80
100
120
Sound data - SyScroll Air
Model
- Version
85
95
105
120
135
S Version
85
95
105
120
135
HT-HPF Version
**
85
95
105
120
135
94
94
94
94
94
81
81
84
84
84
125
83
83
87
87
87
95
95
95
95
95
82
82
85
85
85
250
84
84
88
88
88
Fan RPM
870
910
950
990
1.030
1.000
1.030
1.070
1.100
1.130
Parameter in Service Level:
Max Speed (Vdc)
9,3
9,1
9,3
9,6
9,8
8,1
8,4
8,7
9,0
10,0
93
93
93
93
93
80
80
83
83
83
500
82
82
86
86
86
77
77
80
80
80
79
79
83
83
83
Frequency (Hz)
1000 2000
74
74
78
78
78
90
90
90
90
90
85
85
85
85
85
72
72
75
75
75
73
73
73
73
73
60
60
63
63
63
8000
62
62
66
66
66
79
79
79
79
79
66
66
69
69
69
4000
68
68
72
72
72
Sound
Power dB(A)
82
82
85
85
85
84
84
88
88
88
95
95
95
95
95
Sound
Pressure dB(A)
*
50
50
53
53
53
52
52
56
56
56
63
63
63
63
63
*
Sound pressure level at 10 m. Values refers to ISO Standard 3744 with parallepiped shape.
**
Sound data valid in max air flow rate condition.
28
|
SyScroll 85-135 Air
Cooling Capacities - SyScroll Air CO _ - (STD-HT-HPF)
Model
85
95
105
120
135
LWT
°C
Cool
98,6
104,9
111,4
118,2
125,3
132,6
144,0
110,9 kW
88,5
94,1
100,0
106,0
112,4
118,9
129,2
117,8
124,9
132,2
139,7
147,5
159,3
124,6
132,5
140,6
148,9
157,6
166,6
180,4
140,9
149,8
159,0
168,5
178,5
188,7
204,7
5
7
15
18
11
13
7
9
13
15
18
5
9
11
5
7
18
5
7
9
11
13
15
7
9
18
5
9
11
13
15
11
13
15
18
25
Input
Power
*
22,9
23,4
23,8
24,3
24,8
25,3
26,1
26,6 kW
19,9
20,2
20,6
20,9
21,2
21,5
22,0
26,9
27,2
27,6
27,9
28,2
28,7
30,8
31,2
31,6
32,1
32,6
33,1
34,0
34,4
35,0
35,6
36,2
37,0
37,7
38,9
Cool
93,5
99,5
105,7
112,2
118,9
125,8
136,6
105,3 kW
84,2
89,6
95,1
100,9
106,9
113,2
122,9
111,7
118,3
125,2
132,2
139,4
150,4
117,9
125,3
132,9
140,8
148,9
157,3
170,3
132,9
141,3
150,0
159,0
168,4
178,0
193,1
30
Condensing Air Temperature °C
32
Input
Power
*
Cool
25,2
25,6
26,1
26,7
27,2
27,8
28,7
29,9 kW
21,9
22,3
22,7
23,1
23,5
23,9
24,5
30,2
30,6
30,9
31,2
31,6
32,1
34,5
35,0
35,5
36,0
36,5
37,1
37,9
38,6
39,2
39,8
40,5
41,3
42,1
43,3
91,4
97,3
103,4
109,7
116,2
123,0
133,6
102,9 kW
82,4
87,7
93,1
98,8
104,6
110,7
120,2
109,2
115,7
122,3
129,1
136,1
146,7
115,1
122,3
129,7
137,4
145,3
153,5
166,1
129,6
137,8
146,3
155,1
164,2
173,6
188,3
Input
Power
*
26,1
26,6
27,1
27,7
28,2
28,8
29,7
31,3 kW
22,8
23,2
23,6
24,0
24,4
24,8
25,5
31,7
32,0
32,4
32,7
33,1
33,6
36,2
36,7
37,1
37,7
38,2
38,8
39,7
40,4
41,0
41,7
42,4
43,2
44,0
45,3
35
Input
Power
*
27,7
28,2
28,7
29,3
29,9
30,5
31,4
33,6 kW
24,1
24,5
24,9
25,4
25,8
26,3
27,0
33,9
34,3
34,7
35,1
35,4
36,0
38,8
39,3
39,8
40,3
40,9
41,5
42,4
43,3
44,0
44,7
45,4
46,2
47,0
48,3
Cool
88,1
93,8
99,7
105,8
112,2
118,7
128,9
99,2 kW
79,6
84,7
89,9
95,4
101,1
107,0
116,1
105,3
111,5
117,9
124,4
131,0
141,3
110,8
117,7
124,8
132,2
139,8
147,6
159,7
124,5
132,3
140,5
149,0
157,7
166,8
180,9
*
Only Compressors.
