AAON SS1026, SS1030, SS1032, SS1033, SS1034 VCM-X controller, SS1028 system manager, SS1027, SS1056 service tool, SS1045 RNE controller Technical guide
Below you will find brief information for VCM-X controller SS1026, VCM-X controller SS1030, VCM-X controller SS1032, VCM-X controller SS1033, VCM-X controller SS1034, system manager SS1028, service tool SS1027, RNE controller SS1045, service tool SS1056. This guide provides detailed instructions on how to connect, initialize, program, and troubleshoot the VCM-X and RNE controllers, as well as the System Manager and Service Tools.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
Factory Packaged Controls
VCM-X / RNE Operator
Interfaces Technical Guide
VCM-X Controller Code: SS1026, SS1030, SS1032, SS1033, SS1034
Requires System Manager Code: SS1028 Version 1.0 and up
Requires Service Tool Code: SS1027 Version 1.0 and up
RNE Controller Code: SS1045
Requires Service Tool Code: SS1056
TABLE OF CONTENTS
INTRODUCTION .............................................................................................................................. 3
Modular Service Tool and Modular System Manager ...................................................................................................................3
SYSTEM CONNECTION ................................................................................................................... 4
Modular Service Tool ....................................................................................................................................................................4
Modular System Manager ............................................................................................................................................................5
Power/Comm Board Wiring ..........................................................................................................................................................6
Modular System Manager - Stand Alone......................................................................................................................................7
INTERFACES OVERVIEW ................................................................................................................. 8
Display Screens and Data Entry Keys .........................................................................................................................................8
Mode Selection Buttons ...............................................................................................................................................................9
Entering Unit ID (Address) ...........................................................................................................................................................9
INITIALIZATION ............................................................................................................................ 10
System Manager Initialization ....................................................................................................................................................10
System Manager Passcodes......................................................................................................................................................12
Modular Service Tool Initialization ..............................................................................................................................................13
Setting the Energy Saving Timer ................................................................................................................................................14
Setting the Time and Date ..........................................................................................................................................................15
Week Schedules ........................................................................................................................................................................16
Holiday Schedules......................................................................................................................................................................17
Schedule Override......................................................................................................................................................................17
PROGRAMMING ............................................................................................................................. 18
VCM-X Confi guration Screen Index ...........................................................................................................................................18
Confi guring VCM-X Controllers ..................................................................................................................................................19
RNE Confi guration Screen Index ...............................................................................................................................................28
Confi guring RNE Controllers ......................................................................................................................................................29
VCM-X / RNE Setpoint Screen Index .........................................................................................................................................38
Confi guring VCM-X / RNE Setpoints ..........................................................................................................................................39
VCM-X / RNE Status Screen Index ............................................................................................................................................48
VCM-X / RNE Status Screens ....................................................................................................................................................49
VAV/Zone Confi guration Screens ...............................................................................................................................................58
VAV/Zone Setpoint Screens .......................................................................................................................................................60
VAV/Zone Status Screens ..........................................................................................................................................................64
MiniLink PD Confi guration Screens............................................................................................................................................66
MiniLink PD Status Screens .......................................................................................................................................................67
TROUBLESHOOTING ..................................................................................................................... 68
Damper Force Modes.................................................................................................................................................................68
VCM-X / RNE Outputs Force .....................................................................................................................................................70
INDEX ............................................................................................................................................ 71
WattMaster Controls, Inc.
8500 NW River Park Drive · Parkville , MO 64152
Toll Free Phone: 866-918-1100
PH: (816) 505-1100 · FAX: (816) 505-1101
E-mail: [email protected]
Visit our website at www.orioncontrols.com
www.aaon.com
WattMaster Form : AA-VCMXRNEOI-TGD-01B
Copyright September 2012 WattMaster Controls, Inc.
AAON Part Number: V23670
AAON ® is a registered trademark of AAON, Inc., Tulsa, OK.
Neither WattMaster Controls, Inc. nor AAON ® assumes any responsibility for errors or omissions in this document.
This document is subject to change without notice.
Modular Service Tool
INTRODUCTION
Modular Service Tool and System Manager
Modular System Manager
9.00"
2.02"
4.75”
7
DEC
1
4
8
0
2
5
UP
3
6
9
PREV
ESC
DOWN
CLEAR
NEXT
ENTER
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
6.25"
UP
Mode
Selection
PREV NEXT
STATUS
1.81"
SETPOINTS
ESC
DOWN
CLEAR
10.00”
SCHEDULES
ENTER
OVERRIDES
ALARMS
CONFIGURATION
BALANCE - TEST
ON
7
DEC
1
4
2
5
8
0
3
6
-
9
MINUS
Figure 2: Modular System Manager Dimensions
NOTE:
The Modular System Manager can be used with the
VCM-X Controller, but not with the RNE Controller. The interface options for the RNE Controller are the Modular
Service Tool, the System Manager Touch Screen II, or
Prism II Software.
1.63"
Figure 1: Modular Service Tool Dimensions
The OE391-11 Modular Service Tool is a system operator interface that provides a direct link to enable the system operator to view the status, confi gure, and adjust the setpoints of the VCM-X, RNE, or VAV/Zone
Controller on the control system communications loop. The Modular
Service Tool is housed in an attractive beige-colored plastic enclosure.
The display area is covered with a clear plastic bezel for protection of the display screen. The Modular Service Tool has a 4-line-by-20-character display panel with adjustable contrast control and a 27-key membrane keypad for data selection and entry. All keypad operations are simple and straight forward, utilizing non-cryptic plain English language messages.
Menu-driven programming allows for easy setup and operation without the need for specialized training. The Modular Service Tool is supplied with (4) AA 1.5 V Volt alkaline batteries, a wall mount DC power supply and a communication cable terminated with an 8-pin DIN connector for connection to the Service Tool. The cable allows you to setup and program any Orion controller with an 8-pin DIN connector socket by simply plugging the service tool into the socket on the controller.
The OE392-07 Modular System Manager provides a direct link to enable you to view the status and adjust the setpoints of the VCM-X and
VAV/Zone controllers on the control system communications loop. The
System Manager is housed in an attractive, off-white colored plastic enclosure. The System Manager is equipped with a 4-line-by-20-character backlighted display panel and a 24-key membrane keypad for data selection and entry. All keypad operations are simple and straight forward, utilizing non-cryptic plain English language messages. Menu-driven programming allows for easy setup and operation without the need for specialized training. The System Manager also has 2 integral LEDs for user notifi cation of system alarm conditions and override initiations.
Protection from unauthorized users is provided by the System Manager’s integral multi-level passcode authorization programming.
On a Networked System, the Modular System Manager is connected to the communications and power loop of the system via modular cables that simply plug into the System Manager board and the Power/Comm
Distribution Board. This virtually eliminates wiring errors and makes installation fast and easy. When it is to be connected to a Stand-Alone system, a cable with modular connectors on one end and stripped wire ends on the other end is provided to facilitate connecting communications and power to the Modular System Manager from the 24 VAC power source and the HVAC unit controller communication wiring terminals.
The Modular Service Tool is designed to be hand-carried. Its rugged plastic housing provides superior protection for the electronic components housed inside. The Modular Service Tool is a top-quality service tool that will stand up to the demands of the typical job site environment for many years.
The Modular System Manager is designed for wall mounting. Mounting holes are provided to attach the Modular System Manager to a standard handy box. It is recommended that the System Manager be mounted at approximately eye level to allow for ease of programming and reading of the display. The System Manager is typically mounted in the building manager’s or superintendent’s offi ce or in an equipment room. The attractive enclosure is quite suitable for mounting in any location.
VCM-X / RNE Operator Interfaces Technical Guide
3
SYSTEM CONNECTION
Modular Service Tool
Zone
Zone
Modular Service Tool
Whether you have a Stand Alone, Interconnected, or Networked Orion
Controls System, the Modular Service Tool always connects to an HVAC unit controller via a prefabricated cable that is supplied with the service tool. The Modular Service Tool cable is terminated on both ends with a mini-DIN connector. Attach one end to the Modular Service Tool and the other end to the mini-DIN connector on the HVAC unit controller. If this is an Interconnected System, all controllers that are interconnected with communications cable can be programmed from any HVAC unit controller on the loop. If this is a Networked System, all controllers on the entire Networked System can be programmed from one HVAC unit controller.
Be sure that the Modular Service Tool has fresh batteries installed or that it is connected to a power source using the supplied power pack before attempting any programming of the controller. See Figure 3 for connection details.
Connector Cable
Male DIN Connector
Female DIN Connector
Typical Controller Board
The Modular Service Tool Can Be
Connected To The VCM-X, RNE
Or VAV/Zone Controller By
Plugging One End Of The
Supplied Cable Into the
Modular Service Tool DIN
Connector And The Other End
Into The DIN Connector On The
Controllers.
Modular Service Tool
Mode
Selection
STATUS
PREV
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE- TEST
ON
7
DEC
1
4
UP
ESC
DOWN
CLEAR
ENTER
2
5
8
0
3
6
-
9
MINUS
NEXT
Power On Button
4
Figure 3: Modular Service Tool
Be Sure The Modular Service
Tool Is Connected To The
Supplied Power Pack Or Has
Fresh Batteries Installed Before
Attempting Programming Of The
Controller. Be Sure The Power Is
Turned Off On The Modular
Service Tool Before Connecting
The Cable To The Controller.
VCM-X / RNE Operator Interfaces Technical Guide
SYSTEM CONNECTION
Modular System Manager
Modular System Manager
Device. By using these plug-in connections, wiring errors are virtually eliminated and system installation is fast and easy. See Figure 4 below for typical connection information. See Figure 5 on page 6 for typical
Power/Comm board wiring and connection information.
NOTE:
The Modular System Manager can be used with the
VCM-X Controller, but not with the RNE Controller. The interface options for the RNE Controller are the Modular
Service Tool, the System Manager Touch Screen, or
Prism II Software.
As previously described, when you are connecting the Modular System Manager to a Networked System, the Modular System Manager is connected to the communications and power loop of the system via modular cables. These cables simply plug into the System Manager board and to any device with modular connectors on any local loop on the system. Devices with modular connectors include the Power/
Comm Distribution Board, VAV/Zone controller, and MiniLink Polling
When the System Manager is to be connected to a Stand Alone system, a 12-foot cable with modular connectors on one end and stripped wire ends on the other end is provided for this purpose. This is used to facilitate connecting communications and power wiring to the Modular
System Manager from a 24 VAC power source and to the HVAC unit controller communication wiring terminals. See Figure 6 on page 7 for wiring details. If the supplied cable wire is not long enough for your installation, a standard modular cable of the correct length can be purchased through WattMaster and one of the modular connectors can be cut off to allow for the transformer and communication terminal wiring connections. It is recommended that you do not splice the communications wire if at all possible. The transformer should be rated at
6 VA minimum power output.
Figure 4: Modular System Manager - Networked
VCM-X / RNE Operator Interfaces Technical Guide
5
SYSTEM CONNECTION
Power/Comm Board Wiring
Zone
Zone
WARNING!
DO NOT GROUND THE 24V TRANSFORMER
THAT IS TO BE USED WITH THE POWER/COMM
BOARDS. GROUNDING OF THE TRANSFORMER
WILL DAMAGE THE POWER/COMM BOARD
AND ALL BOARDS CONNECTED TO IT. A
SEPARATE TRANSFORMER MUST BE USED
FOR EACH POWER/COMM BOARD. NO
EXCEPTIONS. DO NOT CONNECT ANY OTHER
DEVICES TO THE TRANSFORMER USED FOR
THE POWER/COMM BOARD!
A Power/Comm Cable Can Be Used To
Connect With The MiniLink PD Instead
Using
Of
2 Conductor Twisted Pair With Shield
Cable . You Can Also Use A Power/Comm
Cable To Connect With Another Power/Comm
Board, A System Manager Or A VAV/Zone
Controller.
If Desired, Instead Of Using A
Power/Comm Cable, You Can Use 2
Conductor Twisted Pair With Shield
Cable To Connect To The Power/
Comm Board From The VCM-X / RNE
Controller, MiniLink PD, Or Another
Power/Comm Board.
Line Voltage
24VAC
24VAC Transformer (By Others)
4 Amp Slow Blow Fuse
Local Loop RS-485
9600 Baud
T
SH
All Comm Loop Wiring Is
Straight Thru
T
SH
T
SH
T
SH
R R R R
NOTE:
Diagram Shown Is For Wiring Of
Power/Comm Board When Used
For Connecting Local Loop Devices
Such As VAV/Zone Controllers,
System Manager(s) and Other
Power/Comm Boards.
Power/Comm Cable To Other Power/Comm Board(s),
System Manager, Or VAV/Zone Controllers On Local Loop Only.
Local Loop RS-485
9600 Baud
6
Figure 5: Typical Power/Comm Board Wiring
VCM-X / RNE Operator Interfaces Technical Guide
SYSTEM CONNECTION
Modular System Manager - Stand Alone
Figure 6: Modular System Manager - Stand Alone
VCM-X / RNE Operator Interfaces Technical Guide
7
8
INTERFACES OVERVIEW
Service Tool and System Manager Keys
Operator Interfaces Comparison
In order to confi gure and program the Orion System controllers, you must have an Operator’s Interface or a personal computer with the Prism II computer front-end software installed. Three different Operator Interfaces are available for programming of the Orion Controls System—the
Modular Service Tool, the Modular System Manager (VCM-X and VAV/
Zone Controllers only), and/or the System Manager TS II. These devices allow you to access the status and setpoints of the controllers on your communications loop. This manual describes the Modular Service Tool and Modular System Manager. If using the System Manager TS II, please see the System Manager TS II Technical Guide.
The Modular Service Tool and System Manager allow you to view any temperature or output condition and change any setpoint to fi ne-tune the operations of the total system. All keypad operations are simple and straightforward, utilizing non-cryptic plain English messages.
Display Screens & Data Entry Keys
The System Manager’s and Modular Service Tool’s display screens are very similar. For most setpoints and modes, there are only a few difference in the function of the keypads. In this manual, when there are differences in the keypad input or the screens between the two operator’s interfaces, both screens or keypads will be shown. See the chart below for a list of the keypad descriptions and functions.
UP
Mode
Selection
STATUS
SETPOINTS
PREV
ESC
DOWN
CLEAR
NEXT
SCHEDULES
ENTER
OVERRIDES
ALARMS
CONFIGURATION
BALANCE - TEST
ON
1
4
7
DEC
2
5
8
0
3
6
9
Modular Service Tool
System Manager
Keypad
Description
ESC
ENTER
Clear
Minus
DEC
Key Function
System Manager Modular Service Tool
Use this key to exit from screens or from data entry or to return to the Main
Menu from any screen in the system.
Use this key to close a data entry fi eld and advance to the next item or screen.
If a data entry mistake is made, press this key to clear the data entry fi eld and start over.
Same function as
System Manager
Same function as
System Manager
If a setpoint with a negative value is required, press this key for the minus sign.
Press this key when entering data that requires a decimal point.
Same function as System
Manager but also turns off the power to the
Service Tool when on the
Main Menu Screen
Same function as
System Manager
Same function as
System Manager
Use these keys to step to the next controller on the loop on interconnected or networked systems.
Use these keys to step backward or forward through the screens.
Same function as
System Manager
Same function as
System Manager
7
DEC
1
4
2
5
8
0
UP
3
6
9
PREV
ESC
DOWN
CLEAR
NEXT
ENTER
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
Modular System Manager
VCM-X / RNE Operator Interfaces Technical Guide
INTERFACES OVERVIEW
Service Tool and System Manager Keys
Mode Selection Buttons
Both the System Manager and Modular Service Tool are provided with
“Mode Selection Buttons.” These buttons give you instant access to the specifi c mode desired without having to scroll through several menu screens to get there. The Modular Service Tool has two extra function keys (“Confi guration” and “Balance-Test”) that are not available on the
System Manager.
Service Tool and System Manager
Entering Unit ID ( Address)
With both the Modular Service Tool and System Manager, you must enter the ID (Address) of the controller you wish to program.
Unit Selection
Enter Unit ID#
Selected ID#: XXXX
Button
Description
Mode Selection Buttons
STATUS
System Manager Modular Service Tool
Pressing this button takes you directly to the controller “Status” screens.
SETPOINTS
Pressing this button takes you directly to the controller “Setpoints” screens and
“Confi guration” menu.
Pressing this button takes you directly to the controller “Status” screens.
Pressing this button takes you directly to the controller “Setpoints” screens.
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE-TEST
Pressing this button takes you directly to the controller “Schedules” screens.
Pressing this button takes you directly to the controller “Overrides” screen. See the “Override
Button” section on page
12 for a description of this function. See Notes 1 &
2 below.
Pressing this button takes you directly to the controller “Alarms” screen. See the “Alarms
Button” section on
page 11 for a description of this function. See Notes 1
& 2 below.
Not Available. Use
“Setpoints” Button to access Menu.
Not available.
Pressing this button takes you directly to the controller “Schedules” screens.
Pressing this button takes you directly to the controller “Overrides” screen. See the “Override
Button” section on page
14 for a description of this function.
See Note 1 below.
Pressing this button takes you directly to the controller “Alarms” screen. See the “Alarms
Button” section on page
13 for a description of this function.
See Note 1 below.
Pressing this button takes you directly to the controller
“Confi guration” screens.
Pressing this button takes you directly to the controller “Balance-Test” screens.
With the Main Menu Screen displayed, press the function key associated with the operation (setpoints, confi guration, etc.) you want to perform.
The screen shown above will appear, asking you to enter a unit ID#
(controller address). Put in the ID# of the controller you wish to communicate with and then press
<ENTER>
.
If this is a Network System (the system has a CommLink), the Unit ID is actually two separate numbers combined into one value. The fi rst part of the number contains the Loop Address at which the controller is located. The second part of the number contains the actual controller address. See Examples #1 & #2 below.
If this is a Stand Alone System (system without a CommLink), the Unit
ID will be a number between 1 and 59. It is recommended the address be set to 1. See Example #3 below.
EXAMPLE #1
You would like to view the 3 rd controller on the 5 th loop. Enter “503” as the Unit ID.
EXAMPLE #2
You would like to view the 12 th
controller on the 24 th
loop. Enter “2412” as the Unit ID.
EXAMPLE #3
You would like to view the only controller on the loop. Enter “1” as the
Unit ID. No loop number is required since there is only one loop.
Press
<ENTER>
after entering the unit ID. If you are using the Modular
Service Tool, you will be taken directly to the fi rst screen for the operation you are trying to program.
Notes:
(1) This button only functions when the system is confi gured for “Network
Mode” or “Multiple MGRS Mode.” It will not function in “Stand Alone Mode.”
(2) The “Search for Units” function must be performed on the System Manager upon initial system setup before this function will be available. See the “System
Manager NM & MM Loop Search” section of this manual for complete instructions on performing a loop search.
VCM-X / RNE Operator Interfaces Technical Guide
9
INITIALIZATION
System Manager Initialization
Zone
Zone
Modular System Manager
If your display indicates a different mode than the one you need, press
<ENTER>
. The following screen will appear:
System Manager Initialization Screens
When the System Manager is powered up, the fi rst screen displays the current version of the software installed in your System Manager and your system’s confi guration—Network or Stand-Alone operation.
1) Set Time & Date
2) Communications
->) Next Menu
ESC) Exit Menu
Initializing
System Manager vX.XX
WattMaster Controls
Stand-Alone Mode
Press
<2>
on the keypad to enter the Communications Screen.
THIS ACTION REQUIRES
A SPECIAL HIGH LEVEL
PASSCODE CLEARANCE
Enter: XXXXXXX
System Manager vX.XX
Monday Operations
07/16/12 04:26 PM
NM Outdoor Air 87ºF
The screen above will appear a few seconds later. The last line of the display will have the letters SA (Stand-Alone Mode), MM (Multiple
System Manager Mode), or NM (Network Mode) followed by the current outdoor air temperature. The System Manager normally ships from the factory set for SA (Stand-Alone Mode). If you do not have a
CommLink or MiniLink polling device on your system and have one or more controllers connected and only one System Manager, the system must be set for SA (Stand-Alone Mode). If you have a CommLink or
MiniLink PD on your system and only have a single System Manager, the system must be set for NM (Network Mode). If you have a CommLink or MiniLink polling device on your system and have multiple System
Managers on your System, the system must be set for MM (Multiple
System Managers Mode). If you believe your system is incorrectly confi gured, please read the instructions that follow. If your system is confi gured correctly, proceed to the System Manager Network Mode
Loop Search section on page 11.
Confi guring for Stand-Alone Mode, Multiple
System Managers Mode, or Network Mode
The System Manager must be confi gured for the correct mode of operation for your system. There are 3 modes of operation available for the
Orion System—Stand-Alone, Multiple MGRS, and Network Mode.
Look at the bottom line of the display as mentioned in the previous paragraph and determine which mode your System Manager is currently set for. If you are using this System Manager on a communications loop that doesn’t have a MiniLink PD or CommLink connected to it and you have a single System Manager on your system, then you need to operate in Stand-Alone Mode. The fi rst two characters on the bottom line of the display should be SA. If you are using this System Manager on a communications loop, have a MiniLink PD or CommLink installed, and have multiple System Managers, then you need to operate in Multiple
MGRS Mode. The fi rst two characters on the bottom line of the display should be MM. If you are using this System Manager on a communications loop that has a MiniLink PD or CommLink installed and you have a single System Manager for your entire system, then you need to operate in Network Mode. The fi rst two characters on the bottom line of the display should be NM.
Enter the seven digit passcode “2337377” to access the next screen.
These seven digits spell the word “ADDRESS” on your phone keypad.
You will then see the screen below displayed. You must use the keypad to enter the correct number for the mode of operation needed for your system.
0) Stand Alone
1-60) Multiple MGRS
63) Network System
Enter Mode of Op:.xx
For Stand Alone Mode, press
<0>
.
For Multiple MGRS Mode, enter the address at which you want this particular System Manager to be set. When multiple System Managers are used on a local loop, each must be set with a unique address different from any other device on that loop. You must perform this same operation again for each System Manager installed. If you want one of these System Managers to be able to indicate alarms and overrides for the entire system, you must enter
<63>
for Network Mode on that particular System Manager.
For Network Mode (or as explained above for Multiple System Managers when one is to be set to indicate alarms and overrides), enter
< 63>
.
Once you have the correct number per the display above displayed, press
<ENTER>
. The following screen will appear telling you that you have changed the system mode:
You Have Changed The
System Manager Mode
Press Any Key To
Continue
Press any key on the keyboard to exit this screen.
10
VCM-X / RNE Operator Interfaces Technical Guide
INITIALIZATION
System Manager Initialization
System Manager NM & MM Mode Loop Search
When the System Manager is confi gured for Network Mode, a loop search must initially be performed for the System Manager to recognize alarms or overrides. Also, when you have a system that has multiple
System Managers and you have one of the System Managers set to
(63) Network Mode for alarm and override indication, you must also perform a loop search for that System Manager. This allows the System
Manager to be aware of all alarms and overrides for all local loops on the entire system.
System Manager Alarm Search
The System Manager can be used to search for all active alarms on the system. You must confi gure the MiniLink PD to allow for “ Alarm Polling” for each controller you want polled for alarms. See the MiniLink PD programming section on page 56 of this manual for setting information.
Press
<ALARMS>
. The Unit Selection Screen below will be displayed.
Enter the Unit ID of any unit on the system and press
<ENTER>
. The alarm search will begin with the unit you enter. The entire system is searched from this point.
NOTE: The Loop Search function is only required when using the System Manager(s), not the Modular Service Tool.
Unit Selection
Enter Unit ID#
Selected ID#: XXXX
To access the Loop Search Screen, from the Main Menu Screen, press
<ENTER>
.
The following screen will appear. The System Manager will search for any active alarms on the entire system.
1) Set Time & Date
2) Communications
->) Next Menu
ESC) Exit Menu
Alarm Screen
SEARCHING!
Press
<
>
for Next Menu. The following screen will be displayed:
1) Change Passcodes
2) Loop Search
<-) Prev. Menu
ESC) Exit Menu
After the System Manager completes its search, it will list the fi rst unit on the system that currently has an active alarm. Press
<ENTER>
to scroll through all the alarms on that particular unit. To move to the next unit or back to the previous unit, use the “Prev” or “Next” arrows to move between units with alarms.
Press
<2>
for Loop Search. The following screen will be displayed:
Alarm Search Screen
Loop = 1 Unit = 59
Space Sensor Failure
Loop Search
Current Loop = XX
Loops Found = XX
Searching
The System Manager will now proceed to search all loops to fi nd the
MiniLink PDs that are connected to the system. The screen will display the current loop being searched and the number of loops currently found.
To clear any alarms that are found, you must fi x the problem indicated in the alarm. Once the problem is fi xed, the alarm will clear from the screen the next time the unit is polled.
Once the search is completed, the following screen will be displayed:
Loop Search
Finished
Loops Found = XX
Press ESC to Exit
The screen will display the number of loops found on your system. The information will be saved into the System Manager’s memory. No further loop searches will be required unless you add an additional MiniLink
PD to the Network System.
VCM-X / RNE Operator Interfaces Technical Guide
11
INITIALIZATION
System Manager Passcodes
Zone
Zone
System Manager Override Search
When a space sensor with override option is used with any VAV/Zone
Controller or VCM-X Controller, the System Manager can determine and report any controllers that are currently operating in an override condition. This function requires that a MiniLink PD is installed on each loop where the controllers may be located. The MiniLink PD must be confi gured to allow for “Alarm Polling” for each controller that Override
Polling Enabled is desired for this function to work. See the MiniLink PD programming section on page 66 of this manual for setting information.
To access the Space Sensor Overrides Screen, press
<OVERRIDES>
, located on the System Manager keypad. A screen will appear asking you to enter a unit ID. Enter an ID for any active controller on the system and press
<ENTER>
. The following screen will appear:
These two levels of passcodes are programmable by any Level 2 user.
The default Level 1 passcode is “ 1111” and the default Level 2 passcode is “ 2222.”
If you wish to change either Level 1 or Level 2 passcodes, please see the instructions that follow.
From the Main Status Screen, press
<ENTER>
. The following screen will appear:
1) Set Time & Date
2) Communications
->) Next Menu
ESC) Exit Menu
Overrides Screen
Press
<
>
for Next Menu. The following screen will be displayed:
SEARCHING!
After the System Manager completes its search, it will list the fi rst unit on the system that is currently in the override mode. Press the
<>
<> button to scroll through all units that are in the Override Mode.
or
1) Change Passcodes
2) Loop Search
<-) Prev. Menu
ESC) Exit Menu
Press
<1>
for Change Passcodes. The following screen will be displayed:
Overrides Screen
Loop = 1 Unit = 59
Override Unit
Enter New Passcode
Level 1.....: XXXX
Level 2.....: XXXX
[Must Be 4 Digits]
System Manager Passcodes
Anytime you enter a unit ID with the Modular System Manager, you will be asked for a passcode. Passcodes are not required to view Status
Screens. The screen below will appear if this action requires passcode clearance.
This screen allows you to enter new Level 1 or Level 2 passcodes. The actual digits in your passcodes are never displayed. An “X” is used as a place holder for each digit entered. Passcodes must always be four digits in length, so the usable range of numbers is 1000 to 9999.
CAUTION: If you change the Level 2 passcode and cannot remember what it is, you will be locked out of
THIS ACTION REQUIRES
PASSCODE CLEARANCE
Enter Passcode: XXXX
The System Manager has two levels of user access. Level 1 users are limited to viewing status and/or changing the Time and Date and Operating Schedules. Level 2 users have complete system access. Any status or setpoint fi eld can be read or reset from the System Manager.
12
VCM-X / RNE Operator Interfaces Technical Guide
INITIALIZATION
Modular Service Tool Initialization
Modular Service Tool
The Modular Service Tool is very similar to the System Manager in its operations. Two exceptions to this are that unlike the System Manager, the Service Tool does not check the entire system when performing an
“Alarm” or “Override” search, and it does not have any passcoding capability.
Enter
<0>
or
<1>
to select the proper mode of operation. When you are fi nished, press
<ENTER>
to return to the Main Menu.
You Have Changed The
System Mode
Press Any Key To
Continue
NOTE: When you press the
<Alarms>
or
<OVERRIDES>
button on the Modular Service Tool, it will search only the loop number of the unit ID that you have entered; therefore, you must search each local loop individually to access all alarms or overrides on the system.
Modular Service Tool Initialization Screen
After connecting the Service Tool to the controller with the supplied cable, press
<ON>
. The following screen will appear:
Modular Service Tool Alarm Search
To search for alarms, press
< Alarms>
. The Unit Selection Screen will be displayed. Enter the Unit ID of any controller on the system and press
<ENTER>
. Unlike the System Manager, only the alarms on this loop will be searched, not the entire system.
Service Tool vX.XX
Monday Operations
07/16/12 04:26 PM
Stand Alone Mode
Unit Selection
Enter Unit ID#
Selected ID#: XXXX
The following screen will appear. The Modular Service Tool will search for any active alarms on the local loop.
Confi guring the Modular Service Tool for Network or Stand-Alone Operation
As with the System Manager, you must determine if the mode displayed is correct for your system. If it is confi gured for Stand-Alone, Stand
Alone Mode will appear on the bottom line of the display. This is the factory default setting. If you are using this tool on a system or controller that does not have a CommLink or MiniLink PD installed, then this is the correct setting, and you can proceed to the desired screen by pressing the menu key or any function key. If you are using this Service Tool on a communications loop and have installed a MiniLink PD or CommLink, then you need to operate in Network Mode, and the bottom line should display the words, Network Mode.
Alarm Screen
SEARCHING!
After the Modular Service Tool completes its search, it will list the fi rst unit on the local loop whose ID was entered that currently has an active alarm. Press
<ENTER>
to scroll through all the alarms for controllers on that particular loop. To move to the next controller or back to the previous unit, use the
<> or
<> button to move between controllers with alarms on the loop.
