5715V102_UK
5715
Programmable
LED Indicator
No. 5715V102-UK
From serial number:
121496001 (B)
131077001 (D)
DK
PR electronics A/S tilbyder et bredt program af analoge og digitale
signalbehandlingsmoduler til industriel automation. Programmet
består af Isolatorer, Displays, Ex-barrierer, Temperaturtransmittere,
Universaltransmittere mfl. Vi har modulerne, du kan stole på i selv
barske miljøer med elektrisk støj, vibrationer og temperaturudsving,
og alle produkter opfylder de strengeste internationale standarder.
Vores motto »Signals the Best« er indbegrebet af denne filosofi – og
din garanti for kvalitet.
UK
PR electronics A/S offers a wide range of analog and digital
signal conditioning devices for industrial automation. The product
range includes Isolators, Displays, Ex Interfaces, Temperature
Transmitters, and Universal Devices. You can trust our products in
the most extreme environments with electrical noise, vibrations and
temperature fluctuations, and all products comply with the most
exacting international standards. »Signals the Best« is the epitome
of our philosophy – and your guarantee for quality.
FR
PR electronics A/S offre une large gamme de produits pour le
traite­
ment des signaux analogiques et numériques dans tous
les domaines industriels. La gamme de produits s’étend des
transmetteurs de température aux afficheurs, des isolateurs aux
interfaces SI, jusqu’aux modules universels. Vous pouvez compter
sur nos produits même dans les conditions d’utilisation sévères,
p.ex. bruit électrique, vibrations et fluctuations de température.
Tous nos produits sont conformes aux normes internationales les
plus strictes. Notre devise »SIGNALS the BEST« c’est notre ligne
de conduite - et pour vous l’assurance de la meilleure qualité.
DE
PR electronics A/S verfügt über ein breites Produktprogramm
an analogen und digitalen Signalverarbeitungsgeräte für die in­
dustrielle Automatisierung. Dieses Programm umfasst Displays,
Temperaturtransmitter, Ex- und galvanische Signaltrenner, und
Universalgeräte. Sie können unsere Geräte auch unter extremen
Einsatzbedingungen wie elektrisches Rauschen, Erschütterungen
und Temperaturschwingungen vertrauen, und alle Produkte von
PR electronics werden in Überein­stimmung mit den strengsten
internationalen Normen produziert. »Signals the Best« ist Ihre
Garantie für Qualität!
1532
Programmable LED indicator
5715
contents
Warning........................................................................................................
Symbol identification.............................................................................
Safety instructions..................................................................................
Front and back layout............................................................................
Application..................................................................................................
Technical characteristics.......................................................................
Mounting / installation..........................................................................
Applications...............................................................................................
Order: 5715................................................................................................
Electrical specifications........................................................................
Sensor error detection inside and outside range.......................
Connections...............................................................................................
Block diagram............................................................................................
Routing diagram.......................................................................................
Scrolling help texts.................................................................................
Configuration / operating the function keys................................
Programming via PC...............................................................................
Graphic depiction of the relay function setpoint.......................
4
4
5
7
8
8
8
9
10
10
14
15
16
18
19
21
22
22
5715V102-UK3
Warning
GENERAL
This module is designed for connection to hazardous electric voltages. Ignoring this warning can result in severe personal injury
or mechanical damage. To avoid the risk of electric shock and fire,
the safety instructions of this manual must be observed and the
guidelines followed. The specifications must not be exceeded,
and the module must only be applied as described in the following. Prior to the commissioning of the module, this manual must
be examined carefully. Only qualified personnel (technicians)
should install this module.
If the equipment is used in a manner not specified by the
manufacturer, the protection provided by the equipment may be
impaired.
WARNING
Until the module is fixed, do not connect hazardous voltages to
the module.
HAZARD­OUS The following operations should only be carried out on a disconnected module and under ESD safe conditions:
VOLTAGE
Troubleshooting the module.
Repair of the module must be done by PR electronics A/S only.
Symbol identification
Triangle with an exclamation mark: Warning / demand. Potentially lethal
situations.
The CE mark proves the compliance of the module with the essential
requirements of the directives.
45715V102-UK
Safety instructions
Definitions
Hazardous voltages have been defined as the ranges: 75 to 1500 Volt DC, and 50
to 1000 Volt AC.
Technicians are qualified persons educated or trained to mount, operate, and also
troubleshoot technically correct and in accordance with safety regulations.
Operators, being familiar with the contents of this manual, adjust and operate the
knobs or potentiometers during normal operation.
Receipt and unpacking
Unpack the device without damaging it. The packing should always follow the
device until this has been permanently mounted. Check at the receipt of the
device whether the type corresponds to the one ordered.
