Buderus Logamatic EMS RC35 Installation And Service Instructions Manual

Installation and service instructions 6 720 618 477-00.1RS Room controller For contractors RC35 programming unit Read carefully before installation and servicing. 6 720 642 298 (10/2009) GB Logamatic EMS Contents Contents Guide to instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1 Key to symbols and safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.1 Key to symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2 Product information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.1 Correct use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.2 EU Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3 Standard delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.4 Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5 Validity of these instructions for function modules (accessories) . . . . . . . . . . . . . . . . . . 2.6 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.1 Choosing the right installation position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.1.1 Installation in reference room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.1.2 Installation on boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.2 Types of installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.3 Installation and connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.4 Attaching or removing the programming unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 10 10 11 11 12 13 4 Principles of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1 Overview of controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.2 Introduction to the service menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3 Overview of the service menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 14 15 17 5 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1 General commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.2 Checklist: important parameters for commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3 Quick commissioning (menu quick operation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.4 Detailed commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.5 System handover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.6 Shutting down/switching off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.7 Operating information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 18 19 20 21 21 22 22 2 7 7 7 7 8 9 9 Logamatic EMS RC35 programming unit - Subject to technical modifications Contents 6 System settings (Service menu – Settings) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.1 Plant data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.1.1 Building type (adjusting the outside temperature) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.1.2 Minimum outside temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2 Boiler data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.3 Heating circuit data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.3.1 Assignment of programming unit/remote control unit in the software . . . . . . . . . . . . . . 6.3.2 Control mode (outside temp. contr./room influence) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.3.3 Heating curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.3.4 Setback modes (night setback) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.3.5 Frost protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.4 DHW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.5 Solar data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.6 RC35 calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.7 Contact details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 23 24 25 26 27 31 31 32 33 34 36 39 40 41 7 Diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.1 Function test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.2 Monitor value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.3 Error message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.4 Heating curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.5 Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 42 43 44 45 45 8 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 9 Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 10 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 11 Service menu RC35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Logamatic EMS RC35 programming unit - Subject to technical modifications 3 Guide to instructions Guide to instructions These installation and service instructions contain all information on the function and settings of the Logamatic RC35 programming unit. Introduction to the service menu Chapter 4.2 explains in detail the steps needed for programming all the settings in the service menu. Operation is only briefly dealt with in the following sections. Display texts Words appearing on the display are shown in bold in flowing text. Example: USER MENU 4 USER MENU standard display operation modes switching programme sum./win. threshold Logamatic EMS RC35 programming unit - Subject to technical modifications Key to symbols and safety instructions 1 1 Key to symbols and safety instructions 1.1 Key to symbols Warning information Warnings in this document are identified by a warning triangle and printed against a grey background. If there is a danger due to electricity, the exclamation mark in the warning triangle is replaced by a lightning symbol. Signal words at the start of a warning indicate the type and seriousness of the ensuing risk if measures to prevent the risk are not taken. • NOTE indicates that material losses may occur. • CAUTION indicates that minor to medium injury may occur. • WARNING indicates that severe injury may occur. • DANGER indicates a risk to life. Important information Important information where there is no risk to people or property is indicated with the adjacent symbol. It is bordered by horizontal lines above and below the text. Additional symbols Symbol Explanation B Action step Æ Cross-reference to other parts of this document or to other documents • List/list entry – List/list entry (second level) Tab. 1 Logamatic EMS RC35 programming unit - Subject to technical modifications 5 1 Key to symbols and safety instructions 1.2 Safety instructions Installation and commissioning B Observe these instructions to ensure correct operation. B The appliance must only be installed and commissioned by an authorised installer. Risk to life from electric shock B The power supply must be connected by a qualified electrician. B Observe the connection diagram. B Before installation: isolate all poles of the power supply (230 V AC). Secure against unintentional reconnection. B Never install this appliance in wet rooms. B Never connect this appliance to the 230 V mains. Risk of damage due to operator error Operator errors can lead to injuries and/or material losses. B Ensure that children never operate this appliance unsupervised or play with it. B Ensure that only individuals who can operate this appliance correctly have access to it. Warning: frost The heating system can freeze up in cold weather if it is not in operation. B Leave the heating system permanently switched on. B Enable frost protection. B In case of faults: immediately remedy the fault. 6 Logamatic EMS RC35 programming unit - Subject to technical modifications Product information 2 2 Product information 2.1 Correct use The RC35 programming unit must only be used to operate and control Buderus heating systems. B Always use this appliance correctly and in conjunction with the specified control systems. B Observe all regulations and standards applicable to the installation and operation of the system in your country! The boiler must be equipped with EMS (energy management system) or UBA1.x (universal burner controller). Never operate the programming unit with the control units of the Logamatic 2000/4000 series. We recommend always operating the heating system with the programming unit (only emergency operation possible without programming unit). If using remote control units RC2x produced before or in 2005, only two remote control units can be connected. In case of related questions, please contact your local Buderus sales office. These instructions describe all possible functions of the RC35 programming unit. Some of these functions may not be available, depending on which boiler (combustion controller) is used. You will find information on this in the relevant chapter. For information regarding the combustion controller, see menu DIAGNOSIS\VERSIONS (Æ page 45). 2.2 EU Declaration of Conformity The design and operation of this product conform to the European Directives and the supplementary national requirements. Its conformity is demonstrated by the CE designation. You can call up the Declaration of Conformity for this product on the internet at www.buderus.de/konfo or request it from your local Buderus sales office. 2.3 Standard delivery • • • • RC35 programming unit Operating instructions Installation and service instructions Wall mounting base, mounting materials Logamatic EMS RC35 programming unit - Subject to technical modifications 7 2 Product information 2.4 Specification Unit V W W mm g °C °C % Power supply via BUS system Power consumption Power consumption with backlighting Dimensions (width/height/depth) Weight Operating temperature Storage temperature Relative humidity CE designation Tab. 2 RC35 16 V DC 0.3 0.6 150/90/32 233 0 to +50 0 to +70 0 to 90 Specification - RC35 programming unit Temperature sensor characteristics When measuring temperature sensors, observe the following requirements: • Isolate the system before measuring. • Measure the resistance at the cable ends. • The resistances represent mean values and are subject to tolerances. Flow temperature sensor Outside temperature sensor °C kΩ – 20 96.358 – 15 72.510 – 10 55.054 –5 42.162 0 32.556 5 25.339 10 19.872 15 15.699 20 12.488 25 10.001 30 8.060 Tab. 3 8 DHW temperature sensor °C kΩ 10 19.872 16 15.699 20 12.488 25 10.001 30 8.060 35 6.535 40 5.331 45 4.372 50 3.606 55 2.989 °C 60 65 70 75 80 85 90 95 100 kΩ 2.490 2.084 1.753 1.481 1.256 1.070 0.915 0.786 0.677 Resistances of the temperature sensors, for EMS only Logamatic EMS RC35 programming unit - Subject to technical modifications Product information 2 2.5 Validity of these instructions for function modules (accessories) These instructions also apply to the programming unit when used in conjunction with the MM10 mixer module and the WM10 low loss header module. Additional setting options may be found in some menus, if your heating system is equipped with alternative function modules (e.g. solar module SM10). These setting options are explained in a separate manual. 