SyScroll 85-135 Air |
29
Model
LWT
°C
85
95
105
120
135
5
7
15
18
11
13
7
9
13
15
18
5
9
11
5
7
18
5
7
9
11
13
15
7
9
18
5
9
11
13
15
11
13
15
18
38
Input
Power
*
29,4
29,9
30,4
31,0
31,6
32,2
33,2
36,0 kW
25,5
25,9
26,3
26,8
27,3
27,7
28,5
36,4
36,8
37,2
37,6
38,0
38,6
41,6
42,2
42,7
43,2
43,8
44,4
45,4
46,5
47,2
47,8
48,6
49,4
50,2
51,5
Cool
84,8
90,3
96,0
101,9
108,0
114,3
124,1
95,3 kW
76,7
81,5
86,6
91,9
97,4
103,0
111,9
101,1
107,1
113,3
119,5
125,9
135,7
106,2
112,8
119,7
126,8
134,1
141,6
153,2
119,2
126,7
134,5
142,6
151,0
159,7
173,2
Cool
82,5
87,8
93,4
99,1
105,1
111,3
120,8
92,5 kW
74,6
79,4
84,3
89,5
94,8
100,3
108,9
98,2
104,1
110,1
116,2
122,4
131,9
103,0
109,5
116,1
123,1
130,2
137,5
148,8
115,4
122,8
130,4
138,2
146,4
154,8
168,0
40
Condensing Air Temperature °C
42
Input
Power
*
Cool
30,6
31,1
31,7
32,2
32,8
33,5
34,5
37,7 kW
26,5
26,9
27,3
27,8
28,3
28,8
29,5
38,2
38,6
39,0
39,4
39,8
40,4
43,7
44,2
44,7
45,3
45,9
46,5
47,4
48,8
49,4
50,1
50,8
51,6
52,5
53,8
80,2
85,4
90,8
96,3
102,2
108,2
117,5
89,6 kW
72,5
77,1
82,0
87,0
92,2
97,6
105,9
95,2
101,0
106,8
112,7
118,8
128,0
99,7
106,0
112,5
119,2
126,1
133,2
144,2
111,6
118,7
126,1
133,7
141,6
149,8
Input
Power
*
31,9
32,4
32,9
33,5
34,1
34,8
35,8
39,5 kW
27,5
27,9
28,4
28,8
29,3
29,8
30,6
40,0
40,4
40,9
41,3
41,7
42,3
45,8
46,3
46,9
47,4
48,0
48,6
49,6
51,1
51,8
52,5
53,2
54,0
54,9
45
Input
Power
*
33,9
34,4
35,0
35,6
36,2
36,9
37,9
42,4 kW
29,2
29,6
30,0
30,5
31,0
31,5
32,2
42,9
43,4
43,8
44,3
44,8
45,4
49,1
49,7
50,3
50,8
51,5
52,1
53,1
54,9
55,6
56,3
57,0
57,8
58,6
Cool
76,5
81,5
86,7
92,1
97,6
103,4
112,3
85,0 kW
69,2
73,6
78,3
83,1
88,1
93,2
101,3
90,5
96,0
101,6
107,4
113,2
122,0
94,4
100,5
106,8
113,2
119,9
126,7
137,1
105,6
112,4
119,4
126,7
134,3
142,1
*
Only Compressors.
HT Version
30
|
SyScroll 85-135 Air
Cooling Capacities - SyScroll Air CO S - (STD)
Model
85
95
105
120
135
LWT
°C
Cool
95,2
101,1
107,2
113,5
120,0
126,7
137,1
108,3 kW
86,0
91,3
96,8
102,5
108,4
114,5
124,0
114,9
121,6
128,5
135,5
142,7
153,7
121,7
129,2
136,9
144,8
153,0
161,4
174,3
134,9
143,2
151,7
160,5
169,6
179,0
193,4
5
7
15
18
11
13
7
9
13
15
18
5
9
11
5
7
18
5
7
9
11
13
15
7
9
18
5
9
11
13
15
11
13
15
18
25
Input
Power
*
24,4
24,9
25,5
26,1
26,8
27,4
28,5
28,1 kW
21,1
21,5
22,0
22,4
22,9
23,3
24,1
28,5
28,9
29,3
29,7
30,1
30,8
32,4
32,9
33,5
34,0
34,7
35,3
36,3
36,7
37,5
38,2
39,1
39,9
40,9
42,4
Cool
90,0
95,6
101,4
107,4
113,5
119,9
129,7
102,6 kW
81,6
86,6
91,9
97,2
102,8
108,6
117,5
108,7
115,0
121,4
128,0
134,6
144,8
114,9
121,9
129,1
136,5
144,2
152,0
164,1
126,9
134,7
142,7
150,9
159,5
168,2
181,8
30
Condensing Air Temperature °C
32
Input
Power
*
Cool
26,8
27,4
28,0
28,6
29,3
30,0
31,2
31,5 kW
23,2
23,6
24,1
24,6
25,1
25,7
26,5
31,9
32,4
32,8
33,3
33,7
34,4
36,3
36,9
37,5
38,1
38,8
39,4
40,5
41,2
41,9
42,8
43,6
44,5
45,5
47,1
87,9
93,4
99,0
104,8
110,9
117,0
126,6
100,1 kW
79,7
84,7
89,7
95,0
100,5
106,1
114,8
106,1
112,2
118,5
124,9
131,3
141,2
112,0
118,8
125,9
133,1
140,5
148,2
159,9
123,6
131,1
138,9
146,9
155,2
163,8
177,0
Input
Power
*
27,8
28,4
29,0
29,7
30,4
31,1
32,3
33,0 kW
24,0
24,5
25,0
25,5
26,1
26,6
27,4
33,4
33,9
34,4
34,8
35,3
36,0
38,0
38,6
39,2
39,9
40,5
41,2
42,3
43,1
43,9
44,7
45,6
46,5
47,5
49,1
35
Input
Power
*
29,5
30,1
30,8
31,4
32,1
32,9
34,1
35,4 kW
25,4
25,9
26,4
26,9
27,5
28,1
28,9
35,8
36,3
36,8
37,3
37,8
38,5
40,8
41,4
42,0
42,7
43,4
44,1
45,2
46,2
47,0
47,9
48,8
49,7
50,7
52,4
Cool
84,6
89,9
95,3
100,9
106,7
112,7
121,8
96,3 kW
76,8
81,6
86,5
91,6
96,8
102,2
110,6
102,1
107,9
114,0
120,1
126,3
135,7
107,6
114,1
120,9
127,8
134,9
142,3
153,5
118,4
125,6
133,0
140,7
148,7
156,9
169,5
*
Only Compressors.
