Marathon Monitors VersaPro Dew Point Dew Point Controller Installation and Operation Handbook
Below you will find brief information for VersaPro Dew Point. The VersaPro is a single loop process controller / monitor that can be configured to perform a number of specific control functions. It includes features such as two channel 24 bit Sigma-Delta ADC, two form A alarm contacts, an internal relay for carbon sensor burnoff, an internal relay for sensor impedance testing, a serial EEPROM stores setup and calibration values, two 4-20 mA outputs for control or chart recorder, a sixteen character LCD with two four digit LED segment displays, an RS 485 serial communication port, two form A user configurable alarm contacts, and two form A control contacts (controller only).
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
VersaPro Dew Point
Controller/Monitor
Installation and Operation Handbook
MARATHON MONITORS, INC.
COPYRIGHT © 2008
Marathon Monitors Inc. Dew Point
Part # F200062
Revision 1.00 March 15, 2002
Revision 2.00 October 31, 2002
Revision 2.01 February 20, 2003
Revision 2.02 August 15, 2003
Revision 2.03 August 27, 2003
Revision 2.04 December 8, 2004
Revision 2.05 February 25, 2005
Revision 2.06 March 29, 2005 for Firmware Revision 1.11
Revision 2.07 September 2, 2005 for Firmware Revision 1.13
Revision 2.08 February 6, 2006 for Firmware Revision 1.15 and higher
Revision 2.09 July 19, 2006 for Firmware Revision 1.20 (2.20) and higher
Revision 2.10 April 19, 2007 for Firmware Revision 1.22 (2.22) and higher
Revision 2.11 Oct 7, 2008 for logo, address
COPYRIGHT © 2008
MARATHON MONITORS INC.
All trademarks used in this publication are duly marked and the sole property of their respective owners. No attempt at trademark or copyright infringement is intended or implied.
Modbus is a registered trademark of MODICON, INC.
Marathon Monitors makes no warranties express or implied beyond the written warranty presented at initial purchase. Marathon Monitors Inc. is not responsible for any product, process, damage or injury incurred while using this equipment. Marathon Monitors makes no representations or warranties with respect to the contents hereof and specifically disclaims any warranties of merchantability or fitness for any particular application or purpose.
For assistance please contact:
Marathon Monitors Inc.
TEL: +1 513 772 1000 • FAX: +1 513 326 7090
Toll-Free North America +1-800-547-1055 [email protected]
www.group-upc.com
Marathon Monitors Inc. Dew Point
Table of Contents
SAFETY AND ENVIRONMENT INFORMATION ........................................................................ 1
S
ERVICE AND REPAIR
......................................................................................................................... 1
INSTALLATION SAFETY REQUIREMENTS............................................................................... 1
S
AFETY
S
YMBOL
................................................................................................................................ 1
P
ERSONNEL
........................................................................................................................................ 1
E
NCLOSURE OF LIVE PARTS
................................................................................................................ 1
L
IVE SENSORS
.................................................................................................................................... 2
W
IRING
.............................................................................................................................................. 2
P
OWER
I
SOLATION
............................................................................................................................. 2
E
ARTH LEAKAGE CURRENT
................................................................................................................ 2
O
VER
C
URRENT PROTECTION
............................................................................................................. 2
V
OLTAGE RATING
.............................................................................................................................. 2
C
ONDUCTIVE POLLUTION
................................................................................................................... 3
O
VER
-
TEMPERATURE PROTECTION
..................................................................................................... 3
G
ROUNDING OF THE TEMPERATURE SENSOR SHIELD
.......................................................................... 4
I
NSTALLATION REQUIREMENTS FOR
EMC.......................................................................................... 4
R
OUTING OF WIRES
............................................................................................................................ 4
VERSAPRO FEATURES.................................................................................................................... 5
INSTALLATION ................................................................................................................................. 6
M
OUNTING
......................................................................................................................................... 7
PROCESS CONTROL OPTIONS ..................................................................................................... 7
CONTROL MODES............................................................................................................................ 8
T
IME
P
ROPORTIONING
(TP)................................................................................................................ 8
T
IME
P
ROPORTIONING
D
UAL
(TD)..................................................................................................... 9
T
IME
P
ROPORTIONING WITH
C
OMPLEMENT
(TC)............................................................................... 9
P
OSITION
P
ROPORTIONING
(PP) ......................................................................................................... 9
ON/OFF (OF) ................................................................................................................................... 9
ON/OFF D
UAL
(OD) ....................................................................................................................... 10
ON/OFF
WITH
C
OMPLEMENT
(OC) ................................................................................................. 10
D
IRECT
C
URRENT
O
UTPUT
............................................................................................................... 10
D
IRECT OR
R
EVERSE
C
ONTROL
A
CTION
.......................................................................................... 11
ANALOG OUTPUT CHANNELS.................................................................................................... 12
ALARMS ............................................................................................................................................ 13
P
ROCESS
A
LARMS
............................................................................................................................ 14
OFF ............................................................................................................................................ 15
Full Scale HI............................................................................................................................... 15
Full Scale LO.............................................................................................................................. 15
Deviation Band ........................................................................................................................... 15
Deviation High ........................................................................................................................... 15
Deviation Low............................................................................................................................. 15
Output High ................................................................................................................................ 15
Output Low ................................................................................................................................. 15
Fault ........................................................................................................................................... 15
Probe .......................................................................................................................................... 16
Marathon Monitors Inc. Dew Point
Time ............................................................................................................................................ 16
Start ............................................................................................................................................ 16
Soak ............................................................................................................................................ 16
A
LARM
A
CTION
............................................................................................................................... 16
A
LARM
D
ELAY
T
IMES
...................................................................................................................... 16
D
IAGNOSTIC
A
LARMS
...................................................................................................................... 17
SERIAL INTERFACE ...................................................................................................................... 18
FRONT PANEL OPERATION ........................................................................................................ 19
E
NTER
K
EY
...................................................................................................................................... 20
R
EMOTE
K
EY
................................................................................................................................... 20
S
ETPT
K
EY
....................................................................................................................................... 21
S
ETUP
K
EY
....................................................................................................................................... 21
D
UAL
K
EY
F
UNCTIONS
.................................................................................................................... 32
Starting Probe Tests ................................................................................................................... 32
Start Timer.................................................................................................................................. 32
Edit Timer................................................................................................................................... 32
Monitor Mode............................................................................................................................. 32
DIGITAL INPUT EVENT ................................................................................................................ 33
OFF ............................................................................................................................................ 33
PROB.......................................................................................................................................... 33
AUTO (controller only)............................................................................................................... 33
rEn (controller only).................................................................................................................. 33
ACK ............................................................................................................................................ 33
TIMER FUNCTION.......................................................................................................................... 35
S
ETTING THE
T
IMER
......................................................................................................................... 35
T
IME
................................................................................................................................................. 36
G
UARANTEED
S
TART
T
IMER
............................................................................................................ 36
G
UARANTEED
S
OAK
T
IMER
............................................................................................................. 37
T
IMER
A
LARM
B
EHAVIOR
................................................................................................................ 38
T
IMER
S
TATE
D
IAGRAM
................................................................................................................... 38
TIMER SIO OPERATIONS ............................................................................................................. 40
C
ONTROLLING THE
T
IMER
R
EMOTELY
............................................................................................. 41
PROBE IMPEDANCE TEST ........................................................................................................... 43
W
HY
M
EASURE
S
ENSOR
I
MPEDANCE
? ............................................................................................. 44
PROBE BURNOFF............................................................................................................................ 45
PROCEDURE TO TEST THE SENSOR ........................................................................................ 47
C
ORRECTLY SET UP THE PARAMETERS IN THE
V
ERSA
P
RO FOR THE
P
ROBE
T
ESTING
........................ 47
T
O MANUALLY START A PROBE TEST PROCEDURE
............................................................................ 47
I
F A
P
ROBE
F
AULT OCCURS
.............................................................................................................. 47
TUNING.............................................................................................................................................. 49
W
HAT IS TUNING
? ............................................................................................................................ 49
SCALING ANALOG INPUTS ......................................................................................................... 52
L
INEAR
A E
XAMPLE
......................................................................................................................... 52
SCALING ANALOG OUTPUTS ..................................................................................................... 53
Marathon Monitors Inc. Dew Point
CALIBRATION ................................................................................................................................. 54
C
ALIBRATION
D
ISPLAYS AND
K
EYBOARD
O
PERATION
.................................................................... 54
P
REPARING FOR
I
NPUT
C
ALIBRATION
.............................................................................................. 55
Calibration of the Thermocouple Input ...................................................................................... 55
Calibration of the Cold Junction Temperature........................................................................... 55
Calibration of the Probe Millivolt Input..................................................................................... 57
P
REPARING FOR
A
NALOG
O
UTPUT
C
ALIBRATION
............................................................................ 57
COMMUNICATIONS....................................................................................................................... 59
M
ODBUS
.......................................................................................................................................... 59
RTU Framing.............................................................................................................................. 59
Address Field.............................................................................................................................. 59
Function Field ............................................................................................................................ 60
Data Field................................................................................................................................... 60
Error Check Field (CRC) ........................................................................................................... 60
MMI M
ESSAGE
P
ROTOCOL
.............................................................................................................. 61
I
NSTRUMENT
T
YPE
‘U’ C
OMMAND
S
ET
........................................................................................... 64
‘X’ Command.............................................................................................................................. 64
Block Commands ........................................................................................................................ 66
MMI Error Codes ....................................................................................................................... 69
PROCESS CALCULATION ............................................................................................................ 70
D
EW
P
OINT
P
ROCESS
C
ONTROL
....................................................................................................... 70
TROUBLESHOOTING QUESTIONS ............................................................................................ 71
A
NALOG
I
NPUTS
............................................................................................................................... 71
C
ONTROL
O
UTPUTS
.......................................................................................................................... 71
D
IGITAL
C
OMMUNICATIONS
............................................................................................................. 72
D
ISPLAY
F
UNCTIONS
........................................................................................................................ 72
P
ROBE
C
ARE
.................................................................................................................................... 72
T
IMER
F
UNCTION
............................................................................................................................. 73
VERSAPRO MONITOR MODE...................................................................................................... 74
P
REPARE FOR
C
ONNECTION
............................................................................................................. 74
H
OW TO
C
ONNECT
........................................................................................................................... 74
S
TART
M
ONITOR
M
ODE
................................................................................................................... 75
‘D’ D
ISPLAY
C
OMMAND
.................................................................................................................. 76
‘L’ W
RITE
FLASH
TO
RAM D
EFAULTS
.......................................................................................... 77
‘K’ W
RITE
RAM
TO
EEPROM........................................................................................................ 77
‘J’ D
ISPLAY
EEPROM V
ALUES
....................................................................................................... 77
‘S’ S
TATUS
D
ISPLAY
........................................................................................................................ 77
‘W’ W
RITE
RAM
WITH
EEPROM
OR
D
ATA
V
ALUES
...................................................................... 77
‘X’ E
XIT
C
OMMAND
........................................................................................................................ 78
V
IEWING
S
TATUS AND
M
EMORY
...................................................................................................... 78
L
OADING
D
EFAULT
V
ALUES
............................................................................................................ 78
W
HAT IF AN ERROR OCCURS
............................................................................................................. 79
TECHNICAL SPECIFICATION..................................................................................................... 81
E
NVIRONMENTAL RATINGS
.............................................................................................................. 81
E
QUIPMENT RATINGS
....................................................................................................................... 81
G
ENERAL
......................................................................................................................................... 81
E
LECTRICAL SAFETY
(
PENDING APPROVAL
) ..................................................................................... 82
E
LECTROMAGNETIC
C
OMPATIBILITY
(
PENDING APPROVAL
) ............................................................ 83
VERSAPRO MEMORY MAP.......................................................................................................... 84
Marathon Monitors Inc.
Safety and Environment Information
Dew Point
Please read this section carefully before installing the controller
This instrument is intended for industrial applications used in conjunction with Marathon
Monitors zirconia carbon sensors and standard thermocouple types. It is assumed that any installation meets either CE standards for industrial safety or NEC standard wiring practices.
Failure to observe these standards or the installation instructions in this manual may degrade the safety or electrical noise protection provided by this instrument. It is the installer’s responsibility to ensure the safety and electrical noise compatibility of any installation.
Service and repair
This controller has user replaceable fuses but no other user serviceable parts. Contact your
Marathon Monitors Service (800-547-1055) for repair.
Caution: Charged capacitors
Before removing an instrument from its case, disconnect the supply and wait at least two minutes to allow capacitors to discharge. Failure to observe this precaution will expose capacitors that may be charged with hazardous voltages. In any case, avoid touching the exposed electronics of an instrument when withdrawing it from the case.
Electrostatic Discharge (ESD) Precautions
When the controller is removed from its case, some of the exposed electronic components are vulnerable to damage by electrostatic discharge. Anyone who is not probably ground using an ESD wrist strap or in contact with a ground while handling the controller may damage exposed electronic components.
Installation Safety Requirements
Safety Symbol
Various symbols are used on the instrument, they have the following meaning:
!
Caution, (refer to the accompanying documents)
Functional earth
(ground) terminal
The functional earth connection is required for safety ground add to ground RFI filters.
Personnel
Installation must be carried out by qualified personnel.
Enclosure of live parts
To prevent hands or metal tools touching parts that may be electrically live, the controller should be installed in an enclosure. The contacts on the rear of the instrument case or finger save but it is still possible for loose wiring, or metal objects to come in contact with live terminal connections. It is recommended that power be removed from the instrument connections before they are disconnected. However, instrument’s power connector can be
1
Marathon Monitors Inc. Dew Point
removed with power applied. Care should be taken that the connector does not come in contact with any grounded object.
Live sensors
The dc inputs, dc logic, and dc outputs are all electrically isolated from chassis ground. If the temperature sensor is connected directly to an electrical heating element then the inputs will also be live. The controller is designed to operate under these conditions. However you must ensure that this will not damage other equipment connected to these inputs and that service personnel do not touch connections to these terminals while they are live. With a live sensor, all cables, connectors and switches for connecting the sensor and non-isolated inputs and outputs must be mains rated.
Wiring
It is important to connect the controller in accordance with the wiring data given in this handbook. Take particular care not to connect AC supplies to the low voltage sensor input or other low level inputs and outputs. Only use copper conductors for connections (except thermocouple inputs) and ensure that the wiring for installations comply with all local wiring regulations. For example, in the UK, use the latest version of the wiring regulations,
BS7671. In the USA use NEC Class 1 wiring methods.
Power Isolation
The installation must include a power isolating switch or circuit breaker. This device should be in close proximity to the control actuator, and within easy reach of the operator. There is no means of disconnecting power from the instrument other than removing the connectors from the rear of the instrument. It is recommended that additional power disconnects are provided in the installation to remove power from these connectors as well.
Earth leakage current
Due to RFI Filtering there is an earth leakage current of less than 0.5mA. This may affect the design of an installation of multiple controllers protected by Residual Current Device,
(RCD) or Ground Fault Detector, (GFD) type circuit breakers.
Over Current protection
The instrument has an internal 3.15 Amp fuse (P/N MFU-3.15PCTT) for instrument power and 1 Amp fuses (P/N MFU-1.0PCTT) for the control contacts and alarms. It is recommended that additional protection against excess currents be used for loads exceeding this rating. Fusing and interposing relays should be added to the control circuit if high current or large inductive loads are used.
Voltage rating
The maximum continuous voltage applied between any of the following terminals must not exceed 250VAC:
• line or neutral to any other connection;
• relay output to logic, dc or sensor connections;
2
Marathon Monitors Inc.
• any connection to ground.
Dew Point
The controller should not be wired to a three phase supply with an unearthed star connection.
Under fault conditions in this supply could rise above 264VAC with respect to ground and the product would not be safe.
Voltage transients across the power supply connections, and between the power supply and ground, must not exceed 2.5kV. Where occasional voltage transients over 2.5kV are expected or measured, the power installation to both the instrument supply and load circuits should include a transient limiting device.
These units will typically include gas discharge tubes, metal oxide varistors, and constant voltage transformers help suppress voltage transients on the supply line due to lightning strikes or inductive load switching. Devices are available in a range of energy ratings and should be selected to suit conditions at the installation.
Conductive pollution
Electrically conductive pollution must be excluded from the cabinet in which the controller is mounted. For example, carbon dust is a form of electrically conductive pollution. To secure a suitable atmosphere in conditions of conductive pollution, fit an air filter to the air intake of the cabinet. Where condensation is likely, for example at low temperatures, include a thermostatically controlled heater in the cabinet.
Over-temperature protection
When designing any control system it is essential to consider what will happen if any part of the system should fail. In temperature control applications the primary danger is that the heating will remain constantly on. Apart from scrapping the product, this could damage any process machinery being controlled, or even cause a fire.
Reasons why the heating might remain constantly on include:
• the temperature sensor becoming detached from the process;
• thermocouple wiring becoming a short circuit;
• the controller failing with its heating output constantly on;
• an external valve or contactor sticking in the heating condition;
• the controller setpoint set too high.
Where damage or injury is possible, we recommend fitting a separate over-temperature protection unit. Factory Mutual requires that any over temperature device use an independent temperature sensor, which will isolate the heating circuit.
Please note that the alarm relays within the controller will not give protection under all failure conditions. This instrument is not suited for over temperature protection and should not be used as a safety device.
3
Marathon Monitors Inc. Dew Point
Grounding of the temperature sensor shield
In some installations it is common practice to replace the temperature sensor while the controller is still powered up. Under these conditions, as additional protection against electric shock, we recommend that the shield of the temperature sensor be grounded at one end of the wire. Do not rely on grounding through the framework of the machine.
Installation requirements for EMC
To ensure compliance with European EMC directives certain installation precautions are necessary as follows:
• When using relay outputs it may be necessary to fit a filter suitable for suppressing the emissions. The filter requirements will depend on the type of load. For typical applications such as Schaffner FN321 or FN612 line filters or equivalents.
• If the unit is used in table top equipment which is plugged into a standard power socket, it is likely that compliance to the commercial and light industrial emissions standard is required. In this case, to meet the conducted emissions requirement, a suitable mains filter should be installed. Recommended filters would be Schaffner types FN321 and
FN612 or equivalents.
Routing of wires
To minimize the pick-up of electrical noise, the wiring for low voltage dc and particularly the sensor input should be routed away from high-current power cables. Where it is impractical to do this, use shielded cables with the shield grounded at one end.
4
Marathon Monitors Inc.
VersaPro Features
Dew Point
The VersaPro is a single loop process controller / monitor has the following capabilities:
Both Controller and Monitor
• Two channel 24 bit Sigma-Delta ADC for thermocouple, probe millivolt, with cold junction compensation.
• Two (2) Form A alarm contacts.
• Internal relay for carbon sensor burnoff.
• Internal relay for sensor impedance testing.
• Serial EEPROM stores setup and calibration values.
• Two (2) 4-20 milliamp outputs for control or chart recorder.
• Sixteen character LCD with two four digit LED segment displays.
• RS 485 serial communication port for either MMI protocol or Modus.
• Two (2) Form A user configurable alarm contacts.
Controller only
• Two (2) Form A control contacts.
• PID control mode.
5
Marathon Monitors Inc.
Installation
Dew Point
The VersaPro instrument is designed for up to 1/8" panel mounting in a DIN standard opening of 3.62" square (adapter panels available by special order). Required rear clearance is 7” to allow for wiring.
As with all solid state equipment, the controller should be located away from excessive heat, humidity, and vibration. Since the unit uses LED and LCD display devices, it should also be located so that direct sunlight will not interfere with the display's visibility. The instrument requires 120/240 VAC 50/60 Hz and should not be on the same circuit with other noise-producing equipment such as induction machines, large electrical motors, etc. Signal wiring must be run separate from control wiring. It is suggested that signal wiring at the rear terminals of the instrument be routed in one direction (up or down) while the AC power wires are routed in the opposite direction.
The following figure shows the rear terminals locations on the rear of the VersaPro.
Figure 1 VersaPro Rear Panel
The next figure shows a typical wire schematic for the Versapro Dew Point controller.
6
Marathon Monitors Inc. Dew Point
Figure 2 Typical Wiring Schematic
Mounting
To mount the instrument in a control panel, a hole must be cut 3.62" square in the necessary location on the panel. The following procedure should be followed to mount the VersaPro in the panel.
1) Insert the unit into previously cut out 3.62" square hole in panel.
2) While supporting unit, insert one clamping bracket into the groove on the bottom of unit, and then install the 6-32 set screw.
3)
4)
Repeat step 2 for the top of the unit.
With a HEX KEY wrench, alternately tighten the screw on either side of instrument to a torque of six in.-lbs. Insure rigidity of mounting. DO NOT OVER TIGHTEN.
This can wrap the instrument enclosure and make removal difficult.
To remove the instrument from the panel, reverse the above procedures.
Process Control Options
7
Marathon Monitors Inc. Dew Point
The Versapro can be configured to perform a number of specific control functions. The following table outlines the available process functions for the dew point controller / monitor.
Table 1 Instrument Control Options
Function
Dew Point
Linear Input A
Linear Input B
Description
Uses the millivolt and temperature signals from a zirconia sensor to calculate Dew
Point concentrations and control to an Dew
Point set point.
Uses the millivolt signal from a linear sensor connected to terminals +TC / -TC
Uses the millivolt signal from a linear sensor connected to terminals +MV / -MV
Control Modes
The VersaPro controller provides:
• Time Proportional Single (TP)
• Time Proportional Dual (TD)
• Time Proportional Compliment (TC)
• Position Proportioning (PP)
• On/Off (OF)
• On/Off Dual (OD)
• On/Off Compliment (OC)
• Direct Signal Output (4-20mA)
The instrument controls with two control contacts or direct 4-20mA output from two analog output channels. The control function can be set to direct acting or reverse acting.
Direct acting increases the output control signal to increase the process. Reverse acting decreases the output control signal to increase the process.
Time Proportioning (TP)
Time proportioning adjusts the duty cycle of the control device to maintain control. This is usually done with solenoid valves controlling the flow of a trim gas or addition to the process. The control loop percent output is the ON time percentage of the value relative to total cycle time. The cycle time is the ON time plus OFF time.
For example if the control loop percent output is 34% and the cycle time is 10 seconds, then the ON time would be 3.4 seconds and the OFF time would be 6.6 seconds. The selection of the proper cycle time is a trade off between excess wear and tear on the solenoid valve with short cycle times and rough (pulsing) flow of the control material with long cycle times.
Only the first control contact is used in this mode.
8
Marathon Monitors Inc. Dew Point
Time Proportioning Dual (TD)
This mode is used when there are two processes to control that have complementary effects; like gas and air. The time proportioning dual mode uses two control outputs; one for gas and one for air. There is never a time when both outputs are on simultaneously. The control loop computes a percent output from -100 to +100%. When positive, the proportioning action applies to the forward output (gas). When negative the proportioning action applies to the reverse (air) output.
Time Proportioning with Complement (TC)
This mode is identical to the time proportioning mode except that both control outputs are used. The second control output is the complement of the first. That is when the first output is ON then the second is OFF and vice versa. This mode is used with single action motorized valves that open quickly when a voltage is applied to one terminal and close quickly when voltage is applied to the other terminal.
Position Proportioning (PP)
This mode is used with motorized valves that do not have slidewire feedback. This mode is sometimes referred to as the "bump" mode because it "bumps" the valve slightly more open or closed. This mode uses both control outputs; one to drive the motor forward (open) and the other to drive it reverse (closed). The control output is the difference between the new percent output and the last percent output. If the difference is positive than the valve motor is driven open for that percentage of the cycle. If negative it is driven closed by that percentage of the cycle time.
For example if the new percent out is 60% and the old was 45% then the motor is driven open for 15% of the cycle time. If the cycle time is set to the time that the motor takes to move from fully closed to fully open, then the flow is theoretically increased by 15%. Two special cases exist. If the control output is computed at 100% then the motor is driven continuously in the open direction. Likewise if the control output is computed as 0% then the motor is driven continuously closed.
There is a built in deadband for this control based on the length of the cycle time. The comparison between the previous and current output values are made at the end of each cycle time. Faster comparisons can be made by shortening the cycle time assuming that a
100% command output is a continuously closed control contact.
ON/OFF (OF)
ON/OFF control is exactly what it implies, the control action is either ON or OFF. With true
ON/OFF control the control output is ON whenever the process is below the setpoint value and OFF when the process is at or above the process value. In many real world applications this simple control method will cause "contact chatter" because of noisy signals which will switch the ON and OFF states rapidly. Also since the control action does not turn OFF until the setpoint is reached, the process will overshoot due to lags in the control action.
Marathon controllers incorporate two features that prevent these problems from occurring; hysteresis and deadband. Hysteresis provides a delay between the control on point and the
9
Marathon Monitors Inc. Dew Point
off point. Noise will not cause the control output to “chatter” with this gap applied.
Hysteresis is ±20% of the deadband value.
Deadband allows the process to deviate away from the setpoint by the width of the deadband before any control action occurs. The deadband is adjusted through the Proportional Band in units of the displayed setpoint value. The reset and rate values have no effect in ON/OFF control.
Let’s assume the process setpoint is 50° dew point with a proportional band of 5. This represents a deadband of 5°, which is a band of ±5° dew point around setpoint. The hysteresis is 1° of the setpoint or 20% of the deadband. The output is turned on when the process drops below 45° and turns off then it reaches 49°.
ON/OFF Dual (OD)
This mode is similar to the time proportioning dual mode. The forward output acts as described in the ON/OFF description above. The reverse output responds when the process is above the setpoint.
Using the dew point example with a proportional band (deadband) of 5, the gas contact would turns on when the process is 45° and will turn off when it comes to 49°. Likewise the air contact would turn on when the process exceeds 55° and will turn off when it drops to
51°.
ON/OFF with Complement (OC)
This mode is exactly like ON/OFF control with the addition of a second control output. The second control contact is turned ON when the first is control contact is OFF and vice versa.
Direct Current Output
The Versapro has two analog output channels that provide an isolated 4 to 20mA signal proportional to selectable process values. The analog outputs can be configured to control the process by driving actuators with a 4-20mA signal proportional to the calculated percent output of the PID loop. One or both output channels can be used depending on the control mode selected. POUT selection drives the output signal based on the HIPO and LOPO settings. If a Dual Time Proportioning control mode is selected with a HIPO = 100 and a
LOPO = -100 then the output will be 4mA for –100%, 12mA for 0%, and 20mA for +100% output. This setting is helpful if one actuator is driving two valves in a split configuration where air is fully opened at –100% and gas is fully opened at +100% or both are closed at
0%.
It is possible to drive two actuators independently by setting on output to PO1 or PO2 where
PO1 is the 0 to +100% control output and PO2 is 0 to –100%. In this configuration both outputs are at the maximum (±100%) with an output of 20mA.
It is also possible to drive one actuator with an output channel and a solenoid with a control contact. For example, select PO1 for one analog output channel to drive a gas actuator and connect an air solenoid to the reverse control contact. The percent output for both functions
10
Marathon Monitors Inc. Dew Point
is determined by the PID settings. The cycle time should be set to the stroke time required to fully open the actuator from a fully closed condition. Typical stroke times would be 30 to 45 seconds.
Direct or Reverse Control Action
Control action determines how the output of the controller will react to effect a change on the process. The control action is considered ‘direct’ if an increase in the output produces an increase in the process value. A ‘reverse’ control action would be when an increase in the output produces a decrease in the process.
For example oxygen would require a reverse acting control if the process component the instrument is controlling is a trim gas. Increasing the trim gas will result in a decrease in the oxygen reading. It would be considered a direct acting control if the process component under control is additional air. Either process would use the first control contact, it would just be activated above or below the process set point depending on what is being added to the process.
11
Marathon Monitors Inc.
Analog Output Channels
Dew Point
The two analog output channels can also be set to retransmit selectable process values. The
Analog Output Offset and Range can be set to correspond to the process range. The default settings for these channels is –99.9° – 212.0° for channel 1 and 0 to 2000° temperature for channel 2.
The Versapro output channels can drive a chart recorder or PLC input. The remote input should be configured for of 0 - 5 VDC or 4 - 20 mA. If the input device only responds to a
DC voltage input, it will be necessary to add a 250 ohm dropping resistor across its input terminals and scale the analog output as 0 – 20mA.
The ideal location of the input device such as a recorder is adjacent to the instrument but it may be located remotely if the connecting wires are properly shielded. For best results, the chart recorder input(s) should be isolated from ground with the cable shield grounded on one end of the cable.
12
Marathon Monitors Inc.
Alarms
Dew Point
The instrument has two types of alarms, process alarms and diagnostic alarms. If an alarm has been selected and conditions are such that the alarm becomes active, the instrument will display this condition on the center LCD display. Alarms can be configured as latched or non-latched and as direct or reverse.
A reverse configuration would be considered a failsafe setting since the alarm contact is closed during normal conditions and opens if power is removed to the instrument or the configured alarm condition occurs.
The alarm message will be displayed on the LCD screen with it occurs. If the LCD screen is written with another message all active alarms can be seen be pressing the up or down arrow keys.
The display can not be cycled to other parameters such as temperature or probe millivolts if an alarm is active.
ALARM DISPLAY CONDITION
HIGH ALARM Alarm contact assigned to FSHI, dUbd, bdHI,
HIPO
LOW ALARM
PROBE CARE
FAULT
TIMER END
LLLL
HHHH
Alarm contact assigned to FSLO, dUbd, bdLO,
LOPO
Alarm contact assigned to PrOb
Alarm contact assigned to TinE, Strt, SOAK
Display only
Display only
ACTION
Full Scale High, above
Deviation Band, or above percent output setting. Contact automatically resets unless latched.
Full Scale Low or below
Deviation Band, or below percent output setting. Contact automatically resets unless latched.
Probe impedance high or probe recovery time exceeds limit. Contact resets monetarily unless latched.
Timer end alarm when the timer counts to zero for Timer, Start, or Soak timer modes. The contact latches until reset by pressing the
Enter key or through the
Input Event.
Displays process value is negative and exceeds display range or exponent setting
Displays process value is
13
Marathon Monitors Inc.
FLASH CSUM Alarm contact assigned
FALt
EEPROM CSUM Alarm contact assigned
FALt positive and exceeds display range or exponent setting
Reset instrument power.
Return to Marathon if error does not clear.
Reset instrument power.
Return to Marathon if error does not clear.
Dew Point
FLASH ERASE
FLASH / EE SIZE
ADC FAULT
TEMP OPEN
FALt
Alarm contact assigned
FALt
Alarm contact assigned
FALt
Alarm contact assigned
FALt
Alarm contact assigned
FALt
Do not push any keys while instrument is powered on. Return to
Marathon if error does not clear.
Programming error,
Reset instrument power, attempt reload.
Programming error,
Reset instrument power, attempt reload.
Reset instrument power.
Return to Marathon if error does not clear.
Check thermocouple for open condition or loose connection.
MV OPEN
CPU FAULT
Alarm contact assigned
FALt
Alarm contact assigned
FALt
Check probe millivolt signal for open condition or loose connection.
This signal can only be tested if the probe temperature is above
1300°F and exposed to process gas.
Reset instrument power.
Return to Marathon if error does not clear.
CPU IDLE ZERO Alarm contact assigned
FALt
Idle timer of CPU has counted to zero. This means that a CPU process has exceeded an allocated time slot.
Possible during extended block transfer requests.
Process Alarms
The process alarms can be setup to activate either or both of the two alarm contacts provide on the VersaPro. Nine user selectable modes are available.
14
Marathon Monitors Inc.
OFF
Disables the alarm function and the alarm contacts.
Dew Point
Full Scale HI
An alarm is generated any time the process value goes above the Full Scale HI alarm value. This alarm is reset if the process falls below the alarm value or acknowledgement from the front panel or through the event input (if configured).
Full Scale LO
An alarm is generated any time the process value drops below the Full Scale LO alarm value. The alarm will arm once the process is measured above the alarm value. This alarm is reset with an acknowledgement from the front panel or through the event input
(if configured).
Deviation Band
An alarm is generated any time the process value goes above or below the band alarm setting. The alarm setting is
± value of the band. For example, if a value of 10 is entered as the alarm value, an alarm is generated if the process goes 10 units above or
10 units below the set point. Units are the process units such percent or degrees. This alarm will not arm until the process is in-band of the set point.
Deviation High
An alarm is generated any time the process value goes above the band alarm setting.
The alarm setting is number of units allowed above set point. Units are the process units such percent or degrees. This alarm will not arm until the process is in-band of the set point.
Deviation Low
An alarm is generated any time the process value goes below the band alarm setting.
The alarm setting is number of units allowed below the set point. Units are the process units such percent carbon or degrees. This alarm will not arm until the process is inband of the set point.
Output High
An alarm is generated any time the control percent output exceeds the alarm value. The alarm setting is maximum percent output allowed.
Output Low
An alarm is generated any time the control percent output drops below the alarm value.
The alarm setting is minimum percent output allowed.
Fault
An alarm is generated any time an open input occurs on either the T/C or MV inputs.
Both inputs are pull up to a maximum value if no input is connected or if the input fails in an open circuit mode. An open T/C input fault is ignored for the Linear configuration. The center display will indicate which of these conditions has caused the alarm. The alarm process will also become active if any of the listed hardware faults occur. The center display will indicate which of these conditions has caused the alarm.
15
Marathon Monitors Inc. Dew Point
Probe
An alarm is generated any time the probe exceeds the maximum probe impedance setting, or the verification test tolerance. All of the probe values and limits are configured in the Probe Menu. The center display will indicate which of these conditions has caused the alarm.
Time
This alarm setting is necessary for the timer function to work. The timer will only run if it is enabled in the Ctrl Setup menu and a timer setpoint value other than zero has been assigned. This alarm setting allows the timer to start running when it is activated at the Start Timer parameter in the Setpt key menu, when the dual key combination Left
Arrow and Enter keys are pressed, or if the Input Event has been configured for Start and a contact closure occurs. The timer will start running as soon as it starts, independent of any process values. See the Timer section for more details.
Start
This alarm setting is necessary for the timer function to work. The timer will only run if it is enabled in the Ctrl Setup menu and a timer setpoint value other than zero has been assigned. This alarm setting allows the timer to be activated from the Start Timer parameter in the Setpt key menu, when the dual key combination Left Arrow and Enter keys are pressed, or if the Input Event has been configured for Start and a contact closure occurs. The timer will start running as soon as the process level is above the alarm value and will continue to run once it has started. See the Timer section for more details.
Soak
This alarm setting is necessary for the timer function to work. The timer will only run if it is enabled in the Ctrl Setup menu and a timer setpoint value other than zero has been assigned. This alarm setting allows the timer to be activated from the Start Timer parameter in the Setpt key menu, when the dual key combination Left Arrow and Enter keys are pressed, or if the Input Event has been configured for Start and a contact closure occurs. The timer will start running as soon as the process level is with in the band around set point determined by the alarm value. The timer will stop any time the process falls outside the band limit. See the Timer section for more details.
Alarm Action
Each alarm can be configured to operate in several different modes. Each alarm can be configured as a reverse (normally closed) contact. This mode is usually used for failsafe alarms that will open during an alarm condition, fault, or power failure. Each alarm can also be configured as a direct (normally open) contact that closes when an alarm condition occurs. In both cases the alarm will automatically clear if the alarm condition is resolved.
Each alarm can also be configured for either reverse or direct latched conditions. In this mode the alarm contact will remain active until an acknowledgement is received through the configured Event Input terminals or by pressing the ENTER key.
Alarm Delay Times
16
Marathon Monitors Inc. Dew Point
Each alarm can have delay ON, delay OFF, or both delays applied. Delays can be applied in increments of a second, up to a maximum of 250 seconds. ON delays are helpful if a known upset in the process can be ignored. This avoids nuisance alarms but still maintains an active alarm if the alarm condition persists following the delay. OFF delays will hold the alarm contact active for a determined period of time once the alarm condition has cleared. This can be helpful as an interlock to other process functions that may have to recover following an alarm condition.
Diagnostic Alarms
A diagnostic alarm is shown on the instrument’s center display when a fault is detected in the internal hardware during power up. These alarms included:
FLASH CSUM FAULT A fault has been detected in the Flash memory.
EEPROM CSUM FAULT A fault has been detected in the EEPROM.
KEYBOARD FAULT A key is stuck or was held down during power up.
FLSH ERASE FAULT This error may occur during instrument programming.
The Flash memory may be faulty. Retry programming, make sure the communications link to the instrument is working properly.
FLSH SIZE FAULT This error may occur during instrument programming. The
Flash memory may be faulty. Retry programming, make sure the communications link to the instrument is working properly.
ADC FAULT The analog / digital converter has failed to initialize or failed self calibration.
CPU IDLE ZERO A CPU process has exceeded the allotted process time.
Maybe due to extended serial communications block transfers. Limit the number of parameters requested in a block in this condition occurs.
CPU FAULT Occurs if the CPU has not initialized correctly. Try resetting power.
If either alarm contact is configured for a fault this alarm will engage if any of the above faults occur. The LCD display will indicate the fault condition.
The front panel display will show LLLL if the process value is below the display resolution, or HHHH if the process value is above the display resolution. It may be necessary to adjust the decimal point settings if these symbols occur.
17
Marathon Monitors Inc.
Serial Interface
Dew Point
The VersaPro has a single RS-485 half duplex (two wire) communications port. This port can be configured for either the Marathon protocol of Modbus RTU protocol. Baud rates and parities are selectable. The Modbus protocol only uses a parity of none. See the section on communications for details on both of these protocols.
The Versapro can be connected to networks with up to 128 similar devices. The differential transceiver used in the Versapro meets or exceeds the TIA/EIA-485 and ISO/IEC
8482:1993(E) standards.
Connections for the serial interface should be connected to the following terminals:
TB-B 13
TB-B 14
RTX +
RTX –
All connections to any RS-485 bus should be made with shielded twisted pair wires using a low capacitance cable specified for RS-485 multi-drop connections. The shield should be connected to ground on one end of the wire run. Shield continuity should be maintained between wire segments. Each end of the network should be terminated with a resistor that is close to the impedance of the cable. 100 to 120 ohms are typical values. All connections to multiple instruments should be made in a daisy-chain fashion, from one instrument to the next. A star network connection should never be used. A repeater should be considered for cable distances beyond 3900 feet (1.2Km). Any network that is run between buildings should use repeaters with optical fiber connections between buildings to avoid any noise spikes generated by lightening strikes.
18
Marathon Monitors Inc.
Front Panel Operation
Dew Point
The instrument has a display/keyboard assembly. This assembly has a 2 x 4 keyboard group, two groups of four LED seven segment displays (upper and lower), and a single line sixteen character LCD display.
45.0
1753
Figure 3 Versapro Display
The LEDS to either side of the LED segment arrays light when the corresponding function is active.
• COMM flashes when the instrument is properly interrogated over the RS485 port.
• PWR is hard wired to the instrument 5VDC supply
• AUTO is lit when the instrument is controlling to a set point (controller option)
• REM is lit when the instrument is controlling to a remote set point (controller option)
• REM and AUTO flash together if the instrument is in manual mode.
• REM will flash if timer is running.
The upper display indicates the process value or the Setup Menu Heading when the SETUP key has been pressed.
The center display indicates what the measured process calculation is and what the lower display indicates. In figure 3 the instrument is indicating dew point that is being measured.
This measurement range is –99.9° to 212.0°. The lower display can show a number of parameters depending on how many times the Enter key is pressed. The default low display is set point.
19
Marathon Monitors Inc. Dew Point
The center display also shows the parameter name in Setup mode or fault and alarm messages if any are active.
The lower display shows the instrument set point if the controller is in automatic or remote mode. The display will switch to control output level when the instrument is changed to manual. The lower display can also be configured to show the probe temperature
Enter Key
If the normal process display is showing on the LED and LCD displays, then pressing the
Enter key will cycle the LCD and lower LED through various controller parameters. The display will cycle through
DEWPT / SETPT
DEWPT / TEMP
DEWPT / %OUT
PROBE MILLIVOLT
BOFF MILLIVOLT
PROBE IMPEDANCE
PROBE IMP RECOVERY
NEXT PROBE TEST
REMAINING TIME
The dew point process value will always be displayed in the top LED display. The display can not be cycled if there is an active alarm. If the alarm is not displayed on the LCD screen then the UP or DOWN arrow keys can be pressed to display all of the active alarms.
Remote Key
Pressing the REM key causes the VersaPro to cycle between Remote, Automatic, or Manual control. This key has no function in the monitor version. When switching from Automatic to Manual or Manual to Automatic, the control output remains at the last output value in either mode. This allows for a bumpless control transition between either mode.
When the controller is set to Automatic mode the “Auto” LED lights and the lower display indicates the process setpoint (default).
When the controller is set to Remote mode the “Rem” LED lights and the VersaPro will accept a remote setpoint from a master on the host serial interface. The lower display indicates the process setpoint (default). The Setpt key does not work if the instrument is in remote mode.
When the controller is set to Manual mode both the “Rem” and “Auto” LED’s will flash together and the lower display indicates the power output of the controller. This value can be manually increased or decreased in 1% steps by pressing the UP or DOWN arrow keys.
Pressing the RIGHT or LEFT arrow keys changes the output in 10% steps. The output will remain in the last control level if the instrument is switched into manual mode from remote or automatic or back to either setpoint control mode.
20
Marathon Monitors Inc. Dew Point
Setpt Key
The Setpt key provides access to the instrument process set point. When the key is pressed the center display will show “SET POINT”. The set point value in the lower display can then be manually changed by moving the flashing digit cursor with the RIGHT or LEFT arrow keys and increasing or decreasing the selected digit with the UP or DOWN arrow keys. You can exit the set point function by pressing the Setpt key again. Any changes that are made to the set point are then displayed in the lower window if the instrument is set up of
Automatic control.
The following table outlines the options available under the Set Point key.
Table 2 Setpoint Ranges
Parameter Name
SET POINT
TIMER SETPOINT
START TIMER
Range
0 – 2.55% DEWPT
-999 – 9999
0 – 9999
YES / NO
Description
Units for DEWPT or linear input.
Units in minutes
Starts timer when YES is selected. This is the same as pressing the dual keys LEFT arrow and Enter to start the timer.
Setup Key
The instrument can be placed in setup mode by pressing and holding the SETUP key for 5 seconds. The upper display initially shows the first setup menu while the center and lower displays are blank. At this level you can select different menus by pressing the RIGHT or
LEFT arrow keys. The upper display will change accordingly.
You can enter a menu by pressing the ENTER key when the desired menu heading is being displayed. Pressing the arrow keys will change menu parameters. Value changes can be saved or the next parameter can be selected by pressing the ENTER key. The menu parameters will continue to cycle through the display as long as the ENTER key is pressed.
A new menu can be select only when the menu heading is displayed. You can exit from the
Setup mode by pressing the SETUP key at any time.
The following tables outline the Setup menus available in the VersaPro Controller and
Monitor when the operator presses the SETUP key.
Table 3 Setup Menus
Setup Menu Heading
CtrL
Inpt
CaLc
Prob
Description
Control functions and PID
Thermocouple type and Millivolt setup
DEWPT process values
Probe tests and verification parameters
21
Marathon Monitors Inc.
Aout
ALr
Host
Info
CaL
Analog output selection and parameters
Alarm contact configurations
Communication protocols and parameters
General information displays
Input / Output calibration
Dew Point
You have to press the SETUP key for five seconds to activate the setup mode. Initially when the setup mode is activated, the upper LED display will show the first menu heading, the LCD and lower LED displays are blank. Page to the next Menu heading by pressing the
RIGHT or LEFT arrow keys. The menu headings will continue to wrap around as the
RIGHT or LEFT arrow keys are pressed. Pressing the SETUP key at any point while in the
Setup Menus will return the display to the normal process display.
Ct r L dPT
The displayed menu is selected by pressing the ENTER key. The first parameter name in the selected menu list will appear in the center display. The upper LED group continues to display the menu name, and the lower LED group shows the parameter value. A flashing cursor in the lower LED display indicates which digit can change if the parameter value is numeric. The UP or
DOWN arrows increase or decrease the digit value. The RIGHT or LEFT arrow keys move the cursor to the right or left digit. Numeric wrap-around is provided as well as wrap-around for the menu parameters. No wrap-around is provided for the cursor position when changing a parameter value.
If the parameter has a table of choices such as thermocouple types, the various selections can be displayed by pressing the UP or DOWN arrows. No digit flashes in parameters that have a list selection. In either case, the selection is set when the ENTER key is pressed and the display advances to the next parameter.
In the example shown above, the selected menu is Control (CtrL), the selected parameter is
Process Source, and the selected source is DEWPT. Different source selections can be made by pressing the UP or DOWN arrow keys.
Pressing the SETUP key at any time escapes from the menu display and returns to the normal process display. You can only select another menu heading when the display is at a menu heading.
The following figures and tables outline the menu options and parameters under the Setup key.
22
Marathon Monitors Inc.
Figure 4 Setup Menu Tree
Dew Point
23
Marathon Monitors Inc.
Table 4 Control Menu (
CtrL)
Dew Point
Parameter Name
PROCESS SOURCE
TC OR MV BREAK
Units or Options Range
DEWPT, E A,
E B
Display range:
00.00 to 02.55 for DEWPT
-999 to 9999 for
Input A or Input B
ZERO,
HOLD
Description
Control type only available on instrument’s specific configuration. This selection controls what other parameters will be available. E A is input
A (0-50mV), E B is input B (0-
2000mV)
ZERO sets the control output to
0 if a thermocouple break and/or an open mV input are detected. HOLD holds the output and the last process value prior to an opened input.
HOLD will take effect temporarily if the mV signal changes by more then 50mV between samples. This prevents changes if the mV signal is failing.
The following parameters in this table are only available in the controller
CONTROL MODE
CONTROL ACTION
PROPORTIONAL
BAND
RESET
RATE
CYCLE TIME
TP, TC, TD, PP,
OF, OC, OD or
NON
DIR/REV
Process Value repeats/min
Minutes
SECONDS
HI PERCENT OUT MAXIMUM
OUTPUT
LOW PERCENT OUT MINIMUM
OUTPUT
TIMER ENABLE YES / NO
0 – 9999
00.00 – 99.99
00.00 – 9.99
0 – 250
0 – 100
-100 to 100
See Control Modes if configured as a controller, shows NON (MONITOR) only if the instrument is configured as a monitor.
Direct or Reverse control action
Proportional Band value in displayed process units for PID control or Deadband in
ON/OFF control
Integral control value, no effect in ON/OFF settings
Derivative control value, no effect in ON/OFF settings
Proportional time period (TP,
TC, TD)
Motor cycle time (PP)
Minimum ON time
(OF,OC,OD)
Sets max. forward control.
Output
Sets min. reverse control output
Enables timer function
24
Marathon Monitors Inc.
Table 5 Input Menu (
InPt)
Parameter Name
TC TYPE
Units or Options Range
B, E, J, K, N, R, S,
T
COLD JUNC APPLY YES or NO
IN A OFFSET
IN A SLOPE
TEMP SCALE
TC FILTER
IN B OFFSET
IN B SLOPE
MV FILTER
Only in Linear mode
Only in Linear mode
F OR C
-999 – 9999
-999 – 999
-99.9 – 99.9
-9.99 – 9.99
-.999 - .999
0 – 450
Works only in mV
Mode
-999 – 9999
Works only in mV
Mode
-999 – 999
-99.9 – 99.9
-9.99 – 9.99
-.999 - .999
0 – 450
Dew Point
Description
See Input calibration for thermocouple ranges.
Linear mode allows for input scaling, see IN A OFFSET and IN A SLOPE.
Applies the cold junction correction or not when a thermocouple type is selected.
In LINEAR mode the cold junction is never applied.
Default is NO.
Linear offset to scale Input A to Engineering Units when
INPUT A is selected as the process source.
Linear slope to scale Input A to Engineering Units when
INPUT A is selected as the process source.
This is the slope number in the linear calculation where:
EU = SLOPE(mV) +
OFFSET
See key
Sets temperature scale.
Temperature filter setting in seconds. Filters the temperature value with a moving average time window.
Linear offset to scale Input B to Engineering Units when
INPUT B is selected at the process source. This is the offset in used in the
SLOPE(mV) + OFFSET equation.
Linear slope to scale Input B to Engineering Units when
INPUT B is selected as the process source.
This is the slope number in the linear calculation where:
EU = SLOPE(mV) +
OFFSET
Millivolt filter setting in seconds. Filters the millivolt
25
Marathon Monitors Inc.
Parameter Name Units or Options Range
Dew Point
DIG EVENT OFF, PrOb,
AUtO, rEn, ACK,
PrOC, Strt, HOLd,
End
Description reading with a moving average time window.
See Digital Event section for an explanation of selections.
See the Timer section for the
Strt, HOLd, and End selections.
Table 6 Calculation Menu (
CALC)
Parameter Name Units or Options Range
DISPLAY DECML PT Decimal point 0-4
DEWPT PROCESS
FACTOR
0 – 1999
Description
Sets decimal pt., for Input A and Input B. DEWPT defaults to 2.
Used to correct displayed
DEWPT value when compared to shim stock readings.
Table 7 Probe Setup Menu (
PrOb)
Parameter Name
PROBE TEST
START TEST
TEST INTERVAL
PROBE IMP LIMIT
IMP RECVRY
TIME
BURNOFF DELAY
Units or Options Range
NONE
RES
BOFF
BOTH
HRS.TENTHS
KOHMS
SECONDS
SECONDS
YES/NO
0 – 99.9
10 – 100
0 – 250
0 – 999
Description
No test (NONE),
Impedance (RES), Burnoff
(BOFF), or BOTH impedance and burnoff can be selected.
If probe test interval is 0, then test only runs once. If probe test interval is set then test run continuously from start point and at each interval time. Test stops when changed back to NO. Probe temp must be >= the minimum probe temperature setting.
Sets time interval between automatic probe tests, 0 disables automatic testing.
Sets maximum impedance for
Probe alarm
Sets maximum Probe recovery time, timer cut short if probe recovers faster. The
Probe alarm is set if the probe signal does not recover while this timer is active.
The period of time when air is allowed to flow to the tip of
26
Marathon Monitors Inc.
Parameter Name Units or Options Range
Dew Point
BURNOFF
RECOVERY
MIN PROBE TEMP
SECONDS
F OR C
0 – 999
1100° – 2000° F
590° – 1090° C
Description the sensor.
Recovery time for probe following the burnoff test.
The PROBE alarm is set if the probe signal does not recover before this timer expires.
Minimum temperature for probe impedance and verification tests.
Table 8 Analog Output Menu ( AOUt)
Parameter Name
ANALOG 1 UNIT
Units or Options Range
DEWPT, LInA,
TENP, POUT,
PO1, PO2,
PROG, LInB
Description
4 to 20mA output. DEWPT – retransmits
DEWPT if DEWPT is selected as process source.
LInA – scaled millivolt value of input A depends on which input selected as process source.
TENP – probe temperature when DEWPT is selected as process source and a thermocouple type is selected.
POUT – Power output is available for the controller, allows for –100% to 100% for split actuators. PO1 or
PO2 allow for just 0 – 100% output for either control contact.
PROG - allows the output to be controlled from the
DACV1 memory location.
LInB – scaled millivolt value of input A depends on which input selected as process source.
ANALOG 1 OFFSET Offset for selected process value or percent output.
-30.0 to 300.0 for
DEWPT, LInA or
LInB
-300 to 3000 for temperature
LOPO for POUT
This is the minimum value of the process associated with the 4mA output. The magnitude of this number is based on the display resolution.
In POUT mode the offset is fixed to the LOPO value.
When PROG is selected the
27
Marathon Monitors Inc.
Parameter Name Units or Options Range
ANALOG 1 RANGE Span scaling for selected process value or percent output.
0 or
DAC_OFFSET for PROG
0 to 9999 for
DEWPT, LInA,
LInB, and Temp
HIPO for POUT
4096 or
DAC_SPAN for
PROG
ANALOG 2 UNIT CARB, LInA,
TENP, POUT,
PO1, PO2, PROG,
LInB
ANALOG 2 OFFSET Offset for selected process value or percent output.
ANALOG 2 RANGE Span scaling for selected process value or percent output.
Table 9 Alarm Menu (
ALr)
Parameter Name
ALARM 1 TYPE
Units or Options
OFF
FSHI,
FSLO dUbd dbHI dbLO
HIPO
LOPO
FALt
PROB tinE
Strt
SOAk
Range
Dew Point
Description offset is fixed at 0
This is the maximum value of the process associated with the 20mA output. The magnitude of this number is based on the display resolution.When POUT is selected this value is fixed to the HIPO value.
When PROG is selected the range is fixed at 4096
Same as Analog 1
Same as Analog 1
Same as Analog 1
Description
OFF disables alarm contact.
FSHI - Full Scale HI, active when process is above
ALARM 1 VALUE.
FSLO - Full Scale LO, active when process is below
ALARM 1 VALUE.
dUbd – Deviation Band available for the controller only, active when process is outside of symmetrical band around setpoint.
dbHI – Deviation High, defines a process band above the process setpoint. The alarm is active if the process moves outside this band.
dbLO – Deviation Low, defines a process band below the process setpoint. The alarm is active if the process
28
Marathon Monitors Inc.
Parameter Name Units or Options Range
ALARM 1 VALUE
ALARM 1 ACTION REV, LREV, DIR,
LDIR
ALRM 1 TM ON DLY 0 – 250 SECONDS
ALRM 1 TMOFF DLY 0 – 250 SECONDS
ALARM 2 TYPE Same as ALARM 1
TYPE
ALARM 2 VALUE
ALARM 2 ACTION
ALRM 2 TM ON DLY 0 – 250 SECONDS
OFF
ALRM 2 TMOFF DLY 0 – 250 SECONDS
29
Dew Point
Description moves outside this band.
HIPO – Output High, this alarm sets the threshold for the maximum control output allowed which is set by
ALARM 1 VALUE.
LOPO – Output Low, this alarm sets the threshold for the minimum control output allowed which is set by
ALARM 1 VALUE.
FALt – Fault, open inputs for mV, thermocouple or hardware fault.
Prob – Probe, fault active if impedance or verification are out of range.
tinE – Time, establishes alarm contact as the contact used for the End alarm.
Strt – Start, same as Time.
SOAk – Soak, same as Time.
Trigger set point value
REV = Reverse (N.C.) can be acknowledged even if the condition still exists.
LREV = Latched Reverse
(N.C.) can not be acknowledged if the condition still exists.
DIR = Direct (N.O.) can be acknowledged even if the condition still exists.
LDIR = Latched Direct
(N.C.) can not be acknowledged if the condition still exists.
Delay ON time for ALARM1
Delay OFF time for
ALARM1
Same as ALARM 1 TYPE
Trigger set point value
Same as ALARM 1 ACTION
Delay ON time for ALARM2
Delay OFF time for
ALARM2
Marathon Monitors Inc.
Table 10 Communication Menu (
HOST)
Parameter Name
PROTOCOL
ADDRESS
BAUD RATE
PARITY
Units or Options Range
PROP OR BUSS
1 TO 15 (MMI)
NA,600,1200,
2400,4800,9600,
19.2K,38.4K
None/Even/Odd
Dew Point
Description
PROP is Marathon Monitors ,
Inc. slave protocol, BUSS is
RTU Modbus protocol.
DELAY NONE, 10, 20, 30
Modbus uses None parity only.
NONE = 0 Delay, other selections are millisecond delay in response.
Table 11 Info Menu (
InFO)
Parameter Name
MILLIVOLT TEMP
IN
Units or Options Range
MILLIVOLTS
MILLIVOLT PROB IN MILLIVOLTS
-10-100
0-2000
COLD JUNCTION
BURNOFF MV
BURNOFF TEMP
DEG (F OR C)
PERCENT OUTPUT % Output
PROB IMPEDANCE Kohms
IMP RECVRY TIME SECONDS
MILLVOLTS
°F OR °C
0 – 60°C
LOPO to HIPO
0 – 100
0 – 250
0 – 2000
0 – 2000
Description
Displays direct mV of
Temperature input
Displays direct mV reading of probe input
Displays actual cold junction temperature
Displays actual % output
Displays last probe impedance value.
Displays last impedance recovery time.
Millivolts read at the end of the probe burnoff cycle
Displays probe temperature read at the end of the probe burnoff cycle
BURNOFF RECVRY
TIME
NEXT TEST
FIRMWARE REV
SECONDS
Hours.tenths
Version number
0 – 250 Time taken for probe to return to 98% of pre-test millivolt reading.
Time to next probe test, shows 00.0 if test automatic test is disabled.
Parameter Name
CAL INPUT
Table 12 Calibration Menu
Units or Options Range
NO / YES
Description
Default to NO, must be
30
Marathon Monitors Inc. Dew Point
changed to YES to enter input calibration routine.
TC mV ZERO
(CAL IN)
TC mV SPAN
(CAL IN)
PROBE mV ZERO
(CAL IN)
PROBE mV SPAN
(CAL IN)
CJ OFFSET
(CAL IN) thermocouple zero thermocouple span millivolt zero
CAL OUTPUT
OUTPUT 1 MIN
(CAL OUTPUT)
OUTPUT 1 SPAN
(CAL OUTPUT)
NO / YES
0 – 60° C
0 – 140° F millivolt span
Sets the cold junction offset depending on the temperature range selected
Default to NO, must be changed to YES to enter output calibration routine.
Sets signal level for the minimum mA output.
Sets signal level for the maximum mA output.
OUTPUT 2 MIN
(CAL OUTPUT)
OUTPUT 2 SPAN
(CAL OUTPUT
Sets signal level for the minimum mA output.
Sets signal level for the maximum mA output.
Pressing the Setup key once at any point in the Setup menu will return the instrument to the normal process display.
31
Marathon Monitors Inc. Dew Point
Dual Key Functions
The VersaPro was four dual key functions as defined below:
RIGHT arrow / Enter
LEFT arrow / Enter
DOWN arrow / Enter
Rem / Enter
Start probe test sequence
Start Timer
Edit Remaining Timer
Monitor Mode
Starting Probe Tests
Pressing the RIGHT arrow / Enter keys simultaneously will start the probe tests if a probe test function has been selected in the Probe Setup Menu, parameter Probe Test, and the probe temperature is above the minimum probe temperature parameter in the same menu.
If there is a value other than 0 entered in the Probe Test Interval parameter the probe test will be preformed after the selected interval time has elapsed from the time the test was manually started. If the interval time is set to 0 then no additional tests will be preformed until the next manual start. Starting the test through this dual key function is the same as if the Start
Test parameter in the Probe menu had been changed from NO to YES.
Start Timer
Pressing the LEFT arrow / Enter keys simultaneously will start the timer if the timer has been enabled in the Control Setup menu, the timer set point is greater then zero, and an alarm contact has been assigned a timer function. Press both keys while the timer is running will stop the timer.
Edit Timer
Pressing the DOWN arrow / Enter keys simultaneously while the timer is running will allow the remaining time to be changed. The remaining time can be increased or decreased. The change in time takes effect when the Enter key is pressed and the display returns to the normal remaining time display.
Monitor Mode
Monitor Mode is used by factory personnel only. Return to operate mode by cycling power or sending the appropriate command word to the instrument.
32
Marathon Monitors Inc.
Digital Input Event
Dew Point
The VersaPro has a single digital input. This input is activated by making an isolated contact closure between terminals TB-B 11 and 12. This input is debounced for a momentary closure of at least 0.6 seconds.
NOTE
Do not connect either terminals TB-B 11 or 12 to any AC or DC potentials. These terminals are internally connected to an isolated 5VDC source. Use only an isolated contact closure across these terminals.
The input event can be set to any one of the following functions: OFF, PrOb (start probe test), AUTO (set to auto), rEn (set to remote), ACK (alarm acknowledge), PrOC (process hold), Strt (timer start), HOLd (timer hold), End (timer end acknowledge). These settings can be selected in the Input Setup menu at the DIG EVENT parameter. The selections can be made by pressing the up or down arrow keys and then pressing the Enter key.
OFF
This selection disables the input event function. This is the default condition of this feature unless another function is selected.
PROB
This selection will start the impedance (10Kohm) test and/or probe burnoff. The various probe tests will run only if they are selected in the Probe Menu. The PrOB input event will have no effect if no probe tests are selected.
If a probe test interval time is set to any value other than zero, activating this function will reset the interval count down timer. If the probe test interval time is set to zero this function will operate only when the contact closure is made across the event input terminals. The contact closure must open and close each time to initiate another probe test.
AUTO (controller only)
This selection will force the instrument from manual mode or remote mode into local automatic mode. No change will occur if the instrument is already in automatic mode.
rEn (controller only)
This selection will force the instrument from local setpoint mode or manual mode into remote setpoint mode. No change will occur if the instrument is already in remote setpoint mode.
ACK
This selection will acknowledge any latched active alarm except the timer end alarm.
This function will have no effect if the alarm condition persists when the acknowledge signal is issued. This function resets a latched alarm similar to pressing the Enter key.
PrOC
(controller only)
This selection will place the process calculation in hold. The control output is also held at the output level when the process hold event was set. This includes
33
Marathon Monitors Inc. Dew Point
all analog output signals as well as control contacts. This is similar to the state the instrument is set to when the probe tests are running.
Strt
(controller only)
This selection will start the timer function if the timer is enabled, the set point is greater than 0, and one alarm contact is assigned to a timer function.
HOLd
(controller only)
This selection will place the timer in a hold state for as long as the event input is active.
End
(controller only)
This selection will acknowledge the end condition of the timer, clear the end state, and reset the timer for another start.
34
Marathon Monitors Inc.
Timer Function
Dew Point
The Versapro timer function is available on all process controller options. The timer can operate independently or it can be dependent on the process based on how either alarm contact is configured. The instrument has three possible functions; timer, guaranteed start timer, and guaranteed soak timer. These functions are set through the mode selection of alarm 1 or alarm 2 in the Setup menu. Only one alarm should be set to a timer function at any time.
The timer will only work if three conditions are met; the timer function must be enabled in the
Setup Control Menu, an alarm contact must be configured for a timer function, and the timer set point must be greater then zero.
The timer set point is set in the Setpt Key menu. The remaining time is displayed in the display cycle list and can be edited when the timer is running. The timer set point is entered in whole minutes. The remaining time will show the tenths of a minute if the timer is less than 1000 and shown as whole minutes. The timer start setting follows the remaining time display in the Setpt
Menu.
Setting the Timer
The first step for using the timer is to enable the timer function in Setup Control Menu. This allows the timer to be started in various ways and also allocates a serial port channel for the timer.
The next step is to move to the Alarm menu and select a timer function for one of the alarms.
The alarm that is selected will close its alarm contact with the timer counts to zero. Only one alarm should be selected for a timer function and any time.
NOTE
Do not set both alarms to timer functions at the same time.
The final step is to press the Setpt key and the Enter key until the TIMER SETPT parameter appears. Enter the desired value of the timer. This value is the only set point for the timer.
This value will be used as the timer set point if the instrument is in the local automatic or remote control mode. There is no separate remote timer set point value. The local timer set point value will be over written by the value received from a remote device like a computer or master instrument.
The final step is to start the timer. This can be done in the Setpt menu by pressing the Enter key until the TIMER START parameter appears and selecting ‘YES’. The timer can also be started by pressing a dual key sequence LEFT arrow and Enter, through the serial interface, or through the digital event input.
Timer Dual Key Functions
⇐ + Enter
In Auto or Remote mode this two key combination will activate or deactivate the timer function.
+ Enter
This two key combination allows the timer function remaining time to be edited.
35
Marathon Monitors Inc. Dew Point
The behavior of the timer is controlled through the selection of the alarm modes. If no timer alarm is selected for either alarm 1 or alarm 2 then the timer will not start. The Time, Start, or Soak alarm modes must be selected for one alarm contact before the timer will start.
The Rem LED on the front panel will flash while the timer is active in the RUN, HOLD, or
END modes. The timer will go inactive when END is acknowledged or if the timer is disabled.
The timer can be stopped by pressing the Enter and Right arrow keys during an active RUN state, sending a remote timer set point of 0 when the instrument is in remote mode, or by changing the remaining time to zero.
The Event Input can be configured to start the timer, hold the timer, or acknowledge the End state.
Time
The Time alarm mode it will run continuously once it has started and the alarm contract will close when the remaining time reaches zero. The alarm value has no effect in the simple timer mode and the timer will not stop or hold if the process value changes. The alarm message is ‘End’ will display on the LCD screen and the appropriate alarm contact will activate.
Guaranteed Start Timer
The guaranteed start timer function works in conjunction with the alarm value. The timer will hold until the process value is greater then the lower band value of the process. The alarm value is the band value. In the figure below the alarm value is 10, which represents a band around set point of
∀10°. The timer will not HOLD once it has met the initial starting conditions. The process can fluctuate outside of the alarm band after the timer has started without placing the timer in a HOLD state. The following figure shows the behavior of the guaranteed start timer.
36
Marathon Monitors Inc. Dew Point
Figure 5 Guaranteed Start
Guaranteed Soak Timer
The guaranteed soak timer works in conjunction with the alarm process value. The alarm value is the valid band around the process set point. The process must be within the band around the process set point to start the timer once it has been activated. If the process passes above or below the alarm band setting, the timer will go to a HOLD state. The timer will be allowed to continue only when the process is within the band setting. In the following figure the alarm value is set to 10 degrees for a temperature process.
37
Marathon Monitors Inc. Dew Point
Figure 6 Guaranteed Soak
Timer Alarm Behavior
The alarm contacts do not work like normal process alarms when the timer, soak, or start timer functions are selected. If the alarm is configured for the timer, the contact will only activate when the remaining time counts down to zero and the timer reaches the END state.
Once this occurs the END Alarm message will appear on the LCD display. The alarm will stay latched until it is acknowledged by pressing the Enter key or closing a contact across the
Digital Event terminals if the End setting is selected as the Digital Event function. The Rem light flashes during the END state and stops flashing when the timer is acknowledged and returns to the IDLE state.
Timer State Diagram
The following diagram shows the conditions that control the state of the timer function.
38
Marathon Monitors Inc.
Timer Enable = NO OR
Timer Start = NO OR
Enter key OR
Remote Time Setpt = -1 OR
Event(END) = ON
IDLE
Timer Enable = YES
Timer Start = NO
Remaining Time = 0
END
Time Enable = YES
Timer Start = YES
Display = END Alarm
End Alarm = ON
Alarm contact = ON
Rem Light = Flash
Timer Enable = NO OR
Timer Start = NO OR
Remote Time Setpt = -1 OR
Enter/Left arrow
Remain Time counts to 0
Dew Point
Event(STRT) = ON OR
Remote Timer SP = -2 OR
Enter / Left arrow OR
Timer Start = YES AND
Timer SP > 0
RUN
Timer Start = YES
Remain Timer = countdown
Time Alarm = OFF
Alarm Contact = OFF
Rem Light = Flash
Event(HOLD) = OFF OR
Time Alarm = OFF
Event(HOLD) = ON OR
Time Alarm = ON
Timer Enable = NO OR
Timer Start = NO OR
Remote Time Setpt = -1 OR
Enter / Left arrow
HOLD
Timer Start = YES
Remain Time = hold
Time Alarm = ON
LCD Display = Hi/Lo Alarm
Alarm Contact = OFF
Rem Light = Flash
Figure 7 Versapro Timer State Diagram
The timer has four states. The IDLE state is the inactive condition. The RUN state is the active state when the timer is counting down. The HOLD state is when counting is paused due to either Digital Event = HOLD or a configured alarm is active. The END state is when the timer has timed-out but has not been acknowledged. The configured alarm contact will activate when the END state is entered.
The following is a summary of ways to change the state of the Timer. These assume the standard setups are in effect. It is assumed that the Timer is enabled for it to start or run.
Timer will start if:
1.
Timer Enable = YES and
2.
3.
4.
5.
6.
7.
Alarm is set to timer function and
Timer Setpoint > 0 and
Digital STRT event = ON or
Enter/Left keys = CLOSE or
Timer Start = YES or
Remote Setpoint = -002
39
Marathon Monitors Inc.
Timer will hold if:
1.
2.
Digital HOLD event = ON or
Alarm Soak or Run deviation is active
Timer will run if:
1. Timer Enable = YES and
2. Timer Start = YES and
3. Timer Setpoint > 0 and
4. Digital HOLD event = OFF and
5. Remaining Time > 0
Timer will reset to IDLE without activating END if:
1.
Enable = NO or
2.
3.
Timer Start = NO or
Remote Timer setpoint = -001 or
4.
Enter/Left keys pressed
Dew Point
Timer goes to END state if:
1.
Timer count down reaches 0
Timer returns to IDLE state from END when:
1.
Enable = NO or
2.
3.
Timer Start = NO or
Operator presses Enter key or
4.
Remote Timer setpoint = -001 or
Digital END input = ON
5.
Timer SIO Operations
The Versapro allocates a second host address if the timer function is enabled and the host port protocol is set to PRoP (Marathon) using the Marathon slave protocol. If the host port protocol is set to buss (Modbus) or the Marathon block protocol is used, then the timer information is accessed directly. For the Marathon slave protocol, the first address is the primary address set by the Address parameter setting in the Setup HOST menu. The second address is assigned as Address +1 and will respond to 10Pro type commands. The setpoint commands affect the timer set point. The initial state conditions must be met for the timer to run.
The remaining timer value will be transmitted as the process value when responding in
10Pro slave mode. The timer values and process values are available at the host address if the instrument is responding to the Marathon block command or Modbus. The Address + 1 address is always active while the timer is enabled and the serial port protocol selection is
MMI and inactive when Modbus is selected. It is important to consider this extra address allocation if multiple slaves with timers are going to be connected to a master. Only eight addresses are possible when the 10Pro command mode is used. See the section on serial communication for details on these differences. If only the Marathon block command is going to be used then the instrument will not respond on the second address.
40
Marathon Monitors Inc. Dew Point
In the MMI 10Pro protocol, the value returned for the percent output command is the timer control byte. The bits in the control byte are defined in the following table.
Timer Control Byte
0
1
2
Bit Description
Timer Enabled
Timer Running
End
Purpose
Indicates that the timer is enabled in the setup menu.
Indicates that the timer has started.
Indicates that the timer has timed out and not acknowledged.
3 Hold
4 & 6 N/A
Indicates that the timer is in hold mode.
Not used.
7 Control Set when the timer is started. Reset when timer has stopped. Is toggled by the Enter + Left Arrow or set by the SIO sending a time setpoint.
Controlling the Timer Remotely
All timer setpoint values must be written to the host address + 1 and the timer function must be enabled in the instrument control menu for the instrument to recognize any host address +
1 command.
Control of the timer via the serial port using the 10Pro commands has limited capabilities since the only value that can be written is the time set point. There are special cases if the
Versapro is connected to Dualpro/Multipro as a slave. The master instrument must first send a valid setpoint value from 1 to 9999. The master can then send a setpoint of –002 to start the timer assuming all other configuration requirements are met. If the master sends a setpoint of –001 the timer is reset and stopped with no End alarm.
The master can set the timer functions, alarm values, and delay times using the Marathon
Block or Modbus protocols. The sequence of events is similar for either Marathon Block or
Modbus protocol.
The timer control word is located at parameter 70, Timer Control and Event (TCE). The timer control byte is the upper byte of this word. The input event configuration is in the lower byte of this word. Any configuration of the input event must be added to the timer function values when this word is written to the Versapro. In this example the event configuration is set to none (0). It is suggested that this word be read by masking the upper byte of the word to record the input event configuration. This value can then be added to the following timer control values to retain the input event configuration.
The timer will only work when it is enabled, the timer setpoint is greater then 0, and at least one alarm mode is set to a timer function. The alarm mode has to be manually configured.
Programming the timer involves the following sequence:
Enable the timer by writing a value 32768 (0x8000) to TCE.
Set the timer setpoint by writing setpoint value to parameter 3 (TSETPT)
Start the timer by writing a value 33024 (0x8100) to TCE.
The timer will indicate that it has timed out when TCE changes to value 34560
(0x8300).
Acknowledge the end alarm by writing a value 0 (0x0000) to TCE.
41
Marathon Monitors Inc. Dew Point
A description the TCE word and the timer flags in the TCE word can be found in the
Versapro Memory Map table.
42
Marathon Monitors Inc.
Probe Impedance Test
Dew Point
The probe impedance test is performed by measuring the open circuit voltage of the probe, applying a known shunt resistor across it and measuring the shunted voltage output. The value of the shunt resistor is 10kohm for DEWPT sensors.
To run a probe impedance test it is necessary setup the probe testing parameter in the
SETUP Probe Menu. Please refer to Probe parameters table for an explanation of these setup parameters. It is necessary to have the impedance (RES) test or both (BOTH) selected at the PROBE TEST parameter in order to run the impedance test. You may choose to accept the defaults for the other parameters in this menu or change them to suit your applications.
NOTE
It is necessary that the sensor be above the MIN PROBE TEMP parameter setting for this test to run. It is also necessary that the probe is measuring a stable process gas during this test.
There are two ways to start this test. From the Probe Setup menu at the START TEST parameter, you can change this parameter from NO to YES and then press the ENTER key.
The instrument will exit the Setup mode and display the test name and sequence number on the front display. The LCD display will indicate “IMPEDANCE TEST” while the lower
LED display will show the test sequence number as listed in the following table.
It is also possible to start the test in the process display mode by pressing the ENTER and
RIGHT ARROW keys at the same time. The test can be stopped by returning to the START
TEST parameter and changing YES to NO and then pressing ENTER or by pressing the
ENTER and RIGHT ARROW keys again.
If the TEST INTEVAL parameter has a number other than 00.0 then the test will continue to run each time the test interval timer counts down to 0. This test interval can be stopped by setting the interval timer to 00.0.
The following table explains the various operations of the impedance test.
Sequence #
1
2
Table 13 Probe Impedance Sequence
Description
Inhibit process variable calculations. Freeze all process controls and outputs.
Freeze alarms at last state except clear any previous probe test failure alarm.
Store present probe millivolt reading
Apply shunt resistor across probe
Wait for impedance test timer, fixed time of 30 seconds
Compute impedance of probe and remove shunt resistor. Save measured impedance as
PROBE IMPEDANCE in INFO menu.
43
Marathon Monitors Inc.
Sequence # Description
If impedance is greater than PROBE IMP
LIMIT then set probe test failure alarm.
Dew Point
3 Wait for probe to recover to >=99% of original millivolts.
Evaluate actual recovery time to IMP
RECVRY TIME
If recovery time is greater than IMP RECVRY
TIME then set probe test failure alarm.
Store recovery time (or max value ) as IMP
RECVRY TIME in INFO menu
4 If verification is to be performed then go to step 1 of verification sequence
Otherwise wait 30 seconds and resume normal operation of all instrument functions.
Why Measure Sensor Impedance?
It is important to track sensor impedance over a period of time to help determine the replacement schedule for the sensor. A high impedance (>50 K
Ω) indicates that the electrode contact on the probe zirconia has deteriorate to a level that probably warrants replacement. High sensor impedance results in a lower signal output from the sensor and an eventual failure of the electrode connection on the process side of the zirconia ceramic. This deterioration is more of a factor in highly reducing atmospheres. In such applications, it may be necessary to check the impedance at least once a month. Under light reducing, annealing, or brazing operations, the impedance may not have to be check unless there is a question about the probe’s performance.
A typical impedance for a new probe is less than 1 K
Ω. As the probe starts to age the impedance will increase. Past 20 KOHM the sensor should be monitored more closely.
Above 50 K
Ω, the sensor should be replaced. If it is necessary to replace the sensor, remove it carefully, following the instructions supplied with the sensor. Do not discard a sensor with a high impedance. It may be possible to rebuild the sensor if the ceramic parts are intact.
Contact Marathon Monitors , Inc. for information on rebuilding your sensor.
An impedance test can only be performed if the probe temperature is at or above 1300°F with stable atmosphere present. The instrument freezes all control functions and process signals during the test.
A 10
Ω resistor is shunted across the sensor output. The sensor impedance is calculated as:
Rx = [(Eo/Es)-1]*Rs
Where Rx = sensor impedance, Eo = sensor’s open circuit voltage, Es = shunted sensor’s voltage, and Rs = shunt resistor. The units of Rx are the same as Rs.
44
Marathon Monitors Inc.
Probe Burnoff
Dew Point
Probe burnoff is performed by flowing air into and around the oxygen sensor internal ceramic substrate. This air creates a flame at the tip of the sensor that burns off any accumulated DEWPT or soot. A ¼” CPI compression fitting at the mounting hub of
Marathon Monitors sensor is provided for the air connection. This air floods the probe sheath and flows out and around the sensor. The sensor does have to be above the MIN
PROBE TEMP parameter found in the PROBE setup menu. This value is typically 1300°F or higher.
To run a probe burnoff it is necessary setup the probe test parameters in the SETUP Probe
Menu. Please refer to Probe parameters table for an explanation of these setup parameters.
It is necessary to have the burnoff (BOFF) test or both (BOTH) selected at the PROBE
TEST parameter in order to run the burnoff. You may choose to accept the defaults for the other parameters in this menu or change them to suit your application. It is necessary that the sensor be above the MIN PROBE TEMP parameter setting for this test to run. It is not necessary for the probe to be measuring a stable process gas during this test.
There are two ways to start this test. From the Probe Setup menu at the START TEST parameter, you can change this parameter from NO to YES and then press the ENTER key.
The instrument will exit the Setup mode and display the test name and sequence number on the front display. The LCD display will indicate “BURNOFF TEST” while the lower LED display will show the test sequence number as listed in the following Table.
It is also possible to start the test in the process display mode by pressing the ENTER and
RIGHT ARROW keys at the same time. The test can be stopped by returning to the START
TEST parameter and changing YES to NO and then pressing ENTER.
If the TEST INTEVAL parameter has a number other than 00.0 then the test will continue to run each time the test interval timer counts down to 0. This test interval can be stopped by setting the interval timer to 00.0.
Readings are averaged to eliminate variations in measurement due to initial flow conditions.
There are three operator inputs for verification time periods;
• TEST INTERVAL is an interval timer that sets the time between automatic verifications in hours and tenths. The verification can be manually initiating by pressing and holding the Enter key and then the Right Arrow key. Setting the test interval time to zero disables automatic testing.
• BURNOFF TIME is the period in seconds burnoff air is flowing to the sensor.
• BURNOFF RECOVERY is the time period in seconds that allows the probe to recover and return to the process level.
The following table outlines the actions the instrument takes at each sequence step.
Table 14 Probe Burnoff Sequence
Sequence #
1
Description
Inhibit process variable calculations. Freeze all process controls and outputs.
45
Marathon Monitors Inc.
Freeze alarms at last state except clear any previous probe test failure alarm.
2
3
Close burnoff contact and wait the BURNOFF time period.
Release the burnoff contact and wait the
BURNOFF RECOVERY time period.
Save the mV reading as in INFO menu.
Resume normal operation of all instrument functions.
Dew Point
46
Marathon Monitors Inc.
Procedure to Test the Sensor
Dew Point
The following section describes the steps required to do an automatic or manual test of an oxygen sensor using the Versapro controller or monitor.
Correctly set up the parameters in the VersaPro for the Probe Testing.
1. Press the SETUP key for five seconds to activate the setup mode
2. Page to the Prob Menu heading by pressing the RIGHT or LEFT arrow keys. When
Prob appears in the LCD display, press the Enter key.
3. The first parameter is probe test. Press the UP or Down Arrow keys until the lower display reads Both. Press the Enter key to advance to the next parameter.
4. The next parameter is the Start Test. The default setting is NO. This parameter will change to YES if the probe test is running or if the interval timer is running.
5. The next parameter is the Test Interval (hours). This should be set to 0 for a manual start test. A flashing cursor in the lower LED display indicates which digit can change if the parameter value is numeric. The UP or DOWN arrows increase or decrease the digit value. The RIGHT or LEFT arrow keys move the cursor to the right or left digit. If a number is entered here it is the interval in hours between automatic repeats of the probe test. The probe test must be started manually the first time to initiate the repeat function.
6. The next parameter is the Probe Impedance Limit. This should be set to 20 (Kohms).
This setting is where the sensor electrodes are starting to wear and should be watched. If the impedance reaches 50 Kohms, the sensor should be replaced.
7. The next parameter is the Impedance Recovery Time (seconds). The default value is 30.
This value should always be greater than the millivolts filter value in the Input menu.
8. The next parameter is the Burnoff Time (seconds). The default value is 30. This value typically should not exceed 60 seconds if burnoff is being done at regular intervals.
9. The next parameter is the Burnoff Recovery (seconds). The default value is 30. This value may have to be increased if there is low re-circulation in the furnace.
10. The next parameter is the Minimum Probe Temperature. This should be set to 590 if C is used or 1100 if F is used.
11. After pressing the ENTER key for the last parameter, press the SETUP key to exit the
Menu and return to regular process operation.
To manually start a probe test procedure
1. Simultaneously press the RIGHT arrow/Enter keys with the display in normal process mode.
2. The instrument will cycle through the test steps and return to normal operation after completing the test if results are satisfactory.
3. You may access the results by cycling the display with presses of the Enter key. If a probe fault alarm is displayed it will be necessary to go to the Info section of the
SETUP Menu. The measured probe impedance, probe impedance test recovery time, probe millivolts and probe temperature during burnoff, and burnoff recovery time are listed.
If a Probe Fault occurs
To clear a Probe Fault alarm, you must run a successful probe test procedure, also see the
Troubleshooting section of this document.
47
Marathon Monitors Inc. Dew Point
Access the Probe Test Results data from the Info section of the SETUP Menu. Check the probe impedance and recovery times against the parameter settings in the Probe setup section. If necessary, adjust the test parameters to allow a successful test. Take the necessary actions to correct the problem.
48
Marathon Monitors Inc.
Tuning
Dew Point
Before attempting to tune the instrument make sure you understand the Operation and Setup part of the instrument.
What is tuning?
Tuning the controller means that the control characteristics of the controller are matched to those of the process in order to obtain hold the process to setpoint. Good control means:
• Stable, ‘straight-line’ control of the process variable at setpoint without fluctuation
• No (minimum) overshoot, or undershoot, of the process variable relative to setpoint
• Quick response to deviations from the setpoint caused by external disturbances, thereby rapidly restoring the process variable to the setpoint value.
Tuning involves calculating and setting the value of the parameters listed the following table. These parameters appear in the Control Setup menu.
Table 15
Parameter
Proportional band
Meaning or Function
The bandwidth, in display units, over which the output power is proportioned between minimum and maximum.
Integral time
(Reset)
Determines the time taken by the controller to remove steady-state error signals.
Derivative time
(Rate)
Determines how strongly the controller will react to the rate-of-change of the measured value.
Cycle Time The total amount of time used to calculate the combination of percent on and percent off periods of the control function.
The Versapro uses the Proportional Band as a representation of the Proportion section of
PID, the Reset as a representation of the Integral section of PID, and the Rate as a representation of the Derivative section of PID. Thus by following a simple procedure, PID tuning can easily be implemented in any control situation. A suggested procedure is diagramed in the next figure.
All of the PID parameters may be altered by changing these parameters in the Setup / Ctrl menu. The following procedure assumes the initial PID values for a typical batch furnace.
You may be able to start with a proportional band setting of 10 or less for a smaller box or temper furnace.
You must determine want the initial cycle time should be. If you are using control motors or continuous motors, set the cycle time to the time it takes the control motor or actuator to
49
Marathon Monitors Inc. Dew Point
fully open and fully close. If you are using quick acting solenoids to control the process the cycle time setting is a compromise between longer times to limiting contact cycles and extend the life of the actuator or shorter times to maintain good control. A good rule is to watch to process value and turn on the solenoid. Measure the time it takes for the process to react with a 5% change. Double this time and enter it as the cycle time. Decrease the cycle time to get a smoother control.
If, after following the procedure, the process continues to oscillate, it may be necessary to change the HIPO or LOPO parameters. Make sure that the control output is linear through the full range from LOPO to HIPO. In situations where the system is difficult to tune, it is most likely the output is not linear or there is too much lag time between the control command and measurable changes in the process. Test the system in manual mode to verify the output is linear.
A much higher proportional band may be necessary for extreme lag in the process response.
In most cases, the derivative part of the control equation is not necessary. Generally, furnace control can be maintained using only the proportional band and the reset parameters.
Make sure you record all operating parameters and keep them in a secure place for later reference.
50
Marathon Monitors Inc. Dew Point
Figure 8 PID Manual Tuning Procedure
51
Marathon Monitors Inc.
Scaling Analog Inputs
Dew Point
If either input is set to Linear mode the displayed value for that input can be scaled to desired engineering units. This is helpful if the measured linear value has to be scaled and re-transmitted on one of two analog output channels.
Using the equation y = mx + b, where
Y is the desired engineering unit to be displayed
X is the linear millivolt value
M is the Slope of the y/x relationship
B is the y intercept
Linear A Example
Let us use Input A input for a linear oxygen transducer that outputs a 0mV to 53.2mV signal for a 0% to 100% oxygen range. Since both the signal output and the process minimum are both 0, the Input A offset will be 0.
The slope can be calculated by dividing the maximum process value (100) by the maximum input level (53.2mV). This gives a slope value of 1.879. This number can be entered as the
Input A slope. The decimal point can be shifted by placing the flashing cursor on the most significant digit and pressing the Left arrow key until decimal point shifts to the required position.
These scaling values will produce a process value of 100.0160% DEWPT for a maximum sensor input of 53.2mV. The process display can be configured to display either 100 or
100.0. This process value can then be retransmitted to other control devices are a recorder.
The control model of the Versapro will be able to control to a set point for the new process value.
Keyboard Function during Input Slope
The four digits in the slope display can be change from 0 to 9 or the left digit and change to the negative sign. This most significant digit position also allows you to shift the decimal point by pressing the LEFT arrow key. The decimal point will shift from first digit to the third digit as the LEFT arrow key is pressed. Pressing the RIGHT arrow key when the cursor is on the least significant digit will shift the decimal point to the right.
52
Marathon Monitors Inc.
Scaling Analog Outputs
Dew Point
The analog outputs are scaled as simple offset and span values. For example if analog output 1 is to be scaled for a 0 to 46.0° dew point value, the offset value would be 0 and the span value would be 46.0.
It is possible to narrow the range of the output even if the instrument can measure a larger process range. If a smaller range of dew point were to be retransmitted it would be necessary to change the offset value to the lowest value to be retransmitted. The span would be set to the highest value. For example if a dew point span of 20° to 50° was to be retransmitted then the offset would be 20.0, the span would be 50.0. The full 4mA to 20mA output range would respond to this narrower range of dew point.
The same rules apply to analog output 2. The range of the offset and span numbers depends on the range of the process value that has been selected for either analog output.
Additional selections for Power Output and Program mode have fixed offset and span values. The power output offset and span values are fixed to the LOPO and HIPO values selected for the control outputs under the Setup Control menu.
The Program mode selection has a fixed offset of 0 and a fixed span of 4096. When this output mode is selected the analog output can only be changed by writing a value to either the DACV1 or DACV2 registers.
53
Marathon Monitors Inc.
Calibration
Dew Point
There are two analog inputs, a cold junction compensation sensor, and two analog outputs on the VersaPro. The input level is determined by which terminals are used for the input signal.
There are two pairs of input terminals: TB-B 1, 2 for the thermocouple (T/C) input and TB-B
3, 4 for the probe millivolt input.
The 4 – 20mA analog outputs are at TB-B 5, 6 and TB-B 7, 8.
The following is a brief description of input/output and its specifications.
Input
-10
± 2 μV b) Probe mV Input to
± .1 mV, linear
Calibration Displays and Keyboard Operation
When entering the Calibration Menu, the operator has to answer one of two questions depending on which I/O functions have to be calibrated. If the CALIBRATION IN prompt is answered with a YES, then the parameters related to the thermocouple input, millivolt input, and cold junction can be changed. If this prompt is skipped by pressing the Enter key, then a second prompt, CALIBRATION OUT is displayed. If this prompt is answered with a
YES, then the zero and span values for both analog outputs can be changed.
In the Calibration Menu the displays and front panel keys take on special assignments. The
LCD display shows the input and calibration point being calibrated. The upper LED display indicates that the instrument is in CAL mode. The lower LED display indicates the actual input level for the input channels or the calibration factor for the output channels.
It is very important that the display is indicating the proper I/O parameter before making an adjustment or the wrong value will be changed.
For the CAL INPUT calibration mode, the following keys perform the described functions:
54
Marathon Monitors Inc. Dew Point
UP ARROW
DOWN ARROW
RIGHT ARROW
Increases the displayed value.
Decreases the displayed value.
Shifts the flashing digit to the right and decreases the amount of adjustment or sensitivity of the adjustment.
LEFT ARROW Shifts the flashing digit to the left and increases the amount of adjustment or sensitivity of the adjustment.
ENTER
SETUP
Advances to next input value and saves the calibration changes.
Exits the calibration mode.
Preparing for Input Calibration
The following is required to calibrate thermocouple and millivolt inputs:
Calibrated millivolt source, 0 – 2000mV with a 0.1 mV resolution
Calibrated microvolt source, -10mV to 50mV with a 0.1 uV resolution.
Copper wire to connect the millivolt source to the instrument.
Calibrated thermocouple simulator with internal cold junction compensation
Thermocouple extension wire for the type of thermocouple to be used.
In the Input Setup menu, select the thermocouple type to be used in the process. Enable
Cold Junction Compensation.
The first part of the calibration is in linear mode first. The thermocouple setting has no effect on the millivolt readings in the first part of the input calibration but will effect the reading during the cold junction adjustment.
Calibration of the Thermocouple Input
Calibration procedure:
1. Connect terminals TB-B 1, 2 to an isolated, stable millivolt source calibrator using standard copper wire, 20 AWG is sufficient.
2. Set the calibrator output to 0.00 mV.
3. Activate the calibration mode by entering the SETUP menus, selecting the Calibration menu and changing Calibration IN - NO to YES.
4. Use the Enter key to select the TC ZERO mode.
5. Using the arrow keys, adjust the displayed value to equal the calibrator input.
6. Press the Enter key to select the TC SPAN mode.
7. Set the calibrator output to 50.0mV (70mV maximum).
8. Using the arrow keys, adjust the displayed value to equal the calibrator output.
Calibration of the Cold Junction Temperature
Calibration procedure:
55
Marathon Monitors Inc. Dew Point
1. Change the millivolt source calibrator to thermocouple mode with internal cold junction compensation. Change the copper wire with the correct thermocouple extension wire
2. Set the calibrator to a typical temperature level.
3. Use the Versapro Enter key to advance to the CJ Adjustment display.
4. Using the arrow keys, adjust the displayed value to equal the calibrator input.
Ref to the following tables for the valid range of thermocouple inputs that can be used to calibrate the cold junction compensation.
Table 16 Thermocouple Calibration Values
B
E
J
K
N
R
T/C type Minimum Value
°F (°C)
800 (426)
-454 (-270)
32 (0)
32 (0)
32 (0)
300 (150)
Maximum Value
°F (°C)
3000 (1800)
1832 (1000)
1300 (900)
2300 (1200)
2300 (1200)
3000 (1800)
S
T
300 (150)
32 (0)
3000 (1800)
700 (350)
The usable ranges for the thermocouple types are shown in the following table. If it is desirable to have a higher accuracy over a specific operating range then the input should be calibrated over that range.
56
Marathon Monitors Inc.
Table 17 Usable Thermocouple Range (°F)
T/C type Minimum
Value (°F)
Maximum
Value (°F)
Dew Point
R 300
T -380
3210
3210
755
* Due to the extreme non-linearity of low level signals, using type R and S below 300° F is not recommended.
Calibration of the Probe Millivolt Input
Calibration procedure:
1. Connect terminals TB-B 3, 4 to an isolated, stable millivolt source calibrator using standard copper wire, 20 AWG is sufficient. A maximum output of 2000 mV is required.
2. Set the calibrator output to 0.00 mV.
3. Activate the calibration mode by entering the SETUP menus, selecting the Calibration menu and changing Calibration IN - NO to YES.
4. Use the Enter key to select the MV ZERO mode.
5. Using the arrow keys, adjust the process value to equal the calibrator input.
6. Press the Enter key to select the MV SPAN mode.
7. Set the calibrator output to the required millivolt span (2000 mV maximum).
8. NOTE: The displayed number will change in resolution. The millivolt value will show the tenths digit if the measured value is less than 1000 mV. Above 999.9 mV the display will shift to whole numbers. Use the arrow keys to adjust the process value to equal the calibrator output.
Preparing for Analog Output Calibration
The same calibration procedure can be used for either output channel. For the CAL
OUTPUT mode, the following keys perform the described functions:
UP ARROW
DOWN ARROW
RIGHT ARROW
Increases the value of the flashing digit.
Decreases the value of the flashing digit.
Shifts the flashing digit to the right.
57
Marathon Monitors Inc. Dew Point
LEFT ARROW Shifts the flashing digit to the left.
ENTER Advances to next calibration value and saves the calibration changes.
SETUP
Calibration procedure:
Exits the calibration mode.
1. Connect terminals TB-B 5, 6 (or 7, 8) to a multimeter such as a Fluke 77. Select the milliamp measurement range and verify that the test leads are plugged into the milliamp jack and common on the multimeter.
2. Activate the calibration mode by entering the SETUP menu, selecting the Calibration menu, press the ENTER key until CAL OUTPUT - NO is displayed.
3. Change the NO prompt to YES using the UP arrow key.
4. Press the ENTER key to select the OUTPUT 1 MIN mode. If OUTPUT 2 is required, continue pressing the ENTER key until OUT 2 MIN is displayed.
5. Using the UP or DOWN arrow keys, adjust the displayed number from 0 to 9. Press the
RIGHT or LEFT arrow keys to select the adjustment sensitivity. Adjust the displayed value until the multimeter indicates the desired minimum output. This is typically set for 4 mA (cal factor ~ 800), but this level can be adjusted to 0mA (cal factor ~ 0).
6. Press the ENTER key to select the OUTPUT 1 SPAN mode. If OUTPUT 2 is required, continue pressing the ENTER key until OUTPUT 2 SPAN is displayed.
7. Using the arrow keys as explained in step 5, adjust the output to read 20mA on the multimeter. A typical cal factor for 20mA is 3200. The maximum cal factor is 4095.
8. Press the SETUP key to save the calibration values and exit the calibration routine.
58
Marathon Monitors Inc.
Communications
Dew Point
Modbus
The MODBUS protocol describes an industrial communications and distributed control system (DCS) that integrates PLCs computers, terminals, and other monitoring, sensing, and control devices. MODBUS is a Master/Slave communications protocol, whereby one device, (the Master), controls all serial activity by selectively polling one or more slave devices. The protocol provides for one master device and up to 247 slave devices on a half duplex twisted pair line. Each device is assigned an address to distinguish it from all other connected devices.
The VersaPro recognizes three Modbus RTU (Remote Terminal Unit) commands. These are: read single I registers (command 4), read a single H register (command 3), and preset a single H register (command 6)
In the RTU protocol sends data in 8-bit binary characters. Message characters are transmitted in a continuous stream. The message stream is setup based on the following structure:
Number of bits per character:
Data bits (least significant first) 8
Parity 0 (no bits for no parity)
Error Checking CRC (Cyclical Redundancy Check)
In Modbus mode, the VersaPro can be only be configured for the ‘none’ parity option.
The instrument never initiate communications and is always in the receive mode unless responding to a query.
RTU Framing
Frame synchronization can be maintained in RTU transmission mode only by simulating a synchronous message. The instrument monitors the elapsed time between receipt of characters. If three and one-half character times elapse without a new character or completion of the frame, then the instrument flushes the frame and assumes that the next byte received will be an address. The follow command message structure is used, where T is the required character delay. Response from the instrument is based on the command.
T1,T2,T3 ADDRESS FUNCTION DATA CHECKSUM T1,T2,T3
8-BITS 8-BITS N X 8-BITS 16-BITS
Address Field
The address field immediately follows the beginning of the frame and consists of 8-bits.
These bits indicate the user assigned address of the slave device that is to receive the message sent by the attached master.
59
Marathon Monitors Inc. Dew Point
Each slave must be assigned a unique address and only the addressed slave will respond to a query that contains its address. When the slave sends a response, the slave address informs the master which slave is communicating.
Function Field
The Function Code field tells the addressed slave what function to perform. MODBUS function codes are specifically designed for interacting with a PLC on the MODBUS industrial communications system. Command codes were established to manipulate PLC registers and coils. As far as the VersaPro is concerned, they are all just memory locations, but the response to each command is consistent with Modbus specifications.
The high order bit in this field is set by the slave device to indicate an exception condition in the response message. If no exceptions exist, the high-order bit is maintained as zero in the response message.
Data Field
The data field contains information needed by the slave to perform the specific function or it contains data collected by the slave in response to a query. This information may be values, address references, or limits. For example, the function code tells the slave to read a holding register, and the data field is needed to indicate which register to start at and how many to read.
Error Check Field (CRC)
This field allows the master and slave devices to check a message for errors in transmission.
Sometimes, because of electrical noise or other interference, a message may be changed slightly while it is on its way from one device to another. The error checking assures that the slave or master does not react to messages that have changed during transmission. This increases the safety and the efficiency of the MODBUS system.
The error check field uses a CRC-16 check in the RTU mode.
The following is an example of a function 03 call for timer setpoint value (TSETPT) at memory location 03. The value returned by the instrument is the hex value 1E (30 seconds).
Transmit from Host or Master
Address Cmd Reg
HI
Reg
LO
Count
HI
Count
LO
CRC
HI
CRC
LO
01 03 00 03 00 01 74 0A
Response from Versapro
Address Cmd Byte
Count
HI
01 03 00
Byte
Count
LO
Data
HI
Data
LO
CRC
HI
CRC
Lo
02 00 1E 38 4C
60
Marathon Monitors Inc. Dew Point
Note that all the values are interpreted as hexadecimal values. The CRC calculation is based on the A001 polynomial for RTU Modbus. The function 04 command structure is similar to the 03 structure.
The following is an example of a function 06 call to change the remote setpoint (RSETPT) to 200 (2.00%). The response from the instrument confirms the new value as being set.
Transmit from Host or Master
Address Cmd Reg
HI
Reg
LO
Data
HI
Data
LO
CRC
HI
CRC
LO
Response from Versapro
Address Cmd Reg
HI
Reg
LO
Data
HI
Data
LO
CRC
HI
CRC
LO
The Versapro will respond to several error conditions. The three exception codes that will generate a response from the instrument are:
01 – Illegal Function
02 - Illegal Data Address
03 – Illegal Data Value
04 – Slave Device Failure
The response from the Versapro with an exception code will have the most significant bit of the requested function set followed by the exception code and the high and low CRC bytes.
MMI Message Protocol
The basic Marathon Monitors message protocol format is shown below.
61
Marathon Monitors Inc. Dew Point
As indicated, the MMI or proprietary mode allows communication using the 10PRO ‘A’ command protocol or the ‘U’ block protocol.
The following command set applies to the ‘A’ command and is used for the Versapro and other 10PRO type instruments such as temperature controller slaves. The command set is sent by a master to a 10PRO slave instrument. These commands can also be used by any device such as a computer communicating with instruments via an instrument network. The commands that are supported are shown in the following table.
62
Marathon Monitors Inc.
Table 18 10Pro / 10Pro-T Command Set
Dew Point
COMMAND
LETTER
p (low case) o (low case) i (low case) h (low case)
I (upper case as in
Instrument)
J (upper case)
Process ( temperature) Timer
Read Auto / Manual mode
Read Remote / Local
Read Remote Process
Setpoint
Read Auto Process
Setpoint
Update Process Setpoint
Temporarily
Update Process Setpoint
Permanently
Read Actual Process
Same
Returned Value
A = auto, B = manual
Same A = local, B = remote
Read Remote Time
Setpoint integer decimal number
Read Auto Time Setpoint integer decimal number
Update Time Setpoint
Temporarily integer decimal number
Update Time setpoint
Permanently
Read Remaining Time integer decimal number integer decimal number l (lower case as in limits) m (low case)
P (upper case)
Read % Output
Update Auto/Manual mode
Read Time control byte
Same integer decimal number
A = auto, B = manual
The following are examples of commands and responses using the 10Pro type command set.
The first row in each table shows the ASCII characters of the command as they would appear if monitored on the serial port. The second row in each table is the hexadecimal translation of the characters transmitted on the serial port. These values must be known to calculate the checksum.
This is the command and response for reading the actual process value of a 10Pro type slave instrument. In this example the 10Pro instrument address is 2 and the return value is 0071.
This could be 71 degrees. 0.71% DEWPT, 7.1 degrees dewpoint, or 0.71% oxygen depending on the process and the instrument settings. Other parameters and scaling are available if the linear inputs are selected. In general the number that is returned is the number displayed on the instrument. Decimal point information is assumed.
Add
2
Transmit from Host or Master
Prefix Cmd
A l
Delim LRC
<NULL> <HEX 1F > <EOT>
Add Prefix Cmd
Response from 10Pro
D1 D2 D3 D4 Delim LRC
0x06 0x32 0x41 0x6C 0x30 0x30 0x37 0x31 0x00 0x1F
Here is an example of a request and response for the local setpoint of the instrument in
Automatic mode. The response indicates that the instrument’s address is 2 and the local setpoint is 1500.
Transmit from Host or Master
Add
2
Prefix Cmd
A h
Delim LRC
<NULL> <HEX 1B > <EOT>
0x04
63
Marathon Monitors Inc. Dew Point
Response from 10Pro
Add Prefix Cmd D1 D2 D3 D4 Delim LRC
<ACK> 1 5 0 0 <NULL>
0x06 0x32 0x41 0x68 0x31 0x35 0x30 0x30 0x00 0x19
Here is an example that shows how the HOST changes the instrument’s remote set point.
The instrument’s address is 15. The HOST has sent a command to update the remote setpoint with 1450. The instrument responds by echoing the command.
Transmit from Host or Master
0x04
Add Prefix Cmd
F A I
D1 D2 D3 D4 Delim LRC
0x46 0x41 0x49 0x31 0x34 0x35 0x30 0x00 0x4E
<EOT>
0x04
Add Prefix Cmd
Response from 10Pro
D1 D2 D3 D4 Delim LRC
0x06 0x46 0x41 0x49 0x31 0x34 0x35 0x30 0x00 0x48
Instrument Type ‘U’ Command Set
The MMI (Marathon Monitors Inc.) command set supports the extensive capabilities of the
Dualpro the 10Pro-E and the Versapro. The command set consists of the characters shown in the following table.
<EOT>
0x04
Table 19 MMI Command Set
Update Read Description
X x
Not Allowed *
Read / Writer Table
Parameters
Read Block Transfer
‘X’ Command
The ‘X’ command allows almost unlimited access to all the instrument parameters. The ‘X” command accesses the various parameter tables in the instrument. A typical parameter table for most Marathon instruments has 240 parameters numbered consecutively from 0 to
239 (0 – 0xEF). Instruments such as the Dualpro have many tables (0 – 31), where each table has 11 blocks or more.
The Versapro, 10Pro-E, and Version 3.5 Carbpro have only table 0. The table value is assumed to be 0 and the parameter is addressed directly with the possible range of 0 to 71.
These number correspond with the decimal numbers in the Versapro Memory Map table.
To READ a data value from a table / parameter number in the instrument, use the following format:
AUx (Table # Parameter #) <delimiter> <checksum> <EOT>
64
Marathon Monitors Inc. Dew Point
Here is an example of a request and response for the instrument’s proportional band setting in table 0, parameter 10 (0x0A). The instrument address is 1. The data value that is returned by the instrument is hexadecimal 0014 or 20.
Transmit from Host or Master
Add
1
0x31
Prefix
U
0x55
Cmd x
0x78
Table #
00
Par #
0A
Delim
NULL
0x30 0x30 0x30 0x41 0x00
LRC
<HEX 6D >
0x6D
Add Prefix Cmd Table
#
Par
#
Instrument Response
Data
Delim
D1 D2 D3 D4 Delim
EOT
0x04
LRC
0x06 0x32 0x55 0x78 0x30
0x30
0x30
0x41
0x24 0x30 0x30 0x31 0x34 0x00 0x4A 0x04
The response from the instrument includes the ‘$’ character. This characters acts as the data delimiter, which separates the parameter data from the parameter address.
Here is an example of a request and response for the instrument’s Alarm 1 value in table 00
(0x00) parameter 06 (0x06). The instrument address is 1. The data value that is returned by the instrument is 50 (0x32). The actual value is 0.50 where the decimal point is implied by the process.
Transmit from Host or Master
Add Prefix Cmd Table # Par # Delim LRC
0x31 0x55 0x78 0x31
0x30
0x31
0x33
0x00 0x1A 0x04
Add Prefix Cmd Table
#
Response from Instrument
Par
#
Data
Delim
D1 D2 D3 D4 Delim LRC
0x06 0x31 0x55 0x78 0x30
0x30
0x30
0x36
0x24 0x30 0x30 0x33 0x32 0x00 0x39 0x04
The parameter write command uses the following format:
AUX (Table # Parameter #) $ data <delimiter> <LRC> <EOT>
To write a value to the instrument for a specific parameter use the uppercase X. To read a specific parameter from the instrument, use the lowercase x.
65
Marathon Monitors Inc. Dew Point
Here is an example of a parameter write command and response for data in table 00 (0x00) parameter 06 (0x06). The instrument address is 1. The data value that is written to the instrument is 0000 (0x0000).
Transmit from Host or Master
Add Prefix Cmd Table
#
Par
#
Data
Delim
D1 D2 D3 D4 Delim LRC
0x31 0x55 0x58 0x30
0x30
0x30
0x36
0x24 0x30 0x30 0x30 0x30 0x00 0x1E 0x04
Response from Instrument
Add Prefix Cmd Table
#
Par
#
Data
Delim
D1 D2 D3 D4 Delim LRC
0x06 0x31 0x55 0x58 0x30
0x30
0x30
0x36
0x24 0x30 0x30 0x30 0x30 0x00 0x18 0x04
The parameters for the Versapro are listed in the manual appendix. This listing includes the parameter name, number, and a short description that includes bit and byte mapping information.
Block Commands
Block transfer commands are used to read and write data in a group of 24 words. The
Versapro has only three blocks in table zero. The block transfer command has to identify the table as well as the block.
A block read command format is shown below.
66
Marathon Monitors Inc.
A U * tt bb D L E
Dew Point
(E)End of Transmission (EOT) HEX(04)
(L) LRC is the result of an XOR function performed on all previous character in the messeage.
(D) Delimter marks the end of DATA and signals the up coming EOT character.
NUL HEX(00) or Backspace HEX(08)*
*If LRC was going to be an EOT HEX(04) then D =
HEX(08).
(bb) Block number 0 - 2
(tt) Table number (HEX)
(*) Block Read command character
(I) Instruement Prefix: U = Dualpro/10Pro-E/V3.5/
Versapro.
(A) Address of instrument.
Figure 9 Block Read Command Format
The reply to a Block read request follows.
67
Marathon Monitors Inc.
A U * tt bb $ ddd-------ddd CC D L E
Dew Point
(E)End of Transmission (EOT) HEX(04)
(L) LRC is the result of an XOR function performed on all previous character in the messeage.
(D) Delimter marks the end of DATA and signals the up coming EOT character.
NUL HEX(00) or Backspace HEX(08)*
*If LRC was going to be an EOT HEX(04) then D =
HEX(08).
(CC) MOD 256 checksum of data characters ASCII values in two (2) HEX digits.
Ninety-six (96) HEX digits of data, four (4) digits, (2) bytes, (24) parameters
($) Data separator
(bb) Block number (HEX)
(tt) Table number (HEX)
(*) Block Read command character
(I) Instruement Prefix: U = Versapro instrument prefix.
(A) Address of instrument.
Figure 10 Block Read Response Format
The following is an example is for a block request from the Host and a reply from the instrument. The Host sends the command:
1U*0000<00>N<04><06>
Where the instrument address is ‘1’, the instrument type is ‘U’, the table and block are both zero (TTBB), and the delimiter, LRC and EOT follow.
The instrument responds with the string shown in the following table.
Table 20 Sample Block Response
Hex ASCII
Address 1 31
Command * 2A
Register 0000 30 30 30 30
Delimiter $ 24
Parameter 1
Parameter 2
Parameter 3
Parameter 4
C11C
00E5
8112
0096
43 31 31 43
30 30 45 35
38 31 31 32
30 30 39 36
68
Marathon Monitors Inc.
Parameter 5
Parameter 6
Parameter 7
Parameter 8
Parameter 9
Parameter 10
Parameter 11
Parameter 12
Parameter 13
Parameter 14
Parameter 15
Parameter 16
Parameter 17
Parameter 18
Parameter 19
Parameter 20
Parameter 21
Parameter 22
Parameter 23
Parameter 24
0096
00C8
03B6
07D0
0000
0C00
03E8
03E8
0000
0000
0000
0000
0060
1C25
00F3
3C69
0001
03E8
0000
3D62
30 30 39 36
30 30 43 38
30 33 42 36
30 37 44 30
30 30 30 30
30 43 30 30
30 33 45 38
30 33 45 38
30 30 30 30
30 30 30 30
30 30 30 30
30 30 30 30
30 30 36 30
31 43 32 35
30 30 46 33
33 43 46 39
30 30 30 31
30 33 45 38
30 30 30 30
33 44 36 32
MOD 256 BF 42 46
Delimiter 00 00
Dew Point
Note that the MOD 256 is the 256 modulus of the sum of the ASCII values of the parameters. The delimeter and LRC are calculated as described in a previous section.
MMI Error Codes
The Marathon protocol for the Versapro has three error codes that can be generated by the instrument: E1 = Incorrect LRC detected on received message, E2 = Invalid command detected, and E3 = Invalid table or parameter address.
The format for the error message is
<NAK> Error Code DEL LRC <EOT>
Where <NAK> is the hexadecimal value 15 followed by the ASCII characters for the appropriate error code. The delimiter and LRC are calculated the same as for a normal message. The EOT (hexadecimal 04) end every message in the MMI protocol.
69
Marathon Monitors Inc.
Process Calculation
Dew Point Process Control
4238.7
Dew Point
Dewpoint = ----------------------------------
9.55731 - log10(E / (Tk x 0.0215)
Where:
E = probe millivolts + mv offset, Tk = probe temperature in degrees Kelvin.
NOTE:
This calculation is only valid for Endothremic Rx gas in a state of equilibrium. The equation will not work for a dew point calculation on Exothermic gases.
70
Marathon Monitors Inc.
Troubleshooting Questions
Dew Point
This section is organized alphabetically by the functional name of various instrument operations and features. Some explanations may be listed in more than one category since the problem can be approached from several different points of view. Each problem is presented as a question for typical problems that may be encountered. In most cases the problem can be resolved by changing a setup parameter in the instrument.
Analog Inputs
How come the display flashes HHHH or LLLL when I try to read a signal at input A or input B in linear mode?
There are possibly two reasons; the decimal point setting in the Calc menu has to be adjusted for the maximum signal level to be read or the signal level has exceeded the range of the input channel. Channel A is set up primarily for thermocouple levels from –10mV to 70mV.
Channel B is set up for oxygen sensor millivolt ranges of 0 to 2000 mV. The display decimal point setting will not truncate the input value, it just increases the resolution of the input signal. If the value is within the input range of the channel but greater than or less than the possible display setting then the limit warnings will flash on the display.
I am trying to offset the temperature using the offset and scaling number in the Input menu but the temperature does not change.
The input offset and scaling numbers for inputs A and B only work if either Linear A or
Linear B are selected as the process source in the Control Menu. If it is necessary to offset the temperature slightly it is possible to do this by changing the cold junction trim adjustment in the Input Calibration menu. It is not recommended that the actual linear calibration values for input A are changed.
Control Outputs
I have a dual contact control mode selected but my second contact does not work.
When a dual control mode is selected it is necessary to also set the high percent output
(HIPO) and low percent output (LOPO). In single time proportioning, the default mode, the
HIPO is 100 and the LOPO is 0. When a dual mode is selected it is necessary to change the
LOPO to –100. In the case of DEWPT control it is typically required to control gas and air.
The first control contact would be connected to the gas solenoid and the second control contact would be connected to the air solenoid. The gas solenoid would be turn on all the time when the control output goes to 100%. Likewise the air solenoid would be on all the time if the control output was –100%.
When would I change my HIPO or LOPO settings to something other then the 100% or –100%?
These values rarely have to be changed but one case that requires it is when the control actuator is not acting an expected linear fashion. An example would be an SCR driving a heater. If the SCR is not actually turning on until the control signal is at 20% and stops increasing at 80% then the linear response of the actuator is only between 20% and 80%. If the controller assumes the full output range of 0 to 100% then a large delay in process reaction will drive the reset function in the PID control calculation into oscillation. It would be necessary to set the LOPO to 20% and the HIPO to 100% to achieve stable control.
71
Marathon Monitors Inc. Dew Point
Digital Communications
How come I have communications problems with an instrument address following a
Versapro address setting.
If the timer function has been enabled and the Versapro host protocol is set to ‘Prop’ for the
Marathon protocol, the instrument will take the next host address setting to respond with the timer parameters. The problem can be corrected by turning of the timer function in the
Control menu or setting to next instrument address to Versapro host address + 2.
Display Functions
How come the display flashes HHHH or LLLL when I try to read a signal at input A or input B in linear mode?
There are possibly two reasons; the decimal point setting in the Calc menu has to be adjusted for the maximum signal level to be read or the signal level has exceeded the range of the input channel. Channel A is set up primarily for thermocouple levels from –10mV to 70mV.
Channel B is set up for oxygen sensor millivolt ranges of 0 to 2000 mV. The display decimal point setting will not truncate the input value. If the value is within the input range of the channel but greater than or less than the possible display setting then the limit warnings will flash on the display.
How come the process values will not cycle on the display when I press the Enter key?
The display will not cycle through the process values if there is an active alarm. Press the
Enter key to see any active alarms. If multiple alarms are active it will be necessary to press the UP or DOWN keys until all of the alarms have been displayed. It is necessary to clear these alarms before the display will cycle by pressing the Enter key.
Probe Care
How can I clear the Probe Fault alarm?
The probe fault can only be cleared with a successful test. Several ways to force this are to start and then quickly stop the probe tests or set the test criteria above the last test data collected during the failure.
I keep getting the Probe Fault alarm but do not know what the problem is?
A probe fault can occur if one of several parameters exceed defined limits. These parameters are set in the Probe Care menu. For the DEWPT, oxygen, and dew point processes the probe impedance and probe impedance recovery time are tested when the ‘res’ or ‘both’ modes are selected in the probe menu. If the Probe Impedance Limit (Kohm) or
Impedance Recovery Time limit (seconds) are exceeded then the probe fault condition is set.
The ‘burnoff’ or ‘both’ test modes for DEWPT and dewpoint are compared to a burnoff test recovery time setting (seconds). If the mV output of the sensor measured prior to the test does not return to previous level within the recovery time setting then the probe fault condition is set.
The ‘verify’ or ‘both’ test modes for oxygen measure the oxygen during the introduction of a known test gas. If this measurement does not fall within the limits of the standard verification gas setting and the allowed tolerance then the probe fault will be set. Most of the probe test results are displayed in the display cycle by pressing the Enter key but if a
72
Marathon Monitors Inc. Dew Point
fault has occurred this function is disabled so that multiple alarms may be viewed. It is necessary to go to the Info menu to view the probe test measurements and compare these data to the probe test settings.
How come I am failing the recovery time limit?
Check the filter time for the temperature or millivolt input. A small filter time will allow the instrument to update the measured values faster and give a more accurate recovery time.
The recovery time setting can no be shorter than the filter time setting. Both are set and displayed in seconds.
How come the probe test will not start?
One of the probe test parameters is minimum test temperature. The default of this temperature is 1400. If the measured temperature is below this value the test will not run.
This minimum temperature setting is limited by the minimum temperature required for the sensor to operate. This limit is typically 1000 to 1100 mV. Trying to do a probe test below these temperatures or with no process atmosphere present will not produce any reliable information.
Timer Function
How come I can not enter a timer setpoint.
Two things have to be set for the timer to work; the timer has to be enabled in the Control
Menu, and a timer alarm function has to be selected for alarm 1 or alarm 2 but not both alarms at the same time. Only when these conditions have been met will the instrument accept a timer setpoint.
How come I can not start a timer function when the Input Event is set to Start and
activated?
Make sure all of the conditions explained in the first question of this time section have been met.
Why is there a delay between the Timer display changing to zero and the End alarm coming on?
The timer is counting in milliseconds but only displays whole seconds. When the display first changes from 1 to 0 it actually changes to 0.99. It continues to count down for the remaining milliseconds until the timer reaches zero at which point it turns on the End alarm.
73
Marathon Monitors Inc.
Versapro Monitor Mode
Dew Point
The Versapro’s internal EEPROM can be reprogrammed when placed in Monitor Mode.
This mode allows the user to perform checks and set default conditions in the instrument by using a RS232 to RS485 converter and the popular Windows
program HyperTerminal.
It is necessary to enter this mode when a CPU has been re-programmed or if a checksum fault has occurred in EEPROM.
The user can also use advanced features of Monitor Mode such as status check, read RAM and FLASH memory, write to RAM memory, load FLASH defaults to RAM, load EEPROM defaults from RAM to EEPROM, or write from EEPROM into RAM.
Prepare for Connection
Make sure you have recorded all the operational parameters of the instrument before you change the EEPROM values. These parameters will include the thermocouple type, alarm functions, and probe care settings. For the controller version of the Versapro this will also include control and PID settings as well. Note the instrument calibration settings for the two analog output channels by going into the SETUP mode, selecting CAL OUT – Yes and recording the offset and span values shown for each channel. Advance to the each parameter by pressing the <Enter> key. Press <Setup> to return to the process mode.
How to Connect
The Versapro has a RS485 half-duplex port located on terminals TB-B 13 and 14, where 13 is the +RS485 connection and 14 is the –RS485 connection.
Insure your converter is plugged into the serial port of your computer. Insure that your converter is configured as a half-duplex (two wire) output and not as a full-duplex (four wire) output.
Apply power to the instrument and observe that it is operating in normal process mode where the process name is displayed in the center LCD display.
NOTE
Your version of HyperTerminal may be different then the steps outlined in this procedure.
The basic information provide here will apply to any configuration. Accept the setup defaults if you are not sure about a specific feature that is not addressed here.
When HyperTerminal starts up it asks for a name of a new connection. Enter a name that you can associate with the Versapro setup.
The ‘Connect To’ window will then appear.
Make the following selections in the Connect To window;
Connect using: (select the comm port the RS485 is connected to)
Press the ‘OK’ button.
74
Marathon Monitors Inc. Dew Point
In the ‘Port Settings’ window that appears next, make the following selections;
Bits per second: 19200
Data bits: 7
EVEN bits:
Flow control: None
Select the File \ Properties \ Settings tabs and make the following selections;
Select the ‘Terminal Keys’ button
Select the ‘Ctrl+H’ button
Set ‘Emulation’ to ANSI
Set ‘Telnet terminal ID’ to ANSI
Set ‘Backscroll buffer lines’ to 500
Click on the ASCII Setup… button;
Set ‘Line delay’ to 25 msec
Set ‘Character delay’ to 0 msec
Click on the ‘OK’ button to escape the Connections window.
HyperTerminal will now be connected to the comms port waiting for serial data from the
Versapro.
Start Monitor Mode
At the Versapro press and hold the <REM> and <Enter> keys. Hold these keys until the center display changes to "MONITOR MODE”, (about 5 seconds). The instrument will send a prompt to the HyperTerminal screen that should look like figure 1. If the Versapro is already in Monitor Mode it may only have the Power light on with no other display. Cycle power on the instrument while connected to see the “Marathon Monitors , Inc.” prompt.
75
Marathon Monitors Inc. Dew Point
Figure 11 Initial Prompt Screen
The following table lists the commands that are available in Monitor mode.
Command
D
Command Description
Displays 16 rows by 16 bytes of memory
J
K
Displays all values in EEPROM
Programs EEPROM for RAM values
L
S
W
X
Z
Loads RAM EEPROM area with FLASH defaults
Displays status of processor
Writes a byte from EEPROM to RAM
EEPROM mirror or writes data to RAM.
Exits Monitor mode
Resets processor idle counter
The Versapro is placed into Monitor mode when the <Enter> and <Rem> keys on the instrument are pressed simultaneously and held for about 5 seconds. The LCD display will display the prompt ‘MONITOR MODE’ and the LED display will be blank. The instrument also sends banner and prompt character to the HyperTerminal screen. The following figure shows this display.
At the ‘>’ prompt type any of the above commands.
At this point the instrument is not performing any process or control functions but is only waiting for Monitor mode commands.
‘D’ Display Command
76
Marathon Monitors Inc. Dew Point
The ‘D’ command is a multiple character command that displays a block of memory. The command format is D xxxx <Enter>. The xxxx is any memory location in four character hexadecimal format. The <Enter> is pressing the computer keyboard <Enter> key.
If no memory starting address is entered the Monitor assumes a starting location of 0000.
Each line of the display starts with the first memory address followed by 16 bytes of data stored in the following 16 memory locations. 16 lines are displays, showing 255 bytes of data.
The range of memory must be between 0000 and FFFF. The display will wrap to the beginning of the memory if it exceeds the limit of the FFFF location. Some of the zero page memory values will change when the Monitor mode is started. This command is useful for looking at data in upper memory that stays relatively static.
‘L’ Write FLASH to RAM Defaults
The ‘L’ command is the first command used to program the EEPROM with default values in
FLASH. The EEPROM is written for a RAM area that mirrors the structure of the
EEPROM. To initialize the EEPROM it is first necessary to write the default values from
FLASH into the RAM mirror.
This is a single character command that is sent to the instrument when the character is typed at the HyperTerminal display and the keyboard <Enter> key is pressed. The computer will display all the values that have been written into the RAM area. See the ‘K’ command for the next step in programming the EEPROM.
‘K’ Write RAM to EEPROM
The ‘K’ command is a single character command that copies the values in the RAM mirror into the EEPROM. The EEPROM is completely erased before any values are written. There is no display that is generated while this function is executed. It is necessary to wait about 5 seconds for the display prompt (>) to return before another command is issued.
‘J’ Display EEPROM Values
This is a single character command that displays all of the EEPROM values in the same format as the ‘D’ command.
‘S’ Status Display
This is a single character command that displays the status of the processor. This command is helpful when trying to determine what fault may have caused a reset. The display will show any fault codes and a thumb twiddler value. This value is an idle counter for the processor and should be greater than zero for normal operation.
‘W’ Write RAM with EEPROM or Data Values
The ‘W’ command is a multiple character command that writes a byte from EEPROM to
RAM memory if the RAM address is within the range of the EEPROM - RAM image.
Otherwise if the RAM address is an address is outside the EEPROM image address it will
77
Marathon Monitors Inc. Dew Point
write input data to a RAM address. The formate is W <addr> for the first condition and W
<addr> <data> for the second condition where both the address and data are four character hexadecimal values.
‘X’ Exit Command
This is a single character command the turns off the Monitor mode, resets the processor, and returns the processor to normal process mode. If the processor does not return to normal mode following this command, check the status for any fault conditions.
Viewing Status and Memory
The next figure shows the displays for the status command and the memory display command. The status command will show any faults or resets that have occurred in the instrument. The Thumb Twiddler number is a count of idle time for the processor. The reset number for this is 3000 (‘Z’ command). This number should never reach zero.
The ‘D’ command is followed by the start of the memory locations to be displayed. In this case the EEPROM memory block is being displayed starting at hexadecimal address 0800.
Figure 12 ‘S’ and ‘D’ Commands
Loading Default Values
The most common use of the Monitor Mode is to re-set or load the processor’s internal
EEPROM with default values and re-calculate the EEPROM checksum. This is done with a series of commands starting with the ‘L’ command.
78
Marathon Monitors Inc. Dew Point
The instrument holds default operational parameters in FLASH. This area of memory is mapped the same way the EEPROM memory is. The instrument also uses a pre-defined area in RAM to change and then copy data into EEPROM. This RAM area is also mapped the same as the EEPROM. It is necessary to copy the FLASH values to the RAM area first using the ‘L’ command.
At the > prompt, type in the character ‘L’ and press the Enter key. This command will tell the instrument to load the RAM area with default values from the FLASH memory.
A series of character lines will print down the screen followed by another prompt. At the prompt, type in the character ‘K’ and press Enter. This command will tell the instrument to load the EEPROM from the RAM image that has just been programmed.
The screen will advance one line and display the prompt. At the prompt, type in the character ‘X’ and press Enter. The ‘X’ command causes the instrument to exit monitor mode, resets the processor, and returns to operation mode. This sequence is shown in the following figure.
Figure 13 ‘L’ and ‘K’ Commands
At the prompt, type in the character ‘X’ and press Enter. The ‘X’ command causes the instrument to exit the Monitor Mode, reset, and return to operation mode. Check the instrument parameter settings and verify the input and output calibration settings.
What if an error occurs
79
Marathon Monitors Inc. Dew Point
If you receive check sum errors following the ‘L’ or ‘K’ commands, retry these commands.
If this does not resolve errors during the RAM or EPROM procedures then the instrument memory maybe damaged. The instrument should be returned to Marathon Monitors , Inc. for testing and possible repair.
80
Marathon Monitors Inc.
Technical Specification
Dew Point
Environmental ratings
Panel sealing:
Operating temperature:
Relative humidity:
Atmosphere:
Instruments are intended to be panel mounted. The rating of panel sealing is IP64.
0 to 55 o
C. Ensure the enclosure provides adequate ventilation.
5 to 95%, non-condensing.
The instrument is not suitable for use above 2000m or in explosive or corrosive atmospheres.
Equipment ratings
Supply voltage:
Supply frequency:
Power consumption:
Relay 2-pin (isolated):
100 to 240Vac -15%, +10%, or optionally:
48 to 62Hz.
15 Watts maximum.
Maximum: 264Vac, 2A resistive. Minimum: 12Vdc,
100mA.
Relay changeover (isolated): Maximum: 264Vac, 2A resistive. Minimum: 6Vdc, 1mA.
Over current protection: External over current protection devices are required that match the wiring of the installation. A minimum of 0.5mm
2
Relay outputs:
Low level I/O:
DC output (Isolated):
Fixed digital inputs: or 16awg wire is recommended. Use independent fuses for the instrument supply and each relay output. Instrument supply: 85 to 264Vac, 2A.
Triac outputs: 1A.
All analog input and output connections are intended for low level signals less than 24VDC.
0 to 20mA (650
Ω max), 0 to 10V (using a 500Ω dropping resistor).
Contact closure. (common to internal 5VDC source.)
DC or PV input:
Transmitter supply:
Digital Comms:
As main input plus 0-1.6Vdc, Impedance, >100M
Ω.
(isolated.)
30Vdc at 20mA. (isolated.)
EIA-485 half duplex. (isolated).
General
Thermocouple input:
Millivolt input :
Type B, K, R, and S accuracy after linearization +/- 1 deg F
0 to 2000 millivolts +/- 0.1 millivolt
Cold junction compensation: 0 to 60°C +/- 1 deg F
Calibration accuracy: The greater of +0.2% of reading, +1 LSD or +1 o
C.
Calculations:
Accuracy:
Power input to signal inputs
Power input to communications
Percent DEWPT 0 – 2.55% (no CO compensation)
Dewpoint -99 – 212 °F (no hydrogen compensation)
(Small oxygen concentrations can be measured by changing the exponent setting.)
+/- 1 of LSD of process value.
81
Marathon Monitors Inc.
Communications port:
Protocol:
Baud rates:
Parity:
Control Mode
RS-485 Half Duplex Only
10Pro, MMI block transfer, or Modbus RTU
1200, 2400, 4800, 9600, 19.2K
Even, odd, or None
Time Proportioning Single Contact Direct
Time Proportioning Single Contact Reverse
Time Proportioning Dual Contact Direct
Time Proportioning Dual Contact Reverse
Time Proportioning Complement Contact Direct
Time Proportioning Complement Contact Reverse
Dew Point
On / Off Reverse
On / Off Dual Direct
On / Off Dual Reverse
On / Off Complement Direct
On / Off Complement Reverse
Alarm Type (both Alarm 1 and 2)
High Limit Temp
Input Fault (mV or Thermocouple)
Time (start timer no conditions)
Start (guaranteed timer at set point)
Soak (guaranteed timer run in band)
Digital Event Input (isolated contact closure)
Manual/Auto
Local/Remote
Start
Hold Timer
Acknowledged End
Electrical safety (pending approval)
Standards: EN 61010, Installation category II, pollution degree 2.
Installation category II: Voltage transients on any mains power connected to the instrument must not exceed 2.0 kV.
82
Marathon Monitors Inc. Dew Point
Pollution degree 2: Conductive pollution must be excluded from the cabinet in which the instrument is mounted.
Environmental Conditions
Operating Temperature
Storage Temperature
Operating and Storage Humidity
-20 °C to 65 °C (-4 to 176 F)
-40 °C to 85 °C (-40 to 185 F)
85% max relative humidity, noncondensing, from –
20 to 65°C
Electromagnetic Compatibility (pending approval)
Immunity
Electromagnetic RF fields EN 61000-4-3
±8 kV air
Level 2:
±4 kV contact
Level 3: 10 V/m
MHz MHz
RF conducted interference EN 61000-4-6
±1 kV I/O
Level 3:
±2 kV power
Level 3: 10 V/rms
150 MHz
Power Freq Magnetic Fields EN 61000-4-8 30 A/m, x y z planes
Voltage Variations
61000-4-5
±1kV L-L, ±2kV L-PE
/ 0°,
EN 61000-4-11 70% of operating voltage
0.5 cycles/10ms
Emissions
RF Emissions
Conducted Emissions
CSIPR Class B
CISPR Class B
Harmonic Current Emissions EN 61000-3-2
Note: Specifications may change without notification.
83
Marathon Monitors Inc.
Versapro Memory Map
Dew Point
NOTE: Modbus refers to the hexadecimal address location. These parameters are formatted as unsigned 16 bit integers. Any real number such as temperature can be evaluated as a signed number, other parameters are bit mapped words that must be evaluated as single bits are bit groups.
BLOCK 0
HEX
00
01
03
05
06
07
DEC PARAMETER DESCRIPTION
0
1
Not used
RSETPT
3 TSETPT
04 4
5
6
7
PROC
TIME
ALARM1
ALARM2
READ/WRITE
READ ONLY
Remote setpoint sent to the instrument from the Host port. This number has to be scaled to the range of the displayed process value based on the decimal point and exponent settings of the instrument.
Range = -999 to 9999
Default = 0.000
For example: If the process = oxygen, display decimal point = 2, and exponent = 6, as remote setpoint of 1234 would be interpreted and displayed as 12.34 ppm.
Process setpoint set by the operator through the Setpoint menu. This number is scaled to the range of the displayed process value based on the decimal point and exponent settings of the instrument.
Range = -999 to 9999
Default = 0.000
Timer setpoint set via the Host port or locally.
Range = 0 to 999 minutes
Default = 0
This value is the calculated process value shown as an integer. The decimal point and exponent values are required to determine the actual scaled value.
Range = -999 to 9999.
For example: If the process = oxygen, display decimal point = 2, and exponent = 6, and
PROC = 1234, then the actual value and displayed as 12.34 ppm.
This is the remaining time on the timer as it counts down from Time Setpoint. Zero indicates timer has stopped.
Range = 0 to 999 minutes
Default = 0
READ/WRITE
READ ONLY
READ/WRITE
READ ONLY
READ ONLY
Alarm value is based on process value display decimal point and exponent. Both are required to determine the real alarm value.
READ/WRITE
Range = -999 to 9999.
Default = 0000
Alarm value is based on process value display decimal point and exponent. Both are required to determine the real alarm value.
READ/WRITE
84
Marathon Monitors Inc.
HEX
BLOCK 0
DEC PARAMETER DESCRIPTION
Range = -999 to 9999.
Default = 0000
BITS 0 – 3
0000 = OFF (DEFAULT)
0001 = DEVIATION BAND
0010 = BAND LOW
0011 = BAND HIGH
0100 = PERCENT OUT LOW
0101 = PERCENT OUT HIGH
0110 = FULL SCALE LOW
0111 = FULL SCALE HIGH
1000 = PROBE IMPEDANCE / VERIFY
1001 = SPARE
1010 = SPARE
1011 = SPARE
1100 = START
1101 = SOAK
1110 = TIMER
1111 = FAULT
BIT 4 ACTION CONTROL
0 = DIRECT
1 = REVERSE
BIT 5 NO LATCH = 0, LATCHED = 1
BIT 6 – 15 SPARE
BITS 0 – 3
0000 = OFF (DEFAULT)
0001 = DEVIATION BAND
0010 = BAND LOW
0011 = BAND HIGH
0100 = PERCENT OUT LOW
0101 = PERCENT OUT HIGH
0110 = FULL SCALE LOW
0111 = FULL SCALE HIGH
1000 = PROBE IMPEDANCE / VERIFY
1001 = SPARE
1010 = SPARE
1011 = SPARE
1100 = START
1101 = SOAK
1110 = TIMER
1111 = FAULT
BIT 4 ACTION CONTROL
0 = DIRECT
1 = REVERSE
Dew Point
READ/WRITE
READ/WRITE
READ/WRITE
85
Marathon Monitors Inc.
HEX
BLOCK 0
DEC PARAMETER DESCRIPTION
0A
0B
0C
0D
0E
0F
10
Dew Point
10
11
PB
RESET
BIT 5 NO LATCH = 0 LATCHED = 1
BIT 6 – 15 SPARE
Proportional Band – Based on display units
Range = 1 to 9999
Default = 20
Reset – Based on seconds
Range = OFF to 9999
Where 0020 is assumed to be 00.20 seconds
Default = OFF (reset value = 0)
12
13
14
15
16
RATE
CYCTIM
LDLN
HIPO
LOPO
Rate – Based on seconds
Range = OFF to 9999
Where 0020 is assumed to be 00.20 seconds
Default = OFF (rate value = 0)
Cycle Time – Based on seconds
Range = 0.2 to 9999
Where 0002 is assumed to be 0002 seconds
Default = 30
Load Line – Range = -100 to 100
Default = 0
Control Output High Limit
Range = -100 to 100 where HIPO is always greater than LOPO.
Default = 100
Control Output Low Limit
Range = -100 to 100 where LOPO is always less than HIPO.
Default = 0
Type
BITS 0 – 2 = CONTROL PARAMETER
000 = SPARE
001 = Temperature
010 = Millivolt INPUT B
011 = DEWPT
100 = Dewpoint
101 = Oxygen
110 = Redox
111 = Millivolt INPUT A
BIT 3 = NORMAL (0) FREEZE CONTROL
OUTPUT (1)
BITS 4 – 6 = MODE
000 = TIME PROPORTIONING
001 = TIME PROP W/ COMPLEMENT
010 = TIME PROP, DUAL
011 = SPARE
100 = ON/OFF
101 = ON/OFF W/ COMPLEMENT
110 = ON/OFF, DUAL
111 = VALVE POSITIONING W/ FEEDBACK
READ/WRITE
READ/WRITE
READ/WRITE
READ/WRITE
READ/WRITE
READ/WRITE
READ/WRITE
READ/WRITE
READ/WRITE
86
Marathon Monitors Inc.
HEX
BLOCK 0
DEC PARAMETER DESCRIPTION
12
13
14
15
18 CONFIG0
19 CTRLOUT
20 ALRMT1
21 ALRMT2
Dew Point
BIT 7 = DIRECT (0) OR REVERSE (1)
ACTING
BIT 8 = MANUAL (0) OR AUTO (1)
BIT 9 = SETPT LOCAL (0) OR SETPT
REMOTE (1)
BIT 10 = MONITOR (0), CONTROLLER (1)
BITS 11 = SENSOR BREAK OUTPUT 0 (0),
OUTPUT HOLD (1)
BITS 12 – 15 NOT USED
Input Configuration
BITS 0-3 TC Input TYPE
0000 = B (DEFAULT)
0001 = E
0010 = J
0011 = K
0100 = N
0101 = R
0110 = S
0111 = T
1000 = SPARE
1001 = SPARE
1010 = SPARE
1011 = SPARE
1100 = SPARE
1101 = SPARE
1110 = SPARE
1111 = SPARE
BIT 4 = SPARE
BIT 5 0 = NO CJ APPLIED, 1 = CJ APPLIED
BIT 6 0 = °F, 1 = °C
BIT 7 0 = 60HZ FILTER
BIT 8 – 11 Millivolt Input TYPE
0000 = LINEAR (DEFAULT)
All other bit combinations are spare
BITS 12 – 15 are spare
Control Output, unsigned integer
Actual control output where:
1000 = 100.0% and 64536 = -100.0%
ALARM 1 ON/OFF TIMES
RANGE = 0 – 255 SECONDS
DEFAULTS = 0
BIT 0-7 = ON TIME
BIT 8-15 = OFF TIME
ALARM 2 ON/OFF TIMES
RANGE = 0 – 255 SECONDS
DEFAULTS = 0
BIT 0-7 = ON TIME
BIT 8-15 = OFF TIME
READ/WRITE
READ/WRITE
READ ONLY
READ/WRITE
READ/WRITE
87
Marathon Monitors Inc.
HEX
BLOCK 0
DEC PARAMETER DESCRIPTION
16
17
22 FAULT
23 CJTRM AND
COMP
Dew Point
FAULT BIT MAP
BIT 0 = Temperature Input Open
BIT 1 = MV Input Open
BIT 2 = Range of input is low
BIT 3 = Range of input is high
BIT 4 = Timer End
BIT 5 = Probe Care Fault
BITS 6 – 7 = SPARE
BIT 8 = CPU Fault
BIT 9 = Min Idle counter = 0
BIT 10 = Keyboard failure, stuck key or a key was pressed during power up.
BIT 11 = Flash Erase Failed
BIT 12 = Flash Checksum Failed
BIT 13 = EEPROM Checksum Failed
BIT 14 = Flash/EEPROM Size Fault
BIT 15 = ADC Fault
LOW BYTE – CO / H COMPENSATION
RANGE 0 – 255
DEFAULT = 20 (% CO FOR DEWPT)
DEFAULT = 40 (% H2 FOR DEWPOINT)
HIGH BYTE – COLD JUNCTION TRIM
COLD JUNCTION TRIM (unsigned integer)
RANGE = –128 TO +127 WHERE
1 COUNT = 1 DEG (C or F) and –128 = 65408
READ/WRITE
READ ONLY
READ/WRITE
HEX
18
BLOCK 1
DEC PARAMETER DESCRIPTION
24 ASRC ANALOG OUT SOURCES
LOW BYTE, ANALOG OUTPUT 1
BITS 0 – 3
0000 = N/A
0001 = Temperature
0010 = Linear Input A
0011 = DEWPT value
0100 = Dewpoint value
0101 = Oxygen value
0110 = Redox value
0111 = Output Power
1000 = Control Output 1
1001 = Control Output 2
1010 = Linear Input B
1011 = Programmable*
*For Programmable, write required output value into DACV1, where DACV1 = 0 is minimum output and
DACV1 = 4096 is maximum output.
BITS 4 – 7 SPARE
READ/WRITE
READ/WRITE
88
Marathon Monitors Inc.
HEX
BLOCK 1
DEC PARAMETER DESCRIPTION
19
1A
1B
1C
1D
25 AOUTOF1
26 AOUTRN1
27 AOUTOF2
28 AOUTRN2
29 TEMPFIL
Dew Point
READ/WRITE
HIGH BYTE, ANALOG OUTPUT 2
BITS 8 – 12
0000 = N/A
0001 = Temperature
0010 = Linear Input A
0011 = DEWPT value
0100 = Dewpoint value
0101 = Oxygen value
0110 = Redox value
0111 = Output Power
1000 = Control Output 1
1001 = Control Output 2
1010 = Linear Input B
1011 = Programmable*
*For Reference Number and Programmable , write required output value into DACV2, where
DACV2 = 0 is minimum output and
DACV2 = 4096 is maximum output.
BITS 13 – 15 SPARE
Special case: If Analog Output 1 = CONTROL
OUTPUT 1 and Analog Output 2 = CONTROL
OUTPUT 2 and the Control Mode is dual, then
Analog Output 1 is 4-20ma for 0 to +100% PO and Analog Output 2 is 4-20ma for 0 to -100%
PO.
ANALOG OUTPUT 1 OFFSET
Minimum source value that correlates to minimum Analog Output of 4 mA. The source value is based on the selection in ASRC lower byte
ANALOG OUTPUT 1 RANGE
Maximum source value that correlates to maximum Analog Output of 20 mA. The source value is based on the selection in
ASRC lower byte where
ANALOG OUTPUT 2 OFFSET
Minimum source value that correlates to minimum Analog Output of 4 mA. The source value is based on the selection in ASRC upper byte
ANALOG OUTPUT 2 RANGE
Maximum source value that correlates to maximum Analog Output of 20 mA. The source value is based on the selection in
ASRC upper byte where
Temperature Input Filter in seconds
Range = 0 to 3276. The higher the number
READ/WRITE
READ/WRITE
READ/WRITE
READ/WRITE
READ/WRITE
89
Marathon Monitors Inc.
HEX
BLOCK 1
DEC PARAMETER DESCRIPTION
Dew Point
READ/WRITE
1E
1F
30
31
MVFIL
CONFIG2 the faster the reading update.
DEFAULT = 1000
Millivolt Input Filter in seconds
Range = 0 to 3276. The higher the number the faster the reading update.
DEFAULT = 1000
SETUP VALUES
BITS 0 - 4 OXYGEN EXPONENT
RANGE = 0 to 31, where 2 = % and 6 = ppm
DEFAULT = 2
BITS 5 - 6 DISPLAY DECIMAL PLACE where:
0 = no decimal point in display
1 = Display XXX.X
2 = Display XX.XX
3 = Display X.XXX
DEFAULT = 0
BITS 8 – 12 REDOX METAL NUMBER
RANGE = 0 – 14
DEFAULT = 0
BITS 13 – 15 SPARE
COLD JUNCTION 20 32 COLDJCT
Where 1 COUNT = 1°F (°C), RANGE = -99 TO
255°F (°C). Note this parameter is an unsigned integer.
21 33 TEMPERATURE
Where temperature is presented in degrees C or F, based on the C/F setting. Note this parameter is an unsigned integer of temperature -2721 = 62815
Range = max / min range of selected thermocouple.
MILLIVOLT
Where this value is scaled in 0.1 mV increments, i.e. 10001 = 1000.1.
Range = 0 to 2000 mV.
READ/WRITE
READ/WRITE
READ ONLY
READ ONLY
READ ONLY
READ/WRITE
SIOSET BITS 0-7
RANGE = 0 – 255
HIGH BYTE – SIO SETUP
BITS 8 – 9 PARITY SETTING
00 = Even Parity, 7 bits, 1 Stop bit
01 = No Parity, 8 bits, 1 Stop bit
10 = Odd Parity, 7 bits, 1 Stop bit
BITS 10 – 11 RESPONSE DELAY
0 = No delay applied to response
1 = 10ms delay applied to response
2 = 20ms delay applied to response
3 = 30ms delay applied to response
90
Marathon Monitors Inc.
HEX
BLOCK 1
DEC PARAMETER DESCRIPTION
24
25
26
27
28
29
2A
2B
2C
2D
Dew Point
READ/WRITE
36 PF
BITS 12 – 14 BAUD SELECT
000 = 76.8K
001 = 38.4K
010 = 19.2K (DEFAULT)
011 = 9600
100 = 4800
101 = 2400
110 = 1200
111 = 600
BIT 15 HOST FORMAT
0 = MMI (PROP)
1 = MODBUS (DEFAULT)
PROCESS FACTOR FOR DEWPT OR
DEWPOINT
READ/WRITE
37
38
DACV1
DACV2
RANGE = 0 to 4095
DEFAULT = 150
ANALOG OUTPUT 1
0 to 4095 is 4 to 20 mA In dual mode 4mA = -
100, 12mA = 0, 20mA = +100
ANALOG OUTPUT 2
0 to 4095 is 4 to 20 ma In dual mode 4mA = -
100, 12mA = 0, 20mA = +100
READ/WRITE
READ/WRITE
39 LOCK AND PLIM LOW BYTE – LOCK LEVEL
BITS 0 – 2
LOCK LEVEL; 0-3 0 is full lock, 3 is wide open
READ/WRITE
BITS 3 – 7 SPARE
HIGH BYTE – PROBE IMPEDANCE LIMIT
0 – 255 KOHMS, DEFAULT VALUE = 20K
40 PIMP READ ONLY
41 PRTM
LAST PROBE IMPEDANCE VALUE (KOHMS
X 10) i.e. 25 = 2.5 KOHMS
LAST PROBE RECOVERY TIME FROM
IMPEDANCE TEST (SECONDS)
RANGE = 0 to 255
Available for Redox, DEWPT, and Dewpoint.
READ ONLY
42 PBOMV
43
44
45
PBOTC
PBORT
PREMT
LAST MILLIVOLTS DURING PROBE BURN
OFF
RANGE = -99 TO 2048 i.e. 1018 = 1018 mV
Available for Redox, DEWPT, and Dewpoint.
LAST TEMPERATURE DURING PROBE
BURNOFF RANGE = 0 to 3000 i.e. 1715 = 1715° (F or C based on CONFIG0
BIT 6)
Available for Redox, DEWPT, and Dewpoint.
LAST PROBE BURNOFF RECOVERY TIME
RANGE = 0 – 255 SECONDS
Available for Redox, DEWPT, and Dewpoint.
REMAINING TIME TO NEXT PROBE TEST
RANGE = 0 – 999
READ ONLY
READ ONLY
READ ONLY
READ ONLY
91
Marathon Monitors Inc.
HEX
BLOCK 1
DEC PARAMETER DESCRIPTION
2E
2F
46 VGAS
47 PMC
Dew Point
Where 999 = 99.9 hours
MEASURED VERIFY GAS VALUE
Value = Actual measured oxygen (0.1%)
Verify function available for Oxygen.
PROBE MAINTENANCE CONTROL WORD
BITS 0 – 1
00 = START FULL MAINTENANCE
01 = START BURNOFF (VERIFY) ONLY
10 = START PROBE IMP ONLY
11 = NONE
BITS 2 – 6 UNDEFINED
BIT 7 = NORMAL (0), CANCEL (1)
BITS 8 – 15 = PROBE MAINTENANCE
SEQUENCE NUMBER
READ/WRITE
READ ONLY
READ/WRITE
HEX
30
31
32
33
34
35
DEC PARAMETER
48 PTINT
49 PTRECT
50 BOTM
51 BOREC
52 VSTD
53 VTOL
BLOCK 2
DESCRIPTION
PROBE TEST INTERVAL SETTING (HRS)
Operator input for interval setting
RANGE = 0 – 999
Where 999 = 99.9 hours
DEFAULT = 0 (Disable Probe test)
PROBE TEST RECOVERY TIME SETTING
(SECONDS)
RANGE = 0 to 999
DEFAULT = 30
BURN OFF TIME SETTING (SECONDS)
RANGE = 0 to 999
DEFAULT = 30
Burnoff function available for Redox, DEWPT, and Dewpoint.
BURN OFF RECOVERY TIME SETTING
(SECONDS)
RANGE = 0 to 999
DEFAULT = 30
Burnoff function available for Redox, DEWPT, and Dewpoint.
VERIFY TEST GAS STANDARD
This is the test standard value used to verify the probe.
RANGE = 0 to 999
Where the value 999 = 99.9% oxygen
DEFAULT = 30 (3.0%)
Verify function available for Oxygen.
VERIFY TEST TOLERANCE SETTING
This setting establishes the limit as VSTD
±
VTOL when comparing to the measured value
VGAS
Range = 0 to 999
Where 0005 = 00.5%
DEFAULT = 0005
READ/WRITE
READ/WRITE
READ/WRITE
READ/WRITE
READ/WRITE
READ/WRITE
READ/WRITE
92
Marathon Monitors Inc.
HEX
37
38
39
3A
3B
3C
3D
3E
3F
40
43
45
Dew Point
DEC PARAMETER
BLOCK 2
DESCRIPTION
55
56
57
TDEL1
TDEL2
TMIN
58 TC_ZERO
59 TC_SPAN
60 MV_ZERO
Verify function available for Oxygen.
VERIFICATION SAMPLE AVERAGING
SETTING (SECONDS)
RANGE = 0 to 999
DEFAULT = 2
Verify function available for Oxygen.
VERIFY DELAY 1 SETTING (SECONDS)
RANGE = 0 to 999
DEFAULT = 30
Verify function available for Oxygen.
VERIFY DELAY 2 SETTING (SECONDS)
RANGE = 0 to 999
DEFAULT = 30
Verify function available for Oxygen.
MINIMUM TEMPERATURE FOR PROBE
CARE TEST
This setting establishes the lowest process temperature allowed for a probe test to proceed.
RANGE = 500°F to 2000°F (260°C to 1090°C)
DEFAULT = 1400°F (760°C)
TC ZERO CALIBRATION NUMBER
TC SPAN CALIBRATION NUMBER
MV ZERO CALIBRATION NUMBER
61 MV_SPAN MV SPAN CALIBRATION NUMBER
62 DAC_OFFSET_1 DAC 1 OFFSET CALIBRATION
READ/WRITE
READ/WRITE
READ/WRITE
READ/WRITE
READ/WRITE
READ/WRITE
READ/WRITE
READ/WRITE
READ/WRITE
READ/WRITE
63 DAC_SPAN_1 DAC 1 SPAN CALIBRATION READ/WRITE
64 DAC_OFFSET_2 DAC2 OFFSET CALIBRATION READ/WRITE
DAC2 CALIBRATION READ/WRITE
READ/WRITE
67
69
ANUM
BNUM
OFFSET, Y INTERCEPT LINEAR
SCALING FOR INPUT A
LINEAR SPAN VALUE FOR INPUT A
OFFSET, Y INTERCEPT LINEAR
SCALING FOR INPUT B
LINEAR SPAN VALUE FOR INPUT B
READ/WRITE
READ/WRITE
READ/WRITE
TIME
AND EVNT
LOW BYTE – INPUT EVENT
CONFIGURATION
Bits 0 – 3
0000 = None
0001 = Auto Mode Selected
0010 = Remote Setpoint Selected
0011 = Acknowledge alarms
0100 = Timer Hold
0101 = Timer End
0110 = Timer Start
0111 = Start probe test
1000 = Process hold
Bits 4 – 7 not used.
HIGH BYTE - TIMER CONTROL
READ/WRITE
93
Marathon Monitors Inc.
HEX DEC PARAMETER
Dew Point
BLOCK 2
DESCRIPTION
BIT 0 – SPARE
BIT 1 – Timer stop(0), Timer start(1)
BIT 2 – Timer running(1)
BIT 3 – Timer End Active(1)
BIT 4 – Timer Hold Active(1)
BIT 5 – 6 SPARE
BIT 7 = Timer Disabled (0), Timer Enabled
(1)
READ/WRITE
94
advertisement
Key Features
- Single loop process controller
- Two channel 24 bit Sigma-Delta ADC
- Two 4-20mA outputs
- RS 485 serial communication
- Two Form A alarm contacts
- Internal relay for sensor burnoff
- Internal relay for sensor impedance testing
Frequently Answers and Questions
What are the required rear clearance for the VersaPro?
What is the power supply required for the VersaPro?
What type of sensors can be used with the VersaPro?
What are the available process functions for the VersaPro?
Related manuals
advertisement
Table of contents
- 6 SAFETY AND ENVIRONMENT INFORMATION
- 6 INSTALLATION SAFETY REQUIREMENTS
- 10 VERSAPRO FEATURES
- 11 INSTALLATION
- 12 PROCESS CONTROL OPTIONS
- 13 CONTROL MODES
- 17 ANALOG OUTPUT CHANNELS
- 18 ALARMS
- 20 Full Scale HI
- 20 Full Scale LO
- 20 Deviation Band
- 20 Deviation High
- 20 Deviation Low
- 20 Output High
- 20 Output Low
- 20 Fault
- 21 Probe
- 21 Start
- 23 SERIAL INTERFACE
- 24 FRONT PANEL OPERATION
- 37 Starting Probe Tests
- 37 Start Timer
- 37 Edit Timer
- 37 Monitor Mode
- 38 DIGITAL INPUT EVENT
- 40 TIMER FUNCTION
- 45 TIMER SIO OPERATIONS
- 48 PROBE IMPEDANCE TEST
- 50 PROBE BURNOFF
- 52 PROCEDURE TO TEST THE SENSOR
- 54 TUNING
- 57 SCALING ANALOG INPUTS
- 58 SCALING ANALOG OUTPUTS
- 59 CALIBRATION
- 60 Calibration of the Thermocouple Input
- 60 Calibration of the Cold Junction Temperature
- 62 Calibration of the Probe Millivolt Input
- 64 COMMUNICATIONS
- 64 RTU Framing
- 64 Address Field
- 65 Function Field
- 65 Data Field
- 65 Error Check Field (CRC)
- 69 ‘X’ Command
- 71 Block Commands
- 74 MMI Error Codes
- 75 PROCESS CALCULATION
- 76 TROUBLESHOOTING QUESTIONS
- 79 VERSAPRO MONITOR MODE
- 82 EEPROM
- 86 TECHNICAL SPECIFICATION
- 89 VERSAPRO MEMORY MAP