460MCBC Modbus TCP/IP to BACnet/IP FEATURES

460MCBC Modbus TCP/IP to BACnet/IP FEATURES
460MCBC
Contact Us:
1-800-249-1612
Modbus TCP/IP to BACnet/IP
FEATURES
 Fully Compliant BACnet/
IP Client
Connect Modbus TCP/IP Servers to BACnet/IP Servers
The 460MCBC moves data between up to 32 Modbus TCP/IP Servers and up to 32 BACnet/
IP Servers. It’s a perfect tool to move data between your Modbus power meters, boilers,
chiller and other Server devices and your BACnet/P Server devices.
 Fully User Configurable
Modbus TCP/IP Client
 Exchange BACnet/IP
Server Data with
Modbus TCP/IP Servers
 BACnet/IP Supports up
to 150 Analog Input and
150 Analog Output
Properties
 BACnet/IP Supports up
to 1600 Binary Input and
1600 Binary Output
Properties
 Support for up to 32
Modbus TCP/IP Servers
and 32 BACnet/IP
Servers
 Support for Modbus
Function Codes 1, 2, 3,
4, 5, 6, 15 and 16
 Effortless Browser
How Do I use the 460MCBC in My Application?
For most applications the mapping is very straight forward. Modbus Register data is mapped
to BACnet Analog objects and Modbus Coil data is mapped to Binary objects on BACnet. The
only additional piece required for BACnet is adding meta data which is nothing more than an
ASCII description of each object. No other deep understanding of either protocol is required to
configure the gateway.
It really is that simple.
Why Use Real Time Automation as a Gateway Supplier?
The 460MCBC provides an option to connect Modbus TCP/IP Server devices with your
BACnet/IP Server devices. While there are certainly a number of other companies offering
stand alone gateways, there is no one who provides the level of support and service that you
receive from RTA.
When you call, a live person answers the phone. When you talk with sales, you will get honest
answers and recommendations even if that means recommending someone else's solution.
When you get support, it is from an engineer who had a hand in the product’s development,
and support doesn't require a ticket or 24 hour wait. We are unashamed of the fact that we are
a smaller company because that means you mean a lot more to us.
Try the RTA difference today and give us a call at 1-800-249-1612 or check out more
information on us and our other solutions at www.rtaautomation.com.
Based Configuration
 No Programming
Required
A Word from our Founder
“It’s likely that your business isn’t industrial networking and it shouldn’t be. You make products, design systems, or manage some process. Whatever it
is that you make, monitor or install the process inevitably creates data. If you’re a control engineer and your plant has been around for a few years your
line is probably littered with devices that send out all kinds of data over many different protocols. If you’re an automation device developer you probably
have customers that need to move your data into some other network. Either way, you’ve got a device conversion problem. You have devices that generate ASCII , Modbus RTU, Modbus TCP, BACnet, Profinet, Profibus, Ethernet TCP/IP , Ethernet/IP, DeviceNet or some other completely proprietary
data and now you’re the person that has to move that data to some other network!
I feel your pain… and rather than just my sympathy, I have a solution for you. You see, while your business may not be moving data around a factory
floor mine is. In fact, it’s all that we have done for over twenty years now. Our 460 series of Device Converters is the culmination of those twenty years.
You can now move all of your data, where you want, when you want and how you want. Try us on your next project, I guarantee you wont regret it.
John Rinaldi
460MCBC
www.rtaautomation.com
BACnet/IP FEATURES
BACnet/IP Operation Modes
BACnet/IP Client
Supported Object Types
Device, Binary I/O, Analog I/O, Character String Value
Supported Service Codes
Maximum Connections
Read & Read Multiple-B, Write & Write Multiple-B, COV & COV unsolicited-B, Device Dynamic Binding, Dynamic
Object Binding-B, Device Communication Control-B
32
Analog Objects Supported
1200 Input and 1200 Output
Binary Objects Supported
1600 Input and 1600 Output
MODBUS TCP/IP FEATURES
Modbus Operation Modes
Modbus TCP/IP Client
Function Codes Supported
1, 2, 3, 4, 5, 6, 15 & 16
Swapping
Byte and Word Swapping
Maximum Modbus TCP/IP Server Devices
32
Number Read/Write Scan Lines per TCP/IP Server
Device
Scan Line Support
200 Total - 100 reads & 100 writes
Up to 125 Registers or 2000 Coils
INCLUDED WITH GATEWAY
120 volt AC Wall Wart Power Supply
Manual
6’ power cable with Flying leads
5 Year Hardware Warranty
IPSetup software — Automatically locates RTA Gateway on the network
Unlimited Firmware Feature Upgrades for Life
CAT5 Cross over cable for direct connection to PC during programming
Complete, Unlimited Access to our Industry Leading Support Staff
ELECTRICAL/ENVIRONMENTAL
DC Input Voltage
8 V @ 230 mA to 28 V @ 80 mA
Maximum Baud Rate
115K Baud
Operating Temperature
-40 C to 85 C
Certification
DIMENSIONS
RoHS-Compliant, UL, CUL, CE Approvals
ENCLOSURE / HARDWARE
Size
4.2” x 3.25” x 1”
Weight
5 oz.
Enclosure Type
Anodized Aluminum
Mounting
Din Rail or Panel Mount
LEDs
Ethernet Link/Data LED, Ethernet Speed LED, Power LED,
& 2 general purpose LEDS on side
GATWAY FEATURES & FUNCTIONS
Gateway Security
You can configure up to 9 different users access to
diagnostic and configuration screens.
Alarming
Set <, <=, >=, >, ==, !=, and Change-of-State rules on
any data moving through the gateway. If alarm rule is
triggered an email notification can be sent.
Translation Table
Allows for data manipulation during protocol translation. Scaling and other data format changes can occur
in the gateway.
Status and
Counters
Protocol specific status, counters and error messages
are accessible within the gateways diagnostics page.
They can also be delivered to a connected device.
Diagnostic Logging
Page
Allows users to see and log start up sequences, protocol specific messages & error messages.
NOT EXACTLY WHAT YOU WERE LOOKING FOR?
Real Time Automation offers a full line of gateway products. If this isn’t the one
you were looking Give us a call at 1-800-249-1612 or check out a listing at
www.rtaautomation.com/products. We also offer custom gateways to help customers dealing with unique needs or proprietary protocols.
CATALOG #
DESCRIPTION
460MCBC
Connects Modbus TCP/IP Servers to BACnet/IP Servers
For More Information:
1-800-249-1612
[email protected]
.
www.rtaautomation.com
2014 Copyright Real Time Automation. All rights reserved. The Real Time Automation logo is a registered trademark of Real Time Automation Inc.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement