GOLD LP_AHUdescription
GOLD LP
TM
Air Handling Units with Built-in Control Equipment that offer Economical Operation.
GOLD LP
General
The GOLD LP is a complete air handling unit with directdriven supply air and extract air fans, supply air and extract air filters, rotary heat exchanger and built-in control
equipment.
Thanks to its low installation height, the GOLD LP can be
installed in false ceiling voids, horizontally in an attic space
or in other confined spaces. In order to save floor space,
the GOLD LP can also be mounted by a wall, as an alternative to a conventional unit.
Contents
Page
General
2
Technical Description of the Air Handling Units
4
Accessories
9
Specification
18
Sizing
22
Control System
25
1
GOLD LP
Gold LP – The new model that
really keeps a low profile
► Extremely thin
► Optimal heat recovery
► Very low noise level
► Sliding doors
As member of the new GOLD generation, we present a
completely new model: the GOLD LP. LP stands for ’Low
Profile’. The air handling unit is extremely thin in relation
to its performance and its energy efficiency. It can be
installed without having to occupy valuable floor space.
Typical installation possibilities are horizontal installation
inside a suspended ceiling or vertical installation inside a
closet. The unit has space-saving sliding doors which simplify service and maintenance.
The patent-pending Super Silence innovation distributes the
airflow, which means essentially less noise in the most sensitive
frequency bands. The GOLD LP can therefore be installed inside
suspended ceilings or closets without disturbing noise.
2
We reserve the right to alter specifications.
The RECOnomic rotary heat exchanger is tilted, which provides
a large face surface and thus excellent heat recovery with small
pressure losses.
20101005
www.swegon.com
GOLD LP
Installation Examples
Inside suspended ceilings
In a corridor
In a closet
GOLD LP
Visible on the ceiling
In the attic
We reserve the right to alter specifications.
20101005
www.swegon.com
3
GOLD LP
Technical Description of the Air Handling Units
General
The GOLD LP is a complete air handling unit with directdriven supply air and extract air fans, supply air and extract air filters, rotary heat exchanger and built-in control
equipment.
The concept of the GOLD LP is patent pending.
Built-in control equipment
The GOLD LP has built-in control equipment that can be
operated from a hand-held micro terminal.
The electrical and control system is completely integrated into the air handling unit. The microprocessor-based
equipment controls and regulates temperatures, airflows
and other functions. A large number of functions are built
into the system and are simple to activate.
GOLD LP
Range of Application
The GOLD LP is designed for comfort ventilation and can
be used in offices, schools, day nurseries, public premises,
shops and residential buildings.
Thanks to its low installation height, the GOLD LP can
be installed in suspended ceilings (mounting brackets are
supplied with the unit), horizontally in an attic or in other
confined spaces. In order to save floor space, the GOLD
LP can also be mounted upright by a wall, as an alternative to a conventional unit (a base is available as an accessory).
Certification
Swegon AB has a certified Quality Assurance System that
conforms to ISO 9001 Standard and a certified Environmental Management System to ISO 14001.
The GOLD LP air handling system is also certificated by
Eurovent, No. AHU-06-06-319.
The unit must be installed indoors.
The GOLD LP units generate low noise levels. This makes
it possible to install the units near utility areas and workplaces.
N° 06.06.319
Range: GOLD
www.eurovent-certification.com
www.certiflash.com
The air handling units have an attractive and modest
design making them ideal for installation where they can
be seen in the premises.
The GOLD LP is designed and tested for temperatures,
in the surroundings and the air stream, from -40°C to
+40°C.
Environmental Product Declaration
Swegon AB has a certified environmental management
system that conforms to ISO 14001 Standard and is registered on the REPA Register, no. 5560778465.
Simple installation
A standard installation is simple. Over and above installing
the air handling unit, duct system and air diffusers and
registers, all that remains to be done is to connect the
unit to a power supply and locate a temperature sensor
inside the supply air duct.
Ready-to-use wiring terminals and control functions are
provided for accessories such as dampers, air heaters and
air coolers.
4
We reserve the right to alter specifications.
The GOLD LP is made of the following materials:
Type of Material
Percentage of total weight
Sheet steel
Approx. 80%
Aluminium
Approx. 9.5%
Polymeric materials
Approx. 0.5%
Mineral wool insulation
Approx. 2%
Filters
Approx. 1%
Electronic components, motors
Approx. 7%
20101005
www.swegon.com
GOLD LP
Technical Description of the Air Handling Units
Mechanical Design
Casing
The visible sides of the air handling unit consist of galvanized sheet steel that has been prepainted in a shade
of white NCS S 0502-G. The exterior back side and the
inside consist of aluminium-zinc plated sheet steel.
The exterior surfaces of the air handling unit conform to
Environmental Class C4. The casing, inclusive inspection
panels, has 30 mm thick mineral wool insulation.
There are two slide rails on the inspection side of the unit.
The inspection panel opens down into a slide rail when
it is opened. The inspection panel can then be pulled to
the side like a sliding door. If desired, the slide rails can be
dismantled.
The inspection panels can be opened and closed using a
special key. Lockable handles are available as accessories.
GOLD LP
The unit is equipped with extra inspection panel on the
long sides. Together with inspection panels on the inspection side, these facilitate filter change from two sides.
Slide rail
GOLD LP
Extra inspection panel
Fans
The fans are direct-driven plenum fans of the following
types: GOLD Wing (size 05) or Wing+ (size 08). They are
equipped with EC motors that provide high efficiency
across the entire operating range. Flow measurement and
control are standard.
The fans are effectively vibration-isolated from the casing.
