Zennio IRSC Plus Air Conditioning Controller User Manual
Below you will find brief information for Air Conditioning Controller IRSC Plus. This device controls air conditioning systems using infrared signals. It receives commands over the KNX bus and uses them to control the various functions of the air conditioner, including temperature, fan speed, swing, and mode selection. The IRSC Plus can be configured to automatically switch off the air conditioner after a set time, or to turn off the air conditioner when an open window is detected to save energy. The device can also be configured to switch the air conditioning system off when a presence detector indicates that there is no one in the room.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
IRSC Plus
Air Conditioning Controller
ZN1CL-IRSC
Application program version: [6.1]
User manual edition: [6.1]_a
www.zennio.com
IRSC Plus
Contents
http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
2
DOCUMENT UPDATES
IRSC Plus
Version Changes
Changes in the application program:
- Additional split models available for control (*).
Page(s)
[6.1]_a
Description added about the “Disable device” object, and other objects available by default.
Reference added about A/C systems that allow multiple still positions for the swing function.
Details added about orders received during the “open window” state.
Details added about orders received during the “no detection” state.
General revision of texts and styles.
8, 9
9, 13
20
21
-
[5.14]_b
Changes in the application program:
- Improved compatibility with models 13 and 18.
- Method implemented for diagnosing the IR transmitter.
- Additional split models available for control (*).
(*) Please refer to the updated correspondence table, available at http://www.zennio.com
- http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
3
1
INTRODUCTION
IRSC Plus
1.1
THE IRSC CONTROLLER
The IRSC controller from Zennio is aimed at controlling air conditioning systems featuring infrared receivers (such as splits, ducted units with an integrated infrared interface, etc) through the emulation of their IR remote control systems. Therefore,
IRSC combines the following functions into the same device:
Control of the main functionalities of A/C units (On/Off, temperature, mode, fan speed, etc).
Compatibility with most air conditioning manufacturers (please refer to the correspondence table, available at: http://www.zennio.com
.
Device management through infrared codes:
Split units (application program: IRSC Plus).
A/V systems (application program: IRSC Open).
Ducted cooling/heating machines, with multiple zones to be acclimated
(application program: IRSC Zone).
Figure 1. IRSC controller
1.2
INSTALLATION
The IRSC controller is connected to the KNX bus via the bus connecting terminals. http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
4
IRSC Plus
Once the controller is provided with power from the KNX bus, both the physical address and the associated application program may be downloaded.
In Figure 2, the connection scheme of IRSC is shown.
Figure 2. Element diagram
1.- KNX connector.
2.- Programming LED.
3.- Programming button.
4.- Aerial connector.
5.- IR emitter.
6.- Socket for the aerial connector.
The functionality of the main elements is described next.
Programming button (3): a short press on this button sets the device into the programming mode, making the associated LED (2) light in red. If this button is held while plugging the device into the KNX bus, IRSC goes into secure mode.
IR emitter (5): infrared flashing diode to send commands to the air conditioning system. It must be placed in front of the air conditioning IR receiver (see Figure 1.3).
Air connector base (6): slot for the insertion of the aerial connector, through which the IR commands are outputted from IRSC.
Figure 3 shows how to locate the IR emitter (5) in front of the climate system.
http://www.zennio.com
Figure 3. IRSC - A/C unit interface
Technical Support: http://zennioenglish.zendesk.com
5
IRSC Plus
Once IRSC is connected and properly parameterised, it will be possible to control the
A/C unit from within the installation (for instance, from the InZennio Z38i or InZennio
Z41 touch panels), thus achieving an easier and more intuitive control.
Note: only one air conditioning unit may be controlled by each IRSC.
To obtain detailed information about the technical features of IRSC, as well as on security and installation procedures, please refer to the device Datasheet, provided with the original packaging of the device and also available at http://www.zennio.com
.
1.3
THE IRSC PLUS APPLICATION PROGRAM
The IRSC Plus application program has been developed to control
common air
conditioning systems via IR commands.
This application allows sending control orders to the A/C system through
infrared
commands, with IRSC acting as a KNX-IR interface, as explained in Section 1.1.
The IR commands required to control the different air conditioning systems have been already preset in the application. It is only necessary to check the IRSC Plus
correspondance table, available at http://www.zennio.com
, in order to identify the remote control model associated to the system. http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
6
2
CONFIGURATION
IRSC Plus
The IRSC Plus application program permits controlling air conditioning systems from different manufacturers as if they were being controlled through the infrared remote control of the machine.
A correspondence table is available at the Zennio homepage ( http://www.zennio.com
) with the codes (from 0 to 255) corresponding to the different remote controls that can be emulated. This number is the first parameter to be set in ETS, so that the orders sent by IRSC become particularised for the actual A/C unit to be controlled.
Moreover, the following functionalities of the A/C system can be configured:
ON/OFF control of the A/C system.
Status objects, which also work as acknowledgement objects for the orders sent to the system.
Working mode: the desired working mode (Automatic, Heat, Cool, Fan, Dry) may be chosen through independent binary objects (one per mode) or through a sole object (only one object for the mode selection). Moreover, apart from these conventional controls, it is possible to enable a simplified control, which only permits commuting from Heat to Cold and vice versa.
Fan speed: step-controlled or through a precise control.
Possibility of enabling and configuring:
Up to 4 different scenes.
Timed ON/OFF switching.
Energy saving functions, such as window sensor and presence
detection.
All these options are explained in detail in Section 3. ETS Parameterization.
http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
7
3
ETS PARAMETRIZATION
IRSC Plus
To begin with the parameterization process of the IRSC controller it is necessary, once the data base of the product ( IRSC Plus application program) has been imported to
ETS, to add the device to the project where desired. After that, one right-click on the device will permit selecting "Edit parameters", in order to start the configuration.
In the following sections a detailed explanation can be found about the different functionalities of IRSC Plus in ETS.
3.1
DEFAULT CONFIGURATION
This section shows the default configuration the device parameterization starts from for the first time.
Figure 4. IRSC Plus. Default topology
The following communication objects are available by default:
ON/OFF, aimed to receive orders from the bus to switch on or off the A/C unit.
Temperature, which will receive setpoint temperatures (in ºC) to be sent to the machine. Moreover, this object can work as a status object, as the “R”
(read) flag is active by default.
Fan [1 byte], aimed to receive orders from the bus to switch the A/C machine from one fan speed to another (automatic, minimum, medium or maximum, depending on the range the received value belongs to). http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
8
Mode
Auto
Min
Middle
Received value
0%
1% - 33%
34% - 66%
Maximum > 66%
Table 1. Fan speed
IRSC Plus
Fan [1 bit], aimed to receive orders from the bus to speed up (value “1”) or down (value “0”) the current air flow. This allows stepping through the different fan speed levels sequentially, which will be reflected in the value of the fan status object, if enabled (see section 3.3).
Swing, which is provided for the reception from the bus of orders to control the “swing” function (if available) of the A/C unit. The slats in the output air duct permit leading the air flow towards certain directions, and, depending on the machine, the behaviour may vary slightly. In general, receiving a “1” through this object will make the slats swing (i.e., perform a progressive sweep), while one “0” will make them stop. In the case of machines that permit multiple still positions for the slats, the arrival of the value “0” more than once will make IRSC send the A/C unit successive orders to switch from the current position to the next one, reverting the sequence order after reaching the last position.
Modes [1 byte], aimed to receive from the bus orders to switch the A/C unit from one working mode to another one (automatic, heat, cool, fan or dry, depending on the received value).
Mode
Auto
Heat
Cool
Fan
Dry
Received value
0 (0x00)
1 (0x01)
3 (0x03)
9 (0x09)
14 (0x0E)
Table 2. Modes (1 byte)
A set of independent binary objects, each destined to switching to a certain working mode ( auto, heat, cool, fan or dry) on the reception of the value “1”, as an alternative to the 1-byte Modes object, already described. http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
9
IRSC Plus
Disable device: binary object that will set IRSC into a standby mode on the reception of the value “1” from the bus. This prevents IRSC from reacting to control orders received from the bus –only read requests will be processed– and from sending IR orders to the A/C unit until the value “0” is received.
Therefore, once a certain state has been set to the A/C unit, sending the value “1” to this object will lock that state, preventing bus orders from changing it. This function makes sense, for example, when a centralised control system sends orders simultaneously to several IRSC controllers, and therefore to different A/C units. At a certain time (for power saving reasons, for instance), it may be required that any of them stops reacting to the centralised control orders, which can be done by sending a “1” to its corresponding IRSC controller (through the address of the “Disable device” object).
On the other hand, when IRSC Plus is parameterised for the first time, the following window will be shown:
Figure 5. Configuration screen by default
As shown in Figure 5, the configuration screen is divided into the following main tabs:
General parameters: general features of the air conditioning system being controlled.
Status: allows enabling and disabling a set of status objects over which it will be possible to send read requests from externally. These objects will report information about the current state of the machine and will also work as an acknowledgement signal of any changes made over this state whenever a control order is received from the bus. http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
10
IRSC Plus
Reset: allows customizing the status of the A/C system after a bus power failure or after an application program or parameter download, as well as selecting whether to send or not the updated status objects to the KNX bus.
Scenes: makes it possible to enable and configure up to 4 different climate scenes, or presets.
Timers: allows configuring an automatic switch-off or switch-on of the A/C system after a certain time.
Window sensor: permits switching the A/C system off when an “open window” signal arrives from the bus, in order to save energy.
Presence detector: permits switching the A/C system off when a “no presence detection” signal referring to the zone being acclimatised arrives from the bus, in order to save energy.
All the aforementioned tabs are detailed next.
3.2
GENERAL PARAMETERS
As shown in Figure 5, from the
General parameters tab it is possible to configure the main parameters of the A/C system to be controlled. These are the following:
Split model: sets a code (between 0 and 255) associated to the model of the
IR remote of the system to be controlled (please refer to the correspondence table at http://www.zennio.com).
Min. time set between two consecutive IR messages: allows establishing a minimum time gap (in tenths of a second) between consecutive IR commands sent from IRSC Plus to the A/C system (or split), thus restricting the rate of these commands and ensuring the proper reception of all of them.
It is recommended to set a value of 20 tenths of a second.
Note: setting a value lower than this does not necessarily imply an
improvement in the performance, and may turn into communication issues
between the KNX system and the A/C system. http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
11
IRSC Plus
Simplified mode: selecting this option brings the 1-bit communication object
"Simplified mode", which permits switching from the Cool to the Heat (working modes easily (0=Cool, 1=Heat, or alternatively 0=Heat, 1=Cool). This option is normally intended for simple installations where only binary orders are possible and for climate systems where other modes are not implemented.
Temperature range: when enabled ("Yes"), this functions allows restricting the values of the setpoint temperatures sent to the machine in the Heat and
Cool modes:
Cool mode Min. Temperature: lower limit, between 16 and 30ºC (21ºC by default).
Heat mode Max. Temperature: upper limit, between 16 and 30ºC (24ºC by default).
Enabling this option will bring a new 1-bit communication object, “Disable temperature limitation”, which will need to have the value “1” (default value) in order to have the parameterised temperature limitation effectively applied; in such case, the system will always keep the setpoint over the lower limit for
Cool mode and under the upper limit for Heat mode (truncating it when required). While the value of this object is “0”, temperature limitation is ignored.
Note: this temperature limitation only applies to modes Heat and Cool, no
matter if the simplified mode switching has been enabled or not.
3.3
STATUS
The Status tab permits enabling several status communication objects (all of them with the “R” flag enabled by default, making it possible to perform read requests over them).
Doing so implicitly makes IRSC Plus confirm the reception of the orders it receives from the KNX bus, so that after transmitting the IR commands to the A/C machine,
IRSC Plus also sends the corresponding status objects to the bus, thus reflecting whether the state has been changed or not as requested. http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
12
IRSC Plus
Figure 6. Status window
It is possible to activate status objects for the following actions:
ON/OFF: enables the "ON/OFF (status)" binary object, which shows the A/C system operation status: value "1" indicates that the system is active, whereas the value "0" indicates the system is inactive.
Mode: enables one status object per available mode ("Heat Mode (status)",
"Cool Mode (status)", "Dry Mode (status)", "Fan Mode (status)" and "Auto
Mode (status)") as well as the "Mode [1 byte] (status)" object. The first five objects (1-bit) are set to "1" when their corresponding modes are active, while
"0" indicates that the mode is not active. The 1-byte object is set to a certain
integer value according to the currently active mode (according to Table 2).
Fan: enables the "Fan (status)" 1-byte object, which shows the current fan
speed, in percentage, of the A/C system (according to Table 1).
Swing: enables the "Swing (status)" 1-bit object, which shows the current status of the slats of the A/C system (if available): the value "1" means that the swing is active, while "0" indicates that the slats are still. Note that the swing function may differ slightly depending on the A/C system model. Please
refer to section 3.1 for more details.
3.4
RESET - INITIAL CONFIGURATION
From the “Reset (initial configuration)” and the “Reset (data update)” tabs, the integrator will be able to set the desired response to be performed by IRSC Plus upon
KNX power losses as well as the initial status after a download or a device reset from http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
13
IRSC Plus
ETS. On the one hand, the former permits defining the desired status in the air machine after the power recovery and after a download (default and custom values are available for the ON/OFF, Temperature, Mode, Fan and Swing functions), whereas, on its side, the latter permits selecting whether the related communication objects should be sent or not to the KNX bus on power recovery or after a download.
Figure 7. Reset (Initial configuration)
Under the default configuration, after a power recovery IRSC Plus will assume the same status it had (and therefore, the air conditioning machine) before the power loss. This will not happen, however, after a download or a device reset from ETS (the previous status will be lost during the download or the device reset); in such case, IRSC Plus will assume ON/OFF=Off,
Temperature=25ºC, Mode=Cool, Fan=0%, Swing=Stopped.
Note: although IRSC Plus assumes the status it had before the bus power
loss, if during the interruption the A/C machine is externally manipulated or is also affected by the power loss (most models do not automatically switch on after a power loss), inconsistence between IRSC and the A/C unit may occur.
To avoid this, it is recommended to enable the “Send reset configuration to the split when reset occurs” parameter (explained below). Note that no orders will be sent to the A/C unit on power recovery unless this parameter is enabled.
Under a Custom configuration, it is possible to parameterise the following: http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
14
IRSC Plus
ON/OFF: after a bus failure, a download or a device reset, the A/C system it will be possible to send the A/C system an order to recover the last saved status
before the power loss or be switched off or on.
Temperature: after a bus failure, a download or a device reset, the it will be possible to send the A/C system an order to recover the last setpoint temperature (last saved position
1
) or a preset value ("Initial temperature", in Celsius degrees).
Mode: after a bus failure, a download or a device reset, the A/C system may be set to the last registered mode (last saved status
1
) or to one of the following: Heat, Cool, Auto, Dry or Fan.
Fan: after a bus failure, a download or a device reset, the A/C system may be required to recover the last registered fan level (last saved status
1
) or a particular one: Auto, Low, Medium or High.
Swing: after a bus failure, a download or a device reset, the status of the slats can be set to: Last saved status
1
, Swing or Stopped.
Note that for both, a default and for a custom configuration, the
“Send reset
configuration to the split (when reset occurs)” parameter needs to be enabled to actually send the corresponding initial values to the A/C system on the power recovery.
If disabled, such IR commands will not be sent, but IRSC will still assume the parameterized configuration as the initial state after the power recovery.
Important: it is recommended, in any case, to enable this sending to avoid
inconsistence between the state assumed by IRSC and that actually acquired by the
A/C unit once the power failure is solved. On the other hand, sending the corresponding communication objects to the bus (so that the other devices in the KNX environment are properly kept up to date) may be enabled from the “Reset (Data
Update)” screen (see Section 3.5)
1
This specific option has no effect after downloads or device resets because the previous status of the device is always lost; default values (ON/OFF=Off, Temperature=25ºC,
Mode=Cool, Fan=0%, Swing=Stopped) will be then assumed http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
15
3.5
RESET - DATA UPDATE
IRSC Plus
Independently of the status of IRSC Plus after bus power interruptions, a download or a device reset from ETS, and also independently of whether the related orders should be
sent or not to the air machine (see Section 3.4), it is possible to activate initial sendings
of the status objects to the KNX bus, so that other KNX devices are informed about the
(new or not) state of the IRSC Plus controller (and thus, of the state sent to –or assumed in– the A/C system) after a bus interruption, a download or a device reset.
This is done from the “Reset (Data Update)” screen.
Figure 8. Reset (Data update)
It is possible to select which status objects will be sent to the bus (“Send”) and which will not (“Don’t send”), among the following:
ON/OFF: the On/Off status of the A/C system will be sent to the bus through the "ON/OFF (status)" object.
Temperature: the setpoint assumed after the bus failure, the download or the device reset will be sent to the bus through the "Temperature" object.
Mode: the working mode assumed by the A/C system after the bus failure, the download or the device reset will be sent to the bus through the "Mode
(status)" object. http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
16
IRSC Plus
Fan: the fan level assumed by the A/C system after the bus failure, the download or the device reset will be sent to the bus through the "Fan (status)" object.
Swing: the slats status assumed by the A/C system after the bus failure, the download or the device reset will be sent to the bus through the "Swing
(status)" object.
As stated, these values are sent to the KNX bus through the corresponding status object (the status of the temperature setpoint, however, is sent through the
“Temperature” general object, also intended for the reception of the control orders).
Therefore,
the required status objects should have been enabled (see section 3.3)
in order to have these values effectively sent to the bus.
Important: if this sending is not enabled, the KNX bus will definitively not be informed
about the initial status of IRSC Plus, no matter if it is a custom status or the status it
already had before the bus failure (see Section 3.4).
To sum up, selecting "Send" for the above parameters (some or all of them) will make
IRSC send its initial status to the rest of the devices connected to the bus, to have them properly updated.
3.6
SCENES
Scenes consist in simultaneously sending various IR commands to the air conditioning system, so that a certain climate configuration can be activated by simply sending the proper value (i.e., the numeric value associated to that particular scene) through the
KNX bus.
IRSC Plus allows enabling and configuring up to 4 different scenes. http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
17
IRSC Plus
Figure 9. Scenes window
After selecting the option "Yes" for "Scenes (will scenes be used?)", the "Scenes [1 byte]" object will be shown. This is the object intended to receive from the KNX bus the scene activation orders.
Four additional fields will appear, from which it is possible to independently enable
("Yes") the four available scenes. For every enabled scene, the following options should be parameterised according to the atmosphere to be generated.
Scene number: the numeric value (1 to 64) on whose arrival from the bus
(through the “Scenes [1 byte]” object, decreased by one –0 to 63–) the air conditioning system will execute the scene.
ON/OFF: permits selecting whether, on the execution of the scene, the A/C system should be switched on (“ON”), off (“OFF”) or left as is (“No change”).
Temperature: permits selecting whether, on the execution of the scene, the setpoint temperature of the A/C system should be changed to a certain value
(between 16 and 30ºC) or left as is (“No change”).
Mode: permits selecting whether, on the execution of the scene, the A/C system should be set to a certain mode (Auto, Heat, Dry, Fan or Cool) or left as is (“No change”). http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
18
IRSC Plus
Fan: permits selecting whether, on the execution of the scene, the fan level of the A/C system should be set to a certain value (Auto, Low, Medium, High) or left as is (“No change”).
Swing: permits selecting whether, on the execution of the scene, the swing function of the A/C system should be set to a certain status (“Stop” or
“Swing”) or left as is (no change).
3.7
TIMERS
This function permits timed on/off switches of the air conditioning system.
Figure 10. Timers screen
Automatic switching on and off can be independently enabled and configured. After activating the Automatic OFF, the "Fixed Auto-OFF [1 bit]" object will appear, and the following parameters will also be shown in ETS:
Automatic OFF value: sets the time interval (between 0 and 255) that IRSC
Plus waits once the “Fixed Auto-OFF” object is activated (value "1) before proceeding with the switch-off.
Automatic OFF time units: sets whether the above value is expressed in hours or minutes.
After activating the Automatic ON, the "Fixed Auto-ON [1 bit]" object will appear, and the following parameters will also be shown in ETS:
Automatic ON value: sets the time interval (between 0 and 255) that IRSC
Plus waits once the “Fixed Auto-ON” object is activated (value "1) before proceeding with the switch-on. http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
19
IRSC Plus
Automatic ON time units: sets whether the above value is expressed in hours or minutes.
3.8
WINDOW SENSOR
After activating this feature the 1-bit object "Window sensor" is shown, with the aim to be linked (via the same group address) to any binary input in the installation that monitors whether a window has been opened in the air conditioned zone.
Figure 11. Window sensor
After activating this function, the " Waiting period" parameter can be configured. It shows the time interval (in seconds) that the window must remain open before the A/C system switches off.
This way, once IRSC Plus receives through the "Window sensor" object the value "1"
(value associated to the "window open" event) it will wait for the configured waiting period and then it will send a switch-off order to the A/C system. When the window is closed again ("Window sensor"=0), the A/C system will be automatically switched on – it will not be necessary to send a switch-on order.
Note: during the “open window” state, the device will still accept requests from the bus
and update its objects according to them. Although the machine is off, as soon as it is switched on again, IRSC will send the proper commands to update its state as corresponding. Because of this, in the particular case of receiving a switch-off order while the window is open (therefore, being the machine already off), closing the window will not make the A/C unit turn on again as IRSC will then send an order to switch it off.
In such case, an explicit ON order will be required.
http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
20
3.9
PRESENCE DETECTOR
IRSC Plus
Presence detectors (like Zennio’s ZN1IO-DETEC sensor), installed inside a room, permit multiple applications, such as switching lights on and off, detecting intruders, dimming lights, etc. Besides, if combined with the IRSC controller, presence detectors contribute to energy saving by switching the A/C system off when the room is empty.
Figure 12. Presence detector
Activating this feature brings the 1-bit "Presence detection" object, which should be linked to the presence detection object, so that it is aware of presence/no presence changes.
Also the "Waiting period" parameter becomes visible, and defines the time period (in minutes) that IRSC Plus should wait after receiving the value "0" (empty room) through the detection object before switching the A/C unit off.
As soon as the "Presence detection" object receives the value "1", IRSC Plus considers the room is again occupied, so if the value "0" arrives again, the time count will start again.
Note: during the “no detection” state, the device will still accept requests from the bus
and update its objects according to them. Although the machine is off, as soon as it is switched on again, IRSC will send the proper commands to update its state as corresponding. Because of this, in the particular case of receiving a switch-off order under “no detection” (therefore, being the machine already off), a later presence detection will not make the A/C unit turn on again as IRSC will then send an order to switch it off. In such case, an explicit ON order will be required.
http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
21
IRSC Plus
ANNEX I. DIAGNOSING THE IR TRANSMITTER
This annex describes a method for testing that the IRSC Plus built-in infrared transmitter is working and therefore is properly emulating the remote control of the air conditioning unit and, thus, sending the corresponding orders to the unit.
The procedure explained below consists in emulating, from IRSC Plus, presses made on the remote control (models ZN1IR-ZAS and ZN1IRZ38) of any of the various Zennio devices capable of receiving IR signals (ZAS, InZennio Z38i, ACTinBOX Hybrid,
ACTinBOX MAX6 or ACTinBOX QUATRO). One of these devices will be therefore required during the test.
Suggested procedure
Set the value “0” to the Split model parameter in the “General parameters” screen.
Link the ON/OFF object (at least) to a group address.
After downloading parameters and group addresses, IRSC Plus will respond to the ON/OFF orders by emitting infrared signals similar to those emitted by the ZN1IR-ZAS and ZN1IRZ38 remotes when the upper left pair of buttons are pressed (left button after an OFF order; right button after an ON order). http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
22
OFF ON
OFF ON
IRSC Plus
Figure 13 Switch-on and switch-off orders
This way, sending switch-on and switch-off orders through the ON/OFF object makes it possible to check the effect, over the receiver device (ZAS, InZennio Z38i, ACTinBOX
Hybrid, ACTinBOX MAX6 or ACTinBOX QUATRO), of the signals generated by the emitter, and therefore whether IRSC Plus is behaving anomalously or not.
Important: it is highly advisable to locate the IRSC Plus infrared transmitter in front of
the optimal reception point in the receiver. In case of using an ACTinBOX actuator as a
receiver, the transmitter should be directly attached to the device housing. http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
23
ANNEX II. COMMUNICATION OBJECTS
IRSC Plus
Column RESET shows the values of the communication objects after a reset, although this does not necessary imply that such values are sent to the bus.
Cells marked as (*) in the 1
ST
TIME and RESET columns show the possibility of sending such object to the bus (either as a write message or as a read request) when those events occur.
SIZE
1 Bit
1 Bit
1 Bit
1 Bit
1 Byte
1 Byte
1 Bit
1 Bit
2 Bytes
1 Byte
1 Bit
1 Byte
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
NUMBER
5
6
3
4
0
1
2
7
8
9
10
11
12
13
14
15
16
17
18
19
I/O
I
O
I
O
I
O
I
O
I
O
I/O
I
I
O
I
O
I
O
I
O
FLAGS
C - - W U
C T R - -
C T R W U
C T - W U
C - - W -
C T R - -
C T - W U
C T R - -
C T - W U
C T R - -
C T - W U
C T R - -
C T - W U
C T R - -
C T - W U
C T R - -
C T - W U
C T R - -
C T - W U
C T R - -
DATA TYPE (DPT)
On/off
On/off
Temperature (°C)
Percentage (0..100%)
On/off
Percentage (0..100%)
On/off
On/off
On/off
On/off
On/off
On/off
On/off
On/off
On/off
On/off
On/off
On/off
[20.105] DPT_HVACContrMode
[20.105] DPT_HVACContrMode
RANGE
0/1
0/1
-273 - 670760
0 - 100
0/1
0 -100
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0, 1, 3, 9, 14
0/1
VALUES
1ST TIME
0 / Param
Param (*)
25 / Param (*)
-
-
0 / Param (*)
-
0 / Param (*)
-
0 / Param (*)
-
0 / Param (*)
-
0 / Param (*)
-
0 / Param (*)
-
0 / Param (*)
-
3 / Param (*)
RESET
Param
Param (*)
Last / Param (*)
Last /Param
-
Last / Param (*)
Last /Param
Last / Param (*)
Last /Param
0 / Param (*)
Last /Param
0 / Param (*)
Last /Param
0 / Param (*)
Last /Param
0 / Param (*)
Last /Param
0 / Param (*)
Last /Param
3 / Param (*)
NAME
ON/OFF
ON/OFF (status)
Temperature
Fan [1byte]
Fan [1bit]
Fan (status)
Swing
Swing (status)
Heat Mode
Heat Mode (status)
Cool Mode
Cool Mode (status)
Dry Mode
Dry Mode (status)
Fan Mode
Fan Mode (status)
Auto Mode
Auto Mode (status)
Modes [1byte]
Modes [1byte] (status)
FUNCTION
Turn ON/OFF the split
Split state (ON/OFF)
Value sent to the split
0%Au;1-33%Mi;34-66%Mid;>67%Max
0=Lower, 1=Higher
Actual Fan Level
1=Swing, 0=Stop/Step
Swing state: 0=Stopped,1=Swing
1=Set mode, 0=Nothing
1=Heat mode is Set, 0=Not Set
1=Set mode, 0=Nothing
1=Cool mode is Set, 0=Not Set
1=Set mode, 0=Nothing
1=Dry mode is Set, 0=Not Set
1=Set mode, 0=Nothing
1=Fan mode is Set, 0=Not Set
1=Set mode, 0=Nothing
1=Auto mode is Set, 0=Not Set
0=Aut;1=Ht;3=Cool;9=Fan;14=Dry
Actual Mode:0=Auto,1=Heat,etc.
http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
24
NUMBER
23
24
25
20
21
22
26
27
SIZE
1 Byte
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
1 Bit
I/O
I/O
I
I
I
I
I/O
I/O
I
I/O
FLAGS
C - - W U
C - R W U
C - R W U
C - R W U
C - - W U
C - - W U
C - - W U
C - - W U
C - R W U
DATA TYPE (DPT)
[18.1] DPT_SceneControl
Enable
Start/stop
Start/stop
Boolean
[1.19] DPT_Window_Door
[1.100] DPT_Heat_Cool
[1.100] DPT_Heat_Cool
Enable
RANGE
0 - 63
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
VALUES
1ST TIME
-
0
-
-
Param.
0
-
0
0
RESET
-
Last
Last
Last
Last
Last
Last
Last
Last
NAME
Scenes [1byte]
Disable Device
Fixed Auto-OFF [1bit]
Fixed Auto-ON [1bit]
Presence Detection
Window Sensor
Simplified Mode
Simplified Mode
Disable Temperature Limitation
IRSC Plus
FUNCTION
0-63(Run(1-64));128-191(Learn)
0=Normal Running, 1=Disabled
1=Sw.OFF after "param. value"
1=Sw. ON after "param. value"
0=Empty Room, 1=Presence
1=Window Open, 0=Closed
0=Cool, 1=Heat
0=Heat, 1=Cool
0=Disabled, 1=Enabled
http://www.zennio.com
Technical Support: http://zennioenglish.zendesk.com
25
Join and send us your inquiries about Zennio devices: http://zennioenglish.zendesk.com
Zennio
Avance y Tecnología S.L.
C/ Río Jarama, 132. Nave P-8.11
45007 Toledo (Spain).
Tel. +34 925 232 002.
Fax. +34 925 337 310.
www.zennio.com
info@zennio.com
advertisement
Key Features
- KNX-IR interface
- Control of main A/C functionalities
- Compatibility with most air conditioning manufacturers
- Scenes for climate control
- Timers for timed on/off switching
- Energy saving function: Window sensor
- Energy saving function: Presence detection