2.6 Accessories For detailed information regarding suitable accessories, see the catalogue. • Mixer module MM101) for control of a 3-way valve. A description of the MM10 is included in the RC35 instructions. • Low loss header module WM101) for operating a low loss header • Solar module and additional EMS modules (e.g. connection module ASM10)1) • Remote control1) (e.g. RC2x, RC20/RF) respectively for controlling one heating circuit • Outside temperature sensor, external room temperature sensor 1) The use of modules is not possible for boilers with UBA1.x or DBA. Logamatic EMS RC35 programming unit - Subject to technical modifications 9 3 3 Installation Installation 3.1 Choosing the right installation position 3.1.1 Installation in reference room If the system is room-temperature controlled, the following requirements must be observed: • Installation position on an internal wall (Æ Fig. 1) • Maintain the specified distance from the door (to avoid draughts). • Allow clearance below the programming unit (Æ Fig. 1, shaded area) (to ensure correct temperature measurement). • The reference room (= installation room) must be as representative as possible of the entire home. External heat sources in the reference room (e.g. sunlight or other heat sources such as an open fire) affect the control functions. This means it may be too cold in rooms without external heat sources. • Always open the thermostatic radiator valves fully in the reference room to prevent the two temperature controllers influencing each other. If there is no suitable reference room, we recommend setting the system to weathercompensated control instead (this requires an outside temperature sensor). Alternatively, you could install an external room temperature sensor in the room with the greatest heating requirements (e.g. living room). 6 720 618 477-01.1RS Fig. 1 10 Minimum clearances for installation in a reference room Logamatic EMS RC35 programming unit - Subject to technical modifications Installation 3 3.1.2 Installation on boiler Installation directly on the boiler is possible where the boiler is equipped with the Energy Management System (EMS). The outside temperature sensor for weather-compensated control is not delivered as standard, but can be ordered as an accessory. 3.2 Types of installation The programming unit can be installed in three different ways: • As only programming unit in the system (factory setting): the programming unit is installed in the living space (reference room) or on the boiler. Example: detached house with one heating circuit. • As the only programming unit in a heating system with two or more heating circuits1) (Æ Fig. 2 [1]). Examples: underfloor heating on one floor, radiators on the others; or a main flat together with a separate granny flat or doctor's surgery. • In conjunction with a remote control (e.g. RC2x, RC20/RF, Fig. 2, [2]). In this case there are always two separate heating circuits. Remote control units cannot be used for boilers with UBA1.x. Examples: underfloor heating on one floor, radiators on the others; or a main flat together with a separate granny flat or doctor's surgery. 1 2 HC1 HC1 HC2 HC2 6 720 641 642-01.1RS Fig. 2 1 2 Options for a heating system with two heating circuits Both heating circuits are controlled by one programming unit. Each heating circuit has its own programming unit / remote control unit. 1) Not possible with boilers with UBA1.x and DBA. Logamatic EMS RC35 programming unit - Subject to technical modifications 11 3 Installation 3.3 Installation and connections Only use the wall mounting base with screw terminals. B Replace wall mounting bases without screw terminals that may already be installed. The wall mounting base can be attached directly to the wall or on a flush box. When mounting on a flush box, note the following: B Draught from within the flush box must not be able to falsify the capture of the room temperature by the programming unit. If required, stuff the flush box with insulation material. B Use horizontal or vertical fixing holes [4]. B Fit the wall mounting base (Æ Fig. 3, left). B Connect the two-core BUS cable from the Energy Management System (EMS) at terminals “RC” [5]. – Cable type: 2 x 0.75 mm2 (0.5 – 1.5 mm2), max. length 100 m – Polarity is irrelevant for the two wires. B Do not lay the cables parallel to power cables. 1 3 2 5 4 6 4 1 3 2 6 720 618 477-03.1RS Fig. 3 1 2 3 4 5 6 12 Mounting the wall mounting base (left) and connecting the wires (right) Hole drilled in the wall Screws (included with the unit) for surface-mounting on the wall Vertical mounting holes for mounting on a flush box Horizontal mounting holes for mounting on a flush box “RC” terminals for EMS (boiler) “EXT” terminals for external room temperature sensor or for jumper Logamatic EMS RC35 programming unit - Subject to technical modifications Installation 3 B A jumper is required at terminals “EXT” [6] (delivered condition) if the RC35 programming unit is operated without an external room temperature sensor. B If the RC35 programming unit operates together with an external room temperature sensor, remove the factory-fitted jumper at “EXT” and connect the external room temperature sensor in its place. 3.4 Attaching or removing the programming unit Attaching the programming unit 1. Hook the programming unit at the top into the mounting plate in the direction of the arrow. 2. Push the programming unit at the bottom in the direction of the arrow against the mounting plate until it clicks into place. 1. 2. 6 720 618 477-04.1RS Fig. 4 Attaching the programming unit Removing the programming unit 1. Press the button underneath the mounting plate in the direction of the arrow. 2. At the same time pull the programming unit forwards. 3. Remove the programming unit by lifting upward. 3. 2. 1. Fig. 5 6 720 618 477-10.1RS Removing the programming unit Logamatic EMS RC35 programming unit - Subject to technical modifications 13 4 4 Principles of operation Principles of operation 4.1 Overview of controls Key to diagram: 1 2 Flap; pull the recessed grip on the left to 3 4 open 2 Display 3 Rotary selector for changing values and temperatures or for navigating through the menus 1 4 Buttons for basic functions: When the LED lights up, “AUT” (automatic) • “Daytime operation” (manual) • 5 6 720 618 477-08.1RS the switching program is active (automatic changeover between day and night room temperatures). the heating system operates at the set day room temperature. DHW heating is enabled (factory setting). “Nighttime operation” (manual) • the heating system operates at the set nighttime room temperature. Frost protection is active. DHW heating is off (factory setting). “DHW” • the DHW temperature has fallen below its set value. Pushing this key means DHW will be heated up again (the LED flashes during heat-up). 5 Buttons for additional functions: Function: “Menu/OK” Open the user menu and confirm the selection. “Time” Set the time. “Date” Set the date. “Temperature” Set the room temperature. “Info” Open the Info menu (to view values). “Back” Go back one step or one menu item. When rotary selector is turned at the same time: change setting. In Automatic mode, an additional LED lights up with the “AUT” LED to indicate which operating status is currently active (“day mode” or “night mode”). Exception: in the case of boilers with UBA1.x, only the “AUT” LED lights up. The “DHW” LED can also be switched off. On boilers with UBA1.x the “DHW” LED does not illuminate. 14 Logamatic EMS RC35 programming unit - Subject to technical modifications Principles of operation 4 4.2 Introduction to the service menu You can use the SERVICE MENU to set the parameters for the system. It also contains functions for diagnosis, maintenance purposes, and carrying out a reset. The procedure for operation is always the same: 1. 2. 3. 4. 5. Open the flap (by pulling the recessed grip on the left). Press + + at the same time to open the SERVICE MENU. Turn rotary selector to change the selection. Press to make your selection. To change the value, hold down (the value starts flashing) and turn rotary selector same time. Release . The modified value is saved. 6. Press to go back one step. Press several times or close the flap to show the standard display again. at the Example: Setting the building type (adjusted time) Operation 1. Open the flap (by pulling the recessed grip on the left). 2. Press + + simultaneously, to open the SERVICE MENU. Result Fr outside temp. h 1 SERVICE MENU Bquick operation settings diagnosis servicing 3. Turn rotary selector anti-clockwise, until settings is selected. Press to confirm the selection. SERVICE MENU quick operation Bsettings diagnosis servicing Tab. 4 How to use the service menu (example) Logamatic EMS RC35 programming unit - Subject to technical modifications 15 4 Principles of operation Operation 4. 5. Result The SERVICE\SETTINGS menu opens. Turn rotary selector anti-clockwise until boiler data is selected. Press to select boiler data. Menu SETTINGS\BOILER opens. SERVICE\SETTINGS Bplant data boiler data domestic hot water heating circuit 1 SETTINGS\BOILER What type of building do you have? medium 6. To change the value, hold down (the value starts flashing) and turn rotary selector same time. at the SETTINGS\BOILER What type of building do you have? medium 7. Release . The value stops flashing. The modified value is saved. SETTINGS\BOILER What type of building do you have? light 8. If you have carried out this example as practice only, make sure that the original setting is retained. To do so, repeat steps 6 and 7 if necessary. SETTINGS\BOILER What type of building do you have? medium 9. Press to go back one step. -orTo finish entering the settings: press shut the flap. several times or The standard display re-appears. You can enter all settings in the SERVICE MENU using this procedure. Tab. 4 16 How to use the service menu (example) Logamatic EMS RC35 programming unit - Subject to technical modifications Principles of operation 4 4.3 Overview of the service menu The SERVICE MENU is divided into the following menus and submenus: Menu quick operation settings (all parameters) diagnosis servicing1)2) Reset1) Tab. 5 Submenu Contents/function The most important parameters from the “settings” menu to configure the heating system plant data1) Parameters: language, number of heating circuits, installed modules, building type, minimum outside temperature Parameters: pump run-on time and modulation boiler data1)2) 1) heating circuit data Parameters of the installed heating circuits domestic hot water1) Parameters for domestic hot water solar data2) If solar is installed: see documentation for the solar module RC35 calibration Parameters: calibration of the displayed room temperature contact data Entering the heating contractor's name and telephone number Activating individual components for test function test1)2) purposes monitor value Viewing target values and actual values Viewing error messages error message1) htg. charact. curve Viewing the set heating curve in the form of a graph versions Viewing software versions service interval Setting times for maintenance, by hours run or by date current messages Viewing service messages RESET servicing Resetting service messages factory setting Resetting all parameters to their factory settings error list service message operating hours Page 20 23 26 27 36 39 40 41 42 43 44 45 45 46 46 46 47 47 47 47 Service menu navigator 1) Limited use depending on the boiler used. 2) May not be available or possible, depending on the boiler used. Logamatic EMS RC35 programming unit - Subject to technical modifications 17 5 5 Commissioning Commissioning 5.1 General commissioning Operation 1. Result Switch on the heating system. While setting up the connection between the RC35 and EMS or UBA1.x, the display shows the message on the right. RC35 version: connect to: connection setup ... please wait If the display shows a different message, look it up in Chapter 10, page 48. 