Environment
Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock,
as well as rain and heavy moisture. If necessary, heating in excess of the stated
limits for ambient temperatures should be avoided by way of ventilation.
All modules fall under Installation Category II, Pollution Degree 1, and Insulation
Class II.
Mounting
Only technicians who are familiar with the technical terms, warnings, and instructions in the manual and who are able to follow these should connect the module.
Should there be any doubt as to the correct handling of the module, please contact your local distributor or, alternatively,
PR electronics A/S
www.prelectronics.com
Mounting and connection of the module should comply with national legislation
for mounting of electric materials, i.e. wire cross section, protective fuse, and
location. Descriptions of Input / Output and supply connections are shown in the
block diagram and side label.
5715V102-UK5
The following apply to fixed hazardous voltages-connected modules:
The max. size of the protective fuse is 10 A and, together with a power
switch, it should be easily accessible and close to the module. The
power switch should be marked with a label telling it will switch off the
voltage to the module.
UL installation requirements
For use on a flat surface of a type 1 enclosure
Use 60/75°C copper conducters only
Enclosure rating (face only)........................... Type 4X, UL50E
Max. ambient temperature.............................60°C
Max. wire size, pins 41...46............................ AWG 30-16
Max. wire size, others....................................... AWG 30-12
UL file number.....................................................E248256
Calibration and Adjustment
During calibration and adjustment, the measuring and connection of external
voltages must be carried out according to the specifications of this manual. The
technician must use tools and instruments that are safe to use.
Normal operation
Operators are only allowed to adjust and operate modules that are safely fixed in
panels, etc., thus avoiding the danger of personal injury and damage. This means
there is no electrical shock hazard, and the module is easily accessible.
Cleaning
When disconnected, the module may be cleaned with a cloth moistened with
distilled water.
Liability
To the extent the instructions in this manual are not strictly observed, the
custom­er cannot advance a demand against PR electronics A/S that would otherwise exist according to the concluded sales agreement.
65715V102-UK
Front and back layout
Picure 1: Front of PReview 5715.
Picture 2: Back of PReview 5715.
5715V102-UK7
Programmable LED indicator
PReview 5715
• 4-digit 14-segment LED display
• Input for mA, V, potentiometer, Ohm, RTD and TC
• 4 relays and analogue output
• Universal supply
• Programmable via front keys and PC
Application
• Display for digital readout of current / voltage / resistance / temperature or
3-wire potentiometer signals.
• Process control with 4 pairs of potential-free change-over relays and analogue
output.
• For tank level control, with the possibility of customer linearisation ensuring
correct level measurement and control in non-linear tanks.
Technical characteristics
• 4-digit LED indicator with 13.8 mm 14-segment characters. Max. display
read­out -1999...9999 with programmable decimal point and relay ON / OFF
indication.
• All standard operational parameters can be adjusted to any application by way
of the front function keys. When programming is carried out by way of a PC and
the configuration program PReset, additional configuration options are available,
such as customer-defined linearisation and special input signals.
• Help texts in eight languages can be selected via a menu item.
• A menu item allows the user to minimise the installation test time for the relay
outputs by activating / deactivating each relay independently of the input signal.
Mounting / installation
• To be mounted in panel front. The included rubber packing must be mounted
between the panel cutout hole and the display front to obtain a protection
degree of IP65 (type 4X). For extra protection in extreme environments,
PReview 5715 can be delivered with a specially designed splash-proof cover as
accessory.
85715V102-UK
Applications
Input signals:
Current
46
+
-
RTD & Lin R -
45
2-twire transmitter
Potentio­ Connection, wires
meter
432
44
+
Voltage
-
+
+
-
-
TC
43
1
2
3
4
42
41
Output signals:
1
2
3
4
12
+
26
66
25
65
24
64
23
63
22
62
-
21
11
Analogue, 0/4...20 mA
61
4 change-over relays
Supply:
32
21.6...253 VAC
or
19.2...300 VDC
1
2
3
4
31
5715V102-UK9
Order: 5715
Type
Version
5715
4 relays . . . . . . . . . . . . . . . . . . . . . . . . : B
Analogue output and 4 relays . . . : D
Electrical specifications
Specifications range:
-20°C to +60°C
Common specifications:
Supply voltage, universal...................................... 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC
Consumption:
Type
Internal consumption
Max. consumption
5715B
3.0 W
3.3 W
5715D
3.5 W
3.8 W
Isolation voltage, test / operation.....................
Signal / noise ratio...................................................
Communications interface....................................
Response time (0...90%, 100...10%):
Temperature input...............................................
Current / voltage input......................................
Calibration temperature.........................................