SyScroll 85-135 Air |
31
Model
LWT
°C
85
95
105
120
135
5
7
15
18
11
13
7
9
13
15
18
5
9
11
5
7
18
5
7
9
11
13
15
7
9
18
5
9
11
13
15
11
13
15
18
38
Input
Power
*
31,3
31,9
32,6
33,3
34,0
34,8
36,0
37,9 kW
26,9
27,4
27,9
28,4
29,0
29,6
30,5
38,4
38,9
39,5
40,0
40,5
41,3
43,7
44,4
45,0
45,7
46,4
47,1
48,3
49,6
50,4
51,2
52,1
53,1
54,1
Cool
81,2
86,2
91,5
96,9
102,4
108,1
117,0
92,2 kW
73,8
78,4
83,1
88,0
93,0
98,2
106,2
97,8
103,5
109,2
115,1
121,1
130,1
102,8
109,1
115,6
122,3
129,1
136,2
146,9
112,9
119,8
126,9
134,3
141,9
149,7
Condensing Air Temperature °C
40
Cool
Input
Power
*
78,8
83,7
88,8
94,1
99,5
105,0
113,6
89,3 kW
71,7
76,1
80,7
85,5
90,4
95,4
103,2
94,8
100,3
106,0
111,7
117,5
126,2
99,5
105,7
112,0
118,5
125,1
131,9
142,4
109,1
115,8
122,7
129,9
137,2
144,8
32,6
33,2
33,9
34,6
35,3
36,1
37,3
39,7 kW
27,9
28,4
28,9
29,5
30,0
30,6
31,6
40,2
40,8
41,3
41,9
42,4
43,2
45,8
46,5
47,1
47,8
48,6
49,3
50,5
52,0
52,8
53,6
54,5
55,5
56,5
76,4
86,3
96,1
105,2
Cool kW
69,5
42
Input
Power
* kW
29,0
34,0
41,6
48,0
54,5
*
Only Compressors.
32
|
SyScroll 85-135 Air
Cooling Capacities - SyScroll Air HP _ - (STD-HT-HPF)
Model
85
95
105
120
135
LWT
°C
Cool
92,4
98,2
104,2
110,4
116,9
123,5
133,8
104,1 kW
83,3
88,5
93,9
99,5
105,3
111,3
120,7
110,4
116,9
123,5
130,3
137,3
147,9
121,5
129,1
136,9
145,0
153,4
162,0
175,3
133,4
141,7
150,3
159,2
168,5
178,0
192,7
5
7
15
18
11
13
7
9
13
15
18
5
9
11
5
7
18
5
7
9
11
13
15
7
9
18
5
9
11
13
15
11
13
15
18
25
Input
Power
*
23,7
24,2
24,7
25,3
25,8
26,4
27,4
27,7 kW
20,3
20,7
21,1
21,5
21,9
22,3
22,9
28,1
28,5
28,9
29,3
29,7
30,3
30,1
30,6
31,1
31,6
32,1
32,6
33,5
33,8
34,4
35,1
35,8
36,5
37,3
38,6
Cool
87,5
93,0
98,7
104,6
110,7
116,9
126,7
98,6 kW
79,1
84,1
89,2
94,5
100,0
105,7
114,5
104,5
110,5
116,7
123,1
129,5
139,4
115,0
122,1
129,4
137,0
144,9
152,9
165,4
125,8
133,6
141,7
150,1
158,8
167,7
181,6
30
Condensing Air Temperature °C
32
Input
Power
*
Cool
26,0
26,5
27,1
27,7
28,3
29,0
30,0
31,1 kW
22,3
22,7
23,2
23,6
24,1
24,6
25,3
31,5
31,9
32,4
32,8
33,2
33,9
33,8
34,3
34,8
35,3
35,9
36,5
37,4
37,9
38,5
39,2
40,0
40,8
41,6
43,0
85,4
90,8
96,4
102,1
108,1
114,2
123,8
96,2 kW
77,4
82,2
87,2
92,4
97,7
103,3
111,9
102,0
107,9
113,9
120,1
126,4
136,0
112,2
119,2
126,3
133,7
141,4
149,2
161,3
122,7
130,3
138,2
146,3
154,8
163,5
177,0
Input
Power
*
27,0
27,6
28,1
28,7
29,4
30,0
31,1
32,6 kW
23,2
23,6
24,1
24,5
25,0
25,5
26,3
33,0
33,4
33,9
34,3
34,8
35,5
35,4
35,9
36,4
37,0
37,6
38,2
39,1
39,7
40,3
41,0
41,8
42,6
43,5
44,8
35
Input
Power
*
28,6
29,2
29,8
30,4
31,1
31,8
32,8
34,9 kW
24,5
24,9
25,4
25,9
26,4
26,9
27,7
35,4
35,8
36,3
36,8
37,3
38,0
38,0
38,5
39,1
39,6
40,2
40,8
41,8
42,5
43,2
43,9
44,7
45,5
46,4
47,8
Cool
82,3
87,5
92,8
98,4
104,1
110,1
119,2
92,6 kW
74,6
79,2
84,1
89,1
94,3
99,6
107,9
98,1
103,8
109,6
115,5
121,5
130,7
107,9
114,6
121,5
128,6
135,9
143,5
155,1
117,7
125,0
132,6
140,4
148,5
156,9
169,9
*
Only Compressors.