2. Set the language: Open flap. Hold down rotary selector . and select the language with Open cover in order to set language with OK key. language set: English 3. Set the date and time: SET DATE Hold down and set the flashing values with rotary selector . Release button. set year Hold down and set the flashing values with rotary selector . Release button. 01.01.2000 In the event of a power failure, the date and time are retained for up to 8 hours. All other settings are saved. 4. Press + + SERVICE MENU. simultaneously, to open the SERVICE MENU Bquick operation settings diagnosis servicing Tab. 6 General commissioning If necessary, you can change the contrast on the display: B Hold down and and turn rotary selector at the same time. 18 Logamatic EMS RC35 programming unit - Subject to technical modifications Commissioning 5 5.2 Checklist: important parameters for commissioning When commissioning the device, ensure the satisfaction of both parties, making sure that the heating system meets the customer's needs and will not give cause for complaints. In our experience, the following parameters are very important for the satisfaction of the system user: B Find out the system owner's requirements and preferences regarding: Setting options Factory setting SERVICE MENU\ settings\ The required type of reduction (night setback) Outdoor setback mode; reduced operation; Room setback mode; shut-down mode Outdoor setback mode heating circuit x, page 28 The required control mode outside temp. contr., room temp. controlled outside temp. contr. heating circuit x, page 31 The correct heating curve By means of the following parameters: design temperature, minimum outside temperature, offset, and set room temperature The correct building type (adjusting the outside temp.) light, medium, heavy medium plant data, page 24 The switching frequency of the DHW circulation pump1) permanent operation, 1 x, 2 x, 3 x, 4 x, 5 x, 6 x per hour for 3 minutes at a time 2x domestic hot water, page 37 Priority DHW yes, no yes heating circuit x, page 29 Switching program (times) Standard program (e.g. family), user defined program family heating circuit x, page 30 Tab. 7 heating circuit x, page 28 Checklist: important parameters for commissioning 1) This function is not available for boilers with UBA1.x, DBA, UBA-H3 or for DHW heating according to the instantaneous water heating principle. Logamatic EMS RC35 programming unit - Subject to technical modifications 19 5 Commissioning 5.3 Quick commissioning (menu quick operation) B Press to open menu quick operation. SERVICE MENU Bquick operation settings diagnosis servicing SHORTCUT\ BASIC SETUP HYDR. SEP. Input Menu item range Which language should English, ... be used? Have you installed a yes, no module for the hydraulic separator? Is a sensor for a low loss header connected? SYSTEM NO. OF MIXERS Is heating circuit 1 installed (unmixed heating circuit)? How many mixed heating circuits are installed? HEATING CIRCUIT Which operating unit is 1 assigned to heating circuit 1? (and other heating circuits) How should heating circuit 1 be controlled? Which heating system does heating circuit 1 have? Tab. 8 20 Factory setting Francais no no, no on the boiler, on the low loss header module yes, no yes 0 to 3 0 RC2x/ RC20/RF, RC35, none outside temp. contr., room temp. controlled radiator, convector, floor RC35 outside temp. contr. radiator Other information In conjunction with MCM10 this setting is automatically set to “yes”; the mask is hidden.1)2) When a low loss header is used, connect the temperature sensor to the low loss header module.3) Set the address at the rotary coding switch on the mixer module (factory setting HC2).1) Assigning programming units to heating circuits (Æ page 31). General heating circuit data (Æ page 27). Set up any other heating circuits as per heating circuit 1. Heating curve (Æ page 32) Quick operation menu navigator Logamatic EMS RC35 programming unit - Subject to technical modifications Commissioning SHORTCUT\ DHW 5 Menu item Have you installed domestic hot water? What should be used for domestic hot water heating? To which temperature should your domestic hot water be heated? SOLAR MODULE Tab. 8 Have you installed a solar module? Input range yes, no Factory setting no 3-way switching valve cylinder primary pump 30 °C to 80 °C 3-way switching valve 5) 60 °C To be able to change the DHW temperature, set DHW on the boiler programming unit to “AUT” or enable DHW. yes, no no 1) Other information 4) Quick operation menu navigator 1) Not possible or available on boilers with UBA1.x or DBA. 2) Not possible on boilers with UBA4. 3) Only possible on boilers with UBA4. 4) Not possible or not available with boilers with DBA. 5) Not available with boilers with UBA1.x, DBA or UBA-H3. Check whether further settings are required using the checklist on page 19. 5.4 Detailed commissioning B Check whether the factory settings in menu SERVICE\SETTINGS suit your heating system. B Note down modified settings if needed. 5.5 System handover B Ensure that no temperature limits for central heating and DHW have been set at the boiler programming unit, so DHW and flow temperature can be regulated via the RC35 programming unit. B Explain to the customer how the device works and how to operate it. B Inform customer about the selected settings. Logamatic EMS RC35 programming unit - Subject to technical modifications 21 5 Commissioning We recommend you hand these installation and service instructions to the customer for safekeeping near the heating system. 5.6 Shutting down/switching off The RC35 programming unit is powered via the heating system and remains permanently ON. The heating system is only switched off, for example, for maintenance work. B To start up and shut down the heating system: set the ON/OFF switch on the boiler programming unit to 1 (ON) or 0 (OFF). After shutting down or in the event of a power failure, the date and time are retained for up to 8 hours. All other settings are retained permanently. 5.7 Operating information EMS BUS subscribers In a BUS system, only one subscriber can carry out the calculations for a heating circuit. Consequently, only one RC35 programming unit may be installed in each heating system. If additional room controllers (e.g. RC2x) are required, these must be installed as remote control units1) with a set heating circuit address (Æ page 27). Disable this on boilers with integral weather-compensated control. Thermostatic radiator valves in the reference room Radiators in the reference room do not require thermostatic valves2) for room temperaturedependent control. Fully open any thermostatic radiator valves in the reference room. Pump kick1) In all operating modes, all the heating circuit pumps are switched on and then off again for 10 seconds every Wednesday at 12 noon to prevent pump damage. The mixers are then set to “OPEN” for 10 seconds and then “CLOSED”. All pumps and mixers then return to their normal, regulated operation. 1) This function is not available on boilers with UBA1.x or DBA. 2) Room where a RC35 or RC2x/RC20/RF is installed. 22 Logamatic EMS RC35 programming unit - Subject to technical modifications System settings (Service menu – Settings) 6 6 System settings (Service menu – Settings) B Press + + simultaneously to open the SERVICE MENU. B Turn rotary selector anti-clockwise, until settings is selected. B Press to open menu SERVICE\SETTINGS. SERVICE MENU quick operation Bsettings diagnosis servicing Note that the menu items shown will vary depending on the heating system. 6.1 Plant data B Press to select plant data. The menu SETTINGS\SYSTEM opens. SERVICE\SETTINGS Bplant data boiler data domestic hot water heating circuit 1 Input Menu item range Which language should be used? English, ... Have you installed a module for yes, no the hydraulic separator? Is a sensor for a low loss header connected? Is heating circuit 1 installed (unmixed heating circuit)? How many mixed heating circuits are installed? Have you installed a solar module? Tab. 9 Factory setting Francais no no, no at the boiler, at the low loss header module yes, no yes Other information In conjunction with MCM10, this setting is automatically set to “yes”; the mask is hidden.1)2) When a low loss header is used, connect the temperature sensor to the low loss header module.3) 0 to 3 0 Set the address at the rotary coding switch on the mixer module (factory setting HC2).1) yes, no no 1) Navigator for service menu SETTINGS\SYSTEM Logamatic EMS RC35 programming unit - Subject to technical modifications 23 6 System settings (Service menu – Settings) Input Menu item range Should the outside temp. damping yes, no be switched off? What type of building do you have? What is the lowest expected outside temp. in your region? Tab. 9 Factory setting no light, medium medium, heavy – 30 °C to – 10 °C 0 °C Other information When selecting “yes” the following parameter building type will be hidden. Building type (heat storage capacity), Æ Chapter 6.1.1, page 24. Æ Chapter 6.1.2, page 25 Navigator for service menu SETTINGS\SYSTEM 1) Not possible or available on boilers with UBA1.x or DBA. 2) Not possible on boilers with UBA4. 3) Only possible on boilers with UBA4. 