If your display indicates a different mode than the one you need, press
<ENTER>
and the following screen will appear:
Alarm Search Screen
Loop = 1 Unit = 59
Space Sensor Failure
1) Set Time & Date
2) Communications
3) Energy Saving
ESC) Exit Menu
Press
<2>
to access the Communications Screen.
To clear any alarms that are found, you must fi x the problem indicated in the alarm. Once the problem is fi xed, the alarm will clear from the screen the next time the unit is polled.
0) Stand Alone Mode
1) Network System
Enter Mode Of Op:.xx
VCM-X / RNE Operator Interfaces Technical Guide
13
INITIALIZATION
Modular Service Tool Initialization
Zone
Zone
Modular Service Tool Override Search
When a space sensor with override option is used with any VAV/Zone
VCM-X, or RNE Controller, the Modular Service Tool can determine and report any controllers that are currently operating in an override condition on the local loop whose ID (Address) has been entered before running the search. This function requires that a MiniLink Polling
Device is installed on each loop where the controllers may be located.
Setting the Energy Saving Timer
The Modular Service Tool has a built-in timer that can be programmed to shut the Service Tool off after a specifi ed period of time if no buttons are pressed. This is a very useful feature if you are powering the
Service Tool from the internal batteries. To access this setting from the
Main Status Screen, press
<ENTER>
. The following screen will appear:
To access the Overrides Screen, press
<OVERRIDES>
from the
Modular Service Tool’s keypad. A screen will appear asking you to enter a unit ID. Enter an ID for any active controller on the local loop you wish to search and press
<ENTER>
. Unlike the System Manager, only the overrides on this loop will be searched, not the entire system.
The following screen will appear:
Overrides Screen
1) Set Time & Date
2) Communications
3) Energy Saving
ESC) Exit Menu
Press
<3>
to access the Energy Saving Screen. The following screen will appear:
SEARCHING!
Energy Saving
Automatic Power Down
Minutes: xx
Press ESC to Exit
After the Service Tool completes its search, it will list the fi rst unit on the selected local loop that is currently in the override mode. Press the previous or next button to scroll through all units on the local loop you have selected that are in the Override Mode.
Enter the number of minutes you want the Service Tool to stay active before it automatically powers down. To cancel the automatic power down, enter
<99>
. After you have entered a number between 1 and 99 minutes, press
<ESC>
to exit the screen.
Overrides Screen
Loop = 1 Unit = 59
Override Unit
14
VCM-X / RNE Operator Interfaces Technical Guide
INITIALIZATION
Setting the Time & Date
Setting Time & Date
Both the Modular Service Tool and Modular System Manager are equipped with a real time clock chip allowing them to maintain the correct time. Once you have programmed the correct time and date, the information is broadcast globally to all controllers on the entire system.
The System Manager will also broadcast this information once every day at midnight to synchronize all of the controllers on the system.
Programming the Date
Program Time/Date
Month (1-12): XX
Day (1-31): XX
Year (00-99): XX
Programming Times
From the Main Menu, press
<ENTER>
. The following screen will appear:
Month - Enter the Month (1 to 12)
Day - Enter the Day of the Month (1 to 31)
Year - Enter the current Year with two digits (00 to 99)
1) Set Time & Date
2) Communications
3)
ESC) Exit Menu
Press
<1>
on your keypad to access the Set Time & Date Screens.
Although the times are displayed on the Main Screen in a standard 12hour format, you must program them using the 24-hour military format.
If you confi gured the VCM-X or RNE Controller to use its own Internal
Schedules, the Occupied/Unoccupied modes are calculated on the basis of the current real time clock reading.
Daylight Savings
After you have programmed the date, the Daylight Savings Time Auto
Adjust Screen will be displayed. If you want the time to be automatically adjusted for daylight savings time, use the arrow key to select Yes, or if not, use the arrow key to select No.
Daylight Savings
Auto Adjustment: Yes
Use Left/Right Arrow
Program Time/Date
Day (Sunday=0): X
Enter Hr. (0-23): XX
Enter Minutes : XX
Day - Enter the Day of the Week (0 to 6)
NOTE:
The U.S. government has seen fi t recently to arbitrarily determine the switch-over dates each year, so we recommend that you disable this function and manually change the schedules from year to year.
If you enable this operation, be aware that the time will change the fi rst Sunday in April and then switch back the last Sunday in October. These used to be the standard dates that were constant from year to year.
Hours (Hr) - Enter Hours in 24-Hour Military Format
Minutes - Enter the Minutes
VCM-X / RNE Operator Interfaces Technical Guide
15
INITIALIZATION
Scheduling
Zone
Zone
Scheduling
You can access the VCM-X or RNE Controller Scheduling Screens by
pressing
<SCHEDULES>
on either the System Manager (VCM-X only) or the Modular Service Tool. Press the number button for the scheduling function you wish to view.
All times are in 24-hour military format, so 5:00 PM would be entered as 1700.
If both the Start and Stop Times are ZERO, the schedule is in a continuous OFF mode. (Use for Remote Signal Contact.)
If both the Start and Stop Times are 2359, the schedule is in a continuous ON mode.
1) Schedule Override
2) Week Schedules
3) Holidays
ESC) Exit Menu
NOTE: The second line displays which day of the week is currently being programmed. The day of the week automatically increments as you exit the Event #2 screen for the day and continue to the next day’s Event #1 screen.
Week Schedules
Event #1
VCM-X / RNE Schd
Sunday Event #1
Start Time..: XXXX
Stop Time...: XXXX
CAUTION: The controller ships with all schedules set to
zero so that the controller will not attempt to heat
or cool before you have confi gured the system.
Holiday Start/Stop Day Selection
Event #2
VCM-X / RNE Schd
Sunday Event #2
Start Time..: XXXX
Stop Time...: XXXX
If you are using the internal scheduling capability of the VCM-X or
RNE Controller, set the schedule hours and holiday periods from the menu shown above. You can also force the unit to operate continuously in occupied or unoccupied mode by selecting the Schedule Override menu item and entering the desired command.
If you are using an external contact closure to signal the occupied mode, you must access the Week Schedule Screens and set all start and stop times to zero to prevent the internal schedule from turning the equipment on when you don’t want it to operate.
VCM-X / RNE Hldy
Holiday # 1
Stop Mon/Day.: XXXX
[ July 5 th
= 705 ]
The screens will step through the fourteen possible holidays, one period at a time. Line 2 shows which holiday is currently being programmed.
Since a holiday period can encompass more than one day, you need to program the day the holiday starts and the day the holiday ends. If your holiday only lasts one day, simply set both the Start Day and the Stop
Day to the same value. Remember to combine the month and day into a single four-digit value.
The screens will step through the Start Time and then the Stop Time for each day of the week. You can quit at any point in the process by
pressing
<ESC>
. There are two Start/Stop events available per day, so the screen will show which event is being programmed. If you need only one event, keep Event #2’s times set at ZERO.
EXAMPLE:
VCM-X / RNE Hldy
Holiday # 1
Start Mon/Day.: XXXX
[ July 4 th
= 704 ]
704 = July 4 th (NOTE: Leading zero not required)
16
VCM-X / RNE Operator Interfaces Technical Guide
INITIALIZATION
Holiday Scheduling and Schedule Override
Holiday Start/Stop Times
VCM-X / RNE Hldy
Holiday Schedule
Start Event #1: XXXX
Stop Event #1: XXXX
Schedule Override
VCM-X / RNE Ovrd
Schedule Override
Enter Override...: X
[0=Auto 1=ON 2=OFF]
VCM-X / RNE Hldy
Holiday Schedule
Start Event #2: XXXX
Stop Event #2: XXXX
If you want to force the unit to operate in a continuous Occupied or
Unoccupied mode, select this menu item to activate the desired method.
If a Schedule Override is active, all other methods of schedule control are ignored (Push-Button, Internal, and Remote).
As you can see on the last line of the display, enter
<1>
to run continuously in the Occupied Mode or
<2>
to run continuously in the Unoc-
cupied Mode. To restore normal schedule operations, enter
<0>
.
The fourteen holidays all use the same Start and Stop times which you program on this screen and the next. You must enter the time in 24-hour military format, the same as a regular week schedule.
This override remains in effect until canceled and does not time-out like the Output Overrides do after 10 minutes of no communications.
Normally, the holidays will operate in an unoccupied mode or a reduced schedule mode. There are two start/stop events available on holidays to match the standard schedule number of events.
NOTE: Do not use the Force OFF mode in place of setting all the week schedules to ZERO if you are using a Remote
Signal for your scheduling since the Override has priority over the Remote Signal.
VCM-X / RNE Operator Interfaces Technical Guide
17
VCM-X CONFIGURATION
VCM-X Confi guration Screen Index
VCM-X Confi guration Screen Index
The available Confi guration Screens for the VCM-X Controller are listed on the next few pages by sequential screen number. When each
VCM-X Controller is confi gured for the fi rst time, it is best to start with screen #1 and proceed to each screen in numerical order until you have viewed all available Confi guration Screens. This ensures that you have seen all the available VCM-X Controller confi guration possibilities and have the opportunity to change or accept the defaults for each screen.
Once the unit is confi gured and you decide to change one of the screen options, it is helpful to know what screen number contains the confi guration you wish to change. With this in mind, the following is a list of all the VCM-X Confi guration Screens in numerical order with a brief listing of the confi guration feature available on each screen.
Screen #1 Duct Static Pressure Control
Screen #2 Supply Fan Cycle Mode
Screen #3 HVAC Mode Enable
Screen #4 HVAC Reset Source
Screen #5 Reset Interval Rate
Screen #6 Dehumidifi cation Control
Screen #7 Dehumidifi cation Priority
Screen #8 Dehumidifi cation Unoccupied
Screen #9 Outdoor Humidity Sensor
Screen #10 Indoor Humidity Sensor
Screen #11 Heat During Dehumidify
Screen #12 Economizer Control
Screen #13 Proof of Flow Input
Screen #14 Modulating Cooling/Heating
Screen #15 Modulating Heat Output Signal
Screen #16 Modulating Heat Reverse Acting
Screen #17 Modulating Heat Proportional Window
Screen #18 Modulating Cooling Output Signal
Screen #19 Digital Compressor Signal
Screen #20 Modulating Cooling Reverse Acting
Screen #21 Modulating Cool Proportional Window
Screen #22 Head Pressure Module Installed
Screen #23 Full Digital Module Installed/WSHP with
Multiple Digital Scroll Compressors OR
Zone
Zone
Screen #24 Split Condenser (VCM-X Modular/WSHP)
Screen #25 Monitor Outdoor Air CFM
Screen #26 Control Outdoor Air CFM
Screen #27 Outdoor Duct/Damper Size
Screen #28 Monitor Return Air CFM
Screen #29 Return Duct/Damper Size
Screen #30 Monitor Supply Air CFM
Screen #31 Supply Duct/Damper Size
Screen #32 CO
2
Sensor Output Signal
Screen #33 CO
2
Sensor Maximum Scale
Screen #34 Building Pressure Modulating Control
Screen #35 Building Pressure Reverse Acting
Screen #36 Building Pressure Output Signal
Screen #37 Heat Pump Control
Screen #38 Reversing Valve Active For Heat/Cool
Screen #39 Emergency Shutdown Input
Screen #40 Return Air Bypass Control
Screen #41 Broadcast Outdoor Temperature
Screen #42 Broadcast Outdoor Humidity
Screen #43 Broadcast Supply Temperature
Screen #44 Broadcast Status Fan & Heat
Screen #45 Broadcast Internal Time Clock
Screen #46 Broadcast Internal Schedule
Screen #47 Broadcast VAV Boxes Force to Max
Screen #48 Broadcast VAV Boxes Force to Fixed
Screen #49 1 HVAC Unit w/Boxes on Multiple Loops
Screen #50 Unit Uses R410A Refrigerant
Screen #51 Main Fan Maximum Voltage
Screens #52-55 Cooling & Heating Staging Delays
Screens #56-75 Relay Confi guration Screens
18
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Confi guration Screens
In order to correctly set up the VCM-X Controller, you must fi rst confi gure several parameters in regard to the type of HVAC unit and system you have installed. Most of these values and operating parameters are only set once at the initial system setup and are never changed.
Confi guration Screen #3 - HVAC Mode Enable
VCM-X Cnfg ID 59
HVAC Mode Enable
Supply Air
Press “0” to Change
System Manager Instructions
No matter what screen or menu you’re in, press
<SETPOINTS>
. The
Unit Selection Screen will appear, requesting that you enter the unit ID number. Enter the correct unit ID number of the VCM-X Controller you want to confi gure and press
<ENTER>
. You will see the screen shown below.
Enter
<0>
to select the Temperature Sensor that will determine the
Heating, Cooling, or Vent Mode of operation. The selections are:
Supply Air
This is typical for VAV applications. Occupied Cooling
1) Change Setpoint
2) Configure Unit
3) Damper Force
ESC) Exit Menu
Press
<2>
to enter Confi guration Screen #1.
Modular Service Tool Instructions
No matter what screen or menu you’re in, press
<CONFIGURATION>
.
The Unit Selection Screen will appear, requesting that you enter the unit
ID number. Enter the correct unit ID number of the VCM-X Controller you want to confi gure and press
<ENTER>
. You will then see Unit
Confi guration Screen #1.
Confi guration Screen #1 - Duct Static
Pressure
This is for 100% Outdoor Air (MUA) units.
Dehumidifi cation utilizes a Dewpoint Calculation if equipped with an Outdoor Air Humidity Sensor.
This is for any unit that conditions a space and is not 100%
Outdoor air. Occupied/Unoccupied Heating, Cooling, and
Vent Modes of operation.
This selection can be used when an Average Building
Temperature (the Return Air Temperature) needs to determine Heating, Cooling, and Vent Modes of operation.
Supply Air/Tempering
This selection is for VAV “cooling only” applications where because of cold outdoor temperatures, even at minimum damper position, you may need to enable heat to maintain the cooling near its Cooling Supply Air Setpoint. When heat is enabled during this sequence, it will control to a non-adjustable setpoint that is 2ºF less than the Cooling
Supply Air Setpoint. Includes a Morning Warm-up
sequence.
VCM-X Cnfg ID 59
Duct Static Pressure
Control: YES
[0=NO 1=YES]
Confi guration Screen #4 - HVAC Reset Source
If the HVAC unit has a Supply Fan that delivers a Constant Volume of air, enter
<0>
for NO. If the HVAC unit has a Supply Fan that delivers a Variable Volume of Air using a VFD or a Bypass Damper, enter
<1>
for YES. Default is YES.
VCM-X Cnfg ID 59
HVAC Reset Source
No Reset
Press “0” to Change
Confi guration Screen #2 - Supply Fan Cycle
VCM-X Cnfg ID 59
Supply Fan Cycle
Mode: NO
[0=NO 1=YES]
If you want the HVAC unit’s Supply Fan to run during Heating, Cooling, or Dehumidifi cation Modes, enter
<1>
for YES. If you want the
HVAC unit’s Supply Fan to run continuously while in the Occupied
Mode, regardless of the Heating, Cooling, or Dehumidifi cation Modes,
enter
<0>
for NO. Default is NO.
The Supply Air Heating and Cooling Temperature Setpoints can be reset using various input sources. Default is No Reset. Enter
<0>
to change/ select the desired Reset Source for Supply Air Temperature Reset. The
Single Zone VAV option should be selected in applications where the
Supply Fan VFD speed is reset based on the Space Temperature. If you select No Reset, then neither the Supply Air Setpoint nor the Supply
Fan VFD Reset will occur. The selections are:
No Reset
Sp ace Sensor
Return Air Sensor
Remote Reset Signal
Fan VFD Percentage
Outdoor Sensor
Single Zone (SZ) VAV
SZ VAV with CV Heating
VCM-X / RNE Operator Interfaces Technical Guide
19
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Zone
Zone
Confi guration Screen #5 - Reset Interval Rate
Confi guration Screen #9 - Outdoor Humidity
Sensor
VCM-X Cnfg ID 59
Reset Interval
Rate...: 20 s
[1-250 Seconds]
VCM-X Cnfg ID 59
Outdoor Humidity
Sensor: NO
[0=NO 1=YES]
If you selected Space or Return Air Temperature Reset in Screen #4, enter a value in seconds between 1-250. This value determines how fast the Supply Air Temperature Setpoint is adjusted as the Reset Source changes. Default is 20 seconds.
Enter
<1>
for YES if the HVAC unit is equipped with an Outdoor Air
Humidity Sensor. Enter
<0>
for NO. Default is NO.
Confi guration Screen #6 - Dehumidifi cation
Control
Confi guration Screen #10 - Indoor Humidity
Sensor
VCM-X Cnfg ID 59
Dehumidification
Control: NO
[0=NO 1=YES]
VCM-X Cnfg ID 59
Indoor Humidity
Sensor: NO
[0=NO 1=YES]
Enter
<1>
for YES if your system requires Dehumidifi cation Control.
Enter
<0>
for NO. Default is NO.
Enter
<1>
for YES if the HVAC unit is equipped with an Indoor Air
Humidity Sensor. Enter
<0>
for NO. Default is NO.
Confi guration Screen #7 - Dehumidifi cation
Priority
Confi guration Screen #11 - Heat During
Dehumidify
VCM-X Cnfg ID 59
Dehumidification
Priority: NO
[0=NO 1=YES]
VCM-X Cnfg ID 59
Heat During
Dehumidify: NO
[0=NO 1=YES]
Enter
<1>
for YES if Dehumidifi cation is a Priority during the Occupied
Mode. Priority means that the Cooling stages will activate based on Coil
Temperature and Reheat will be used regardless of Heating, Cooling, or
Vent Modes of Operation. Enter
<0>
for NO.
Enter
<1>
for YES if your application needs to use unit heat during
Dehumidifi cation to supplement Reheat. If Reheat is not available, this selection will allow unit heat to operate in place of Reheat. Enter
<0>
for NO. Default is NO.
Confi guration Screen #8 - Dehumidifi cation
Unoccupied
Confi guration Screen #12 - Economizer
Control
VCM-X Cnfg ID 59
Dehumidification
Unoccupied: NO
[0=NO 1=YES]
VCM-X Cnfg ID 59
Economizer
Control: NO
[0=NO 1=YES]
Enter
<1>
for YES if Dehumidifi cation is required during the Unoccupied mode. Unoccupied Dehumidifi cation is activated based on Indoor
Air Humidity only. Enter
<0>
for NO. Default is NO.
Enter
<1>
for YES if the VCM-X is controlling the Economizer. Enter
<0>
for NO. Default is NO.
20
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Confi guration Screen #13 - Proof of Flow Input
Confi guration Screen #16 - Modulating
Heating Reverse Acting
VCM-X Cnfg ID 59
Proof Of Flow
Input: NO
[0=NO 1=YES]
VCM-X Cnfg ID 59
Mod Heating
Rev Acting: NO
[0=NO 1=YES]
Enter
<1>
for YES if the unit is equipped with a Proof of Flow Switch and it is connected to the VCM-X. If selected as YES and the Proof of
Flow Switch is open, only the Supply Fan Relay will be active. If any other relays such as Heating Stages or Cooling Stages are active, they will be deactivated when the Proof of Flow Switch input is lost. Enter
<0>
for NO. Default is NO.
Confi guration Screen #14 - Modulating Cooling/
Heating
VCM-X Cnfg ID 59
Mod Cooling: NO
Mod Heating: NO
[0=NO 1=YES]
Confi guration Screen #18 - Modulating Cooling
Output Signal
VCM-X Cnfg ID 59
Mod Heating
Prop. Window.: 10ºF
Time Period..: 5 s
Enter
<1>
for YES if the HVAC unit is controlling Modulating Heating or Modulating Cooling or both. If your HVAC unit is going to use a Modulating Chilled Water Valve or is equipped with a Digital Compressor, you must select YES for Modulating Cooling. If your HVAC is using a Modulating Hot Water Valve, Modulating Steam Valve, or a
SCR Controlled Electric Heater, you must select YES for Modulating
Heating. This confi guration does not apply to MODGAS using the
MODGAS Controller. Enter
<0>
for NO. Default is NO.
The Modulating Heating Proportional Window is the control range of the Modulating Signal above and below the Active Supply Air Setpoint.
The larger the Modulating Heating Proportional Window, the smaller the signal adjustment per Time Period will be for each ºF the supply air is from the Active Supply Air Temperature Setpoint. The Time Period is the delay before another signal increase or decrease can be made and is user-adjustable. Short Time Periods may cause hunting of the Modulating Signal. Defaults are 10ºF and 5 seconds.
Confi guration Screen #15 - Modulating
Heating Output Signal
Confi guration Screen #17 - Modulating
Heating Proportional Window
VCM-X Cnfg ID 59
Mod Heating
Output Signal.: 0
[0=0-10V 1=2-10V]
Enter
<1>
for YES if the Modulating Heat Source requires 0 VDC to open and 10 VDC to close. Enter
<0>
for NO. Default is NO.
VCM-X Cnfg ID 59
Mod Cooling
Output Signal: 0
[0= 0-10V 1= 2-10V]
Enter
<0>
for a 0-10 VDC signal to a Modulating Cool source such as a Chilled Water Valve. Enter
<1>
for a 2-10 VDC signal to a Chilled
Water Valve. Default is 0.
Enter
<0>
for a 0-10 VDC signal to a Modulating Heat Source such as a Hot Water Valve or SCR Electric Heater. Enter
<1>
for a 2-10 VDC signal to a Hot Water Valve or SCR Electric Heater. Default is 0.
Confi guration Screen #19 - Digital Compressor
Signal
VCM-X Cnfg ID 59
Digital Compressor
Signal 1-5V : NO
[0=NO 1=YES]
Enter
<1>
for YES if the HVAC unit is equipped with a Digital Compressor. Enter
<0>
for NO. Default is NO.
VCM-X / RNE Operator Interfaces Technical Guide
21
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Zone
Zone
Confi guration Screen #20 - Modulating Cooling
Reverse Acting
Confi guration Screen #23 - Full Digital Module/
WSHP w/Multiple Digital Scroll
Compressors OR Dual Digital Module/WSHP w/2 Digital Scroll Compressors Installed
VCM-X Cnfg ID 59
Mod Cooling
Rev Acting: NO
[0=NO 1=YES]
VCMX-M/HP Cnfg ID 102
Full Digital Module
Installed: NO
[0=NO 1=YES]
Enter
<1>
for YES if the Modulating Cooling Source requires 0 VDC to open and 10 VDC to close. You cannot use a Reverse Acting Signal if a Digital Compressor is being used. Enter
<0>
for NO. Default is NO.
Confi guration Screen #21 - Modulating Cooling
Proportional Window
VCM-X Cnfg ID 59
Mod Cooling
Prop. Window.: 10ºF
Time Period..: 30 s
If a VCM-X Modular Controller ( OE332-23-VCMX-MOD-A) or
VCM-X WSHP Controller ( OE332-23-VCMX-WSHP-A) is being used, this screen will appear. Enter
<1>
for YES if you have either a
Full Digital Module installed or if you have a Water Source Heat Pump
Module installed and in both cases all the compressors in the unit are
Digital Scroll Compressors (2 Digital Compressors only or all 4 Digital
Compressors). If you have a combination of Digital Compressors and
Fixed Compressors, enter
<0>
for NO.
VCMX-M/HP Cnfg ID 102
Dual Digital Module
Installed: NO
[0=NO 1=YES]
The Modulating Cooling Proportional Window is the control range of the Modulating Signal above and below the Active Supply Air Setpoint.
The larger the Modulating Cooling Proportional Window, the smaller the signal adjustment per Time Period will be for each ºF the supply air is from the Active Supply Air Temperature Setpoint. The Time Period is the delay before another signal increase or decrease can be made and is user-adjustable. Short Time Periods may cause hunting of the Modulating Signal. Defaults are 10ºF and 30 seconds.
If a VCM-X Modular Controller ( OE332-23-VCMX-MOD-C) or
VCM-X WSHP Controller ( OE332-23-VCMX-WSHP-C) is being used, this screen will appear. Enter
<1>
for YES if you have a Dual Digital
Module installed or if the VCM-X WSHP Controller has two Digital
Scroll Compressors. Enter
<0>
for NO.
Confi guration Screen #22 - Head Pressure
Module Installed
Confi guration Screen #24 - Split Condenser
VCMX-M/HP Cnfg ID 102
Head Pressure
Module Installed: NO
[0=NO 1=YES]
VCMX-M/HP Cnfg ID 102
Is this a
Split Condenser: NO
[0=NO 1=YES]
Enter
<1>
for YES if you have a Head Pressure Module installed. Enter
<0>
for NO. This screen only applies if using the VCM-X Modular or
WSHP Controller. Default is NO.
Enter
<1>
for YES if you have a Split Condenser with two physically separate condenser sections. This requires a Two Condenser Head Pressure Module. Enter
<0>
for NO. This screen only applies if using the
VCM-X or WSHP Modular Controller. Default is NO.
22
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Confi guration Screen #25 - Monitor Outdoor
Air CFM
VCM-X Cnfg ID 59
Monitor Outdoor
Air CFM: NO
[0=NO 1=YES]
Confi guration Screen #29 - Return Duct/
Damper Size
VCM-X Cnfg ID 59
Return Duct/Damper
Size: 0.00
[Area in sq. ft.]
Enter
<1>
for YES if you have an Airfl ow Monitoring station measuring the CFM of the Outdoor airfl ow stream of this unit. Enter
<0>
for
NO. Default is NO.
Confi guration Screen #26 - Control Outdoor
Air CFM
For the controller to properly calculate the return air CFM, you need to
enter the area in square feet of the return air duct/damper. When measuring the return air damper area, be sure to measure the inside dimensions of the damper. The more accurate the measurements, the more accurate the CFM reading will be. This value needs to be accurate to 2 decimal places. Default is 0.00.
VCM-X Cnfg ID 59
Control Outdoor
Air CFM: NO
[0=NO 1=YES]
Enter
<1>
for YES if you want to control the Outdoor Air Damper to a CFM setpoint. Enter
<0>
for NO. Default is NO.
Confi guration Screen #30 - Monitor Supply Air
CFM
VCM-X Cnfg ID 59
Monitor Supply
Air CFM: NO
[0=NO 1=YES]
Confi guration Screen #27 - Outdoor Duct/
Damper Size
Enter
<1>
for YES if you have an airfl ow monitoring station measuring the CFM of the supply airfl ow stream of this unit. Enter
<0>
for NO.
Default is NO.
VCM-X Cnfg ID 59
Outdoor Duct/Damper
Size: 0.00
[Area in sq. ft.]
Confi guration Screen #28 - Monitor Return Air
CFM
Confi guration Screen #31 - Supply Duct/
Damper Size
For the controller to properly calculate the outside air CFM you need to enter the inside area (sq. ft.) of the outdoor air duct/damper. When measuring the outdoor air damper area, be sure to measure the inside dimensions of the damper. The more accurate the measurements, the more accurate the CFM reading will be. This value needs to be accurate to 2 decimal places. Default is 0.00.
VCM-X Cnfg ID 59
Supply Duct/Damper
Size: 0.00
[Area in sq. ft.]
For the controller to properly calculate the supply air CFM, you need to enter the area in square feet of the supply air duct/damper. When measuring the supply duct damper area, be sure to measure the inside dimensions of the damper. The more accurate the measurements, the more accurate the CFM reading will be. This value needs to be accurate to 2 decimal places. Default is 0.00.
VCM-X Cnfg ID 59
Monitor Return
Air CFM: NO
[0=NO 1=YES]
Enter
<1>
for YES if you have an airfl ow monitoring station measuring the CFM of the return airfl ow stream of this unit. Enter
<0>
for NO.
Default is NO.
VCM-X / RNE Operator Interfaces Technical Guide
23
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Zone
Zone
Confi guration Screen #32 - CO
2
Output Signal
Sensor
VCM-X Cnfg ID 59
CO2 Sensor
Output Signal: 0
[0=None 1=mA 2=VDC]
Confi guration Screen #35 - Building Pressure
Reverse Acting
VCM-X Cnfg ID 59
Building Pressure
Rev Acting: NO
[0=NO 1=YES]
The VCM-X needs to know what type of CO
2
sensor signal output is being provided. Enter
<2>
for a 0-10 VDC CO
2 sensor used). Enter
<1>
for a 4-20 mA CO
2 sensor signal (standard
sensor signal. Enter
<0>
if no CO
2
sensor is used. Default is None.
Enter
<1>
for YES if Reverse Acting Building Pressure control is needed. Reverse Acting Building Pressure Control can either be On/
Off or Modulating Control. Modulating Control is normally used for this confi guration. On a drop in Building Pressure, below the Building
Static Pressure Setpoint, the Outdoor Air Damper will modulate open to increase pressure. Enter
<0>
for NO. Default is NO.
Confi guration Screen #33 - CO
2
Maximum Scale
Sensor
Confi guration Screen #36 - Building Pressure
Output Signal
VCM-X Cnfg ID 59
CO2 Sensor Maximum
Scale: 2000 PPM
Enter 0 If No Sensor
Confi guration Screen #34 - Building Pressure
Modulating Control
VCM-X Cnfg ID 59
Building Pressure
Output Signal: 0
[0=0-10V 1=2-10V]
Default is 2000 PPM. The VCM-X needs to know the CO scaling for proper reading of the CO
2
Sensor output. The Standard CO
Sensor should be scaled to 2000 PPM. Enter
<0>
if no CO
2
Sensor
2
2
sensor is used. Default is 2000.
This Screen is used to confi gure the Building Pressure Output Signal voltage needed for your application. You can select either a 0-10 VDC signal (default) or enter
<1>
to make the output signal 2-10 VDC as required by the device you are using to control the pressure. Enter
<0>
for 0-10 VDC. Default is 0.
