G83/2 Appendix 4 Type Verification Test Report Type Approval and manufacturer/supplier declaration of compliance with the requirements of Engineering Recommendation G83/2. SSEG Type reference number M215-60-230-S22 SSEG Type Photovoltaic Microinverter System Supplier name Enphase Energy Inc. Address 1420 North McDowell Blvd. Petaluma, CA 94954 USA Tel +1-707-763-4784 Fax +1-707-763-0784 E:mail [email protected] Web site www.enphase.com 3.655 Maximum rated capacity, use separate sheet if more than one connection option. Connection Option kW single phase, single, split or three phase system kW three phase kW two phases in three phase system kW two phases split phase system SSEG manufacturer/supplier declaration. I certify on behalf of the company named above as a manufacturer/supplier of Small Scale Embedded Generators, that all products manufactured/supplied by the company with the above SSEG Type reference number will be manufactured and tested to ensure that they perform as stated in this Type Verification Test Report, prior to shipment to site and that no site modifications are required to ensure that the product meets all the requirements of G83/2. Signed On behalf of Enphase Energy Inc. Peter L. Tarver Note that testing can be done by the manufacturer of an individual component, by an external test house, or by the supplier of the complete system, or any combination of them as appropriate. Where parts of the testing are carried out by persons or organisations other than the supplier then the supplier shall keep copies of all test records and results supplied to them to verify that the testing has been carried out by people with sufficient technical competency to carry out the tests. enphase.com Doc # HPV-00089-2.0 Power Quality. Harmonics. The requirement is specified in section 5.4.1, test procedure in Annex A or B 1.4.1 SSEG rating per phase (rpp) kW NV=MV*3.68/rpp 3.655 Harmonic At 45-55% of rated output Measured Normalised Value Value (MV) in (NV) in Amps Amps 100% of rated output Measured Value (MV) in Amps Normalised Value (NV) in Amps Limit in BS EN 610003-2 in Amps 2 0.002 0.004 0.097 0.103 1.080 3 0.075 0.146 0.036 0.038 2.300 4 0.003 0.006 0.027 0.029 0.430 5 0.065 0.127 0.067 0.071 1.140 6 0.004 0.008 0.018 0.019 0.300 7 0.053 0.103 0.075 0.080 0.770 8 0.013 0.025 0.012 0.013 0.230 9 0.063 0.123 0.074 0.079 0.400 10 0.004 0.008 0.01 0.011 0.184 11 0.063 0.123 0.052 0.055 0.330 12 0.004 0.008 0.007 0.007 0.153 13 0.06 0.117 0.073 0.078 0.210 14 0.005 0.010 0.006 0.006 0.131 15 0.051 0.100 0.058 0.062 0.150 16 0.006 0.012 0.006 0.006 0.115 17 0.048 0.094 0.065 0.069 0.132 18 0.006 0.012 0.005 0.005 0.102 19 0.071 0.139 0.111 0.118 0.118 20 0.006 0.012 0.006 0.006 0.092 21 0.053 0.103 0.066 0.070 0.107 enphase.com Higher limit for odd harmonics 21 and above 0.160 Doc # HPV-00089-2.0 22 0.005 0.010 0.005 0.005 0.084 23 0.05 0.098 0.046 0.049 0.098 24 0.006 0.012 0.005 0.005 0.077 25 0.038 0.074 0.032 0.034 0.090 26 0.006 0.012 0.005 0.005 0.071 27 0.014 0.027 0.015 0.016 0.083 28 0.006 0.012 0.005 0.005 0.066 29 0.011 0.021 0.013 0.014 0.078 30 0.006 0.012 0.005 0.005 0.061 31 0.033 0.064 0.035 0.037 0.073 32 0.006 0.012 0.006 0.006 0.058 33 0.026 0.051 0.029 0.031 0.068 34 0.006 0.012 0.004 0.004 0.054 35 0.013 0.025 0.035 0.037 0.064 36 0.006 0.012 0.004 0.004 0.051 37 0.018 0.035 0.025 0.027 0.061 38 0.006 0.012 0.005 0.005 0.048 39 0.025 0.049 0.04 0.043 0.058 40 0.006 0.012 0.003 0.003 0.046 0.147 0.135 0.124 0.117 0.109 0.102 0.096 0.091 0.087 Note the higher limits for odd harmonics 21 and above are only allowable under certain conditions, if these higher limits are utilised please state the exemption used as detailed in part 6.2.3.4 of BS EN 61000-3-2 in the box below. enphase.com Doc # HPV-00089-2.0 Power Quality. Voltage fluctuations and Flicker. The requirement is specified in section 5.4.2, test procedure in Annex A or B 1.4.3 Starting Stopping Running dmax dc dmax dc Pst Plt 2 hours d(t) d(t) Measured Values Normalised to standard impedance and 3.68kW for multiple units Limits set under BS EN 61000-3-2 0.11 0.06 0 0.11 0.06 0 0.09 0.12 0.06 0 0.12 0.06 0 0.096 4% 3.3% 3.3% 4% 3.3% 3.3% 1.0 500ms 0.08 0.085 0.65 500ms Test start date 26DEC2013 Test end date Test location Enphase Energy Inc 1400 North McDowell Blvd. Petaluma, CA 94954 USA 26DEC2013 Power quality. DC injection. The requirement is specified in section 