6.1.1 Building type (adjusting the outside temperature) A building's heat storage capacity and its characteristic resistance to heat transfer will delay the effect of outside temperature fluctuations on the rooms inside. Consequently, it is not the current outside temperature that is crucial but the so-called adjusted outside temperature. Parameter building type enables the adjustment to be applied that takes account of the fluctuating outside temperatures. This enables the control to be matched to the characteristics of the building. The control unit calculates the time constant for adjusting the outside temperature, using the factor given in Tab. 10 for the stated building type and an internal multiplier, the “runtime” (= 6 minutes). The time constant is the product of: factor x runtime = adjustment time constant in hours. Parameter: building type light medium heavy Type of construction E.g. prefabricated building, wood-frame construction E.g. a building constructed of hollow breeze blocks (factory setting) E.g. brick house Factor 10 30 50 Tab. 10 Calculating the adjustment time constant 24 Logamatic EMS RC35 programming unit - Subject to technical modifications System settings (Service menu – Settings) 6 Example: 2 1 6 720 618 477-05.1RS Fig. 6 1 2 This greatly simplified example shows how the adjusted outside temperature follows the outside temperature, but does not reach its extreme values. Current outside temperature Adjusted outside temperature With the factory settings, changes in the outside temperature affect the calculation of weather-compensated control after no more than three hours (30 x 6 minutes = 180 minutes). B To monitor the calculated, adjusted outside temperature and the currently captured outside temperature: open the menu diagnosis\monitor valueboiler / burner. 6.1.2 Minimum outside temperature The minimum outside temperature is the mean of all the coldest outside temperatures of recent years, and helps to determine the heating curve. The value can be taken from the heat requirement calculation which should be done for every building, or from the climatic zone chart for your region. Logamatic EMS RC35 programming unit - Subject to technical modifications 25 6 System settings (Service menu – Settings) 6.2 Boiler data B Turn rotary selector anti-clockwise until boiler data is selected. B Press to select boiler data. The menu SETTINGS\BOILER is opened. SERVICE\SETTINGS plant data Bboiler data domestic hot water heating circuit 1 Factory Menu item Input range setting Boiler pump after-run time deactivated, 5 min after burner stops? 1 to 60 min, 24 h Set the pump logic 0 to 65 °C 47 °C temperature: Other information Setting only possible with boilers with internal pump.1) Setting only possible in conjunction with BRM10. Tab. 11 Navigator for service menu SETTINGS\BOILER 1) Not possible or not available with boilers with UBA1.x. 26 Logamatic EMS RC35 programming unit - Subject to technical modifications System settings (Service menu – Settings) 6 6.3 Heating circuit data This chapter explains the settings for all heating circuits using heating circuit 1 as an example. B Turn rotary selector anti-clockwise until heating circuit 1 is selected. B Press to select heating circuit 1. SERVICE\SETTINGS The menu SETTINGS\HTG. CIRC. 1 is opened. plant data boiler data domestic hot water Bheating circuit 1 Menu item Should heating circuit 1 be activated? Which operating unit is assigned to heating circuit 1? How should heating circuit 1 be controlled? Which heating system does heating circuit 1 have? Input range yes, no RC2x/RC20/RF, RC35, none Factory setting yes Other information RC35 See page 31. For UBA1.x, RC2x is not available. outside temp. contr., room temp. controlled outside temp. contr. radiator, convector, floor radiator If “none” is selected, then the type of control is changed over to “outside temp. contr.” and is then hidden. “room temp. controlled” can only be set if RC2x or RC35 have been assigned. When selecting “room temp. controlled” room flow will be used. In case of HC1 setting “floor” only if this concerns an oil/gas condensing boiler. Additional heating circuits can then be installed. Use a safety thermostat with underfloor heating systems. Tab. 12 Navigator for service menu SETTINGS\HTG. CIRC. 1 Logamatic EMS RC35 programming unit - Subject to technical modifications 27 6 System settings (Service menu – Settings) Menu item Heating curve std. tmp. ( – 10 °C) Input range 30 °C to 90 °C Factory setting Other information 75 °C (radiator, convector) 45 °C (floor) radiator, convector: 75 °C The value in brackets is the setting for the minimum outside temperature (Æ page 27). Adjustment only if the control type is set to “outside temp. contr.” ( Æ page 32). max flow temp. radiator, Adjustment only if the control type is convector: set to “outside temp. contr.” 30 °C to 90 °C1) ( Æ page 32). Enter the maximum Adjustment only if the control type is floor: floor: 50 °C flow temperature: set to “room temp. contr.” 30 °C to 60 °C ( Æ page 32). min flow temp. 5 °C to 70 °C 5 °C Adjustment only if the control type is set to “outside temp. contr.” ( Æ page 32). Enter the minimum flow Adjustment only if the control type is temperature: set to “room temp. contr.” ( Æ page 32). rm. tmp. offset – 5.0 K to +5.0 K 0.0 K Offset of heating curve. Enter the maximum room influence: 0 K to 10 K 3K Which type of reduction should be implemented? Outdoor setback Outdoor mode, setback reduced operation, mode Room setback mode (only if RC35 or RC2x has been assigned to the heating circuit), shut-down mode Adjustment only if the control type is set to “outside temp. contr.” ( Æ page 32). Adjustment only if the control type is set to “outside temp. contr.” ( Æ page 31) Night setback (Æ page 33) Tab. 12 Navigator for service menu SETTINGS\HTG. CIRC. 1 28 Logamatic EMS RC35 programming unit - Subject to technical modifications System settings (Service menu – Settings) Menu item What outside temp. should be used for reduced operation? Frost protection What temp. should be used to trigger frost protection? Which frost protection temp. should be used? At what outside temp. should reduction be interrupted? Should domestic hot water priority be activated? Mixer2) Is a mixer installed? What running time does the mixer have? What increase should be used for the boiler? Screed drying2) Should a drying cycle be carried out? Every how many days should the flow temp. be raised? By how many Kelvin should the flow temp. be raised each time? Input range – 20 °C to +10 °C 6 Factory setting 5 °C Other information Temperature threshold for outdoor setback mode (Æ page 33). Adjustment only if the setback mode is set to “Outdoor setback mode”. outside temp., room temperature, no frost protection – 20 °C to +10 °C OFF, – 30 °C to +10 °C yes, no outside temp. yes, no yes Can only be set for heating circuit 2 onwards.2) 10 sec. to 600 sec. 0 K to 20 K 120 sec. 2) 5K 2) yes, no no Adjustment only if floor has been selected. DHW heating is not enabled while screed is drying.2) every day, every 2nd day to every 5th day 0 K to 40 K every day 2) 5K 2) 5 °C OFF Room temperature adjustment only if RC2x or RC35 have been assigned to the heating circuit (Æ page 34). Refers to outside temperature (Æ page 34). Setback in accordance with EN 12831 standard (Æ page 34). no Tab. 12 Navigator for service menu SETTINGS\HTG. CIRC. 1 Logamatic EMS RC35 programming unit - Subject to technical modifications 29 6 System settings (Service menu – Settings) Menu item What is the desired maximum flow temperature? For how many days should maximum flow temp. be maintained? Every how many days should the flow temp. be reduced? Input range 25 °C to 60 °C Factory setting 45 °C 0 days to 20 days 4 days direct normal Every day operat., every day, every 2nd day to every 5th day By how many K should 0 K to 20 K 5K the flow temp. be reduced each time? Do you wish to change yes, no no the switching programme? Should the switching yes, no no programme be optimised? What reduction mode should be used for holiday? What outside temp. should be used? Outdoor setback Outdoor mode, setback reduced operation, mode Room setback mode, shut-down mode – 20 °C to +10 °C 5 °C Other information 2) 2) 2) Adjustment only if, for flow temperature reduction,“direct normal operat.” has not been selected.4) When selecting “yes” the system jumps to the heating circuit switching program. Start and stop times are automatically adjusted according to the outside temperature, room temperature and building type (heat storage capacity). See page 33. Adjustment “Room setback mode” only if a remote control (e.g. RC2x) has been allocated to the heating circuit. If “reduced operation” has been selected, the standard night temperature will be applied. Temperature threshold for outdoor setback mode (Æ page 33). Adjustment only if setback mode for holiday was set to “Outdoor setback mode.” Tab. 12 Navigator for service menu SETTINGS\HTG. CIRC. 1 1) The setting range can be limited, subject to boiler. 2) Not possible or available on boilers with UBA1.x or DBA. 30 Logamatic EMS RC35 programming unit - Subject to technical modifications System settings (Service menu – Settings) 6 6.3.1 Assignment of programming unit/remote control unit in the software This function is not available with boilers with UBA1.x and DBA. Example: heating system with heating circuit 1 and heating circuit 2 (Æ page 11) Setting: Which operating unit is Alternative assigned to the heating circuit? A HC 1 = RC35, HC 2 = RC35 (Æ Fig. 2, [1], page 11) B HC 1 = none, HC 2 = RC35 (Æ Fig. 2, [1], page 11) C HC 1 = RC2x, HC 2 = RC35 (Æ Fig. 2, [2], page 11) Effect Same room temperatures for HC 1 and HC 2 Room temperatures for HC 1 and HC 2 can be set separately Room temperatures for HC 1 and HC 2 separately adjustable; adjust the room temperature for HC 1 at the RC2x Tab. 13 Settings for room temperature depending on programming unit 6.3.2 Control mode (outside temp. contr./room influence) The temperature of the heating water in the boiler is defined by the heating curve in the Logamatic control unit. You can select whether this heating curve will be influenced solely by the outside temperature, or by a mixture of outside temperature and room temperature. • outside temp. contr.: If this setting is entered, the boiler temperature calculated in the control unit will be regulated by variation in the adjusted outside temperature in combination with selected settings for set room temperature, offset, design temperature and minimum outside temperature. This temperature is then delivered to the radiators or underfloor heating system by means of permanent operation of the heating circuit pump. The