2.3 kVAC / 250 VAC
Min. 60 dB (0...100 kHz)
USB Loop Link
<1s
< 400 ms
20...28°C
Accuracy, the greater of general and basic values:
General values
Input type
Absolute
accucary
Temperature
coefficient
All
≤ ±0.1% of reading
≤ ±0.01% of reading / °C
105715V102-UK
Basic values
Basic
accuracy
≤ ±4 µA
≤ ±20 µV
≤ ±0.2°C
≤ ±0.1 Ω
≤ ±0.1 Ω
Input
type
mA
Volt
Pt100
Linear resistance
Potentiometer
TC type:
E, J, K, L, N, T, U
TC type: R, S, W3,
W5, LR
TC type: B
85...200°C
TC type: B
200...1820°C
Temperature
coefficient
≤ ±0.4 µA / °C
≤ ±2 µV / °C
≤ ±0.01°C / °C
≤ ±0.01 Ω / °C
≤ ±0.01 Ω / °C
≤ ±1°C
≤ ±0.05°C / °C
≤ ±2°C
≤ ±0.2°C / °C
≤ ±4°C
≤ ±0.4°C / °C
≤ ±2°C
≤ ±0.2°C / °C
EMC immunity influence................................................... < ±0,5% of reading
Auxiliary supply:
2-wire supply (pin 46...45)............................... 25...15 VDC / 0...20 mA / 30 mA nom.
Vibration....................................................................... IEC 60068-2-6 Test FC
2...25 Hz................................................................... ±1.6 mm
25...100 Hz............................................................. ±4 g
Wire size, pin 41...46 (max.)................................. 1 x 1.5 mm2 stranded wire
Wire size, others (max.).......................................... 1 x 2.5 mm2 stranded wire
Relative humidity..................................................... < 95% RH (non cond.)
Dimensions (HxBxD)................................................ 48 x 96 x 120 mm
Cutout dimensions................................................... 44.5 x 91.5 mm
Protection degree (mounted in panel)............. IP65 / Type 4X, UL50E
Weight........................................................................... 260 g
RTD, linear resistance and potentiometer input:
Input
type
Min.
value
Max.
value
Standard
Pt10...Pt1000
Ni50...Ni1000
Cu10...Cu100
Lin. R
Potentiometer
-200°C
-60°C
-200°C
0Ω
10 Ω
+850°C
+250°C
+260°C
10000 Ω
100 kΩ
IEC 60751
DIN 43760
α = 0.00427
-
5715V102-UK11
Input for RTD types:
Pt10, Pt20, Pt50, Pt100, Pt200, Pt250, Pt300, Pt400, Pt500, Pt1000
Ni50, Ni100, Ni120, Ni1000, Cu10, Cu20, Cu50, Cu100
Cable resistance per wire, RTD (max.)............. 50 Ω
Sensor current, RTD................................................. Nom. 0.2 mA
Effect of sensor cable resistance
(3- / 4-wire), RTD...................................................... < 0.002 Ω / Ω
Sensor error detection, RTD................................. Yes
Short circuit detection, RTD................................. < 15 Ω
TC input:
Type
Min.
value
Max.
value
Standard
B
E
J
K
L
N
R
S
T
U
W3
W5
LR
+0°C
-100°C
-100°C
-180°C
-200°C
-180°C
-50°C
-50°C
-200°C
-200°C
0°C
0°C
-200°C
+1820°C
+1000°C
+1200°C
+1372°C
+900°C
+1300°C
+1760°C
+1760°C
+400°C
+600°C
+2300°C
+2300°C
+800°C
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
ASTM E988-90
ASTM E988-90
GOST 3044-84
Cold junction compensation (CJC)
via internal sensor.............................................. ±(2.0°C + 0.4°C * Δt)
Δt = internal temperature - ambient temperature
Sensor error detection, all TC types................. Yes
Sensor error current:
when detecting.................................................... Nom. 2 μA
else........................................................................... 0 μA
Current input:
Measurement range................................................. 0...20 mA
Programmable measurement ranges................ 0...20 and 4...20 mA
Input resistance........................................................ Nom. 20 Ω + PTC 25 Ω
Sensor error detection:
loop break 4...20 mA........................................... Yes
125715V102-UK
Voltage input:
Measurement range................................................. 0...12 VDC
Programmable measurement ranges................ 0...1, 0.2...1,
0...10 and 2...10 VDC
Input resistance........................................................ Nom. 10 MΩ
Outputs:
Display:
Display readout.........................................................
Decimal point..............................................................
Digit height.................................................................
Display updating.......................................................
Input outside input range is
indicated by................................................................
Current output:
Signal range (span)..................................................
Programmable signal ranges................................