SyScroll 85-135 Air |
33
Model
LWT
°C
85
95
105
120
135
5
7
15
18
11
13
7
9
13
15
18
5
9
11
5
7
18
5
7
9
11
13
15
7
9
18
5
9
11
13
15
11
13
15
18
38
Input
Power
*
30,4
31,0
31,6
32,2
32,9
33,6
34,7
37,4 kW
25,9
26,4
26,9
27,4
27,9
28,4
29,2
37,9
38,4
38,9
39,4
39,9
40,7
40,8
41,3
41,9
42,4
43,1
43,7
44,7
45,6
46,3
47,1
47,8
48,7
49,6
51,0
Cool
79,0
84,0
89,2
94,5
100,1
105,8
114,6
88,7 kW
71,7
76,2
80,8
85,6
90,6
95,8
103,8
94,0
99,5
105,1
110,8
116,5
125,3
103,4
109,9
116,5
123,3
130,3
137,6
148,7
112,6
119,6
126,8
134,3
142,1
150,1
162,5
Condensing Air Temperature °C
40
Cool
Input
Power
*
76,8
81,6
86,7
91,9
97,3
102,8
111,4
85,9 kW
69,7
74,1
78,6
83,3
88,1
93,1
100,9
91,2
96,5
101,9
107,5
113,1
121,6
100,3
106,6
113,0
119,7
126,5
133,5
144,3
109,0
115,8
122,8
130,1
137,6
145,4
157,5
31,6
32,2
32,8
33,5
34,2
34,9
36,0
39,2 kW
26,9
27,4
27,9
28,4
28,9
29,4
30,3
39,7
40,3
40,8
41,3
41,8
42,6
42,7
43,3
43,9
44,5
45,1
45,7
46,7
47,8
48,5
49,3
50,1
50,9
51,8
53,2
74,5
79,2
84,1
83,0
88,2
93,4
97,0
103,1
109,4
105,3
111,8
118,7
Cool kW
67,6
71,9
76,3
42
Input
Power
* kW
28,0
28,4
28,9
33,0
33,5
34,2
41,1
41,6
42,2
44,8
45,4
45,9
50,2
50,9
51,6
*
Only Compressors.
HT Version
34
|
SyScroll 85-135 Air
Heating Capacities - SyScroll Air HP _ - (STD-HT-HPF)
Model
85
95
105
120
135
LWT
°C
40
45
50
30
45
50
30
35
50
30
35
40
30
35
40
45
30
35
40
45
35
40
45
50
50
Heat kW
61,5
61,2
61,0
69,1
68,9
68,9
77,4
77,7
77,6
86,0
86,4
86,8
94,8
95,3
96,2
-7
Input
Power
* kW
17,2
19,0
21,1
19,8
21,9
24,4
24,2
27,1
30,4
27,1
30,5
34,3
30,2
34,1
38,6
Heat kW
64,8
64,4
64,1
63,8
81,2
81,5
81,5
81,1
90,2
90,7
91,0
91,2
72,8
72,5
72,3
99,2
99,8
100,6
-5
Ambient Air Temperature °C
-3
Input
Power
* kW
17,3
19,1
21,2
23,7
Heat kW
68,3
67,8
67,2
66,9
Input
Power
* kW
17,5
19,3
21,3
23,8
20,0
22,0
24,4
24,2
27,2
30,4
34,1
27,1
30,5
34,3
38,7
30,2
34,1
38,6
76,7
76,3
76,0
75,8
85,2
85,5
85,6
85,1
94,8
95,1
95,4
95,6
104,6
104,7
105,3
106,2
20,1
22,1
24,5
27,3
24,2
27,2
30,5
34,1
27,1
30,5
34,4
38,7
30,2
34,1
38,6
43,7
0
Input
Power
*
24,7
27,4
30,6
24,2
27,2
30,5
34,2
38,3 kW
17,7
19,5
21,5
23,9
26,6
20,3
22,3
27,1
30,5
34,4
38,7
43,6
30,3
34,1
38,5
43,6
Heat
81,8
81,4
81,3
91,4
91,7
91,8
91,5
90,8 kW
73,8
73,2
72,5
72,0
71,5
82,8
82,2
101,9
102,0
102,2
102,3
102,1
111,9
112,1
112,5
113,1
*
Only Compressors.