They can be dismantled and removed from the air handling unit if required.
Direct-driven fans with EC motors.
Heat exchanger
The rotary heat exchanger is of RECOnomic type, patented by Swegon. The heat exchanger is driven by a step
motor that controls the rotor speed with high precision
and controls the heat recovery efficiency as well.
The rotary heat exchanger is tilted in order to save on installation height.
The rotation monitor and control system are standard
equipment.
The heat exchanger is also available in a hygroscopically
treated design.
The heat exchanger is equipped with a purging sector.
RECOnomic rotary heat exchanger.
Filters
The air handling unit has Class F7 bag filters for both the
supply air and the extract air. A filter monitoring function
is integrated into the control system.
Class F7 bag filter.
We reserve the right to alter specifications.
20101005
www.swegon.com
5
GOLD LP
Technical Description of the Air Handling Units
Electrical and Control System
General
The IQnomic control system is completely integrated into
the air handling unit. The microprocessor-based equipment controls and regulates temperatures, airflows and
other functions. A large number of functions are built into
the system and are simple to activate. See the special section entitled “Description of the Control System”.
The air handling unit can be automatically controlled in
several ways via the integrated time switch, however it
can also be demand-controlled via a CO2 sensor or presence detector. Manual control is also possible.
IQnomic control unit
A large number of functions and settings can be also activated/entered via communication.
Control Inaccuracy:
Temperature ± 1oC.
Airflow ± 5%.
Power Efficiency
The design and performance of the air handling unit are
optimized for achieving excellent power efficiency.
Standards
The air handling unit conforms to the provisions in the
SS-EN 60204-1 Standard.
Interference Level
The air handling units conform to the provisions of the
EMC Directive and are tested according to EN 61000-62 and EN 61000-6-3 Standards. (radiation in residential
buildings, office buildings, shops and similar indoor environments and for immunity in industrial facilities).
Use of an earth fault circuit breaker
The earth fault circuit breaker, if required, should only
serve the air handling unit and must be of a type designed for use with the controller of the EC motor.
Communication
Communication via TCP/IP and EIA 485 is included as
standard. The TBLZ Communication unit is used for communication via LON and Trend.
The GOLD also has built-in web communication. Communication with the GOLD can be established via an ordinary
web browser (such as Internet Explorer) and your own
network, i.e. without any main control systems whatever.
In addition to the above, the GOLD units have inputs and
outputs for external functions such as the forwarding of
alarms or overtime operation that can be keyed in.
Typical flow diagram for web communication.
6
We reserve the right to alter specifications.
20101005
www.swegon.com
GOLD LP
Technical Description of the Air Handling Units
Electrical and Control System
Flow Diagrams
When you calculate performance data in the ProUnit AHU
selection program, the program furnishes a project-specific flow diagram and a description of the unit’s functions.
The individual components are specified below.
GOLD LP
By making a simple adjustment in the control equipment, you can change the
directions of airflow through the GOLD LP at the building site (small arrows).
The relevant components automatically change function as well.
Outdoor air
Supply air
Extract air
Exhaust air
Components
V1
Outdoor air filter.
V2
Extract air filter.
BT3
Outdoor air temperature sensor. Indicates for control
of functions that affect temperature.
BT2
Extract air temperature sensor. Indicates for control
of functions that affect temperature.
E1
Variable speed-controlled RECOnomic rotary heat
exchanger with air purging operation.
G2
Direct-driven extract air fan with EC motor.
T2
M3
Step motor for variable speed control of the rotary
heat exchanger.
Motor controller for variable control of the extract
air fan.
BF2
BG1
Rotation monitor sensor for monitoring the heat
exchanger’s rotation.
Extract air flow pressure sensor. Indicates for control
of the extract air fan’s speed and monitors the filter
status.
G1
Direct-driven supply air fan with EC motor.
K1
T1
Motor controller for variable control of the supply air
fan.
IQnomic control unit containing control circuit card
and other electrical equipment for controlling internal and external functions.
BF1
Flow pressure sensor, supply air. Indicates for control
of the supply air fan’s speed and monitors the filter
status.
P1
Hand-held micro terminal for setting and reading airflows, temperatures, control functions, in-operation
periods, etc. as well as alarms.
BT1
Supply air temperature sensor. To be positioned in
the ductwork. Indicates for control of functions that
affect temperature.
We reserve the right to alter specifications.
20101005
www.swegon.com
7
GOLD LP
Technical Description of the Air Handling Units
Electrical and Control System
Hand-held micro terminal
All the settings and readings can be entered/viewed in
plain text via a user-friendly, hand-held micro terminal.
The hand-held micro terminal has keys for entering the
various commands. The display screen and the keys have
background lighting. A red indicating LED flashes in the
event of an alarm. The preset values are stored and will
not be affected in the event of a power failure.
The control panel contains logically composed menus arranged in various levels as follows:
• Main menu. Intended for reading the operating status
and for entering temporary changes in how the unit
operates.
• User level. Intended for entering settings and viewing
readings for the functions selected.
• Installation level. An access code is required (obtainable
in the maintenance instructions). Selection of functions
and the setting of limit values.
• Service level. An access code is required (disclosed on
completion of special training course).
MAIN MENU
OPERATION
SETTINGS
Hand-held micro terminal
AUTO OPERATION
MANUAL LOW SPEED
MANUAL HIGH SPEED
STOP
USER LEVEL
INSTALLATION LEVEL
SERVICE LEVEL
Principle structure of the menu system.
8
We reserve the right to alter specifications.