only circumstances in which this setting can result in the heating circuit pump being switched off are summer mode, night setback (subject to the selected setback mode) or DHW mode (only with DHW priority). • outside temp. contr. with room temperature hook-up (factory setting): this form of control functions like a pure weather-compensated control with the difference that parameter maximum room influence enables the determination whether and to what extent the room temperature can influence the heating curve. The programming unit/remote control must be installed in a reference room to ensure that a representative room temperature is captured. The higher the parameter is set, the higher the proportion of the room temperature effect on the heating curve (factory setting 0 Kelvin). This applies when the room temperature exceeds or falls below the set room temperature. If the maximum room influence parameter is set to 0, the heating characteristics will be controlled solely by outside temperature. Logamatic EMS RC35 programming unit - Subject to technical modifications 31 6 System settings (Service menu – Settings) 6.3.3 Heating curve Parameters: design temperature, maximum and minimum flow temperature and room temperature offset (parallel offset) The heating curve is the basis for economical and comfortable operation of the heating system with weather-compensated control. To calculate this curve, the Logamatic control system requires you to enter a number of parameters for the heating system, from which it automatically calculates the optimum heating curve by means of a mathematical formula, taking the adjusted outside temperature and room control temperature into account. The room control temperature is an internal operand which is a combination of the required room temperature (set room temperature) and room influence. This can be used by the user to influence the heating curve directly by varying the set room temperature. The heating curve (Æ Fig. 7, page 33) is generally determined by its base and end points. The base point is located at 20 °C flow temperature at a room temperature of 20 °C with an adjusted outside temperature of 20 °C. The end point of the heating curve must be set in accordance with the design temperature of the heating system. The two parameters minimum outside temperature (the lowest outside temperature to be expected in a region, page 25) and std. temp. (the flow temperature that should be reached at minimum outside temperature) are crucial for the heating curve (level/slope) (Æ Fig. 7, left). The X-axis of the heating curve graph refers to the range from +20 °C to – 20 °C. For parameter std. temp. the minimum outside temperature set under system data is shown by a circle. However, if a minimum outside temperature below – 20 °C is entered, then the depiction is no longer accurate (the circle then lies away from the heating curve). The minimum flow temperature parameter can be used to define a minimum set value (Æ Fig. 7, [4], page 33). The burner starts again if the set value is no longer achieved. The heating curve is offset in parallel either up or down by adjusting parameter rm. tmp. offset and/ or the set room temperature (Æ Fig. 7, right, page 33). Setting the offset may be advisable should the room temperature measured by a thermometer deviate from the selected set value. 32 Logamatic EMS RC35 programming unit - Subject to technical modifications System settings (Service menu – Settings) 1 6 5 2 4 3 TA TA 6 T minA 7 T minA 6 720 618 477-06.1RS Fig. 7 Setting the heating curve. Left: setting the gradient by means of design temperature and minimum outside temperature. Right: parallel offset possible by means of offset or set room temperature. TminA Minimum outside temperature TA Design temperature (flow temperature that should be achieved at min. outside temperature) 1 Setting: design temperature 75 °C, minimum outside temperature – 10 °C (standard curve) 2 Setting: design temperature 75 °C, minimum outside temperature – 20 °C 3 Setting: design temperature 50 °C, minimum outside temperature – 10 °C 4 Setting: minimum flow temperature 35 °C 5 Setting: design temperature 75 °C, minimum outside temperature – 10 °C (standard curve) 6 Parallel offset of standard curve by changing the offset +3 or by increasing the set room temperature 7 Parallel offset of the standard curve by changing the offset – 3 or by reducing the set room temperature 6.3.4 Setback modes (night setback) There are a number of different setback modes available, which allow night setback to be adjusted to suit the differing needs of the user: • reduced operation: the rooms are maintained at a reasonable temperature at night by constant heating operation (pump runs constantly). A set room temperature for nighttime can be set. It is at least 1 K lower than the set day temperature. The heating curve is calculated in accordance with these details. We recommend these settings for an underfloor heating system. • shut-down mode: boiler and heating circuit pump are off, frost protection is active. The pump only starts in frost protection mode. This setting is not recommended if there is a risk that the building would cool down too severely. Logamatic EMS RC35 programming unit - Subject to technical modifications 33 6 System settings (Service menu – Settings) • Room setback mode: The heating system operates as if in setback mode (as described under “reduced operation”), if the room temperature falls below the selected night temperature (set value). Boiler and heating circuit pump stop (as described under setback mode “shut-down mode”) if the room temperature exceeds the set night temperature by more than 1 K. This setback mode is only possible if a programming unit/remote control is installed in a representative room (reference room) or if the room temperature is captured by an external room temperature sensor. • Outdoor setback mode: The heating system operates as in reduced heating mode (as described under setback mode “reduced operation”) if the adjusted outside temperature does not reach the value of an adjustable outside temperature threshold. The heating system remains off above this threshold (as described under setback mode “shut-down mode”). This setback mode is suitable for heating circuits which do not have their own programming unit / remote control unit. The operating mode protects the rooms from cooling down too much once a certain outside temperature is reached. 6.3.5 Frost protection The frost protection function offers the following options: • no frost protection (frost protection is switched off). • outside temp. (outside temperature sensor required) The heating circuit pump starts automatically if the outside temperature falls below the adjustable frost protection temperature threshold. • room temperature (room temperature sensor of the RC35 or RC2x) The heating circuit pump starts automatically if the room temperature falls below the permanently set value of 5 °C. The heating circuit pump stops automatically if the room temperature rises above 7 °C. CAUTION: System damage due to frost! The settings no frost protection and room temperature provide either no frost protection or inadequate frost protection. When these settings are selected, the display shows a message indicating the risk of freezing. B For reliable frost protection, use the outside temp. setting. The setting room temperature offers no absolute frost protection, as lines routed through external walls may freeze up, for example, although the temperature in the reference room may be significantly above 5 °C. At what outside temp. should reduction be interrupted? EN 12831 requires that, for the maintenance of a level of comfortable heat, heating areas and heat sources be designed to deliver a specific output if the heating system cools down to a specific value through night setback. 34 Logamatic EMS RC35 programming unit - Subject to technical modifications System settings (Service menu – Settings) 6 In parameter At what outside temp. should reduction be interrupted?, you can set an outside temperature threshold (relative to the adjusted outside temperature, Æ page 24). 1 2 5°C TV TV Fig. 8 shows how the frost protection function works, with and without this parameter activated. Settings selected: frost protection by outside temp.; frost protection temp. 5 °C. TA 1 2 5°C TA 3 -15°C 6 720 618 477-07.1RS Fig. 8 TA TV 1 2 3 Effects of the parameter “At what outside temp. should reduction be interrupted?”. Left: parameter set “OFF” (factory setting). Right: parameter set to – 15 °C. Outside temperature Flow temperature Standby Reduced mode (at set nighttime room temperature) Heating mode (at set daytime room temperature) The heating system changes from reduced mode to standard heating mode [3] if the outside temperature falls below – 15 °C. This allows smaller heating surfaces to be utilised. Logamatic EMS RC35 programming unit - Subject to technical modifications 35 6 System settings (Service menu – Settings) 6.4 DHW WARNING: Risk of scalding at the hot water draw-off points. There is a risk of scalding at the hot water draw-off points if DHW temperatures can be set above 60 °C and during thermal disinfection. B Advise customers that they should only draw off mixed water. B Turn rotary selector anti-clockwise until DHW is selected. B Press to select domestic hot water. Menu SETTINGS\DHW opens. Menu item Input range Have you installed domestic yes, no hot water? Limiting value for maximum 60 °C to 80 °C dom. hot water temp. setting: Factory setting no 60 °C To which temperature should 30 °C to 80 °C your domestic hot water be heated? 60 °C What should be used for 3-way switching domestic hot water heating? valve, cylinder primary pump Do you wish to change the yes, no dom. hot water switching programme? 3-way switching valve no SERVICE\SETTINGS plant data boiler data Bdomestic hot water heating circuit 1 Other information DHW cannot be uninstalled in the case of boilers with DBA. Subject to the boiler in use, a the maximum possible set DHW temperature is limited to 60 °C. If the limit has been set to > 60 °C, this higher value can also be selected in the “USER MENU”. 