Load (max.)..................................................................
Load stability..............................................................
Sensor error detection............................................
NAMUR NE 43 Up- / Downscale.........................
Output limitation:
on 4...20 and 20...4 mA signals......................
on 0...20 and 20...0 mA signals......................
Current limit................................................................
Relay outputs:
Relay function............................................................
Hysteresis....................................................................
On and Off delay.......................................................
Sensor error detection............................................
Max. voltage...............................................................
Max. current................................................................
Max. AC power...........................................................
Max. current at 24 VDC..........................................
Marine approval:
Det Norske Veritas, Ships & Offshore..............
Observed authority requirements:
EMC 2004/108/EC...................................................
LVD 2006/95/EC.......................................................
UL, Standard for Safety..........................................
EAC TR-CU 020/2011.............................................
-1999...9999 (4 digits)
Programmable
13.8 mm
2.2 times / s
Explanatory text
0...20 mA
0...20, 4...20,
20...0 and 20...4 mA
20 mA / 800 Ω / 16 VDC
≤ 0.01% of span / 100 Ω
23 / 0 / 3.5 mA / none
23 mA / 3.5 mA
3,8...20.5 mA
0...20.5 mA
≤ 28 mA
Setpoint
0...100%
0...3600 s
Make / Break / Hold
250 VRMS
2 A / AC
500 VA
1A
Standard for Certification No. 2.4
Standard:
EN 61326-1
EN 61010-1
UL 508
EN 61326-1
5715V102-UK13
Sensor error detection inside and outside range
Sensor error check in 5715 variants:
Variant:
5715B
5715D
Input
VOLT
CURR
POTM
TEMP
LIN R
Configuration
ERR1, ERR2, ERR3 and ERR4 = NONE
Else:
Sensor error detection:
OFF
ON
OFF
ON
ERR1, ERR2, ERR3 and ERR4=NONE, O.ERR=NONE.
Else:
Outside range readout (IN.LO, IN.HI):
If the valid range of the A/D converter or the polynomial is exceeded
Range
Readout
Limit
IN.LO
< -25 mV
0...1 V / 0,2...1 V
IN.HI
> 1,2 V
IN.LO
< -25 mV
0...10 V / 2...10 V
IN.HI
> 12 V
IN.LO
< -1,05 mA
0...20 mA / 4...20 mA
IN.HI
> 25,05 mA
IN.LO
< -0,5%
IN.HI
> 100,5%
IN.LO
< temperature range -2°C
TC / RTD
IN.HI
> temperature range +2°C
IN.LO
< 0 ohm
0...800 ohm
IN.HI
> 1 kohm
IN.LO
< 0 ohm
0...10 kohm
IN.HI
> 15 kohm
Sensor error detection (SE.BR, SE.SH):
Input
CURR
Range
Loop break (4..20mA)
TC
TEMP
RTD, 2-, 3- & 4-wire
No SE.SH for Cuxx, Pt10, Pt20 & Pt50
LIN R
0...800 ohm
0...10 kohm
Readout
SE.BR
SE.BR
SE.BR
SE.SH
SE.BR
SE.BR
Limit
<= 3,6 mA; > = 21 mA
> ca. 750 kohm / (1,25 V)
> 12 kohm
< 15 ohm
> 875 ohm
> 12 kohm
Display readout below min. / above max. (-1.9.9.9, 9.9.9.9):
Input
CURR /
VOLT / Lin R
POTM
Range
All
-
Readout
-1.9.9.9
9.9.9.9
-1.9.9.9
9.9.9.9
Limit
Display readout <-1999
Display readout >9999
Display readout <-1999
Display readout >9999
Readout at hardware error
! Error indications in the display blink once a second. The help text explains the error
Error search
Readout
Error cause
Test of internal communication uC / ADC
HW.ER
Permanent error in ADC
Test of internal CJC sensor
CJ.ER
CJC sensor defect
Check-sum test of the configuration in RAM
RA.ER
Error in RAM
Check-sum test of the configuration in EEprom
EE.ER
Error in EEPROM
145715V102-UK
Connections
Supply:
31 32
Inputs:
RTD & Lin R, 2-wire
41 42 43 44 45 46
RTD & Lin R, 3-wire
41 42 43 44 45 46
TC
41 42 43 44 45 46
-
2-wire transmitter
41 42 43 44 45 46
+
-
Voltage
41 42 43 44 45 46
-
RTD & Lin R, 4-wire
41 42 43 44 45 46
Tx
+
Current
41 42 43 44 45 46
-
+
Potentiometer
41 42 43 44 45 46
+
Output:
Relays
Current
11 12
-
mA
+
21 22 23 24 25 26
R1
R2
Relays
61 62 63 64 65 66
R3
R4
5715V102-UK15
165715V102-UK
1
3
2
Potm.