5.5, test procedure in Annex A or B 1.4.4 Test power 10% 55% 100% level Recorded 0.00 0.00 0.00 value as % of rated AC 0.00 0.00 0.00 current Limit 0.25% 0.25% 0.25% Power Quality. Power factor. The requirement is specified in section 5.6, test procedure in Annex A or B 1.4.2 216.2V 230V 253V Measured value 0.99 0.99 0.99 Limit >0.95 >0.95 >0.95 Measured at three voltage levels and at full output. Voltage to be maintained within ±1.5% of the stated level during the test. enphase.com Doc # HPV-00089-2.0 Protection. Frequency tests The requirement is specified in section 5.3.1, test procedure in Annex A or B 1.3.3 Function Setting Trip test “No trip tests” Time Time Frequency Frequency delay Frequency delay /time Confirm no trip 47.7Hz U/F stage 1 47.5Hz 20s 47.5 Hz 20 s Confirmed 25s 47.2Hz U/F stage 2 47Hz 0.5s 47 Hz 0.7 s Confirmed 19.98s 46.8Hz Confirmed 0.48s 51.3Hz O/F stage 1 51.5Hz 90s 51.6 Hz 90 s Confirmed 95s 51.8Hz O/F stage 2 52Hz 0.5s 52.1 Hz 0.7 s Confirmed 89.98s 52.2Hz Confirmed 0.48s Protection. Voltage tests The requirement is specified in section 5.3.1, test procedure in Annex A or B 1.3.2 Function Setting Trip test “No trip tests” Time Time Voltage Voltage delay Voltage delay /time Confirm no trip 204.1V U/V stage 1 200.1V 2.5s 197.8 V 2.65 s Confirmed 3.5s 188V U/V stage 2 184V 0.5s 182.8 V 0.79 s Confirmed 2.48s 180V Confirmed 0.48s 258.2V O/V stage 1 262.2V 1.0s 262.1 V 1.07 s Confirmed 2.0s 269.7V O/V stage 2 273.7V 0.5s 273.6 V 0.79 s Confirmed 0.98s 277.7V Confirmed 0.48s Note for Voltage tests the Voltage required to trip is the setting ±3.45V. The time delay can be measured at a larger deviation than the minimum required to operate the protection. The No trip tests need to be carried out at the setting ±4V and for the relevant times as shown in the table above to ensure that the protection will not trip in error. enphase.com Doc # HPV-00089-2.0 Protection. Loss of Mains test. The requirement is specified in section 5.3.2, test procedure in Annex A or B 1.3.4 To be carried out at three output power levels with a tolerance of plus or minus 5% in Test Power levels. Test Power 10% 55% 100% 10% 55% 100% Balancing load on islanded network 95% of SSEG output 95% of SSEG output 95% of SSEG output 105% of SSEG output 105% of SSEG output 105% of SSEG output Trip time. Limit is 0.5 seconds 0.152 s 0.048 s 0.416 s 0.168 s 0.032 s 0.448 s enphase.com Doc # HPV-00089-2.0 Protection. Frequency change, Stability test The requirement is specified in section 5.3.3, test procedure in Annex A or B 1.3.6 Start End Frequency Change Frequency Confirm no trip Positive Vector Shift 49.5Hz +9 degrees Confirmed Negative Vector Shift 50.5Hz - 9 degrees Confirmed Positive Frequency drift 49.5Hz +0.19Hz/sec 51.5Hz Confirmed Negative Frequency drift 50.5Hz -0.19Hz/sec 47.5Hz Confirmed Protection. Re-connection timer. The requirement is specified in section 5.3.4, test procedure in Annex A or B 1.3.5 Test should prove that the reconnection sequence starts after a minimum delay of 20 seconds for restoration of voltage and frequency to within the stage 1 settings of table 1. Time delay Measured Checks on no reconnection when voltage or frequency setting delay is brought to just outside stage 1 limits of table 1. At 266.2V At 196.1V At 47.4Hz At 51.6Hz Confirmation that the SSEG does Confirmed not re-connect. Confirmed Confirmed Confirmed 20 s 25 s Fault level contribution. The requirement is specified in section 5.7, test procedure in Annex A or B 1.4.6 For a directly coupled SSEG For a Inverter SSEG Parameter Peak Short Circuit current Initial Value of aperiodic current Initial symmetrical shortcircuit current* Decaying (aperiodic) component of short circuit current* Reactance/Resistance Ratio of source* Symbol Value ip 13.6 A Time after fault Volts Amps 20ms 0 0 13.6 100ms 0 0 Ik 14.1 250ms 0 0 iDC 0 500ms 0 0 2.5 Time to trip 0 X /R enphase.com In seconds Doc # HPV-00089-2.0 Self-Monitoring solid state switching The requirement is specified in Yes/or NA section 5.3.1, No specified test requirements. It has been verified that in the event of the solid state switching device failing to disconnect the SSEG, the voltage on the output side of the switching N/A device is reduced to a value below 50 volts within 0.5 seconds. Additional comments enphase.com Doc # HPV-00089-2.0
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
advertisement