20101005
www.swegon.com
GOLD LP
Accessories
Duct accessories, uninsulated, circular connection
General
The duct accessories must be positioned in the ductwork
outside the GOLD unit. The air handling unit fans make it
possible to place a duct accessory, via a TBRB end connection adapter, directly against the air handling unit without
pressure losses or non-uniform air distribution.
The duct accessories for the GOLD LP are fitted with
rubber seal rings.
Other particulars for sizing can be obtained by using the
ProUnit air handling unit selection program.
TBRB End connection adapter
End connection adapter between rectangular inlet/outlet
on the air handling unit and circular duct or duct accessory with circular connections.
Installation
To be secured to the unit with screws (predrilled holes).
Install the duct accessory or duct.
GOLD LP
Technical data
Aluminum-zinc-plated sheet steel outer skin. Galvanized
sheet steel inner skin. 30 mm thick intervening insulation.
B
I
J
K
D
H
K
32
36
TBRB
05
08
B
526
605
H
458
533
D
400
400
I
242
302
J
284
302
K
229
266
kg
4
5
TBSA Circular damper
TBSA 000-040, is compatible with GOLD LP size 08
The TBSA circular damper with damper actuator can be
used as a shut-off damper or boosting damper. Shut-off
dampers are normally used if the air handling unit is idle
during some period, for example at night, or if an air
heater for hot water without anti-frost bursting protection is used.
The TBSA circular damper without damper actuator, with
hand lever, is used for achieving the correct air leakage
direction across the heat exchanger. This prevents the
extract air from being carried over to the supply air. To be
mounted inside the extract air duct.
Technical Data
Complete without or with damper actuator for 230 V.
The actuator can be selected with spring return or on/off
actuation. Galvanized sheet steel. Tightness Class 3 to EN
1751 Standard.
TBSA
1-000-040-1-0
1-000-040-1-1/2
A
Ø 400
Ø 400
B
210
210
kg
6
7
Installation
Can be mounted in a horizontal or vertical duct. Wire the
control and power supply cables to the appropriate wiring
terminal on the air handling unit.
We reserve the right to alter specifications.
20101005
www.swegon.com
9
GOLD LP
Accessories
Duct accessories, uninsulated, circular connection
TBDA Unit sound attenuator
The TBDA unit sound attenuator is a circular sound attenuator designed for installation in a duct.
Technical Data
Galvanized sheet steel.
TBDA 000-040, matches GOLD LP sizes 05 and 08
Sound attenuating material consisting of 100 mm thick
long-fibred glass wool slabs that offer excellent sound
attenuation, especially in the mid-frequencies. Glass wool
covered with a layer of EUROLON that withstands substantially higher air velocities and mechanical strain than
staple fibre. Sound attenuating material covered with
perforated sheet steel outside the EUROLON layer.
H
Installation
Provision for inspection and cleaning must be guaranteed.
B
L
TBDA
1-000-040
B
Ø 400
H
Ø 600
L
1200
kg
29.5
TBDB Unit sound attenuator
The TBDB unit sound attenuator is a rectangular sound
attenuator designed for installation in a run of ducts with
circular connections.
TBDB 000-040, matches GOLD LP sizes 05 and 08
Technical Data
Galvanized sheet steel. Low installation height. The fibre
migration-proof Fartex inner lining has excellent density,
hence no perforated sheet steel lining is needed between
the insulation and the sound attenuating air passage.
Installation
Provision for inspection and cleaning must be guaranteed.
H
B
L
TBDB
1-000-040
10
We reserve the right to alter specifications.
20101005
B
Ø 400
H
458
L
1000
kg
27.5
www.swegon.com
GOLD LP
Accessories
Duct accessories, uninsulated, circular connection
TBLA Air heater, for hot water
The TBLA air heater is used, if required, for reheating the
supply air with hot water as the heating medium.
Technical Data
Uninsulated casing made of galvanized sheet steel.
Finned-tube heat exchanger fabricated of copper tubes
and profiled aluminium fins. The headers and the pipework to the water connections are made of copper.
The pipe connections are made of brass and have male
threads.
Accessories
Circulation pump
Circulation pump used for ensuring the frost guard function for the air heater. Supplied with T coupling, non-return valve and commissioning valve. The automatic pump
control system is integrated into the control equipment of
the GOLD unit.
Installation
The TBLA air heater can be installed for horizontal or vertical airflow. Provision for inspection and cleaning must be
guaranteed.
Conn.
R male
threads.
G
A
H
TBLA 000-040, matches GOLD LP sizes 05 and 08
60
300
60
F
B
TBLA
A
B
5-000-040-2-1 Ø 400 590
5-000-040-2-2 Ø 400 590
F
255
255
G
250
250
H
500
500
R
kg*
DN20 22
DN20 18
* Excluding water.
The installation of accessories (if required), fitting of pipe
connections and filling the circuit with liquid must be
done at the building site.
Basic Installation Diagram
2(3)-way valve
Anti-frost protection sensor
in T piece
T-piece
Commissioning valve
Shut-off
valve
Heating water
Non-return valve
Secondary pump
We reserve the right to alter specifications.
Shut-off
valve
20101005
www.swegon.com
11
11
GOLD LP
Valve set/Set of electrical connection components
The TBVL valve set with 2(3)-way valve, actuator, antifrost protection sensor and connection cable with quickfit connector can be ordered. If you install a valve of your
own, you can instead select a set of electrical connection components. This set contains a connection cable
with quick-fit connector, resistor and insertion or strap-on
sensor.
GOLD LP
Accessories
Duct accessories, uninsulated, circular connection
TBLE Electric Air Heater
The TBLE electric air heater is used reheating the supply
air
Technical Data
Uninsulated casing made of galvanized sheet steel and
heating elements made of stainless material.