SyScroll 85-135 Air |
35
Model
LWT
°C
85
95
105
120
135
40
45
50
30
45
50
30
35
50
30
35
40
30
35
40
45
30
35
40
45
35
40
45
50
50
5
Input
Power
*
25,0
27,7
30,8
24,2
27,2
30,6
34,3
38,5 kW
18,0
19,8
21,8
24,1
26,7
20,6
22,6
27,2
30,6
34,4
38,7
43,6
30,4
34,2
38,5
43,5
49,2
Heat
91,9
91,3
90,8
102,5
102,6
102,5
102,2
101,6 kW
83,3
82,5
81,7
80,8
79,8
93,5
92,7
114,4
114,2
114,0
113,8
113,5
126,4
125,5
125,4
125,5
125,7
Heat
96,7
95,8
95,0
108,1
108,0
107,5
107,0
106,3 kW
87,8
86,9
85,9
84,8
83,7
99,0
98,0
120,8
120,5
120,0
119,2
118,6
132,7
132,2
132,0
131,8
131,2
7
Ambient Air Temperature °C
10
Input
Power
*
25,1
27,8
30,9
24,2
27,2
30,6
34,3
38,5 kW
18,1
20,0
22,0
24,3
26,8
20,7
22,8
27,2
30,6
34,4
38,7
43,6
30,4
34,2
38,6
43,5
49,1
Heat
103,7
102,6
101,6
115,6
115,1
114,7
114,1
113,4 kW
94,3
93,4
92,2
91,0
89,6
106,1
104,9
129,6
128,5
127,9
127,2
126,4
142,7
141,8
140,8
140,1
139,5
Input
Power
*
25,3
28,0
31,1
24,2
27,2
30,6
34,3
38,5 kW
18,3
20,2
22,2
24,5
27,0
20,9
23,0
27,2
30,6
34,4
38,7
43,6
30,5
34,3
38,6
43,5
49,1
15
Input
Power
*
25,7
28,4
31,4
24,1
27,1
30,5
34,3
38,5 kW
18,5
20,5
22,6
24,9
27,4
21,2
23,3
27,2
30,6
34,4
38,7
43,5
30,5
34,3
38,6
43,5
49,0
Heat
117,2
115,6
114,1
131,1
129,4
128,2
127,2
126,2 kW
106,8
105,6
104,1
102,5
100,8
121,0
118,8
147,0
145,4
143,4
142,3
141,0
161,7
160,2
158,8
156,9
155,5
*
Only Compressors.
36
|
SyScroll 85-135 Air
Cool
89,2
94,6
100,2
106,0
111,9
118,0
127,4
101,9 kW
80,9
85,8
90,9
96,1
101,5
107,1
115,7
107,9
114,0
120,2
126,6
133,0
142,8
119,8
127,1
134,6
142,3
150,3
158,4
171,0
131,0
139,0
147,2
155,6
164,4
173,3
187,1
Cooling Capacities - SyScroll Air HP S - (STD)
Model
85
95
105
120
135
LWT
°C
15
18
5
7
11
13
7
9
13
15
18
5
9
11
5
7
18
5
7
9
11
13
15
7
9
18
5
9
11
13
15
11
13
15
18
25
Input
Power
*
25,2
25,8
26,4
27,1
27,8
28,5
29,7
29,3 kW
21,5
21,9
22,4
22,9
23,5
24,0
24,8
29,8
30,3
30,8
31,3
31,8
32,6
31,3
31,9
32,5
33,1
33,7
34,3
35,4
35,3
36,0
36,8
37,6
38,5
39,5
41,0
Condensing Air Temperature °C
30
Cool
Input
Power
*
84,2
89,3
94,6
100,0
105,6
111,3
120,2
96,2 kW
76,6
81,2
86,0
90,9
96,0
101,3
109,4
101,8
107,5
113,3
119,2
125,2
134,2
113,1
119,9
126,9
134,2
141,6
149,2
161,0
123,2
130,6
138,3
146,3
154,4
162,8
175,8
27,6
28,3
29,0
29,7
30,4
31,2
32,5
32,8 kW
23,5
24,0
24,6
25,1
25,7
26,3
27,2
33,4
33,9
34,5
35,0
35,6
36,5
35,2
35,7
36,3
37,0
37,7
38,3
39,4
39,5
40,3
41,1
42,0
43,0
43,9
45,5
32
Input
Power
*
28,7
29,4
30,1
30,8
31,6
32,4
33,6
34,4 kW
24,4
24,9
25,5
26,0
26,6
27,2
28,1
34,9
35,5
36,1
36,7
37,3
38,1
36,8
37,4
38,0
38,7
39,4
40,1
41,2
41,4
42,2
43,0
43,9
44,9
45,9
47,5
Cool
82,1
87,1
92,2
97,5
103,0
108,6
117,2
93,7 kW
74,8
79,3
83,9
88,8
93,7
98,8
106,7
99,2
104,7
110,4
116,1
121,9
130,7
110,2
116,9
123,7
130,8
138,0
145,4
156,8
120,0
127,2
134,6
142,4
150,3
158,5
171,1
*
Only Compressors.
SyScroll 85-135 Air |
37
Model
LWT
°C
85
95
105
120
135
5
7
15
18
11
13
7
9
13
15
18
5
9
11
5
7
18
5
7
9
11
13
15
7
9
18
5
9
11
13
15
11
13
15
18
35
Input
Power
*
30,4
31,1
31,8
32,6
33,4
34,2
35,5
36,8 kW
25,8
26,3
26,9
27,5
28,1
28,7
29,6
37,4
38,0
38,6
39,2
39,9
40,8
39,5
40,1
40,7
41,4
42,1
42,9
44,0
44,4
45,2
46,0
47,0
47,9
48,9
50,6
Cool
78,9
83,7
88,6
93,7
99,0
104,3
112,6
89,9 kW
71,9
76,3
80,8
85,4
90,2
95,1
102,6
95,1
100,5
105,9
111,4
116,9
125,3
105,8
112,2
118,8
125,5
132,5
139,6
150,5
114,9
121,8
128,9
136,3
143,9
151,7
163,8
Condensing Air Temperature °C
38
Cool
Input
Power
*
75,6
80,2
84,9
89,8
94,8
99,9
107,8
85,7 kW
68,9
73,1
77,4
81,9
86,5
91,1
98,4
90,8
95,9
101,2
106,4
111,8
119,8
101,1
107,3
113,6
120,1
126,7
133,5
144,0
109,5
116,1
122,9
130,0
137,2
144,7
156,2
32,3
33,0
33,7
34,5
35,3
36,1
37,5
39,4 kW
27,3
27,8
28,4
29,0
29,6
30,2
31,2
40,1
40,7
41,4
42,0
42,7
43,7
42,3
43,0
43,7
44,3
45,1
45,8
47,0
47,6
48,4
49,3
50,2
51,2
52,2
53,9
73,3
82,8
97,9
105,8
Cool kW
66,9
40
Input
Power
* kW
28,3
33,7
41,3
44,4
49,9
*
Only Compressors.