1) When selecting “yes” the system jumps to the DHW switching program. Tab. 14 Navigator for service menu SETTINGS\DHW 36 Logamatic EMS RC35 programming unit - Subject to technical modifications System settings (Service menu – Settings) Menu item DHW circulation2)3) Is a circulation pump installed? How frequently should the circul. pump be switched on per hour? 6 Input range Factory setting yes, no no once for 3 minutes, Twice for twice for 3 minutes, 3 minutes 3 times for 3 minutes, 4 times for 3 minutes, 5 times for 3 minutes, 6 times for 3 minutes, permanent operation switch on circ. pump Do you wish to change the circulation switching programme? Other information yes, no Thermal disinfection2) Should a thermal yes, no disinfection be carried out? What temperature should 60 °C to 80 °C4) be used for thermal disinfection? On which day should the Monday, Tuesday, thermal disinfection be Wednesday, performed? Thursday, Friday, Saturday, Sunday, daily At what time of day 0:00h to 23:00h should the th. disinfection be performed? no Graphical display of number of times the pump is switched on per hour. When selecting “yes” the system jumps to the DHW circulation switching program. no 70 °C At temperatures above 60 °C there is a risk of scalding at the draw-off points during and after thermal disinfection! Tuesday 1:00h Times entered must be whole hours only (no minutes). Tab. 14 Navigator for service menu SETTINGS\DHW Logamatic EMS RC35 programming unit - Subject to technical modifications 37 6 System settings (Service menu – Settings) Menu item Input range Should the LED of the single yes, no charge key be activated? Start delay for preheated DHW (e.g. solar): OFF, 1 sec. to 50 sec. Factory setting yes OFF Other information The heating once only function is retained, but is no longer indicated by the LED.5) This function depends on the boiler used. Tab. 14 Navigator for service menu SETTINGS\DHW 1) Not possible or available on boilers with UBA1.x, UBA-H3 or DBA. 2) Not possible or available on boilers with UBA1.x or DBA. 3) On boilers with UBA-H3 subject to the availability of the PZ output (e.g. with module LM10). 4) Subject to the boiler in use, the temperature is permanently fixed an cannot be modified. 5) Not possible or available on boilers with UBA1.x. 38 Logamatic EMS RC35 programming unit - Subject to technical modifications System settings (Service menu – Settings) 6 6.5 Solar data B Turn rotary selector anti-clockwise, until solar data1) is selected. B Press to select solar data. Menu SETTINGS\SOLAR opens. Menu item What is the max. stor. cylinder temp. of the solar system? What temp. must the storage cylinder not fall below? What is the minimum pump rating? SERVICE\SETTINGS boiler data domestic hot water heating circuit 1 Bsolar data Other information Input range 30 °C to 90 °C Factory setting 60 °C 30 °C to 54 °C, OFF OFF 1) 20 % to 100 % 100 % 1) 1) Tab. 15 Navigator for service menu\Settings\Solar data 1) Not possible or not available with boilers with UBA1.x or DBA. For explanations of the settings, see the documentation for the solar module. Logamatic EMS RC35 programming unit - Subject to technical modifications 39 6 System settings (Service menu – Settings) 6.6 RC35 calibration B Turn rotary selector anti-clockwise, until RC35 calibration is selected. B Press to select RC35 calibration. SERVICE\SETTINGS Menu SETTINGS\CALIB. RC35 opens. domestic hot water heating circuit 1 solar data BRC35 calibration Menu item RC35 calibration Input range – 5.0 K to +5.0 K Factory setting 0.0 K Other information Tab. 16 Navigator for service menu SETTINGS\CALIB. RC35 Calibrating the displayed room temperature (calibration) If there is a separate thermometer near the programming unit, it may show a different room temperature to that shown on the programming unit. You can use this function to adjust (“calibrate”) the programming unit to match the thermometer. Before calibrating the room temperature, consider the following: • Is the thermometer more accurate than the programming unit? • Is the thermometer located close to programming unit so that they are both subject to the same heat influences (e.g. sunlight, fireplace)? A thermometer may indicate temperature fluctuations more slowly or rapidly than the programming unit. B Therefore, never calibrate the programming unit during phases when your heating system is cooling down or heating up. Example: if the thermometer is showing a temperature 0.5 °C higher than the programming unit, enter +0.5 K as the calibration value. 40 Logamatic EMS RC35 programming unit - Subject to technical modifications System settings (Service menu – Settings) 6 6.7 Contact details Contact details are automatically displayed to the end user if a fault develops. B Turn rotary selector anti-clockwise, until contact data is selected. B Press to select contact data. Menu SETTING\CONTACT opens. Menu item Name and tel. No. of supplier: Input range ___________ SERVICE\SETTINGS heating circuit 1 solar data RC35 calibration Bcontact data Other information ___________ Tab. 17 Navigator for service menu SETTING\CONTACT Entering company name and telephone number Two rows are available, each with 21 characters (capital letters, numbers and some other symbols). The current cursor position will flash (marked by “_”). 1. Hold down and turn rotary selector at the same time to select another character. Release . The modified character is saved. 2. Turn rotary selector anti-clockwise or clockwise to move the cursor. 3. Enter a space to delete a character. 4. Press to save your entries and leave the menu. Logamatic EMS RC35 programming unit - Subject to technical modifications 41 7 7 Diagnosis Diagnosis The diagnosis service menu contains a number of tools for diagnosis: • • • • • function test1)2) monitor value error message3) htg. charact. curve versions B Press + + simultaneously to open the SERVICE MENU. B Turn rotary selector anti-clockwise until diagnosis is selected. B Press to open the SERVICE\DIAGNOSIS menu. SERVICE MENU quick operation settings Bdiagnosis servicing Note that the menu items shown will vary depending on the heating system. 7.1 Function test You can use this menu to activate separate EMS components individually in order to test their functions1), 2). The available functions and the possible settings vary depending on the system installed. B Hold down and simultaneously turn the rotary selector to change the setting: e.g. BURNER OFF to BURNER ON. The change takes effect when you release . B Turn rotary selector (function test). to change between different displays FCT. TEST\BOILER valve 1 cl. 2 cl. ignition OFF flame OFF flame current 0.0μA BBURNER ON FCT. TEST\BOILER act. boil. tmp. 60°C air temperature 32°C flue gas temp. 78°C flame OFF BBURNER OFF 1) This function has a limited application on boilers with UBA-H3. 2) Not possible or not available with boilers with UBA1.x or DBA. 3) Boilers with DBA, UBA1.x or UBA-H3: restricted functionality only. 42 Logamatic EMS RC35 programming unit - Subject to technical modifications Diagnosis 7 Observe the information which appears on the display when you switch to menus or enter settings. Press any key or turn the rotary selector to confirm the information. No settings will be allowed that might result in damage to the components. This is why some settings may not be accepted. 7.2 Monitor value You can use the monitor value menu to view the set and actual values for the heating system. The set value will be displayed first and then the actual value. The values displayed for monitoring purposes vary depending on the system installed. If the values to be displayed do not all fit on the screen, they are displayed as a list. The list can be moved up or down by turning rotary selector. DIAGNOSIS\MONITOR VALUE boiler/burner MCM10/cascade boiler1) Pump module hydraulic separator2) domestic hot water heating circuit 1 solar2) module UM102) wireless transm.2) bus users2) Other information Only in conjunction with MCM10 (instead of “boiler/burner”) Only in conjunction with MCM10 (instead of “boiler/burner”) Values are displayed for additional heating circuits, if these are installed. For solid fuel boilers; EV2 = external interlock (input) FB = strength of the wireless signal Tab. 18 Navigator for service menu DIAGNOSIS\MON. VALUE 1) Depending on the boiler used, the monitor values are displayed in individual masks. Call up the monitor values for the next boiler by turning the rotary selector. Symbol present = the corresponding function is active. Explanation of symbols Æ Tab. 19, page 44. 2) Not possible or available on boilers with UBA1.x or DBA. Logamatic EMS RC35 programming unit - Subject to technical modifications 43 7 Diagnosis Burner operational Heating demand DHW demand Flue gas test active Service required / fault has occurred Tab. 19 Explanation of the symbols for footnote 1), page 43 7.3 Error message You can use the error message menu to view the most recent faults in the fault memory, in order to investigate a fault, for example. Faults are categorised as follows: • current errors are all unresolved faults currently present in the system. These can be one of the following types: locking, blocking or plant error. • locking fault1): Manually reset the heating system after the fault has been removed. For this, press RESET on the boiler. • blocking fault1): With blocking faults, the heating system continues to operate automatically, as soon as the fault has been removed. • plant errors relating to the heating system are logged in the RC35. Exceptions are boiler or burner faults that are either “locking” or “blocking” faults. The heating system keeps operating as much as possible during the fault; a reset is not required. For a list of the locking and blocking faults, which vary depending on the boiler, see the installation and maintenance instructions for the boiler. B Turn rotary selector to show the next message. 1) Not possible on boilers with UBA1.x, DBA or UBA-H3 44 Logamatic EMS RC35 programming unit - Subject to technical modifications Diagnosis 7 7.4 Heating curve With the htg. charact. curve you can graphically display the heating curves of individual heating circuits. B If the system comprises several heating circuits: Turn rotary selector to display the heating curve of the next heating circuit. DIAG.\CHAR. CURVE HC2 90 21 targ. flow tmp. 57°C 7.5 Versions You can use the INFO\VERSIONS menu to view the software versions for heating system components. B If the information cannot be shown in one display: Turn rotary selector to scroll to the next display. Logamatic EMS RC35 programming unit - Subject to technical modifications INFO\VERSIONS RC35 UBA1.5 1.02 1.21 45 8 8 Service Service With the servicing menu (not possible on boilers with UBA1.x and DBA) you can set a service interval as well as view and reset current service messages. The interval can expire after a certain number of hours run or when a specific date is reached1). The RC35 programming unit will then show a service message so that the customer can notify you to arrange an appointment. Service messages are indicated by an Hxx code, e.g. H07. SERVICE MENU\ SERVICE service interval Menu item How should servicing messages be triggered? For “by date”: Annual servicing, starting on: current messages RESET servicing Input range No messages, by date, by operation hours 01.01.2000 For “by operation 1.000 h to hours”: Boiler 6.000 h operation hours until next servicing message Message/code Do you wish to no, yes reset the servicing messages? Factory setting No messages Other information When selecting “date” or “operating hours” the system changes automatically to the corresponding setting. 01.01.2000 To set the date: hold down and turn rotary selector at the same time. 1.000 h Number of hours of operation with burner switched on. no To view further messages: turn rotary selector. When selecting “yes” all service messages are reset. Observe the information on the display. Tab. 20 Navigator for SERVICE MENU\SERVICE 1) Depending on the boiler used, additional service intervals may be able to be set at the boiler programming unit. 46 Logamatic EMS RC35 programming unit - Subject to technical modifications Reset 9 9 Reset The RESET menu allows you to reset • • • • all parameters to their factory setting1), the fault list1), the service message2) and the hours run2). Following a reset to factory settings, you may need to adjust the parameters in accordance with the actual system configuration. B Turn rotary selector to select a menu, e.g. error list. B Press to change to the display, e.g. Do you wish to reset the error list? B Press and turn rotary selector to set the display to yes. The reset is implemented after you release the button. An appropriate message is shown during the reset; this will close automatically. B Once reset is complete: confirm the new message by pressing any key. 1) On boilers with UBA1.x, DBA or UBA-H3 only all RC35 parameters are reset, but not the combustion controller parameters. 2) This function is not available with boilers with UBA1.x or DBA. Logamatic EMS RC35 programming unit - Subject to technical modifications 47 10 Troubleshooting 10 Troubleshooting This fault table lists possible system faults, i.e. faults in EMS components. The heating system keeps operating as long as possible in the event of a system fault; in other words, heating can continue. Only use original Buderus spare parts. Losses caused by the use of parts not supplied by Buderus are excluded from the Buderus warranty. The fault displays are subject to the specific type of boiler used. Abbreviations used: SC = Fault code; x = heating circuit with number x, e.g. A23 for heating circuit 3 FC = Fault code HCx = Heating circuit with the number x Events SC FC display A01 800 Outside sensor is defect. Effect on control Possible cause Remedy characteristics The minimum outside Temperature sensor is B Check sensor temperature is applied. incorrectly connected connection and or fitted. sensor lead. Breakage or short cir- B Check sensor mounting. cuit in the sensor lead. B Compare resistance Temperature sensor is values with the faulty. sensor curve. A01 808 DHW sensor DHW heating has Temperature sensor is B Check sensor 1 is defect. stopped. incorrectly connected connection and or fitted. sensor lead. A01 809 DHW sensor B Check sensor 2 is defect. Breakage or short cirmounting. cuit in the sensor lead. B Compare resistance Temperature sensor is values with the faulty. sensor curve. Tab. 21 Fault table 48 Logamatic EMS RC35 programming unit - Subject to technical modifications Troubleshooting Events SC FC display A01 810 DHW stays cold. 10 Effect on control characteristics The system continuously tries to heat the DHW cylinder to the set DHW temperature. Possible cause Remedy Constant drawing or B Stop any leaks. system leak. Temperature sensor is B Check sensor incorrectly connected connection and or fitted. sensor lead. Priority DHW is Breakage or short cir- B Check sensor mounting. switched off once the cuit in the sensor lead. error message has B Compare resistance Temperature sensor been displayed. values with the faulty. sensor curve. Cylinder primary pump B Check that the incorrectly connected cylinder primary or faulty. pump is working, e.g. by carrying out a function test. Thermal disinfection Too much water B Select thermal A01 811 Thermal disinfection at a disinfection has been interrupted. drawn during thermal disinfection. time when no was unsuccessful. additional heat Boiler output is too demand is made. low for heat to be used simultaneously for other purposes (e.g. second heating circuit). Temperature sensor is B Check sensor incorrectly connected connection and or fitted. sensor lead. B Check sensor Breakage or short cirmounting. cuit in the sensor lead. B Compare resistance Temperature sensor is values with the faulty. sensor curve. Cylinder primary pump B Check that the faulty. cylinder primary pump is working, e.g. by carrying out a function test. Tab. 21 Fault table Logamatic EMS RC35 programming unit - Subject to technical modifications 49 10 Troubleshooting Events SC FC display A01 815 Low loss header sensor faulty. A01 A01 A02 A11 A11 A11 Effect on control characteristics This may result in the following heating circuits receiving insufficient heat. Possible cause Remedy Temperature sensor is B Check sensor incorrectly connected connection and or fitted. sensor lead. Breakage or short cir- B Check sensor mounting. cuit in the sensor lead. B Compare resistance Temperature sensor is values with the faulty. sensor curve. 816 No communi- The boiler no longer EMS BUS system is B Reset by switching cation with receives heat demand overloaded. the heating system UBA/MC10, signals; the heating ON and OFF. UBA3/MC10, DBA, DBA, UBA-H3 system may no longer UBA-H3 or MCM10 is B If necessary inform or MCM10. generate heat. faulty. your local service centre. 828 Water Digital water pressure B Replace the water pressure sensor is faulty. pressure sensor. sensor is defect. 816 No commu- BC10 settings are no Contact problem on B Check BC10 nication with longer adopted by BC10 or BC10 is connection. BC10. RCxx devices. faulty. B Replace BC10 if required. 801 internal error Heating system is in Internal runtime error B Replace RC35. emergency mode. in RC35. 802 Time is not Restricted functionality Time details are B Enter the current yet set. for: time. missing, e.g. due to lengthy power failure. • All switching programs • Error messages 803 Date is not Restricted functionality Date details are B Enter the current yet set. for: missing, e.g. due to date. lengthy power failure. • All switching programs • Holiday function • Error messages Tab. 21 Fault table 50 Logamatic EMS RC35 programming unit - Subject to technical modifications Troubleshooting 10 Events Effect on control SC FC display characteristics A11 804 internal error Heating system is in emergency mode. A11 806 Room Since the actual room temperature temperature is sensor is missing, the following defect. cannot function: • Room influence (for weathercompensated control) • Switching point optimisation In the case of room temperaturedependent control, the system is regulated to max. temperature for HCx. A11 816 No commu- RC20/RF unable to nication with transmit data to RC35. RC35. Room temperature control therefore not possible for HC. Possible cause Remedy Internal runtime error B Replace RC35. in RC35. Faulty integral B Replace the remote temperature sensor on control unit. the heating circuit's programming unit / remote control unit. RC20/RF has incorrect address. B Check the address (parameter P1) in RC20/RF. B Check connection to RC35. RC35 not present or not connected correctly. A12 815 Low loss This may result in the Temperature sensor is B Check sensor header following heating incorrectly connected connection and sensor circuits receiving or fitted. sensor lead. faulty. insufficient heat. B Check sensor Breakage or short cirmounting. cuit in the sensor lead. B Compare resistance Temperature sensor values with the faulty. sensor curve. A12 816 No commu- Heating circuit pump WM10 or BUS B Check connections nication with for heating circuit 1 is incorrectly connected on WM10 and BUS separator permanently activated. or faulty. cable. module. B Replace WM10. RC35 does not recognise WM10. Tab. 21 Fault table Logamatic EMS RC35 programming unit - Subject to technical modifications 51 10 Troubleshooting Events SC FC display A18 825 Two master operating units in system. Effect on control characteristics RC35 and RC2x regulate both heating circuits and DHW. Subject to the selected heating programs and the required room temperature, the heating system may no longer function correctly. DHW heating is malfunctioning. A2x 806 Room Since the actual room temperature temperature is for HCx is missing, the following defect. cannot function: • Room influence (for weathercompensated control) • Switching point optimisation Possible cause RC2x and RC35 are both logged on as master. Remedy B Change parameter P1 in RC2x or remove RC35 from the EMS BUS. Faulty integral B Replace the remote temperature sensor on control unit. the heating circuit's programming unit / remote control unit. In the case of room temperaturedependent control, the system is regulated to max. temperature for HCx. A2x 816 No commu- Since the actual room RC2x incorrectly B Check address in nication with temperature is RC2x. addressed, wired or operating missing, the following faulty. B Check function and unit HCx. cannot function: connection of the Heating circuit has not remote control unit. been registered on the • Room influence B Replace the remote RFM20. • Switching point control unit. optimisation Tab. 21 Fault table 52 Logamatic EMS RC35 programming unit - Subject to technical modifications Troubleshooting Events SC FC display A2x 829 RC20/RF as remote control. A2x 830 Low battery for wireless oper. unit HCx. A2x 839 No wireless comm. with oper. unit HCx. Wireless malfunction. 