VCM-X Cnfg ID 59
Building Pressure
Mod Control: NO
[0=NO 1=YES]
Enter
<1>
for YES if Modulating Building Pressure Control is needed.
Modulating Building Pressure Control is used for a VFD Exhaust Fan or a Modulating Exhaust Fan Damper Actuator for Direct Acting Building
Pressure Control. Modulating Building Pressure Control is also used for a modulating outdoor air damper actuator for Reverse Acting Building
Pressure Control. Enter
<0>
for NO if Modulating Building Pressure
Control is not needed when using a Constant Volume Exhaust Fan for
On/Off Control. Default is NO.
Confi guration Screen #37 - Heat Pump Control
VCM-X Cnfg ID 59
Heat Pump
Control: NO
[0=NO 1=YES]
Enter
<1>
for YES if the HVAC unit is a Heat Pump. Enter
<0>
for
NO. Default is NO.
Confi guration Screen #38 - Reversing Valve
Active During Heat/Cool
VCM-X Cnfg ID 59
Rev. Valve Active
For: Cool
[0=Heat 1=Cool]
Enter
<0>
for Heat if your Heat Pump unit activates its Reversing Valve during Heating operation. Enter
<1>
for Cool if your Heat Pump unit activates its Reversing Valve during Cooling operation. Default is Heat.
24
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Confi guration Screen #39 - Emergency
Shutdown Input
VCM-X Cnfg ID 59
Emergency Shutdown
Input: NO
[0=NO 1=YES]
Confi guration Screen #43 - Broadcast Supply
Temperature
VCM-X Cnfg ID 59
Broadcast Supply
Temperature: YES
[0=NO 1=YES]
Enter
<1>
for YES if a Smoke Detector/Firestat or other Emergency
Shutdown input is connected to the binary input. If the Emergency
Shutdown input is active, the Supply Fan, Heating and Cooling Relay
Outputs will be disabled. Enter
<0>
for NO. Default is NO.
This broadcast sends the VCM-X’s Supply Air Temperature to all controllers on its local loop. This broadcast needs to be confi gured on a VAV or Zoning System using the VCM-X with Orion VAV/Zone Controllers.
A network communications device is required in order for this feature to operate. Enter
<1>
for YES or
<0>
to NO. Default is NO.
Confi guration Screen #40 - Return Air Bypass
Control
Confi guration Screen #44 - Broadcast Status
Fan & Heat
VCM-X Cnfg ID 59
Return Air Bypass Control: NO
[0=NO 1=YES]
The VCM-X can broadcast its Outdoor Air Temperature Reading to other HVAC units if they are not equipped with their own Outdoor Air
Temperature sensors. A network communications device is needed in order for this feature to operate. Enter
<1>
for YES - Broadcast Outdoor
Temperature. Enter
<0>
for NO. Default is NO.
VCM-X Cnfg ID 59
Broadcast Status
Fan & Heat: NO
[0=NO 1=YES]
Enter
<1>
for YES if your HVAC unit requires Return Air Bypass
Control for Dehumidifi cation Reheat. Enter
<0>
for NO. Default is NO.
Confi guration Screen #41 - Broadcast OA Temp
This broadcast sends the VCM-X’s Supply Fan and Heating Status to all controllers on its local loop. This broadcast needs to be confi gured on a VAV or Zoning System using the VCM-X with Orion VAV/Zone
Controllers. A network communications device is required in order for this feature to operate. Enter
<1>
for YES or
<0>
for NO. Default is NO.
VCM-X Cnfg ID 59
Broadcast Outdoor
Temperature: NO
[0=NO 1=YES]
Confi guration Screen #45 - Broadcast Internal
Time Clock
VCM-X Cnfg ID 59
Broadcast Internal
Time Clock: NO
[0=NO 1=YES]
Confi guration Screen #42 - Broadcast OA Humidity
VCM-X Cnfg ID 59
Broadcast Outdoor
Humidity: NO
[0=NO 1=YES]
This broadcast sends the time from the VCM-X’s Internal Time Clock to all controllers on its local loop. This broadcast needs to be confi gured on a VAV or Zoning System using the VCM-X with Orion VAV/Zone controllers. A network communications device is required in order for this feature to operate, but can also be used to synchronize all controllers on the local loop. Enter
<1>
for YES or
<0>
for NO. Default is NO.
The VCM-X can broadcast its Outdoor Air Humidity reading to other
HVAC units if they are not equipped with their own Outdoor Air Humidity sensors. A network communications device is required in order for this feature to operate. Enter
<1>
for YES - Broadcast Outdoor
Humidity. Enter
<0>
for NO. Default is NO.
VCM-X / RNE Operator Interfaces Technical Guide
25
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Zone
Zone
Confi guration Screen #46 - Broadcast Internal
Schedule
Confi guration Screen #49 - 1 HVAC Unit with
Boxes on Multiple Loops
VCM-X Cnfg ID 59
Broadcast Internal
Schedule: NO
[0=NO 1=YES]
VCM-X Cnfg ID 59
1 HVAC Unit w/ Boxes
On Multi. Loops: NO
[0=NO 1=YES]
This is always required when you have VAV/Zone controllers connected to this VCM-X Controller. This will broadcast the Occupied and Unoccupied Condition of the VCM-X Controller to all VAV/Zone controllers on the local loop. Enter
<1>
for YES or
<0>
for NO. Default is NO.
Confi guration Screen #47 - Broadcast VAV
Boxes Force to Max
Enter
<1>
for YES to have all broadcasts that have been confi gured on Confi guration Screens 43 through 48 sent to all local loops on the entire system, not just the local loop the VCM-X Controller is on. This is normally only required if you have a large HVAC unit that requires more than the 58 VAV/Zone Controllers normally allowed on the local loop. This allows other VAV/Zone Controllers connected on additional local loops to receive the required broadcasts. This only is allowed when you have a single VCM-X Controller with VAV/Zone Controllers on multiple loops. Other VCM-X or add-on devices may be connected but no other VCM-X with VAV/Zone Controllers can be connected on the system. Enter
<0>
for NO. Default is NO.
VCM-X Cnfg ID 59
Broadcast VAV Boxes
Force To Max: YES
[0=NO 1=YES]
Confi guration Screen #50 - Uses R410A
Refrigerant
This broadcast is to ensure the VAV/Zone Controllers will drive their dampers to the Max Airfl ow Damper Position during Morning Warmup. This is important to allow the proper amount of airfl ow for Heating in the HVAC unit. Enter
<1>
for YES or
<0>
for NO. Default is YES.
VCM-X Cnfg ID 59
Unit Uses R410A
Refrigerant: NO
[0=NO 1=YES]
Confi guration Screen #48 - Broadcast VAV
Boxes Force to Fixed
Enter
<1>
for YES if your HVAC unit uses R410A Refrigerant. Enter
<0>
for NO. Default is 1.
VCM-X Cnfg ID 59
Broadcast VAV Boxes
Force To Fixed: NO
[0=NO 1=YES]
Confi guration Screen #51 - Main Fan
Maximum Voltage
Enter
<1>
for YES to have all VAV/Zone controllers connected to this
VCM-X Controller forced to their “Fixed Airfl ow” Position during the
Morning Warm-up Mode of operation. Enter
<0>
for YES if you do not want this to occur. See the VAV/Zone controller Setpoint Screens for setting of the “Fixed Airfl ow” position. Default is NO.
VCM-X Cnfg ID 59
Max Main Fan Aout
Voltage: XX.X VDC
Enter a value between 0.0 and 10.0 VDC for the main fan’s maximum output voltage. The Static Pressure and Output % Status Screen will display 0% to 100%, but the output will range from 0 VDC to the value set in this screen. Default is 0 VDC.
This screen will appear if using a If a VCM-X Modular Controller ( OE332-23-VCMX-MOD-A or OE332-23-VCMX-MOD-C) or
VCM-X WSHP Controller ( OE332-23-VCMX-WSHP-A or OE332-
23-VCMX-WSHP-C).
26
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Confi guration Screens #52-55 - Cooling &
Heating Stage Delays
VCM-X Cnfg ID 59
Cooling Stage Delays
Staging Up...: 3 Min
Staging Down : 1 Min
Confi guration Screens #56-75 - Relay
Confi guration Screens
VCM-X Cnfg ID 59
Relay Configurations
Rly xx: Not Used
Press “0” To Change
VCM-X Cnfg ID 59
Cooling Stage Delays
Min Run Time: 5 Min
Min Off Time: 3 Min
Relay #1 is not confi gurable as it is reserved for the Supply Air Fan.
Relays #2-#21 are confi gurable for the following options:
• •
•
VCM-X Cnfg ID 59
Heating Stage Delays
Staging Up...: 3 Min
Staging Down : 1 Min
•
•
• •
OA Damper
HGR
•
VCM-X Cnfg ID 59
Heating Stage Delays
Min Run Time: 2 Min
Min Off Time: 1 Min
Both the Heating Stages and the DX Cooling Stages utilize Staging Up and Down Delay Periods between stages and Minimum Run Times and Off Times.
Both modes have their own set of Staging and Run Delay Times. The
Heating Timer Screens look exactly the same as the Cooling Timer
Screens except they reference the Heating settings instead of the Cooling settings.
• •
Relays #2 through #21 can be individually confi gured. By using the 4 relay outputs available on the VCM-X Controller, the 4 relays on the
VCM-X Expansion Module, and the 12 relays on the 12 Relay Expansion
Module, you have the ability to confi gure up to a combined total of 20
Heating Stages, Cooling Stages, and the rest of the options listed above.
Only the Heating and Cooling relays can be confi gured with multiple outputs. If any other option is selected more than once, it will simply activate redundant relays, but no multiple staging will occur. Default is
“Not Used.”
See the Sequence of Operation Manual for information on how these
Delays and Run Times are used.
Description
Cooling Stage Up
Cooling Stage Down
Cooling Min Run Time
Cooling Min Off Time
Heating Stage Up
Heating Stage Down
Heating Min Run Time
Heating Min Off Time
Minimum
3 Min
1 Min
5 Min
3 Min
3 Min
1 Min
2 Min
1 Min
Default
3 Min
1 Min
5 Min
3 Min
3 Min
1 Min
2 Min
1 Min
Maximum
15 Min
15 Min
15 Min
15 Min
15 Min
15 Min
15 Min
15 Min
VCM-X / RNE Operator Interfaces Technical Guide
27
RNE CONFIGURATION
RNE Confi guration Screen Index
RNE Confi guration Screen Index
The available Confi guration Screens for the RNE Controller are listed on the next few pages by sequential screen number. When each RNE
Controller is confi gured for the fi rst time, it is best to start with screen
#1 and proceed to each screen in numerical order until you have viewed all available Confi guration Screens. This ensures that you have seen all the available RNE Controller confi guration possibilities and have the opportunity to change or accept the defaults for each screen.
Once the unit is confi gured and you decide to change one of the screen options, it is helpful to know what screen number contains the confi guration you wish to change. With this in mind, the following is a list of all the RNE Controller Confi guration Screens in numerical order with a brief listing of the confi guration feature available on each screen.
Screen #1 Duct Static Pressure Control
Screen #2 Supply Fan Cycle Mode
Screen #3 HVAC Mode Enable
Screen #4 HVAC Reset Source
Screen #5 Reset Interval Rate
Screen #6 Dehumidifi cation Control
Screen #7 Dehumidifi cation Priority
Screen #8 Dehumidifi cation Unoccupied
Screen #9 Outdoor Humidity Sensor
Screen #10 Indoor Humidity Sensor
Screen #11 Heat During Dehumidify
Screen #12 Economizer Control
Screen #13 Proof of Flow Input
Screen #14 Modulating Cooling/Heating
Screen #15 Modulating Heat Output Signal
Screen #16 Modulating Heat Reverse Acting
Screen #17 Modulating Heat Proportional Window
Screen #18 Modulating Cooling Type
Screen #19 RNE Tonnage
Screen #20 Water Source Heat Pump Installed
Screen #21 Modulating Cooling Reverse Acting
Screen #22 Modulating Cool Proportional Window
Screen #23 Head Pressure Module Installed
Screen #24 Monitor Outdoor Air CFM
Screen #25 Control Outdoor Air CFM
Screen #26 Outdoor Duct/Damper Size
Screen #27 Monitor Return Air CFM
Screen #28 Return Duct/Damper Size
Screen #29 Monitor Supply Air CFM
Screen #30 Supply Duct/Damper Size
Screen #31 CO
2
Sensor Output Signal
Screen #32 CO
2
Sensor Maximum Scale
Screen #33 Building Pressure Modulating Control
Screen #34 Building Pressure Reverse Acting
Screen #35 Building Pressure Output Signal
Screen #36 Heat Pump Control
Screen #37 Reversing Valve Active For Heat/Cool
Screen #38 Emergency Shutdown Input
Screen #39 Return Air Bypass Control
Screen #40 Broadcast Outdoor Temperature
Screen #41 Broadcast Outdoor Humidity
Screen #42 Broadcast Supply Temperature
Screen #43 Broadcast Status Fan & Heat
Screen #44 Broadcast Internal Time Clock
Screen #45 Broadcast Internal Schedule
Screen #46 Broadcast VAV Boxes Force to Max
Screen #47 Broadcast VAV Boxes Force to Fixed
Screen #48 1 HVAC Unit w/Boxes on Multiple Loops
Screen #49 Unit Uses R410A Refrigerant
Screen #50 Main Fan Maximum Voltage
Screens #51-54 Cooling & Heating Staging Delays
Screens #54-74 Relay Confi guration Screens
28
VCM-X / RNE Operator Interfaces Technical Guide
RNE CONFIGURATION
RNE Confi guration Screens
Confi guration Screens
In order to correctly set up the RNE Controller, you must fi rst confi gure several parameters in regard to the type of HVAC unit and system you have installed. Most of these values and operating parameters are only set once at the initial system setup and are never changed.
Confi guration Screen #3 - HVAC Mode Enable
RNE Cnfg ID 101
HVAC Mode Enable
Supply Air
Press “0” to Change
No matter what screen or menu you’re in, press
<CONFIGURATION>
.
The Unit Selection Screen will appear, requesting that you enter the unit ID number.
Unit Selection
Enter Unit ID#
Selected ID#: XXXX
Enter
<0>
to select the Temperature Sensor that will determine the Heating, Cooling, or Vent Mode of operation. The selections are:
Supply Air
This is typical for VAV applications. Occupied Cooling
Enter the correct unit ID number of the RNE Controller you want to confi gure and press
<ENTER>
. You will then see Unit Confi guration
Screen #1.
Confi guration Screen #1 - Duct Static
Pressure
RNE Cnfg ID 101
Duct Static Pressure
Control: YES
[0=NO 1=YES]
If the HVAC unit has a Supply Fan that delivers a Constant Volume of air, enter
<0>
for NO. If the HVAC unit has a Supply Fan that delivers a Variable Volume of Air using a VFD or a Bypass Damper, enter
<1>
for YES. Default is YES.
This is for 100% Outdoor Air (MUA) units.
Dehumidifi cation utilizes a Dewpoint Calculation if equipped with an Outdoor Air Humidity Sensor.
This is for any unit that conditions a space and is not 100%
Outdoor air. Occupied/Unoccupied Heating, Cooling, and
Vent Modes of operation.
This selection can be used when an Average Building
Temperature (the Return Air Temperature) needs to determine Heating, Cooling, and Vent Modes of operation.
Supply Air/Tempering
This selection is for VAV “cooling only” applications where because of cold outdoor temperatures, even at minimum damper position, you may need to enable heat to maintain the cooling near its Cooling Supply Air Setpoint. When heat is enabled during this sequence, it will control to a non-adjustable setpoint that is 2ºF less than the Cooling
Supply Air Setpoint. Includes a Morning Warm-up
sequence.
Confi guration Screen #2 - Supply Fan Cycle
RNE Cnfg ID 101
Supply Fan Cycle
Mode: NO
[0=NO 1=YES]
Confi guration Screen #4 - HVAC Reset Source
RNE Cnfg ID 101
HVAC Reset Source
No Reset
Press “0” to Change
If you want the HVAC unit’s Supply Fan to run during Heating, Cooling, or Dehumidifi cation Modes, enter
<1>
for YES. If you want the
HVAC unit’s Supply Fan to run continuously while in the Occupied
Mode, regardless of the Heating, Cooling, or Dehumidifi cation Modes,
enter
<0>
for NO. Default is NO.
The Supply Air Heating and Cooling Temperature Setpoints can be reset using various input sources. Default is No Reset. Press
<0>
to change/ select the desired Reset Source for Supply Air Temperature Reset. The
Single Zone VAV option should be selected in applications where the
Supply Fan VFD speed is reset based on the Space Temperature. If you select No Reset, then neither the Supply Air Setpoint nor the Supply
Fan VFD Reset will occur. The selections are:
No Reset
Sp ace Sensor
Return Air Sensor
Remote Reset Signal
Fan VFD Percentage
Outdoor Sensor
Single Zone (SZ) VAV
SZ VAV with CV Heating
VCM-X / RNE Operator Interfaces Technical Guide
29
RNE CONFIGURATION
RNE Confi guration Screens
Confi guration Screen #5 - Reset Interval Rate Confi guration Screen #9 - Outdoor Humidity
Sensor
RNE Cnfg ID 101
Reset Interval
Rate...: 20 s
[1-250 Seconds]
RNE Cnfg ID 101
Outdoor Humidity
Sensor: NO
[0=NO 1=YES]
If you selected Space or Return Air Temperature Reset in Screen #4, enter a value in seconds between 1-250. This value determines how fast the Supply Air Temperature Setpoint is adjusted as the Reset Source changes. Default is 20 seconds.
Enter
<1>
for YES if the HVAC unit is equipped with an Outdoor Air
Humidity Sensor. Enter
<0>
for NO. Default is NO.
Confi guration Screen #6 - Dehumidifi cation
Control
Confi guration Screen #10 - Indoor Humidity
Sensor
RNE Cnfg ID 101
Dehumidification
Control: NO
[0=NO 1=YES]
RNE Cnfg ID 101
Indoor Humidity
Sensor: NO
[0=NO 1=YES]
Enter
<1>
for YES if your system requires Dehumidifi cation Control.
Enter
<0>
for NO. Default is NO.
Enter
<1>
for YES if the HVAC unit is equipped with an Indoor Air
Humidity Sensor. Enter
<0>
for NO. Default is NO.
Confi guration Screen #7 - Dehumidifi cation
Priority
Confi guration Screen #11 - Heat During
Dehumidify
RNE Cnfg ID 101
Dehumidification
Priority: NO
[0=NO 1=YES]
RNE Cnfg ID 101
Heat During
Dehumidify: NO
[0=NO 1=YES]
Enter
<1>
for YES if Dehumidifi cation is a Priority during the Occupied
Mode. Priority means that the Cooling stages will activate based on Coil
Temperature and Reheat will be used regardless of Heating, Cooling, or
Vent Modes of Operation. Enter
<0>
for NO.
Enter
<1>
for YES if your application needs to use unit heat during
Dehumidifi cation to supplement Reheat. If Reheat is not available, this selection will allow unit heat to operate in place of Reheat. Enter
<0>
for NO. Default is NO.
Confi guration Screen #8 - Dehumidifi cation
Unoccupied
Confi guration Screen #12 - Economizer
Control
RNE Cnfg ID 101
Dehumidification
Unoccupied: NO
[0=NO 1=YES]
RNE Cnfg ID 101
Economizer
Control: NO
[0=NO 1=YES]
Enter
<1>
for YES if Dehumidifi cation is required during the Unoccupied mode. Unoccupied Dehumidifi cation is activated based on Indoor
Air Humidity only. Enter
<0>
for NO. Default is NO.
Enter
<1>
for YES if the RNE is controlling the Economizer. Enter
<0>
for NO. Default is NO.
30
VCM-X / RNE Operator Interfaces Technical Guide
RNE CONFIGURATION
RNE Confi guration Screens
Confi guration Screen #13 - Proof of Flow Input Confi guration Screen #16 - Modulating
Heating Reverse Acting
RNE Cnfg ID 101
Proof Of Flow
Input: NO
[0=NO 1=YES]
RNE Cnfg ID 101
Mod Heating
Rev Acting: NO
[0=NO 1=YES]
Enter
<1>
for YES if the unit is equipped with a Proof of Flow Switch and it is connected to the RNE. If selected as YES and the Proof of
Flow Switch is open, only the Supply Fan Relay will be active. If any other relays such as Heating Stages or Cooling Stages are active, they will be deactivated when the Proof of Flow Switch input is lost. Enter
<0>
for NO. Default is NO.
Enter
<1>
for YES if the Modulating Heat Source requires 0 VDC to open and 10 VDC to close. Enter
<0>
for NO. Default is NO.
Confi guration Screen #17 - Modulating
Heating Proportional Window
Confi guration Screen #14 - Modulating Cooling/
Heating
RNE Cnfg ID 101
Mod Cooling: NO
Mod Heating: NO
[0=NO 1=YES]
RNE Cnfg ID 101
Mod Heating
Prop. Window.: 10ºF
Time Period..: 5 s
Enter
<1>
for YES if the HVAC unit is controlling Modulating Heating or Modulating Cooling or both. If your HVAC unit is going to use a
Modulating Chilled Water Valve or is equipped with a VFD Compressor, you must select YES for Modulating Cooling. If your HVAC is using a
Modulating Hot Water Valve, Modulating Steam Valve, or a SCR Controlled Electric Heater, you must select YES for Modulating Heating.
This confi guration does not apply to MODGAS using the MODGAS
II Controller. Enter
<0>
for NO. Default is NO.
The Modulating Heating Proportional Window is the control range of the Modulating Signal above and below the Active Supply Air Setpoint.
The larger the Modulating Heating Proportional Window, the smaller the signal adjustment per Time Period will be for each ºF the supply air is from the Active Supply Air Temperature Setpoint. The Time Period is the delay before another signal increase or decrease can be made and is user-adjustable. Short Time Periods may cause hunting of the Modulating Signal. Defaults are 10ºF and 5 seconds.
Confi guration Screen #18 - Modulating Cooling
Type
Confi guration Screen #15 - Modulating
Heating Output Signal
RNE Cnfg ID 101
Mod Heating
Output Signal.: 0
[0=0-10V 1=2-10V]
RNE Cnfg ID 101
Mod Cooling Type
None
[Press ‘0’ to Change]
Enter
<0>
for a 0-10 VDC signal to a Modulating Heat Source such as a Hot Water Valve or SCR Electric Heater. Enter
<1>
for a 2-10 VDC signal to a Hot Water Valve or SCR Electric Heater. Default is 0.
Press
<0>
to change/select the desired Modulating Cooling Type. Default is None. The selections are:
None
VFD Full
2-10 VDC CW
VFD Half
0-10 VDC CW
VCM-X / RNE Operator Interfaces Technical Guide
31
RNE CONFIGURATION
RNE Confi guration Screens
Confi guration Screen #19 - RNE Tonnage Confi guration Screen #23 - Head Pressure
Module Installed
RNE Cnfg ID 101
RNE Tonnage
55–75 Tons
[Press ‘0’ to Change]
VCMX-M/HP Cnfg ID 102
Head Pressure
Module Installed: NO
[0=NO 1=YES]
Press
<0>
to change/select the desired Tonnage. Default is 55–75 Tons.
The selections are:
55–75 Tons
120–140 Tons
95–105 Tons
Enter
<1>
for YES if you have a Head Pressure Module installed.
Enter
<0>
for NO. This screen only applies if using the RNE Modular or WSHP Controller. Default is NO.
Confi guration Screen #20 - Water Source Heat
Pump Installed
Confi guration Screen #24 - Monitor Outdoor
Air CFM
RNE Cnfg ID 101
Water Source
Heat Pump: NO
[0=NO 1=YES]
RNE Cnfg ID 101
Monitor Outdoor
Air CFM: NO
[0=NO 1=YES]
Enter
<1>
for YES if this is a Water Source Heat Pump. Enter
<0>
for
NO. Default is NO.
Enter
<1>
for YES if you have an Airfl ow Monitoring station measuring the CFM of the Outdoor airfl ow stream of this unit. Enter
<0>
for
NO. Default is NO.
Confi guration Screen #21 - Modulating Cooling Reverse Acting
Confi guration Screen #25 - Control Outdoor
Air CFM
RNE Cnfg ID 101
Mod Cooling
Rev Acting: NO
[0=NO 1=YES]
RNE Cnfg ID 101
Control Outdoor
Air CFM: NO
[0=NO 1=YES]
Enter
<1>
for YES if the Modulating Cooling Source requires 0 VDC to open and 10 VDC to close. You cannot use a Reverse Acting Signal if a VFD Compressor is being used. Enter
<0>
for NO. Default is NO.
Enter
<1>
for YES if you want to control the Outdoor Air Damper to a CFM setpoint. Enter
<0>
for NO. Default is NO.
Confi guration Screen #22 - Modulating Cooling Proportional Window
RNE Cnfg ID 101
Mod Cooling
Prop. Window.: 10ºF
Time Period..: 30 s
Confi guration Screen #26 - Outdoor Duct/
Damper Size
RNE Cnfg ID 101
Outdoor Duct/Damper
Size: 0.00
[Area in sq. ft.]
The Modulating Cooling Proportional Window is the control range of the Modulating Signal above and below the Active Supply Air Setpoint.
The larger the Modulating Cooling Proportional Window, the smaller the signal adjustment per Time Period will be for each ºF the supply air is from the Active Supply Air Temperature Setpoint. The Time Period is the delay before another signal increase or decrease can be made and is user-adjustable. Short Time Periods may cause hunting of the
Modulating Signal. Defaults are 10ºF and 30 seconds.
For the Controller to properly calculate the outside air CFM you need to enter the inside area (sq. ft.) of the outdoor air duct/damper. When measuring the outdoor air damper area, be sure to measure the inside dimensions of the damper. The more accurate the measurements, the more accurate the CFM reading will be. This value needs to be accurate to 2 decimal places. Default is 0.00.
32
VCM-X / RNE Operator Interfaces Technical Guide
RNE CONFIGURATION
RNE Confi guration Screens
Confi guration Screen #27 - Monitor Return Air
CFM
Confi guration Screen #30 - Supply Duct/
Damper Size
RNE Cnfg ID 101
Monitor Return
Air CFM: NO
[0=NO 1=YES]
RNE Cnfg ID 101
Supply Duct/Damper
Size: 0.00
[Area in sq. ft.]
Enter
<1>
for YES if you have an airfl ow monitoring station measuring the CFM of the return airfl ow stream of this unit. Enter
<0>
for NO.
Default is NO.
Confi guration Screen #28 - Return Duct/
Damper Size
For the Controller to properly calculate the supply air CFM, you need to enter the area in square feet of the supply air duct/damper. When measuring the supply duct damper area, be sure to measure the inside dimensions of the damper. The more accurate the measurements, the more accurate the CFM reading will be. This value needs to be accurate to 2 decimal places. Default is 0.00.
RNE Cnfg ID 101
Return Duct/Damper
Size: 0.00
[Area in sq. ft.]
Confi guration Screen #31 - CO
Output Signal
2
Sensor
For the Controller to properly calculate the return air CFM, you need to
enter the area in square feet of the return air duct/damper. When measuring the return air damper area, be sure to measure the inside dimensions of the damper. The more accurate the measurements, the more accurate the CFM reading will be. This value needs to be accurate to 2 decimal places. Default is 0.00.
RNE Cnfg ID 101
CO2 Sensor
Output Signal: 0
[0=None 1=mA 2=VDC]
The RNE needs to know what type of CO provided. Enter
<2>
for a 0-10 VDC CO
2
2
sensor signal output is being sensor signal (standard sensor used). Enter
<1>
for a 4-20 mA CO
2
sensor signal. Enter
<0>
if no CO
2 sensor is used. Default is None.
Confi guration Screen #29 - Monitor Supply Air
CFM
Confi guration Screen #32 - CO
2
Maximum Scale
Sensor
RNE Cnfg ID 101
Monitor Supply
Air CFM: NO
[0=NO 1=YES]
RNE Cnfg ID 101
CO2 Sensor Maximum
Scale: 2000 PPM
Enter 0 If No Sensor
Enter
<1>
for YES if you have an airfl ow monitoring station measuring the CFM of the supply airfl ow stream of this unit. Enter
<0>
for NO.
Default is NO.
Default is 2000 PPM. The RNE needs to know the CO
2
Sensor scaling for proper reading of the CO
2
Sensor output. The Standard CO
2
Sensor should be scaled to 2000 PPM. Enter
<0>
if no CO
2
sensor is used.
Default is 2000.
VCM-X / RNE Operator Interfaces Technical Guide
33
RNE CONFIGURATION
RNE Confi guration Screens
Confi guration Screen #33 - Building Pressure
Modulating Control
Confi guration Screen #36 - Heat Pump Control
RNE Cnfg ID 101
Building Pressure
Mod Control: NO
[0=NO 1=YES]
RNE Cnfg ID 101
Heat Pump
Control: NO
[0=NO 1=YES]
Enter
<1>
for YES if Modulating Building Pressure Control is needed.
Modulating Building Pressure Control is used for a VFD Exhaust Fan or a Modulating Exhaust Fan Damper Actuator for Direct Acting Building
Pressure Control. Modulating Building Pressure Control is also used for a modulating outdoor air damper actuator for Reverse Acting Building
Pressure Control. Enter
<0>
for NO if Modulating Building Pressure
Control is not needed when using a Constant Volume Exhaust Fan for
On/Off Control. Default is NO.
Enter
<1>
for YES if the HVAC unit is a Heat Pump. Enter
<0>
for
NO. Default is NO.
Confi guration Screen #37 - Reversing Valve
Active During Heat/Cool
RNE Cnfg ID 101
Rev. Valve Active
For: Cool
[0=Heat 1=Cool]
Confi guration Screen #34 - Building Pressure
Reverse Acting
RNE Cnfg ID 101
Building Pressure
Rev Acting: NO
[0=NO 1=YES]
Enter
<1>
for YES if Reverse Acting Building Pressure control is needed. Reverse Acting Building Pressure Control can either be On/
Off or Modulating Control. Modulating Control is normally used for this confi guration. On a drop in Building Pressure, below the Building
Static Pressure Setpoint, the Outdoor Air Damper will modulate open to increase pressure. Enter
<0>
for NO. Default is NO.