38
|
SyScroll 85-135 Air
Heating Capacities - SyScroll Air HP S - (STD)
Model
85
95
105
120
135
LWT
°C
40
45
50
30
45
50
30
35
50
30
35
40
30
35
40
45
30
35
40
45
35
40
45
50
50
Heat kW
59,5
59,2
59,2
66,8
66,7
-
75,8
76,2
76,0
84,1
84,7
85,0
92,4
93,3
94,4
-7
Input
Power
* kW
17,1
18,9
21,1
19,8
21,9
-
24,2
27,1
30,4
27,0
30,5
34,3
30,1
34,0
38,6
Heat kW
62,6
62,3
62,2
70,1
69,9
70,0
-5
Ambient Air Temperature °C
-3
Input
Power
* kW
17,2
19,0
21,2
Heat kW
66,0
65,6
65,3
65,2
Input
Power
* kW
17,4
19,2
21,2
23,7
19,9
22,0
24,5
74,0
73,7
73,5
20,0
22,1
24,5
79,3
79,7
79,8
88,0
88,5
89,0
96,6
97,4
98,4
24,2
27,1
30,4
27,1
30,5
34,3
30,2
34,1
38,6
83,4
83,7
83,7
83,5
92,7
93,1
93,3
93,6
101,8
102,4
103,2
104,1
24,2
27,2
30,5
34,1
27,1
30,5
34,4
38,7
30,2
34,1
38,5
43,7
0
24,2
27,2
30,5
34,2
27,1
30,5
34,4
38,7
Input
Power
* kW
17,6
19,3
21,4
23,8
26,5
20,2
22,3
24,7
27,5
30,3
34,1
38,5
43,6
89,2
89,6
89,7
89,6
99,2
99,5
99,8
100,1
Heat kW
71,0
70,6
70,3
69,9
69,6
79,5
79,1
78,9
78,8
109,2
109,2
109,9
110,7
*
Only Compressors.
SyScroll 85-135 Air |
39
Model
LWT
°C
85
95
105
120
135
40
45
50
30
45
50
30
35
50
30
35
40
30
35
40
45
30
35
40
45
35
40
45
50
50
5
Input
Power
*
25,0
27,7
30,8
24,2
27,2
30,6
34,3
38,5 kW
17,9
19,7
21,7
24,0
26,7
20,5
22,6
27,2
30,6
34,4
38,7
43,6
30,3
34,2
38,5
43,5
49,2
Heat
88,5
88,1
87,9
100,4
100,1
100,1
100,0
99,6 kW
80,2
79,6
78,9
78,3
77,7
90,1
89,5
111,8
111,5
111,3
111,3
111,2
122,8
122,7
122,8
122,6
123,1
Heat
93,4
92,8
92,3
105,2
105,3
105,3
105,1
104,3 kW
84,7
84,1
83,3
82,4
81,3
94,7
94,0
117,4
117,2
117,1
116,9
116,5
128,8
128,5
128,5
128,6
128,9
7
Ambient Air Temperature °C
10
Input
Power
*
25,1
27,8
30,9
24,2
27,2
30,6
34,3
38,5 kW
18,0
19,9
21,9
24,2
26,7
20,7
22,7
27,2
30,6
34,4
38,7
43,6
30,4
34,2
38,5
43,5
49,1
Heat
100,2
99,1
98,3
113,0
112,7
112,3
111,7
111,1 kW
91,2
90,1
89,1
88,1
87,0
102,1
101,1
126,2
125,7
125,2
124,3
123,8
138,5
138,0
137,5
137,2
136,5
Input
Power
*
25,3
28,0
31,1
24,2
27,2
30,6
34,3
38,6 kW
18,2
20,1
22,1
24,3
26,9
20,9
22,9
27,2
30,6
34,4
38,7
43,6
30,4
34,2
38,6
43,5
49,1
15
Input
Power
*
25,7
28,4
31,4
24,2
27,2
30,5
34,3
38,5 kW
18,4
20,4
22,5
24,7
27,2
21,2
23,3
27,2
30,6
34,4
38,7
43,5
30,5
34,3
38,6
43,5
49,0
Heat
113,3
112,1
110,3
127,5
126,7
125,9
124,8
123,7 kW
103,4
102,4
100,7
99,2
97,7
115,9
114,6
142,8
141,7
140,7
139,5
138,0
156,6
155,6
154,6
153,6
152,7
*
Only Compressors.