10 Effect on control characteristics RC20/RF unable to transmit data to RC35. Room temperature control therefore not possible for this HC. Possible cause Remedy RC20/RF address B Set the operating incorrectly allocated in unit parameter in RC35 or not installed RC35 to RC20/RF. in RC35. B Check the assignment of the RC20/RF. No effect if the battery Battery in RC20/RF B Replace batteries. is replaced in time. for HCx is low. Since the actual room RC20/RF is outside temperature is the range of reception. missing, the following cannot function: Heating system has been switched off. • Room influence When RFM20 was • Switching point replaced, the RC20/ optimisation RF was not registered The RFM20 operates on the new RFM20. with the last values set on the remote control unit. A2x 842 Frost Since the actual room No programming unit / prot.selected temperature is remote control unit but no missing, the following assigned, although rem.contr. cannot function: frost protection is HCx. set to room • Room influence temperature. • Switching point optimisation No programming unit / A2x 843 Room EMS operates with the remote control unit control selected but last values set on the assigned, although remote control unit. no room temp. rem.contr. controlled is set. HCx. B Bring the RC20/RF within the range of reception. B Switch on the heating system. B Register the RC20/ RF (see documentation for RC20/RF). B Check the operating unit parameter. B Possibly change over frost protection to outside temp. B Check the operating unit parameter. B Possibly change over to outside temp. contr. Tab. 21 Fault table Logamatic EMS RC35 programming unit - Subject to technical modifications 53 10 Troubleshooting Events SC FC display A3x 807 HCx flow sensor is defect. Effect on control characteristics The heating circuit pump continues to be controlled with reference to the default value. Possible cause Remedy Temperature sensor is B Check sensor incorrectly connected connection and or fitted. sensor lead. Breakage or short cir- B Check sensor mounting. cuit in the sensor lead. B Compare resistance The actuator is Temperature sensor is values with the switched to zero volt faulty. sensor curve. and remains in the last active state (manually adjustable). A3x 816 No commu- Heating circuit x Heating circuit B Check rotary coding nication with cannot be operated addresses on MM10 switch on MM10. HCx mixer correctly. and RC35 do not module. match. MM10 and actuator MM10 or BUS cable B Check connections (mixer) are running incorrectly connected on MM10 and BUS independently in or faulty. cable. emergency mode. B Replace MM10. Heating circuit pump RC35 does not recognise MM10. is being continuously actuated. Hxx Service message, no plant error. Monitor data in RC35 is invalid. The heating system Example: service keeps operating as far interval has expired. as possible. Maintenance is required, see boiler documentation. Tab. 21 Fault table System faults do not need resetting. Contact your local service engineer or your Buderus sales office if you cannot remedy the system fault yourself. Other faults are described in the documents relating to the individual boiler. 54 Logamatic EMS RC35 programming unit - Subject to technical modifications Logamatic EMS RC35 programming unit - Subject to technical modifications Push & turn to set parameter. room quick operation settings diagnosis servicing RESET SERVICE MENU room SERVICE\SETTINGS factory setting error list service message operating hours SERVICE MENU\RESET service interval current messages RESET SERVICE MENU\SERVICE function test monitor value error message htg. charact. curve versions SERVICE\DIAGNOSIS plant data boiler data heating circuit 1 heating circuit 2 etc. domestic hot water solar data RC35 calibration contact data ON OPEN OFF ON date no / yes Do you wish to reset all parameters to the factory settings? SERVICE MENU\RESET How should servicing messages be triggered? Hours run SERVICE MENU\SERVICE fuel valve ignition flame flame current BURNER FCT. TEST\BOILER e.g. Heating circuit enabled, remote control, type of control, heating system, night setback, holiday setback, interrupt setback, htg. charact. curve, htg. charact. curv SETTINGS\HTG. CIRC. 2 yes / no Which language should be used? English SHORTCUT\HYDR. SEP. Have you installed a module for the hydraulic separator? SHORTCUT\BASIC SETUP RC35 Service menu flame current boil.tmp. boiler pump outside temp. damp.out.tmp. MON. VALUE\BOILER e.g. std. tmp. (-10) Max. flow min flow temp. rm. tmp. offset SETTINGS\HTG. CIRC. 2 heating circuit 1, no. mixers, remote control units, DHW, charge pump, solar SHORTCUT 6 720 618 477-09.1TL from: 09.10.06 durat.: Outside sensor is defect. A01 ERROR\PLANT e.g. SETTING\CONTACT Name and tel. No. of supplier: Service menu RC35 11 11 Service menu RC35 55 Index Index A Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Actual values, viewing . . . . . . . . . . . . . . . . . . 43 Adjusting the outside temperature . . . . . . . . 24 B Boiler data, Service menu – settings . . . . . . 26 Building type. . . . . . . . . . . . . . . . . . . . . . . . . . 24 C Calibration, room temperature display . . . . . 40 Checklist, parameters for commissioning . . . . . . . . . . . . . . . . . . . . . . . . 19 Combustion controller . . . . . . . . . . . . . . . . 7, 47 Commissioning. . . . . . . . . . . . . . . . . . . . . . . . 18 Commissioning, quick . . . . . . . . . . . . . . . . . . 20 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Contact details, entering . . . . . . . . . . . . . . . . 41 Control mode . . . . . . . . . . . . . . . . . . . . . . . . . 31 Controls, overview of . . . . . . . . . . . . . . . . . . . 14 Correct use. . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Curve, Service menu – diagnosis. . . . . . . . . 45 D Design temperature (standard temperature) . . . . . . . . . . . . . . . . . DHW - Service menu – settings. . . . . . . . . . . . . . - set value. . . . . . . . . . . . . . . . . . . . . . . . . . . - temperature limit . . . . . . . . . . . . . . . . . . . . DHW circulation. . . . . . . . . . . . . . . . . . . . . . . DHW priority. . . . . . . . . . . . . . . . . . . . . . . . . . Diagnosis, Service menu . . . . . . . . . . . . . . . . Disinfection, thermal . . . . . . . . . . . . . . . . . . . Display contrast . . . . . . . . . . . . . . . . . . . . . . . 32 36 36 36 36 27 42 36 18 E EMS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 22 EMS BUS subscribers . . . . . . . . . . . . . . . . . 22 56 F Faults, Service menu diagnosis . . . . . . . . . . 44 Flow temperature. . . . . . . . . . . . . . . . . . . . . . 32 Frost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Frost protection . . . . . . . . . . . . . . . . . . . . . . . 34 Function test, Service menu – diagnosis. . . 42 H Heat storage capacity . . . . . . . . . . . . . . . . . . Heating circuit - installing. . . . . . . . . . . . . . . . . . . . . . . . . . . - more than one heating circuit . . . . . . . . . - Service menu – settings . . . . . . . . . . . . . Heating curve - instructions for setting . . . . . . . . . . . . . . . - viewing. . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 23 11 27 32 45 I Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 L Language, setting . . . . . . . . . . . . . . . . . . . . . 23 Low loss header module WM10 . . . . . . . . . . 9 Low loss header, installing . . . . . . . . . . . . . . 23 M Minimum clearances . . . . . . . . . . . . . . . . . . . 10 Minimum outside temperature . . . . . . . . . . . 25 Mixer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Mixer module MM10 . . . . . . . . . . . . . . . . . . . . 9 Modulation, boiler pump . . . . . . . . . . . . . . . . 26 Monitor value, Service menu – diagnosis . . 43 N Night setback . . . . . . . . . . . . . . . . . . . . . . . . . 33 O Outdoor setback mode . . . . . . . . . . . . . . . . . 33 Outside temperature control . . . . . . . . . . . . 31 Outside temperature, adjusted. . . . . . . . . . . 24 Logamatic EMS RC35 programming unit - Subject to technical modifications Index P Plant data, Service menu – Settings . . . . . . . 23 Power failure . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Programming unit - assignment in software . . . . . . . . . . . . . . . 31 - attaching or removing . . . . . . . . . . . . . . . . 13 - for heating circuit . . . . . . . . . . . . . . . . . . . . 27 - only programming unit in the system . . . . 11 Pump kick . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Pump logic temperature . . . . . . . . . . . . . . . . . 26 Pump run-on time . . . . . . . . . . . . . . . . . . . . . . 26 Q Quick operation, Service menu . . . . . . . . . . . 20 R Reduced operation . . . . . . . . . . . . . . . . . . . . . 33 Reference room. . . . . . . . . . . . . . . . . . . . . . . . 10 Remote control unit. . . . . . . . . . . . . . . . . . . . . 11 Reset, Service menu. . . . . . . . . . . . . . . . . . . . 47 Room influence . . . . . . . . . . . . . . . . . . . . . . . . 31 Room setback mode. . . . . . . . . . . . . . . . . . . . 33 Room temperature offset . . . . . . . . . . . . . . . . 32 Solar module, installing . . . . . . . . . . . . . . . . . 23 Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Standard delivery . . . . . . . . . . . . . . . . . . . . . . . 7 Switching off . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Switching program, optimising . . . . . . . . . . . 27 System handover . . . . . . . . . . . . . . . . . . . . . . 21 T Temperature sensor . . . . . . . . . . . . . . . . . . . . . 8 Testing components. . . . . . . . . . . . . . . . . . . . 42 Thermal disinfection . . . . . . . . . . . . . . . . . . . . 36 Thermostatic valves in reference room . . . . . 22 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . 48 V Versions, Service menu – diagnosis. . . . . . . 45 Versions, viewing . . . . . . . . . . . . . . . . . . . . . . 45 W Weather-compensated control . . . . . . . . . . . 31 S Safety instructions . . . . . . . . . . . . . . . . . . . . . . 6 Screed, drying . . . . . . . . . . . . . . . . . . . . . . . . . 27 Sensor characteristics . . . . . . . . . . . . . . . . . . . 8 Service interval, setting. . . . . . . . . . . . . . . . . . 46 Service menu, introduction. . . . . . . . . . . . . . . 15 Service menu, overview of the menus. . . . . . 17 Service messages, viewing/resetting . . . . . . 46 Service, Service menu . . . . . . . . . . . . . . . . . . 46 Set values, viewing . . . . . . . . . . . . . . . . . . . . . 43 Setback mode (night setback). . . . . . . . . . . . 33 Setback, interrupting (frost protection) . . . . . 34 Showing the fault memory . . . . . . . . . . . . . . . 44 Shutdown operation . . . . . . . . . . . . . . . . . . . . 33 Shutting down . . . . . . . . . . . . . . . . . . . . . . . . . 22 Single charge LED, switching off . . . . . . . . . 36 Solar data, Service menu – settings . . . . . . . 39 Logamatic EMS RC35 programming unit - Subject to technical modifications 57 Notes 58 Logamatic EMS RC35 programming unit - Subject to technical modifications Notes Logamatic EMS RC35 programming unit - Subject to technical modifications 59 Buderus Cotswold Way, Warndon, Worcester WR4 9SW Customer service: 0844 892 3004 Technical support: 0844 892 4224 Fax: 01905 753130 www.buderus-commercial.co.uk In the UK and IE, Buderus is a brand name of Bosch Thermotechnology Ltd.
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
Download PDF
advertisement