4
3
2
RTD & Lin R
wires
+
+V
Tx
+
TC
Input gnd.
+
Input +,
mA
2-wire supply
> 15 VDC
41
42
Int.
CJC
43
44
45
46
20 W
PTC
0.2 mA
AD
5715
EEPROM
CPU
Version D
PC communication
1
2
3
4
R4
R3
R2
R1
66
64
65
63
61
62
26
24
25
23
21
22
11
12
31
32
mA
Relay 4 N.C.
Common
Relay 4 N.O.
Relay 3 N.C.
Common
Relay 3 N.O.
Relay 2 N.C.
Common
Relay 2 N.O.
Relay 1 N.C.
I
Output
Common
Relay 1 N.O.
Gnd.
I+
Supply
21.6...253 VAC
or
19.2...300 VDC
Supply
Block diagram
Power up
1.2
F.SET
1 2
1 2
REL1
REL2
REL3
REL4
50.0
1.0
3
1.3
3
Fast setpoint adjustment and relay test
SETP
1 2
-1999
9999
/OFF
3
1
Increase setpoint
2
Decrease setpoint
3
Save and exit the menu
1
and 2 simultaneously =
relay changes state
1.1
PASS
ADV
IN
DEC.P
DI.LO
DI.HI
1 2
0000
9999
1 2
NO
YES
1 2
1 2
1111
1.1.1.1
1 2
a999
9999
1 2
a999
9999
3
3
1.4
C.LIN 3
3
3
PERC
3
1 2
PERC
DISP
3
YES
ADV.SET
3
POTM
CURR 3 RANG
1 2
0-20 4-20
3
VOLT 3 RANG
1 2
0-1 0.2-1
0-10 2-10
1.0 = Default state
1.1 = Only if password-protected
1.2 = Only is FastSet is enabled
1.3 = Setpoint adjustment and
relay test disabled at password 5000...9999.
1.4 = Only for special configuration
via PC
1.5 = Not valid for these input
signals: Potentiometer, 0...20
mA and voltage
1.6 = Only if input signal is temperature
1.7 = No analogue output
1.8 = In default state press and
hold 1 or 2 to change
display intensity between
damped and full
(7 = full intensity)
3
LIN.R 3 LR.LO
LR.HI
CONN
1 2 3 1 2 3 1 2
3
0-9998
1-9999 2W 3W 4W
TEMP 3 TYPE
1 2
PT
3
PT.TY
CONN
1 2 3 1 2
10-1000 2W 3W 4W
NI
3
NI.TY
1 2 3 1 2
50-1000 2W 3W 4W
TC
3
CONN
3
3 TC.TY
DEC.P
1 2
TC.B-E-J-K-L-N-R
S-T-U-W3-W5-LR
CU
3
CONN
3
1 2
2W 3W 4W
3
CU.TY
1 2
10-100
1 2
1111
111.1
3
UNIT
3
1 2
'C
'F
5715V102-UK17
3
Routing diagram
If no key is activated for 2 minutes, the display returns to default state 1.0
without saving configuration changes.
1 Increase value / choose next parameter
2 Decrease value / choose previous parameter
3 Accept the chosen parameter and go to the next menu
Hold 3 Back to previous menu / return to default state 1.0 without saving
REL.1
SETP
ACT1
HYS1
1 2
SET
SKIP
OFF
1 2
0.0
100.0
1 2
INCR
DECR
1 2
0.0
100.0
3
3
3
3
1.5
ERR1
ON.DE
1 2
HOLD
ACTI
DEAC
NONE
1 2
0000
3600
3
X = 2...4
REL.X
SETP
ACTX
HYSX
1 2
SET
SKIP
OFF
1 2
0.0
100.0
1 2
INCR
DECR
1 2
0.0
100.0
3
3
3
3
1.5
3
3
OF.DE
ERRX
ON.DE
1 2
HOLD
ACTI
DEAC
NONE
1 2
0000