Enter
<0>
for Heat if your Heat Pump unit activates its Reversing Valve during Heating operation. Enter
<1>
for Cool if your Heat Pump unit activates its Reversing Valve during Cooling operation. Default is Heat.
Confi guration Screen #38 - Emergency
Shutdown Input
RNE Cnfg ID 101
Emergency Shutdown
Input: NO
[0=NO 1=YES]
Confi guration Screen #35 - Building Pressure
Output Signal
RNE Cnfg ID 101
Building Pressure
Output Signal: 0
[0=0-10V 1=2-10V]
This Screen is used to confi gure the Building Pressure Output Signal voltage needed for your application. You can select either a 0-10 VDC signal (default) or enter
<1>
to make the output signal 2-10 VDC as required by the device you are using to control the pressure. Enter
<0>
for 0-10 VDC. Default is 0.
Enter
<1>
for YES if a Smoke Detector/Firestat or other Emergency
Shutdown input is connected to the binary input. If the Emergency
Shutdown input is active, the Supply Fan, Heating and Cooling Relay
Outputs will be disabled. Enter
<0>
for NO. Default is NO.
Confi guration Screen #39 - Return Air Bypass
Control
RNE Cnfg ID 101
Return Air Bypass Control: NO
[0=NO 1=YES]
Enter
<1>
for YES if your HVAC unit requires Return Air Bypass
Control for Dehumidifi cation Reheat. Enter
<0>
for NO. Default is NO.
34
VCM-X / RNE Operator Interfaces Technical Guide
RNE CONFIGURATION
RNE Confi guration Screens
Confi guration Screen #40 - Broadcast OA Temp Confi guration Screen #43 - Broadcast Status
Fan & Heat
RNE Cnfg ID 101
Broadcast Outdoor
Temperature: NO
[0=NO 1=YES]
RNE Cnfg ID 101
Broadcast Status
Fan & Heat: NO
[0=NO 1=YES]
The RNE can broadcast its Outdoor Air Temperature Reading to other
HVAC units if they are not equipped with their own Outdoor Air Temperature sensors. A network communications device is needed in order for this feature to operate. Enter
<1>
for YES - Broadcast Outdoor
Temperature. Enter
<0>
for NO. Default is NO.
This broadcast sends the RNE’s Supply Fan and Heating Status to all
Controllers on its local loop. This broadcast needs to be confi gured on a VAV or Zoning System using the RNE with Orion VAV/Zone Controllers. A network communications device is required in order for this feature to operate. Enter
<1>
for YES or
<0>
for NO. Default is NO.
Confi guration Screen #41 - Broadcast OA Humidity
RNE Cnfg ID 101
Broadcast Outdoor
Humidity: NO
[0=NO 1=YES]
Confi guration Screen #42 - Broadcast Supply
Temperature
Confi guration Screen #44 - Broadcast Internal
Time Clock
RNE Cnfg ID 101
Broadcast Internal
Time Clock: NO
[0=NO 1=YES]
The RNE can broadcast its Outdoor Air Humidity reading to other HVAC units if they are not equipped with their own Outdoor Air Humidity sensors. A network communications device is required in order for this feature to operate. Enter
<1>
for YES - Broadcast Outdoor Humidity.
Enter
<0>
for NO. Default is NO.
This broadcast sends the time from the RNE’s Internal Time Clock to all
Controllers on its local loop. This broadcast needs to be confi gured on a
VAV or Zoning System using the RNE with Orion VAV/Zone Controllers.
A network communications device is required in order for this feature to operate, but can also be used to synchronize all Controllers on the local loop. Enter
<1>
for YES or
<0>
for NO. Default is NO.
RNE Cnfg ID 101
Broadcast Supply
Temperature: YES
[0=NO 1=YES]
Confi guration Screen #45 - Broadcast Internal
Schedule
This broadcast sends the RNE’s Supply Air Temperature to all Controllers on its local loop. This broadcast needs to be confi gured on a VAV or Zoning System using the RNE with Orion VAV/Zone Controllers. A network communications device is required in order for this feature to operate. Enter
<1>
for YES or
<0>
to NO. Default is NO.
RNE Cnfg ID 101
Broadcast Internal
Schedule: NO
[0=NO 1=YES]
This is always required when you have VAV/Zone Controllers connected to this RNE Controller. This will broadcast the Occupied and Unoccupied
Condition of the RNE Controller to all VAV/Zone Controllers on the local loop. Enter
<1>
for YES or
<0>
for NO. Default is NO.
VCM-X / RNE Operator Interfaces Technical Guide
35
RNE CONFIGURATION
RNE Confi guration Screens
Confi guration Screen #46 - Broadcast VAV
Boxes Force to Max
RNE Cnfg ID 101
Broadcast VAV Boxes
Force To Max: YES
[0=NO 1=YES]
Confi guration Screen #49 - Uses R410A
Refrigerant
RNE Cnfg ID 101
Unit Uses R410A
Refrigerant: NO
[0=NO 1=YES]
This broadcast is to ensure the VAV/Zone Controllers will drive their dampers to the Max Airfl ow Damper Position during Morning Warmup. This is important to allow the proper amount of airfl ow for Heating in the HVAC unit. Enter
<1>
for YES or
<0>
for NO. Default is YES.
Enter
<1>
for YES if your HVAC unit uses R410A Refrigerant. Enter
<0>
for NO. Default is 1.
Confi guration Screen #50 - Main Fan
Maximum Voltage
Confi guration Screen #47 - Broadcast VAV
Boxes Force to Fixed
RNE Cnfg ID 101
Max Main Fan Aout
Voltage: XX.X VDC
RNE Cnfg ID 101
Broadcast VAV Boxes
Force To Fixed: NO
[0=NO 1=YES]
Enter
<1>
for YES to have all VAV/Zone Controllers connected to this
RNE Controller forced to their “Fixed Airfl ow” Position during the
Morning Warm-up Mode of operation. Enter
<0>
for YES if you do not want this to occur. See the VAV/Zone Controller Setpoint Screens for setting of the “Fixed Airfl ow” position. Default is NO.
Enter a value between 0.0 and 10.0 VDC for the main fan’s maximum output voltage. The Static Pressure and Output % Status Screen will display 0% to 100%, but the output will range from 0 VDC to the value set in this screen. Default is 0 VDC.
Confi guration Screen #48 - 1 HVAC Unit with
Boxes on Multiple Loops
RNE Cnfg ID 101
1 HVAC Unit w/ Boxes
On Multi. Loops: NO
[0=NO 1=YES]
Enter
<1>
for YES to have all broadcasts that have been confi gured on
Confi guration Screens 42 through 47 sent to all local loops on the entire system, not just the local loop the RNE Controller is on. This is normally only required if you have a large HVAC unit that requires more than the 58 VAV/Zone Controllers normally allowed on the local loop. This allows other VAV/Zone Controllers connected on additional local loops to receive the required broadcasts. This only is allowed when you have a single RNE Controller with VAV/Zone Controllers on multiple loops.
Other RNE or add-on devices may be connected but no other RNE with
VAV/Zone Controllers can be connected on the system. Enter
<0>
for
NO. Default is NO.
36
VCM-X / RNE Operator Interfaces Technical Guide
RNE CONFIGURATION
RNE Confi guration Screens
Confi guration Screens #51-54 - Cooling &
Heating Stage Delays
RNE Cnfg ID 101
Cooling Stage Delays
Staging Up...: 3 Min
Staging Down : 1 Min
Confi guration Screens #55-74 - Relay
Confi guration Screens
RNE Cnfg ID 101
Relay Configurations
Rly xx: Not Used
Press “0” To Change
RNE Cnfg ID 101
Cooling Stage Delays
Min Run Time: 5 Min
Min Off Time: 3 Min
Relay #1 is not confi gurable as it is reserved for the Supply Air Fan.
Relays #2-#21 are confi gurable for the following options:
• •
•
RNE Cnfg ID 101
Heating Stage Delays
Staging Up...: 3 Min
Staging Down : 1 Min
•
•
•
•
OA Damper
HGR
•
RNE Cnfg ID 101
Heating Stage Delays
Min Run Time: 2 Min
Min Off Time: 1 Min
Both the Heating Stages and the DX Cooling Stages utilize Staging Up and Down Delay Periods between stages and Minimum Run Times and Off Times.
Both modes have their own set of Staging and Run Delay Times. The
Heating Timer Screens look exactly the same as the Cooling Timer
Screens except they reference the Heating settings instead of the Cooling settings.
• •
Relays #2 through #21 can be individually confi gured. By using the
4 relay outputs available on the RNE Controller, the 4 relays on the
VCM-X Expansion Module, and the 12 relays on the 12-Relay Expansion Module, you have the ability to confi gure up to a combined total of 20 Heating Stages, Cooling Stages, and the rest of the options listed above. Only the Heating and Cooling relays can be confi gured with multiple outputs. If any other option is selected more than once, it will simply activate redundant relays, but no multiple staging will occur.
Default is “Not Used.”
See the Sequence of Operation Manual for information on how these
Delays and Run Times are used.
Description
Cooling Stage Up
Cooling Stage Down
Cooling Min Run Time
Cooling Min Off Time
Heating Stage Up
Heating Stage Down
Heating Min Run Time
Heating Min Off Time
Minimum
3 Min
1 Min
5 Min
3 Min
3 Min
1 Min
2 Min
1 Min
Default
3 Min
1 Min
5 Min
3 Min
3 Min
1 Min
2 Min
1 Min
Maximum
15 Min
15 Min
15 Min
15 Min
15 Min
15 Min
15 Min
15 Min
VCM-X / RNE Operator Interfaces Technical Guide
37
VCM-X / RNE SETPOINTS
VCM-X / RNE Setpoint Screen Index
Setpoints - General Procedures
System Manager Instructions
From any menu screen, press
<SETPOINTS>
. The Unit Selection
Screen will appear requesting that you enter the unit ID number. Enter the correct unit ID number of the VCM-X Controller you want to change
Setpoints for and press
<ENTER>
. You will see the screen shown below.
1) Change Setpoint
2) Configure Unit
3) Damper Force
ESC) Exit Menu
Enter
<1>
on the keypad to display the fi rst unit Setpoint screen.
Modular Service Tool Instructions
From any menu screen, press
<SETPOINTS>
. The Unit Selection
Screen will appear requesting that you enter the unit ID number. Enter the correct unit ID number of the VCM-X or RNE Controller you want to change Setpoints for and press
<ENTER>
. You will then see
Setpoint Screen #1.
Setpoint Screen Index
The available Setpoint Screens for the VCM-X or RNE Controller are listed on the next few pages by sequential screen number. When each
VCM-X or RNE Controller is confi gured for the fi rst time, it is best to start with screen #1 and proceed to each Setpoint Screen in numerical order until you have viewed all available Setpoint Screens. This ensures that you have seen all of the available VCM-X or RNE Controller
Setpoint possibilities and have the opportunity to change or accept the defaults for each screen. Once the unit Setpoints are confi gured and you decide to change one of the screen options, it is helpful to know what screen number contains the confi guration you wish to change. With this in mind, the following is a list of all the VCM-X or RNE Setpoint
Screens in numerical order with a brief listing of the Setpoint feature available on each screen:
Setpoint Screen #1 HVAC Mode Setpoints
Setpoint Screen #2 HVAC Mode Select Deadband
Setpoint Screen #3 Unoccupied Setbacks
Setpoint Screen #4 SAT Cooling Setpoints
Setpoint Screen #5 Cool Reset Source Setpoints
Setpoint Screen #6 SAT Heating Setpoints
Setpoint Screen #7 Heat Reset Source Setpoints
Setpoint Screen #8 Stage Control Window
Setpoint Screen #9 Outdoor Air Lockouts
Setpoint Screen #10 Cutoff Temperatures Lo SAT
Setpoint Screen #11 Minimum Supply Fan VFD Speed
Setpoint Screen #12 Morning Warm-up Target Temp &
Setpoint Screen #13 Dehumidifi cation Indoor RH & OA
Dewpoint
Setpoint Screen #14 Dehumidifi cation Coil Temperature
Setpoint Screen #15 Cooling Head Pressure Setpoint
RNE)
Setpoint Screen #16 Reheat Head Pressure Setpoint
RNE)
Setpoint Screen #17 Economizer Setpoints OAT/WB Enable
Setpoint Screen #18 Economizer Setpoints Min Position &
Setpoint Screen #19 Outdoor Air CFM Min & Max Control
Setpoint Screen #20 Outdoor Air CFM Deadband
Setpoint Screen #21 Maximum Economizer Position if High
CO
2
Level Occurs
Setpoint Screen #22 CO
2
Protection Limit Max Level &
Setpoint Screen #23 Static Setpoint, Deadband & Control
Rate
Setpoint Screen #24 Building Pressure Setpoint & Deadband
Setpoint Screen #25 Return Air Bypass Damper Factor
Setpoint
Setpoint Screen #26 Fan Starting Delay Timer
Setpoint Screen #27 Mechanical Heat Cool Failures Occur
After For
Setpoint Screen #28 Preheat/Low Ambient Temperature
Setpoint Screen #29 Max OA Damper Tempering Limit
Setpoint Screen #30 HVAC Schedule
Setpoint Screen #31 Push-Button Override Duration
Setpoint Screen #32 HVAC Mode Sensor Slide Offset
Setpoint Screen #33 Heat Pump Auxiliary Heating Delay
Setpoint Screen #34 Heat Pump Defrost Temp and
Setpoint Screen #35 Adaptive Defrost Adjustment
Setpoint Screen #36 Heat Wheel Defrost
Setpoint Screen #37 Internal Schedule Optimal Start Soak
Multiplier
Setpoint Screen #38 Trend Log Interval
Setpoint Screen #39 Sensor Calibration For SPC & SAT
Setpoint Screen #40 Sensor Calibration For RAT & OAT
Setpoint Screen #41 Sensor Calibration For Coil
38
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X / RNE SETPOINTS
VCM-X / RNE Setpoint Screens
Setpoint Screen #1 - HVAC Mode Setpoints
VCM-X / RNE Spts
HVAC Mode Setpoints
Cooling......: 75ºF
Heating......: 70ºF
Setpoint Screen #4 - SAT Cooling Setpoints
VCM-X / RNE Spts
SAT Cooling Spts
Cooling..: 55ºF
Rst Limit: 55ºF
These Setpoints are used to determine the Heating, Cooling, or Vent
Modes of operation in reference to the HVAC Mode Enable Sensor.
If the Supply Air Sensor is confi gured to be the HVAC Mode Enable, these Setpoints are used in conjunction with the Unoccupied Setbacks if equipped with a Space Temperature Sensor.
Description
HVAC Mode Setpoints Cooling
HVAC Mode Setpoints Heating
Minimum Default Maximum
0ºF 75ºF 99ºF
0ºF 70ºF 99ºF
If no Reset Source has been confi gured in Confi guration Screen #4, then this setpoint will be the Supply Air Temperature Cooling Setpoint. Line
4 will be blank. If a Reset Source has been confi gured in Confi guration
Screen #4, then Line 4 will read Rst Limit. Reset is always upward from the SAT setpoint to the Reset Limit setpoint. So, the SAT will be the lowest temperature the Supply Air Setpoint can be reset to and Reset
Limit will be the highest temperature the Supply Air Setpoint can be reset to. The Cooling Supply Air Temperature Setpoint will automatically be reset warmer or colder within this range as the Reset Source (next screen) moves within its range.
Setpoint Screen #2 - HVAC Mode Select
Deadband
Description
SAT Cooling Setpoint
Cooling Reset Limit
Minimum
40ºF
40ºF
Default
55ºF
55ºF
Maximum
80ºF
150ºF
VCM-X / RNE Spts
HVAC Mode Select
Deadband....: 1.0ºF
Setpoint Screen #5 - Cool Reset Source
This Setpoint is added to and subtracted from the HVAC Mode Setpoints.
It provides you with fl exibility on when the Heating and Cooling Modes should be active above or below the HVAC Mode Setpoints.
Description
HVAC Mode Select Deadband
Minimum Default Maximum
0ºF 1ºF 10ºF
Setpoint Screen #3 - Unoccupied Setbacks
VCM-X / RNE Spts
Cool Rst Source Spts
SpcHi: 75 SAT: 55º
SpcLo: 75 RST: 55º
VCM-X / RNE Spts
Unoccupied Setbacks
Cooling.........: 30ºF
Heating.........: 30ºF
If no Reset Source has been confi gured in Confi guration Screen #4, then this screen will read Cool Rst Not Confi g and will not be used. If a Reset Source has been confi gured in Confi guration Screen #4, then the names of the values on the left side of this screen will correspond to the Reset Source that was confi gured. This screen will then allow you to input the upper and lower limits for the range of values of the Reset
Source on the left side of the screen and will show the corresponding
Cooling Supply Air SAT and Rst Limit values that were entered on the previous screen. Single Zone VAV Reset of the Supply Fan VFD is addressed in the last paragraph.
During the Unoccupied Mode of Operation, these Setpoints spread the
HVAC Mode Setpoints out by a user-adjustable amount. Use only positive numbers for these Setpoints. If you do not want Cooling or Heating to operate during the Unoccupied Mode, use the default setting of 30°F for these setpoints.
Description
Unoccupied Setbacks Cooling
Unoccupied Setbacks Heating
Minimum Default Maximum
0ºF 30ºF 30ºF
0ºF 30ºF 30ºF
Please note that the SAT and Rst Limit values on the right side of this screen cannot be changed on this screen; they are simply displayed from what was entered on the Setpoint Screen #4. For each line, the value on the left corresponds to the value on the right. So, if the Space Temperature
Sensor has been confi gured as the Reset Source, then when the Space
Temperature is at or above the SpcHi Temperature Setpoint, the Supply
Air Cooling Setpoint will be reset to its lowest value, the SAT Setpoint.
If the Space Temperature is at or below the SpcLo Setpoint, the Supply
Air Cooling Setpoint will be reset to its highest value, the Cooling Rst
Limit. Then, as the Space Temperature moves from its low value to its high value, the Supply Air Cooling Setpoint will be proportionally reset from its high value to its low value.
Depending on whether reset has been confi gured or not, the options for the names of the values on the left side of the screen are SpcHi, SpcLo,
OatHi, OatLo, RatHi, RatLo, VLT, VFD, NoRST.
VCM-X / RNE Operator Interfaces Technical Guide
39
VCM-X / RNE SETPOINTS
VCM-X / RNE Setpoint Screens
In the examples that follow, the desired Space Temperature in
Cooling Mode is 75ºF:
Setpoint Screen #7 - Heat Reset Source
Space Temperature Cool Reset:
Space Temperature (SPC Hi) = 75ºF SAT Setpoint (SAT) = 55ºF
Space Temperature (SPC Lo) = 74ºF SAT Setpoint (Rst) = 65ºF
Setpoint Screen #6 - SAT Heating Setpoints
VCM-X / RNE Spts
Heat Rst Source Spts
SpcHi: 70 SAT: 120º
SpcLo: 70 RST: 120º
VFD Percentage Cool Reset:
VFD Percentage (VFD) = 70% SAT Setpoint (SAT) = 55ºF
VFD Percentage (VFD) = 30% SAT Setpoint (Rst) = 65ºF
Input Voltage Cool Reset:
Input Voltage (VLT) = 0 Volts SAT Setpoint (SAT) = 55ºF
Input Voltage (VLT) = 10 Volts SAT Setpoint (Rst) = 65ºF
In the Cooling Mode in a Single Zone VAV application, the Supply Fan
VFD speed will proportionally modulate as the Space Temperature rises within the range set on this screen. Upon entering the Cooling Mode, the fan will start at 30% and modulate up to 100% as the Space Temperature rises from the SpcLo Setpoint to the SpcHi Setpoint. The SpcLo Setpoint should be the same as the Space Cooling Setpoint (Mode Enable
Setpoint) from Setpoint Screen #1. The SAT and RST Setpoints on the right side of the screen are not used.
If no Reset Source has been confi gured in Confi guration Screen #4, then this screen will read Heat Rst Not Confi g and will not be used. If a Reset Source has been confi gured in Confi guration Screen #6, then the names of the values on the left side of this screen will correspond to the Reset Source that was confi gured. This screen will then allow you to input the upper and lower limits for the range of values of the Reset
Source on the left side of the screen and will show the corresponding
Heating Supply Air SAT and Rst Limit values that you entered on the previous screen. Single Zone VAV Reset of the Supply Fan VFD is addressed in the last paragraph.
If no Reset Source has been confi gured in Confi guration Screen #4, then this setpoint will be the Supply Air Temperature Heating Setpoint. Line
4 will be blank. If a Reset Source has been confi gured in Confi guration
Screen #4, then Line 4 will read Rst Limit. Reset is always upward from the SAT setpoint to the Reset Limit setpoint. So, the SAT will be the lowest temperature the Supply Air Setpoint can be reset to and Reset
Limit will be the highest temperature the Supply Air Setpoint can be reset to. The Heating Supply Air Temperature Setpoint will automatically be reset warmer or colder within this range as the Reset Source
(next screen) moves within its range.
Please note that the SAT and Rst Limit values on the right side of this screen cannot be changed on this screen; they are simply displayed from what was entered on the Setpoint Screen #6. For each line, the value on the left corresponds to the value on the right. So if the Space Temperature
Sensor has been confi gured as the Reset Source, then when the Space
Temperature is at or above the SpcHi Temperature Setpoint, the Supply
Air Heating Setpoint will be reset to its lowest value, the SAT Setpoint.
If the Space Temperature is at or below the SpcLo Setpoint, the Supply
Air Heating Setpoint will be reset to its highest value, the Heating Rst
Limit. Then, as the Space Temperature moves from its low value to its high value, the Supply Air Heating Setpoint will be proportionally reset from its high value to its low value.
Depending on whether reset has been confi gured or not, the options for the names of the values on the left side of the screen are SpcHi, SpcLo,
OatHi, OatLo, RatHi, RatLo, VLT, VFD, NoRST.
In the examples that follow, the desired Space Temperature in
Heating Mode is 71ºF:
VCM-X / RNE Spts
SAT Heating Spts
Heating..: 120ºF
Rst Limit: 120ºF
Space Temperature Heat Reset:
Space Temperature (SPC Hi) = 71ºF SAT Setpoint (SAT) = 90ºF
Space Temperature (SPC Lo) = 70ºF SAT Setpoint (Rst) = 120ºF
Description
SAT Heating Spt
Reset Limit Spt
Minimum
40ºF
40ºF
Default
120ºF
120ºF
Maximum
200ºF
200ºF
VFD Percentage Heat Reset:
VFD Percentage (VFD) = 30% SAT Setpoint (SAT) = 90ºF
VFD Percentage (VFD) = 70% SAT Setpoint (Rst) = 120ºF
Input Voltage Heat Reset:
Input Voltage (VLT) = 0 Volts SAT Setpoint (SAT) = 90ºF
Input Voltage (VLT) = 10 Volts SAT Setpoint (Rst) = 120ºF
In the Heating Mode in a Single Zone VAV application, the Supply Fan
VFD speed will proportionally modulate as the Space Temperature falls within the range set on this screen. Upon entering the Heating Mode, the fan will start at 50% and modulate up to 100% as the Space Temperature falls from the SpcHi Setpoint to the SpcLo Setpoint. The SpcHi Setpoint should be the same as the Space Heating Setpoint (Mode Enable
Setpoint) from Setpoint Screen #1. The SAT and RST Setpoints on the right side of the screen are not used.
40
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X / RNE SETPOINTS
VCM-X / RNE Setpoint Screens
Setpoint Screen #8 - Stage Control Window
SAT Cutoff Temperature Setpoint. See the VCM-X Controller Technical
Guide, VCM-X Modular E-BUS Controller Technical Guide, or RNE
Controller Technical Guide for detailed information on the Low and
High Supply Air Temperature Cutoff sequence of operation.
VCM-X / RNE Spts
Stage Control Window
Cooling.........: 5ºF
Heating.........: 5ºF
Description
Lo SAT Cutoff
Hi SAT Cutoff
Minimum
0ºF
0ºF
Default
40ºF
170ºF
Maximum
250ºF
250ºF
When the VCM-X or RNE is in Cooling Mode, if the Supply Air
Temperature drops below the Active Supply Air Temperature Setpoint minus the Cooling Stage Control Window value, a Cooling Stage will be deactivated after its Minimum Run Time. In the Heating Mode, if the
Supply Air Temperature rises above the Active Supply Air Temperature
Setpoint plus the Heating Stage Control Window value, a Heating stage will be deactivated after its Minimum Run Time. This staging window is also used for the coil temperature during Dehumidifi cation Mode.
Description
Stage Control Window Cooling
Stage Control Window Heating
Minimum Default Maximum
5ºF
5ºF
5ºF
5ºF
30ºF
30ºF
Setpoint Screen #11 - Minimum Supply Fan
VFD Speed For Heating
VCM-X / RNE Spts
Minimum Supply
Fan VFD Speed
For Heating..: 30%
If the Supply Fan VFD Signal falls below the Minimum Supply Fan
VFD Speed For Heating Setpoint, Heating will be disabled.
Setpoint Screen #9 - Outdoor Air Lockouts
Description
Min Supply Fan VFD
Speed For Heating
Minimum
0%
Default
30%
Maximum
100%
VCM-X / RNE Spts
Outdoor Air Lockouts
Cooling......: 50ºF
Heating......: 70ºF
Setpoint Screen #12 - Morning Warm Up Temp
The VCM-X or RNE will Lockout Mechanical Heating or Cooling when the Outdoor Air (OA) Temperature is above or below these Setpoints.
On Air to Air Heat Pump units, Compressor Cooling and Heating can only operate if the OA Temperature is above the Outdoor Air Cooling
Lockouts. If using the VCM-X WSHP (Water Source Heat Pump) Controller, the OA Cooling Lockout is ignored. Since Emergency Heat can only be used below the Compressor Lockouts, Emergency Heat is therefore not available on WSHP units using the VCM-X WSHP Controller.
Description
OA Lockouts Cooling
OA Lockouts Heating
Minimum
0ºF
50ºF
Default
50ºF
70ºF
Maximum
100ºF
150ºF
VCM-X / RNE Spts
Morning WarmUp
Target Temp: 72º F
Max Length.: 60 Min
When the VCM-X or RNE is confi gured for VAV operation and the controller enters the Occupied Mode, the VCM-X or RNE looks at the
Return Air Temperature to determine if the unit should initiate Morning
Warm-up Mode. If the Return Air Temperature is below the Morning
Warm-up Target Temperature and the Max Length is greater than “0,” the VCM-X or RNE will initiate Heating. This is considered Morning
Warm-up and will run until the Return Air Temperature rises above the
Morning Warm-up Target Temperature or until the Max Length Setpoint time expires.
Setpoint Screen #10 - Cutoff Temperature
VCM-X / RNE Spts
Cutoff Temperatures
Lo SAT.......: 40ºF
Hi SAT.......: 170ºF
Description
Morning Warm Up
Target Temp
Morning Warm Up
Max Length
Minimum
50ºF
0 Min
Default
72ºF
60 Min
Maximum
90ºF
240 Min
The VCM-X or RNE will temporarily disable Heating or Cooling if while in Heating or Cooling Mode the Supply Air Temperature rises above the High SAT Cutoff Temperature Setpoint or falls below the Low
VCM-X / RNE Operator Interfaces Technical Guide
41
VCM-X / RNE SETPOINTS
VCM-X / RNE Setpoint Screens
Setpoint Screen #13 - Dehumidifi cation Indoor
RH & OA Dewpoint
Setpoint Screen #15 - Cooling Head Pressure
Setpoint
VCM-X / RNE Spts
Dehumidification Spt
Indoor RH....: 50%
OA Dewpoint..: 55ºF
VCM-X / RNE Spts
Cooling
Head Pressure
Setpoint: 315PSI
On VAV or CAV confi gured units that are not using 100% Outdoor Air, when the Indoor Relative Humidity percentage rises above the Indoor
RH Setpoint, the unit will start operating in Dehumidifi cation Mode.
If an Indoor Humidity Sensor is installed, the unit will reset the Coil
Suction Temperature Setpoint as needed to maintain this Indoor RH
Setpoint. This includes VAV, CAV and MUA applications.
On MUA confi gured units that are using 100% Outdoor Air, when the
Outdoor Air Dewpoint Temperature rises above the OA Dewpoint Setpoint, the unit will start operating in Dehumidifi cation Mode.
See the One Condenser Head Pressure Module Technical Guide, the
Two Condenser Head Pressure Module Technical Guide, or the RNE
Controller Technical Guide for detailed information.
Description
Dehumidifi cation Setpoint
Indoor RH
Dehumidifi cation Setpoint
OA Dewpoint
Minimum Default Maximum
1% 50% 100%
35ºF 55ºF 80ºF
If you are using the Head Pressure Module, this is the Cooling Setpoint for control of the condenser fan speed. This is based on the highest head pressure reading of up to 4 Head Pressure Sensors. This screen only applies if using the VCM-X Modular, VCM-X WSHP Controller, or RNE Controller.
Description
Cooling Head Pressure
Setpoint
Setpoint Screen #16 - Reheat Head Pressure
Setpoint
Minimum
200 PSI
Default Maximum
315 PSI 400 PSI
Setpoint Screen #14 - Dehumidifi cation Coil
Temperature
VCM-X / RNE Spts
Dehumidification
Coil Temperature
Setpoint.....: 45ºF
During the Dehumidifi cation Mode, the VCM-X / RNE uses the calculated Coil Temperature to activate DX Cooling based on this Dehumidifi cation Coil Temperature Setpoint. The VCM-X / RNE uses a Suction
Pressure Transducer to read Suction Pressure (the Saturation Vapor
Pressure of the Refrigerant) and converts this Suction Pressure reading to a Coil Temperature value. This calculation is based on using R22 or
R410A refrigerant only and will not work with any other refrigerant.
This setpoint determines the number of compressor stages that need to be activated to maintain the Dehumidifi cation Coil Temperature Setpoint.
VCM-X / RNE Spts
Reheat
Head Pressure
Setpoint: 400PSI
If you are using the Head Pressure Module, this is the Reheat Setpoint for control of the condenser fan speed during dehumidifi cation. This is based on the highest head pressure reading of up to 4 Head Pressure
Sensors. This screen only applies if using the VCM-X Modular, VCM-X
WSHP Controller, or RNE Controller.
See the One Condenser Head Pressure Module Technical Guide, the
Two Condenser Head Pressure Module Technical Guide, or the RNE
Controller Technical Guide for detailed information.
Description
Reheat Head Pressure
Setpoint
Minimum
200 PSI
Default Maximum
400 PSI 400 PSI
Description
Dehumidifi cation Coil
Temperature Setpoint
Minimum Default Maximum
35ºF 45ºF 70ºF
42
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X / RNE SETPOINTS
VCM-X / RNE Setpoint Screens
Setpoint Screen #17 - Economizer OAT/WB
Enable
VCM-X / RNE Spts
Economizer Setpoints
OAT/WB Enable: 55ºF
Setpoint Screen #19 - Outdoor Air CFM Control
VCM-X / RNE Spts
OA CFM CONTROL
Min CFM.: 0.10 K
Max CFM.: 0.10 K
If an Outdoor Air Humidity Sensor is not connected to the VCM-X or
RNE and the Outdoor Air Temperature falls below this Setpoint, the
Economizer can be used for Free Cooling. If an Outdoor Air Humidity
Sensor is connected to the VCM-X or RNE, then a Wetbulb Temperature will be calculated and used instead of the Outdoor Air Drybulb Temperature to determine when Free Cooling can be used.
If controlling the Outdoor Air Damper to a CFM setpoint, this screen allows you to set the design Minimum and Maximum required Outdoor
Airfl ow CFM values for the Air Handler. The OA Max CFM limits the damper operation during CO
2
override conditions. K = 1000
Description
OA Minimum CFM
OA Maximum CFM
Description
Economizer Setpoints
OAT/WB Enable
Minimum Default Maximum
0ºF 55ºF 80ºF
Minimum
0.10 K
0.10 K
Default
.10 K
.10 K
Maximum
200 K
200 K
Setpoint Screen #20 - Outdoor Air CFM
Deadband
Setpoint Screen #18 - Economizer Minimum
Position & Control Rate
VCM-X / RNE Spts
OA CFM CONTROL
OA CFM DB...: 10CFM
VCM-X / RNE Spts
Economizer Setpoints
Min Position.: 10 %
Control Rate.: 90
The is the deadband above and below the OA CFM Control Setpoint which helps prevent hunting.
The Economizer (OA Damper) Min Position Setpoint is maintained during the Occupied Mode even if the Economizer is disabled due to the
OA Temperature or Wetbulb Temperature being above the Economizer
Enable Setpoint. The Control Rate Setpoint allows you to adjust the
Economizer to modulate the OA Damper Actuator faster or slower as desired. The Control Rate Setpoint range is 10-99. Larger numbers make the Economizer Outdoor Air Damper Actuator modulate faster, smaller numbers make the Outdoor Air Damper Actuator modulate slower.
Description
OA CFM Deadband
Minimum
0 CFM
Default Maximum
10 CFM 20,000 CFM
Setpoint Screen #21 - Economizer Maximum
Position if High CO
2
Level
Description
Economizer Min Position
Economizer Control Rate
Minimum
0%
10
Default Maximum
10% 100%
90 99
VCM-X / RNE Spts
Maximum Economizer
Position if High CO2
Level Occurs.: 100%
This Setpoint allows you to set the Maximum Position the Economizer will open if high CO
2
conditions occur in the space. The Maximum
Economizer Position Setpoint is used to limit the amount of Outdoor Air that will be introduced to the HVAC unit in order to ensure the unit is operating within its Heating and Cooling design limitations. As shown in the table below, the Minimum setting for this Setpoint is the value previously set for the Economizer Min Position Setpoint.
Description
Maximum Economizer
Position If High CO
2
Level Occurs
Minimum
Economizer
Minimum
Position
Default Maximum
100% 100%
VCM-X / RNE Operator Interfaces Technical Guide
Revised: 9/14/12
43
VCM-X / RNE SETPOINTS
VCM-X / RNE Setpoint Screens
Setpoint Screen #22 - CO
2
Protection Limit
VCM-X / RNE Spts
CO2 Protection Limit
Max Level.: 900 PPM
Reset Rnge: 100 PPM
Setpoint Screen #24 - Building Pressure
VCM-X / RNE Spts
Building Pressure
Setpoint....: 0.10”
Deadband....: 0.02”
When the CO
2
level rises above the CO
2
Protection Limit Max Level, the
Economizer’s Minimum Position will begin to reset open proportionally between the CO
2
Protection Limit Max Level Setpoint and the Reset
Range Setpoint. The Reset Range value is added to the Max Level value.
If the CO
2
levels are equal to or above the Max Level plus the Reset
Range, the Economizer will be opened to its Maximum Economizer
Position if high CO
2
levels occur.
Description
CO
2
Protection Limit
Max Level
CO
2
Protection Limit
Reset Range
Minimum
0 PPM
0 PPM
Default
900 PPM
100 PPM
Maximum
3000 PPM
1500 PPM
Direct Acting Control
If an Exhaust Fan Relay is confi gured, when the Building Static Pressure rises above the Building Pressure Setpoint plus the Deadband, the
Exhaust Fan Relay will activate. It will remain on until the Building
Pressure falls below the Building Pressure Setpoint minus the Deadband.
If Modulating Building Pressure is confi gured, when the Building Static
Pressure rises above the Building Pressure Setpoint plus the Deadband, the Building Pressure Output Signal will increase until the Building
Static Pressure falls within the Deadband. If the Building Static Pressure falls below the Building Pressure Setpoint minus the Deadband, the
Building Pressure Output Signal will decrease until the Building Static
Pressure rises within the Deadband. The Building Pressure Output Signal is confi gurable for 0-10 or 2-10 VDC. For more detailed operation information, see the VCM-X Controller Technical Guide, VCM-X Modular
E-BUS Controller Technical Guide, or RNE Controller Technical Guide for the complete Building Pressure Control Sequence of Operation.
Setpoint Screen #23 - Static Setpoint,
Deadband & Control Rate
VCM-X / RNE Spts
Static Spt...: 0.50”
Deadband.....: 0.10”
Control Rate.: 10 s
Reverse Acting Control
The Building Pressure Output Signal remains a Direct Acting 0-10 or
2-10 VDC signal, but the logic is reversed. On a drop in Building Static
Pressure below the Building Pressure Setpoint minus the Deadband, the
Building Pressure Output Signal will increase.
For VAV units, a Supply Fan VFD or Bypass Damper Actuator is used to maintain the Duct Static Pressure Setpoint. The Static Pressure Output
Signal varies to control the Static Pressure Setpoint. If the Duct Static
Pressure is above the Static Setpoint plus the Deadband, the Static Pressure Output Signal will be reduced at every Control Rate interval. If the
Static Pressure is below the Static Setpoint minus the Deadband, the
Output signal will be increased at every Control Rate interval.
Description
Building Pressure Spt
Building Pressure
Deadband
Min.
-0.20″ WG
0.01″ WG
Default Max.
0.10″ WG 0.20″ WG
0.02″ WG 0.10″ WG
Setpoint Screen #25 - RAB Damper Factor
The Duct Static Pressure Control Output Signal is a non-confi gurable
Direct Acting Signal (0-10 VDC). This can be used to directly connect to a Supply Fan VFD without any modifi cations.
Description
Static Spt
Deadband
Control Rate
Minimum
0.10″ WG
0.10″ WG
1 Sec
Default Maximum
0.50″ WG 3.0″ WG
0.10″ WG 1.0″ WG
10 Sec 30 Sec
VCM-X / RNE Spts
Return Air Bypass
Damper Factor
Setpoint..: 40%
When you are using a Bypass Damper Actuator to control the Duct
Static Pressure, you must set up the Bypass Damper Actuator or the
Bypass Damper so that it is Reverse Acting in operation. The Output
Signal increases (closes Bypass Damper) if the Duct Static Pressure is below the Duct Static Pressure Setpoint by the Deadband amount and the Output Signal decreases (opens Bypass Damper) if the Static Pressure is above the Setpoint by the Deadband amount.
This setpoint is used when your HVAC unit is confi gured for Return
Air Bypass Damper control. The Return Air Bypass Damper Factor
Setpoint is a percentage value that is used to calculate the Return Air
Damper position in relation to the Return Air Bypass Damper position.
This provides a method for adjusting the airfl ow through the Return
Air Bypass Damper.
Increasing this percentage increases the airfl ow through the Return Air
Bypass Damper by causing the Return Air Damper to move further towards its closed position in relation to the Return Air Bypass Damper moving towards its open position.
44
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X / RNE SETPOINTS
VCM-X / RNE Setpoint Screens
Decreasing this percentage decreases the airfl ow through the Return
Air Bypass Damper by causing the Return Air Damper to move further towards its open position in relation to the Return Air Bypass Damper moving towards its closed position.
Setpoint Screen #28 - Preheat/ Low Ambient
Temperature
Description
Return Air Bypass
Damper Factor
Minimum
0%
Default
40%
Maximum
100%
VCM-X / RNE Spts
Preheat/Low
Ambient Temperature
Setpoint: 0ºF
Setpoint Screen #26 - Supply Fan Starting
Delay Timer
VCM-X / RNE Spts
Fan Starting Delay
Timer...: 255 s
For cold climates where freezing temperatures may be experienced, a Pre-Heater relay output can be activated based on the Outdoor Air
Temperature to prevent freezing of Water Coils. One of the VCM-X
/ RNE Relay Outputs must be confi gured for the Pre-Heater control.
When confi gured, if the Outdoor Air Temperature falls below the Low
OAT Ambient Protection Temperature Setpoint and the HVAC unit is in Occupied Mode, the Pre-Heater relay will activate.
Description
Preheat/Low Ambient
Temperature
Minimum Default Maximum
0ºF 0ºF 70ºF
This is the Supply Fan Starting Delay Timer initiated whenever the
VCM-X / RNE initiates Supply Fan operation. This is useful when you are using multiple VCM-X / RNE-controlled HVAC units and want to be sure that all the units do not start at exactly the same time when the
Occupied schedule occurs. Each VCM-X or RNE should be set with staggered Fan Starting Delay Timer Setpoint values. When the 255
Second default setpoint is used, it multiplies each VCM-X or RNE’s address by 5 and uses this value in seconds as the Fan Starting Delay
Time. This provides a staggered start for each VCM-X or RNE on the system without having to individually set each VCM-X or RNE for its own time delay.
Setpoint Screen #29 - Max OA Damper
Tempering Limit
VCM-X / RNE Spts
Max OA Damper
Tempering Limit
Setpoint: 50%
Description
Fan Start Delay Timer
Minimum
0 Sec
Default
255 Sec
Maximum
255 Sec
The Maximum OA Damper Tempering Limit Setpoint allows you to set the maximum damper position the economizer can open to while the heat is running during the VAV Supply Air tempering mode in this sequence (to prevent potential wasting of energy).
Setpoint Screen #27 - Mechanical Heat/Cool
Failure Time Period
Description
Maximum Outdoor Air
Damper Tempering Limit
Minimum Default Maximum
0% 50% 60%
VCM-X / RNE Spts
Mechanical Heat/Cool
Failures Occur After
No Change For 15 Min
Setpoint Screen #30 - HVAC Schedule
When Heating or Cooling Mode is initiated and staging is activated, if the
Supply Air Temperature does not rise or fall 5°F within the Mechanical
Heat/Cool Failures Occur After No Change For Setpoint time period, a Mechanical Heating or Cooling failure alarm will be generated. The
Alarm is for Status Reporting only. The HVAC unit will continue to run.
VCM-X / RNE Spts
HVAC Schedule...: 0
[ 0 = Internal ]
[1-5 = External ]
Description
Mechanical Heat/Cool
Failures Occur After
No Change For
Minimum
0 Min
Default
15 Min
Maximum
255 Min
The VCM-X / RNE has an Internal Scheduler. If you want the VCM-X or
RNE to use its own Internal Schedule to schedule the HVAC unit, enter
<0>
for Internal. To use the External Schedule option, you must have a
GPC Plus controller installed and operating on your system. To use one of the (5) External Schedules available on the GPC Plus controller, enter the number of the GPC Plus Schedule (1 through 5) you wish to use.
Description
HVAC Schedule
Minimum
0
Default
0
Maximum
5
VCM-X / RNE Operator Interfaces Technical Guide
45
VCM-X / RNE SETPOINTS
VCM-X / RNE Setpoint Screens
Setpoint Screen #31 - Push-Button Override
Duration
Description
Heat Pump
Auxiliary Heating Delay
Minimum Default Maximum
0 Min 3 Min 30 Min
VCM-X / RNE Spts
Push-Button Override
Duration....: 2.0 Hr
Setpoint Screen #34 - Heat Pump Defrost
Setpoints
If the VCM-X or RNE has a Space Temperature Sensor installed and it has the Override Button option, the HVAC unit will initiate Occupied
Mode any time the Override Button is pressed and held for less than
3 seconds. The Push-Button Override Duration Setpoint allows you to adjust the amount of time the Override will remain in effect when the
Override Button is pressed. To cancel the Override before the Override
Duration time period expires, press the Override Button for 5 to 10 seconds.
Description
Push-Button
Override Duration
Minimum
0.0 Hr
Default
2.0 Hr
Maximum
8.0 Hr
Setpoint Screen #32 - HVAC Mode Sensor
Slide Offset
VCM-X / RNE Spts
HVAC Mode Sensor
Slide Offset: 0ºF
VCM-X / RNE Spts
Heat Pump Defrost
Defrost Tmp: 30ºF
Defrost Tmr: 30 Min
The Defrost Temp Setpoint is the Coil Suction Temperature at which the unit will go into Defrost Mode during Heat Pump Heating operation. This unit will operate in the Defrost Mode for 10 minutes or until the Head Pressure reaches 450 PSI. The Defrost Timer determines the length of time between Defrost Modes. The length of the Defrost Timer can be automatically be adjusted by the Adaptive Defrost Adjustment described in Setpoint Screen # 35. This Defrost Mode is only available if using the VCM-X Modular Controller or RNE Controller and a Head
Pressure Module. A Suction Pressure Transducer is also required. This screen only applies if using the VCM-X Modular Controller or RNE
Controller with a Suction Pressure Sensor, a Head Pressure Module, and
Head Pressure Transducer(s). This screen does not apply if using the
VCM-X WSHP Controller and a WSHP Protection Module.
Description
Heat Pump Defrost Temp
Heat Pump Defrost Timer
Minimum Default Maximum
0ºF 30ºF 50ºF
10 Min 30 Min 90 Min
If the VCM-X or RNE has a Space Temperature Sensor with the Slide
Adjust option installed, the HVAC Mode Enable Heating and Cooling
Setpoints can be offset by the HVAC Mode Sensor Slide Offset Setpoint value. When the Slide Adjust bar is in the middle, no offset will occur.
If the Slide Adjust bar is moved all the way to the top of the Sensor, the
Heating and Cooling Setpoints will be raised by the Setpoint value you have entered. If the Slide Adjust bar is moved all the way down to the bottom of the Sensor, the Heating and Cooling Setpoints will be lowered by the Setpoint value you have entered.
Description
HVAC Mode Sensor
Slide Offset
Minimum Default Maximum
0ºF 0ºF 10ºF
Setpoint Screen #35 - Adaptive Defrost Adj.
Setpoint
VCM-X / RNE Spts
Adaptive Defrost
Adj. Setpoint: 0 MIN
Setpoint Screen #33 - Heat Pump Auxiliary
Heating Delay
VCM-X / RNE Spts
Heat Pump
Auxiliary Heating
Delay: 3 Min
Once initiated, the Defrost Mode is active until the Head Pressure reaches
450 PSIG or until a 10 minute timer has expired. Enter a value greater than zero to enable the Adaptive Defrost Adjustment of the Heat Pump
Defrost Timer (Screen #34). This adjustment value will be subtracted from the Heat Pump Defrost Timer if the Defrost Mode lasts the entire
10 minutes. A proportion of this adjustment value will be added to the
Heat Pump Defrost Timer if the Defrost Mode only lasts between 8 minutes and 0 minutes. This screen only applies if using the VCM-X
Modular Controller or RNE Controller with a Suction Pressure Sensor, a Head Pressure Module, and Head Pressure Transducer(s). This screen does not apply if using the VCM-X WSHP Controller and a WSHP
Protection Module.
If the VCM-X or RNE is confi gured to operate as a Heat Pump, the Heat
Pump Auxiliary Heating Delay Setpoint can be confi gured to provide a time delay period before Auxiliary Heating Stages can be activated once activation of the Compressor Heating Stages have been initiated.
46
Description
Adaptive Defrost Adj.
Minimum Default Maximum
0 Min 0 Min 30 Min
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X / RNE SETPOINTS
VCM-X / RNE Setpoint Screens
Setpoint Screen #36 - Heat Wheel Defrost Setpoint Screen #39 - Sensor Calibration for
SPC & SAT
VCM-X / RNE Spts
Heat Wheel Defrost
Setpoint: 30ºF
VCM-X / RNE Spts
Sensor Calibration
SPC: XX.Xº 0.00º
SAT: XX.Xº 0.00º
The unit will go into Heat Wheel Defrost Mode when the Outdoor Air is below this setpoint.
Description
Heat Wheel Defrost
Minimum Default Maximum
0ºF 30ºF 50ºF
If the Space or Supply Air Temperature Sensors are reading incorrectly, you can use this option to enter an offset temperature to adjust the Sensor’s Temperature. Enter a positive Sensor Calibration value to raise the
Space Temperature and/or Supply Air Temperature Sensor reading and a negative value to lower the Sensor reading.
Setpoint Screen #37 - Internal Schedule
Optimal Start Soak Multiplier
Description
Sensor Calibration SPC
Sensor Calibration SAT
Minimum Default Maximum
-100.0ºF 0.0ºF +100.0ºF
-100.0ºF 0.0ºF +100.0ºF
VCM-X / RNE Spts
Internal Schedule
Optimal Start Soak
Multiplier: 0.0
Setpoint Screen #40 - Sensor Calibration for
RAT & OAT
The Internal Schedule Optimal Start Soak Multiplier Setpoint is a multiplier that if set to a number greater than 0 will be used as a multiplier for calculating the Optimal Start Time for the HVAC unit. This multiplier is only applied if the unit has been off for more than 24 hours. See the
VCM-X Controller Technical Guide, VCM-X Modular E-BUS Controller
Technical Guide, or RNE Controller Technical Guide for more detailed information regarding the Optimal Start. This multiplier is only applied if you are using the VCM-X / RNE Internal Schedule.
Description
Internal Schedule Optimal
Start Soak Multiplier
Minimum Default Maximum
0.0
0.0
5.0
VCM-X / RNE Spts
Sensor Calibration
RAT: XX.Xº 0.00º
OAT: XX.Xº 0.00º
If the Return Air or Outdoor Air Temperature Sensors are reading incorrectly, you can use this option to enter an offset temperature to adjust the Sensor’s Temperature. Enter a positive Sensor Calibration value to raise the Return Air Temperature and/or Outdoor Air Temperature Sensor reading and a negative value to lower the Sensor reading.
Setpoint Screen #38 - Trend Log Interval
Description
Sensor Calibration RAT
Sensor Calibration OAT
Minimum Default Maximum
-100.0ºF 0.0ºF +100.0ºF
-100.0ºF 0.0ºF +100.0ºF
VCM-X / RNE Spts
Trend Log
Interval: 15 MIN
Setpoint Screen #41 - Sensor Calibration for
COIL
VCM-X / RNE Spts
Sensor Calibration
COIL: XX.Xº 0.00º
An internal Trend Log is constantly updated at a rate equal to this value.
Description
Trend Log Interval
Minimum Default Maximum
1 Min 15 Min 60 Min
If the Coil Temperature reading is too high, enter a negative calibration offset to decrease the reading. If it is too low, enter a positive value to increase the reading.
Description
Sensor Calibration COIL
Minimum Default Maximum
-30.0ºF 0.0ºF +30.0ºF
VCM-X / RNE Operator Interfaces Technical Guide
47
VCM-X / RNE STATUS
VCM-X / RNE Status Screen Index
VCM-X / RNE Status Screen Index
Status Screen #1 HVAC Mode
Status Screen #2 Cooling/Heating/Economizer Status
Status Screen #3 Mode Enable Temperature and
Cooling Setpoints
Status Screen #4 Current SAT Temperature and Setpoint
Status Screen #5 Space Temperature, Return Air
Temperature, Adjust
Status Screen #6 VCM-X Leaving Water Temperature A
Status Screen #7 VCM-X Leaving Water Temperature B
Status Screen #8 Coil Temperature or Lowest Coil and
Status Screen #9 Current Outdoor Air Temperature and
Outdoor Humidity
Status Screen #10 Current Calculated Outdoor Air
Dewpoint Dewpoint
Temperature
Status Screen #11 Current Indoor RH Percentage and
Indoor Percentage
Status Screen #12 Current Static Pressure and Output
Percentage
Status Screen #13 Economizer Percentage, Outdoor Air
Wetbulb/Drybulb, CO
2
Level
Status Screen #14 Outdoor Air CFM & Outdoor Air
Setpoint
Status Screen #15 Supply Air CFM & Return Air CFM
Status Screen #16 Current Building Pressure & Output
Percentage
Status Screen #17 MODGAS Output Percentage &
Status Screen #18 Current Modulating Heating & Cooling
Status Screen #19 VCM-X Coil Temperatures for Full
Digital Coil
Temperatures Full
Status Screen #20 VCM-X Coil Temperatures for Full
Digital Coil
Temperatures Full
Status Screen #21 VCM-X Full Digital Module Signal,
OR RNE Full Digital Module Signal or
Signal
Status Screen #22 Current Head Pressure Cooling or
Status Screen #23 Head Pressure and Condenser Fan #1
Speed
Status Screen #24 Head Pressure and Condenser Fan #2
Speed
Status Screen #25 Return Air Bypass Damper Signal &
Status Screens #26-32 Supply Fan and Other Relays
Status Screens #33 Alarm Conditions
48
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X / RNE STATUS
VCM-X / RNE Status Screens
Status
The VCM-X / RNE Controller Status Screens are accessed by pressing the
<STATUS>
button on either the System Manager or the Modular
Service Tool. Following are the available status screens and a description of their functions:
Status Screen 1 - Mode
Status Screen 3 - Mode Enable Temperature &
Mode Cooling and Heating Setpoints
VCM-X / RNE v1.00
Enable Tmp.: XX.XºF
Cooling Spt: XX.XºF
Heating Spt: XX.XºF
VCM-X / RNE v1.00
Occupied Mode
Vent Mode
02/15/10 05:00 PM
Line 2 Mode Enable Temperature
Can be the Supply Air Temperature, Return Air
Temperature, Outdoor Air Temperature, or Space
Temperature, depending on which one has been
confi gured as the Mode Enable Sensor.
Line 3 Cooling Mode Setpoint
Based on the current Occupied/Unoccupied Mode
Line 2 Displays one of the following:
Unoccupied Mode Remote FRC Occupied
Occupied Mode
Holiday
Forced Schedule Mode OUTPUT FORCE MODE!
SUPPLY AIR CUTOFF! High CO2 Level Mode!
Line 4 Heating Mode Setpoint
Based on the current Occupied/Unoccupied Mode
Line 3
If you selected Supply Air as the controlling sensor, this line will display:
Supply Air Control
If you select Space Temp or Return Air Control, the
display will show one of the following:
Off Mode Dehumid. Mode Defrost Mode
Vent Mode Cool Dehumid. Mode
Cool Mode Heat Dehumid. Mode
Heat Mode Warm Up Mode
Line 4 Displays one of the following:
MM/DD/YY HH:MM XX (XX = AM or PM)
Fan Starting Delay and then time will display xx Left in WarmUp (Number of Minutes Left)
Status Screen 2 - Cooling, Heating, Economizer
VCM-X / RNE v1.00
Cooling Enabled
Heating Enabled
Economizer Disabled
Status Screen 4 - Supply Air Temperature &
Setpoint
VCM-X / RNE v1.00
Supply Air.: XX.XºF
Supply Spt.: XX.XºF
Line 2 Current Supply Air Temperature
The Supply Air Temperature is always required. If a
Supply Air Temperature Sensor is not installed, the VCM-X
/ RNE Controller will not operate correctly and will display
0°F.
Line 3 Current Active Supply Air Setpoint
This is the Supply Air Setpoint for the mode that the unit is currently operating in. If the Supply Air Reset is
confi gured, this is the calculated setpoint based on the current Reset Source conditions.
Line 2 Displays one of the following:
Line 3 Displays one of the following:
Line 4 Displays one of the following:
Economizer Enabled
VCM-X / RNE Operator Interfaces Technical Guide
49
VCM-X / RNE STATUS
VCM-X / RNE Status Screens
Status Screen 5 - Space Temp, Return Air &
Slide Adjust
Line 3 Leaving Water Temperature A
This line will display the Leaving Water Temperature of
VCM-X / RNE v1.00
Space Tmp.: XX.XºF
Return Air.: XX.XºF
Slide Adj.: XX.XºF
Line 2 Space Temperature
If you are using a Space Temperature Sensor, this line will display the current Space Temperature during the Occupied
Source Heat Pump Module. If using (2) Water Source Heat
Pump Modules, this will be the fi rst sensor on the Module
Line 4 Leaving Water Temperature B
This line will display the Leaving Water Temperature of the second Leaving Water Temperature Sensor on a Water
Source Heat Pump Module. If using (2) Water Source Heat
Pump Modules, this will be the second sensor on the
Module with address 1.
Line 3 Return Air Temperature
This sensor is optional. If a Return Air Temperature Sensor is not used, it will display 0°F.
Line 4 Slide Adjust
This is the current value of the Space Temperature offset based on the position of the slide adjust switch on the Space
Sensor.
Status Screen 7 / VCM-X - Leaving Water
Temperature B
VCM-X v1.00
Leaving Water
Temp B: 0.0ºF
Status Screen 6 / VCM-X - Leaving Water
Temperature A
VCM-X v1.00
Leaving Water
Temp A: 0.0ºF
Line 2-3 Leaving Water Temperature B
If using the VCM-X Controller and you have a Water
Source Heat Pump Unit installed with two leaving water temperature sensors, this screen will display the
Leaving Water Temperature of System B.
Status Screen 7 / RNE - Leaving Water
Temperature 2
Line 2-3 Leaving Water Temperature A
If using the VCM-X Controller and you have a Water
Source Heat Pump Unit installed, this screen will appear and display the Leaving Water Temperature of the unit. If this unit has two leaving water temperature sensors, this is the Leaving Water Temperature of System A.
RNE v1.00
Leaving Water 2
Temp A: 0.0ºF
Temp B: 0.0ºF
Status Screen 6 / RNE - Leaving Water
Temperature 1
RNE v1.00
Leaving Water 1
Temp A: 0.0ºF
Temp B: 0.0ºF
Line 2 Leaving Water Temperature 2
If using the RNE Controller and a second Water Source
Heat Pump Module has been installed and confi gured, this screen will display Water Temperatures. If not, this screen
Line 3 Leaving Water Temperature A
This line will display the Leaving Water Temperature of
Source Heat Pump Module. If using (2) Water Source Heat
Pump Modules, this will be the fi rst sensor on the Module
Line 2 Leaving Water Temperature 1
If using the RNE Controller and you have a Water Source
Heat Pump Module installed or if there are two Water
Source Heat Pump Modules installed and this is the fi rst
Module, then this screen will display Water Temperatures of this Module. If not, this screen will display 0°F.
Line 4 Leaving Water Temperature B
This line will display the Leaving Water Temperature of the second Leaving Water Temperature Sensor on a Water
Source Heat Pump Module. If using (2) Water Source Heat
Pump Modules, this will be the second sensor on the
Module with address 2.
50
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X / RNE STATUS
VCM-X / RNE Status Screens
Status Screen 8 - Coil Temp & Setpoint
VCM-X / RNE v1.00
Coil Tmp...: XX.XºF
Coil Tmp Spt: XX.XºF
Status Screen 10 - OA Dewpoint & Dewpoint
Temp
VCM-X / RNE v1.00
OA Dewpoint.: XX.XºF
Dewpoint Spt: XX.XºF
Line 2 Coil Temperature or Lowest Coil
If a Suction Pressure Transducer has been installed and
confi gured on the unit, the calculated Evaporator Coil
Temperature will appear on this line. If not, this line will
If this unit has multiple digital scroll compressors and has a
Full Digital Module or Dual Digital Module installed, this line will display Lowest Coil and will display the lowest of the multiple suction temperatures. The coil temperatures of all the coils will be displayed on Status Screens 19 & 20.
Line 2 Current Calculated Outdoor Air Dewpoint
Temperature
If both an Outdoor Humidity Sensor and an Outdoor Air
Temperature Sensor have been installed and confi gured on the unit, the calculated Outdoor Air Dewpoint Temperature will appear on this line. If not, this screen displays 0°F.
Line 3 Current Outdoor Air Dewpoint Setpoint
The user adjustable Outdoor Air Dewpoint Temperature
Setpoint will appear on this line.
Line 3 Coil Temperature Setpoint
Setpoint is automatically reset based on the current space humidity conditions. This is the current calculated Coil
Temperature Setpoint based on that reset.
Status Screen 11 - Indoor RH & Indoor RH
Setpoint
Status Screen 9 - Outdoor Air Temperature &
Outdoor Air Relative Humidity
VCM-X / RNE v1.00
Indoor RH....: XXX%
Indoor RH Spt: XXX%
VCM-X / RNE v1.00
Outdoor Tmp: XX.XºF
Outdoor RH.: XX.X%
Line 2 Current Outdoor Air Temperature
If an Outdoor Air Temperature Sensor has been installed on the system, the Outdoor Air Temperature will appear on this line. If not, this line will display a temperature that is half way between the Cooling and Heating Lockout
Setpoints.
Line 3 Current Outdoor Air Relative Humidity
If an Outdoor Humidity Sensor has been installed and
confi gured on the VCM-X or RNE, the Outdoor Air
Relative Humidity Percentage will appear on this line. If not, this line will display 0%.
Line 2 Current Indoor Relative Humidity Percentage
If an Indoor Humidity Sensor has been installed and
confi gured on the unit, the current Indoor Air Relative
Humidity Percentage will appear on this line. The installed
Indoor Humidity Sensor can be either a Wall Mounted type or a Return Air Mounted type. If an Indoor Humidity
Sensor is not installed, this line will display 0%.
Line 3 Current Indoor Relative Humidity Setpoint Percentage
This is the adjustable Indoor Air Relative Humidity
Setpoint Percentage that has been set by the user.
VCM-X / RNE Operator Interfaces Technical Guide
51
VCM-X / RNE STATUS
VCM-X / RNE Status Screens
Status Screen 12 - Static Pressure & Output % Status Screen 14 - Outdoor Air CFM & Setpoint
VCM-X / RNE v1.00
Static Pr...: X.XX”
Press Output: XXX%
[Optional Output]
VCM-X / RNE v1.00
OA CFM: 0.00 K
OA Sp.: 0.00 K
[Optional Input]
Line 2 Current Static Pressure
Requires the installation and wiring of a Duct Static
Pressure Sensor. If you do not have a Duct Static Pressure
Sensor correctly installed and wired to the controller, this line will display “0.0”.
Line 2 Outdoor Air CFM
If an outdoor air airfl ow monitoring station is being used, this is the current CFM reading of that device. K = 1000
Line 3 Outdoor Air Setpoint
If control of the OA Damper based on CFM is confi gured, this is the controlling setpoint. K = 1000
Line 3 Current Static Pressure Output Signal Percentage
Indicates the output signal percentage being supplied to the
VFD Controller or Bypass Damper Actuator when you
Line 4 Indicates That This is An Optional Input
This input may or may not have live data to display.
If you have not confi gured Duct Static Pressure Control, this line will display [No Press Out Confg].
Status Screen 15 - Supply Air & Return Air
CFM
Line 4 Indicates That This is An Optional Output
This output may or may not have live data to display.
Status Screen 13 - Economizer %,
OA Wetbulb, and CO
2
Level
VCM-X / RNE v1.00
SA CFM: 0.00 K
RA CFM: 0.00 K
[Optional Inputs]
VCM-X / RNE v1.00
Economizer.: XXX %
OA Wetbulb.: XX.XºF
CO2 Level.: XXXXPPM
Line 2 Supply Air CFM
If a supply air airfl ow monitoring station is being used, this is the current CFM reading of that device. K = 1000
Line 3 Return Air CFM
If a return air airfl ow monitoring station is being used, this is the current CFM reading of that device. K = 1000
Line 2 Current Economizer Open Percentage
The Economizer is optional. This shows the Outdoor Air
Damper open percentage. If Economizer Control is not
confi gured, it will display 0%.
Line 4 Indicates That These are Optional Inputs
These inputs may or may not have live data to display.
Line 3 Current Wetbulb/Drybulb Temperature
The Outdoor Air Wetbulb Temperature is optional. To display the Outdoor Air Wetbulb Temperature, you must install an Outdoor Air Temperature Sensor (or an Outdoor
Air Temperature Broadcast) and an Outdoor Air Relative
Humidity Sensor. If these conditions exist, this line will
Outdoor Temperature.
If these conditions do not exist, it will display 0°F.
Line 4 Current CO
2
Level
CO
2
CO
2
Level is optional. You must install and confi gure a
Sensor to display the CO
2
Level. If a CO
2
Sensor is not
installed confi gured, this line will display 0 PPM.
52
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X / RNE STATUS
VCM-X / RNE Status Screens
Status Screen 16 - Building Pressure & Output % Status Screen 18 - Mod Heating & Cooling %
VCM-X / RNE v1.00
Building Pr..: X.XX”
Press Output: XXX%
[ Optional Outputs ]
VCM-X / RNE v1.00
Mod Heating: XXX%
Mod Cooling: XXX%
[ Optional Outputs ]
Line 2 Current Building Pressure
Indicates the current Building Pressure. This display requires the installation of a Building Pressure Sensor.
If you don’t have a Building Pressure Sensor correctly installed and wired to the controller, this line will display
“0.0”.
Line 3 Current Building Pressure Output Signal Percentage
Indicates the output signal percentage being supplied to the Exhaust Fan VFD controller or Exhaust Damper
Actuator when you have confi gured one of these options for your HVAC unit.
If you have not confi gured Building Pressure Control, this line will display [No Press Out Confg].
Line 4 Indicates That These Are Optional Outputs
This output may or may not have live data to display.
Line 2 Current Modulating Heating Output Signal Percentage
Indicates the percentage of the output signal being supplied to a Modulating Heating device when you have
confi gured this option for your HVAC unit. If Reverse
Acting operation is confi gured, this percentage will be
Reversed. See the following examples for clarifi cation:
Standard Operation:
0-10 VDC 0% = 0 VDC 100% = 10 VDC
2-10 VDC 0% = 2 VDC 100% = 10 VDC
Reverse Acting Operation:
0-10 VDC 0% = 10 VDC 100% = 0 VDC
2-10 VDC 0% = 10 VDC 100% = 2 VDC
If you do not have a Modulating Heating device confi gured, this screen will indicate [No Mod Heat Confi g].
Status Screen 17 - MODGAS Output %
& MHGRV Output %
Line 3 Current Modulating Cooling Output Signal Percentage
Indicates the percentage of the output signal being supplied to a Modulating Cooling device when you have confi gured this option for your HVAC unit. If reverse acting is
confi gured, this percentage will be reversed. See the following examples for clarifi cation:
VCM-X / RNE v1.00
MODGAS Pos..: XXX%
MHGRV Pos...: XXX%
[Optional Equipment]
Line 2 Current MODGAS Heating Output Signal
Indicates the percentage of the output signal being supplied
to the MODGAS Controller when you have one
connected to your HVAC unit. If you do not have a
MODGAS controller connected to your VCM-X or RNE
Controller, this screen will indicate [MODGAS NOT
CONNECTED].
0-10 VDC 0% = 0 VDC 100% = 10 VDC
2-10 VDC 0% = 2 VDC 100% = 10 VDC
1.5-5.0
Reverse Acting Operation:
0-10 VDC
2-10 VDC
0% = 10 VDC
0% = 10 VDC
100% = 5.0 VDC
100% = 0 VDC
100% = 2 VDC
Line 3 Current MHGRV Reheat Valve Output Signal
Percentage
Indicates the percentage of the output signal being supplied to the MHGRV controller when you have one connected to your VCM-X or RNE Controller. If you do not have an MHGRV controller connected to your VCM-X controller, this screen will indicate [MHGRV NOT
CONNECTED].
If you do not have a Modulating Cooling device connected to your HVAC unit and confi gured, this screen will indicate [No Mod Cool Confi g].
If this unit has a Dual Digital Module, Full Digital
Module, or Water Source Heat Pump with multiple
Digital Scroll Compressors, this line will be blank.
Line 4 Indicates That These Are Optional Outputs
These outputs may or may not have live data to display.
Line 4 Optional Equipment
Indicates that these outputs are optional and therefore may or may not have live data to display.
VCM-X / RNE Operator Interfaces Technical Guide
53
VCM-X / RNE STATUS
VCM-X / RNE Status Screens
Status Screen 19 / VCM-X - Full Digital Module
OR Dual Digital Module
Status Screen 19 / RNE - Full Digital Module
VCMX-M/HP Cnfg ID 102
Full Digital Temp
Coil A1: X.Xº F
Coil A2: X.Xº F
RNE Cnfg ID 102
Full Digital Temp
Coil A1: X.Xº F
Coil A2: X.Xº F
Line 2 Full Digital Temperature
If using a VCM-X Modular Controller ( OE332-23-VCMX-
MOD-A) with a Full Digital Module ( OE370-23-FD-A) or if you are using the VCM-X WSHP Controller ( VCMX-23-
VCMX-WSHP-A) with multiple Digital Scroll
Compressors, this screen will appear.
Line 2 Full Digital Temperature
If using a Full Digital Module ( OE370-23-FD-A) or
Water Source Heat Pump Module (OE334-23-WPM-A), this screen will appear.
Line 3 Coil A1 Temperature
This is the current Coil Suction Temperature of
Line 3 Coil A1 Temperature
This is the current Coil Suction Temperature of
Line 4 Coil A2 Temperature
This is the current Coil Suction Temperature of
Line 4 Coil A2 Temperature
This is the current Coil Suction Temperature of
Status Screen 20 /
VCM-X
- Full Digital Module
VCMX-M/HP Cnfg ID 102
Dual Digital Temp
Circuit A: X.Xº F
Circuit B: X.Xº F
VCMX-M/HP Cnfg ID 102
Full Digital Temp
Coil B1: X.Xº F
Coil B2: X.Xº F
Line 2 Dual Digital Temperature
If using a VCM-X Modular Controller ( OE332-23-VCMX-
MOD-C) with a Dual Digital Module ( OE370-23-DD) or if you are using the VCM-X WSHP Controller ( VCMX-23-
VCMX-WSHP-C) with two Digital Scroll Compressors, this screen will appear.
Line 3 Circuit A Temperature
This is the current Coil Suction Temperature of Circuit A.
Line 4 Circuit B Temperature
This is the current Coil Suction Temperature of Circuit B.
Line 2 Full Digital Temperature
If using a VCM-X Modular Controller (OE332-23-VCMX-
MOD-A) with a Full Digital Module (OE370-23-FD-A) or if you are using the VCM-X WSHP Controller (VCMX-23-
VCMX-WSHP-A) with at least two Digital Scroll
Compressors, this screen will appear. Values will show zero if not using 4 Digital Scroll Compressors.
Line 3 Coil B1 Temperature
This is the current Coil Suction Temperature of
Line 4 Coil B2 Temperature
This is the current Coil Suction Temperature of
54
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X / RNE STATUS
VCM-X / RNE Status Screens
Status Screen 20 / RNE - Full Digital Module
RNE Cnfg ID 102
Full Digital Temp
Coil B1: X.Xº F
Coil B2: X.Xº F
VCMX-M/HP Cnfg ID 102
Dual Digital
Comp A Sig: 0%
Comp B Sig: 0%
Line 2 Full Digital Temperature
If using a Full Digital Module ( OE370-23-FD-A) or
Water Source Heat Pump Module (OE334-23-WPM-A), this screen will appear. If not using (2) Full Digital
Modules, this screen will show no values.
Line 3 Coil B1 Temperature
This is the current Coil Suction Temperature of
Line 2 Dual Digital Signal
If using a VCM-X Modular Controller ( OE332-23-VCMX-
MOD-C) with a Dual Digital Module ( OE370-23-DD) or if you are using the VCM-X WSHP Controller ( VCMX-23-
VCMX-WSHP-C) with two Digital Scroll Compressors, this screen will appear.
Line 3 Compressor A Signal
This is the modulating signal percentage for Circuit A
Line 4 Compressor B Signal
This is the modulating signal percentage for Circuit B
Line 4 Coil B2 Temperature
This is the current Coil Suction Temperature of
Status Screen 21 / RNE - Full Digital Signal
Status Screen 21 / VCM-X - Full Digital Signal
OR Dual Digital Signal
RNE Cnfg ID 102
Full Digital
Stage 1 Sig: 0%
Stage 2 Sig: 0%
VCMX-M/HP Cnfg ID 102
Full Digital
Stage 1 Sig: 0%
Stage 2 Sig: 0%
Line 2 Full Digital Signal
If using a VCM-X Modular Controller ( OE332-23-VCMX-
MOD-A) with a Full Digital Module ( OE370-23-FD-A) or if you are using the VCM-X WSHP Controller ( VCMX-23-
VCMX-WSHP-A) with at least two Digital Scroll
Compressors, this screen will appear.
Line 3 Stage 1 Signal Percentage
This is the modulating signal percentage for Compressor
1 (A1) if there are two Digital Scroll Compressors, or for
Compressors 1 (A1) and 3 (B1) if there are four Digital
Line 2 Full Digital Signal
If using a Full Digital Module ( OE370-23-FD-A) or
Water Source Heat Pump Module (OE334-23-WPM-A) this screen will appear.
Line 3 Stage 1 Signal Percentage
This is the modulating signal percentage for Compressor
1 if there are two Compressors, or for the fi rst two
Compressors if there are four Compressors.
Line 4 Stage 2 Signal Percentage
This is the modulating signal percentage for Compressor
2 if there are two Compressors, or for the last two
Compressors if there are four Compressors.
Line 4 Stage 2 Signal Percentage
This is the modulating signal percentage for Compressor
2 (A2) if there are two Digital Scroll Compressors, or for
Compressors 2 (A2) and 4 (B2) if there are four Digital
VCM-X / RNE Operator Interfaces Technical Guide
55
VCM-X / RNE STATUS
VCM-X / RNE Status Screens
Status Screen 22 - Head Pressure Setpoint Status Screen 24 - Head Pressure Condenser
Fan #2
VCMX-M/HP Cnfg ID 102
Current
Head Pr Spt: 0 PSI
VCMX-M/HP Cnfg ID 102
Cond. Fan Sect. #2
Head Pr.....: 0PSI
Cond Fan Spd: 0%
Line 2-3 Current Head Pressure Cooling or Reheat Setpoint
If you are using the VCM-X Modular, VCM-X WSHP, or RNE Controller and have a One Condenser or Two
Condenser Head Pressure Module attached to the unit, the Head Pressure Cooling or Reheat Setpoint will display, depending on what mode the Module is in. This status value will show 0 if not in the Cooling or Dehumidifi cation
Mode.
Status Screen 23 - Head Pressure Condenser
Fan #1
Line 2 Condenser Fan #2
If you are using the VCM-X Modular, VCM-X WSHP, or RNE Controller and have a Two Condenser Head
Pressure Module attached to the unit, this line displays
Condenser #2.
Line 3 Head Pressure
This line indicates the highest of the second two Head
Pressure readings of the Two Condenser Head Pressure
Module.
Line 4 Condenser Fan Speed
This line displays the speed of the associated Condenser
Fan (0-100%) that is currently necessary to maintain the
VCMX-M/HP Cnfg ID 102
Cond. Fan Sect. #1
Head Pr.....: 0PSI
Cond Fan Spd: 0%
Status Screen 25 - Return Air Damper Signal
& Bypass Damper Signal
Line 2 Condenser Fan #1
If you are using the VCM-X Modular, VCM-X WSHP, or
RNE Controller and have a One Condenser or Two
Condenser Head Pressure Module attached to the unit, this line displays Condenser Fan #1.
VCM-X / RNE v1.00
Return Dmp..: XXX%
Bypass Dmp..: XXX%
[Optional Outputs]
Line 3 Head Pressure
This line indicates the highest of up to 4 current Head
Pressure readings on a One Condenser Head Pressure
Module. If using a Two Condenser Head Pressure Module, this line indicates the highest of the fi rst 2 current Head
Pressure readings on that module.
Line 2 Current Return Air Damper Signal
Indicates the current Output Signal percentage being sent to the Return Air Damper Actuator. If you haven’t confi gured a Return Air Bypass Damper, [No Return Dmp Confg] will be displayed instead.
Line 4 Condenser Fan Speed
This line displays the speed of the associated Condenser
Fan (0-100%) that is currently necessary to maintain the
Line 3 Current Return Air Bypass Damper Signal
Indicates the current Output Signal percentage being sent to the Return Air Bypass Damper Actuator. If you haven’t
confi gured a Return Air Bypass Damper, [No Bypass Dmp
Confg] will be displayed instead.
Line 4 Indicates That These Are Optional Outputs
This output may or may not have live data to display.
56
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X / RNE STATUS
VCM-X / RNE Status Screens
Status Screens 26-32 - Supply Fan Relay
VCM-X / RNE v1.00
Fan Relay: OFF
Cool Stage 1: OFF
Heat Stage 1: OFF
Status Screen 33 - Alarm Conditions
VCM-X / RNE v1.00
NO ALARMS
Line 2 Current Supply Fan Relay Status
The letters FRC will appear before the colon if this Relay is in a Force Mode. On screens 24 to 30, this line will indicate the relays use and the ON/OFF condition for that relay.
Possible options are as follows:
Pre-Heater
Heat Relay
Override
Line 2 Blank
Line 3 Alarm Conditions
Can be one of the following:
Gas Re-Heat ( HGR Relay) Heat Wheel
Emergency
Line 3 Current relay status and description of what it is
confi gured for
The letters FRC will indicate the relay is forced to its
Line 4 Current relay status and description of what it is
confi gured for
The letters FRC will indicate the relay is forced to its
If press
<ENTER>
, the screen will scroll through
VCM-X / RNE Operator Interfaces Technical Guide
57
VAV/ZONE CONTROLLER PROGRAMMING
VAV/Zone Confi guration Screens
VAV Zone Confi guration
In order to correctly set up the VAV/Zone Controller, you must fi rst confi gure several parameters in regard to the type of system and operating parameters for the VAV/Zone Controller you have installed. Most of these values and operating parameters are only set once at the initial system setup and are never changed.
Confi guration Screen #2 - Damper Operation
XX Box Cnfg IDXXXX
Damper Operating
Mode: DIRECT ACTING
[0=Direct 1=Reverse]
System Manager Instructions
From any Menu Screen, press the
<SETPOINTS>
button. The Unit
Selection Screen will appear requesting that you enter the unit ID number.
Enter the correct unit ID number of the VAV/Zone Controller you want to confi gure and press
<ENTER>
. You will see the screen shown below.
Enter
<0>
for Direct Acting or
<1>
for Reverse Acting. If the damper opens in a clockwise direction, it is DIRECT ACTING. If the damper opens in a counter-clockwise direction, it is REVERSE ACTING.
1) Change Setpoint
2) Configure Unit
3) Damper Force
ESC) Exit Menu
CAUTION: If you change this setting, you MUST cycle power to the controller to allow it to re-calibrate the damper feedback positions for its new direction of control!
Confi guration Screen #3 - Voting Zone
Press
<2>
on the keypad to enter the fi rst Unit Confi guration Screen.
Modular Service Tool Instructions
From any Menu Screen, press the
<CONFIGURATION>
button. The
Unit Selection Screen will appear requesting that you enter the unit ID number. Enter the correct unit ID number of the VAV/Zone controller you want to confi gure, and press
<ENTER>
. You will then see Unit
Confi guration Screen #1.
XX Box Cnfg IDXXXX
Is This Box a
Voting Zone..: YES
[0=NO 1=YES]
If this is a Zoned System, select this option so that the box can be included as a voting zone.
Confi guration Screen #1 - Box Confi guration
Confi guration Screen #4 - Pressure
Independent Airfl ow Constant
XX Box Cnfg IDXXXX
Box Configuration
COOLING ONLY BOX
[Enter Type 0 - 3]
XX Box Cnfg IDXXXX
Pr Independent Boxes
Airflow @ 1” WG
Constant..: 1200 CFM
This Box Control Code will operate in one of four possible modes. The box designation will display on the top line of all screens.
If this is a Pressure Independent Box, you must enter this airfl ow constant so that the CFM readings can be correctly calculated. This airfl ow constant is provided by the box manufacturer and depends on the diameter of the duct.
0 = COOLING ONLY BOX (will display as CO Box)
1 = H/C CHANGEOVER BOX (will display as HC Box)
2 = SERIES FAN BOX (will display as SF Box)
3 = PARALLEL FAN BOX (will display as PF Box)
58
VCM-X / RNE Operator Interfaces Technical Guide
VAV/ZONE CONTROLLER PROGRAMMING
VAV/Zone Confi guration Screens
Confi guration Screen #5 - Expansion Relays
Heating Stages
XX Box Cnfg IDXXXX
Expansion Relays
[Optional]
Steps of Reheat.: 2
Confi guration Screen #9 - Push-Button
Override
XX Box Cnfg IDXXXX
Push-Button Override
Group ID #: 1
If you require the VAV/Zone Controller to control reheat for the zone it is installed in, you must include a relay expansion board and then confi gure the number of heating stages (1, 2, or 3) that it will be controlling whenever there is a heating demand in the space. Enter
<0>
if you don’t require this option.
During Unoccupied Mode, all zones with a corresponding Group ID # will resume Occupied operation whenever any of the zones in that group has its push-button depressed to initiate an override condition. This allows you to group zones in various areas of the building. For example, individual tenants with several offi ces could restore occupied mode for just their zones and not affect other zones in the building.
Confi guration Screen #6 - Proportional
Heating Signal
XX Box Cnfg IDXXXX
Proportional Heating
Signal..: 0 - 10 VDC
[0 = 0-10 1 = 2-10]
The default group ID number for all VAV/Zone Controllers is set at the factory to 1. If you don’t want a specifi c zone(s) to be part of that group, you must give each one a distinct Group ID number between 2 and 16.
Setting a zone’s Group ID number to 0 will disable the Space Sensor
Override Button function.
If you don’t want a specifi c zone to be a part of any group, enter
<0>
for its Group ID #.
Select this option to change the range of the proportional heat output from 0-10 VDC to 2-10 VDC.
Confi guration Screen #10 - Dump Zone
Confi guration Screen #7 - Box Heat Allow
XX Box Cnfg IDXXXX
Is This A Dump Zone
(No Actuator): NO
[0=NO 1=YES]
XX Box Cnfg IDXXXX
Allow Box Heat With
HVAC Heat....: NO
[0=NO 1=YES]
A “Dump Zone” is used when you want to control a duct heater or baseboard heater independently. A VAV/Zone Controller board with a relay expansion board is used for this purpose. No damper or actuator is used. If you need to control an auxiliary heater, select 1=YES; otherwise, be sure it is set to 0=NO.
Set this option to 1 = YES to allow the Heating Relay’s Controlling Box
Heat to remain on even when the HVAC unit is in Supply Air Heating
Mode. This is used as a method to provide supplemental heat if for some reason the HVAC heat cannot satisfy the heating demand.
Confi guration Screen #11 - HVAC Unit is on
Separate Loop
Confi guration Screen #8 - Main Fan Status
XX Box Cnfg IDXXXX
This Unit Needs Main
Fan Status...: NO
[0=NO 1=YES]
XX Box Cnfg IDXXXX
HVAC Unit is on
Separate Loop: NO
[0=NO 1=YES]
This setting only applies to the unoccupied mode of operation. Select
1=YES to activate the heating stages only when the main fan is operating on non-fan terminal units. For series fan terminal units, if this setting is set to 1=YES, the series box fan will only run when the main HVAC unit fan is running or when a space heating demand is made. For series fan terminal units, if this setting is set to 0=NO, the series box fan will only run when a space heating demand is made. This setting has no effect on the parallel fl ow fan terminal unit.
If this system has 1 HVAC unit controlling boxes on multiple loops and the HVAC unit is on a different loop than this box, select 1=YES; otherwise, be sure it is set to 0=NO.
VCM-X / RNE Operator Interfaces Technical Guide
59
VAV/ZONE CONTROLLER PROGRAMMING
VAV/Zone Setpoint Screens
VAV/Zone Controller Setpoints
Setpoint Screen #4 - Auxiliary Heat Setpoint
Setpoint Screen #1 - Occupied Setpoints
XX Box Spts IDXXXX
Occupied Setpoints
Cooling.....: XXºF
Heating.....: XXºF
XX Box Spts IDXXXX
Auxiliary Heat
Setpoint..: XXºF
Enter the Occupied Cooling Setpoint as the maximum temperature you would like the zone to reach before modulating the damper open to bring in more cold air to cool the space. Enter the Occupied Heat-
ing Setpoint as the minimum temperature you would like the zone to reach before activating the Reheat Stages on the optional Expansion
Relay board. If this is a Cooling Only box that doesn’t contain reheat, this setpoint will be ignored.
This setpoint allows you to set a Space Temperature that will enable the Auxiliary Heat Relay (Relay 4) on the VAV/Zone Controller Reheat Expansion Board for heating options other than box heat, such as baseboard heat or an external duct heater. This could control a stage of electric heat or an on/off hot water valve. The Auxiliary Heat Relay will energize at .5˚F below this setpoint and will de-energize at .5˚F above this setpoint. The Auxiliary Heat will continue to function regardless of the HVAC Mode the unit is in and at any airfl ow condition.
Description
Cooling Setpoint
Heating Setpoint
Minimum Default
50ºF 74ºF
50ºF 70ºF
Maximum
90ºF
90ºF
Description
Auxiliary Heat Setpoint
Minimum Default
50ºF 70ºF
Maximum
90ºF
Setpoint Screen #5 - Damper Airfl ow Integral
Setpoint Screen #2 - Unoccupied Setbacks
Minimum Default
0ºF
0ºF
+10ºF
-10ºF
Maximum
+30ºF
-30ºF
Setpoint Screen #3 - AHU Heat Call Space Temp
XX Box Spts IDXXXX
Damper/Airflow Spt
Integral [Ki]..: XXX
XX Box Spts IDXXXX
Unoccupied Setbacks
Cooling SetUp: XXºF
Heating SetBk: XXºF
During unoccupied hours, the Occupied Cooling Setpoint is adjusted up by the amount entered for the Cooling SetUp. The Occupied Heating Setpoint is adjusted down by the amount entered for the Heating SetBk.
Description
Cooling SetUp
Heating SetBk
The VAV/Zone Controller normally opens its damper based on a Proportional Error from Setpoint. That means if the zone temperature is 4°F from setpoint, the damper would be 100% open, or it would be modulating to provide the Maximum CFM on Pressure Independent boxes. If the error is less than 4°F, the damper may stagnate at that position and never satisfy the zone. If you add Integral into the damper calculation process, this will cause the damper or airfl ow calculations to continue to increase as long as the zone temperature is still above the setpoint. That means it can provide 100% or Maximum CFM before the 4°F error is achieved, bringing the zone under control faster than it normally would.
Start with a small (5 or 10) value, if you use this, and monitor the effect it has. If you enter too large a value, you can create “hunting” situations that can cause the damper actuator to prematurely wear out.
XX Box Spts IDXXXX
AHU Heat Call
Space Temp...: XXºF
Description
Integral
Minimum Default
0 0
Maximum
100
This setpoint allows you to set a Space Temperature that will cause the
VAV/Zone Controller to send a call for heat to the HVAC unit. This only occurs in the Unoccupied Mode.
Description
AHU Heat Call Space Temp
Minimum Default Maximum
50ºF 70ºF 90ºF
60
VCM-X / RNE Operator Interfaces Technical Guide
VAV/ZONE CONTROLLER PROGRAMMING
VAV/Zone Setpoint Screens
Setpoint Screen #6 - Damper Airfl ow Max &
Vent Min
XX Box Spts IDXXXX
Damper/Airflow Spt
Maximum..: XXX %
Vent Min.: XXX %
Setpoint Screen #8 - Damper Airfl ow Night Min and Fan On Min
XX Box Spts IDXXXX
Damper/Airflow Spt
Night Min.: XXX %
Fan On Min.: XXX %
The VAV/Zone Controller will not allow the damper or airfl ow calculation to exceed the Maximum setpoint while it is allowing the damper to modulate. During Vent mode when there is no heating or cooling demand, the damper or airfl ow will maintain at least the Vent Min amount of airfl ow into the zone for ventilation.
The Night Min is the position the damper will move to when the system is in Override Mode and this particular damper is not part of the override group. This Night Min position only affects non-fan powered boxes. The Fan On Min is the minimum damper or airfl ow setting used to activate the parallel fan if installed. Pressure Independent = CFM.
Pressure Dependent = %.
Description
Maximum
Vent Min
Minimum
0% or 0 CFM
0% or 0 CFM
Default
100% or
1000 CFM
25% or
250 CFM
Maximum
100% or
30000 CFM
100% or
30000 CFM
Description
Night Min
Fan On Min
Minimum
0% or
0 CFM
0% or
0 CFM
Default
0% or
0 CFM
25% or
250 CFM
Maximum
100% or
9999 CFM
100% or
9999 CFM
Setpoint Screen #7 - Damper Airfl ow Cool/
Heat Minimum
Setpoint Screen #9 - Damper Airfl ow Reheat Min
XX Box Spts IDXXXX
Damper/Airflow Spt
Cool Min.: XXX %
Heat Min.: XXX %
XX Box Spts IDXXXX
Damper/Airflow Spt
Reheat Min.: XXX %
During Supply Air Cooling Mode, if the space being served by this damper is satisfi ed and has no cooling demand, the damper will close to this Cool Min setting. This provides a minimum amount of airfl ow into the space for ventilation, even if the space does not require additional cooling. During Supply Air Heating Mode, if the space being served by this damper is satisfi ed and has no heating demand, the damper will close to this Heat Min setting. This provides a minimum amount of airfl ow into the space for ventilation, even if the space does not require additional heating.
The Reheat Min is the damper or airfl ow setting used during the Space
Reheat Mode of operation.
Description
Reheat Min
Minimum
0% or
0 CFM
Default
0% or
0 CFM
Maximum
100% or
30000 CFM
Description
Cool Min
Heat Min
Minimum
0% or
0 CFM
0% or
0 CFM
Default
10% or
1000 CFM
10% or
100 CFM
Maximum
100% or
30000 CFM
100% or
30000 CFM
Setpoint Screen #10 - Damper Airfl ow Fixed
Position
XX Box Spts IDXXXX
Damper/Airflow Spt
Fixed Pos: XXX %
Many times while troubleshooting a system, it is useful to have the zone damper set to a specifi c damper position or airfl ow setting. This setpoint can be used to determine where the damper/airfl ow will remain when the
VAV/Zone Controller receives a Force to Fixed Position command.
Description
Fixed Pos
Minimum
0% or
0 CFM
Default
0% or
0 CFM
Maximum
100% or
9999 CFM
VCM-X / RNE Operator Interfaces Technical Guide
61
VAV/ZONE CONTROLLER PROGRAMMING
VAV/Zone Setpoint Screens
Setpoint Screen #11 - SAT HVAC Mode
Deadband
XX Box Spts IDXXXX
SAT HVAC Mode
Deadband.: XXºF
Setpoint Screen #13 - Zone Alarm Delay
XX Box Spts IDXXXX
Zone Alarm Delay
Must Be Out Of
Limits For.: XXX Min
If the supply air temperature is above the space temperature by this amount, the VAV/Zone Controller enters the Supply Air Heating Mode.
It will remain in the Supply Air Heating Mode until the supply air drops to 2ºF above the space temperature. At that point the unit enters the
Supply Air Vent Mode and remains there until the supply air drops this deadband below the space temperature. At that point the VAV/Zone
Controller enters the Supply Air Cooling Mode and will remain there until the supply air temperature rises to 2ºF below the space temperature.
As mentioned above, if you confi gure the controller to generate zone temperature alarms, this is the amount of time after the box goes into the
Occupied Mode that the temperature must be outside the alarm limits before an alarm is generated.
Description
Out of Limits
Minimum Default
1 Min 30 Min
Maximum
300 Min
Setpoint Screen #14 - Day/Night Schedule
Description
SAT HVAC Mode
Deadband
Minimum
0ºF
Default
10ºF
Maximum
20ºF
Setpoint Screen #12 - Zone Alarm Offsets
XX Box Spts IDXXXX
Day/Night Schedule
Control #: X
0=AHU 1-5=Scheduler
XX Box Spts IDXXXX
Zone Alarm Offsets
Hi Zone......: XXºF
Lo Zone......: XXºF
The VAV/Zone Controller can be setup to generate an alarm anytime the box goes into the Occupied Mode and the Zone Temperature exceeds the user-defi ned alarm limits for a user-defi ned period of time. A High
Temperature Alarm Setpoint is created by adding the Hi Zone Alarm offset to the current Cooling Setpoint. The Low Temperature Alarm
Setpoint is created by adding the Lo Zone Alarm offset to the current
Heating Setpoint. If the zone temperature exceeds either of these limits for a period defi ned by the Alarm Delay setpoint, the controller can generate an alarm callout if all the optional hardware components required for this to occur are installed.
This screen allows you to set the VAV/Zone Controller to operate on a remote schedule instead of the schedule that is contained in the VCM-X or RNE Controller. Enter
<0>
to operate on the AHU schedule. Enter
<1-
5>
to use an external schedule. A GPC Plus is required for schedules 1-5.
Description
Schedule Control Number
Minimum Default Maximum
0 0 1 to 5
Setpoint Screen #15 - Maximum Slide Offset
XX Box Spts IDXXXX
Maximum Slide Offset
Effect on Spt.: XºF
Description
Hi Zone Alarm
Lo Zone Alarm
Minimum Default
+1ºF +30ºF
-1ºF -30ºF
Maximum
+50ºF
-50ºF
If the Flush Mount Wall Sensor has the optional Setpoint Slide Adjust, this is the maximum amount you can adjust the heating and cooling setpoints up or down as the slide is moved from the center position to its full up or down position.
Description
Effect on SP
Minimum Default
0ºF 0ºF
Maximum
6ºF
62
VCM-X / RNE Operator Interfaces Technical Guide
VAV/ZONE CONTROLLER PROGRAMMING
VAV/Zone Setpoint Screens
Setpoint Screen #16 - Push-Button Override
Duration
XX Box Spts IDXXXX
Push-Button Override
Duration : X.X Hr
Setpoint Screen #18 - Sensor Calibration for
Space Temp and Supply Air Temp
Sensor Calibration
SPC: XXX.Xº XXX.Xº
SAT: XXX.Xº XXX.Xº
[SAT Only if Sensor]
If the Flush Mount Wall Sensor has the optional Push-Button Override, this is the amount of the VAV/Zone Controller will resume using its Occupied Setpoints during unoccupied mode. This will generate a call for the Air Handler to start its fan and provide heating or cooling, depending on how you confi gure the Air Handler.
The Thermistor Type III sensor readings can be calibrated. Enter a
Positive value to increase a reading and a Negative value to decrease a reading.
Description
Duration
Minimum Default
0.0 Hr 0.0 Hr
Maximum
8.0 Hr
NOTE: The Supply Air Temperature calibration offset only operates on the reading when the VAV/Zone Controller has its own Supply Air Temperature sensor installed on the
AUX2 input. If the supply temperature is received from a global broadcast, you will need to go to the air handler to calibrate the temperature reading.
Setpoint Screen #17 - Maximum EMS Offset
XX Box Spts IDXXXX
Maximum EMS Setpoint
Offset...: XXºF
Description
SPC (Space Temp)
SAT (Supply Air)
Minimum Default
-100ºF 0ºF
-100ºF 0ºF
Maximum
+100ºF
+100ºF
If the Energy Management System (EMS) is activated, the heat and cool setpoints can be spread apart by this amount.
Description
Maximum EMS Setpoint
Offset
Minimum Default
0ºF 0ºF
Maximum
30ºF
VCM-X / RNE Operator Interfaces Technical Guide
63
VAV/ZONE CONTROLLER STATUS
VAV/Zone Status Screens
VAV/Zone Status
Status Screen #1 - Mode of Operation
XX Box v4.01 IDXXXX
Occupied Mode
Vent Mode
Belongs to Group # 1
Zone
Zone
Status Screen #3 - Slide Offset & H/C Demand
XX Box v4.01 IDXXXX
Slide Offset: XXºF
H/C Demand.: XX.XºF
Line 2
Unoccupied Mode
Line 2 If the optional Setpoint Slide Adjust is installed on the
Flush Mount Wall Sensor, this line will display the amount Slide Offset is affecting the
Heating and Cooling Setpoints.
Line 3 Current based on the current Heating and Cooling Setpoints when compared to the current Zone Temperature.
Line 4
Blank
Line 3 OFF Mode
Status Screen #4 - Supply Air Temperature &
Box Air Temperature
XX Box v4.01 IDXXXX
Supply Air: XX.XºF
Box Air..: XX.XºF
Line 4 Belongs to Group # xx
* Not displayed when using a Digital Room Sensor.
** Displays for either a temperature sensor failure or an airfl ow sensor failure.
Status Screen #2 - Zone Temperature and
Cooling/ Heating Setpoints
XX Box v4.01 IDXXXX
Zone Temp..: XX.XºF
Cooling Spt: XX.XºF
Heating Spt: XX.XºF
Line 2
Current Zone Temperature
Line 3
Currently active Cooling Setpoint based on the current
Occupied / Unoccupied mode of operation.
Line 4 Currently active Heating Setpoint based on the current
Occupied / Unoccupied mode of operation.
Line 2 Current Supply Air Temperature received via broadcast from the DX Air Handler or from the Box
Controller’s own installed Box Air Temperature Sensor connected to the AUX input of the VAV/Zone
Line 3
Current Box Air Temperature
If you have confi gured the VCM-X or RNE Controller to broadcast the Supply Air Temperature to the VAV/
Zone Controller and don’t have a Box Air Temperature
Sensor attached to the AUX input on the VAV/Zone
Controller board, this line will display the Supply Air
Temperature the same as line 2.
If you have a Box Air Temperature Sensor attached to the AUX input on the VAV/Zone Controller board, this line will display the Box Air Temperature at the location where the Box Air Temperature Sensor is
installed.
Line 4
Blank
64
VCM-X / RNE Operator Interfaces Technical Guide
VAV/ZONE CONTROLLER STATUS
VAV/Zone Status Screens
Status Screen #5 - Zone Damper Position,
Airfl ow, and Desired CFM
Examples:
“1 Reheat Stages On” or
“2 Reheat Stages On” or
XX Box v4.01 IDXXXX
Damper FRC: XXX %
Airflow : XXXX CFM
Desired : XXXX CFM
Line 2 Current Zone Damper Position
If you entered a FORCE command, the letters FRC will appear. If this is normal damper operation, the
FRC will not be displayed.
Line 3 If this is a Pressure Independent box, the current
Airfl ow will be displayed. If not, this line will display the desired damper position.
Line 4 If this is a Pressure Independent box, this line will display the Desired CFM the box would like to provide to the zone. If not, this line will display
[Controls to +/- 3%] to indicate how accurately the damper will maintain the desired position.
If proportional heating is used (you have no relays
confi gured for heat), this line will display
“Heating Signal: xxx %”.
Line 4
If your VAV/Zone Controller has been confi gured to control reheat stages, this line refl ects the On/Off
Status of the second stage of Reheat. If you have 3 stages of reheat as explained on line 2, this line will be
blank.
Status Screen #7 - Alarm Status
XX Box v1.04 IDXXXX
NO ALARMS!
Status Screen #6 - Fan Status & Reheat
Stages
XX Box v1.04 IDXXXX
Fan Status : OFF
Heating Relay#1 : OFF
Heating Relay#2 : OFF
Line 2 Blank
Line 3 NO ALARMS!
This is displayed if no alarms are detected. If there are one or more alarms active, the possible messages are
Line 2
If this is a Fan Powered box, this line will display the
Fan On/Off Status. On non-fan powered boxes, this line will display [Exp Relay 1 Not Used].
Line 3
If your VAV/Zone Controller has been confi gured to control reheat stages, this line refl ects the On/Off of fi rst stage of Reheat. If you have 3 stages of reheat, this line will display the total number of
HI SPACE TEMP ALARM
Line 4
Blank
VCM-X / RNE Operator Interfaces Technical Guide
65
MINILINK PD PROGRAMMING
MiniLink PD Confi guration Screens
MiniLink PD Confi guration
In order to correctly setup the MiniLink PD, you must fi rst confi gure several parameters in regard to the type of system and operating parameters for the system it is installed on. Most of these values and operating parameters are only set once at the initial system setup and are never changed.
Confi guration Screen #3 - Mode Changeover
Time
Polling Unit Config
Mode Changeover Time
Minutes: XX
[Enter Period Time]
System Manager Instructions
From any Menu Screen, press the
<SETPOINTS>
button. The Unit
Selection Screen will appear requesting that you enter the unit ID number. All MiniLink PDs are set at address 60. Enter the correct unit loop number for the loop the MiniLink Polling Device is connected to (Loop
1 you would enter 1) and then enter
<60>
. Press
<ENTER>
. You will see the screen shown below.
This is the amount of time that you want to allow between changeover from heating to cooling modes.
Confi guration Screen #4 - Optimal Start
Target Zone
1) Change Setpoint
2) Configure Unit
3) Damper Force
ESC) Exit Menu
Polling Unit Config
Optimal Start
Target Zone..: XXX
[Enter Target Zone]
Press
<2>
on the keypad to enter the fi rst Unit Confi guration Screen.
Modular Service Tool Instructions
From any Menu Screen, press the
<CONFIGURATION>
button. The
Unit Selection Screen will appear requesting that you enter the unit ID number. Enter the correct unit ID number of the controller you want to confi gure and press
<ENTER>
. You will then see Unit Confi guration
Screen #1.
This is the unit ID of the Zone that you want to be satisfi ed by the normally scheduled start time. If you enter “-1” into this box, it will average all zones instead of picking a specifi c zone. If you do not require Optimal
Start, enter “0”.
Confi guration Screen #5 - Maverick Testing
Confi guration Screen #1 - System Type
Polling Unit Config
Maverick Testing
Disabled: YES
[0=NO 1=YES]
Polling Unit Config
System Type
Selection: X
[0=Zoning 1=VAV]
Disabling the Maverick Testing allows known troubled zone(s) to continue voting without causing a Maverick alarm. In other words, all zones are included in the voting regardless of whether they are more than four degrees from setpoint.
This screen allows you to select whether you want the system to behave as a VAV system or a Zoning System. If you select VAV, this will allow tenant logging for your VAV system.
Confi guration Screens #6-65 - Alarm Polling
Confi guration Screen #2 - Last Polled Zone
Polling Unit Config
Enable Alarm Polling
Unit XX : YES
[0=NO 1=YES]
Polling Unit Config
Last Polled Zone
Address: XX
[Enter Last Zone]
Enabling Alarm Polling allows any alarm from the loop to be polled.
You must set this for each controller on the loop.
This zone is the last zone on the local loop of your zoning system that is to be included in zone voting.
66
VCM-X / RNE Operator Interfaces Technical Guide
MiniLink PD Status
Status Screen #1 - Schedule Mode, System
Status, and Minutes Left
Polling Device
System Occupied
Venting Mode
XXX Min Left in Mode
Line 2 Current Schedule Mode
Can be System Occupied or System Unoccupied.
Line 3
Currently System Status
Can be Vent Mode, Cooling Mode, or Heat Mode.
Line 4
Minutes Left In Mode
The number of minutes left in the current mode of operation before it can switch modes. This value is
user-adjustable. Confi guration Screen #3.
MINILINK PD STATUS
MiniLink PD Status Screens
Status Screen #2 - Mode Priority, Cool Total, and Heat Total
Polling Device
No Mode Priority
Cool Total.: XX.XºF
Heat Total.: XX.XºF
Line 2 Mode Priority
Can be Heat Priority or Cool Priority. This is based on the voting zones and their demand.
Line 3 Cool Total
Total cooling temperature demand from all zones.
Line 4 Heat Total
Total heating temperature demand from all zones.
VCM-X / RNE Operator Interfaces Technical Guide
67
Zone
TROUBLESHOOTING
VCM-X / RNE / VAV/Zone Damper Force Modes
Zone
Damper Force Modes
Damper Force Modes are available for testing or balancing the system.
These Force Modes can be accessed and programmed from either the
System Manager or Modular Service Tool.
System Manager Instructions
To access the Damper Force Modes from the System Manager, press
<SETPOINTS>
. You will then see the Unit ID Screen. Enter the unit
ID of the controller you wish to access and press
<ENTER>
. The following screen will appear:
1) Change Setpoint
2) Configure Unit
3) Dampers Force
ESC) Exit Menu
Dampers Force Mode Screen
If the unit ID you entered is for a VCM-X or RNE Controller that has
VAV/Zone Controllers connected to its communication loop, the Damper
Force Mode will act as a “Global” Damper Force Mode. That is, all VAV/
Zone Controllers on that VCM-X or RNE Controller’s communication loop will be forced to the same Damper Force Mode setting. If the unit
ID you entered is for a VAV/Zone Controller, the Damper Force Mode setting will only apply to that VAV/Zone Controller.
Damper Force
Enter Force Mode: 0
0=Auto 1=Open 2=Clsd
3=Max 4=Min 5=Fixed
Set the appropriate Damper Force Mode by entering numbers 0 through
5. Following is a list of the force modes and their meaning:
Press
<3>
on the keypad and then press
<ENTER>
. You will then see the Unit ID Screen. Enter the unit ID of the controller you wish to access and press
<ENTER>
. At this time the Passcode Screen will be displayed.
Enter your level 2 passcode. Press
<ENTER>
and the Damper Force
Modes Screen will be displayed.
0 = Auto This is the default setpoint. With this setting, the damper will operate normally and modulate according to the controller setpoints.
1 = Open This setting will force the dampers to their fully-
2 = Clsd This setting will force the damper to its fully-
Modular Service Tool Instructions
When using the Modular Service Tool, simply press the
<BALANCE -
TEST>
key. You will then see the Unit ID Screen. Enter the unit ID of the controller you wish to access and press
<ENTER>
. The following screen will be displayed:
1) Outputs Force
2) Dampers Force
ESC) Exit Menu
Press
<2>
to access the Dampers Force Mode Screen.
3 = Max This setting will force the damper to its
Setpoint.
VAV/Zone
4 = Min This setting will force the damper to its Minimum
Setpoint.
VAV/Zone Controller
5 = Fixed This setting will force the damper to a fi xed position based on the Fixed Position Setpoint.
on page 61 for complete setpoint information.
CAUTION: The Damper Force Modes should only be used
by qualifi ed service personnel. Serious damage to
the ductwork could result if the dampers are all
forced closed and the HVAC unit fan is operating.
68 VCM-X / RNE Operator Interfaces Technical Guide
TROUBLESHOOTING
VCM-X / RNE Outputs Force
Outputs Force
Outputs Force settings are available for testing or troubleshooting the system. These Force settings can only be accessed and programmed from the Modular Service Tool. The System Manager does not allow for programming of this function.
The next screen displays the Relay Overrides for Relay 2. After press-
ing
<ENTER>
, the next relay will be displayed. All 20 Relay Over-
ride Screens (including the AHU fan relay) are available by pressing
<ENTER>
after each setting is made.
Relay Overrides
Relay 2 Override: 0
CAUTION: The Outputs Force settings should only be applied
by qualifi ed service personnel. Serious damage to
the HVAC unit could result from improper use of
these Outputs Force settings.
[0=Auto 1=ON 2=OFF]
After the screen for relay 21 is displayed, the fi rst Analog Output Over-
ride Screen will be displayed.
Analog Output 1 Screen
To access the Outputs Force settings, simply press the
<BALANCE -
TEST>
button on the Modular Service Tool. You will then see the Unit
ID Screen. Enter the unit ID of the VCM-X or RNE Controller you wish to access and press
<ENTER>
. The Outputs Force settings are only available for the VCM-X or RNE Controller. They are not supported for the VAV/Zone Controllers or other Add-on controllers. If you enter a unit ID for any other type of unit except a VCM-X or RNE Controller, the following screen will be displayed:
Economizer Overrides
Analog Output #1
Override Volts: -1.0
[-1.0=Auto]
Unit XXX Does Not
Support The Function
Press Any Key To
Continue
The default setting for normal operation is -1.0 volts. Voltages between
0 to 10.0 can be set for any of the Analog Output Overrides. Press
<ENTER>
after making a setting change and the next Analog Output
Override Screen will be displayed.
Analog Output 2 Screen
If you entered the unit ID of a VCM-X or RNE Controller, the following screen will be displayed:
1) Outputs Force
2) Dampers Force
Supply VFD Override
Analog Output #2
Override Volts: -1.0
[-1.0=Auto]
Press
<1>
to access the Outputs Force Screen.
Supply Fan Override
Enter Override...: 0
[0=Auto 1=ON 2=OFF]
Analog Output 3 Screen
Exhaust VFD Override
Analog Output #3
Override Volts: -1.0
[-1.0=Auto]
The fi rst Outputs Force Screen allows the AHU fan relay to be set for
Auto, ON, or OFF by entering a 0, 1, or 2 as desired. The default setting is 0=Auto. After you complete all troubleshooting or testing procedures, all relays should be changed back to this setting. The 1=ON setting will force the relay to the ON (energized) position. The 2=OFF selection will force the relay to the OFF (de-energized) position.
VCM-X / RNE Operator Interfaces Technical Guide
69
TROUBLESHOOTING
VCM-X / RNE Outputs Force
Analog Output 4 Screen
Mod Heating Override
Analog Output #4
Override Volts: -1.0
[-1.0=Auto]
Analog Output 5 Screen
Mod Cooling Override
Analog Output #5
Override Volts: -1.0
[-1.0=Auto]
Analog Output 6 Screen
RA Damper Override
Analog Output #6
Override Volts: -1.0
[-1.0=Auto]
Analog Output 7 Screen
RA Bypass Override
Analog Output #7
Override Volts: -1.0
[-1.0=Auto]
Zone
Zone
70 VCM-X / RNE Operator Interfaces Technical Guide
INDEX
A-C
0-10 VDC CW.........31
1 HVAC Unit w/Boxes on Multiple Loops Screen.........26,36
2-10 VDC CW.........31
24-Hour Military Format.........16
55 - 75 Tons.........32
63.........10
95 - 105 Tons.........32
120 - 140 Tons.........32
1111.........12
2222.........12
2359.........16
A
Adaptive Defrost Timer Adjustment.........46
Address, Entering.........9
AHU Heat Call Space Temperature, VAV/Zone.........60
Airfl ow
VAV/Zone Status.........65
Alarm Relay Confi guration.........27,37
Alarms
Button.........9
Clearing.........11,13
MiniLink Polling.........11,66
Modular Service Tool.........11,13
Search Screen.........13
VAV/Zone Status.........65
Alarms for VCM-X / RNE.........57
Analog Output Override Screen.........69
Arrow Keys, Defi ned.........8
Auto Damper Force Mode.........68
Automatic Power Down.........14
B
Balance-Test Button.........69
Defi ned.........9
Box Air Temperature
VAV/Zone Status.........64
Box Confi guration
VAV/Zone.........58
Box Heat Allow
VAV/Zone.........59
Broadcast
Internal Schedule Screen.........26,35
Internal Time Clock Screen.........25,35
Outdoor Air Humidity Screen.........25,35
Outdoor Air Temperature Screen.........25,35
Status Fan & Heat Screen.........25,35
Supply Temperature Screen.........25,35
VAV Boxes Force to Fix Screen.........26,36
VAV Boxes Force to Max Screen.........26,36
Broadcast to Multiple Loops.........26,36
Building Pressure
Deadband Setpoint.........44
Modulating Control Screen.........24,34
Output %.........53
Output Signal Screen.........24,34
Reverse Acting Control Screen.........24,34
Setpoint.........44
VCM-X / RNE Status.........53
Buttons
Balance Test.........69
Confi guration.........58
Overrides.........12
Schedule.........16
Setpoints.........38,58
Status.........49
Bypass Damper.........19,29
Bypass Damper Signal.........56
C
CFM, Outdoor Air.........23,32
CFM, Return Air.........23,33
CFM, Supply Air.........23,33
Change Passcodes.........12
Circuit A.........55
Circuit A Temperature.........54
Circuit B.........55
Circuit B Temperature.........54
Clear Alarms.........13
Alarms.........11
Clear Key
Defi ned.........8
Closed
Damper Force Mode.........68
CO
2
Level.........52
Protection Limit Max Level.........44
Protection Limit Reset Range.........44
Protection Limit Setpoint.........44
Sensor Maximum Scale Screen.........24,33
Sensor Output Signal Screen.........24,33
Coil 1 Temperature.........54
Coil 2 Temperature.........54
Coil A1 Temperature.........54
Coil A2 Temperature.........54
Coil B1 Temperature.........54
Coil B2 Temperature.........54
Coil Suction Temperature.........54
Coil Temperature.........51,54,55
Coil Temperature Setpoint.........51
Coil Temperature Status.........54
CommLink.........10
Communications Screen.........10,13
Compressor A1.........54
VCM-X / RNE Operator Interfaces Technical Guide
71
INDEX
C-D
Compressor A2.........54
Compressor A Signal.........55
Compressor B1.........54,55
Compressor B2.........54,55
Compressor B Signal.........55
Condenser Fan Speed.........56
Confi guration.........58
Button.........9,19,58
Reset Interval Rate.........20,30
Screen Index.........18
Confi guring
Main Fan Maximum Voltage.........26,36
Multiple System Managers Mode.........10
Network Mode.........10
Stand-Alone Mode.........10
Connection Diagram
Modular Service Tool.........4
System Manager.........5
Continuous OFF Mode.........16
Continuous ON Mode.........16
Controlling
Outdoor Air CFM.........43
Control Outdoor Air CFM.........23,32
Cooling Head Pressure Setpoint.........42
Cooling & Heating Stage Delays Screens.........27,37
Cooling Min Off Time.........27,37
Cooling Min Run Time.........27,37
COOLING ONLY BOX
VAV/Zone.........58
Cooling Setpoints, VAV/Zone Status.........64
Cooling Stage Relay.........57
Cooling Stage Relay Confi guration.........27,37
Cooling Status
VCM-X / RNE Controller.........49
Cool Total
MiniLink PD Status.........67
Current Active Supply Air Setpoint.........49
Current CO
2
Level.........52
Current Economizer Open Percentage.........52
Current Supply Air Temperature.........49
Current Wetbulb Temperature.........52
Cutoff Temperature Setpoints.........41
D
Damper Airfl ow
Cool/Heat Minimum.........61
Fan On Min.........61
Fixed Position.........61
Integral.........60
Maximum.........61
Night Minimum.........61
Reheat Minimum.........61,62
Vent Minimum.........61
72
Damper Force
Modes.........68
Damper Operation
VAV/Zone.........58
Dampers Forced Closed.........68
Data Entry Keys
Described.........8
Date
Programming.........15
Daylight Savings.........15
Time Auto Adjust Screen.........15
Day/Night Schedule
VAV/Zone.........62
Deadband
Outdoor Air CFM.........43
DEC Key
Defi ned.........8
Defrost Adaptive Timer.........46
Defrost Heat Wheel Setpoint.........47
Dehumidifi cation
Coil Temperature Setpoint.........42
Control Screen.........20,30
Indoor RH & OA Dewpoint Setpoints.........42
Priority Screen.........20,30
Unoccupied Screen.........20,30
Desired CFM
VAV/Zone Status.........65
Dewpoint Temp
VCM-X / RNE Status.........51
Digital Compressor Signal Screen.........21
Digital Scroll Compressor.........22,55
Dimensions
Modular Service Tool.........3
System Manager.........3
Direct Acting Control.........44
Display Screen
Described.........8
Dual Digital Module.........48,53,54,55
Status Screen.........48,54
Dual Digital Module Screen.........22
Dual Digital Signal.........55
Dual Digital Temperature.........54
Duct/Damper Size
Outdoor.........32
Return.........33
Supply Air.........33
Duct/Damper Size, Outdoor.........23
Duct/Damper Size, Return.........23
Duct/Damper Size, Supply Air.........23
Duct Static Pressure Screen.........19,29
Dump Zone
VAV/Zone.........59
VCM-X / RNE Operator Interfaces Technical Guide
E
Economizer
Control Screen.........20,30
Maximum Position if High CO
2
Level Setpoint.........43
OAT/WB Enable Setpoint.........43
Overrides.........69
Relay Confi guration.........27,37
Status.........49
Economizer %.........52
Economizer Open Percentage.........52
Economizer Relay.........57
Emergency Heat Confi guration.........27,37
Emergency Shutdown Input.........25,34
Energy Saving.........15
Screen.........14
Enter
Timer.........14
Key.........8
New Passcode.........12
ESC Key, Defi ned.........8
Exhaust Fan Relay.........57
Exhaust Fan Relay Confi guration.........27,37
Exhaust VFD Override.........69
Expansion Relays Heating Stages
VAV/Zone.........59
F
Fan On Min.........61
Fan Status.........65
Fan VFD Percentage.........19,29
Firestat Input.........25,34
Fixed Damper Force Mode.........68
Fixed Position Damper Airfl ow.........61
Free Cooling.........43
Full Digital Module.........53,54,55
Coil Temperature Status.........54
Signal Status.........55
Status Screen.........54
Full Digital Module Screen.........22
Full Digital Signal.........55
Full Digital Temperature.........54
G
Gas Reheat Relay.........57
INDEX
E-H
H
H/C Changeover Box VAV/Zone.........58
Head Pressure Condenser Fan #1 Status.........56
Head Pressure Condenser Fan #2 Status.........56
Head Pressure Cooling Setpoint Status Screen.........48,56
Head Pressure Module Screen.........22,32
Head Pressure Reheat Setpoint Status Screen.........48,56
Head Pressure Setpoint Cooling.........42
Head Pressure Setpoint Reheat.........42
Heat During Dehumidify Screen.........20,30
Heating
Min Off Time.........27,37
Min Run Time.........27,37
Setpoints.........64
Stage Down.........27,37
Stage Up.........27,37
Status.........49
Heating/Cooling Demand VAV/Zone Status.........64
Heating Stage Relay.........57
Heating Stage Relay Confi guration.........27,37
Heat Pump
Auxiliary Heating Delay.........46
Control Screen.........24,34
Heat Pump Defrost Setpoints.........46
Heat Pump Defrost Temperature.........46
Heat Pump Defrost Timer.........46
Heat Reset Source Setpoints.........40
Heat Total MiniLink PD Status.........67
Heat Wheel Defrost Setpoint.........47
Heat Wheel Relay.........57
HGR Relay.........57
Hi SAT Cutoff.........41
Holidays
Programming.........16
Start/Stop Times.........17
HVAC Mode
Cooling Setpoints.........39
Heating Setpoints.........39
Reset Source Screen.........19,29
Schedule Setpoint.........45
Select Deadband Setpoint.........39
Sensor Slide Offset Setpoint.........46
Setpoints.........39
HVAC Mode Enable Screen.........19,29
HVAC Reset Source.........19,29
Fan VFD Percentage.........19,29
No Reset.........19,29
Outdoor Air Temperature Sensor.........19,29
Remote Reset Signal.........19,29
Return Air Temperature Sensor.........19,29
Single Zone VAV.........19,29
Space Temperature Sensor.........19,29
VCM-X / RNE Operator Interfaces Technical Guide
73
INDEX
I-M
I
Indoor
Humidity Screen.........20,30
RH.........51
RH Setpoint.........51
Initialization
Modular Service Tool.........13
Screen.........13
System Manager.........10