The TBLE air heater is available in several capacity variants.
The integrated thyristor is controlled via signals from the
GOLD air handling unit. The TBLE has two series-coupled
overheat protection devices The electrical equipment conforms to the provisions of Degree of Protection IP43.
Installation
The TBLE air heater can be installed for horizontal or vertical airflow.
TBLE 000-040, matches GOLD LP sizes 05 and 08
278
71
Provision for inspection and cleaning must be guaranteed.
The end panel on the connection side can be dismantled
for inspection and wiring electrical connections.
The distance from or to a duct bend, damper, filter or the
like should be at least the distance that is equivalent to
double the diameter of the duct. Otherwise the airflow
through the electric air heater is likely to be non-uniform,
involving risk of overheating and the overheat protection
device will then trip.
42
42
375
TBLE
4-000-040-06-1
4-000-040-12-1
4-000-040-06-2
A
Ø 400
Ø 400
Ø 400
kg
9
12
9
19
H
A
200
Power must be supplied directly from the electrical distribution box. Connect the control signal cable with quick-fit
connector to the air handling unit’s control unit.
A
19
B
TBLE
4-000-040-20-1
4-000-040-27-1
4-000-040-36-1
4-000-040-47-1
4-000-040-12-2
4-000-040-20-2
4-000-040-27-2
4-000-040-36-2
4-000-040-47-2
12
We reserve the right to alter specifications.
20101005
19
A
Ø 400
Ø 400
Ø 400
Ø 400
Ø 400
Ø 400
Ø 400
Ø 400
Ø 400
65...70
B
400
400
400
400
400
400
400
400
400
L
H
400
400
400
400
400
400
400
400
400
L
500
600
700
700
500
700
700
800
800
65...70
kg
29
35
40
47
25
33
38
48
56
www.swegon.com
GOLD LP
Accessories
Duct accessories, uninsulated, circular connection
TBKA Air Cooler, for chilled water
TBKC Air cooler, direct expansion
The TBKA/TBKC air coolers are used for cooling the
supply air with chilled water or evaporative refrigerant as
the cooling medium.
The TBKA/TBKC air coolers are available in several capacity variants that cover existing needs of the GOLD LP.
Technical Data
Uninsulated casing made of galvanized sheet steel.
TBKA, chilled water
Accessories
TBKA 000-040, matches GOLD LP sizes 05 and 08
F
The regular outputs of the air handling unit are used for
cooling with direct expansion in one step. If this is not
sufficient then the IQnomic Plus should be used.
Valve set
The TBVA Valve set consisting of a 2(3)-way valve including actuator can be ordered.
Installation
The TBKA/TBKC air cooler must be installed for horizontal
airflow.
øD
Conn. R male
threads.
A
Controls
The IQnomic Plus, an extra module for the air handling
unit control system, is required for controlling waterborne
cooling.
60
500
60
E
B
Drain pipe conn. DN 15 male threads
TBKA
4-000-040-1
4-000-040-2
4-000-040-4
*
A
475
475
475
B
590
590
590
D
400
400
400
E
255
255
255
F
238
238
238
R
DN20
DN25
DN32
kg*
27
29
35
Excl. cooling medium
Provision for inspection and cleaning must be guaranteed.
TBKC (direct expansion)
TBKC 000-040, matches GOLD LP sizes 05 and 08
Outer diameter, di male
threads
F
øD
A
The installation of accessories (if required), fitting of pipe
connections and filling the circuit with liquid must be
done at the building site.
60
500
60
E
Outer diameter, du male
threads
B
Drain pipe conn. DN 15 male threads
TBKC
A
B
D
E
F
di
3-000-040-1-1 455 590 400 255 228 12
3-000-040-2-1 475 590 400 255 238 18
du
22
22
kg*
23
25
* Excl. cooling medium
We reserve the right to alter specifications.
20101005
www.swegon.com
13
GOLD LP
The TBKA/TBKC air coolers consist of copper tubes and
profiled aluminium fins. The TBKA has water connections
made of copper/brass, with male connection threads. The
TBKC has water connections made of copper designed for
soldered joints.
GOLD LP
Accessories
Duct accessories, uninsulated, rectangular connection
General
Uninsulated duct accessories with rectangular connection
can be located directly against the air handling unit without pressure losses or non-uniform air distribution. Use
the TBRB end connection adapter for further connection
to circular ducts/duct accessories.
Other particulars for sizing can be obtained by using the
ProUnit air handling unit selection program.
Duct accessories, uninsulated
TBSB rectangular double damper
The TBSB rectangular double damper with damper actuator can be used as a shut-off damper or boosting damper.
Shut-off dampers are normally used if the air handling
unit is idle during some period, for example at night, or
if an air heater for hot water without anti-frost bursting
protection is used.
TBSB 045-040, matches GOLD LP size 05
TBSB 053-047, matches GOLD LP size 08
The TBSB is used when interconnected dampers are
desirable for both the inlet and outlet on the same end
connection of the air handling unit.
Technical Data
Complete with damper actuator for 230 V. The actuator
can be selected with spring return or on/off actuation.
Galvanized sheet steel. Tightness class 3 to EN 1751.
Installation
To be mounted directly against the air handling unit. Wire
the control and power supply cables to the appropriate
wiring terminal on the air handling unit.
14
We reserve the right to alter specifications.
A H
C
C
L
B
TBSB
1-045-040
1-053-047
20101005
A
400
475
B
1032
1190
C
454
533
H
450
527
L
200
200
kg
25
32
www.swegon.com
GOLD LP
Accessories
Roof Hoods
General
The roof ducts are made of galvanized sheet steel. Lined
inside with 50 mm thick insulation to Fire-resistance Class
EI30, with a surface covering of type-approved synthetic
woven fabric. Two angle brackets for connection to the
relevant roof slope are included.
The hoods are made of aluminium-zinc plated sheet steel
covered with a Plastisol (black) surface coating that conforms to Environmental Class C4.
The hoods have round duct connection, fitted with
rubber seal rings for spiral ducts.
TBHA Outdoor Air Hood
TBHB Exhaust Air Hood
Designed for the discharge of exhaust air. The hood can
be opened on hinges and is equipped with air deflectors
that effectively direct the exhaust air upward and give
the air high discharge velocity. To achieve low pressure
drop, the air deflectors are rounded off on both their long
sides. The hoods are equipped with effective provision for
drainage.
TBHC Dual-purpose Hood
The TBHC is a combination of TBHA outdoor air hood and
TBHB exhaust air hood
TBHA Outdoor air hood and TBHB Exhaust air hood
TBHC Dual-purpose
Hood
TBHC Dual-purpose Hood
A
C
C
A
E
620
2 angle brackets
(unmounted)
are supplied
with the hood.
H
D
B
For the GOLD LP
05, 08
800
D
B
A
600
B
500
2 angle brackets
(unmounted)
are supplied
with the hood.
C
950
D
B
D
E
Ø400 620
We reserve the right to alter specifications.
H
800
kg
44
For the GOLD LP A
05, 08
1200
20101005
G
B
1100
C
950
D
G
Ø400 500
www.swegon.com
kg
100
15
GOLD LP
TBHB Exhaust Air
Hood
TBHA Outdoor
Air Hood
Designed for the intake of outdoor air. The design of the
hood makes it difficult for snow and rain drops to enter
the hood with the incoming air. The hood is hinged and
has air intake louvres on both sides.
GOLD LP
Accessories
TBHE Exterior wall hood
Designed for the admission of outdoor air and the discharge of exhaust air.
The exhaust air is horizontally discharged through a circular wire mesh grille at the front of the hood. Outdoor air
is admitted through a wire mesh grille at the bottom of
the hood.
This design effectively prevents short-circuit flow between
the outdoor air/exhaust air.
The TBHE exterior wall hoods are made of aluminium-zinc
plated sheet steel covered with a Plastisol (light grey) surface coating that conforms to Environmental Class C4.
Installation
The 400 mm dia. connections are fitted with rubber seal
rings. When you cut an opening in a wall, bear in mind
that the ducts must be insulated with at least 30 mm
thick insulation and with damp-proof outer layer material.
The front panel of the external wall hood can be lifted off
(after removing its screws), reversed and resecured. This
makes the duct connections for exhaust air and outdoor
air optional.
L
c/c
H
Exhaust air
< Can be reversed. >
D
Outdoor air
D
B
For the GOLD LP B
05, 08
250
c/c
500
D
Ø400
H
580
L
1150
kg
15
Mechanical Equipment
L
TBLZ Stand
Specially designed floor stand for the GOLD LP For locating the air handling unit by a wall.
The stand is made of galvanized sheet steel profiled sections. The stand is supplied in assembly kit form.
500
For the GOLD LP
05
08
L
1368
1354
kg
14
16
TBLZ Lockable door handle
For use where more stringent demands on security are
made as opposed to locking with a standard special key.
Supplied in sets of 4 door handles with key for replacement of existing locks at the building site.
16
We reserve the right to alter specifications.
20101005
www.swegon.com
GOLD LP
Accessories
Electrical and control equipment
Connection Cable
Presence detector
0.25-15 m for hand-held micro terminal, pressure transducer
and IQnomic Plus.
For controlling high and low speed operation instead of the
unit’s built-in timer. As soon as the sensor registers the presence
of an occupant in the room, the air handling unit is controlled
to the high speed mode; when there are no occupants, to the
low speed mode.
To be connected via appropriate terminals on the control unit.
Pressure sensor
For use in conjunction with the VAV pressure control function,
when constant pressure must be kept in the ductwork. Also for
use in conjunction with the heat exchanger defrosting function,
when the pressure across the heat exchanger is checked and
the condition of the filters is monitored. The connection cable is
included. A 1–15 m long cable can be selected.
To be connected via appropriate terminals on the control unit.
Air quality sensor
VOC sensor
5-8 m long for air heater for hot water, electric air heater and
supply air temperature sensor, 8 m long for hand-held micro
terminal.
Extension kit for hand-held micro terminal
For lengthening the cable, 6-50 m
Extra hand-held micro terminal
Including holder and 3 m long cable
Strap-on sensor
Temperature sensor for mounting against the surface where
readings are to be taken.
MMC circuit card
For program transmissions and logging
IQnomic Plus
The extra functions for which the inputs and outputs are not
included as standard in the unit’s control unit, for example external monitoring and cooling.
Humidity sensor, IQnomic Plus
For variable control of the airflow. The VOC sensor senses the
content of emissions/impurities in the room and the airflow is
regulated within preset limits.
Temperature sensor, for the IQnomic Plus module for dehumidification and dew point control.
To be mounted inside the air handling unit. To be connected to
appropriate terminals on the control unit.
Room sensor
TBLZ Communication unit
For communication via LON FTT-10 – Lon Works and Trend
(communication via TCP/IP and EIA 485 as well as via internal
webserver is standard in the COMPACT).
For use when the unit’s built-in extract air temperature sensor
does not provide representative values.
Designed for wall-mounting and is available for Enclosure Class
IP 20. To be connected to appropriate terminals on the control
unit.
To be connected to the communication port of the control unit.
Power can be supplied from appropriate terminals on the control unit.
Timer, Mechanical
Control equipment cubicle for controlling the primary water
circuit for cooling and/or heating. For climate beams, perimeter
climate systems, etc.
For time-limited overtime operation when the unit’s built-in time
switch has controlled the unit to operate in the low speed mode
or to stop.. For strap-on mounting.
To be connected to appropriate terminals on the control unit.
Timer, electronic
For time-limited overtime operation when the unit’s built-in time
switch has controlled the unit to operate in the low speed mode
or to stop. For strap-on mounting.
To be connected to appropriate terminals on the control unit.
Separate power supply
Pushbutton
For overtime operation when the unit’s built-in time switch has
controlled the unit to operate in the low speed mode or to stop.
For strap-on mounting. Can be selected with or without indication.
To be connected to appropriate terminals on the control unit.
We reserve the right to alter specifications.
All Year Comfort
Fire and smoke protection
The fire and smoke protection function consists of three separate units:
• TBLZ Equipment cubicle
• TBLZ Smoke detector
• ELQZ* Damper actuator.
The cubicle contains the control unit and connections. The
smoke detector stops the air handling unit and controls the
damper actuators to close the dampers. An alarm is presented
in the hand-held micro terminal of the COMPACT air handling
unit.
*) Applicable to installations in Sweden: The ELQZ damper actuator can be used where type-approved solutions are not required. If a type-approved solution is required, the damper and
actuator must be supplied as a unit in a type-approved version.
In these cases, a pump-exercising mode is also required.
20101005
www.swegon.com
17
GOLD LP
For controlling high and low speed operation instead of the
unit’s built-in time switch. The air quality sensor registers the
carbon dioxide content in the room air and the control unit regulates the airflow required within preset limits.
Available installation in a duct or in a room. To be connected to
appropriate terminals on the control unit.
Extension Cable
GOLD LP
Specification
Air handling units
Duct accessories, uninsulated casing
GOLD LP Air handling unit
GOLD-aa-D-LP-c
Size 08
05
= 08
Heat exchanger
standard = 1
Hygroscopic = 2
S ize = 05
uct connection size:
D
Ø 400
Set of filters, bag filters, GOLD LP located in false ceiling or horizontal
TBFZ-1-12-aa-7
For one airflow direction, filter class F7
05
08
= 05
= 08
Set of filters, bag filters, GOLD LP located by a wall
For one airflow direction, filter class F7
Size 05
08
= 05
= 08
= 000-040
Damper motor:
Without damper motor, with handle
With spring return
On/Off
= 0
=1
=2
Double damper, rectangularTBSB-1-aaa-aaa-1-b
Tightness class 3, uninsulated damper blades
TBFZ-1-13-aa-7
= 05
= 08
uct connection size:
D
454 x 400
533 x 475
Damper motor:
With spring return
On/Off
Hoods
Outdoor air hood
Including roof duct
TBHA-1-aaa
Extract air hood Including roof duct
TBHB-1-aaa
Dual-purpose hood
Including roof duct
TBHC-1-aaa
AHU sound attenuator
uct connection size:
D
Ø 400
L ength:
1,200 mm
05/08= 040
uct connection size:
D
Ø 400
L ength:
1,000 mm
= 045-040
= 053-047
=1
=2
TBDA-1-aaa-aaa-bbb
= 000-040
For sound attenuator
Ø 400
= 120
AHU sound attenuator
Exterior wall hood
TBHE-1-aaa
Combination hood for outdoor air/exhaust air
For unit size 05
08
TBRB-2-aa
Damper, circularTBSA-1-aaa-aaa-1-b
Tightness class 3, uninsulated damper blades
Replacement Material
Size End connection adapter
TBDB-1-aaa-aaa-bbb
= 000-040
For sound attenuator
Ø 400
= 100
Mechanical Equipment
Stanv GOLD LP TBLZ-1-aa-06
Assembly kit, floor stand, for installation by a wall
S ize 05
08
= 05
= 08
Lockable door handle
Set of four door handles with key.
18
We reserve the right to alter specifications.
TBLZ-1-63
20101005
www.swegon.com
GOLD LP
Specification
Air heater for hot water:
uct connection size:
D
Ø 400
TBLA-5-aaa-aaa-2-b
Duct connection size:
Ø 400
= 000-040
Capacity variant:
1 2 =1
=2
Valve set, heating
TBVL-2-aaa
2(3)-way valve incl. actuator, cable and insertion sensor
= 002
= 004
= 006
= 010
= 016
= 025
= 040
= 063
Set of electrical connections:
For air heater for hot water
Cable, resistor and insertion sensor
Cable, resistor and strap on sensor
TBLZ-1-27-a
= 1
=2
Circulation pump
TBPA-3-aaa
Set of pump components for the secondary side
for air heater without anti-frost protection, including non-return valve and commissioning valve.
Capacity at max 25 kPa
pressure drop in air heater and pipework:
< 0.09 l/s =009
0.091-0.17 l/s
=017
0.171-0.35 l/s
=035
0.351-0.6 l/s
=060
Electric air heater
uct connection size:
D
Ø 400
Capacity variant:
6 kW
12 kW
20 kW
27 kW
36 kW
47.5 kW
TBKA-4-aaa-aaa-b
= 000-040
Capacity variant:
1 2 4 =1
=2
=4
Valve set, cooling and heating
2(3)-way valve including actuator.
Valve size:
Kvs 0.25
Kvs 0.40
Kvs 0.63
Kvs 1.0
Kvs 1.6
Kvs 2.5
Kvs 4
Kvs 6.3
Kvs 10
Kvs 16
Kvs 25
Capacity variant:
1 2 TBVA-1-aaa
= 002 = 004 = 006 = 010
= 016
= 025
= 040
= 063
= 100
= 160
= 250
Air cooler, direct expansion
1 section
Duct connection size:
Ø 400
GOLD LP
Valve size:
Kvs 0.25
Kvs 0.40
Kvs 0.63
Kvs 1.0
Kvs 1.6
Kvs 2.5
Kvs 4
Kvs 6.3
Air cooler, water
TBKC-3-aaa-aaa-b-1
= 000-040
=1
=2
TBLE-4-aaa-aaa-bb-c
= 000-040
= 06
= 12
= 20
= 27
= 36
= 47
Voltage:
400V
230V (Norway) =1
=2
We reserve the right to alter specifications.
20101005
www.swegon.com
19
GOLD LP
Specification
Electrical and Control Equipment
Presence detector
TBLZ-1-56
Pressure Sensor TBLZ-1-23-aa
Contains pressure sensor and connection cable.
Version:
1 m
3 m
5 m
10 m
15 m
= 01
= 03
= 05
= 10
= 15
ELQZ-2-504
ELQZ-2-504-2
Mounting fittings for air quality sensor, for circular or insulated ducts
VOC sensor
ELQZ-1-42
TBLZ-1-60-1-1
Room Sensor For wall mounting. Enclosure Class IP 20.
TBLZ-1-24-2
Humidity sensor
For dehumidification and dew point control
Measuring point:
Supply air duct =1
Extract air duct =2
TBLZ-1-31-a
Timer, mechanical
For strap-on mounting.
0-2 hour prolonged operation
ELQZ-1-406-1
Timer, Electronic
TBLZ-1-47
Pushbutton for prolonged operation ELQZ-2-455-a-b
Version:
For surface mounting
=1
Without indicating LED
With indicating LED
=0
=1
20
ersion:
V
5 m long for air heater, electric or water coil
=1
5 m long for supply air sensor
= 2
8 m long for hand-held micro terminal, pressure sensor, TBIQ
=3
= 00
= 01
= 03
= 05
= 10
= 15
We reserve the right to alter specifications.
Strap-on Sensor TBLZ-1-32
Extra Hand-held Micro Terminal
TBLZ-1-22
MMC Circuit Card
TBLZ-1-28-a
Multi-media circ. card for prog. transmissions and logging
Version:
Without software = 1
With software, GOLD LP)
=3
IQnomic Plus
Functional module and connection cable
Version:
0.25 m
1 m
3 m
5 m
10 m
15 m
= 00 = 01
= 03
= 05
= 10
= 15
Communication unit For interface:
LON FFT-10
Tend
TBIQ-2-1-aa
TBLZ-3-1-a-41
=1
=2
All Year Comfort
TBLZ-1-59-a-b-cc
Control equipment cubicle for controlling the supply water flow.
Connection Cable
TBLZ-1-26-aa
For hand-held micro terminal, pressure sensor, TBIQ
Version:
0.25 m
1 m
3 m
5 m
10 m
15 m
TBLZ-1-05-a
Extension kit for Hand-held Micro Terminal TBLZ-2-13
For extending the cable 6 – 50 m
Air quality sensor, room
Air quality sensor, duct
Extensioncable With quick-fit connector
Operation
Cooling control = 1
Heating control = 2
Cooling and heating control = 3
Room Sensor
Without
With
Connection Cable
1 metre
3 metre
5 metre
10 metre
15 metre
> 15 metres
20101005
= 0
=1
= 01
= 03
= 05
= 10
= 15
= xx
www.swegon.com
GOLD LP
Specification
Fire and smoke protection
Equipment cabinet for fire and smoke protection function
TBLZ-1-48-1
Control box for fire and
smoke protection function
TBLZ-2-48-2
Including control unit for smoke detector and damper
exercising, damper: 24 V AC Also requires the TBIQ accessory.
Including control unit for smoke detector
Smoke detector, optical
Venturi tube, 600 mm
TBLZ-2-49-1
Mounting fittings for smoke detector, for circular
or insulated ducts
TBLZ-1-53
Damper actuator
GOLD LP
With spring return
With spring return and
limit switch
ELQZ-1-428-3-a
=1
=2
We reserve the right to alter specifications.
20101005
www.swegon.com
21
GOLD LP
Sizing
GOLD LP, size 05
Airflow, m3/h
SFP v
2.5
1.5
2.0
Available total pressure rise, Pa
Extract air fan
80
1
2
70dB
L w,tot
75
80
Supply air fan
80
1
2
70dB
L w,tot
75
80
Airflow, m3/s
The lower limit for the airflow when the unit is operating in the airflow regulation mode.
Recommended working range for sizing.
Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to
zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows GOLD LP
GOLD LP
Correction factors KOK , dB
Sound path
The tabulated flows are those that are possible to set. The practical flow limits are determined by the external pressure drop.
Octave band, No./mid-frequency, Hz
Range
in
chart
1
2
3
63
125
250
4
5
6
7
8
500 1000 2000 4000 8000
To
outlet duct
1
-1
-8
-11
-7
-7
-6
-6
-11
2
-3
-3
-5
-11
-11
-12
-15
-21
To
inlet duct*
1
-11
-14
-23
-13
-27
-39
-41
-41
2
-8
-7
-12
-21
-31
-42
-42
-41
1
-21
-26
-37
-39
-41
-39
-44
-54
2
-23
-21
-31
-43
-45
-45
-53
-64
To room unit’s
surroundings**
GOLD
LP
05
Min. airflow
Max. airflow
m /h*
3
m /s
m3 /h*
m3 /s
300
0.08
1900
0.53
3
* When adjusting the flow, round off the value to the nearest
settable step.
* Includes the integral attenuation of filters and the rotary heat exchanger.
** The total sound power level emitted to the surroundings is the sum of the
supply air and extract air sound levels.
22
We reserve the right to alter specifications.
20101005
www.swegon.com
GOLD LP
Sizing
GOLD LP, size 08
Airflow, m3/h
SFP v
2.5
2.0
1.5
Extract air fan
4
2
1
3
75dB
L w,tot
80
GOLD LP
Available total pressure rise, Pa
85
85
Supply air fan
85
4
3
2
1
75dB
L w,tot
80
85
Airflow, m3/s
The lower limit for the airflow when the unit is operating in the airflow regulation mode.
Recommended working range for sizing.
Permissible operating range when the fan is controlled to operate at a lower speed. The lower limit for the airflow when the unit is operating in the airflow regulation mode; see the black broken line in the diagram. If pressure regulation is used, the airflow can be regulated to
zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa).
Min. and max. airflows, GOLD LP
GOLD LP
Correction factors KOK , dB
Sound path
To outlet duct
To inlet duct*
To air handling
unit surroundings**
The tabulated flows are those that are possible to set. The practical flow limits are determined by the external pressure drop.
Octave band, no./mid-frequency, Hz
Range
in
diagram
1
2
3
63
125
250
500 1000 2000 4000 8000
1
2
3
4
1
2
3
4
1
2
3
4
-1
-1
-1
-2
-6
-7
-6
-7
-21
-21
-21
-22
-6
-5
-2
-3
-9
-10
-4
-5
-24
-23
-20
-21
-6
-8
-6
-5
-12
-17
-14
-12
-32
-34
-32
-31
-8
-8
-15
-13
-22
-18
-27
-22
-40
-40
-47
-45
4
5
-7
-7
-14
-13
-31
-29
-35
-34
-41
-41
-48
-47
6
-7
-9
-16
-14
-33
-31
-39
-36
-40
-42
-49
-47
7
-12
-13
-22
-20
-38
-37
-44
-42
-50
-51
-60
-58
8
-15
-16
-25
-25
-37
-38
-43
-43
-58
-59
-68
-68
GOLD
LP
m3 /h*
Min. airflow
m3 /s
m3 /h*
Max. airflow
m3 /s
08
300
0.08
2600
0.74
* When adjusting the flow, round off the value to the nearest
settable step.
* The integral attenuation of filters and rotary heat exchanger has been taken
into account.
** Total sound power level emitted to the surroundings is calculated as the sum
of the levels in the supply air and the extract air.
We reserve the right to alter specifications.
20101005
www.swegon.com
23
GOLD LP
Sizing
GOLD LP
Delivery and Transport within the Site
Rated data per fan
Size 05: 1 x 230 V, 50/60 Hz, 0.74 kW.
Size 08: 3 x 400 V, 50/60 Hz, 1.0 kW.
The air handling unit is delivered on a wooden pallet. The
slide rails, inspection panels and fans can be dismantled
from the unit to make it easier to transport the unit within
the site.
The GOLD LP is produced in one variant in which all the
components are arranged at their given physical locations
inside the unit.
Thanks to its low installation height, the GOLD LP can be
installed in false ceiling voids, horizontally in an attic space
or in other confined spaces. In order to save floor space,
the GOLD LP can also be mounted by a wall (a floor stand
is available as an accessory) as an alternative to a conventional unit arrangement. If the unit is mounted on a wall,
the electric equipment cubicle must always be located
upwards.
The air handling unit is supplied in the right-hand version.
The unit can be changed to the left-hand version at the
building site by making a simple adjustment in the control
equipment.
Rated data for the heat exchanger drive motor
Step motor, 3-phase, 5.8 A (2A)*, 50 V* max 90 V.
*) The motor control system limits the output power/voltage to the value specified.
Right-hand version
Left-hand version
Electrical equipment cubicle
Electrical equipment cubicle
Electrical Data
Power supply
Size 05: 1-ph., 3-wire, 230 V -10/+15%, 50/60 Hz, 10AT.
Size 08: 3-ph., 5-wire, 400 V -10/+15%, 50/60 Hz, 10AT.
The unit is equipped with a main switch.
Outdoor air
Supply air
Extract air
Exhaust air
Dimensions and Weights
Clear service space
Electrical equipment cubicle
A
500
A clear space of 500 mm open space must be provided in front
of inspection panels on the inspection side or in front of the
extra inspection panel on the long sides for changing the filters.
A clear space of at least 200 mm must be provided above the
electrical equipment cubicle for opening its cover.
C
Centre-to-centre dimension between holes in the mounting brackets
F
Excluding slide rails.
Ø 11
D
E
B1
62
L
30
J
72
95
J
12
36
12 36
Power connection
G
150
Extra inspection panel.
340
H2
K
H1
Slide rail
B2
I
Including slide rails.
GOLD LP
05
08
24
A
B1
B2
C
D
E
F
G
H1
H2
I
J
K
L
kg
731
807
1052
1210
1100
1258
635
675
1210
1410
481
480
1111
1269
425
500
507
582
560
635
50
48
454
533
400
475
2172
2370
247
301
We reserve the right to alter specifications.