3600
3
1 2
0000
3600
3
3
OF.DE
1 2
0000
3600
3
3
1.7
1.7
A.OUT
1.6
1 2
4-20
0-20
20-4
20-0
3
ADV.SET
O.LO
1 2
a999
9999
1.6
3
O.HI
1 2
a999
9999
DE
ES
IT
UK
LANG
DISP
CAL
12
1.5
3
O.ERR
RESP
E.PAS
1 2
0/3.5mA
23mA
NONE
1 2
0.0
60.0
1 2
YES
NO
3
DK
FR
SE
CZ
3
N.PAS
1 2
0000
9999
3
3
NO
To default state 1.0
----
12
LANG 3
UK
3
HLP.T
1...7
12
1.8 DISP
3
7
3
LIGH
100.0
0.0
12
YES NO
12
100.0
0.0
12
YES NO
12
YES NO
12
CAL 3 YES 3 2.0 3 YES 3 90.0 3 YES 3
CA.LO
VAL.L
NO
185715V102-UK
CA.HI
VAL.H
3
NO
USE.C
Scrolling help texts
Display in default state xxxx, hardware error:
SE.BR --> SENSOR WIRE BREAKAGE
SE.SH --> SENSOR SHORT CIRCUIT
IN.HI --> INPUT OVERRANGE
IN.LO --> INPUT UNDERRANGE
9.9.9.9--> DISPLAY OVERRANGE
-1.9.9.9
-->DISPLAY UNDERRANGE
HW.ER --> HARDWARE ERROR
EE.ER --> EEPROM ERROR CHECK CONFIGURATION
RA.ER --> RAM MEMORY ERROR
CJ.ER --> CJC SENSOR ERROR
DI.HI
xxxx
Fastset (Enabled):
F.SET
REL1 --> FAST SET MENU REL2 --> SELECT RELAY
REL3
REL4
SETP
xxxx --> RELAY SETPOINT - PRESS OK TO SAVE
CU.TY
10
--> SELECT CU SENSOR TYPE
20
--> SELECT CU SENSOR TYPE
50
--> SELECT CU SENSOR TYPE
100
--> SELECT CU SENSOR TYPE
PT.TY
10
--> SELECT PT SENSOR TYPE
20
--> SELECT PT SENSOR TYPE
50
--> SELECT PT SENSOR TYPE
100
--> SELECT PT SENSOR TYPE
200
--> SELECT PT SENSOR TYPE
250
--> SELECT PT SENSOR TYPE
300
--> SELECT PT SENSOR TYPE
400
--> SELECT PT SENSOR TYPE
500
--> SELECT PT SENSOR TYPE
1000 --> SELECT PT SENSOR TYPE
NI.TY
50
--> SELECT NI SENSOR TYPE
100
--> SELECT NI SENSOR TYPE
120
--> SELECT NI SENSOR TYPE
1000 --> SELECT NI SENSOR TYPE
CONN When Cu, Pt and Ni sensor is selected
2W
--> SELECT 2-WIRE SENSOR CONNECTION
3W
--> SELECT 3-WIRE SENSOR CONNECTION
4W
--> SELECT 4-WIRE SENSOR CONNECTION
TC.TY
TC. B --> SELECT TC SENSOR TYPE
TC. E --> SELECT TC SENSOR TYPE
TC. J
--> SELECT TC SENSOR TYPE
TC. K --> SELECT TC SENSOR TYPE
TC. L --> SELECT TC SENSOR TYPE
TC. N --> SELECT TC SENSOR TYPE
TC. R --> SELECT TC SENSOR TYPE
TC. S --> SELECT TC SENSOR TYPE
TC. T --> SELECT TC SENSOR TYPE
TC. U --> SELECT TC SENSOR TYPE
TC.W3 --> SELECT TC SENSOR TYPE
TC.W5 --> SELECT TC SENSOR TYPE
TC.LR --> SELECT TC SENSOR TYPE
DEC.P When temperature selected
1111 --> DECIMAL POINT POSITION
111.1 --> DECIMAL POINT POSITION
Fastset (Disabled):
SETP
xxxx --> RELAY SETPOINT - READ ONLY
Configuration menus:
ADV
YES
--> ENTER ADVANCED SETUP MENU?