40
|
SyScroll 85-135 Air
Condensing unit - SyScroll Air RE _ - (STD-HT-HPF)
Model
85
95
105
120
135
LWT
°C
15
18
5
7
11
13
7
9
13
15
18
5
9
11
5
7
18
5
7
9
11
13
15
7
9
18
5
9
11
13
15
11
13
15
18
25
Input
Power
*
23,0
23,4
23,9
24,3
24,8
25,3
26,2
26,6 kW
19,5
19,8
20,1
20,5
20,8
21,1
21,6
26,9
27,2
27,6
27,9
28,2
28,7
30,4
30,8
31,3
31,7
32,2
32,7
33,5
34,3
34,8
35,4
36,1
36,8
37,5
38,7
Cool
98,6
104,9
111,5
118,3
125,3
132,6
143,9
110,4 kW
88,1
93,7
99,6
105,6
111,9
118,4
128,6
117,3
124,4
131,7
139,1
146,8
158,5
123,7
131,6
139,7
148,1
156,8
165,7
179,6
135,6
144,2
153,2
162,4
172,0
181,9
197,3
Cool
93,1
99,1
105,4
111,8
118,5
125,3
136,1
104,3 kW
83,5
88,9
94,4
100,1
106,1
112,2
121,9
110,8
117,4
124,2
131,1
138,2
149,1
116,6
124,0
131,6
139,5
147,6
156,0
168,9
127,4
135,5
143,9
152,6
161,6
170,9
185,4
30
Input
Power
*
Condensing Air Temperature °C
35
Cool
Input
Power
*
25,2
25,6
26,1
26,7
27,2
27,8
28,6
29,8 kW
21,5
21,8
22,2
22,6
23,0
23,4
24,0
30,2
30,5
30,9
31,2
31,5
32,1
34,1
34,6
35,0
35,5
36,0
36,5
37,4
38,4
39,0
39,6
40,3
41,1
41,8
43,1
87,4
93,0
98,9
105,0
111,3
117,7
127,8
97,9 kW
78,6
83,6
88,8
94,3
99,9
105,7
114,7
103,9
110,1
116,4
122,9
129,4
139,5
109,1
116,0
123,1
130,5
138,1
145,9
157,9
118,8
126,4
134,2
142,4
150,8
159,4
173,0
27,7
28,2
28,7
29,2
29,8
30,4
31,4
33,5 kW
23,5
23,9
24,4
24,8
25,2
25,7
26,3
33,9
34,2
34,6
35,0
35,4
35,9
38,3
38,8
39,3
39,8
40,3
40,9
41,7
43,1
43,7
44,4
45,1
45,9
46,7
47,9
Cool
81,3
86,6
92,2
97,8
103,7
109,8
119,3
90,8 kW
73,2
78,0
82,9
88,0
93,2
98,7
107,2
96,5
102,3
108,2
114,3
120,4
129,7
101,0
107,4
114,1
121,0
128,1
135,3
146,5
109,6
116,6
123,9
131,5
139,3
147,4
159,9
40
Input
Power
*
30,5
31,0
31,6
32,1
32,7
33,4
34,4
37,6 kW
25,9
26,3
26,7
27,1
27,6
28,1
28,8
38,0
38,5
38,9
39,3
39,7
40,3
43,1
43,6
44,1
44,6
45,2
45,8
46,7
48,5
49,1
49,8
50,5
51,3
52,1
53,4
75,0
79,9
85,1
90,4
95,9
82,9
88,3
93,8
99,4
105,0
92,1
98,2
104,4
110,8
117,4
99,6
106,1
112,9
119,8
127,1
Cool kW
67,5
72,0
76,5
81,3
86,2
45
Input
Power
* kW
28,4
28,8
29,3
29,7
30,2
48,5
49,0
49,5
50,1
50,7
54,6
55,2
55,9
56,6
57,4
42,2
42,7
43,2
43,7
44,1
33,8
34,3
34,8
35,4
36,0
*
Only Compressors.
HT Version
SyScroll 85-135 Air |
41
Cool
95,0
100,9
107,0
113,2
119,7
126,3
136,6
107,7 kW
85,4
90,7
96,2
101,9
107,7
113,7
123,1
114,2
120,9
127,7
134,7
141,8
152,6
120,1
127,5
135,2
143,0
151,1
159,3
172,1
131,1
139,1
147,4
156,0
164,9
174,0
188,0
Condensing unit - SyScroll Air RE S - (STD)
Model
85
95
105
120
135
LWT
°C
5
7
15
18
11
13
7
9
13
15
18
5
9
11
5
7
18
5
7
9
11
13
15
7
9
18
5
9
11
13
15
11
13
15
18
25
Input
Power
*
24,4
24,9
25,5
26,1
26,8
27,4
28,5
28,0 kW
20,7
21,1
21,5
21,9
22,4
22,8
23,5
28,4
28,8
29,3
29,7
30,1
30,7
32,3
32,8
33,4
33,9
34,5
35,2
36,2
36,5
37,2
38,0
38,8
39,7
40,6
42,1
Cool
89,4
95,0
100,7
106,7
112,7
119,0
128,7
101,5 kW
80,7
85,7
90,9
96,2
101,7
107,4
116,2
107,6
113,8
120,2
126,7
133,3
143,3
112,9
119,9
127,0
134,3
141,9
149,6
161,4
122,8
130,3
138,1
146,1
154,4
162,9
176,1
30
Condensing Air Temperature °C
35
Input
Power
*
Cool
26,7
27,3
27,9
28,6
29,3
30,0
31,1
31,4 kW
22,6
23,1
23,6
24,1
24,6
25,1
25,9
31,9
32,3
32,7
33,2
33,6
34,3
36,2
36,7
37,3
37,9
38,6
39,2
40,3
40,9
41,7
42,5
43,3
44,2
45,2
46,7
118,4
125,2
132,2
139,4
150,5
114,0
121,0
128,2
135,7
143,4
151,3
163,5
83,6
88,8
94,2
99,8
105,5
111,4
120,4
94,9 kW
75,6
80,4
85,2
90,2
95,4
100,7
108,9
100,6
106,4
112,4
118,4
124,5
133,8
105,2
111,7
Input
Power
*
41,8
42,5
43,1
43,8
44,9
45,9
46,7
47,5
48,4
49,3
50,3
51,9
29,4
30,0
30,7
31,3
32,0
32,8
33,9
35,3 kW
24,8
25,3
25,8
26,3
26,8
27,4
28,2
35,7
36,2
36,7
37,2
37,7
38,4
40,6
41,2
40
Input
Power
*
32,5
33,1
33,7
34,4
35,2
35,9
37,1
39,5 kW
27,2
27,7
28,2
28,7
29,3
29,8
30,7
40,1
40,6
41,2
41,7
42,2
43,0
45,6
46,2
46,9
47,6
48,3
49,0
50,1
51,6
52,4
53,2
54,1
55,0
56,0
57,6
Cool
77,5
82,4
87,4
92,6
97,9
103,4
111,8
87,5 kW
70,2
74,6
79,1
83,8
88,6
93,6
101,3
92,9
98,4
104,0
109,6
115,3
124,0
96,9
102,9
109,1
115,5
122,0
128,7
139,0
104,5
111,0
117,7
124,6
131,7
139,0
150,3
(*) Only Compressors.