Internal Schedule Optimal Start Soak Multiplier
Setpoint.........47
K
Keys
Described.........8
Function.........8
L
Last Polled Zone
MiniLink PD.........66
Leaving Water Temperature.........50
Level 1 User, Defi ned.........12
Level 2 User, Defi ned.........12
Loop
Address.........9
Search.........11
Search Screen.........11
Lo SAT Cutoff.........41
Lowest Coil.........51
M
Main Fan.........26,36
Main Fan Maximum Voltage.........26,36
Main Fan Status
VAV/Zone.........59
Maverick Testing
MiniLink PD.........66
Maximum
Damper Force Mode.........68
EMS Offset VAV/Zone.........63
Slide Offset VAV/Zone.........62
Maximum Outdoor Air CFM.........43
Maximum Voltage.........26,36
Maximum Voltage for Main Fan.........26,36
Max OA Damper Tempering Limit.........45
Mechanical Heat/Cool Failure Time
Period Setpoint.........45
MHGRV Output % VCM-X / RNE Status.........53
74
Min Damper Force Mode.........68
MiniLink PD Confi guration.........66
Alarm Polling.........66
Last Polled Zone.........66
Maverick Testing.........66
Mode Changeover Time.........66
Optimal Start Target Zone.........66
System Type.........66
MiniLink PD Status.........10
Adding Additional.........11
Cool Total.........67
Heat Total.........67
Minutes Left.........67
Mode Priority.........67
Schedule Mode.........67
System Status.........67
Minimum Outdoor Air CFM.........43
Minimum Run Times and Off Times.........27,37
Min Supply Fan VFD Speed for Heating Setpoint.........41
Minus Key, Defi ned.........8
Minutes Left
MiniLink PD Status.........67
MM (Multiple System Manager Mode).........10
Mod
Cooling %.........53,56
Cooling Override.........70
Heating %.........53
Heating Override.........70
Mode
Changeover Time.........66
Cooling Setpoint.........49
Enable Temperature.........49
Heating Setpoint.........49
of Operation.........13,64
Priority.........67
Selection Buttons Defi ned.........8
VCM-X / RNE Status Screen.........49
MODGAS Output %
VCM-X / RNE Status.........53
Modular Service Tool.........13
Alarms Button.........13
Alarm Search.........13
Confi guration Button.........19
Connection Diagram.........4
Defi ned.........3
Dimensions.........3
Energy Saving Timer.........14
Initialization.........13
Initialization Screen.........13
Mode Selection Buttons.........9
Network Confi guration.........13
Overrides Button.........14
Override Search.........14
VCM-X / RNE Operator Interfaces Technical Guide
INDEX
M-P
Overrides Tool.........13
Stand-Alone Confi guration.........13
VCM-X / RNE Setpoints.........38
Modular System Manager
Connection Diagram.........5
Defi ned.........3
Dimensions.........3
Network Connection.........5
Stand-Alone Connection.........7
Modulating
Cooling/Heating Screen.........21,31
Cooling Output Signal Screen.........21
Cooling Proportional Window Screen.........22,32
Cooling Reverse Acting Screen.........22,32
Heating Output Signal Screen.........21,31
Heating Proportional Window Screen.........21,31
Heating Reverse Acting Screen.........21,31
Modulating Cooling Type
0-10 VDC CW.........31
2-10 VDC CW.........31
VFD Full.........31
VFD Half.........31
Modulating Cooling Type Screen.........31
Monitor Supply Air CFM.........23,33
Month.........15
Morning Warm Up
Max Length.........41
Target Temp.........41
Temp Setpoint.........41
Multiple Loops.........26,36
Multiple MGRS.........10
Multiple System Managers Mode
Confi guring for.........10
N
Network Confi guration
Modular Service Tool.........13
Network Connection
Modular System Manager.........5
Network Mode (NM).........13
Confi guring for.........10
Night Minimum
Damper Airfl ow.........61
No Reset.........19,29
O
OA Dewpoint
VCM-X / RNE Status.........51
Occupied
Mode.........17
Setpoints.........60
Occupied Relay.........57
Occupied Relay Confi guration.........27,37
OE332-23-VCMX-MOD-A.........22,26,54,55
OE332-23-VCMX-MOD-C.........22,54,55
OE370-23-DD.........54,55
OE370-23-FD-A.........54,55
OE391-11.........3
OE392-07.........3
OFF Mode, Continuous.........16
ON Mode, Continuous.........16
Open Damper Force Mode.........68
Optimal Start Target Zone
MiniLink PD.........66
Outdoor
Humidity Sensor Screen.........20,30
Temperature.........51
Outdoor Air
Confi guration.........19,29
Cooling & Heating Lockouts Setpoints.........41
Relative Humidity.........51
Temperature.........51
Outdoor Air Airfl ow
VCM-X / RNE Output.........52
Outdoor Air CFM.........43,52
Outdoor Air CFM Deadband.........43
Outdoor Air Setpoint.........52
Outdoor Air Temperature Sensor.........19,29
Outdoor Duct/Damper Size.........23,32
Outputs Force Screen.........69
Override Relay.........57
Override Relay Confi guration.........27,37
Overrides
Button.........9,12,14
Screen.........12,14
Search.........12,14
P
PARALLEL FAN BOX
VAV/Zone.........58
Passcode
1111.........12
2222.........12
Clearance.........10
Codes.........12
Enter New.........12
System Manager.........12
Power/Comm Board Wiring.........6
Power Down.........14
Preheat Ambient Temperature.........45
Pre-Heater Relay.........57
Pre-Heater Relay Confi guration.........27,37
Pressure Independent Airfl ow Constant
VAV/Zone.........58
VCM-X / RNE Operator Interfaces Technical Guide
75
INDEX
P-R
Programming
Confi guring RNE.........29
Date.........15
Daylight Savings.........15
Day of Week.........15
Holidays.........16
Holiday Start/Stop Times.........17
Month.........15
Time & Date.........15
Year.........15
Proof of Flow Input Screen.........21,31
Proportional Heating Signal
VAV/Zone.........59
Push-Button Override
Duration.........63
Duration Setpoint.........46
VAV/Zone.........59
R
R22 Refrigerant.........42
R410A Refrigerant Screen.........26,36
RA Bypass Override.........70
RA Damper Override.........70
Real Time Clock.........15
Refrigerant.........42
Reheat Head Pressure Setpoint.........42
Reheat Minimum Damper Airfl ow.........61,62
Re-Heat Relay.........57
Reheat Relay Confi guration.........27,37
Reheat Stages.........65
Relay
Confi guration Screens.........27,37
Overrides.........69
Relay Confi guration
Alarm.........27,37
Cooling Stage.........27,37
Economizer.........27,37
Emergency Heat.........27,37
Exhaust Fan.........27,37
Occupied.........27,37
Override.........27,37
Pre-Heater.........27,37
Reheat.........27,37
Reversing Valve.........27,37
Warm-up Mode.........27,37
Relays.........57
Remote Reset Signal.........19,29
Remote Signal Contact.........16
Reset Source.........19,29
Cooling Setpoint.........39
Reset Interval Rate Screen.........20,30
76
Return Air
Bypass Control Screen.........25,34
Bypass Damper Factor Setpoint.........44
Confi guration.........19,29
Return Air CFM
Status.........52
Return Air Damper Signal.........56
Return Air Temperature.........50
Return Air Temperature Sensor.........19,29
Return Duct/Damper Size.........23,33
Reverse Acting Control.........44
Reversing Valve Active During Heat/Cool.........24,34
Reversing Valve Relay.........57
Reversing Valve Relay Confi guration.........27,37
RNE Controller.........49
Alarm Conditions.........57
Analog Output Override.........69
Building Pressure Output %.........53
Bypass Damper Signal.........56
Coil Temperature.........51
Confi guration Screens.........29
Cooling.........49
Damper Force Modes.........68
Date.........15
Dewpoint Temp.........51
Economizer.........49
Economizer Overrides.........69
Exhaust VFD Override.........69
Heating.........49
Holidays.........16
Holiday Start/Stop Times.........17
Indoor RH Setpoint.........51
Leaving Water Temperature.........50
MHGRV Output %.........53
Mod Cooling %.........53,56
Mod Cooling Override.........70
Mode.........49
Mode Cooling Setpoint.........49
Mode Enable Temperature.........49
Mode Heating Setpoint.........49
MODGAS Output %.........53
Mod Heating %.........53
Mod Heating Override.........70
OA Dewpoint.........51
Occupied Mode.........17
Outdoor Air Relative Humidity.........51
Outdoor Air Temperature.........51
Outputs Force.........69
RA Bypass Override.........70
RA Damper Override.........70
Relay Overrides.........69
Return Air Damper Signal.........56
Schedule Override.........17
VCM-X / RNE Operator Interfaces Technical Guide
INDEX
R-S
Scheduling.........16
Space Temperature Return Air and Slide Adjust.........50
Static Pressure Output %.........52
Status Screens.........49
Supply Air Temperature & Setpoint.........49
Supply Fan Relay.........57
Supply VFD Override.........69
Time & Date.........15
Unoccupied Mode.........17
Week Schedules.........16
RNE Setpoints.........38
Adaptive Timer Defrost Adj. Setpoint.........46
Building Pressure.........44
Building Pressure Deadband.........44
CO
2
Protection Limit.........44
COIL Sensor Calibration.........47
Cool Reset Source.........39
Cutoff Temperature.........41
Dehumidifi cation Coil Temperature.........42
Dehumidifi cation Indoor RH & OA Dewpoint.........42
Economizer Maximum Position if High
CO
2
Level.........43
Economizer Minimum Position & Control Rate.........43
Economizer OAT/WB Enable.........43
Head Pressure.........42
Heat Pump Auxiliary Heating Delay.........46
Heat Pump Defrost Setpoints.........46
Heat Reset Source.........40
Heat Wheel Defrost Setpoint.........47
HVAC Mode Select Deadband.........39
HVAC Mode Sensor Slide Offset.........46
HVAC Schedule.........45
Internal Schedule Optimal Start Soak Multiplier.........47
Low Ambient Temperature.........45
Max OA Damper Tempering Limit.........45
Mechanical Heat/Cool Failure Time Period.........45
Minimum Supply Fan VFD Speed for Heating.........41
Morning Warm Up Temp.........41
Outdoor Air CFM.........43
Outdoor Air CFM Deadband.........43
Outdoor Air Cooling & Heating Lockouts.........41
Preheat Ambient Temperature.........45
Push-Button Override Duration.........46
Reset Source Cooling.........39
Return Air Bypass Damper Factor.........44
SAT Cooling.........39
SAT Heating Setpoints.........40
Screens.........39
Sensor Calibration for RAT & OAT.........47
Sensor Calibration for SPC & SAT.........47
Stage Control Window.........41
Static Setpoint, Deadband & Control Rate.........44
Supply Fan Starting Delay Timer.........45
Trend Log Interval.........47
Unoccupied Setbacks.........39
RNE Tonnage
55 - 75 Tons.........32
95 - 105 Tons.........32
120 - 140 Tons.........32
RNE Tonnage Screen.........32
S
SA (Stand Alone).........10
SAT Heating Setpoints.........40
Saturation Vapor Pressure.........42
Schedule
Button.........9,16
Mode.........67
Override.........16,17
Time & Date.........15
Scheduling
VCM-X / RNE Controller.........16
Screens
1 HVAC Unit w/Boxes on Multiple Loops.........26,36
Adaptive Defrost Adjustment Setpoint.........46
Alarm Search Screen.........13
Analog Output Override Screen.........69
Broadcast Internal Schedule Screen.........26,35
Broadcast Internal Time Clock Screen.........25,35
Broadcast Outdoor Air Humidity Screens.........25,35
Broadcast Outdoor Air Temperature Screen.........25,35
Broadcast Status Fan & Heat Screens.........25,35
Broadcast Supply Temperature Screen.........25,35
Broadcast VAV Boxes Force to Fixed Screen.........26,36
Broadcast VAV Boxes Force to Max Screen.........26,36
Building Pressure Deadband Setpoint.........44
Building Pressure Modulating Control Screens.........24,34
Building Pressure Output Signal Screens.........24,34
Building Pressure Reverse Acting Screens.........24,34
Building Pressure Setpoint.........44
CO
2
Protection Limit Setpoint.........44
CO
2
Sensor Maximum Scale Screen.........24,33
CO
2
Sensor Output Signal Screen.........24,33
Communications Screen.........10,13
Confi guration Screens.........18
Control Outdoor Air CFM.........23,32
Cooling & Heating Stage Delays Screens.........27,37
Cool Reset Source Setpoints.........39
Cutoff Temperature Setpoints.........41
Daylight Savings Time Auto Adjust Screen.........15
Dehumidifi cation Coil Temperature Setpoints.........42
Dehumidifi cation Control Screens.........20,30
Dehumidifi cation Indoor RH & OA Dewpoint
Setpoints.........42
Dehumidifi cation Priority Screen.........20,30
Dehumidifi cation Unoccupied Screens.........20,30
Digital Compressor Signal Screen.........21
Dual Digital.........22
VCM-X / RNE Operator Interfaces Technical Guide
77
S
INDEX
SCREENS, continued
Duct Static Pressure Screen.........19,29
Economizer Control Screen.........20,30
Economizer Maximum Position if High CO
2
Setpoint.........43
Level
Economizer Minimum Position & Control Rate
Setpoints.........43
Economizer OAT/WB Enable Setpoint.........43
Economizer Overrides.........69
Emergency Shutdown Input.........25,34
Energy Saving Screen.........14
Exhaust VFD Override.........69
Full Digital Module.........22
Head Pressure Module.........22,32
Head Pressure Setpoint Cooling.........42
Head Pressure Setpoint Reheat.........42
Heat During Dehumidify Screen.........20,30
Heat Pump Auxiliary Heating Delay.........46
Heat Pump Control.........24,34
Heat Pump Defrost Setpoints.........46
Heat Reset Source.........40
Heat Wheel Defrost Setpoint.........47
Holiday Schedule.........17
HVAC Mode Enable Screen.........19,29
HVAC Mode Select Deadband Setpoints.........39
HVAC Mode Sensor Slide Offset Setpoint.........46
HVAC Mode Setpoints.........39
HVAC Reset Source.........19,29
HVAC Schedule Setpoint.........45
Indoor Humidity Sensor Screen.........20,30
Initialization for Modular Service Tool.........13
Initialization Screen.........10
Internal Schedule Optimal Start Soak Multiplier
Setpoint.........47
Loop Search Screen.........11
Max OA Damper Tempering Limit.........45
Mechanical Heat/Cool Failure Time Period
Setpoints.........45
MiniLink PD Confi guration.........66
Minimum Supply Fan VFD Speed for Heating
Setpoint.........41
Mod Cooling Override.........70
Mod Heating Override.........70
Modulating Cooling/Heating Screen.........21,31
Modulating Cooling Output Signal.........21
Modulating Cooling Proportional Window
Screen.........22,32
Modulating Cooling Reverse Acting Screens.........22,32
Modulating Cooling Type.........31
Modulating Heating Output Signal Screen.........21,31
Modulating Heating Proportional Window
Screen.........21,31
Modulating Heating Reverse Acting Screen.........21,31
78
Monitor Outdoor Air CFM.........23,32
Monitor Return Air CFM.........23,33
Monitor Supply Air CFM.........23,33
Morning Warm Up Temp Setpoint.........41
Outdoor Air CFM Deadband Setpoint.........43
Outdoor Air CFM Setpoint.........43
Outdoor Air Cooling & Heating Lockouts Setpoints.........41
Outdoor Duct/Damper Size.........23,32
Outdoor Humidity Sensor Screen.........20,30
Outputs Force Screen.........69
Overrides Screen.........12,14
Preheat/Low Ambient Temperature Setpoint.........45
Proof of Flow Input Screen.........21,31
Push-Button Override Duration Setpoint.........46
RA Bypass Override.........70
RA Damper Override.........70
Relay Confi guration Screens.........27,37
Relay Overrides.........69
Return Air Bypass Control Screens.........25,34
Return Air Bypass Damper Factor Setpoint.........44
Return Duct/Damper Size.........23,33
Reversing Valve Active During Heat/Cool.........24,34
RNE Confi guration Screens.........29
RNE Status Screens.........49
RNE Tonnage.........32
SAT Cooling Setpoints.........39
Schedule Override.........17
Sensor Calibration for COIL.........47
Sensor Calibration for RAT & OAT.........47
Sensor Calibration for SPC & SAT.........47
Set Time & Date Screens.........15
Space Sensor Overrides Screen.........12
Split Condenser.........22
Stage Control Window Setpoints.........41
Static Setpoint, Deadband & Control Rate
Setpoints.........44
Supply Duct/Damper Size.........23,33
Supply Fan Cycle Screen.........19,29
Supply Fan Starting Delay Timer Setpoint.........45
Supply VFD Override.........69
Trend Log Interval Setpoint.........47
Unit Selection Screens.........9,29
Unoccupied Cooling & Heating Setbacks
Setpoints.........39
Uses R410A.........26,36
VAV/Zone Box Confi guration.........58
VAV/Zone Confi guration.........58
VAV/Zone Controller Setpoints.........60
VAV/Zone Damper Operation.........58
VAV/Zone Status.........64
VCM-X Confi guration Screens.........19
VCM-X / RNE Controller Status Screens.........49
VCM-X / RNE Operator Interfaces Technical Guide
Water Source Heat Pump Installed.........32
Week Schedules.........16
WSHP Protection Module.........22
Search
For Loops.........11
For Overrides.........12
Selection Buttons, Defi ned.........9
Sensor
RAT & OAT Setpoint.........47
Sensor Calibration
COIL.........47
Space Temperature.........63
SPC & SAT Setpoint.........47
Supply Air Temperature.........63
SERIES FAN BOX
VAV/Zone.........58
Setpoints.........43
Button.........9,19,38,58
Cool Reset Source.........39
Defrost Heat Wheel.........47
SAT Heating Setpoints.........40
Setting
Date.........15
Day of Week.........15
Month.........15
Year.........15
Signal Percentage.........55
Signal Status.........55
Single Zone VAV Mode.........19,29
Slide Adjust.........50
Slide Offset
VAV/Zone Status.........64
Smoke Detector Input.........25,34
Software, Current Version.........10
Space Sensor Overrides Screen.........12
Space Temperature.........50
Confi guration.........19,29
Space Temperature Return Air and Slide Adjust
VCM-X / RNE Status.........50
Space Temperature Sensor.........19,29
Split Condenser Screen.........22
Stage 1 Signal Percentage.........55
Stage 2 Signal Percentage.........55
Stage Control Window Setpoint.........41
Staging Up and Down Delay Periods.........27,37
Stand-Alone
Confi guration.........13
Connection.........7
Mode.........10,13
Start and Stop Times
2359.........16
ZERO.........16
VCM-X / RNE Operator Interfaces Technical Guide
INDEX
S
Static Pressure
Output % VCM-X / RNE Status.........52
VCM-X / RNE Output.........52
Static Spt, Deadband & Control Rate Setpoints.........44
Status
Button.........49
Key.........9
Status Screens
Dual Digital Module.........48,54
Full Digital Module.........54
Head Pressure Condenser Fan #1.........56
Head Pressure Condenser Fan #2.........56
Outdoor Air CFM.........52
Supply Air & Return Air CFM.........52
Suction Pressure.........42
Suction Pressure Transducer.........42
Supply Air
Confi guration.........19,29
Temperature.........64
Supply Air CFM
Status.........52
Supply Air & Return Air CFM.........52
Supply Air Temperature Reset.........19,29
Supply Air Temperature & Setpoint.........49
Supply Air with Supply Air Tempering.........19,29
Supply Duct/Damper Size.........23,33
Supply Fan
Cycle Screen.........19,29
Relay.........57
Starting Delay Timer Setpoint.........45
Supply Fan VFD.........19,29
Supply VFD Override.........69
System
Status.........67
Type.........66
System A.........50
System A Signal.........55
System A Signal Percentage.........55
System B.........50
System B Signal.........55
System B Signal Percentage.........55
System Manager
Connection Diagram.........5
Dimensions.........3
Initialization Screens.........10
Mode Selection Buttons.........9
Override Search.........12
Passcodes.........12
Setpoints Button.........19
VCM-X Setpoints.........38
System Manager TS II.........8
79
INDEX
T-V
T
Temperature
Circuit A.........54
Circuit B.........54
Coil B1.........54,55
Coil B2.........54,55
Dual Digital.........54
Full Digital.........54
Testing the System
Outputs Force.........69
Time
24-Hour Military Format.........16
Daylight Savings.........15
Time & Date.........15
Touch Screen System Manager.........8
Trend Log Interval.........47
Troubleshooting the System
Outputs Force.........69
Two Condenser Head Pressure Module.........56
U
Unit ID
Entering.........9
for Network System.........9
Stand Alone System.........9
Unit Selection Screen.........9,29
Unoccupied
Cooling & Heating Setbacks Setpoints.........39
Mode.........17
Setbacks.........60
V
VAV/Zone
AHU Heat Call Space Temperature.........60
Box Heat Allow.........59
Confi guration.........58
Controllers.........58,68
COOLING ONLY BOX.........58
Damper Airfl ow
Cool/Heat Minimum.........61
Integral.........60
Maximum.........61
Vent Minimum.........61
Damper Airfl ow Fixed Position.........61
Damper Airfl ow Night Minimum.........61
Damper Airfl ow Reheat Minimum.........61,62
Day/Night Schedule.........62
Dump Zone.........59
Expansion Relays Heating Stages.........59
H/C CHANGEOVER BOX.........58
Main Fan Status.........59
80
Maximum EMS Offset.........63
Maximum Slide Offset.........62
Occupied Setpoints.........60
PARALLEL FAN BOX.........58
Pressure Independent Airfl ow Constant.........58
Proportional Heating Signal.........59
Push-Button Override.........59
Push-Button Override Duration.........63
Sensor Calibration for Space Temperature.........63
Sensor Calibration for Supply Air Temperature.........63
SERIES FAN BOX.........58
Unoccupied Setbacks.........60
Voting Zone.........58
Zone Alarm Delay.........62
Zone Alarm Offsets.........62
VAV/Zone Confi guration, Damper Operation.........58
VAV/Zone Setpoints
AHU Heat Call Space Temperature.........60
Damper Airfl ow
Cool Minimum.........61
Heat Minimum.........61
Integral.........60
Maximum.........61
Vent Minimum.........61
Damper Airfl ow Fixed Position.........61
Damper Airfl ow Night Minimum.........61
Damper Airfl ow Reheat Minimum.........61,62
Day/Night Schedule.........62
Fan On Min.........61
Maximum EMS Offset.........63
Maximum Slide Offset.........62
Occupied Setpoints.........60
Push-Button Override Duration.........63
Sensor Calibration for Space Temperature.........63
Sensor Calibration for Supply Air Temperature.........63
Unoccupied Setbacks.........60
Zone Alarm Delay.........62
Zone Alarm Offsets.........62
VAV/Zone Status
Airfl ow.........65
Alarm Status.........65
Box Air Temperature.........64
Cooling Setpoints.........64
Desired CFM.........65
Fan Status.........65
Heating/Cooling Demand.........64
Heating Setpoints.........64
Mode of Operation.........64
Reheat Stages.........65
Screens.........64
Slide Offset.........64
Supply Air Temperature.........64
Zone Damper Position.........65
Zone Temperature.........64
VCM-X / RNE Operator Interfaces Technical Guide
INDEX
V-Z
VCMX-23-VCMX-WSHP-A.........22,26,54,55
VCMX-23-VCMX-WSHP-C.........22,54,55
VCM-X Controller.........49
Alarm Conditions.........57
Analog Output Override.........69
Building Pressure Output %.........53
Bypass Damper Signal.........56
Coil Temperature.........51
Confi guration Screens.........19
Cooling.........49
Damper Force Modes.........68
Date.........15
Dewpoint Temp.........51
Economizer.........49
Economizer Overrides.........69
Exhaust VFD Override.........69
Heating.........49
Holidays.........16
Holiday Start/Stop Times.........17
Indoor RH Setpoint.........51
Leaving Water Temperature.........50
MHGRV Output %.........53
Mod Cooling %.........53,56
Mod Cooling Override.........70
Mode.........49
Mode Cooling Setpoint.........49
Mode Enable Temperature.........49
Mode Heating Setpoint.........49
MODGAS Output %.........53
Mod Heating %.........53
Mod Heating Override.........70
OA Dewpoint.........51
Occupied Mode.........17
Outdoor Air Relative Humidity.........51
Outdoor Air Temperature.........51
Outputs Force.........69
RA Bypass Override.........70
RA Damper Override.........70
Relay Overrides.........69
Return Air Damper Signal.........56
Schedule Override.........17
Scheduling.........16
Space Temperature Return Air and Slide Adjust.........50
Static Pressure Output %.........52
Status Screens.........49
Supply Air Temperature & Setpoint.........49
Supply Fan Relay.........57
Supply VFD Override.........69
Time & Date.........15
Unoccupied Mode.........17
Week Schedules.........16
VCM-X Modular Controller.........22,54,55,56
VCM-X Schedule Holidays.........16
VCM-X Setpoints.........38
Adaptive Timer Defrost Adj. Setpoint.........46
Building Pressure.........44
Building Pressure Deadband.........44
CO
2
Protection Limit.........44
COIL Sensor Calibration.........47
Cool Reset Source.........39
Cutoff Temperature.........41
Dehumidifi cation Coil Temperature.........42
Dehumidifi cation Indoor RH & OA Dewpoint.........42
Economizer Maximum Position if High CO
2
Level.........43
Economizer Minimum Position & Control Rate.........43
Economizer OAT/WB Enable.........43
Head Pressure.........42
Heat Pump Auxiliary Heating Delay.........46
Heat Pump Defrost Setpoints.........46
Heat Reset Source.........40
Heat Wheel Defrost Setpoint.........47
HVAC Mode Select Deadband.........39
HVAC Mode Sensor Slide Offset.........46
HVAC Schedule.........45
Internal Schedule Optimal Start Soak Multiplier.........47
Low Ambient Temperature.........45
Max OA Damper Tempering Limit.........45
Mechanical Heat/Cool Failure Time Period.........45
Minimum Supply Fan VFD Speed for Heating.........41
Morning Warm Up Temp.........41
Outdoor Air CFM.........43
Outdoor Air CFM Deadband.........43
Outdoor Air Cooling & Heating Lockouts.........41
Preheat Ambient Temperature.........45
Push-Button Override Duration.........46
Reset Source Cooling.........39
Return Air Bypass Damper Factor.........44
SAT Cooling.........39
SAT Heating Setpoints.........40
Screens.........39
Sensor Calibration for RAT & OAT.........47
Sensor Calibration for SPC & SAT.........47
Stage Control Window.........41
Static Setpoint, Deadband & Control Rate.........44
Supply Fan Starting Delay Timer.........45
Trend Log Interval.........47
Unoccupied Setbacks.........39
VCM-X WSHP Controller.........22,26,54,55
VFD.........19,29
VFD Full.........31
VFD Half.........31
Voltage
Maximum for Main Fan.........26,36
Voting Zone Confi guration.........58
VCM-X / RNE Operator Interfaces Technical Guide
81
INDEX
W-Z
W
Warm-up Mode Relay.........57
Warm-up Mode Relay Confi guration.........27,37
Water Source Heat Module
Coil Temperature Status.........54
Signal Status.........55
Water Source Heat Pump.........53
Water Source Heat Pump Installed Screen.........32
Week Schedules
VCM-X / RNE Controller.........16
Wetbulb Temperature.........52
Wiring
Power/Comm Board.........6
WSHP Protection Module Screen.........22
Y
Year.........15
Z
Zone Alarm
Delay.........62
Offsets.........62
Zone Damper Position
VAV/Zone Status.........65
Zone Temperature
VAV/Zone Status.........64
82
VCM-X / RNE Operator Interfaces Technical Guide
NOTES
VCM-X / RNE Operator Interfaces Technical Guide
83
www.aaon.com
2425 So. Yukon Ave • Tulsa, OK 74107-2728
Ph: (918) 583-2266 • Fax: (918) 583-6094
AAON
®
Manual Part No. V23670
WattMaster Manual Form No: AA-VCMXRNEOI-TGD-01B
advertisement
Key Features
- Controller connection
- Initialization & configuration
- Programming & setpoints
- Status & alarm monitoring
- Troubleshooting tips
- System manager & service tool
- Stand-alone & networked systems
- Data entry keys
- Mode selection buttons
- Energy saving timer
Frequently Answers and Questions
How do I connect the Modular Service Tool to the VCM-X controller?
What are the different modes of operation for the Orion System?
What is the purpose of the Energy Saving Timer on the Modular Service Tool?
Related manuals
advertisement
Table of contents
- 3 INTRODUCTION
- 3 Modular Service Tool and Modular System Manager
- 4 SYSTEM CONNECTION
- 4 Modular Service Tool
- 5 Modular System Manager
- 6 Power/Comm Board Wiring
- 7 Modular System Manager - Stand Alone
- 8 INTERFACES OVERVIEW
- 8 Display Screens and Data Entry Keys
- 9 Mode Selection Buttons
- 9 Entering Unit ID (Address)
- 10 INITIALIZATION
- 10 System Manager Initialization
- 12 System Manager Passcodes
- 13 Modular Service Tool Initialization
- 14 Setting the Energy Saving Timer
- 15 Setting the Time and Date
- 16 Week Schedules
- 17 Holiday Schedules
- 17 Schedule Override
- 18 PROGRAMMING
- 18 VCM-X Confi guration Screen Index
- 19 Confi guring VCM-X Controllers
- 28 RNE Confi guration Screen Index
- 29 Confi guring RNE Controllers
- 38 VCM-X / RNE Setpoint Screen Index
- 39 Confi guring VCM-X / RNE Setpoints
- 48 VCM-X / RNE Status Screen Index
- 49 VCM-X / RNE Status Screens
- 58 VAV/Zone Confi guration Screens
- 60 VAV/Zone Setpoint Screens
- 64 VAV/Zone Status Screens
- 66 MiniLink PD Confi guration Screens
- 67 MiniLink PD Status Screens
- 68 TROUBLESHOOTING
- 68 Damper Force Modes
- 70 VCM-X / RNE Outputs Force
- 71 INDEX