NO
PASS
xxxx --> SET CORRECT PASSWORD
IN
C.LIN* --> TEXT ENTERED BY USER IN PRESET
CURR --> CURRENT INPUT
VOLT --> VOLTAGE INPUT
POTM --> POTENTIOMETER INPUT
LIN.R --> LINEAR RESISTANCE INPUT
TEMP --> TEMPERATURE SENSOR INPUT
RANG
When current selected:
0-20 --> INPUT RANGE IN mA
4-20 --> INPUT RANGE IN mA
RANG
When voltage selected:
0-10 --> INPUT RANGE IN VOLT
2-10 --> INPUT RANGE IN VOLT
0.0-1 --> INPUT RANGE IN VOLT
0.2-1 --> INPUT RANGE IN VOLT
DEC.P
1111 --> DECIMAL POINT POSITION
111.1 --> DECIMAL POINT POSITION
11.11 --> DECIMAL POINT POSITION
1.111 --> DECIMAL POINT POSITION
LR.LO
xxxx --> SET RESISTANCE VALUE LOW
LR.HI
xxxx --> SET RESISTANCE VALUE HIGH
DI.LO
xxxx --> DISPLAY READOUT LOW
--> DISPLAY READOUT HIGH
REL.U
PERC --> SET RELAY IN PERCENTAGE
DISP --> SET RELAY IN DISPLAY UNITS
TYPE
CU
--> SELECT CU SENSOR TYPE
PT
--> SELECT PT SENSOR TYPE
NI
--> SELECT NI SENSOR TYPE
TC
--> SELECT TC SENSOR TYPE
UNIT
°C
--> DISPLAY AND RELAY SETUP IN CELSIUS
°F
--> DISPLAY AND RELAY SETUP IN
FAHRENHEIT
5715V102-UK19
REL1
SET
--> ENTER RELAY 1 SETUP
SKIP --> SKIP RELAY 1 SETUP
OFF
--> RELAY 1 DISABLED
SETP
xxxx --> RELAY SETPOINT
ACT1
INCR --> ACTIVATE AT INCREASING SIGNAL
DECR --> ACTIVATE AT DECREASING SIGNALL
HYS1
xxxx --> RELAY HYSTERESIS
ERR1
HOLD --> HOLD RELAY AT ERROR
ACTI --> ACTIVATE RELAY AT ERROR
DEAC --> DEACTIVATE RELAY AT ERROR
NONE --> UNDEFINED STATUS AT ERROR
ON.DE
xxxx --> RELAY ON-DELAY IN SECONDS
OF.DE
xxxx --> RELAY OFF-DELAY IN SECONDS
RELX (X = 2...4)
SET
--> ENTER RELAY 2 SETUP
SKIP --> SKIP RELAY 2 SETUP
OFF
--> RELAY 2 DISABLED
SETP
xxxx --> RELAY SETPOINT
ACTX (X = 2...4)
INCR --> ACTIVATE AT INCREASING SIGNAL
DECR --> ACTIVATE AT DECREASING SIGNAL
HYSX (X = 2...4)
xxxx --> RELAY HYSTERESIS
ERRX (X = 2...4)
HOLD --> HOLD RELAY AT ERROR
ACTI --> ACTIVATE RELAY AT ERROR
DEAC --> DEACTIVATE RELAY AT ERROR
NONE --> UNDEFINED STATUS AT ERROR
ON.DE
xxxx --> RELAY ON-DELAY IN SECONDS
OF.DE
xxxx --> RELAY OFF-DELAY IN SECONDS
A.OUT
0-20 --> OUTPUT RANGE IN mA
4-20 --> OUTPUT RANGE IN mA
20-0 --> OUTPUT RANGE IN mA
20-4 --> OUTPUT RANGE IN mA
O.LO
xxxx --> DISPLAY VALUE FOR OUTPUT LOW
O.HI
xxxx --> DISPLAY VALUE FOR OUTPUT HIGH
O.ERR
23 mA -->
3,5 mA -->
0mA -->
NONE -->
RESP
xxx.x --> ANALOGUE OUTPUT RESPONSE TIME
IN SECONDS
E.PAS
NO
--> ENABLE PASSWORD PROTECTION
YES
N.PAS
xxxx --> SELECT NEW PASSWORD
ADV MENU:
LANG --> ENTER LANGUAGE SETUP
DISP --> ENTER DISPLAY SETUP
CAL
--> PERFORM PROCESS CALIBRATION
HLP.T
DE
-->
DK
-->
ES
-->
FR
-->
IT
-->
SE
-->
UK
-->
CZ
-->
LIGH
xxxx
DE - WAEHLE DEUTSCHEN HILFETEXT
DK - VAELG DANSK HJAELPETEKST
ES - SELECCIONAR TEXTO DE
AYUDA EN ESPANOL
FR - SELECTION TEXTE D’AIDE
EN FRANCAIS
IT - SELEZIONARE TESTI DI
AIUTO ITALIANI
SE - VALJ SVENSK HJALPTEXT
UK - SELECT ENGLISH HELPTEXT
CZ - VYBER CESKOU NAPOVEDU
--> ADJUST DISPLAY LIGHT INTENSITY
CA.LO
YES
--> CALIBRATE INPUT LOW TO PROCESS
VALUE?
NO
CA.HI
YES
--> CALIBRATE INPUT HIGH TO PROCESS
VALUE?
NO
VAL.L
xxxx --> SET VALUE FOR LOW CALIBRATION
POINT
VAL.H
xxxx --> SET VALUE FOR HIGH CALIBRATION
POINT
USE.C
YES
--> USE PROCESS CALIBRATED VALUES?