42
|
SyScroll 85-135 Air
Evaporator Water Pressure Drop Curves
SySroll Air CO
50
40
30
20
10
0,5
50
40
30
20
10
2,5
SyScroll HP
85
95
105
120
135
5
Water flow rate (l/s)
7,50
50
40
30
20
85
95
105
10
120
135
2,5
Desuperheater pressure drop
5
Water flow rate (l/s)
7,50
85
95
105
120
135
Water flow rate (l/s)
1,50
10
10
2 2,50
SyScroll 85-135 Air |
43
Water pump curves 1 or 2 pump available static pressure (1P/2P-SP)
275
250
225
200
175
150
125
100
75
50
25
0
3,0 3,5 4,0 4,5 5,0
85-95
5,5 6,0 6,5
Water flow rate (l/s)
7,0
105-120
7,5 8,0
135
8,5 9,0
Water pump curves 1 or 2 pump available static pressure (1P/2P-HP)
350
225
200
175
150
125
325
300
275
250
135
100
75
50
25
85-95
0
105-120
2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5 7,0 7,5 8,0 8,5 9,0 9,5 10,0 10,5 11,0 11,5 12,0
Water flow rate (l/s)
44
|
SyScroll 85-135 Air
Dimensions SyScroll 85-105 Air
Front view
I
M
I
M
N
O
N
O
218
218
A
E
=
D
B =
178
C
=
Back view
178
C
L
L
F
G
F
G
650
650
1095
1095
70
70
NOTES
A B C D E Water connection 2” 1/2 Gas M
F
G
I
L
M
Electrical auxiliary lines
Electrical power supply
Gauge kit (Accessory)
Main switch
Control keypad / display
OPTIONAL
N
O
Desuperheater water inlet ø 1” GAS M
Desuperheater water outlet ø 1” GAS M
P1, P2, P3, P4 Anti-vibration mount position
45
45
P1
552
P1
552
P2
P2
Side view
1385
1600
2905
B
B
A
1600
Top view
P4 4x 17
P4 4x 17
155
155
650
E
C-D
E
90
C-D
90
650
970
1800
971
P3
971
P3
970
1800
619
553
619
553
Hydraulic option
STD
1P
2P
1PT
2PT
Water in
D
C
A
C
D
Water out
B
E
B
B
E
SyScroll 85-135 Air |
45
Dimensions SyScroll 120-135 Air
Front view
N
O
N
O
218
218
=
A
E
E
B
D
B
=
178
178
C
C
F
G
F
G
653
653
M
M
I
I
L
L
P2
P2
1095
1095
70
70
45
45
P1
552
P1
552
NOTES
A B C D E Water connection 2” 1/2 Gas M
F
G
I
L
M
Electrical auxiliary lines
Electrical power supply
Gauge kit (Accessory)
Main switch
Control keypad / display
OPTIONAL
N
O
Desuperheater water inlet ø 1” GAS M
Desuperheater water outlet ø 1” GAS M
P1, P2, P3, P4 Anti-vibration mount position
Side view
1985
A
B
A
1985
B
2200
3505
2200
P4 4x 17
P4 4x 17
155
155
E
653
653
90
970
2400
1214
1214
P3
P3
732
553
732
553
Hydraulic option
STD
1P
2P
1PT
2PT
Water in
D
C
A
C
D
Water out
B
E
B
B
E
46
|
SyScroll 85-135 Air
Space requirements
1 MT.
3 MT
.
0,8 MT
.
1 MT
.
1,2
MT.
Systemair srl
Via XXV Aprile, 29
20825 Barlassina (MB)
Italy
Tel. +39 0362 680 1
Fax +39 0362 680 693 [email protected]
www.systemair.com
Systemair · May 2014 · EDM SyScroll 85-135 Air-S-1GB/05.14 • E34013 As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos.
advertisement
Key Features
- Air cooled water chiller
- Cooling or heating operation
- Tandem scroll compressor
- Plate heat exchanger
- Quiet fans
- 2 acoustic options: standard and super low noise
- Electronic control and management system
- Safety features
- Control features
- Wide range of operating limits