NO
NAMUR NE43 UPSCALE AT ERROR
NAMUR NE43 DOWNSCALE AT ERROR
DOWNSCALE AT ERROR
UNDEFINED OUTPUT AT ERROR
205715V102-UK
Configuration / operating
the function keys
Documentation for the routing diagram
In general:
When configuring the display you are guided through all parameters, allowing you
to choose the settings which fit the application. For each menu there is a scrolling help text which is automatically shown in the display if no key has been
activated for appr. 5 seconds.
Configuration is carried out by way of the 3 function keys 1 2 and 3.
1 will increase the numerical value or choose the next parameter. 2 will
decrease the numerical value or choose the previous parameter. 3 will accept
the chosen value and go to the next menu. If a function does not exist in the
hardware, all parametres belonging to that function will be skipped in order to
make configuration as simple as possible. The configuration will not be saved
until the end of the menu structure when the display shows - - - -.
Pressing and holding 3 will return to the previous menu or go back to the default
state (1.0) without saving the changed values or parameters.
If no key is activated for 2 minutes, the display will return to the default state
(1.0) without saving the changed values or parameters.
Furhter explanations:
Fast setpoint adjustment and relay test: These menus are interactive and allow
you to adjust the setpoints while the display is measuring the input signal.
The diodes will then indicate when the relays change state, thus easing the
setpoint adjustment in many situations. By activating 1 and 2 simultaneously, a relay test will be initiated and the relay will change state. The setpoint
adjustment will be saved by a quick press of 3 . Holding down 3 for more that
0.5 seconds wil return the display to the default state (1.0) without changing
the setpoint.
Password protection: Using a password will block access to the menu and parameters. There are two levels of password protection. Passwords be­tween 0000
and 4999 allow access to the fast setpoint adjustment and relay test menus
(using this password blocks access to all other parts of the menu). Passwords
between 5000 and 9999 block access to all parts of the menu, fast setpoint
and relay test (current setpoint is still shown). Default password 2008 allows
access to all configuration menus.
5715V102-UK21
Programming via PC
By way of PReset, a simple yet sophisticated PC program, all operational parameters in the 5715 can be quickly configured to suit any application. Furthermore,
the PC configuration allows you to set up a customer-defined input type for the
input signals current, voltage, resistance and potentiometer. This input type
can be defined with special input spans, e.g. 5...12 mA, and customer-defined
linearisation with or without offset. The customer-defined input type is saved
in the 5715 in the input menu C.LIN. If the display is later configured by way
of the front keys for e.g. temperature input, the input type C.LIN containing all
the original parameters can be subsequently selected. The PC configuration is
sent to the display by way of the communications interface USB Loop Link.
Graphic depiction of the relay function setpoint
100
100
Relay units
90
90
80
80
70
70
60
60
50
Relay units
Hysteresis = 10
50
Setpoint = 50
40
30
20
Off N.O.
On N.O.
Off N.O.
10
On N.C.
Off N.C.
On N.C.
0 10203040506070 8090100
Relay action: Increasing
Setpoint = 50
40
Hysteresis = 10
30
t
20
Off N.O.
On N.O.
Off N.O.
10
On N.C.
Off N.C.
On N.C.
0 10203040506070 8090100
Relay action: Decreasing
225715V102-UK
t
Displays
Programmable displays with a wide
selection of inputs and outputs for display of temperature,
volume and weight, etc. Feature linearization, scaling, and
difference measurement functions for programming via
PReset software.
Ex interfaces Interfaces for analog and digital signals as
well as HART® signals between sensors / I/P converters /
frequency signals and control systems in Ex zone 0, 1 & 2
and for some devices in zone 20, 21 & 22.
Galvanic isolators for analog and digital
Isolation
signals as well as HART® signals. A wide product range
with both loop-powered and universal isolators featuring
linearization, inversion, and scaling of output signals.
Temperature A wide selection of transmitters for DIN
form B mounting and DIN rail devices with analog and
digital bus communication ranging from applicationspecific to universal transmitters.
Universal
PC or front programmable devices with
universal options for input, output and supply. This range
offers a number of advanced features such as process
calibration, linearization and auto-diagnosis.
www.prelectronics.fr
[email protected]
www.prelectronics.de
[email protected]
www.prelectronics.es
[email protected]
www.prelectronics.it
[email protected]
www.prelectronics.se
[email protected]
www.prelectronics.com
[email protected]
www.prelectronics.com
[email protected]
www.prelectronics.cn
[email protected]
www.prelectronics.be
[email protected]
Head office
Denmarkwww.prelectronics.com
PR electronics A/S
Lerbakken 10
DK-8410 Rønde
[email protected]
tel. +45 86 37 26 77
fax +45 86 37 30 85